Witte Software Modbus Poll User manual

image

Contents

1. 42001 000000 Temp 1 42002 000000 Temp 2 42003 000000 nanna annnnan 5 10 Enron Daniel Mode Enron or Enron Daniels Modbus is Standard Modbus with a few Vendor Extensions The exact impact of these extensions is context dependent but most common Modbus commands works as expected There are some custom vendor defined functions available but few users expect or use them The largest impact has to do with how 32 bit data values are read written Enron Modbus defines two special 4x holding register ranges e 4 x5001 to 4x5999 are assumed 32 bit long integers 4 bytes per register e 4x7001 to 4x7999 are assumed 32 bit floating points 4 bytes per register Dealing with 32 bit values in Modbus is NOT unique to Enron MB However Enron MB takes the debatable step of returning 4 bytes per register instead of the 2 bytes implied by the term holding register in the Modbus specification This means a poll of registers 4x5001 and 4x5002 in Enron Modbus returns 8 bytes or two 32 bit integers whereas Standard Modbus would only return 4 bytes or one 32 bit integer treated as two 16 bit integers In addition polling register 4x5010 in Enron MB returns the tenth 32 bit long integer whereas Standard Modbus would consider this 1 2 of the fifth 32 bit long integer in this range 5 11 Rows Specify the number of rows in the grid you prefer http www modbustools com 16 Modbus Poll User manual 6 Display formats Mark the cells to be
2. Longs Index newvalue 11 4 5 Float Property Floats Index As Integer As Single Description Sets a float in the write array structure or return a float from the read array Syntax Floats Index newvalue 11 4 6 Double Property Doubles Index As Integer As Double Description Sets a double in the write array structure or return a double from the read array Syntax Doubles Index newvalue http www modbustools com 35 Modbus Poll User manual 11 5 Automation Write Functions The write functions write the values stored in the array filled by the properties The functions are associated with a Modbus Poll document The window with data 11 5 1 WriteSingleCoil Function WriteSingleCoil SlavelD As Integer Address As Long As Integer Return Value True if write array is ready and the data are sent False if array empty or error in parameters The controlling application is responsible for verifying the write operation by reading back the value written Parameters SlavelD The slave address O to 255 Address The data address Base 0 Description Writes the first coil stored in the write array Function 05 is used 11 5 2 WriteSingleRegister Function WriteSingleRegister SlavelD As Integer Address As Long As Integer Return Value True if write array is ready and the data are sent False if array empty or error in parameters The controlling application is responsible for verifying the write operation
3. Public docl As Object Public doc2 As Object Public app As Object Dim res As Integer Dim n As Integer Private Sub StartModbusPoll Click Set app CreateObject Mbpoll Application Set docl CreateObject Mbpoll Document Set doc2 CreateObject Mbpoll Document Read 10 Holding Registers every 1000ms res docl ReadHoldingRegisters 1 0 10 1000 Read 10 Coil Status every 1000ms res doc2 ReadCoils 1 0 10 1000 docl ShowWindow app Connection 1 Modbus TCP IP app IPAddress 127 0 0 1 local host app ServerPort 502 app ConnectTimeout 1000 res app OpenConnection End Sub Private Sub Read Click Cells 5 7 docl ReadResult Show results for the requests Cells 6 7 doc2 ReadResult For n 0 To 9 Cells 5 n 2 docl SRegisters n Next n For n 0 To 9 Cells 18 n 2 doc2 Coils n Next n End Sub http www modbustools com 26 Modbus Poll User manual 11 2 Connection Functions Properties The following properties and functions do the same as you setup in the connection dialog F3 Connection selects the desired connection A serial port or one of the Ethernet connections can be 11 2 1 Connection selected Property Connection as Integer Valid values 0 Serial port 1 Modbus TCP IP 2 Modbus UDP IP 3 Modbus ASCII RTU over TCP IP 4 Modbus ASCII RTU over UDP IP 11 2 2 BaudRate Applicable only for Connection 0 Property BaudRate as Long
4. 3 5 char time gap between response and a new request can t be guaranteed This is because the Windows scheduler switch tasks every 10 20ms 1 If you Polls several slaves in a serial RS485 network you should NOT set the value lower than 20ms This is to ensure the 3 5 char time gap 2 Ina TCP IP network less than 20ms is ok 3 Serial connection to only one slave device less than 20ms is ok 4 6 Remote Server Remote server settings are only available when use an Ethernet connection e IP Address Servers IP address Default is local host 127 0 0 1 e Port Server port number Default 502 e Connect Timeout Max time to use to establish a connection Default 1000 4 7 Advanced settings 4 7 1 RTS Toggle RTS Toggle specifies that the RTS line will be high if bytes are available for transmission After all buffered bytes have been sent the RTS line will be low You can use this to switch direction if you have a 232 485 converter without automatic direction switch Warning The use of RTS controlled RS232 RS485 converters should be avoided if possible It is difficult to determine the exact time when to switch off the transmitter with non real time operating systems like Windows and Linux If it is switched off to early characters might still sit in the FIFO or the transmit register of the UART and these characters will be lost Hence the slave will not recognize the message On the other hand if it is switched off too late then the slave s
