1. 3 Live Brown Neutral Blue a Install the DS700RF docking base on the ceiling no closer than 300mm from the nearest light fitting Always refer to your Smoke Heat alarm manual for positioning and installation guidance b Bring wires through either the YT2 trunking knockout on the side of the base or the knockout in the base itself and install the wires into the connector terminals marked L live Neutral N and Earth E See Fig 3 c Install ALL bases that will be required in the system in their appropriate positions IMPORTANT The circuit used to power the alarm must be a constant 230V AC 50Hz voltage circuit that cannot be turned off by a switch BS5839 Part 6 states that For mains powered alarms each with an integral standby supply Grade D the mains electricity supply should take the form of either 1 An independent circuit at the dwelling s main circuit board in which case no other electrical equipment should be connected to this circuit other than a dedicated monitoring device installed to indicate failure of the mains electricity supply to the alarms or 2 A separately electrically protected regularly used local lighting circuit For mains powered alarms with no standby supply Grade E the mains electricity supply may only take the form of an independent circuit as per 1 above If it is necessary to use an RCD for protection it should operate independently of any RCD protection for circuits s
2. THE PROFESSIONAL STANDARD RF INTERLINK BASE DS700RF IMPORTANT Please read this manual before installation If installing the alarm for others please leave a copy for the end user ce Oe 5 Year Guarantee CONTENTS 1 Introduction 2 Quick installation guide 3 Installation guide 3 1 DS7OORF installation and set up 3 2 Learning in a new system 3 3 Learning in an additional unit to an existing DS700RF system Operating conditions Trouble shooting Disposal Limited guarantee On Oo Technical specification 1 INTRODUCTION This DS7OORF RF interlink base is designed to be used in conjunction with any BRK mains operated Smoke and Heat alarms in the 670 650 680 series ONLY Interlinked Smoke and Heat alarms which utilise RF interlink technology have the benefit of being able to be used in a Grade D or E alarm system without the need for hardwiring connection between each alarm in the system This is particularly useful when refurbishing or extending a property and allows the Grade D or E system to be wired by way of the un switched part of a local lighting circuit or independent circuits at the dwelling s main distribution board ref BS5839 Part 6 The DS7OORF utilises a unique system which provides in excess of 16 million separate ID codes one of which is automatically selected when the system is learnt in on installation The high number of alternative codes helps prevent individual systems i
3. e batteries and other accessories must not be disposed of as unsorted municipal waste and must be collected separately at the end of the product s life Contact your local authority for HM information about collection points in your area 16 7 LIMITED GUARANTEE BRK the BRK Brands Europe Ltd products as distributed by Sprue Safety Products Ltd the Distributor are guaranteed by the Distributor to be free from defects in materials and workmanship under normal use and service for a period of five years from the date of purchase Neither the Distributor nor BRK Brands Europe Ltd make any other express guarantees for this product No agent representative dealer or employee from the Distributor or BRK Brands Europe Ltd has the authority to increase or alter the obligations or limitations of the Guarantee The Distributor s obligation of this guarantee shall be limited to the repair or replacement of any part of the DS700RF base which is found to be defective in materials or workmanship under normal use and service during the five year period commencing from date of purchase The Distributor shall not be obligated to repair or replace DS700RF bases which are found to be in need of repair because of damage unreasonable use modifications or alterations occurring after the date of purchase This warranty does not affect a customer s statutory rights in any way How to obtain guarantee service If service is required re
4. isolate the mains power once again g Install the new Smoke Heat alarm onto the DS700RF as outlined in the alarm owner s manual See Fig 2 h RESTORE MAINS POWER TO ALL ALARMS Ensure all Smoke Heat alarms in the system display a green power light and red operating light as per the user s manuals i Press the test button on the new alarm in the system to ensure that 1 the alarm sounds and 2 it links with the existing alarms in the system NOTE The amber LED will stop flashing 5 minutes after the learn in process has completed Test i should be carried out regardless of this j Installation is now complete NOTE If after a period 15 minutes the unit has failed to learn in it will sound a double beep for a period of 5 minutes 12 4 OPERATING CONDITIONS Amber operating LED Located on the side of the DS7OORF this LED will remain off during normal working conditions Any fault with the DS700RF will be indicated by a flash of the LED and a single chirp Low battery warning When a low battery condition on the DS7OORF occurs the internal buzzer will chirp along with a single flash of the amber LED once every minute for a period of at least 30 days IMPORTANT The DS7OORF has a sealed in battery and circuitry therefore should you encounter a fault warning the DS700RF will need to be replaced As with all work involving electrical wiring always consult a qualified electrician 5 TROUBLE SHOOTING For q
5. n separate properties from interfering with one another and resulting in unwanted nuisance alarms Utilising the DS700RF allows up to 50 alarms to be interlinked in each system 2 QUICK INSTALLATION GUIDE a Install each DS700RF base in an appropriate position at least 300mm from the nearest light fitting ref Smoke Heat alarm instructions and connect to the nearest mains circuit DO NOT SWITCH ON MAINS POWER b Learn in each base by pressing the button See Fig 1 using a small screwdriver c Plug in the Smoke and Heat alarms as appropriate onto each base See Fig 2 Switch on mains power d Ensure that at least 2 minutes has elapsed before pressing the test button on each alarm When the test button on one of the alarms is pressed all of the other alarms in the system should sound within 10 seconds Fig 2 Fig 1 Learn in button 3 INSTALLATION GUIDE Please consult the Smoke Heat alarm owner s manual for details of where and where not to site your Smoke and Heat alarms WARNING Wiring should be installed by a qualified electrician in accordance with BS7671 Permanent connection to the fixed wiring of the building should be made in a suitable junction box This alarm must not be exposed to dripping or splashing Connect the alarm as late as possible in an installation particularly in new build to avoid contamination Remove the dust cover before applying power 3 1 DS700RF INSTALLATION AND SETUP Fig
