Home
Moisture Monitor Series 3
Contents
1. Figure 1 1 Series 3 Back Panel Installing Optional Features 1 1 September 2003 Making Electrical Connections cont IWARNING Division 2 applications may require special installation Consult the National Electric Code for proper installation requirements The analyzer must be configured in a suitable enclosure and installed according to the applicable sections of the National Electric Code Article 500 that pertain to the hazardous environment in which the electronics will be used IWARNING Turn off the Series 3 before making any connections Make connections by placing the press lock lever into the desired terminal One press lock lever is supplied with each terminal block Press and hold the lever against the terminal block and insert the stripped and tinned portion of the wire into the terminal Release the lever to secure the connection Proper connections and cabling are extremely important to accurate measurement Be sure to use the correct cable type for each probe and make sure that the cables are not damaged
2. WI Channel Card Retainer Bar I o E Screws 4 ah Gh Top View Figure 1 14 Location of Channel Cards Setting the Switch Block 1 Locate switch block S1 see Figure 1 12 on page 1 16 for switch S1 location Switch block S1 has two switches 1 for Auxiliary 1 and 2 for Auxiliary 2 2 Setthe switches in one of two positions ON for current or OFF for voltage 1 18 Installing Optional Features September 2003 Replacing the Channel 1 Once switches are set replace the channel card Card If you intend to connect another type of input device to the Series 3 do not replace the cover because you will need to set switches on the channel card for those inputs as well 2 Replace the retainer bar Make sure the slots on the retainer bar are seated correctly against the printed circuit boards Secure the bar with two screws 3 Slide the electronics unit back into its enclosure and replace the screws Tighten the screws until they are snug Do not over tighten You have completed connecting the output device Refer to Reco
3. Figure 1 2 Location of Channel Cards 1 4 Installing Optional Features September 2003 Setting the Switch 1 Locate switch blocks S2 and S3 see Figure 1 3 below Switch Blocks block S2 controls the output signal for Recorder A and switch block S3 controls the output signal for Recorder 2 Set the switches in the appropriate positions I for current or V for voltage Replacing the Channel 1 Once the switches are set replace the channel card Card If you intend to connect pressure inputs or other input devices to the Series 3 do not replace the retainer bar and cover because you will need to set switches on the channel card for those inputs as well 2 Replace the retainer bar Make sure the slots on the retainer bar are seated correctly against the printed circuit boards Secure the bar with two screws 3 Slide the electronics units into its enclosure and replace the screws Tighten the screws until they are snug Do not over tighten You may now connect the recorder s oF lt a Doo 1 0 0090000 E EEE 00 Ip Ba
4. 2 22 Entering Oxygen Reference 2 23 Entering Pressure Reference 2 24 Replacing and Recalibrating the Moisture Probes 2 25 Recalibrating the Pressure Sensors 2 25 Calibrating the Delta F Oxygen Cell II 2 26 Checking the Oxygen Cell 2 26 Entering the New Span Value 0 0 2 28 Delta Oxygen Cell Background Gas Correction 2 29 Correcting for Different Background 2 29 Entering the Current eh 2 30 Range Error Description u d usd o d Barend est edd t oe ety eed 2 32 Signal Error Description er ee A LEVE ET RAM VR 2 32 Calibration Error Description l l 2 32 vi September 2003 EO Table of Contents cont Appendix A Application of the Hygrometer 900 901D1 Introductions ds E ern ee pU Uu gene ne 1 Moisture Monitor Hints 2 0 I 2 luc ju PIC ar Re a RE ae Coes ur ee A 3 Response Time yt ie ec else s IS en EM pe S Pd SES A 3 Temper t re Oe epp ee Rn Re A 4 BIOWSR see ese etit Din BOA ed irre ne eg tempe
5. 2 32 H Channel Card Installing 2 19 High and Low Reference Values Common Problems t oia So a 2 11 Reference 2 21 Communications Port 1 20 Contaminants RON A 5 Inputs Corrosive A 6 Connecting 1 17 Moisture Probes 1 9 Oxygen 1 5 1 9 Pressure 1 9 Installation Channel Card 2 19 Electrical Connections 1 17 Instrument Program Replacing gt o ee ee Bee 2 14 Index September 2003 Index cont L Linear Memory Card 2 14 Liquids Applications A 22 6 Flow Rates 19 Maintenance Channel Card Installing 2 19 Instrument Program Replacing 2 14 Oxygen Cell une 2 13 Replacing and Recalibrating Probes 2 25 Menu Options Entering Reference Values 2 21 Messages Screen 2 8 Modifying 1 3 Calibration Adjustment 1 22 Moisture Probe Cleaning A 7 Contaminants A 5 Corrosive Substances A 6 Gas Flow A 19 Liqui
6. saith dae ten ptt ts spes ee eal eos tots 1 22 Calibration Procedure nre a ERU ele 1 22 September 2003 EU CD AALLAEGE DEDEAAAB Be ker k thA Table of Contents cont Chapter 2 Troubleshooting and Maintenance Introduction een nee er ea ne mn Se eae aes 2 1 Testing the Alarm Relays en a a ann 2 2 Testing the Recorder 88 2 3 Trimming the Recorder Outputs 8 8 ees 2 5 Preliminary Steps rer re a eee ee eee 2 5 Trimming the Recorder Outputs eens 2 5 What s Next ssc aed bee le EB ER ID eee 2 7 Screen Messages oce ete RL IRRE ee ee e ee 2 8 Common Problems en a 2 11 Checking the Delta F Oxygen Cell 1 1 2 13 Checking the Electrolyte Level 0 0 III 2 13 Replenishing the 1 8 ences 2 13 Adding or Removing a PCMCIA Card 0 0 ee eect ences 2 14 Recharging the Battery Pack 0 2 17 Installing a Channel I 2 19 Entering Reference Values fora Channel 2 21 Entering Moisture Reference Data
7. 1 0 721 0 0000 1 O ua 1 Zero SPAN To exit press RUN Use the arrow keys to move the brackets to SYSTEM and press YES Use the arrow keys to move the brackets to O and press YES Use the arrow keys to move the brackets to CURVES and press YES Use the arrow keys to move the brackets to CURVE and press YES Use the arrow keys to move the brackets to SPAN and press YES Enter the new span percentage value Press YES and press the left arrow key Enter the new span microamp value and press YES 2 28 Troubleshooting and Maintenance September 2003 Delta F Oxygen Cell Background Gas Correction Factors Correcting for Different Background Gases The factory calibration procedure for Delta F oxygen cells uses nitrogen as the reference background gas The Series 3 will measure oxygen incorrectly if the transport rate of oxygen through the cell diffusion barrier is different than the cell is calibrated for Therefore if you want to use a background gas other than nitrogen you must recalibrate the Series 3 for the desired gas The Series 3 can easily be recalibrated for a number of different background gases Correct your system for the appropriate background gas by referring to Table 2 6 on page 2 31 and entering the correct current multiplier into the Oxygen Probe Calibration section of the System Calibration Menu A detailed explanation and description of th
8. Once you complete the pressure connections you must set switch block S1 on the Series 3 channel card for either current or voltage depending on the type of pressure sensor you are using refer to C Setting Input Switches on page 1 15 STD TF PROBE 2 1 TIE CHANNEL 1 CHANNEL ALM A ALMB ALMA ALMB NO NCRIN NO C NC NO NCRTN NO C NC REC AUX REC AUX 4 85 1 2 24V i g 585 1 2 24V 00000 00000 AUX Terminal Blocks Figure 1 10 AUX Terminal Block Location Installing Optional Features September 2003 B Connecting the Four Wire or Self Powered Transmitter Use a four wire non shielded cable to make connections to the terminal block labeled AUX on the back of the electronics unit refer to Figure 1 10 on page 1 13 Use Table 1 5 below to make the proper pin connections Note Twisted pair cables work well with this circuit Table 1 5 Wire Connections for Four Wire or Self Powered Transmitters Connect To AUX Terminal Block Negative Lead Input pin RTN Positive Lead Output pin 2 aux input 2 or pin 1 aux input 1 IMPORTANT Connect the remaini
9. Clean the sensor and the sensor shield as described in Appendix A Then reinstall sensor Also install a proper filter i e sintered or coalescing element Return the probe to GE Panametrics for evaluation Return the probe to GE Panametrics for evaluation Return the probe to GE Panametrics for evaluation Screen always reads the wettest highest pro grammed mois ture calibration value while dis playing dew frost point Probe is saturated Liquid water present on sensor surface and or across electrical connections Shorted circuit on sensor Sensor is contaminated with conductive particles refer to Appendix A Improper cable connection N A Clean sensor and sensor shield as described in Appendix A Then reinstall sensor Run dry gas over sensor surface If high reading persists the probe is proba bly shorted and should be returned to GE Panametrics for evaluation Clean sensor and sensor shield as described in Appendix A Then reinstall sensor Check cable connections to both the probe and the Series 3 Troubleshooting and Maintenance 2 11 September 2003 Table 2 3 Troubleshooting Guide for Common Problems Continued Possible Cause System Response Screen always Open circuit on sensor N A Return probe to GE Panametrics for eval reads the driest uation lowest pro Non conductive material is Clean sensor and sensor shield as grammed mois t
10. Sensor or sensor shield affected by process contaminants refer to Appendix A Sensor is contaminated with conductive particles refer to Appendix A Sensor is corroded refer to Appendix A Sensor temperature is greater than 70 C 158 F Stream particles causing abra sion Probe reads too wet during dry down conditions or too dry in wet up conditions Probe reads too wet or too dry Probe reads too wet or too dry Probe reads high dew point Probe reads too wet or too dry Probe reads too dry Probe reads too wet or too dry Change the flow rate A change in dew point indicates the sample system is not at equilibrium or there is a leak Allow suf ficient time for sample system to equili brate and moisture reading to become steady Check for leaks Readings may be correct if the sampling point and main stream do not run under the same process conditions The differ ent process conditions cause readings to vary Refer to Appendix A for more information If sampling point and main stream conditions are the same check sample system pipes and any pipe between the sample system and main stream for leaks Also check sample sys tem for water adsorbing surfaces such as rubber or plastic tubing paper type fil ters or condensed water traps Remove or replace contaminating parts with stain less steel parts Clean the sensor and the sensor shield as described in Appendix A Then reinstall sensor
11. GE Panametrics Moisture Monitor Series 3 Service Manual LE September 2003 Process Control Instruments Moisture Monitor Series 3 Service Manual 910 110SA3 IATTENTION This manual contains instructions for Series 3 hygrometers equipped with the latest controller card p n 703 1250 This controller card supports the PanaCom PanaView user interface software GE Panametrics September 2003 Warranty Return Policy Each instrument manufactured by GE Panametrics is warranted to be free from defects in material and workmanship Liability under this warranty is limited to restoring the instrument to normal operation or replacing the instrument at the sole discretion of GE Panametrics Fuses and batteries are specifically excluded from any liability This warranty is effective from the date of delivery to the original purchaser If GE Panametrics determines that the equipment was defective the warranty period is one year for general electronic failures of the instrument one year for mechanical failures of the sensor If GE Panametrics determines that the equipment was damaged by misuse improper installation the use of unauthorized replacement parts or operating conditions outside the guidelines specified by GE Panametrics the repairs are not covered under this warranty The warranties set forth herein are exclusive and are in lieu of all other warranties whether statutory express or implied
12. September 2003 Performing a Calibration Test Adjustment Preliminary Steps Calibration Procedure If you modify the supplied cables or do not use standard GE Panametrics supplied cables you must perform a calibration test adjustment to test the cable and if necessary compensate for any error or offset introduced by splicing or long cable lengths This procedure is also recommended for testing the installation of GE Panametrics cables Use the following steps to perform a calibration adjustment 1 Power up the Series 3 2 Set up the matrix format on the screen to display MH Refer to Displaying Measurements on page 1 4 of the Programming Manual 3 Make sure the high low and zero reference values are recorded on the sticker located on the outside chassis of the Series 3 1 Disconnect the moisture probe from the cable leave the probe cable connected to the Series 3 and verify that the displayed MH value equals the zero reference value within 30 0003 MH Ifthe reading is within specification no further testing is necessary Ifthe reading is less than the specified reading previous recorded zero reference value on the sticker 40 0003 add this difference to the low reference value Ifthe reading is greater than the specified reading previous recorded zero reference value on sticker 40 0003 subtract this difference from the low reference value 2 Note the final corrected low reference value and rec
13. 900 901D1 A 31 September 2003 a gt p u g o e o e o 2 o zx oo 0 9 8 7 6 5 4 3 TEMPERATURE C a MOISTURE CONTENT PPMw HENRY S LAW CONSTANT w o oo 0 SATURATION VALUE TEMPERATURE PPMw DEW FROST POINT AT TEMPERATURE C A a e o N o a Libra ua du ud a E Figure A 2 Moisture Content Nomograph for Liquids 32 Application of the Hygrometer 900 901D1 September 2003 Stainless Steel Tubing soft soldered to cover 3 4 26 THD Female soft soldered to cover M2 Probe Rubber Septum Exhaust Soft Solder Metal Cover with Teflon Washer Glass Bottle Magnetic Stirrer Bar Magnetic Stirrer Figure A 3 Moisture Content Test Apparatus Application of the Hygrometer 900 901D1 A 33 September 2003 Solids Applications A In Line Measurements GE Panametrics moisture probes may be installed in line to continuously monitor the drying process of a solid Install one sensor at the process system inlet to monitor the moisture content of the drying gas and install a second sensor at the process system outlet to monitor the moisture content of the discharged gas When the two sensors read the same or close to the same dew point the drying process is complete For example a system of t
14. Oxide Moisture Sensors Since the moisture probe pore openings are small in relation to the size of most organic molecules admission into the sensor cavity is limited to much smaller molecules such as water Thus the surface of the aluminum oxide sensor which acts as a semi permeable membrane permits the measurement of water vapor pressure in organic liquids just as easily as it does in gaseous media In fact an accurate sensor electrical output will be registered whether the sensor is directly immersed in the organic liquid or it is placed in the gas space above the liquid surface As with gases the electrical output of the aluminum oxide sensor is a function of the measured water vapor pressure Moisture Content Henry s Law Type Analysis Measurement Organic When using the aluminum oxide sensor in non polar liquids having Liquids water concentrations lt 1 by weight Henry s Law is generally applicable Henry s Law states that at constant temperature the mass of a gas dissolved in a given volume of liquid is proportional to the partial pressure of the gas in the system Stated in terms pertinent to this discussion it can be said that the PPMy of water in hydrocarbon liquids is equal to the partial pressure of water vapor in the system times a constant As discussed above a GE Panametrics aluminum oxide sensor can be directly immersed in a hydrocarbon liquid to measure the equivalent dew point Since the dew point is fun
