Home

User`s Manual - Voltronic Power

image

Contents

1. The default value is 54 0Hz 64 0Hz reserved reserved Pr e Lr reserved 15 e 08 Bypass mode setting Interface Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected it s not allowed for running in Bypass mode under any situations Parameter 3 ENA Bypass enabled When selected Bypass mode is activated DIS Bypass disabled When selected automatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode e 09 Battery maximum discharge time setting Parameter 3 000 999 Set the maximum discharge time from 0 min to 999 min UPS will shut down to protect battery after discharge time arrives The default value is 990 min DIS Disable battery discharge protection and backup time will depend on battery capacity reserved reserved reserved e 13 Battery voltage calibration 16 Interface Parameter 2 Select Add or Sub function to calibrate battery voltage to real figure Parameter 3 The voltage setting range is from OV to 5 7V The default value is OV Parameter 2 you may choose Add or Sub to calibrate inverter voltage Parameter 3 The voltage setting range is fr
2. 11 None Overoad 43 mw High Inverter voltage 12 Nome S 3 9 Warning Indicator waring icon fashino arm ff o EPO enable Beeping every second Over temperature AE Beeping every second Charger failure Beeping every second Overload 3 times in 30min Beeping every second 20 4 Trouble Shooting If the UPS system does not operate correctly please solve the problem by using the table below Symptom No indication and alarm in the front display panel even though the mains is normal The icon an the warning code E P flash on LCD display and alarm beeps every second The icon A and BATT FAULT flash on LCD display and alarm beeps every second The icon A and OVER LOAD flash on LCD display and alarm beeps twice every second Fault code is shown as 43 The icon OVER UG lights on LCD display and alarm beeps continuously Fault code is shown as 14 the icon lights on LCD display and alarm beeps continuously Other fault codes are shown on LCD display and alarm beeps continuously Battery backup time is shorter than nominal value Possible cause The AC input power is not connected well EPO function is enabled internal incorrectly The external battery is connected or UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass After repetitive overloads the
3. PFO 9 6K 10K Online UPS Uninterruptible Power Supply System Version 1 00 Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully Table of Contents 1 SAFETY AND EMC INSTRUCTIONS oooooccocccoccoococccc rra 1 1 1 TRANSPORTATION AND STORAGE c0occocconconcnnnnonrannn nr 1 52 PREPARATI ON addt 1 LS e INSTALLAT ON A A A ev cmaeneunenietnta ss 1 1 4 PP tiie WARNING S id 2 ES OPERA O a a A O 3 VS A A A A 3 2 INSTALLATION AND OPERATION sincroniza 4 Zed VINPACKING AND NSPECIION E N T E a alias 4 ZN SPR en mR eT eee EY Oe eee ee eT ee OP 4 2 3 SINGLE UPS INSTALLATION crisi de a a LS ALS dd 5 2 4 SOFTWARE INSTALLATION e a dot A AS 7 3 OPERATIONS cisne 8 SL BUTTON OPERATION o A 8 32 LEDINDICATORS ANDO PAN lao 8 325 AUDIBLE ACA MS iio tenses 10 3 4 SINGLE UPS OPERATION cooccccncconccnnrcnnrrnnn ran rr rr 10 3 5 ABBREVIATION MEANING IN LCD DISPLAY sccceccccccccccccucecacecueecueecueenuuenueenueecueenunenuneeunenunenunecanenunenunenanenags 13 On SE NN E E E eee ET alee en adidas 13 3 7 OPERATING MODE STATUS DESCRIPTION secececcecececucceceeuacaceeuavseeeeavseeeuaveeeeuaeaeueuavaeeevavaeuevaveneevaveneeuanenenas 18 Sere AFAT sae ae ter eater pe mE a ola ORR ORE ELEN OO SORE OE ED o O
4. Test Up gt Press and hold the two buttons simultaneous more than 1s to enter escape the Mute Down Button setting menu CVCF mode means converter mode 3 2 LED Indicators and LCD Panel LCD panel BYPASS LINE BATTERY FAULT o O O O E gt LED indicators LED Indicators There are 4 LEDs on front panel to show the UPS working status Twod te bypass te mate Feat wss Se dP Ce a e wsm if ew STS eme o ae a o seyme o o a a o wem o ed CO e e e o ew Eo aoa l Note e means LED is lighting and O means LED is faded LCD Panel Backup Time Info Fault Info Input amp Battery Mute Operation Voltage Info Output amp Battery Voltage Info Battery Info 4 E Load Info Mode Operation Info Display Backup time information 5 TIN Indicates the backup time in numbers i E s sf tt H hours M minutes S seconds Fault information N Indicates that the warning and fault occurs BE Indicates the fault codes and the codes are listed in details in section 3 9 Mute operation Indicates that the UPS alarm is disabled Output Battery voltage information NN LI a Indicates the output voltage frequency or battery voltage IL uz Vac output voltage Vdc battery voltage Hz frequency DUTP Load information 7 Indicates the load level by 0 25 26 50 51 75 and 76 100 l SHORT Indicates the load or
