User`s manual ENG Rev. 1

image

Contents

1. wv X 3 Connect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm Config Command COMMUNICATION COMMUNICATION COMM PORT Used to select the port of the PC to be used for communication with the UPS e USB NET COM1 COM2 COM9 USB For PC UPS communication via USB select the USB port and press Connect gt Connect A Password NET For PC lt UPS communication via NET select the NET port and click on Connect A pop up will appear where you need to enter the IP address of the network card to query Please insert net address Port 2 mJ NOTE Changes are disabled max gt Oe Connect Password Communication via NET allows you to only view the UPS configurations You cannot make settings using the NET communication For PCUPS communication via COM port select the COM ports of the PC and click on Connect Connect Password The default communication speed for all UPSs is 1200 baud For some optional cards the communication speed could by 9600 baud PASSWORD Used to enter the password to access the Service level NOMINAL DATA NOMINAL DATA VIEW NOMINAL The Nominal Data page shows the rating data of the UPS model identification code firmware version rated power rated voltage and battery capacity the type of operation input output configuration the number of batteries per bank and the number of banks 1 7
2. This setting appears only if the UPS supports this function Output 4 Alarm type signaled by output 4 This setting appears only if the UPS supports this function 21 UPS CONFIGURATION ON LINE Mode Allows you select the function of the programmable outputs shown in the box Battery low Battery working Load on bypass Inverter locked Lock or Fault Any alarm Overload Overtemperature Replace battery External input Load on inverter Output powered Bypass bad Eco mode Manual bypass UPS OK In case of low battery charge In battery operation In case of load powered by bypass In case the inverter locks In case of UPS faults or locks In case of any type of active alarm In case of overload In case of overtemperature In case of faulty battery In case of External input 1 connected In case of load powered by inverter In case of output voltage present In case of bad bypass In case of operation by ECO In case of Manual bypass active In case of correct functioning no type of fault alarm or lock is active 22 UPS CONFIGURATION ON LINE BATTERY The Battery page is used to configure the UPS after a Battery Box or battery charger has been added U UPSTools 2 0 7 File Help gt v X ct Disconnect Reload Open Save Print Send Send amp Exit Exit Comm Battery voltage Ydc Config A Battery capacity Ah 29 Operating mode hs Configuration Actual battery capacity Ah
3. gt 2277h 13m Load 212595 cad 51 gt 2309h 14m cad 51 gt 2309h 15m cod 51 gt 2310h 34m cod 51 gt 2311h 14m cod 52 gt 2312h 55m cod 51 gt 2313h 11m Displays the log of recent lock events with details on the cause of each one the code and time with reference to the total operation clock when they occurred The and symbols if present indicate the start and end of a condition By clicking on Download you can see the events file The event counter file can be cleared by clicking on the Reset button but only if the Service password has been entered By clicking on the Export button you can create a text file history txt in the program installation directory which contains all history log file data shown on the screen o The Export command is active only if the configuration has been downloaded beforehand For some UPS families event management is not handled In this case the Events window is not shown For some UPS families the event visualization could vary from the picture above 10 NOMINAL DATA STATUS The Status page shows the current status updated in real time and will continue to do so until Disconnect on the File menu is selected The last data detected will remain visible after disconnection U UPSTools 2 0 6 Ses File Help D P eO H o Connect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm 01 UPS ON
4. External I O Threshold For auto on Teleservice Command Battery voltage Battery voltage Ydc EE Enter the battery voltage indicated on the data plate of the Battery Box To prevent errors a control has been included on the entered voltage if this is incorrect the warning light on the side will turn red and the program will not allow for configuration to be completed If the warning light is green the voltage value entered is correct and you can continue with the configuration o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function Battery capacity Battery capacity Ah If the warning light is green enter the Ah value indicated on the data plate of the Battery Box plus those of the UPS additional Battery Boxes for example by adding a 14Ah Battery Box to a 7Ah UPS the value to enter is 21Ah in total o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function 2 UPS CONFIGURATION ON LINE Actual battery capacity Actual battery capacity Ah IN Shows the actual battery capacity settings o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function Threshold for auto on Threshold Far auto on C2 11 0V 11 3V C 11 67 11 8 12 0V Used to set the voltage level of the battery for automatic re start 24 UPS CONFIG
