Home

TR400SGA User Manual - Instrumentation Systems & Services Ltd.

image

Contents

1. Float Low High 32 bit Transmit Most Significant word Last 2 Long High Low 32 bit Transmit Most Significant word First 3 Long Low High 32 bit Transmit Most Significant word Last 4 Signed Integer default 16 bit 5 Unsigned Integer 16 bit 8 ats amp 01943 602001 sales issltd co uk k www issitd co uk Programming the Analog Inputs The ways to get the display and analog output you desire from the PM500 are presented below 1 Input is calibrated default is typically accurate enough for temp probes otherwise you will need to go to diagnostics and perform the offset and scale calibrations 2 Verify Input is properly programmed a If channel A is used Variables 10 amp 11 must be programmed lower and upper setpoints b If channel B is used Variables 12 amp 13 must be programmed lower and upper setpoints c Variable 15 must be set appropriately for your input configuration 3 Verify output is programmed Programming the Relay Outputs In order for the relays to operate you must do the following 1 Enter the setpoints for the relays by setting the variables 1 through 4 2 Set the relays to trigger on the right input by using variable 7 3 Turn on the relay to over or under setpoint tripping in variable 8 Programming the Analog Outputs There are several aspects to getting the display and analog output you desire from the PM500 They are as follows 1 Calibrate inputs Default is typically accurate enough for tem
2. To install the PM500 into an instrument panel e Remove the mounting brackets e Slide the PM500 into the panel cutout e Replace the mounting brackets and tighten the bracket screws do not over tighten the bracket screws Allow a minimum of 1 5 inches clearance on all sides of the PM500 2 58 Te Mi IE 5 13 atts t 01943 602001 sales issltd co uk b www issitd co uk Wiring Practices for Industrial Equipment 1 All control signals must be shielded cable The shield must be tied to common or earth ground at the receiving end only In some environments earth ground may contain excessive electrical noise If you have problems using earth ground as a shield tie point switch the shields to signal common All connections to the controller are considered signal unless they carry AC power 2 Never use a shielded cable with unused conductors The unused conductors act as antennas Attempting to tie the unused conductors to ground or other signals just creates different antenna configurations In many cases unshielded wire would have received less electrical noise Always insure that a shielded cable with the correct number of conductors is pulled 3 All control signals must be separated from power wiring Power wiring includes any AC or DC voltages with a current potential of greater than 1 Amp or a voltage greater than 24 V This includes but is not limited to 115 VAC 230 VAC and 460 VAC Do not bundle shielded cable
3. e User units for ADC A are programmed Var 10 is set to 0 and Var11 is set to 100 to read 0 100 when the analog input is 4 to 20 mA The plant engineer also wants the PM500 to signal an Under alarm when the gate is in the 2 open position and a Over alarm when the gate is in the 98 open position To accomplish this he programs the PM500 s Relays as follows below e Relay Actuation Var06 to XX21 Relay Output 1 as a Under alarm Relay Output 2 as a Over alarm e Relay Setpoint Var01 is programmed at 0002 to trip at 2 display value and Var02 is programmed at 0098 to trip at 98 display value The plant engineer tests the final system by closing the slide gate beneath the hopper bin and verifies that the PM500 reads 0 i e 0 for the 4 mA signal coming from the SG1000x When he runs the slide gate wide open the PM500 shows 100 i e 100 for the 20 mA signal coming from the SG1000x He notices that when the slide gate was fully closed relay was off and remained so until the slide gate opened up to 4 2 setpoint and 2 hysteresis He also noticed that the PM500 s relay 2 was on the entire time the slide gate was near the fully closed position and remained ON until the slide gate opened up to the 98 open position then relay 2 turned OFF This is the over setpoint alarm he wanted 12 amp 01943 602001 sales issltd co uk b www issitd co uk A Appendix A Panel Cutout Dimensions
4. Common Note If the 3 wire device draws more than 50mA you can use both 24 VDC internal supplies together or use an external 24 VDC supply and disconnect from PM500 supply Fuse device to protect input from excess current wt fee PM500 Wiring Diagram 24 VDC Supply Analog Input B Input Common Figure 1 PM500 Wiring Diagram 16 t 01943 602001 sales issltd co uk b www issitd co uk mi Wiring Diagrams continued 3 a Oo N J 2 lt 5 Q COM 1 N O Relay 1 N C Relay 1 COM 2 N O Relay 2 N C Relay 2 Figure 2 2 Relay outputs wiring diagram 6 8 L 9 St eEZI o N w A v a m N COM 1 N O Relay 1 N C Relay 1 COM 2 N O Relay 2 N C Relay 2 COM 3 N O Relay 3 N C Relay 3 COM 4 N O Relay 4 N C Relay 4 N C N C N C N C N C N C buram Aejay v OOSWd Figure 3 6 Relay outputs wiring diagram amp 01943 602001 sales issltd co uk b www issitd co uk Ta Appendix C PM500 Specifications Power Description Input power Standard 115 VAC 50 60 Hz 9 VA Switchable 230 VAC 50 60 Hz 9 VA Fusing internal 100mA TR5 Slow Blow recommended for 115 VAC 50mA TR5 Slow Blow recommended for 230 VAC Sensor Supply Description Transducer Power Supply 24 VDC regulated 50 mA max 2 channels Fusing Internal resettable
