Home
Remote control operation procedure
Contents
1. cz 5 TELA 5 5 Than a si LI FATES TALATA Hi IN Air out E E Handling switch AUTO Wiring cover ee Surface panel RUN Filter STOP Deflector l r Singal window Front panel Piping and wiring HEAT RUN COOL Signal transmit Airin RH q Drain hose Air outlet net CAI ALA AA NAA AA ESS WAWA o SS LI o SS p L l s E 5 3 NA 5 Air out Tm l Hi Remote control operation procedure Q Name and Function Remote control Note e Be sure that there are no obstructions e The remote control signal can be received at a distance of up to about 10m Don t drop or throw the remote control Don t place the remote control in a location exposed to direct sunlight SWING button When it is pressed the louvers start to rotate automatically and stop when repressed TEMP button SET TEMP increases 1 C by pressing button once and decreases 1 C by pressing button once At COOL mode operation SET
2. TIMER mode operation procedure TIMER ON TIMER OFF ANION At stopping press TIMER ON button set ON TIME in range of 0 to 24 hour to start the unit automatically At operating press TIMER OFF button set OFF TIME in range of 0 to 24 hour to stop the unit automatically Hi Q How to insert batteries 1 Remove the cover from the back of the remote control 2 Insert the two batteries Two AAA dry cell batteries and press but ton ACL 3 Re attach the cover NOTE Don t confuse the new and worn or different batteries e Remove batteries when not in use for a long time e The remote control sig nal can be received at a 2 Insert the two AAA batteries distance of up to about 10m VI OPEN Remove the cover 3 Re attach the cover Emergency run operation procedure If Wireless remote controller lost open the surface panel and operate as following Manual switch Auto Test Run Stop a When turning it to Auto position unit will run in Auto mode if there 1s remote control signal it will run at the remote control signal b When turning it to Test position the main unit will enter into Cool mode indoor fan will run at high fan speed if there is remote control signal main unit will run at the remote control signal at this time to shield the low pressure switch c When turning it to Run position the main unit will run at th
3. 5 Make sure that the wiring has been con nected firmly 6 Tighten the wire with clamp and clasp front side plate NOTE Wrong wiring connection will cause electrical mal function Do not pull the wire when fixing it with wire clamp Do not let the wire too loose in the outdoor unit Nut of connection pipe Joint Fig 7 black e lee power connection cord rubber bush brown wire So power supply cord power connection cord Wire clamp Wire clasp Tm l Install the outdoor unit Q Connecting the pipe 1 Remove the flare nuts from the cut off valves of the outdoor unit 2 Align the center of the piping flare with the relevant valve and screw in the flare nut about 3 4 turns by hand 3 Tighten the flare nut with spanner and torque wrench 4 Remove the valve caps of the gas valve and liquid valve and the ser vice port nut Q Air purging and leakage test For the air conditioners with R22 refrigerant as the below step 1 Loosen the valve stem of the liquid valve with a hex wrench 2 Push the check valve core of the gas valve to discharge air and mois ture remaining in the refrigerant system 3 Stop pushing the valve core as soon as the refrigerant starts to be discharged and reinstall the service port nut 4 Open t
4. Check earth wire Is it broken or loose Accident will happen Cleaning filters Air filters should be cleaned once every two weeks 1 Open surface panel only after air conditioner stops at all 1 Pull here up both sides of the surface panel 2 Push filters up till hooks are free from the front panel 3 Pull down and take out filters 2 Clean filters with a vacuum cleaner or by typing them gently If they are very dirty wash them in warm water below 40 C dissolved with neutral scouring agent then dry them in cool air 3 Insert them at original position then push down and close surface panel AN ARERR Check air inlet and outlet of outdoor unit A
5. TEMP can be selected from 16 C to 30 C At DRY mode operation SET TEMP can be selected from 16 C to 30C At HEAT mode operation SET TEMP can be selected from 16 C to 30 C MODE button Press this button to change the operation mode in order of mode in order of AUTO 8 beg ese ED TIMER LI LI Jm ON OFF II II AI HR FAN button Press this button to change the fan speed of AUTO FAN d lag gt in 88 COOL mode taf DRY mode FAN mode gt HEAT mode ON OFF button Press this button to turn on or turn off the unit Hi Q Name and Function Remote control Remove the cover Note This type of remote controller is a kind of new current controller some buttons of the controller which are not available to this Air condi tioner will not be described below TIMER ON TIMER OFF ANION SAVE TIMER ON button At stopping press TIMER ON button set ON TIME in range of O to 24 hour to start the unit automatically Liquid crystal displayer It shows all set contents SLEEP button Press this button to set SLEEP operation TIMER OFF button At operating press TIMER OFF button set OFF TIME in range of 0 to 24 hour to stop the unit automatically Q COOL mode operation procedure e According to difference between room temp and set temp microcomputer can control cooling on or not e Tf room temp is higher than set temp compresso