15. September 2003 Connecting the Alarms cont STD TF PROB CHANNEL 1 CHANNEL AUX REG AUX V er o 0000 o 0000 o OXYGEN o o oonourwm HAZARDOUS AREA CONNECTIONS OH 1 2 3 4 5 2 MAE NS RA and ALM B Terminal Blocks Figure 1 6 ALM A and ALM B Terminal Block Locations 1 8 Installing Optional Features September 2003 Connecting Pressure Sensor Inputs The Series 3 accepts either pressure transducers or pressure transmitters with 0 4 to 20 mA or 0 to 2 V output Each type of sensor is connected to the Series 3 differently therefore it is important to know which type of pressure sensor you are using IMPORTANT The transducer must be supplied by GE Panametrics or approved by GE Panametrics for use in this circuit A pressure transducer is an electrically passive device that requires a well regulated excitation voltage or current The transducer produces a low level signal output typically in the millivolt or microamp range wh
16. 1 500 1 000 800 600 500 400 300 200 150 100 80 60 50 40 30 DEW FROST POINT F DEW FROST POINT C PRESSURE PSIG PRESSURE ATMOSPHERES MOISTURE CONTENT PPM by volume Figure A 1 Moisture Content Nomograph for Gases A 20 Application of the Hygrometer 900 901D1 Comparison of PPMy Calculations September 2003 EO _ _ There are three basic methods for determining the moisture content of a gas in PPMy the calculations described in this appendix calculations performed with the slide rule device that is provided with each GE Panametrics hygrometer values determined from tabulated vapor pressures For comparison purposes examples of all three procedures are listed in Table A 4 below Table 4 Comparative PPMy Values Application of the Hygrometer 900 901D1 Calculation Method DewPoint Pressure Appendix Vapor psig Slide Rule A Pressure 80 0 0 5 0 55 0 526 100 0 065 N A 0 0675 800 0 009 N A 0 0095 1500 0 005 N A 0 0051 50 0 37 40 38 88 100 4 8 5 2 4 98 800 0 65 0 8 0 7016 1500 0 36 0 35 0 3773 20 0 20 000 23 072 36 100 3000 3000 2956 9 800 420 400 416 3105 1500 220 200 223 9 21 September 2003 Liquid Applications Theory of Operation The direct measurement of water vapor pressure in organic liquids is accomplished easily and effectively with GE Panametrics Aluminum
17. 187 54 189 20 190 90 192 60 194 30 66 196 09 197 80 199 50 201 30 203 10 67 204 96 206 80 208 60 210 50 212 30 68 214 17 216 00 218 00 219 90 221 80 69 223 73 225 70 227 70 229 70 231 70 70 233 70 235 70 237 70 239 70 241 80 71 243 90 246 00 248 20 250 30 252 40 72 254 60 256 80 259 00 261 20 263 40 73 265 70 268 00 270 20 272 60 274 80 74 277 20 279 40 281 80 284 20 286 60 75 289 10 291 50 294 00 296 40 298 80 76 301 40 303 80 306 40 308 90 311 40 77 314 10 316 60 319 20 322 00 324 60 78 327 30 330 00 332 80 335 60 338 20 79 341 00 343 80 346 60 349 40 352 20 80 355 10 358 00 361 00 363 80 366 80 81 369 70 372 60 375 60 378 80 381 80 82 384 90 388 00 391 20 394 40 397 40 83 400 60 403 80 407 00 410 20 413 60 Application of the Hygrometer 900 901D1 September 2003 Table 1 Vapor Pressure of Water Continued Aqueous Vapor Pressure Over Water cont Temp C 0 0 0 2 0 4 0 6 0 8 84 416 80 420 20 423 60 426 80 430 20 85 433 60 437 00 440 40 444 00 447 50 86 450 90 454 40 458 00 461 60 465 20 87 468 70 472 40 476 00 479 80 483 40 88 487 10 491 00 494 70 498 50 502 20 89 506 10 510 00 513 90 517 80 521 80 90 525 76 529 77 533 80 537 86 541 95 91 546 05 550 18 554 35 558 53 562 75 92 566 99 571 26 575 55 579 87 584 22 93 588 60 593 00 597 43 601 89 606 38 94 610 90 615 44 620 01 624 61 629 24 95 633 90 638 59 643 30 648 05 652 82 96 657 62 662 45 667 31 672 20 677 12 97 682 07 687 04 692 05 697 10 702 17
18. 3 816 3 753 3 691 3 630 1 4 217 4 147 4 079 4 012 3 946 0 4 579 4 504 4 431 4 359 4 287 Application of the Hygrometer 900 901D1 A 15 September 2003 eee Table A 1 Vapor Pressure of Water Continued Aqueous Vapor Pressure Over Water Temp C 0 0 0 2 0 4 0 6 0 8 0 4 579 4 647 4 715 4 785 4 855 1 4 926 4 998 5 070 5 144 5 219 2 5 294 5 370 5 447 5 525 5 605 3 5 685 5 766 5 848 5 931 6 015 4 6 101 6 187 6 274 6 363 6 453 5 6 543 6 635 6 728 6 822 6 917 6 7 013 7 111 7 209 7 309 7 411 7 7 513 7 617 7 722 7 828 7 936 8 8 045 8 155 8 267 8 380 8 494 9 8 609 8 727 8 845 8 965 9 086 10 9 209 9 333 9 458 9 585 9 714 11 9 844 9 976 10 109 10 244 10 380 12 10 518 10 658 10 799 10 941 11 085 13 11 231 11 379 11 528 11 680 11 833 14 11 987 12 144 12 302 12 462 12 624 15 12 788 12 953 13 121 13 290 13 461 16 13 634 13 809 13 987 14 166 14 347 17 14 530 14 715 14 903 15 092 15 284 18 15 477 15 673 15 871 16 071 16 272 19 16 477 16 685 16 894 17 105 17 319 20 17 535 17 753 17 974 18 197 18 422 21 18 650 18 880 19 113 19 349 19 587 22 19 827 20 070 20 316 20 565 20 815 23 21 068 21 324 21 583 21 845 22 110 24 22 377 22 648 22 922 23 198 23 476 25 23 756 24 039 24 326 24 617 24 912 26 25 209 25 509 25 812 26 117 26 426 27 26 739 27 055 27 374 27 696 28 021 28 28 349 28 680 29 015 29 354 29 697 29 30 043 30 392 30 745 31 102 31 461 30 31 824 32 191 32 561 32 934 33 312 31 33 695 34 082 34 471 34 864 35 261 32 35 663
19. Channel 2 19 Entering Reference Values for a Channel Card 2 21 Replacing and Recalibrating the Moisture Probes 2 25 Recalibrating the Pressure Sensors 2 25 Calibrating the Delta F Oxygen Cell 2 26 Delta F Oxygen Cell Background Gas Correction Factors 2 29 Range Error Description 2 32 Signal Error Description 2 32 Calibration Error Description 2 32 September 2003 9 EO Introduction The Moisture Image Series 3 is designed to be maintenance and trouble free however because of process conditions and other factors minor problems may occur Some of the most common problems and procedures are discussed in this section If you cannot find the information you need in this section please consult GE Panametrics Caution Do not attempt to troubleshoot the Series 3 beyond the instructions in this section If you do you may damage the unit and void the warranty This section includes the following information Testing the Alarm Relays Testing the Recorder Outputs Trimming the Recorder Outputs Screen Messages Common Problems Checking and Replenishing the Electrolyte in the Delta F Oxygen Cell Adding or Removing a PCMCIA Card Recharging the Battery Pack Installing a Channel Card Entering Referenc
20. N J N mall Onn ip 10000000 cu 40000000 FEN oO oY 5 i 0 0 E F 000 0000 uw EN EN S AN 5 Figure 1 3 S2 and S3 Locations on the Channel Card Installing Optional Features 1 5 September 2003 Connecting the Recorders Connect the recorders to the terminal block on the back panel labeled REC See Figure 1 4 below for terminal block location Make connections for recorder outputs using Table 1 1 below Table 1 1 Recorder Connections Connect Recorder A To REC Terminal Block out pin A return pin A Connect Recorder B To REC Terminal Block w tc OXYGEN P e o AZARDOUS A CONNECTIONS CHANNEL 1 ALM A ALMB NO C NC NO C NC BEENDEN AUX 3 69 ALMA ALI NO NC RTN NO C NC su vg AREG UX 40559 o
21. Road Cheam Surrey SM2 7AJ England Telephone 020 8643 5150 Fax 020 8643 4225 E mail uksales panametrics ie USA GE Panametrics 221 Crescent Street Suite 1 Waltham MA 02453 3497 Telephone 781 899 2719 Toll free 800 833 9438 Fax 781 894 8582 E Mail panametrics ps ge com Web www gepower com panametrics Ireland GE Panametrics Shannon Industrial Estate Shannon County Clare Ireland Telephone 353 61 470200 Fax 353 61 471359 E Mail info 9 panametrics ie
22. compressed the partial pressures of all the gaseous components are proportionally increased Conversely when a gas expands the partial pressures of the gaseous components are proportionally decreased Therefore increasing the pressure on a closed aqueous system will increase the vapor pressure of the water and hence increase the dew point This is not just a mathematical artifact The dew point of a gas with 1000 PPMv of water at 200 psig will be considerably higher than the dew point of a gas with 1000 PPMv of water at 1 atm Gaseous water vapor will actually condense to form liquid water at a higher temperature at the 200 psig pressure than at the 1 atm pressure Thus if the moisture probe is exposed to pressure changes the measured dew point will be altered by the changed vapor pressure of the water It is generally advantageous to operate the hygrometer at the highest possible pressure especially at very low moisture concentrations This minimizes wall effects and results in higher dew point readings which increases the sensitivity of the instrument Response Time The response time of the GE Panametrics standard M Series Aluminum Oxide Moisture Sensor is very rapid a step change of 63 in moisture concentration will be observed in approximately 5 seconds Thus the observed response time to moisture changes is in general limited by the response time of the sample system as a whole Water vapor is absorbed tenaciously by many materi
23. including warranties or merchantability and fitness for a particular purpose and warranties arising from course of dealing or usage or trade If a GE Panametrics instrument malfunctions within the warranty period the following procedure must be completed 1 Notify GE Panametrics giving full details of the problem and provide the model number and serial number of the instrument If the nature of the problem indicates the need for factory service GE Panametrics will issue a RETURN AUTHORIZATION NUMBER RAN and shipping instructions for the return of the instrument to a service center will be provided 2 If GE Panametrics instructs you to send your instrument to a service center it must be shipped prepaid to the authorized repair station indicated in the shipping instructions 3 Upon receipt GE Panametrics will evaluate the instrument to determine the cause of the malfunction Then one of the following courses of action will then be taken f the damage is covered under the terms of the warranty the instrument will be repaired at no cost to the owner and returned f GE Panametrics determines that the damage is not covered under the terms of the warranty or if the warranty has expired an estimate for the cost of the repairs at standard rates will be provided Upon receipt of the owner s approval to proceed the instrument will be repaired and returned lii September 2003 Table of Contents Chapter 1 Instal
24. n STD TF PROBE OXYGEN CHANNEL 2 MB 0 0 0 0 0 0 REC Terminal Block Figure 1 4 REC Terminal Block Location 1 6 Installing Optional Features September 2003 Connecting the Alarms You can order the Series 3 with optional high and low alarm relays Hermetically sealed alarm relays are also available Each alarm relay is a single pole double throw relay that contains the following contacts see Figure 1 5 below normally closed NC armature contacts normally open Use Table 1 2 below to make connections for the high and low alarm relays on the terminal block labeled ALM A and ALM on the back panel of the electronics unit See Figure 1 6 on page 1 8 for the terminal block location Table 1 2 Alarm Connections Connect Low Alarm To ALM Terminal Block NC contact C contact NO contact Connect High Alarm To ALM Terminal Block NC contact C contact NO contact Note The alarm terminal block has an additional Return connection that you can use to ground the alarms if desired See Figure 1 6 on page 1 8 Figure 1 5 Alarm Relay Contact Points Installing Optional Features 1 7
25. or actual gas temperature is known the table will yield the saturated water vapor pressure Ps in mm of Hg Water Vapor Pressure Over Ice Temp 0 2 4 6 8 90 0 000070 0 000048 0 000033 0 000022 0 000015 80 0 000400 0 000290 0 000200 0 000140 0 000100 70 0 001940 0 001430 0 001050 0 000770 0 000560 60 0 008080 0 006140 0 004640 0 003490 0 002610 50 0 029550 0 023000 0 017800 0 013800 0 010600 40 0 096600 0 076800 0 060900 0 048100 0 037800 30 0 285900 0 231800 0 187300 0 150700 0 120900 Temp 0 0 0 2 0 4 0 6 0 8 29 0 317 0 311 0 304 0 298 0 292 28 0 351 0 344 0 337 0 330 0 324 27 0 389 0 381 0 374 0 366 0 359 26 0 430 0 422 0 414 0 405 0 397 25 0 476 0 467 0 457 0 448 0 439 24 0 526 0 515 0 505 0 495 0 486 23 0 580 0 569 0 558 0 547 0 536 22 0 640 0 627 0 615 0 603 0 592 21 0 705 0 691 0 678 0 665 0 652 20 0 776 0 761 0 747 0 733 0 719 19 0 854 0 838 0 822 0 806 0 791 18 0 939 0 921 0 904 0 887 0 870 17 1 031 1 012 0 993 0 975 0 956 16 1 132 1 111 1 091 1 070 1 051 15 1 241 1 219 1 196 1 175 1 153 14 1 361 1 336 1 312 1 288 1 264 13 1 490 1 464 1 437 1 411 1 386 12 1 632 1 602 1 574 1 546 1 518 11 1 785 1 753 1 722 1 691 1 661 10 1 950 1 916 1 883 1 849 1 817 9 2 131 2 093 2 057 2 021 1 985 8 2 326 2 285 2 246 2 207 2 168 7 2 537 2 493 2 450 2 408 2 367 6 2 765 2 718 2 672 2 626 2 581 5 3 013 2 962 2 912 2 862 2 813 4 3 280 3 225 3 171 3 117 3 065 3 3 568 3 509 3 451 3 393 3 336 2 3 880
26. pulling the board straight up see Figure 2 4 on page 2 19 Insert the new channel card into the vacant slot Push down on the board and make sure it makes contact with the connectors on the bottom of the unit Replace the retainer bar Make sure the slots on the retainer bar are seated correctly against the printed circuit boards Secure the bar with two screws Replace the cover on the electronics unit Make sure when you are sliding the electronics into the enclosure the electronics line up with the sliding guides on the inside of the enclosure Replace the screws in the front panel Do not over tighten the screws You have completed installing the channel card Enter calibration data as described in Entering Calibration Data for New Probes Sensors on page 3 37 of the Programming Manual and reference data as described in the next section 2 20 Troubleshooting and Maintenance September 2003 Entering Reference Values for a Channel Card The high and low reference values are entered at the factory However if you replace the channel card you will have to re enter the reference values for moisture oxygen and pressure The references are unit specific factory calibration values Reference values are located on a label placed on the left side of the Series 3 chassis Compare the data on the Series 3 screen to the reference data printed on the label placed on the side of the unit or supplied with the
27. replacement channel card If the replacement channel card is the old version for models with serial numbers below 2001 the label is on the back of the card If the replacement card is the new version the values are on a tag attached to the card Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Note f you have already entered the user program refer to the menu maps in the Programming Manual to navigate in the Programming Menu Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 Use the arrow keys to move the SYSTEM AUTOCALD brackets to SYSTEM and press YES Measurement Mode 1 You only need to enter reference H T P AUX1 gt data for moisture oxygen and or pressure Use the arrow keys to move to the desired measurement mode and press YES Refer to Table 2 4 on page 2 22 for a list of available measurement modes Troubleshooting and Maintenance 2 21 September 2003 Entering Reference Values for a Channel Card cont Entering Moisture Reference Data Table 2 4 Measurement Modes Display Abbreviation Measurement Mode Oxygen Hygrometry Temperature Pressure AUXI Auxiliary 1 AUX2 Auxiliary 2 CONSTANT PPMV PPMv Multiplication Factor System Menu 1 Usethe arrow keys to move the CONFIG REF gt brac
28. step Ifthe charge time is acceptable press YES followed by RUN Battery Test 1 Use the arrow keys to move to Change ChgTime CHANGE CHGTIME and press YES Time to Charge Bat 1 Enter the desired value and press XX XX HH MM YES To exit press RUN The Series 3 will charge for 16 hours 960 minutes When the Series 3 is charging it displays a reverse video C in the right hand corner of the display 2 18 Troubleshooting and Maintenance September 2003 nn ren Installing a Channel The Series 3 can have up to two channel cards If you need to replace Card one GE Panametrics will ship you a channel card that you can insert into the electronics unit Use the following steps to install a channel card 1 Turn the Series 3 off and unplug the main AC power cord WARNING Remove power by disconnecting the main AC power cord before proceeding with this procedure 2 To access the channel cards remove the screws on the front panel and slide the electronics unit out of its enclosure Caution Channel cards can be damaged by static electricity Observe ESD handling precautions 3 Remove the retainer bar by removing the two screws on the outside of the chassis see Figure 2 4 below Retainer Bar Channel Cards Figure 2 4 Location of the Channel Cards Troubleshooting and Maintenance 2 19 September 2003 Installing a Channel Card cont Remove the old channel card by
