Home
        PCS 4000 Single Well Controller User Guide
         Contents
1.    you may want to set B DELAY TIME  See    B DELAY  TIME    on page 13 for more information     6 The controller counts down the DELAY TIME  SALES    SET 02  while monitoring the casing pressure  flow  rate  or both     Note  DELAY TIME  SALES  is the maximum time the   well is allowed to stay open after the plunger arrives    The controller responds to the first input to close the   well  The close input may be      Casing pressure     see step 7      Low flow rate     see page 12      Critical flow K factor     see page 12      DELAY TIME  SALES  countdown reaches zero      see page 13      Another close input unrelated to casing pressure   low flow rate  critical flow K factor  or time  For  example  low or high sales line pressure  a manual  input to close the well  and so on     7 Casing pressure normally drops while the plunger  rises  When the casing pressure starts to build  the  controller monitors the increase in pressure  When  the increase equals the DIFFERENTIAL CLOSE  PRESSURE  DIP  value  the controller goes to step 8   Usually  a minimal increase in pressure  such as 1 or 2  psi  is desirable     8 The controller counts down the DELAY CLOSE TIME   SET 08   When the DELAY CLOSE TIME countdown  reaches zero  the controller checks the casing  pressure again to see if it has still increased by the  DIFFERENTIAL CLOSE PRESSURE  DIP  value     If the increase is a brief spike in pressure  the   controller continues the DELAY TIME  SALES    countdown  The controller
2.   H   high sales line pressure input  a L  low sales line pressure input    M   manual close    O   open time ran out    S increase in casing pressure input    U  drop in casing pressure input    CLS information shows      How long the A valve was closed  E A letter that explains why the A valve opened       C   CLOSE TIME counted down to zero   a D differential open pressure input    M   manual open    R  load factor input   a T   casing time input            Note  If the A valve opens because a close input stops   there is no letter  For example  the A valve closes in  response to a close input caused by low or high sales line  pressure  When the sales line pressure returns to normal   the A valve opens  The CLS information does not include  a letter     Operating Mode Report     READ 11  The controller   s operating mode    E TIME MODE  mode 1    m TUBING LINE MODE  mode 2    E CASING TUBING MODE  mode 3   m CASING LINE MODE  mode 4     For more information  see    How Pressure Operation  Works    on page 7     Battery Status Report      READ 00  This report displays the current voltage of the battery and  the solar panel     Example   BATTERY   7 00V  SOLAR   9 24V    Sensor Status      READ 09  This report shows whether the sensor is ON or OFF     Note  The sensor must be ON to read the sensor input     When using the Time operating mode  you can set the  sensor to OFF  PCS recommends setting the sensor to off  only if you are not running a plunger     Software Version R
3.  2  Check sensor   1 Press ON   2 Run a steel wrench along the back of the sensor     If the controller goes to DELAY TIME  SALES   the  sensor is OK     If the controller does not go to DELAY TIME   SALES   call your PCS sales and service  representative     Test 3  Check sensor alignment    1 Realign the sensor by 90 degrees   Example  If the sensor is aligned on the north or south  side  realign it on the east or west side    2 If realigning the sensor does not solve the problem  call  your PCS sales and service representative    Short term fix for the sensor problem  Use the CASING   DROP PRESSURE feature  see page 12      Plunger has surfaced  but Plunger Travel Time History   READ 06  shows C instead of A or B    E Make sure sensor is turned on  Press READ 09  The  controller   s display should show SENSOR  ON     If the display shows SENSOR  ON  go to Test 1     If the display shows SENSOR  OFF  press SET 09  and then press ON  Go to Test 3  step 2     Test 1  Check CASING DROP PRESSURE    1 Press READ 20    2 Make sure the CASING DROP PRESSURE is high  enough that the plunger surfaces before the pressure  is reached  For instructions  see page 12   If the CASING DROP PRESSURE is set correctly  go to  Test 2     Test 2  Check controller by disconnecting the sensor   1 Disconnect the sensor from the sensor and ground  terminals on the inside of the controller   s faceplate   2 Press ON  The controller should count down the OPEN  TIME     If the controller goes from OPEN
4.  Check sensor alignment    1 Realign the sensor by 90 degrees   Example  If the sensor is aligned on the north or south  side  realign it on the east or west side    2 If realigning the sensor does not solve the problem  call  your PCS sales and service representative    Short term fix for the sensor problem  Use the CASING   DROP PRESSURE feature  see page 12      Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    Plunger has surfaced  but Plunger Travel Time History   READ 06  shows NO PLUNGER instead of a travel time    Make sure sensor is turned on  Press READ 09  The  controller   s display should show SENSOR  ON      f the display shows SENSOR  ON  go to Test 1     If the display shows SENSOR  OFF  press SET 09  and then press ON  Go to Test 2  step 2     Test 1  Check controller by disconnecting the sensor   1 Disconnect the sensor from the sensor and ground  terminals on the inside of the controller   s faceplate   2 Press ON  The controller should count down the OPEN  TIME     If the controller goes from OPEN TIME to DELAY  TIME  SALES   the controller   s circuit board is not  working properly  Call your PCS sales and service  representative     If the controller does not go to DELAY TIME   SALES   continue with the next step   3 Use a wire to short the sensor and ground terminals   The controller is OK if it goes to DELAY TIME  SALES    4 Reconnect the sensor to the terminals  Make sure the  wires are put back in correctly     Test
5.  TIME to DELAY  TIME  SALES   the controller   s circuit board is not  working properly  Call your PCS sales and service  representative      f the controller does not go to DELAY TIME   SALES   continue with the next step   3 Use a wire to short the sensor and ground terminals   The controller is OK if it goes to DELAY TIME  SALES    4 Reconnect the sensor to the terminals  Make sure the  wires are put back in correctly     Test 3  Check sensor   1 Press ON   2 Run a steel wrench along the back of the sensor     If the controller goes to DELAY TIME  SALES   the  sensor is OK      f the controller does not go to DELAY TIME   SALES   call your PCS sales and service  representative     Test 4  Check sensor alignment    1 Realign the sensor by 90 degrees   Example  If the sensor is aligned on the north or south  side  realign it on the east or west side    2 If realigning the sensor does not solve the problem  call  your PCS sales and service representative    Short term fix for the sensor problem  Use the CASING   DROP PRESSURE feature  See page 12      Solenoid  Shift Valve  Problems    Solenoid  shift valve  does not operate at any time or does  not operate at night   If the solenoid does not operate at night  the solar panel  may be powering the controller during the day     Test 1  Check fuse   1 With a screwdriver  move the power switch to off  see  page 3    2 Remove the controller   s faceplate   3 Remove the fuse from its yellow casing     Ifthe fuse is defective  repla