5. button for at least 1s and then the buzzer will beep once The UPS will turn into Bypass mode NOTE 1 If the UPS has been set to enable the bypass output it will bypass voltage from utility power to output sockets and terminal even though you have turned off the UPS inverter NOTE 2 After turning off the UPS please be aware that the UPS is working at Bypass mode and there is risk of power loss for connected devices 2 In Bypass mode output voltage of the UPS is still present In order to cut off the output switch off the input breaker A few seconds later there is no display shown on the LCD panel and UPS is complete off 7 Turn off the UPS without utility power supply in Battery mode 1 Turn off the UPS by pressing OFF button for at least 1s and then the buzzer will beep once 2 Then UPS will cut off power to output and there is no display shown on the display panel 8 Mute the buzzer 1 To mute the buzzer please press the Mute button for at least 1s If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 9 Operation in warning status 1 When Fault LED flashes and the buzzer beeps once every second it means that there are some problems for UPS operation Users can get the fault code from LCD panel Please check the trouble shooting table in chapter 4 for details 2 Som
6. This is a product for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances 2 Installation and Operation There are two different types of online UPS standard and long run models Please refer to the following model table 6K Standard GKL Long run model model model model 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains e One UPS e One user manual e One monitoring software CD e One RS 232 cable option e One USB cable e One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts Please keep the original package in a safe place for future use 2 2 Rear Panel View Diagram1 6K 10K Rear Panel Diagram 2 6KL 10KL Rear Panel Diagram 3 6K L 10K L Input Output Terminal External battery connector RS 232 communication port Intelligent slot USB communication Emergency power off function connector EPO connector Cooling fan Input circuit breaker Input Output terminal Refer to Diagram 3 for the details O Se tet SS Se oe Maintenance bypass switch option 10 Output terminal 11 Grounding terminal 12 Utility input terminal 2 3
7. UPS is locked in the Bypass mode Connected devices are fed directly by the mains UPS is overload too long and becomes fault Then UPS shut down automatically The UPS shut down automatically because short circuit occurs on the UPS output fault has A UPS _ internal occurred Batteries are not fully charged Batteries defect Remedy Check if input cable firmly connected to the mains closed EPO circuit in to disable Set the position function Check if all connected well batteries are Remove excess loads from UPS output Remove excess loads from UPS output first Then shut down the UPS and restart it Remove excess loads from UPS output and restart it Check output wiring and if connected devices are in short circuit status Contact your dealer Charge the batteries at least 7 hours and then check capacity If the problem still persists consult your dealer Contact your dealer to replace the battery Check fans and notify dealer The icon Dana flash on LCD The UPS temperature is too display and alarm beeps every second high 21 5 Storage and Maintenance 5 1 Storage Before storing charge the UPS at least 7 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 5 2 Maintenance A The UPS system operates with
