Home
        User guide - BaltGaz Group
         Contents
1.        0 5 m pipe    In case of possible appearance of condensation in the smoke exhauster pipe  a condenser tank 4 must be installed  before the boiler  see Scheme 6      The slope of the horizontal parts of the smoke exhauster pipe must be 3   towards the condenser tank  if there is one      9 2 1  Installation of separate pipes of smoke exhauster and air duct by means of transitional set KHG       714061510  10   7  AN    10  8  3  air inlet pipe 080 mm    mm  10   ventilator plug   4  condenser tank    7  Smoke exhauster adapting pipe  11   thermoinsulation    8  clip     User   s manual    Scheme 6  Installation of separate pipes of smoke exhauster and air duct by means of transitional set    The transitional set consists of details 7  8  9  see Scheme 6    The smoke exhauster adapting pipe 7 is installed to the  central orifice on the upper surface of the boiler and is fixed by clip 8    The boiler   s construction provides a possibility of installation of the air duct pipe 3  air inlet  both on the left and on  the right side from the smoke exhauster pipe     Technical staff manual    9 2 2  Installation of separate pipes of smoke exhauster and air duct by means of channel separator 8023 10 000  CAUTION  In order to install the channel separator 8023 10 000 onto the boiler you must have the following items   not included into the supply package      screw  self driving screw  Ph   4 8x60 DIN 7981     4 pcs      plain washer 5 3x10 DIN 125  GOST 11371      4 pcs      ri
2.    MARE iei     f         KKRRKKKR    xe    rT Ti hhh  UPLLLLA Ld dddd    rt    mee    a    wde  m           Ee    bebe bebe et ee  E    Scheme14  Manifold dismantling Scheme15  Burner dismantling    12  Unscrew four self threading screws 3  see scheme 15  of the fastening of burner to the back wall of the boiler   2 from each side  and put a burner off   Assembly is performed in the reverse order     Heat exchanger dismantling    Do dismount a heat exchanger it is necessary     1  Switch the boiler off  see p 10 4  page 21     2  Block the boiler   s inlet stop valves on pipes of heating  systems  drain the water out of the boiler  see p  10 5   page21   if there are not stop valves  drain the water out of  the whole heating system     3  Puta burner block off  see section17 1  page36     4  disconnect cables from the thermo relay 4  see scheme 15     5  By means of the turnkey 30 to unscrew 2 nuts 1 of pipes  fastening to the heat exchanger    Unscrew two self threading screws 2 from each side of   heat exchanger s fastening to the back sidec     Unscrew seven self threading screws 1  see scheme 16  of    the exhaust flue bar s fastening 2 and put a bar off  Schemel6  Heat exchanger dismantling  8  Remove heat exchanger by pulling it up     6        7     Assembly is performed in the reverse order     17 2 Pump dismantling  To dismount a pump it is necessary     1  switch the boiler off  see section 10 4  page 21    2  block inlet and output stop valve in the boiler  drain 
3.    Switch the boiler off  see p 10 4  page 21    Put off a casing from the boiler  For this it is necessary to unscrew 4 casing   s fastening screws  self threading  screws  to the low panel of a boiler and 6 casing   s fastening screws  self threading screws  to the front panel   Throw a front panel together with a cover down  then remove a casing while pulling it up and over yourself   Remove a sealing cap  unscrew 4 screws  self threading screws  and pull a cap hard up over yourself  When  reassembling  take into consideration  a correct installation of the cap   s sides which should enter the slots on  the back side of the boiler   Remove a manifold  For this to unscrew 2 fastening screws  self threading screw  of the manifold to the front  burner   s bracket and with a turnkey 30 to unscrew a nut fixing a manifold to the gas pipe  detailed description  of removing the manifold see in p 17 1  page 36    To replace nozzles in the burner   s manifold to the nozzles with aperture diameter        0 79 vv for LPG        1 31 for NG   Remove a housing closing an electronic board by unscrewing 6 screws  self threading screw  on the hosing  and mount a jumper CM1  see Appendix  page 53  in the position         B C  for LPG         A B  for NG   Adjust boiler   s power  see section11  page 22    Assemble boiler   s elements in the reverse order     10  Make an entry into the section  Certificate of rendering to another gas type  of user   s manual   11  Make an entry on the boiler
4.    s label and in the section 21  page40  of the present User   s manual     13  BOILERS FLOWCHARTS AND CONTROL BOILER   S OPERATION    13 1  Boilers flow chart   BaltGaz NEVALUX 7224      Inlet air    urne  Boso    HC outlet DHW outlet    1  Air pressure switch    2  fan    3  exhaust flue    4  heat exchanger    5  burner block  burner    6   ignition plug    7   sealed chamber    8  gas supply regulator    9   thermo relay    10  CH temperature sensor     Combustion products  Inlet air     Doda CERA       User s manual    RA 1    HC inlet    Gas inlet Cold water inlet    11  Ionization plug    12  Bypass valve    13  Drain valve    14  DHW temperature sensor   15  DHW flow sensor    16  CH feeding valve    17  Safety valve  CH     18  manometer     Scheme  12  Flow chart    19  pump    20  air duct valve  automatic    21  expansion tank    22  electronic board    23  igniter    24  power cable    25   pressure sensor     User   s manual    132  Main components    13 2 1  Control system    Electronic board 22  see p 13 1  page 24  To control boiler s operation and ensure safety in  case of emergency    A set of cables for connecting a board with sensors   components and mechanisms       13 22  Hydraulic system    Heat exchanger 4  see p 13 1  page 24  To transfer produced heat while gas burning to the  heat carrier  transfer heat from heat carrier to water  of DHW system     Pump 19 A component to create a compulsory water  circulation  Air duct valve 20 Automatic air remov
5.   Initial  pressure in the expansion vessel should be approximately  8x0 01  x 1 120 09 MPa  To sum I up  calculated pressure  is considered as initial one in the heating system with cold water    Membrane expansion vessels have nipple apertures which serve for regulating and monitoring of pressure   s  values in the gas part of the vessel  After you define the initial pressure  it is necessary to measure pressure in the gas  part of the vessel  for instance  by the car gauge  and then release or add  for instance  by the car gauge  the air up to  the set pressure value  Simultaneously you should consider that for the boilers BaltGaz NEVALUX the initial  pressure in the expansion tank should be at least 0 1 MPa and not more than 0 3 MPa    Lower pressure can cause the boiler   s operating failure    To calculate the full volume of the expansion vessel you can use the following formula    Vc z1 099 Vi  Av  Pmax  0 1     Pmax     P     where    Vi     full volume of heating system dim       Av     growth of water volume in the heating system from the heating up to the maximal possible temperature    Pmax 0 3 MPa     maximal calculated pressure in the expansion tank  equals to the pressure of the safety relief  valve     P     initial pressure in the expansion tank nauajrHoe JaBJIeHme B paclIMpHTebHOM Gare  calculated according the  mentioned above method      3  A  z        d               S    Ionas emxocro pacmnspsrea  noro cocyna  dm    Ha aassHoe napremne m paetos       e  
6.   see p 17 1  page 36      4  put off a bracket1 of CH output pipe s fastening   see     scheme        5  take a pipe 2 out of the bithermic manifold 3  Ly a  6  take out a bypass valve  see Annex I  e  M  page45         7  afaulty bypass valve to replace  rar            Scheme 18 bypass valve dismantling    Assembly is performed in the reverse order     17 4 Expansion tank dismantling  To dismount an expansion tank it is necessary   1  switch the boiler off see p 10 4  page 21      2  block inlet and output stop valve in the boiler  drain the water out of the boiler  see section 10 5  page 21   if  there are not stop valves  drain the water out of the whole heating system      User   s manual       Scheme 19  Dismantling of the tube of expansion tank Scheme20  expansion tank dismantling    3  by means of the turnkey 22 to unscrew a nut 1  see scheme  19  of the pipe of the expansion tank 4    4  by means of the turnkey 22 to unscrew two fastening of the expansion tank 4 to the bracket 3    5  unscrew two screws of the fasteningo 5  see scheme  20  of the upper bracket 6 to the boiler   s channel bars   6  put off an upper bearing 6 and take out a tank out of the channel bars by pulling it up     Assembly is performed in the reverse order     18 UTILIZATION    Upon completion of using the boiler  it is necessary to dismantle it by the following operations    1  Disconnect the boiler from the main power    2  block stop valves on the pipes of heating system  drain water out of
7.  11 SP 41 108   2004 the boiler installation should be provided in the  following conditions     On the walls made from non flammable  NG  or low flammable  G1  materials    On the walls covered by non flammable  RG  or low flammable  G1  materials  for example roofing steel on a sheet  of heat insulating layer of non flammable materials not less than 3 mm thick  lime plaster not less than 10 mm thick     User   s manual    on a distance of not less than 3 cm from the wall  The above mentioned wall covering must get outwards the boiler   s  coating   s dimensions for not less than 10 cm     Placing the boiler above the gas stove or kitchen sink is prohibited     In front of the boiler there should be a service zone of not less than 1 meter      You should choose a place for installing the boiler taking into account the fact that for convenient service a free  space of not less than 150 mm on the boiler   s lateral sides and not less than 200mm under it is needed  The boiler   s  overall dimensions are represented on Scheme 1  page 6       Mark the boiler   s attachment points  applying the carriers from the supply package and perforate holes O 10 mm  In  order to mark the holes on the wall it is recommended to use a harness board  included in the boiler   s supply package   Put the wall dowels from the supply package into the holes and fix the boiler mounting carrier  using the screws from  the supply package     hang the boiler by the mounting holes  located on the channel b
8.  Le be fo AT 12  TA DEW  syste id eee e RI UE ee eee dete RH t pete 12  1 2  Heating System    e ene A mt rein petite cated ode et Ye lens dae e oct pe Rete ge oe eee eae eee 12  7 2 1  New heating  A E ETE 12  7 2 2  Existing heating  EV A NANO 12  7 3  Selection of an additional expansion  IP A                                                                     tet 12     BOILER INSTALLATION tots teas ha ere Eee Peer RR ER E EE eels a tbl ree Salons ite 13  8 1  Mounting the boiler to the  Wallis T 13  8 2  Connecting the boiler to the CH and the DHW  A idet ete eoe teet duces tut sede HE REED reor ee tera ee Ue iet bee Ub se dtt ova dg tee dU ern 13  8 3  Connecting the boiler to the gas  SS Mn aue er eee ot dob re ede ts ek ee Dr een Horne eerte ROE c TT 13  8 4  Connecting the boiler to the balloon with liquefied  no EHE 14  8 5  Connecting the boiler to the power  ecos IER 14    9  SMOKE EXHAUSTER  INSTALLATION    iuit cette eto t e EE RE e CREE eese ehe o 15    User   s manual    9 1  Installation of coaxial smoke    exliauster    is hate ease UR es Ud A ede ede be iR UL 15  9 2  Installation of separate pipes of smoke exhauster and air   UCU   aac ze e UE ge e eroe ER E ee ete tad adf ido 16  9 2 1  Installation of separate pipes of smoke exhauster and air duct by means of transitional set KHG 714061510       EEUU 16  9 2 2  Installation of separate pipes of smoke exhauster and air duct by means of channel separator 8023    TO  pm  17  10  PUTTING THE BOILER INTO OPER
9.  circuit  kWt 24 0  Rated heating effect   Rated input heating power  Qnom   KW 26 7  Rated gas consumption m  h 2 95 1 00  Water consumption at heating for   l min 14 0  AT 25   C   Temperature regulation range GE 30   60  Operating water pressure MPa 0 02   0 60  Minimal water pressure  Pmin MPa 0 015  Maximum water pressure  Pmax MPa 1 0    at heat extension of water the   pressure must not exceed this   level    Minimal water flow for switching   l min 2 5   the boiler on   Minimal water flow for switching   l min 1 5   the boiler off   Specific water consumption  D dm3 min 11 6  Mass consumption of combustion   g s 17 0 18 5  products   Average combustion products   C 120  temperature   Type of combustion products Forced   output   Heat transfer medium Water       Water circulation type    Airtight forced circulation       Ignition type    Automatic ignition  electronic ignition       Maintenance of set temperature       Automatic maintenance with accuracy  1   C                                                          Temperature indication LCD display   Rated power tension V 220  10   Rated electric current frequency Hz 50  Maximum electric power kW 0 125  consumption   Safety fuse A 2  Electrosecurity class I   Protection rate IP X4D  Overall dimensions  height widths   mm 720x410x326  x depth   Net  Gross weight kg 34 0   36 5  Connection dimensions  inch G3 4   Gas inlet   Heating circuit inlet and output inch G3 4   Hot water supply circuit inlet and   inch G1 2   
10.  in gas and water systems  in such connections where disassemble of water and gas pipes or in  the places where water or gas leakage occur    4  Check air tightness of boiler s water and gas systems   5  Lubricate moving connections  if necessary   dense based on silicon lubricants are recommended   6  Check operation of safety devices and sensors see p 16 2 2  page  34    7  Check air pressure in the extension tank  once per 3 years    8  Check air duct system and removal of combustion products on leakage   9  Check water flow in DHW  should be enough for switching DHW mode on    10  Check the heating system on contamination   Caution  Operations related to technical maintenance of the boiler  disassemble of its gas and water pipes   are necessary to perform only when the boiler is completely switched off  taps on boiler s inlet water and gas  lines should be closed  boiler should be disconnected from the power       16 1  Technical service    16 1 1 Cleaning the burner block   Caution  Keeping burner block in pure conditions will protect heat exchanger from the soot and increase its  service live    To clean the burner block 5  p 13 1  page24  it is necessary    1  To dismount a burner  see p 17 1  page 36     2  Remove dust by the brush from the external burner s surfaces and manifold    3  Remove carbon deposit with the sandpaper from the ignition and ionization electrodes    4  Wipe with wet rag manifold and nozzles    5  Remove dust with a brush cleaner out of inner cha
