KNX DALI gateway REG-K/1/16(64)/64 For your safety

image

Contents

1. 8 Gruppen Szenen 1 g B 2 10 B 3 aa 4 12 s 13 6 14 13 8 16 Device Id 15 15 255 Fertig o To set a scene first select it on the right side The select ed scene if present will be called up in the DALI seg ment The set light values will be displayed in the corresponding group windows The light values can be individually adjusted using the buttons On off dim up dim down The light value can be modified in groups by a short switch or long dim click on the corresponding group field Save The altered value in the selected scene will be saved Group scene assignment This button regulates the assignment of groups to the individual scenes Technical data Supply voltage AC 110 240 V 50 to 60Hz max 0 1A Additionally via KNX bus Operating elements Learning button for toggling between normal mode and addressing mode SCROLL Prg Set ESC key on the front for instrument setting and parameterisation Display elements LED red Normal addressing mode PWR LED green Availability ERR LED red Error status LCD display 2 rows with 12 characters to navigate menu during commis sioning and parameterisation Inputs Passive floating input for con necting push buttons or pres ence detectors DC 9 32 V or AC 8 26 V Cable length max 15 m DALI bus output Connection of up to 64 electronic ballasts according to IEC 60
2. This sets the send condition for the light status of the DALI groups 4 communication object of each group One page is available for each group on which the group specific parameters can be set Page Group 1 16 Group 1 Switch on value fox O Dimming time 10 Seconds kad Minimum value for dimming 5 bA Maximum value for dimming fi 00 xl Behavior when receiving On Accept value immediately bd Behavior when receiving Off Accept value immediately xl Behavior when receiving value Accept value immediately Dimming time for On Off set value fio Seconds z Type of status object Switch status 1Bit ha Type of recognized failures flampfaiuesony S Cancel Default Info Help Behaviour on KNX bus No change voltage failure Change to failure value Switch off Parameters Settings This determines which lighting condition is to be set in the event of KNX bus voltage failure Behaviour on KNX bus voltage recovery No change Change to last value Change to failure value Switch off Switch on value 0 5 10 continued in steps of 5 90 95 100 Last value This determines which lighting condition is to be set on return of KNX bus voltage Behaviour on recovery after No change DALI failure Change to last value Switch off This sets the parameter for the lighting value which is to be set in the corresponding DALI group on receipt of a 1 t
3. ECGs should be controlled individually If the parameter Yes is selected additional parameters will appear to set the individual control Detectable failure types No failure status Only lamp failures by 1Bit object Only ECG failures by 1Bit object Lamp and ECG failures by 1Bit object Lamp and or ECG failures by 1Byte object The user can set here whether errors are to be detected individually for each ECG and which error type is to be detected The error objects 176 to 239 will appear depending on the parameter Attention In case of total parameters in group 1 control via DALI Broadcast the apply e g switch on value dimming time etc They can be set on the corresponding parameter page The DaliControl SC64IP als a permanent or temporary o enables DALI commissioning via IP network The operations necessary for the commissioning process can be performed via the web pages of the integrated web server The IP address is usually assigned by the DHCP service of a DHCP server on the network If no DHCP server is available the settings need to be performed manually The required network config Page IP configuration I urations are set via parameters P configuration Device name 30 char max IP Address assignment DaliControl by DHCP Server z Cancel Default nfo Help ECG 1 No Individual Control Bates Switch only via 1 Bit object ECG 64 Dim only via 4
4. IP V 2 0 _ setting IPADDRESS Displays the IP address setin the ETS or assigned by the DHCP server NEW Resets the connected DALI devices INSTALLATION and starts the automatic search run for electronic ballasts REINSTAL Starts the automatic search run and LATION configuration adjustment where re quired GROUP Assignment of the electronic ballasts ASSIGNMENT _ found to desired DALI groups GROUP Setting modifying the parameters of PARAMETERS the individual groups SCENE Assignment of DALI scenes to the de ASSIGNMENT sired associated groups GROUP Switching the entire installation TEST broadcast and individual channels for test purposes SCENE Retrieves the individual programmed TEST scenes for test purposes SYSTEM Present system errors can be re TEST trieved individually FUNCTION Setting the function of the floating INPUT B1 push button input B1 FUNCTION Setting the function of the floating INPUT B2 push button input B2 If a process is activated in a lower level or if a parameter is altered the programming mode must be switched to at the selection position To do this actuate the Prg Set button for longer than 2 s If the respective function is in programming mode a gt symbol appears in the display If the programming mode is active a possible parameter or setting can be changed using the SCROLL button Briefly pressing the Prg Set button again completes the pro
5. a portable PDA This gives the commissioning technician the opportunity to move around the installation freely In addition two binary inputs are available on the device Via simple pushbuttons which are connected to the device switch functions can be performed directly The pushbutton function is available without an existing KNX Bus and is particularly advantageous for the installation phase construction site operation As an REG device 6TE the DaliControl SC64IP is suitable for DIN Rail mounting in standard sub distributions Connection to the bus is via a standard bus coupler The DALI power supply and pushbuttons are connected using screw connectors The application program 3927 DaliControlSC64 01 0120 is available to operate the device Communication objects A maximum of 252 communication objects is available for communication of the device via the KNX The objects are in parts displayed or hidden depending on how the parameters are set The communication objects can be connected to 255 group addresses via 255 associations 5 objects are assigned to each of the 16 DALI groups The objects for group 1 are Obj Function Object name Type Flags 0 On Off Switch group 1 1 bit CWT The lamps assigned to DALI group 1 are switched to the set switch ON or switch OFF value using this object Whether switching is to be carried out immediately or whether dimming is to be performed to the f