29. steps To exit select DONE followed by RUN 2 2 Troubleshooting and Maintenance September 2003 Testing the Recorder Outputs The Recorder Output Test Menu enables you to test outputs to make sure they are operating properly When you enter this menu the Series 3 stops making measurements Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Note f you have already entered the user program refer to the menu maps in Chapter 3 of the Programming Manual to navigate to the Programming Menu Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 Use the arrow keys to move the rEsT CONTRAST brackets to TEST and press YES Test Menu 1 Usethe arrow keys to move to ALARM RECORDER gt RECORDER and press YES Select Recorder 1 Use the arrow keys to move the A B brackets to the recorder you want to test and press YES Select RCD Range Use the arrow keys to move the 0 20mA 4 20mA P brackets to the output range and press YES RCD Test Option Use the arrow keys to move the SCALE TRIM brackets to SCALE and press YES Percent of Scale 1 Enter the percentage between 0 50 and 100 and press YES The recorder pen should swing to the appropriate value Press YES Note The recorder output depends on th
30. 1 on page A 20 connect 60 psig on the Pressure scale with 20 C on the Dew Frost Point scale Read 200 PPMy on the Moisture Content scale 2 Find the expected dew frost point for a helium gas stream having measured moisture content of 1000 PPM and a system pressure of 0 52 atm Solution In Figure A 1 on page A 20 connect 1000 PPM on the Moisture Content scale with 0 52 atm on the Pressure scale Read the expected frost point of 27 C on the Dew Frost Point scale Application of the Hygrometer 900 901D1 September 2003 Parts per Million by Weight Relative Humidity Weight of Water per Unit Volume of Carrier Gas The water concentration in the gas phase of a system in parts per million by weight can be calculated directly from the PPMy and the ratio of the molecular weight of water to that of the carrier gas as follows My PEM pS BEM YX 2 2 Relative humidity is defined as the ratio of the actual water vapor pressure to the saturation water vapor pressure at the prevailing ambient temperature expressed as a percentage P RH x 100 2 3 Ps 1 Find the relative humidity in a system if the measured dew point is 0 C and the ambient temperature is 20 C Solution From Table 1 on page A 20 the water vapor pressure at dew point of 0 C is 4 579 mm of Hg and the saturation water vapor pressure at an ambient temperature of 20 C is 17 535 mm of Hg Therefore the relative humidity of the s
31. 10 000 PPM 2 5 to 10 Hydrogen H5 Helium He Methane CH3 Ethane C2H6 Propylene C3H6 Propane C4Hg Butene C4Hg Butane C4H 0 Butadiene C6H6 Acetylene C2H3 Hexane 4 Cyclohexane CH gt Vinyl Chloride CH CHC Vinylidene Chloride gt Neon Ne Xenon Xe Krypton Kr Sulfur Hexaflouride SF Freon 318 C4Fg Tetrafluoromethane CF4 Carbon Monoxide CO Troubleshooting and Maintenance September 2003 September 2003 Range Error Description Signal Error Description Calibration Error Description Range Errors occur when an input signal that is within the capacity of the analyzer exceeds the calibration range of the probe The Series 3 displays Range Errors with an Over Rng or Under Rng message The error condition extends to all displayed measurements of that mode For example if dew point displays Over Rng then moisture in PPMv will also display Over Rng In addition since several moisture modes such as RH ppmv PPMw and MMSCE are dependent on more than one input to calculate their results some modes can generate an error opposite to the initial error For example RH is dependent on moisture and temperature The nature of the RH calculation is such that low temperatures result in ahigh RH Therefore it is possible for tem
32. 22 all in the Programming Man ual data is OK turn power off and then on If RAM error occurs again replace battery Troubleshooting and Maintenance 2 9 September 2003 Table 2 2 Screen Messages and the Possible Causes Continued Screen Message Possible Cause System Response Action Sig E r See Signal Error Descrip tion on page 2 33 Under Rng See Range Error Descrip tion on page 2 33 The input signal from the probe exceeds the capacity of the analyzer electronics The input signal is below the calibrated range of the probe Alarms and recorders respond as programmed Refer to page 2 33 Alarms and recorders respond as programmed Refer to page 2 33 Check for a short in the probe Contact GE Panametrics Check wiring for shorts Contact GE Panametrics 2 10 Troubleshooting and Maintenance September 2003 Common Problems Symptom If the Series 3 measurement readings seem strange or do not make sense there may be a problem with the probe or a component of the process system Table 2 3 below contains some of the most common problems that affect measurements Possible Cause System Response Table 2 3 Troubleshooting Guide for Common Problems Action Accuracy of mois ture sensor is ques tioned Insufficient time for system to equilibrate Dew point at sampling point is different than the dew point of the main stream
33. 326 1998 Class A Annex A Continuous Unmonitored Operation EN 61010 1 1993 A2 1995 Overvoltage Category II Pollution Degree 2 gem den Europ ischen Richtlinien Niederspannungsrichtlinie Nr 73 23 EWG und EMV Richtlinie Nr 89 336 EWG Die oben aufgef hrten Ger te und zugeh rige mitgelieferte Sensoren und Handhabungssysteme tragen keine CE Kennzeichnung gem der Druckger te Richtlinie da sie in bereinstimmung mit Artikel 3 Absatz 3 gute Ingenieurpraxis der Druckger te Richtlinie 97 23 EG f r DN lt 25 geliefert werden Shannon June 1 2002 Et Mr James Gibson GENERALDIREKTOR LS ENISO9002 T V ESSEN Shannon ISO 9001 U S CERT DOC Rev G2 5 28 02 GE Panametrics WORLDWIDE OFFICES MAIN OFFICES GE PANAMETRICS INTERNATIONAL OFFICES USA Australia Japan GE Panametrics P O Box 234 2F Sumitomo Bldg 221 Crescent St Suite 1 Gymea N S W 2227 5 41 10 Koishikawa Bunkyo Ku Waltham MA 02453 3497 Australia Tokyo 112 0002 USA Telephone 781 899 2719 Toll Free 800 833 9438 Fax 781 894 8582 E mail panametrics ps ge com Web www gepower com panametrics ISO 9001 Certified Ireland GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland Telephone 353 61 470200 Fax 353 61 471359 E mail info panametrics ie 150 9002 Certified July 2003 Telephone 61 02 9525 4055 Fax 61 02 9526 2776 E mail panametrics panametrics com au Au
34. 36 068 36 477 36 891 37 308 33 37 729 38 155 38 584 39 018 39 457 34 39 898 40 344 40 796 41 251 41 710 35 42 175 42 644 43 117 43 595 44 078 36 44 563 45 054 45 549 46 050 46 556 37 47 067 47 582 48 102 48 627 49 157 38 49 692 50 231 50 774 51 323 51 879 39 52 442 53 009 53 580 54 156 54 737 40 55 324 55 910 56 510 57 110 57 720 41 58 340 58 960 59 580 60 220 60 860 16 Application of the Hygrometer 900 901D1 Table 1 Vapor Pressure of Water Continued September 2003 EEO __ _ Aqueous Vapor Pressure Over Water cont Temp C 0 0 0 2 0 4 0 6 0 8 42 61 500 62 140 62 800 63 460 64 120 43 64 800 65 480 66 160 66 860 67 560 44 68 260 68 970 69 690 70 410 71 140 45 71 880 72 620 73 360 74 120 74 880 46 75 650 76 430 77 210 78 000 78 800 47 79 600 80 410 81 230 82 050 82 870 48 83 710 84 560 85 420 86 280 87 140 49 88 020 88 900 89 790 90 690 91 590 50 92 51 93 50 94 40 95 30 96 30 51 97 20 98 20 99 10 100 10 101 10 52 102 09 103 10 104 10 105 10 106 20 53 107 20 108 20 109 30 110 40 111 40 54 112 51 113 60 114 70 115 80 116 90 55 118 04 119 10 120 30 121 50 122 60 56 123 80 125 00 126 20 127 40 128 60 57 129 82 131 00 132 30 133 50 134 70 58 136 08 137 30 138 50 139 90 141 20 59 142 60 143 90 145 20 146 60 148 00 60 149 38 150 70 152 10 153 50 155 00 61 156 43 157 80 159 30 160 80 162 30 62 163 77 165 20 166 80 168 30 169 80 63 171 38 172 90 174 50 176 10 177 70 64 179 31 180 90 182 50 184 20 185 80 65
35. 9 Materials of Construction A 10 Calculations and Useful Formulas in Gas Applications A 11 Liquid Applications A 22 Empirical 28 Solids lt A 34 September 2003 Introduction This appendix contains general information about moisture monitoring techniques System contaminants moisture probe maintenance process applications and other considerations for ensuring accurate moisture measurements are discussed The following specific topics are covered Moisture Monitor Hints Contaminants Aluminum Oxide Probe Maintenance Corrosive Gases and Liquids Materials of Construction Calculations and Useful Formulas in Gas Applications Liquid Applications Empirical Calibrations e Solids Applications Application of the Hygrometer 900 901D1 A 1 September 2003 _ Moisture Monitor Hints GE Panametrics hygrometers using aluminum oxide moisture probes have been designed to reliably measure the moisture content of both gases and liquids The measured dew point will be the real dew point of the system at the measurement location and at the time of measurement However no moisture sensor can determine the origin of the measured moisture content In addition to the moistur
36. 98 707 27 712 40 717 56 722 75 727 98 99 733 24 738 53 743 85 749 20 754 58 100 760 00 765 45 770 93 776 44 782 00 101 787 57 793 18 798 82 804 50 810 21 18 Application of the Hygrometer 900 901D1 September 2003 fl Table A 2 Maximum Gas Flow Rates Based on the physical characteristics of air at a temperature of 77 F and a pressure of I atm the following flow rates will produce the maximum allowable gas stream linear velocity of 10 000 cm sec in the corresponding pipe sizes Inside Pipe Diameter in Gas Flow Rate cfm 0 25 7 0 50 27 0 75 60 1 0 107 2 0 429 3 0 966 4 0 1 718 5 0 2 684 6 0 3 865 7 0 5 261 8 0 6 871 9 0 8 697 10 0 10 737 11 0 12 991 12 0 15 461 Table A 3 Maximum Liquid Flow Rates Based on the physical characteristics of benzene at a temperature of 77 F the following flow rates will produce the maximum allowable fluid linear velocity of 10 cm sec in the corresponding pipe sizes Inside Pipe Diameter in Flow Rate gal hr Flow Rate l hr 0 25 3 11 0 50 12 46 0 75 27 103 1 0 48 182 2 0 193 730 3 0 434 1 642 4 0 771 2 919 5 0 1 205 4 561 6 0 1 735 6 567 7 0 2 361 8 939 8 0 3 084 11 675 9 0 3 903 14776 10 0 4 819 18 243 11 0 5 831 22 074 12 0 6 939 26 269 Application of the Hygrometer 900 901D1 September 2003 ee 10 000 8 000 10 000 6 000 8 000 5 000 4 000 6 000 5 000 8 000 4 000 2 000 3 000 2 000
37. a Inputs 0 4 20 mA or 0 2 VDC output including a variety of process control instruments available from GE Panametrics Inputs may be self or loop powered Self powered inputs are either current or voltage Loop powered inputs are usually current In either case after you make connections to the electronics unit you must set the switch block on the channel card for current or voltage depending on the type of input you are using Use the instructions that follow to connect and set up the auxiliary inputs Use Figure 1 13 below as a guide for making auxiliary input connections to the terminal block labeled AUX on the back of the electronics unit 4 20 mA 4 20 mA Transmitter Loop Powered 4 20 mA Transmitter Self Powered Voltage Output Signal Figure 1 13 Auxiliary Input Connections Installing Optional Features 1 17 September 2003 Connecting Auxiliary After making auxiliary input connections you must set switch block Inputs cont S1 the Series 3 channel card for current or voltage input as described in the following sections Accessing the Channel 1 Remove the screws on the front panel and slide the electronics unit Card out of its enclosure 2 Remove the retainer bar by removing the two screws on the outside of the chassis see Figure 1 14 below 3 Remove the channel card by sliding it straight up
38. actory and must remain at this setting for normal operation 7 Replace the controller card 8 Slide the electronics unit back into place on the Series 3 and reinsert the screws on the front panel 9 Plug in the meter Troubleshooting and Maintenance 2 15 September 2003 Adding or Removing a PCMCIA Card cont PCMCIA Card E 3 0 0 0 sale us vw is C26 G CRI MULA nnmnnnmmonnn Figure 2 3 Insertion of the PCMCIA Card on the Controller Board 2 16 Troubleshooting and Maintenance September 2003 Recharging the Battery When the battery pack is fully charged it provides 8 hours of Pack continuous operation continuous use of the backlight and or alarms will shorten the battery life approximately 1 2 hours When the battery pack needs recharging a Battery Low message appears on the display You can recharge the battery pack using either an auto charge or a full charge The Series 3 begins an auto charge when you plug it into AC line power and turn it on An auto charge recharges the battery pack for twice as long as the unit ran off of battery power For example if the unit ran of
39. adsit Prae e Ba cn 4 2 ee Eee BB u Bea a 5 Non Conductive Particulates cece eens 5 Conductive Particulates aa es A 6 Corrosive Particulates 2 2 8 aa ann ra ieh A 6 Aluminum Oxide Probe A 7 Corrosive Gases And Liquids sr re eyes A 9 Materials of Construction s renes m 10 Calculations and Useful Formulas in Gas Applications A 11 Nomenclature i ass a gen Re ee ao er ed 11 Parts per Million by Volume ssseeeeeeeeeee arere A 12 Parts per Million by Weight 0 0 III A 13 Relative eem elm e pep RU ed eee eheu Nu Rees ie A 13 Weight of Water per Unit Volume of Carrier A 13 Weight of Water per Unit Weight of Carrier A 14 Comparison of PPMV Calculations 00 eee eee A 21 Liquid Applications oio rb nee iw Pee htt ao Dace bare A 22 Theory of Operation o Diner me A 22 Moisture Content Measurement in Organic 4 A 22 Empirical Calibrations sce gm Ye adhe A 28 Solids Appl Cations ss s s ey ea ie ea emg heeled went Abe A eae A 34 vii Chapter 1 Installing Optional Feature
40. al different moisture contents have been analyzed Note The accuracy of this technique can be checked at any point by withdrawing a sample and performing a Karl Fischer titration Be aware that this will change the total liquid weight in calculating the next point A 30 Application of the Hygrometer 900 901D1 September 2003 C Additional Notes for Liquid Applications In addition to the topics already discussed the following general application notes pertain to the use of GE Panametrics moisture probes in liquid applications 1 Series Aluminum Oxide Moisture Sensors can be used in either the gas phase or the liquid phase However for the detection of trace amounts of water in conductive liquids for which an empirical calibration is required the M2 Sensor is recommended Since a background signal is caused by the conductivity of the liquid between the sensor lead wires use of the M2 Sensor which has the shortest lead wires will result in the best sensitivity The calibration data supplied with GE Panametrics Moisture Probes is applicable to both liquid phase for those liquids in which a Henry s Law analysis is applicable and gas phase applications As indicated in Table A 3 on page A 19 the flow rate of the liquid is limited to a maximum of 10 cm sec Possible probe malfunctions and their remedies are discussed in the Troubleshooting chapter of this manual Application of the Hygrometer
