Home
        TRX User Manual - Dual-Lite
         Contents
1.               A       i             D S a S a S a a S a E aaa             Breaker  Detail    Breaker  Detail    Connection  Detail    OR       T    Mal  L j 7    UPS Module 27  Battery Cabinet 59  Battery Cabinet  Front View Front View Front View  with doors removed without doors and without doors and   protective plates protective plates    NOTES   1  All Dual Lite supplied cable must be repositioned prior to and while the cabinets are being placed in  their final installed location     All interconnection hardware supplied by Dual Lite   All interconnection cables supplied by Dual Lite when bolted together   Interconnection cables field supplied when battery cabinets are stand alone     ote a aS    Refer to the individual drawing of each piece of equipment for additional details     Table 11 Dual Lite supplied interconnect wiring    am   m   o    o    UPS battery terminal block External 27  or 59  battery cabinet   Positive  midpoint  negative  Battery cabinet terminal block   UPS monitor board Battery breaker aux contacts       49    Installation Drawings    Figure 37 Maintenance Bypass interconnection  Refer to Table 12 for key to interconnection               n  th ha    al        a ARP  er jai a m a    stale eii      jai a JU            ot    ta  tale       O  Un       LL ES eG OSO o o o  ING YU E  Maintenance Bypass Transformer Cabinet UPS Module  front view without front door and panel left side view without side panel    NOTES  1  All Dual Lite supplied cable must be
2.       EPO NO EPO NC  EPO input contact relays     Position   Name   Description  J28 1 EPO _NC   EPO Activated when opened to J28 2  J282   EPO _ NC   EPO Activated when opened to J28 1    J28 2    J28 3 EPO NO   EPO Activated when shorted to J28 4  J28 4 EPO NO   EPO Activated when shorted to J28 3    O O Q       NOTE    The Emergency Stop action within the UPS shuts down the rectifier  inverter and static  bypass  It does not internally disconnect the input power supply  To disconnect ALL power to  the UPS  open the upstream feeder breaker s  when the remote EPO is activated     NOTE    Normally Closed EPO     X2  1 2  these terminals are supplied factory linked on the monitor  board and must remain installed if using NC contacts     NOTE    All auxiliary cables of terminal must be double insulated  Wire should be 20 16AWG stranded  for maximum runs between 82 and 197 feet  25 60m   respectively     18    Battery Installation    3 0 BATTERY INSTALLATION    3 1    3 2    3 3    Introduction    Dual Lite recommends that the batteries in external cabinets match the internal batteries in the TRX  in manufacturer and type     If using multiple sets of batteries connected in parallel to provide the required battery backup run  times  fit each set with an isolating device to permit working on one of the battery sets while leaving  the others in service and providing backup protection     When replacing batteries  replace with the same manufacturer and type  or equivalent  See your
3.      95    Specifications and Technical Data    11 2 Cable Lengths  Floor to Connection Point Inside UPS    To help calculate the total cable length required  refer to Table 43 for the distance from the floor to  selected connection points inside the TRX  Determine the cable length required to reach the TRX   then add the appropriate length from the table and adequate slack for repair and maintenance     Table 43 Distance to connection points on the TRX UPS    From  Top of Unit  Connection Point on UPS in   mm     Bypass AC input supply 30  750  30  750   UPS output AC 30  750  30  750   Neutral busbars    Input and Output 11  280  55  1397  Battery power 16  400  58  1474   Auxiliary cables  Monitor board  U2    60  1500  20  508   Communications 55  1400  25  635   Ground 8  197  56  14227   Parallel Board 70  1780  20  508     Use wiring rated at 75  C or greater        96    UPS Status Messages    APPENDIX A   UPS STATUS MESSAGES    Table 44 shows all event messages as they appear in the current status area of the LCD or the his   tory log  along with a description and recommended actions  1f any  For further information on the  current status area and the history log  see 2 11   UPS Status Messages     Table 44 UPS status messages    Event Message Description   Suggested Action  if any     inverter Comt Bai The RS485 communication between internal monitor and inverter fails  Contact the manufacturer  at 800 543 2378 for assistance    a l The RS485 communication between i
4.      Install battery racks  cabinets and batteries in accordance with the manufacturer s instructions     Verify that the battery area has adequate ventilation and battery operating temperature complies  with the manufacturer s specifications and with all applicable national and local codes     If you have any questions concerning batteries  battery racks or accessories  contact Technical Ser   vices at 1 800 543 2378     24    Maintenance Bypass Cabinet    4 0 MAINTENANCE BYPASS CABINET    The Maintenance Bypass Cabinet 1s designed to operate in UPS mode  bypass mode and maintenance  mode  The mode is selected using the Bypass Switch     Figure 17 Single UPS with external Maintenance Bypass Cabinet   typical configuration    208 120 VAC O ee  3 PHASE MAINTENANCE BYPASS PANELBOARD    MBB  N               208 120 VAC  3 PHASE  3 OR 4W   GND    AC OUTPUT  AC INPUT      4W   GND 4W   GND l       INTERNAL MAINTENANCE BYPASS        STATIC BYPASS       CONVERTER       UPS CABINET      41 Bypass Switch    The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass  source     4 2 Normal  UPS  Mode    While the Maintenance Bypass Cabinet rotary switch is in the NORMAL position  the UPS is supply   ing the connected load with continuous  high quality AC power  In this mode of operation  the load is  protected by the UPS     25    Maintenance Bypass Cabinet    4 3    4 4    4 5    4 6  4 6 1    Figure 18 Maintenance Bypass Cabinet   access plate remov
5.     A transfer to bypass occurred due to a large step load  The UPS should recover automatically   Load Impact Transfer Turn on connected equipment in sequential order to reduce the step loading of the inverter     The load is on bypass power due to excessive number of transfers that occurred within the last  hour    The UPS will recover automatically and will transfer the load back to inverter power within an  hour     UPS working within a parallel system are not sharing load current correctly  Contact the  Load Sharing Fault manufacturer at 800 543 2378 for assistance   Shut off inverter due to abnormal DC bus voltage   DG Bus Abnormal Contact the manufacturer at 800 543 2378 for assistance   The whole paralleled UPS system transferred to bypass at the same time  This message will  System Transfer appear on the UPS which passive transfer to bypass   Parallel board is not working correctly  Contact the manufacturer at 800 543 2378 for  Parallel Board Fault Assictanee    Rectifier  inverter and battery converter were shutdown because DC bus voltage is too high   Check whether there is a fault in rectifier side  If no  then check whether overload occurs   Restart the inverter after resetting the fault  If fault does not clear  contact the manufacturer at  800 543 2378 for assistance           Transfer Timeout       DC Bus Overvoltage       99    UPS Status Messages    Table 44 UPS status messages  continued     Event Message Description   Suggested Action  if any     The paral
6.     The circuit breaker has the following features        e Short circuit protection   e Protection against battery cabinet and ups connection errors  polarity reversal          36    Option Installations    Figure 27 Battery circuit breaker box connections     3  1 2   12 7mm     10 8    274mm     5 4    137mm     3 0    98mm             Connect to UPS Module   field installed                  dia  knockouts  101 2mm  A    for control wiring 8 3 alol  S a     211 7mm  ojog 81  12  conduit entry Top View 7 551319    9    20 0  3   508mm  4  2 5  15 0  5 Midpoi  oint   63 5mm   381mm  6 p  EA  O    CB  Load  TBI Side  CB  Line  Side  32 3  31 5  ie Se   819 2mm   800 1mm   72 Cells 72 Cells           _ a  From Customer   s Battery System  Front View  field supplied and field installed   leo   31  dia   7 9mm    38    Typ  4 places   9 5mm   1 93    3  1 2   12 7mm  25 4mm   49mm      o dia  knockouts  Bottom View TOF Powel ang  Se conduit entry   refer to top dimension   NOTES  62   1  NEMA 1 enclosure provided which is suitable for  15 8mm  47   wall mounting only  Approximate weight is 60 Ib  4 1  2  Hardware for connecting cables to the breaker supplied   11 8mm   3  Circuit breaker  Cutler  Hammer FD4125ED13D15A02 for 20 30 kVA  l      FD4070ED13D15A02 for 10 15 kVA Midpoint Busbar Detail  4  Color  IBM off white   5  Mount enclosure and pull all cables into enclosure before installing dry contacts   6  Low voltage wiring needs to enter from the top of the enclosure  in se
7.    30   28   29   so f 208   t  r    25    3o   220   207   so f 208   t  r   25      o  480   95   15 f 28   t  r   25    20  28   14   20 f 28   m   150    OR EE e ee ee    208 210     gt   E    208 140 20    208 104  208    125    208 167 225          aro   w   o   7   20   220 400 208 250 400   480 200 208 250 400   wf eo   na   50   e FE o  Pa    93                                                          Specifications and Technical Data                            Table 38 Maintenance bypass cabinet lug sizes  Input  Maximum Recommended Lug   Rating Input Voltage Bolt Size One Hole 54000 One Hole REDDY  30 600 M  1 4   54105 62204  30 480 M  1 4   54106 62204  30 240 M  1 4   54152 62205  30 220 M  1 4   54152 62205  30 208 M  1 4   54152 62205  20 600 M  1 4   NA 62204  20 480 M  1 4   54130 62204  20 240 M  1 4   54107 62204  20 220 M  1 4   54107 62204  20 208 M  1 4   54107 62204  15 600 M  1 4   NA 62204  15 480 M  1 4   NA 62204  15 240 M  1 4   54106 62204  15 220 M  1 4   54106 62204  15 208 M  1 4   54106 62204  10 600 M  1 4   NA 62204  10 480 M  1 4   NA 62204  10 240 M  1 4   54130 62204  10 220 M  1 4   54130 62204  10 208 M  1 4   54130 62204   Output   Maximum Recommended Lug  Rating Output Voltage Bolt Size One Hole 54000 One Hole REDDY                                                          30 500 M4   30 280 M  17A   30 240 MCW  20 220 M 17a    30 208 MA   20 500 may   NA 220  20 480 M 1 4   20 240 M C1    20 220 M  1 4   20 208 M4   E 500 may   NA 22
8.    The monitor board  arranged for this purpose  is located on the rear of the operator access door  The  main features are      Input and Output dry contacts signal  one pair of contacts of relay     gt  Emergency Power Off control  KPO      Environmental parameter input interface   e User communication  for data setting and user background monitor    e IntelliSlot   interface   e Modem interface     Temperature detect interface    Figure 6 shows the relationship and connection between the monitoring  U2  board and other boards  in the UPS     Figure 6 Monitor board U2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           14    Electrical Connections    Figure 7 Auxiliary terminal block detail  Monitoring Board           L J8             J1    LCD    J2       MODEM  J15     SNMP CARD X5    J16 E           O J13 J21 J25 J28 J4 J26 J30 J10 J24   eoomforom oron   teen      roonfoconforon os n          6  ee ene ae A E  ee NOTE  The black square  m   X1 X2 AB on each slot 
9.    and     Output frequency level    respectively       lf the displayed voltage is believed to be abnormal  then verify the bypass voltage and  frequency presented to the UPS  Check the external bypass supply if it is found to be faulty  If  the utility is likely to trigger this alarm frequently  the bypass limit can be changed a little larger  through the configuration software according to the customer s agreement    Contact the manufacturer at 800 543 2378 for assistance     This alarm is triggered by an inverter software routine when the inverter and bypass waveforms   are misaligned by more than 6 degrees in phase  This alarm resets automatically once the   condition is no longer true    1  First check if the alarm    Bypass unable to trace    or    Bypass abnormal    occurs  If so  solve it  first    2  Verify the waveform of the bypass voltage  If it is too distorted  ask the customer to verify and  seek any possible measurements    Contact the manufacturer at 800 543 2378 for assistance     Inverter Fault This alarm indicates a fault condition exists within the inverter   Contact the manufacturer at 800 543 2378 for assistance     The temperature of the output filter inductor is too high to keep inverter running    This alarm is triggered by the signal from a thermostat mounted in the output filter inductor   The UPS would recover automatically after a 5 minute delay from the disappearance of the  overtemperature signal    If the overtemperature condition is true the
10.   11 0 SPECIFICATIONS AND TECHNICAL DATA        0oooccocc ees 90  11 1 Lug Size and Torque Requirements    90  11 2 Cable Lengths  Floor to Connection Point Inside UPS               oo oooooooo ooo    96  APPENDIX A   UPS STATUS MESSAGES     00ccoccccc es 97  FIGURES  Fistre bt   Cabimettartrase net A o A A ia 8  Figure 2 Single module block diagram   dual input configuration        0  0 00000 ooo    o    10  Foie    Input si ada tia eli a A o da et 11  Figure 4 Battery fuses and connections    11  Figure 5 Ground and neutral busbar connections    12  Bieure 6   Monitor board Dl 608 ba aes a8 as ae e a aa  d eis ee ee cee ach a 14  Figure 7 Auxiliary terminal block detail  Monitoring Board           0 0 0 0  ccc ee ens 15  Picure   s    Inputary contacts  beso ds SAA A BAR EERE Ree ees 15  Figure 9 Jumper connection for BCB interface           00  0c eee eee eens 16  Figure 10 Output dry contacts and EPO wiring for firmware before M170             o  o oooooooo o 17  Figure 11 EPO wiring for firmware M200 or later             o    ce eee eee 18  Figure 12  Battery cabinet     etd lS cesarea bate oe a ia a ito E a do 20    Figure 13  Figure 14  Figure 15  Figure 16  Figure 17  Figure 18  Figure 19  Figure 20  Figure 21  Figure 22  Figure 23  Figure 24  Figure 25  Figure 26  Figure 27  Figure 28  Figure 29  Figure 30  Figure 31  Figure 32  Figure 33  Figure 34  Figure 35  Figure 36  Figure 37  Figure 38  Figure 39  Figure 40  Figure 41  Figure 42  Figure 43  Figure 44  Figure 4
11.   A a   oe    a 14 UPS  1  UPS  4 O  Output Breaker Aux Contact       53    Installation Drawings    Figure 41 Lineup detail   1 N Type B1 connection to TRX            A  Tear ty  ent x    8  18         E                   1   N Cabinet Side View 1   N Parallel Cabinet 1   N Cabinet Interior View   without side panel or door   front view without front door and panel   neutral and ground busbar location     1  All Dual Lite supplied cable must be repositioned prior to and while  setting the cabinets in their installed location    2  All interconnection cables and hardware supplied by others    3  AC connections must be made to the UPS modules before attaching  paralleling cabinet to UPS modules    4  The interconnecting input cables between the paralleling cabinet and  the UPSs must be the same size and the same length    5  The interconnecting output cables between the paralleling cabinet and  the UPSs must be the same size and the same length    6  The location of the system output neutral busbar  connection K  and  the ground busbar  connections H  I and J  are shown for a left access  style  For right access version  these busbars are at opposite locations    7  Refer to the individual drawing of each piece of equipment for  additional details           Es e  e       Ab dh   e   A Ai E    OTER    rR    TT           UPS Module Left Side Vie   without side panel     Table 16 Interconnect wiring   1 N Type B1 connection to TRX    man Jam  os  Ce   _Uility AC Souree   Paraleli
12.   STS  for single corded equipment     Performance Requirements  The DBS operates under the following conditions     e Both master and slave are on inverter   either system may be on inverter through the rectifier or on inverter through the batteries     e Master on inverter  and slave on bypass  e Master on bypass  and slave on inverter  e Master and slave on bypass IF the bypass source is the same for both systems    DBS Cable and Settings    For TRX to TRX dual bus configuration  only one optional LBS cable is required  the built in LBS will  operate normally without extra LBS control box or interface box  The LBS port is X4 on the parallel  board  M3   The parallel board is on the interior of the TRX  above and left of the power electronics   see Figure 32     An optional  9 pin LBS cable is used to connect two UPS systems through each system s DB9 port on  its parallel board  For two parallel systems  the LBS cable can be mounted between any two units  belonging to different parallel systems  For information about the LBS kit or to order the optional  equipment  see your local sales representative     The LBS cable is connected as illustrated in Figure 21     Figure 21 Load Bus Synchronization cable connection    LBS Cable    Parallel Board Parallel Board                                                          The parallel board is on the  interior of the TRX  above and  left of the power electronics   see Figure 32                               UPS Module or UPS Module
13.  1    9 2    9 3  9 4  9 5  9 6  9 7  9 8    INSTAEEATION DRAWING S cauca nannan 44    OPERATION css raia AA aR 58  General Descriptions   ooa  id ss nadas rd dad 58  BY Pass UPPER be A AAA A A AA AA 58   peratino Modes serte pr ias ii rd ewe  amp  58  OPERATOR CONTROL AND DISPLAY PANEL      0 0ccccccc cece eee eee eee ees 60  Operator Control  Panel sas tata es cee te Rees BHR ra wee 60  Oe ADs Vari ae WAY Oo at ass ad e eet eh sen ee E 60  Nime Isp lay IMA ICAOES  hte ees AA AAA AT AA OD EDR 61  WONG Ol Nott A II IN hh tee ee aoa ead eid ae 62  Alarm PAZ LON O cee ce Bae dP erect oa thd ne ae eh coe ach he wh GRE Sg seh dances es 62  CID OV Crier otk we keh daa AA ee he ee thee Sa 63  INVA AU LOM y Sree niet ty ta isaac a ie et IU O ae oe  eon ede ee yk 64  UPS System Iniorinia tOW   di Gea os Sa ste ae id id ee he eet eS 64  ECD Me  us and Data Nems ereis aes Ce ae NA Ad 65  Lansuase Selectos  ii acral tec bln te ae id ds cata ee ee 66  Current Date and  Lime  sais aid a Eee a ERE 66  WPS DtdbUSVICSSASCS 04 a ls bah ee ea alee Mea cee 69  ira EA avai cade By O tees 70  MO O a WA a a ings rath SA ata A ante ew Seda Sarath Oats Bete mead 70  Ook Zee io esteriai aa kre  Ste 4b d ae We aad hes Ras eee ars eae Sa baat ea ee Buea 70  Sl Zio  WES Help  Screen  nia ouverte we Sd abet Pe ee apd ea he ee eek a 71  812 4  Screen Saver  WINdOW   cistitis 71  Pops UDWINdOWS  an oe S65 DR A ai BR tt e a Ad a a 72  8 13 1 From Bypass to Inverter Mode With Power Interruption              
14.  220  480    208  220  240  480    220    208  480    208  208    480  220    480  ci    fe  220    220    208  208  208    480    208  220  2    208    40    480    480    220    220    91    Specifications and Technical Data    Table 35 Maintenance bypass cabinet electrical data  single input   continued     Maintenance  Bypass Bypass Cabinet Cabinet  I P Voltage Max Input Input OCP   O P Voltage Nominal O P Output  Current i Current Rating  A    OCP CB Size  A     CEOE E A E    afr     es  ies   tor  mes 08   rao  FP    o AI or A  as  Oee 60m   2   3   8   0   ae     70  20 JAP  208   eo   8   7s   80  e  o so   70  ee ee EN EN ee CE ee  BG ee ee E E E ae  5  API 60   7   30   te  e    eo    APA TA LAA AAC AO A  PEE ee E O ee  AA E 0 E a E  O E  EI E E A O O       92    Specifications and Technical Data  Table 37 Multi module bypass cabinet electrical data    System Nominal O P Output OCP  Size Type i Current Rating  A    CB Size  A     a a a e II       CA 20  tor  E   208 fas tas  emon  so   600   a7   oa   20  8   tes  emon  20  220   68   100A   208   ss   70  cmon  20   600   25   40a   208   ss   7  em  is   208   s   o        42   00  emon 1s   220   sr   80a   20  42   60  emon 1s    80   23   40a   20  42   e  emon  1s   600   19   90a   ae   2   60  gt   rotor   o  eo   12   20a  em  e   4    so  28   10    135 f 28   1607        28   7       f 28   m   150    i 20   220   13   20 f 28   m   150    2  48o   e   10 f 28   m   150    2    eo   5   7  f 28   m   150 
15.  Crest Factor  Sout  Apparent power  Pout  Active power  System  Qout Wan Qout  Reactive power  When configured as a single unit  UPS has only native load  no system load                                   67    Operator Control and Display Panel    Table 22 Descriptions of UPS menus and data window items  continued     Menu Type Item Type Explanation  Display contrast Adjust the LCD display contrast    Date format set Choose the format for date display  M D Y  D M Y  M D Y  Y M D  Date  amp  time Set the date and time     Setthedateandime OSS O    Callback times When IntelliSlot 1 Communication mode is Modem  this parameter sets the  number of times a number is redialed to send an alarm notification    Phone No 1 When IntelliSlot 1 Communication mode is Modem  this is the first phone  number to be dialed  to send an alarm notification     Phone No 2 When IntelliSlot 1 Communication mode is Modem  this is the second phone  number to be dialed  to send an alarm notification      Phone No 3 When IntelliSlot 1 Communication mode is Modem  this is the third phone          number to be dialed  to send an alarm notification      Command password User can modify the command password     Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate  of the battery capacity  Load must be between 20  and 80      Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of  the battery capacity  Load m
16.  E id ia cita 30  DileZ  DBS Cable andinas  ii be aa 30  Configuring Parallel System Operation              ro  31  Dl General e id pleno ea Fc dt a a ee ae ies ease da lie 31  a2  Featuresol Parallel oysters cis oe A ee ei is eon donee ene AGE 32  S220 Operating Principles ii A a biel ce aot Ad ADAN aida 33  5 24     Operation  Modes Summary sul  lt 4 soe asd RI ad WOR OA SRO AA ad 33  Instalhine Parallel oy stems  ie ys aca Mae ak es biG hak Cae ater See ae Os GANEA 33  DSL    Conditions tor Parallel Systems AA eee be eee eke ee eas 33  Do2 Caninet lnstallanion A AS A A BS ee AA OO 33  A e lor an A ht tote Res eS EERE O19 SORES RACER ERE ORO Ob OS 33  Dat Protective Devices tr ica A AP RAE AA A A EA BRS 33  nro    HOWE ales Aha NN 34  Do   Patallel Control Cables    ea a a aa 34  Sd Mmergency Power Ot  HPO  5103 ti a ds Aa Gees      36  Battery Circuit breaker BOX 2d E a dl 36  Batteraostatt si AA Ss at edad 38  Remote lari  MONO  caviar dio 38  Aa loo Input Inter aces aii da aa id iaa ey dl 38  POWer OULD UU cco det teen anc dd il da Dal Bo did da isa 38  IntelliSlot Communications ie hace 64 tak bSe ias eRe 38  OC Web Card   SNMP HTTP Network Interface Card           0 0    0 0 cee eee 39  DIOT Contisutino Baud Rates i  6 se a RES ore Ba SAA A Pee wees 40  Relay Can tus cient ewe Wek A ne AA ee eb eat o da 42  M  nni Fon Card seats Laprida A dato 43    ii    6 0    7 0  1 1  1 2  7 3    8 0  8 1    3 2  3 9  3 4  3 0  3 6  8 7  8 8  8 9  8 10  3 11  3 12    3 13    9 0  9
17.  ESC  key  The pop up window disappears         NOTE  For a battery capacity test to function properly  the load must be between 20  and 100      Battery Self Test Aborted  Condition Not Met   When a battery capacity test 1s started from the Command menu and   the battery self test condition is inadequate  the TRX will not perform Battery Self Test aborted   a battery test  User should check whether the battery state is boost Conditions not met       charging and whether the load level is greater than 20 percent     e Press the F4  Enter  key and the pop up window closes   Battery Refresh Charge Aborted  Condition Not Met    When a battery refreshening charge is started from the Command  menu and battery refreshening condition fails to meet requirements  Battery Refresh Charge  the TRX will not perform a battery refreshening charge  User should aborted    check if boost charging condition is not enough  such as  No battery  Conditions not met  charger failed  etc          e Press the F4  Enter  key and the pop up window closes     72    Operating Instructions    9 0 OPERATING INSTRUCTIONS    9 1 TRX Operating Modes    The TRX can operate in any of four modes  as shown in Table 23  This section provides instructions  on switching between modes  resetting the UPS  switching the inverter On and Off and performing  other operations     Table 23 UPS operating modes    Operating Rotary Switch   Mode Position Description  Normal NORMAL The UPS is powering the load    Operation    Th