6. on or off to gether via a DALI broadcast telegram using this function Switch to the scene page This button is used to switch to the scene setting page Toggle key Below the header are the fields with which the elec tronic ballasts or group assignment can be identi fied To identify the electronic ballasts all luminaires should first be set to a defined value e g off via broadcast This button can be used to switch on or off individual electronic ballasts by clicking on them with the mouse which simplifies identification of the electronic ballasts which are arranged in random or der Image key This button can be used to assign individual elec tronic ballasts to groups following identification Subsequently the group which is to be assigned can also be selected by clicking on it with the mouse If the electronic ballast is then clicked on it will be assigned to the selected group The group assignment will be indi cated by a small green field containing the group number in the upper right corner of the electronic ballast list Electronic ballasts which are not yet assigned to any group receive afield highlighted in yellow with a question mark Besides identifying and assigning groups the scene va lues and scene assignments can also be set on another web page From the commissioning page the scene page is reached by clicking on the Scenes button The page has the following layout
7. scenes SCENE01 XXXX Retrieve the individual scenes using XXXXXXXXXXX the SCROLL key First display row Number of the selected scene After the scene number Symbolic display of which of the groups 1 to 16 is assigned to the respective scene X the corresponding group is as signed to the scene the group is not assigned First display row The four characters after the scene number correspond from left to right with the groups 1 to 4 The 12 charac ters in the second display row corre spond from left in ascending order with groups 5 to 12 SCENE03 Long actuation of the Prg Set key Switches to the programming mode Flashing cursor on the first X select ed group 1 Brief actuation of the SCROLL button Selects whether the corresponding group should be as signed to the selected scene switch es between X and characters Brief actuation of the Prg Set key Cursor and possible setting is moved to the next group After cycling through all 16 groups Setting is saved and taken into account during the next scene programming Actuating the Prg Set key automatically returns to the level above Press ESC key or automatically after approx 30 s Returns to the level above Any changes made will not be saved FUNCTION INPUT B1 submenu level 2 and 3 Press the Prg Set key Switches from the FUNC TION INPUT B1 main menu to the submenu Within this menu the function of the floating push button co
8. three different ways 1 Commissioning via the device The DALI can be commissioned entirely on the device by using the integrated display and programming buttons without KNX and previous ETS programming Commissioning on the device is particularly recommended for DALI installations performed by an electrician and where the ETS is programmed subsequently by a system integrator 2 Commissioning via the DaliControl Service and Commissioning Wizard In addition an easy to use and free commissioning tool is available Using this tool the DALI can be commissioned via an interface connected to the KNX Bus RS 232 USB IP This method is particularly recommended for installations where the Gateways are located separately from the lights or where the lights are not visible to the Gateways Using this tool enables the identification of the lights locally at the place of installation 3 Commissioning via integrated web server In addition to the KNX and DALI interface the DaliControl SC64IP also has an RJ 45 interface which makes it possible to connect the device with an existing IP network The integrated web server ensures easy DALI commissioning via any web browser The IP address which will have been programmed with ETS or assigned by a DHCP server is entered in a browser Web access is also possible via WLAN 2008 Merten GmbH amp Co KG The commissioning website is designed in such a way that the display is possible on
9. 143 the set lighting state is saved in the corresponding scene Light value on DALI and No change KNX failure 0 5 10 continued in steps of 5 90 95 100 Adjustment per group This determines which lighting value is to be set in case of a DALI or KNX error In case of the Setting per group parameter two additional pages appear on which the error values can be chosen individually per group Invoke Save Scene 1 0 128 Scene 2 1 129 Scene 3 2 130 Scene 14 13 141 Scene 15 14 142 Scene 16 15 143 Parameters For the purpose of clarity the parameters are spread over several pages The following parameters are available General page General Sending condition of status object Sendingonchange i x Behaviour on KNX bus voltage failure No Chane O Bshavious on KNX bus voltage recovery Nocne O iea moes Sending condition failure object Sendingonchange x Light value on DALI and KNX failure 100 z Start of DALI new and post installation Jenabed o by push buttons Cancel Default nfc Help Enabled Disabled Start of DALI new and post installation by pushbuttons This sets whether a new or additional DALI installation can be performed via the pushbuttons on the device The device can thus be protected against unauthorised access Parameters Settings Sending condition of status Sending on request only object Sending on change