5. Output 3 2 Over setpoint pH Relay Output 4 Table 5 Var08 Relay Output Function Codes The unused function keeps the respective relay permanently dropped out The Under setpoint function pulls in the relay when the 4 20 mA input signal rises to the trip point level and drops out the relay when the 4 20 mA input signal falls below the trip point level by 2 The Over setpoint function pulls in the relay when the 4 20 mA input signal falls to the trip point level and drops out the relay when the 4 20 mA input signal rises above the trip point level by 2 Note The relay hysteresis is fixed at 2 of the Maximum Rate in User Units value t 01943 602001 sales issltd co uk b www issitd co uk A Ta Var 09 Switch Input Function This is not implemented at this time Var 10 amp Var 12 Analog Input A amp B User Units at Lower Calibration Point User Variable 10 Analog Input A User Units at lower calibration point typically at 4 mA input User Variable 12 Analog Input B User Units at lower calibration point typically at 4 mA input This variable a k a Minimum Rate in User Units is used to scale a 4 mA signal into a displayed maximum value in user units The value entered into Var 10 amp 12 is the number of user defined units position capacity speed etc processed by the system when the analog input signal is at its lowest calibration point The lowest calibration point is usually
6. Variable VAR key PROG LED amp Disp reads Prxx Change User Variable DIAG key PROG LED amp disp reads dIAG Perform Diagnostic Action Table 1 Associations Between Keys LEDs and Menus The Input A LED is associated with input channel A The Input B LED is associated with input channel B The Input LED that is illuminated shows the user which input channel is being displayed l The KEY ERR LED is used to indicate an invalid key press an invalid user variable number or an invalid user variable value It shuts off after a timeout period of 500 ms The PROG LED is OFF when the display is showing a real time value selected by the display function variable amp 01943 602001 sales issltd co uk b www issitd co uk it The User Interface Tables DIAG Menu How to Perform the Diagnostic Functions 1 Press the DIAG key 2 Use the arrow keys to select desired variable and press ENTER a When finished hit DIAG key to exit menu 3 Press DIAG key one more time to exit the DIAG Menu Note See table on next page for Diagnostics description SECR Menu How to Change the Security Settings 1 Select the Security menu by pressing the Decimal Point Key 2 Use up and down arrows to select the desired variable a Press Enter b Change variable and accept by pressing Enter Key or aborting change by hitting Decimal Point Key 3 Press Decimal Point Key to exit Security Menu VAR Menu How to Change a User Vari
7. Variable 11 and 13 reflects the point you calibrated 8 You are done DP ah H 11 t 01943 602001 sales issltd co uk b www issitd co uk da Application Examples A plant engineer is using an Electro Sensors Inc SG1000x SlideGate Monitor to sense the position of a slide gate controlling the amount of grain flowing out of a hopper storage bin The Electro Sensors SG1000x SlideGate Monitor is programmed to output a 4 mA DC signal when the gate is in the fully closed position and output a 20 mA DC signal when the gate is in the fully open position Any gate position between the fully closed and fully open positions will be represented by the SG1000x output signal being proportionally between 4 mA and 20 mA Typically in such an application the fully closed slide gate position is referred to as being 0 open Likewise the fully open slide gate position is referred to as being 100 open In this example an Electro Sensors PM500 can be used to read the 4 20 mA signal coming from the SG1000x The PM500 can be programmed to display the slide gate position as a percentage from 0 open to 100 open The user simply then has to view the PM500 displayed value to know the position of the slide gate at the bottom of the hopper storage bin In this example using Input A the PM500 s variables are set as follows below e ADC select Var 05 is set to xx11 relay 1 and 2 are programmed to use ADC input A
8. da NOTES amp 01943 602001 sales issltd co uk b www issitd co uk mn NOTES amp 01943 602001 sales issltd co uk b www issitd co uk
9. e aa sab ag aman Taun nana Bia Nak 8 Var 33 Modbus Data Type sansen a ag a TA ga Nu aa Ne Da anna an ite bana aah 8 Programming the Analog Inputsi 54 srada pa ara ua Ta ea SUNG KNA bik Ga Ae KUNG KE KAN na aa akan 9 Programming the Relay Outputs usandt ana An GEN Ge ENENG AB UNG ida naas 9 Programming the Analog Outputs oo oom 9 The LRC Non volatile Memory Check Feature ooooooooooo onani 9 DIAG Menu The Diagnostic Functions ooooWoooomoWmoW allah 10 Anou How to Check the Analog Output ooroooooooo nana 10 SIn How to Check the Switched Inputs oooWoomoWoW WWW 10 MELY How 10 Test the Relay Outputs 4 dasi ente a are kaan enakan anna naa bana 10 HEyP How to Verify that the Keypad is Working nana 10 UEr How to Find out the Firmware Version Number oooooWoo oom 10 TESE How to Reset the User Variables to their Factory Default Values oooWoWoWoomoooWooo WWW 10 OFFS How to Calibrate the Analog Input Offset ooooooo oo oo 11 SCAL How to Calibrate the Analog Input Scale ooooooooo o oo 11 Applicaton EX ANPI ES kemanan em anna BEDE DENS BE FE DER de ak DRE DN Ore aan Naren UENO D GG AR agi bal Ag ON eee cannes 12 Appendix A Panel Cutout Dimensions 0ss0soso ose naon 5 apen ae GE naa eea ONE a GEN GEN ee ao ente DENENG NGENGRENGAN tedo s ssi osei viesse 13 Wiring Practices for Industrial Equipm
10. given out This can be useful for trouble shooting SIn How to Check the Switched Inputs Select SIn from the diagnostics menu The display will show the status of the switch inputs The right most digit represents the first switch input 000X The digit that is the second most right represents the second switch input 00X0 The DIAG key exits the SIn switch input test rELY How to Test the Relay Outputs Select rELY from the diagnostics menu The display will show the status of the relay outputs The right arrow key pulls in relay output 1 amp 3 and sets the corresponding digit of the display to a 1 The left arrow key pulls in relay output 2 amp 4 sets the corresponding digit of the display to a 1 The ENTER key drops out all relays clears the corresponding digits of the display to 0 The DIAG key exits the rELY Relay Output test HEyP How to Verify that the Keypad is Working Select HEyP from the diagnostics menu Each key corresponds to a unique display Press each key to test its response The DIAG key exits the test UEr How to Find out the Firmware Version Number Select Uer from the diagnostics menu The firmware version and revision are displayed in XX XX format The two digits before the decimal point reflect the version number The two digits after the decimal point reflect the revision number The DIAG key exits the test rESE How to Reset the