11.  kPa  300 mm of water column   To measure pressure is necessary while the boiler is on    Before to check gas and water tract on leakage  or any other safety device  it is necessary to put a casing and   sealing cap off from the boiler  see p 17 1  page 36      16 2 1 Checking gas and water systems leak resistance   Note  Checking leak resistance of gas joints is performed by soup solution bubble test  or any other safe  methods without using open flame sources   Appearance of bubbles means gas leakage    Check on leakage is performed in such joints as  gas supply regulator with gas supply pipe  gas pipe with burner  block and gas supply regulator  and also in the control points A and B of gas supply regulator  see p 11  page 22     Checking water system on leakage is performed alternatively in CH and DHW modes  The following joins are  checked  boiler with the heating system and DHW  heat exchanger with the hydraulic group  tightness of hydraulic  group elements  Leakage in the joints is not allowed    In case of gas or water leakage it is necessary to remove it by tightening the nuts  gauges  or installing a new  sealing     16 2 2 Checking of safety device operation    16 2 2 1 Checking of water sensor in heating system  Before switching the boiler on  put the cables off from the water pressure sensor 25  see p 13 1  page 24   During  the start up  boiler will display a symbol  04   signaling about the emergency in CH   After eliminating the reasons of boiler s emergent sw
12.  necessary changes in the boiler s construction  The following changes might  not be displayed in the user s manual     28 08 2012    User s Manual  1  SAFETY MEASURES  For the purpose of your own safety and in order to avoid the boiler s breakdown it is strictly prohibited to     Use the boiler when it is out of order      Putthe boiler into operation with no flue pipe installed or with a defective flue pipe     All gas dangerous works  all technical service works and reparations of the boiler must be effectuated only by  a specialized service organization     To effectuate boiler treatment  being in a state of alcohol or drug intoxication   To insert changes into the boiler s construction  To    uch the combustion products outlet pipe while the boiler is in operation  as the temperature of heating of this pipe  might reach more than 100   C  for separate pipes of smoke exhaustion and air output      To use gas and water systems  and also the heating system  for earth bonding     To touch the boiler if you are standing barefoot  or your shoes are wet  on wet floor     To effectuate boiler treatment if it is not disconnected from the electric network and gas system     To insert changes into the safety and control systems operation with no permission and indication from the  boiler s manufacturer    To damage and deform the elements of electrical wiring of the boiler  even if the electric power supply is  disconnected     User   s manual      To expose the boiler to the impac
13.  nozzles    1 31 mm  NG  G20  2 family  group  H  1 3 kPa     Heat exchanger 256350881801    User   s manual    Pos   Designation                                    Note        0 Ek    Burner block 7224 22 000 01 insu    0 79 mm  LPG  G30 3 family  group   8  cap 8223 10001   9 T bearimg8223 10 002 _ _  o   10   Viewing window 8223 10 005 P S    OE   11  fan ERR97 34L o  o    Air pressure switch  fn E  Air pressure switch RB21001  manometer 066206  Electronic board MIAD300 p  igniter ACOBABKSIQ a O    panel 8223 15 001  panel8223 15 001 02 White grey color    cap 8324 15 100   Magnet in assembly 8223 15 200  housing 8223 15 002   button 8223 15 003    pU  Output CH pipe 7324 05 000 pn    6          Inlet CH pipe 7324 06 000  Tank   s pipe 7324 07 000  Output DHW pipe 7324 08 000  Inlet DHW pipe7324 09 000  pipe 7324 11 000   pipe 8223 00 003  spacer 8223 01 004   spacer 8223 01 007   spacer 8023 00 003   spacer 3103 00 014   spacer 8023 00 004   spacer 8023 00 005   spacer 8023 00 005 01   spacer 8223 00 013   O Ring OR 17 86x2 62  21000606701200   Cuff 8023 06 002   hub 8023 00 007   housing 8223 00 006   housing CCUC 1   thermo insulation 8230 00 002  thermo insulation 8230 01 003  thermo insulation 8230 01 004  pin 18   21000607000600   Casing in assembly 8223 12 000  Gauge 8223 01 003   flange 8223 01 006   Plate 8223 16 001   axle 8223 15 004   pipe Venturi PP270   Wall 8230 00 001   Side wall 8230 01 002   nut 8023 01 004   cuff 8223 15 005   Gas supply regulator EBR200
14.  of gas and gas pressure in the place of the boiler   s installation  In case  of non compliance it is necessary to render the boiler to the used type of gas and pressure in accordance with  section 12  page23     To make sure that the installation was correct and the smoke exhauster is airtight    In order to provide correct boiler operation ant to keep the warranty it is necessary to follow the requirements  of this manual     7 1 DHW System   For normal boiler operation it is necessary to install a water filter before the boiler on the DHW line    If water hardness exceeds 200 mg of calcium carbonate per 1 liter water  it is necessary to install a  polyphosphates dose meter or another water softening device    7 2  Heating system   The boiler is connected to the heating system and hot water supply system  DHW   in accordance with  its characteristics and heating power    Minimal heat output of the heating system must be more than 8 9 kWt  Otherwise  the boiler will  operate unstably  what would lead to reduction of its working lifespan    Water chemical makeup requirements are indicated in section 10  page 19     Presence of rust  dirt and other depositions in the heating system leads to the boiler s operation disturbance  and performance degradation  overheating  noise in the heat exchanger  heating effect reduction   In  connection to this  the heating system must be washed before the boiler s installation    For this acid and alkaline based detergents or detergents  cor
15.  staff manual  10  PUTTING THE BOILER INTO OPERATION  INITIAL RUN     As a heating agent in the heating system it is necessary to use water  The quality of water used in the heating system  must comply with the following parameters    Hydrogen ion exponent PH 6 8   General hardness not more than 4 mg eq L   Iron concentration not more than 0 3 mg l   If source water hardness exceeds 4 mg eg l  it is necessary to install by the water inlet into the boiler a polyphosphates  dose meter  that processes water coming into the boiler  protecting the heat exchange equipment of the boiler from  hardness deposition  Polyphosphate dose meter is not included into the boiler s standards supply package and is  purchased separately    If source water hardness exceeds 9 mg eq l  more powerful water softening installations should be used     10 1  Filling the heating circuit with water and prelaunching check    1  Release the air output valve 20  see p 13 1  page24   located on the pump19   turning off its cap for  1 5   2 turns    2  Open step by step the cold water inlet tap on the DHW line in front of the boiler  heating circuit feed tap  16  see p 13 1  page24  and stop valves on the direct and reverse lines of the heating circuit  if they are  installed     3  Close the boiler s feed tap 16  when the pressure in the heating circuit reaches 1 2 bar  in accordance with  the technical characteristics table  see p 2 2  page 5 according to the pressure indicator readings  The  recommended pre
16.  the boiler  if there are not stop valves    drain water out of the whole heating system     3  shut a gas block valve    4  disconnect pipe connection from the CH  DHW and gas    5  take a boiler off from the wall    It is essential to remember that the boiler is considered to be a potentially traumatic object  Therefore when  utilizing the boiler  it is necessary to ensure maximum safety for others    Boiler and its package consist of materials suitable for recycling  Dismounted boiler is recommended to hand over  to a specialized organization     19 DELIVERY SET    Table 6      BaltGaz NEV ALUX 7224      3 pes   2 pes     1 pes     1 pes        1 pes     User   s manual    Annex I  Catalog of boilers components   BaltGaz NEVALUX 7224    47     EM     10  Lr 2 59 2 58 60 59 576150 28 12  29   i             Consists of   1  Back side 7224 01 051  Exhaust flue 8223 01 200  Back wall in assembly damper 8223 01 002  bar 8230 01 005  bearing 8223 00 014  bearing 8223 00 015  Applied together with a clamp 0409001010  pos  58    thermo relay HD8 5FC 9  Pos  57   temperature sensor  TPO1AHILO  pos  59  and copper spacers 8223 02 003   pos  60     2  Applied together with thermo relay TY60 A B230AG   Heat exchanger QF DSGLS L270 90  C  pos  61   temperature sensor JXW 54  14   pos  62   and temperature sensorJXW 54  18   pos  63   L     4   Channel bar 8223 01 110 01     5   Bearing 8023 01 002_   S   E    6   Hydraulic group 10037608006050      7 Burner block 7224 22 000 13 blades 
17.  the viewing window   an   ionization plug1l sends a signal to the electronic board about successful ignition  If a signal from    8           9           User   s manual    ionization plug 11 is absent  electronic board repeats a procedure of boiler   s staring up from the  beginning  There are 2 consecutive start up attempts taken  If both attempts failed  electronic board stops  ignition    8  Electronic board changes voltage in the modulator coil of gas supply voltage 8  Gas supply regulator  increases gas supply to the burner block up to maximal power in order to quickly warm the water in the  heating system up to the set temperature    9  Electronic board equals a signal of DHW temperature sensor 10 with a value set by the user by means of  buttons K3 n K4  see p 3 1   page7   If the difference of set temperatures is more than 1   C  electronic  board changes voltage on the gas supply regulator in order to change gas supply to the burner block in  accordance with DHW requirement     13 4 3 Boiler s operation in combined mode  In this type of mode DHW has a priority over CH  If water flow is absent in the DHW line  a boiler is working in  CH   If there is water flow in the line DHW  DHW water flow sensor 15 operates  A signal about presence of water  flow in the DHW line is sent to the electronic board  in DHW mode a pump doesn t operate    If there is termination of water flow in DHW line  signal from DHW water flow sensor 15 is absent  a boiler  enters to the CH mode  
18. 1   2   3     4     5   6     7   8     9     l  Switch the boiler off consequently pushing a button K5  see scheme  2  page 7   until a symbol O is mapped   Disconnect boiler from the power line   Connect boiler again to the power line  Within 5 seconds there is a chance of activating of the programming  function   Push and simultaneously press buttons of temperature reducing DHW and CH  K2 and K4  for activating  parameters programming function     Release the buttons when a code    P0    and symbol F will be mapped on the display   Choose a parameter which you would like to change pressing the buttons K3 or K4     Push the button K5 in order to display a parameter value  Symbol A  starts blinking    To change the value of the chosen parameter by pressing a button K1  increasing  or K2  value reducing    Keep the button K1 or K2 pressed for increasing speed of changing parameter    Press button K5 in order to keep a set parameter value and come back to choosing parameters     10  To repeat cycle starting from p 6 in order to modify all the parameters which you would like to change   11  Press button K6  RESET  to escape from programming mode   Do not change a parameter P3 without any emergency     User   s manual    13 3 2 Gas analysis function  Gas analysis function enables to control  analyze combustion process and adjust a gas supply regulator  see p 11 2  and11 3  page 22   This function works in CH and Combined modes     To activate a gas analysis function it is necess
19. 5  Expansion tank   dismantling       te eate eet ER ge pe eer s 38  TSUTIEIZATION go EE 38  23  SUPPLY   PACKAGE  iie ene etit eai ata de cs 42  S 0 O 45  o T H 51  Annex Ille  et e Uo eim at eet petet trs prof Lee c ue  d cce edt neta Mc 53    User   s manual    User s Manual    Dear Customer   Thank you for choosing our product  You have purchased a double circuit wall hung boiler with a closed combustion  chamber   Before purchasing the boiler please check     scope of delivery  see section 23  p  42  and the boiler s resalable condition     compatibility of the type of gas  natural or liquefied  used by you with the type of gas indicated in sections 20  and 21  p 40  of the following manual and with the table on the boiler s housing   You should also require from the selling organization to fill in the warranty repair coupons   When purchasing the boiler against a credit  the payment schedule must be drawn up with indication of the full due  and payable amount  The payment schedule must be signed by the Customer with the date indicated and with print full  name   The boiler and the following manual are two integral parts of the offered goods  The manual contains information  about the order of installation of the boiler  rules of its exploitation and technical service  following them will provide  long term failure free and safe operation of the boiler  Please acquaint yourself carefully with this manual before  putting the boiler into operation  follow the instructions 
20. 8N    ON io     oo    9    WIN    8    CA  WIN    4  5     54         User   s manual     Pos   Designation   Note           Ek   DU NNI  8023 02 002    58  elampO409001010___    Applied only together with heat exchanger    Temperature sensor TPO1IAHILQ     256350881801  60   Copper sensor 8223 02 003 P     Thermo relay TY60 A B230AG 90  C   Temperature sensor JX W 54  14   F DSGLS L270   Temperature sensor JX W 54  18  TARS    Applied only together with heat exchanger       Components of hydraulic group pos  6    64 73 77 81 73 7       65     Pos   Designation               Pressure sensor 21000605300200 0 5 bar    65 DHW flow sensor  21000605000800  Safety valve  Infeed unit 500 110  30029607800400 SIUS  Pump OTSL 15 5 3 CRR9    68   21000606506910 83 W  2200 turns min  DHW flow restrictor 10 L min  21000607300400  70 Low panel 7324 02 001   21000608010200   Pump   s fitting 21000605800200    72 O Ring OR 13 95x2 62  21000606700700    User   s manual    21000606701000  21000606700500    O Ring OR 5 5x2    21000606701700    Manometer   s connector  Pump   s fitting 21000607603700    nut G1 2  000462402 10080      Pos       E            spacer 21x28x2  21000607900800    86      89      90      bracket 8   bracket 14   Bithermic manifold  Bypass valve HDS 15 300    fitting G1 2  21000607602700  fitting 21000607603800    gauge 21000607608800  gauge 21000607609300       Components of the infeed unit pos  67     Pos   Pesignation   Note    aet E               21000606700100   Pis
21. ATION  INITIAL   RUIN   dcos A nee eh dott id eaten e tese one tete ere erii e ee oe Ete deret Pest 19  10 1  Filling the heating circuit with water and prelaunching   eh CM KCN X 19  10 2 Check of combustion   propetti    s a ar a a cee ee teat edo EDI t 20  10 3  Additional abilities    io MC                                                                 eR 20  10 3 1 Connection of room    ls dn                                               S         20  10 3 2  Remote control   CODDECLUODS cu niece toot uf T 20  10 3 3  Connection of external temperature   oio E LE 21  10 3 4  Connection of a computer for   diagnostics NEP LE 21  10 3 5  Connection of several room   thermosStats   5 dede tec eeu pee ot e le ese e ee iia ted Gert tae t estet ene 21  10 4  Swithching the boiler   ME si A A A a ii dai 21  10 5  Water drain from the boiler   s   CH A ON 21  11  BOILER   S POWER   REGUERXTION     5 tret ter ence tere no PD I ERE e n aD Ene on RU eue esee cedo UTR eden 22  11 1  Prestarting   Proceduresz d E aeree teretes E e ee date entras TE cete c aid edie eet 22  11 2  Checking gas pressure on entering the   regulator  5 4 o e RTI selbe tees de eere e Het ie HER Lee Red eec eee uet  22  11 3  Regulating rated   Dressute zie antec lou dere ett aue Ee DIR EE D eti Maus D HERR Ee re DERI REESE 22  11 4  Regulating minimal   lur m OR 23  T T5  End of operation    not Rr dene ne eb e ree be Le RU HE ig 23  12  RENDERING THE GAS BOILER TO ANOTHER TYPE OF   LE cos nee eet atte t e