6. strong enough to withstand the full weight and vibration of the unit Be sure that the installation conforms to the installation dimension diagram Be sure to leave enough space to allow access for routine maintenance On NWN NM BW N Install in a location where is Im or more away from other electric appliances such as television audio device etc 9 Select location where is easy to remove and clean the filter 10 Do not use the unit in the immediate surroundings of a laundry a bath a shower or a swimming pool Q Outdoor unit 1 Select location from which noise and outflow air emitted by unit will not inconvenience neighbors 2 Select location where there should be sufficient ventilation 3 The inlet and outlet should not be covered 4 The location should be able to withstand the full weight and vibration of the outdoor unit 5 There should be no danger of flammable gas or corrosive gas leaks 6 Be sure that the installation conforms to the installation dimension diagram NOTE Install in the following place may cause malfunction If it is unavoidable contact with service center of SINCLAIR please e Place where oil machine oil is used e The place where a lot of salinities such as coast exists e Place where a sulfured gas such as the hot spring zones 1s generated e Place where high frequency waves are generated by radio equipment welders and medical equipment e Other place with special circumstance e Wron
7. USER S MANUAL SINCLAIR AIR CONDITIONING Please read this OWNERS MANUAL carefully prior to Functions and Working temperature range Operation mechanism Technical specifications Important notices Structure description Name and Function Remote control Name and Function Remote control Remove the cover CoOL ma opeten proste HEAT mode operation procedure TIMER mode operation procedure How to insert batteries Emergency run operation procedure Air flow direction adjustment procedure Special performance Operation conditions Installation precaution Care and maintenance When malfunction happening Installation dimension diagram Installation location Install the indoor unit Install the outdoor unit Routine check after installation For to prevent flicker impressions during the start of the compressor technical process following installation conditions do apply 1 ASH 28AT will be connected only to a supply with the relevant system impedance no more than Zmax 0 267 Q 2 The power connection for the air conditioner has to be done at the main power distribution This distribution has to be of an low impedance Normally the required impedance is eached at a 32A fusing point 3 No other equipment has to be connected to this power line 4 For detailed installation acceptance please refer to your contract with the power supplier if restrictions do apply far products like washing mac
8. e received remote control order d When turning it to Stop position the unit will stop running Air flow direction adjustment procedure With wireless remote controller adjust air flow direction As shown move the LEFT RIGHT deflectors by hand by rotating the UP DOWN deflectors up and down adjust air flow left or right or three different directions automatically or stopping at an angle Press SWING button the deflectors start to rotate and stop when repress to every corner of room so as to make everywhere temp average deflectors Adjusting left right air flow direction Special performance Time delay in heating When power is failed To avoid cold air indoor fan motor does not start All operations stop till compressor works for 30 seconds Press ON OFF button to restore operations To keep heating when room temp reaches SET If made mistakes in operation plug out then plug in TEMP and compressor stops indoor fan motor well and press ON OFF button works at LOW speed Operation conditions COOL mode operation Avoiding evaporator frost Outdoor temp should be in range of 18 C to 43 C After compressor continually working more than otherwise it is possible for air conditioner to 6 minutes and evaporator pipe temp keeping no breakdown higher than 0 C in 3 minutes the compressor and Room temp should be in range of 16 C to 32 C Room humidity should be low