5. 8 N 1 This picture shows two open windows One reading 10 Holding registers from address 4000 44001 and another reading 10 Holding registers from address 2000 42001 3 1 Help from anywhere Press F1 and get context sensitive help on a topic associated with the current selected item SHIFT F1 invokes a special help mode in which the courser turns into a help courser arrow question mark The user can then select a visible object in the user interface such as a menu item toolbar button or window This opens help on a topic that describes the selected item 3 2 Alias cells Here you can type any text for designation of the value cells You can also copy paste text from Excel cells http www modbustools com 7 Modbus Poll User manual 3 3 Value cells Show the data values of the Modbus registers If you double click a value cell a dialog box lets you write a new value to the slave device Typing a number in a value cell shows the dialog as well It is possible to select the used Modbus function used to write the value The check box Close dialog on Response ok is used to automatically close the dialog box when a value is successfully sent This is convenient when a lot of values are to be changed In that way it is fast to select a new cell and then type a new value again Write Single Register Value Result N A 7 Close dialog on Response ok Use Function 06 Write single register 16 Write multiple
6. Valid values 300 600 1200 2400 4800 9600 14400 19200 38400 56000 57600 115200 128000 256000 Default value 9600 Example BaudRate 9600 11 2 3 DataBits Applicable only for Connection 0 Property DataBits as Integer Valid values 7 8 Default value 8 Example DataBits 8 http www modbustools com 27 Modbus Poll User manual 11 2 4 Parity Applicable only for Connection 0 Property Parity as Integer Valid values 0 None 1 Odd 2 Even Default value 2 Example Parity 2 11 2 5 StopBits Applicable only for Connection 0 Property StopBits as Integer Valid values 1 2 Default value 1 Example StopBits 1 11 2 6 SerialPort Applicable only for Connection 0 Property SerialPort as Integer Valid values 1 255 Default value 1 Example SerialPort 1 11 2 7 ResponseTimeout The ResponseTimeout specifies the length of time in ms that Modbus Poll should wait for a response from a slave device before giving up Property ResponseTimeout as Integer Valid values 50 100000 Default value 1000 Example ResponseTimeout 1000 11 2 8 ServerPort Applicable only for Connection 1 4 Property ServerPort as Long Valid values 0 65535 Default value 502 Example ServerPort 502 http www modbustools com 28 Modbus Poll User manual 11 2 9 ConnectTimeout The ConnectTimeout specifies the length of time that Modbus P
7. by reading back the value written Parameters SlavelD The slave address O to 255 Address The data address Base 0 Description Writes the first register stored in the write array Function 06 is used 11 5 3 WriteMultipleCoils Function WriteMultipleCoils SlavelD As Integer Address As Long Quantity As Integer As Integer Return Value True if write array is ready and the data are sent False if array empty or error in parameters The controlling application is responsible for verifying the write operation by reading back the values written Parameters SlavelD The slave address 0 to 255 Address The data address Base 0 Quantity The number of data 1 to 1968 Description Write the coils stored in the write array Function 15 is used http www modbustools com 36 Modbus Poll User manual 11 5 4 WriteMultipleRegisters Function WriteMultipleRegisters SlavelD As Integer Address As Long Quantity As Integer As Integer Return Value True if write array is ready and the data are sent False if array empty or error in parameters The controlling application is responsible for verifying the write operation by reading back the value written Parameters SlavelD The slave address O to 255 Address The data address Base 0 Quantity The number of data 1 to 123 Description Write the registers stored in the write array Function 16 is used http www modbustools com 37 Modbus Poll User manual 12 Exception and error
8. formatted Select one of the 16 display formats from the display menu 6 1 Native Modbus registers The 16 bit Modbus registers can be displayed in 4 different modes e Signed e Unsigned e Hex e Binary 6 2 32 bitlong This combines 2 16bit Modbus registers It can be displayed in 4 different word byte orders e Long AB CD e Long CD AB e Long BA DC e Long DC BA Example Byte Order AB CD The decimal number 123456789 or in hexadecimal 07 5B CD 15 Order as they come over the wire in a Modbus message 07 5B CD 15 6 3 32 bit floating This combines 2 16bit Modbus registers It can be displayed in 4 different word byte orders e Float AB CD e Float CD AB e Float BA DC e Float DCBA Example Byte Order AB CD The floating point number 123456 00 or in hexadecimal 47 F1 20 00 Order as they come over the wire in a Modbus message 47 F1 20 00 6 4 64 bit double This combines 4 16bit Modbus registers It can be displayed in 4 different word byte orders e Double AB CD EF GH e Double GH EF CD AB e Double BA DC FE HG e Double HG FE DC BA Example Byte Order AB CD EF GH The floating point number 123456789 00 or in hexadecimal 41 9D 6F 34 54 00 00 00 Order as they come over the wire in a Modbus message 41 9D 6F 34 54 00 00 00 http www modbustools com 17 Modbus Poll User manual 7 Save Open Workspace If you open many related Modbus windows it is convenient to save a snapshot of the current layout of all open and ar
