1. Syntax AARL CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RL The command to read the low latch values for all Analog Input channels Response Valid Command AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The low latch values for all Analog Input channels See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RL Response 103 02 000 00 000 00 000 00 000 00 000 00 000 00 000 00 000 Reads the low latch values for all Analog Input channels on module 03 and returns a response indicating that the command was successful with the data in engineer ing units format Related Commands Section 7 4 52 AACL Section 7 4 53 AACLi Section 7 4 68 AARL i Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 130 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 67 AARLC1 Description This command is used to read the status of the low alarm for a specific A
2. ICP DAS ZT 2026 User Manual Version 1 0 1 Page 23 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 6 2 Analog Output The Analog Output calibration procedure is as follows 1 Z 3 i Warm up the module for at least 30 minutes Set the Type Code to the type you wish to calibrate Refer to Section 5 and Section 7 4 23 for details Enable calibration Refer to Section 7 4 46 for details Set the zero Analog Output voltage current Refer to Section 7 4 5 for details Check the meter and trim the output until zero output is achieved Refer to Section 7 4 11 for details Send the Analog Output zero calibration command Refer to Section 7 4 8 for details Set the span Analog Output voltage current Refer to Section 7 4 9 for details Check the meter and trim the output until span output is achieved Refer to Section 7 4 11 for details Send the Analog Output span calibration command Refer to Section 7 4 9 for details Notes For Analog Output channels calibration must be performed for each channel individually so the calibration voltage current should be connected to the specific channel to be calibrated Calibration voltages current are shown below gt Calibration Voltage Type used by the ZT 2026 Type Code 2 3 4 5 Zero Output 0V 0V 0V 0V Span Output 10 V 10 V 5 V 5 V ICP DAS ZT 2026 User Manual Version 1 0 1 Page 24 Copyright 2013 by ICP D
3. Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The Analog Output power on value for the specified Analog Output channel There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 032 00 000 Response gt Sets the Analog Output value for Analog Output channel 2 of module 03 to 00 000 0 0 V and returns a response indicating that the command was successful Command 0342 Response 103 Stored the current Analog Output as the power on value for Analog Output channel 2 of module 03 and returns a response indicating that the command was successful Command 0372 Response 103 00 000 Reads the Analog Output power on value for Analog Output channel 2 of module 03 and returns a response indicating that the command was successful with a value of 00 000 signifying that the Analog Output power on value is 0 0 V ICP DAS ZT 2026 User Manual Version 1 0 1 Page 55 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0379 Response 203 Attempts to read the Analog Output power on value for Analog Output channel 9 of module 03 but returns a respons
4. Command 0340 Response 103 06 000 Reads the Analog Output safe value for Analog Output channel 0 of module 03 and returns a response indicating that the command was successful with a value of 06 000 6 0 V ICP DAS ZT 2026 User Manual Version 1 0 1 Page 83 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0349 Response 203 Attempts to read the Analog Output safe value for Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 37 AA3ETT Section 7 4 40 AA5N Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 84 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 40 AA5N Description This command is used to set the safe value for Analog Output channel N of a specified module Syntax AADN CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 5 The command to set the Analog Output safe value N The Analog Output channel to be set zero based Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command 2 Delimiter character to indicate an invalid
5. Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF D The command to enable or disable the counter for the Digital Input channels nn A two digit hexadecimal value representing the Digital Input channel where bit 0 corresponds to Digital Input channel 0 and bit 1 corresponds to Digital Input channel 1 etc When the bit is 0 it denotes that the counter for the Digital Input channel will be disabled and 1 denotes that the counter for the Digital Input channel will be enabled Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D03 Response 103 Enables the counters for Digital Input channels 0 and 1 on module 03 and disables the counters for all other Digital Input channels The module returns a response indicating that the command was successful Command 03D Response 10303 Reads the status of the counters for all Digital Input channels on module 03 and returns a response indicating that the command was successful with a value of 03 which denotes that the counters f