6.  This may save wear  and tear on the plunger     If the casing pressure drops by the specified value  the  controller starts the DELAY TIME  SALES  countdown  even if it does not receive an input from the arrival sensor     1 Note the casing pressure at the moment when the  A valve opens  for example  400 psi     2 Note the casing pressure when the plunger surfaces   for example  300 psi     3 Set the CASING DROP PRESSURE to the difference  between these 2 values  400     300   100   Add an  additional 10 15 psi  for example  115 psi     The additional 10 15 psi makes sure the plunger surfaces  before the CASING DROP PRESSURE is reached  If   the CASING DROP PRESSURE replicates a plunger  arrival too closely  it may be reached before the plunger  surfaces  The Plunger Travel Time History then shows a C  when the CASING DROP PRESSURE is reached     Example   LAST PLUNGER  0  C 0 10 20    The C in the example above shows that the CASING  DROP PRESSURE was reached after 10 minutes and 20  seconds of OPEN TIME  and B OPEN TIME  if any   The  plunger did not surface during that time or the arrival  sensor malfunctioned  Test the sensor  If it is OK  the  CASING DROP PRESSURE may need to be increased     If you are not using CASING DROP PRESSURE  set it to  0 psi     B DELAY TIME     SET B2  B DELAY TIME is normally set to 00 00 00     For those few wells that have liquid trailing behind the  plunger  you may want to set a few seconds of B DELAY  TIME to let the liquid clear out of
7.  a The element should be free from dirt  oil  and so on     Check for cracks in the solar panel     Check whether the solar panel is shaded during any  part of the day  If it is  position it so it receives the  most sunlight each day     N    USER GUIDE    4 Check the solar panel wire connection    5 Make sure the power switch is on  The controller   s  display should be on    6 If the solar panel tests good  but the batteries are not  lasting as long as they should  call your PCS sales and  service representative     Test 4  Check solenoid  shift valve     1 Press ON    2 Ifthe solenoid won   t open  clean the supply hoses and  puck inside the solenoid valve    3 Retest    4 lf they are good  replace the puck or the entire  solenoid     Transducer Problems    Display shows transducer reading of 0 psi   The surge protector or transducer may be defective  or   the transducer wire may have been completely cut    1 Re calibrate the transducer  See    Calibrating the  Transducers    on page 8    2 If the transducer won   t hold the calibration  change the  controller to Time Mode  Press SET 11 and enter 1    3 Call your PCS sales and service representative     Display shows fluctuating or false transducer reading   The transducer wire may be defective    1 Re calibrate the transducer  See    Calibrating the  Transducers    on page 8    2 If the transducer won   t hold the calibration  change the  controller to Time Mode  Press SET 11 and enter 1    3 Call your PCS sales and servi
8.  be reached     LOAD FACTOR     SET 24   LOAD FACTOR is a feature used with Mode 2  tubing   pressure minus line pressure  or Mode 4  casing pressure   minus line pressure   Load Factor helps insure that the   liquid load in the tubing is less than the energy needed to   lift the load to surface  When Load Factor is enabled  the   controller will not open the well until 2 set points are met      The controller compares the line pressure to the tubing  pressure  Mode 2  or the casing pressure  Mode 4     E In both modes  the controller compares casing  tubing   and line pressures as a ratio to determine the net lifting  energy  See the calculation below     When both set points and all other    open    criteria are met   the controller opens the well to production     A well   s load factor is the ratio of casing pressure minus  tubing pressure to casing pressure minus line pressure     LOAD FACTOR   Casing Pressure   Tubing Pressure  Casing Pressure   Line Pressure       If you set the LOAD FACTOR to 50  the controller opens  the A valve when the ratio is 50  or lower  and the other     open    criteria have been met      Example        Casing Pressure   Tubing Pressure   100 psi        Casing Pressure   Line Pressure   500 psi   m 100 500   20    E If the LOAD FACTOR is set to 20  or a lower value   the controller opens the A valve     Normal values for LOAD FACTOR range from 40  to  60  depending on the well   s individual characteristics     If you are not using LOAD FACTO
9.  controller by disconnecting the sensor   1 Disconnect the sensor from the sensor and ground  terminals on the inside of the controller   s faceplate   2 Press ON  The controller should count down the OPEN  TIME     If the controller goes from OPEN TIME to DELAY  TIME  SALES   the controller   s circuit board is not  working properly  Call your PCS sales and service  representative     If the controller does not go to DELAY TIME   SALES   continue with the next step   3 Use a wire to short the sensor and ground terminals   The controller is OK if it goes to DELAY TIME  SALES    4 Reconnect the sensor to the terminals  Make sure the  wires are put back in correctly     Test 3  Check plunger   1 Check whether the plunger is stuck in the lubricator   2 If the plunger is not stuck in the lubricator  go to Test 4     Test 4  Check the sensor   1 Remove the sensor from the wellhead   2 Press ON     If the controller counts down the OPEN TIME  go to  step 3      f the controller goes straight into DELAY TIME   SALES   there is a short  Either the wire going  to the controller is bad  or the sensor must be  replaced  Go to step 5   3 Hold the sensor in your hand  and move a steel wrench  through the sensor band     If the controller goes to DELAY TIME  SALES   the  problem may be a wellhead electrical current     Go to step 4     USER GUIDE    4 Possible causes of a wellhead electrical problem     The sensor or sensor wire may be defective  or    The well may need PCS newest style 2 
10.  goes back to step 7      f the increase is an actual or solid pressure   increase  the controller goes back to step 1     7    Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    CALIBRATING THE TRANSDUCERS    Pressure operation uses pressure transducers   E Casing transducer  SET 16    E Tubing transducer  SET 17    H Sales line transducer  SET 18     You must calibrate all pressure transducers being used     Transducers may be wired to the controller and calibrated  using the controller  or they may report information to the  controller over a wireless connection     Important  Sales line information is available on the  electronic flow measurement  EFM  device  Sales line  information can also be obtained from a transducer you  may want to install  There may be mitigating reasons to  install a    Line Pressure    transducer     Calibrate Transducers Wired to the Controller    Casing Transducer Calibration   1 Calibrate the casing transducer for the low pressure     With transducer in place  remove pressure     Press SET 16  ON  OFF  OFF  ON     2 Calibrate the casing transducer for the high pressure     Apply pressure to the transducer     After applying pressure  measure with an accurate  pressure gauge to obtain the pressure value for the  next step     Press SET 16  ON  OFF  ON  enter the pressure  value     For example  if the current casing pressure is 200 psi   enter 00200     Tubing Transducer Calibration   1 Calibrate the tubing tr
11.  great in this situation  See     CASING PEAK TIME    on page 11     Features for Closing the A Valve    In addition to the basic functions for intermitting a well  with pressure operation  you can use any of the features  for closing the A valve  For more information  see      Features for Closing the A Valve    on page 12     Features for Special Circumstances    CASING DROP PRESSURE     SET 20   Because the well does not have a plunger  the controller  can   t start the DELAY TIME  SALES  when the plunger  surfaces during OPEN TIME or B OPEN TIME  Instead   the controller monitors the casing pressure  When the  casing pressure drops by the CASING DROP PRESSURE  value  the controller starts the DELAY TIME  SALES   countdown     To specify the CASING DROP PRESSURE  follow these  instructions     1 Note the casing pressure at the moment when the  A valve opens  Example  A well  intermitting without a  plunger into a 100 psi sales line and trying to produce  1 barrel of water each cycle  should have a beginning  casing pressure near 400 psi     2 Note the casing pressure when the fluid hits surface   Example  300 psi     3 Set the CASING DROP PRESSURE to the difference  between these 2 values  Example  100 psi     The Plunger Travel Time History shows a C when the  CASING DROP PRESSURE is reached     Example   LAST PLUNGER  0  C 0 10 20    The C in the example above shows that the CASING  DROP PRESSURE was reached after 10 minutes and 20  seconds of OPEN TIME  and B OPEN TIME 
