Home
Instruction Bulletin
Contents
1. 11 Re install the terminal cover Tighten the three M3 screws until snug maximum torque 1 2 Ibs in 0 113 0 226 Nm Do not overtighten 12 Restore control power to the circuit monitor To do this a Reconnect control power to the circuit monitor and I O devices b Remove the short on the CT shorting block c Re install the voltage input fuses 13 Run the Wiring Error Test to verify that the module is wired properly From the display Main Menu select Diagnostics gt Wiring Error Test For detailed instructions refer to the installation manual that shipped with your circuit monitor Electrical equipment should be installed operated serviced and maintained only by qualified personnel This document is not intended as an instruction manual for untrained persons No responsibility is assumed by Square D for any consequences arising out of the use of this manual Class No 3020 2002 Schneider Electric All Rights Reserved Schneider Es Electric Notice d utilisation Module courant tension CVM 0 63230 301 200C1 10 2002 pour POWERLOGIC Circuit Monitor s rie 4000 INTRODUCTION S CURIT OUTILS REQUIS REMPLACEMENT DU CVM Les raccordements de courant et de tension sont abrit s dans le module de courant tension CVM s par fix par des vis Allen et branch en usine dans le Circuit Monitor Toutes les donn es de mesure sont acquises via le module ce qui permet un raccordement direct pouvant alle
2. 12 R tablissez l alimentation du Circuit Monitor Pour ce faire proc dez comme suit a Rebranchez l alimentation du Circuit Monitor et des appareils d E S b Retirez le court circuit du bloc de court circuitage du TC c R installez les fusibles d entr e de tension 13 Effectuez le test d erreur de cablage pour v rifier que le module a t correctement cabl Dans le menu principal de l cran s lectionnez Diagnostics gt Test Erreur Cablage Pour des instructions d taill es reportez vous au manuel d installation livr avec votre Circuit Monitor L quipement lectrique doit tre entretenu seulement par un personnel de maintenance qualifi Ce document ne pr tend aucunement servir de guide d utilisation aux personnes inexp riment es Schneider Electric d cline toute responsabilit quant aux cons quences ventuelles d coulant de l utilisation de ce manuel Classe N 3020 2002 Schneider Electric Tous droits r serv s Es Electric Manual de instrucciones 24 63230 301 200C1 10 2002 Modulo de intensidad tension CVM del Circuit Monitor Serie 4000 de POWERLOGIC INTRODUCCION SEGURIDAD HERRAMIENTAS SUSTITUCION DEL CVM Las conexiones de intensidad y tensi n se encuentran en el interior del m dulo de intensidad tensi n CVM independiente que a su vez est sujeto con tornillos Allen y conectado en f brica al Circuit Monitor Todos los datos medidos se obtienen a tra
3. 615 287 3400 www PowerLogic com BW Merin Gerin Telemecanique L quipement lectrique doit tre entretenu seulement par un personnel de maintenance qualifi Ce document ne pr tend aucunement servir de guide d utilisation aux personnes inexp riment es Schneider Electric d cline toute responsabilit quant aux cons quences ventuelles d coulant de l utilisation de ce manuel Schneider Es Electric S lo el personal de mantenimiento el ctrico cualificado puede reparar los equipos el ctricos Este documento no pretende ser un manual de instrucciones para personas sin formaci n Square D no asume ninguna responsabilidad de las consecuencias que se deriven de la utilizaci n de este material Clase n 3020 2002 Schneider Electric Reservados todos los derechos
4. la intensidad Vuelva a instalar los fusibles en el TT y vuelva a conectar los conductores del TI y del TT Vuelva a colocar la cubierta del terminal Apriete los tres tornillos M3 hasta que queden bien fijados par de apriete maximo 0 113 0 226 N m No apriete demasiado 2002 Schneider Electric Reservados todos los derechos 63230 301 200C1 10 2002 12 Restablezca la alimentaci n del Circuit Monitor Para realizar esta operaci n a Vuelva a conectar la alimentaci n al Circuit Monitor y al resto de los dispositivos de E S b Deshabilite el cortocircuito del bloque de cortocircuitos de los TI c Vuelva a instalar los fusibles de entrada de tensi n 13 Ejecute la prueba de error de cableado para verificar que el m dulo est bien cableado En la pantalla Men principal seleccione Diagn sticos gt Pr error cableado Para obtener instrucciones m s detalladas consulte el manual de instalaci n que se entrega junto al Circuit Monitor O 2002 Schneider Electric Reservados todos los derechos 63230 301 200C1 10 2002 Electrical equipment should be installed operated serviced and maintained only by qualified personnel This document is not intended as an instruction manual for untrained persons No responsibility is assumed by Square D for any consequences arising out of the use of this manual Schneider Electric Power Management Operation 295 Tech Park Drive Suite 100 LaVergne TN 37128 USA Tel 1