18.  Faria  A he ci the Oe ane Re ae eae a 62  DCCEONG lt 01 TNC LCD RDA AAA EDS OR EEG EAs ROPES 63  Men tree tes AR RA AS Baca TR 65  Current status and history log records            00 0 cc ccc eee eee eee eee eens 69  Open oe displasia fons ee nats wae ed is cee tee ee Gee dae bee eee BS 70  DEAE Cros A ANS endl Gol SU ed ea ees a8 oS wk oes 70  Melp Screen A O O 71  SOLER Saver WINdOW  a A E AR AAA IA ATAR 71  Power swatches LORVATRX   0000 oi a OOH a a Gee 74  Typical configuration for single UPS with external maintenance bypass cabinet              78  Single UPS with external Maintenance Bypass Cabinet   typical configuration              84  Dust titer replacement  ty sc ats sorta eo had ee A RS EA ES AA eet 85    Table 1   Table 2   Table 3   Table 4   Table 5   Table 6   Table 7   Table 8   Table 9   Table 10  Table 11  Table 12  Table 13  Table 14  Table 15  Table 16  Table 17  Table 18  Table 19  Table 20  Table 21  Table 22  Table 23  Table 24  Table 25  Table 26  Table 27  Table 28  Table 29  Table 30  Table 31  Table 32  Table 33  Table 34  Table 35  Table 36  Table 37  Table 38  Table 39  Table 40  Table 41  Table 42  Table 43  Table 44    TABLES    Popat dry contacts aL ta A e A a a a   15  Maintenance bypass cabinet Interface    16  DGB OX MSc  sisi A a EG OS HS adan abad 16  Output dry contact relays  iii das A ea bas eae 17  EPO input contact relay erea Adi ake dee hehe a Ea 17  EPO  Mnpurcont ace relays ips bite a A os AS A A ES a 18  Available battery circ
19.  Operation  The load is powered by the inverters of all the UPS modules in the system  If the frequency of  bypass 1s within the synchronous range  the inverter will be synchronized with the bypass  Other   wise  the system will operate at nominal frequency      Battery Mode Operation  The batteries of all UPS modules power the load through their inverters  The system operates at  nominal frequency      Bypass Mode Operation    The condition to transfer to bypass mode 1s essentially the same as that of single module system   The bypass of all the UPS modules powers the load     e Maintenance Bypass Mode Operation    The sequence to transfer to maintenance bypass mode is the same as for transferring a single   module system  The maintenance bypass switches should be switched on as synchronously as pos   sible  Thus the system can be repaired without interrupting the power supply to critical load     Installing Parallel System  The basic installation procedure of parallel system is the same as that of single module system  The    following sections introduce only the installation procedures specific to the parallel system     Conditions for Parallel System  e Each UPS module should have the same rating  the same firmware and hardware version     Each UPS module must have the same bypass source    e The outputs of all UPS modules are connected altogether       The main inputs can be from different sources  but the phase rotation sequence of main inputs   bypass inputs and output
20.  SILENCE ON OFF                AA    14    15 16    Mimic indicators    Rectifier indicator  Battery indicator  Bypass indicator  Inverter indicator  Load indicator  Status indicator    Buzzer    17       gt   i  18 19    Control buttons Navigation keys    8  Button cover 15 F1  9  EPO button 16  F2  10  INVERTER ON button 17 F3  11  INVERTER OFF button 18  F4  12  FAULT CLEAR button 19  Help    13  SILENCE ON OFF button    60    Operator Control and Display Panel    8 2 Mimic Display Indicators    The Mimic display on the front panel consists of six indicators arranged in a single line diagram  depicting the various paths of UPS power  as shown in Figure 48     Figure 48 Mimic display indicators location  2    Mimic indicators 1134 A6   1  Rectifier indicator   2  Battery indicator   3  Bypass indicator NN al  4  Inverter indicator  m   5  Load indicator ey bate  6  Status indicator      ae eee       Vline V 208  RIR   0 99   INVERTERON INVERTER OFF    Input Breaker Closed 01 12 12 28 16   amp     Manual Turn On 01 12 12 30 06  UPS in Normal Mode 01 22 12 30 16  FAULT CLEAR SILENCE ON OFF       OO O E       The current operational status of the Dual Lite TRX is indicated by the color of the indicators   green   amber or red   and whether they are ON  solid   flashing or OFF  Table 18 provides a guide to inter   preting the various states of the indicators     Table 18 Mimic display status indicators    Indicator   see  Figure 48  Flashing Green   Amber    Dni Load on rectifi
21.  any packaging material  then visually examine the UPS and battery equipment for  transit damage  both internally and externally  Report any such damage to the shipper and to the  manufacturer immediately    2  Check the nameplate inside the cabinet door to verify that the model number and rating  correspond to the ones specified  Record the model number and serial number in the front of this  installation manual  This information is necessary should service be required    3  Check for loose connections or unsecured components in the cabinet    4  Check for shipping damage to internal components     1 2 1    1 3  1 3 1    1 4  1 4 1    1 4 2    Installation    Storing for Delayed Installation    If the equipment will not be installed immediately  it must be stored indoors where the humidity is no  higher than 90  and the temperature 1s no higher than 104  F  40  C   The storage area must protect  the TRX from excessive moisture  see 10 2   UPS Environmental      YN CAUTION    If the UPS must remain disconnected from power for more than six  6  months  the battery  must be recharged before use  To charge the batteries  the unit must be connected to utility  power and started up   the charger operates only while the TRX is operating     YN CAUTION    When batteries are installed in the UPS or are cabinet mounted adjacent to the UPS unit  the  battery   not the UPS   dictates the designed maximum ambient temperature     Preliminary Checks    Identification    The equipment suppl
22.  be installed by a qualified engineer in accordance with the  information contained in this section     YN WARNING    Special care should be taken when working with the batteries associated with this equipment   When connected together  the nominal battery voltage is 288VDC and is potentially lethal      Eye protection should be worn to prevent injury from accidental electrical arcs      Remove rings  watches and all metal objects    e Only use tools with insulated handles    e Wear rubber gloves    If a battery leaks electrolyte or is otherwise physically damaged  it must be replaced  stored in  a container resistant to sulfuric acid and disposed of in accordance with local regulations     If electrolyte comes into contact with skin  the affected area should be washed immediately  with large amounts of water     NOTE  The TRX UPS can be used in TN utility system     External Inspections   1  While the UPS system is still on the truck  inspect the equipment and shipping container s  for  any signs of damage or mishandling  Do not attempt to install the system if damage is apparent   If any damage is noted  file a damage claim with the shipping agency within 24 hours and contact  Technical Services at 1 800 543 2378 to inform them of the damage claim and the condition of the  equipment    2  Compare the contents of the shipment with the bill of lading  Report any missing items to the  carrier and your local sales representative immediately     Internal Inspections    1  Remove
23.  dad A A aos oe 19  3 2 DALEL piara ceases dates  a A neh i Se oA 19  3 3 o ieee cue fae sees EN 19    3 4    3 0  4 0  4 1  4 2  4 3  4 4  4 5  4 6    4 7  9 0  5 1    5 2    5 3    5 4  5 5  5 6  5 7  5 8  5 9  5 10    5 11  5 12    External Battery Cabinet Installation                o    ooo    ooo    ooo 20    dl Matchine Battery Cabilebs 62 ies ow dio a A ee eae    20  Sie  Connecting the Batternesuarniddas regida ews ead tad oS coe kde eRe oA 20  343    Installation Considerations 42 i444 a TIA Gabe E PGS AR AA AA A 22  3 4 4 Connecting the Battery Cabinet to the UPS             o oo oooooooomoooooooo eee 24  Nons gt tandard  BICOS a ES ERA doe AA oe he Se eS 24  MAINTENANCE BYPASS CABINET       000 cece eee eee ee 25  DY Pas o Wisin sia cda ea na ae a a ow eed 25  Normal  UPS Modest AR oe Als eS ARE RRO AAS aes 25  Bypass Mode  seirer kes Gnd hee a Baar Ech e oe ye ehh ae SP Ace decada l 26  Maintenance Mods  creo dace so E eA AE PA A OS He RO AA Gees eR 26  TOCA LING UMC OAD INCU  ss a A A ete eae i AR 26  Cable Installation fyb e ii rs ia Baw aed  ae dow a ae De E 26  AG Wina Erepara ti  n dia atone ey eth Raed blot ae Reese baa eats 26  462  Power Cable nstallati perset oebdenee bb aa yaad bo bared 6648 a dades d 2q  110 30     Input Output WIRE  ias al A A aaa E AE AA AT EA A ak 27  Boltine Cabinets   OOCONEMS ui aa la Aaaa aia e a d 29  OPTION   NSTALLATIONS iii a we moe 30  Load  Bus oyNcHroni Zat Oeean ds De IE E OS BREE wee 30  SLL  Pertormance  Requirements A
24.  door  Further internal safety screens  make the equipment protected to IP20 standards     No risk exists to any personnel when operating the equipment in the normal manner   following the recommended operating procedures     All equipment maintenance and servicing procedures involve internal access and should be  carried out only by trained personnel     WARNING    High ground leakage current  Ground connection 1s essential before connecting the input  supply   This equipment must be grounded in accordance with local electrical codes     Maximum load must not exceed that shown on the UPS rating label     WARNING    This product contains chemicals known to the state of California to cause cancer  birth defects  and or other reproductive harm  Thoroughly wash hands after installing  handling  cleaning  or otherwise touching this product     A    A    CAUTION    This equipment is fitted with RFI suppression filters   Ground leakage current exceeds 3 5 mA and is less than 1000 mA     Transient and steady state ground leakage currents  which may occur when starting the  equipment  should be taken into account when selecting instantaneous residual current  circuit breakers  RCCBs  or residual current devices  RCDs      RCCBs must be selected sensitive to DC unidirectional pulses  Class A  and insensitive to  transient current pulses     Note also that the ground leakage currents of the load will be carried by this RCCB or RCD     WARNING    Under typical operation and with all UPS
25.  doors closed  only normal safety precautions are  necessary  The area around the UPS system should be kept free of puddles of water  excess  moisture and debris     Special safety precautions are required for procedures involving handling  installation and  maintenance of the UPS system and the battery  Observe all safety precautions in this  manual before handling or installing the UPS system  Observe all precautions in the  Operation and Maintenance Manual  before as well as during performance of all maintenance  procedures  Observe all battery safety precautions before working on or near the battery     This equipment contains several circuits that are energized with high voltage  Only  test equipment designed for troubleshooting should be used  This is particularly true for  oscilloscopes  Always check with an AC and DC voltmeter to ensure safety before making  contact or using tools  Even when the power is turned Off  dangerously high electric charges  may exist within the UPS     All power and control wiring should be installed by a qualified electrician  All power  and control wiring must comply with the NEC and applicable local codes     ONLY qualified service personnel should perform maintenance on the UPS system   When performing maintenance with any part of the equipment under power  service  personnel and test equipment should be standing on rubber mats  The service personnel  should wear insulating shoes for isolation from direct contact with the floor  earth gr
26.  e   atte te Su ea ide als a Pe  ca das ars agri Bs Nate eR SR  edhe oe 7  O2 DPloor Installation a cde Ooh oa he ie a be eee a ko ees 7  LO    LADEN doors tai e a dirias retake Tata Mae dar daa T  LGA Optional Cabinet  SES AAA ad 8  2 0    ELECTRICAL  CONNECTIONS a vsaiisunaa A aa 9  2 1 Power Cable a SA A a a 9  21  Gable Rat  ds E A SR EG we OS ADE a aw A eras A RRS A 9  DEZ  OPSInpat COON OUrAl lO Nc da Baca ede eo arerl dh bBo Ra NR Wee a RE Be Cot nts ioe Bass 10  Delgo  Cabine CUINA A A eeang Mood as dy 10  Zalat    able CONMCCHONS seis a da A ele tue Awe ma a eek 11  Zig   oalety Grounds  2 4  acbiaceak tae e hock gan baeaeod eet sdoes bute heck a AA boas s   12  2 O Protective DECS dere fonts Gace ces todas chat  Bat eb cp edn A al Bion aes ae cea  heme a 12  Zi Gablmea Procedure is Bees eh a Bae wee ek eee eh ae eae eae 18  22 Control Cables Areria wy Gude ee CAs FAROESE ee ASSES Aaa tee eos 14  22 1   Monitor Board Features    vcd  ciaavdoma bowen 4 ad Jb ned ee ee PO ae RAS Yee eed 14  2 3 MT CON AC Ss cian Ses te Come ae al oe od aac rane dG asa ay eens Gee teed ae ee T arta 15  Zot pat Ory Contacts  si stead hate ated Grapes ae SA hen eh Ewe tee oa 15  2 3 2 Maintenance Bypass Cabinet Interface         0 0    0  ee ne eens 16  220 0   BOB Bor Tte Osr vhadtodeebenn oboe nae dais adidas 16  Zoe     OutputDry Contacte La AN SAA AAA dew wee eee Aa eee  17  Zo  EPO Mpm  Opina eraa aa e En oe wee 17  3 0 BATTERY INSTALLATION o esuicasa ra 19  3 1 INTEOAUCUHON  a as as
27.  input line to line voltage amplitude of rectifier   Mans Eei Abnormal Mains frequency is out of limit range and results in rectifier shutdown   q  Check the rectifiers input voltage frequency    Battery Fuse Fail Battery Fuse is open  Contact the manufacturer at 800 543 2378 for assistance   Rectifier Fault Rectifier Fault  Contact the manufacturer at 800 543 2378 for assistance     The temperature of rectifier inductor is too high to keep the rectifier running   Input Inductor Overtemp    Check the ambient temperature and ventilation  contact the manufacturer at  800 543 2378 for assistance     The temperature of heat sink is too high to keep the rectifier running        Battery Low Pre warning             Rectifier Overtemp     The UPS can recover automatically  Check the environment and ventilation     Charger Fault The Charger is fault  Contact the manufacturer at 800 543 2378 for assistance   Input Fuse Fail Input fuse is open  Contact the manufacturer at 800 543 2378 for assistance     l Control Power 1 has failed or has been lost  Contact the manufacturer at 800 543 2378 for  Control Power 1 Fail S E anne    Mains Phase Reversed Input phase sequence is inverse  Contact the manufacturer at 800 543 2378 for assistance   Rectifier Overcurrent The current of Rectifier is over limit  Contact the manufacturer at 800 543 2378 for assistance       Rectifier could not start due to low DC bus voltage  Contact the manufacturer at 800 543 2378 for  Soft Start Fail Zee AnG       9
28.  moving the unit a short distance  For longer distances   move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration     The optional battery cabinets should be moved with a forklift or similar equipment     YN WARNING    Ensure that any equipment that will be used to move the TRX has sufficient lifting capacity   The TRX weight ranges from 850 to 1400 lb   886 to 635kg   See Table 26 for details  The  UPS presents a tipping hazard  Do not tilt the TRX further than 15 degrees from vertical     The UPS is fitted with casters   take care to prevent movement when unbolting the  equipment from its shipping pallet  Ensure adequate personnel and lifting equipment are  available when taking the TRX off its shipping pallet  Do not tilt the unit more than 15  degrees from center     YN WARNING    The casters are strong enough for movement across even surfaces only  Casters may fail if  they are subjected to shock loading  such as being dropped or rolled over holes in the floor or  obstructions  Such failure may cause the unit to tip over  injuring personnel and damaging  the equipment     Care must be taken when maneuvering units fitted with batteries  Keep such moves to a  minimum  For further information  see Battery Cabinet Precautions on page 2     Final Position    When the equipment has been finally positioned  ensure that the adjustable stops are set so that the  UPS will remain stationary and stable  see 6 0   Installation Drawings      Me
29.  o oooooo oo ooo  72  8 13 2 From Inverter to Bypass Mode With Interruption           0  0 000000  ooo    oo  12  Sd System Della estos ber bid e das bla o ars Dis 12  8 13 4 Battery Capacity Test Confirmation s  gt  ei A AA a A ia a 12  8 13 5 Battery Self Test Aborted  Condition Not Met             o oooooocooooooooooo eee T   8 13 6 Battery Refresh Charge Aborted  Condition Not Met             0 00 00    cece eee 12  OPERATING INSTRUCTIONS raira a e sean eee ee he Aa 73  TRX Operatina Modesto  ir ds a a a E a EN 73  LT    tPOWERS WINS  dia dad ds di cia la 74  US  Taro Us ale a ra a BE Bd Bh A a al Ae ke 75  O21  Start Up Procedure SA LISAS A ADE ees bashes ck PE SARE 75  9 2 2 Verify Switching Between Operation Modes              0 00  76  Switching the UPS from Normal to Maintenance BypasS              ooo coco  ooo    17  rower Dowwe UPS ricardo diia ida 17  Powering Down the UPS and Maintaining Power to Load                   o o  o     78  Emergency Shutdown With EPO             o o o oooooooooooooo ooo    oo    79  AUTO NES tata ado ai Oda dara 79  Reset After Shutdown for Emergency Stop  EPO Action  or Other Conditions            79    iii    9 9 Battery    FOleCtlOn  6 dyna 4 ods  idad we oe bea owe mowers 80  9 9 1 Battery Undervoltage Pre Warning           cc ee eee eee ee eee 80  9 9 2 Battery End of Discharge  HOD  Protection          0 0 0 000 0000 ccc eee 80  99 3     Battery Puse  Blow Warne seis ede a Si E ae eee tc 80  9 10 Isolating and Integrating One Mo
30.  or  System  1 System  2    The LBS function is activated with configuration software  when the LBS takes effect  the graphic  LCD will display    LBS active        30    9 2  5 2 1    Option Installations    Configuring Parallel System Operation    General    The TRX uses intelligent and reliable decentralized technology to achieve parallel operation of two or  more modules of the same rating     The 1 N system is used to       Increase the reliability of the system to ensure adequate power supply to the critical load con   nected      Increase serviceability and allow the execution of maintenance operations and reparations with   out affecting the ordinary operating conditions of the system  depending on the redundancy level      31    Option Installations    5 2 2 Features of Parallel System     The hardware and firmware for parallel UPS module operation is standard in the TRX  and the  configuration can be set up by changing the settings in configuration software      It is easy to install the parallel cables in a ring  providing high reliability and redundancy  And  the intelligent paralleling logic provides the user with maximum flexibility  For example  shut   ting down or starting up the UPS modules in the parallel system can be done in any sequence  If  an overload transfer occurs  the whole system can recover automatically from bypass mode after  the overload is cleared    e The total load of the parallel system can be queried from each module   s liquid crystal dis
31.  recorded   The history log can hold up to 512 records  History log records may be viewed by accessing the  Records menu     Figure 53 Current status and history log records    DuakLite TRX 2009 01 22 12 30 36  30kVA 3X3 Single Normal     d  system Battery    Bypass abnormal  01 22 2004 09 57 13  01 22 2004 10 02 16  Inverter asynchronous    01 22 2004 09 57 13 History log  01 22 2004 10 02 21  records menu   Mains freq  abnormal  01 22 2004 09 57 14  01 22 2004 10 02 14    Fault reset  Manual turn on  Normal mode    Current status  messages          See Table 44 in Appendix A for a complete list of status messages  along with a description and any  recommended actions        69    8 12 Types of LCD Screens    Operator Control and Display Panel    This section provides a quick guide to the main types of LCD screens     8 12 1 Opening Display    As the UPS begins powering up  the opening display appears  as shown in Figure 54     Figure 54 Opening display       8 12 2 Default Screen    After the UPS has powered up and completed a self test  the output screen appears  as shown in  Figure 55  This window is the default screen     Figure 55 Default screen    DuakLite TRX  30KVA 3X3    L N voltage V   L N current  A   Frequency  Hz   L L voltage A   Power factor    Fault reset  Manual turn on  Normal mode    2009 01 22  Single    L1 N L2  119 8  0 3  59 97  207 1  0 00    01 22 10 32    01 22 10 32  01 22 11 05       70    Operator Control and Display Panel    8 12 3 UPS Help Scre
32.  repositioned prior to and while the cabinets are being placed in  their final installed location     2  All interconnection hardware supplied by Dual Lite     3  AC connections must be made to the UPS module before attaching maintenance bypass transformer  cabinet to UPS module     4  Utility AC source neutral not required for maintenance bypass transformer cabinet types D  E  M  N     5  All cabling will be field supplied when maintenance bypass transformer cabinet is configured as stand   alone cabinet     6  Maintenance bypass transformer cabinets must attach to the left side only   7  Refer to the individual drawing of each piece of equipment for additional details     Table 12 Dual Lite supplied interconnect wiring for Maintenance Bypass Cabinet     mun  om  aeare  6   Unity Ao source   Maintenance   Neutral bypess  transformer cabinet  0  Maintenance   UPS module ACinput   PRA  O UPS par  E   UPS module AC ouput   Maintenance   PRA BO UPSOMBar    E  17 iy AC source   Al ground connections  eoa       50    Installation Drawings    Figure 38 TRX 1 1 parallel cabinet interconnections    1 1 Parallel Cabinet   Front View Without Front Door and Panel        A      EN ES   PI R2     Fl E1 E2  UPS Module Left Side View Type A00 Type BRO Type DR1 8 CR1   Without Side Panel   NOTES     1  All Dual Lite supplied cable will need to be repositioned prior to and while setting the cabinets in their  installed location     All interconnection cable and hardware supplied by others    
33.  sales  representative for a list of approved batteries       NOTE  The TRX  as shipped  has 24 12 volt batteries installed internally in each unit     Safety    Special care should be taken when working with the batteries associated with the TRX system equip   ment  When all batteries are connected together  the battery terminal voltage may exceed 324V and is  POTENTIALLY LETHAL     YN WARNING    The TRX s internal batteries are connected and energized even 1f the UPS is turned Off  To  minimize the risk of injury  a qualified service person should disconnect internal batteries  before any maintenance is performed on the unit    The center of the battery is connected to the neutral of the UPS and is grounded    A battery can present a risk of electrical shock and high short circuit current  The following  precautions should be observed when working on batteries    e Remove watches  rings and other metal objects    e Use tools with insulated handles    e Wear rubber gloves and boots    e Do not lay tools or metal parts on top of batteries    e Disconnect charging source prior to connecting or disconnecting battery terminals     UPS Batteries    The TRX s internal batteries are fully charged before the unit 1s shipped  During storage and trans   portation  some charge is lost  All batteries should be recharged before use  The battery charger  works only when the TRX is connected to input power and turned On       NOTE  Full safety instructions concerning the use and maintenanc