12.  if any      Sales Line Safeguard Features    Follow the plunger instructions for    Sales Line Safeguard  Features    on page 13 to program these functions    LOW LINE CLOSE PRESSURE   SET 15   m HIGH LINE CLOSE PRESSURE   SET 14   m DELAY LINE CLOSE TIME   SET B8   m DELAY TIME  SALES    SET 02    TROUBLESHOOTING    If you have a problem with the controller  try these  troubleshooting tips  If they don   t solve the problem  call  your PCS sales and service representative     Controller Display Problems    Controller won   t turn on or controller   s display is blank  The controller never sleeps  The display should never be  blank while the controller is on   1 With a screwdriver  move the power switch to off  see  page 3    2 Wait a few seconds and then move the power switch  back to on   If the display remains blank  go to Test 1     Test 1  Check fuse   1 With a screwdriver  move the power switch to off   2 Remove the controller   s faceplate   3 Remove the fuse from its yellow casing     Ifthe fuse is defective  replace it with a 5 amp  250  volt fuse  The controller   s box contains 1 extra fuse   When you are done  replace the controller   s  faceplate and move the power switch to on     Ifthe fuse is OK  go to Test 2     Test 2  Check battery and wire connection    The battery life is approximately 1 to 3 years    The controller has a safety feature  If the battery voltage is   low  the controller closes the motor valve and shuts in    1 Check the battery voltage wit
13.  pressure     CASING PEAK TIME     SET 21  CASING PEAK TIME is normally set to 99 00 00 when the  feature is not used     When you use this feature  the controller opens the  A valve after the casing pressure peaks  The controller  monitors the casing pressure independently of the  DIFFERENTIAL OPEN PRESSURE  The controller counts  down the CASING PEAK TIME  It restarts the countdown  whenever the casing pressure increases by 1 psi     For example  the CASING PEAK TIME is 10 minutes   When the A valve closes  the controller counts down  the CASING PEAK TIME  If the casing pressure builds  1 psi within 10 minutes and the FALL TIME has reached  zero  the controller restarts the CASING PEAK TIME  countdown  If the casing pressure does not build 1 psi  within 10 minutes  the controller counts down the  CASING PEAK TIME to zero  It then checks the FALL  TIME countdown  It opens the A valve when both the  CASING PEAK TIME and FALL time countdowns have  reached zero     Note  While the controller counts down the CASING PEAK  TIME  the display shows CLOSE 0 00 00     Typical CASING PEAK TIME values for a well with casing  pressure that builds fast are 10 12 minutes  For a well  with casing pressure that builds slowly  a typical value is  30 minutes     USER GUIDE    Note  You can use both DIFFERENTIAL OPEN PRESSURE  and CASING PEAK TIME to control the well  If you want  to use only CASING PEAK TIME to open the well  set the  DIFFERENTIAL OPEN PRESSURE to a high value that will  never
14.  sales and  service representative     Controller   s display is scrambled   Static electricity may have made the controller lose its   place in the program cycle    1 Reset the controller  With a screwdriver  move the  power switch to off  see page 3   Wait a few seconds  and then move the power switch back to on    2 If the display is still scrambled after this test  call your  PCS sales and service representative     Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    Program Cycle Problems    Controller won   t run program cycle or won   t open motor  valve  1 Press READ 14 to check the HIGH LINE CLOSE  PRESSURE  Make sure the pressure is set above the  well   s     Expected casing peak pressure and    Normal high line pressure  2 Goto Test 1     Test 1  Check transducer and transducer wire    The controller   s display must show values for the 2   pressures specified by the operating mode    1 Check the transducers    calibration  If necessary   re calibrate the transducers  See    Calibrating the  Transducers    on page 8    2 Ifa transducer won   t hold the calibration     Change the controller to Time Mode  Press SET 11   and enter 1     Call your PCS sales and service representative     Test 2  Check battery and wire connection    The battery life is approximately 1 to 3 years    The controller has a safety feature  If the battery voltage is   low  the controller closes the motor valve and shuts in    1 With a screwdriver  move the po
15.  the dump valve on the  separator     When the B DELAY TIME is set and when the plunger  arrives during the B OPEN TIME countdown  the  controller delays closing the B valve by starting the   B DELAY TIME countdown  When the countdown reaches  zero  the controller closes the B valve and starts the  DELAY TIME  SALES  countdown     Sales Line Safeguard Features    LOW LINE CLOSE PRESSURE     SET 15   If the sales line pressure reaches this low value  the  controller prevents the A valve from opening and closes  the A valve if it is open  If you don   t want the controller  to monitor low sales line pressure  set LOW LINE CLOSE  PRESSURE to 0 psi     HIGH LINE CLOSE PRESSURE     SET 14   If the sales line pressure reaches this high value  the  controller prevents the A valve from opening and closes  the A valve if it is open  You can use HIGH LINE CLOSE  PRESSURE to shut in the well when the line pressure  increases to the point where the plunger will not surface     Venting  If the HIGH LINE CLOSE PRESSURE is reached  during B OPEN TIME  which is used to vent the well  the  controller does not close the B valve     USER GUIDE    DELAY LINE CLOSE TIME     SET B8   If you are using HIGH LINE CLOSE PRESSURE  LOW  LINE CLOSE PRESSURE  or both  you can use DELAY  LINE CLOSE TIME to keep the controller from shutting   in the well if there is a brief spike or drop in sales line  pressure  Brief spikes in pressure often occur when the  controller opens the well after an extended shut 
16. 0  the controller closes the  well as soon as the casing pressure flutters up  Because  the casing pressure is still falling  the controller has closed  the well too soon     DELAY CLOSE TIME     SET 08   This time ensures that the casing pressure increase is not  a brief spike in pressure  During the level period before  the casing pressure starts to build  the pressure may  flutter up and down  The controller delays closing the  A valve to make sure that the casing pressure has not  dropped again     If you set DIFFERENTIAL CLOSE PRESSURE  DIP  to  1  2  or 3 psi  set DELAY CLOSE TIME to 10  20  or 30  seconds     Important  Don   t set the DELAY CLOSE TIME to 00 00 00   If you do  the controller may close the well too soon  while  the casing pressure is still falling  A good minimum DELAY  CLOSE TIME is 10 30 seconds     Features for Opening the A Valve    CLOSE TIME     SET OFF   CLOSE TIME is normally set to 00 00 00 because the  controller opens the A valve in response to changes in  pressure     If you want to open the A valve after a period of time   regardless of pressure changes  you can set the CLOSE  TIME  If you do program a CLOSE TIME  make sure to set  the time no lower than your FALL TIME  This will ensure  that the plunger has time to reach the bottom of the  tubing before the controller opens the A valve     If the controller opens the well when the CLOSE TIME  countdown reaches zero  you are using the controller to  operate the well based on time instead of