5. Enables the mode used by the UPS to establish communication with the modem and remote assistance UPS CONFIGURATION LINE INTERACTIVE UPS CONFIGURATION LINE INTERACTIVE CONFIG DISPLAY The Display page is used to change the brightness settings on the LCD display to save energy or to keep the back light on at all times Default AUTOMATIC U UPSTools 2 0 7 File Help P BM 2 Hby X Connect Disconnect Reload Open Save Print Send Send amp Exit Exit Brightness Automatic 53 Operating mode hs Configuration External I O id Battery Always ON Back light always on Automatic Back light is managed automatically by the UPS Always OFF Back light always off This page may not be available on some models 28 UPS CONFIGURATION LINE INTERACTIVE OPERATING MODE Used to set the main UPS operating parameters U UPSTools 2 0 7 File Help bh Ou v X Disconnect Reload Open Save Print Send Send amp Exit Exit Comm i gt JPS basic configuration View iv Operating mode Config Operating mode IL I normal range H Display l 9 ls Configuration External I O M Battery Output Output voltage 230 are 8 Command Output frequency Auto AVR amp battery threshold Line buck activation Line buck comeback Line boost comeback Line boost activation Battery high activation Battery high comeback Battery low comebac
6. Stand by Off configure the delay expressed in seconds between the return of the mains power and shut off of the load Default Osec Output The Output settings page is used to configure the UPS voltage between 220 and 240 Volt and frequency parameters Output Output voltage 230 Output Frequency Enable frequency converter Output voltage Use to set the desired output voltage of the UPS Default 230V Output frequency Use to select the desired output frequency 50 or 60 Hz of the UPS Default Auto Enable frequency converter In this mode the UPS can operate as a frequency converter Default DISABLED UPS Tools For some families when the UPS functions as a Frequency converter or the link to the mains is disabled the rated power of the UPS will be downgraded The configuration of the set frequency is activated only when the UPS is powering up Therefore if you make a change you need to shutdown the UPS and then restart it Incorrect output frequency conversion may cause damage to the loads connected to the UPS Before configuring the parameter check the rated frequency of the loads connected to the UPS gt gt 14 UPS CONFIGURATION ON LINE CONFIGURATION U UPSTools 2 0 8 PEDES File Help b E Ou X Disconnect Reload Open Save Print Send Send amp Exit Exit Comm 9 UPS function and bypass configuration View C2 General Config Autorestart
7. charged Command Command Shutdown qu you to run a shutdown test of the UPS setting the delay in seconds from sending the command to shutdown of the Shutdown amp Restore Allows you to run a shutdown and restore test of the UPS setting the time in seconds from sending the command to shutdown of the UPS and the delay in minutes for the subsequent restarting of the UPS 38
8. is connected to Comm port 1 The modem is connected to Comm port 2 25 UPS CONFIGURATION ON LINE Modem config Modern contig Telephone nr 1 Telephone nr 2 Telephone nr 3 Init modem string Call modern string Wait time recall Number of recall Identif number LM SUTS 70870001 Telephone no Allows you to enter three telephone numbers that the UPS can communicate with Init modem string Specifies the modem command or sequence of commands without AT suffix for the initialization of the modem refer to the modem handbook Example amp 0 The commands indicated in this parameter are sent by the UPS to the modem preceded by the sequence with prefix ATEOVOXOSO 1 Call modem string Specifies the modem command or sequence of commands without AT suffix to activate the call refer to the modem handbook For example DT DP The commands indicated in this parameter are sent by the UPS to the modem preceded by the sequence with prefix AT Wait time recall Specifies the number of seconds to wait between one call and the next call in case of attempt to recall due to failed connection busy no answer etc Number of recall Specifies the maximum number of call attempts for each of the three telephone numbers in case of failed connection busy no answer etc Identif Number This is the UPS identification code When a call is made to remote assistance the UPS sends the ID number to be recognized da
9. port No function No function is performed Remote on UPS start up Remote off UPS shutdown Remote on off UPS start up or shutdown REPO UPS shutdown The setting appears only in those UPSs that support this function In the UPS models Rack or Rack Tower that have the REPO contact the inputs may be displayed in a slightly different manner and Input 1 can be set only as a remote shutdown contact REPO db To prevent unwanted start up or shutdown of the UPS enable the Remote on Remote off function only if the device connected to the communication port of the UPS PC or otherwise is capable of correctly handling the signal Input 3 Input 3 Slot card pin 9 Mode Remote bypass Delay time an ms ka Mode Allows you to select the input function of the remote command pin 9 of the Slot card Remote on turns the UPS in bypass mode No function No function is performed o The Remote bypass setting appears only in those UPSs that support this function Delay time Minimum impulse time for the input mode signal active high Autorestart Enables or disables the automatic re start after turning off the UPS subordinate to the re starting defined on the Configuration page 20 UPS CONFIGURATION ON LINE Output 1 185232 Pin 1 Slot card Output z RSz32 Pin 8 Slot card Output 1 Alarm type signaled by output 1 Output 2 Alarm type signaled by output 2 Output 3 Alarm type signaled by output 3