9. in the top most 3 lines in the Excel sheet o Alias cells in top row Insert alias names in row 3 o Poll definition Insert ID Function etc in row 2 o Name Insert a log name in row 1 http www modbustools com 22 Modbus Poll User manual Poll definition ID 1 Function 03 Address 0 ScanRate 1000 Power Levell Temp 01 29 12 22 33 45 471 232 01 29 12 22 33 46 753 234 01 29 12 22 33 47 768 235 01 29 12 22 33 48 784 236 01 29 12 22 33 49 799 237 01 29 12 22 33 50 815 238 01 29 12 22 33 51 831 239 01 29 12 22 33 52 846 240 Excel log with header information http www modbustools com 23 Modbus Poll User manual 10 Communication traffic Select the menu Display gt Communication to show the traffic on the serial line or Ethernet cable Use the stop button to temporary stop the update for inspection Use the copy button to copy selected line to the clipboard Note This window show only data sent and received by Modbus Poll You can t use it as a data sniffer Hint Leave this window open while doing other commands http www modbustools com 24 Modbus Poll User manual 11 OLE Automation Automation formerly known as OLE Automation makes it possible for one application to manipulate objects implemented in another application An Automation client is an application that can manipulate exposed objects belonging to another application This is also called an Automation controller An Automation server is a
10. message is corrupted and the master will not recognize the message 4 7 2 DSR DSR specify whether the DSR data set ready signal is monitored for output flow control If this member is TRUE and DSR is turned off output is suspended until DSR is sent again http www modbustools com 11 Modbus Poll User manual 4 7 3 CTS CTS specify whether the CTS clear to send signal is monitored for output flow control If this checkbox is enabled and CTS is turned off output is suspended until CTS is sent again 4 7 4 DTR DTR specifies whether the DTR will be enabled or disabled whenever the port is opened 4 7 5 Remove Echo If your device or RS232 RS485 converter echoes the chars just sent http www modbustools com 12 Modbus Poll User manual 5 Read Write definition Use this command to define the data to be monitored for the active window To open the Read Write Definition dialog you have 3 options e Press F8 e Select Read Write Definition from the Setup menu oo e Press onthe tool bar Slave ID Function 03 Read Holding Registers 4x Cancel Address 0 Protocol address E g 40011 gt 10 Quantity 10 Scan Rate 1000 ms Apply Disable _ Read Write Disabled _ Disable on error Read Write Once View Rows 010 20 50 100 Fitto Quantity _ Hide Alias Columns PLC Addresses Base 1 Address in Cell Enron Daniel Mode 5 1 Slave ID Range 1 to 255 MODBUS protocol specifi
11. messages Modbus Exceptions and error messages are display in red text in 2 line in each window E device 1 x 4114 Err 4 ID 1 F imeout Error 12 1 Modbus Exceptions Modbus exceptions are errors returned from the slave device Illegal Function The function code received in the query is not an allowable action for the server or slave This may be because the function code is only applicable to newer devices and was not implemented in the unit selected It could also indicate that the server or slave is in the wrong state to process a request of this type for example because it is not configured and is being asked to return register values Illegal Data Address The data address received in the query is not an allowable address for the server or slave More specifically the combination of reference number and transfer length is invalid For a controller with 100 registers a request with offset 96 and length 4 would succeeds a request with offset 96 and length 5 will generate exception 02 Illegal Data Value A value contained in the query data field is not an allowable value for server or slave This indicates a fault in the structure of the remainder of a complex request such as that the implied length is incorrect It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the MODBUS protocol is unaware of the signific
12. registers 3 4 Change color and font Select the cells to be changed and then right click Then a context menu is shown with 3 options to change colors and font E d Read write Definition F8 T Cuat Ctrl x O Copy Ctrl C q Paste Ctrl V Select All Ctri A q d Foreground Color N Ctrl F Background Color Ctrl B Font http www modbustools com 8 Modbus Poll User manual 3 1 4 e Big font 1150 1200 Colorize for better overview 3 5 Opena new window To open another window you have 3 options e Press CTRL N e Select new in the file menu e Press D on the tool bar http www modbustools com 9 Modbus Poll User manual 4 Connection dialog To open the connection dialog you have 2 options Press F3 Select connect from the connection menu Connection Setup Connection OK Cancel Serial Settings PCI Serial Port COM3 Mode e ATU ASCII 9600 Baud v Response Timeout 8 Data bits v 200 ms None Parity e Delay Between Polls 1 Stop Bit 0 ms Remote Modbus Server 192 168 1 27 502 3000 4 1 Connection There are 5 different connection types http Serial Modbus over serial line RS232 or RS485 A USB serial converter can be used Modbus TCP IP Select TCP IP if you want to communicate with a MODBUS TCP IP network In this case slave ID is the same as the Unit ID used in MODBUS TCP IP The port number is defaul