8. battery polarity is connected Wrong connection may cause permanent damage of the UPS e Make sure the protective earth ground wiring is correct The current spec color position connection and conductance reliability of wire should be checked carefully e Make sure the utility input amp output wiring is correct The current spec color position connection and conductance reliability of wire should be checked carefully Make sure the L N terminal is correct not reverse or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown 3 Operations 3 1 Button Operation gt Turn on the UPS Press and hold the button more than is to turn on the UPS ON Enter Button gt Enter Key Press this button to confirm the selection in setting menu gt Turn off the UPS Press and hold the button more than 1s to turn off the UPS OFF ESC Button gt Esc key Press this button to return to last menu in setting menu gt Battery test Press and hold the button more than 1s to test the battery while in Test Up Button AC mode or CVCF mode gt UP key Press this button to display next selection in setting menu gt Mute the alarm Press and hold the button more than 1s to mute the buzzer Mute Down Button Please refer to section 3 4 Mute the buzzer for details gt Down key Press this button to display previous selection in setting menu
9. the output is short Mode operation information OQ ooo Indicates the UPS connects to the mains I P Ea Indicates the battery is working AE A Indicates the bypass circuit is working BYPASS EA Indicates the Inverter circuit is working E Indicates the output is working Battery information Indicates the Battery capacity by 0 25 26 50 51 75 and 76 100 Indicates the battery is fault Indicates low battery level and low battery voltage Input amp Battery voltage information OOO Indicates the input voltage or frequency or battery voltage Y uz Vac Input voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Description Buzzerstatus Muted Bypass mode Beeping once every 2 minutes ves Yes Battery mode Beeping once every 4 seconds Fault mode Beeping continuous Overload Beeping twice every second Low battery Battery unconnected Over charge EPO enable Fan failure Over temperature Beeping once every second Charger failure Overload 3 times in 30min EPO status Cover of maintain switch is open Bus start failure Bus over Bus under Bus unbalance Inverter soft start failure High Inverter voltage Beeping continuously Low Inverter voltage Inverter output short circuited Battery SCR short circuited Over temperature Overload 3 4 Single UPS Operation 1 Turn on the UPS with utility power supply in AC mode 1 After power supply is connected co
10. E 2 Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if necessary 6 Put the terminal block cover back to the rear panel of the UPS A Warning Only for standard model e Make sure the UPS is not turned on before installation The UPS should not be turned on during wiring connection e Do not try to modify the standard model to the long run model Particularly do not try to connect the standard internal battery to the external battery The battery type and voltage and numbers may be different If you connect them together it maybe causes the hazard of electric shock or fire A Warning Only for long run model e Make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery breaker before installation A Warning e For standard battery pack there are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery breaker before installation NOTE Set the battery pack breaker in OFF position and then install the battery pack e Pay highly attention to the polarity marking on external battery terminal block and make sure the correct
11. N 20 5 9 WARNING INDICATOR ti ee eae e ee E AA eed abies 20 A TROUBLE SHOOTING usina 21 5 STORAGE AND MAINTENANCE iuris 22 Be Tee FORAGE scared tine ated A ea iat Ota ha ala A Oa lo i ath et Ort to 22 Br AEN E TAA ac T Cate Gee o ARATE oe 22 6 SPECIFICATIONS iccivansananconsi cis dn anar A A a aaa aaa aara Kaaa naaa Raai 23 1 Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit 1 1 Transportation and Storage A Please transport the UPS system only in the original package to protect against shock and Impact A The UPS must be stored in the room where it is ventilated and dry 1 2 Preparation A Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or nearby heater A Do not block ventilation holes in the UPS housing 1 3 Installation A Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not block air vents in the housing of UPS The UPS must be installed in a l
12. Single UPS Installation Installation and wiring must be performed in accordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Meda Wiring spec AWG ode a AA 2 o r r r MC NOTE 1 It is recommended to use suitable wire in above table or thicker for safety and efficiency NOTE 2 The selections for color of wires should be followed by the local electrical laws and regulations 5 Remove the terminal block cover on the rear panel of UPS Then connect the wires according to the following terminal block diagrams Connect the earth wire first when making wire connection Disconnect the earth wire last when making wire disconnection Input Neutral Output Line l Input Line Output Neutral Ground Terminal Block wiring diagram for 6K L 10K L NOTE 1 Make sure that the wires are connected tightly with the terminals NOT