11. the 4 20 mA analog output holds at 4 00 mA due to the corruption of the user variables To prevent the PM500 from performing abnormally the PM500 essentially stops performing because any inadvertent change to the user variables may have changed its performance The user then obviously knows something is wrong with the PM500 s user variables Note It is important the user fills in their application s values in the User Variable Log near the back of this PM500 User Manual Because if an LRC error does occur then there will be a correct list of variable values to compare to when attempting to fix a corrupted variable situation During a LRC error e Access to the Diagnostic Menu is allowed Access and changes to the Security Menu are allowed having no effect on the LRC error Access to the Var Menu is allowed for read only Changes to the Var Menu are not allowed The unit can be reset to factory defaults 485 communications will continue to work amp 01943 602001 sales issltd co uk b www issitd co uk A DIAG Menu The Diagnostic Functions The DIAGNOSTIC menu is accessed by pressing the DIAG key Once inside the Diagnostics Menu press the UP and DOWN arrow keys to scroll through the list of diagnostic functions Each of the diagnostic functions is explained below Anou How to Check the Analog Output At this time the 4 20 mA outputs are a fixed calibration This diagnostic allows you to force the outputs to a
12. value ADC 2 Bits 0 to FFFF 30xx0 Boolean State 0 or 1 see i Reyon Table 9 for more detail Bi 5 Analog A output DAC value 0 4095 30xx0 6 Analog B output DAC value 0 4095 30xx0 7 Switch Inputs 00XX 30xx0 Table 6 Var17 Display Function Codes a Digit Function Status Code ia 0 Dropped Out a Relay Output 1 1 Pulled In Dena 2 Relay Output 2 CP a Relay Output 3 ae 4 Relay Output 4 Table 7 Var17 Display Function Code 4 Relay Output Status Var01 Maximum Rate in User Units scales the 4 20 mA analog input signal into user units for display function 0 Var01 Maximum Rate in User Units scales the 4 20 mA analog input signal into user units for display function 0 amp 01943 602001 sales issltd co uk b www issitd co uk mi Var 20 amp 22 Analog Output Minimum Rate in User Units Analog Output Minimum Rate in User Units 4 mA output setpoint Var20 is used to set the point where the PM500 will output 4 mA on channel A when the display is at this value Var22 is used to set the point where the PM500 will output 4 mA on channel B when the display is at this value Var 21 amp 23 Analog Output Maximum Rate in User Units Analog Output Maximum Rate in User Units 20 mA output setpoint Var21 is used to set the point where the PM500 will output 20 mA on channel A when the display is at this value Var23 is used to set the point where the PM500 will output 20 mA on
13. 5 communications TB1 4 to TB1 6 A two conductor shielded cable should be used for this connection The shield should be tied to the PM500 common not earth ground Switch inputs T1 7 to TB1 9 The switches are contact closure and require only 2 or 3 wires depending on number of switches used Use of signal wire and shielding is advised but is not mandatory 4 20 mA Analog Input TB2 10 TB2 15 A two conductor shielded cable should be used for this connection The shield should be tied to the PM500 common not earth ground 4 20 mA Analog Output TB1 16 to TB1 18 A two three conductor shielded cable should be used for this connection depending on the number of outputs used The shield is not counted as a conductor The shield is tied to the PM500 s common Relay Outputs TB3 1 to TB3 18 Relay wiring is dependent on user needs 15 amp 01943 602001 sales issltd co uk b www issitd co uk da A Wiring Diagrams Note TYPE 1 ENCLOSURE MAX TEMP 60C Line L1 Power 115 VAC THIS DEVICE IS 115VACOR230vAC Neutral L2 Switchable to 230 VAC INTERNALLY SWITCHABLE AND IS INTERNALLY FUSED WITH N C 115 VAC TRS 100mA SLO BLOFUSE age A 230 VAC TRS 50mA SLO BLO FUSE 485B 485 Shield SW1 Contact Closure SW2 Contact Closure Switch Common 24 VDC Supply Analog Input A Input Common 24 VDC Supply Analog Input B Input Common 4 20mA Out Ch A 4 20mA Out Ch B HH pic a 2oma input Output
14. Calibration ADC value in hexadecimal of the actively displayed ADC input amp 01943 602001 sales issltd co uk Table 2 How to perform diagnostic functions b www issitd co uk SECR Menu The Security Variables The SECURITY menu is accessed by pressing the DECIMAL POINT key In the security menu the user has access to three variables The input password variable PIn the password definition variable PdEF and the security definition variable SdEF The security features defined by the security definition variable SdEF are enabled anytime the input password PIn is different from the password definition PdEF In other words in order to access locked out functions the user has to enter an input password that matches the password definition PIn PdEF In order to lock out unauthorized changes to user variables the user must enter a password definition that is unknown to unauthorized users PIn PdEF Any attempt to access the password definition by an unauthorized user will result in a display of HIdn hidden The following table indicates how menu access is controlled by the digits of the security definition variable Ia a Digit Function Function Codes VAR Menu Digit 1 When this menu is locked the user variables can be viewed but not changed DIAG Menu Digit 2 O Menu Unlocked When this menu is locked access to the 1 Menu Locked diagnostic functio