17. 0 gjefy And Solar Conditions     Valve Delay  Sales  Time  Mandatory Shut In Time  Plunger Fall Time  Delay Close Time  Sensor Status  On or Off   Auxillary Close Delay   On   No Delay or Off   Close Delay   Controller Operating Mode  Differential Open Pressure  Casing Tubing or Casing Line  Casing PSI Increase  Casing Dip  Close  High Line Pressure Close  Low Line Pressure Close POWER  Activate and Calibrate Trans  1 Casing    Activate and Calibrate Trans  2 Tybing    Current  well status    Casing Drop  CasinePeak Build Time    Equalize Time   C Valve    Scan   Set Entire Prograi  Power Nes    On Off    B Valve Open and Close Times  Line Delay Times   PLUNGER HISTORY  Press  READ  Function Key    Reads reports  and function  values    Press  SET  Function Key  CE   A Valve Plunger and Valve Counts  Plunger Travel Times  Last 25  Avg  Run  A Valve Open and Close Times    A amp B Plunger and Valve Counts  Plunger Travel Times  Last 25   Open and Close Times  Last 10     THIS PCS CONTROLLER IS MANUFACTURED BY PCS  INC    1998    Figure 1     Controller   s Faceplate     gt      PCSplungerlift com    DISPLAY STATUS    CLOSE  C315 7250 L150    HRS MIN SEC                PATENT NO 6 196 324 B1       Time remaining  in hrs  min  sec     When A valve is closed     Casing pressure     Tubing pressure     Line pressure   When A valve is open      Casing pressure     Flow rate     Line pressure    Opens A valve    Closes A valve and  B valve    Used with other keys   to access functio
18. 500 and 1000 feet per minute    E If the plunger is running fast  lower the DIFFERENTIAL  OPEN PRESSURE    E If the plunger is running slow  increase the  DIFFERENTIAL OPEN PRESSURE     OPEN TIME     SET ON   OPEN TIME is when the well is first opened and gas is  flowing through the A valve  motor valve   During OPEN  TIME  the plunger starts to surface and the well sells its  initial head gas     B OPEN TIME     SET B ON Optional   B OPEN TIME is after the well has sold its initial head gas   but the plunger has not arrived  During B OPEN TIME    the plunger surfaces with the liquid load it is carrying   Typically  gas during B OPEN TIME is vented to the low  side of the separator or to a tank     If you are not using a B valve  set B OPEN TIME to  00 00 00             Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    MANDATORY SHUT IN TIME      SET 03 Optional   This time is used when a plunger does not surface   Usually  after the A valve and B valve are opened  but a  plunger does not surface  a well likely needs more time to  rebuild pressure for the next plunger attempt     Set the MANDATORY SHUT IN TIME to at least twice  the time required to build enough pressure to surface  the plunger  For example  if a well usually takes 2 hours  to build enough pressure to surface the plunger  set  MANDATORY SHUT IN TIME to 4 hours or more     Note  The MANDATORY SHUT IN TIME must be greater  than FALL TIME  and CLOSE TIME  if any   If the plunge
19. E   96 shows that the A valve opened 96 times    m A PLUNGER2  92 shows that the plunger arrived 92  times while the A valve was open    m 96 92 4  The plunger did not arrive 4 times while the  A valve was open     Note  If the well has a B valve  this report shows 2 A valve  counts for each B valve count in the B Valve and Plunger  Counts History  If the plunger did not arrive 4 times while   the A valve was open  the plunger may have arrived up to  2 times while the B valve was open     B Valve and Plunger Counts History      READ B4   This report shows how many times the B valve opened   and how many times the plunger arrived while the B valve  was open     Example   B PLUNGER  2  B VALVE   2    In the example      B VALVE   2 shows that the B valve opened 2 times    m B PLUNGER  2 shows that the plunger arrived 2 times  while the B valve was open     A Valve Total Time Report      READ 07   This report shows 2 times of up to 999 hrs   59 min   59   sec  accumulated since the report was last cleared    Em Total OPEN TIME and DELAY TIME  SALES     E Total time that the controller was closed  MANDATORY  SHUT IN  if any   FALL TIME  if any   and CLOSE TIME  are accumulated under TOT CLS time     Example   A TOTAL 16 31 13  TOT CLS 8 12 45    B Valve Total Time Report      READ B7   This report shows 2 times of up to 999 hrs   59 min   59   sec  accumulated since the report was last cleared    Em Total B OPEN TIME    Total time that the controller was closed  MANDATORY  SHUT I
20. N  if any   FALL TIME  if any   and CLOSE TIME  are accumulated under TOT CLS time     Example   B TOTAL 1 24 32  TOT CLS 8 12 45    ol      Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    Clearing Report Values      SET 10  The display shows   ZERO ALL TOTALS   ON YES OFF NO    Press the ON button to clear all of the valve and plunger  counts  READ 04 and READ B4  and total times  READ 07  and READ B7      This option does not clear the Plunger Travel Time History   READ 06  and the Time Open and Closed History  READ  19   History information is always available     Note  Press the OFF button to exit the Clearing Report  Values function without clearing any of the report values     Time Open and Closed History      READ 19   This report provides information about the last 10 times   the A valve was open  and the last 10 times the A valve   was closed      OPN O and CLS 0 show the most recent open and  close information      OPN 1 and CLS 1 show the 2nd most recent open and  close information       OPN 9 and CLS 9 show the 10th most recent open  and close information     Example   OPN O0 0 00 20 00  CLS 0 C 00 15 00    OPN information shows   m How long the A valve was open  Time Open includes     OPEN TIME    DELAY TIME  SALES     DELAY CLOSE TIME  if any   Time Open does not include B OPEN TIME  if any    E A letter that explains why the A valve closed     F   low flow rate input or critical flow K value input    G   switch gauge input  
21. OPEN TIME 9  CLOSE TIME OFF CLOSE TIME 11  DELAY TIME  SALES  02 A DELAY TIME 13  MANDATORY 03 MAND  SHUT IN 10  SHUT IN TIME  B OPEN TIME BON B OPEN TIME 9  B DELAY TIME B2 B DELAY TIME 13  FALL TIME 05 FALL TIME 9  DELAY CLOSE TIME 08 DELAY CLOSE TIME 10  Sensor Operation 09 SENSOR  9  SET SENSOR  A Valve Location 60 VALVE A LOCATION none   local or remote   B Valve Location 61 VALVE B LOCATION none   local or remote   C Valve Location 62 VALVE C LOCATION none   local or remote   Operating Mode 11 1  TIME 2  T L 9  3 C T 4 C L  DIFFERENTIAL 12 OPEN PRESSURE 9  OPEN PRESSURE  DIFFERENTIAL 13 CLOSE PRESSURE 10  CLOSE PRESSURE   DIP   HIGH LINE CLOSE 14 HIGH LINE PRES  13  PRESSURE  DELAY LINE CLOSE B8 LINE DELAY TIME 13  TIME  LOW LINE CLOSE 15 LOW LINE PRES  13  PRESSURE  CASING DROP 20 CASING DROP PRS  12  PRESSURE  CASING PEAK TIME 21 CASING TIME 11  LOW FLOW RATE 23 MIN  FLOW RATE 12  LOAD FACTOR 24 LOAD FACTOR 11  CRITICAL FLOW K 25 TURNER CRIT 12  FACTOR FLOW CONSTANT  EFM Device Setup 31 READ REMOTE 9  FLOW  READ ACCUM  FLOW  SELECT EFM TYPE  Flow Rate Unit of 33 METRIC 3  Measurement  B LOW FLOW RATE 35 B LOW FLOW RATE 12  B LOW FLOW 36 B LOW FLOW 12  DELAY TIME DELAY       CONTROLLER REPORTS    Plunger Travel Time History      READ 06   This report provides information about the 25 most recent  plunger travel times  The first display shows the number  of times the plunger surfaced and the average travel time     Example   GOOD RUNS  25  AVE  0 08 22    Use the READ b
