1.  dynamic data about its  associated object     Each symbol can also display certain information  such as the object   s  Focus window  when the user double clicks the symbol     Designer can modify a bound symbol without destroying its binding if  it is given the same Symbol ID  If the symbol is a combination of  drawing elements  use Designer to break it apart  modify it  and  recombine it  You can also use this process to change the location of  Metasys text associated with an object     Change the binding associations of symbols and objects in the  displayed graphics by unbinding the symbol from an object and  rebinding it to a new one  See Detailed Procedures for further  instructions     An object symbol can be made to flash when it goes into certain alarm  states  The color of the object alternates between its static and alarm  state colors  This feature is turned on by setting three parameters in the  METASYS INI file  Refer to the Jnitialization Parameters Technical  Bulletin  LIT 636345  for details     Note  If the flashing interval is set too low and there are many  flashing objects within the drawing  the operation of the  system may slow down  A flashing interval of less than  0 5 second is not recommended     The OWS indicates changes of state in an object by changing the color  of the object and its associated text within the dynamic drawing     The OWS provides default colors for each state that an object can  experience  To change the color settings  click Se
2.  object   s current value   If  analog  the engineering units are also displayed   The Text options  vary depending on the type of object     Operator Workstation User   s Manual 19 9    9  Specify what the workstation should display when the object   s  symbol is double clicked     Select Item   s Standard Display to display the object   s Focus  window     Note  The PC User Option on the SetUp menu should be set to  the To Focus Window option  For more information   refer to the Using Object Focus Windows chapter   LIT 120174      To return to the Network Map after double clicking the symbol   select Item   s Standard Display  and leave the Item text box blank     To access another drawing after double clicking the symbol  click  the Other button  Enter the complete path and file name of the  drawing in the text field  For a list of available drawings  click on  the File button  Select the drawing from this list  The path name of  the selected drawing appears in the Drawing Name text box     Select Neither if nothing should happen when the user  double clicks the object symbol     10  Click OK     11  Repeat Steps 8 through 13 until all objects are bound to their  object symbols     12  When finished working with the drawing  including setting  colors   save the drawing  On the Item menu  click Save     13  Close the Binding Editor by double clicking the Control menu  box  or clicking it once and selecting the Close option  The  Binding Editor closes     Setting Colors for 
3.  use this option  the PC must  have a copy of the archive database on its hard drive     Import drawing  This option is only available if there is no  drawing in the selected system   s directory  If a drawing exists   delete it before selecting this option  or use DOS copy command  or the Windows File Manager to copy over the existing drawing     Click OK  The program is now in Binding Editor mode and the  system drawing appears     Select a symbol to bind to an object  Handles appear around the  selected symbol    Either double click the object  or click Bind on the Action menu   The Bind dialog box appears  Figure 19 5      Binding Editor   Bind    Network  JCHDQTRS       Text   Status  Name    Attribute Class   te hl nll ae          Go To    Standard Display       C Other Drawing    O File         Available Selections              Figure 19 5  Bind Dialog Box    19 8   Operator Workstation User   s Manual    7  Type the object name of the object in the Item text box  the  Group System name is already entered      The Available Selections list box lists the names of all items  available for the PC group system in the next sublevel  For  example  if there is no valid item specified in the Item text box or  this box is empty  a list of all PC groups and systems defined  under the network appears  Click on an item  The selected item is  added to the text in the Item text box  and the next sublevel of  names appears  If the selected name specifies a system  the list  contains 