22. MINA TION EE CUT RC EOI ERE Sc nai 29  141  EtfOt COd6S8  A e EY EET We ORTA dis 29  14 2  SET AUR CS uoi ebore n pao halt c i Re aloe isco onal og x Ea wae ETE A PUN ciue ADU AR RR TANS 31  15  HANDING THE BOILER OVER TO THE   CUSTOMER cr           r       iaaa 32  16  TECHNICAL SERVICE AND OPERATION   CHECK  etie tet deste Hee iem bue uet idee EU e HE Fe Ue Ee eet tiene eta Pete o teet date 32  16 1  Technical   din aa lino 32  16 1 1  Cleaning the burner   A T NN 32  16 1 2  External cleaning of heat   exchanget   ied DU AU ATA e i Ee cage 33  16 1 3  Internal cleaning  washing  of heat   EX CHAN SET ice  iae ee RO eee eo UR RR ERE UE td eee ERE deci t a d dene e e e Da ced 33  16 2  Boiler s operation   Mrd d                                                33  16 2 1  Checking of gas and water boiler systems  leak    edid  E A                       34  16 2 2  Checking of safety devices   Operation sis ce ire iie i efe RO e re Or tcr salves thieves sea eid cetero ue LE ee eerie eter Pase ope Dd dees ECTS 34  16 2 2 1  Checking of water pressure sensor in the heating   ic                                                            M 34  16 2 2 2  Checking of water overheating protection in the heating   AR ER HER HER Perse NN 34  16 2 2 3  Checking of bypass valve   Oper  atlOEi   6 tee Ded d da RO en UR EPOR E RO Oe b edt 34  16 2 2 4  Checking of safety valve   OPETAMOMN a  cita Dd                                                  9   O      M alai aiea 34  16 2 2 5  Air re
23. Protect heat exchanger against overheating while  increasing resistance in the heating system    Safety valve 17 Water relief out of the heating system when pressure is  higher than 3 bars    Air duct valve 20 Automatic air removal out of the heating system    Gas supply regulator 8 Ignition at low pressure in order to avoid    clap       see p 13 1  page 24  Blocking gas supply if emergent case happens  heat  carrier overheating  absence of draught etc      Ionization plug 11 Flame control on the burner  If flame lacks  it stops gas  supply to the burner    For combustion products    Air pressure switch 1 Control fan   s operation    see p 13 1  page 24  When draught is present or fan is out of control  it stops  boiler s working    13 3  Service functions  13 3 1 Parameters programming function    Parameters programming function enables to modify main parameters of boiler s starting up and operating  This  function works only in the stand by mode and allows modifying the following parameters       PO        ignition power 0   99  100 steps        P1        minimal heating power 0   39  40 steps        P2        minimal heating power40   99  60 steps        P3        minimal time from turning off until restarting working 0   14  min     Factory settings of the boiler   BaltGaz NEVALUX 7224       P0    40 for boilers working on NG     P0    60 for  boilers working on LPG     P1    0     P2    99     P3    3 min     To use a parameters programming function it is necessary     
24. User   s manual    TABLE OF CONTENTS  T SAPETY MEASUREBS    5  saitees iaa aie Glee eased etes a a aaa at 4  2  Technical description  eos we  ested E ade HET a au ais Atta E ah a e a dde o eS 5  Del Bower    S  purpose T 5  2 2  Technical characteristics    etii O Ebenen ra eb o E Rage eie Pat SR 5  2 3  Overall and connection  CUISINE S 6  3   USERS  MANUAL  ce e ted a is Ree a ee ee o RT cedros 7  331 Control  Panel  uite eh A a b tete e ee Pee eei Aa ete pea 7  3 2  Boiler s operating  ia R S TT D MEE MERCREDI 8  3 2 1  Standby  MOC Ss ii ge e AS ate da dete m 8  32 25 DHW Modena aia aii ieee 8  3 2 3  Combined  mode  aoo edepol cati e tete fto po EE t E eter et eodem eee  9  3 2 4  Heating  i EIC EE 9  3 3  Additional  TunctiOnsic  54e bI A RE eb a e e e oed ade e 9  3 3 1  Antifreeze  infesto gh EET O ON UN 9  3 3 2  Anti blocking  A     9  3 3 3  Boiler s operation in heating mode with an external  outdoor  temperature  GL T E CLE EN 9  3 3 4  Boiler s operation at low  high source  MCI o a ME E 10  4  BOILER SERVICE donee deter nhe een ui an eee ies 10  4 1 Exaimmn  tion     bd ete re e e eere i eee e e Lee Qe Hd te 10  4 2 Boilet Treatiment   iie eee or ee ue Een 10  4 3  Operations effectuated at technical   jui oc EE 11  5  STORAGE  PRECAUTIONS     53 2 2 RE BH UU E ata ee ea eed aM WARS AUR n E 11  6  GENERAL  REQUIREMENTS wastes xe eti e e a ae ee 11  7  OPERATIONS BEFORE  INSTALLATION 2 et ee bte te bete eet PE Ee eb deba beet oe e aree LER ee ep tede t eot euet
25. W temperature sensor 14  see p 13 1  page 24    When trying to start up the boiler in DHW mode  it should display a symbol  06  which signals about refusal of the  DHW temperature sensor to operate   After eliminating the reason of boiler   s emergent switching off  connecting cables to the sensor back  boiler  should automatically switch on   To check the temperature sensor  measure its resistance  R 10 kOhm  at 25   C      User   s manual    16 2 2 11 Checking DHW flow sensor  Render boiler into DHW mode  see p 3 2 2  page 8   open a tap in DHW line  Put the cables off from the DHW  flow sensor 15  see p 13 1  page 24   Boiler should enter into the stand by mode   After connecting the cables back  boiler should automatically switch on     16 2 3 Checking of air pressure in the expansion tank  Demount an expansion tank  see p  17 5  page 38   without putting it off from the boiler  Through the valve   nipple   located in the upper part of the tank  measure air pressure  Pressure should be  0 1 0 02  MPa  If the pressure  in the expansion tank is lower than the allowed one  it is necessary to increase it up to the required value by the pump  or any other safe device  If the inner membrane is damaged  when measuring the air pressure  there is water in the  valve or air pressure doesn   t restore   it is necessary to replace the expansion tank     16 2 4 Checking of the air inlet and combustion products output systems on leak resistance  Visually check exhaust flue integrity  S
26. ae IN  21000606400100       User   s manual    Components of the burner block pos  7    Note  e mee blade 3295 07 40 000    nozzles 1 31 mm  NG  G20    Manifold in assembly 3295 07 20 000 10 2 family  group H   1 3 kPa   nozzles    0 79 mm  LPG  G30    Manifold in assembly 3295 07 20 000 11 3 family  group B P   2 9 kPa      1 31 mm  NG  G20      gt  nozzle 3295 07 20 005 19 2 family  group H   1 3 kPa     nozzle3295 07 20    nozzle3295 07 20 005 20   20 GL    3 family  groupB P   2 9 kPa     bar 8223 22003    bracket 8223 22 006      Plugs in assembly 8223 22 060   SSI    Compound elements of the plugs in assembly pos  98       _       Pos   Designation   Note        E   99   plate 822322061      100   Ionization plug ELB21001      101   Ignition plug ELB21002 __ OOOO       User   s manual    Components of wiring    Gas supply regulator cable CBABOW009 To connect modulator coil of gas supply regulator  DHW  flow sensor  pressure sensor    CH temperature sensor cableCBABOW010 To connect CH temperature sensor    To connect ignition plug    Annex II    Guidance to select an expansion membrane tank  If to connect a boiler to the eating system with a volume more 70 liters  it is necessary to install an additional  expansion membrane tank  by connecting it to the return line     by pass     really close to the boiler   In the tables presented below  you can find water volume necessary for fulfilling elements of the heating system   Volume of the boiler by itself is 2 liters  This 
27. ags and gaps in the joints of the exhaust flue elements are not allowed   Joints of the separate exhaust flues which elements do not consist of presence of O Rings  should be sealed with  aluminum heat resistant tape or any other material with similar properties     16 2 5 Checking of DHW water consumption  Determine maximum water flow in DHW line with a draw down gauge  Water consumption should be at least 2 5  l min  If water flow is less than 2 5 l min  it is necessary to clean the boiler s inlet water filter in DHW line  if filter is  mounted      16 2 6 Checking of heating system s with respect to its stoppage  When boiler is operating in CH  see p 3 2 4  page 9  it is necessary to check whether a bypass pipe heats  If  bypass pipe is heated constantly  it is necessary to clean a boiler s inlet water filter in CH line  if filter is mounted    and also in other heating areas where contamination is possible  Before cleaning a filter  it is necessary to Switch the  boiler off and drain the water out of the boiler  see p  10 4 and10 5  page 21   if there are no shut off valves  to drain  the water out of all heating systems      17 BOILER S DISASSEBMBLING AND DISMANTLING OF MAIN UNITS   Boiler s disassembling and all dismantling activities of the main units are performed only when the boiler is off   electricity power  gas and water supply are off  For any work concerning dismantling  it is necessary to drain the  water out of the boiler  see p  10 5  page 21      17 1 Burne
28. al out of the heating system    Expansion tank 21 Compensation of water expansion in CH as a result  of heating       13 2 3  Gas system    Burner block  burner  5 Mixing gas and air and ensuring uniform   see p 13 1  page 24  combustion of gas air mixture in the combustion  chamber    Igniter 23 Forming a spark on the ignition plug  Ignition plug 6 To create a spark for igniting of the gas air mixture  on the burner       13 24  Smoke exhausting system    Fan 2  see p 13 1  page 24  Compulsory removal of combustion products    13 2 5  Regulation devices    Gas supply regulator 8 Regulate gas supply to the burner block    see p 13 1  page 24    CH temperature sensor 10 Measuring temperature of the heat carrier  Signal  from the sensor is applied for maintaining set  temperature of heat carrier in CH       DHW temperature sensor 14 Measuring water temperature in DHW  Signal is  applied for maintaining DHW set temperature    DHW flow sensor 15 Defining DHW water flow  Signal from the sensor  is applied for rendering boiler into the DHW mode  while opening a hot water tap       13 2 6  Safety devices       User   s manual    Fuse 21 Protect electronic board and electric circuits against   cm  Annex III  page 53  overloading in the electric system and short circuit  protection    For water    Pressure sensor 25  see p 13 1  page 24  Control minimal water pressure and air absence in the  heating system    Thermo relay9 Protect heat exchanger against overheating    Bypass valve 12 
29. an 0 5 bar the safety  system will be switched on and it would be impossible to put the boiler into operation    In the center of the control panel there is an LCD display  showing the temperature in currently active mode at  normal operation of the boiler  at operation in the heating mode it shows the water temperature in the heating  system by the output from the boiler  at operation in the DHW mode    the DHW temperature by the output  from the boiler   In case of failure the error code appears on the display instead of temperature  The boiler s  error codes are represented in the p  14 1  page 29      User   s manual    The symbols on display show the boiler   s operation mode  Around the display there are 6 boiler control  buttons  The designation of the control buttons and of the symbols shown on display are represented in the  tables 2 and 3 respectively     Control buttons designation                                                       Table 2  Symbol Function  Kl DHW temperature increase  K2 DHW temperature reduction  K3 Heating temperature increase  K4 Heating temperature reduction  K5 Choosing the boiler   s operation mode  switching the  boiler on off  see p 3 2   K6 Reset of the boiler   s electronic board blocks   RESET   User   s manual  Displayed symbols designation Table 3  Symbol Is always glowing Flickering  Antifreeze function operating symbol   see  p  3 3 1  page9   U Presence of flame on the burner  A Standby mode   N Boiler in the DHW standby mode Bo
30. and b   see schemeScheme 11      1   2   3   4   5     6   7     D    3   4   5     User s manual    11 1  Prestarting       Schemell  Gas supply regulator    11 2  Checking gas inlet pressure in the regulator   Unscrew a gauge on 1   2 turns from the control point B and connect a manometer    Switch a boiler on and render it to the CH mode  see p 3 2 4  page 9     Set rated power by turning on a function of gas analysis  see p 13 3 2  page 27     Keep boiler in the CH mode within 1 minute    Check gas pressure in the control point B  It should be 1 3 kPa     2 0 kPa    130   200 mm of water column  for NG and 2 9 kPa  300 mm of water column  for LPG  In other case it is  necessary to Switch the boiler off and address to the emergency service of gas facilities  telephone number 04  or replace a cylinder  for LPG     Render boiler into stand by mode consequently pushing a button K5  see p 3 2 4  page 9     Disconnect a manometer and wrap a gauge in the control point until bumping     11 3  Regulating rated pressure  To perform regulating rated pressure you must effectuate the following   Unscrew a gauge on 1   2 turns from the control point A and connect a manometer   Switch the boiler on and render it to the CH mode  see p 3 2 4  page 9    Set rated power by turning on a function of gas analysis  see p 13 3 2  page 27    Keep boiler in the CH mode within 1 minute   Check gas pressure in the control point A  It should be 1 kPa  105 mm of water column  for NG and 2 5 kPa   250 
31. ars  on the hooks of the carrier     8 2 Connecting the boiler to the heating system and the DHW system     Connecting the boiler to the heating system and the DHW system must be made with metal pipes or flexible hoses  with inner diameter not less than 20 mm for attaching them to the heating circuit and not less than 15 mm for attaching  them to the water supply system  The hoses must be resistant to the inlet water with set parameters of pressure and  temperature  The hoses must be not more that 2 5 meters long  The hoses should be installed in accordance with the  instructions of their manufacturer     We strictly recommend to install two stop valves G3 4  by the inlet into the heating system and the output from it   they are not included in the delivery package  in order to effect the technical service operations without water drain  from all the heating system     In order to avoid boiler   s heating circuit   s dirtying on the heating system   s reverse line  before the boiler  it is  necessary to install net filter     mud flap   and slime tank     A stop valve G1 2   not included in the supply package  must be installed on the DHW line before the filter    Remove cover plugs from connection pipes     connect the boiler to the heating and water supply systems  Check the joints    air tightness     CAUTION  The heating circuits pipelines must pass through inner heated premises  otherwise water freezing  inside of the heating circuit is possible at sub zero temperature o