10. positive bank 2 positive negative bank U UPSTools 2 0 7 File Help B fF Od wv X Connect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm Config Command v UPS Madel LPS Code Firmware version Nominal power V Nominal power W Nominal battery voltage V Mominal battery capacity Ah UPS type I O Configuration Batteries number for bench Battery benches UOD1 LN43UT970870001 SWMO35 01 07 11000 800 36 On Line Line Interact MonojMono 3 L 1 The command is active only if the UPS was previously connected to the PC For some UPS families the UPS Code window is not managed so in the relative windows could not be shown the UPS identification code NOMINAL DATA HISTORY The History page shows the data from the history log file of the UPS the screen is divided into the following three sections U UPSTools 2 0 7 ER File Help P E X nnect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm View i Nominal Counters Timers EO 3 History Nr battery working Total working time 2313h 15m Nr bypass work 12 Total time on battery 35m Config v Locks due to short circuit Inverter work time in L I Oh 29m Command v Locks due to overload Locks due to overtemp Other locks
11. the bypass parameters when the UPS is in Eco mode Eco made m Minimum eco made threshold v 253 Maximum eco mode threshold v E t ux This setting appears only if the UPS supports this function Sensibility Used to select the sensibility of the bypass line quality control Default NORMAL When the voltage of the bypass line goes below the minimum threshold setting the UPS switches mign immediately to ON LINE operation Normal ane At the selected minimum voltage threshold hysteresis is added to prevent continuous ECO Low ON LINE passages due to fluctuations of the mains o This setting appears only if the UPS supports this function Minimum eco mode threshold Used to set the minimum threshold for the bypass voltage range accepted for operating in Eco mode below this threshold the UPS switches to On line mode The values can be set between 180V to 220V in 1V increments Default 200V Maximum eco mode threshold Used to set the maximum threshold for the bypass voltage range accepted for operating in Eco mode over this threshold the UPS switches to On line mode The values can be set between 240V to 264V in 1V increments Default 255V The Default values may vary according to the UPS family 18 UPS CONFIGURATION ON LINE EXTERNAL I O The External Input Output page allows you to change the configuration of the communication port when used as a contact port or the conf
12. those supported For Stand by off mode you can configure the delay time in seconds for shutdown after the mains power is restored Operating mode Mode Select the operating mode desired Default On line On line This mode ensures the maximum protection of the load and the best quality of the output waveform This is the mode with the lowest consumption of the UPS and therefore with the greatest efficiency The load is normally powered by bypass and in case the mains go outside of the tolerance range the UPS switches to On line operation About five minutes after the mains return within the tolerance range the load is switched back to bypass Eco mode In this mode the UPS based a statistic detected the quality of the input mains it decides its Smart active own whether to work in On line mode or Eco mode In this mode the UPS is used as an emergency unit When the mains power is present the load is not Stand by Off supplied while if a black out occurs it is powered by the inverter via the batteries with a trip time less than 0 5 seconds see also Delay power off In this mode the UPS can operate with an input frequency at 50Hz and output frequency at 60Hz and Frequency converter vice versa In this case the automatic bypass is disabled Some UPS families may not have several of the operating modes listed above 13 UPS CONFIGURATION ON LINE Delay power off If the operating mode is set to
