Home
Indoor unit Ceiling/Floor type
Contents
1. Z l 13 WIRE CONTROLLER o 1 TO INDOOR POWER To Central Control TO OUTDOOR 220V 50Hz 60Hz Monitor CCM COMM BUS COMM BUS To wire controller The reserved wire control function isindicated j eta in broken linetable users can purchase the Please adopt the shielded twisted pair wire wire controller when Note cary and connect the shielded layer to E CONTROL Please number the indoor units during the installation For example for the first outdoor unit the number of the first indoor unit is 1 1 the second indoor unit is 1 2 and the set address is 1 and 2 respectively the others is analogical Hoursepower code System address code Model 1 show the address 0 F respectively that is 0 15 indoor unit Model 2 show the address 0 F respectively that is 16 31 indoor unit Model 3 show the address 0 F respectively that is 32 47 indoor unit Model 4 show the address 0 F respectively that is 48 63 indoor unit A Cautions 1 The system together have 64units 0 63 everyone has only system addresscode If two addresses are the same in one system the abnormal operation will occur 2 Please switch off the power before setting otherwise the unexpected error will occur ENC1 Toggle switch For set horsepower Note The h Code Capacity Horsepower AE ES 0 2200W 0 8HP has been set befor
2. conditioner has to be done at the main power distribution The distribution has to be of a low impedance normally the required impedance reaches at a 32A fusing point 2 No other equipment has to be connected with this power line 3 For detailed installation acceptance please refer to your contract with the power supplier if restrictions do apply for products like washing machines air conditioners or electrical ovens 4 For power details of the air conditioner refer to the rating plate of the product 5 For any question contact your local dealer ACCESSORIES Name of Accessories Q ty Qutline Usage Owner s manual Installation manual This manual Hook For wall mounting installation Hanging arm 2 For ceiling installation Mounting screw B ST2 9x10 C H iP Ow TK Remote controller holder Cautions on remote controller installation e Never throw or beat the controller 3 Mounting screw e Before installation operate the remote controller ST2 9x10 C H to determine its location in a reception range Keep the remote controller at least 1m apart from or the nearest TV set or stereo equipment It is 4 Alkaline dry batteries AM4 necessary to prevent image disturbances or noise interferences e Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a stove Note that the positive and negative poles are in right positions when loading batt
3. make the refrigerant pipe conne cting the indoor unit with the outdoor unit fluently flow 5 Be sure of no leakage by checking it with leak detector or soap water 6 Cover the joint of the connecting pipe to the indoor unit with the soundproof insulating sheath fittings and bind it well with the tapes to prevent leakage SIZES OF THE PIPES R22 R407C R410A R410A ese ee ee Gas 19 12 7 15 9 Liquid 9 53 6 35 9 53 Models All 36 45 140 CONNECT THE DRAIN PIPE 1 Install indoor unit drain pipe The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC pipes CAUTIONS e The drain pipe of indoor unit must be heat insulated or it will condense dew as well as the connections of the indoor unit e Hard PVC binder must be used for pipe connection and make sure there is no leakage e With the connection part to the indoor unit please be noted not to impose pressure on the side of indoor unit pipes e When the declivity of the drain pipe downwards is over 1 100 there should not be any win ding e The total length of the drain pipe when pulled out traversely shall not exceed 20m when the pipe is over long a prop stand must be installed to prevent winding Refer to the figures on the right for the installation of the pipes Put as deep as possible about 10cm 1 5m 2m Bend Xx S shape x Insulating Downward declivity material l
4. with 3600 7100W type as rated capacity which may differ from the unit you purchased The dimension of the unit 3600 7100W type 203 8000 9000W type INSTALL THE CONNECTING PIPE e Do not let air dust or other impurities fall in the pipe system during the time of installation e The connecting pipe should not be installed until the indoor and outdoor units have been fixed already e Keep the connecting pipe dry and do not let moisture in during installation The Procedure of Connecting Pipes 1 Measure the necessary length of the connecting pipe and make it by the following way 1 Connect the indoor unit at first then the outdoor unit e Bend the tubing in proper way Don t harm them A Cautions e Daub the surfaces of the flare pipe and the joint nuts with frozen oil and wrench it for 3 4 rounds with hands before fasten the flare nuts Refer to chart 12 e Be sure to use two wrenches simultaneously when you connect or disconnect the pipes 2 The stop valve of the outdoor unit should be closed absolutely as original state Every time you connect it first loosen the nuts at the part of stop valve then connect the flare pipe immediately in 5 minutes If the nuts have been loosened for a long time dusts and other impurities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection 3 Expel the air refer to the Expel The
