Home
        Stamford Automatic Voltage Regulator
         Contents
1.  V Hz line as the speed falls below nominal  Turning the  DIP potentiometer more clockwise increases the V Hz  slope  providing a greater voltage dip and aiding engine  recovery  The DIP potentiometer can be set at any  desired position to suit a particular engine type     OVER EXCITATION  EXC TRIP  ADJUSTMENT    The adjustment is set and sealed in the works and  should not be altered    An over excitation condition is indicated on the common  LED which also indicates under speed running    The generator must be stopped to reset an over  excitation condition     Qa NEWAGE  J avk SEG    PO Box 17   Barnack Road   Stamford     Lincolnshire e PE9 2NB       2003 Newage International Limited   Reprinted with permission of N I  only   Printed in England     Tel  00 44  0 1780 484000   Fax  00 44  0 1780 484100  Website  www newage avkseg com    TD_MX341 GB_05 03 02    
2.  input  0 33 A  OVER EXCITATION PROTECTION    300 ms    Set point 75 V de   Time delay 10 seconds  fixed   ENVIRONMENTAL   Vibration 20 100 Hz 50mm sec    100Hz   2kHz 3 3g    Operating temperature  40 to  70  C  Relative Humidity 0 70  C 95   see note 6   Storage temperature  55 to  80  C    NOTES  1  With 4  engine governing    2  After 10 minutes    3  Applies to Mod status D onwards  Generator de rate may  apply  Check with factory    Factory set  semi sealed  jumper selectable    Any device connected to the analogue input must be fully  floating  galvanically isolated from ground   with an  insulation strength of 500V ac    6  Non condensing     at    TD_MX341 GB_05 03 02    DESIGN DETAIL    Stator Voltage  Sensing             Droop Potential Low Hz Synchronising  Divider  amp  Detection Circuit  Hand Rectifier  Trimmer  Reference  Voltage  Level Power  Anal  ip na Ramp Detector  amp  Control  ppu Generator Driver Devices    Stability  Circuit    The main functions of the AVR are     Potential Divider and Rectifier takes a proportion of the  generator output voltage and attenuates it  The  potential divider is adjustable by the AVR Volts  potentiometer and external hand trimmer  when fitted    The output from the droop CT is also added to this  signal  An isolating transformer is included allowing  connection to various winding configurations  A rectifier  converts the a c  input signal into d c  for further  processing        The DC Mixer adds the Analogue input signal 
3. STAMFORD    power    MX341 AUTOMATIC VOLTAGE    REGULATOR  AVR   SPECIFICATION  INSTALLATION AND ADJUSTMENTS    General description    MX341 is a two phase sensed Automatic Voltage  Regulator and forms part of the excitation system for a  brush less generator  Excitation power is derived from a  three phase permanent magnet generator  PMG   to  isolate the AVR control circuits from the effects of non   linear loads and to reduce radio frequency interference on  the generator terminals  Sustained generator short circuit  current is another feature of the PMG system     The AVR senses the voltage in the main generator  winding and controls the power fed to the exciter stator  and hence the main rotor to maintain the generator output  voltage within the specified limits  compensating for load   speed  temperature and power factor of the generator     Soft start circuitry is included to provide a smooth  controlled build up of generator output voltage     A frequency measuring circuit continually monitors the  shaft speed of the generator and provides under speed  protection of the excitation system by reducing the  generator output voltage proportionally with speed below  a pre settable threshold  A further enhancement of this  feature is an adjustable volts per Hertz slope to improve  engine recovery time on turbo charged engines  Soft start  circuitry is included to provide a smooth controlled build  up of generator output voltage     Uncontrolled excitation is limited to a sa