22. PRESSURE OPERATION TO  INTERMIT A WELL WITHOUT A PLUNGER    The fastest way to program the time and pressure  functions is to press SET 90  See    SET 90 Program  Function List    on page 4     Pressure Operation Selection Functions    Follow the plunger instructions for    Pressure Operation  Selection Functions    on page 9 to program these  functions    E Operating Mode   SET 11     Sensor Operation   SET 09   E Transducer Calibration   SET 16  SET 17  and SET 18  m  EFM Device Setup   SET 31   E Status of A Valve when B Valve Is Open   SET BO  Note  Make sure the SENSOR  SET 09  is ON  Don   t turn  it off     Pressure Operation Control Functions    FALL TIME     SET 05  Set FALL time to 00 00 00     FALL TIME is not needed because there is no plunger     MANDATORY SHUT IN TIME     SET 03  Set MANDATORY SHUT IN TIME to 00 00 00     MANDATORY SHUT IN TIME is not needed because there  is no plunger     Other Functions   Follow the plunger instructions for    Pressure Operation  Control Functions    on page 9 to program these functions   DIFFERENTIAL OPEN PRESSURE   SET 12   OPEN TIME   SET ON   B OPEN TIME   SET B ON   DIFFERENTIAL CLOSE PRESSURE  DIP    SET 13  DELAY CLOSE TIME   SET 08    Features for Opening the A Valve    In addition to the basic functions for intermitting a well  with pressure operation  you can use any of the features  for opening the A valve  For more information  see      Features for Opening the A Valve    on page 11     Tip  CASING PEAK TIME works
23. R  set it to 00 percent     Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    Features for Closing the A Valve    LOW FLOW RATE     SET 23   If you want the controller to close the A valve when the  sales line   s flow rate falls below a specified value  set  the LOW FLOW RATE  For example  if you set the LOW  FLOW RATE to 300  the controller closes the A valve  when the flow rate falls below 300 mcf  This function  keeps the flow rate from dropping to the point where  liquids fall back into the tubing     You can use this function by itself or together with  CRITICAL FLOW K FACTOR     PCS provides a Microsoft   Windows   critical flow  calculator program to help calculate LOW FLOW RATE  and CRITICAL FLOW K FACTOR values for your well   For more information  call your PCS sales and service  representative     Note  If you have metric  SET 33  on  the flow rate unit of  measurement is thousand cubic meters  E  M        CRITICAL FLOW K FACTOR     SET 25   If you want the controller to close the A valve when   the sales line   s flow rate falls below a critical flow rate  computed with Turner   s equation  you can set both the  LOW FLOW RATE and the CRITICAL FLOW K FACTOR   The K factor is a gas constant that allows for fluctuating  sales line pressures  These 2 functions together keep  the flow rate     in combination with fluctuating sales line  pressure     from dropping to the point where liquids fall  back into the tubing     Example    E 
24. REPORT AND PROGRAM FUNCTION  REFERENCE    The tables in this section cross reference the reports and  program functions described in this User Guide                                                                                            Reports  Report READ Page  Software Version Report CE 6  Battery Status Report 00 6  Status of A Valve when B Valve Is Open BO 9  A Valve and Plunger Counts History 04 5  B Valve and Plunger Counts History B4 5  Plunger Travel Time History 06 5  A Valve Total Time Report 07 5  B Valve Total Time Report B7 5  Valve Plunger Counts History  Total Time 10 5  Reports  and Plunger Travel Time History  Time Open and Closed History 19 6  Modbus Address Report 22   Clearing Report Values  Program Function SET Display Name Page  Clearing Report 10 ZERO ALL TOTALS 6  Values          Program Functions    READ 90 Program Function List   Press READ 90 to display the current times  pressures   and flow rate values programmed for all functions listed in  the table on the right side of this page     SET 90 Program Function List  Press SET 90 to program all functions listed in the table  on the right side of this page     Additional Program Function  To program this function  press SET B 0   To display its current value  press READ B 0                             SET or  Program Function READ Display Name Page  Status of A Valve BO A OPEN W  B VAL  9    when B Valve Is Open              gt       SET or  Program Function READ Display Name Page  OPEN TIME ON A
25. Set the CRITICAL FLOW K FACTOR to 65506    E Set the LOW FLOW RATE to 300 mcf    E The controller closes the A valve when the flow rate  falls below 300 mcf or the critical flow K factor falls  below 65506     B LOW FLOW RATE     SET 35   If you want the controller to open the B valve during  A OPEN TIME when flow rate falls below a specified  value  set the BLOW FLOW RATE     Example    m Set the BLOW FLOW RATE to 50      The controller opens the B valve when the flow rate  falls below 50 mcf     B LOW FLOW DELAY TIME     SET 36   If you are using BLOW FLOW RATE  you can use B LOW  FLOW DELAY TIME to keep the controller from opening  the B valve if there is a brief drop in flow rate     Typical settings for BLOW FLOW DELAY TIME are 1 to 2  minutes     Features for Special Circumstances    CASING DROP PRESSURE     SET 20   CASING DROP PRESSURE is used in these 3 situations      The wellhead configuration affects the plunger travel  into the lubricator  The plunger arrives but the plunger  arrival sensor can   t sense the plunger arrival every  time  Use CASING DROP PRESSURE as a backup       A well is intermitted without a plunger  CASING DROP  PRESSURE allows the well to flow if it unloads    E The plunger arrival sensor malfunctions  and the  operator does not have an immediate replacement   Use CASING DROP PRESSURE as a temporary fix     Note  If the arrival sensor malfunctions  the CASING  DROP PRESSURE function prevents the B valve from  opening if the well is unloading 
26. USER GUIDE    PCS 4000      SINGLE WELL CONTROLLER    CONTENTS    Basic Operatloins scisc secceceanecteceecdtecsnsessscsncesecsseensctaseeeess  Controllers Faceplate s str tssis  Turning the Controller On and Off    eeeeeeseeeeneeeeeees  Status  DIS play  aeina te ceetucesveseied Havbiecneutes state deities  Units of Measurement              ccccsceceessseseceeeeeseeeesseenenees  Operating the A Valve and B Valve Manually                  Reading Reports and Program Functions    s     Setting Program FUNCTIONS                ccssecessereeeserenssees    How Pressure Operation WOrkKS               eeccesseeeeeeeeeeees 7    Calibrating the Transducers           ccssssecccesseseeeteeeeeeeeeeee  Calibrate Transducers Wired to the Controller                   Calibrate Transducers Reporting Wireless to the  Controlle eisssiicsssicceecaierececeaxscnstucessusevedsavontendbeeoapaenteateens    Turn Off a Transducer             eeeeeeseeeeeceeeeeeeeeeeeeeseeeeeeesenees 8    Creating a Pressure Operation Plunger Program          Pressure Operation Selection Functions           a f PRODUCTION  G     CONTROL  Sew ee  SERVICES      2008 Production Control Services  Inc     Pressure Operation Control Functions           c ceeee 9  Features for Opening the A ValVe          eeseeeesrereeeees 11  Features for Closing the A ValVe sereen 12  Features for Special Circumstances    12  Sales Line Safeguard Features             cccsecsesereseeeees 13    Using Pressure Operation to Intermit a Well wit
27. ansducer for the low pressure     With transducer in place  remove pressure     Press SET 17  ON  OFF  OFF  ON     2 Calibrate the tubing transducer for the high pressure     Apply pressure to transducer     After applying pressure  measure with an accurate  pressure gauge to obtain the pressure value for the  next step     Press SET 17  ON  OFF  ON  enter the pressure  value     For example  if the current tubing pressure is 200 psi   enter 00200            Sales Line Transducer Calibration  If the sales line transducer is wired directly to the  controller     1 Calibrate the sales line transducer for the low pressure     With transducer in place  remove pressure     Press SET 18  ON  OFF  OFF  ON     2 Calibrate the sales line transducer for the high   pressure      Apply pressure to transducer      After applying pressure  measure with an accurate  pressure gauge to obtain the pressure value for the  next step      Press SET 18  ON  OFF  ON  enter the pressure  value     For example  if the current sales line pressure is 50 psi   enter 00050     Calibrate Transducers Reporting Wireless to the  Controller    Casing Transducer and Tubing Transducer Calibration  1 Set the transducer for remote operation     Casing transducer   Press SET 16  ON  ON     Tubing transducer   Press SET 17  ON  ON     2 Calibrate the transducer at the remote device     Sales Line Transducer Calibration  1 Set the sales line transducer for remote operation     Press SET 18  ON  ON     2 Calibrate th
