Home
ENGLISH
Contents
1. line of sight and properly aligned with the Tx Rx unit as shown in the picture below Upper view Normal position of the reflector on the P central line of sight ____ New location of the reflector shifted from Reflector the central line of sight and perpendicular realignment of the Tx Rx unit and the reflector with the optical beam GLOSSY WALL Figure 4 Installation of a Tx Rx unit and a passive reflector on glossy surfaces FASTENING Detector Tx Rx Tx Rx Unscrew the four screws placed on the front cover of the detector and remove it Drill the wall where the detector will be mounted fix the detector by using the proper screw anchors and screws using all the four fixing points then insert the plastic stopper in each screw seat Insert the rubber gasket in the perimetric seat of the base contact point with the front cover taking care to positioning the conjunction point of the two ends downward Prepare the electrical conduits used for cables and relevant cable glands by using the knock out plugs available on the plastic bottom of the container in order for the container to be airtight at the end of installation Before closing the cover of the detector perform all the electrical connections and the alignment operations of the system as described later Passive reflector Drill the surface wall on which the passive reflector will be mounted By using the screw anchors and screws fix the reflector and clean
2. D OFS Alarm relay contact Conventional detection gt circuit from a fire 6 basso S SS detection control panel Pa Optional only use on Rx or Tx Rx units Tx Rx or Tx Rx unit Figure 8 Example of connections of the Tx Rx or Tx Rx unit MECHANICAL CHARACTERISTICS Figure 9 Overall dimensions and drilling template TECHNICAL CHARACTERISTICS Consumption in idle 12 Vdc Tx Rx Tx Rx 45 mA 35 mA 45 mA 20 25 30 35 Maximum overatina distance 150 meters separate Tx and Rx i 100 meters Tx Rx and passive reflector Wavelength of the transmitter beam 890nm Tolerance to the beam misalignment separate 1 Tx and Rx Tolerance to the beam misalignment TxRx unit 0 5 5 and passive reflector selectable via jumper selectable via jumper selectable via jumper Conventional detection circuit input voltage 10 20 Vdc range pre alarm condition alarm condition duration 10 3 C 55 2 C Relative humidity 10 cm x 10 cm Passive reflector dimensions 20 cm x 20 cm 30 cm x 20 cm 248x122x120 mm Weight 900 g Compliant with the standard EN54 12 2002 Line smoke detector using an optical light beam Fire security FLR100 Urmet S p A 1293 CPR 0407 DoP n 1293 CPR 0407 14 FL100 1293 Urmet S p A 1293 CPR 0406 DoP n 1293 CPR 0406
3. ENGLISH GENERAL DESCRIPTION FLR100 and FL100 are the optical beam smoke detectors whose working principle is based on the attenuation of the light intensity of an infrared light beam due to smoke The infrared light beam is transmitted by a transmitter unit Tx and received and properly processed by a receiver unit Rx More specifically the receiver unit Rx processes an electrical signal proportional to the intensity of the received light and notifies an alarm or fault condition if the signal falls below an alarm or fault threshold continuously for a predefined amount of time FLR100 and FL100 can work in either one of the following configurations e transmitter receiver unit FLR100 Tx Rx passive reflector e transmitter unit FL100 Tx receiver unit FL100 Rx The former requires a single device FLR100 configured to work simultaneously as transmitter and receiver and a passive reflector whose purpose is to reflect towards the receiver the light beam sent by the transmitter The latter involves two separate FL100 devices one configured to work exclusively as transmitter and one as receiver FLR100 and FL100 are equipped with three LED indicators and two 7 segment displays for notification of several types of information Also there are a fault relay and two relays used to signal the pre alarm and alarm conditions FLR100 and FL100 can be connected to a conventional fire detection circuit for signalling any alarm condition to the
4. control panel CONTENTS OF THE PACKAGE The package of the optical beam smoke detector contains the following items Optical beam smoke detector FLR100 e 1 transmitter receiver unit e 1 filter for alarm and fault condition verification e 1 installation and user manual e 4 plastic stoppers e 1 rubber gasket Optical beam smoke detector FL100 e 1 transmitter unit 1 receiver unit 1 filter for alarm and fault condition verification 1 installation and user manual 8 plastic stoppers 2 rubber gaskets The transmitter unit differs from the receiver unit because on the optical section of the transmitter a lens is mounted and is clearly visible A Warning since the device contains fragile optical parts it is recommended to protect it from accidental falls and hits CE LABELING AND RELEVANT DOCUMENTATION According to the requirements of the EN54 12 Standard below we report the CE labelling along with the required information C E C 3 1293 1293 IMELKRON ELKRON is a tademark of URMETS p A isa tademark of URMETS p A Via Bologna 188 C 10154 Torino Italy Via Bologna 188 C 10154 Torino Italy 14 14 1293 CPR 0407 DoP n 1293 CPR 0407 FLR100 1293 CPR 0406 DoP n 1293 CPR 0406 FL100 EN 54 12 Line detector using an optical light beam Fire safety EN 54 12 Line detector using an optical light beam Fire safety Documentation see doc LBT80777 Documentation see doc LBT80777 INSTALLATION The opt