4. er factor     Clockwise increases the amount of C T  signal injected  into the AVR and increases the droop with lagging  power factor  cos      With the control fully anti   clockwise there is no droop     TRIM ADJUSTMENT    An analogue input  A1 A2  is provided to connect to the  Newage Power Factor Controller or other devices  It is  designed to accept dc signals up to     5 volts     CAUTION  Any devices connected to this input must be  fully floating and galvanically isolated from ground  with  an insulation capability of 500 Vac  Failure to observe  this could result in equipment damage     The dc signal applied to this input adds to the AVR  sensing circuit  A1 is connected to the AVR O volts   Positive on A2 increases excitation  Negative on A2  decreases excitation     The TRIM control allows the user to adjust the  sensitivity of the input  With TRIM fully anti clockwise  the externally applied signal has no effect  Clockwise it  has maximum effect     Normal setting is fully clockwise when used with a  Newage Power Factor Controller     DIP ADJUSTMENT    The DIP adjustment allows some control over the  generator voltage dip upon the application of load  This  feature is mostly used  when the generator is coupled to  turbo charged engines with limited block load  acceptance and operates only when the speed is below  the UFRO knee point   LED illuminated      With the DIP potentiometer fully anticlockwise  the  generator voltage characteristics will follow the normal 
5. fe period by  internal shutdown of the AVR output device  This  condition remains latched until the generator has  stopped     Provision is made for the connection of a remote voltage  trimmer  allowing the user fine control of the generator s  output     An analogue input is provided allowing connection to a  Newage Power Factor controller or other external devices  with compatible output     The AVR has the facility for droop CT connection  to allow  parallel running with other similarly equipped generators     Technical specification  SENSING INPUT    Voltage 190 264V ac max  1 phase  2 wire  Frequency 50 60 Hz nominal  POWER INPUT  PMG   Voltage 140 220V ac max  3 phase  3 wire  Current 3A phase  Frequency 100 120 Hz nominal  OUTPUT  Voltage max 120V dc  Current continuous 2 7 A  Intermittent 6A for 10 secs   Resistance 15 ohms minimum  REGULATION      1   see note 1   THERMAL DRIFT  0 03  per   C change in AVR ambient  note 2   SOFT START RAMP TIME  3 seconds  TYPICAL SYSTEM RESPONSE  AVR Response 10 ms  Filed current to 90  80 ms    Machine Volts to 97   EXTERNAL VOLTAGE ADJUSTMENT     10  with 1 k ohm 1 watt trimmer  see note 3   UNDER FREQUENCY PROTECTION  Set point 95  Hz  see note 4   Slope 170  down to 30 Hz  UNIT POWER DISSIPATION  12 watts maximum  ANALOGUE INPUT  Maximum input     5V dc  see note 5   Sensitivity 1v for 5  Generator Volts  adjustable   Input resistance 1k ohm  QUADRATURE DROOP INPUT  10 ohms burden  Max  sensitivity  0 07 A for 5  droop OPF  Max 
6. nt of the VOLTS control on position   the AVR board  or by the external hand trimmer if fitted  3  Turn STABILITY control to midway position   Terminals 1 and 2 on the AVR will be fitted with a shorting 4  Connect a suitable voltmeter  0 300V ac  across  link if no hand trimmer is required  line to neutral of the generator     5  Start generator set  and run on no load at nominal  CAUTION  Do not increase the voltage above the rated frequency e g  50 53Hz or 60 63Hz     generator voltage  If in doubt  refer to the rating plate 6  If the red Light Emitting Diode  LED  is illuminated   mounted on the generator case  refer to the Under Frequency Roll Off  UFRO   CAUTION  Do not ground any of the hand trimmer adjustment   terminals  as these could be above earth potential  7  Carefully turn VOLTS control clockwise until rated  Failure to observe this could cause equipment damage  voltage is reached    8  If instability is present at rated voltage  refer to  If a replacement AVR has been fitted or re setting of the stability adjustment  then re adjust voltage if  VOLTS adjustment is required  proceed as follows  necessary     9  Voltage adjustment is now completed     TD_MX341 GB_05 03_02    FITTING AND OPERATING    STABILITY ADJUSTMENT    The AVR includes a stability or damping circuit to  provide good steady state and transient performance of  the generator     The correct setting can be found by running the  generator at no load and slowly turning the stability  control anti cl