34.  shown for a left access  style  For right access version  these busbars are at opposite locations   Refer to the individual drawing of each piece of equipment for  additional details     Table 17 Interconnect wiring   1 N Type C connection to TRX    Pron  From  TOC Conos  e  Lily AC Source   Paraleing Cabinet   Ground System input    1   Paralling Cabinet   Load AC Connection   PhAB C Load  ramm mmm A    UPS  1 UPS  4 Module    L1 14 Output Breaker Aux Contact  T ad Le aI  UPS Parallel Logic Board  M3  a    UPS  1 UPS  4 Module       M1 M4 Rotary Switch Aux Contact  a ae Li UPS Parallel Logic Board  M3    IOMA EDAD    55    Installation Drawings    Figure 43 Suggested placement   single TRX with auxiliary cabinets                Dual Lite  Battery Battery    Cabinet Cabinet    Dual Lite    Trident    UPS    c  2  pur       Ko   E  ho   m               0                   Front of Units Front of Units Front of Units                      Dual Lite Dual Lite  Trident    UPS    Battery Battery  Cabinet Cabinet    Battery  Cabinet    Slimline Distribution  Slimline Distribution                         Front of Units Front of Units Front of Units    Duak Lite Dual Lite  Trident    UPS    imline Distribution  Slimline Distribution       Front of Units Front of Units Front of Units           Dual Lite         Trident  UPS    Battery  Cabinet    Slimline Distribution          Front of Units    56    Installation Drawings    Figure 44 Suggested placement  multiple TRX units with auxil
35.  sure to connect the battery tray support to the front of the cabinet  before sliding a battery tray out for connection or service  Without the support  the battery tray may  fall out of the cabinet  See Figure 16 for details     22    Battery Installation    Figure 15 Internal cable wiring from battery cabinet to TRX  Power cables from output power switch                  Power cables    from batteries Power cables exit battery    cabinet  enter Dual Lite TRX    Power cables run  across top  of Dual Lite TRX    BATTERY  CABINET    RIGHT SIDE  INTERIOR  OF UPS    Power cables     black  enter RIGHT SIDE CABLE    channel down side ENTRY SHOWN    of TRX to power CUTOUTS ON LEFT   input connections SIDE PERMIT  CONNECTION    LEFT SIDE FROM THAT SIDE     INTERIOR  OF UPS    Battery tray supports attach  to interior surface of TRX  front door  note notched    ends of supports  Me    E       Slot in support secured by     and notched end of support  screw in connector at slips into slot at top corner  corner of battery tray     of battery compartment    23    Battery Installation    3 4 4 Connecting the Battery Cabinet to the UPS    3 5    After the battery cabinet equipment has been positioned and secured for operation and the batteries  have been connected  connect the power cables as described below   See Figure 36      1  Verify that all incoming high and low voltage power circuits are de energized and locked out or  tagged out before installing cables or making any electrical 
36.  warnings   Warning     Warning   UPS has a general alarm   Faut   UPS has a serious fault       64    Operator Control and Display Panel    8 8 LCD Menus and Data Items    The LCD menus provide access to the following categories of information and settings for the UPS   Selecting a menu changes the information displayed in the UPS data items portion of the LCD  The  menu choices are listed below and described in detail in Table 22     Mains   view utility power input data  voltage  current  frequency and power factor  TX Input   view input transformer voltages   Bypass   view bypass data  voltage and frequency   Output   view output data  voltage  current  frequency and power factor   Load   view load data  load percent  output current  output power and crest factor  CF   System   view system data    Battery   view battery characteristics   voltage  current  temperature  remaining time and capac   ity   and messages when the battery is boost float charging or disconnected    Records   access the history log   displays all records in the log  newest records added at end   Language   select a language for LCD text  choices appear in the native language    Settings   configure UPS settings  adjust the display contrast  choose a format for date display   set the date and time  set up the UPS for modem communications  baud rate  address  mode and  phone numbers to dial for alarm notifications  and change the password   Command   start or stop a battery maintenance test  battery c
37. 0  1 480 mca    na   emos  1 240 Ma  1 220 M 1 4   15 208 M4   10 600 may   NA  2204  10 480 may    na   ea  10 240 M  17A   10 220 M 1 4   10 208 M  1 4   62204          94    Specifications and Technical Data    Table 39 Battery cabinet physical characteristics    Battery Cabinet Dimensions Net Weight Without  Type WxDxH in   mm  Batteries  lb   kg     27 2x31 4x63 551   Short Narrow    690x825x1600   250   58 5x31 4x63 889   SMON Wide  1488x825x1600   400     Table 40 Maintenance Bypass Cabinet weights       UPS Maintenance Bypass Cabinet Style  Ib   kg     Rating  A  B  eK tm  oN   P   10kVA 408 545 675 602 732 630 403 540 670 597 128 630   185     247     306     273     332     286     183     245     304     271     330     286   15kVA 408 567 728 659 822 680 403 562 723 655 818 680   185     257     330     299     373     308     183     255     328     297     371     308   DOKVA 408 646 842 139 935 750 403 642 838 134 930 750   185     293     382     335     424     340     183     291     380     333     422     340   30kVA 408 694 893 807 1027 840 403 690 888 802 1023 840   185   315   405   366   466   381   183   313   403   364   464   381   Table 41 Maintenance bypass cabinet dimensions    Unit   win   Depth   Height  mm   090   e25          Table 42 Multi module paralleling cabinet dimensions    1 1 Cabinet Type   With   Depth   Height  Tees oo  BF  OFF  DAT   soo   e25   1600  CTN Cabinet Type   wih   Depth   Height    ies 00     00 00   soo   e25   1600  
38. 5  Figure 46  Figure 47  Figure 48  Figure 49  Figure 50  Figure 51  Figure 52  Figure 53  Figure 54  Figure 55  Figure 56  Figure 57  Figure 58  Figure 59  Figure 60  Figure 61    Narrow battery cabinet  27 in   690mm    rear Vie W            o o    o    o  21  Wide battery cabinet  57 in   1488mm    front view          oo    ee eens 21  Internal cable wiring from battery cabinet to TRX   0    0  ens 23  battery tray and Supports  2254 55 56 da E eee eae sae ewe haw Rakes oe oe 23  Single UPS with external Maintenance Bypass Cabinet   typical configuration              25  Maintenance Bypass Cabinet   access plate removed          0 00 0  cece eee eee ees 26  Maintenance Bypass Cabinet wiring access panel         0    ce ee ees 21  Maintenance bypass control wire locati0D             o           28  Load Bus Synchronization cable connection    30  IFN eyen plock  datar dl ais id ds ainda Dial mere 32  Connecting  1 N  system parallel control cables                 o ooooooooooooooo oo ooo   34  Auxiliary dry contact cables for output breaker in multi module systeM                    35  Dry contacts  multiple UPS modules with distribution panel                  o ooo ooo    35  Connectine HPO push DUO A EAS AE AS MERA ED di da id 36  Battery circuit breaker box connections         eee ee ee nent eee 37  OG Webcard aA pia 433m is alee es ias OD eee ee beac wate aw eee e eae 41  MultiPort 4 card pin assignment      0    ee ee ee eee eee ee ees 43  Dimensional view  front and l
39. 54107 62204  30 75 94 113 125 6M  1 4     54152 62205                                        Bypass input  for dual input units                                                                 Nominal Ps a Lug T amp B  Input OCP One Hole One Hole  Current Current Bolt Size 54000 REDDY  28 om  174   42   s   o  ooe  seios   62204  56  SM  1 4   Output  Output OCP Device Lug T amp B Lug T amp B  Current Current Rating Bolt Size  10 28 35 6M  1 4     54130 62204  15 42 53 6M  1 4     54106 62204  20 56 70 6M  1 4     54106 62204  30 84 105 110 6M  1 4     54108 62205  Battery  OCP Maximum Recommended Lug  Unit Battery OCP Lug T amp B Lug T amp B  Rating Current Current Bolt Size One Hole REDDY  10 15 55 55 70 6M  1 4     54106 62204  20 30 110 110 125   8M  5 16     54153 62212                         Nominal  Nom  current is based on full rated output load   Maximum  Max  current  125  of nominal  is short duration for battery recharge conditions   UPS input and bypass cables must be run in separate conduit from output cables   Nominal battery voltage is shown at 2 0 volts cell per NEC 480 2   OCPD   Overcurrent Protection Device  Recommended AC input and AC output overcurrent protection represents 125  of nominal full  load current  continuous  per NEC 215   Minimum sized grounding conductors to be per NEC 250 122  Parity sized ground conductors are recommended  Neutral conductors to  be sized for full capacity per NEC 310 15  b  4   References are per NEC 2005   7  Wiring requ
40. 7    UPS Status Messages    Table 44 UPS status messages  continued   Event Message Description   Suggested Action  if any     This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass   voltage is beyond the normal range    The amplitude threshold is fixed for positive and negative 10  rating    This alarm automatically resets once the bypass voltage goes normal    1  First verify that the bypass voltage and frequency displayed on the panel is within the selected  range  Note here the rated voltage and frequency are specified by    Output voltage level    and     Output frequency level    respectively    2  If the displayed voltage is believed to be abnormal  then verify the bypass voltage and  frequency presented to the UPS  Check the external supply if it is found to be faulty    Contact the manufacturer at 800 543 2378 for assistance     Bypass Unable to Trace    This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass  voltage exceeds the limit   This alarm automatically resets once the bypass voltage goes normal     First check if there are some relevant alarms such as    Bypass disconnect open        Bypass phase  reverse    and    Mains neutral lost     If they appear  solve them first   1  Then verify that the bypass voltage and frequency displayed on the panel is within the bypass  Bypass Abnormal limit  Note here the rated voltage and frequency are specified by    Output voltage level 
41. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules   Utility AC source neutral not required for maintenance bypass transformer cabinet type CR1   Paralleling cabinets must between both UPS modules     Gs PE e e    Refer to the individual drawing of each piece of equipment for additional details    Table 13 Dual Lite supplied interconnect wiring    Run  From e  Conos  Cabinet Type  6   Vii AC Source   Paraleling Cabinet   Neutral  Bypass   BRO CR1 DR1  1 Vii AO Source   Al Ground Gonnecions   Grond   A00  BRO  CR1  DR1       51    Installation Drawings       Figure 39 Lineup detail    SlimLine distribution cabinet to TRX                                      gt   le el  Le a   ta E E                                                                                                                                                                                                                                                                                 E    MAINTENANCE BYPASS TRANSFORMER CABINET UPS MODULE LEFT SIDE VIEW   FRONT VIEW WITHOUT FRONT DOOR AND PANEL   WITHOUT SIDE PANEL     NOTES   1  All Dual Lite supplied cable will need to be repositioned prior to and while setting the cabinets in their  installed location     All interconnection cables and hardware supplied by Dual Lite   AC connections must be made to the UPS module before attaching   See Figure 43 for placement of distribution cabinet     ee ie    Refer to the ind
42. DUAL LITE    Dual Lite Trident TRX Series    User Manual                a CL f f   ON SSS     HUBBELL  AAA A       Hi  a  F r aa       HUBBELL LIGHTING  INC     MANUFACTURER SUPPORT    For information or repair service in the United States  call 800 543 2378  A complete range of startup ser   vices  repair services  preventive maintenance plans and service contracts are available     Please have the following information available     Tag Number   Site ID    Part Numbers   Serial Numbers   Rating    Date Purchased   Date Installed   Location     TABLE OF CONTENTS    MANUFACTURER SUPPORT 2 iivacudandia rada tiva ad a dani adan arte 2  IMPORTANT SAFETY INSTRUCTIONS     0oocccoc eee ees 1  GLOSSARY  OF SYMBOLS usaste pe iaw eee heen eae Geeta 3  0  INSTALLATION Sanitaria ds ai 4  1 1 External I NSpeetions  ve ars Dd wees koe Bult we ak ae Bok Gale  hea eh Ah ae Beats 4  1 2 is o ienaa sane oO es ROH a Bk ob OS Be ee we 4  1 2 1 Storing tor Delayed Installation s3 6426463442420 500 5 842 0288 PASO ASS A REAPER DOE ES 5  1 3 Preliminary CHeCKS iia is e ie a8 risa 5  Lot   Id LMC  eee AA AS ae ae A A A 5  1 4 UPS LOCA On cdas rra dean 5  Lak Position the UPS  ta e NA A A a n a a bho we 5  t42 Environmental Consideras  dos ias rs EIA a ada 5  1 43 Special Considerations for 1 N Systems            c ce ee eee eee ee 6  1 5 Considerations in Movino  he TRX scassati tet Ew aaa 6  1 6 Mechanical Considerations dor aid VA erases dw odie ARSS WR da a Siac BBR SS 6  LO ci ok earner hene ae
43. Out    Q1Ext Q2Ext j QnExt                QUPS o QByp    To Load    Option Installations    5 3 7 Emergency Power Off  EP O     The external emergency stop facility is identical to that described for the single unit installation     that an individual emergency stop button 1s provided for each unit     Figure 26 Connecting EPO push button    9 4    X2 3  X2 4 Monitor Board                   X2 3  X2 4       Monitor Board    Normally  Open EPO        X2 1    E y5 9 Monitor Board       hs    Normally  Closed EPO    Battery Circuit Breaker Box  The box contains the same battery isolating circuit breaker as mounted in the battery cabinet     Two battery circuit breaker boxes are available for use in installations where the battery is not  installed in the battery cabinet  in which case the appropriate battery box is fitted as close as possible  to the battery and connected to the UPS equipment as illustrated in Figure 27     The battery circuit breaker box  is required to protect the battery from overcurrents  It also provides  electrical isolation between the UPS and the battery  permitting technical service personnel to reduce  the risks involved in maintenance work to a minimum     A separate safety earth must be connected between the UPS unit and circuit breaker box   Two boxes are available depending on the UPS power rating     Table 7 Available battery circuit breaker boxes    Dimensions  in   H W D     Breaker    10 15 kVA 32 25x20 25x8 3  20 30 kVA 32 25x20 25x8 3        
44. TE  Both the rectifier and bypass feeds MUST come from the same utility source  except if the UPS  system includes either a configuration F or P external maintenance bypass cabinet     Output System Connections   Ensure Correct Phase Rotation    10  Connect the system output cables between the UPS output busbars  A B C N terminals  and the  critical load and tighten the connections to 44 lb in   5 N m   M6 bolt      YN WARNING    If the load equipment will not be ready to accept power on the arrival of the commissioning  engineer  then ensure that the system output cables are safely isolated     13    2 2  2 2 1    Electrical Connections    Internal UPS Battery Connections    The UPS internal batteries will be connected at the factory  EXCEPT the Anderson connections  between the shelves and to the fuses     YN WARNING    The DC bus is live when this internal battery connection is made  This connection is to be  performed ONLY by Technical Services at startup     Observe the battery cable polarity  Be sure that the battery connector is made with the cor   rect polarity     11  Refit all protective covers removed for cable installation    Control Cables    Monitor Board Features    Based on your site   s specific needs  the UPS may require auxiliary connections to manage the battery  system  external battery circuit breaker  battery temperature sensor   communicate with a personal  computer or provide alarm signaling to external devices or for Remote Emergency Power Off  REPO 
45. TER ON button  Input Breaker Closed 01 12 12 28 16  a  a ll 11  INVERTER OFF button  12  FAULT CLEAR button  FAULT CLEAR SILENCE ON OFF 13  SILENCE ON OFF button    OOO Ee       Table 19 Control buttons    Button   see Figure 49     EPO Completely shuts down the UPS  including the static switch   CAUTION  Use caution before pressing the Emergency Power Off  EPO  button  This  button completely shuts down the unit and the critical load     INVERTER ON Press this button to start the inverter and transfer from static bypass to inverter   NOTE  If the inverter is not ready  this will not activate the UPS     INVERTER OFF Press this button to shut down the inverter during operation  The load will be transferred  to static bypass    FAULT CLEAR After the UPS shuts down due to a fault and the alarm condition has been resolved  press  this button to clear the fault and restart the UPS     SILENCE ON OFF Press this button once to silence the alarm buzzer when an alarm is active  Any new fault  will sound the buzzer again   If the alarm buzzer is not beeping  press this button to test the alarm sound        8 4 Alarm Buzzer  The alarm buzzer produces three types of sounds       Single beep   when any Control button is pressed     Single beep repeating every two seconds   the system has a general alarm  e Continuous   the system has a serious fault    If the alarm buzzer makes no sound  the system may be operating properly or the alarm may have  been silenced manually     Figure 50 Alar
46. VLRA batteries        88    UPS Specifications    10 4 4 Inverter Output  Table 31 Inverter output    Fate Power MJ Y JO    min  load 1 minute   126 150  load   Voltage Regulation    1 0  three phase RMS average for a balanced three phase load   2 0  three phase RMS average for a 100  unbalanced load   Frequency Regulation   Nominal frequency regulation is  0 05  in single module mode   and    0 25  in parallel mode    Maximum rate of change of For single mode  the slew rate is adjustable from 0 1Hz s to 3Hz s   frequency  Hz sec    Current rating of neutral cable  A 1 5 x input current       10 4 5 Bypass Input  Table 32 Bypass input    Rated Power 10kVA 15kVA 20kVA 30kVA  Rated voltage  VAC 120 208  Supply Three phase  4 wire plus ground    Rated Current  A    Upper limit   10    15  or  20  Upper limit default   15     Bypass voltage tolerance   Lower limit   10    20    30  or  40  Lower limit default   20     Frequency  Hz 50   60  Input frequency tolerance     10 or   20   default  10   Current rating of neutral cable  A 1 5 x input current    Time Load  Bypass overload capacity Long term operation   lt 135  load   all ratings  10 minutes  135    170  load  100milliseconds  1000  full UPS rated output current       89    Specifications and Technical Data    11 0 SPECIFICATIONS AND TECHNICAL DATA    11 1          Lug Size and Torque Requirements   Use commercially available solderless lugs for the wire size required for your application  Refer to  Table 33  Connect wire 
47. acteristics     The ground conductor should be sized according to such factors as the fault rating  cable lengths  and type of protection  The ground cable connecting the UPS to the main ground system must  follow the most direct route possible  Control wiring and power wiring must be run in separate  conduit  Output and input cables must be run in separate conduit     Consider using paralleled smaller cables for heavy currents   this can ease installation     When sizing battery cables  a maximum voltage drop of 4VDC is permissible at the current  ratings in Table 27  For terminal connection sizing  see Table 27    In most installations  especially parallel multi module systems  the load equipment is connected  to a distribution network of individually protected busbars fed by the UPS output  rather than  connected directly to the UPS itself  When this is the case  the UPS output cables can be rated to  suit the individual distribution network demands rather than being fully load rated       NOTE  If more load is added to the distribution panel  the unit   s cabling must be resized     6     When laying power cables  do not form coils  this will help avoid increasing formation of  electromagnetic interference       NOTE  Left side access may be required when making power connections  Cable connections should be    made before a cabinet is attached to the left side of the TRX or before the UPS is placed where  another obstruction  such as a wall  is against the TRX   s the le
48. al position on Maintenance Bypass Cabinet   2  Close the system input circuit breaker    3  Start the UPS as instructed in 9 2   UPS Start Up    4  Close system output circuit breaker     Shutting Down the UPS    Use the following procedure to power down the system     1  Turn the TRX off by following the procedures in 9 4   Powering Down the UPS   2  Open system output circuit breaker   3  Open system input circuit breaker     Transferring System from UPS to Maintenance Bypass Operation    1  Turn the bypass switch  SW  to the bypass position on the Maintenance Bypass Cabinet  The UPS  will switch to bypass mode     The connected equipment is now powered from the bypass source and is NOT protected   2  To isolate the UPS from the system  rotate the bypass switch to the maintenance position     Transfer the System from Maintenance Bypass to UPS Operation    1  Turn the bypass switch  SW  to the Normal position on the Maintenance Bypass Cabinet  The  UPS will go to bypass mode     2  Press the    Inverter On    button on the UPS and allow the UPS to go to normal mode   3  The connected equipment is now powered and protected by the UPS     Transfer the System from UPS Operation to Maintenance Bypass  If the UPS needs to be shut down completely while maintaining power to the load  follow these steps     1  Perform Steps 1 through 5 in 9 3   Switching the UPS from Normal to Maintenance  Bypass   2  Rotate Maintenance Bypass Switch to Maintenance position     3  Post a label on th
49. allel  system may be assumed to be operating normally       NOTE  If one module cannot transfer to inverter mode long after its inverter is on  its output    connection may not be good or its output phase rotation may not be coincident with other  modules  At this time  the LCD for the UPS module will display    inverter asynchronous    and  the inverter indicator will flash continuously  If either UPS module makes abnormal noise  after it transfers to inverter  its parallel cables may be incorrectly connected     9 17 Replacing Dust Filters    l   2     3   4   5     Figure 61    Open the UPS door     The dust filters are behind the door  For each filter  there is a bracket on either side holding the  dust filter in place  as shown in Figure 61     Remove one bracket and loosen the other  The second bracket need not be removed   Remove the old filter and replace with the new filter  Reinstall the bracket that was removed and tighten the other bracket     Dust filter replacement        Bracket    Sems screw   Bracket       85    UPS Specifications    10 0 UPS SPECIFICATIONS    These specifications describe requirements for the Dual Lite TRX UPS     10 1 Conformity and Standards  The UPS has been designed to conform to the following standards     e  EEC1000 4 5    gt  ASME   e CSA 22 2  No  107 1   e FCC Part 15  Class A   e ISO 9001   e National Electrical Code  NFPA 70   e NEMA PE 1     OSHA   e UL Standard 1778    The UPS system has UL and c UL approval     10 2 UPS Environ