5. Air after connecting the refrigerant pipe with the indoor unit and the outdoor unit Then fasten the nuts at the repair points E Notices For Benable pipe e The bending angle should not exceed 90 C e Bending position is preferably in the bendable pipe The larger the better it is e Do not bend the pipe more than three times E Bend the connecting pipe of small wall thickness e Cut out a desired concave at the bending part of the insulating pipe e Then expose the pipe cover it with tapes after bending e To prevent collapsing of deforming please bend the pipe at its biggest radius e Use bender to get a small radius pipes E Use the market brass pipe Be sure to use the same insulating materials when you buy the brass pipe More than 9mm thick Use frozen oil Ll Bend the pipe with thumb 25 gt 5 ane _ ATM oX Make the ends straight Min radius 100mm Chart 12 Chart 13 Chart 14 2 Locate The Pipe 1 Drill a hole in the wall suitable just for the size of the wall conduit 90mm in general then set on the fittings such as the wall conduit and its cover 2 Bind the connecting pipe and the cables together tightly with binding tapes Do not let air in which will cause water leakage by condensation 3 Pass the bound connecting pipe through the wall conduit from outside Be careful of the pipe allocation to do no damage to the tubing 3 Connect the pipes 4 Then open the stem of stop valves of the outdoor unit to
6. WEAK ELECTRIC WIRING mm SIGNAL Table 3 Caution 1 PHASE 220 50Hz 60Hz A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation E Wiring Chart Power 220 50Hz 60Hz INDOOR UNIT CENTRAL CONTROL MONITOR CCM I COMPUTER INDOOR UNIT D m _ OUTDOOR UNIT INDOOR UNIT 4 a the shielded twisted pair wire Caution The reserved function is indicated in broken line table users can select it when necessary Indoor Outdoor Unit Signal Wire Connect the wire according to their numbers Wrong connection may cause malfunction Wiring Connection Seal the wiring connection with the insulation material or the condensing dew will be caused Panel Wiring Connect the Swing Motor terminal block according to the Panel Installation Manual Please refer to the indoor unit wiring diagram for the wiring Note The air conditioners can connect with Central Control Monitor CCM Before operation please wiring correctly and set system address and network address of indoor units Single phase indoor unit DISPLAY BOARD GRAY XT1 gt lt mE lt fame BLACK QT YELLOW amp Q amp
7. e The ceiling is horizontal and its structure can endure the weight of the indoor unit The air outlet and the air inlet are not impeded and the influence of external air is the least The air flow can reach throughout the room The connecting pipe and drainpipe could be extracted out easily There is no direct radiation from heaters A Cautions Location in the following places may cause malfunction of the machine If unavoidable please consult your local dealer a There exists petrolatum b There is salty air surrounding near the coast c There is caustic gas the sulfide for example existing in the air near a hot spring d The Volt vibrates violently in the factories e In buses or cabinets f In kitchen where it is full of oil gas g There is strong electromagnetic wave existing h There are inflammable materials or gas i There is acid or alkaline liquid evaporating j Other special conditions E Notes Before Installation 1 Select the correct carry in path 2 Move this unit as originally packaged as possible 3 If the air conditioner is installed on a metal part of the building it must be electrically insulated according to the relevant standards to electrical appliances NOTE Remark per EMC Directive 89 336 EEC For to prevent flicker impressions during the start of the compressor technical process following installation conditions apply 1 The power connection for the air
8. e leaving the factory sae anyone can t 2 3600W 1 2HP modify it except the 3 4500W 1 5HP maintenance person 4 5600W 2 0HP 5 7100W 2 5HP 6 8000W 3 0HP 7 9000W 3 2HP 8 11200W 4 0HP 9 14000W 5 0HP ENC2 TOGGLE SWITCH FOR SETTING ADDRESS 0 F show the address 0 F respectively that is 0 15 indoor unit together 16 units and the others follow the analogy If two addresses are the same in one system the abnormal operation will occur DE COMMISSIONING DISMANTLING amp DISPOSAL This product contains refrigerant under pressure rotating parts and electrical connections which may be a danger and cause injury All work must only be carried out by competent persons using suitable protective clothing and safety precautions A A Read the Manual Risk of electric shock Unit is remotely controlled and may start without warning Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit Ensure that all points of electrical and gas isolation are secured in the OFF position The supply cables and gas pipework may then be disconnected and removed For points of connection refer to unit installation instructions Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circumstances sh
