Data Sheet DB EN IB IL 24 DI 4 (-PAC)

image

Contents

1. 2 Grp A B C D T5 INTERBUS 5561B001 Figure 4 Labeling example of terminals for use in potentially explosive areas Ensure that the following points and instructions are observed before startup When working on the Inline terminal always switch off the supply voltage The Inline terminal must only be installed started up and maintained by qualified personnel Install the Inline terminals in a control cabinet or metal housing with a minimum of IP54 protection according to EN 60529 The Inline terminal must not be subjected to any mechanical or thermal strain which exceeds the limits specified in the product documentation The Inline terminal must not be repaired by the user Repairs may only be carried out by the manufacturer The Inline terminal must be replaced by an approved terminal of the same type Only Category 3G equipment may be connected to Inline terminals in Zone 2 Observe all applicable standards e g EN 60079 and national safety and accident prevention regulations for installing and operating equipment Restrictions When using terminals in potentially explosive areas observe the technical data and limit values specified in the corresponding documentation user manual data sheet package slip AN Restrictions regarding the Inline system The maximum permissible current flowing through the potential jumpers Up and Us total current is limited to 4 A when using the Inline terminal in potentially explos
2. Accessories Description Connector for digital 4 channel or 16 channel Inline terminals w o color print Connector for digital 4 channel or 16 channel Inline input terminals with color print Documentation Description User manual Configuring and Installing the INTERBUS Inline Product Range User manual Automation Terminals of the Inline Product Range Application note Inline Terminals for Use in Zone 2 Potentially Explosive Areas Technical Data General Data Housing dimensions width x height x depth Weight Operating mode Transmission speed Connection method for sensors Ambient temperature operation Ambient temperature storage transport Permissible humidity operation storage transport Permissible air pressure operation storage transport Degree of protection Class of protection Connection data for Inline connector Connection method Conductor cross section Interface Local bus Power Consumption Communications power Current consumption at U Power consumption at UL Segment supply voltage Us Nominal current consumption at Us Type Order No IB IL SCN 12 2726340 IB IL SCN 12 ICP 2727611 Type Order No IB ILSYS PROUME 2743048 IL SYS INST UME 2698737 AH EN IL EX ZONE 2 7217 12 2 mm x 120 mm x 71 5 mm 44 g without connectors 66 g with connectors Process data operation with 4 bits 1 nibble 500 kbps 2 and 3 wire technology 25 C to 55 C 25 C to 85 C 10 to 95 accordin
3. IB IL 24 DI 4 PAC Inline Terminal With Four Digital Inputs VA GA Q SNENA NN AS AUTOMATIONWORX Data Sheet 5550 en 04 PHOENIX CONTACT 03 2007 Description The terminal is designed for use within an Inline station It is used to acquire digital input signals Features Connections for four digital sensors Connection of sensors in 2 and 3 wire technology Maximum permissible load current per sensor 250 mA Maximum permissible load current from the terminal 1 0A Diagnostic and status indicators This data sheet is only valid in association with the IL SYS INST UM E user manual or the Inline system manual for your bus system Make sure you always use the latest documentation It can be downloaded at www download phoenixcontact com A conversion table is available on the Internet at www download phoenixcontact com general 7000 en OO pdf IEP This data sheet is valid for all products listed on the following page DOGO M000 Weonnc ODE INSPIRING INNOVATIONS IB IL 24 DI 4 PAC Ordering Data Products Description Inline terminal with four digital inputs complete with accessories connector and labeling field Inline terminal with four digital inputs without accessories Type Order No IB IL 24 DI 4 PAC 2861234 IB IL 24 DI 4 2726214 Pcs Pkt 1 IR One of the listed connectors is needed for the complete fitting of the IB IL 24 DI 4 terminal
4. g to DIN EN 61131 2 70 kPa to 106 kPa up to 3000 m above sea level IP20 according to IEC 60529 Class 3 according to VDE 0106 IEC 60536 Spring cage terminals 0 2 mm to 1 5 mm solid or stranded 24 16 AWG Through data routing 7 5 V 40 mA maximum 0 3 W maximum 24 V DC nominal value 1 0 A maximum Pcs Pkt Pcs Pkt 1 PHOENIX CONTACT 2 5550_en_04 IB IL 24 DI 4 PAC Supply of the Module Electronics and I O Through Bus Coupler Power Terminal Connection method Through potential routing Digital Inputs Number 4 Input design According to EN 61131 2 Type 1 Definition of switching thresholds Maximum low level voltage Ulme 8 V Minimum high level voltage Uumin gt 15 V Common potentials Segment supply ground Nominal input voltage Uin 24V DC Permissible range 30 V lt Uj lt 30 V DC Nominal input current for UIN 3 mA minimum Delay time None Permissible cable length to the sensor 30 m to ensure conformance with EMC directive 89 336 EEC Use of AC sensors AC sensors in the voltage range lt Uy are limited in application corresponding to the input design Characteristic Curve Current Depending on the Input Voltage and the Ambient Temperature T4 Supply Voltage Input Current Input Current With t gt 20s For Ty 25 C For Ty 55 C 18 V 3 0 mA 2 9mA 2 5mA 24 V 3 9 mA 3 8 mA 3 5 mA 30 V 4 5 mA 4 2 mA 3 0 mA The current is reduced depending on the ambient temperature T and the number of