15. FA erumentation trumentation Systems amp Services u MAN ELECTRO SENSORS NY PM500 User s Manual K 01943 602001 sales issltd co uk k www issitd co uk A Table of Contents Table ot Contents cx sasa kwa vil anka Zan baka sake po vwa bo kk lo e kat a ple RE nan Rn angan iii List Of FIF UNE Site aan atu kan mangan anne aan an Beginner a ke aapa eeh iv Biso TableS ena re ye maan NN NE PN E ad gak a ga a sw usus iv Introduction to this Manual sa kek ke kek eske pasa pena Bas aan odone ped pan Ba aa pa aa pa padana rena uan v Introduction to this PrOdBEt a aks k s ma yaa Eks an Nan BBB NN una vi The User Interfate Maan an un anna nun 1 The User Interface TablOS sa 5 5 sora eke sayo pad nasa ke e papan a pae ke ke iye nia gada Bag aas oak da pulpen a pad NN un Run 2 DIAG Menu How to Perform the Diagnostic Functions ooWoWoWmo Wb 2 SECR Menu How to Change the Security Settings u sssesessrrererererre renerne nerne renerne 2 VAR Menu How to Change a User Variable oooooooWoWoW Woo Wanna 2 IB Es Tog ate SAW hana Ra EN A Ri an BR Ea an Folens EN andai 3 SECR Menu The Security Variables oooo WWoWooW mann 4 User Variable Descriptions and Formats 00 0 ccc cecceseecseesseeseesecesecesecaecaecsaecaeecaeecaeeeaeeeaeeseeseeeeseesaesaeesaeesaecsaeeaaeeaeeeaes 5 Var01 to Var04 Relay Output Setpoints ooooooonnnnnnnlnnnnnaa 5 Var07 Rela
16. Reserved 0000 FFFF No 41480 49 Reserved 0000 FFFF No 41490 50 Reserved 0000 FFFF No 41500 51 Reserved 0000 FFFF No 41510 Table 10 Calibration Variables Log Security Variable Log Variable Number Variable Name Password Definition Default Value Range of Values 0001 9999 DP move enabled Password Input 0001 9999 Table 11 Security Variables Log 20 da Security Definition amp 01943 602001 X00X X is 0 or 1 sales issltd co uk b www issitd co uk 4 4 20mA input wiring 15 16 4 20mA output wiring 16 A AC input power wiring 15 16 18 ADC Averaging 6 Analog Input User Units Lower Cal Point 6 Analog Input User Units Upper Cal Point 6 Analog output maximum rate in user units 8 Analog output minimum rate in user units 8 Analog output test 10 Analog outputs response 8 Appendix Panel cut out dimension 13 Specifications 18 Wiring the PM500 15 C Calibrating the input 12 Communications Variable Log 20 D Diagnostic functions 10 H How to calibrate the analog input offset 11 How to calibrate the analog input scale 11 How to Check the Analog Output 10 How to Check the Relay Outputs 10 How to reset the unit 10 Introduction to this manual v Introduction to this product vi L List of figures iv List of tables iv LRC display 9 Modbus baud rate 8 Modbus data type 8 Modbus node address 8 M
17. User Variables to their Factory Default Values 1 Select rESE from the diagnostics menu Then press the ENTER key This does not reset the processor it only resets the user variables VarO1 through Var08 in both the RAM memory and the non volatile FRAM memory When the display shows done press the DIAG key to exit 2 Or hold down the DIAG key on power up When the display shows rESE then release the DIAG key This does everything the rESE diagnostic does but also resets the processor Note After doing a reset to factory defaults the analog inputs may need recalibration 10 amp 01943 602001 sales issltd co uk b www issitd co uk it OFFS How to Calibrate the Analog Input Offset This procedure calibrates the analog input via calibrating the A D converter s low end point The 4 mA low end is initially factory calibrated via defaults which for temperature probes should be more than adequate When necessary follow the steps below Calibrating the 4 20 mA analog input 1 Set the display to read the input you want to calibrate The diagnostic will calibrate whichever input is active The front panel LED s will tell you which input is active for calibration Press the Diag key Scroll to OFFS Set your sensor to its minimum value Press the enter key and the display will start reading the ADC It will display it in Hexadecimal The 1 s digit will vary 1 or 2 ADC bits I
18. Variables Log Variable i Range of Number Variable Name Values User units limitation User units limitation User units limitation User units limitation User units limitation User units limitation Set Point 1 Set Point 2 Set Point 3 Set Point 4 reserved reserved Analog input User units A Max Value limitation User units limitation Analog input User units B Max Value limitation Analog Input Enable ADC Factory Calibration select Display options Reserved User units limitation Channel B User units 20mA set point limitation Channel B 4mA User units setpoint limitation User units limitation Table 8 User Variable Log t 01943 602001 sales issltd co uk b www issitd co uk it Variable Number Calibration Variables Log Table 9 Co Communication Variables Log Variable Name Modbus Node Modbus Baud Modbus Parity Modbus Data _ type mmunications Variab Default Tes Log Range of Values DP angan Variable Name zone SO Range of Values move Madhus Page Number Value Value 9 Address Ref enabled 4o User ADC 1 offset 40465 0000 FFFF No 41400 41 mi RE 0000 FFFF No 41410 a ak 06s 0000 FFFF No 41420 43 User ADGA 52323 0000 FFFF No 41430 span cal 44 Fader ADGA 0000 FFFF No 41440 offset cal 45 pact ADG 0000 FFFF No 41450 1 span cal 46 Factory AHG amp 0000 FFFF No 41460 offset cal 47 aoto ADG 0000 FFFF No 41470 2 span cal 48