13. the data in an Excel spreadsheet 203 228 20 228 http 13 lt 40001 gt 14 lt 40001 gt 15 lt 40001 gt 16 lt 40001 gt 17395 17396 17394 13350 www modbustools com hero Seo e 21 ae EN E mM OO SS O OS oe EH E D EH EN Modbus Poll User manual 9 2 Microsoft Excel This feature requires that Microsoft Excel is installed Excel 2003 log is limited to 65535 logs as this is the max number of rows in an Excel sheet Excel 2007 is limited to 1 048 576 rows Each Modbus Window logs to its individual Excel sheet Select Excel Log from the setup menu or use short cut keys Alt X Do not touch the Excel sheet while logging as this will interrupt the logging Excel Log Setup Log rate Each read Rate 1 S Stop after 1000 Logs Log if data changed only Header intormation Y Insert header Yi Alias cells in top row Y Poll definition Name Type log name here 9 2 1 Log Rate e Each read Write a log line for all Modbus requests Log frequency as scan rate e Select Specify the log rate in seconds Log is independent of scan rate Remark If the scan rate is e g 10000ms it makes no sense to set a 1 sec log rate as data are logged only when new data are ready e Stop after Specify the number of log lines Note that Excel 2003 is limited to 65 536 rows and Excel 2007 1 048 576 rows 9 2 2 Header information e Insert header Information is inserted
14. to 3600000ms Note that setting the scan rate lower than the transaction time does not make sense If a serial connection at 9600baud is used and 125 registers are requested the transaction time is roughly 8 2 250 2 262ms the gap gt 3 5 char time between the request and the response In this case setting the scan rate at e g 100ms do not make sense as the transaction time is at least 262ms delay in the slave gap min time between polls Set in the connection dialog 5 6 Read Write Disabled The Read Write Disabled check box can be used to temporary enable or disable the communication for this window A text Disabled is then shown along with the Tx and Error counters Di device2 Colas x 1284 Err 0 ID 255 F 03 SR 1000ms DISABLED If Read Write is disabled you can make single requests with the Read Write Once button or press F6 SL 05 5 6 1 Disable on error The Disable on error check box is used to disable Read Write in case of error 5 7 Hide alias columns The Hide Alias Columns is used to hide all alias columns This is convenient to make more space if they are not used 5 8 Address in cell If enabled the address is also shown in the value cell like 2000 00000 Temp 2 2002 000000 MA nnnnnn http www modbustools com 15 Modbus Poll User manual 5 9 PLC Addresses Base 1 This option will show the addresses as device address Alias
15. 00 00 00 00 00 06 01 03 00 00 00 OA The first 6 bytes are the TCP IP header 8 3 Test center string file With a text editor such as notepad or similar you can prepare strings to be used in the test The first line in the file must be the string Test Center This is how Modbus Poll knows that the file is the correct format Press Open list to open the prepared text file 8 3 1 Content of a string list Modbus Poll 3A 30 31 30 33 30 30 30 30 30 30 30 41 3A 30 32 30 33 30 30 30 30 30 30 30 41 3A 30 33 30 33 30 30 30 30 30 30 30 41 8 4 Copy Use the Copy button to copy selected Tx Rx strings to the clipboard The SHIFT and CTRL keys can be used together with the mouse to select and deselect strings select groups of strings and select non adjacent strings Hint Leave this window open while doing other commands http www modbustools com 19 Modbus Poll User manual 9 Modbus Data logging You can log data to either a text file or direct to Microsoft Excel 9 1 Text file Select Log from the setup menu or use short cut keys Alt L Each Modbus Window logs to its individual text file When you want to stop the data logging then select the logging off command on the setup menu Log Rate Delimiters Each Read Fixed Width O Select D Comma Rate 1 D Tab Log if data changed only Start Log when OK is pressed Log Errors Start Log when mbs file is opened Log Date Flush to file immedi
16. 4 means Holding registers and 4x registers counts from 1 And even more confusing 4x means function code 03 and 3x means function code 04 5 3 3 5 digits vs 6 digits addressing The address format 4x counts from 40001 to 49999 The next address is not 50000 In old days 9999 addresses was enough There are cases where 9999 is not enough Then a zero is added 40101 become 400101 and so on This is called 6 digits addressing or extended addressing This is not a problem with Modbus Poll 410001 become 10000 The 4 is thrown away and the rest 10001 is decremented by 1 as we count from 0 instead of 1 5 4 Address examples These examples show how to setup Modbus Poll if a specification use device addresses 5 4 1 Read Holding Registers You want to read 20 registers from device address 40011 from slave ID 2 every 1000ms From the 4 we know this is function 03 Read Holding Registers Slave ID 2 Function 03 Read Holding Registers 4x Address 10 11 minus 1 Quantity 20 Scan rate 1000 http www modbustools com 14 Modbus Poll User manual 5 4 2 Read Discrete Inputs You want to read 1000 coils from address 110201 from slave ID 5 every 500ms From the 1 we know this is function 02 Read Discrete Inputs Slave ID 5 Function 02 Read Discrete Inputs 1x Address 10200 10201 1 Quantity 1000 Scan rate 500 5 5 Scan rate The scan rate can be set from 0