32. ary to hold the button K6  RESET  until a symbol A  will be  displayed  Within 15 minutes a boiler will work on the rated power  Afterwards it will automatically come back to the  operating mode  To turn the gas analysis function off before than in 15 minutes it is necessary at first to Switch the  boiler off and then switch it on using a button K5     13 4  134  Boiler   s operating logic   Boiler s starting up in the heating mode happens if actual water temperature in the heating system is lower than a   set one for 5   C  Boiler starts up working in DHW mode if there is water flow in DHW line present    The following pre starting operations happen while a boiler starts up    1  Electronic board 22  see p 13 1  page 24  checks voltage    2  Water pressure sensor 25 works out  Signal about water presence in CH goes to the board  If CH is not full   boiler s starting up stops    3  Electronic board checks status of the thermo relay 9 and operating conditions of CH temperature sensors 10  and DHW 14  Failure of any of these sensors causes the stoppage of boiler s starting cycle    4  On the display of control panel is mapped a value of CH and DHW water temperature  depends on operating  mode     If boiler s starting up stops due to any failure  an error code is displayed  see p 14 1  page 29      13 4 1  Boiler s operating in CH    1  Electronic board 22  see p 13 1   page 24  provides voltage to the pump 19  to check the voltage on the  pump s terminals is possible by means o
33. data allows to make an approximate calculation of the water quantity in  the heating system to which boiler will be connected     DHW temperature sensor cable CBABOWO026 To connect DHW temperature sensor       Tables to calculate volumes of water     Copper pipes Water volumes in the radiators       lt  Water  Pipe diameter  tit Tvpe of radiator power  Volume      des    WO   ww    p    mum 11 600 1000 1310  PP 22 600 1000 2225    Pipe diameter Wa  5 quantity  11 600 900 1179 3 10  dm TM         HE  ek ar 460 1    Power is indicated for the parameters 90 70 20  C  where     G21 2 90     temperature in direct heating line   G    70     temperature in reverse heating line   pS AA al    20     temperature in the area     m  1  2  3  4       User   s manual    Another way to determine water volume in the heating system is to compare values of the water sensor before and  after filling with water    Minimal initial pressure in the expansion tank should not be less than the static pressure at the connection point of  the vessel    Static pressure  is a pressure of the water column between the expansion vessel and the highest point of the  heating system  Measuring this height in meters  we calculate static pressure taking 0  001 MPa of overpressure for  each height of meter  Initial pressure in the expansion tank should be approximately 10  more than calculated static  pressure    For instance  Measured height is 8 meters  which corresponds to the value of the static value 0 08 MPa
34. double pipe and single pipe     Children must be kept away from contact with package elements  plastic bags  polystyrene etc    as they represent a  potential source of danger    The boiler s initial run and warranty liabihties must be fulfilled by a special service organization                                               User   s manual    Technical staff manual  6  OPERATIONS BEFORE INSTALLATION   CAUTION  Boiler installation  putting the boiler into operation and technical service can be effectuated  only by a specialized service organization  Boiler installation must be effectuated according to the  project which complies with the requirements of Federal and local normative acts  regulating gas  appliances installation   The boiler is designed for heating water to the temperature lower than the boiling point at atmospheric  pressure   The boiler should be connected to the heating system  and also to the water supply network in order to receive  domestic hot water for housekeeping needs  hereinafter referred to as DHW   and after that to the gas pipeline   Heating and water supply systems must be compatible with the boiler   s exploitation characteristics and power   Boiler   s technical characteristics are represented in p 2 2   page 5    Before putting the boiler into operation it is necessary to effect the following    To check the compliance of the type of gas and pressure indicated in the sections 20 and 21  page 40  and in  the table o the boiler with the used type
35. e 27  it is necessary to make sure that the boiler is switched on and operates in the  heating mode or in the combined mode  and the smoke exhauster pipe has an orifice for the gas sensor  input on the straight section on a distance of not less than 250mm from the gas removal device outlet   During the combustion process analysis the water overheating protection system remains active  when  the water reaches the temperature of 88   C the boiler will pass to standby mode  After finishing the  measurements the gas sensor inlet orifice must be made airtight    10 3  Additional abilities  options    10 3 1  Connection of room thermostat   For more effective operation of the boiler it has a possibility to connect a room thermostat  that is  installed in the heated premise  In order to install the thermostat it is necessary to remove the plug  wire from the contacts 28 and 29  connector M10  from the room thermostat   s connector  see Annex  II  page 53  and place the cables with a terminal strip from the contacts 26 and 27 to the contacts 28  and 29  Then you must effect the connection of interconnecting wires of the room thermostat to the  terminal strip  the thermostat   s wires    connection polarity does not matter   The plug wire must be  given to the boiler   s owner so that he keeps it    The room thermostat is not included in the standard supply package and is purchased separately if  desired by the customer  The cable for connecting the room thermostat to the boiler is no
36. e that it is prepared for putting it into  operation in accordance with the installation and connection manuals that are included in the remote  control   s supply package     User   s manual    The remote control is not included in the boilers standard supply package and is purchased separately  if desired by the customer  The cable for connecting the remote control to the boiler is not included in  the remote control   s supply package and is purchased separately  The standard cable consists of a  connector for connecting the remote control to the electronic board  two wires 1 meter long and a  terminal strip for connecting the wires  If the cable is long enough  it is necessary to disconnect the  terminal strip and connect the cable wires to the remote control  see the instructions for the remote  control   If a connection wires    length of more than 1 meter is required  it is necessary to connect two  additional wires of required length to the terminal strip  herewith the wires must be convolved like a  twisted pair wire  The main requirements for choosing wires are  flexible copper multiple core cable  with cross sectional area of 0 5   1 5 mm   maximum wire length is 29 meters  plus 1 meter standard  cable     Technical staff manual  10 3 3  Connection of external temperature sensor    It is recommended to use an external  street  temperature sensor of the TPEB type  The sensor is  connected to the terminal strip of the room thermostat s connector  installed into the c
37. e the boiler operates only for the heating system  The boiler ignores the signal from the    is glowing  and the    flow sensor of DHW 15   see p 13 1  page 24   In this mode the symbol Mir is flickering on display  The  heating system temperature regulation range is 30   85   C    3 3  Additional functions   The boiler is provided by additional functions that may be used under several operation modes  These  functions provide additional safety and easiness in exploitation and in the boiler   s operation    3 3 1 Antifreeze function   The antifreeze function is an inserted safety system  which automatically launches the boiler in the heating  mode when the temperature when the temperature in the heating system reduces for less than   8   C and  switches the boiler off when the water temperature reaches the level of   30   C  This mode is activated  automatically in case if the following conditions are fulfilled    The boiler is connected to the electricity network and to the gas pipeline    The boiler is not in blocked position because of failure    The pressure in the heating system corresponds with the set parameters    3 3 2  Anti blocking function    User   s manual    The pump anti blocking function permits to exclude blocking of the pump shaft in case of the boiler   s long   term idleness  This function works only in standby mode  Once in 24 hours the pump is launched for 15  seconds    3 3 3  Boiler   s operation in heating mode with an external  outdoor  temperature 
38. ecessary  it will permit to reduce scum  formation in the heat exchanger  Before coming long term idleness of the boiler in winter time it is necessary to  drain the water from the heating system in order to avoid damaging the pipelines when it freezes    CAUTION  All boiler treatment operations must be effectuated only after it is disconnected from the network  and has cooled down     Technical staff manual  4 3 Operations effectuated at technical service  At technical service the following operations are effectuated   1  Cleaning of the burner assembly  burner    2  Cleaning of the heat exchanger from soot and cleaning  washing  the pipes from scum  if necessary    3  Replacement of grease retainers in the gas and water systems   4  Checking of the gas and water boiler systems air tightness   5  Lubrication of flexible joints  if necessary   it is recommended to use thick lubricant greases on  silicone base   6  Checking of safety devices  they must work without failures   7  Checking of air pressure in the expansion tank  once in 3 years   the pressure must be 1 bar   8  The air inlet system and combustion products outlet must be checked for air tightness   9  Water flow in DHW supply system must be enough for switching the DHW mode on   10  Checking of the heating system in order to detect stoppage   CAUTION  Technical service operations connected with disassembling of its gas or water pipelines  must be effectuated only after switching off the boiler completely  taps on 
39. electronic board provides voltage to the pump 19 and it starts operating      14  SEARCH FOR FAILURES AND THEIR ELIMINATION    13 5  14 1  Error codes  Stoppage of the boiler s operation  caused by the refuse or faulty operation of any of its systems  is accompanied  by an appropriate error code displayed on the boiler s control panel  see p  3 1  page 7  which facilitates fault  detection   possible reasons and methods of troubleshooting are presented below     Eu Reason of failure Troubleshooting    Open shut off valve on the pipeline  Failure of gas supply Check pressure in the cylinder  LPG  Address to gas service  Failure of ignition plug Replace a plug  mm    01    Table 4    Spark of electrode of ignition plug slips   in the place of ignition plug  on the shell of combustion chamber installation    Electric circuit of ignition plug is ree cucuitahd Pis  damaged  Wrong gap between ignition plug and 40 5  burner blade netata sapo  Defects related to the   Ignition plug is contaminated Wipe a plug from dust and degrease  taah tenon Failure of ionization plug Replace a plug    Bend a shell of combustion chamber  Boiler doesn   t operate     Electric circuit of ionization plug is  damaged    Wrong gap between ionization plug and 40 5  burner blade Install a gap  3  mm    Failure of igniter Replace igniter    Electric circuit of igniter is damaged Check electric circuit and pins  Clean a burner block  Burner block is contaminated Gemo T page 30   Electric circuits of gas sup
40. eplace gas supply regulator  Failure of modulator coil  resistance of modulator coil 80  of gas supply regulator Ohm     Boiler doesn   t work     Electric circuit    modulator coil  TES      i  Check electric circuit and pins  electronic board  is damaged      After troubleshooting it is necessary to push a button K6  RESET    see p 3 1  page7       After troubleshooting boiler starts up automatically     14 2 Other failures    Failures that don t have any code are displayed on the boiler s control panel  see p  3 1  page   as follows   Table 5    Reason of failure Troubleshooting  Lack of electricity Address to the service  Replace fuse on the board    Dry the board by means of warm air or leave  it for 2 days in a dry place for full ware  evaporation    Broken modulator coil of gas supply    regulator       Boiler doesn t switch on   Water entry on the electronic board    Electronic board failure De energize and re start boiler   RESET doesn t help  Replace electronic board    Minimal gas pressure and ignition Adjust minimal gas pressure  see p 11 4  page   power are wrong adjusted 23  and ignition power    PO     see p 13 3 1   page 26    Electrode spark of ignition plug slips Bend the ignition plug or shell of combustion   on the edge of burner section or the chamber allowing a spark to slip on the   shell of combustion chamber aperture area of the nozzles of burner section    Burner block is contaminated Clean burner Diooke   see p 16 1 1  page 32     Check all the gas 
41. f a tester   Pump starts working  noise of running pump is heard     2  Electronic board 22 inquires an air pressure switch 1  its pins should be open If they are closed  boiler   s staring  up stops    3  Electronic board provides voltage to the fan s electric motor 2  Fan starts working  it is heard   By means of  the air flow there is pressure difference created in the air pressure switch 1  To the electronic board a signal  about draught is provided  If signal is absent  boiler s starting up stops    4  A pause for ventilation of combustion chamber is hold  it is necessary for gas removal in case of previous fail  start up     5  igniter 23 by the signal of the electronic board provides high voltage to the ignition plug 6 within  10 seconds   sound of discharge is heard     6  electronic board provides a signal for opening a gas valve in the gas supply regulator 8  and gas is coming to  the burner block 5    7  if ignition happened  if casing is removed  you can see the flame through the viewing window   an ionization   plug11 sends a signal to the electronic board about successful ignition  If a signal from ionization plug 11 is   absent  electronic board repeats a procedure of boiler s staring up from the beginning  There are 2 consecutive  start up attempts taken  If both attempts failed  electronic board stops ignition    Electronic board changes voltage in the modulator coil of gas supply voltage 8  Gas supply regulator increases   gas supply to the burner block up t
