Home
        Panasonic/Sanyo A/C Interface – Modbus RTU Installation Instructions
         Contents
1.                 Switch   switch value when ON  1 10  2 20  3 40  4 80             To get the Slave ID  add together the value for each switch set to ON  For example  to set  address 130  set switches 1  3 and 4 ON  1   4  8  x 10   slave ID 130     Please note  Each Modbus interface connected to the same BMS RS 485 network must be set to  a unique address and there must be at least 30 slave IDs between a converter and another  device  For example if the first is set to slave ID 10 the next converter  or other MODBUS device   should be set to 40 or greater     A C Gateway baud rate    The baud rate of communications used between the Modbus interface and A C Gateway can be  set to 19200 or 9600 baud using the 5  DIP switch                 Switch 5 A C Gateway  Baud Rate  OFF 19200  ON 9600               10      RS 485 Modbus baud rate    The baud rate of communications used between the Modbus interface and Modbus Master can  be set between 1200 and 115200 baud using the 6   7  and 8  DIP switch  9600 baud is set as  default                                Switch 6 Switch 7 Switch 8 Modbus Baud Rate  OFF OFF OFF 1200  ON OFF OFF 2400  OFF ON OFF 4800  ON ON OFF 9600  OFF OFF ON 19200  ON OFF ON 38400  OFF ON ON 57600  ON ON ON 115200                      Fixed communications settings    The following Modbus interface to A C Gateway communication settings are fixed and cannot be  changed        Adaptor address 0  Link 1    8 Data bits     Even Parity     1 Stop Bit     The followi
2.     Poor communication of group processing control caused by miswiring   Unused   Poor transmission of CCU to outdoor sub bus    Poor reception of CCU from outdoor sub bus    Poor setting of outdoor sub bus address   duplicated    Discord of number of outdoor sub bus units    Miswiring of outdoor sub bus    Misconnection of outdoor units    Poor reception of outdoor serial    Poor transmission of outdoor serial    Unused   Abnormal sensor for the inlet temp  on the heat exchanger of the indoor unit   Abnormal sensor for mid point temp  on the heat exchanger of the indoor unit   Abnormal sensor for the outlet temp  on the heat exchanger of the indoor unit   Abnormal sensor for the outlet temperature of the PC compressor   Abnormal sensor for the outlet temperature of the AC compressor   Abnormal sensor for the inlet temp  on the heat exchanger of the outdoor unit   Abnormal sensor for the outlet temp  on the heat exchanger of the outdoor unit   Abnormal sensor for outdoor temperature    Actuation of scroll compressor protective thermostat    Abnormal sensor for suction temperature of indoor unit    Abnormal sensor for discharge temperature of indoor unit    Abnormal sensor for cooling water temperature    Abnormal sensor for engine room temperature    Abnormal sensor for suction and discharge gas    Abnormal sensor for exhaust gas temperature    Abnormal sensor for compressor bottom temperature    Abnormal sensor for compressor 3 current    Abnormal sensor for discharge gas te
3.  MaC    technologies    Panasonic Sanyo A C  Interface     Modbus RTU  Installation Instructions    Preface    Safety warnings    To avoid injury  or damage to the Modbus interface  read all installation and configuration  instructions in this guide before installing     A  CAUTION    Do not expose to rain or moisture     Ax CAUTION  The installation and assembly of electrical equipment may only be performed by a skilled  electrician  improper installation by the user may result in electric shock or fire     Maintenance  This product contains no user serviceable parts     WEEE Directive   At the end of their useful life the packaging  product  and any battery should be disposed of by a  suitable recycling centre    Do not dispose of with normal household waste     Do not burn     Disclaimer    Warranty    All products manufactured by t mac Technologies Ltd are warranted against defective materials  for a period of one year from the date of delivery to the original purchaser     A  Warning   If the Modbus interface is installed in a manner other than that specified in these instructions  the  protection provided by the unit may be impaired  t mac Technologies Ltd assume no liability for  damages consequent to the user installer of this product  We reserve the right to change this  manual at any time without notice  The information furnished by us is believed to be accurate and  reliable  However  no responsibility is assumed by us for its use  nor for any infringements of  pat