5. control panel with open circuit fault generation caused by a fault on the detector The value of the end of line resistor depends on the control panel in use This type of connection must be performed only when the Tx or Tx Rx unit is the last point of the detection circuit ERROR CODES If an error condition occurs while the device operates the En information is displayed where n is an error code reported in the table below se eee Autocalibration error due to too high or too low signal level YES 6 Dataflash block deletion error NO 8 Dataflash word write error NO _9 Transmission error of a response frame to an UART1 command NO When an error condition occurs other than displaying the error code the device also performs the following operations e The fault relay switches e The yellow LED is turned ON e The program blocks itself Errors 1 and 2 are typical of the autocalibration procedure Error 3 is an internal error which occurs if the device cannot compensate a signal with a too high level The remaining errors are due to broken peripherals internal to the microcontroller mounted on the board The recoverable errors can be cancelled by moving the dip switch DS8 to the ON position in order to restart the alignment procedure The unrecoverable errors conversely block the program indefinitely CONNECTIONS Power Supply 24 Vdc Fault relay contact Pre alarm relay contact LON OS
6. he NO contact Pre alarm relay PC terminal connected to the NC contact JP2 2 3 Pre alarm relay PC terminal connected to the NO contact Alarm relay PC terminal connected to the NC contact 2 3 Alarm relay PC terminal connected to the NO contact Factory settings DIP SWITCHES FLR100 and FL100 are equipped with 10 dip switches which allow the user to configure the working mode of the detector and the relevant parameters Working mode i O DS DS Pre obscuration threshold only for Rx and Tx Rx modes DS3 DS4 DSS DS6 Fault signalling delay only for Rx and Tx Rx modes 5 seconds Alignment procedure only for Rx and Tx Rx modes DSBs Conventional detection circuit handling only for Rx and Tx Rx modes DS Conventional detection circuit handled CONT Reserved always leave in OFF position OFF Factory settings DS1 DS2 The DS1 and DS2 dip switches define the working mode of the device and its configuration is performed only at the factory Do not modify the DS1 DS2 settings the removal of the applied seals will cause the non compliance to the EN54 12 standard If the device is configured in the Tx mode the remaining dip switches are not used Conversely when the device is configured in the Rx mode or the Tx Rx mode the remaining dip switches must be properly configured by following the indications reported below DS3 DS4 The receiver section of the detector consta
7. he dip switch DS9 allows the user to enable this section By moving DS9 to the ON position the detector handles the conventional detection circuit as follows e Continuous check of the presence of the circuit voltage coming from the conventional control panel any interruption of this voltage leads to the cancellation of any ongoing alarm and or fault condition and to the reset of the detector to the normal working mode e The pre alarm and alarm conditions are signalled to the control panel by drawing some current from the conventional detection circuit by the conventional circuit section The physical connection with the control panel can be performed on the Rx or Tx Rx unit and on this unit the dip switch DS9 must be moved to ON On the Tx unit DS9 must remain in the OFF position By letting DS9 in the OFF position the conventional detection circuit section is disabled lt is important to highlight that this connection does not involve any transmission of the fault condition from the detector to the control panel In order to transmit the information of a fault condition to the control panel it is suggested to use the fault relay to open the detection circuit and break the electrical continuity of the circuit with its end of line resistor Power Supply 24 Vdc Conventional detection circuit from a fire detection control panel Rx or Tx Rx unit Figure 7 Example of connection with the detection circuit of a conventional
8. ical beam smoke detectors FLR100 and FL100 imply two different types of installation FLR100 Transmitter receiver unit Tx Rx passive reflector This configuration involves a single FLR100 which operates simultaneously as transmitter and receiver Tx Rx and a passive reflector placed at a distance from the Tx Rx unit between 5 and 100 meters The passive reflector must be chosen according to the distance from the FLR100 device Distance Type of passive reflector 5 20 meters 10cm x 10cm 20 50 meters 20cm x 20cm 50 100 meters 30cm x 20cm FL100 Separate transmitter unit Tx receiver unit Rx This configuration involves two separate FL100 devices One of them is configured as transmitter Tx and the other one as receiver Rx In this case the transmitter Tx and the receiver Rx can be placed at a distance between 5 and 150 meters PLACEMENT Locate the spot where the Tx and Rx units or the Tx Rx unit and the passive reflector must be placed by verifying that the walls must not be subject to movements vibrations and deformations due to temperature variations e g metallic supports there must not be any light reflection even temporary due to glossy surfaces mirrors or glasses located near the devices the optical path must be free from obstacles in a range of at least 50 cm the distance between the devices and the ceiling must be greater than 30 cm in case of sloping ceiling the rece