6. Digital Input channel 9 does not exist Related Commands Section 7 4 25 AAD Section 7 4 26 AADnn Section 7 4 62 AAREC i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 99 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 49 AACH Description This command is used to clear the high latch values for all Analog Input channels of a specified module Syntax AACH CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CH The command to clear the high latch values for all Analog Input channels Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RHO Response 103 05 000 Reads the high latch value for Analog Input channel O of module 03 and returns a response indicating that the command was successful with a value of 05 000 5 0 V Command 03CH Response 103 Clears the high latch values for all Analog Input channels of module 03 and returns a response indicating that th
7. Syntax AAROO j CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RO The command to read the alarms associated with the specific Digital Output port 0j j specifies the Digital Output channel to be read zero based Response Valid Command 1 AAHHLL CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF HH A two digit hexadecimal value representing the status of the high alarms associated with the specified Digital Output channel where bit 0 corresponds to channel 0 bit 1 corresponds to channel 1 etc When the bit is 0 it denotes that the high alarm for the channel is disabled and 1 denotes that the high alarm for channel is enabled Lt A two digit hexadecimal value representing the status of the low alarms associated with the specified Digital Output channel where bit 0 corresponds to channel 0 bit 1 corresponds to channel 1 etc When the bit is 0 it denotes that the low alarm for the channel is disabled and 1 denotes that the low alarm for the channel is enabled There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Example Command 03RO001 Response 1
8. A 9 42 x2A Writing the Miscellaneous Settings Description This sub function code is used to configure the miscellaneous settings for a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x2A Code 03 Miscellaneous 1 The data format See Section 4 for details Settings of the format Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 Ox2A Code 03 Miscellaneous 1 0 OK Settings Others Error Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 2A 00 FF 6D Response 01 46 2A 00 FF 6D ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 158 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Appendix 8 1 Software Configuration Mode Each ZT 2000 1 0 device contains a built in EEPROM memory that is used to store configuration information such as the address the data format the Analog Input Type Code and other information When the module is powered on with the Address Node ID set to 0x00 the ZT 2000 1 0 device will be set to software configuration mode In this mode the configuration details Address Node ID data format and Analog Input Type Co
9. AAF Reads the Firmware Version of the Module 7 4 29 AAM T Reads the Name of the Module 7 4 30 Reads the Status of the Latched Digital Input SAALS Data bs pore 7 4 31 and Digital Output Channels AAS1 Reloads the Default Calibration Parameters 7 4 32 Reads the Safe Value for a Specific Analo AAAN IAA Data powcr N aga Output Channel Sets the Safe Value for a Specific Analo AABN IAA i aia 7 4 40 Output Channel CAAD IAATT Reads nee Input and Digital Output 7444 Configuration _AADTT IAA Sets i sly Input and Digital Output AAG Configuration AAEV Enables or Disables Calibration for the Module 7 4 46 AAO Name Sets the Name of the Module 74 47 Resets the Counter for a Specific Digital Input AACECi 1AA i a ne ll eaeag Channel Clears the High Latch Values for all Anal AACH IAA ears the High Latch Values for all Analog zidi Input Channels AACH AA Clears the High Latch Value for a Specific T Analog Input Channel ICP DAS ZT 2026 User Manual Version 1 0 1 Page 28 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Specific Analog Input Channel Input Channels Clears the Low Latch Value for a Specific Specific Analog Input Channel Input Channel Output Channels Input Channel AADODD Sets the Status of the Digital Output Ports 7 4 60 Reads the Currently Activated Alarms AARAO IAAHHLL T 7 4 61 associated with a Specific Digital Output Port Reads the Counter for a Specific Digital Input A
10. Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x04 Code 03 New Address 1 1 to 247 04 06 Reserved 3 0x00 0x00 0x00 Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x04 Code 03 New Address 1 1 to 241 04 06 Reserved 3 0x00 0x00 0x00 Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 04 02 00 00 00 F5 1E Response 01 46 04 00 00 00 00 F4 A6 ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 151 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 3 07 0x07 Reading the Analog Input Type Code Description This sub function code is used to read the Type Code information for a specific Analog Input channel of a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x07 Code 03 Reserved 1 0x00 04 Channel Number 1 0x00 to 0x07 Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x07 Code 03 Type Code 1 The Type Code See Section 4 for details of the data format