4.  period  t mac at its option will either repair  using new or  remanufactured parts  or replace  with a new or remanufactured unit  the product at no charge     THE WARRANTY WILL NOT APPLY TO THE PRODUCT IF IT HAS BEEN DAMAGED BY  MISUSE  ALTERATION  ACCIDENT  IMPROPER HANDLING OR OPERATION  OR IF  UNAUTHORIZED REPAIRS ARE ATTEMPTED OR MADE  SOME EXAMPLES OF DAMAGES  NOT COVERED BY WARRANTY INCLUDE  BUT ARE NOT LIMITED TO  BATTERY LEAKAGE   BENDING  OR VISIBLE CRACKING OF THE PCB  WHICH ARE PRESUMED TO BE  DAMAGES RESULTING FROM MISUSE OR ABUSE     Product returns    Customers wishing to return products or other accessories to t mac Technologies Ltd  must first  call our office  0844 287 0007  and obtain a Return Authorisation  RA  number  RA numbers are  valid for 30 days from the date of issuance  and must be obtained within 30 days of purchase  date     Defective products are eligible for credit or replacement within 30 days of Customer invoice date   Replacements will be shipped upon receipt of defective merchandise via ground shipment at our  expense  unless customer requests an upgrade at their expense  Advance replacements are  available  but must be paid for at the time replacement ships  Shipping address will be provided  to customer at issuance of RA  Return shipping on defective merchandise may be reimbursed up  to the original shipping cost of the item  Packages must have RA number written visibly on  shipping box with a brief description of the product defect ins
5. N  RS 485 A C Gateway DC Power in and  interface RS 485 Modbus Interface    Figure 2  Modbus interface hardware overview    e 7      Mounting    The Modbus interface should be mounted next to  or near to the A C Gateway  Suitable space  should be provided all around the Modbus interface to allow for cable conduit and additional  equipment  The Modbus interface should be located so that it is easy to view the LED indicators     Enclosure dimensions    51mm 95mm    IA    Q N con    Figure 3  Modbus interface dimensions    Mounting points    83mm       lt         30mm       Figure 4  Modbus interface mounting points    Note  Appropriate wall fixings must be used       Be    Connecting power  The Modbus interface requires a 10 30VDC supply     10 30VDC supply should be connected to the terminal plugs indicated below        10 30VDC 10 30VDC  Supply Positive Supply Negative    Figure 5  10 30VDC terminal connection    A  DO NOT APPLY POWER YET     For troubleshooting information regarding powering the Modbus interface  see the  Troubleshooting chapter     Qe    Settings    There is a bank of 8 DIP switches on the Modbus interface which is used to configure the RS 485  Modbus slave address  and baud rate  and also the A C Gateway RS 485 baud rate     12343678       RS 485 Modbus slave address    Any Modbus Slave ID in the range 10     150 can be chosen using switches 1     4  The address is  set in binary multiplied by 10  where the switch positions have the following values       
6. ct current value for compressor 2   over current   Incorrect current value for compressor 2   locked compressor   CT sensor is dislocated from compressor 2  short circuit   Protective thermostat for scroll compressor 2    Protective thermostat for scroll compressor 2 is dislocated   No oil in compressor 2    Sensed unbalanced power voltage    Chattering of magnet switch 1  Espacio     Chattering of magnet switch 2     Defective sensor for crank case heater 2    Incorrect current value for compressor 3   over current   Incorrect current value for compressor 3   locked compressor   CT sensor is dislocated from compressor 3  short circuited   Protective thermostat for scroll compressor 3    Protective thermostat for scroll compressor 3 is slipped off   No oil in compressor 3    Incorrect connection of oil sensor 2    Incorrect connection of oil sensor 3    Chattering of magnet switch 3    Defective sensor for crank case heater 3    Unused   Incorrect address for indoor unit   No master indoor unit    Mismatch of indoor and outdoor units    Setting plural master indoor units for group control    Duplicate setting of system address  outdoor unit     Duplicate setting of priority indoor unit   for priority indoor unit   Duplicate setting of priority indoor unit   for other than priority indoor unit    Group control wiring to individually controlled indoor unit    No Setting of indoor unit address    No Setting of indoor unit capacity    No Setting of outdoor unit capacity    Mis wi