42. f surrounding air    8 3  Connecting the boiler to the gas system     In accordance with p  7 SP 62 13330 2011  the connection of the gas line to the boiler should be made with metal  pipes  steel and copper  and heatproof multi layered polymer pipes  including also one metal layer  metallopolymeric  pipes   Multi layered metallopolymeric pipes can be used for inner gas pipelines at natural gas provision to one flat  domestic buildings not higher than 3 floors in condition if they are confirmed as acceptable for construction use  The  boiler may be connected to the gas pipeline by a flexible tubing  hose   resistant to transported gas at set pressure and  temperature  The inner diameter of pipes and hoses must be not less than 20 mm    In accordance with p  5 5 SP 41   108   2004 the flexible connections shall be not longer than 1 5 m  The hoses must be  installed in accordance with the instructions of their manufacturer      Remove cover plugs from connection pipes      nstall the gas filter and stop valve on the gas pipeline before the boiler     The gas valve must me easily accessible     Connect the boiler to the gas pipeline  Check that there are no gas leaks  Air tightness control is effectuated by means  of a soap solution bubble test on the joints or by other safe methods  Appearance of bubbles means that there is a gas  leak  The gas leak is unacceptable    8 4  Connecting the boiler to the balloon with liquefied gas    Before connecting the boiler to the balloon wit
43. gas and water pipelines  before the boilers must be closed  the boiler must be disconnected from the electricity network  5  STORAGE PRECAUTIONS   The boiler is made in climatic category UHL 4 2 under GOST 15150 69 standard    The boiler must be stored and transported in the package only in the position indicated on the handling  symbols     The boiler must be stored in a closed premise that guarantees protection from atmosphere and other harmful impacts  at air temperature from    50   C to  40   C and relative humidity not more than 98      n case of boiler storage for more than 12 month a conservation according to the GOST  9 014   78 standard    Inlet and output hoses orifices must be closed by cover plugs   6  GENERAL REQUIREMENTS  Installation  technical service and initial run of domestic gas facilities must be effectuated in accordance with local  requirements  more specifically           SNiP 1II 35   76   Boiler plants      SP 62 13330 2011   Gas distribution systems  Updated edition SNiP 42 01 2002      SP 41 108 2004   Door to door heating of domestic buildings with gas fueled heat generators     SNiP 41 01 2003 Heating  ventilation and conditioning      Regulation of fire safety in Russian Federation   PPB 01 03     PUE  Electrical Installation Regulations     Also it is necessary to pay CAUTION to the following moments     The boiler may be used with any type of heat exchangers  convectional stoves  radiators and convectors   and their  power system may be both 
44. h liquefied gas make sure that your boiler is set up for operation with  this type of gas  Otherwise it is necessary to effect the boiler s rendering to liquefied gas in accordance with section 12   page23      The balloon with liquefied gas must necessarily be equipped with a reduction unit with vapor phase stabilization  pressure of 2 9kPa and vapor phase capacity not less than 1 m  hour    CAUTION  Using reduction units with stabilization pressure different from 2 9 kPa IS PROHIBITED      The hose length for connecting the boiler must be not more than 1 5 m   the inner diameter  not less than 20 mm  The  gas supply hose must be resistant to the supplied gas at set pressure and temperature  The hoses should be installed in  accordance with the instructions of their manufacturer     Before the boilers inlet a stop gas valve must be installed  which must be easily accessible     After finishing the installation it is necessary to check the joints and the whole length of the connection hose in order  to detect a gas leak  see p  8 3    In order to avoid accidents it is PROHIBITED    1 To keep gas cylinders and lay hoses under direct sunlight  next to heat sources  heating stove  oven  heating  radiators  other heating appliances     2  To heat the cylinders by means of flame or heating appliances     User   s manual    3  To use damaged gas cylinders    It is recommended to keep gas cylinders in a special metal cabinet in order to limit access of children and unauthorized  per
45. ignition plugs with each  other  Sometimes low ionization current can be caused by inappropriate requirement of gas air mixture or appearance  of carbon deposit on the ionization plug while using a boiler    16 2 2 8 Checking of control devices for combustion products removal   Switch the boiler on  preliminary disconnect an exhaust flue from the boiler  Cover a hub  mounted on the fan   s  pipe with a metal sheet  Boiler should switch off and display a symbol  03  which signals that boiler stops operating  because of the draught lack in the exhaust flue    After eliminating the reason of boiler   s emergent switching off  and also realizing the blockage by means of the  button K6  RESET   boiler should automatically switch on  After performing such checking  it is necessary to mount  the exhaust flue back ensuring the joint air  tightness     16 2 2 9Checking of CH temperature sensor  Before switching the boiler on  disconnect the cables from the CH temperature sensor 10  see p 13 1  page24    When trying to start up the boiler in CH mode  it should display a symbol  05  which signals about the refusal of CH  temperature sensor to operate   After eliminating the reason of boiler   s emergent switching off  connecting cables to the sensor back  boiler  should automatically switch on   To check the temperature sensor  measure its resistance  R 10 kOhm  at 25   C      16 2 2 10 Checking of DHW temperature sensor  Before switching the boiler on  disconnect the cables from the DH
46. iler operating in the DHW mode  Ml Boiler in the heating standby mode Boiler operating in the heating mode       RESET   Error code  reset request       Error code  technical service  required       Parameter programming  see p 13 3 1  page26     Parameter number displayed Parameter value displayed              9  Remote control is connected Remote control connection error                3 2  Boiler operation modes  The boiler can function in the following modes    Standby mode  see p 3 2 1     DHW mode  see p  3 2 2     combined mode  see p 3 2 3  page9     heating mode  see p 3 2 4  page9    When the boiler is connected to the electricity network  it automatically sets up to the mode in which it was  before being switched off from the network  Change of boiler s operating mode is effectuated by pressing the  K5 button on the boiler s control panel  see p 3 1  page7   Below the sequence of the boiler   s operating modes  change is represented                                         User   s manual        PexuM  OTOMICHHA        KOM  HHHpOBAHHbI    peknuM        DHW mode Combined mode Heating mode    Scheme 3  Sequence of the boiler s operating modes change     3 2 1 Standby mode    In the standby mode  when the boiler is waiting for the user s commands  the symbol    is shown on  display  The boiler is not in operation  but the possibility of switching on the antifreeze functions  see p 3 3 1   page9  and parameters programming  see p 13 3 1  page 26  remains    3 2 2  DHW m
47. imum acceptable pipe length is 4 m  Each branch pipe 90  is equal 1 m pipe  each knot bend 45      0 5 m  pipe    Use branch pipes at pipe s turn points  The amount of 90  turns must not exceed three  including the branch pipe at  the boiler s outlet      User   s manual    1   boiler   2   coaxial branch  pipe   3   coaxial smoke  exhauster pipe   4   joint sleeve   5   duct slice   6  laying   7   ventilator plug   8   thermoinsulation       Scheme 5  Installation of coaxial smoke exhauster    9 2  Installation of separate pipes of smoke exhauster and air duct  Connecting separate pipes to the boiler is effectuated with a transitional set KHG 714061510  not included  into the boiler   s supply package  or a channel separator 8023 10 000  not included into the boiler   s supply  package    The transitional set   s and the channel separator   s construction provides regulation of amount of  combustion inlet air with a butterfly damper  The amount of inlet air depends on pipe length and is defined  with the help of gas sensor  It is necessary to turn the butterfly damper clockwise  reducing the amount of  inlet combustion air  until the gas sensor detects the increase of CO level  more than 0 05   in smoke  gases  After this you should turn the butterfly damper invertedly and fix   Using separate pipes it is necessary to additionally take into account the following    The total maximum pipe length must not exceed 25 m  Each 90   branch pipe is equal 1 m pipe  each knot bend 45
48. in it and keep it safely for further use   Best regards   Armavirskiy Plant of Gas Equipment Ltd     Telephone number of the unified technical support Service 8 800 555 40 35   free call on the territory of Russian Federation  working hours of the service  Mon Fri 09 00 17 00 Moscow     Boiler installation is allowed only in non living premises with the temperature not less  5   C in strict adherence to the  Gasification project  SP 62 13330 2011    Gas distribution systems  Updated edition of SNiP 42 01 2002     SP 41 108   2004    Door to door heating of domestic buildings with gas fueled heat generators  and SNiP 41 01 2003 Heating   ventilation and conditioning     All installation and mounting works  the instruction of the owner  preventive servicing  failure correction and repair  are effectuated only by a specialized service organization    The boiler is not unappropriated for use for people  including children  with low intellectual abilities or in default of  life experience    The responsibility for safe exploitation of the boiler and its maintenance in appropriate condition is on its owner  Non   compliance with the safety measures and installation rules  rules of use and technical service  stated in this manual   can cause boiler s breakdown  fire  burn  gas poisoning or poisoning with carbonic oxide  CO  and electrical shock     Armavirskiy Plant of Gas Equipment Ltd  Is constantly working on improvement of output products and  reserves the right for insertion of
49. ion    18  jumper  choosing gas type      19  connector of mounting a PC for boiler operating diagnostics    20  ground socket   21  fuse  2 pcs for 2 A    22  Zone controlling zone  option        If a room thermostat 13 is not present  close pins of connector M10  intended for its connecting      While adjusting boiler on LPG  close by means of jumper 18 pins BC of connector CM1  while adjusting on NG  close by a jumper pins AB    see wiring instruction      User   s manual               R  5  ay        t a  tt    ze    Le  ere l E  3 s         d   s g    Li  E 92  e  a  o g  T 5 or         amp      yo A2          Py  Boilers wiring    diagram   BaltGaz o o  NEVALUX 7224    N    20    rrr  7  p   7 8       9 E      gt      a  uU  i  e E    e 5  215  a    g    ex a  e        e     o    z  id o  ES  c eo  ES  a E  T e 7  6 T 1    pd       Cables colors designation   0e1     white  r     blue  x 3     yellow green  Kop     brown  kp     red  op     orange  u     black     omm ddl 7  oversupply   M  Fan    Power supply Power cable 220 V    50 Hz       E  M4 pine Main cable 220 V    50 Hz  13  um M3 S Pump s cable 220 V    50 Hz  S       j        brown   4  o brown Main cable 220 V    50 Hz  11 blue    Gas supply regulator       Modulator coil of gas supply    19 Gas supply 17V  180 MA    User   s manual         Mad regulator seabed        Air pressure switch 24V  10 MA  cable  Air pressure switch 24 V  10 MA  cable  Gas supply   31v toma   md   regulators cable  Gassupply   ziv 
50. iona  regulator   s cable  oe okomi  2    DHW Temperature 10 kOhm  sensor cable  at 25   C     Ionization plug cable MEE  Ignition plug sensor 12kW    24 V  10 mA    regulator    igniter    ret l e l a  ON  tAn oo    Thermo relay 95   C   water overheating sensor     Air pressure switch  Water flow DHW    Temperature sensor CH  Temperature sensor DHW    Ionization plug HE       Ignition plug    Room thermostat  option  see    p 10 3 1     Remote control   option  see p 10 3 2     Outdoor temperature sensor   option     see p 10 3 3     PC for diagnostics   option  see p  10 3 4        Zone control board  option   see p 10 3 5     
51. itching off  installing cables of the pressure sensor back    boiler should automatically switch on     User   s manual    16 2 2 2Checking of water overheating protection in the heating system  From the operating boiler to put the cables off from the thermo relay 9  see p 13 1  page 24   Boiler should switch  off and display a symbol  02   After eliminating the reasons of the emergent switching off  connecting cables to the  thermo relay back  and pressing a button K6  RESET    boiler should automatically switch on     16 2 2 3Checking of bypass valve operation  When the boiler is working in the heating mode  see p 3 2 4  page 9  it is necessary to shut off a stop valve on the  heating system inlet  Bypass valve 12  see p 13 1  page 24  should direct water bypass from the heating system  through the bypass pipe  After checking it is necessary to open a stop valve on the heating system inlet     16 2 2 4Checking of safety valve operation  Checking of safety valve operation 17  see p 13 1  page 24  implies turning the knob on the valve to the left   counterclowise  in order to let water ejection out of the valve  The valve should close by itself     16 2 2 5Air removal valve checking  If a cap of the air removal valve 20  see p 13 1  page 24  is open  there shouldn   t be water leakage  Via the valve  only air should be removed     16 2 2 6Checking of gas supply regulator operation   Set water temperature in the heating system 50   C  During the boiler   s operating it is nece
52. k electric circuit and pins    Draught absence    Boiler doesn   t operte  Faulty air pressure switch  pins of    pressure switch should close at pressure   Replace air pressure switch  drop from 130 Pa     iion l Remove condensate out of air  Condensate in air pressure switch tubes A  pressure switch tubes  ME IIpoBepure   1ekrpuueckyro rer H  Electric circuit of fan is damaged PoBep P pM  KOHTAKTBI    Failure of fan Replace fan    Make CH water pressure up to the  Low water pressure in CH recommended value  see p 10 1   page 19     A i Open air duct valve  Lack of water pressure in   Air Toek in the heating system    see p 16 2 2 5    page 34   CH Failure of CH water pressure sensor  Boiler doesn   t work     Failure of pump or air duct valve Replace pump or air duct valve    Check connector pins in the control  Electric circuit between pressure sensor   block and sensor and electric circuit  and electronic board is damaged of a sensor    Failure of CH temperature sensor Replace CH temperature sensor    Electric circuit    temperature sensor   electronic board    is damaged Check electric circuit and pins    Failure of CH temperature  sensor   Boiler doesn   t work      Failure of DHW Failure of DHW temperature sensor Replace DHW temperature sensor    temperature sensor Boiler  Electric circuit between DHW  works in heating mode   temperature sensor and electronic board   Check electric circuit and pins  only         User   s manual    Reason of failure Troubleshooting    R