13. d it will display total load level in LCD panel If it is necessary to connect the inductive loads such as a printer the in rush current should be calculated carefully to see if it meets the capacity of the UPS because the power consumption of this kind of loads is too big If the UPS is overload the buzzer will beep twice every second When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 80 of its nominal power capacity to prevent overload for system safety If the overload time is over acceptable time listed in spec at AC mode the UPS will automatically transfer to Bypass mode After the overload is removed it will return to AC mode If the overload occurs 3 times in half hour the UPS will be locked in Bypass mode UPS can transfer to Line mode only by manual restart At this time if bypass is enabled the UPS will power to the load via bypass If bypass function is disabled or the input power is not within bypass acceptable range it will cut off output directly 4 Charge the batteries 1 2 3 After the UPS is connected to the utility power the charger will charge the batteries automatically except in Battery mode or during battery self test It s suggested to charge batteries at least 10 hours before use Otherwise the backup time may be shorter than expected time The charging current can be changed from 1A to 6A via LCD or softwar
14. e Please make sure that the charging current is suitable to battery specification 5 Battery mode operation 1 2 3 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery voltage drops to the alarm level the buzzer will beep quickly once every sec to remind users that the battery is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and prolong the backup time If there is no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or power failure In Battery mode if buzzer sound annoys users can press the Mute button to mute the buzzer The backup time of the long run model depends on the external battery capacity 11 4 The backup time may vary from different environment temperature and load type 5 When setting backup time for 16 5 hours default value from LCD panel after discharging 16 5 hours UPS will shut down automatically to protect the battery This battery discharge protection can be enabled or disabled through LCD panel control Refer to 3 7 LCD setting section 6 Turn off the UPS with utility power supply in AC mode 1 Turn off the inverter of the UPS by pressing OFF
15. e warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 10 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Users can get the fault code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems If the problems can t be fixed please contact the distributor or service people immediately 3 For emergency case please cut off the connection from utility external battery and output immediately to avoid more risk or danger 12 3 5 Abbreviation Meaning in LCD Display Abbreviation Display content meann jo OC cre COMME 77 IO CO BEE 1 7 IT ow PA CT 3 6 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternatives Refer Parameter 1 to below table for the programs to set up Parameter 2 and parameter 3 are the setting options or values for each program Note Please select Up or Down button to change the programs or parameters Parameter 2 Parameter 3 Programs available list for parameter 1 o Output voltage O a e o CA a E A A A E r03 Voltage range for bypass e t SYP o4 Frequency range for bypa
16. hazardous voltages Repairs may be carried out only by qualified maintenance personnel Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Batteries may cause electric shock and have a high short circuit current Please remove all wristwatches rings and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing When replace the batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly deposed according to local regulation Do not open or destroy ba