41. als and a large complex processing system can take several days to dry down from atmospheric moisture levels to dew points of less than 60 C Even simple systems consisting of a few feet of stainless steel tubing and a small chamber can take an hour or more to dry down from dew points of 5 C to 70 C The rate at which the system reaches equilibrium will depend on flow rate temperature materials of construction and system pressure Generally speaking an increase in flow rate and or temperature will decrease the response time of the sample system Application of the Hygrometer 900 901D1 A 3 September 2003 Response Time cont Temperature Flow Rate To minimize any adverse affects on response time the preferred materials of construction for moisture monitoring sample systems are stainless steel Teflon and glass Materials to be avoided include rubber elastomers and related compounds The GE Panametrics hygrometer is largely unaffected by ambient temperature However for best results it is recommended that the ambient temperature be at least 10 C higher than the measured dew point up to a maximum of 70 C Because an ambient temperature increase may cause water vapor to be desorbed from the walls of the sample system it is possible to observe a diurnal change in moisture concentration for a system exposed to varying ambient conditions In the heat of the day the sample system walls will be warmed by the a
42. alysis on a sample of the liquid or obtain a dry sample of the liquid Either use the PPMy determined by the Karl Fischer analysis or add a known amount of water i e 10 PPMy to the dry sample Measure the dew point of the known test sample with the GE Panametrics hygrometer For purposes of this example assume the measured dew point to be 10 C Using a straightedge on the nomograph in Figure 2 on page A 32 connect the known 10 PPMy moisture content with the measured dew point of 10 C and read a K value of 5 1 on the center scale Using the straightedge connect the above K value of 5 1 with the measured 10 dew point of the original liquid and read the actual moisture content of 47 PPM y on the left scale A 26 Application of the Hygrometer 900 901D1 September 2003 FF fl B Special Case cont Note The saturation value at 50 C for this liquid could also have been determined by connecting the K value of 5 1 with the ambient temperature of 50 C and reading a value of 475 PPMy on the right scale For many applications a knowledge of the absolute moisture content of the liquid is not required Either the dew point of the liquid or its percent saturation is the only value needed For such applications the saturation value for the liquid need not be known The GE Panametrics hygrometer can be used directly to determine the dew point and then the percent saturation can be calculated fr
43. ard moisture probe can not be used in such applications unless the complete removal of such part by adequate filtration is assured A 6 Application of the Hygrometer 900 901D1 September 2003 Aluminum Oxide Probe Maintenance Other than periodic calibration checks little or no routine moisture probe maintenance is required However as discussed in the previous section any electrically conductive contaminant trapped on the aluminum oxide sensor will cause inaccurate moisture measurements If such a situation develops return of the moisture probe to the factory for analysis and recalibration is recommended However in an emergency cleaning of the moisture probe in accordance with the following procedure may be attempted by a qualified technician or chemist IMPORTANT Moisture probes must be handled carefully and cannot be cleaned in any fluid which will attack its components The probe s materials of construction are Al nichrome gold stainless steel glass and Viton A Also the sensor s aluminum sheet is very fragile and can be easily bent or distorted Do not permit anything to touch it The following items will be needed to properly complete the moisture probe cleaning procedure approximately 300 ml of reagent grade hexane or toluene approximately 300 ml of distilled not deionized water two glass containers to hold above liquids metal containers should not be used To clean the moisture p
44. ave been eliminated and the sample system has been allowed to come to equilibrium then the measured dew point will equal the actual dew point of the process fluid Some of the most frequently encountered problems associated with moisture monitoring sample systems include the moisture content value changes as the total gas pressure changes the measurement response time is very slow the dew point changes as the fluid temperature changes the dew point changes as the fluid flow rate changes A 2 Application of the Hygrometer 900 901D1 September 2003 tl Moisture Monitor Hints GE Panametrics hygrometers measure only water vapor pressure In cont addition the instrument has a very rapid response time and it is not affected by changes in fluid flow rate If any of the above situations occur then they are almost always caused by a defect in the sample system The moisture sensor itself can not lead to such problems Pressure GE Panametrics hygrometers can accurately measure dew points under pressure conditions ranging from vacuums as low as a few microns of mercury up to pressures of 5000 psig The calibration data supplied with the moisture probe is directly applicable over this entire pressure range without correction Note Although the moisture probe calibration data is supplied as meter reading vs dew point it is important to remember that the moisture probe responds only to water vapor pressure When a gas is
45. ber 2003 Entering Pressure Reference Data P HiRef Lo Ref Enter the low pressure value 0 05 0 00 Press YES and press the left arrow key P Hi Ref LoRef 1 Enter the low reference value 0 05 99 89 and press YES Press the NO key You may now do one of the following Enter data moisture or oxygen reference data by pressing the NO key until you return to Measurement Mode then select the desired mode and press YES Refer to Entering Moisture Reference Data on page 2 22 or Entering Oxygen Reference Data on page 2 23 Refer to another section and perform a different procedure Refer to the menu maps in Chapter 3 of the Programming Manual to navigate through the user program Exit by pressing NO followed by the RUN key 2 24 Troubleshooting and Maintenance September 2003 Replacing and Recalibrating the Moisture Probes Recalibrating the Pressure Sensors For maximum accuracy you should send the probes back to the factory for recalibration every six months to one year depending on the application Under severe conditions you should send the probes back more frequently in milder applications you do not need to recalibrate probes as often Contact a GE Panametrics applications engineer for the recommended calibration frequency for your application When you receive new or recalibrated probes be sure to install and connect them as described in Chapter 1 Installation of the Startup Guide Once yo
46. brown or a change in potential indicates that the end point has been reached Either of the empirical calibration techniques described above can be conducted using an apparatus equivalent to that shown in Figure A 3 on page A 33 The apparatus pictured can be used for both the Karl Fischer titrations of unknown test samples and the preparation of test samples with known moisture content Procedures for both of these techniques are presented below A 28 Application of the Hygrometer 900 901D1 September 2003 A Instructions for Karl To perform a Karl Fisher analysis use the apparatus in Figure A 3 on Fischer Analysis page A 33 and complete the following steps 1 Fill the glass bottle completely with the sample liquid 2 Close both valves and turn on the magnetic stirrer 3 Permit sufficient time for the entire test apparatus and the sample liquid to reach equilibrium with the ambient temperature Turn on the hygrometer and monitor the dew point reading When a stable dew point reading indicates that equilibrium has been reached record the reading Insert a syringe through the rubber septum and withdraw a fluid sample for Karl Fischer analysis Record the actual moisture content of the sample Open the exhaust valve Open the inlet valve and increase the moisture content of the sample by bubbling wet N through the liquid or decrease the moisture content by bubbling dry through the liquid When th
47. connector Refer to Table 1 6 for the pin connections for the cable connectors Note See EIA RS Serial Communications document 916 054 for more details Table 1 6 Pin Connections for the Connectors on the RS232 Cable Pin number on Connector 25 Pin to 9 Pin to 9 Pin to Output Output Wire Series 3 Device Device Red Lead 2 2 Transmit Green Lead 3 2 2 Receive Black Lead 1 Return The RS232 switch setting DTE or DCE determines the functions of pins 2 and 3 Connect one end of cable to the 9 pin connector on the rear of the electronics unit see Figure 1 16 below Connect the other end of the cable to your output device and set up the communications port as described in Setting Up the Communication Port on page 3 7 in the Programming Manual j CONNECTIONS OXYGEN HAZARDOUS ARE acest CHANNEL 1 B ALMA ALM ALMA ALI NO C NO C NC NO NCRIN NO C NC 6 CHANNEL 2 B 6 AUX REC AUX AL B_ RTN 1 2 24V AT B RIN 1 2 24V 00000 5 0000 RS232 Communication Figure 1 16 RS232 Communications Port Installing Optional Features 1 21
48. ctionally related to the vapor pressure of the water a determination of the dew point will allow one to calculate the PPMy of water in the liquid by a Henry s Law type analysis A specific example of such an analysis is shown below For liquids in which a Henry s Law type analysis is applicable the parts per million by weight of water in the organic liquid is equal to the partial pressure of water vapor times a constant PPMy Kx Py a where K is the Henry s Law constant in the appropriate units and the other variables are as defined on page A 11 A 22 Application of the Hygrometer 900 901D1 September 2003 EEO tl Henry s Law Type Analysis cont Also the value of K is determined from the known water saturation concentration of the organic liquid at the measurement temperature Saturation PPM x E o S For a mixture of organic liquids an average saturation value can be calculated from the weight fractions and saturation values of the pure components as follows n Ave C 1 1 where X is the weight fraction of the i component Cs is the saturation concentration PPM y of the je component and n is the total number of components In conclusion the Henry s Law constant K is a constant of proportionality between the saturation concentration Cs and the saturation vapor pressure Ps of water at the measurement temperature In the General Case the Henry s Law cons
49. d Flow A 19 Materials of Construction A 10 Monitoring Hints 1 Moisture Probes 2 25 Common Problems 2 11 Monitoring Hints Flow Rate 4 Moisture wann ana nern 1 Pressure 2 lei su au an age ae Dr A 3 Response 4 Temperaturen Rem 4 Outputs Connecting 1 1 7 Connecting Recorders 1 4 Testing Alarm Relays 2 2 Oxygen Cell Background Gas Correction Factors 2 29 Checking and Replenishing Electrolyte 2 13 P PCMCIA Card Replacing 0 0 2 14 Personal Computer Communications Port 1 20 PPMv Calculating A 12 PPMw Calculating A 13 Pressure Monitoring Hints A 3 Pressure Sensors Setting Switches 1 15 1 16 Pressure Transducers 1 10 1 11 Pressure Transmitter Connecting nosio eese 1 13 Printer Communications Port 1 20 Probes Replacing and Recalibrating 2 25 R Recorders Conmecting 4 els Steak dee 1 4 Setting Switches 1 4 Reference Menu Setting High amp Low Values 2 21 Relative Humidity Calculating A 13 Relays Alarms 1 82 EIS JE ze
50. during installation If you are not using a GE Panametrics supplied cable or you are using a modified cable read the following section carefully 1 2 Installing Optional Features September 2003 Precautions for Modified or Non GE Panametrics Cables Many customers must use pre existing cables or in some cases modify the standard GE Panametrics supplied moisture cable to meet special needs If you prefer to use your own cables or to modify our cables observe the precautions listed below In addition after connecting the moisture probe you must perform a calibration adjustment as described in Performing a Calibration Test Adjustment on page 1 22 to compensate for any electrical offsets Caution GE Panametrics cannot guarantee operation to the specified accuracy of the Series 3 unless you use GE Panametrics supplied hygrometer cables Use cable that matches the electrical characteristics of GE Panametrics cable contact the factory for specific information on cable characteristics The cable must have individually shielded wire sets A single overall shield is incorrect e If possible avoid all splices Splices will impair the performance When possible instead of splicing coil the excess cable If you must splice cables be sure the splice introduces minimum resistive leakage or capacitive coupling between conductors Carry the shield through any splice A common mistake is to not connect the shields over the s
51. e Optional auxiliary inputs are required Two wire or loop powered transmitter this is always a 4 to 20 mA system Four wire or self powered transmitter this can be either a current or voltage output system Connect the pressure transmitter to the designated pins on the AUX terminal block Pin connections include at least one of the auxiliary inputs pin 1 or 2 see Figure 1 9 below Note Because you are connecting the sensor to one of the auxiliary inputs you must set the corresponding auxiliary switch to either current or voltage refer to C Setting Input Switches on page I 15 Use the appropriate section that follows to connect a pressure transmitter to the Series 3 Loop Powered gt o o 424 Source Auxiliary Inputs Figure 1 9 AUX Terminal Block Pin Designations 1 12 Installing Optional Features September 2003 A Connecting the Two Wire or Loop Powered Transmitter Use a two wire non shielded cable to make connections to the terminal block labeled AUX on the back of the electronics unit refer to Figure 1 10 below Use Table 1 4 below to make the proper pin connections Note Twisted pair cables work well with this circuit Table 1 4 Wire Connections for Two Wire or Loop Powered Transmitters Connect To AUX Terminal Block Positive Lead Output pin 24V Negative Lead Input pin 2 aux input 2 or pin 1 aux input 1
52. e content of the fluid to be analyzed the water vapor pressure at the measurement location may include components from sources such as moisture from the inner walls of the piping external moisture through leaks in the piping system and trapped moisture from fittings valves filters etc Although these sources may cause the measured dew point to be higher than expected it is the actual dew point of the system at the time of measurement One of the major advantages of the GE Panametrics hygrometer is that it can be used for in situ measurements i e the sensor element is designed for installation directly within the region to be measured As a result the need for complex sample systems that include extensive piping manifolds gas flow regulators and pressure regulators is eliminated or greatly reduced Instead a simple sample system to reduce the fluid temperature filter contaminants and facilitate sensor removal is all that is needed Whether the sensor is installed in situ or in a remote sampling system the accuracy and speed of measurement depend on the piping system and the dynamics of the fluid flow Response times and measurement values will be affected by the degree of equilibrium reached within system Factors such as gas pressure flow rate materials of construction length and diameter of piping etc will greatly influence the measured moisture levels and the response times Assuming that all secondary sources of moisture h
53. e Values for a Channel Card Replacing and Recalibrating the Moisture Probes Recalibrating the Pressure Sensors Calibrating the Delta F Oxygen Cell Delta F Oxygen Cell Background Gas Correction Factors Range Error Descriptions e Signal Error Descriptions Calibration Error Descriptions Troubleshooting and Maintenance 2 1 September 2003 Testing the Alarm Relays The Test Menu enables you to either trip or reset the alarm relays While in this menu the Series 3 stops making measurements Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Note f you have already entered the user program refer to the menu maps in Chapter 3 of the Programming Manual to navigate in the Programming Menu Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 Use the arrow keys to move the rEsT CONTRAST gt brackets to TEST and press YES Test Menu 1 Use the arrow keys to move to ALARM RECORDER P ALARM and press YES Select Alarm 1 Use the arrow keys to move the brackets to the alarm you want to test and press YES Alarm Relay 1 Use the arrow keys to select TRIP RESET TRIP to trip the relay or RESET to reset the relay You can now do one of the following To test the other alarm press NO and repeat the final two
