Emerson PC642 Installation Manual
Contents
1. 2 MAX CLAMPING 4 screws PCB1B may also be DIN rail mounted using optional DIN MODEL OPERATING VOLTAGE clip assembly 11604KIT PC ordered separately VOLTAGE 1000V 1 mA 3 Attach field side pairs 26 10 AWG to positions 3 5 and 7 9 attach electronics side pairs 26 10 AWG to positions 2 4 and 6 8 Attach _PC642C 008LC NDE RIDES ground wire 10 AWG to positions 1 or 10 on base See Drawing 1 PC642C 036LC 30 VDC 36 VDC Torque wires to 44 Ibf in 8 kgf cm EEASE aae e Se 4 Insert PC642C module into keyed PCB1B WKEY base See Drawing2 _PC642C 043LC 36VDC 43 VDC 5 Apply power to protected circuit PC642C 200LC 43 250 VDC 300 VDC Emerson Network Power Contact information www EmersonNetworkPower com Surge Surge Protection 100 Emerson Parkway AS Binghamton NY 13905 gt T 607 721 8840 T 800 288 6169 EM ERSON F 607 722 8713 Network Power E SurgeTech Emerson com Emerson Network Power the Emerson Network Power logo and Edco are trademarks 10 50105 5 14 Rev 7 Printed in USA and service marks of Emerson Electric Co 2014 Emerson Electric Co While every precaution has been taken to ensure accuracy and completeness herein Emerson Network Power Surge Protection assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Specifications are subject to change without notice
2. Edco PC642 Series Zone Loop Data The Edco PC642 Series surge protective device SPD is a two pair four wire module implementing three stage hybrid technology This SPD addresses over voltage transients with gas tubes and silicon avalanche components In addition sneak and fault currents are mitigated with resettable fuses PTCs The PTCs increase resistance several orders of magnitude when over currents exceed safe levels A normal state resumes when over currents are removed The ability to self restore in this manner significantly increases suppressor performance and survivability The Edco PC642 card edge is gold plated double sided and is designed to mate with the Edco PCB1B WKEY gold plated female terminal connector sold separately When snapped together the data circuits pass thru the protector in a serial fashion from the four Field Side terminals to the four Electronics Side terminals Terminals 1 or 10 of the PCB1B must be attached to Building Approved Ground EDCO PCB1B WKEY BASE SOLD SEPARATELY General Technical Specifications Maximum Operating Voltage 5 30 36 250 VDC Features Clamping Voltage 8 36 43 300 VDC Operating Current 015A m Three stage hybrid protection Peak Surge Current 10 kA 8 x 20 us m Sneak fault current protection Frequency Range 0 to 20 MHz m Resettable fuses PTCs Insertion Loss lt 0 1 dB at 50 MHz m Low capacitance option SPD Technology GDT SAD w Series P
3. TC Connection Type Terminal Block w compression lugs m Plug in module Terminals accept up to 10 AWG m Requires Edco PCB1B WKEY base Operating Temperature 40 C to 85 C Dimensions in mm 2 0 Hx 1 0 Wx 2 5 L PC642 Base m Fast response time 50 8 x 25 4x 63 5 mm m ULlisted 497B Weight oz kg 1 oz 0 03 kg Certifications UL 497A m 5 year warranty Caution Do not place this product in service on any signal line capable of supplying more than 150 mA continuously Attention Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en permanence plus de 150 mA AN DANGER Only qualified personnel should install or service this system Electrical safety pre cautions must be followed when installing Seulement le personnel qualifi doit installer ou maintenir ce syst me Des pr cautions de s curit en lectricit doivent tre suivis or servicing this equipment To prevent risk lors de l installation ou de la maintenance ss of electrical shock turn off and lock out all de cet equipement Pour eviter tout risque Ss power sources to the unit before making de choc lectrique d branchez et verouiller electrical connections or servicing toutes les sources d alimentation de cet EMERSON equipement avant de Installation Instructions Terminal Assignments DRAWING 1 PCB1B WKEY DRAWING 2 Odd Terminals Even Terminals i 9 oe f S e Protected ae Unpeon
4. edetpart 3 Seen E 1 PCB1B WKEY Ground Terminal 1 or 10 to Building Approved Ground preferably AC Power safety ground DO NOT daisy chain grounds NOT intended for shield termination Install ground in accordance with all applicable codes Read and Understand These Instructions Ordering Information Note APPLICATIONS PART NUMBER e These protectors are intended for indoor use on communication loop i 5 circuits which have been isolated from the Public Switch Telephone RAB RSMA _ __ FEAT S PCB UE EY Network RS232 PC642C 036LC amp PCB1B WKEY The communication loop circuits shall not be exposed to accidental E NET 10 BASE T PC642C 036LC amp PCB1B WKEY contact with the electric light or power conductors e The protectors shall be installed per the applicable requirements of 4 20 ma PC642C 036LC amp PCB1B WKEY the National Electric Code ANSI NFPA 70 e Measure DC operating voltage of system to insure it does not exceed the rating of the selected surge device 5 250 VDC depending on the OPTION PART NUMBER device DIN Rail Kit Available 11604KIT PC Installation How to Specify the Appropriate Model 1 Turn off power to circuit to be protected prior to installation Other configurations available please contact factory 2 Screw mounting base PCB1B WKEY ordered separately in desired location preferably as close to protected equipment as possible and in close proximity to a building approved grounding point using
Download Pdf Manuals
Related Search
Related Contents
Catler DF 4010 deep fryer National Instruments VXI/VME 600 User's Manual Betriebsanleitung Operating instructions Mode d'emploi Copyright © All rights reserved.
Failed to retrieve file