19. aa adan ena da ba ba nan aa Ne Nan 16 Figure 2 2 Relay outputs wiring diagram nk 17 Figure 3 6 Relay outputs wiring diagram oo ee eee eeecesecesecesecsecssecaeecaeeeseseaeeseeeeeeesecaeceaecsaecnaecsaecaeeeseseaeeeeeeeeees 17 List of Tables Table 1 Associations Between Keys LEDs and Menus oooooWoW oo Woo WWW mna 1 Table 4 How to perform diagnostic functions ooooo one 3 Table 5 Security Variable SdEF Security Definition 00esen0esenen ona awanan wanan awanan nawan n naen anane n anan nenen n anane 4 Table 6 Var07 ADC select Variable c ccccccccccssssecccececsesssnececececsesssaececccecseneaesecececsesesaaeseeececseaaeseeeesesenssaeaeeeeeeeene 5 Table 7 Var08 Relay Output Function Codes oooooooo oom 5 Table 8 Varl7 Display Function Codes woo mens nedre rea aea bea ba an piki yode ga opa dan aa ES 7 Table 9 Var17 Display Function Code 4 Relay Output Status W u u u ssssseeerree renerne renerne 7 Table 10 User Variable LO 522 5605 sty path ana panrus paka dun REE ea pad EN Bwa byn RERE UN 19 Table 11 Communications Variables LOg eecceesecesecessseceeneecsseceneecaeceeneecaececeecsaeceeneecsaeceeeecsaeceeneesnaeceeeeesaeeeeneees 20 Table 12 Calibration Variables TOR aapa ap pak udun asas pena Pung ilan E ena 20 Table 13 Security Variables LoS ss sus sesanan gate ai one page naa awe ABA ele DUR two boue efe TURE aa PG Ne Kemas
20. able 1 Press the VAR key 2 Use the Arrow Keys to navigate to desired parameter a Press enter key to select or abort by hitting Var Key b Change variable using arrow keys and press ENTER key to accept or Var Key to abort 3 Press Var Key to exit Variable Menu Note Access to the VAR menu is still permitted during an LRC error in the PM500 s non volatile memory afte amp 01943 602001 sales issltd co uk b www issltd co uk A Diagnostics Diagnostic Display Value Function You have Entered Diagnostic Mode dIAG dIAG Diagnostics Output percent OXXX A Verify your analog out by scrolling Oey ae from 0 to 100 0 4 mA die 100 20mA Read current Switch state SIn Switch Input Read current switch state rELY Relay states KX XX Relay one 1 s 0000 Relay two 10 s Relay Test When relays are off 1 value denotes Relay one 100 s on Relay two 1000 s VAR key 1111 Up arrow key 222 2 REV key 33 33 HeyP Left arrow key 4 4447 Tests individual buttons on keypad Keypad Test ENTER key 5555 Right arrow key 666 6 Decimal point key 77 77 Down arrow key 8 888 A ko XX XX Displays Firmware Version Firmware Version dOnE rESE e Reset Unit Resets Unit to Factory Defaults OFFS ADC value in hexadecimal of the ADC Offset Calibration actively displayed ADC input SPAN ADC Span
21. ak kn nba 20 iv amp 01943 602001 sales issltd co uk b www issitd co uk A Introduction to this Manual What is in this This installation and operation manual provides detailed technical information about the manual PM500 Programmable Process Ratemeter It should serve as your technical resource to install set up operate and test the PM500 Who should Keep in mind that the function of the PM500 installed in a mechanical process is to monitor use this manual position capacity speed etc therefore it must be installed by qualified personnel only This audience manual is designed for persons who have the primary responsibility to install set up operate and test the PM500 The secondary audience would be those persons seeking technical information about the electrical concepts and operation of the PM500 Knowledge Persons installing setting up and operating the PM500 should have good knowledge and level understanding of electrical and mechanical concepts and principles pertaining to Programmable Process Ratemeters Again the PM500 should be installed by qualified personnel only Notices e Installing Electro Sensors Inc products is the responsibility of the purchaser and is in no way guaranteed by Electro Sensors Inc e While the information in this manual has been carefully reviewed Electro Sensors Inc assumes no liability for any errors or omissions in this manual Additionally Electro Sensors Inc rese
22. at 4 mA but that is not a requirement Notes 1 When used with TT420 s this value would typically be 40 2 When used with ST420 s this would be the min value in RPM s the ST420 was programed for 3 When used as a percentage meter the value in Var 10 and Var 12 should be 0 Var 11 amp Var 13 Analog Input A amp B User Units at Upper Calibration Point User Variable 11 Analog Input A User Units at upper calibration point typically at 20 mA input User Variable 13 Analog Input B User Units at upper calibration point typically at 20 mA input This variable a k a Maximum Rate in User Units is used to scale a 20 mA signal into a displayed maximum value in user units The values entered into Var 11 amp 13 is the number of user defined units position capacity speed etc processed by the system when the analog input signal is at its upper calibration point The upper calibration point is usually set to 20mA but that is not a requirement Notes 1 When used with TT420 s this value would typically be 248 2 When used with ST420 s this would be the max value in RPM s the ST420 was programmed for 3 When used as percentage meter the value in Variable 11 and 13 should be 100 Var 14 ADC Averaging Is not implemented at this time Var 15 Analog Input Enable Analog enable is used to enable or disable inputs individually The outputs can be disabled to prevent a sensor error signal when only one sensor
23. channel B when the display is at this value Var 24 Analog Selection When analog selection is set to 0001 it makes the analog output user units track the analog input user units You will not set variables 20 23 as they are ignored When variable 24 is cleared 0000 20 23 again has authority over analog outputs Var 25 Analog Output Response Sets the analog output response time This is the time it takes to change from 10 90 out Time is listed below in seconds This can be used to smooth the output or to filter out slight deviations 1 0 00 7 1 3 2 0 020 8 2 5 3 0 040 9 4 8 4 0 080 10 9 5 5517 11 20 0 6 0 57 Var 30 Modbus Node Address Modbus Node Address sets the address for Modbus communications values 1 to 247 are valid Var 31 Modbus Baud Rate Modbus baud rate sets the baud rate for Modbus communications values 0 4 are valid 0 1200 BAUD 1 2400 BAUD 2 4800 BAUD 3 9600 BAUD 4 19200 BAUD Var 32 Modbus Parity Modbus Parity sets the parity for Modbus communications values 0 2 are valid 0 No Parity default 1 Odd Parity 2 Even Parity Var 33 Modbus Data Type Modbus data type the slave must use the same data type as the master Different slaves can use different data types as long as the data type of the slave s response is the same as the data type of the master s query Values 0 to 5 are valid 0 Float High Low 32 bit Transmit Most Significant word First 1