10. 926 DALI voltage DC 18 21 V short circuit proof No other control units DALI masters may be used Ethernet IP connection via ethernet speed 10Mbit second used only for DALI commissioning Connections Bus line KNX bus terminal Mains supply Screw terminal 3x 1 5mm single core and multi core DALI bus Screw terminal 2x 1 5mm sin gle core and multi core Floating contactinput Screw terminal 2x 1 5mm single core and multi core Ethernet RJ 45 connector for standard patch cable KNX bus Safety extra low voltage SELV DC 24V Ambient conditions during operation 0 C to 45 C Storage temperature 25 C to 70 C Rel humidity not condensing 5 to 93 Type of protection IP 20 in accordance with EN 60529 Protection class I in accordance with IEC 1140 Corresponds with EN 14606 Dimensions WxHxD 106mm x 55mm x 86mm 6TE Directive EMC directive residential commercial buildings low voltage directive Merten GmbH amp Co KG Merten GmbH amp Co KG Solutions for intelligent buil dings Service Center Fritz Kotz Str 8 Industriegebiet Bomig West D 51674 Wiehl Phone 49 2261 702 204 Fax 49 2261 702 136 E Mail servicecenter merten de Internet www merten com If you have technical questions please contact our InfoLine Phone 49 1805 212581 or 49 800 63783640 Telefax 49 1805 212582 or 49 800 63783630 E Mail infoline merten de fee required D6801 581 01 07 08 Application
11. Bit object Set value only via 1 Byte object Parameters Settings Device name max 30 characters DaliControl The user can set here which object type is to be used for the individual control of the ECG Only one object is available for each ECG in this case The object type appears depending on the parameter The device name User Frie device can be entered here ndly Name for IP identification of the IP adress assignment by DHCP Service manually In addition to group and individual control the application also offers complete control of all connected ECGs at the same time Communication in this case is via DALI Broadcast Telegrams and no new installation of the DALI is required Page Common control Common control DAL bosdeast fe E DALI broadcast feasible I Parameters from group 1 are valid if using broadcast commands Cancel Default ni Help 2008 Merten GmbH amp Co KG The user can set here whether the address will be assigned automatically by a DHCP se rver on the network or whether a fixed IP address will be entered manually IP address byte 1 0 0 255 If the address is assigned manually the 1 Byte of the IP address can be set here The setting s of Bytes 2 4 are analogue IP subnet mask Byte 1 255 0 255 If the address is assigned manually the 1 Byte of the IP subnet mask can be set here The settings of B
12. DALI pau evaj e 6 e m pau evaj e 6 e KNX L panj An exact description of the commissioning procedure using the tool can be found in the Dali Control Service and Commissioning Wizard s user manual DALI commissioning via web server ALI EVG au eve paneve ALI EVG ALI EVG pareve an eve ob ob bi Besides commissioning using the push buttons and the additional software tool DALI commissioning can also be performed very conveniently using the device s inte grated web server For this purpose the gateway can be connected directly to the IP network A RJ 45 socket is located at the bottom left edge of the housing above the KNX bus terminal The device can be connected to a switch hub or router of the IP network using a standard patch cable As the network connection is only required for commissioning a temporary connection is normally sufficient After the work has been completed the net work connection can then be removed again When con necting the network connection ensure sufficient distance between the IP cable and the mains supply by appropriate cable routing Of course a WLAN access point can also be used as a network coupler In this case commissioning can be performed using a laptop PDA or other operator device After the network connection has been established the commission
13. ally recognised in ascending order The search process lasts several minutes depending on the number of connected ECGs FOUND ECGs 47 After the search process is completed Display Number of ECGs found Press ESC or automatically after approx 30 s Re turns to the level above REINSTALLATION submenu level 2 Press the Prg Set key Switches from the REINSTALLATION main menu to the SEARCH ECGs submenu via PROG MODE SEARCH Long actuation of the Prg Set key Switch ECGs via es to the programming mode Briefly PROG pressing the Prg Set key Starts the verifi MODE cation and search process Connected ECGs will be searched for via their long ad dress and automatically compared with the previous configuration DELETED Have been removed from the DALI seg ECGs 3 ment ECGs and the corresponding entries in the device will be automatically deleted During the verification process The number of deleted devices is displayed NEW Searches for newly installed devices in the ECGs 1 DALI segment Recently added ECGs are automatically reset previously set param eters group assignments are deleted The search process lasts several minutes de pending on the number of connected ECGs During the search process The number of newly found devices is dis played DEL NEW After the entire process has been complet ECGs 3 1 ed verification and search The number of deleted and newly found ECGs is dis
14. cess The set parameter is saved or the correspon ding process is activated DALI CONTROL submenu level 2 Press the Prg Set key Switches from the DALI CONTROL main menu to the LANGUAGE sub menu LANGUAGE Display current display language GERMAN Long actuation of the Prg Set key Switches to the programming mode Language selection GERMAN ENG LISH FRENCH SPANISH SWEDISH using the SCROLL button Press the Prg Set key set parameterisation is con firmed and saved and the display works in the cor responding language IP ADDRESS submenu level 2 Press the Prg Set key Switches from the IP ADDRESS main menu to the submenu IP 192 168 Displays the IP address currently set in 004 101 the ETS or assigned by a DHCP server in the IP network The setting cannot be changed on the device Setting is per formed via the ETS or via DHCP REINSTALLATION submenu level 2 Press the Prg Set key Switches from the INSTALLATION main menu to the SEARCH ECGs submenu via PROG MODE SEARCH Long actuation of the Prg Set key ECGs via Switches to the programming mode PROG Then press the Prg Set key briefly Starts MODE the initialisation and search process All of the electronic ballasts connected to the DALI segment are automatically reset and any previously set parameters group as signments are deleted The connected ECGs are then searched for via their ran domly generated long address and auto matic