54. e following specifications 1 G EEx ia 20 C to 50 C 1180 BASO1ATEX7097 Furthermore the following additional requirements and specifications apply to the product Having been designed in accordance with EN 50014 and EN 50020 the product meets the fault 665 99 tolerance requirements of electrical apparatus for category ia The product is an electrical apparatus and must be installed in the hazardous area in accordance with the requirements of the EC Type Examination Certificate The installation must be carried out in accordance with all appropriate international national and local standard codes and practices and site regulations for flameproof apparatus and in accordance with the instructions contained in the manual Access to the circuitry must not be made during operation Only trained competent personnel may install operate and maintain the equipment The product has been designed so that the protection afforded will not be reduced due to the effects of corrosion of materials electrical conductivity impact strength aging resistance or the effects of temperature variations The product cannot be repaired by the user it must be replaced by an equivalent certified product Repairs should only be carried out by the manufacturer or by an approved repairer The product must not be subjected to mechanical or thermal stresses in excess of those permitted in the certification documentation and the ins
55. e hygrometer reading indicates the approximate moisture content expected close both valves Repeat steps 3 8 until samples with several different moisture contents have been analyzed Application of the Hygrometer 900 901D1 A 29 September 2003 Te B Instructions for Note This procedure is only for liquids that are highly miscible with Preparing Known water Excessive equilibrium times would be required with Samples less miscible liquids To prepare samples of known moisture content use the apparatus in Figure A 3 on page A 33 and complete the following steps Weigh the dry empty apparatus Fill the glass bottle with the sample liquid 1 2 3 Open both valves and turn on the magnetic stirrer 4 While monitoring the dew point reading with the hygrometer bubble dry N through the liquid until the dew point stabilizes at some minimum value 5 Turn off the N supply and close both valves 6 Weigh the apparatus including the liquid and calculate the sample weight by subtracting the step 1 weight from this weight 7 Insert a syringe through the rubber septum and add a known weight of H O to the sample Continue stirring until the water is completely dissolved in the liquid 8 Record the dew point indicated by the hygrometer and calculate the moisture content as follows weight of water 6 PPM 5 W total weight of liquid 9 Repeat steps 6 8 until samples with sever
56. e mode and or units None Check configuration as described selected require more on page 3 33 ofthe Programming data or need a different Manual Choose a different mode probe For example and or units as described on page you will not be able to 1 5 of the Programming Manual read RH with a mois Connect the required probe ture probe that does not have the temperature option Over Rng The input signal is Alarms and recorders Contact GE Panametrics for a See Range Error Descrip tion on page 2 33 above the calibrated range of the probe respond as programmed Refer to page 2 33 higher calibrated probe Change the measurement units so that the measurement is within range For example change ppb to ppm Refer to page 2 3 of the Programming Manual to change the measurement units Printing The Series 3 is printing None None report RAM failed RAM is changed or cor RAM is reset Program Press YES to continue with rupted info will be lost power up Check reference and Battery may need to be replaced Screen is reset to display signal ground Same as above calibration values against refer ence stickers and calibration data sheets then do one of the follow ing Re enter data that is lost or does not match See Reconfiguring a Channel for a New Sensor page 3 33 Entering Calibration Data for New Probes Sensors page 3 37 and Entering Reference Val ues for a Channel Card page 3
57. e recorder range 0 20 mA 4 20 mA 0 2 V Troubleshooting and Maintenance 2 8 September 2003 Testing the Recorder You can now do one of the following Outputs cont To test another percentage repeat the Percent of scale step To test the other recorder press NO twice and repeat the last four steps To exit press RUN 2 4 Troubleshooting and Maintenance September 2003 Trimming the Recorder Outputs Preliminary Steps Trimming the Recorder Outputs The measured value of the recorder outputs can vary from the programmed value due to load resistance tolerance e g chart recorder display computer interface etc The Series 3 provides a trimming feature you can use to compensate for any variation in the recorder outputs To accurately trim the recorder outputs you will need a digital multimeter capable of measuring 0 2 V with a resolution of 0 0001 VDC 0 1 mV or 0 20 mA with a resolution of 0 01 mA The range you use depends on your recorder output Most good quality 3 1 2 digit meters are adequate for recorder output trimming Use the following steps to trim recorder outputs 1 Make sure the recorder switches on the corresponding channel card s are set for the correct output current or voltage V Refer to page 1 5 to check switch settings 2 Disconnect the load e g chart recorder indicator from the end of the recorder output signal wires 3 Attach the digital m
58. e values In fact only one of the values is required to determine PPMy from the nomograph in Figure 2 on page 32 To perform such an analysis proceed as follows 1 Obtain a sample of the test solution with a known water content or perform a Karl Fischer titration on a sample of the test stream to determine the PPMw of water Note The Karl Fischer analysis involves titrating the test sample against a special Karl Fischer reagent until an endpoint is reached 2 Measure the dew point of the known sample with the GE Panametrics hygrometer 3 Measure the temperature of the test solution 4 Using a straightedge connect the moisture content PPMw with the measured dew point and read the K value on the center scale 5 Using a straightedge connect the above K value with the measured temperature of the test solution and read the saturation concentration PPM y Note Since the values of K and Cs vary with temperature the hygrometer measurement and the test sample analysis must be done at the same temperature If the moisture probe temperature is expected to vary the test should be performed at more than one temperature A 24 Application of the Hygrometer 900 901D1 September 2003 B Special Case As mentioned earlier saturated straight chain hydrocarbons represent a special case where the Henry s Law constant does not vary appreciably with temperature In such cases use the nomograph for l
59. ection and perform a different procedure Refer to the menu maps in Chapter 3 of the Programming Manual to navigate through the user program Exit by pressing NO followed by the RUN key Oxygen Ref Menu 1 Use the arrow keys to move the LOW HIGH brackets to LOW and press YES Lo O2 Zero Span 1 Enterthe low oxygen zero value 0 0499 0 0000 Press YES and then press the right arrow key Lo O2 Zero Span 1 Enter the low oxygen span value 0 0499 1 9923 Press YES Then press the NO key Note The reference values shown above are for example only You should verify the actual values as listed on the label placed on the left hand side of the Series 3 chassis or supplied with the new channel card Oxygen Ref Menu 1 Press the right arrow key to LOW HIGH move to HIGH and then press YES Repeat the zero and span value steps to enter the high reference values You may now do one of the following Enter data moisture or pressure reference data by pressing the NO key until you return to Measurement Mode then select the desired mode and press YES Refer to Entering Moisture Reference Data on page 2 22 or Entering Pressure Reference Data on page 2 24 Refer to another section and perform a different procedure Refer to the menu maps in Chapter 3 of the Programming Manual to navigate through the user program Exit by pressing NO followed by the RUN key Troubleshooting and Maintenance 2 23 Septem
60. en pressure is applied to it A pressure transmitter is an electrically active device containing electronic circuits A pressure transmitter requires some sort of power source such as a 24 VDC or 120 VAC It produces a larger output signal than a pressure transducer in either current or voltage The more common pressure transmitters produce a 4 20 mA current output IMPORTANT The following connection information does not pertain to the TF Series Probe To properly connect your pressure sensor use the appropriate section that follows Installing Optional Features September 2003 Connecting a Pressure Transducer Using a two pair shielded cable connect the pressure transducer to the terminal block labeled STD TF PROBE on the back of the electronics unit refer to Figure 1 7 below Refer to Table 1 3 below for the proper pin connections for the pressure transducer If you are not using a GE Panametrics supplied cable refer to Figure 1 8 on page 1 11 to make the proper pin connections to the pressure transducer connector IMPORTANT The transducer must be supplied by GE Panametrics or approved by GE Panametrics for use in this circuit Table 1 3 Pressure Transducer Connections Connect Pressure To STD TF PROBE Transducer Terminal Block Positive Excitation Lead red 1 pin 5 Negative Excitation Lead white pin 6 1 Positive Output Lead black 2 pin 7 Negative Output Lead green P2
61. er that calibrate the oxygen cell once a month for the first three months and then as needed You should also calibrate the oxygen cell if you change the electrolyte Calibrating the oxygen cell involves two parts checking the oxygen cell calibration entering the new span value Note The oxygen cell is calibrated using nitrogen as the background gas Checking the Oxygen 1 Determine which channel is connected to the Delta F Oxygen Cell Calibration Cell 2 Set up the display to read the oxygen content in PPMv and pA Refer to Displaying Measurements on page 2 3 of the Programming Manual for details Note f your operational range of measurement is significantly below the span gas you are using you may elect to input the PPM content of the span gas and the measured uA value as an alternative to the following procedure To perform this part of calibration you must have a calibration gas with a known PPMv value and a calibration gas inlet valve Note GE Panametrics recommends a span calibration gas be 80 100 of the span of the sensor s overall range in a background of nitrogen e g 80 100 PPM N for a 0 100 PPM sensor 3 Run the calibration gas through the oxygen cell 2 26 Troubleshooting and Maintenance September 2003 Calibrating the Delta F Oxygen Cell cont Procedure for Checking the Oxygen Cell Calibration cont 4 Read the PPM value If it is correct your oxygen cell do
62. es not need calibration If the reading is incorrect you must calculate the new span reading x Solve the following equation for x Xi 9X900 109 OX OX where OX Correct PPMv for calibration gas OX Zero value in PPMv OX Span value in PPMv IO Actual reading for calibration gas in uA IO Zero value in uA x New span reading in u A See the Calibration Data Sheet for the oxygen cell to obtain the necessary zero and span values Example If the calibration data for your cell is as follows OX 75 PPMv Correct PPM for cal gas OX 0 050 PPM Zero value in PPM OX 100 PPMv Span value in PPMv IO 290 uA Actual reading for calibration gas IO 0 4238 uA Zero value Therefore 100 75 290 0 423 75 0 05 x 290 The new span value x is 100 PPM 387 uA Enter the new value as described in the next section Troubleshooting and Maintenance 2 27 September 2003 Entering the New Span Value Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 SYSTEM AUTOCALD Measurement Mode 1 H T Aui System Menu 1 4 CURVES O2 Curve Menu 1 S N CURVE BkGd Sel O2 Curve Pts 1 ZERO SPAN 1
63. eter 900 901D1 September 2003 Calculations and Useful Formulas in Gas Applications Nomenclature A knowledge of the dew point of a system enables one to calculate all other moisture measurement parameters The most important fact to recognize is that for a particular dew point there is one and only one equivalent vapor pressure Note The calibration of GE Panametrics moisture probes is based on the vapor pressure of liquid water above 0 C and frost below 0 C GE Panametrics moisture probes are never calibrated with supercooled water Caution is advised when comparing dew points measured with a GE Panametrics hygrometer to those measured with a mirror type hygrometer since such instruments may provide the dew points of supercooled water As stated above the dew frost point of a system defines a unique partial pressure of water vapor in the gas Table A 1 on page A 15 which lists water vapor pressure as a function of dew point can be used to find either the saturation water vapor pressure at a known temperature or the water vapor pressure at a specified dew point In addition all definitions involving humidity can then be expressed in terms of the water vapor pressure The following symbols and units are used in the equations that are presented in the next few sections RH relative humidity e temperature K C 273 Tp temperature R F 460 PPM parts per million by volume PPM
64. f the battery for 5 hours the auto charge will charge the unit for 10 hours Use of the auto charge does not ensure your battery is fully charged To make sure your battery will hold enough power for 6 to 8 hours of operation perform a full charge which takes 16 hours 960 minutes Use the following section to recharge the battery pack using the full charge option IWARNING Do not attempt to recharge the battery pack when the temperature is 0 C 32 F or below Plug the Series 3 into an AC power source and turn the unit on Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Note f you are already in the Battery Test Menu skip to the Battery Test step Programming Menu 1 Use the arrow keys to move the rEsT CONTRAST gt brackets to TEST and press YES Test Menu 1 Use the arrow keys to move to 4 BATTERY BATTERY and press YES Troubleshooting and Maintenance 2 17 September 2003 Recharging the Battery Pack cont Battery Test 1 Use the arrow keys to move to STATUS RDCHGTIME RDCHGTIME and press YES The Series 3 displays the charge time The charge time indicates the rate of the auto charge which is typically twice as long as the run time read introductory paragraph on page 2 18 If you charge the battery for the indicated charge time this does not guarantee your unit will be fully charged To fully charge the unit press YES and skip to the next
65. gen Cell Replenishing the Once the oxygen cell receives the initial charge of electrolyte you Electrolyte should monitor the level regularly DO NOT let the fluid level drop below the MIN level mark on the window IWARNING Electrolyte contains a strong caustic ingredient and can be harmful if it comes in contact with skin or eyes Follow proper procedures for handling the caustic Potassium Hydroxide solution Consult your company safety personnel To raise the fluid level in the reservoir add DISTILLED WATER slowly in small amounts Check the level as you add the distilled water making sure you do not overfill the reservoir The electrolyte mixture should cover approximately 60 of the min max window Troubleshooting and Maintenance 2 13 September 2003 Adding or Removing a PCMCIA Card To expand the memory or replace software the Series 3 controller board has brackets for a linear not flash or ATA SRAM PCMCIA expansion card that can hold up to 1 MB of data Please contact GE Panametrics for a list of compatible devices and formatting To install or remove the card open the enclosure and handle the card as described below Caution Make sure you have record of the data listed below before you reinitialize the system 1 Make sure you have a record of the following data as described on the pages listed below in the Programming Manual Note This information should have been recorded on a separate sheet