24. ent 000eaneneeneenennnonan anane n nenen nn anna anane nane renerne 14 Appendix B Wiring the PM 500 5 sssas tenis bandana Banana TETEG DENE an RAN an ena Ea 15 AC Input Power Supply TB I l IBI sui dentin nisan mna naura mann ea an manset 15 485 communications TB 1 4 to TB 1 6 mann 15 Switch 1mputs T 17 10 TB 1E iira pie NB Nas ngga 15 4 20 mA Analog Input TB2 10 TB2 15 oo ciccccccescsssbeisssccsscnesbesecescunsctesososbistscsissossbesedsssascedsoasucnsedsecersnesonseds ssssedaeses 15 4 20 mA Analog Output TB1 16 to TB1 18 eee eee oma 15 Relay Outputs TB3 1 to TBI 18 kene mn ente nine Pa an aan kan an Tendangan Sa 15 W rins Did grams ss sisi warisan eag gas aaa paga Dena ea ae BNN EN ia 16 Waring Dia prams COntIMUEd e inn bana ban Ben inn BE ARE e NN an en nana 17 iii atts amp 01943 602001 sales issltd co uk k www issitd co uk Appendix C PM500 Specifications secies orisi cesses binaan aka NN EN NE SEN ana 18 Variable LOS ww its Ana an aa Ba NE ARE EN aah 19 User V rlables LOS 2 sun SENO Tanya sanam cies us ieee a BG Pak ie ue aa an ne 19 Communication Variables Log desi banana samaan aman asas 20 Calibration Variables Lop aoi anna asa sasa Ega 20 Security Vanable LOS Webm nasnu bantahan sa bean aa ah aus nee aan 20 Index s2 maba RN Ea EN a zan Ka en Steed nee 21 PM500 User s Manual Back Covers mnt emuna aan Baen naa 26 List of Figures Figure 1 PM500 Wiring Dia tan saosan aaa a
25. f it varies more wait until the sensor has settled Press enter to save the value or diag to back out without updating the ADC input Calibration is done for that channel now you should verify that variable 10 and 12 reflect the point you calibrated This step can be done after calibrating both channels upper and lower ADC points 8 You are done SA he AA SCAL How to Calibrate the Analog Input Scale This procedure calibrates the analog input via calibrating the A D converter s high end point The 20 mA high end calibration is initially factory calibrated via defaults This should be more than adequate for temperature probes When necessary recalibration of the analog input is possible to do so follow the instructions below Calibrating the 4 20 mA analog input 1 Set the display to read the input you want to calibrate The diagnostic will calibrate whichever input is active The front panel LED s will tell you which input is active for calibration Press the Diag key Scroll to SCAL and press enter Set your sensor to its Maximum value 20mA point or a known operating value Press the enter key and the display will start reading the ADC It will display it in Hexadecimal The 1 s digit will vary 1 or 2 ADC bits If it is varying more wait until the sensor has settled Press enter to save the value or diag to back out without updating the ADC input Calibration is done for that channel now you should verify that
26. is being monitored Var 15 selections are e 0000 disables both inputs e 0001 enables input A e 0010 enables input B e 0011 enables both the A amp B inputs The default is 0001 Var 16 Factory Calibration Selection When factory calibration select is set to 0001 it makes the ADC inputs use factory calibrated ADC values not the default user calibration value These value are not cleared when resetting the unit They can however be set using the 485 communications When cleared variable 16 is resets to 0000 and the unit uses the default values user set values 6 amp 01943 602001 sales issltd co uk b www issitd co uk Var 17 Display Function Select Controls which real time value is displayed by the user interface The default function code is 0 display in User Units The following table gives the display function codes and a description of their meanings lif both inputs are enabled pressing the rate key will toggle between the inputs So pressing the rate key will toggle the rate code between 0 and 1 It also will allow toggling between rate code 2 and 3 a Function Description Display Units Modbus Address 0 ADC A Process position capacity User Units 30xx0 speed etc 1 ADC B Process position capacity User Units 30xx0 speed etc 2 ADC A current value ADC 1 Bits Oto FFFF 30xx0 3 ADC B current
27. ns are denied Digit 3 Not used Digit 4 Not used Table 3 Security Variable SdEF Security Definition amp 01943 602001 sales issltd co uk b www issitd co uk A User Variable Descriptions and Formats Var01 to Var04 Relay Output Setpoints User Variable 01 Variable 04 These variables contains the trip point levels for relays It is a value entered as user units They can have decimal places and be positive or negative Var07 Relay ADC Select User Variable 07 Relay ADC select Var07 allows the user to select the ADC input that is assigned to the given relay output The user can choose from three function codes one is unused The following table gives the relay output function codes and shows which Var07 digit corresponds to which relay output ae Digit Function Function Codes za Relay Output 1 Digit 2 Relay Output 2 0 Unused 8 1 Analog input A SE Relay Output 3 2 Analog input B As Relay Output 4 Table 4 Var07 ADC select Variable Var08 Relay Output Function Allows the user to select the relay output function s The user can choose from three function codes one is unused The following table gives the relay output function codes and shows which Var08 digit corresponds to an individual relay output Ee Digit Function Function Codes a Relay Output I Digit 2 Relay Output 2 0 Unused nder setpoint LE 1 Und poi A Relay