15. connection RJ 45 socket KNX bus terminal Programming LED Programming button Mains connection DALI output terminal Connection for 1st floating key Connection for 2nd floating key Display SCROLL key Prg Set key ESC key PWR LED green Operating display ERR LED red Error display S GOQOO OOH OQHOOO Mounting the Gateway Insert the gateway into the DIN rail from above and slide downwards Press from underneath and hook onto the rail Connect the connecting cable for the DALI bus to the upper left terminal The DALI control cables can be guided into a 5 core ca ble together with the power line basic insulation suffi cient according to IEC90929 Clear labelling must be guaranteed however A maximum line length of 300 m for the entire DALI installation of a segment must not be exceeded recommended cross section 1 5mm After connecting the DALI cable the two external push buttons can be fitted according to the connection dia gram if necessary The push button inputs are passive which means that an auxiliary voltage of AC 8 26 V or DC 9 32 V is required Connect the mains voltage according to the con nection order shown on the housing to the lower right terminal To connect the KNX cable a standard bus terminal is plugged into the corresponding terminal receiver on the device Double basic insulation between the KNX installation and the mains
16. ct is used to inform about the error status within a DALI group Whether only a lamp malfunction only an ECG malfunction or both types result in an error status can be set in the parameters An object value of 0 means that no error has occurred within the group A value of 1 means that at least one error has been detected within the group The requirement for sending the object can be adjusted 241 Brighter Darker Dimming 4 Bit CWT Broadcast This object is used to dim all lamps that are connected to the Dali either up or down via DALI Broadcast telegrams For Broadcast dimming always use the parameters of group 1 Like objects 0 to 4 for DALI group 1 objects 7 to 11 are assigned to DALI group 2 objects 14 to 18 to DALI group 3 etc up to objects 105 to 109 for DALI group 16 Using the DaliControl SC64IP all 64 ECGs lamps can also be controlled individually However in this case only one object is available per ECG The type of control and thus the object type can be set via a corresponding parameter see below Individual control is performed via the objects 112 to 175 242 Value Value group 1 1 Byte CWT This object is used to set all lamps that are connected to the Dali to a lighting value via DALI Broadcast telegrams For Broadcast value setting always use the parameters of group 1 Obj Function Object name Type Flags 112 On Off Switch ECG 1 1 bit CWT Bright
17. description 7305 Dali Control Function description The DaliControl SC64IP brings together the cross functional KNX installation bus and the lighting control specific DALI Bus Lights with cost effective digital DALI ECGs can therefore be integrated into an overall KNX architecture and operated via the multitude of existing KNX devices The DaliControl SC64IP serves both as DALI Master and power supply for up to 64 connected ECGs The ECGs can be switched dimmed or set to a defined value in up to 16 groups per Gateway The current lighting value or error status of each group lamp ECG error status within the group can be exported to e g a visualisation via KNX In addition to the group control the SC64IP also enables the individual control of up to 64 ECGs In the latter case one object is available per ECG A parameter determines whether the individual ECG is to be switched dimmed or set to a defined value An error status object is available for each ECG This makes it possible to locate exactly lamp and ECG errors Full control of all connected ECGs via Broadcast no DALI commissioning is necessary in this case is also possible via three objects In addition the individual groups can be used to program and load up to 16 light scenes The scene control is performed via a 1Byte object Using the SC64IP the DALI can be commissioned assignment of DALI ECGs to the various groups and changes in configuration in
18. desired groups In the GROUP TEST menu item cf Operation and menu structure the individual groups can be switched on and off for test purposes If push buttons are connected to the device s inputs the push button function can be adjusted in the FUNCTION INPUT B1 and B2 menu items and the inputs can be as signed to individual DALI groups This means that DALI functions can be performed even if no KNX is available yet building site operation Of course the inputs can also be used in normal operation to integrate cost effec tive standard push buttons or movement detectors into the system Finally in the last stage of DALI commissioning groups can be assigned to the individual scenes in the SCENE ASSIGNMENT menu item cf Operation and menu structure Commissioning of the DALI segment is complete when the steps described have been completed KNX com missioning can then be carried out immediately or later with the ETS and the associated application program as usual DALI commissioning using the device keys and the display The DALI segment can also be commissioned using the free software tool Dali Service and Commissioning Wiz ard For this purpose the device must already be con nected to the KNX bus and a physical address must be assigned Communication to the device is then effected via an interface connected to the KNX ALEVE X