9. e piping and wiring from the left or right side of the indoor unit cut off the tailings from the chassis in necessary shown in Fig 5 W Cut off tailing 1 when only power cord is routed 2 Cut off tailings 1 and 2 when connect pipe and power cord are routed Tailings ma mg 7 Tailings1 2 Wrap the piping and wiring and pull them through the cut off tailings hole shown in Fig 6 3 Hang the 2 mounting slots of the indoor unit on the upper tabs of the rear panel upa and check 1f it is firm enough Power connection cord 4 The height of the installed location should be 2 3m or more from the floor eS a Connection pipes Drain hose Wrapping tape Fig 6 Tm l Install the outdoor unit Q Install the connection pipe 1 Align the center of the piping flare with the relevant valve 2 Screw in the flare nut by hand and then tighten the nut with spanner and torque wrench refer to the diagram at right Note Exceeding tightening torque will damage the flare surface Tightening torque table Hex nut diameter mm Tightening torque N m Q12 50 55 O16 60 65 D9 5 31 35 Electric wiring connection 1 Remove the front side plate Fig 8 2 Break through the hole for wires and put on rubber bush 3 Pull all wires throught the rubber bush 4 Remove the wire clamp and connect the end of the power connection cord with screws to the wiring terminal board ac cording to the WIRING DIAGRAM of outdoor unit
10. el applied on the unit For the split type air conditioner apply on the outdoor unit Factory charge Extra charge 1 2 Total charge NI ma EN frn
11. er Important notices Air Conditioner should be operated with stable voltage in range of 198 253 V 1Ph otherwise compressor would vibrate terribly to damage refrigeration system Do not insert any foreign materials into the air inlet or air outlet lt is very dangerous Do not cut or pull strongly power lines and connecting lines fresh air better using contains while operating air conditioner to avoid cool or heat leakage which affects air condition If room air is quite turbid you should open a door or window a little for a moment to get some outdoo It is only specific technician who can operate the stop valve of outdoor unit otherwise it is possible to make refrigerant leak out and compressor breakdown Delay operation To avoid action of overload protector or other security devices we design a delay for 3 4 minutes before starting cooling or heating or dehumidifying cycle in following situations To start again immediatelly after stopping To adjust operation mode Smell Sometimes there is some smell out of indoor unit as does not mean any machine failure but because of suction air mixed with smell of furniture or smoking etc Electric circuit Must use special electric circuit do not use longer power lines do not share a same socket with other electric appliances to avoid fire etc Structure description Air in I E
12. er than 80 otherwise it is possible to dew at air conditioner surface and even drop water outdoor fan motor stop while indoor fan motor runs at SET SPEED When evaporator pipe temp is not lower than 10 C and after 3 minutes delay air conditioner restores previous operation DRY mode operation HEAT mode operation Outdoor temp should be in range of 18 Cto 43 Outdoor temp should be over 5 C otherwise it C otherwise it is possible for air conditioner to is possible for protect devices inside to act and air breakdown Room temp should be in range of 16 C to 32 C conditioner can not start Installation precaution Installation position Drain the condensed water from indoor unit into ground pipe Install indoor unit far away TV set or radio etc to avoid disturbing video or voice In salt and coastal area or place where is near thermal springs and polluted by sulphureous gas or other special areas please contact with seller before use Avoid place where 1s possible for flammable gas to leak out Avoid other heat sources or direct sun light Avoid place where is easy for children to touch When remove air conditioner to other place it needs special technician so contact with seller firstly Earth wire Do not connect earth wire to following places Water pipe Sometimes there is some plastic material such as polythene used as part of water pipe which is not available for earth Install o
13. ething into air conditioner Electrical lines are much hot or lines cover breaks Other strange situations iT Installation dimension diagram Space to the ceiling MOW JO W M Jem Or More Space to the wall 5 SS D EC N IMPORTANT NOTES The installation must be done by trained and qualified service personnel with reliability according to this manual Contact with service center of SINCLAIR before installation to avoid the malfunction due to unprofessional installation When picking up and moving the units you must be guided by trained and qualified personnel The distance between air outlet and the combustible must be over 50cm if the heater element is equipped D _ a O S LO Space to the cover 570 Rg Space to the wall sem of HO Piping hole sleeve Q A e Wrapping tape soe Ar aS SS KIN Space to the Wall AGUA 50cm or more SA HI D f VG b Installation location Indoor unit 1 The inlet and outlet should not be covered so that the outflow air can reach all parts of the room Install in a location where 1s permitting easy connection with the outdoor unit A location from which the condensation water can be drained out conveniently Avoid a location where there is heat source high humidity or inflammable gas Install in a location where is
