1.     Ouick Start    Installation Checklist  O 24 VAC power supplied to the ECO3  Fuses fitted and in place  Force Save test is successful  Compressor runs correctly with ECO3 wired in    Customer is briefed on ECO3 indicator lights and  knows how to perform a Manual Bypass    Customer is given the ECO3 User Manual and  contact details for technical support    Customer is happy with the installation       SMARTCOOL          PDF Handouts       e Quick installation guide  e Full installation  operation and trouble shooting manual  e On site user manual    Fa   gt  SS     bri  TAA    u 5    Gum uu Gw fee            i       Post Installation    Performance verification    SMARTCODL          The Smartcool Display       e Validation of energy saving measures can be hard    e Smartcool products have a simple display to show status and  performance    Status indicators  Hours Run   Hours Saved   Hours Bypassed    Saved hours  Run hours   Save hours   Automatic override hours      Saved      kWh Saved   Saved hours x kW motor size          s y    i e     erm AS Us agg       Saving Calculator       Visit the ECO3 web site for an online  savings calculator    Ss MART n a wt Me Home The ECO3 Distribution About Smartcool Contact Us    Savings Calculator    h tt D   www e S m a rtco O   eco 3  CO m The ECO3 logs demand from the compressor right on its large display SMART  ECO3 Savings Calculator    screen  You can scroll through the data using the Enter button     For a detailed explanation 
2.    Todays Agenda    e Overview about Smartcool      How our products work       Installation of an ECO3   e Post installation validation      View the actual installation  e Lunch   e Hands on ECO3 demo unit  e Q amp A    SMARTCODL          About Smartcool    SMARTCODL          Smartcool Systems Inc       e Founded over 20 years ago by an Australian refrigeration engineer  e Purchased by a team of Canadian investors in 2006        Developed as a an energy efficiency solution for commercial and  industrial HVAC R systems    e Smartcool s energy efficiency solutions have been adopted by some of  the world s most prominent companies across a range of industries    e Over 30 000 installations worldwide       SMARTCOOL     What Is Smartcool       e Smartcool is the developer   manufacturer   distributor of a unique  hardware   software control solution    e Reduces the electricity usage  kWh  of air conditioning  refrigeration  and heat pump compressors by improving the performance of the  compressors while maintaining temperature and humidity control    e Smartcool is a modular retrofit technology  can be applied in air  conditioning  refrigeration and heat pumps systems    e Risk free solutions compatible with all existing equipment and controls    e Average payback period for customers is 18 to 36 months       gt   gt   ex   TM  f ca f       a e Lo  un    Our Products       ECO3            SMART    SMARTCOOL       The ECO3              Suitable for single and twin compressor  s
3.  far the most  amount of energy is the electric motor  of the compressor     Electrical Load        Often this one element can consume up  to 7090 of the total energy used by the  refrigeration plant     e Smartcool s energy saving controls  focuses on this one item       E The Compressor    Everything Else  SMARTCOUOOL      Run Time           As a control solution  the aim of Smartcool is to reduce the amount of  time the compressor needs to run for  over and above that ofthe  existing control strategy     e When a compressor is not running it doesn t use any energy     e You could just switch the compressor off and save energy  but the  downside would be an impact on the end temperatures reguired     e Smartcool has a method of reducing the run time of a compressor  AND still maintain the reguired temperatures       We don t use    magic    but rely on science and the physical  characteristics of refrigerant  These principals are known by every  cooling engineer     SMARTCOOL          The Science           n simple terms  the compressor is just a pump  pumping an amount  of refrigerant gas around the cooling system     e Like a car engine the compressor has a fixed volumetric compression  chamber         However  at different refrigerant temperatures  and pressures  the  capacity of the compressor changes     SMARTCOOL       Temperature  amp  Pressure    v Capacity       e At higher refrigerant temperatures  and pressures   when the gas is more  dense  the refrigerant molec
4. already  wire into the ECO3 Remove the small green terminal connector marked 24  channel terminal connector  An ECO3 Dual will have two VAC and wire in the power supply inputs    channels to wire in     Remove the wire casing to access the connector blocks     Remove the green terminal connector from the base of the Check that all the wiring connections are secure   ECO3 and wire into the IN  NO  NC and CMN points  Make a  note of which coloured wire connects to each point        SMARTCOOL       Installation   Quick Start    Step 5   Step 6  Confirm that the wiring is running smoothly out of the Mount the ECO3 on the backplate by sliding it up until it  wiring casing  clicks onto the metal bracket     Close the base of the ECO3     Screw the wiring casing base into the main body of the  ECOS        SMARTCODL       Installation   Quick Start    Step 7 Step 8  Run the wiring from the ECO3 to where you will wire into Install the correctly rated fuse and associated fuse carrier    the control circuit  for circuit protection     Use zap straps  cable ties  or other suitable means  like in  the image below on the left  to make sure the wiring is  neat and tidy     ASIN the example in the lower right image  you may need  to drill inte a control panel  using the appropriate rubber  seals to maintain the integrity of the panel and to protect  the cabling        SMARTCOOL       Installation     Ouick Start    Step 9  Fit the appropriate terminals onto the wiring from the  ECO3  ensurin