19. elegram If the parameter setting last value is selected the value switched on receipt of a 1 telegram is the value that was set via dimming or value setting before the last 0 telegram was received 2008 Merten GmbH amp Co KG Application description 7305 Dali Control 2 5 seconds 5 seconds 10 seconds 15 seconds 20 seconds 30 seconds 1 minute Dimming time 30 minutes 1 hour This determines whether the status object should only make the ON OFF switch status for the corresponding DALI group available or also the value status 0 100 Type of recognized failures No error status Only lamp error Only ECG error Lamp and ECG error This determines the error types for which the error object of each group makes an error status available This sets the time it should take to dim from 0 to 100 on receiving a dim telegram dimming speed Minimum value for dimming 0 5 10 15 20 25 30 This sets the minimum dimming value The setting 0 means that the dimmer can also be used to switch off the light The light can always be switched on using the dimmer Maximum value for dimming 50 55 60 continued in steps of 5 90 95 100 This sets the maximum dimming value Behaviour when receiving on Accept value immediately Dim to the value This determines whether to apply the switch ON value immediately or whether
20. er Darker Dim ECG1 4 bit CWT Value Set Value ECG 1 1Byte CWT By using objects 243 and 244 the signal of the potential free pushbutton can also be made available to the KNX The pushbutton function is set on the device itself via the operating menu see Operating and Assembly Manual It is important to remember that even when the pushbutton is configured as a dim button for Dali groups only the switch object short key press is available for the KNX If the parameters of the pushbutton are set to call up a Dali scene the corresponding object has no function Using this object the lamp controlled by ECG1 can be switched dimmed or set to a lighting value depending on parameters individually and independent of belonging to a group Obj Function Object name Type Flags 243 On Off Switch Input 1 1 Bit CRWT Attention Inconsistency between the actual set lighting value of a lamp and the status value of the group can occur when both individual control and group assignment of ECGs are used We therefore recommend that when using individual control you do not assign the corresponding ECG to a group or use it via group control This is the only way to avoid erroneous status reports Like object 112 for ECG 1 objects 113 to 175 are used for ECGs 2 to 64 The DaliControl SC64IP offers the possibility to make the error status of each connected ECG available individually via one comm
21. inal value when the object is received can be set in the parameters The dimming time can be set independently of the time on receipt of a dim telegram 1 Brighter Darker Dimming group 1 4 bit CWT The lamps assigned to DALI group 1 are dimmed up or down using this object The dimming time required to dim from 0 to 100 can be set in the parameters 2 Value Value group 1 1 byte CWT The lamps assigned to DALI group 1 are set to a brightness value using this object Whether the value is accepted immediately or dimmed to the final value when the object is received can be set in the parameters The dimming time can be set independently of the time on receipt of a dim telegram 3 On Off Status group 1 1 bit CRT Value Status group 1 1 byte CRT The status of the lamps assigned to DALI group 1 can be made available using this object Whether a 1 bit status On Off or a 1 byte value status 0 100 is transmitted can be set in the parameters The object type changes depending on the parameter settings The requirement for sending the object can be adjusted Attention When parameters are set as value status the value during the dimming process is sent immediately on modification This results in an in increased burden on the bus during dimming 4 Failure Error status group 1 bit CRT 1 Application description 7305 Dali Control This obje
22. ing di rectly on the devices serves only to quickly chan ge individual parameters later It should be noted that each ETS download overwrites settings which have been made on the device GROUP 01 Retrieve the individual groups using PARAMETER the SCROLL key First display row Number of the selected group Long actuation of the Prg Set key Switches to the programming mode The fol lowing parameters can be modified directly on the device GROUP 12 Starting value ON VALUE 100 0 to 100 in 5 step width GROUP 12 Minimum dimming value MIN DIM 0 0 to 40 in 5 step width GROUP 12 Maximum dimming value MAX DIM 100 50 to 100 in 5 step width GROUP 12 Dimming time for dimming from DIM TIME 10s 0 100 5sto60s In programming mode the selected parameter can be modified by briefly actuating the SCROLL key Press the Prg Set key The set value is saved and the programming mode is automatically activated for the next parameter of this group e g if only the maximum dimming value parameter is to be modi fied the starting value and the minimum dimming value must be cycled through first menu level 2 Press ESC key or automatically after approx 30 s Returns to the level above SCENE ASSIGNMENT submenu level 2 and 3 Press the Prg Set key Switches from the SCENE ASSIGNMENT main menu to the submenu Within this menu the respective DALI groups can be assi gned to single or up to 16 possible
23. ing from 0 to 100 on receiving an On Off or Set value telegram if the parameter was set to Dim to value Type of status object Switch status 1 bit Value status 0 100 2008 Merten GmbH amp Co KG The function of the page Error Values Groups 9 16 is analogue to the one described on the previous page In addition to group control the DaliControl SC64IP also offers individual control of ECGs Whether individual control is possible as well as the type of individual control can be set on a separate page Application description 7305 Dali Control Page ECG individual control ECG individual control Parameters Settings Common control by DALI No broadcast feasible Yes The user can set here whether complete control of all ECGs should be possible If the an dimming time max dim val swer is yes the group 1 parameters ue etc are applied to all ECGs ECG individual control feasible A Detectable failure types No failure status X I Light status of groups can be wrong if individual control is choosen ECG1 No individual control Ss ECG 2 No individual control z ECG 3 No individual control d 4 1 ECG 62 No individual control z ECG 63 No individual control hd ECG 64 No individual control hal M Cancel Default Info Help Parameters Settings ECG individual control No feasible Yes The user can set here whether