14. g wiring connection will cause electrical malfunction e Do not pull the wire when fixing it with wire clamp e The appliance is not intended for use by young children or infirm persons without supervision e Young children should be supervised to ensure that they do not play with the appliance saan Install the indoor unit Q Install the rear panel 1 Always mount the rear panel horizontally 2 Fix the rear panel on the selected location with screws supplied with the unit 3 Be sure that the rear panel has been fixed firmly i ie dll enough to withstand the weight of an adult of 0 ye Jog 60kg furthermore the weight should be aa aI g g O65 evenly shared by each screw l Fig 2 Install the drain hose 1 For well draining the drain hose should be placed at a downward slant 2 Do not wrench or bend the drain hose or flood its end by water Wrenched Bent Install the piping hole ve P 1 Make the piping hole D 65 in the wall at a slight downward Kr slant to the outdoor side The center of the hole should be x x Flooded determined refer to Fig 2 2 Insert the piping hole sleeve into the hole to prevent the Fig 3 connection piping and wiring from being damaged when passing through the hole Q Install the connection pipes Connect the con
15. he liquid valve and gas valve entirely shown in Fig 9 5 Tighten the valve caps and test leakage at all joints of the piping both indoor and outdoor with liquid soap or leak detector 6 If possible discharge air and moisture remaining in the refrigerant system with a vacuum pump shown in Fig 10 1 Remove the nuts of one way valve 2 Evacuate from the one way valve with a vacuum pump until the vacuum meter is 5 Torr and keep up evacuating hour or more 3 Turn off the valve and fighten the nuts 4 Fully open valves Fig 9 5 Tighten the nuts then check whether there is gas leaking out Moisture inside pipeline must be less 200 PPm Q Outdoor condensation drainage Heat pump type only When the unit is heating or defrosting the waste water formed in the outdoor unit can be drained out reliably through the drain hose Installation Install the outdoor drain elbow in the 25 hole on the base plate as shown in Fig 11 and joint the drain hose to the elbow so that the waste water formed in the outdoor unit can be drained out to a proper place gas valve Liquid valve Manifold gauge Boe Liquid tube Gas tube Fig 10 Vacuum pump a Base plate 5 Outdoor drain elbow Fig 11 EETTT ZT UN Routine check after installation Q Check after installation Items to be checked Possible malfunction Has the air conditioner been fixed firmly The unit may drop shake or emit noise l It may ca
16. hines air conditioners or electrical ovens 5 For power details of the air conditioner refer to the rating plate of the product 6 For any question contact your local seller 7 This product must not be disposed together with the domestic waste This product has to be disposed at an authorized place for recycling of electrical and electronic appliances 8 The fuse indoor TSAL AC250V outdoor T3 15AL AC250V oa Functions In hot summer air conditioner can cool room air by Without reducing TOOM temp air conditioner can transfering heat out dehumidify and make room air dry and comfortable Operating automatically Heating in winter heat pump type According to room temp change microcomputer can In cold winter air conditioner can supply warm air to automaticlly set COOL or HEAT or FAN operation mode rise room temp so as for best effect X Working temperature range Outdoor side DB WB C X Working voltage 50Hz 230V X Installation precaution 1 To prevent possible hazards due to insulation failure the unit must be grounded 2 Provide a power outlet to be used exclusively for each unit and a power supply disconnect and circuit breaker and current fuse p
17. hould be in range of 16 C to 30 C 3 Press SWING button the louvers start to ro tate automatically and stop when repress it AUTO FAN o am O 4 Press TEMP button set suitable SET TEMP 2 Press MODE button set Li operation mode 1 Plug in press ON OFF button then air conditioner is turned on Q SLEEP mode operation procedure e When the unit is cooling or drying if SLEEP operation is set SET TEMP would increase 1 C in 1 hour and 2 C in 2 hours Indoor fan motor runs at low speed e When the unit is heating if SLEEP operation is set SET TEMP would decrease 1 C in 1 hour and 2 C in 2 hours Indoor fan motor runs at low speed 4 Press FAN button set fan speed 3 Press SWING button the louvers start to rotate automatically and stop when repress 6 SLEEP button o Press it to set SLEEP operation 5 Press TEMP but ton set suitable SET TEMP TIMERON TIMEROFF ANION 2 Press MODE button set la or op eration mode 1 Plug in press ON OFF button then air conditioner is turned on Q AUTO mode operation procedure e At AUTO mode operation standard SET TEMP is 25 C for COOL mode and 20 C for HEAT mode AUTO FAN oper AUTO TIMER ON TIMER OFF ANION 1 Plug in Press ON OFF button then air conditioner is turned on 2 According to room temp micro computer can automatically set 2 8 Nf operation mode so as for best effect