4. GRFXLIB DEFAULT  DRW 96  C  FMS GRFXLIB FIREPRTS  DRW 96       Figure 19 2  Example of SLIDES TXT File in Notepad    Operator Workstation User   s Manual 19 5    Detailed Procedures    Accessing Designer or DRAW    Program Manager Method    To access Designer or DRAW     l     On the Exit menu  click Program Manager  A dialog box appears  asking if the BAS should continue to run     2  Click Yes or No   Double click the Designer Draw icon    4  When finished  exit and double click the Metasys icon to return to  the Metasys program    Designer Method    Note  To access Designer using the Exit Menu described below  set    Designer   Yes in the Metasys section of the METASYS INI  file   This is the default  if Designer was installed before  Metasys      To access Designer     1     On the Exit menu  click Designer  A dialog box appears asking if  the BAS should continue to run     Click Yes  The Network Map becomes an icon in the lower portion  of the screen and Designer opens     When finished  close Designer  Click on the Network Map icon   The Network Map appears     Unbinding Objects and Symbols    To unbind an object and a symbol     l   2     Display the system with the object     On the Action menu  click Graphic Binding  The Binding Editor  appears     Select the object  Handles appear around the selected object     On the Action menu  click Unbind  The binding between the object  and the object symbol is deleted  The object symbol remains in the  drawing as a static ele
5. Operator Workstation User   s Manual 19 1    Chapter 19    Editing Graphics    Introduction    The OWS can provide information on the entire facility in both textual  and graphical formats  A System summary displays an air handling  unit as a textual list of objects  A system drawing displays the same  system with graphical symbols representing the objects     This section discusses system drawings and provides some examples  of drawings created with Micrografx Designer    software  The chapter  assumes the reader knows how to use Designer or DRAW software to  create system drawings  While drawing procedures in Micrografx  Designer and Micrografx   DRAW are similar  refer to the appropriate  manual for detailed instructions     Designer and DRAW are no longer supported at Metasys   Release 11 00  Thus  you cannot create new graphics for the OWS  with these programs  This chapter only describes how to modify  drawings that already exist     This chapter describes how to   e access Designer DRAW   e unbind objects and symbols  e bind symbols and objects   e set colors for a symbol   e modify a bound symbol   e delete a bound symbol    e modify slide show settings       November 1  2001 Johnson Controls  Inc  www johnsoncontrols com  Code No  LIT 120161    19 2 Operator Workstation User   s Manual    Key Concepts    Graphic Binding    Alarm Flashing    Setting Colors    All graphics symbols are bound  or associated  to certain objects in the  system  The graphic symbol indicates
6. a Symbol  To set colors for an object symbol     1  Inthe Binding Editor  select the bound object symbol  Handles  appear around the selected object symbol     Note  The program allows the selection multiple symbols at  once  However  doing so means all of the symbols will  use the same color for a particular state  for example  all  disabled symbols will change to red      2  On the Action menu  click Set Colors Test  The Binding  Editor Colors dialog box appears  Figure 19 6      19 10 Operator Workstation User   s Manual        Binding Editor   Colors         Graphical Display State Color    Gblect offline   Standard Color             J    Cyan x  Cancel           Color Scheme       Custom Color      Line Border Text Test  oe R G B     para R p  e  255  p fess     C Background a ee    TELE                      Figure 19 6  Set Colors Dialog Box    In the Graphical Display State box  select a state  for example   Offline  Communication Disabled  to assign colors to by clicking  the option button     Note  Items in the Graphical Display State box vary depending  on the type of object     In the Color Scheme box  click the Line Border Text radio button  and select a color from the Standard Color list box for the lines   border  and text to have in the selected state  For example  click  Green  When the object reaches the selected state  the border and  text in the object symbol changes to green  Customize the color by  changing the color intensity with the R  G  and B setting