28. odbus parity 8 P Panel cut out dimension 13 Programming the analog inputs 9 Programming the analog outputs 9 Programming the relay outputs 9 21 amp 01943 602001 Index sales issltd co uk Relay ADC Select 5 Relay output Setpoints 5 relay test 10 Relay wiring 15 16 Resetting the unit 10 S Specifications 18 Switch input functions 6 T Table of contents iii iv The user interface 1 U User variable log 19 V Variable 01 Relay output Setpoint 1 5 02 Relay output setpoint 2 5 03 Relay output setpoint 3 5 04 Relay output setpoint 4 5 05 Relay ADC Select 5 09 Switch input function 6 10 Analog Input User Units Lower Cal Point CH A 6 11 Analog Input User Units Upper Cal Point CH A 6 12 Analog Input User Units Lower Cal Point CH B 6 13 Analog Input User Upper Cal Point Units CH B 6 14 ADC Averaging 6 15 Analog Enable 4 16 Factory calibration selection 6 20 Analog output minimum rate in user units CH A 21 Analog output maximum rate in user units CH A 22 Analog output minimum rate in user units CH B 8 23 Analog output maximum rate in user units CH B 8 24 Analog selection 8 25 Analog output response 8 30 Modbus node address 8 31 Modbus baud 8 32 Modbus parity 8 33 Modbus data type 8 Variables User Variable Log 19 Version number 3 Wiring diagram 16 Wiring practices 14 b www issitd co uk NOTES 22 t 01943 602001 sales issltd co uk b www issitd co uk
29. p probes otherwise you will need to go to diagnostics and preform the offset and scale calibrations 2 Verify input is properly programmed 3 Verify Program output is properly programmed a If channel A is used Variables 21 amp 22 must be programmed lower and upper setpoints b If channel B is used Variables 23 amp 24 must be programmed lower and upper setpoints c Ifyou want to use the input setpoints to also be the output setpoints set variable 24 analog selection to 0001 This is an easy way to make sure any changes to the inputs will always be reflected in the outputs mirror otherwise leave variable 24 to 0000 and set your outputs independent of the inputs The LRC Non volatile Memory Check Feature The LRC feature is a self check the PM500 performs on its non volatile memory upon power up User variables are stored in the non volatile memory If upon a power up the new LRC sum matches the previous LRC sum from the non volatile memory then the LRC self check passes But if the new LRC sum does not match the previous LRC sum then the LRC self check flags an error An LRC error means the values of at least one variable have been corrupted in the non volatile memory i e they don t contain all the user s previous values During an LRC error the PM500 goes into a fail safe mode It does not show the real time display but rather shows the message LrC Also for an LRC error the relay outputs drop out and
30. power down remove short and wait 1 min Control I O Description Standard Inputs 2 Switch inputs contact closure Standard Outputs 2 standard or 4 optional SPDT form C fully programmable relays e 250 VAC 5 A Resistive Load e 30 VDC 5 A Resistive Load Relay update rate 100mS Relay setpoint hysteresis 2 Fo Analog Inputs Description Quantity 2 channels Type 4 20mA Input Resolution 16 bit ADC 15 bits of usable range Accuracy 0 02 uncalibrated 25C typical 0 15 uncalibrated 25 C max 0 25 uncalibrated for full temperature range max ADC update rate 50mS Analog outputs Description Quantity 2 channels Type 4 20mA outputs one associated with each input Resolution 16 bit DAC Accuracy 0 1 uncalibrated 25C maximum 0 15 uncalibrated full temperature range maximum DAC update rate 25mS Input to Output isolation 1000 VAC isolation Analog input to Analog output Mechanical Description Enclosure ABS Plastic 94V 0 Keypad Polycarbonate Tactile Switch Pad Chemical Resistant Splash Proof Operating temperature 0 50 C 32 122 F Humidity 0 90 Non Condensing Operational Specifications Description Display 4 digits 0 3 seven segment LED 5 Status LEDs Display update rate 500mS 18 amp 01943 602001 sales issltd co uk b www issitd co uk Variable Logs User
31. rves the right to make changes to any part of the information in this manual or the product described herein without further notices e No part of this manual may be photocopied reproduced or translated to another language without the prior written consent of Electro Sensors Inc amp 01943 602001 sales issltd co uk b www issitd co uk da Introduction to this Product The PM500 is a stand alone display device that accepts up to two 4 20 mA DC analog input signals e The display has four 7 segment LED digits with decimal points e The PM500 can be programmed to display any value of user units from 700 00 to 9999 and from 0 00 to 999 e The PM500 has either two SPDT relay outputs or four SPDT with programmable functions UNUSED UNDER and OVER e The PM500 has an option for 2 16 bit 4 to 20 MA output signals which are isolated from the 4 to 20 mA input signals e The PM500 display has 5 status LED s so you can determine which input you are viewing as well as for indicating when the PM500 is in the programming or diagnostics modes It also signals the user when there is a sensor failure e The PM500 has 2 regulated 24 VDC outputs that can each supply 50 mA maximum This supply can be used to power sensors etc vi amp 01943 602001 sales issltd co uk b www issitd co uk A The User Interface The user interface consists of a keypad the four character display five discrete LEDs several u