5. art    Recommended Pre Installation Steps  ECO3 Before setting out to complete any ECO3 installation  you          should be familiar with the detailed content of the ECO3  Q Ul ck In sta lla tion G ul d e Installation Manual  In addition  Smartcool recommends    you take the following steps prior to installation     1  Know what power supply is available at the installation  site  understand the control circuit of the system and  determine where you will be mounting the ECO3   Collect the necessary peripheral items    Remove the wiring cover on the ECO3    Connect the wiring to the channel s  inputs and to the  24 VAC input    Close the wiring cover and fasten with the supplied  screws     Pre wiring the ECO3 will make the installation itself much  easier  Alternatively you can do this on site by following  the steps in this guide        SMARTCOOL          Installation   Quick Start    Step 1   Decide where you will mount the ECO3 and how much  wire is needed to reach from the ECO3 to where you will  wire into the control circuit     The ECO3 needs to be mounted on a flat surface  If  installed outdoors  it needs additional protection correctly  rated to the environment     SMARTCOOL       Step 2  Mount the ECO3 backplate  Ifyou need a transformer for  the power supply  mount this as well     Make sure that you are mounting the backplate straight   and using the appropriate fixtures for the surface        Installation   Quick Start    Step 3 Step 4   If you have not done so 
6. g that you are referencing the correct wires     Refer to the ECO3 Installation Manual for further detail   wiring diagrams and any aditional wiring that may be  necessary for your specific installation     SMARTCOOL       Step 10  You are now ready to connect the power supply to the  ECO3     Ensure that the system is free from voltage before you wire  in     Ideally  you will wait until the compressor cycles off  then  turn off the master power supply rather than cutting the  compressor off mid cycle     On the power supply input to the ECO3  wire in a circuit  breaker or appropriate fuse        Installation   Quick Start    Step 11  Ensure all your wiring is correct before turning the master  power supply to the system back on     Start the ECO3 in Force Save  also known as false save   mode to check that you have installed the unit correctly   To do this  press and hold down the ENTER button as you  turn the master power supply back on  The display will  read    FS     The compressor should stop for the duration of the Force  Save  If it does not  refer to the ECO3 Installation Manual for  troubleshooting steps     SMARTCOOL       Step 12   Provided the Force Save test is successful  you can allow it  to exit the Save cycle on its own  The display will change  to    ON     The installation is now complete  Make sure you leave the  ECO3 User Manual and Installation Sticker with the ECO3  unit for easy reference  Also leave your contact details on  site        Installation 
7. of what the data means  watch our short Want to know how much your ECO3 is saving you   You ll need the following information   video demonstration     1  On your ECO3  use the Enter button to cycle through the Run  Save   Bypass and Override hours  Write down the information from the screen   Using only this information  you will be able to see the percentage of  compressor run time the ECO3 is saving you  See Step 2 for additional  results     Note  If you have an ECO3 Dual  you need to cycle  through the hours for both Channel 1 and Channel 2     2  If you want to calculate your estimated energy savings as kWh as well  as a percentage of hours  write down the RLA  amperage   voltage and  number of phases from your compressor face plate or label        Unit ID         Choose your Model        SMART OO     Help using this calculator is available by emailing info smartcooLnet        SMARTCOC    PDF Handouts          ECO3    Proof of savings    SMARTCOOL          i          O     XL       O   C            
8. ules are all more closely packed   the  compressor is able to    pump    more refrigerant     we say it has a greater     mass flow    rate        At lower refrigerant temperatures  when the gas is less dense  the  compressor is able to    pump    less refrigerant     we say it has a lower    mass  flow  rate     SMARTCOOL       What Smartcool Does          The Smartcool control solution aims to dynamically adjust the    cut in     and    cut out    point of the compressor  By doing this it can effect the    suction pressure that the compressor is working at  increasing its  COP 2     e lf we can increase the amount of cooling being provided when the  compressor runs  to achieve the same amount of cooling as the  existing control we can run the compressor for less time and  therefore save energy    SMARTCOOL          Installation          The Smartcool is installed in series with the existing control solution    e It monitors the load of the plant and when the existing control is  demanding for cooling it can allow the compressor to run of it can  turn it off        Typical run time savings are between 15  and 25  equating to a  reduction in kWh consumption of similar levels       There will be no negative impact on the    end temperatures       SMARTCOOL          PDF Handouts       e Elevator Pitch Presentation      ECO3    FAQ    SMARTCOOL          i          Installation       i a  Sa NL rd rr      i    NI  BER  1  o     a e  Eb n    SMARTCODL       Installation   Quick St
9. ystems    e Refrigeration  Air Conditioning or Heat  Pumps    e  P64 Rated for outdoor installation    e Minimal technical knowledge needed  for installation    SMART        The ESM          e Modular systems provides total  flexibility   e Refrigeration  Air Conditioning       Single stage of multi stage compressors    e Turbo core  Centrifugal  Screw   Reciprocating  Scroll    e Remote Coms package available          Dynamic demand response available    cool    SE Y ni a CAST    Key Features           Reduces compressor run times through more efficient control      Average kWh savings    ECO3    15  to 25   ESM    10  to 20   e Interfaces with existing controls  does not replace them     e Provable savings  e Zero risk to current equipment or effect on manufacturer warranty  e Maintains temperature performance            MAL TM  Lan y Y     Con fe          AA  gt        Target Markets         Food Retail   e Fast Food Outlets      Coffee Shops   e Banks   e High Street Non Food Retail   e Data Centres   e Food Manufacturing   e Manufacturing Process Cooling      i 5      thas er ho muf Qa gi ny    Cold   Chilled Storage  Hotels   Hospitals   Large Office Buildings  Gyms    PDF Handouts       e Smartcool Corporate Brochure  e Product Brochure for ECO3   and ESM     e Some case studies    SMARTCOOL          i              o How Does It Work     Non Technical Explanation    SMARTCODL       The Compressor       e In any refrigeration system  the piece of  equipment that uses by
    