7. ept in the directory assigned to the  GRAPHICSLIBPATH parameter in the METASYS INI file  The  default setting for this parameter is C  FMS GRFXLIB  Unless  this default setting has changed  the SLIDES TXT file is in the  C  FMS GRFXLIB directory     For more information on the METASYS INI file  refer to the  Initialization Parameters Technical Bulletin  LIT 636345      Specify the full network PC group system name of each drawing  in the order in which the drawings should cycle  Start each  DRW  file on a separate line     For the slide show to display dynamic object data  the system  drawing must be in the same directory and have the same name as  the system it represents     For example  to have the slide show display dynamic data about  the AHU1 system in the WEST PC group  specify the full  directory path and name of the system drawing     The full network name is the name assigned to the FMSDATA  parameter in the METASYS INI file combined with the name of  the network  The default setting for the FASDATA parameter is  C  FMS DATA  If the default has not been changed  and the  network name is HDQTRS  the name of the AHU1 system  drawing would be as follows     C  FMS DATA HDOTRS  WEST AHU1 AHU1   DRW    Operator Workstation User   s Manual 19 13    Specify the number of seconds each drawing should remain on the  screen before the slide show cycles to the next drawing  Insert a  space between the drawing name and the number of seconds     The recommended settings are 5 sec
8. he Symbol ID dialog box  appears    7  Assign the original Symbol ID to the symbol  Click OK     Note  When working with the default symbols in Designer  click    the Symbol ID option on the Edit menu to find out the name  of the object to which the symbol is bound  The Symbol ID  is usually the object name  This is true only for default  symbols that have been added and saved via the Binding  Editor in the Metasys program     Deleting a Bound Symbol    To delete a bound symbol     l   2     Unbind the symbol from the object     If the object has a graphic symbol number  delete the number  Be  sure to change the graphic symbol   in the Focus window to 0     Note  This is only necessary if the bound object belongs to this  system  If the bound object belongs to another system   this step is not necessary     Access Designer and delete the symbol from the drawing by  selecting the symbol and pressing the Delete key     19 12 Operator Workstation User   s Manual    Modifying the Slide Show Settings  To modify the slide show settings     1     Select drawings to use in the slide show  These drawings must  have been created in Micrografx Designer and have a  DRW  extension  The slide show can use the same drawings used to  represent the PC groups and systems within the facility  If these  drawings are bound to objects through the Graphic Binding  process  the slide show displays the dynamic object data     Display the SLIDES TXT file in any text editor     The SLIDES TXT file is k
9. ment     After unbinding the object  click Save on the item menu     19 6 Operator Workstation User   s Manual    Binding Symbols and Objects  To bind a symbol to an object     1  From the Stair Step in the PC Group summary  see Figure 19 3    select the system that contains the objects                                      Stair Step  HDQTRS wa  WEST  AHU2  Status Item Description Value Units       SFSST Supply Fan Start Stop OFF   RFSST Return Fan Start Stop OFF   SFSTAT Supply Fan Status OFF   RATEMP Return Air Temperature 71 Deg F  Stairstep             Figure 19 3  Stair Steps ina Summary  2  On the Action menu  click Graphic Binding  The Binding Editor  dialog box appears  Figure 19 4    Binding Editor    Bind Drawing For  JCHDQTRS    Options    geecescesosccccseseesoccoccccsccsoscecoscsoesoccoseessscsesseseesesea       l   erify With Archive Cancel  M Import               Ae h    File       Drawing Name        Figure 19 4  Binding Editor Dialog Box    Operator Workstation User   s Manual 19 7    Choose the options in the Binding Editor dialog box     Use default symbols  This selection is the default if no drawing  exists in the selected system   s directory  It imports all of the  symbols that have been defined in object Definition or Focus  windows  Once the symbols are imported  they will need  editing    Verify with archive  To bind symbols offline rather than online   select this option   CS objects must be bound online   When  selected  an X appears in the box  To