24. ing website can be accessed via a web browser e g Microsoft Internet Explorer or Mozilla Fire fox For this purpose the IP address URL set in the ETS or automatically assigned by the DHCP server is simply called up in the browser Please note that the complete URL is made up of the IP address and header record http Thus for example http 192 168 1 07 must be entered to launch the site bute The website will be displayed in the browser 0000 fia rafio fT Date Bearbiften Ayficht ct gea o rer IX a a a a a e3 64 Device Id 15 15 255 Fertig o The higher level commissioning functions can then be performed via the header Meaning and function of the icons shown in the header Update This function updates the electronic ballast assign ments displayed In particular it should particularly be used if additional assignment changes have been performed manually on the device or using the software tool New installation This button starts new installation of the connected DALI segment Reinstallation This button starts reinstallation within the DALI seg ment In doing so ballasts which are no longer present will be deleted and new devices will be add ed Abort Any procedures which have already been started will be cancelled by this function Broadcast on off All ECGs luminaires can be switched
25. merten KNX DALI gateway REG K 1 16 64 64 Operating instructions o o o oo Art no 680191 For your safety A DANGER Risk of fatal injury from electrical current All work carried out on the unit may only be per formed by skilled electricians Observe the regu lations valid in the country of use as well as the valid KNX guidelines Getting to know the Gateway The KNX DALI gateway REG K 1 16 64 64 referred to below as the gateway connects the cross function KNX bus with the DALI bus designed exclusively for lighting control Luminaires with cost effective digital DALI elec tronic ballasts can therefore be integrated into a KNX complete system in the form of a subsystem and operat ed by a wide range of available KNX devices The gateway serves as the DALI master and power sup ply for the connected electronic ballasts Up to a maxi mum of 64 electronic ballasts in a total of 16 groups can be switched dimmed or set to a defined value The cur rent light value or the error status of each group lumi naire or electronic ballast errors within the group can be made available for a visualisation via KNX In addition the 64 electronic ballasts can be individually activated via KNX or via KNX group addresses In the case of indi vidual activation one programmable object is available per electronic ballast One error status is available for each electronic ballast Lamps and electro
26. n the set lighting value and the displayed status This problem is inherent in the Dali system A failure of the Gateway power supply always leads to a complete re set of the device The behaviour after a device re set is also determined by the parameter Behaviour on return of bus voltage Please remember that if Switch to last value is set the device is switched off as the internal memory is deleted during the device re set Please also remember another characteristic in the event of simultaneous return of Gateway power supply and ECG voltage Principally all DALI ECGs are switched on as soon as the power is switched on If the parameter for behaviour on return of bus voltage is set to Switch Off the switch off command needs ca 1 second to take effect after the system is re started On return of the voltage the ECGs will have initially been switched on automatically and only then switched off As a result the lamps will be lit briefly when the respective parameters are set This behaviour is also system inherent and cannot be prevented 2008 Merten GmbH amp Co KG 10
27. nic ballast errors can thus be precise ly located Total activation of all connected electronic bal lasts via broadcast without requiring DALI commissioning can also be carried out via three ob jects Additionally up to 16 lightscenes can be pro grammed and called up from the individual groups Scene activation is effected via a 1 byte object DALI commissioning and configuration can be per formed as follows 1 via the device 2 via a software tool free of charge 3 via the integrated web server 4 via a portable web panel or a PDA 5 via two binary inputs e g for connecting push buttons to the device building site operation Suitable for installation on DIN rails EN 50022 The bus is connected using a bus terminal A data rail is not required Network DALI and push button lines are connected us ing screw terminals on the device Connections displays and operating elements The appliance connections and the learning button and programming LED elements required for KNX commis sioning can only be accessed in the distribution board when the cover is removed The keys required for DALI commissioning and parame terisation SCROLL Prg Set ESC can only be operated when the distribution board s cover is closed Similarly the 2 row display and the control LEDs PWR and ERR can only be seen when the distribution board s cover is closed 0 PE LN T OO Ethernet
28. nnected to input B1 can be adjusted DIM TOGGLE Retrieve the individual functions using INPUT B1 the SCROLL key First display row Dis plays the selected function DIM TOGGLE The following functions can be adjust CHANNEL ed ALL ON switch on by pushing button OFF switch off by pushing button TOGGLE toggle by pushing button DIM ON brief push button action on long push button action dim with stop telegram DIM OFF brief push button action off long push button action dim with stop telegram DIM TOGGLE brief push button action toggle long push button action dim ming with one button SCENE Retrieve scene DIM TOGGLE Long actuation of the Prg Set key CHANNEL 07 Switches to the programming mode Use the SCROLL key to select the chan nel or scene which the selected function is to be linked to Press ESC key or automatically after approx 30 s Returns to the level above D6801 581 01 07 08 FUNCTION INPUT B2 submenu level 2 and 3 Press the Prg Set key Activates the submenu SCENE Retrieve the individual functions using the INPUT B2 SCROLL key First display row Displays the selected function SCENE The following functions can be adjusted SCENE 03 ON switch on by pushing button OFF switch off by pushing button TOGGLE toggle by pushing button DIM ON brief push button action on long push button action dim up with stop telegram DIM OFF brief push button action off long