28. ce it with a 5 amp  250  volt fuse  The controller   s box contains 1 extra fuse   When you are done  replace the controller   s  faceplate and move the power switch to on     Ifthe fuse is OK  go to Test 2     Test 2  Check battery and wire connection    The battery life is approximately 1 to 3 years    The controller has a safety feature  If the battery voltage is   low  the controller closes the motor valve and shuts in    1 Check the battery voltage with a volt meter    Replace the battery if it is below 6 volts    Check the battery wire connection    Replace the controller   s faceplate    With a screwdriver  move the power switch to on    Check whether the solenoid is operating properly      If the solenoid is now operating properly and if you  replaced the battery  check the manufacture date  on the battery  If the battery is less than 3 years old   check the solar panel  Go to Test 3      If the solenoid still does not operate  go to Test 4     ak wh    Test 3  Check solar panel   1 Disconnect the solar panel from the terminals  Use a  volt meter to obtain the voltage and amperage  A good  solar panel reading in full sun exposure is 10 7 volts  and 350 430 mA   If the solar panel is defective  change it   3 Check the solar panel installation     The solar panel should face south     The tilt of the solar panel should be the latitude  of the location plus 15 degrees  Example  if the  latitude is 45 degrees  tilt the solar panel 60 degrees  with respect to the horizon  
29. ce representative     PREVENTIVE MAINTENANCE    Battery  Always replace the controller   s battery when it is 3 years  old     Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    You can get more information about the PCS  products at  ProductionControlServices com        Ig   PRODUCTION     CONTROL        SERVICES    3771 Eureka Way  Frederick  CO 80516  1 800 619 2241    Warranty  Production Control Services  Inc  warrants all PCS manufactured equipment to be free of defects in material and workmanship for ONE YEAR from  date of purchase by original buyer only  Warranty is completely void if abuse  neglect  misuse or misapplication is the cause of the malfunction  Determination  of abuse or damage to be made solely by PCS     PCS 4000    is a trademark of Production Control Services  Inc     Copyright   2008 Production Control Services  Inc   All rights reserved  5 22 08    
30. coil  sensor  This sensor is available in 2 wire or 3 wire  connections   5 Call your PCS sales and service representative   Short term fix for the sensor problem  Use the CASING  DROP PRESSURE feature  see page 12      Plunger has surfaced  but OPEN TIME does not go to DELAY    TIME  SALES   E Make sure sensor is turned on  Press READ 09  The  controller   s display should show SENSOR  ON     If the display shows SENSOR  ON  go to Test 1      f the display shows SENSOR  OFF  press SET 09  and then press ON  Go to Test 2  step 2     Test 1  Check controller by disconnecting the sensor   1 Disconnect the sensor from the sensor and ground  terminals on the inside of the controller   s faceplate   2 Press ON  The controller should count down the OPEN  TIME     If the controller goes from OPEN TIME to DELAY  TIME  SALES   the controller   s circuit board is not  working properly  Call your PCS sales and service  representative      f the controller does not go to DELAY TIME   SALES   continue with the next step   3 Use a wire to short the sensor and ground terminals   The controller is OK if it goes to DELAY TIME  SALES    4 Reconnect the sensor to the terminals  Make sure the  wires are put back in correctly     Test 2  Check sensor   1 Press ON   2 Run a steel wrench along the back of the sensor     If the controller goes to DELAY TIME  SALES   the  sensor is OK      f the controller does not go to DELAY TIME   SALES   call your PCS sales and service  representative     Test 3 
31. e is either  thousand cubic feet  mcf  or thousand cubic meters   E8M        USER GUIDE    Operating the A Valve and B Valve Manually    Open the A Valve     ON  E Press ON     ON overrides all programmed functions such as FALL  TIME and MANDATORY SHUT IN TIME     ON does not override safeguard functions such as  LOW LINE CLOSE PRESSURE and HIGH LINE CLOSE  PRESSURE     Open the B Valve      B ON  E Press B ON     Close the A Valve  and B Valve if Used       OFF  E Press OFF     OFF overrides all programmed functions such as OPEN  TIME and DELAY TIME  SALES      Reading Reports and Program Functions    Read a Report or the Value of a Single Program Function  1 Press READ     The status display shows   READ     2 Enter the number of the report or function you want to  display  Example  10     Read the Values of All Program Functions      READ 90  For a list of the program functions  see    READ 90  Program Function List    on page 4     Setting Program Functions    Set a Single Program Function  1 Press SET     The status display shows   SET    2 Enter the number of the function you want to set   Example  05     3 Enter the value for the function  See    Units of  Measurement    on this page     To exit the function without changing its value  press  CE     Set All Program Functions      SET 90    For a list of the program functions  see    SET 90 Program  Function List    on page 4     3    Y4TIOYULNOD TIIM ATINIS OOOV S  d    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    
32. e sales line transducer at the remote  device     Important  If you are using an EFM device  follow the  instructions for calibrating the sales line transducer in  the manual for setting up your EFM device     Turn off a Transducer    If you are not using a transducer  you can turn it off       To turn off the casing transducer  press SET 16  OFF       To turn off the tubing transducer  press SET 17  OFF       To turn off the sales line transducer  press SET 18  OFF     When you turn off a transducer  it appears on the status  display with a pressure value of 0     CREATING A PRESSURE OPERATION  PLUNGER PROGRAM    The fastest way to program the time  pressure  and flow  functions is to press SET 90  See    SET 90 Program  Function List    on page 4     Pressure Operation Selection Functions    Operating Mode     SET 11   Set the operating mode  which specifies the 2 pressures  that the controller uses for the DIFFERENTIAL OPEN  PRESSURE set point       Mode 2  tubing pressure minus sales line pressure       Mode 3  casing pressure minus tubing pressure   m Mode 4  casing pressure minus sales line pressure    Sensor Operation      SET 09  1 Set SENSOR to ON     2 Specify local  OFF  or remote  ON  operation of sensor     Transducer Calibration      SET 16  SET 17  and SET 18  See    Calibrating the Transducers    on page 8     EFM Device Setup     SET 31  If you are using an electronic flow measurement  EFM   device     1 Select ON YES for READ REMOTE FLOW     2 Select ON YES 
33. eport      READ CE  This report displays the chip and software version  numbers     Example  VERSION 138 41    Modbus Address Report      READ 22  This report displays the controller   s modbus address     Example  MODBUS ADDR 005    Important  Do not change the modbus address     HOW PRESSURE OPERATION WORKS    When set to a pressure operating mode  the controller  opens the A valve based on the difference between 2  pressure values  The pressure values used are      Mode 1  Time only input  no pressure      Mode 2  Tubing pressure minus sales line pressure  m Mode 3  Casing pressure minus tubing pressure   m Mode 4  Casing pressure minus sales line pressure    Note  When set to Mode 1 or time mode  the controller  opens and closes the A valve and B valve based on time  input  It does not respond to pressure input or flow rate  input     Here are the steps in the pressure operation cycle     1 The controller closes the A valve and counts down the  FALL TIME  SET 05   This gives the plunger time to fall  to the bottom of the well  The status display shows  CLOSE 0 00 00     Note  CLOSE TIME is normally set to 00 00 00 because  the controller opens the A valve in response to  changes in pressure     2 While the A valve is closed  the casing pressure and  tubing pressure rise     3 The controller monitors     Tubing pressure minus line pressure differential in  Mode 2    Casing pressure minus tubing pressure differential  in Mode 3    Casing pressure minus line pressure differe