18. ir lock could result in bad efficiency Tm l When malfunction happening Please check the following items before ask for repair it saves your time and money Fault phenomenon Trouble shooting Is power fail l _ Is plug out Air conditioner Is power fuse or switch off does not operate Is voltage higher than 264V or lower than 206V at all Is SET TIME suitable Ts air inlet or outlet locking Is there any other heat source in room Are air filters dirty very much Cooling efficiency Is indoor fan speed set at LOW is not good Is SET TEMP suitable If disturbed abnormally or operation modes changed Wireless remote too frequently sometimes the electric controller would lose function Please plug out and plug in again it maybe OK available Check batteries of wireless remote controller if voltage is little change batteries GG If wireless remote controller displays unclear or displays all symbols please change batteries controller is not Foggy air flows At COOL or DRY mode operation sometimes there out 1s foggy air flowing out of indoor unit this 1s because that room humid air has been cooling rapid Immediately stop all operations and plug out contact with your seller in the following situations Operation starts or stops abnormally Power fuse or switch often breaks Carelessly splash water or som
19. n place firmly enough to avoid transmitting or increasing noise and vibration Do not put objects in front of outdoor unit air outlet to avoid increasing noise Be sure not to make trouble to neighbors with hot air or noise from outdoor unit Please contact with saler as soon as there 1s strange noise during operation Electric lines location Must connect with ground Must use rated voltage and electric circuit specific GG for air conditioner Avoid octopus type of multi plug which would cause over heat Do not pull power lines strongly To fit an electrical leakage proof switch please contact with special eletric seller Chose proper fuse to meet with the current specification Power lines should be thick enough Gas pipe If there is electrical leakage accidently from air conditioner it is easy to cause fire or explosion as is very dangerous Tm l Care and maintenance Cleaning unit 1 Switch off first before cleaning Switch off only after air conditioner stops at all 2 Clean surface panel with a soft and dry cloth which is soaked warm water below 40 C Must dry the cloth by hands before 4 Do not splash water directly to indoor unit in which there are microcomputer and circuit plate SS they must not be touched by water A
20. nection pipes with the relevant union pipes of the indoor unit Shown in P25 Install the connection DI pipes NOTE e Connect the connection pipes with the indoor unit firstly and the outdoor unit secondly e Be careful in bending the connection pipes or you will damage the pipes e If the tightening torque is too great in tightening the flare nuts leakage will happen Q Electrical wiring 1 Open the surface panel 2 Remove the wiring cover Fig 4 3 Route the power connection cord from the back of the indoor unit and pull it toward the front through the wiring hole for connection 4 Connect the blue wire of the power connection cord to the terminal N 1 the brown one to 2 the black one to 3 and the yellow green one earth wire to Dm as shown in Fig 4 Wiring cover plate Power connection cord type HO7RN F4G1 5mm Fig 4 NOTE e All the electrical work must be done by qualified personnel according to relative wiring regulation and this manual e The power supply is type Y comnection If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard e The rated voltage and the exclusive circuit must be used e Leakage circuit breaker and air switch of correct capacity must be installed The air switch of 32A should be used in these models Install the indoor unit 1 When routing th
21. r runs at COOL mode e Tf room temp is lower than set temp compressor stops and only indoor fan motor runs e SET TEMP should be in range of 16 C to 30 C 3 Press SWING button the louvers start to ro tate automatically and stop when repress 5 Press TEMP but ton set suitable SET TEMP 2 Press MODE button set operation mode Hi TIMERON TIMER OFF ANION 4 Press FAN button set fan speed 1 Plug in press ON OFF button then air conditioner is turned on Q HEAT mode operation procedure e If room temp is lower than set temp compressor runs at HEAT mode e Tf room temp is higher than set temp compressor and outdoor fan motor stop only indoor fan motor runs e SET TEMP should be in range of 16 C to 30 C 3 Press SWING button the louvers start to rotate automatically and stop when repress It 5 Press TEMP but ton set suitable SET TEMP 1 Plug in press ON OFF button then air conditioner is turned on TIMERON TIMEROFF ANION SAVE 4 Press FAN button set fan speed AUTO FAN oper 2 Press MODE button set operation mode NOE oe o Tm l DRY mode operation procedure e If room temp is lower than set temp compressor outdoor and indoor fan motor stop If room temp is between 2 C of set temp Air conditioner is drying If room temp is higher than set temp it s at COOL mode e SET TEMP s