5. inputs that are switched on internal module temperature Power Dissipation Formula to Calculate the Power Dissipation of the Electronics Pror 0 24 W Ui x 0 003 A Where Prot Total power dissipation in the terminal n Number of set inputs n 1 to 4 Uyi Input voltage of input i i Index Power Dissipation of the Housing Pyoy 0 6 W maximum within the permissible operating temperature Limitation of Simultaneity Derating No limitation of simultaneity no derating Safety Equipment Overload in segment circuit No Surge voltage Protective elements in the power terminal Polarity reversal Protective elements in the power terminal 5550_en_04 PHOENIX CONTACT 3 IB IL 24 DI 4 PAC Electrical Isolation To provide electrical isolation between the logic level and the I O area it is necessary to supply the station bus coupler and the digital input terminal described here via the bus coupler or a power terminal from separate power supply units Interconnection of the power supply units in the 24 V area is not permitted See also user manual Common Potentials The 24 V main voltage 24 V segment voltage and GND have the same potential FE is a separate potential area Separate Potentials in the System Consisting of Bus Coupler Power Terminal and I O Terminal Test Distance Test Voltage 5 V supply incoming remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 5 V supply outgoing remote bus 7 5 V supply bus
6. ive areas 5550_en_04 PHOENIX CONTACT 7 IB IL 24 DI 4 PAC Programming Data Configuration Data Process Data Local Bus INTERBUS IEJ For the assignment of the illustrated BE ox 190a Input address area 4 bits byte bit view to your INTERBUS control or computer system please refer to the DB GB IBS SYS ADDRESS data sheet Order No 9000990 Parameter channel PCP Other Bus Systems Assignment of the Terminal Points to the IN Process Data Byte bit Byte Bit 0 3 0 2 0 1 view Modus IRTP For the programming data configuration data Terminal point 24 V of other bus systems please refer to the Terminal point GND 2 6 1 6 2 3 1 3 corresponding electronic device data sheet ee a e g GSD EDS Status LED 4 3 2 Po indicator PHOENIX CONTACT 03 2007 5550 en 04 PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany 8 OO Phone 49 52 35 30 0 Fax 49 0 5235 3 4 12 00 www phoenixcontact com
7. line system manual for your bus system 5550_en_04 IB IL 24 DI 4 PAC Connection Example When connecting the sensors observe the assignment of the terminal points to the process data see page 8 5550A004 Figure 3 Typical sensor connections A 3 wire termination B 2 wire termination PHOENIX CONTACT 6 IB IL 24 DI 4 PAC Notes on Using the Terminal in Potentially Explosive Areas Approval According to EC Directive EG RL 94 9 ATEX II 3G EEx nAC IIC T4 U This Inline terminal conforms to standard EN 50021 and can be installed in a Zone 2 potentially explosive area This Inline terminal is a Category 3 item of equipment UL Approval This Inline terminal of the indicated hardware version or later is suitable for use in Class Division 2 Groups A B C D Before using an Inline terminal in a Zone 2 potentially explosive area check that the terminal has been approved for installation in this area For a list of terminals approved for use in Zone 2 potentially explosive areas please refer to the AH EN IL EX ZONE 2 application note Check the labeling on the Inline terminal and the packaging see Figure 4 amp Il13G EExnAC IIC T4U r inun Potential I routin g 4 A maximu for use in Ex areas IBx IL xx xx x Order No XXXXXXX Module ID xx HW FW XxX PHOENIX C _Locs COESNTAct amp SG epee For tez Locs XX LISTED CI 1 Zn 2 Ex nC IIC T5 LAA J 31ZN Cl I Div
8. logic 500 V AC 50 Hz 1 min 7 5 V supply bus logic 24 V supply I O 500 V AC 50 Hz 1 min 24 V supply I O functional earth ground 500 V AC 50 Hz 1 min Error Messages to the Higher Level Control or Computer System None Approvals For the latest approvals please visit www download phoenixcontact com 5550 _en_04 PHOENIX CONTACT 4 IB IL 24 DI 4 PAC Local Diagnostic and Status Indicators and Terminal Point Assignment Local Diagnostic and Status Indicators Desig Color Meaning FD Green Diagnostics 72 34 Status indicators of the inputs Function Identification Light blue Terminal Point Assignment Terminal Point Assignment aa Sioralinput 10N 1 21 Signatinput 2 N2 Segment voltage Us for 2 and 3 wire termination Ground contact GND for 3 wire termination 44 Signal input 3 IN3 24 Signalinput 4 N4 Segment voltage Us for 2 and 3 wire termination Ground contact GND for 3 wire termination 5550B002 Figure 1 Terminal with appropriate connector 5550_en_04 PHOENIX CONTACT 5 Internal Circuit Diagram 5550C003 Figure 2 Internal wiring of the terminal points Protocol chip bus logic including voltage conditioning LED status indicators acy Optocoupler H E f Digital input Electrically isolated area Other symbols used are explained in the IL SYS INST UM E user manual or in the In

Download Pdf Manuals

image

Related Search

Related Contents

USER'S MANUAL  Omega Speaker Systems OS550-BB Series User's Manual  NuTone Hampton Series User's Manual  cahier des charges techniques plafonds suspendus  Bibliographie  Abspielen - Disc Players  Modo de empleo recetas para baristas  Coudre ce qui fait plaisir  Lancement du Budget Participatif 2015 Mardi 13  GPS, o la lección del Dakar  