Home

ST Series User Manual

image

Contents

1. Trickle Charge to the battery is always present When the battery voltage is below the LVD re connect voltage lt 9V and the mains power is available the battery will be charging at 1 2A When the battery voltage sufficient gt 9V the LVD will connect the battery and allow float charging at 5A 10A ST20 ST35 This feature is provided to allow very flat batteries to be charged at a rate which will extend their life External Input Voltage This provides an alternative option for powering of the load and float charging of the batteries when mains voltages are not present This input is to be powered by a suitable 12V system ie CAR or SOLAR cells with regulator When operating via the external input current and voltage control for the battery must be provided from the external source The ST20 35 does not provide battery current limit or voltage control when operating in this configuration Suitable fuse protection must be provided for this input Protection the power supply provides automatic protection for overload including short circuit over voltage over temperature and reverse connected battery In such instances the Fault indicator will illuminate and the power supply will shut down It will attempt to automatically restart every 5 seconds until such case that the fault is removed Fusing Each load circuit and the battery have been fused to provide fault protection and discrimination Refer to servicing section for max
2. ST Series POWER SUPPLIES USER INSTRUCTIONS Batteries When using batteries with this product always consult with the battery manufacturer for a detailed description of the installation use and maintenance of the battery manufactures specific batteries This product is suitable for charging 12V lead acid batteries Charging current is limited to 5A ST20 and 10A ST35 CAUTION Ensure that there is good ventilation from the battery area Ensure that cable connections to batteries have the correct polarity and are protected against accidental short circuit Ensure that the shrouding supplied with the battery is fitted to the terminals Provide visual notification that batteries are being used in area of use Before servicing a battery disconnect the power supply Batteries are electrically alive at all times and must be treated with extreme caution They can supply high short circuit currents even if they appear damaged Take care that dropping our touching of metal objects onto the battery cell does not cause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury Servicing Personnel This product contains hazardous voltages and energy hazards which can result in death or injury Only properly qualified service personnel may service it There are no internal user serviceable parts Only the fuses located in the fuse panel located on
3. the front panel are serviceable Isolate mains power Vext and battery before servicing Replacement of Fuses Only the DC output Load and Battery fuses may be replaced Fuse ratings Load fuses 20A max Battery Fuse 35A max Fuse types 32V Automotive Bussmann ATC series or Littelfuse 257 series or equivalent Page 5 of 7 Issue F ST Series POWER SUPPLIES USER INSTRUCTIONS Specification Input Voltage ST20 220 240Vac nominal 10 50 60Hz ST35 230 240Vac nominal 10 50 60Hz The power supply will withstand a 5 minute 15 surge on the maximum nominal voltage Input Surge lt 40A cold start Holdup Time gt 10mS at full load current and over nominal input voltage operating range Output Current ST20 20A Continuous load battery current ST35 35A Continuous load battery current Factory Set Voltage 13 65V 0 1V Load Regulation lt 2 Output Ripple lt 100mV Voltage Over Voltage lt 17V Protection Over Current Protection ST20 20A to 25A load battery current ST35 35A to 38A load battery current Battery Current Limit 5A 1A ST20 10A 1A ST35 Battery Disconnect Connect 11 65 0 3V Input Mains not present Connect gt 9 0V Input Mains present Disconnect 10 5 0 3V Hysteresis 1 1V typ Battery Trickle 1 2A Charge Battery Drain LVD closed lt 250mA 12V LVD open lt 10mA 12V
4. Efficiency ST20 gt 84 ST35 gt 88 Ambient 0 C 50 C Weight lt 2kg Standards Safety EN60335 1 amp EN60335 2 29 EMC EN55022 class B Compliance OCEI ACA RCM Page 6 of 7 Issue F ST Series POWER SUPPLIES USER INSTRUCTIONS Electromagnetic compatibility EMC Electromagnetic compatibility EMC is defined as the ability of a device equipment or system to function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetic disturbance to anything in that environment Switch mode power supplies are good generators of EMI and as such care needs to taken during their designs to limit their emissions Requirements of the local regulator ACA limit the emissions to protect the frequency spectrum Limits are set down in standards such as EN55022 for radiated and conducted emissions However these limits are not satisfactory for devices in close proximity lt 3m and as such do not guarantee that the power supply will not cause interference with devices such as TV s or radios The ST20 35 have been designed with equipment interoperability in mind The emissions are in the order of 10 100 times below the regulator requirements this is expressed in dB uV and greatly reduce the likelihood of causing interference with Radios and TV s located in close proximity 0 15MHz 5MHz 30MHz EN55022 Class B Limit AM Band 30dB Margin wee aa Lo Ss ST20 35 C