50. apacity test or system test  Version   view firmware versions for the inverter  rectifier and software display board and the  model information for the UPS    Figure 52 shows a menu tree of the options available from the LCD menus     Figure 52 Menu tree    Mains  input  TX Input   TX Output       L N voltage  V  L N voltage  V  L N voltage  V  L N voltage  V  L N voltage  V   L N current  A  L L voltage  V  Frequency  Hz  L N current  A  L L voltage  V     Frequency  Hz  L L voltage  V  Frequency  Hz   L L voltage  V  L L voltage  V   Power factor Power factor       Records  Sout  kVA  Sout  kVA  Battery voltage  V   history log   Pout  kW  Pout  kW  Battery current  A         Qout  kVAR  Qout  kVAR  Battery temperature    C   Loadlevel   Single unit  no Remain Time Min   Crest factor parallel data Battery capacity           Battery boost charging  Battery float charging  Battery disconnected    Command Version     Choices for Display contrast Battery maintenance test UPS version  display  Date format set Battery capacity test UPS model    Date  amp  time System test   Comm1 baud rate Stop testing   Comm2 baud rate Freshening Charge   Comms baud rate Stop Freshening Charge  Communication address Modem Auto answer enable  Communication mode       Callback times  Phone No 1  Phone No 2  Phone No 3      When configured  input transformer voltages are  displayed on the front LCD  When not activated   the values are hidden       When configured  output transformer voltages  are d
51. ass voltage  returns to normal before the user makes confirmation  the UPS will transfer to inverter mode auto   matically  At the same time  the prompt window will close        From Inverter to Bypass Mode With Interruption    If the bypass voltage or frequency exceeds the synchronized range and  the UPS is in inverter mode  the system must let the user to confirm This operation leads to  and accept the power interruption danger before pressing the output shutdown  INVERTER OFF button to shut down the output of the inverter  The Confirm or cancel  user can also cancel the shutdown operation  as shown at right  If the  bypass voltage returns to normal before the user makes the confirma   tion  the UPS will transfer to bypass operation mode automatically  and at the same time the prompt  window will disappear soon        System Self Test    When a system self test 1s completed  a pop up window reports the  results of the test  as shown at right  System Self Test finished     Press the F4  Enter  key and the pop up window closes  OS    Battery Capacity Test Confirmation    When a battery capacity test 1s started from the Command menu  the  battery will be discharged to low battery warning level  The TRX asks Battery will be depleted   for confirmation before the test 1s started  as shown at right  Confirm or cancel         To confirm the choice and begin the battery capacity test  press the  F4  Enter  key and the pop up window disappears       To cancel the test  press the F1 
52. be started     Start Up Procedure  To start the UPS from a fully powered down condition     1  Open the UPS door to gain access to the main power switches     YN WARNING    During this procedure the output terminals will become live     If any load equipment is connected to the UPS output terminals  please check with the load  user and ascertain whether it is safe to apply power to the load  If the load is not ready to  receive power  then ensure that it 1s safely isolated from the UPS output terminals     YN CAUTION    Do not operate the rotary switch too fast  Always wait at least three seconds when rotating  the switch from one position to another     2  Turn the rotary switch to TEST   3  Close CB1   The bypass contactor  M2  closes automatically and the LCD begins to show start up screens     The Rectifier indicator flashes green while the rectifier is starting up  It stops flashing and  becomes solid green about 30 seconds after the rectifier enters the normal operation state     After initialization  the bypass static switch closes   Because output switch SW1 A is still open  the UPS  channels power through Maintenance Bypass Supply    line  SW1 D   The bypass indicator extinguishes  pro  g j  vided that the bypass is normal     The opening display is shown in the figure at right   The UPS Mimic display indicators will be     Rectifier indicator  Battery indicator  Bypass indicator       DUALE        Inverter indicator Off      A WARNING    Do NOT turn the rotary switc
53. bles    Parallel System Control Cables    Make the connections listed below on the parallel logic board  M3  inside the TRX   See Figure 32 for  the location of the parallel logic board      Shielded and double insulated control cables available in lengths of up to 100 feet  30m  must be  interconnected in a ring configuration between UPS modules as shown below  The ring configuration  ensures high reliability of the control  refer to Figure 23      See Figure 25 for dry contacts control cable wiring diagram     Figure 23 Connecting  1 N  system parallel control cables    o D  S    4         Parallel Board Parallel Board    X4  X2 2 X2 1                Interconnecting  Cables                                                    N  A                                                        Auxiliary Dry Contact Cables    The external output breaker of each UPS must have Normally Open auxiliary contacts  These con   tacts must be wired to connector X3 on the Parallel Logic Board  M3   See Figure 24     34    Option Installations    Figure 24 Auxiliary dry contact cables for output breaker in multi module system       CAUTION    The auxiliary control wire must be installed to ensure proper operation of the system        NOTE  For startup procedure  refer to 9 0   Operating Instructions     Figure 25 Dry contacts  multiple UPS modules with distribution panel    Input Distribution    UPS N  M3 Board M3 Board M3 Board  X3 X3 X3  Ext  Maint  Ext Out Ext  Maint  Ext  Out Ext  Maint  Ext 
54. bypass transformer cabinets  MBC T  are available  These cabinets house the  components necessary to     e Provide an external wrap around maintenance bypass switch for servicing the UPS  e Provide voltage transformation for site or application requirements  e Provide a means for neutral isolation and allow installations for site without a neutral conductor    MBC T cabinets are designed to be bolted to the left side of the UPS  see Figure 1   Refer to 4 5    Locating the Cabinet  for further details     System Composition    A UPS system can comprise a number of equipment cabinets  depending on the individual system  design requirements   e g   UPS cabinet and External Bypass cabinet  In general  all cabinets used  will be the same height and are designed to be positioned side by side to form an aesthetically appeal   ing equipment suite     Installation    1 6 4 Optional Cabinets  If your TRX installation includes a Maintenance Bypass Cabinet  the TRX must be positioned to allow  the Maintenance Bypass Cabinet to be bolted to left side of the TRX  see Figure 1   Cables from the  Maintenance Bypass Cabinet must be brought through the bottom side of the TRX for connection     The Maintenance Bypass Cabinet must be cabled and bolted to the TRX before the UPS and bypass   cabinet are moved into their final position  Connect the input wiring to the Maintenance Bypass Cab   inet ONLY after the units are connected and positioned    Battery cabinets may be bolted to either side of 
55. ce bypass control wire location    Lt   Lo   pe ES    i de    LM WIX   v    Terminal Block Location    Ne    KERERE lah       NOTE  For startup procedure  refer to 9 0   Operating Instructions     28    Maintenance Bypass Cabinet    4 7 Bolting Cabinets Together        NOTE  UPS wiring must be completed before the cabinets are bolted together     1  Line up cabinets so that mounting holes are aligned        peta C  SCALE 1 2         LD  DETAIL A  SCALE 1 2           pera D  SCALE 1 2      peta B  SCALE 1 2    see DETAIL B  Place cabinets so mounting holes are  aligned    A bolt from the adjacent cabinet may be  screwed into the threaded top hole  or a  bolt may be inserted through the lower  hole and screwed into the threaded hole  in the adjacent cabinet     2  Using supplied hardware  bolt the cabinets together  The bolts may be inserted from either the  UPS side or from the MBS side  whichever is more convenient     29    9 0    9 1    9 1 1    Option Installations    OPTION INSTALLATIONS    Load Bus Synchronization    The Load Bus Synchronizer  LBS  keeps the output of two independent UPS systems or parallel UPS  systems in synchronization even when the systems are operating in different modes and even when  either or both systems are operating on batteries  When the LBS is used  one UPS system is desig   nated as master  the other as slave     The LBS option is typically used with dual corded equipment or with either the Dual Lite Smart   Switch or Static Transfer Switch
56. chanical Considerations    The TRX is constructed with a steel frame and removable panels  Top and side panels are secured to  the chassis by screws  The doors may be opened for access to power connections bars  auxiliary termi   nals blocks and power switches     The UPS comes with an operator control panel  which provides basic operational status and alarm  information  The cabinet houses both the power components and the internal batteries  Cooling is  provided by internal fans  The unit sits on four casters  Adjustable stops are provided to prevent the  UPS from moving once it has been moved to its final position     1 6 1    1 6 2    1 6 3    Installation    Clearances    There are no ventilation grilles on the sides or rear of the UPS  The sides must be accessible during  installation  After installation  the unit may be placed with the rear against a wall and optional cabi   nets on either side     To enable routine tightening of power terminations within the UPS  make sure there 1s sufficient  clearance in front of the TRX to permit free passage of personnel with the door fully opened     Leave a minimum of 2 ft   610mm  between the top of the UPS and the ceiling to permit adequate air  circulation above the unit  Dual Lite recommends against using air conditioning or other systems  that blow air onto the top of the unit     Floor Installation    The diagrams in 6 0   Installation Drawings show the location of holes in the base plate for bolting  the equipment to the 
57. connections     2  Remove the UPS left side panel to gain access to the equipment ground busbar     3  Remove the external battery terminal block plate on the lower left side of the UPS behind the  front door     4  Remove the battery cabinet front panel to gain access to the connection bars     5  Connect the safety ground and any necessary bonding ground cables to the copper ground busbar    example  UPS located on the bottom of the equipment below the power connections      All cabinets in the UPS system must be connected to the user s ground connection       NOTE  The grounding and neutral bonding arrangement must be in accordance with the National  Electrical Code and all applicable local codes     6  Connect the system battery cables from the UPS battery terminals    N    to battery cabinet BCB     N    as shown in Figure 36  Be sure that the battery connections are made with the right  polarity  and tighten the connections to 44 lb in   6 N m   M6 Bolt   Do not close the battery circuit  breaker before the equipment has been commissioned     7  Connect supplied auxiliary control cable to pins J10 2 and J10 3 on the U2 monitoring board  see  2 3   Dry Contacts   Add a jumper wire between J10 3 and J10 4     Non Standard Batteries    When batteries other than a matching battery cabinet are used  a remote battery disconnect switch  with overcurrent protection 1s required per the National Electrical Code  Contact your local Dual Lite  sales representative about this option
58. dule in a Multi Module SysteM                     80  9 11 Inserting One Module into a Multi Module SysteM             o ooooooo cece een 81  9 12 Shutting Down a Multi Module System Without System Bypass Switch                82  9 13 Shutting Down a Multi Module System With System Bypass Switch                   82  9 14 Commissioning a Parallel SysteM            o                  83  9 15 Maintenance Bypass Cabinet Operating Procedures            o oooooooo momo   o   83  das  Start Uo amd  mittal zation  aa hee a e ci 83  9 152 asnuttine Down the UPS acia SAA AD AA A 83  9 15 3 Transferring System from UPS to Maintenance Bypass Operation                      83  9 15 4 Transfer the System from Maintenance Bypass to UPS Operation                      83  9 15 5 Transfer the System from UPS Operation to Maintenance Bypass                      83  916 Parallel system Start Ub  cid A A a Es de 85  91r   Replacine mst ter sara as a DA ee ieee 85  10 0 UPS SPECIFICATIONS  2 5 dadasa mr ia daa e das da 86  10 1  Conformity and Standards  usa e aa pra EAA OA li vd bee a 86  10 2 UPS Payvtrtonmentals cra daa sai aaa 86  10 3 UPS Mechanical Characteristics  isis AS AAA 86  104   U BS  Bl  ectrcal Characteristics  traia a Sak be eee A A oie eee a 87  10 4 1 Battery Manufacturers and Models             o             88  OA 2 o AI 88  LO  3  DE Intermediate Lic SO O A a aA 88  IOA Inverter OU PUT e casitas ad rada bd a ds we Res wre eee 89  LUNAS    By pass  Ut os toa a a dei EA a 89
59. e UPS is shut down but the load is connected to utility power via the   On Maintenance Maintenance Bypass Supply line    Bypass NOTE  The load is not protected against disturbances in AC input power in this  mode     No load power is supplied by the UPS  The load is connected to utility power  via the Maintenance Bypass Supply line    NOTE  The load is not protected against disturbances in AC input power in this  mode     On Test    On Static BYPASS The load power is supplied through the static bypass line  This may be  Bypass or considered as a temporary mode during load transfers between inverter and  yp NORMAL maintenance bypass or supply under abnormal operating conditions        NOTE   1  The user controls and indicators mentioned in these procedures are identified in 8 0    Operator Control and Display Panel    2  The audible alarm may sound at various points during these procedures  It can be canceled  at any time by pressing the SILENCE ON OFF push button        NOTE   This unit refers to some modes and conditions that are set or adjusted using proprietary service  software  To take advantage of all the available features for the TRX  the unit must be  commissioned by a factory trained service engineer        73    9 1 1    Operating Instructions    Power Switches    The UPS can be isolated by means of power switches  mounted inside the cabinet and accessible after  opening the front door     The location of the UPS power switches is shown in Figure 58     Figure 58 P
60. e of UPS batteries are provided in  the appropriate battery manufacturer s manuals  available on the manufacturer s Web site     The battery safety information contained in this section relates to key considerations that must  be taken into account during the installation design process and might affect the design  outcome  depending on your installation     19    3 4  3 4 1    3 4 2    Battery Installation    External Battery Cabinet Installation    Matching Battery Cabinets    Two sizes of optional battery cabinets are available  Refer to Figures 13 and 14  The same model bat   tery cabinet may be installed in parallel in multiple cabinet strings for additional capacity  Battery  run time depends on the cabinet model  the number of cabinets and the load on the UPS     Handling   The battery cabinet has casters to facilitate movement over short distances  The bottoms  of the battery cabinets are reinforced to permit movement by forklift over longer distances     Inspection   Remove all panels and visually inspect the batteries  bus connections  and cabinet for  any damage  Exercise caution  voltage is present within the battery cabinet even before installation   If there are signs of damage  do not proceed  Call Technical Services at 1 800 542 2378     Storage   The batteries can be stored for up to six months without appreciable deterioration  If plan   ning to store a battery cabinet for longer than six months or at temperatures higher than 77  F  25  C    contact Technica
61. e primary input distribution panel  which often is installed outside the UPS  area  advising personnel that the UPS circuit is under maintenance     The UPS is now completely powered down     YN WARNING    Wait 5 minutes for the internal DC busbar capacitors to discharge       NOTE  The Maintenance Bypass power switch may be operated at any time while the UPS is powered  down to connect the load to the maintenance bypass supply     83    Operating Instructions    The procedure can be performed only after the installation has been completed  which includes the  maintenance bypass cabinet   after the system has been placed in operation by authorized personnel  and after the external power switches have been closed  See Figure 60 for more information     Figure 60 Single UPS with external Maintenance Bypass Cabinet   typical configuration  Input Supply    ABC  N    mer tale      sys in CB1        QinfUPS          Input Mains  Supply AB C       Static  Switch    ES o  e e  e e e es re  a    Ext    UJ   lt   Lo        Qout UPS  Sys Out CB2    A       To Load    84    Operating Instructions    9 16 Parallel System Start Up    1   2   3     4     Start each UPS normally as described in 9 2   UPS Start Up   Turn on the inverter of each UPS module one at a time    Apply the load after the last UPS module transfers to inverter  The total load can be determined  through the LCD of either UPS    Verify the load rate of each UPS module  If the load rates are roughly the same  then the par
62. e safety ground cable must be connected to the ground busbar and bonded to each  cabinet in the system     All cabinets and cable conduit should be grounded in accordance with local regulations     YN WARNING    Failure to follow proper grounding procedures can result in electric shock hazard to personnel  or the risk of fire  should a ground fault occur         NOTE  Proper grounding significantly reduces problems in systems caused by electromagnetic  interference     NOTE   Q The ground and neutral busbars are easily accessible when the left protective cover plate is  removed  Cable connections should be made before a cabinet is attached to the left side of the  TRX or before the UPS is placed where another obstruction  such as a wall  is against the  TRX   s the left side     Figure 5 Ground and neutral busbar connections    Output neutral    busbar  A wy wy CITO TO  NEUTRAL NEUTRAL busbar  Ground  busbar    ODO O       2 1 6 Protective Devices    For safety  it is necessary to install circuit breakers in the input AC supply and external battery bat   tery cabinets  external to the UPS system  Given that every installation has its own characteristics   this section provides guidelines for qualified installation engineers with knowledge of operating prac   tices  regulatory standards and the equipment to be installed     UPS Rectifier and Bypass Input Supply   e Protection from excessive overcurrents and short circuits in power supply input  External overcurrent protection 
63. ed       Extract screws  from corners to  remove the  access plate    Bypass Mode    When the Maintenance Bypass Cabinet is in the Bypass mode  it provides an alternate path for power  to the connected equipment  Should the UPS need to be taken out of service for limited maintenance  or repair  manual activation of the bypass will cause an immediate transfer of the equipment from the  UPS inverter to the bypass source  In this mode  power will still be supplied to the UPS  however  the  load is NOT protected by the UPS     Maintenance Mode    When the maintenance bypass cabinet is in the Maintenance mode  it provides an alternate path for  power to the connected equipment  Should the UPS need to be taken out of service for limited mainte   nance or repair  In this mode of operation  no power is supplied to the UPS and the load is NOT pro   tected by the UPS     Locating the Cabinet    This Maintenance Bypass Cabinet may be mounted to the left of the UPS or installed as a stand alone  unit  In either case  ensure that the unit is in a well ventilated area and that there is clearance for  access to the switches and cable connections as required by national and local codes     Cable Installation    Wiring Preparation    Be sure that the unit is not connected to any AC utility power source or UPS before installing any wir   ing to this unit  This Maintenance Bypass Cabinet should be installed by a qualified   certified electri   clan     WARNING    Please read this section thorou
64. eft side views     0 0    en ee nee eens 44  Dimensions continued   top and bottom VIEWS       0    ee ee ee eee 45  Main components   typical unto 45  Cable conte OMS  a ds ve as thatch ahs di rito rv Ea to Sik  s Sek 46  Edcati  on o tinternal Datteries siii rara as A Goa se Eee 47  Battery connections   aa a a aed oe eee dad ls eee 48  Battery cabinet interconnection       0 0    0c ee ee ee ee ee eee eee eee nee 49  Maintenance Bypass interconnection      0 0    0  0c ee ee eee ee ee eens 50  TRX 1 1 parallel cabinet interconnections      0    0 0  0c ee eee ee eens 51  Lineup detail    SlimLine distribution cabinet to TRX            ooooooooooo oo ooomo ooo    52  Lineup detail   1 N Type A connection to TRX        0    ooo    o    os 53  Lineup detail   1 N Type B1 connection to TRX       0 0 0    ce eee 54  Lineup detail   1 N Type C connection to TRX        0    0  eee 55  Suggested placement   single TRX with auxiliary CablnetS              ooooo ooo    eee 56  Suggested placement  multiple TRX units with auxiliary cabinets                         57  Single module block diagram  dual input configuration          0 0 0 000000 cee eee ee eee 58  Overview Of control panel        rar ohn Oe da ed awe eee wad A aw ba he Sd ee 60  Detailed view OL control panel  sa hoes E A AS et eee eva E 60  Mimic display indicators location              ee eee eee eee eens 61  Location ol control DULLONS acm eee ao hn eat Seanad Bel eeu RAs ee Oa eee a 62  Alara puzzo r local OMe tid a
65. ellislot 3 Relaycard int  Bottom IntelliSlot  On Monitor Board  Comm 3 DE WEBS ae  Modbus Jbus   2400    MultiLink Not simultaneous with Web  Top DB9 port RS232 1 Serial 9600   card in top IntelliSlot   Service Not simultaneous with Web  Bottom DB9 port RS232 2 Comm 2 Software 9600   card in middle IntelliSlot    Reserved        39    Option Installations    5 10 1 Configuring Baud Rates    The default baud rate for IntelliSlots is 9600  To communicate with the OCWEB LB  Modbus Jbus  or  the MultiLink cards  the baud rate must be set to 2400     To change the baud rate  refer to Table 8      l   Ze  3     4   5   6     Use the Navigation keys directly below the LCD to highlight the Settings Screen   Press F1 to move the highlight into the Data  amp  Settings area of the LCD     Use the Navigation keys to scroll down to highlight the current baud rate across from the  appropriate Comm Channel     NOTE    The Comm channel settings are not immediately visible because of window size constraints   Scroll down to view them on the screen     Press the Enter  F4  key to select the Comm Channel to change   Navigate to underline the desired baud rate  2400    Press the Enter  F4  key to lock in the new baud rate     40    Option Installations    Figure 28 OC Web card display    EL Liebert OpenComms Web Card   Microsoft Internet Explorer provided by Liebert Corporation            monitor configure support    Summary  Updated  September 21  2004 01 22 21PM     Legend Y       Device Infor
66. en    Press the HELP key below the LCD to display the Help window shown in Figure 56   Press the  HELP key again to exit the Help window      Figure 56 Help screen    Help information    Select the current record window     lt   Select the previous menu item    Q3  Q2    Press help key back to main menu    a        8 12 4 Screen Saver Window    If there has been no interaction with the TRX   s LCD for 2 minutes  the screen saver window appears   It remains on the LCD for 2 minutes  then the screen will go dark  The LCD will become active again  when any key 1s pressed     Figure 57 Screen saver window    DuakLite TRX 2006 01 22  30kKVA 3X3 Sinql    Press any key back to main menu       71    8 13    8 13 1    8 13 2    8 13 3    8 13 4    8 13 5    8 13 6    Operator Control and Display Panel    Pop Up Windows    Pop up prompt windows appear when the user must confirm a choice or perform an operation  This  section describes the pop up windows     From Bypass to Inverter Mode With Power Interruption    If the bypass voltage or frequency exceeds the synchronized range and  utility voltage or frequency is normal  the inverter cannot be in syn  Transfer with Interrupt   chronization with the bypass  and the output can only transfer to please confirm or cancel  inverter after an interruption of about 15ms when the user presses the  INVERTER ON button  Before transferring  the system will let the  user confirm whether the interruption can be accepted  as shown at right  If the byp