53. kets  rubber gaskets should be lubricated with the silicon oil    5  Check the joints of gas and water subject to disassembling on leakage  see p 16 2 1  page33      16 1 2 Internal cleaning  washing  of heat exchanger  While applying heat exchange there is a chance of scale appearance on heat exchanger   s 4  see p 13 1  page24   inner surfaces   To remove scale it is necessary     1  Demount the heat exchanger  see p 17 2  page37  and put it into a container    2  prepare 10  solution of citric acid  100 g of powdered citric acid for 1 liter of warm water     3  Fill this solution into heat exchanger   s tube    4  Keep this solution there for 10 15 minutes  then drain it and wash heat exchanger   s tube  coil   thoroughly with water and if necessary to repeat all the procedure    5  Mount the heat exchanger with new gaskets    6  Check the joints of gas and water subject to disassembling on leakage  see p  16 2 1   page 33      Also it is necessary to clean DHW filter  It is located in the DHW flow sensor and can be demounted by means of  corkscrew or any other instrument     16 2  Boiler s operation check   At every boiler s service it is necessary to check    1  Constant voltage regulator presence    2  Voltage and frequency of inlet current in the boiler in accordance with indicated technical requirements on the  data plate  see p 2 2  page5     3  Whether NG is supplied with the rated pressure 1 3 2 0 kPa  130 200 mm of water column  or LPG with the  rated pressure 2 9
54. line on air tightness  see  Smell of gas Gas leakage p 8 2  page13    Remove gas leakage    Lack of inlet DHW water pressure Address to the Housing and Public utilities  Little hot water output service  or its absence Water filter is contaminated Clean the filter on DHW line    Heat exchanger is contaminated Ceara ezohi  8  see p 16 1 3  page 33     Increase water flow through DHW or mix  Set hot water temperature  High temperature of inlet water how water with cold and don   t let flow  is not maintained reduce through DHW     too high  Little water flow through DHW line Increase water flow through DHW    Jumper of the room thermostat is  absent Install a jumper of the room thermostat    Claps in burner    Boiler doesn t work in  CH mode   but works in DHW     Room thermostat   s jumper connecting  pins 28 and 29 is failed  cm  Annex Replace a jumper of a room thermostat  IMI  page 53     Failure of room thermostat  if it is     Replace a room thermostat  installed   Inlet water temperature Clean temperature sensor from scale  if dip  in the heating system is   temperature sensor is used  E SY Failure of CH temperature sensor p    lower than the set one  Replace temperature sensor       User   s manual    Reason of failure Troubleshooting    Boiler is in stand by  mode  a symbol        is    Restore power voltage in range 190   250 V   Within 30 seconds will be automatic boiler   s   Power voltage is over 190   250 V start up in the previous mode that boiler used  to be befo
55. lt a ooo 4     10 30 50 70 90 110 130 150 170 190 210 230 250 270 290 310 330 350    EMKOCTb CHCTeMbI HCHTDaJIbHOTO OTOILICHHA  dor     Central heating system capacity   dm    Expansion tank full capacity   dm  Starting pressure in the expansion tank    In case  volume of the tank is between tyschemeal values  when choose  follow by the rule    first is larger     In the boiler is installed a vessel with a volume 6 dm       If after calculating it will turn out that for such heating system it is necessary to have an extension tank of bigger  volume  it is necessary to install an additional extension tank  where its value will be equal to the difference between  calculated value and volume of the boiler s extension tank  6 dm     For instance  according to the calculation  the heating system requires to install an expansion tank with a volume 6  dm     i e  13     6   7 dm     Consequently  it is necessary to install additionally a vessel with a volume 7 dm  On the  monograph you should choose the next bigger standard expansion tank with a volume 8 dm        User   s manual    Annex III  1  Ignition plug   2  igniter   3  gas supply regulator   4  fan   6  pump     7   air pressure switch   8  thermo relay 95  C   9   modulator coil of gas supply regulator   10  pressure sensor   11  flow sensor TBC   12  temperature sensor  outdoor  option    13  room thermostat  ooption     14  CH temperature sensor   15  DHW temperature sensor   16  Ionization plug   17  Remote control  opt
56. matically  restored in the mode in which the boiler was before  before voltage comes outside the range 190   250 V     BOILER SERVICE  In order to provide long term and failure free boiler operation and to keep its operational characteristics it is  necessary to regularly effect the examination  treatment and technical service of the boiler   Examination and treatment must be effectuated by the boiler s owner   Boiler technical service can be effectuated only by a specialized service organization not less than once a  year  The recommended time for technical service if before the heating season   Boiler technical service might be required more often than once a year  in case of intensive work of the boiler  in a premise where there is much dust in the air or in case of higher water hardness  The unscheduled boiler  cleaning must also be effectuated also in case if in the premise where the boiler is installed there were  construction or reparation works and much construction dust and waste got into the boiler   CAUTION  Works connected with technical service are not warranty liabilities of the manufacturer  company and are effectuated by the customer s cost   4 1 Examination  Every time before putting the boiler into operation during the heating season once a day  it is necessary to   Make sure that there are no highly flammable objects next to the boiler or next to the smoke exhauster   Make sure that there is no smell of gas inside the premise  is the smell of gas in the pre
57. mise was detected you  must address to the gas facilities service   Make sure that there are no water leaks in the heating and hot water supply systems  in case if leaks are  detected you must address to a special service organization   Make an external examination of the smoke exhauster in order to detect damages  If smoke exhauster damages  are detected  you must address to a special service organization   4 2 Boiler treatment   The water filters of the heating and DHW supply systems must be cleaned regularly  especially before the  beginning of the heating season  The DHW filter must also be cleaned at water flow reduction in the  DHW supply line     User   s manual      The air from the heating system must be removed from time to time  see section10  page19      The heating system must be filled with water until the needed pressure is reached  see section10  page19      The boiler must be kept clean  for this it is necessary to remove dust from the boiler   s front surface regularly  and also  to clean the boiler   s coating first with a wet wiper and then with a dry wiper  In case of bigger dirtying you should first  wipe the boiler   s coating with a wet wiper  moistened in a neutral detergent  and then with a dry wiper  It is prohibited  to use detergents of heightened effect and containing abrasive particles  gasoline and other organic solvents for  cleaning the coating   s surface and plastic details     CAUTION  Do not change the water in the heating system unless n
58. mm of water column  for LPG  In other case to adjust pressure by an adjusting screw C while keeping an  internal screw B from turning over     11 4 Regulating minimal pressure    1     2     3   11 5  1   2   3   4   5   6   7   8     Disconnect a cable from the terminal E  boiler will render to the minimal power and on the display will be  mapped an error   07    see p 14 1  page 29     Check gas pressure in the control point A  It should be 0 15 kPa  15 mm of water column  for NG and 0 3 kPa   30 mm of water column   for LPG    In other case to adjust pressure by turning the adjusting screw b  while turning over an external screw C   Connect cable to the terminal E     End of operation   switch the boiler off    disconnect manometer and wrap a gauge in the control point A until bumping   put a plastic cap on the adjusting screws C and b    Switch the boiler on and render it to the CH mode  see p 3 2  page9     check the gas leakage in the control points A and B  see p 11 2  page 22    render the boiler into a stand  by mode consequently pushing a button K5   install a front panel and fix it by means of 6 self threading screws    close a cover of the front panel     12  RENDERING A BOILER TO ANOTHER TYPE OF GAS   Type of gas  which a boiler is adjusted to  is indicated on the boiler body   s data plate and user   s manuals  see  section20  page 40     To render a boiler to another gas type it is necessary     1   2     3     4     5     6     7     8   9     User   s manual 
59. moval valve   Checkin on C 34  16 2 2 6  Checking of gas supply regulator   OperdtlODt eno Le ei roe IR t ETE n e a ate cae bas ee da ev a tee asec o a bre ta ete eee eerte 34  16 2 2 7  Ionization plug   chec D og Pee cheesy cosets ovata lates te Fal ON O 34  16 2 2 8  Checking of control devices for combustion products   removal  A n engen e eat e uet eR cdd he reda do ge e IE ie heehee ete sede 35  16 2 2 9  Checking of CH temperature   SOS RP AR 35  16 2 2 10 Checking of DHW circuit temperature   O ia tete tee Utt ob E Lee e HEEL ede PL RP E UE EU OR AERE EE E EET S PE EUR E Gogh etie Head Lo E e TTT 35  16 2 2 11  Checking of flow sensor of hot water supply    oir e EIL 35  16 2 3  Checking of water pressure in the expansion    Pul S NN 35  16 2 4  Checking of the air inlet and combustion products output system s air   tig htnesszii ut E GG m eee roe UR Ug AR ge LUCI C E Pe toe E ere e 35  16 2 5 Checking of water consumption in   DEW  aieo dep eee o eed ete nd iet ab T Od abe aed cat e adeb tied RE end pde 35    16 2 6  Checking of heating system s with respect to its  o5 IC HUI 35    User   s manual    17  BOILER   S DISASSEMBLING AND DISMANTLING OF MAIN    BEOQGCHKS    aee DR Se ys Seeded a  ed ipto te eee Aa edie SE GA ale ee li 36  17 1  Burner assembly   dismi pde Ade atoll ee a ces ee atte 36  17 2  Heat exchanger   Cistman thingy OOO NN 37  13  Pump dismantling  inci HR Re etn edel Re ah edo e d rede 37  17 4  Bypass valve   dismantling   Ee et e e ta iio 38  17 
60. ng 005   008   19   2 2 GOST 9833 73 or a sealing laying with inner diameter 5 mm and external diameter 8   10  mm  material paronite      4 pcs     The channel separator installation sequence     Unscrew eight screws 1 and take off the duct slice 2  see Scheme 7         Scheme 7  Duct slice dismantling 2  install the laying 1  supplied together with the boiler   See Scheme 8            Scheme 8  Plug and laying installation    User   s manual    3  Make sure that the sealing ring 6 is placed  at the place of connection of the ventilator plug  before  installing the separator onto the boiler  see Scheme 9     4  Install the channel separator 2 onto the boiler  controlling that the plug won   t    bite on    the sealing ring 6   see Scheme 9     5  Fix the channel separator by four screws 3  previously install first the plain washer4  and then the ring 5 on  each screw   see Scheme 9     6  Make sure that there are sealing rings 7  2 pcs   placed on the inlet and outlet of the channel separator before  further installation of the smoke exhauster and air duct pipes  see Scheme 9     7  The installation of the air inlet pipe and the smoke exhauster pipe must be effectuated in accordance with    Scheme 6  see p 9 2 1  page16            1  Boiler  4  plain washer 5 3x10 DIN 125  6  sealing ring  2  Channel separator 5  ring 005 008 19 2 2 GOST 9833 73  7  sealing ring  3  Screw Ph   4 8x60 DIN 7981     Scheme 9  Channel separator installation scheme    User   s manual    Technical
61. nnels of the burner blade    6  Wash a burner in soup water  particularly spaces of its sections by means of the brush cleaner  thoroughly   wash it in running water  dry and then put it back    7  Check joints on leak proof subject to disassembling  see p 16 2 1  page 33     8  Check if ignition plug is on the distance 5 9  mm above the burner blade    9  Check if ionization plug is on the distance 3      mm above the burner blade   It is necessary to check whether burner s sections and nozzles are not damaged     User   s manual    External cleaning of heat exchanger   In order to improve gas combustion and to achieve maximum heat exchange in the appliance  it is necessary to  keep finning of the heat exchanger 4  p 13 1  page 24  in order  If heat exchanger is contaminated  it is necessary to  clean its surfaces where soot has appeared    Before disassembling it is necessary    1  Switch the boiler off    2  Close CH inlet and output taps    3  Cover pump and other electrical  electronic  appliances with the foil against water entry    4  Drain the boiler    To remove the soot it is necessary     1  To disassembly the heat exchanger  see p  17 2  page 37  and put it into soap solution or any other  synthetic detergent    2  Keep it in the soap solution for 10 15 minutes and clean the top and low surfaces by means of the soft  brush  then wash under strong current of water    3  Repeat above mentioned process again if necessary    4  Maintain heat exchanger with the new gas
62. o maximal power in order to quickly warm the water in the heating system   up to the set temperature    Electronic board equals a signal of CH temperature sensor 10 with a value set by the user by means of buttons   K3 u K4  see p  3 1   page7   If the difference of set temperatures is more than 1   C  electronic board changes   voltage on the gas supply regulator in order to change gas supply to the burner block in accordance with CH   requirement     13 4 2  Boiler s operation in DHW    1  DHW flow sensor 15 sends a signal  see p 13 1  page 24  about presence of water flow in DHW    2  Electronic board inquires air pressure switch 1  its pins should be opened  If they are closed  boiler s start up  Stops    3  Electronic board provides voltage to the electric motor of fan 2  Fan starts working  it is heard   Air flow  creates pressure differences in the air pressure switch 1  A signal about draught presence is given to the  electronic board 22  If signal is absent  boiler s start up stops    4  A pause for ventilation of combustion chamber is hold  it is necessary for gas removal in case of previous fail  start up     5  igniter 23 by the signal from electronic board provides high voltage to the ignition plug 6 within   10 seconds   sound of discharge is heard     6  electronic board provides a signal for opening a gas valve in the gas supply regulator 8  and gas is coming to  the burner block 5   7T  if ignition happened  if casing is removed  you can see the flame through
