Data Sheet IB IL AO 1/U/SF

image

Contents

1. I O connector with six terminals using spring IB IL SCN 6 SHIELD 27 26353 cage method and shield connection green w o color print pack of 5 Configuring and Installing the INTERBUS Inline IB IL SYS PRO UME 27 43048 Product Range user manual 5736CC01 PH NIX 15 CONTACT IB IL AO 1 U SF Phoenix Contact GmbH amp Co KG Flachsmarktstr 8 32825 Blomberg Germany TEP 49 0 52 35 3 00 E 49 0 52 35 3 4 12 00 www phoenixcontact com lu PHCENIX CONTACT 5736CC01 O Phoenix Contact 05 2001 Technical modifications reserved TNR 94 24 47 0
2. gt 99 of the final value lt 10 us isat Maximum Error at 23 C 73 4 F Temperature response at 25 C to 55 C 13 F to 131 F Total error of the voltage output 25 C to 55 C 13 F to 0 30 0 60 131 F Offset error gain error linearity error drift error 5736CC01 PH NIX 13 CONTACT IB IL AO 1 U SF Electromagnetic fields Field strength 10 V m acc to IEC 61000 4 3 Fast transients Supply 2 KV output 1 kV acc to IEC 61000 4 4 Conducted interference Class 3 test voltage 10 V acc to IEC 61000 4 6 None The DC DC converter ensures electrical isolation between the logic level and the I O area Common potentials 24 V I O voltage 24 V segment voltage and GND have the same potential FE functional earth ground is a separate potential area Separate system potentials consisting of bus terminal power terminal and I O terminal Test distance Test voltage 7 5 V supply bus logic 24 V supply Unna I O 500 V AC 50 Hz 1 min 7 5 V supply bus logic 24 V supply Uana functional earth ground 500 V AC 50 Hz 1 min 24 V supply I O functional earth ground 500 V AC 50 Hz 1 min Breakdown or dropping of communications Yes I O error message to the bus terminal power U 14 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF Ordering Data Terminal with one analog voltage output IB IL AO 1 U SF 2727776 2 You need 1 connector total for the AO 1 U SF terminal
3. IB IL AO 1 U SF INTERBUS Inline Terminal With One Analog Voltage Output Data Sheet 5736CC01 05 2001 2 This data sheet is intended to be used in conjunction with the Configuring and Installing the INTERBUS Inline Product Range user manual IB IL SYS PRO UM E Function This terminal is used to output analog voltage signals The signals are available with 16 bit resolution Features One analog signal output to connect voltage outputs Actuator connection using 2 wire technology and shield connection Voltage range 0 V to 10 V Process data update including conversion Figure 1 time of the digital analog converter lt 1 ms 5736CC01 PHCENIX CONTACT 5736A001 5736A007 IB IL AO 1 U SF terminal with the connector plugged in Please note that the connector is not supplied with the terminal Refer to the Ordering Data Table at the end of this data sheet to choose the appropriate connector for your application IB IL AO 1 U SF Local Diagnostic and Status Indicators D Ed Bus diagnostics Terminal Assignment Voltage output OVto 10 V a fonu 1222 Notused 18 28 GND Ground Shield Shield connection N gt ONA SA Q AGU SEAS 5736A002 Figure 2 IB IL AO 1 U SF terminal with the appropriate connector Installation Instruction High current flowing through the voltage jumpers Um and Us leads to a temperature rise of the voltage jum
4. alog supply voltage of the terminal U Supply voltage of the module electronics logic supply XXXX Any value ranging from 000016 to FFFFhex 5736CC01 PH NIX 9 CONTACT IB IL AO 1 U SF Response of the Control System or Computer to a Hardware Signal for Different Control or Computer Systems NORM Schneider Automation 0000 On controller boards for Schneider Automation control systems it is possible to set the NORM signal in such a way that the INTERBUS OUT process data word and the analog output keep the last value Response of the Voltage Output to a Control Command of the INTERBUS Controller Board STOP Keep last value Keep last value ALARM STOP reset Keep last value Keep last value 10 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF Technical Data Housing dimensions width x height x depth 12 2 mm x 120 mm x 71 5 mm 0 480 in x 4 724 in x 2 795 in Connection type of the actuators Permissible temperature operation Permissible temperature storage transport 25 C to 85 C 13 F to 185 F Permissible humidity operation 75 on average 85 occasionally IS Ranging from 25 C to 55 C 139F to 131 F Appropriate measures against increased humidity gt 85 must be taken Permissible humidity storage transport 75 on average 85 occasionally 2 For a short period slight condensation may appear on the housing if for example the terminal is brought into a closed room from a vehicle Permis