17. hen input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode 18 Battery mode Bypass mode Battery Test Fault status LCD display Description LCD display Description LCD display Description LCD display Description LCD display When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery and alarm will beep every 4 seconds When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes gt F m gt a a S IP When UPS is in AC mode or CVCF mode press Test key for more than 1s Then the UPS will beep once and start Battery Test The line between I P and inverter icons will blink to remind users This operation is used to check the battery status When UPS has fault happened it will display fault codes in LCD panel ey ong nan I o Zz bal LLL Hz INPUT OUTPUT gt Ea Y A 19 3 8 Fault Code Faultevent_ Fault code Icon Faultevent T Fault code Kon Bus start failure AO roe Low Inverter voltage circuited Bus under 03 None Battery SCR short circuited 21 None Bus unbalance 04 None Over temperature 41 None Inverter soft start failure
18. nt can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide e Connect your UPS power module s grounding terminal to a grounding electrode conductor e The UPS is connected to a DC energy source battery The output terminals may be live when the UPS is not connected to an AC supply Before working on this circuit Isolate Uninterruptible Power System UPS Then check for Hazardous Voltage between all terminals including the protective earth AN Risk of Voltage Backfeed 1 5 Operation A Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF button and then disconnect the mains A Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Category C3 Category C3 Warning
19. ocation with good ventilation Ensure enough space on each side for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device as short circuit backup protection should be provided in the building wiring installation An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation Connect the earth before connecting to the building wiring terminal A Installation and Wiring must be performed in accordance with the local electrical laws and regulations 1 4 NConnection Warnings e There is no standard backfeed protection inside please isolate the UPS before working according to this circuit The isolation device must be able to carry the UPS input current External Distribution Panel UPS fi i 8 i i i G Legend a Coil Remote Switch Magneto Thermal Input Main Switch AC Contactor as backfeed protection device Neutral Line Input e This UPS should be connected with TN earthing system e The power supply for this unit must be single phase rated in accordance with the equipment nameplate It also must be suitably grounded e Use of this equipment in life support applications where failure of this equipme
20. om OV to 6 4V The default value is OV Parameter 2 you may choose Add or Sub to adjust floating charger voltage Parameter 3 the voltage range is from OV to 8V the default value is OV Parameter 2 you may choose Add or Sub to adjust constant charger voltage Parameter 3 the voltage range is from OV to 4V the default value is OV 17 eo 18 Maximum charger current setting Interface Parameter 3 The maximum charging current could be adjusted Default value is 4A for long run model and 1A for standard model The available options are 1A 2A 4A Parameter 2 Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Parameter 3 Set battery group range from 1 to 6 The default value is 1 group These parameters are for the battery backup time calculation Parameter 3 Calibrate the displayed backup time by adjusting this multiplier factor The formulation is listed below Displayed backup time Original calculated backup time x Multiplier factor The default value of multiplier factor is 1 0 and the setting range is from 0 5 to 2 3 7 Operating Mode Status Description Operating mode status AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode O gt E eg l CVCF mode Description W
21. rrectly set the breaker of the battery pack at ON position the step only available for long run model Then set the input breaker at ON position At this time the fan is running and the UPS supplies power to the loads via the bypass The UPS is operating in Bypass mode NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you Switch on the input breaker In Bypass mode the load is not protected by UPS To protect your precious devices you should turn on the UPS Refer to next step 10 2 3 Press and hold the ON button for 1s to turn on the UPS and the buzzer will beep once A few seconds later the UPS will enter to AC mode If the utility power is abnormal the UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto restart in AC mode 2 Turn on the UPS without utility power supply in Battery mode 1 2 3 Make sure that the breaker of the battery pack is at ON position only for long run model Press and hold the ON button for 1s to turn on the UPS and the buzzer will beep once A few seconds later the UPS will be turned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 2 3 4 5 Switch on the devices one by one an