17. CII on RS232 or RS485 networks USB RS232 485 Converter 2 2 2 3 2 4 Modbus TCP IP Modbus Over TCP IP Modbus RTU ASCII encapsulated in a TCP packet Modbus UDP IP Modbus over UDP IP Modbus RTU ASCII encapsulated in a UDP packet Supported Modbus Functions 01 Read coils 02 Read discrete inputs 03 Read holding registers 04 Read input registers 05 Write single coil 06 Write single register 15 Write multiple coils 16 Write multiple registers 17 Report slave ID 22 Mask write register 23 Read Write registers Data logging Log data to a text file Log data direct into Excel Display formats Each cell can be individual formatted 2 5 http Signed 16 bit register Unsigned 16 bit register Hex Binary 32 bit long with any word byte order 32 bit float with any word byte order 64 bit double float with any word byte order Miscellaneous features OLE Automation for interfacing with Excel VB etc Monitoring of data traffic Print and print preview Font and color selection www modbustools com 6 Modbus Poll User manual 3 Overview Modbus Poll uses a multiple document interface That means several windows can be opened Each one with different data contents from different slave devices at the same time File Edit Connection Setup Functions Display View Window Help Dae x S 1 05 06 15 16 17 22 23 Tc H KW wolls Din amp iwinikK o For Help press Fl Port 7 9600
18. Witte Software Modbus Poll User manual Modbus Master Simulator June 2015 Modbus Poll version 6 3 Copyright Witte Software 2002 2015 http www modbustools com Table of content L O 5 2 Modbus Poll Features cuina iria 6 2 1 lee ge EE 6 2 2 Supported Modbus FUNCIONS wcscisscccacsasvecasissedeasessetecetaessnasedsaacesudssdeedss Aa a 6 2 3 RECH 6 2 4 BIS NIE Ate 6 2 5 Miscellaneous features 6 A A 7 3 1 Help from ANY WIN OL iio iii 7 3 2 LIEGE H 3 3 MANS EE 8 3 4 Change Color ANd FONE 2 c650563ccccscdeeissssenncacecteciapascundereecessanssennseseetecsanssen seseedecssossensseseetcdsnassasiesestesss 8 3 5 OPEN a New WIN Wisin E diia A edi 9 A Connection dialog resar A iaa in 10 4 1 CONNECCION EE 10 4 2 S nial SEtiNE eeh eeh eegen 11 4 3 Mode EE 11 4 4 RESPONSE dl Ee UE 11 4 5 Min delay between polls coconcocococncnononononannnonononanonononnnnnnnnnnnnno nn nnnnncnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnns 11 4 6 un eg EE 11 4 7 PANO WE gel e ET 11 4 7 1 RER TEE 11 4 7 2 NEE 11 4 7 3 E EE 12 4 7 4 RU 12 4 7 5 REMOVE ECNO ici A SEAN 12 5 Read Write deftnitton nono nanrnnnnannn nn nn nnnnnnnnnonn nn nan rannnnnno nono naninnnnanns 13 5 1 Slave ID REH 13 5 2 FUNCION Re TEE 13 5 2 1 Read Kelte de 13 5 2 2 Writ functions 3 hectic ti A ai 14 5 3 Lee PA 14 5 3 1 Protocol message address scccsscecesseeesseceesceceseccsseeecsaececseecessecesaececaueceeseecsseecesaeeseateceetess 14 5 3 2 DEVICE AO TESSA
19. ance of any particular value of any particular register Slave Device Failure An unrecoverable error occurred while the server or slave was attempting to perform the requested action Acknowledge Specialized use in conjunction with programming commands The server or slave has accepted the request and is processing it but a long duration of time will be required to do so This response is returned to prevent a timeout error from occurring in the client or master The client or master can next issue a Poll Program Complete message to determine if processing is completed Slave Device Busy Specialized use in conjunction with programming commands The server or slave is engaged in processing a long duration program command The client or master should retransmit the message later when the server or slave is free http www modbustools com 38 Modbus Poll User manual 12 2 Modbus Poll error messages Timeout error The response is not received within the expected time Response Error The response is not the expected one Different slave ID CRC Error The CRC value of the received response is not correct Write Error This is an error reported by the serial driver This could happen if a USB RS232 485 converter is used and the USB cable is unplugged There are 4 types Break condition l1 O error Serial connection error Output buffer overflow Write error using TCP IP connection is nor
20. ately Append File name Browse 9 1 1 Log Rate e Each read Write a log line for all Modbus requests Log frequency as scan rate e Select Specify the log rate in seconds Independent of scan rate Remark If the scan rate is e g 10000ms it makes no sense to set a 1 sec log rate as data are logged only when new data are ready 9 1 2 Delimiters As delimiter you can use one of following options e Fixed width Means that the values are organized in columns e Comma Values separated by a comma e Tab Values separated by a tab 9 1 3 Log if data changed only Specify that a new log line is written only if any data is changed since last log 9 1 4 Log Errors Specify that errors such a timeout etc are logged http www modbustools com 20 Modbus Poll User manual 9 1 5 Log Date Specify that the current date is added to the log time 9 1 6 Start Log when ok is pressed Specify that logging is started when ok button is pressed Otherwise the log setup is just stored when mbp file is saved 9 1 7 Start Log when mbp is opened Specify that logging is automatically started when a mbp file is opened 9 1 8 Flush to file immediately This ensures that log lines are not cashed in the file system but physical written immediately 9 1 9 Append Specify that logs are appended to selected file Otherwise a new file is created Example of a text file with fixed width 22 22 22 22 You can import