9. iver unit must be placed near the top of the ceiling if there is more than one receiver in the same room they must be placed at a maximum distance of 15 meters from each other the device positioning must be compliant with the national installation standards the devices must be horizontally mounted with the display correctly readable CEILING N 0 5 7 5m A distance between detectors 0 5 7 5 m P lt aa CEILING CEILING WALL 05 7 5m A distance between detectors 05 7 5m D 4 P lt Figure 2 Multiple optical beams installation Ee z m 12 10 HHA CREEL 0 O 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Minimum A distance between detectors m B distance between Tx and Rx units or between Tx Rx unit and reflector m Figure 3 Multiple optical beams installation Graph to be used to find out the distance between the detectors and the distance between the Tx and Rx units of each detector Moreover it is fundamental that the Tx and Rx units or the Tx Rx unit and the passive reflector are placed in front of each other with the beam light perpendicular to them as far as possible the light optical beam should be parallel to the ceiling and should follow the line of sight between the units In the special case of a passive reflector to be installed in a room with glossy surfaces e g glazed walls the reflector must be placed about 30 cm away from the
10. le to detect the fault the following condition is verified as well the signal arriving to the receiver is reflected exclusively by the passive reflector NORMAL OPERATING MODE When the optical beam smoke detector is working in normal operating mode the display is OFF and any signalling is performed exclusively by using the LEDs and the relays The signalling generated by the unit depends on the working mode it is configured for Tx Rx or Tx Rx e The transmitter unit Tx can only generate fault signalling due to internal malfunctioning of the unit The transmitter unit can never generate a pre alarm or an alarm condition e The receiver Rx or transmitter receiver Tx Rx unit can signal a pre alarm or alarm condition a fault condition caused by lack of received signal need for maintenance and fault condition due to an internal malfunctioning of the unit During the normal operating mode of the device the green LED is fixed ON Optical compensation and maintenance procedure During the normal operating mode the Rx or Tx Rx unit performs periodically every 15 minutes a procedure whose purpose is to compensate the reduction of received light intensity due to e accumulation of contaminating material dust etc on the lids of the units e slight mechanical misalignments between Tx and Rx units or between Tx Rx unit and passive reflector due to the structure where they are installed The compensation is performed by increasing the gain of the
11. n air After having installed and configured the detector either in the case of separate Tx and Rx units or in the case of a Tx Rx unit and a passive reflector perform the following operations power on the transmitter and the receiver by leaving the lids of each unit removed set the DS8 dip switch of the Rx or Tx Rx unit in the ON position the display will show the level of the received signal verify that the hexagonal nuts D1 D2 and D3 used to regulate the mechanical alignment on each unit are not at the limit stop and the Rx and Tx units are optically aligned by acting on the nuts D2 and D3 of the Rx or Tx Rx unit D1 is kept fixed look for any received signal during the procedure ensure to do not interfere with the infrared beam obtain the maximum signal on the receiver also acting on the nuts of the Tx unit repeat this procedure by alternating the regulations on both units in order to get the maximum signal level on the receiver unit for the autocalibration procedure to complete successfully the received signal level must be higher than 12 mount the lid of the Tx unit and verify that the received signal level has decreased by no more than 3 4 points otherwise re check the alignment move the dip switch DS8 on the Rx or Tx Rx unit to the OFF position the alignment procedure will be ended and the autocalibration procedure will be started within a period of 3 minutes mount the lid of the Rx or Tx Rx unit during this phase the yello