5. Instruction Bulletin Current Voltage Module CVM 4 63230 301 200C1 10 2002 for POWERLOGIC Circuit Monitor Series 4000 INTRODUCTION SAFETY PRECAUTIONS TOOLS REQUIRED REPLACING THE MODULE Schneider ES Electric The current and voltage connections are housed in the separate current voltage module CVM which is attached by Allen head screws and plugged into the circuit monitor at the factory All metering data is acquired through this module which allows up to 600 Vac direct connection The CVM can detect and capture up to 10 amperes continuously on directly connected loads The CVM is an IEC 60687 0 2S class module This document describes how to replace the module The circuit monitor is calibrated in the factory at the time of manufacture and normally does not need to be recalibrated However in special cases where annual calibration is specified by the user the module can be removed and sent to the factory for recalibration without removing the entire circuit monitor If you need to do this replace the module part no CVM with a spare while the other is being calibrated A DANGER HAZARD OF ELECTRIC SHOCK BURN OR EXPLOSION Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm that power is off Failure to observe these instructions will result in death or serious injury 3mm Allen wren
6. ch e Phillips head screwdriver To remove and reinstall the module follow these instructions and refer to Figure 1 on the back of this sheet 1 Ifthe circuit monitor is connected to power turn OFF all power to the circuit monitor To do this a Disconnect the metered voltage by removing the fuses from the potential transformer PT or from the voltage disconnect b Short circuit the current transformer CT secondaries to disconnect the metered current c Remove the control power from the circuit monitor and to any I O device d Always use a properly rated voltage sensing device to confirm that power is off Remove the terminal cover by loosening its three M3 mounting screws Ensure that the voltage and current input wiring is labeled accurately Remove the voltage and current input wires Loosen the three Allen head screws of the module until they disengage ar amp D 2002 Schneider Electric All Rights Reserved 63230 301 200C1 10 2002 6 Pull the module straight up until it disengages from the circuit monitor as shown in Figure 1 Eo Terminal cover Circuit monitor Figure 1 Removing and installing the module 7 Align the replacement module with the mounting holes on the circuit monitor 8 Seat the module and tighten the three Allen head screws until snug 9 Reconnect the voltage and current input wires 10 Re install the fuses to the PT and reconnect the CT and PT leads
7. ion TT ou du sectionneur de tension b Court circuitez les secondaires du transformateur de courant TC pour d brancher le courant mesur c Coupez l alimentation du Circuit Monitor et de tous les appareils d E S d Utilisez toujours un dispositif de d tection de tension nominale ad quat pour v rifier que l alimentation est hors service 2 D posez le couvercle du bornier en desserrant les 3 vis de montage M3 3 V rifiez que les c bles d entr e de courant et de tension sont correctement tiquet s 4 Retirez les cables d entr e de courant et de tension O 2002 Schneider Electric Tous droits r serv s Schneider TP Electric 63230 301 200C1 10 2002 D Merin Gerin Telemecanique 5 Desserrez les trois vis Allen du CVM et d gagez les 6 Tirez sur le module verticalement jusqu a ce qu il se d solidarise du Circuit Monitor comme illustr a la Figure 1 Couvercle du bornier Circuit Monitor Schneider Figure 1 D pose et installation du module 7 Alignez le module de rechange sur les trous de montage du Circuit Monitor 8 Positionnez le module et serrez les trois vis Allen compl tement 9 Rebranchez les cables d entr e de courant et de tension 10 R installez les fusibles sur le PT et reconnectez les cables du CT et du PT 11 R installez le couvercle du bornier Serrez les trois vis M3 compl tement couple maximum de 0 113 0 226 N m Ne serrez pas trop