22. ss O 05 Reseved o S S S 06 Reserved 07 Reseved MES ME FE IES S 08 Bypassmodesetting Y YJ 0 09 Battery maximum discharge time setting Y Y Y Y Y 40 Reseved o S S S S 13 u Reeved oo y a a a ST s iz Reserved o S a a a frese OO T a a 15 Inverter voltage Calibration v yv 16 Floating charger voltage adjustment Y Y Y Y Y 17 Constant charger voltage adjustment Y Y Y Y Y 18 Charger maximum current setting Y Y Y Y Y 19 Battery capacity and groups setting Y Y Y Y Y 20 Backup time calibration Y Y Y Y Y Y means that this program can be set in this mode e 01 Output voltage Parameter 3 Output voltage You may choose the following output voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac Parameter 2 Output Frequency Setting the output frequency You may choose following three options in parameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode Set
23. table Charging Voltage PHYSICAL Model Long run Model ENVIRONMENT 0 50 C 0 40 C Operation Temperature battery life cycle will be shorten when battery life cycle will be shorten when temperature is above 25 C temperature is above 25 C lt 95 and non condensing lt 1000m Operation Humidity Operation Altitude coustic Noise Level MANAGEMENT Less than 55dB 1 Meter Less than 58dB 1 Meter Smart RS 232 or USB Supports Windows imei aide Windows 7 8 Linux Unix and Optional SNMP Power management from SNMP manager and web browser Derate capacity to 60 of capacity in CVCF mode and to 90 when the output voltage is adjusted to 208VAC Tf the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated one percent per 100m Product specifications are subject to change without further notice
24. ting output frequency at CVCF mode or non CVCF mode You may choose following two options in parameter 3 CF Setting UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode non CVCF mode If selected the output frequency will synchronize with the input frequency within 46 54 Hz at 50Hz or within 56 64 Hz at 60Hz according to setting in parameter 2 If 50 Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not within 46 54 Hz If 60Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency 14 e 03 Voltage range for bypass Interface Parameter 2 Set the acceptable low voltage for bypass Setting range is from 110V to 209V and the default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V Parameter 2 Set the acceptable low frequency for bypass 50 Hz system Setting range is from 46 0Hz to 49 0Hz 60 Hz system Setting range is from 56 0Hz to 59 0Hz The default value is 46 0Hz 56 0Hz Parameter 3 Set the acceptable high frequency for bypass 50 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz
25. tteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards A Do not disassemble the UPS system 22 6 Specifications MODEL pK OK CAPACITY 6000 VA 5400 W 10000 VA 9000 W INPUT 110 VAC 3 at 50 Load 176 VAC 3 at 100 Load Voltage Range Low Line Comeback Low Line Loss Voltage 10V 300 VAC 3 High Line Loss Voltage 10V 46Hz 54 Hz O 50Hz system 56Hz 64 Hz 60Hz system Single phase with ground gt 0 99 at 100 Load U U gt oy un D 208 220 230 240VAC 1 46Hz 54 Hz O 50Hz system 56Hz 64 Hz 60Hz system 50 Hz 0 1 Hz or 60Hz 0 1 Hz nA n Wa lt 0 gt OA O CE 5 O 5 2 o y T yv 0 gt Q MD A eoa 100 110 30min 110 130 5min gt 130 10sec Battery mode 100 110 3min 110 130 30sec gt 130 10sec 3 1 max lt 3 THD Linear Load lt 5 THD Non linear Load urrent Crest Ratio Harmonic Distortion __ Line gt Battery 0 ms Transfer Time Inverter gt Bypass 0 ms EFFICIENCY gt 93 gt 91 gt 92 gt 90 Type amp Numbers 12VW 9Ahx16 12W 9Ah x 20 Recharge Time 9 hours recover to 90 capacity Charging Current Default 1 A 10 sl Max 1A 2A Adjustable C C mode attery Mode BATTERY onan Model Default 4 A 10 Max 1A 2A 4A Adjus

Download Pdf Manuals

image

Related Search

Related Contents

lecciones en pdf - Alumnos de Pablo Iglesias Simon  User Manual - OMEGA Engineering  TRACK TIMER USER MANUAL    Page 1 ISOMATE® OFM `IT ORIENTAL FRUIT MOTH PHEROMONE  売却希望物件掲載依頼書  

Copyright © All rights reserved.
Failed to retrieve file