12. ntly monitors an electrical signal proportional to the received light intensity If any smoke is present the light intensity decreases compared to the intensity received in clean air and the device detects an alarm condition when the light intensity decreases at least of 35 compared to the value in clean air for a continuous interval of at least 5 seconds Once detected the alarm condition is notified to the user by turning the red LED on and by activating the pre alarm and alarm relays Dip switches DS3 and DS4 allow the user to set a pre obscuration threshold which if crossed leads to the activation of the pre alarm relay and makes the red LED blink For instance DS3 DS4 OFF OFF define a 20 pre obscuration threshold In such a case when the light intensity undergoes an attenuation between 20 and 35 for at least 5 seconds the pre obscuration condition is detected and notified to the user by activating the pre alarm relay RELAY1 and making the red LED blink If the light intensity is further reduced and goes under the 35 threshold for at least 5 seconds the detector enters the alarm condition which is notified to the user by activating the alarm relay and turning the red LED fixed ON lf DS3 DS4 ON ON the pre obscuration threshold equals the alarm threshold In such a case when both thresholds are crossed the alarm condition is notified directly to the user DS5 DS6 If the received light intensity undergoes an atte
13. nuation of at least 95 fault threshold for at least n consecutive seconds n is defined base on the settings of DS5 and DS6 the device detects a fault condition which is notified to the user by switching the fault relay and turning the yellow LED ON DS7 The Memory ON working mode implies that when the device detects a fault this condition is signalled until the device is powered off or it receives a reset pulse on the detection circuit the latter condition must be enabled by properly setting the DS9 dip switch The Memory OFF working mode conversely implies that the fault condition signalling ends by turning the yellow LED OFF and switching the fault relay when the light intensity signal goes above the fault threshold for a continuous period of n seconds n fault signalling delay DS8 This dip switch is thoroughly described in the chapter related to the alignment and autocalibration DS9 This dip switch is thoroughly described in the section related to the conventional detection circuit DS10 This dip switch must be always left in the OFF position ALIGNEMENT AND AUTOCALIBRATION The alignment and autocalibration procedure is composed of a manual phase and an automatic phase The manual phase consists of searching the mechanical alignment between the transmitter and the receiver the automatic phase consists of a fine tuning of the gain of the receiving amplifier in order to get a valid reference signal in clea
14. r can take on one of the three aforementioned states based on the current condition Terminal board The detector is equipped with 2 terminal boards used for the electrical connections described below Terminal board M1 POWER IN Power supply positive input 12 24Vdc Hat Power supply negative input toe Fault relay output contact selectable between NO and NC see JP1 ie 2 Alarm relay output contact selectable between NO and NC see JP3 RELAY 2 Alarm relay output common contact Terminal board M2 pa Positive input of the Conventional circuit section LINE as tf ae ct f Negative input of the Conventional circuit section Relays The detector is equipped with 3 signalling relays described below the left column reports the silk screen printing of each relay This relay signals the fault and maintenance conditions lt works in safe mode i e when the detector is powered on and no fault or maintenance condition is present the relay is excited When the detector is powered off or a fault or maintenance condition occurs the relay is not excited RELAY 1 This relay is used to signal the pre alarm condition RELAY 2 This relay is used to signal the alarm condition Jumpers The detector is equipped with a set of jumpers described below Jumper _ Position Description gt Z gt S JP Fault relay PC terminal connected to the NC contact 2 3 Fault relay PC terminal connected to t
15. received signal amplifier If the gain reaches a predefined maximum value the reduction of the light intensity cannot be further compensated and the device enters the maintenance state the fault relay switches and the yellow LED starts blinking In such a condition the lid of the device must be cleaned by the operator without being removed Once the cleaning is done the received signal level should increase and suddenly go beyond the reference level In such a condition an 1 minute verification interval starts During this interval both green and yellow LEDs blink simultaneously If the signal level goes below the reference level the device exits the verification phase and remains in maintenance state When the verification interval expires the gain of the receiver amplifier is automatically reduced in order to bring the received signal level to the reference value and the device returns in the normal operating mode Note that in case of a pending alarm or fault condition the periodic optical compensation procedure is not performed If an Rx or a Tx Rx unit is turned OFF in normal operating mode i e without any pending alarm condition the optical compensation procedure is performed automatically when the unit is turned ON again CONVENTIONAL DETECTION CIRCUIT SECTION The optical beam smoke detector can be connected to a conventional detection circuit of a conventional control panel by enabling a suited conventional circuit section T