13. with the configuration o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function Battery capacity Battery capacity Ah If the warning light is green enter the Ah value indicated on the data plate of the Battery Box plus those of the UPS additional Battery Boxes for example by adding a 14Ah Battery Box to a 7Ah UPS the value to enter is 21Ah in total o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function 36 UPS CONFIGURATION LINE INTERACTIVE Actual battery capacity Actual battery capacity Ah IN Shows the actual battery capacity settings o This setting appears only if the UPS is equipped with a battery expansion socket and supports this function Threshold for auto on Threshold Far auto on C2 11 0V 11 3V C 11 67 11 8 12 0V Used to set the voltage level of the battery for automatic re start 37 COMMANDS COMMANDS CONTROL U UPSTools 2 0 8 SE File Help D B X C Disconnect Reload Open Save Print Send Send amp Exit Exit Comm Config v Command Test Test Panel Allows you to run a panel test of the UPS all icons on the screen will turn on for several seconds Battery Activates the battery test The command is performed only if the UPS is operating from the mains the load is supplied by the inverter and the batteries are at least 90
14. 14 Battery inserted 02 Battery not working 15 Battery voltage good Btok 1 03 Bypass line good 04 Line present 06 Input contact CLOSED 07 Booster PFC ON 08 Inverter OFF 09 Inverter output synchronized 10 Bypass contact CLOSED 11 Output contact CLOSED 12 Battery charger ON 13 Battery contact OPEN ttttttttttttttttt NO ALARMS Some UPS families do not have a status management page 11 UPS CONFIGURATION ON LINE UPS CONFIGURATION ON LINE CONFIG DISPLAY The Display page is used to change the brightness settings on the LCD display in order to save energy of the UPS U UPSTools 2 0 6 Seca File Help P P e X nnect Disconnect Reload Open Save Print Send Send amp Exit Exit 5 Operating mode Configuration i External I O ij Battery Teleservice Brightness This page may not be available on some models 12 UPS CONFIGURATION ON LINE OPERATING MODE Used to set the main UPS operating parameters U UPSTools 2 0 8 File Help bo E gt H bv wv X Disconnect Reload Open Save Print Send Send amp Exit Exit Comm Xx View Operating made Operating made Configuration External I O id Battery T Teleservice Output Output voltage Command x Output Frequency Enable frequency converter Operating mode The Operating mode page is used to configure the operating mode from one of
15. CONFIGURATION LINE INTERACTIVE Mode Allows you to select the input function of the remote command pin 7 or pin 4 of the RS 232 port No function No function is performed Remote on UPS start up Remote off UPS shutdown Remote on off UPS start up or shutdown REPO UPS shutdown In the UPS models Rack or Rack Tower that have the REPO contact the inputs may be displayed in a slightly different manner and Input 1 can be set only as a remote shutdown contact REPO E To prevent unwanted start up or shutdown of the UPS enable the Remote on Remote off function only if the device connected to the communication port of the UPS PC or otherwise is capable of correctly handling the signal Delay time Minimum duration of the impulse for the input mode signal active high Autorestart Enables or disables the automatic re start after turning off the UPS subordinate to the re starting defined on the Configuration page Output Output 1 R5232 Pin 1 Slat card Gutpuk 2 R5232 Pin 8 Slat card Output 1 Alarm type signaled by output 1 pin 1 of the RS 232 port Output 2 Alarm type signaled by output 2 pin 8 of the RS 232 port 34 UPS CONFIGURATION LINE INTERACTIVE Mode Allows you select the function of the programmable outputs shown in the box Battery low In case of low battery charge Battery working In battery operation Load on bypass In case of load powered by bypass Inverter locked In case the inverter locks
16. Events Auxiliary power KO cod 03 gt 2277h 13m Load gt 125 51 gt 2309h 14m mmm UNS Load gt 125 cod 51 gt 2309h 15m Download Load 212595 cod 51 gt 2310h 34m 3 Load gt 125 cod 51 gt 2311h 14m Load gt 150 cod 52 2312h 55m Load gt 125 cod 51 2313h 11m Y 7 979 e LESI cal 424 Counters Counters Mr battery working J Mr bypass work 12 Locks due to short circuit Locks due to overload Locks due to avertemp Other lacks Reset Displays the number of times of operation from the battery the number of times of operation from the bypass and the number of locking events that occurred subdivided by type of alarm short circuit overload over temperature and other alarms The event counter file can be cleared by clicking on the Reset button but only if the Service password has been entered NOMINAL DATA Timers Timers Total working time 2313h 15m Total time on battery o T zm na ea n cen Inverter work kime in L I Reset Displays the time hour minutes of total UPS operation device switched on from the mains battery bypass etc of battery operation and operation via the inverter with the UPS configured in Line Interactive mode The event counter file can be cleared by clicking on the Reset button but only if the Service password has been entered Events Events Auxiliary power KO cad 03