10. names of all of the objects in the system  After selecting  an object  the Available Item list box disappears  To leave the  Available Item list box after selecting a group or system  either  click another area of the dialog box  click OK or Cancel  or press  Tab     When binding an attribute  type the name of the attribute after the  object name  separating the two with a colon       For example   the Object AHU2 and the attribute Display would appear in the  Item Name field like this     West  2ndFloor AHU2 DISPLAY     To see a list of available types of attributes  type a question mark      after the colon  The Attribute Class box appears in the Bind  dialog box  Click on a class to select it  and the Available  Selections list box lists the available attributes  Click the desired  attribute  It appears in the Item field     Note  Fire Object input and output devices can also be  specified  however  the devices do not appear in the  Available Items box  The names of these devices are  available from the Input and Output Device summaries   When indicating a device  precede it with a pound  sign      For example  an entry might look like this     GRP1 FIRESYS ZONE  7BF1     8  Specify the text to display in place of the dummy string for the  object or attribute by clicking any  all  or none of the check boxes     For example  click the Description check box to display the  object   s 24 character expanded ID next to the symbol of the  object  Click Value Units to display the
11. onds for drawings without  dynamic data  and 31 seconds for drawings with dynamic data   The data in a dynamic drawing set for less than 31 seconds is  current when the drawing appears on screen  however  it does not  refresh     To have the slide show to display a particular drawing indefinitely   or until someone attempts to log on   enter 0 for the number of  seconds     The format of each line  including the full network PC  group system drawing name and number of seconds  should be as  follows     C    FMS  DATA HDOTRS  WEST AHU1  AHU1  DRW 40  Save the edited SLIDES TXT file in the text editor     
12. s  For  more detailed information  refer to the Graphics Technical  Bulletin  LIT 636108      Click the Pattern radio button in the Color Scheme box  and  assign a color for the symbol   s pattern when the object reaches the  selected state  For best results  set the pattern color to As In Static  Drawing     Click the Background radio button in the Color Scheme box  and  assign a color for the symbol   s background when the object  reaches the selected state     After specifying the colors for the Lines Border Text  Pattern  and  Background of the object symbol  click the next state and repeat  Step 4 to set its colors  Repeat this process to define colors for all  states     Test the colors by selecting a state in the Graphical Display State  list box and clicking the Test button  The colors of the symbol  appear as they would in the selected state     When finished with the drawing  click Save on the Item menu     Operator Workstation User   s Manual 19 11    Modifying a Bound Symbol    To modify a bound symbol    1  In Designer  select the symbol    2  On the menu  click edit  gt  Symbol ID  The Edit Symbol ID dialog  box appears with the symbol   s current name in it  Make note of  the symbol name  Click Cancel  The dialog box closes    On the Arrange menu  click Break Apart    4  Make the necessary changes to the symbol    5  Recombine the symbol or symbol elements  To do this  refer to  Creating Symbols earlier in this section    6  On the Edit menu  click Symbol ID  T
13. t Colors Test on the  Binding Editor Action menu     Default colors are described in the Graphics Technical Bulletin   LIT 636108      Slide Show    Operator Workstation User   s Manual 19 3    The slide show is a series of images that appears on the OWS screen  when no one is logged on  The images can include a company logo   floor plans  or the dynamic drawings that represent the PC groups and  systems within the facility  Each image remains on the screen for a  defined time period before the slide show cycles to the next image        FIG102    Figure 19 1  Example Slide Show Image    Slide show images can be pictures drawn with Micrografx Designer   including the same drawings that represent the actual PC groups and  systems in the facility software   or the default drawings provided with  the OWS  If the facility software drawings are dynamic drawings  the  slide show displays the current values and changes of state for the  objects in the drawings     Specify the slide show parameters in the SLIDES TXT file  To add or  delete drawings  or to change the number of seconds that a drawing  remains on the screen  simply edit the SLIDES TXT file in any text  editor     19 4 Operator Workstation User   s Manual    Figure 19 2 is an example of a SLIDES TXT file displayed in  Notepad     ij Slides txt   Notepad  OO  x   File Edit Search Help     E   FMS GRFXLIB JOHNSON DRW 96  C  FMS GRFXLIB DCTPRIS1 DRW 96  C  FMS GRFXLIB DCTPRTIS2 DRW 96  C  FMS GRFXLIB DCTPRTS3 DRW 96  C  FMS 
    