66. he Henry s Law Constant of 5 2 on the center scale Using the straightedge connect the above K value of 5 2 with the measured dew point of 3 C and read the correct moisture content of 29 PPM where the straightedge crosses the moisture content scale Application of the Hygrometer 900 901D1 A 25 September 2003 B Special Case cont Note f the saturation concentration at the desired ambient temperature can not be found for any of these special case hydrocarbons the value at any other temperature may be used because K is constant over a large temperature range 3 Find the moisture content in hexane at an ambient temperature of 10 C if a dew point of 0 C is measured with the GE Panametrics hygrometer a From the literature it is found that for hexane at a temperature of 20 C is 101 PPM y Using a straightedge on Figure A 2 on page A 32 connect the 101 PPMy saturation concentration with the 20 C ambient temperature and read the Henry s Law Constant of 5 75 on the center scale Using the straightedge connect the above K value of 5 75 with the measured dew point of 0 C and read the correct moisture content of 26 PPM where the straightedge crosses the moisture content scale 4 Find the moisture content in an unknown organic liquid at an ambient temperature of 50 C if a dew point of 10 C is measured with the GE Panametrics hygrometer a Either perform a Karl Fischer an
67. his type has been used successfully to monitor the drying of photographic film If one wishes to measure the absolute moisture content of the solid at any time during such a process then an empirical calibration is required 1 Ata particular set of operating conditions i e flow rate temperature and pressure the hygrometer dew point reading can be calibrated against solids samples with known moisture contents 2 Assuming the operating conditions are relatively constant the hygrometer dew point reading can be noted and a solids sample withdrawn for laboratory analysis 3 Repeat this procedure until a calibration curve over the desired moisture content range has been developed Once such a curve has been developed the hygrometer can then be used to continuously monitor the moisture content of the solid as long as operating conditions are relatively constant A 34 Application of the Hygrometer 900 901D1 September 2003 B Laboratory If in line measurements are not practical then there are two possible Procedures laboratory procedures 1 The unique ability ofthe GE Panametrics sensor to determine the moisture content of a liquid can be used as follows Note Using the apparatus shown in Figure A 3 on page A 33 dissolve a known amount of the solids sample in a suitable hydrocarbon liquid The measured increase in the moisture content of the hydrocarbon liquid can then be used to calculate the mois
68. hn 2 2 Response Time Moisture Probe A 4 Return 1 1 RS232 Communications Port 1 20 Index September 2003 ZZ GGF il Index cont Screen Messages 2 8 Common Problems 2 11 Setting Up Entering Reference Values 2 21 Signal Errors 0 0 0 00 0 eee eee 2 32 Solids Applications A 34 Specifications Moisture A 10 Switch Blocks Switch 1 17 Switch Settings Auxiliary 1 17 Pressure 1 15 1 16 Recorders a er ner 1 4 T Temperature Monitoring A 4 Testing Alarm 2 2 Calibration Adjustment 1 22 Troubleshooting Common Problems 2 11 Screen Messages 2 8 Troubleshooting and Maintenance 5 User Program 2 2 14 Warranty lesse eee eee 1 iii Index 3 GE Panametrics ATEX COMPLIANCE GE Panametrics 221 Crescent Street Suite 1 Waltham MA 02453 U S A as the manufacturer declare under our sole responsibility that the product Moisture Monitor Series 3 Analyzer to which this document relates in accordance with the provisions of ATEX Directive 94 9 EC Annex II meets th
69. ies 3 will apply the appropriate correction to the oxygen signal The original calibration values for nitrogen are programmed into the Oxygen Probe Calibration section However the Series 3 uses the current multiplier to determine the correct oxygen concentration Note The default setting for the Current Multiplier is 1 00 To change the Current Multiplier first select a Current Multiplier from Table 2 6 on page 2 31 Then press the PROG key to enter the Enter Passcode Enter the passcode c a oO a 09 Hd e Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 Use the arrow keys to move the SYSTEM AUTOCALP brackets to SYSTEM and press YES Measurement Mode 1 Use the arrow keys to move the D H T P AUX1 brackets to O and press YES System Menu 1 Usethe arrow keys to move the 4 CURVES CONSTANTE brackets to CURVES and press YES O2 Curve Menu 1 Use the arrow keys to move the S N CURVE _ BkGd brackets to BkGd and press YES O2 uA Multiplier Use the numeric keys to enter the 1 00 Current Multiplier Press YES to confirm your entry exit press the RUN key 2 30 Troubleshooting and Maintenance Table 2 6 Background Gas Current Multipliers Background Gas Current Multipliers Up to 1000 PPM Argon Ar 5000
70. iquids in Figure A 2 on page A 32 to complete the analysis Determination of moisture content if the Henry s Law constant is known 1 Using a straightedge connect the known K value on the center scale with the dew frost point as measured with the GE Panametrics hygrometer Read moisture content PPM where the straightedge crosses the scale on the left Typical Problems 1 Find the moisture content in benzene at an ambient temperature of 30 C if a dew point of 0 is measured with the GE Panametrics hygrometer a From the literature it is found that for benzene at a temperature of 30 C is 870 PPM y Using a straightedge on Figure A 2 on page A 32 connect the 870 PPMy saturation concentration with the 30 C ambient temperature and read the Henry s Law Constant of 27 4 on the center scale Using the straightedge connect the above K value of 27 4 with the measured dew point of 0 C and read the correct moisture content of 125 PPM yw where the straightedge crosses the moisture content scale 2 Find the moisture content in heptane at an ambient temperature of 50 C if a dew point of 3 C is measured with the GE Panametrics hygrometer a From the literature it is found that for heptane at a temperature of 50 C is 480 PPM Using a straightedge on Figure A 2 on page A 32 connect the 480 PPM saturation concentration with the 50 C ambient temperature and read t
71. is condition is suspected refer to the Probe Cleaning Procedure section of this appendix for the recommended cleaning procedure Application of the Hygrometer 900 901D1 A 5 September 2003 Conductive Particulates Corrosive Particulates Note Metallic particles carbon particles and conductive liquid droplets are typical of this category Since the hygrometer reading is inversely proportional to the impedance of the sensor a decrease in sensor impedance will cause an increase in the meter reading Thus trapped conductive particles across the sensor leads or on the sensor surface which will decrease the sensor impedance will cause an erroneously high dew point reading The most common particulates of this type are carbon from furnaces iron scale from pipe walls and glycol droplets from glycol based dehydrators Ifthe system contains conductive particulates it is advisable to install a Teflon or stainless steel filter in the fluid stream Note Sodium chloride and sodium hydroxide particulates are typical of this category Since the active sensor element is constructed of aluminum any material that corrodes aluminum will deleteriously affect the operation of the moisture probe Furthermore a combination of this type of particulate with water will cause pitting or severe corrosion of the sensor element In such instances the sensor cannot be cleaned or repaired and the probe must be replaced Obviously the stand
72. is process follows Note n order for you to use the current multipliers in this appendix your calibration data sheet should contain calibration data for nitrogen If your calibration data sheet contains data for a background gas other than nitrogen contact the factory for the nitrogen calibration sheet A single Background Gas Correction Factor based on the reference nitrogen measurement can be derived for each background gas because in practice the diffusion rate for a typical background gas is stable and predictable and because the cell s response is linear The current multiplier that is entered into the Oxygen Probe Calibration section is the inverse of this Background Gas Correction Factor For example Table 2 5 below represents the calibration values two points for a specific oxygen cell calibrated in nitrogen This data is supplied with the cell and is stored in the Series 3 user program Table 2 5 Supplied Oxygen Cell Calibration Data referenced to nitrogen Zero Calibration Point Zero PPMy Value 0500 PPMy Zero uA Value 9867 uA Span Calibration Point Span PPM Value 100 0 PPM Troubleshooting and Maintenance 2 29 September 2003 Correcting for Different Background Gases cont Entering the Current Multiplier When the oxygen cell is used in a background gas other than nitrogen users must enter the gas s current multiplier listed in Table 2 6 on page 2 31 The Ser
73. kets to REF and press YES IMPORTANT Make sure you have selected the correct channel before you proceed Press the CHAN key to select the desired channel The remaining prompts depend on the measurement mode you selected Refer to one of the following sections to properly program your unit Entering Moisture Reference Data below Entering Oxygen Reference Data on page 2 23 Entering Pressure Reference Data on page 2 24 Note You do not have to enter reference data for temperature auxiliary 1 auxiliary 2 or constant ppmv MH Hi Ref Lo Ref 1 Enter the low reference value 0 1660 0 0000 Press YES and press the left arrow key MH Hi Ref Lo Ref 1 Enter the high reference value 0 1660 2 9335 and press YES Note The reference values shown above are for example only You should verify the actual values as listed on the label placed on the left hand side of the Series 3 chassis or supplied with the new channel card Press the NO key and proceed to the next page 2 22 Troubleshooting and Maintenance September 2003 Entering Moisture Reference Data cont Entering Oxygen Reference Data You may now do one of the following Enter data for oxygen or pressure reference data by pressing the NO key until you return to Measurement Mode then select the desired mode and press YES Refer to B Entering Oxygen Reference Data below or C Entering Pressure Reference Data on page 2 24 Refer to another s
74. le The multimeter should display one of the readings listed in Table 2 1 below Table 2 1 Voltmeter Readings For the Recorder Output Range 0 to 20 mA Desired Voltmeter Reading 4 to 20 mA 0to2V Note The recorders cannot be trimmed to output a value of 0 00 mA 0 00 V due to the limits imposed by electronic noise The recorders will typically output 0 01 mA at zero output therefore you should use 5 for the test value for 0 to 20 mA and 0 to 2 V ranges 2 6 Troubleshooting and Maintenance September 2003 Trimming the Recorder Outputs cont What s Next RCD A Zero TRIM 1 Use the arrow keys to select VIEW TRIM UP VIEW and press YES The Series 3 displays the zero and span readings for 2 seconds Use the arrow keys to select TRIM UP or TRIM DOWN to correct the difference between the desired multimeter reading and the actual voltmeter reading The Series 3 displays the new zero and span value Note The trim resolution is limited to 30 05 mA or 0 5 mV Choose the trim value that produces an output closest to the value desired Continue trimming until you reach the desired value Then press NO and repeat the last four steps for the SPAN value Note The zero trim is an offset adjustment while the span trim is a slope adjustment As a result the zero and span trim affect each other Therefore after you adjust one you may have to adjust the other You can now do one of
75. ling Optional Features Making Electrical Connections 0 0 cece 1 1 Precautions for Modified Non GE Panametrics 1 3 Connecting the Recorder Outputs ce eee teens 1 4 Accessing the Channel Cards 0 0 2c eee eee ene nes 1 4 Setting the Switch Blocks 0 0 ee ee cnet een eee 1 5 Replacing the Channel eh 1 5 Connecting the 1 6 Connecting the Alarms er rtu AU ae he eis 1 7 Connecting Pressure Sensor 1 9 Connecting a Pressure 1 10 Connecting Pressure Transmitters 1 12 Connecting Auxiliary nee eee ees 1 17 Accessing the Channel Card 0 0 1 1 18 seitinsithe Switch Block we on na 1 18 Replacing the Channel Card 1 19 Connecting a Personal Computer or 1 20 Setting the RS232 Switch seeded Pe ere EP 1 20 Connecting the PC or Printer 1 21 Performing a Calibration Test 1 22 Preliminary Steps duoi
76. mbient air and an off gassing of moisture into the process fluid with a corresponding increase in measured moisture content will occur The converse will happen during the cooler evening hours GE Panametrics hygrometers are unaffected by the fluid flow rate The moisture probe is not a mass sensor but responds only to water vapor pressure The moisture probe will operate accurately under both static and dynamic fluid flow conditions In fact the specified maximum fluid linear velocity of 10 000 cm sec for The M Series Aluminum Oxide Moisture Sensor indicates a mechanical stability limitation rather than a sensitivity to the fluid flow rate If the measured dew point of a system changes with the fluid flow rate then it can be assumed that off gassing or a leak in the sample system is causing the variation If secondary moisture is entering the process fluid either from an ambient air leak or the release of previously absorbed moisture from the sample system walls an increase in the flow rate of the process fluid will dilute the secondary moisture source As a result the vapor pressure will be lowered and a lower dew point will be measured Note Refer to the Specifications chapter in this manual for the maximum allowable flow rate for the instrument A 4 Application of the Hygrometer 900 901D1 September 2003 Contaminants Non Conductive Particulates Industrial gases and liquids often contain fine particulate matter Par
77. mode No channel card is installed at the position selected Computer Enhanced Response is activated Select a different channel None Fluid Low The fluid level in the Delta F Oxygen Cell is low Add fluid to the cell as described on page 2 13 KD or KH as the mea surement mode A constant dew point is being used None None KT as the measurement mode A constant tempera ture is being used None None KP as the measurement mode A constant pressure is being used None None Log is Full The Series 3 memory is full The Series 3 continues to log but does not store the data in the memory If you have an external display device connected to the unit the log data will dis play The next time you set up a log the Series 3 will ask you to over write the log Respond YES 2 8 Troubleshooting and Maintenance September 2003 Table 2 2 Screen Messages and the Possible Causes Continued Screen Message Possible Cause System Response Action No option board installed There is no option None None board installed in your unit NO PROBE Unit has not been con N A Make sure the correct probe is figured for the probe activated as described on page 3 activated For example 33 ofthe Programming Manual you will not be able to Connect the required probe display pressure when Series probe is connected NOT AVAIL Th