7. e summarised below        Register Name Register Type Description       Discrete Input Digital Input Read only register used for holding status information  which holds a value of 0 or 1  Can be read using  function code 0x02        Coil Digital Output Read and write accessible register which holds a  value of 0 or 1  Can be read using function code  0x01  Can be written using function code 0x05 or  OxOF        Input Register Analogue Input Read only register used for status information which  holds a 16 bit value  0 65535   Can be read using  function code 0x04        Holding Register   Analogue Output   Read and write accessible register used for status  information which holds a 16 bit value  0 65535    Can be read using function code 0x03  Can be  written using function code 0x06 or 0x10                      14      Native Modbus interface registers    The Modbus interface will provide the following MODBUS registers at the Slave ID specified by    the DIP Switches     Holding registers       Holding Registers  Analogue Outputs                       Register Name Location   Length Details   decimal   Converter State 0 1 Startup   2   Read   3   Write   5   Error   6    Write 0x55  85 decimal  to reset the  device        Input registers       Input Registers  Analogue Inputs                                         Register Name Location   Length Details   decimal   Number of indoor units 0 1 0 64  detected  Global Fault code 1 1 0 255  Firmware version 2 1 0 65535  A C Gate
8. ents or other rights of third parties resulting from its use     Copyright and acknowledgements    Copyright O 2012 by t mac Technologies Ltd  All rights reserved     t mac Technologies Ltd  Stand Park   Sheffield Road  Chesterfield  Derbyshire   S41 8JT   United Kingdom    Tel   44  0  844 287 0007  FAX   44  0  844 287 0006    Sales email  sales t mac co uk  Support email  support t mac co uk  Support telephone   44  0  844 287 0008  t mac website  www t mac co uk  t mac user web portal  www my t mac co uk    t mac   is a registered trademark of t mac Technologies Ltd  All other product names are  trademarks or registered trademarks of their respective owners     User Manual Part no  065 0057    User Manual revision  3 0 0    Contents    Preface   Safety warnings   Disclaimer   Warranty   Copyright and acknowledgements    Contents  Introduction  Unpacking    Installation  Overview  Mounting  Comnecting power    Settings   RS 485 Modbus slave address  A C Gateway baud rate  RS 485 Modbus baud rate  Fixed communications settings  RS 485 termination    Initial power on  Summary of Status indicators    Modbus   Modbus explained   Modbus register table   Native Modbus interface registers  System information   Indoor unit information    Troubleshooting  Technical specification    Appendix A  Manufacturer s 1 year limited warranty  Product returns    Appendix B  Fault codes    ceive    14  14  14  15  16  16    18  19    20  20  20    21  21    Introduction    Sanyo Panasonic manu
9. factures a Communication adaptor  A C Gateway  to allow their air   conditioning units to be controlled by an external Building Management System  BMS      The Sanyo  SHA KA128AGB  and Panasonic  CZ CFUNC2  A C Gateways have an RS 485 port  which allows them to interface with the Panasonic Sanyo A C Interface  Modbus interface  using  Panasonic Sanyo s proprietary S NET protocol  The Modbus interface will analyse the system on  power up and expose information over Modbus  The system will update the information  continuously and relevant air conditioning settings will have read write access while other  information will be read only     ede    Unpacking    The Modbus interface kit contains the following items       Installation   y User  Instructions       Modbus Interface    Figure 1  Kit content    Ge    Installation    This chapter gives step by step instructions for setting up a new Modbus interface installation     Overview    The Modbus interface has been designed to be installed in residential  commercial  light and  heavy industrial environments  The Modbus interface system should be installed in a manner that  complies with the Health and Safety Executive  HSE  Memorandum of Guidance on Electricity at  Work Regulations 1989     Modbus interface hardware overview    A C Gateway    Acknowledge      Indicator    RS 485 Modbus  _     Address and Baud  pa Rate DIP    Switches    Modbus  Acknowledge  Indicator             A BGND  V GNDAB    4 A  I    I         1 N  4 N  KA 