29. no error has occurred The value 1 means that an error has occurred in the segment 246 Error Error status DALI 1 Bit CRT Bus This object is used to inform about the error status Dali short circuit The value 0 means that no error has occurred The value 1 means that a Dali short circuit has occurred Like object 176 for ECG 1 objects 177 to 239 are used for ECGs 2 to 64 In addition to group and individual control the application can also be used for the complete control of all ECGs Communication in this case is via DALI Broadcast telegrams and no new installation of the DALI is required For complete control use objects 240 to 242 247 Error Error status total 1 Bit CRT Lamp error This object is used to inform about any lamp error status in the Dali segment The value 0 means that no error has occurred The value 1 means that an error has occurred in at least one lamp in the segment 248 Error Error status total 1 Bit CRT ECG error Obj Function Object name Type Flags 240 On Off Switch Broadcast 1 bit CWT This object is used to inform about any ECG error status in the Dali segment The value 0 means that no error has occurred The value 1 means that an error has occurred in at least one ECG in the segment This object is used to switch all lamps that are connected to the Dali segment to the set Switch ON or OFF
30. played deleted devices new devices from left to right Press ESC key or automatically after approx 30 s Returns to the level above GROUP ASSIGNMENT submenu level 2 and 3 Press the Prg Set key Switches from the GROUP ASSIGNMENT main menu to the submenu Within this menu the individual ECGs found during the search process can be assigned to the 16 DALI groups or existing assignments can be altered GROUP AS Retrieve the different ECGs found using SIGNMENT the SCROLL key ECG no 12 First display row Number of the select GROUP ed ECG If an ECG is selected the con nected luminaire flashes This enables the programer to determine which lumi naire is assigned to the corresponding number ECG no 12 Long actuation of the Prg Set key GROUP 1 Switches to the programming mode Retrieve the setting of the group which the ECG is to be assigned to using the SCROLL button Press the Prg Set key Setting is confirmed and saved During new installation this process must be performed once for all ECGs found Press ESC key or automatically after approx 30 s Returns to the level above GROUP PARAMETER submenu level 2 and 3 Press the Prg Set key Switches from the GROUP PARAMETER main menu to the submenu Within this menu the individual parameters for each group can be set e Ingeneral the group parameters should be set in 1 the ETS during KNX commissioning Sett
31. push button action dim down with stop telegram DIM TOGGLE brief push button action toggle long push button action dim ming with one button SCENE Retrieve scene SCENE Long actuation of the Prg Set key Switch SCENE 03 es to the programming mode Use the SCROLL key to select the channel or scene which the selected function is to be linked to Press ESC key or automatically after approx 30 s Returns to the level above DALI commissioning using the device keys and the display After the wiring has been completed according to the connection diagram above the DALI line can be com missioned Commissioning can be carried out by an electrician independently of KNX commissioning The red ERR LED lights up to signal an error provided no KNX is connected DALI commissioning can still be per formed For initial operation the DALI line must first be searched for connected electronic ballasts Searching is performed within the NEW INSTALLATION menu item cf Operation and menu structure After all of the con nected devices have been found indicated by an ESC after the number of found devices shown in the display this menu item can be exited Subsequently the devices found must be assigned to the individual DALI groups Assignment is performed under the GROUP ASSIGN MENT menu item cf Operation and menu structure Basic installation is completed when all electronic bal lasts have been assigned to the respective
32. to dim up to it when a 1 telegram is received Behaviour when receiving off Accept value immediately Dim to the value If on the General Page the parameter Lighting value in the event of DALI and KNX errors is set to Setting per group two additional pages will appear on which the error values can be selected individually Page Failure values group 1 8 Failure value group 1 8 Light value on DALI and KNX failure This determines whether to apply the switch OFF value immediately or whether to dim down to it when a 0 telegram is received Value group 1 100 x Value group 2 7 Value group 3 fi 00 x Value group 4 100 X Value group 5 100 bd Value group 6 100 hd Value group 7 100 X Value group 8 100 bd Cancel Default nfa Help Parameters Settings Value Group 1 No change se 0 Value Group 8 5 10 continued in steps of 5 90 95 100 The user can set here which lighting value will be set in the corresponding group in the event of a DALI or KNX error Behaviour when receiving Accept value immediately value Dim to the value This determines whether to apply the light value immediately or whether to dim up or down to it when a 1 Byte telegram is received Dimming time for On Off 2 5 seconds Set Value 5 seconds 10 seconds 15 seconds 20 seconds 30 seconds 1 minute 30 minutes 1 hour This sets the time for dimm