5. ST Series POWER SUPPLIES USER INSTRUCTIONS SETEC Introduction These instructions detail the installation and operation requirements for the ST20 amp ST35 power supplies These have been designed for operation in RV s providing a DC power system with optional battery back up The units operate from 240Vac and provide an isolated 13 65Vdc output at 20A and 35A respectively for powering the load and charging of batteries All the necessary protection and operating features for the load and batteries are provided An optional DC input is also provided to enable charging of batteries and powering of the load from an external 13 8V dc power source The units are fully enclosed ready for direct wall mounting All connections are at the rear of unit providing convenient wiring and installation User access to all load and battery fusing has been provided from the front of the unit Operation Safety Refer to the installation section before operating Correct installation is the most critical factor in ensuring the safe use of the power supply If every consideration of these instructions has been satisfied the power supply will be safe to operate Functional Diagram Fuse Panel DC External Input TVE AC DC Power Supply 5 x Load Outputs Vadj mm ve AC Input Isense EE e Battery Output Ve Trickle Figure 1 Functional Block Diagram AC DC Power Supply This provides an isolated 13 65Vdc output for powerin
6. g of the load and float charging of the battery Battery current is sensed and monitored by the power supply to ensure that the maximum charging current is not exceeded Battery Features The power supply provides automatic battery operation of the following Charging current is limited to a maximum of 5A ST20 and 10A ST35 This provides optimum life for the batteries To charge at the maximum battery charge current above ensure the load current plus battery current is equal or less than the maximum output current The charging current will be reduced in situations Page of 7 7982 ST Series POWER SUPPLIES USER INSTRUCTIONS were the difference between the rated output current and the load current the available charging current is less than the maximum charging current Also note that the battery current sense is provided in the ve battery output For this feature to work the load and battery ve should not be cross connected Appliances connected to the chassis must also be taken into consideration ie if the battery is connected to the chassis then cannot have an appliance with its ve connected to the chassis Low Voltage Disconnection of the batteries is provided to prevent deep discharge of the battery Automatic reconnection occurs when battery voltage recovers Battery Current Drain is always present The battery should be isolated if the unit is not in regular use See specifications for details
7. imum fuse ratings CAUTION This appliance is not intended for use by young children or infirm persons without supervision Young children should be supervised to ensure that they do not play with the appliance Page 2 of 7 Issue F ST Series POWER SUPPLIES USER INSTRUCTIONS Installation Host Equipment The host equipment must ensure that access to the unit other than the front panel by the user is prevented Personnel Installation is to be carried out only by suitably qualified personnel Ventilation Provide a minimum of 80mm clearance above and below the unit The final enclosure must also provide adequate ventilation to the outside world or larger internal cavity to prevent the build up of hot air Failure to provide adequate ventilation will mean the unit may prematurely trip thermal shutdown The ST35 unit utilizes an internal fan thermally controlled which intakes air from the left hand side of the unit A clearance of 50mm is required to this surface of the power supply CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Mechanical and Mounting _ _ _ 303 5 _ Four by 4 5 x 9mm Fuse Panel Door mounting holes at 129 5 h x 287 w centres 156 5 O Cut out for mounting Fault LED 1 152 h x 272 w Depth of unit is 125mm After mounting unit clip on the front fascia ensure that all locking clips have engaged and secure w
8. ith screw located inside the fuse panel door Orientation The unit is to be installed with the front fascia in a vertical plane Failure to do this will cause premature temperature shutdown Page 3 of 7 Issue F ST Series POWER SUPPLIES USER INSTRUCTIONS Wiring Up Mains This is pre cabled and fitted with AS NZ mains plug ready for connection to internal GPO Ensure that the connection to the mains supply is in accordance with the national wiring rules and that the earth connection is installed Load Battery and External DC Input Connections Connectors are 0 8 x 6 3mm QC tabs Use mating QC connector suitable for cable size Connector pin out is shown below l L Tae 1 Fl e es T CAUTION L204 Do not cross connect L to VBATT TF pete Doing so will disable the battery T current limit feature i 1 L3 Jj Vext must be supplied from a fused i Fext external voltage 1 1 L4 Ce T 1 L5 CE G i i VBATT FBATT pee 2 es i i i E 2 a ee To External Fuse z Voltage Panel T x ve ve terminals terminals plus Vext input Cabling sizes DC cables must be sized to carry the maximum full load current and not exceed the system volt drop requirements The following cable sizes are recommended Current AWG mm Were cables pass thru any part of a metal panel or 0 10 A 18 1 0 cover ensure that a cable gland or bush is fitted to 10 20 A 14 3 0 ere 20 30A 10 5 5 Page 4 of 7 Issue F
9. onducted Emissions However care still needs to be taken with the routing of cables and placement of the unit with respect to appliances Small emissions can still cause interference If interference is present then locate cables from the power supply away from appliance so far as possible and also locate the power supply away as far as practical Page 7 of 7 Issue F

Download Pdf Manuals

image

Related Search

Related Contents

  Kenwood KAC-X520 Stereo Amplifier User Manual  Samsung UD55D دليل المستخدم    B1080PX-3 User Manual  PeopleAdmin User Guide - Creating Postings  Installation & User Manual V2.03  Elma Instrument Full Cat 2014 - CIE  Philips SWV2233W User's Manual  Electronic Wait List (EWL) for Scheduling and Primary Care  