16. rning the red LED fixed ON and activating the pre alarm and alarm relays RELAY1 and RELAY2 Now remove the alarm filter and then remove the alarm condition by e either turning OFF and then ON the receiver unit e ofr issuing a reset command on the fire detection control panel this method is applicable if the detection circuit coming from the control panel is connected to the LINE terminals see dip switch DS9 Now perform the fault detection verification use the alarm fault filter and place the area F on the optics of the receiver and verifying that e after n seconds n fault signalling delay configurable via dip switches DS5 DS6 the fault condition is detected and notified by turning the yellow LED fixed ON and switching the fault relay After removing the obscuration of the receiver restore the normal working mode of the device by performing one of the following operations e wait for n seconds if the device is configured in memory OFF mode see dip switch DS7 e turn the receiver unit OFF and then ON if the device is configured in memory ON mode e issue a reset command on the fire detection control panel this method is applicable if the detection circuit coming from the control panel is connected to the LINE terminals see dip switch DS9 The fault condition on an installation composed of a Tx Rx unit and a passive reflector is verified by covering the passive reflector This way other than verifying that the device is ab
17. the reflecting surface at the end of installation Electronic board of the detector The detector is composed of one single electronic board which is the same for all the models Tx Rx and Tx Rx This board hosts the electronic components and the optical section Do not remove or separate the parts which compose the optical section of the detector O a POWER R 8 LED PC B FAULT m A Be RELAY 1 i CC 2 l RELAY 2 amp Bers x 2 M2 g A DISPLAY O gt Gia P o Figure 5 View of the board of the detector Indicators The detector is equipped with three LED indicators and two 7 segment displays used to provide the following information LED indicators OFF the device is powered off GREEN ON the device is working normally LED Blinking the device is working normally but the received signal level is higher than the normal reference level RED OFF the device is working normally LED ON the device is in alarm condition Blinking the device is in pre alarm condition YELLOW OFF the device is working normally LED ON the device is in fault condition Blinking the device requires maintenance DISPLAY When ON it shows the received signal level lf a fault condition occurs the message Enis shown where n is the identifier of the fault During the alignment and auto calibration procedure each LED indicato
18. w and red LEDs of the unit blink alternatively whereas the green LED is fixed ON at the end of 3 minutes period the Rx or Tx Rx unit will activate the automatic regulation of the gain of the amplifier chain on the receiver side in order to align the received signal to a reference value a typical value is 25 and verify that the received signal is stable enough for a specific amount of time during this phase the red LED is ON when the signal is higher than the reference value the yellow LED is ON when the signal is lower than the reference value at the end of the automatic gain regulation the red and yellow LEDs are turned OFF whereas the green LED is fixed ON NOTE please take into account that the autocalibration procedure can last several minutes If the procedure fails the yellow LED is fixed ON and the display shows the error cause Transmitter optical section Receiver optical section D3 Figure 6 Internal view of the detector the hexagonal nuts used for mechanical regulations are highlighted FUNCTIONAL VERIFICATION The functional verification of the device must be performed at the end of the alignment and autocalibration procedure and in general whenever suitable In order to perform the alarm detection verification use the provided alarm fault filter and place the area A on the optics of the receiver Then verify that e after an interval of 5 seconds the alarm condition is detected and notified by tu
Download Pdf Manuals
Related Search
ENGLISH english to spanish english to russian english to french english to japanese english to german english english to korean english to tamil english to spanish translation english to italian english to chinese english to hindi english to tagalog english to marathi english to latin english to arabic english to tagalog translator english bulldog english to telugu english to vietnamese english to spanish google translate english to polish english alphabet english breakfast english language
Related Contents
Connecting an LCD or VFD to the PiXi (2.0) Instruction Manual DATA LOGGING SOFTWARE FOR 4 Team2 SW Help User Manual - Carousel Port 2.1 Fiche constructeur Tympanic Thermometer - Nurse Rosie Products Manual do utilizador 65721 feuillet.FH11 Lightolier LFK4 User's Manual 取扱説明書 - 日東工業株式会社 N-TEC Copyright © All rights reserved.
Failed to retrieve file