6. turn the product to your supplier The Distributor makes no guarantee express or implied written or oral including that of merchantability or fitness for any particular purpose with respect to battery In the event of a problem with your DS700RF base or you have any questions concerning its use care and service please consult this manual If you require any further help or clarification please write to Sprue Safety Products Ltd Unit 6 Carter Court Davy Way Waterwells Business Park Quedgeley Gloucester GL2 2DE United Kingdom or phone our Helpline on 44 0 1452 887 570 www brkelectronics eu Please note that specifications may be subject to change 18 8 TECHNICAL SPECIFICATION Power Independent 10 year battery for life lithium cell Temperature operating 0 C 40 C Humidity 0 95 non condensing Warning Visual and audible low battery warning Radio Frequency 868MHz Wireless Range Minimum 150m open air Dimensions 140mm D x 30mm H Approvals Independently tested and compliant with EMC Electrical Safety and Radio Regulations to include requirements of the R amp TTE Directive EN300220 v2 3 2 2010 02 EN301489 1 EN301489 3 EN50130 4 EN60065 BRK Sprue Safety Products Ltd 6 Carter Court Davy Way Waterwells Business Park A Sprue Safety Products Brand O Gloucester GL2 2DE UK GNTaB OS
7. ueries on Smoke Heat alarm related issues refer to the specific owner s manual Fault Action When press the learn in button the amber LED on the base does not flash Wait for at least 2 minutes to allow the system to respond If there is no response within 5 minutes ensure unit is correctly positioned Attempt to learn in again by pressing the button When press the test button on the Smoke Heat alarm no other alarms sound 14 Ensure all alarms are powered up green and red LEDS indicating as per Smoke Heat alarm owners manual Repeat learn in process in section 3 2 or 3 3 as appropriate When press the test button on the Smoke Heat alarm some alarms sound and others do not The unit gives an occasional single chirp but there is no amber flash The amber LED flashes and base chirps Base emits a double beep Remove the alarms and repeat learn in process in the section 3 2 or 3 3 as appropriate This indicates a problem with the Smoke Heat alarm Refer to the Smoke Heat alarm owner s manual Low battery Replace base Base is not learnt in correctly Repeat the learn in process in section 3 2 amp 3 3 If you have any questions about the operation of your Smoke Heat alarms or DS70ORF FF interlink base please contact the Technical Support line on 44 0 1452 887570 or email us via the link on our website www brkelectronics eu 6 DISPOSAL This product th
8. upplying sockets or portable equipment All interconnected alarms should be installed on a single final circuit 3 2 LEARNING IN A NEW SYSTEM Learn in button Amber LED NOTE The system must be learnt in before the alarms are installed on the base a Locate the push button on an installed DS700RF and press briefly using a small screwdriver See Fig 1 The amber LED will illuminate for 3 seconds to indicate that it is activated See Fig 4 The buzzer will also give an audible chirp to show that it is working b Repeat this process on every remaining DS700RF required to be in the system As each alarm is successfully learnt in the amber LED will start to flash once every 3 seconds NOTE The DS700RF allows for a period of 15 minutes during which all bases need to be learnt in c Once all bases are learnt in install Smoke Heat alarms onto each DS7OORF as outlined in the owner s manual See Fig 2 d Turn on mains power e Ensure all Smoke Heat alarms in the system display a green power light and red operating light as per the Smoke Heat alarm manual f Ensure the amber LED on every DS700RF flashes once every three seconds g Press the test button on each alarm in the system in turn and ensure 1 the alarm sounds and 2 it links with every other alarm in the system h Installation is now complete NOTE If all DS700RF bases have been learnt in before 15 minutes has elapsed pressing the test b
9. utton on any installed Smoke Heat alarm will cause the learn in procedure to finish early This will also test every alarm in the system The amber LED on every DS700RF will flash twice every 3 seconds for a period of 5 minutes after the learn in process has completed If after a period of 15 minutes a unit has failed to learn in it will sound a double beep for a period of 5 minutes 3 3 LEARNING IN AN ADDITIONAL UNIT TO AN EXISTING DS700RF SYSTEM If you require an additional alarm to be added to an existing DS700RF system 10 a Following section 3 1 install the new DS7OORF in the required location b Restore mains power to all the installed alarms and the new DS7OORF c Locate the push button on the new DS7OORF and press briefly using a small screwdriver The amber LED will illuminate for 3 seconds to indicate it has been activated The buzzer will also give an audible chirp to show that it is working NOTE If the existing Smoke Heat alarms in the property are mains only powered it is important that they remain connected with the mains power on during step d d Press the test button on one of the alarms in the existing system long enough to trigger the other alarm s in the system This should be carried out within 5 minutes e Wait until the amber LED on the new DS7OORF flashes twice every 3 seconds This indicates that the learn in process has completed f Before you install the new Smoke Heat alarm
Download Pdf Manuals
Related Search
Manual manual manual forklift manualslib manual hoist manual pallet jack manual car manual timesheet manual transmission manuale digitale manual winch manually meaning manual wheelchair manual arts high school manually update your device drivers windows manual labor manual definition manual for courts martial manual muscle testing manual muscle testing grades manually register devices with autopilot manual keyboard manual blood pressure cuff manualidades manual lawn mower manual transfer switch