17. ICE UPS CONFIGURATION LINE INTERACTIVE CONFIG DISPLAY OPERATING MODE CONFIGURATION EXTERNAL I O BATTERY 9 90090 aa gH IQ Co N N N Aw A ND NO w MN M COMMANDS COMMAND CONTROL 38 38 38 MAIN WINDOW MAIN WINDOW KES U UPSTools 2 1 0 File Help b o Odo wv X Connect Reload Open Save Print Send Send amp Exit Exit LETTER U UPSTools 2 1 0 conet aly y X i Reload Ctrl F ave Print Send Send amp Exit Exit l Open Ctrl 5 Config 35 Command 22 Print Ctrl P w Send Crw if Send amp Exit Ctrl M Exit Ctrl g Command FILE MENU 1 CONNECT Activates the PC UPS connection using the set serial communication port Once this operation is performed the UPS connected status will appear in the status bar on the bottom left For the PC UPS connection use e USB 2 0 cable m m if using the USB port of the UPS e Pin to Pin cable D Sub 6 pins 1 1 m f if using the standard RS232 port of the UPS e Null Modem cable D Sub 9 pins f f if using an optional port of the UPS Communication Slot 1 or 2 For the PC UPS remote connection use e UTP cable for LAN if using an optional port of the UPS Communi
18. Lock or Fault In case of UPS faults or locks Any alarm In case of any type of active alarm Overload In case of overload Overtemperature In case of overtemperature Replace battery In case of faulty battery External input In case of External input 1 connected Load on inverter In case of load powered by inverter Output powered In case of output voltage present Bypass bad In case of bad bypass Eco mode In case of operation by ECO Manual bypass In case of Manual bypass active UPS OK In case of correct functioning no type of fault alarm or lock is active 35 UPS CONFIGURATION LINE INTERACTIVE BATTERY The Battery page is used to configure the UPS after a Battery Box or battery charger has been added U UPSTools 2 0 7 File Help gt v X ct Disconnect Reload Open Save Print Send Send amp Exit Exit Comm lt Battery voltage Ydc Config A Battery capacity Ah 29 Operating mode s Configuration Actual battery capacity Ah External I O Threshold For auto on Teleservice Command Battery voltage Battery voltage Ydc EE Enter the battery voltage indicated on the data plate of the Battery Box To prevent errors a control has been included on the entered voltage if this is incorrect the warning light on the side will turn red and the program will not allow for configuration to be completed If the warning light is green the voltage value entered is correct and you can continue
19. Service Document 5 UPSTools USER MANUAL Compatibile with UPS series LINE INTERACTIVE UPS VST VSD ON LINE UPS SEP SDH SDL SPW SPT SPM SPH Doc name RM903 Rev01 EN Release date 02 05 2013 INTRODUCTION UPSTools is a utility program for the configuration of UPSs from 500VA to 20KVA It is compatible with Windows 2000 XP 2003 Vista and 7 Linux x86 and Solaris 8 9 and 10 SPARC Java virtual machine 32 bit version 6 or higher is required for this program Conventions used in this manual me Sander Indicates information that cannot be ignored d Failure to comply with these warnings could cause serious damage to the UPS batteries or charger b TM Indicates important information Failure to comply with these warnings could cause the UPS to malfunction o Information Provides useful notes and tips for the user No part of this manual may be reproduced without the prior permission by the manufacturer For the purpose of improvement the manufacturer reserves the right to change the product described at any time and without notice CONTENTS MAIN WINDOW FiLE MENU 1 CONNECT 2 RELOAD 3 OPEN 4 SAVE 5 PRINT 6 SEND 7 SEND amp ExIT 8 EXIT DROP DOWN MENU COMMUNICATION COMM PORT PASSWORD NOMINAL DATA VIEW NOMINAL HISTORY STATUS UPS CONFIGURATION ON LINE CONFIG DISPLAY OPERATING MODE CONFIGURATION EXTERNAL I O BATTERY TELESERV
20. URATION ON LINE TELESERVICE This page requires a Service password The Teleservice page is used to activate and configure the automatic call procedure via modem in order to contact remote assistance for UPS faults and alarms U UPSTools 2 0 7 File Help e X nnect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm View Config A 23 Operating mode hs Configuration External I O Battery Wb Teleservice Command v Modem Optional port Modem config Call logic Telephone nr 1 Event Telephone nr 2 Lock Telephone nr 3 Init modem string Alarm Call modem string Anomaly Wait time recall 0 Number of recall 0 On bypass LN43UT970870001 Identif number On battery Battery low Insert PIN ecccc Please confirm PIN Enable command Mode recall If a PIN code has been previously set the operator has to enter the security code in order to be enabled to edit the data To enable this function an optional card is required to insert in the expansion slot This setting appears only if the UPS supports this function Modem Used to select the communication port of the UPS that the modem is connected to Not installed Optional port Comm port 1 Comm port 2 No modem remote assistance function disabled The modem is connected to the optional port card for expansion slot The modem