21. cations say 247 The value O is also accepted to communicate directly to a MODBUS TCP or MODBUS UDP device 5 2 Function code You can select 1 of 8 function codes 5 2 1 Read functions The data returned by the read functions are displayed on the grid window e 01 Read coils Ox e 02 Read discrete inputs 1x e 03 Read holding registers 4x e 04 Read input registers 3x http www modbustools com 13 Modbus Poll User manual 5 2 2 Write functions The write functions write the data displayed on the grid window e 05 Write single coil Writes to Coil status e 06 Write single register Writes to Holding registers e 15 Write multiple coils Writes to Coils e 16 Write multiple registers Writes to Holding registers 5 3 Address Addresses in the Modbus protocol are confusing Some protocol specifications use the protocol message address and others use device addressing 5 3 1 Protocol message address Some protocol specifications use the protocol message address counting from 0 to 65535 along with a function code This is also what the new Modbus specifications use This is the address inside the message sent on the wire Modbus Poll use protocol message address counting from O to 65535 5 3 2 Device address Some protocol specifications use device address registers Registers counts from 1 The first digit describes the function to be used That means the device address 40101 is identified by address 100 The
22. e O to 3600000ms 11 3 2 ReadDiscreteInputs Function ReadDiscretelnputs SlavelD As Integer Address As Long Quantity As Integer ScanRate As Long As Integer Return Value True if success False if not success Parameters SlavelD The slave address 1 to 255 Address The data address Base 0 Quantity The number of data 1 to 2000 ScanRate O to 3600000ms 11 3 3 HoldingRegisters Function ReadHoldingRegisters SlavelD As Integer Address As Long Quantity As Integer ScanRate As Long As Integer Return Value True if success False if not success Parameters SlavelD The slave address 1 to 255 247 is max according to MODBUS specification Address The data address Base 0 Quantity The number of data 1 to 125 ScanRate O to 3600000ms http www modbustools com 31 Modbus Poll User manual 11 3 4 InputRegisters Function ReadInputRegisters SlavelD As Integer Address As Long Quantity As Integer ScanRate As Long As Integer Return Value True if success False if not success Parameters SlavelD The slave address 1 to 255 Address The data address Base 0 Quantity The number of data 1 to 125 ScanRate O to 3600000ms 11 3 5 ShowWindow ShowWindow As default Modbus document windows are hidden The ShowWindow function makes Modbus Poll visible and show the document with data content 11 3 6 Byte order Property ByteOrder As Integer Description Sets the byte order used by Longs Floats and Doubles prop
23. eccscccsgecssciosatsed ecageadncegecs te caagensici gees ue 249s nance ACEN 34 LAA E e EE ER RE E WE E 35 ILAG DOUD A O AAN 35 11 5 Automation Write FUNCTIONS ccconononccccnncnnnonononancnnnnnnnnnnnononnnnnnnnnnnnnonnnnnnnnnnnnnnnnnnnncnnnannnnnnonnnncnnnanannns 36 11 5 1 WeitesingleCol lie aida dai aan da 36 11 5 2 WriteSingleRegistel vecs ocacion agitados 36 11 5 3 WriteMultiple Coils sesion dau Eed a 36 11 5 4 WriteMultipleRegisters occcccononoononcnncnnnnnononnnnonnnnnnnnononnnnnnnnnnnnnrononnnnnnnnnnnnnnnennnnnnnnnnnnonenannnos 37 12 Exception and error un 38 12 1 Modbus EXCEPtIONS ssrirmssl tees adensiscccteqetieesteqnsscnadeegeraadanGecastaetless tecleaseesace jena abandececsenBeceuvate 38 12 2 Modbus Poll error messages 39 http www modbustools com 4 Modbus Poll User manual 1 Modbus Poll Modbus Poll is an easy to use Modbus master simulator developed for many purposes Among others e Designers of Modbus slave devices for quick and easy testing of protocol interface e Automation engineers that need to test Modbus devices or networks on site e Service engineers that want to read out and or change specific service data from a device e Change Modbus registers in a slave device e Log data from Modbus devices e Troubleshooting and compliance testing http www modbustools com 5 Modbus Poll User manual 2 Modbus Poll Features 2 1 Connections Modbus Poll read write data from devices using Modbus RTU or AS
24. en Mbp is opene 21 9 1 8 Flush to file immediately 0 ccccesscsccccecsssesseaecececeseeseeeseeeeecesseuaeseeeescesseseaaeseeeesensseseaaeeesess 21 9 1 9 AD DONG EE 21 9 2 Microsoft Excel ccoo 22 9 2 1 LOB Ren esst ageseent dee A dla dla dde ada e 22 9 2 2 APP ennidesssuveavsnsnesesesteis 22 10 Communication d ue 24 11 OLE iAutomation ESEE EE EEEE ERAR SE EEEE EA ERESSE EEEE EAER RE RENEE ERRARE EEEE EEEn nnna 25 AS e Ee le EE 25 AS A locas Seen eer geed Bettel Seed TOEA EO 25 A e e e E a dia 25 T113 Excel sample COGS EE 26 11 2 Connection Eunctions Droperties 27 11 21 O e nu ed Le EE 27 T22 UR A eee re 27 Ab e SC EE KEE E 27 i SZ Sr EE 28 Ak e e Let TE 28 TL26 NEIE 28 11 2 7 A E RE 28 112 8 SSORVERP OME EE 28 11 29 CONMECTINIME LEE 29 11 2 10 EA DE 29 11 2 11 NANA II 29 11 2 12 Clos CONNECHON si eege eege EE Ee Eeer 30 11 3 Read Bet le EE 31 113 1 Read UE 31 LSZ ReadDiscreteldputs li eeh iaa 31 11 33 HoldingRegisteriuiiai lia 31 A leg EC 32 113 5 Showen ia 32 11 36 Byte Onder s crisscross a aE eA E Oia e aria E aaae EEES 32 113 7 E IT 33 11 38 WiiteResuUltacin A A Weaken ee eats EA 33 11 4 Automation data properties ccccccccccccssssssssececececssseseaeseceeecssseseeaeaeeeeseeseeseaaeseeeesesssesaaeaeeeeeeeeees 34 HAL COM sivecsavecccess ereescht deeg Ree Eed 34 114 2 Signed EE 34 http www modbustools com 3 Modbus Poll User manual 11 43 Unsigned RESIStEM cecssees