34. for READ ACCUM FLOW if you want  the controller to display Yesterday   s Gas Volume and  Today   s Accumulated Volume  The controller will store  the daily volumes for 30 days  If you select OFF NO   the controller will not store this information     3 Select the type of EFM device you are using     ON CMI for an EFM device provided by PCS    OFF TR485 for a third party EFM device connected  to the controller through a TR485 circuit board    Status of A Valve when B Valve Is Open     SET BO  The controller works on wells that require the A valve to  be either open or closed when the B valve is open    m To keep A valve open when B valve is open  press ON   m To close A valve when B valve is open  press OFF     USER GUIDE    Pressure Operation Control Functions    FALL TIME     SET 05  FALL TIME guarantees a minimum shut in time for the  plunger to fall to the bottom of the well     DIFFERENTIAL OPEN PRESSURE     SET 12  DIFFERENTIAL OPEN PRESSURE is the pressure value  that must be reached before the controller opens the  A valve  See step 3 on page 7     The 2 pressures that determine the DIFFERENTIAL OPEN  PRESSURE vary depending on the mode of operation    E Mode 2  tubing pressure minus sales line pressure   m Mode 3  casing pressure minus tubing pressure   E Mode 4  casing pressure minus sales line pressure    Choose an appropriate value for your well by adjusting   the DIFFERENTIAL OPEN PRESSURE based on the   plunger travel time  The optimal plunger speed is between   
35. h a volt meter    Replace the battery if it is below 6 volts    2 Check the battery wire connection    Replace the controller   s faceplate    4 With a screwdriver  move the power switch to on      f the display is still blank  call your PCS sales and   service representative    5 If the controller   s display is now working and if you  replaced the battery  check the manufacture date on  the battery  If the battery is less than 3 years old  check  the solar panel  Go to Test 3     wo    USER GUIDE    Test 3  Check solar panel   1 Disconnect the solar panel from the terminals  Use a  volt meter to obtain the voltage and amperage  A good  solar panel reading in full sun exposure is 10 7 volts  and 350 430 mA   2 Ifthe solar panel is defective  change it   3 Check the solar panel installation     The solar panel should face south     The tilt of the solar panel should be the latitude  of the location plus 15 degrees  Example  if the  latitude is 45 degrees  tilt the solar panel 60 degrees  with respect to the horizon    a The element should be free from dirt  oil  and so on      Check for cracks in the solar panel      Check whether the solar panel is shaded during any  part of the day  If it is  position it so it receives the  most sunlight each day    4 Check the solar panel wire connection    5 Make sure the power switch is on  The controller   s  display should be on    6 If the solar panel tests good  but the batteries are not  lasting as long as they should  call your PCS
36. hout a    a E cccseescieeuntedecteoetenrienenines 14  Pressure Operation Selection Functions    14  Pressure Operation Control Functions                 cceee 14  Features for Opening the A ValVe          eeseeeerereeeees 14  Features for Closing the A ValVe          eceeeseeeeesreteenees 14  Features for Special Circumstances    14  Sales Line Safeguard Features    ccceseeeseereeeenees 14   Troubleshooting vseiestcccectisececie res cceaicc nde estenncteectesteeeneresiaes 15  Controller Display Problems                seccssseeeesereneeeees 15  Program  Cycle  Problems asirini 16  Solenoid  Shift Valve  ProbleMS            cceeceeeeeeneeeees 19  Transducer Problems ssteissi catessevanevartvecneae ccetaarnans 19   Preventive Maintenance       cccssseesssesssessseeenseenensene 19    ProductionControlServices com    44TIOULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    BASIC OPERATIONS    Controller   s Faceplate    Figure 1 shows the controller   s faceplate with the power on off switch  status display  keypad  and serial port for local    operator input     Ci     PRODUCTION CONTROL SERVICES  INC   CS 1 800 619 2241    4000    OPERATING INSTRUCTIONS  READ B 30  Serial Number  Read CE  Version Number  MANUAL VALVE CONTROL  ON Open A Valve  Sales   OFF Close A  amp  B Valves  BON Open B Valve  Vent   PROGRAM AND READ SETTIN  PROGRAM Press  SET  Function Key  READ Press  READ  Function   ON A Valve Open Time  OFF Close Time  BON B Valve Open Time   0
37. in period     When the controller opens the A valve  it does not  monitor the sales line pressure during the DELAY LINE  CLOSE TIME period     Example      DELAY LINE CLOSE TIME is set at 6 minutes    m When the controller opens the well and starts to count  down the OPEN TIME  there is a 3 to 5 minute spike in  line pressure      For the first 6 minutes of the OPEN TIME countdown   the controller does not shut in the well even if the  HIGH LINE CLOSE PRESSURE is reached    E After 6 minutes  the controller shuts in the well if the  high line condition still exists     DELAY TIME  SALES      SET 02  DELAY TIME  SALES  sells gas through the A valve after  the plunger has arrived     Set DELAY TIME  SALES  to the maximum time that you  want to sell gas     Example  A well normally sells gas for 5 hours  Set DELAY  TIME  SALES  to 6 hours     If you want to limit how long the well flows after a plunger  arrival for any reason  program DELAY TIME  SALES      Important  You must set the DELAY TIME  SALES   The  controller closes the A valve in response to the first     close    input  DIFFERENTIAL CLOSE PRESSURE  DIP    LOW FLOW RATE  CRITICAL FLOW K FACTOR  or  DELAY TIME  SALES   If DELAY TIME  SALES  is 00 00 00   the controller closes the A valve when the plunger arrives   In pressure operation  you want the controller to close the  A valve in response to pressure or flow rate input     Y4TIOYULNOD TIIM ATINIS OOOV SOd    PCS 4000 SINGLE WELL CONTROLLER    USER GUIDE    USING 
38. ns that  control B valve   Example  B ON opens  B valve    Clears current entry  and backspaces    Sets program functions    Local operator input  LOI   serial port for connection  to laptop computer    Turning the Controller On and Off    To turn the PCS 4000 Single Well Controller on or off   insert a screw driver into the slot marked POWER ON   OFF  See Figure 1     Move the toggle switch to the left to turn the controller on     Move the toggle switch to the right to turn the controller  off     The plunger program does not run while the controller is  off  When you turn the controller on  it closes the A valve  and starts counting down the FALL TIME  see step 1 on    page 7      Status Display    After you turn the PCS 4000 Single Well Controller on  the  status display remains on  The controller never sleeps     The first line of the status display shows the current well  status and the time remaining     When the A valve is closed  the second line of the status  display shows the casing pressure  tubing pressure  and  sales line pressure     Example   CLOSE 0 00 00  C315 T250 L150    When the A valve is open  the second line shows the  casing pressure  flow rate  and sales line pressure     Example   A OPEN 0 14 22  C315 Fi23  L150    Units of Measurement    Time is in hours minutes seconds   Example  08 15 00   Pressure is in pounds per square inch  psi    Example  00100    Depending on the setting of the METRIC function  SET  33   the unit of measurement for flow rat