21. allows for the automatic disconnection of the load applied to them in certain operating conditions Setting an event that causes automatic disconnection of the Energyshare socket Default Never Never Battery working Line present Battery low User overload Overload Temperature Ok External input on No lock No fault alarm Normal status Battery low Stand by Always Energyshare socket always connected Disconnection in battery operation Disconnection if the input mains is present Disconnection in case of low battery charge Disconnection for loads greater than the user defined threshold Disconnection for overload Disconnection if the temperature of the UPS is good Disconnection if remote input signal Input 3 is active Disconnection when there are no locking events Disconnection when there are no alarms Disconnection in case of normal operation Disconnection for low battery Disconnection if the UPS is in Stand by Energyshare socket always disconnected 16 UPS CONFIGURATION ON LINE Dly energyshare Used to set the delay expressed in seconds and between 0 and 65535 from when the selected event occurs and automatic disconnection of the Energyshare socket Default 0 o This configuration is possible only for UPS models that have an Energyshare socket Bypass mode Used for setting the bypass operation parameters Bypass made Minimum threshold v 180 Maximum threshold v 264 This
22. cation Slot 1 or 2 2 RELOAD Runs a full interrogation of the UPS status to update the displayed data 3 OPEN Loads the UPS configuration data from a file this is useful to copy the configuration from one UPS to another MAIN WINDOW 4 SAVE Saves the UPS configuration data on a file this is useful to create a backup copy of the configuration 5 PRINT Prints the current configuration 6 SEND Sends and activates the current configuration on the UPS o The commands are not enabled in remote connection 7 SEND amp EXIT Sends and activates the current configuration on the UPS and to exit the program a The commands are not enabled in remote connection No settings made or loaded from the disk will be effective on the UPS until the Send or Send amp Exit command is executed Some screens have a Send button to enable the changes on the page shown on the screen 8 EXIT Used to exit the program DROP DOWN MENU The drop down menu can be expanded only after putting the UPS in communication with the UPSTools software The settings within the drop down menu vary based on the type of UPS a Comm used to set the communication port between the PC and UPS b View used to view the nominal data of the UPS c Config used to configure the UPS and commands and varies based on the type of UPS connected d Command used to send several test and on off commands U UPSTools 7 0 8 File Help gt E
23. equency conversion may cause damage to the loads connected to the UPS Before configuring the parameter check the rated frequency of the loads connected to the UPS AVR amp battery threshold The AVR amp battery threshold page allows you to see the voltage thresholds for the activation return for operating in buck boost and battery mode These thresholds vary with the operating mode and output voltage setting changes AVR amp battery threshold Line buck activation 242W Line buck comeback 23b5V Line boost comeback z208 Line boost activation 2021 Battery high activation 280 Battery high comeback 2T4 Battery low comeback 178 Battery low activation 172V 30 UPS CONFIGURATION LINE INTERACTIVE CONFIGURATION U UPSTools 2 0 7 File Help b B vo X nect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm View Config A Autorestart 5 Batt low time min 3 l C Auto power off C Autonomy limitation Freq tolerance 5 5 Automatic battery test Energyshare Never H Display 53 Operating mode External I O _ Maximum load Dly energyshare sec 0 iM Battery Command Y Autorestart If during operation via battery the UPS shuts off due to end of backup time a remote shutdown or auto power off command if this function is enabled the UPS will automatically start up when the mains power supply is restored if the function is disabled
24. iguration of the REMOTE port if present o The visualizations and the settings of this section may vary according to the UPS family U UPSTools 2 1 0 File Help b G2 Oui wv X t Reload Open Save Print Send Send amp Exit Exit Comm Y A xternal I Set the configuration of the remote contact View lt Input 1 R5232 Pin 7 Slot card pin 5 Config A Mode No Function 53 Operating mode S Configuration External I O Output 1 R5232 Pin 1 Slot card pin 3 alarm Battery Command Y Input 2 95232 Pin 4 Slot card pin 8 Output 2 R5232 Pin 8 Slot card pin 10 Mode function Battery low v Input 3 Slot card pin 9 Output 3 R5232 Pin 9 Slot card pin 11 Mode Remote bypass Battery working Delay time 80 ms Output 4 Slot card 12 Mode Output powered Input 1 2 UPS with REPO function Input 1 REMOTE TERMINAL Pin 1 2 Mode REPO Delay time 80 ms 4ukoreskark Disabled Input 2 REMOTE TERMINAL Pin 2 3 Mode Remote Delay time ms Aukoreskark Disabled UPS without REPO function Input 1 R 5232 Pin 7 Hed A oreskart Disabled Input 2 8 5232 Pin 4 Slot card REPO Made Ma Function Delay time 50 ms Autorestart Disabled 19 UPS CONFIGURATION ON LINE Mode Allows you to select the input function of the remote command pin 7 or pin 4 of the RS 232