5. function areas Connection Always connect the analog actuator using shielded twisted pair cables Connect one end of the shielding to protective earth ground PE At the module fold the outer cable sheath back and connect the shield to the terminal via the shield connector clamp The clamp connects the shield directly to FE functional earth ground on the module side When using cables longer than 10 m 32 8 ft in environments with heavy noise we recommend connecting the shield through an RC element to the FE potential of the actuator Typically the capacitor C should be rated between 1 and 15 nF The resistor R should be at least 10 MW 4 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF Connection Example I Use a connector with shield connection when installing the actuator Figure 5 shows the connection schematically without shield connector N QD O D O g O Oo Bo On 5736A004 Figure 5 Typical actuator connection using 2 wire technology and shield connection 5736CC01 PH NIX 5 CONTACT IB IL AO 1 U SF Programming Data Doos Dre 025a Input address area 0 bytes Output address area 2 bytes Parameter channel 0 bytes PCP Register length bus INTERBUS Process Data Words I The process data input word is not used Assignment of the Terminal Points to the Process Data Output Word INTERBUS james a eaaeo PP EEE e Byte bit Byte Bye gt view pti le
6. pers and the inside of the terminal Note the following instruction to keep the current flowing through the voltage jumpers of the analog terminals as low as possible All of the analog terminals need a separate main circuit If this is not possible in your application and if you are using analog terminals in a main circuit together with other terminals make sure you are placing the analog terminals behind all the other terminals at the end of the main circuit Please note the derating curve on page 12 2 PH NIX 5736CC01 CONTACT Internal Circuit Diagram Key INTERBUS OPC ee UANA tm REF B N 24 V Us 2 9 di 24 V Uy U U ear E P DN I 5736A003 Figure 3 Internal wiring of the terminal points 5736CC01 PHOENIX CONTACT IB IL AO 1 U SF INTERBUS protocol chip Optocoupler DC DC converter with electrical isolation Reference voltage Amplifier Digital analog converter Analog output Analog ground electrically isolated from ground of the voltage jumper Other symbols are explained in the IB IL SYS PRO UM E user manual IB IL AO 1 U SF Electrical Isolation INTERBUS n ne INTERBUS local bus IN Bus interface local bus OUT OPC IK U 7 5 V DC IE mm U 7 5 V DC FE Unn 24 V DC Unna 24 V DC x A B I O interface Electrical isolation between area A and area B Analog output 5736A008 FE potential Figure 4 Electrical isolation of the
7. s 4 ls 2 1 Jo fr le fs Ja ls 2 h Jo Terminal Signal Terminal point 1 1 Voltage output points Signal reference Terminal point 1 3 Shield FE Terminal point 1 4 6 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF INTERBUS OUT Process Data Output Words The process data output word specifies the output value in each cycle Process data word KCIKCI ES ETA DI ECO ECD RECS ER 55620006 Figure 6 Process data output word AV Analog value MSB Most Significant Bit LSB Least Significant Bit All output values are displayed with 16 bit resolution 5736CC01 PHGNIX 7 CONTACT IB IL AO 1 U SF Significant Values in the Process Data Word Voltage output OVto 10 V Process data word Hex Binary two s complement Analog value V MSB LSB 15141312 1110 9 8 7 6 5 4 3 2 1 0 10Vminus2GS 9 99969 FFE 1 1 1 1 1 4 1 1 4 1 1 4 1 1 4 0 HalfFVOR 5 0000 8000 1 0 0 0 0 0 0 0 Of 0 o of of of 0 tas 10158mV 0001 0 0 0 0 0 O o 0 0 0 of Of Of of Zero 0 0000 0000 0 0 o o o o o o o o o o o o o o Abbreviations used QS Quantization Step s MSB Most Significant Bit FVOR Final Value of the Output Range LSB Least Significant Bit 8 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF Output Behavior of the Voltage Output gt Take output behavior in the event of an error into account when planning your system Bus in stop state Uana 24 V 0 V or keep last value Uana An
8. sible air pressure operation 80 kPa to 106 kPa up to 2000 m 6562 ft above sea level Permissible air pressure storage transport 70 kPa to 106 kPa up to 3000 m 9843 ft above sea level Degree of protection IP 20 according to IEC 60529 Class of protection Class 3 according to VDE 0106 IEC 60536 Mechanical Demands Shock test 15g load for 11 ms half sinusoidal wave according to IEC 60068 2 27 three shocks in each space direction and orientation 25g load for 6 ms half sinusoidal wave three shocks in each space direction and orientation INTERBUS interface Data routing 5736CC01 PH NIX 11 CONTACT IB IL AO 1 U SF Current consumption from UL local bus Approx 30 mA typical 40 mA maximum I O supply voltage Uana 24 V DC Current consumption of UANA 15 mA typical 20 mA maximum Total power consumption Approx 585 mW typical method Potential routing 60 55 50 45 40 35 30 25 20 15 10 Ty PC 0 2 4 6 8 10 A 5736A009 Ty C Ambient temperature C A Current flowing through the voltage jumpers Um and Us A 12 PH NIX 5736CC01 CONTACT IB IL AO 1 U SF Number Signals resolution in the process data word quantization Voltage Oto 10 V 0 to 9 99985 V 0 153 mV LSB Measuring value representation 1 INTERBUS cycle depending on the bus time of the digital analog converter configuration lt 1 ms Slew rate