10. ide  All items must be returned in the  original packaging  t mac Technologies Ltd  is not responsible for any item not received at its  return address  Allow 14 21 business days for processing returns      20     Fault codes    Appendix B    The following list details how fault codes are reported by both the Modbus interface and a  Panasonic  Sanyo wall controller     Modbus Wall  interface Controller  32 Coo  33 Co1  34 c02  35 C03  36 C04  37 C05  38 C06  44 C12  48 C16  49 C17  50 C18  51 C19  52 C20  53 C21  54 C22  55 C23  56 C24  57 C25  58 C26  63 C31  64 E00  65 E01  66 E02  67 E03  68 E04  69 E05  70 E06  71 E07  72 E08  73 E09  74 E10  75 E11  76 E12  77 E13  78 E14  79 E15    Description    Unused   Poor setting on Control Address  duplicated     Discord of number of units in central process control    Miswiring of central process control    Misconnection of central process control    Transmission error of central process control    Reception error of central process control    Lump alarm by local adapter    Poor transmission of the adapter to the unit    Poor reception of the adapter from the unit    Duplicated control addresses in the adapter    Duplication of adapter addresses    Unused   Non volatile memory in the adapter is abnormal    Poor setting of adapter address    Faulty host terminal  software     Faulty host terminal  hardware     Abnormal processing of the host terminal    Communication error in the host terminal    Change of constitution  the adapte
11. imal value ZXX  Z   zone  XX   unit  Indoor Unit Address X02 1 Dependent on configuration eg   101  102  201  301    3016  Fault Code X03 1 0x00  system Ok    OxFF  Coils  Coils  Discrete Outputs   Register Name Location   Length Details   decimal   ON OFF status X00 1 0   Off  1   On  Filter status X01 1 0   Clean  1   Dirty                    16         Holding registers       Holding Registers  Analogue Outputs        Register Name    Location   decimal     Length    Details       Temperature Setpoint    X00    Value to write    Setpoint   35    2  255  OxFF    92 5  C  0  0x00     35  C       Mode    X01    1 heat   2 cool   3 fan   4 dry   5 auto  indicates auto heat when read   6 auto cool  this cannot be set  AC will  decide whether to heat or cool when  auto mode is set        Fan Speed    X02    0 auto  1 high  2 med  3 low       Flaps Position       X03             1 swing   2 F1 horizontal  3 F2   4 F3 45 degrees  5 F4   6 F5 vertical         17         Troubleshooting    This chapter gives suggested solutions to problems that users may encounter when installing and  configuring a Modbus interface    If there are problems with either communication channel    e Ensure the baud rate is set correctly     e Try adjusting the termination jumper settings for this channel on the Modbus interface     If the Modbus interface does not seem to be responding to the Modbus Master     e Ensure the correct slave ID has been set using the DIP switches     If the Modbus interface d
12. ions     A C Gateway On steadily  Start up 5s      Device is powered    ACK Intermittent flash     Indicates a valid transaction with the A C Gateway     Please note  if one or both of the LEDs are permanently on  this indicates that the Modbus  interface is powered  but no communication traffic is present  In this case please check the Slave  ID and communication settings  Also ensure that both RS 485 networks are wired correctly      13     Modbus    Modbus explained    Modbus is a master slave protocol  which means there are two types of Modbus device  Modbus  Masters and Modbus Slaves     Slave devices simply wait until they receive a command from a Master  act upon that command  and send a reply to the Master  Slaves do not have the ability to send commands to other devices  on the bus  Master devices are responsible for sending commands to slave devices and receiving  data  Modbus only permits there to be one Master device on the bus at any one time  but up to  247 slaves can be connected at a time     Each Slave device must have a unique ID on the bus  which is referred to as a Slave ID  Each  Modbus command the Master sends will contain this slave ID and only the Slave with that ID will    reply     Modbus register table    Modbus Slave devices store data in registers  There are four register types and each type has its  own register bank  Any 32 bit values exposed over 2 registers will have the most significant word   MSW  in the first register  The register types ar