25. k Battery low activation Operating mode The Operating mode page is used to configure the operating mode from one of those supported Operating made Operating mode L I normal range Mode Select the operating mode desired Default normal range L I normal range Line Interactive Mode standard input voltage range L I wide range Line Interactive Mode extended input voltage range L I narrow range Line Interactive Mode limited input voltage range ECO normal range ECO Mode greater efficiency standard input voltage range ECO wide range ECO Mode greater efficiency extended input voltage range BOOS Mi GL ECO Mode greater efficiency AVR disconnected standard input voltage range normal range Sage AVR off wide ECO Mode greater efficiency AVR disconnected extended input voltage range 29 UPS CONFIGURATION LINE INTERACTIVE Output The Output settings page is used to configure the UPS voltage between 220 and 240 Volt and frequency parameters Output voltage Output Frequency Output voltage Use to set the desired output voltage of the UPS Default 230V Output frequency Use to select the desired output frequency 50 or 60 Hz of the UPS Default Auto The configuration of the set frequency is activated only when the UPS is powering up Therefore if you make a change you need to shutdown the UPS and then restart it me Incorrect output fr
26. n 0 and 65535 from when the selected event occurs and automatic disconnection of the Energyshare socket Default 0 This configuration is possible only for UPS models that have Energyshare socket 32 UPS CONFIGURATION LINE INTERACTIVE EXTERNAL I O The External Input Output page allows you to change the configuration of the communication port when used as a contact port or the configuration of the REMOTE port if present U UPSTools 2 0 7 File Help gt NM Gu vw X nect Disconnect Reload Open Save Print Send Send amp Exit Exit Comm View Input 1 95232 Pin 7 Output 1 85232 Pin 1 Slot card Config A Mode No function Inverter locked 239 Operating mode hs Configuration Delay time 80 ms Autorestart Disabled Battery Teleservice Input 2 R5232 Pin 4 Slot card REPO Output 2 R5232 Pin 8 Slot card Made No Function Mode Battery low Delay time 80 ms Autorestart Disabled Input UPS with REPO function UPS without REPO function Input 1 REMOTE TERMINAL Pin 1 2 Input 1 RS232 Pin 7 Mode REPO Mode Function Delay time 80 ms Delay time ms Aukoreskark Disabled Autoreskart Disabled Input 2 REMOTE TERMINAL Pin 2 3 Input 2 85232 Pin 4 Slat card REPO Made Remote an Made Ma Function Delay time 80 ms Delay time 80 ms Autorestart Disabled Autorestart Disabled 33 UPS
27. o set the threshold of residual backup time expressed in minutes and between and 255 under which the UPS activates the low battery alarm Default 3 Freq tolerance Used to select the percentage that defines the frequency range where the UPS is allowed to synchronize the output s sine curve with the input s Default gt 5 Energyshare The UPS may be equipped with a power outlet that allows for the automatic disconnection of the load applied to them in certain operating conditions Setting the event that causes automatic disconnection of the Energyshare socket Default NEVER Never Battery working Line present Battery low User overload Overload Temperature Ok External input on No lock No fault alarm Normal status Battery low Energyshare socket always connected Disconnection in battery operation Disconnection if the input mains is present Disconnection in case of low battery charge Disconnection for loads greater than the user defined threshold Disconnection for overload Disconnection if the temperature of the UPS is good Disconnection if remote input signal Input 3 is active Disconnection when there are no locking events Disconnection when there are no alarms Disconnection in case of normal operation Disconnection for low battery Stand by Disconnection if the UPS is in Stand by Always Energyshare socket always disconnected Dly energyshare Used to set the delay expressed in seconds and betwee
28. s enabled if the function is disabled it will continue to function as usual from the battery Default Function DISABLED Autonomy limitation Allows if enabled to specify a maximum time in seconds of operation from battery once this time has passed the UPS automatically shuts down even if the battery backup time has not finished this time can be set from 1 to 65534 seconds Default Function DISABLED 15 UPS CONFIGURATION ON LINE Automatic battery test If this function is enabled a battery test is run automatically Default Function ENABLED at scheduled times during UPS operation Default 40 h Maximum load The user can set the load rate after which the UPS will signal a maximum load fault Default Function ENABLED Default gt 103 Auto power on If this function is enabled the UPS will re start automatically when the mains return regardless of the reason why it shutdown Some UPS families may not have the function listed above Batt Low time Used to set the threshold of residual backup time expressed in minutes and between and 255 under which the UPS activates the low battery alarm Default 3 Freq tolerance Used to select the percentage that defines the frequency range where the UPS is allowed to synchronize the output s sine curve with the input s Default gt 5 The Default value may vary according to the UPS family Energyshare The UPS may be equipped with a power outlet that