33. ue has been activated in the event of bus voltage failure this parameter setting will cause the lighting values to be automatically re set to the values before the failure once the voltage returns Please remember that the correct last value can only be set if during the bus voltage failure no other power failure of the Gateway has occurred In the event of a Gateway power failure the lights will be switched off on return of the voltage if the parameter was set to Switch to last value Value 0 If the parameter Switch Off is set the lamps will be switched off in any case A Dali error can occur in the event of a short circuit or when the DALI line is interrupted If an error occurs the error lighting value that is saved in the ECGs Setting via lighting value in the event of DALI and KNX error will be set If the parameter for the behaviour after the occurrence of a DALI error is set to Switch to last value or Switch Off a safe and correct lamp setting can only be ensured if the error has occurred for at least 1 2 minutes depending on the number of connected ECGs In order for the Gateway to be able to recognise the error all ECGs are contacted cyclically Depending on the number this process can take up to 2 minutes It is therefore possible that in the event of a very brief error the Gateway will not yet have detected the error and will not perform the desired function In this case inconsistencies can occur betwee
34. unication object on the KNX Bus Objects 176 to 239 are used for this purpose A switch signal is provided via this object which depends on the set pushbutton function of the potential free input 1 244 On Off Switch Input 2 1 Bit CRWT A switch signal is provided via this object which depends on the set pushbutton function of the potential free input 2 Objects 245 to 248 are used to inform about the status of errors within the entire Dali segment Objects are sent whenever there is a change However they can also be requested The following error objects for the entire segment are available Obj Function Object name Type Flags Obj Function Object name Type Flags 176 Failure Error status ECG1 1 bit CRT 1 byte CRT 245 Error Error status all errors 1 Bit CRT This object is used to inform about the error status of ECG 1 Whether the object is set only for a lamp malfunction only for an ECG malfunction or for both types can be set in the parameters If an error has occurred the 1 bit object has the value 1 if no error has occurred it has the value 0 An error status can also still be configured as a 1Byte object In this case the object values are as follows No error Lamp error 1 ECG error 2 This object is used to inform about the error status of the Dali segment independent of the error type The value 0 means that
35. value via DALI Broadcast telegrams For Broadcast switching always use the parameters of group 1 2008 Merten GmbH amp Co KG Object 252 is required to program and call up set lighting scenes Please remember that individual Dali groups are assigned to the different scenes on the device itself by using the operating menu see Operating and Assembly Manual Application description 7305 Dali Control Attention Lighting values of scenes are saved on the ECGs during programming Please remember therefore to ensure that all ECGs are connected and ready for use during programming If a scene is programmed and the required ECG is not connected there can be inconsistencies between the actual set value and the status reported by the Gateway This determines which lighting condition is to be set on return following a DALI error short circuit or ECG error Sending condition failure Sending on request only object Sending on change Obj Function Object name Type Flags This sets the send condition for the error status of the DALI groups 5 communication object of each group The entire error statistics objects no 245 to 248 are always sent when a change occurs 252 Invoke save scenes Scenes 1 16 1 Byte CW This object is used to invoke scenes 1 16 on receipt of a telegram with values 0 15 If the highest significant bit is also set meaning a value from 128 to
36. voltage must be ensured For this purpo se the cores of the KNX cable must additionally be insu lated with the enclosed shrink hose When connection is complete and the supply voltage is activated the product designation and firmware version will be shown in the display Status LED PWR LED flashes Device is ready for operation ERR LED lights up Commissioning without KNX ERR LED lights up Possible short circuit despite KNX voltage within the DALI segment Check the DALI segment s wir ing The pin assignment shown on the housing must be observed pio Operating and menue structure The connected DALI segment can be commissioned and DALI parameters can be set and altered entirely us ing the three operator buttons SCROLL Set PRG ESC and the 2x12 row display on the front face of the device The operation concept is menu based Up to two lower levels can be selected for each menu item The respec tive menu item is shown in the display Navigation within the menu is as follows SCROLL key Short push button action activates the next menu item within a level Prg Set key Short push button action activates the re spective sub level ESC key Short push button action to leave the selected level and return to the level above Main menu level 1 The main menu level 1 has the following structure DALI Displays the product designation and CONTROL firmware version Display language SC64
37. ytes 2 4 are analogue The settings of the subnet mask must correspond to the settings of the commissioning PC IP standard gateway Byte 1 0 0 255 If the address is assigned manually the 1 Byte of the IP Standard Gateway can be set here The settings of Bytes 2 4 are analogue A Standard G ateway is only required for connection via a Router e g Internet Normally no settings are required Application description 7305 Dali Control Attention Please agree the IP settings with the network administrator If no DHCP service is available on the network the IP settings need to be performed manually It is therefore important to ensure that the selected settings are admissible on the network Behaviour in the event of voltage failure and voltage return The different scenarios for voltage failure and voltage return can be set via the parameters on the General Page The behaviour of the connected lamps can be set via the parameters Behaviour in the event of KNX bus voltage failure and return of KNX bus voltage If the setting No change is selected the lighting value that was set last is retained If the setting Switch to error value is selected the value set on the lamp is the one that was set under Lighting value in the event of DALI or KNX errors The setting Switch to last value is only possible for the return of KNX bus voltage If the error val