7. ockwise until the generator voltage starts  to become unstable     The optimum or critically damped position is slightly  clockwise from this point  i e  where the machine volts  are stable but close to the unstable region      OPTIMUM RESPONSE SELECTION    The stability selection    jumper should be correctly  linked  A B  B C or A C at the bottom of the board for  the frame size of the generator   see drawing      UNDER FREQUENCY ROLL OFF  UFRO   ADJUSTMENT    The AVR incorporates an underspeed protection circuit  which gives a volts Hz characteristic when the  generator speed falls below a presettable threshold  known as the  knee  point     The red Light Emitting Diode  LED  gives indication that  the UFRO circuit is operating     The UFRO adjustment is preset and sealed and only  requires the selection of 50   60Hz  4 pole   6pole using  the jumper link  see diagram   Adjustment of the UFRO  potentiometer will only be necessary if the AVR is being  fitted to a 6 pole generator to replace an AVR of an  earlier type     For optimum setting  the LED should illuminate as the  frequency falls just below nominal  i e  47Hz on a 50Hz  system or 57Hz on a 60Hz system     DROOP ADJUSTMENT    Generators intended for parallel operation are fitted with  a quadrature droop C T  which provides a power factor  dependent signal for the AVR  The C T  is connected to  S1  S2 on the AVR     The DROOP adjustment is normally preset in the works  to give 5  voltage droop at full load zero pow
8. on condition persists  for the specified time period     The Power Supply provides the required voltages for  the AVR circuitry     TD_MX341 GB_05 03_02    FITTING AND OPERATING          REFER TO GENERATOR WIRING DIAGRAM  LJ ae C FOR CONNECTION DETAILS    K1 K2    Power isolation link C    normally fitted  Droop    volts                    Sensing  MX341 links  Frequency EXC  SARA  Selection RIP m p  Stability       Selection  No link 6P50Hz I  Indicator  I 6P60H Stabilit I   gt  550kw  F apill  LED  I 4P50H Y F 0 550kw  UFRO  77  4P60H Tl 1  lt  90kw  321 CBA  O ol   QO  SUMMARY OF AVR CONTROLS   CONTROL FUNCTION DIRECTION   Volts To adjust generator output voltage Clockwise increases output voltage   Stability To prevent voltage hunting Clockwise increase the damping effect   Ufro To set the ufro knee point Clockwise reduces the knee point frequency   Droop To set the generator droop to 5  at Opf Clockwise increases the droop   Vtrim To optimise analogue input sensitivity Clockwise increases the gain or sensitivity   Exc trip To set the over excitation cut off level Clockwise increase the cut off level   Dip To set the frequency related voltage dip Clockwise increases the voltage dip                   ADJUSTMENT OF AVR CONTROLS    CAUTION   VOLTAGE ADJUSTMENT 1  Before running generator  turn the VOLTS control  fully anti clockwise   The generator output voltage is set at the factory  but can 2  Turn remote volts trimmer  if fitted  to midway  be altered by careful adjustme
9. the  Sensing signal     The Amplifier  Amp  compares the sensing voltage to  the Reference Voltage and amplifies the difference   error  to provide a controlling signal for the power  devices  The Ramp Generator and Level Detector and  Driver infinitely control the conduction period of the  Power Control Devices  and hence provide the  excitation system with the required power to maintain  the generator voltage within specified limits        The Stability Circuit provides adjustable negative ac  feedback to ensure good steady state and transient  performance of the control system          Over  Excitation  Detector    Exciter  Field    The Low Hz Detector measures the period of each  electrical cycle and causes the reference voltage to be  reduced approximately linearly with speed below a  presettable threshold  A Light Emitting Diode gives  indication of underspeed running    A further enhancement of this feature is the variable  DIP adjustment  which provides greater voltage roll off  to aid the recovery of turbo charge engines taking large  impact loads     The Synchronising circuit is used to keep the Ramp  Generator and Low Hz Detector locked to the    Permanent Magnet Generator waveform period     Power Control Devices vary the amount of exciter field  current in response to the error signal produced by the  Amplifier     The Over Excitation Detector continuously monitors the  exciter field voltage and provides signals  to shut down  the power device if an over excitati
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Smith & Nephew RENASYS Negative Pressure Wound Therapy  YS-S4 Multi-rotor Autopilot User Manual  Cisco ILPM-4=  Electrolux ER 5763 C User's Manual  COMPACTS NUMÉRIQUES  Sanyo N-6PT User's Manual  Detail Schedule of G15  FISC CDM - ftp cdpro  Manuel d`installation Notice d`installation du thermostat  Efficient Networks S120 Cordless Telephone User Manual    Copyright © All rights reserved. 
   Failed to retrieve file