29. sec 5 Auto power on Auto power off Batt low time 3 Operating mode C Autonomy limitation sec Freq tolerance 5 v External LO Automatic battery test h 40 Energyshare d Battery Maximum load Dly energyshare sec Teleservice Bypass mode Mode Command Minimum threshold v 180 Maximum threshold V 264 Eco mode Sensibility Normal v Minimum eco mode threshold v 200 Maximum eco mode threshold v 253 General Autorestart sec Suto power on Suto power aff Batt low time min Autonomy limitation sec Freq tolerance 5 Automatic battery best h Energyshare Maximum load 55 Dlv energyshare sec Autorestart If during operation via battery the UPS shuts off due to end of backup time a remote shutdown or auto power off command if this function is enabled the UPS will automatically start up when the mains power supply is restored if the function is disabled the UPS will remain in stand by Default e Function ENABLED If the function is enabled you can set the delay expressed in seconds and between 0 and 255 between mains restore and the restart of the UPS Default 5 sec Auto power off If during operation from the battery the percentage of load powered by the UPS goes below the 596 threshold load off or disconnected the UPS will shut off automatically after 40 seconds if the function i
30. setting appears only if the UPS supports this function Mode Used to select the use mode of the bypass line for transitory events and in emergency conditions Enabled high sensibility e bypass enabled with high triggering sensibility control of waveform of the inverter Changeover on bypass enabled with low triggering sensibility control of waveform of the inverter voltage inactive control of the RMS value of the inverter voltage active Disabled Inverter sync Changeover on bypass disabled Disabled w link Output frequency synchronized with the input frequency Disabled Free running Changeover on bypass disabled Disabled w o link Output frequency NOT synchronized with the input frequency Active in stand by When the UPS is in stand by the load connected to the output is powered via the bypass line If the Active in stand by function is enabled the UPS output remains powered o Some UPS families may not have several of the bypass modes listed above Minimum threshold Used to set the minimum threshold for the bypass voltage accepted for its use you can set values from 180V to 220V 1V increments Default 180V Maximum threshold Used to set the maximum threshold for bypass voltage accepted for its use you can set values from 240V to 264V in 1V increments Default gt 264V o The Default values may vary according to the UPS family 17 UPS CONFIGURATION ON LINE Eco mode Used to set
31. ta exchange only takes place if the UPS code is entered in the remote assistance records 26 UPS CONFIGURATION ON LINE Call logic The first column shows the various events and the first line contains the three telephone numbers The boxes can be set to select which telephone number to call in the various cases If there is more than one per line you can select whether to call all the selected numbers AND logic or one of them OR logic Call logic Event Tel 1 Tal 2 Tal 3 Logic Lock Alarm d C F Anomaly d d AMD w On bypass C F AMD On battery F C d Battery low d C d AMD Other settings Insert PIM Please confirm PIM Enable command Mode recall Insert Pin Please confirm Pin For security purposes a PIN code can be entered to change the remote assistance configuration It needs to be entered twice to prevent typing errors After the PIN code is sent to the UPS the data for remote assistance can only be changed if the correct security code is entered if the operator forgets the code the PIN can only be disabled by the manufacturer The PIN should only be entered when required for security purposes and you should make sure to keep a copy of the code in a safe place Enable command If the function is enabled the UPS accepts and executes the commands received remotely via modem test shutdown etoc otherwise the execution of remote commands will be disabled Mode recall
32. the UPS will remain in stand by Default 5 Function ENABLED If the function is enabled you can set the delay expressed in seconds and between 0 and 255 between mains restore and the restart of the UPS Default 5 sec Auto power off If during operation from the battery the percentage of load powered by the UPS goes below the 596 threshold load off or disconnected the UPS will shut off automatically after 40 seconds if the function is enabled if the function is disabled it will continue to function as usual from the battery Default Function DISABLED Autonomy limitation Allows if enabled to specify a maximum time in seconds of operation from battery once this time has passed the UPS automatically shuts down even if the battery backup time has not finished this time can be set from 1 to 65534 seconds Default Function DISABLED Automatic battery test If this function is enabled a battery test is run automatically Default Function ENABLED at scheduled times during UPS operation Default 40 h 3l UPS CONFIGURATION LINE INTERACTIVE Maximum load The user can set the load rate after which the UPS will signal a maximum load fault Default Function ENABLED Default gt 103 Auto power on If this function is enabled the UPS will re start automatically when the mains return regardless of the reason why it shutdown This function may not be available in some models Batt Low time Used t