78. nfiguring a Channel for a New Sensor on page 3 33 and Entering Calibration Data for New Probes Sensors on page 3 37 both in the Programming Manual to properly set up the auxiliary input Installing Optional Features 1 19 September 2003 Connecting a Personal You can connect the Series 3 to a personal computer or serial printer Computer or Printer using the RS232 communications port Refer to the instructions below to set up and connect your PC or printer Setting the RS232 The Series 3 has a special switch that you can use to set the Series 3 Switch up as Data Terminal Equipment DTE or Data Communications Equipment DCE This switch changes the transmit and receive pin functions on the RS232 connector on the back of the Series 3 Use the steps below to properly set the switch 1 Remove the screws on the front panel and slide the electronics unit out of its enclosure 2 Locate the RS232 switch on the display board Use Figure 1 15 below to locate the switch 3 Setthe RS232 switch to the desired position Set the switch to DTE if the Series 3 will be transmitting data and DCE if the unit will be receiving data Note Jf communications do not work properly try changing the RS232 switch position RS232 Switch Figure 1 15 RS232 Switch Location 1 20 Installing Optional Features September 2003 Connecting the PC or Printer You can connect or printer using a serial cable with a 9 pin or 25 pin female
79. ng leads to an external power source Once you complete the pressure connections you must set switch block S1 on the Series 3 channel card for either current or voltage input depending on the type of pressure sensor you are using refer to C Setting Input Switches on page 1 15 Installing Optional Features September 2003 Setting Input Switches Set switch block 1 on the channel card as described below Accessing the Channel Card 1 Remove the screws on the front panel and slide the electronics unit out of its enclosure 2 Remove the retainer bar by removing the two screws on the outside of the chassis see Figure 1 11 below 3 Remove the channel card by sliding it straight up 7 Retainer Bar 4 a 2 15 Top View Figure 1 11 Location of the Channel Cards Setting the Switch Block 1 Locate switch block S1 see Figure 1 12 on page 1 16 for switch S1 location S
80. of paper Probe configuration page 3 33 Probe calibration data see the Calibration Data Sheets See page 3 37 Recorder Outputs page 3 5 Alarm Outputs page 3 2 Data Logger page 3 13 Reference values page 2 22 of this chapter IWARNING Remove power by disconnecting the main AC power cord before proceeding with this procedure 1 Turn the power off and unplug the unit 2 Discharge static from your body 3 Open the Series 3 enclosure by removing the screws on the front panel and sliding the electronics unit out 4 Use Figure 2 2 on page 2 15 to locate the controller board inside the electronics unit and remove the card by pulling it out of the brackets The controller board will appear similar to Figure 2 3 on page 2 16 Troubleshooting and Maintenance September 2003 Adding or Removing a PCMCIA Card cont Retainer Bar Controller Board Top View Figure 2 2 Location of the Controller Board 5 Insert the PCMCIA card into the brackets along the side of the cutout area Orient the card so that Pin 1 ofthe PCMCIA card lines up with Pin 1 of the connector on the controller card Note When you are inserting the PCMCIA card the face of the card with the arrows must be on the side next the controller board 6 Check the switch settings to make sure they match the ones shown in Figure 2 3 on page 2 16 all switches down The switch settings shown in the insert are preset at the f
81. om the vapor pressures of water at the measured dew point and at the ambient temperature of the liquid P Saturation c x 100 E x 100 Cs Ps Application of the Hygrometer 900 901D1 A 27 September 2003 _ Empirical Calibrations For those liquids in which a Henry s Law type analysis is not applicable the absolute moisture content is best determined by empirical calibration A Henry s Law type analysis is generally not applicable for the following classes of liquids liquids with a high saturation value 2 by weight of water or greater liquids such as dioxane that are completely miscible with water liquids such as isopropyl alcohol that are conductive For such liquids measurements of the hygrometer dew point readings for solutions of various known water concentrations must be performed Such a calibration can be conducted in either of two ways perform a Karl Fischer analysis on several unknown test samples of different water content prepare a series of known test samples via the addition of water to a quantity of dry liquid In the latter case it is important to be sure that the solutions have reached equilibrium before proceeding with the dew point measurements Note Karl Fisher analysis is a method for measuring trace quantities of water by titrating the test sample against a special Karl Fischer reagent until a color change from yellow to
82. on of the hygrometer 10 If the sensor is not in proper calibration repeat steps 1 9 using time intervals 5 times those used in the previous cleaning cycle Repeat this procedure until the sensor is in proper calibration A trained laboratory technician should determine if all electrically conductive compounds have been removed from the aluminum oxide sensor and that the probe is properly calibrated Probes which are not in proper calibration must be recalibrated It is recommended that all moisture probes be recalibrated by GE Panametrics approximately once a year regardless of the probe s condition Application of the Hygrometer 900 901D1 September 2003 Corrosive Gases And Liquids GE Panametrics M Series Aluminum Oxide Moisture Sensors have been designed to minimize the affect of corrosive gases and liquids As indicated in the Materials of Construction section of this appendix no copper solder or epoxy is used in the construction of these sensors The moisture content of corrosive gases such as HS 50 cyanide containing gases acetic acid vapors etc can be measured directly Note Since the active sensor is aluminum any fluid which corrodes aluminum will affect the sensor s performance By observing the following precautions the moisture probe may be used successfully and economically 1 The moisture content of the corrosive fluid must be 10 PPMv or less at 1 atmosphere or the concentration of the corro
83. ord it 1 22 Installing Optional Features September 2003 Calibration Procedure cont 3 7 Reprogram the Series 3 with the new corrected low reference value if required as described in Entering Reference Values for a Channel Card on page 2 22 Verify that the probe cable is not connected to the probe Note the zero reference reading and verify that the reading is now within 0 0003 MH out a new high and low reference sticker with the final low reference value Make sure you record the information below HIGH REF ORIGINAL VALUE LOW REF NEW CORRECTED VALUE ZERO REF ORIGINAL RECORDED VALUE Reconnect the probe to the cable Note Repeat this procedure for maximum accuracy if cables are changed in any way The Series 3 is now ready for operation Installing Optional Features 1 23 Chapter 2 Troubleshooting and Maintenance Introduction u kann an aan ana 2 1 Testing the Alarm 2 2 Testing the Recorder 2 3 Trimming the Recorder 2 5 Screen lt lt 2 8 Common Problems 2 nenn 2 11 Checking the Delta F Oxygen Cell Electrolyte 2 13 Adding or Removing a PCMCIA 2 14 Recharging the Battery Pack 2 17 Installing a
84. parts per million by weight M molecular weight of water 18 e Mr molecular weight of carrier gas saturation vapor pressure of water at the prevailing temperature mm of Hg Py water vapor pressure at the measured dew point mm of Hg Pr total system pressure mm of Hg Application of the Hygrometer 900 901D1 A 11 September 2003 Parts per Million by Volume The water concentration in a system in parts per million by volume is proportional to the ratio of the water vapor partial pressure to the total system pressure P W 6 Py x 10 2 1 In a closed system increasing the total pressure of the gas will proportionally increase the partial pressures of the various components The relationship between dew point total pressure and PPMy is provided in nomographic form in Figure 1 on page A 20 Note The nomograph shown in Figure 1 on page A 20 is applicable only to gases Do not apply it to liquids To compute the moisture content for any ideal gas at a given pressure refer to Figure A 1 on page A 20 Using a straightedge connect the dew point as measured with the GE Panametrics Hygrometer with the known system pressure Read the moisture content in PPMy where the straightedge crosses the moisture content scale Typical Problems 1 Find the water content in a nitrogen gas stream if a dew point of 20 C is measured and the pressure is 60 psig Solution In Figure A
85. perature to read Under Rng while RH reads Over Rng If multiple Range Errors occur simultaneously the Series 3 responds to them in the following order 1 Oxygen Errors 2 Moisture Errors 3 Temperature Errors 4 Pressure Errors Signal Errors occur when an electrical fault causes a measurement signal to exceed the capacity of the analyzer electronics The Series 3 displays Signal Errors with a Sig Err message A Calibration Error indicates a failure of the internal reference during Auto Cal During Auto Cal internal reference components are measured and compared to factory calibration values Each reference is read repeatedly and the value measured is compared to a table of acceptable values Any deviation from the factory values is calculated and corrected Should a reference fall outside the acceptable range a Cal Err message appears It is possible for one mode to fail Auto Cal while the others continue to operate Only the failed mode will display a Cal Err Usually Auto Cal errors are indicative of a channel card fault 2 32 Troubleshooting and Maintenance Appendix Application of the Hygrometer 900 901D1 Introduction en aan ann A 1 Moisture Monitor Hints 2 Contaminants i2 ec ceo 5 Aluminum Oxide Probe Maintenance A 7 Corrosive Gases And A
86. pin 8 Shield pin 9 Note If you connect a pressure transducer to the STD TF PROBE terminal block you must activate the TF Probe in the pressure column for that channel as described on page 3 34 of the Programming Manual STD TF Probe Terminal Block OXYGEN CONNECTIONS DE 2 HAZARDOUS AR o o CHANNEL 1 E p CHANNEL 2 ALMA ALMB ALMA ALM NO C NO C NC NO NCRTN NO C NC AUX RIN1 2 24V ot o 0 o Figure 1 7 STD TF Probe Terminal Block Location Installing Optional Features September 2003 Connecting a Pressure Transducer cont STD TF Probe a Excitation ud To Pressure S Transducer ig gt Output 1 2 3 4 5 6 7 8 9 O Figure 1 8 Cable Assembly for Pressure Transducer Installing Optional Features 1 11 September 2003 Connecting Pressure The Series 3 accepts two types of pressure transmitters Transmitters Not
87. plice If you are modifying a GE Panametrics cable the shield will not be accessible without cutting back the cable insulation Also do not ground the shield at both ends You should only ground the shield at the hygrometer electronics Installing Optional Features 1 3 September 2003 Er Connecting the The Series 3 has two optically isolated recorder outputs These Recorder Outputs outputs provide either a current or voltage signal which you set using switch blocks on the channel card Although the Series 3 is configured at the factory you should check the switch block positions before making connections Use the following steps to check or reset these switch settings Accessing the Channel 1 Remove the screws on the front panel and slide the electronics unit Cards out of its enclosure 2 Remove the retainer bar by removing the two screws on the outside of the chassis see Figure 1 2 below 3 Remove the desired channel card see Figure 1 2 below by sliding it straight up Channel Card Retainer Bar
88. rapped under contact arm of described in Appendix A Then reinstall ture calibration sensor sensor If low reading persists return the value while dis probe to GE Panametrics for evaluation playing dew frost Check cable connections to both the point Improper cable connection probe and the Series 3 Slow response Slow outgassing of system N A Replace the system components with Sensor is contaminated with non conductive particles refer to Appendix A stainless steel or electro polished stainless steel Clean sensor and sensor shield as described in Appendix A Then reinstall sensor Troubleshooting and Maintenance September 2003 Checking the Delta As a result of operating the Series 3 particularly when monitoring dry Oxygen Cell gases there may be a gradual loss of water from the electrolyte in the Electrolyte Delta F oxygen cell The electrolyte level should be checked at regular intervals to ensure your cell is always operating properly This section describes how to check and replenish the electrolyte in your oxygen cell Note Some applications require that the electrolyte be changed periodically Consult GE Panametrics Checking the Electrolyte Using the min max window on the oxygen cell check to be sure the Level electrolyte level covers about 60 of the window see Figure 2 1 below Level Indicator Figure 2 1 Electrolyte Level for the Delta F Oxy
89. robe complete the following steps 1 Record the dew point of the ambient air 2 Making sure not to touch the sensor carefully remove the protective shield from the sensor 3 Soak the sensor in the distilled water for ten 10 minutes Be sure to avoid contact with the bottom and the walls of the container 4 Remove the sensor from the distilled water and soak it in the clean container of hexane or toluene for ten 10 minutes Again avoid all contact with the bottom and the walls of the container 5 Remove the sensor from the hexane or toluene and place it face up in a low temperature oven set at 50 2 122 F 4 for 24 hours Application of the Hygrometer 900 901D1 A 7 September 2003 Aluminum Oxide Probe Maintenance cont 6 Repeat steps 3 5 for the protective shield During this process swirl the shield in the solvents to ensure the removal of any contaminants that may have become embedded in the porous walls of the shield Carefully replace probe s protective shield making sure not to touch the sensor Connect the probe cable to the probe and record the dew point of the ambient air as in step 1 Compare the two recorded dew point readings to determine if the reading after cleaning is a more accurate value for the dew point of the ambient atmosphere If the sensor is in proper calibration 2 C accuracy reinstall the probe in the sample cell and proceed with normal operati
90. s Making Electrical 1 1 Precautions for Modified or Non GE Panametrics Cables 1 3 Connecting the Recorder 1 4 Connecting Pressure Sensor Inputs 1 9 Connecting Auxiliary 1 17 Connecting a Personal Computer or Printer 1 20 Performing a Calibration Test Adjustment 1 22 September 2003 Making Electrical Make all connections to the back panel of the Series 3 The panel has Connections connector blocks to make moisture pressure oxygen output and auxiliary connections for each channel Figure 1 1 below shows the back panel Note For compliance with the EU s Low Voltage Directive IEC 1010 this unit requires an external power disconnect device The disconnect device for this unit is its power cord IWARNING To ensure the safe operation of this unit you must install and operate the Series 3 as described in this startup guide In addition be sure to follow all applicable safety codes and regulations for installing electrical equipment in your area STD TF STD TF PROBE PROBE 1 2 250V SLO BLO 3AG G nd CHANN Neu ALMA NO Nd RTN REOg HAZARDOUS AREA CONNECTIONS
91. sive fluid must be 10 PPMv or less at 1 atmosphere 2 The sample system must be pre dried with a dry inert gas such as nitrogen or argon prior to introduction of the fluid stream Any adsorbed atmospheric moisture on the sensor will react with the corrosive fluid to cause pitting or corrosion of the sensor 3 The sample system must be purged with a dry inert gas such as nitrogen or argon prior to removal of the moisture probe Any adsorbed corrosive fluid on the sensor will react with ambient moisture to cause pitting or corrosion of the sensor 4 Operate the sample system at the lowest possible gas pressure Using the precautions listed above the hygrometer has been used to successfully measure the moisture content in such fluids as hydrochloric acid sulfur dioxide chlorine and bromine Application of the Hygrometer 900 901D1 A 9 September 2003 Materials of Construction 1 and 2 Sensors Electrical Connector Sensor Element Back Wire Contact Wire Front Wire Support Pins Glass Shell O Ring Threaded Fitting O Ring Cage Shield 99 99 aluminum aluminum oxide gold Nichrome A6 316 stainless steel gold 304 stainless steel 316 stainless steel Glass Corning 9010 Al 152 Alloy 52 Ni Corning 9010 304L stainless steel silicone rubber 304 stainless steel Viton A 308 stainless steel 304 stainless steel Application of the Hygrom