67. ents and    alarms    The main areas of the control panel are shown below in Figure 46 and detailed in Figure 47     e Mimic Display   view the status of the TRX in single line diagram format   1ndicators show sta   tus by changing color when ON  flashing or OFF    Liquid Crystal Display  LCD  and Navigation keys   view status and operational data from    the TRX in tabular format    e Control buttons   turn the TRX on or off  silence alarms    Figure 46 Overview of control panel    Mimic display  o pe    8 1 1    Figure 47 Detailed view of control panel    Liquid Crystal  Display  LCD     Navigation keys    IH    Display Panel Layout          Dual Lite TRX  30KVA 3X3    2009 01 22  U    B BC        Vphase V 120   Iphase A y 20 5   Freq  Hz y 50 1   Vline V 208 Control  P F  E 0 99 INVERTER ON INVERTER OFF buttons    Input Breaker Closed  Manual Turn On 01 12 12 30 06  UPS in Normal Mode 01 22 12 30 16     TES O O  FAULT CLEAR SILENCE ON OFF    01 12 12 28 16 4          Figure 47 shows the control panel in greater detail  identifying individual items that are described in  the rest of this section     2  1       34 6 7    AA  ye       Vphase V   0  Iphase A   Freq  Hz   Vline V    Dual Lite TRX  30KVA 3X3       PAR    Input Breaker Closed  Manual Turn On  UPS in Normal Mode       Y          2009 01 22  U    B BC  C CA   120 120  20 5 20 5  50 1 50 1  208 208  0 99 0 99 0 99  01 12 12 28 16 4  01 12 12 30 06  01 22 12 30 16         13    INVERTER ON INVERTER OFF    FAULT CLEAR
68. er  which regenerates precise AC power to supply the connected  equipment  The rectifier also uses the utility source power to charge the batteries     Battery Mode    When utility AC power fails  the TRX protects the critical load by instantaneously channeling battery  power to the inverter which continues supporting the critical load without interruption  When utility  power returns and is within acceptable limits  the TRX automatically shifts back to Normal mode   with the rectifier powering the critical load     Bypass Mode    When the TRX is in bypass mode  the load is directly supported by utility power and is without bat   tery backup protection     The TRX s static transfer switch will shift the load from the inverter to bypass mode without an inter   ruption in AC power if the inverter is synchronous with the bypass and any of the following occurs       inverter fails    inverter overload capacity is exceeded    inverter is manually turned off by user    NOTE   Q If the inverter is asynchronous with the bypass  the static switch will transfer the load from the  inverter to the bypass WITH interruption in AC power to the critical load  This interruption  will be less than 15ms  in 50Hz   or less than 13 33ms  in 60Hz   This interruption time may be  altered by modifying the Output transfer interrupt time setting     Maintenance Mode    For maintenance or repair  the TRX may be operated in maintenance mode  To place the TRX in  maintenance mode  the load must be transf
69. er CB1  The Rectifier indicator flashes on the UPS mimic panel during the startup of the rectifier and  becomes steady green once the rectifier reaches normal operation state after about 30s    4  Close external battery circuit breaker QF1  where an external battery is used   This breaker is  inside the battery cabinet  if used  or is otherwise adjacent to the battery racks    5  After the UPS detects the batteries  the red battery indicator extinguishes when the battery  charger starts operation    6  Rotate switch to Bypass position   7  Turn the rotary switch to NORMAL  then press the INVERTER ON control button for 2 seconds   The inverter will start up and the inverter indicator flashes while it synchronizes to the load volt   age and frequency  After the inverter is ready  the UPS connects to the load  the inverter indicator  becomes steady green and the output indicator turns green    8  Check that no    Warning    message is displayed in the top right corner of the LCD Monitor and  that the indicators have the status shown below      LED   LED Function Status    Rectifier indicator  Battery indicator    6  Aermindicar  on        The UPS is now operating in NORMAL mode        81    Operating Instructions    9 12 Shutting Down a Multi Module System Without System Bypass Switch        NOTE  Before beginning this procedure  shut down the connected load to prevent the possibility of    4     5        damage  This procedure will shut off power to the load     Open the UPS do
70. er Flashing Green  Utility normal    Rectifier fault Rectifier is normal  but utility is  1  Rectifier A l  but rectifier not operating abnormal    Battery powering Flashing Green  Battery pre  Battery or battery Battery and converter are  2  Battery the load warning  low battery  converter abnormal    normal  and battery is not  discharging    Load on Bypass Bypass out of Bypass Normal  4   Inverter powering Flashing Green  Inverter on Inverter fault Inverter normal  but off    Inverter  the load normally standby  UPS output on UPS output UPS no output power  atoa e ruses SOOP  No alarms   UPS Amber  UPS has a general UPS has a serious  working normally alarm alarm      Battery or battery converter abnormal events include these event messages  see Table 44 in Appendix A   No Battery  Battery Replaced   Battery Reverse  Batt  Conv  Over  Curr   Batt  Converter Fault  Batt  Converter Overtemp        61    Operator Control and Display Panel    8 3 Control Buttons    The Control Buttons on the front panel may be used to shut down the UPS completely  turn the  inverter on or off  restart the UPS after a fault and silence the alarm  as shown in Figure 49  The  function of each button is described in Table 19         NOTE  To activate a button properly  press and hold until you hear a short beep   about two seconds     Figure 49 Location of control buttons       8  9  pee even 2009 01 22 4 0  A 8  Button cover  Fot E 12 9  EPO button  P F    0 99   INVERTERON INVERTER OFF 10  INVER
71. er and stop powering the load immediately  including the  inverter and bypass   and the battery stops charging or discharging     If the input utility 1s present  the UPS s controls will remain active  however  the output will be  turned off  To remove all power from the UPS  the external feeder breaker should be opened     Auto Restart    When the main and bypass sources fail  the UPS draws power from the battery system to supply the  load until the batteries are depleted  When the UPS reaches its end of discharge  EOD  threshold  1t  will shut down     The UPS will automatically restart and enable output power       after utility power is restored    if    Auto Recovery after EOD Enabling    is enabled    after the    Auto Recovery after EOD Delay Time    expires  the default delay is 10 minutes     During the auto recovery delay  the TRX will be charging its batteries to provide a safety margin  for equipment shutdown if input power fails again     If the    Auto Recovery after EOD Enabling    feature is disabled  the user must restart the system man   ually     Reset After Shutdown for Emergency Stop  EPO Action  or Other Conditions    Once all appropriate measures have been taken to correct the problem indicated by the alarm mes   sage appearing on the operator control panel display  carry out this procedure to restore the UPS to  regular operation following an EPO action or for the following reasons  Inverter Overtemperature   Cut off Overload  Battery Overvoltage  exce
72. erred to bypass and the inverter must be turned off  When  those conditions are met  the rotary switch may be turned to MAINT and the UPS may be shut down   permitting disconnecting the batteries for maintenance     YN CAUTION    The internal maintenance bypass must not be used when the UPS system is in 1 N parallel     YN WARNING    The UPS input and output must be protected with external overcurrent protection devices  In  maintenance mode  the input and output busbars remain energized     Parallel Redundancy Mode  System Expansion     For higher capacity  higher reliability or both  the outputs of up to four UPS modules can be pro   grammed for directly paralleling while a built in parallel controller in each UPS ensures automatic  load sharing     Frequency Converter Mode    The Dual Lite TRX can be programmed into frequency converter mode for either 50Hz or 60Hz stable  output frequency  The input frequency may vary from 40Hz to 70Hz  In this mode  the static bypass  operation is disabled and the battery becomes optional  depending on any requirement to operate in  battery mode  stored energy mode      59    8 0  8 1    Operator Control and Display Panel    OPERATOR CONTROL AND DISPLAY PANEL    Operator Control Panel  The control panel and LCD on the front of the Dual Lite TRX lets the operator     turn the UPS on or off    transfer into the various operating modes    e silence alarms  e check the status of the UPS and its batteries  including all measured parameters  ev
73. ervoltage Pre Warning   Before the end of discharge  the TRX displays a battery undervoltage pre warning  After this pre   warning  the battery has the capacity for 5 minutes discharging with full load  default time   The TRX  can be user configured to display this warning from 3 to 60 minutes before end of discharge    Battery End of Discharge  EOD  Protection   If the battery voltage is lower than the end of discharge voltage  the battery converter will be shut  down    Battery Fuse Blow Warning    Battery current protection is provided by the battery fuses FU7 and FU8  If a battery fuse blows  the  TRX displays the battery fuse blow warning and the battery converter will be shut down         NOTE  All equipment servicing procedures must be carried out only by trained personnel     Isolating and Integrating One Module in a Multi Module System  1  Turn Off inverter  2  Open External Output CB1    The UPS enters Isolation Status automatically  parallel signaling and communication becomes  masked  and output becomes inhabited     3  Power Off unit for maintenance   4  Power On unit with External Output CB1 open   5  Unit enters Test Mode by configuration software setting   6  Diagnosis or testing   7  The UPS exits Test Mode by configuration software setting   Output becomes inhibited because of Isolation Status   8  Return all switches to the Normal position  including External Output Circuit Breaker 1   9  Close External Output Circuit Breaker 1     The UPS exits Isolation S
74. extreme care when handling UPS cabinets to avoid equipment damage or injury to  personnel  The UPS module weight ranges from 850 to 1400 lb   886 to 635kg      Determine unit weight and locate center of gravity symbols 4   before handling the UPS  Test lift and balance the cabinet  before transporting  Never tilt equipment more than 15 degrees from vertical     Battery manufacturers supply details of the necessary precautions to be observed when  working on  or in the vicinity of  a large bank of battery cells  These precautions should be  followed implicitly at all times     Follow all battery safety precautions when installing  charging or servicing batteries  In  addition to the hazard of electric shock  gas produced by batteries can be explosive and  sulfuric acid can cause severe burns  When connected  the nominal battery voltage is 288VDC  and is potentially lethal     In case of fire involving electrical equipment  use only carbon dioxide fire extinguishers or  those approved for use in fighting electrical fires     Extreme caution is required when performing maintenance   Be constantly aware that the UPS system contains high DC as well as AC voltages   Check for voltage with both AC and DC voltmeters prior to making contact     WARNING    As with other types of high power equipment  dangerous voltages are present within the UPS  and battery enclosure  The risk of contact with these voltages is minimized as the live  component parts are housed behind a hinged  lockable
75. f the LCD    Use F2 and F3  up and down  to select the  Date  amp  Time option  then press F4  enter    Position the cursor on the row in which the  date and time are displayed  then press   F4  enter     Using the F2 and F3  up and down  keys   enter the current time and date information   Press F4  enter  to save the settings  then  press F1  ESC  to return to the main menu     66       DuaFLite TRX  30kKVA 3X3    KI  Records   Language     Display contrast   Date format set M D Y  D M Y M D Y Y M D   Date  amp  time  01 22 2004    2009 01 22  Single    12 30 36  Normal          12 30 36    10 32    Manual turn on 01 22 10 32  Normal mode 01 22 11 05    Fault reset 01 22    Operator Control and Display Panel    Table 22 Descriptions of UPS menus and data window items    Menu Type Item Type Explanation             L N voltage  V  Phase voltage  L N current  A  Phase current  Mains   input  Frequency  Hz  Input frequency  L L voltage  v Line line voltage       L N voltage  V  Phase voltage  TX Input                               L L voltage  V  Line line voltage  L N voltage  V  Phase voltage  Bypass Bypass frequency  L L voltage  A  Line line voltage  L N voltage  V  Phase voltage  Phase current  Frequency  Hz  Output frequency  L L voltage  V  Line line voltage       L N voltage  V  Phase voltage  TX Output          L L      V  Line line voltage    Sout  Apparent power  Pout  Active power  Load Qout an Qout  Reactive power  The percent of the UPS rating load  Output current
76. floor  An optional anchoring kit is available  For information  see your local sales  representative     If the equipment is to be placed on a raised floor  it should be mounted on a pedestal that will support  the equipment point loading  Refer to the bottom view in Figure 30 to design this pedestal     Cable Entry    Cables can enter the TRX from the top or bottom  Cable entry is made possible by removing a metal  plate attached to the UPS     These plates are designed to allow the personnel to punch holes for fitting and securing the conduit   Once the conduit holes are punched  these plates should be reattached to the UPS     Connecting cables to the TRX may require that the UPS be accessible from the left side to allow per   sonnel to complete the connections and make necessary adjustments  After installation is complete   the TRX may be serviced from the front     NOTE    When installing the UPS  the customer must provide a disconnect with overcurrent protection  at the output of the UPS     10 30kVA UPS    The 10 30kVA TRX consists of a single cabinet housing the UPS components and the internal battery  string     Optional battery cabinets are available to provide extended run time  Each cabinet houses additional  strings of batteries that operate in parallel with the TRX   s internal batteries  The cabinets are  designed to be bolted to the right side of the UPS  see Figure 1   Refer to 3 4   External Battery  Cabinet Installation for details     Optional maintenance 
77. for the AC output circuit is to be provided  See 10 4   UPS Elec   trical Characteristics and Table 29 for overload capacity   High speed fuses and SCRs are used for internal battery circuit overcurrent protection  When an  external battery supply is used  overcurrent protection for the battery circuit 1s to be provided by  the customer    e Dual Input  When wiring the UPS with dual inputs  the Rectifier input and the Bypass input must be pro   tected separately  Size the breakers according to the input currents shown in Table 27     System Output    When using an external distribution panel for load distribution  the output neutral and input neutral  must be separated at the input to the UPS     12    Electrical Connections    2 1 7 Cabling Procedure    AN CAUTION    The operations described in this section must be performed by authorized electricians or  qualified technical personnel  If you have any difficulties  contact your local sales  representative or Technical Services       NOTE  Hydraulic pressure pliers  combinative tools and piston ring pliers should be used to connect  AC wiring     Once the equipment has been positioned and secured for operation  and the battery and ground col   lars have been connected  see 2 1 4   Cable Connections   connect the power cables as described  below   Study the reference drawing in 6 0   Installation Drawings      1  Verify that all incoming high and low voltage power circuits are de energized and locked out or  tagged out before 
78. ft side     10    Electrical Connections    2 1 4 Cable Connections  The rectifier input  bypass and output are easily accessible from the left side of the unit for installa   tion  All require lug type terminations  They are connected to busbars on the left side of the TRX and  below the switch  as shown in Figure 3  These busbars are accessible when the left side panel is  removed  Busbars to connect external batteries are accessible from the front of the UPS     NOTE  External battery connection access requires removal of a protective panel on the lower front of  the UPS to the left of the bottom two battery shelves     Figure 3 Input busbars    Remove these links  for dual input  configuration and  wire UPS Main input  directly to CB1       D Rectifier Input    Output Busbars  Busbars     Phases are  indicated by  Phases are  letters below the indicated by    bars  z letters below the  o TS bars         B A C B A  OUTPUT BYPASS       The internal batteries are connected with Anderson connectors inside the battery compartment  The  batteries are connected to fuses to protect the TRX and connected equipment  see Figure 4      Figure 4 Battery fuses and connections    H Internal battery input  B D connections    AN Battery fuses     fuses are behind  access plate on   front of UPS  see  Note on page 11           11    Electrical Connections    2 1 5 Safety Ground    The safety ground busbar 1s located below the neutral input and output busbars as shown in  Figure 5 below  Th
79. ge beyond limits or battery fuse failed  Battery converter shuts  Batt  Converter Fault down  Battery backup not available     Batt  Conv  Over  Curr  Battery converter overloaded  Battery converter shuts down  Battery backup not available     Batt  Converter Overtemp  a of battery converter heatsinks  Battery converter shuts down  Battery backup not    101    UPS Status Messages    102    DUALI LITE       While every precaution has been taken to ensure the accuracy   and completeness of this literature  the manufacturer assumes no  responsibility and disclaims all liability for damages resulting from use of  this information or for any errors or omissions     All rights reserved  Specifications subject to change without notice      Dual Lite  Trident  the Dual Lite logo and the Trident logo   are registered trademarks of Hubbell Lighting  Inc       MultiLink and IntelliSlot are registered trademarks of Liebert Corp   All names referred to are trademarks   or registered trademarks of their respective owners     93020448 10 08          HUBBELL LIGHTING  INC     
80. ghly before attempting to install wiring to this unit     Removing the Cover Plates    Plates cover the input and output terminals on the front of the Maintenance Bypass Cabinet  see  Figure 18   Remove these and keep the screws and plates for reinstallation             26    Maintenance Bypass Cabinet    4 6 2 Power Cable Installation  Refer to Tables 35  36 and 38 when selecting cables         NOTE  Transtent and steady state earth leakage currents may occur when starting the equipment   This should be taken into account when selecting ground current detection devices because  these will carry the earth leakage currents of both the UPS equipment and the load     4 6 3 Input Output Wiring    Follow the steps below to connect the input wiring     NOTE    Input wiring must be installed using conduit if cabinet is not mounted to the immediate left of  the UPS     1  Locate the input wiring access  top or bottom access   remove the conduit landing plate and punch  the appropriate size hole for the size conduit being used  Pull the three four input wires through  it  allowing some slack for installation  For cabinets that are located to the immediate left of the  UPS  the access plate is on the lower right of the cabinet  Remove the access plate and verify that  the edge guarding is installed and intact See Figure 19     Figure 19 Maintenance Bypass Cabinet wiring access panel    Di        Wiring access is on  gt  0 3  lower right side of  Maintenance  Bypass Cabinet    Access pa
81. gure 12 Battery cabinet   details       Removable retainer          Tray handle    Insulated post  for cabling    20    Battery Installation    Figure 13 Narrow battery cabinet  27 in   690mm    rear view       Top  cable    entry  BCB plate    and BCB    EE    Br k  camas EE      Battery  trays    Figure 14 Wide battery cabinet  57 in   1488mm    front view    Top cable entry    Batteries      BCB plate and  2Y BCB  F  P i  B 1h  TNE  ra  Battery tray  support  Service  shelf  Battery tray       21    3 4 3    Battery Installation    Installation Considerations    Position   Dual Lite battery cabinets come in versions specific to either the left or right side of the  UPS  Control wires and power cables are cut to different lengths for the different versions  If the sys   tem includes a matching maintenance bypass cabinet  MBC   the MBC should be mounted to the left  of the UPS  nearest the busbars  and the battery cabinet s  should be installed to the right of the  UPS  Otherwise  left side placement of the battery cabinet 1s preferable     The battery cabinet s  are designed to be located conveniently next to each UPS module  and are also  avallable in stand alone configurations with painted side panels  The front access design eliminates  side and rear service clearance requirements  Refer to Table 39 for battery cabinet dimensions and  welghts     Bolt On Cabinets   Matching battery cabinets are designed to bolt onto the side of the UPS module  cabinet  Use bolts that shi
82. h until the rectifier indicator stops flashing green        4  Turn the rotary switch to BYPASS     The maintenance switch SW1 D opens and output switch SW1 A  closes  The UPS powers from static bypass instead of from Indicator    maintenance bypass  The bypass and load indicators turn on  Rectifier indicator    The design of the rotary switch ensures uninterrupted output  Battery indicator Off    Bypass indicator    Inverter indicator Off    Load indicator  Status indicator       75    Operating Instructions    5  Turn the rotary switch to NORMAL  then press the INVERTER ON control button for 2 seconds     The inverter will start and the inverter indicator will flash green  After the inverter 1s ready  the  UPS transfers from bypass to inverter  the bypass indicator turns off and the inverter and load  indicators turn on     The UPS is operating normally  The UPS Mimic display indicators will     Rectifier indicator  Battery indicator  Bypass indicator    Inverter indicator  Output indicator  Status indicator       9 2 2 Verify Switching Between Operation Modes    Switch from Normal Mode to Battery Mode  e Open CB1 to enter battery mode  This breaks the utility connection to the TRX     To return to normal mode  close CB1 after a few seconds  The rectifier will restart automatically  after 10 seconds and resume feeding power to the inverter     Switch from Normal Mode to Bypass Mode    Press INVERTER OFF button to switch to bypass mode         NOTE  In bypass mode  the load 