39. ntial in  Mode 4    The controller opens the A valve when      The difference between the 2 pressures is equal  to or greater than the DIFFERENTIAL OPEN  PRESSURE  SET 12  value  see    DIFFERENTIAL  OPEN PRESSURE    on page 9   and     The FALL TIME countdown reaches zero     If the DIFFERENTIAL OPEN PRESSURE value is  reached during the FALL TIME countdown  the status  display shows the FALL TIME remaining     Note  You can use any    open    function together with or  in place of DIFFERENTIAL OPEN PRESSURE  After the  FALL TIME countdown has reached zero  the controller  opens the A valve as soon as it receives input from any     open    function  For more information  see    Features  for Opening the A Valve    on page 11     USER GUIDE    4 The controller opens the A valve and counts down the  OPEN TIME  SET ON       f the plunger arrives during the OPEN TIME  countdown  the controller goes to step 6     If the plunger does not arrive during the OPEN TIME  countdown  the controller goes to step 5     5 The controller opens the optional B valve and counts   down the B OPEN TIME  SET B ON       If the plunger arrives during the B OPEN TIME  countdown  the controller goes to step 6       f the plunger does not arrive during OPEN TIME or  B OPEN TIME  the controller closes the A valve and  B valve and counts down the MANDATORY SHUT   IN TIME  SET 03   When this countdown reaches  zero  the controller goes to step 4     Note  If the well has liquid trailing behind the plunger
40. r  does not surface  MANDATORY SHUT IN TIME replaces  FALL TIME  MANDATORY SHUT IN TIME is not in addition  to FALL TIME     If you are not using MANDATORY SHUT IN TIME  set it to  00 00 00     DIFFERENTIAL CLOSE PRESSURE     DIP      SET 13 Optional   After the plunger surfaces  the casing pressure falls and  then levels off  The casing pressure then starts to build  as liquids accumulate at depth  The higher you set the  DIFFERENTIAL CLOSE PRESSURE  DIP   the longer the  well attempts to sell gas     Example  During an operation cycle  the controller records   the well   s minimum casing pressure at 150 psi    E If the DIFFERENTIAL CLOSE PRESSURE  DIP  is 3 psi   the controller stops the sale of gas and closes the well  when the casing pressure rises to 153 psi    E If the DIFFERENTIAL CLOSE PRESSURE  DIP  is 10  psi  the controller stops the sale of gas and closes the  well when the casing pressure rises to 160 psi     A good DIFFERENTIAL CLOSE PRESSURE  DIP  setting  for many wells is 1  2  or 3 psi     The casing pressure flutters up and down as it falls   For example  the casing pressure may go  160  159   160  159  158  159  158  157  158  157  156 psi  To  keep the controller from closing the well too soon  use  DIFFERENTIAL CLOSE PRESSURE  DIP  together with  DELAY CLOSE TIME  see below      Important  A good minimum DIFFERENTIAL CLOSE  PRESSURE  DIP  is 1 psi  If you set the DIFFERENTIAL  CLOSE PRESSURE  DIP  to 0 psi and the DELAY CLOSE  TIME  see below  to 00 00 0
41. utton to scan through the report     The next 25 displays show the 25 most recent plunger   travel times    Em This example shows the most recent plunger run  The  plunger surfaced after 8 minutes and 15 seconds of  OPEN TIME    LAST PLUNGER  0  A 0 08 15   Em This example shows the 2nd most recent plunger run   LAST PLUNGER  1  A 0 08 15   m This example shows the 25nd most recent plunger run   LAST PLUNGER 24  A 0 08 15   m This example shows the most recent plunger run  The  plunger surfaced after 10 minutes and 40 seconds of  OPEN TIME and B OPEN TIME    LAST PLUNGER  0  B 0 10 40   m This example shows the most recent plunger run  The  CASING DROP PRESSURE was reached before the  plunger arrived    LAST PLUNGER  0  c 0 09 26     This example shows the most recent plunger run  The   plunger did not surface   LAST PLUNGER  0  NO PLUNGER          To exit the report at any display  press CE     Valve Plunger Counts History  Total Time Reports  and  Plunger Travel Time History      READ 10   This reporting option displays the 2 Valve and Plunger  Counts Histories  READ 04 and READ B4   the 2 Total  Time Reports  READ 07 and READ B7   and the Plunger  Travel Time History  READ 06   To display the next report   press READ     A Valve and Plunger Counts History      READ 04   This report shows how many times the A valve opened   and how many times the plunger arrived while the A valve  was open     USER GUIDE    Example   A PLUNGER  92  A VALVE   96    In the example      A VALV
42. wer switch is on  The controller   s   display should be on    If the solar panel tests good  but the batteries are not   lasting as long as they should  call your PCS sales and   service representative     Test 4  Check solenoid  shift valve      1  2    Press ON    If the solenoid won   t open  clean the supply hoses and  puck inside the solenoid valve    Retest    If they are good  replace the puck or the entire  solenoid     Test 5  Check gas supply pressure  filter  and regulator s      1    2  3    Check the gas supply pressure to the motor valve   The recommended supply pressure is 25 35 psi  If  the pressure is too low or too high  it will not open the  motor valve    Check the filter and regulator s  for debris and ice    If the controller is still not working properly  call your  PCS sales and service representative     After CLOSE TIME has counted down to zero  controller   goes directly to DELAY TIME  SALES        Press READ 06 to check the Plunger Travel Time  History  If the display shows a few seconds of plunger  travel time  such as A 0 00 03  the controller went  through the opening and closing part of the program  even though the plunger did not arrive     Test 1  Check the sensor wire connections    1 Ifa wire was spliced in because of the distance  between the controller and the sensor  check the  connection where the wire was spliced  The wire may  be corroded and causing a short    2 If the sensor wire connections are good  go to Test 2     Test 2  Check
43. wer switch to off  see  page 3     2 Remove the controller   s faceplate    Check the battery voltage with a volt meter    Replace the battery if it is below 6 volts    Check the battery wire connection    Replace the controller   s faceplate    With a screwdriver  move the power switch to on    Check whether the controller is operating properly       f the controller is now operating properly and if you  replaced the battery  check the manufacture date  on the battery  If the battery is less than 3 years old   check the solar panel  Go to Test 3       f the controller still won   t run the program cycle or  open the motor valve  go to Test 4     o    NOOR    Test 3  Check solar panel     1    Disconnect the solar panel from the terminals  Use a   volt meter to obtain the voltage and amperage  A good   solar panel reading in full sun exposure is 10 7 volts   and 350 430 mA    If the solar panel is defective  change it    Check the solar panel installation     a The solar panel should face south      The tilt of the solar panel should be the latitude  of the location plus 15 degrees  Example  if the  latitude is 45 degrees  tilt the solar panel 60 degrees  with respect to the horizon      The element should be free from dirt  oil  and so on      Check for cracks in the solar panel      Check whether the solar panel is shaded during any  part of the day  If it is  position it so it receives the  most sunlight each day    Check the solar panel wire connection    Make sure the po
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
votre sécurité et celle d`autrui sont très importantes informations  Grandstream Networks, Inc.  Wiley AutoCAD 2009 & AutoCAD LT 2009 All-in-One Desk Reference For Dummies  Peavey SP 2G User's Manual  Kingston Brass HBAHK26124785 Installation Guide    owners manual    Copyright © All rights reserved. 
   Failed to retrieve file