13. mperature from compressor 3   Abnormal sensor for refrigerant gas 2 temperature in the heat exchanger   Abnormal sensor for liquid refrigerant 2 temperature in the heat exchanger   Abnormal sensor for heat exchanger coil 1 temperature    Abnormal sensor for heat exchanger coil 2 temperature    Abnormal sensor for compressor 1 current    Abnormal sensor for compressor 2 current    Abnormal non volatile memory  EEPROM  in indoor unit    Abnormal timer  RTC     Abnormal non volatile memory  EEPROM  in outdoor unit    unused   Incorrect current value for compressor 1   over current    Incorrect current value for compressor 1   locked compressor    CT sensor is dislocated from compressor 1  Short circuited    Protective thermostat for scroll compressor 1    Protective thermostat for scroll compressor 1 is slipped off       2206    134  135  136  137  138  139  140  141  142  143  144  145  146  147  148  149  150  151  152  153  154  155  156  157  158  192  193  194  195  196  197  198  199  200  201  202  203  204  205  206  207  224  225  226  227  228    H06  H07  H08  H09  H10  H11  H12  H13  H14  H15  H16  H17  H18  H19  H20  H21  H22  H23  H24  H25  H26  H27  H28  H29  H30  Loo  Lot   L02  L03  L04  L05  Loe  L07  Los  Log  L10  L11   L12  L13  L14  L15  P00  Pot   P02  P03  P04    Activation of low pressure switch    No oil in compressor 1    Incorrect connection of oil sensor 1    Chattering of magnet switch 1   Multi    Defective sensor for crank case heater 1    Incorre
14. ng Modbus interface RS 485 Modbus settings are fixed and cannot be changed     8 Data bits      No Parity    1 Stop Bit      11     RS 485 termination    Depending upon the application  environment and length of connection between the Modbus  interface and the A C Gateway  and between the Modbus interface and Modbus Master   termination and or pull up down resistors might be required  The Modbus interface has built in  jumper selectable termination and pull up down resistors located next to each of the RS 485  connections on the Modbus interface circuit board     AIC Gateway  RS485  Termination    Modbus RS 485  Termination        C3 Termination Resistor  C B Pull down  C3 Termination Resistor    B Pull down    A Pull up  A Pull up    Figure 6  RS 485 termination jumpers      120    Initial power on    Once the Modbus interface has been configured and the A C Gateway and Modbus Master are  connected  apply power to the unit     Both the indicators will begin flashing if both communication channels are operating correctly  If  either indicator remains off there is a problem with this channel     For troubleshooting information regarding communications problems  see the Troubleshooting  chapter     Summary of Status indicators    There are 2 status LEDs on the Modbus interface  During normal operation the LED indications  are as follows     Indicator Description  Modbus ACK On steadily  Start up 5s      Device is powered  Intermittent flash     Indicates valid Modbus communicat
15. oes not appear to be powered up  try the following     e Check the supply to the Modbus interface with a multimeter     If the Modbus interface does not appear to be communicating with the A C Gateway  try the  following     e Ensure the correct address is set on the A C Gateway and this matches the value set on the  Modbus interface     If no units are detected by the Modbus interface     e Ensure AC system wiring is connected correctly to the appropriate link on the A C Gateway       18      Technical specification    Parameter Min  Typ  Max  Comments   Power supply   Voltage 10V DC 24V DC 30V DC Connection via 1x 4 way 3 81mm   Current 0 1A pitch connector   Terminals   Cable size   3 81mm pitch connectors 16AWG   1 5mm    Indicators   2 Status LEDs Modbus ACK  and A C Gateway  ACK   Communication Ports   RS 485  A C Gateway  9600b s 19200b s Connection via 3 81mm 3 way  connector   RS 485  Modbus  1200b s 9600b s 115200b s Connection via 3 81mm 4 way  connector    Environmental    Operating temperature  10  C 40  C   Storage temperature  20  C 50  C   Relative humidity 90  Non condensing  Environment resist IP30   Dimensions   Length 95mm   Width 51mm   Depth 19mm   Weight 0 2kg      19     Appendix A    Manufacturer s 1 year limited warranty    t mac Technologies Ltd      t mac     warrants all products against defects in materials and  workmanship for a period of one  1  year from the date of original consumer purchase in the U K   If a defect exists during the warranty