83. he status  e g   utility power  fallure low battery  of a single UPS     This card is supported in any of the three IntelliSlot bays on the TRX     Figure 29 MultiPort 4 card pin assignment     i  ie  Assignment  i Description  T v      Ti  UPS  I    i  cru e  nausa  p  e  Uy Fal Common     H cru o   vii Fai       43    Installation Drawings  6 0 INSTALLATION DRAWINGS    The diagrams in this section illustrate the key mechanical and electrical characteristics of the TRX  UPS System cabinets     Figure 30 Dimensional view  front and left side views           ae 10mm dia  threaded  Monitoring mounting holes    Panel        M r  CO  sas  Beer A 2    i   ll    DOON y  Da Rd    Na      Detail    A    Rear of unit  shown without side panel    fo    1600    TI   TON  C    Air intake area   Do not block  air filter     Adjustable Stops    FRONT VIEW  see Note 11     LEFT SIDE VIEW    1  All dimensions are in millimeters   A minimum of 24 inches clearance above the unit is required for air exhaust     3  Installation and service access required  Left side access recommended for maximum ease of  installation     4  Keep cabinet within 15 degrees of vertical while handling     5  Top and bottom cable entry available through removal access plates  Remove punch to suit conduit size  and replace     6  Unit bottom is structurally adequate for forklift handling   7  Open door to replace air filter  washable type  size 354x314     8  Threaded mounting holes used for seismic anchoring or floo
84. iary cabinets          AMERO   MER   PELA Y  Trident Trident Trident lleling  UPS UPS UPS Cabinet          Front of Units                   Dual Lite Dual Lite Dual Lite M  add Trident sind Trident lid Trident Heling                    UPS as UPS ll UPS canner                      Front of Units    57    7 0    7 1    Operation    OPERATION    General Description  The standard TRX consists of the UPS and internal batteries in a compact  single cabinet     As shown in Figure 45  the AC utility source is input at CB1 and the rectifier converts the AC utility  into DC power  The inverter converts that DC power from the utility   or DC power from the batter   1es   into AC power for the load  The batteries power the load through the inverter in the event of a  power failure  The utility source can also power the load through the static bypass     If maintenance or repair of the UPS is necessary  the load can be switched without interruption in  service to the maintenance bypass     Figure 45 Single module block diagram  dual input configuration     7 2    7 3    3PHASE 2 INTERNAL MAINTENANCE BYPASS     4W   GND        AC BYPASS INPUT      SSS                                                   STATIC BYPASS    3PHASE 3PHASE  4W   GND 3 OR 4W   GND   gt      a a  gt   AC INPUT AC OUTPUT    Bypass Supplies    The circuit block labeled    Static Switch    and    Contactor    in Figure 45 contains an electronically con   trolled switching circuit that enables the critical load to be co
85. ied has an identification tag on the back of the main door listing the type and  size of the UPS     UPS Location    Positioning the UPS  Choose a location for the UPS that offers     e Easy connection to inputs  outputs and auxiliary equipment     Enough space to service the UPS   e Air circulation sufficient to expel heat produced by UPS   e Protection against moisture and excessive humidity   e Protection against dust and other particulate matter   e Compliance with fire prevention regulations and practices   e Operating environment temperature of 74 80  F  23 27  C  for maximum battery efficiency    Environmental Considerations    Before installing the TRX  verify that the UPS room satisfies the environmental conditions stipulated  in 10 2   UPS Environmental  paying particular attention to the ambient temperature and air  exchange system     The UPS unit should be installed in a cool  dry  clean air environment with adequate ventilation to  keep the ambient temperature within the specified operating range 32  F to 104  F  0  C to 40  C      For optimal UPS and battery system performance and service life  maintain the operating tempera   ture within the range of 74 80  F   28 27  C      The TRX UPS cooled by internal fans  Cooling air enters the unit through the front of the unit and is  exhausted out the top  To permit proper air flow and prevent overheating  do NOT block or cover the  ventilation openings or blow air down onto the unit  Ventilation clearance above the u
86. iled     Inverter Contactor Fail This alarm is triggered when the feedback signal and the state of the contactor is not identical for  a specified time  Contact the manufacturer at 800 543 2378 for assistance     Output Fuse Fail pa ar of the output fuses is open  Contact the manufacturer at 800 543 2378 for    Control Power 2 Fail Control Power 2 is abnormal or lost  Contact the manufacturer at 800 543 2378 for assistance     The UPS is confirmed to be overload when the load arises above 105  nominal rating    The alarm automatically resets once the overload condition is removed    1  Confirm that the alarm is true by checking the load percent indicated on the LCD panel to  determine which phase is being overloaded    2  lf the alarm is true  measure the actual output current to verify that the indications are valid   Disconnect unnecessary load and ensure the safety  In a parallel system  a severe load  sharing error can also leads to the alarm    Contact the manufacturer at 800 543 2378 for assistance        Unit Overload       The UPS parallel system is confirmed to overload when the total load arises above 105  nominal   rating for the set basic number of UPSs  The alarm automatically resets once the overload   condition is removed    1  Confirm that the alarm is true by checking the system load percent indicated on the LCD  panel to determine which phase is being overloaded    2  lf the alarm is true  measure the actual output current to verify that the indications are 
87. indicates Pin 1     2 3 Dry Contacts  The UPS provides input dry contacts and output dry contacts     2 3 1 Input Dry Contacts    There are several input dry contacts at the X3 slot     Figure 8 Input dry contacts    EFE eye Tye        NOTE  The black square  m  on each slot indicates Pin 1   Table 1 Input dry contacts at X3     Position   Name   Description  Battery Room Alarm  N C      Battery Ground Fault Detection  N C    Generator Join Detection  N O      1   Must be configured by configuration software before becoming active   2   When activated  the charger current can be limited  via software  to a percentage of the full charger current  0 100     3   Activating this feature turns the battery charger off        15    2 3 2    2 3 3    Maintenance Bypass Cabinet Interface  J26 and J30 are the MBC interface     Table 2 Maintenance bypass cabinet interface     Position   Name   Description    1   Must be configured by software before becoming active       Electrical Connections        NOTE  All auxiliary cables of terminal must be double insulated  Wire should be 20 16AWG stranded    for maximum runs between  2 and 197 feet  25 60m   respectively     BCB Box Interface  J10 is the BCB box interface   Table 3 BCB box interface     Position   Name   Description              J10 1 BCB Driver Signal   Reserved  J10 2 BCB Contact State    BCB On Line   Input   This pin will become active when  BCB interface is connected   N O           NOTE  All auxiliary cables of terminal mu
88. installing cables or making any electrical connections     2  Remove the left side panel to gain easier access to the connections busbars     3  Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar  located on the bottom of the equipment below the power connections  All cabinets in the UPS  system must be connected to the user s ground connection         NOTE  The grounding and neutral bonding arrangement must comply with the National Electrical  Code and all applicable local codes     4  Identify and make power connections with incoming cables according to Steps 5 through 11     Common Input Connections    5  For common bypass and rectifier inputs  connect the AC input supply cables between the power  distribution panel and the UPS input busbars  A B C terminals  and tighten the connections to  44 lb in   5 N m  using the M6 bolt provided     6  The input neutral cable must be connected to the input neutral busbar  N   See Figure 5     Dual Input Connections    7  For bypass connect the AC input supply cables between the power distribution panel and the UPS  input busbars  A B C terminals  and tighten the connections to 44 lb in   6 N m  using the M6  bolt provided     8  For Rectifier Input connect AC input supply cables between the power distribution panel and the  UPS input circuit breaker  A B C terminals     9  The bypass and rectifier input neutral cables must be connected to the input neutral busbar  N    See Figure 5       NO
89. irements   a  AC Input  3 phase  4 wire  plus ground output   b  AC Output  3 phase  3  or 4 wire  plus ground  8  All wiring is to be in accordance with national and local electric codes     ARI     gt     87    UPS Specifications    10 4 1 Battery Manufacturers and Models    Either of two manufacturers    batteries will be installed in the TRX 10 30 kVA 208V as shipped  Below  are the battery makers and the models they supply     Table 28 Approved batteries    Battery Manufacturer Models Supplied    NPX 80FR NPX 100FR   NPX 150FR  C amp D Dynasty UPS12 100MR   UPS12 140MR ae    10 4 2 Input Rectifier  Table 29 Rectifier input power    ie  Less than 4  at full rated UPS output load    Notes   1  Overload capacity of input current  100  Imax  lt l lt 125  Imax  10 min   125  Imax  lt l lt 150  Imax  1 min   l gt 150   Limits input current immediately          10 4 3 DC Intermediate Circuit  Table 30 DC intermediate circuit    Rated Power 10kVA 15kVA 20kVA 30kVA    Number of batteries is 24 jars  12V per jar   or 144 cells  2V per  Recommended number of lead acid batteries   cell  for VRLA  The unit is shipped with a nominal voltage of  288VDC     Recommended float charge voltage 2 27VDC     Recommended boost charge voltage 2 3VDC   Recommended end of discharge voltage 1 65 1 8 VDC    Maximum boost charge duration  min   1440  Boost float threshold current  A  0 1 C default  3    Temperature voltage compensation  mV  C       Set by configuration software and based on usage of 
90. is being powered by the utility and is not receiving conditioned power  through the inverter     Switch from Bypass Mode to Normal Mode    Turn the rotary switch to NORMAL       In bypass mode  press the INVERTER ON button  When the inverter is ready  the UPS will  switch to normal mode     76    9 3    9 4    Operating Instructions    Switching the UPS from Normal to Maintenance Bypass    Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass  line of the UPS     YN CAUTION    Before performing this operation  read the messages on the LCD to be sure that bypass supply  is regular and the inverter is synchronous with it  If those conditions are not present  there is  a risk of a short interruption in powering the load     This procedure assumes that UPS is operating normally     1  Press the INVERTER OFF button on the right side of the operator control panel for longer than  2 seconds     The Inverter indicator will turn off and the status indicator  6  will turn amber and an audible  alarm will sound  The load will transfer to static bypass and the inverter will shut off         NOTE  Pressing the Alarm Silence Switch cancels the audible alarm  but leaves the warning message  displayed until the appropriate condition is rectified     2  Open the UPS door to gain access to the main power switches  SW1 and CB1     3  Turn the rotary switch to BYPASS position  The UPS Bypass Static Switch still supply power to  load     4  Turn the ro
91. isplayed on the front LCD  When not  activated  the values are hidden     Command password    65    8 9 Language Selection    The LCD menus and data display are available in  12 languages  Chinese  Dutch  English  French   German  Italian  Japanese  Polish  Portuguese   Russian  Spanish and Swedish   To select a differ   ent language     From the main menu  press the F1  shift  key  to move the cursor to the menu at the top of  the screen    Press F2 and F3  left and right arrows  as  needed to select the Language menu    Press F1  shift  to move the cursor to the data  and settings area of the LCD    Use F2 and F3  up and down  to select the  required language    Press the F4  enter  key to accept the language  selection        Operator Control and Display Panel    DuakLite TRX  30kVA 3X3    Kil Battery    ENGLISH  FRANCAIS  NEDERLANDS  PYCCKU      2009 01 22  Single    DEUTSCH  ITALIANO  SVENSKA  PORTUGUES    POLSKI  ESPANOL    a ue    Fault reset 01 22 10 32    Manual turn on 01 22 10 32  Normal mode 01 22 11 05    Return to the main menu by repeatedly pressing F1  ESC  as needed  all text on the LCD will now    be displayed in the selected language     8 10 Current Date and Time    To change the system date and time     From the main menu  press the F1  shift  key  to move the cursor to the menu at the top of  the screen    Press F2 and F3  left and right arrows  as  needed to select the Settings menu    Press F1  shift  to move the cursor to the data  and settings area o
92. itch between    these two terminals using shielded cable  see Figure 10 and Table 5   If this function is not used   terminals EPO L to EPO H must be opened     Table 5 EPO input contact relays    Position Description    J28 2 EPO_L   Emergency Power Off Low       J28 4 EPO_H   Emergency Power Off High      NOTE  The Emergency Stop action within the UPS shuts down the rectifier  inverter and static  bypass  It does not internally disconnect the input power supply     To disconnect ALL power to the UPS  open the upstream feeder breaker s  when the remote  EPO ts activated     17    Electrical Connections    Firmware M200 or Later    The UPS has an Emergency Power Off  EPO  function operated by a button on the control panel or by  a remote contact provided by the user  The EPO button 1s under a hinged  clear plastic shield     The X2 slot  shown in Figure 11  is the remote EPO input interface  The EPO has a NO NC contact  point becomes active when shorting terminals X2  3 and 4 or open terminal connection X2  2 and 1     If an external Emergency Stop facility is required  it is connected terminals X2  1 amp 2 or X2  3 and 4 of  the auxiliary terminal block  X2   It also is connected to the Normally Open or Normally Closed  remote stop switch between these two terminals using shielded cable  see Figure 11 and Table 6   If  this function 1s not used  terminals X2  3 and 4 must be opened and X2  1 and 2 must be closed     Figure 11 EPO wiring for firmware M200 or later    Table 6 
93. ividual drawing of each piece of equipment for additional details     Table 14 Dual Lite supplied interconnect wiring   SlimLine distribution cabinet to TRX    Conductors    Distribution Cabinet Load AC Connection Isolated Ground    eee ad   Neutral  Distribution Cabinet Load AC Connection Distribution Cabinet   oes et Ground  C Distribution Cabinet Load AC Connection Distribution Cabinet    a       52    Installation Drawings    Figure 40 Lineup detail    1 N Type A connection to TRX              TiS  a T  TER     E        e brea    GOA TER  SUCIO 5l       E   ooooco  rae ocococo al    1   a Parallel  gt    front view without front door and panel     1  All Dual Lite supplied cable must be repositioned prior to and while setting the cabinets in their  installed location     A         ee e  ee eee  e          2  All interconnection cables and hardware supplied by others   3  AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules    4  The interconnecting output cables between the paralleling cabinet and the UPSs must be the same size  and the same length     5  The location of the system output neutral busbar  connection K  and the ground busbar  connections H     and J  are shown for a left access style  For right access version  these busbars are at opposite locations    6  Refer to the individual drawing of each piece of equipment for additional details     Table 15 Interconnect wiring   1 N Type A connection to TRX  CONDUCTORS  
94. l Services for reeommended precautions     The following notes  in conjunction with the diagrams  Figure 13 through 12   illustrate the broad  principles to be followed when fitting and connecting the majority of battery cabinet installations     CAUTION    Any battery system should be installed by qualified personnel        When installing an external battery cabinet that is NOT a Dual Lite TRX battery cabinet  the cus   tomer must provide overcurrent protection  See Table 27 for sizing of protection devices     NOTE   Q When using an external battery supply that is not provided with the UPS  please make  reference to the battery manufacturer   s installation manual for battery installation and  maintenance instructions  available on the manufacturer   s Web site  When replacing batteries   Dual Lite recommends that the batteries in external cabinets be the same type used internally  in the TRX  See Table 28 for a list of batteries that are approved for use with this product     Connecting the Batteries    If the TRX battery cabinets are installed on a raised floor  the battery power cables and circuit  breaker control cables may be routed to the UPS cabinet via the floor of the cabinet  bottom entry      If the TRX battery cabinets are installed adjacent to one another on a solid floor  these cables may be  passed between the cabinets through lifting slots in the lower sides of the cabinets     Intertray connections must be made before the battery cabinet may be used     Fi
95. le    01 22  01 22  01 22       L___ UPS system  information  10 32    10 32  11 05  Navigation  key icons    63    8 6    8 7    Operator Control and Display Panel    Navigation Keys    The navigation keys on the front panel    F1 through F4 and Help   are used to access the LCD to view  the current status and other information about the TRX     Navigation key icons on the LCD appear above each key to indicate its operation  see Table 20   The  keys are    soft keys    that can change functions according to the icon     e Use Fl either to move to a different portion of the LCD  shift icon  or to escape to a previous view   ESC icon     e Use F2 and F3 as cursor keys to move left and right or up and down  depending on the icons dis   played above the keys     e Use F4 as an Enter key to confirm a choice     Use HELP to access help information on the LCD     Table 20 Icons for navigation keys    O ky    a    e    a P    Functions Shift Right  Available  Enter Help  Up Down    UPS System Information  The UPS system information displayed at the top of the LCD is detailed in Table 21           Table 21 Description of items in UPS system window    No    itemType   Explanation  UPS name  Current date    030 means UPS model is 30kVA   POORT 3x3 means 3 by 3 system  three phase input and output     sas  1  1 of 6 Paralleled changed to    Unit  1      os Ro Single      UPS is configured as a single unit system running in Normal mode  UPS in normal operation  inverter powering load  no
96. le maintaining power to the load  follow these steps     1  Perform Steps 1 through 5 in 9 3   Switching the UPS from Normal to Maintenance  Bypass     2  Close the external maintenance bypass rotary switch to Maint position     On the primary input distribution panel  which is often located distant from the UPS area  a label  should be posted advising service personnel that the UPS circuit is under maintenance     YN WARNING    Wait 5 minutes for the internal DC busbar capacitors to discharge     The UPS is now completely powered down       NOTE  The Maintenance Bypass Power switch may be operated at any time while the UPS is powered  down to connect the load to the maintenance bypass supply if required     The procedure can be performed only after the installation has been completed  which includes the  maintenance bypass cabinet   after the system has been placed in operation by authorized personnel   See the reference drawing of Figure 59 for more information     Figure 59 Typical configuration for single UPS with external maintenance bypass cabinet    3PHASE INTERNAL MAINTENANCE BYPASS  sd  4W   GND        AC BYPASS INPUT   OOOO SS SS SS    STATIC BYPASS       3PHASE 3PHASE  4W   GND 3 OR 4W   GND   gt    os   a  gt   AC INPUT AC OUTPUT    78    9 6    9 7    9 8    Operating Instructions    Emergency Shutdown With EPO    This circuit has been designed to switch off the UPS in emergency conditions  1 e   fire  flood  etc    The  system will turn off the rectifier  invert
97. lel cables are not connected correctly in a parallel system   1  Reset the fault by pressing the  fault clear  button  then restart the inverter by pressing the  Parallel Connect Fault  inverter on  button     2  If the UPS does not resume normal operation  contact the manufacturer at  800 543 2378 for assistance     Bypass current is over limit above 135  rating  The UPS just alarms and does nothing  Refer to  your installation documentation or contact the manufacturer at 800 543 2378 for assistance     The LBS setting is active  The UPS is acting as an LBS master or slave in a dual bus  Baten owind faii Battery ground fault from dry contact signal  Contact the manufacturer at 800 543 2378 for  assistance   Inverter turned On Manual Turn On via front panel  manually  Inverter turned Off Manual Turn Off via front panel  ES    EN   Emergency Power Off OOOO Power Emergency Power Off    Rema S    100       Bypass Overcurrent    UPS Status Messages    Table 44 UPS status messages  continued     Event Message Description   Suggested Action  if any     Balancen au Internal VDC     and VDC     offset by over 50V exceeding the inverter DC offset compensation  capacity  Inverter shuts down  Load transfers to bypass   Internal Inverter DC offset balancing IGBT current rating exceeded 300   Inverter shuts down   Balancer Over Current Load transfers to bypass     Batt  Contactor Fail Battery contactor or circuit breaker not responding to control signals     Battery converter output volta
98. les can be sized to suit the UPS unit rating according to Table 27     Lug Size and Torque Requirements    Refer to Table 33 for lug size and torque requirements     Electrical Connections    2 1 2 UPS Input Configuration    Figure 2 illustrates the TRX in a split bypass  dual input  configuration  In this configuration the  Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main  input  Both sources must be protected externally with properly sized protective devices  By default   the unit ships with internal links installed between the Bypass input and Main input  single input  configuration   To wire the unit as a dual input UPS  remove the links and wire the bypass to the  input bus bars  then wire the Main input directly to CB1  see Figure 3      Figure 2 Single module block diagram   dual input configuration    AC BYPASSINPUTI I                      gt     gt        3PHASE  4W   GND    Ao    3PHASE 2 INTERNAL MAINTENANCE BYPASS     4W   GND        STATIC BYPASS 3PHASE    3 OR 4W   GND        gt     AC INPUT AC OUTPUT    2 1 3 Cabling Guidelines    The following are guidelines only and are superseded by local regulations and codes of practice where  applicable  Use wiring rated at 75  C or greater     l     Take special care when determining the size of the neutral cable  as current circulating on the  neutral cable may be greater than nominal current in the case of non linear loads  Refer to the  values in 10 4   UPS Electrical Char
99. m buzzer location    Dual Lite TRX 2009 01 22  Unit  1    B BC   Vphase V 120  Iphase A f 20 5  Freq  Hz L 50 1  Vline V 208  Alarm P  F    0 99 INVERTER ON INVERTER OFF    Input Breaker Closed 01 12 12 28 16 YM       Buzzer Manual Turn On 01 12 12 30 06    UPS in Normal Mode 01 22 12 30 16       62    Operator Control and Display Panel    8 5 LCD Overview    The LCD on the front panel has five main sections  as shown in Figure 51  Press the F1 key below    the LCD to scroll through these sections     UPS system information   view UPS name and model  date and time  overall status  see    Table 21      LCD Menu   choose a category of data items to appear below the menus  see Table 22    Data and settings   view data items for the selected menu  see Table 22    Current status messages   check the most recent UPS event and alarm messages  see Table 44    in Appendix A      Navigation key icons   look at the icon above each navigation key to determine how the key  operates when pressed  see 8 6   Navigation Keys      The LCD displays alarm information in real time  After appearing in the current status section of the  LCD  status messages are stored in the history log   512 records can be stored and retrieved     Figure 51 Sections of the LCD    LCD menu    Data  amp  settings    DuabLite TRX  30kVA 3X3    L N voltage V   L N current  A   Frequency Hz   L L voltage A   Power factor    Fault reset    Current status           Manual turn on  messages Normal mode    2009 01 22  Sing