9. eries Remote controller INDOOR UNIT INSTALLATION Installing 10 hanging screw bolts 4 bolts Please refer to the following figure for the distance measurement between the screw bolts e Please install with 10 hanging screw bolts The handling to the ceiling varies from the constructions consult the construction personn els for the specific procedures 1 The size of the ceiling to be handled do keep the ceiling flat Consolidate the roof beam for possible vibration 2 Cut off the roof beam 3 Strengthen the place cut off and consolidate the roof beam e Carry out the pipe and line operation in the ceiling after finishing the installation of the main body While choosing where to start the operation determine the direction of the pipes to be drawn out Especially in case there is a ceiling position the refrigerant pipes drain pipes indoor amp outdoor lines to the connection places before hanging up the machine e The installation of hanging screw bolts New concrete bricks Inlaying or embedding the screw bolts Refer to Chart 2 VW Blade shape insertion Slide insertion Chart 2 Wooden construction Put the square timber traversely over the roof beam then install the hanging screw bolts Refer to Chart 1 Timber over the beam LO Roof beam Ceiling Hanging screw bolts Chart 1 Steel roof beam structre Install and use directly the supporting angle steel Refer
10. ould refrigerant be vented to atmosphere Where appropriate drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes Packaged unit can generally be removed in one piece after disconnection as above Any fixing down bolts should be removed and then unit lifted from position using the points provided and equipment of adequate lifting capacity Reference MUST be made to the unit installation instructions for unit weight and correct methods of lifting Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above After removal from position the unit parts may be disposed of according to local laws and regulations Johnson D Controls E II YDFC 0907 Eee
11. ower than 1 100 Downward declivity lower than 1 100 VP30 2 Drainage test Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling ELECTRIC WIRING Specified power cables should be used Do not apply any pressure on the terminals used to connect Improper connection may cause fire Grounding must be properly done The grounding wire should be away from gas pipes water pipes telephone lightening rods or other grounding wires Improper grounding may cause electric shock Electric Wiring must be done by professionals Use a separate circuit according to national regulations If the wiring capacity is not enough electric shock or fire may occur CAUTION Be sure to Install Current Leakage Protection Switch Or electric shock may occur Power cord is to be selected according to national regulations Outdoor unit power cord should be selected and connected according to the outdoor unit installation manual Wiring should be away from high temperature components or the insulation layer of the wires may melt down Use wire clamp to fix the wires and terminal block after connection e Control wire should be wrapped together with heat insulated refrigerant pipes E The Specification of Power 2200 14000W type FREQUENCY AND VOLT CIRCUIT BREAKER FUSE A INDOOR UNIT POWER WIRING mm INDOOR OUTDOOR GROUND WIRING mm CONNECTING
12. to chart 4 E Hanging screw bolt For Original concrete bricks Use embedding screw bold crock and stick harness Refer to Chart 3 FE Embedding screw bolt Pipe hanging and embedding screw bolt Chart 3 Supporting angle steel l l l l Steel bar l l l Chart 4 Wall Mounting Installtion D Connecting point of refrigerant pipe D gas side Drain point E Connecting point of refrigerant pipe E Liquid side Chart 5 1 Fix the hook with tapping screw onto the wall Refer to Chart 6 Y Chart 6 2 Hang the indoor unit on the hook Ceiling Installation Hanging arm Chart 7 1 Remove the side board and the grille Refer to Chart 8 For models 11200 14000W type do not remove the grille Side board Grille 2 Locate the hanging armon the hanging screw bolt Refer to Chart 9 Prepare the mounting bolts on the unit Refer to Chart 10 8 13mm Screw nut 20 25mm INDOOR UNIT Hanging sare Delt Mounting bolt max 40mm Chart 9 Chart 10 3 Hang the unit onthe hanging arm by sliding backward Securely tighten the mounting bolts on both sides Refer to Chart 11 Hangin screw bolt A Hanging arm D Connecting point of refrigerant pipe D gas Sids E Connecting point of refrigerant pipe E Liquid side gt 20mm Drain point Chart 11 ATTENTION The figures above are based on model
13. ul YORK cc ENGLISH E II YDFC 0907 INSTALLATION MANUAL DIGITAL SCROLL SERIES AIR CONDITIONER CEILING AND FLOOR TYPE 4 Models YDFC 36C A B 15A YDFC 45C A B 15A YDFC 56C A B 15A YDFC 71C A B 15A YDFC 80C A B 15A YDFC 90C A B 15A YDFC 112C A B 15A YDFC 140C A B 15A For correct installation read this manual before starting installation Only trained and qualified service personnel should install repair or service air conditioning equipment Users should not install the air conditioner by themselves All pictures are only sketches If there is any difference between pictures in this manual and the actual shape of the air conditioner you purchased the actual shape shall prevail INSTALLATION PRECAUTION e To install properly please read this manual at first The air conditioner must be installed by qualified persons e When installing the indoor unit or its tubing please follow this manual as strictly as possible e When all the installation work is finished please turn on the power only after a thorough check e No further announcement if there is any change of this manual caused by product improv ement Note The installor should illustrate to users how to correctly use and maintain the air condi tioner as well as remind users to carefully read and keep both Installation Manual and Owner s Manual well INSTALLATION PLACE E The Indoor Unit e There is enough room for installation and maintenanc