63. ode   In the DHW mode the boiler is operating only for the DHW system  The boiler ignores the signals of the room  thermostat and the heating circuit temperature sensor 10  see p 3 3 3  page 9   If hot water is not used  the    symbol m is constantly shown on display  When hot water is used  the symbol m is flickering   The water temperature regulation range is 30   60   C    CAUTION  The possibility of set temperature support in the DHW mode is limited by the boiler s  minimal heating effect   8 9 kW  So in case of higher water temperature by the DHW supply circuit inlet   during the summer season  and its small consumption the temperature by the DHW supply circuit  output might be much higher than the set one  In order to reduce water temperature in this case you  need to increase its flow through the DHW supply circuit  This aspect of the boiler s operation is not a  failure and permits to save the principal possibility of the boiler s operation in DHW mode in given  conditions     User s Manual    3 2 3 Combined mode  In the combined mode the boiler operates both for heating and DHW  While operating in this mode the    symbols Mir and m are shown on display  If there is no water flow in the water supply line the    boiler operates in the heating mode  the symbol Mir is flickering and the symbol eA is glowing   If    Mir    hot water is used  the boiler automatically switches to the DHW mode  the symbol    symbol a is flickering      3 2 4  Heating mode  In the heating mod
64. of breath  nausea  vomiting and disordered motor   function may appear  The injured person may lose consciousness    In order to provide first aid at gas poisoning or combustion products poisoning it is necessary to    1  Bring the injured person outdoors into the fresh air    2  Call the ambulance    3  Unclasp clothes that constrain breath    4  Give household ammonia to smell    5  To cover warmly  but not letting to fall asleep   Prehospital service at electricity impact must be provided immediately  if possible at the place of the  accident  calling the ambulance at the same time   First of all the injured person must be released from the electricity impact as soon as possible  If it is  not possible to disconnect the electric installation from the electricity network  you should  immediately start releasing the injured person from conductive parts  using isolating objects   Releasing the person from voltage  you should use a rope  stick  plank or any other dry object which  doesn   t conduct voltage     Prehospital service after releasing the injured person depends on his state  If he is conscious  you should provide him  profound rest  not letting him move before the doctor arrives    If the injured person breathes very poorly and convulsively  but the pulse can be felt  you must immediately do the  mouth to mouth or mouth to nose resuscitation    In case if there is no breath you must immediately bring the injured person to a warm premise with fresh air and make  resu
65. onnector M10    see Annex III  page 53   It is necessary to control that the plug wire is installed in the room  thermostat s connector on the contacts 28 and 29  In case of connecting the remote control together  with the external sensor to the boiler it is necessary to remove the plug wire from the contacts 28 and  29 in the room thermostat s connector and give it to the boiler s owner so that he keeps it   The cable for connecting the external sensor to the boiler is not included into the sensor s supply  package  The main requirements for choosing the cable are similar to the requirements listed in p   10 3 1  The connecting instruction of the sensor is supplied together with it   10 3 4  Connection of a computer for diagnostics  The electronic board provides a possibility of connecting a stationary or portable computer for boiler  operation parameters diagnostics to the M7 connector  see Annex III  page 53   For this a special  program and an adaptor for connecting the electronic board with the computer is needed  presence of  COM port on the computer is necessary    10 3 5  Connection of several room thermostats  The electronic board provides a possibility of connecting several room thermostats additionally   located in different rooms of the house or flat  to the connector M8  see Annex III  page 53  through  the contacts 38 and 39 of the electronic board  For this a special zone control electronic board is used   not included into the standard supply package   The ins
66. output   Inlet air orifice  Output orifice for   mm 0100      60  combustion products  for coaxial                User   s manual       pipes           Inlet air orifice   Output orifice for  combustion products  for separate  pipes        mm    80     80             2 3  Overall and connection dimensions    100_  ggo       A  Heating circuit output I Cold water inlet G1 2    G3 4  b DHW output G1 2     B  Gas inlet G3 4    L  Heating circuit inlet G3 4 reverse   E  Safety valve connection pipe 016   O18 mm    Scheme 1  Overall and connection dimensions of the boiler    User s Manual    User   s manual    User   s Manual   3  USER   S MANUAL   3 1  Control Panel   The main control element of the boiler is the electronic board which controls all boiler   s operation  The   electronic board   s microprocessor collects and processes signal from the control and safety sensors  All   information about the boiler   s condition is displayed on the LCD display in real time operation mode    All control over the boiler is effectuated from the control panel  the appearance of which is shown on Scheme   2  If a remote control is connected to the boiler  than control is effectuated from it  the buttons of the control   panel are inactive           Scheme 2  Boiler   s control panel  In the left part of the control panel there is a pressure gauge  indicating the pressure inside the heating circuit   Water pressure in the heating circuit must be not lower than 1 bar  with pressure lower th
67. ply regulator CET z  Check electric circuit and pins  are damaged    Gas supply regulator doesn t work Replace gas supply regulator    Failure of thermo relay  normally closed  at temperature up to 95   C  Replace TEE    Check electric circuit and pins       User   s manual    Reason of failure Troubleshooting  Electric circuit of thermo relay is Giek cucuit  nd ping  damaged  overheat sensor     Heating system is contaminated Clean heating system    Failure of thermo relay  normally closed  at temperature up to 95   C  pe piace Menno Teddy         Open air duct valve  Air lock in the heating system  see p  16 2 2 5   page 34   Filter is the heating system is Clean the filter  contaminated    Check proper installation of the  Bypass valve is failed or wrong installed   details of bypass valve and replace it  if necessary    Dover doesnt works Replace a pump or air duct valve  Pump or air duct valve is failed  Faulty pump relay on electronic board Replace electronic board    Gas supply regulator doesn   t work Replace gas supply regulator      S Adjust gas supply regulator  see  Gas supply regulator is not adjusted section 11  page 22   Electric circuit of thermo relay is RGG O cucuit and pins  damaged  overheat sensor     Cod  e  Exhaust flue or air flow valve is Figure out a reason of contamination  contaminated and remove it  Electric circuit of air pressure switch is  03    Water overheating    Faulty leak tightness of air pressure Replace tubes  switch tubes  damaged Chec
68. r bears no responsibilities for failures caused by non compliance with the above   listed requirements  All activities  not complying with the above listed installation guidelines  may not only  cause the boiler s breakdown  but also create a life hazard     Technical stuff manual  9  SMOKE EXHAUSTER INSTALLATION  It is strictly prohibited to put the boiler into operation in case if the smoke exhausting pipe is not  installed  in order to avoid combustion products poisoning   The boiler has an air inlet duct for combustion and a combustion products outlet duct   what permits not to  use the air from the premise  Using different component parts  you may connect a coaxial pipe  see p  9 1  page 15  or two separate pipes  see p  9 2  pagel6  to the upper part of the wall hung boiler with further  output of them from the premise   Herewith the pipes must comply with the following requirements    The pipe must be made from non flammable material  resistant to mechanical deformations  not subject to corrosion   and fully airtight  It also must be protected from overheating  from inflammability and freezing     The joints of the smoke exhauster pipe must be made of thermoresistant material not subject to corrosion    The smoke exhauster pipe must be installed in a place available for service so that  in case of the pipe s damage  there  would be no hindrance for smoke leakage elimination   After installing the smoke exhauster  it if necessary to effect the following    To make sure 
69. r block dismantling   To disassemble a burner and manifold which are concerned to be the parts of the burner block it is necessary    1  Switch the boiler off  see p  10 4  page 21     2  Unscrew 4 self threading screws of casing fastening to the boiler s lowest panel    3  Remove the cap of front panel    4  Unscrew two self threading screws 1 and four self threading screws 2  see scheme 13  of fastening to the  front panel to the casing     2 ee     N           nr A  pn  NA           2       Scheme 13  Casing dismantling to the front panel   5  Throw a front panel with a cap down    6  Puta casing off pulling it up over yourself    7  Unscrew 4 self threading screws sealing cap   s fastening   8  Put acap off pulling it hard up over your self  When assembling take into consideration proper installation of   the cap   s sidewalls which should enter slots on the back side of the boiler    Caution  Ground cables are fixed under left low self threading screw of the sealing cap   s fastening  When  assembling ground cables  they should be mounted on their places and tightly fixed by the self  threading  screws    9  Unscrew 2 self threading screws 1  see scheme 14 of plate   s fastening with the plugs and put a plate off     User   s manual  10  Unscrew 2 screws 4  see scheme 14  of manifold   s fastening to the burner front bracket   11  By means of a turnkey 30 unscrew a nut 5 of the fastening of manifold to the gas pipe and put a manifold off     KRL KKK    L  A  a  r  a     
70. re the power voltage went over the  range 190   250 V    displayed but boiler  doesn   t react to the  pressed control buttons       15  HANDING THE BOILER OVER TO THE CUSTOMER    After mounting a boiler  a specialist of the service department is obliged to check boiler   s operating at minimal  and maximal power in all modes  see section 11  page 22   Gas supply regulator should be obligatory adjusted  see  section 11     After completion of installation and adjustment works  user should be instructed about boiler   s treatment    Y Safety precautions when applying the boiler    v Procedure of switching on off a boiler    Y Management of a boiler    Y    Treatment of a boiler performed by the user    In the section 22  page 41  of present user s manual should be indicated the instruction conduction  There should  also be a mark about boiler mounting     16  TECHNICAL SERVICE AND OPERATION CHECK    Technical service and operation check should be performed by a special service organization   Caution  Activities related to the technical service don t go under the warranty of company  manufacturer  and paid by the consumers   During annual technical service it is necessary to carry out the following   1  Cleaning of the burner block  burner  including wiping of ignition and ionization plugs  see p  16 1 1    2  Cleaning of the heat exchanger from soot and cleaning  wiping  of tubes of heat exchanger from scale  if  necessary   see p 16 1 2  p  16 1 3  page 33    3  Replace seals
71. roding metal  plastic and rubber parts of the  boiler  cannot be used    It is recommended to use SENTINEL X400 u SENTINEL X100  The purchased heating system cleaning  detergent must be used in accordance with the instruction attached to it    7 2 1 New heating system   The new heating system  before connecting it to the boiler must be cleaned from shavings  welding lubrication  burr and other undesirable materials that may have got inside of it at installation  using appropriate means for  it    7 2 2  Existing heating system   The existing heating system must be cleaned from accumulated dirt  rust and scale deposits  using appropriate  means for it    7 3  Selection of an additional expansion tank   The membrane type expansion tank  installed into the boiler is designed for connection of the boiler to the  heating system with a capacity of not more than 70 liters  If the boiler is connected to the heating system with  bigger water volume  it is necessary to install and additional membrane expansion tank  Indications on  selection of an additional membrane tank are represented in Annex II  page51      Technical staff manual   8  BOILER INSTALLATION   8 1  Mounting the boiler to the wall   The boiler must be installed in kitchens or other non living heated premises in accordance with the gasification  project  the set of rules SP 62 13330 2011  SP 41   108   2004 and Regulations of fire safety of Russian Federation PPB  01   03      in accordance with p  4 2 7  4 2 10 and 4 2
72. scitation before the doctor arrives     User   s manual    2  TECHNICAL DESCRIPTION  2 1 Boiler   s destination    The wall mounted double circuit heating boiler with forced water circulation and closed combustion  chamber   BaltGaz NEVALUX   7224    hereinafter referred to as    boiler     is produced according to TU  4931   011   26985921 2012  GOST R 51733 2001  GOST 20548 93     The boiler   BaltGaz NEVALUX 7224   is designed for heating leaving and non dangerous industrial  premises with an area up to 240 m   Also  the boiler is designed for domestic hot water  hereinafter  referred to as    DHW     heating for sanitary purposes     2 2 Technical characteristics                   Table 1  Boiler brand BaltGaz NEVALUX 7224  Gas type Natural G20   Liquified G30  Family  gas group 2 e  H   3 e  B P  Gas pressure in the duct kPa 1 3  2 0 2 9  Minimal heating effect kWt 8 9          Performance index at rated heating     90 0                User   s manual                                                                                                 power   not less than   Performance index at rated heating     87 0  power 30   not less than   Heating circuit  kWt 24 0  Rated heating effect   Rated heating power kW 26 7  Rated gas consumption M  h 2 95 1 00  Temperature regulation range  C 30   85  Operating water pressure MPa 0 1   0 2  Maximum water pressure MPa 0 3  Volume of inserted expansion tank   1 6 0   Air pressure in the expansion tank   MPa 0 1   Hot water supply
73. sensor   For an optimal temperature regulation in the heating circuit depending on external temperature it is  recommended to use an external  street  temperature sensor  The correction of water temperature in the  heating circuit is effectuated in accordance with the external temperature and regulation coefficient Kd  see  Scheme 4   The electronic boar automatically discerns the presence of an external sensor and effects the  temperature regulating function  At water temperature setting in the heating circuit the value of the Kd  coefficient is shown on the boiler   s control panel   s display instead of the temperature value  The regulation  coefficient may be set in a range between 0 and 9 9  Please see the recommendations on connection of the  external sensor in p  10 3 3   page 21     Kd 3 Kd 4 Kd 5       Tiourypa OTONNEHMA   C max    0     KOHTypa OTONNEHMA   C min    Kd 1    Kd 0   30  20  10 0  10  20 425    Tenewnaa C  T  external T  of the heating circuit    Scheme 4  Schedule of dependency of the temperature in the CH from the external temperature     User   s manual  3 3 4  Boiler   s operation at low  high source voltage  When the source voltage comes outside the range 190   250 V the electronic board renders the boiler into the  standby mode  At this moment the symbol     is shown on the boiler s display and the boiler does not react on  pushing the control buttons   In 30 seconds after voltage recovery in the range of 190   250 V the boiler s operation is auto