32. s and power wiring together 4 Do not run signal cables along high magnetic or electrostatic generators This includes but is not limited to motors fans contactors igniters etc Aluminum shielded cable does not stop magnetically induced noise braided shielded cable only partially reduces magnetically induced noise 5 An earth ground wire must be installed on microprocessor based controllers when it is specified Do not rely on enclosure contact with the panel for earth ground Earth ground is often used in noise rejection circuitry and is not just a safety factor 6 Contactors solenoids and relay coils on the same AC power or in the same enclosure panel as the controller must be suppressed with a capacitor resistor filter across the coil These can be made with a 1 kV capacitor and a watt resistor in series or they can be purchased in a pre made package Use a capacitance value of 0 1 uF or larger and a resistance value of 500 ohms or less 7 When power is stepped down from a higher AC voltage for controllers a capacitor resistor network or other filter should be placed across the secondary 14 amp 01943 602001 sales issltd co uk b www issitd co uk da Appendix B Wiring the PM500 AC Input Power Supply TB1 1 TB1 2 The standard PM500 uses 115 VAC power 230 VAC Internal fusing is provided within the unit The recommended fuse size is a TR5 100 mA Slow Blow for 115 VAC TR5 50 mA Slow Blow for 230 VAC 48
33. ser variables and three menus the user variable menu the security menu and the diagnostic menu The three menus are each accessed by a menu key the VAR key accesses the user variable menu the DECIMAL POINT key accesses the security menu and the DIAG key accesses the diagnostic menu In each of these menus there is an intermediate level level 2 enabling you to select a menu item and a final level level 3 enabling you to change or edit the selected menu item The method for selecting which menu item to edit depends on what menu you are in In the VAR menu use the up down left and right arrow keys to edit the two digits of the user variable number In the security menu and in the DIAG menu use the up and down arrow keys to scroll through menu item prompts Once a menu item has been chosen press the ENTER key to move to the final level level 3 to edit the variable value or perform the diagnostic action To edit a user variable value use the left and right arrow keys to move the cursor the flashing digit to the digit whose value you want to change then use the up and down arrow keys to change the value of the digit Press the ENTER key to accept the value or press the abort key to throw away the changes that you have made The abort key depends on which menu you are in i e the VAR key enters the user variable menu and the VAR key aborts the user variable menu For example to change a user variable value press the VAR ke
34. y ADC Select mnunk sauna uan ea nuhun a ah akan 5 Var08 Relay Output Function ae anna ea asn 5 V r 09 Switch Input Function men nana NG ea ate ao o de pep k AG TA las BEN NG TG DENE poko a a Yaa aa ah ab pani aga naa ana 6 Var 10 amp Var 12 Analog Input Ak B User Units at Lower Calibration Point oooooooooco 6 Var 11 amp Var 13 Analog Input A amp B User Units at Upper Calibration Point oooooooooo 6 Var 14 ADC Avera ing asn Sebi oo di ban Sache es oad hase eh as sedans ee aan en eee 6 Var 15 Analog Input Enables 55 55 6 54 ag aa nite GET TAN HEI ras eh di E ed ap os eqs tas ea 6 Var 16 Factory Calibration Seleetion 5 5555555059 ag ADE en d ag ENG Aarh nenen aan 6 Var 17 Display Function Select a sas saa aa aa AG TE TAA TANGGA E YEN dan GRENENGE vese esa 7 Var 20 amp 22 Analog Output Minimum Rate in User Units 000en0enenenon anna anana nanam na anna ne anana nenen ena a en 8 Var 21 amp 23 Analog Output Maximum Rate in User Units 000en0enenenonennenen anem nn nanam nan ananem anana nenen ener een 8 Var 24 Analog Selectiohi sasuwene ena aint anna an Bae bade rer 8 Var 25 Analog Output Response sussie gase agen Tg E EN ere devise kankou nos de naa Dena 8 Var 30 Modbus Nod Address ianen a tet RN Ge l kay serait Ba 8 Var 31 Modbus Band Rate s5 smt bahan Sta Sabah Kemala banten Gavin Baga a ene ES 8 Var 32 Modbus Party sas it apaapa aaa
35. y to go to level 2 select user variable number While in level 2 edit the display so that it shows the user variable number whose value that you want to change Then press the ENTER key to accept the user variable number and go to level 3 change user variable value While in level 3 edit the display so that it shows the new user variable value Then press the ENTER key to accept that value and return to level 1 the user units display level When the user accepts a value the PM500 will test it and will not allow an out of range or illegal value If at any time you don t like the changes that you have made while you are in a particular level press the abort key to discard the changes and go back to level 1 the user units display level The SECR menu works in a similar way to allow you to change the security variable values The diagnostic menu will allow you to perform a diagnostic test to perform calibration actions or to observe the state of the system thereby enabling you to set up your system or to troubleshoot your system installation The five front panel LEDs are used to indicate which menu you are in or to indicate status information about the PM500 There are five LEDs Sensor Error PROG INPUT A INPUT B and KEY ERR When a menu key is pressed the LED associated with that menu turns on to indicate which menu you are in Key LED Menu p Decimal Point key PROG LED on amp Disp reads SEC Change Security

Download Pdf Manuals

image

Related Search

Related Contents

Radio-Controlled Time and 433mhz Temperature Station.  istruzioni PK10-10P  MF Rochette : Bain en Gériatrie  Cー。vis - 錠前・鍵メーカー Clavis(クラビス)  Passeport lecture 2015 - blogs.rpn.ch, plate  Handbuch  Fully automatic blood pressure monitor  DR-40 Owner`s Manual - 6.31 MB  Mise en page 1 - Lojas Colombo  OPERATION MANUAL for Cyclomatic Series AVC  

Copyright © All rights reserved.
Failed to retrieve file