16. r detects the change     Unused   Poor reception of the signal on the remote controller    Poor transmission of the signal on the remote controller    Poor reception of the indoor unit from the remote controller central process control    Poor reception of the indoor unit from the outdoor unit    Poor transmission of the indoor unit to the outdoor unit    Poor reception of the outdoor unit from the indoor unit    Poor transmission of the outdoor unit to the indoor unit    Duplicated setting of indoor unit s address    Setting multiple master remote controllers    Unused   Poor reception of the indoor unit from the signal output P C B    CR 3WAY TG   No auto address setting   Auto address is in setting    Poor transmission of indoor unit to the remote controller   Duplicated address of master indoor unit in group processing control   Alarm for auto address setting  Number of indoor units is too small       21     80  81  82  83  87  88  89  90  91  92  93  94  96  97  98  99  100  101  102  103  104  105  106  107  108  110  112  114  115  117  118  119  120  121  122  123  124  125  126  127  128  129  130  131  132  133    E16  E17  E18  E19  E23  E24  E25  E26  E27  E28  E29  E30  FOO  F01   F02  F03  F04  F05  FO6  FO7  F08  F09  F10  F11   F13  F14  F16  F18  F19  F21   F22  F23  F24  F25  F26  F27  F28  F29  F30  F31   HOO  H01  H02  HO3  H04  HO5    Alarm for auto address setting  Number of indoor units is too large     Poor transmission from outdoor unit to indoor unit
17. ring of group control wire   Espacio    Discord of indoor unit   s capacity   Multi    Poor setting of indoor unit   s type    Discord of power frequency   50 60Hz    Defective double duct bearing    Unused   Abnormal indoor fan motor    Actuation of outdoor fan motor  protective thermostats for CM and AC   High discharge temperature of compressor    Actuation of high refrigerant pressure switch     236    229  233  234  239  241  242  244  245    254  255    PO5  P09  P10  P15  P17  P18  P20  P21    P30  P31    Reversed phase of the power source    Poor connection of ceiling panel connector for indoor unit   Actuation of indoor unit float switch    No refrigerant gas    Abnormal discharge gas temperature from compressor 2   Abnormal discharge gas temperature from compressor 3   Abnormally high refrigerant gas pressure     Abnormal pressure difference in compressor oil   Abnormal sub indoor units in group control   Centralized processing control detected  the abnormality      Abnormal group control      24     
18. way baud rate 3 1 9600 or 19200  DIP switches 4 1 Decimal representation of switches  Indoor Unit 1 Address 20 1 Eg  101  Indoor Unit 2 Address 21 1 Eg  102  Indoor Unit 63 Address 82 1 Eg  415  Indoor Unit 64 Address 83 1 Eg  416                        15           System information    Following on from the Slave ID specified by the DIP Switches  each system appears sequentially  with the following registers detailing system information starting at 0  For example System 1 will  be the next Modbus Slave ID after that specified by the DIP Switches     Input registers                Input Registers  Analogue Inputs   Register Name Location   Length Details   decimal   Number of units in system 0 1 0 16                   Discrete inputs       Discrete Inputs  Discrete Inputs                       Register Name Location   Length Details   decimal   System fault  one or more 0 1 0   no fault  1   fault detected  units in fault           Indoor unit information    The following information starts at register X00  Where X is the unit number within a system eg  for unit 302 its registers will be at 200 on MODBUS slave ID base   3  These will be available for  each indoor unit connected in a system     Input registers                                                    Input Registers  Analogue Inputs   Register Name Location   Length Details   decimal   Return Air Temperature X00 1 Temperature    value   2    35  255  OxFF    92 5  C  0  0x00     35  C  Zone Address X01 1 3 digit dec
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  AmpliVox SB601R  静電容量式レベルセンサ 取扱説明書  De'Longhi DCU50T Series User's Manual  Notice de montage (version pdf > 500 Ko)    Copyright © All rights reserved. 
   Failed to retrieve file