74. sons to them  Placing gas cylinder installations inside the building is unacceptable    8 5 Connecting the boiler to the power line   The boiler corresponds to the I class electric shock hazard protection  It is necessary to make sure that there is an AC  outlet of alternate current monophase network with rated voltage 220 V  50 Hz frequency and with an earth bonding  contact    In order to provide safety when power supply is beyond the range of 190 250 V the electronic board renders the boiler  to standby mode  see p  3 3 4  page 10     The boilers earth bonding must be effectuated following all earth bonding requirements in accordance with GOST  275770 0   87 standard  The earth bonding conductor is connected to the earth bonding screw on the boiler   s bottom  panel  marked with the symbol   by one end  and by the other end to the earth bonding loop of the premise where the  boiler is installed  It is prohibited to use water and gas pipelines and also the heating radiators for earth bonding  The  scheme of the boiler s electric connections is presented in Annex III  page 51     Note  It is recommended to effect the boiler s connection to the power line through a voltage stabilizer in order to  provide stable and failure free operation and also to prevent the boiler s breakdown because of power line surges   CAUTION  In case of power cable damage  in order to avoid danger  its replacement must be effectuated by a  specialized service organization    CAUTION  The manufacture
75. ssary to look after  temperature values on the display and also gas pressure value in the burner  see section  1  page 22   When displayed  temperature will be higher for   1 2   C than a set one  gas supply regulator 8  see p 13 1  page 24  should reduce gas  pressure in the burner  flame height will degrease     Before switch the boiler on  disconnect one of the cables of the modulator coil of gas supply regulator  An  emergency code  07  will blink on the display  which signals about regulator   s refusal to operate  After eliminating the  reason of boiler   s emergent switching off  connect cable to the regulator back   the boiler will switch on automatically     16 2 2 71onization plug checking   From the operating boiler to put a cable off from the ionization plug 11  see p 13 1  page 24   Boiler should  switch off and display a symbol  01   After eliminating the reason of boiler s emergent switching off  connect cable to  the ionization plug back  and pressing a button K6  RESET   boiler will switch on automatically    Flame detection is based on the principle of monitoring ionization current  Ionization current is measured by  micro ammeter  consequently connecting it to the circuit of ionization current  Optimal value of the ionization current  is 3   5 uA    Reasons of reduced ionization current can be the following    current leakage    low connection with the    ground     or wrong plugs connection  In this case it is necessary to replace cables of ionization and 
76. ssure is 1 5 bar    If the pressure is lower than 1 bar it is prohibited to put the boiler into operation    4  Switch the boiler on  not opening the gas tap  so that the pump completely removes the air from the  heating system  Herewith the pressure may reduce lower than 1 bar and the boiler will show the error 04   not enough water pressure in the heating circuit   In order to remove the error you need to press the  button K6  RESET   see p 3 1  page 7     5  Repeat the actions according to the points 1 4 until the pressure in the circuit stabilizes at the level of 1 5  bar  that will indicate that the air is fully removed  The installation of additional air output valves is  recommended at the upper points of the heating system for more fast and complete air removal    Before a test ignition of the boiler it is necessary to check whether    1  The boiler installation was effectuated in accordance with the requirements incicated in section 8   pagel3     2  The pressure in the heating system is 1 2 bar   the recommended pressure is 1 5 bar   If the pressure is  higher than 2 bar     the drain valve 13 must be opened  see p 13 1  page24   reducing the pressure for  1 5 bar  If the pressure is lower than 1 bar     the heating circuit feed tap 16 must be opened and it must  be closed when the pressure reaches the level of from 1 till 1  5 bar    3  The air inlet and air outlet pipes are installed and comply with the requirements of section9   page15     4  The power line s vol
77. t included  into the thermostat   s supply package  The main requirements for choosing the cable are  the cable   s  maximum length is 30 meters  it consists of two wires  flexible copper multiple core cable with cross  sectional area of 0 5   1 5 mm        10 3 2  Remote control connection   The boiler permits to use a remote control console  hereinafter referred to as    remote control    The  remote control has got an inbuilt temperature sensor and permits to control the boiler from a distance   not more than 30 meters from the boiler  and set the same commands as from the control panel  Also  the remote control permits to control the boiler   s operation  keeping the temperature set by the user in  the premise  The remote control is connected to the connector M8 through the contacts 40 and 41 of  the electronic board  see Annex III  page 52   While connecting the remote control it is necessary to  remove the room thermostat   s connector from the M10 connector and give it to the boiler   s owner so  that he keeps it  see p 10 3 1     It is acceptable to connect the remote control together with the external  street  temperature sensor   see p  10 3 3   Herewith the boiler regulates the temperature in the heating circuit either with the help  of the remote control   s temperature sensor  or depending on external temperature  see p  3 3 3  page  9   The remote control can display the street temperature value    Before connecting the remote control it is necessary to make sur
78. t of atmospheric precipitations      In order to avoid poisoning with carbonic oxide the premise where the boiler is installed must have the  ventilation providing air exchange of not less than one premise volume per hour   In case of long term idle state of the boiler in winter or if pipe freezing danger appears it is necessary to drain  the water out of the boiler and the heating system   Do not keep highly flammable and volatile substances  gasoline  solvents etc   in the premise where the boiler  is installed   At the boiler   s normal operation and when the gas pipeline is in good order there should not be the smell of  gas in the premise   IF YOU FEEL THE SMELL OF GAS     1   2   3   4   5   6     Close the gas supply tap  that it situated on the gas pipeline next to the boiler    Open the windows and doors in order to ventilate the premise  providing maximum fresh air inlet    Do not use electric appliances in order to avoid the appearance of spark    Do not use the telephone in a gas polluted premise   Do not smoke and do not use open fire  lighters  matches etc     Call the gas facility emergency operation service immediately   Usage of the boiler when it is out of order or non compliance with the above listed rules of exploitation   may lead to an explosion or fire  or poisoning with gas or combustion products    The first symptoms of poisoning are  heaviness in the head  strong palpitation  buzzing in the ears    swimming of the head  general weakness  Later scant 
79. tage and frequency correspond with the levels indicated in the table  see p 2 2   page 5     5  The type of consumed gas must correspond with the type of gas indicated in the boiler s manual and  the table on the boiler    6  There is no gas leak    7  The air outlet valve on the circulation pump is opened    8  The stop valves on the direct and reverse lines of the heating circuit are opened    9  The pump is not blocked  To find it out you may screw off the pump s cover plug and turn the pump  shaft back and forth several times  see Scheme 10      User   s manual    Scheme 10  Circulation pump check       Than screw the cover plug up tight  While effecting this operation water leaks from the pump are possible  after  installing the cover plug the rests of water must be removed from the boilers components  you must wipe them  also  check the boiler connection to the AC outlet of the monophase network of alternate current with rated voltage of  220V  50Hz frequency  with an earthbonding contact    10  Also check the heating system   s airtightness     CAUTION  Water getting onto the boilers electronic components is unacceptable     10 2 Check of combustion properties   The boiler permit to effect the heating performance parameters analysis not disturbing the boiler   s  settings  For this it is necessary to use the function of gas analysis  measuring of output gases  temperature and of the content of carbonic oxide in them   Before activating this function  see  p 13 2 2  pag
80. that in the smoke exhauster there are no narrowings in the smoke exhauster  and also that outlet  pipeworks of other boilers are not connected to it  It is acceptable only in case if the smoke exhauster is designed for  several users and is produced in accordance with local requirements    If the boiler must be connected to an existing smoke exhauster  it is necessary to make sure that the latter is clean  as  slag separation from the smoke exhauster s walls while the boiler is in operation might encumber the free outlet of  exhausted gases   In order to purchase the necessary parts and details of the smoke exhauster you should contact the trading  organization  effecting realization of accessories for the boilers    BaltGaz NEVALUX  in your region   CAUTION  It is prohibited to use ventilation channels for combustion products removal   9 1  Installation of coaxial smoke exhauster  Connecting the coaxial pipe to the boiler is effectuated by means of a connection set KHG 714101410  not included  into the supply package   which includes a coaxial branch pipe 90     a joint sleeve for connecting to the boiler s outlet  and laying  see scheme 5   If necessary the connection set KHG 714101610 can be used  not included into the supply  package   with a branch pipe 45      When using coaxial pipes it is necessary to additionally take into account the following     The slope of the horizontal part of the smoke exhauster pipe must be 3  towards the street or condenser  tank    The max
81. the water out of the boiler  see section 10 5  page21   if  there are not stop valves  drain the water out of the whole heating system      put a casing and cap off from the boiler  see p 17 1  page 36    by means of the turnkey 30 to unscrew two nuts 1  see scheme 15  and put the pipes aside     3   4     User   s manual       Scheme 17  Pump dismantling    5  unscrew on the low panel three screws of the pump   s fastening 1 and two screws 2 of bithermic manifold  fastening    6  disconnect a screw termination 3  see scheme  17  with the pump   s power cables out of the connector    7  put off a bracket 4 of pipe s fastening from the pump s pipe and put a pipe up    8  disconnect a fitting of manometer 6  by pulling a bracket of fitting   s fastening 5 out of the pump   s body    9  disconnect cables from the pressure sensor 7    10  put off a bracket 8 of CH output fastening and put it aside    11  unscrew screws 9 of bithermic manifold fastening 10 to the pump    12  dismount a bithermic manifold    13  Take out a pump by pulling it hard to the right and up     Assembly is performed in the reverse order     17 3 Bypass valve dismantling  To dismount a bypass valve it is necessary   1  switch the boiler off see p 10 4  page 21      2  block inlet and output stop valve in the boiler  drain the       water out of the boiler  see section 10 5  page 21   if z   there are not stop valves  drain the water out of the whole     heating system      3  puta casing off from the boiler
82. tie inu e CORR BUE t dee e e o at e et eere e eei ene 23  13  BOILERS FLOW CHARTS AND control BOILER S   OPERATION 5e eee teo t E TA e Ee eR tee Glad eee At eee e ERE P eed e AREE E dee sities 24  13 1  Flow chart of the boiler   BaltGaz NEV ALUX    y E A                      M   24  13 2  Main components  cuido etie tepore ed teet tote e eA iia ete ae ei 25  13 2 1  Control   SV SUC TN 25  13 2 2  Hydraulic   SVSLOTIE v  sioe de cocer EUER EP PERPE M E HH t PHP MERE ED IER O 25  13 2 3  Gas  Sy temi  ti HER UR IT Ue EU eed Le eg o e Rah A lee b SEE ee etu itd Ga ee 25  13 2 4  Smoke exhausting   SySteI Ds sio de amne dde eb eh rete tun aont oia b deba beg 25  13 2 5  Regulation   CEVICES 37 i552 LE                   25  13 2 6  Safety   CEVICES REL 26  13 3  Service functions  ae ee be A hei A eel tede en ee 26    13 3 1  Parameters programming  TUNCHON endete et thee o e Ge ley alt sal t Elan Fee er eii eti a E ne tt sect et te Let eode 26    User   s manual    13 3 2  Gas analysis    TUN COM    aee dene LS e oU ER Ge te Ae Ue eee A ae eas 27  13 4  Boiler s operating   VO SIG s rete er re REED UR ONERE ER ER EP RN ER ERR Ren ER ERNEUT D red petes 27  13 4 1  Boiler s operation in CH   ini T                                                                      O   27  13 4 2  Boiler s operation in DHW   Iu NA A NS E A A A teas mens ayouam maa Senses 28  13 4 3  Boiler   s operation in combined    S di ANDA A NAAA ESSE AAA Pohl Said 28  14  SEARCH FOR FAILURES AND THEIR   ELI
83. truction and cable for connecting the zone  control electronic board are supplied together with it   10 4  Switching the boiler off  It is necessary to switch the boiler off before starting reparation works or maintenance service  It is  recommended to switch the boiler off in the following sequence   1  To render the boiler to standby mode  consequently pressing the button K5   2  To disconnect the power cable plug from the AC outlet of the power line   3  To close gas and water taps   10 5  Water drain from the boiler s heating circuit  At heating circuit s elements dismantling it is necessary to drain the water from the boiler  For this  it is necessary to twist off the drain valve 13  see p  13 1 page 24    In case of long term idleness of the boiler in winter time or in case of pipeline freezing  danger appearance it is necessary to drain the water from the boiler and the heating system     11  BOILER S POWER REGULATION  Boiler s power regulation is made by adjusting gas supply regulator     Caution  To adjust a gas supply regulator by a non magnetic screwdriver only   Caution  To adjust a gas supply regulator or rendering boiler from one type of gas to another should be  performed by specialized service organizations only     1  Switch the boiler off  see p 10 4  page 21   and throw a cover of a front panel    2  Unscrew 6 self threading screws from front  panel   s support    3  remove a front panel with a cover    4  Put off a plastic cap from the regulating  screw C 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
mode d`emploi coup de pouce collaborateurs  SD series Digital ac servo system User Manual - Vs  Essedue 220 AFP      Copyright © All rights reserved. 
   Failed to retrieve file