22. rotector should be provide in the exclusive line 3 Each wiring connection must be done in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damage 4 Please cut off power supply when unit will not be used for a long time An all pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring T aan Operation mechanism Cooling cycle Connected with pipes indoor unit and outdoor unit form a refrigeration system With power compressor takes in low temp and low pressure refrigerant vapour from evaporator of indoor unit presses it into high temp and high pressure gas then discharges it into condenser of outdoor unit By help of axialflow fan heat is removed to outdoor air from the gas which then condenses into liquid After capillary tube throtting the liquid drops temp and pressure flows into evaporator There by help of cross flow fan the liquid absorbs heat from room air evaporates and becomes low pressure vapour which then flows into compressor again beginning next cooling cycle Therefore heat is transfered from indoor to outdoor and room gets cool Ventilation cycle Ventilation cycle divides into indoor and outdoor two parts With suction of cross flow fan room air flows through filters exchanges heat in evaporator then returns
23. to room In this way room air can be cool and dehumidified At the same time pumped by axial flow fan outdoor air flows through condenser and exchanges heat Heating cycle Heat pump type air conditioner uses a commutator 4 way electromagnetic valve to change refrigerant flow direction When heating refrigerant firstly enters indoor heat exchanger releasing heat and condensing Then it enters outdoor heat exchanger absorbing heat and evaporating Because consumption power changes into heat which is discharged in room heating efficiency is very good 1 Schematic diagram of cool only type 7 6 o j 1 Compressor 2 Outdoor heat exchanger 3 Filter 4 Capillary tube 5 Stop valve 6 Connecting pipes 7 Indoor heat exchanger 8 Accumulator 2 Schematic diagram of heat pump type 9 1 Compressor 2 4 way electromagnetic valve 3 Outdoor heat exchanger 4 Filter 5 Master capillary tube 6 Check valve 7 Auxiliary capillary tube 8 Stop valve 9 Connecting pipes 10 Indoor heat exchanger 11 Accumulator 3 O O O O Oo Eo i Mo KE E Technical specification ion Power supply 230V 50Hz Rated input Cooling W 4000 Heating W 3600 Input power Cooling W 2800 Heating W 2800 Refrigerant R410A 2600g Outdoor 6 Dimension Indoor unit 117843264227 mm 7 5 T All above should be changed without notice There are latest and accurate specification on the nameplate of your air condition
24. use insufficient refrigerating 9 Have you done the refrigerant leakage test capacity Is heat insulation sufficient It may cause condensation and dripping Does the unit drain well It may cause condensation and dripping Is the voltage in accordance with the rated volt It may cause electric malfunction or damage age marked on the nameplate the part Has the unit been connected to a secure earth It may cause electrical leakage connection aaa A o electric malfunction or damage It may cause insufficient refrigerating capacity Has the inlet and outlet been covered Has the length of connection pipes and the re The refrigerant capacity is not accurate frigerant capacity been recorded Is the electrical wiring and piping connection in It may cause electric malfunction or damage stalled correctly and securely the part ENVIRONMENTAL INFORMATION This unit contains fluorinated gases with greenhouse effect covered by the Kyoto Protocol Maintenance and disposal must be carried out by qualified persons only Refrigerant gas R410A GWP 1730 EXTRA REFRIGERANT CHARGE Pursuant to Regulation EC 842 2006 on certain fluorinated greenhouse gases 1n case of extra refrigerant charge it is compulsory to Fill in the label accompanying the unit inserting the factory quantity of refrigerant charge see the technical label the extra refrigerant charge and the total charge Apply the label next to the technical lab
Download Pdf Manuals
Related Search
Related Contents
Marker 2000 Manual User's Manual Scouting Camera SG860C-HD Manuale d`installazione, uso e manutenzione Tote Vision LCD-2001VB User's Manual APW Wyott w/EZ-Lock User's Manual Lenovo Portable DVD Burner GP20N enables fast recording of Windmere CS1CP Use & Care Manual 「取扱説明書」 SR552シリーズ (20070701-V003) scarica - Benvenuti su Nuova Rocchi ELECTRONIC SCALE BWB-800MA SEPARATE Copyright © All rights reserved.