8. o del Circuit Monitor Para realizar esta operaci n a Extraiga los fusibles del transformador de tensi n TT o desconecte el interruptor de desconexi n de tensi n para desconectar la medici n de tensi n b Cortocircuite los transformadores de intensidad Tl secundarios para desconectar la medici n de intensidad c Desconecte la alimentaci n del Circuit Monitor y de todos los dispositivos de E S d Utilice siempre un dispositivo sensible a la tensi n adecuado para confirmar que el equipo est apagado 2 Retire la cubierta de los terminales aflojando los tres tornillos de montaje M3 _ Merl n Gerin 2002 Schneider Electric Reservados todos los derechos HM Modicon Schneider ff Electric 63230 301 200C1 10 2002 a Compruebe que los cables de entrada de la tensi n y la intensidad est n etiquetados correctamente Extraiga los cables de entrada de la tensi n y la intensidad Afloje los tres tornillos Allen del CVM hasta que se suelten Extraiga el m dulo hacia arriba en vertical hasta que se suelte del Circuit Monitor tal como se muestra en la Figura 1 Cubierta de los terminales Circuit Monitor Figura 1 Desmontaje e instalaci n del m dulo 11 Alinee el m dulo de repuesto con los orificios de montaje del Circuit Monitor Coloque el m dulo y apriete los tres tornillos Allen hasta que quede perfectamente fijado Vuelva a conectar los cables de entrada de la tensi n y
9. r jusqu a 600 Vca Le CVM a la capacit de d tecter et de capturer des tensions de 10 A en continu sur des charges connect es directement Le CVM est un module IEC 60687 classe 0 2S Le pr sent document d crit comment remplacer le module Normalement le Circuit Monitor est talonn en usine au moment de la fabrication et ne n cessite pas d autre talonnage Cependant pour les cas particuliers o un talonnage annuel est sp cifi par l utilisateur le module peut tre d pos et renvoy en usine pour r talonnage sans d pose du Circuit Monitor entier Dans ce cas remplacez le module n de r f rence CVM par un module de rechange pendant le r talonnage DANGER RISQUE D ELECTROCUTION DE BRULURE OU D EXPLOSION Mettez hors service toutes les alimentations avant de travailler sur ou dans cet quipement e Utilisez toujours un dispositif de d tection de tension nominale ad quat pour v rifier que l alimentation est hors service Le non respect de ces instructions peut provoquer des blessures graves voire mortelles e Cl Allen 3 mm Tournevis cruciforme Pour d poser et r installer le module suivez ces instructions et reportez vous la Figure 1 au verso de cette fiche 1 Si le Circuit Monitor est connect COUPEZ toute l alimentation dirig e vers lui Pour ce faire proc dez comme suit a D branchez la tension mesur e en retirant les fusibles du transformateur de tens
10. v s de este m dulo que admite una conexi n directa de hasta 600 V CA El CVM puede detectar y capturar hasta 10 amperios de manera continua con cargas conectadas directamente El CVM es un m dulo de clase 0 25 seg n IEC 60687 En el presente documento se explica c mo se sustituye el m dulo No suele ser necesario volver a calibrar el Circuit Monitor ya que se calibra en la f brica durante su fabricaci n Sin embargo en algunos casos excepcionales como cuando el usuario solicita una calibraci n anual el m dulo CVM se puede desmontar y enviar a la f brica para realizar la calibraci n sin necesidad de desmontar todo el Circuit Monitor Si necesita realizar esta operaci n sustituya el m dulo CVM n mero de referencia CVM que se est calibrando por uno de repuesto A PELIGRO RIESGO DE DESCARGA ELECTRICA QUEMADURAS O EXPLOSION Apague todas las fuentes de energ a del equipo antes de iniciar el trabajo sea dentro o fuera del equipo e Utilice siempre un dispositivo sensible a la tensi n adecuado para confirmar que el equipo est apagado El incumplimiento de estas instrucciones puede provocar la muerte o lesiones graves Llave Allen de 3 mm Destornillador de estrella Phillips Para desmontar y volver a instalar el m dulo siga las instrucciones que se indican a continuaci n y consulte la Figura 1 en el reverso de esta hoja 1 Si el Circuit Monitor est conectado APAGUE el suministro el ctric
Download Pdf Manuals
Related Search
Related Contents
NEC X431BT Mechanical Drawings User Guide and Usage Restrictions of GLO PRP Ⅰ Samsung GT-C3053 Kullanıcı Klavuzu Operating Instructions - Müller Elektronik GmbH & Co. Lowrance electronic PRO X51 User's Manual Canon 300 Printer User Manual PIANOS user manual Genius Luxepad 9000 3A2452A - DutyMax Hydraulic Sprayers Operation Copyright © All rights reserved.