100. mation         Input Output    Active Alarms        No Alarms Present pam                   monitor    configure    Battery  Updated  September 21  2004 01 25 58PM       Supported Status P IL Value  Units     Battery Time Remaining   783 3  min  in ate     IB Battery Voltage   547 1 lv   Device Status     B attery Current  Charge Discharge    0 2 4   Load Protected    B Battery Charge Percentage L 99      No Alarms Present o aao SA     B Battery Charge Compensation   False       B attery Test Result   Unknown     Monitor Categories    le Battery Charge Mode  lt i Float     Ls Supported Alarms   Status  y   CB Battery Under Test I Normal  Input j HT Load On Battery   Normal  Reche  ETE Charger Failed I Normal  j L Low Battery   Shutdown Imminent     NE Battery Fault J Normal  Cb Battery Contact Fail   Normal    Battery Converter Over Temperature   y Normal  EN   Normal    NE Battery Converter Fail   Normal  Cw UPS Load Joint Mode   Normal     Device Information                       41    9 11    Option Installations    Relay Card  The relay card provides voltage free contact closures for remote monitoring of alarm conditions     Delivering On Battery  On Bypass  Low Battery  Summary Alarm  UPS Fault and On UPS sig   nals  the easy to install card integrates with AS 400 computers  additional cable required  and other  relay contact monitoring systems     The relay card 1s rated for 24 VAC DC at 1A  and supported in any of the three IntelliSlot bays on the  TRX     Table 9 Rela
101. mental    The UPS is designed to operate under the following environmental conditions without damage or deg   radation in electrical operating characteristics     Table 25 Environmental characteristics    OS  IN    Acoustical Noise  dBA at 39 in   1m  54   Altitude of Operation  lt 1000m per IEC 62040 3  Storage Transport Temperature  UPS  4  F to 158  F   20  C to 70  C   Storage Transport Temperature  Battery  4  F to 86  F   20  C to 30  C        10 3 UPS Mechanical Characteristics  Table 26 Mechanical characteristics    450 20s  954149    1198  543   384  652  934  1417   Cable Entry Bottom or top    Protection Grade  with open closed front doors  IP 20       86    UPS Specifications    10 4 UPS Electrical Characteristics  Table 27 UPS terminal    Input  for single input unit        Maximum Recommended Lug                                                                      Nominal Maximum OCP  Input Input OCP Lug T amp B Lug T amp B  Current Current Current Bolt Size One Hole 54000   One Hole REDDY  10 28 35 42 45 6M  1 4     54105 62204  15 42 53 63 70 6M  1 4     54106 62204  20 56 70 84 90 6M  1 4     54107 62204  30 83 104 125 125 6M  1 4     54152 62205  Rectifier input  for dual input unit only   Nominal Maximo OCP Maximum Recommended Lug  Input Input OCP Device Lug T amp B Lug T amp B  Current Current Current Rating Bolt Size One Hole 54000   One Hole REDDY  10 25 31 37 40 6M  1 4     54130 62204  15 37 47 57 60 6M  1 4     54106 62204  20 50 63 76 80 6M  1 4     
102. n check for and verify    1  high ambient air temperature    2  blocked cooling airway    3  any fan failure    4  prolonged inverter overload    Contact the manufacturer at 800 543 2378 for assistance     Inverter Asynchronous    Inv  Inductor Overtemp     The temperature of the inverter heat sink is too high to keep inverter running   This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter  bridge heat sink   The UPS will recover automatically after a 5 minute delay from the disappearance of the  overtemperature signal   Inverter Overtemp  If the overtemperature condition is true  then check for and verify   1  high ambient air temperature   2  blocked cooling airway   3  any fan failure   4  prolonged inverter overload   Contact the manufacturer at 800 543 2378 for assistance     Fan Fault At least one of the cooling fans fails  Contact the manufacturer at 800 543 2378 for assistance   Inverter STS Fail At least one of the static switches of inverter side is open or short circuit  This fault is locked until  power off  Contact the manufacturer at 800 543 2378 for assistance     At least one of the static switches of bypass side is open or short circuit  This fault is locked until          Bypass STS Fail power off   Contact the manufacturer at 800 543 2378 for assistance        98    UPS Status Messages    Table 44 UPS status messages  continued     Event Message Description   Suggested Action  if any     The Inverter contactor has fa
103. nel removed   wiring connects the TRX and  the MBC    Edge Guard       2  Secure the conduit to the access plate of the Maintenance Bypass Cabinet     3  Input power cables connect to the system input circuit breaker  Refer to Figure 37    Maintenance Bypass interconnection    4  Connect the ground  earth  wire to the earth busbar and tighten it to 44 lb in   5 N m   M6 bolt    5  Locate UPS input and output cables and access panel to UPS on lower right side  See Figure 19         NOTE  If the maintenance bypass cabinet is not to be bolted to the UPS  use either top or  bottom access plate     6  Connect the system ground cable between the Maintenance Bypass Cabinet and UPS and tighten  the connections to 44 lb in   6 N m   M6 bolt      27    Maintenance Bypass Cabinet    7  Connect the system input cables between the Maintenance Bypass Cabinet  UPS Input  Busbars   A B C N terminals  and UPS input busbars  A B C N terminals  and tighten the connections to  44 lb in   5 N m   M6 bolt     8  Connect the system output cables between the Maintenance Bypass Cabinet  UPS Output   Busbars  A B C N terminals  and UPS output busbars  A B C N terminals  and tighten the  connections to 44 lb in   5 N m   M6 bolt      9  Connect supplied control wire to X3 on the Parallel  M3  board  see Figure 20      WARNING    The control wire must be installed to ensure proper operation of the system and fully protect  the load when switching between bypass cabinet and UPS        Figure 20 Maintenan
104. ng Gabinet   Ground  System Input    1   Paraleling Gabinet   Load AC Connecion   PRA B C Load    L1 L4 UPS  1 UPS  4 Module Output Breaker Aux Contact    UPS  1 UPS  4 Module Rotary Switch Aux Contact  Paralleling Cabinet UPS Parallel Logic Board  M3        54         1   N Cabinet Side View   without side panel or door        A AAA    rl    AS    A m e Eee    ls   y     al    UPS Module Left Side View   without side panel        1   N Parallel Cabinet   front view without front door and panel          Installation Drawings    Figure 42 Lineup detail    1 N Type C connection to TRX    ia  i    ervey     E TU LT  Cy PT  T T  lo    Fila       he E   E       L x    1  se         1   N Cabinet Interior View   neutral and ground busbar location     All Dual Lite supplied cable must be repositioned prior to and while  setting the cabinets in their installed location   All interconnection cables and hardware supplied by others     AC connections must be made to the UPS modules before attaching  paralleling cabinet to UPS modules    Utility AC source neutral not required for maintenance bypass   transformer cabinet Type C    The interconnecting input cables between the paralleling cabinet and  the UPSs must be the same size and the same length    The interconnecting output cables between the paralleling cabinet  and the UPSs must be the same size and the same length    The location of the system output neutral busbar  connection K  and  the ground busbar  connections H  I and J  are
105. nit must be a  minimum of 24 in   610mm      See Table 26 for details on heat dissipation   Battery Location    Temperature 1s a major factor in determining battery life and capacity  Battery manufacturers recom   mend an operating temperature of 77  F  25  C   Ambient temperatures warmer than this reduce bat   tery life  temperatures below this reduces battery capacity  In a typical installation  battery  temperature should be maintained between 74  F and 80  F  23 27  C   Batteries should be placed  where there are no main heat sources or air inlets to prevent portions of batteries from being either  much warmer or much cooler than other parts of the batteries     Installation    1 4 3 Special Considerations for 1 N Systems    1 5    1 6    1  Consider the grounding configuration of your system before finalizing module placement  For  optimal ground performance  the TRX modules should be close together    2  For optimal load sharing performance  the UPS output cables should be approximately the same  length  plus or minus 20 percent    3  Position modules in such a way as to minimize the length of power cables and control wiring  between UPS modules and the paralleling cabinet     Considerations in Moving the TRX    Ensure that the UPS weight is within the designated surface weight loading  1b  ft  or kg cm   of any  handling equipment  See Table 26 for weights of various units     To move the UPS and optional battery cabinets       The TRX may be rolled on its casters when
106. nnected to either the inverter output or  to a bypass power source via the static bypass line  During normal system operation the load is con   nected to the inverter and the inverter contactor 1s closed  but in the event of a UPS overload or  inverter failure  the load is automatically transferred to the static bypass line     To provide a clean  no break  load transfer between the inverter output and static bypass line  the  static switch activates  connecting the load to bypass  To achieve this  the inverter output and bypass  supply must be fully synchronized during normal operating conditions  This is achieved through the  inverter control electronics  which make the inverter frequency track that of the static bypass supply   provided that the bypass remains within an acceptable frequency window     A manually controlled  maintenance bypass supply is incorporated into the UPS design  It enables the  critical load to be powered from the utility  bypass  supply while the UPS is shut down for routine  maintenance     NOTE    When the UPS is operating in bypass mode or on maintenance bypass  the connected  equipment is not protected from power failures or surges and sags     Operating Modes    The UPS is designed to operate as an on line  double conversion  reverse transfer system in the fol   lowing modes     58    Operation    Normal Mode    Operating in normal mode  the TRX   s rectifier derives power from a utility AC source and supplies  regulated DC power to the invert
107. nternal monitor and rectifier fails  Contact the manufacturer  Rectifier Comm  Fail at 800 543 2378 for assistance     The CAN communication between different UPSs within a parallel system fails   1  Check if there are some UPSes not powered on in the parallel system  If so  power on these    Parallel Comm  Fail UPSs and check if the alarm disappears   2  Press Fault Clear push button   3  If alarm does not clear  contact the manufacturer at 800 543 2378    Battery Overtemp  The Battery temperature is over limit  Check the battery temperature and ventilation  Ambient Overtemp  The Ambient temperature is over limit  Check the ventilation of UPS room     Battery Fault Battery is bad   Reserved  Contact the manufacturer at 800 543 2378 for assistance     Replace Battery Battery should be replaced  Contact the manufacturer at 800 543 2378 for assistance     Before the end of discharging  battery under voltage pre warning should occur  After this pre   warning  battery should have the capacity for 3 minutes discharging with full load  The time is  user configured from 3 to 60 minutes    Shut down the load in time    l Inverter turned off due to low battery voltage   Battery End of Discharge Check the utility failure and try to recover it   Mais Vel Abramal Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown   Check the input line to neutral voltage amplitude of rectifier     Mains Voltage is undervoltage  120v 176v  with derated load   an AAE Check the
108. on followed by important instructions    AC input    AN       ai    Requests the user to consult the manual    Lo  Indicates the unit contains a valve regulated lead acid battery    CRY      en     gt     Recycle            DC voltage    Bonded to ground    D Equipment grounding conductor    Ay AC voltage    1 0    1 1    1 2    Installation    INSTALLATION    Dual Lite s Trident TRX    Uninterruptible Power Supply system provides continuous  high quality  AC power to your business critical equipment  such as telecommunications and data processing  equipment  The TRX supplies power that is free of the disturbances and variations in voltage and fre   quency common to utility power  which 1s subject to brownouts  blackouts  surges and sags     The TRX utilizes the latest in high frequency  double conversion pulse width modulation  PWM  tech   nology and fully digital controls to enhance its reliability and increase the ease of use     This section describes the TRX   s environmental requirements and mechanical considerations that  must be taken into account when planning the positioning and cabling of the UPS equipment     Because every site 1s unique  this section presents a guide to general procedures and practices that  should be observed by the installing engineer  rather than step by step installation instructions     YN WARNING    Do not apply electrical power to the UPS equipment before the arrival of the commissioning  engineer     YN WARNING    The UPS equipment should
109. or to gain access to the main power switches  SW1 and CBlof a UPS in the  system     Turn the rotary switch to BYPASS position  Rotating any UPS Rotary Switch  SW1  to the  Bypass position will force all UPS modules to Static Bypass    Repeat Steps 1 and 2 for the rest of the units in the system     NOTE    If this operation will be performed on multiple units  the procedures should be performed on  each untt with as little delay as possible     Turn the rotary switch of each unit in the system to TEST  The load is now on maintenance  bypass     Turn the rotary switch of each unit in the system to MAINT     NOTE  The following step will shut off power to the connected load     Open system output breaker  The load will now be disconnected     Open rectifier switch CB1  All operator indicators and messages will turn off as the utility driven  internal power supplies decay     To isolate a module   a  For systems that have UPS input breakers in paralleling cabinet  open the UPS input breaker  for the unit you want to isolate     b  For systems that do not have UPS input breakers in paralleling cabinet  the utility source to  the UPS will need to be opened     9 13 Shutting Down a Multi Module System With System Bypass Switch    l          to PA Se    In the Bypass Cabinet  rotate the system bypass switch to the Bypass position  This will force the  UPS s in the system to Static Bypass     Open the UPS door to gain access to the main power switches  SW1 and CBlof a UPS in the  sy
110. ound      Never work alone  even if all power is removed from the equipment  A second person should  be standing by to assist and summon help in case an accident should occur     CAUTION    This unit complies with the limits for a Class A digital device  pursuant to Part 15 Subpart J  of the FCC rules  These limits provide reasonable protection against harmful interference in a  commercial environment  This unit generates  uses and radiates radio frequency energy and   if not installed and used in accordance with this instruction manual  may cause harmful  interference to radio communications  This unit is not designed for use in a residential area   Operation of this unit in a residential area may cause harmful interference that the user must  correct at his own expense     Battery Cabinet Precautions    The following warning applies to all battery cabinets supplied with UPS systems  Additional warn   ings and cautions applicable to battery cabinets may be found in 3 0   Battery Installation     A    WARNING    Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet   after initial installation      e Battery cabinets contain non spillable batteries    e Keep units upright      Do not stack      Do not tilt    Failure to heed this warning could result in smoke  fire or electric hazard   Call 1 800 543 2378 before moving battery cabinets  after initial installation      GLOSSARY OF SYMBOLS    IN Risk of electrical shock    Indicates cauti
111. ower switches   10kVA TRX     CB1   Utility  Connection  Inside the door   left side              _       SW1   Rotary Switch    Inside the door  near  the center  above the    batteries     The UPS unit power switches are CB1 and SW1     e CB1   Input Isolator  Connects the utility supply to the UPS input     e SWI   Rotary switch  Has four positions   NORMAL  BYPASS  TEST and MAINT   that corre   spond to different positions of the SW1 A B C D     The positions of the rotary switch  SW1  are   e SW1 A   Output Isolator  Connects the output of the UPS to the load   e SW1 B   Neutral Isolator  Connects neutral to the UPS    gt  SW1 C   Bypass Isolator  Connects the UPS with the bypass supply     SW1 D   Maintenance Bypass Isolator  Permits supply of the load directly by the bypass  line for maintenance of the UPS unit     The functions of the rotary switch are shown in Table 24     Table 24 Rotary switch configuration    Rotary  switch OUTPUT   BYPASS   MAINT   NEUTRAL  position    SW1 A     SW1 C     SW1 D     SW1 B     NORMAL O    revenss   wv   wv    w  rest    wv  v  v  want fd  dP      NOTE  Do NOT turn the rotary switch too fast  Allow the rotary switch to stay in each position at least  three seconds before turning it to the next position        74    9 2    9 2 1    Operating Instructions    UPS Start Up    The TRX must be fully installed and commissioned before start up  and external power isolators must  be closed  Once those general conditions are met  the UPS may 
112. p with each unit to connect cabinet frames at posts  two places in the front  and two places in the rear     Service Clearance    Allow front access to the battery cabinet at all times for maintenance and ser   vicing  Electrical codes require that the battery cabinet be installed with no less than 3 feet  1m  of  clearance at the front of the cabinet when operating  Side and rear panels do not require service clear   ance     Cables   Cables may be run between the cabinets through cutouts in the top of the cabinet  eliminat   ing the need for external conduit runs  Route cables before moving cabinets into final position for bolt   ing together  No top or bottom entry cables are required  except for remotely located cabinets which  require conduits  Refer to Figure 15     Software   To allow the UPS to accurately display the battery run time  the number of battery cabi   nets must be noted when performing initial startup and setup using the configuration software  This  1s to be performed by the Technical Services customer engineer when commissioning the unit     Casters and Adjustable Stops   The adjustable stops are not designed to bear the full weight of the  cabinet  Lower the stops until they are finger tight in contact with the floor  Then tighten a small  amount with a wrench  less than two turns  to give a good friction fit  When mounting the battery  cabinet on seismic stands  ensure that the casters are bearing the weight of the cabinet     Battery Support Tray   Be
113. parate conduit from power cables   7  Line side power connections to lugs   1    6AWG per connection for 10 to 15 kVA    1    2AWG per connection for 20 30 kVA to lugs   load side power connections to busbars  see detail   8  Power cables must be sized to limit voltage drop from battery system to UPS to be a maximum 4 VDC  DPN U3813078 Rev  N      NOTE  1  The signal cables in this figure must be shielded and double insulated   2  Connect the Pes  Protection Earth  of the UPS cabinet and BCB box to the same point     37    5 5    5 6    5 7    5 8    5 9    Option Installations    Battery Start    With this option  the TRX UPS can be started with power supplied only by the batteries  at charged  condition   This type of start  in the absence of utility power  allows independent utilization of battery  power and provides for higher availability in some circumstances     AN CAUTION    Before attemptine to start the UPS without utility power present  ensure that the batteries  are fully charged   over 2 1V per cell   and will supply adequate run time to the load     Remote Alarm Monitor    Status and alarm conditions are available on an optional remote alarm monitor  RAM  panel which is  driven by voltfree alarm status contacts  from an optional relay alarm board      Analog Input Interface    At the X6 slot  there are two analog signal channels  Input range is from 0 to  5V  and the precision is  2 percent     ENV T    is used for environment temperature detecting     Power Out
114. play  screen     Figure 22 1 N system block diagram    AS ASS  ad AAA        Lo  _ 4 al    208V 60Hz   208V 60Hz     3 or 4W                                                            8                     4W    a E              UPS1    208V 60Hz  ASE    r                                 EE OOOO    NOTES    1  Install in accordance with national and local electrical codes    2  The equipment ground connection must be connected to the system ground wire   3  UPS AC input and AC output cables must be run in separate conduits    4  Control wiring and power wiring must be run in separate conduits    5  See Electrical Data Specification Sheet U3818101 for individual configurations     32    5 2 3    9 2 4    9 3    9 3 1    9 3 2    9 3 3    9 3 4    Option Installations    Operating Principles  Redundancy Paralleling    The 1 N parallel redundant system can noticeably improve system reliability  In normal condition   none of the UPS modules work at full load  That means that even if the load 1s increased  the system  will not transfer to bypass  And when a UPS module shuts down due to any failure  the remaining  UPS modules can still power and protect the load  When redundancy 1s lost due to module failure or  load increase  the parallel system will trigger an alarm     Operation Modes Summary    The parallel system also has operation modes such as normal  battery  bypass and maintenance  bypass  All UPS modules in the 1 N parallel system operate in coordination       Normal Mode
115. put    The X5 slot can provide power for a modem or an external SNMP card  Available voltage 1s from 9V to  12V  The maximum current is 500mA     IntelliSlot Communication    The TRX has three IntelliSlot ports to allow field installation of optional communication cards  Intel   liSlot cards communicate via the manufacturer s proprietary ESP2 protocol to cards that translate  the information into such protocols as SNMP  IGMnet  Modbus or Jbus  Other cards provide dry con   tact signals for external signaling of operating status     The IntelliSlot communication ports may be installed or removed while the TRX is operating     38    Option Installations    5 10 OC Web Card   SNMP HTTP Network Interface Card    This network interface card provides all real time data and status information as SNMPvl traps for  connection to a 10 100 baseT Ethernet connection  The same card also will transmit the same status  information and all measured parameters for display via a Web browser     Table 8 TRX communication options    On the UPS  Physical Labeled LCD screen  Monitoring  description ID Name under Settings  Devices Baud  of port of Port controlled by  supported rate Comments      Intellislot 1  Top IntelliSlot  On Monitor Board  Comm 1 OCWEB LB   540    Not simultaneous with  MultiLink in RS232 1    Modbus Jbus    Multiport 4  Middle IntelliSlot A it Comm 2 EA    7   On Monitor Board  OCWEB LB 2400 Not simultaneous with  MultiLink in RS232 2    Modbus Jbus   2400  Multiport 4    Int