25. erties O AB CD Default 1 CDAB 2 BA DC 3 DC BA Example for Longs Byte Order AB CD The decimal number 123456789 or in hexadecimal 07 5B CD 15 Order as they come over the wire in a Modbus message 07 5B CD 15 Syntax ByteOrder newvalue http www modbustools com 32 Modbus Poll User manual 11 3 7 ReadResult Use this property to check if communication established with Read is running successful Property ReadResult As Integer Return Value 0 SUCCESS 1 TIMEOUT ERROR 2 CRC ERROR 3 RESPONSE ERROR The response was not the expected slave id function or address 4 WRITE ERROR 5 READ ERROR 6 PORTNOTOPEN ERROR 10 DATA UNINITIALIZED 11 INSUFFICIENT BYTES RECEIVED 81h ILLEGAL FUNCTION 82h ILLEGAL DATA ADDRESS 83h ILLEGAL DATA VALUE 84h FAILURE IN ASSOCIATED DEVICE 85h ACKNOWLEDGE 86h BUSY REJECTED MESSAGE 87h NAK NEGATIVE ACKNOWLEDGMENT 11 3 8 WriteResult Return a write result as an integer Use this function to check if a write was successful The value is DATA_UNINITIALIZED until the result from the slave is available See ReadResult for a list of possible values Property WriteResult As Integer http www modbustools com 33 Modbus Poll User manual 11 4 Automation data properties The below properties are used to set or get values in the internal write read arrays in Modbus Poll The Index used is not a Modbus Address The Index always counts from 0 no matter o
26. f the address used The data properties are associated with a Modbus Poll document The window with data Example 1 doc is assumed created first See Excel example doc SRegisters 0 al doc SRegisters 1 10 doc SRegisters 2 1234 Write 3 registers stored in Modbus Poll internal array to Modbus address 100 40101 res doc WriteMultipleRegisters 1 100 3 Example 2 with floating point values doc Floats 0 Lo doc Floats 2 10 5 doc Floats 4 1234 12 res doc WriteMultipleRegisters 1 0 6 Write the 6 register stored in Modbus Poll 6 Registers are written as float is 32 bit wide 11 4 1 Coil Property Coils Index As Integer As Integer Description Sets a coil in the write array structure or return a coil from the read array Syntax Coils Index newvalue 11 4 2 Signed Register Property SRegisters Index As Integer As Integer Description Sets a register in the write array structure or return a register from the read array Syntax SRegisters Index newvalue 11 4 3 Unsigned Register Property URegisters Index As Integer As Long Description Sets a register in the write array structure or return a register from the read array Syntax Object URegisters Index newvalue http www modbustools com 34 Modbus Poll User manual 11 4 4 Long Property Longs Index As Integer As Long Description Sets a long in the write array structure or return a long from the read array Syntax
27. mally caused by lost connection Read Error This is an error reported by the serial driver There are 6 types Framing error Character buffer overrun Parity error Input buffer overflow O error Break condition Read error using TCP IP connection is normally caused by lost connection Insufficient bytes The response is not the expected length received Byte count error The byte count in the response is not correct Compared to the expected http www modbustools com 39 Modbus Poll User manual
28. n application that exposes programmable objects to other applications Modbus Poll is an automation server That means you can use any program that supports Automation such as Visual Basic Excel etc to interpret and show the MODBUS data according to your specific requirements 11 1 Excel example You should display the Developer tab or run in developer mode when you want to write macros 11 1 1 Excel 2007 Review View Developer ties ER ze Map Propertie impor lt a gt iI A4S A ode Expansion Packs gt Export Da 1 Click the Microsoft office button Es 2 Click popular and then select the show Developers tab in the ribbon check box and then click Excel options Note the ribbon is part of the Microsoft fluent user interface 11 1 2 Excel 2010 1 Click on the file tab Click options Excel Options window will open On the left pane click Customize Ribbon On the right pane under Main Tabs check the Developer check box BBW Click OK The Developer tab should now show in the ribbon right most tab http www modbustools com 25 Modbus Poll User manual 11 1 3 Excel sample code This example opens two windows One reading registers and another reading Coils Modbus Poll is hidden but you can show it by uncomment the ShowWindow line This will show one of the windows An example is also included with the Modbus Poll installation Start gt All Programs gt Modbus Poll gt Examples
29. o AE AE lees 14 5 3 3 5 digits vs 6 digits addressing occcononococoonnnnononononnnnnnncnnnnnnnononnnnnnnnnnnnno no nnnnnnnnnnnnnnnnnnnnnnnnannns 14 5 4 Address En iii Ad cause ed 14 5 4 1 Read Holding Registers csecsen area eE aE AE e Ea ARENE ia 14 5 4 2 Read Discrete INPUtS iii A A aE EE eiii 15 5 5 SCAN Be 15 5 6 Read Write Disabled E 15 5 6 1 Disable On CMO iaa a dha Bienes 15 5 7 Hide allas COMO A aa 15 5 8 Address lia A ae td 15 5 9 PLC Addresses Base Dia in ita ica AR E dra 16 5 10 Enron Daniel Mode nn nn ne annan SEEE ERRARE EEEE EE ERASERS errar anar rn nn naa 16 Bell CO COP E wactdsbencede Erena Aaea e a a eaa Eea E EERS 16 Le TE te E E 17 6 1 Native Modb s registers tai Ai aaa 17 6 2 A EE 17 6 3 32 Dit Oath E eese O 17 6 4 GA DIV OUD KSEE E E A a A 17 http www modbustools com 2 Modbus Poll User manual 7 S ve Open WorksPaCE cirina e aa aaa a aa ANN aa anaE aaa iE 18 Ss Testconter ias adas 19 8 1 ele ne 19 8 2 TCP IP EXAM EE 19 8 3 Testcenter string le oca ii e 19 8 3 1 Content OF arString list nica gud geed 19 8 4 RN 19 9 Modbus Data log giN8 coc ita 20 9 1 WOMENS AAA RA 20 9 1 1 Log Rates asadas dla da 20 9 1 2 Dette gesend ge 20 9 1 3 Log if data Changed only 20 9 1 4 LO ERRORS ccc cccs ceccscacewcs ca A 20 9 1 5 Log Deeg dese ocean dese cd snes vase seneettid sceieesieaebere A A deere cieceevetedenertudaweevcctaederascens 21 9 1 6 Start Log when Ok iS presse 21 9 1 7 Start Log wh