92. stria Waldgasse 39 A 1100 Wien Austria Telephone 43 1 602 25 34 Fax 43 1 602 25 34 11 E mail panametrics netway at Benelux Postbus 111 3870 CC Hoevelaken The Netherlands Telephone 31 0 33 253 64 44 Fax 31 0 33 253 72 69 E mail info panametrics nl France BP 106 11 Rue du Renard 92253 La Garenne Colombes Cedex France Telephone 33 0 1 47 82 42 81 Fax 33 0 1 47 86 74 90 E mail panametrics panametrics fr Germany Mess und Pruftechnik Robert Bosch Stra e 20a 65719 Hofheim Germany Telephone 49 6122 8090 Fax 49 6122 8147 E mail panametrics t online de Italy Via Feltre 19 A 20132 Milano Italy Telephone 02 2642131 Fax 02 26414454 E mail info panametrics it Japan Telephone 81 03 5802 8701 Fax 81 03 5802 8706 E mail pci panametrics co jp Korea Kwanghee Bldg 201 644 2 Ilwon dong Kangnam Ku Seoul 135 945 Korea Telephone 82 2 445 9512 Fax 82 2 445 9540 E mail jkpark panaeng co kr Spain Diamante 42 28224 Pozuelo de Alarcon Madrid Spain Telephone 34 91 351 82 60 Fax 34 91 351 13 70 E mail info panametrics infonegocio com Sweden Box 160 147 23 Tumba Sweden Telephone 46 0 8 530 685 00 Fax 46 0 8 530 357 57 E mail pana panametrics se Taiwan 7th Fl 52 Sec 3 Nan Kang Road Taipei Taiwan ROC Telephone 02 2788 3656 Fax 02 2782 7369 E mail rogerlin lumax com tw United Kingdom Unit 2 Villiers Court 40 Upper Mulgrave
93. tant varies with the measurement temperature but there is a Special Case in which the Henry s Law constant does not vary appreciably with the measurement temperature This special case applies to saturated straight chain hydrocarbons such as pentane hexane heptane etc A General Case Determination of Moisture Content if Cg is Known The nomograph for liquids in Figure 2 on page 32 can be used to determine the moisture content in an organic liquid if the following values are known the temperature of the liquid at the time of measurement the saturation water concentration at the measurement temperature the dew point as measured with the GE Panametrics hygrometer Application of the Hygrometer 900 901D1 A 23 September 2003 Te A General Case cont Complete the following steps to determine the moisture content from the nomograph 1 Using a straightedge on the two scales on the right of the figure connect the known saturation concentration PPMy with the measurement temperature C 2 Read the Henry s Law constant K on the center scale 3 Using a straightedge connect above K value with the dew frost point as measured with the GE Panametrics hygrometer 4 Read the moisture content PPM where the straight edge crosses the moisture content scale Empirical Determination of K and Cg If the values of and Cg are not known the GE Panametrics hygrometer can be used to determine thes
94. the following To trim the other recorder press the NO key to return to the Select Recorder step and repeat the procedure To exit press RUN Troubleshooting and Maintenance 2 7 September 2003 Screen Messages The Series 3 has several screen messages that may display during operation Refer to Table 2 2 below for a list of these errors and the possible solutions Table 2 2 Screen Messages and the Possible Causes Screen Message Possible Cause System Response Action The Series 3 is running on battery power None None Battery Low Series 3 is running on battery power and the battery is low When this message appears you have approximately 1 hour before the unit automatically shuts off None Recharge battery as described on page 2 18 Battery Pack Installed Your unit is equipped with a battery pack The Series 3 is charging the battery pack Cal Err See Calibration Error Description on page 2 33 During Auto Cal an internal reference is found to be outside its acceptable range Signal Error has occurred Alarms and recorders respond as programmed Refer to page 2 33 Make sure the analyzer is grounded properly Reseat the channel card Follow the first four steps in Installing a Channel Card on page 2 20 Remove source of Signal Error and attempt another Auto Cal Contact GE Panametrics CHANNEL NOT AVAILABLE EH as the measurement
95. ticulates of the following types are commonly found in such process fluids carbon particles salts rust particles polymerized substances organic liquid droplets dust particles molecular sieve particles alumina dust For convenience the above particulates have been divided into three broad categories Refer to the appropriate section for a discussion of their affect on the GE Panametrics moisture probe Note Molecular sieve particles organic liquid droplets and oil droplets are typical of this category In general the performance of the moisture probe will not be seriously hindered by the condensation of non conductive non corrosive liquids However a slower response to moisture changes will probably be observed because the contaminating liquid barrier will decrease the rate of transport of the water vapor to the sensor and reduce its response time Particulate matter with a high density and or a high flow rate may cause abrasion or pitting of the sensor surface This can drastically alter the calibration of the moisture probe and in extreme cases cause moisture probe failure A stainless steel shield is supplied with the moisture probe to minimize this effect but in severe cases it is advisable to install a Teflon or stainless steel filter in the fluid stream On rare occasions non conductive particulate material may become lodged under the contact arm of the sensor creating an open circuit If th
96. truction manual The product contains no exposed parts which produce surface temperature infrared electromagnetic ionizing or non electrical dangers 2 CERT ATEX C 7 16 03 DECLARATION GE Panametrics CONFORMITY GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland declare under our sole responsibility that the Moisture Image Series 1 Analyzer Moisture Image Series 2 Analyzer Moisture Monitor Series 3 Analyzer Moisture Monitor Series 35 Analyzer to which this declaration relates are in conformity with the following standards EN 61326 1998 Class A Annex A Continuous Unmonitored Operation EN 61010 1 1993 A2 1995 Overvoltage Category II Pollution Degree 2 following the provisions of the 89 336 EEC EMC Directive and the 73 23 EEC Low Voltage Directive The units listed above and any sensors and ancillary sample handling systems supplied with them do not bear CE marking for the Pressure Equipment Directive as they are supplied in accordance with Article 3 Section 3 sound engineering practices and codes of good workmanship of the Pressure Equipment Directive 97 23 EC for DN lt 25 Shannon June 1 2002 oss T Ae Mr James Gibson GENERAL MANAGER LS ENISO9002 T V ESSEN Shannon ISO 9001 U S CERT DOC Rev G2 5 28 02 DECLARATION GE Panametrics CONFORMITE GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland d clarons so
97. ture content of the sample For best results the hydrocarbon liquid used above should be pre dried to a moisture content that is insignificant compared to the moisture content of the sample Since the addition of the solid may significantly change the saturation value for the solvent published values should not be used Instead an empirical calibration as discussed in the previous section should be used A dew point of 110 C which can correspond to a moisture content of 10 PPMy or less represents the lower limit of sensor sensitivity The maximum measurable moisture content depends to a great extent on the liquid itself Generally the sensor becomes insensitive to moisture contents in excess of 1 by weight 2 An alternative technique involves driving the moisture from the solids sample by heating a The evaporated moisture is directed into a chamber of known volume which contains a calibrated moisture sensor Convert the measured dew point of the chamber into a water vapor pressure as discussed earlier in this appendix From the known volume of the chamber and the measured vapor pressure dew point of the water the number of moles of water in the chamber can be calculated and related to the percent by weight of water in the test sample Although this technique is somewhat tedious it can be used successfully An empirical calibration of the procedure may be performed by using hydrated solids of kno
98. u have installed and connected the probes enter the calibration data supplied with each probe as described in Entering Calibration Data for New Probes Sensors page 3 37 of the Programming Manual then configure the channel as described in Reconfiguring a Channel for a New Sensor on page 3 33 of the Programming Manual Since the pressure sensor on a TF Series Probe is a strain gage type the pressure calibration is linear and is calibrated at two data points Each point consists of a pressure value and a corresponding voltage value Check or change the two calibration points using the steps below 1 Set one of the lines on the screen to display pressure in mV Refer to Displaying Measurements on page 2 3 of the Programming Manual to set up the screen Select pressure as the measurement mode and pmv to display millivolts 2 Expose the pressure sensor to the air and record the mV reading This reading is the mV reading for the zero pressure 3 Expose the pressure sensor to a known full scale pressure source at least 50 of the full scale capability and record the mV reading This reading is the mV reading for the span pressure 4 Enter the above readings as described in Entering Calibration Data for New Probes Sensors on page 3 37 of the Programming Manual Troubleshooting and Maintenance 2 25 September 2003 Calibrating the Delta F You should calibrate the Delta F Oxygen Cell when you initially Oxygen Cell receive it Aft
99. ultimeter to the signal wires If the recorder location is very distant from the Series 3 you may want to have one person making readings at the recorder location and one person making readings at the Series 3 location Press the PROG key to enter the user program Enter Passcode XXXX Enter the passcode Note f you have already entered the user program refer to the menu maps in Chapter 3 of the Programming Manual to navigate to the Programming Menu Be sure the number displayed in the upper right hand corner of the screen is the channel you want to program If not press the CHAN key to select the desired channel Programming Menu 1 Use the arrow keys to move the 4 TEST brackets to TEST and press YES Troubleshooting and Maintenance 2 5 September 2003 Trimming the Recorder Outputs cont Test Menu ALARM RECORDER gt Select Recorder Select RCD Range 0 20 4 20 RCD Test Option SCALE TRIM Sel RCD A OUTPUT ZERO SPAN Use the arrow keys to move to RECORDER and press YES Use the arrow keys to move the brackets to the recorder you want to test and press YES Use the arrow keys to move the brackets to the output range and press YES Use the arrow keys to move the brackets to TRIM and press YES Use the arrow keys to select ZERO and press YES Observe the multimeter reading Wait at least 5 seconds for the recorder output to sett
100. us notre propre responsabilit que les Moisture Image Series 1 Analyzer Moisture Image Series 2 Analyzer Moisture Monitor Series 3 Analyzer Moisture Monitor Series 35 Analyzer r latif 4 cette d claration sont en conformit avec les documents suivants EN 61326 1998 Class A Annex A Continuous Unmonitored Operation EN 61010 1 1993 A2 1995 Overvoltage Category II Pollution Degree 2 suivant les r gles de la Directive de Compatibilit Electromagn tique 89 336 EEC et de la Directive Basse Tension 73 23 EEC Les mat riels list s ci dessus ainsi que les capteurs et les syst mes d chantillonnages pouvant tre livr s avec ne portent pas le marquage CE de la directive des quipements sous pression car ils sont fournis en accord avec la directive 97 23 EC des quipements sous pression pour les DN 25 Article 3 section 3 qui concerne les pratiques et les codes de bonne fabrication pour l ing nierie du son Shannon June 1 2002 FUP M Mr James Gibson DIRECTEUR G N RAL LS EN 1509002 TUV ESSEN Shannon ISO 9001 U S CERT DOC Rev G2 5 28 02 KONFORMIT TS GE Panametrics ERKL RUNG GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland erkl ren in alleiniger Verantwortung da die Produkte Moisture Image Series 1 Analyzer Moisture Image Series 2 Analyzer Moisture Monitor Series 3 Analyzer Moisture Monitor Series 35 Analyzer folgende Normen erf llen EN 61
101. witch block S1 has two switches 1 for Auxiliary 1 and 2 for Auxiliary 2 2 Setthe switches in one of two positions ON for current or OFF for voltage Installing Optional Features 1 15 September 2003 C Setting Input Switches cont of Enn 1 9g prm 0000000 3 00000000 20000 mi n 0 000 TUN Figure 1 12 Location of Switch 1 on the Channel Replacing the Channel Card 1 Once the switches are set replace the channel card 2 Replace the retainer bar Make sure the slots on the retainer bar are seated correctly against the printed circuit boards Secure the bar with two screws 3 Slide the electronics unit into its enclosure and replace the screws Tighten the screws until they are snug Do not over tighten You have completed connecting the pressure transmitter Installing Optional Features September 2003 tl Connecting Auxiliary The Series 3 accepts up to two auxiliary inputs from any probe with
102. wn moisture content for test samples Application of the Hygrometer 900 901D1 A 35 September 2003 Index A E Alarms Electrical Connections 1 1 Connecting a eses en neusie eee eee 1 7 wea wea ER ERES 1 7 Resetting orowe EE ee eee 2 2 Auxiliary Inputs 1 17 TESNE Les naa ee 2 2 Communications Port 1 20 Applications Pressure 1 9 Gases etui Emi A 11 Recorders ee ie 1 4 Liquids e eee A 22 Empirical Calibrations A 28 SOSA re A 34 Error Message Auxiliary Inputs Screen 2 8 1 17 Error Messages Switch 1 17 Calibration Error Description 2 32 Signal Error Description 2 32 B Background Gas Correction Factors 2 29 Flow Rates Gases u dere A 19 Liquids soe e 19 Cable 1 3 Monitoring 4 Cables Calibration Adjustment 1 22 G Calculations keel eee 11 Calibration Gases Empirical 0 0 een A 28 Cortosive et oes A 6 Making Adjustments for Cables 1 22 Plow Rates uet ea ran A 19 Replacing Probes 2 25 Calibration
103. ystem is 100 x 4 579 17 535 26 1 Three units of measure are commonly used in the gas industry to express the weight of water per unit volume of carrier gas They all represent a vapor density and are derivable from the vapor pressure of water and the Perfect Gas Laws Referenced to a temperature of 60 F and a pressure of 14 7 psia the following equations may be used to calculate these units mg of water _ 289 x Py 2 4 liter of gas Ib of water Pw 0 0324 x T 2 5 ft of gas R 6 Ibof water _ 10 xPy _Ibofwater _ won 2 6 MMSCFofgas 211 21 1 x Py Note MMSCF is an abbreviation for a million standard cubic feet of carrier gas Application of the Hygrometer 900 901D1 A 13 September 2003 Weight of Water per Unit Occasionally the moisture content of a gas is expressed in terms of Weight of Carrier Gas the weight of water per unit weight of carrier gas In such a case the unit of measure defined by the following equation is the most commonly used grains of water _ 7000 x My x Pw 2 7 lb of gas Mr x P For ambient air at 1 atm of pressure the above equation reduces to the following rains of water ETAS Sex Py 2 8 lb of gas A 14 Application of the Hygrometer 900 901D1 September 2003 fl Table A 1 Vapor Pressure of Water Note f the dew frost point is known the table will yield the partial water vapor pressure Pw in mm of Hg If the ambient
Download Pdf Manuals
Related Search
Related Contents
User Guide 土浦市イメージキャラクター「つちまる」着ぐるみ貸出要綱 (趣旨) 第1条 WPI Robotics Library User`s Guide Click - The Hong Kong Institute of Surveyors manuel d`installation, de fonctionnement et d`entretien ANEJOS 1 - 三洋電機 第44回六甲ファミリーまつり 第44回六甲ファミリーまつり Rollei DF-12.1 Feelings Copyright © All rights reserved.
Failed to retrieve file