116. put Neutral Bus                 side view     A A  ETT TA  S  gt  Oo     ee  i Input Output Output Neutral Bus  tt l   Neutral  side view   A fj    EEEE  Power Earth   side view     Battery connections    N     4 1 to battery  4 2 to external battery cabinet    NOTES   1  All dimensions are millimeters    2  Top and bottom cable entry available through removable access plates  Remove  punch to  accommodate conduit size and replace    3  Control wiring and power wiring must be run in separate conduit  Output and input cables must be  run in separate conduit    4  Aluminum and copper clad aluminum cables are not recommended    5  All wiring is to be in accordance with national and local electrical codes     46    Installation Drawings    Figure 34 Location of internal batteries        me 7   11  EA  ler st tal  enema   i i 3    SIE a  Zel  L     47    Installation Drawings    Figure 35 Battery connections    DYNASTY BATTERY    MIDDLE LAYER    TOP LAYER    W501 3pcs    o  te    ZOSM 01 90SM        7   te  W510 to W511    W500 18pc    W504 to W505    W502 to W503 W503 to W502    BOTTOM LAYER    W511 to W510    W507 to W506    W509 to W508    Ss    W505 to W504    CON4    W508 to W509    48    Installation Drawings    Figure 36 Battery cabinet interconnection    am              Refer to Table 11 for key to interconnection          Positive        Midpoint  N   ie Negative                                                         Positive     C   Midpoint  N  E  Negative     C       
117. r stand  Note  If a floor stand is used  the  weight of the unit must be supported under all casters     9  Each mounting location is supported by two 10 GA    135     galvanized steel  The threaded 12mm insert  is approximately 3 4    deep  Mounting bolts must be threaded into unit     10  Includes side panel  Refer to Detail A for dimension to frame with side panel removed  Side panels are  removed between adjacent units that are bolted together     11  Adjustable stops are not designed to carry the full weight of the cabinet  Finger tighten stop against the  floor  then tighten with a wrench less than two turns for friction against the floor     44    Installation Drawings    Figure 31 Dimensions continued   top and bottom views   10mm dia  threaded  mounting holes 4  typ    See Notes 8 and 9 above                 Rear stabiliz   ing foot    100    Air Exhaust    1381    Power Cable  k   Entry Area  Top and  Bottom       025    TOP VIEW    BOTTOM VIEW    Figure 32 Main components   typical unit  Parallel Board  M3     Monitor    Board   U2   IntelliSlot Power    Communication Electronics  Ports  Input  Breaker  Rotary  System Battery  Switch Trays    Input Breaker  Access Plate    Internal and  External Battery  Terminal Block  Access Plate       Eront View   DPN U3812048   with door open  Rev  1    45    Installation Drawings    Figure 33 Cable connections    33  8 AC output cable    connections   l      fi tLe   Bypass AC input cable    4  H             connections    In
118. rs dra da ad A a stilo 88  Rectiner AM PUG Pow r acia iso A a a A a 88  DPO mtermediate CECI A A A AAA A AA Os 88  Merto rotulado 89  Dy Dass tO 2  a Ge honk tne Betas da E ni bisa 89  Torque specifications y a base Bo Nek A A ORES Swe keen REBAR 90  Battery torquetatino seus la ped eas ra Li Ea eee as eee 90  Maintenance bypass cabinet electrical data  single input     20    0 0 0    0c cc eee es 91  Maintenance bypass cabinet electrical data  dual input         0 0 0 0    0 cc cee ee es 92  Multi module bypass cabinet electrical data                o ooooo oooooooo    oo    93  Maintenance bypass cabinet lug SIZES            ee ee ee ee ee eens 94  Battery cabinet physical characteristics     0    0    cc ee eee ee ee eee eee 95  Maintenance Bypass Cabinet WelghtS               ee eee eee ee ees 95  Maintenance bypass cabinet dimensions    95  Multi module paralleling cabinet dimensions    95  Distance to connection points on the TRX UPS         0 0 00  0c eee 96  UPS Slabs Messares   data Reta ee  BS BOS  dda SS  Reatard Se an a oa eee a 97    vi    IMPORTANT SAFETY INSTRUCTIONS    SAVE THESE INSTRUCTIONS    This manual contains important instructions that should be followed during installation of your  Dual Lite Trident   TRX UPS and batteries     Read this manual thoroughly  paying special attention to the sections that apply to your installation   before working with the UPS  Retain this manual for use by installing personnel     A    A    A    A    WARNING    Exercise 
119. s must be correct and the same       The parallel logic cable and load sharing cable must be connected in a ring correctly  see  Figure 23      Cabinet Installation  Parallel system composed of two or more UPS modules using parallel cabinet    The UPS modules that will form the 1 N system should be placed side by side  Each battery cabinet  1s placed next to 1ts corresponding UPS module     The parallel cabinet should be placed in the middle of the system   Preliminary Checks    Each UPS module should have the same rating  the same firmware and the same hardware version   Refer to the instructions in 5 3 1   Conditions for Parallel System     Protective Devices  For each UPS  refer to Table 27  For each system  refer to Table 37     33    Option Installations    5 3 5 Power Cables    Wiring of power cables is similar to that of single module system  See 2 1   Power Cabling   The  bypass sources of all modules should be the same  and the outputs should be connected altogether cor   rectly     Power cables will be supplied by customer  Power cables to the UPS s of the 1 N paralleling cabinet  must be routed through either the top or bottom entry access of the UPS     For systems using a parallel cabinet  see Figures 38 and 40 through 42 for power cable terminations         NOTE  The length and specifications of power cables including the bypass input cables and UPS  output cables should be the same  thus the load can be shared evenly in bypass mode     5 3 6 Parallel Control Ca
120. ssive switching  BYP  XFER COUNT BLOCK   etc     When the user confirms that the fault is cleared     1  Press the FAULT CLEAR button to let the system exit the emergency off state       NOTE   A UPS manufactured before March 2006 may first require a full power down  1 e   manual  opening of the input breakers  for the    Fault Clear    to take effect     NOTE    The rectifier will start again  the battery contactor will close and the bypass will begin to power  the load  The Rectifier indicator  1  flashes while the rectifier is starting up  When the rectifier  enters the normal operation state  about 30 seconds   the rectifier indicator turns green        2  Press the INVERTER ON button  10  on the right side of the operator control panel for longer  than 2 seconds       NOTE  The rectifier will be turned on automatically when the overtemperature fault disappears at  5 minutes after the disappearance of overtemperature signals     After the EPO button is pressed  if the input utility is removed  the UPS will shut down completely   When input utility is returned  if the rotary switch  SW1  is in either Bypass or in Normal position   the UPS will start up on Bypass  There will be power at the output terminals of the UPS     YN WARNING    If the rotary switch is in the Maint  position and input utility is present  there will be power at  the output terminals of the UPS     79    9 9  9 9 1    9 9 2    9 9 3    9 10    Operating Instructions    Battery Protection    Battery Und
121. st be double insulated  Wire should be 20 16AWG stranded    for maximum runs between  2 and 197 feet  25 60m   respectively       NOTE  If BCB interface is connected  a jumper needs to added between Pin 3 and Pin 4     Figure 9 Jumper connection for BCB interface          UPS Monitoring Board       Battery Circuit Breaker    16    Electrical Connections    2 3 4 Output Dry Contacts    There are three output dry contact relays at the X1 slot  see Figure 10 and Table 4      Figure 10 Output dry contacts and EPO wiring for firmware before M170    2 3 5    33  n MN MN T  EE l Goo y         m mM J    EPO H EPO L    O  A   LL  a    Table 4 Output dry contact relays     Position   Name  Description      o    BFP_S  BFP_O  INV_C  INV_S  INV_O  ACF_C  ACF_S  ACF_O        NOTE  All auxiliary cables of terminal must be double insulated  Wire should be 20 16AWG stranded  for maximum runs between 82 and 197 feet  25 60m   respectively     EPO Input   Optional       Firmware Before M200    The UPS has an Emergency Power Off  EPO  function that operates by a button on the control panel  or by a remote contact provided by the user  The EPO button is under a hinged  clear plastic shield     The X2 slot  shown in Figure 10  is the remote EPO input interface  It is active when shorted from   EPO L to EPO H    If an external Emergency Stop facility is required  it is connected terminals EPO L to EPO H of the  auxiliary terminal block  X2   It also is connected to the Normally Open remote stop sw
122. stem     Turn the UPS SW1 to BYPASS position for each module in the system  Repeat Steps 2 and 3 for the rest of the units in the system    Turn the rotary switch of each unit in the system to TEST    Turn the rotary switch of each unit in the system to MAINT     Open rectifier switch CB1  All operator indicators and messages will turn off as the utility driven  internal power supplies decay     To isolate the UPS s  from the bypass cabinet  open the module input and output isolation  breaker s      82    9 14    9 15  9 15 1    9 15 2    9 15 3    9 15 4    9 15 5    Operating Instructions    Commissioning a Parallel System    YN CAUTION    The operations described in this section must be performed by authorized electricians or  qualified technical personnel  If you have any difficult  do not hesitate to contact Technical  Services at 1 800 543 2378     Check the input and output wiring of each UPS module  Ensure that the phase rotation sequence of  the main inputs and the bypass inputs and outputs of each UPS module are the same  Ensure the  parallel cables are connected firmly     It is assumed that the installation is complete  the system has been commissioned by authorized per   sonnel and the external power isolators are closed  Before start up  disconnect the load     Maintenance Bypass Cabinet Operating Procedures  Start Up and Initialization  Follow these steps to start the UPS while connected to the Maintenance Bypass     1  Set Maintenance Bypass switch to the Norm
123. tary switch to TEST  The load is now on maintenance bypass   5  Turn the rotary switch to MAINT     6  Open rectifier switch CB1  All operator indicators and messages will turn off as the utility driven  internal power supplies decay  The unit will power down  but the load will continue to be supplied  by the manual Maintenance bypass     YN WARNING    Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting  to remove the internal protective barriers     YN WARNING    Even with the UPS in maintenance bypass and    Off     portions of the unit are still energized   Service 1s to be performed by qualified personnel only     YN CAUTION    The load equipment is not protected from normal supply aberrations when operating in the  maintenance bypass mode     Powering Down the UPS    To power down the UPS completely  follow the procedures in 9 3   Switching the UPS from Nor   mal to Maintenance Bypass     To completely isolate the UPS from the AC supplies  the main external power input isolator  both 1so   lators  where separate supplies are provided for rectifier and bypass  should be opened  see  Figure 59      YN WARNING    To prevent injury to personnel  lockout or tagout the service supplies     177    Operating Instructions    9 5 Powering Down the UPS and Maintaining Power to Load    NOTE  An external Maintenance Bypass Cabinet must be installed before attempting to perform the    following procedure   If the UPS needs to be shut down completely whi
124. tatus automatically  parallel signaling and communication recovers   output becomes enabled but interlocking works now     10  Turn On inverter and join the parallel system     ZA WARNING    Hazardous Battery Voltage  No operator serviceable parts are located behind covers that require a tool for their removal   Only qualified service personnel are authorised to remove such covers     The UPS battery and connecting terminals remains energized at hazardous voltage levels at  all times  The battery is located behind protective covers that require a tool for their removal   inside the UPS cabinet  inside a free standing battery cabinet or on open racks inside a  dedicated battery room that may be locked     80    9 11    Operating Instructions    Inserting One Module into a Multi Module System    This procedure outlines how to integrate a UPS module that has been previously isolated from other  modules of a group of paralleled UPS modules  It is assumed that the installation is complete  the sys   tem has been commissioned by authorized personnel and the external power isolators are closed     ZA  WARNING    Mains voltage will be applied to UPS output terminals   No operator serviceable parts are located behind covers that require a tool for their removal     Only qualified service personnel are authorised to remove such covers     1  Open the UPS door to gain access to the main power switches     Rotate the switch to Test position  The LCD becomes active    3  Close Input break
125. the TRX  unless used in configurations that include a  Maintenance Bypass Cabinet  If used with a Maintenance Bypass Cabinet  battery cabinets must be   installed on the right side of the UPS  see Figure 1 below     Figure 1 Cabinet arrangement  ALL UNITS VIEWED FROM ABOVE                                                                                                                                                                                                                                                                                                    Jual Lit  Bypass    Battery Battery  Cabinet   Cabinet Cabinet  TRX connected only to MBC TRX connected to Maintenance Bypass Cabinet   MBC must be on left side and Battery Cabinets  of the TRX   MBC must be on left side of the TRX      Battery Cabinets must be on the right side  of the TRX in this configuration                    Battery   Battery  Cabinet Cabinet                                              TRX connected to Battery Cabinets   Battery Cabinets may be on either side  of the TRX     2 0    2 1  2 1 1    Electrical Connections    ELECTRICAL CONNECTIONS    The UPS requires both power and control cabling once it has been mechanically installed  All control  cables must run separate from power cables in metal conduits or metal ducts that are electrically  bonded to the metalwork of the cabinets to which they are connected     YN WARNING    Before connecting input power to the TRX  ensure that you are aware of 
126. the location and  operation of the overcurrent protection devices that connect the UPS input bypass supply to  the power distribution panel     De energize and lockout or tagout all incoming high  and low voltage power circuits before  installing cables or making any electrical connections     Power Cabling  Cable Rating    The main factors affecting the choice and size of cable are voltage  current  also taking into account  overcurrent   room temperature and conditions of installation of the cable     The power cables of the system must be sized with respect to the following description       UPS input cables   The UPS input cables must be sized for the maximum input current  includ   ing the maximum battery recharge current  given in Table 27  with respect to the unit rating and  the input AC voltage     e UPS bypass and output cables   The bypass and output cables must be sized for the nominal  output current  given in Table 27  with respect to the unit rating and the output AC voltage     e Battery cables   Each UPS unit has its own internal batteries factory wired  If connecting an  external battery cabinet  the battery cables must be sized for the battery discharge current at the  end of discharge voltage  as given in Table 27  with respect to the unit rating       NOTE  Table 27 gives nominal currents for determining the size of UPS power cables  Other  important factors to consider include cable route length and coordination with protective  devices     The power cab
127. to the lug using tools and procedures specified by the lug manufacturer   Table 33 Torque specifications    Nut and Bolt CombinationS    Electrical Connections  Grade 2 Standard with Belleville Washers    Bolt Shaft Size    Wire Size or Range   6    4    Circuit Breakers With Compression Lugs  For Power Wiring   Current Rating   on   Nm  Terminal Block Compression Lugs  For Control Wiring    AWG Wire Size orRange   Lbin   Nm        NOTE  Use the values in this table unless the equipment is labeled with a different torque value     Table 34 Battery torque rating    Initial Torque Annual Torque  Battery in lb  N m  in lb  N m   UPS12 100MR 40  4 5  32  3 48     UPS12 140MR 40  4 5  32  3 48  UPS12 200MR 40  4 5  32  3 48  4           5 88     UPS12 370MR 65  7 4  52  5 88  UPS12 475MR 110  12 4  110  12 4     90    Specifications and Technical Data    Maintenance bypass cabinet electrical data  single input     Table 35        oO  C   o   c      p  S           Cabinet    Bypass Cabinet    O  YN   nS  o      Q 0O   gt  gt   Ono       Output  OCP CB Size  A     a  O         z  O       Current Rating  A        Input OCP   O P Voltage    CB Size  A     Current    Max Input    O   lt           208  208  208        O      00  Nps        m  x  i  O  2    125    A     125    125    100    101 125    220  480    125    125    125    208  208  208    150    108    125    125    103    220  240  480    125    125    220  208  208    125    106    220  208  480    100    220  480    480   
128. uit breaker boxes          o ooooooooooor ee eee eens 36  TRA COMMUNICATION ODtIONS ed ots  oi es od Ba eb ida eh A A eee eee eas 39  Relay Card pin CONS UTA ION cs oad che cares AA a ho a IA A AE ed wee eS 42  Relay card jumper configuration    42  Dual Lite supplied interconnect WIVINg    1  ee ee eee ee eas 49  Dual Lite supplied interconnect wiring for Maintenance Bypass Cabinet                   50  Dual Lite supplied interconnect WIVING    1  ee eee eee ee eas 51  Dual Lite supplied interconnect wiring   SlimLine distribution cabinet to TRX              52  Interconnect wiring   1 N Type A connection to TRX             o oooooooooooo momo    53  Interconnect wiring   1 N Type B1 connection to TRX       2 20 0    0  ee ens 54  Interconnect wiring   1 N Type C connection to TRX      0    ens 55  Wimie display statis INOICALOLS Lada bos wd cee SBE AAA AS do seabed okt 61  COMOL O  lt A ma ae eae ERE 62   cons tor mavicaciomkeysS hc heres ain ah dr aa iaa ta da bis 64  Description of items in UPS system WINdO0W          0 0 0  cc cece ee eee eee 64  Descriptions of UPS menus and data window items            0 00  cece ee ee ens 67  UPS operatio modes  pto IE BG Shea IS AS thats BE aoe BE a 73  Rotary switch conh curaio pasgi tine iaa ia Oe Seabed dad 74  Environmental characteristics i  05 03 Gna A Bl OE A A Ga SRE ARSE 86  Mechanical characteristics      e AAA A s 2 la kee ee Ee ee 86  MP terminal socorristas ra tna Sree hace isis oe ls 87  Approved Datter os a repuiratss 
129. ust be between 20  and 80      Command System test This is a self test of the UPS  When the user activates this function  a pop up   start stop window appears about 5 seconds later to show the results        battery  amp  Stop testing Manually stops a battery maintenance test  battery capacity test or system   system test    tests  Freshening Charge Allows a temporary Equalize charge for the batteries  This charge is  configurable for 1 to 36 hours     Stop Freshening Charge Manually stops a Freshening Charge    Modem Auto answer Manually enable the modem s auto answer function   enable   UPS version Provides UPS firmware version numbers for the inverter  rectifier and software  Version display board     UPS model   model Provides UPS model information   for example  208V 60Hz           68    Operator Control and Display Panel    8 11 UPS Status Messages    The TRX displays status changes as they occur in the current status window of the LCD  then  stores that data in the history log  as shown in Figure 53     e Current Status Window  The status messages are displayed chronologically and include the  date and time of the events  Three status messages are visible in the window at a time  To see  other messages  use the navigation keys to scroll up or down the list  A status message remains in  the current status area of the LCD until the status changes  when it is moved to the history log       History Log  When a record moves to the history log  the time the status changed is
130. valid   Disconnect unnecessary load and ensure the safety  In a parallel system  a severe load  sharing error can also leads to the alarm     System Overload    The UPS is confirmed to overload and the overload times out    Note 1  the highest loaded phase will indicate overload timing out first    Note 2  When the timer is active then alarm    unit overload    should also be active as the load is   above nominal    Note 3  When the timer has expired  the inverter Static Switch is opened and the load transferred  Unit Overload Timeout to bypass  The inverter shutdown and will restart after 10 seconds    Note 4  If the load decreases lower than 95  after 5 minutes  the system will transfer back to   inverter mode    Confirm that the alarm is genuine by checking the load percent indicated on the LCD  If an   overload is indicated then check the load  and investigate any additional load connected prior to   the alarm  if applicable      inverernOuereunent The current of inverter IGBT is over limit  If the fault will not reset  contact the manufacturer at  800 543 2378 for assistance     The phase sequence direction of bypass voltage is reversed    Normally  the phase of phase B lags 120 degrees behind phase A  and the phase of phase C lags  Bypass Phase Reversed  120 degrees behind phase B    Verify that the phase rotation of the bypass supply presented to the UPS is correct  and rectify it if   it is found to be in error  Contact the manufacturer at 800 543 2378 for assistance 
131. y Card pin configuration      Pin   Function   Operation         O          O        O          OC   OoOO  UPS Fault Closed if no UPS failure    2 3 Not Used  4 UPS Fault Closed if UPS fails  5 Summary Alarm   Closed if SUMMARY ALARM   occurs    6  Summary larm      Closed if no alarm conditions are preset  pe  Nut CS  9   Common Low Batey     14 Not supported     use External EPO terminal   15 Closed if ON UPS  inverter  power   16 Closed if ON BATTERY power  Utility failure     17 Common   UPS Fault   Summary Alarm  On UPS  On  Battery  On Bypass    18 Closed if not ON Battery power  Utility OK   24 Closed if ON BYPASS  25      A Summary Alarm occurs when any of the following conditions exist    1  Utility power is out of the acceptable range  voltage and or frequency    2  UPS is in BYPASS MODE  load not on Inverter power     3  UPS Battery is LOW    4  UPS fault has occurred        Table 10 Relay card jumper configuration    Number   Connection   Description 222222222222  JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together        ANY JP02 Pin 7 to Pin 17 REMOVE    Interconnects all relay COMMONS and the  not  supported  MODE SHUTDOWN Return    42    Option Installations    5 12 MultiPort 4 Card    The MultiPort 4 card provides four sets of voltage free contact closures for remote monitoring of  alarm conditions UPS operation On Battery and battery low condition  A typical application is to  allow a maximum of four computer systems to simultaneously monitor t
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Benutzerhandbuch  Kodak ULTRA MAX 400  PROBID — Evaluation Pack - Procon Construction Systems  User Manual of the DS-7204HI-VS series Net  User Manual PDF - Heath Consultants  Kodak A-61557 User's Manual  OM, FS700 EX, FS 700 EX, 2010-01  AutoCert + FIX/FAST User Manual  Dell Wyse C10LE  Inspeco e Manuteno de Torres e Postes de Radiocomunicaes    Copyright © All rights reserved. 
   Failed to retrieve file