30. oll should wait for a TCP IP connection to succeed Applicable only for Connection 1 4 Property ConnectTimeout as Integer Valid values 100 30000ms Default value 1000ms Example ConnectTimeout 1000 11 2 10 IPVersion Applicable only for Connection 1 4 Property IPVersion as Integer Valid values 4 IP Version 4 6 IP Version 6 Default value 4 Example IPVersion 4 11 2 11 OpenConnection Opens the connection selected with the Connection property Function OpenConnection As Integer Return Value For error 3 5 Please check if you have the latest serial port driver O SUCCESS 1 Serial Port not available 3 Serial port Not possible to get current settings from port driver 4 Serial port Serial port driver did not accept port settings 5 Serial port Serial port driver did not accept timeout settings 12 TCP UDP Connection failed WSA start up 13 TCP UDP Connection failed Connect error 14 TCP UDP Connection failed Timeout 15 TCP UDP Connection failed IOCTL 17 TCP UDP Connection failed Socket error 21 TCP UDP Connection failed Address information Example how to open a Modbus TCP IP connection Public app As Object Dim res As Integer Set app CreateObject Mbpoll Application app Connection 1 Select Modbus TCP IP app IPVersion 4 app IPAddress S192 168 4 27 app ServerPort 502 ll app ConnectTimeout 1000 app ResponseTimeo
31. ranged Modbus Windows in one workspace A workspace mbw is a file that contains display information and file names of all open windows Not the actual contents To do this go to File gt Save Workspace When you open a workspace file Modbus Poll opens all Modbus Windows and displays them in the layout that you saved http www modbustools com 18 Modbus Poll User manual 8 Test center The purpose of this test dialog is to help MODBUS slave device developers to test the device with any string of their own composition The list box displays the transmitted data as well as the received data You can have several test strings in the pull down list box When you have entered a string then press the Add to List button then the string is added to the list The selected string is sent when the Send button is pressed With the Save list button you can store the strings in a text file Check the Add Check check box if you want to add a CRC or LRC to the end of the input string When using the test center you may want to disable communication from other windows Check the Read Write disable check box in Read Write Definition dialog Setup gt Read Write Definition 8 1 ASCII Example String in the combo box 3A 30 31 30 33 30 30 30 30 30 30 30 41 The transmitted string if LRC is added 3A 30 31 30 33 30 30 30 30 30 30 30 41 46 32 0D OA A CR LF pair are also added 8 2 TCP IP Example Read 10 holding registers
32. t 502 If the connection fails then try if you can ping your device at the command prompt If the ping command fails then Modbus Poll fails too Modbus UDP IP Select UDP IP if you want to communicate with a MODBUS UDP IP network This is the same as Modbus TCP IP but the connection less UDP protocol is used instead Modbus RTU ASCII over TCP IP This is a RTU or ASCII message send over a TCP IP network instead of serial lines Modbus RTU ASCII over UDP IP This is a RTU or ASCII message send over a UDP IP network instead of serial lines www modbustools com 10 Modbus Poll User manual Note Connection type 3 5 is not standard Modbus as specified by www modbus org but they are added for convenience Depending on your selection some other settings will be grayed 4 2 Serial Settings Use these parameters to set serial port settings They are only available if connection type is Serial Port 4 3 Mode Use this option to select RTU or ASCII mode Default RTU 4 4 Response timeout Response timeout specifies the length of time that Modbus Poll should wait for a response from a slave device before giving up Default is 1000ms 4 5 Min delay between polls This setting ensures a minimum delay until next request is transmitted no matter of the scan rate The resolution of this setting is approximately 15ms It s possible on some computers to obtain better resolution but not all Important If you set this value lower than 20ms the
33. ut 1000 res OpenConnection http www modbustools com 29 Modbus Poll User manual Example how to setup a serial connection Public app As Object Dim status As Integer Create an object to Modbus Poll Set app CreateObject Mbpoll Application app Connection 0 Mode is serial port app SerialPort 1 Com port 1 app BaudRate 9600 9600 baud app Parity 0 None parity app Mode 0 RTU mode app ResponseTimeout 1000 Wait 1000ms until give up status app OpenConnection 11 2 12 CloseConnection Function CloseConnection As Integer Return Value Zero if success Nonzero value if failed http www modbustools com 30 Modbus Poll User manual 11 3 Read Functions The following functions do the same as you setup in the read write definition dialog F3 Read functions are associated with a Modbus Poll document The window with data Example First a Modbus Poll document is needed Public doc As Object Set doc CreateObject Mbpoll Document res doc ReadCoils 1 0 100 1000 Read 100 coils every 1000ms Remarks You must create a Read before you can use properties to get data 11 3 1 ReadCoils Function ReadCoils SlavelD As Integer Address As Long Quantity As Integer ScanRate As Long As Integer Return Value True if success False if not success Parameters SlavelD The slave address 1 to 255 Address The data address Base 0 Quantity The number of data 1 to 2000 ScanRat