11. 10 Voc 5 Voc 0 10 Voc 0 5 Voc Resolution 12 bit Accuracy 0 1 of FSR Zero Drift 30 uV C Span Drift 25 ppm C Programmable Output Slope 0 0625 1024 V Sec Voltage Capability 20 mA 10 V Power on and Safe Value Yes ICP DAS ZT 2026 User Manual Version 1 0 1 Page 9 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Digital I nput Event Counters Input Channels 2 Sink On Voltage Level 3 5 Voc 50 Voc Off Voltage Level 1 Vpc Max Input Impedance 10K ohm Channels 2 Max Count 32 bit 4 294 967 295 Max Input Frequency 50 Hz Min Pulse Width 10 ms Digital Output Output Channels 2 Sink Output Type Isolated Open Collector Max Load Current 700 mA Channel Load Voltage 5 Voc 50 Voc Short Circuit Protection Yes LED I ndicators ZigBee PWR ZigBee Device Power ZigBee Net ZigBee Communication Indicator Power Power Consumption 1 7 W Max Environment Operating Temperature 25 to 75 C Storage Temperature 30 to 80 C Humidity 10 to 90 Non condensing Wireless RF Channels 16 RF Transmit Power 11 dBm Antenna 2 4 GHz 5 dBi Omni directional Transmission Range LOS 700 m Typical Max Slaves Supported 205 EMI Certification CE FOG FCC ID ICP DAS ZT 2026 User Manual Version 1 0 1 Page 10 Copyright 2013 by ICP DAS Co
12. AAEV Related Topics Section 6 Calibration Notes 1 The Enable Calibration command AAEV must be sent before this command is used See Section 7 4 46 for details 2 This command must be sent before the Analog Output Span Calibration command AAIN is used See Section 7 4 9 for detai ls 3 For Analog Output channels calibration must be performed for each channel individual ly ICP DAS ZT 2026 User Manual Version 1 0 1 Page 42 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 9 AAIN Description The command is used to perform an Analog Output span calibration on Analog Output channel N of a specified module Syntax AA1N CHECKSUM CR Delimiter character AA The address of the module to be calibrated in hexadecimal format 00 to FF 1 The command to perform the Analog Output span calibration N The Analog Output channel to be calibrated zero based Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0311 Response 203 Attempts to perfo
13. Error Response Byte Description Length Value 00 Address 1 1 to 241 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 07 00 01 7C 89 Response 01 46 07 08 E3 FB ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 152 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 4 8 0x08 Setting the Analog Input Type Code Description This sub function code is used to set the Type Code for a specific Analog Input channel of a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x08 Code 03 Reserved 1 0x00 04 Channel Number 1 0x00 0x07 05 Type Code 1 The Type Code See Section 4 for details of the data format Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x08 Code 03 Type Code 1 0 OK Others Error Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 20 13 B8 Response 01 46 20 01 00 00 D2 05 ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 153 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 5 32 0x20 Reading the Firmware V
14. Related Commands Section 7 4 5 AAN Data Section 7 4 23 AA9NTS Section 7 4 37 AA3ETT Section 7 4 39 AA4N Section 7 4 40 AAD5N Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 90 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 44 AAD Description This command is used to read the Digital Input and Digital Output configuration for a specified module Syntax AAD CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF D The command to read the Digital Input and Digital Output configuration Response Valid Command 1 AATT CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF TT Two hexadecimal digits that represent the miscellaneous settings as fol lows Bit 0 Specifies the active state of the Digital Input signal 0 an output value of 1 indicates that the relay is active an output value of 0 indicates that the relay is inactive 1 an output value of 0 indicates that the relay is active an output value of 1 indicates that the relay is inactive Bit 1 Specifies the active state of the Digital Output signal 0 an input value of 1 indicates that there is no signal or the v
15. 0 5 V Second 1 0 V Second 2 0 V Second 4 0 V Second 8 0 V Second 16 V Second 32 V Second 64 V Second 128 V Second 256 V Second 512 V Second 1024 V Second 7TAMVUOIWTreAa on7ont wh ICP DAS ZT 2026 User Manual Version 1 0 1 Page 22 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Calibration gt Warning Performing calibration is not recommended until the process is fully understood 6 1 Analog Input The Analog Input calibration procedure is as follows j id COND Oo Warm up the module for at least 30 minutes Set the Type Code to the type you wish to calibrate Refer to Section 4 and Section 7 4 19 for details Enable calibration Refer to Section 7 4 46 for details Apply the zero calibration voltage current Send the zero calibration command Refer to Section 7 4 7 for details Apply the span calibration voltage current Send the span calibration command Refer to Section 7 4 6 for details Repeat steps 3 to 7 three times gt Notes 1 a 3 The calibration voltage current source should be connected to channel 0 Calibration voltages and currents are shown below Switch to DCON protocol mode before calibrating the module Refer to Section 3 2 for details of how to switch protocols gt Calibration Voltage Type used by the ZT 2026 Type Code 08 09 OA 0B 0C oD Zero Input 0V 0V 0V 0 mV 0 mV 0 mA Span Input 10 V 5 V 1 V 500 mV 150 mV 20 mA
16. 00 to FF D The command to set the Digital Input and Digital Output configuration TT Two hexadecimal digits that represent the miscellaneous settings as follows Bit 0 Specifies the active state of the Digital Input signal 0 an output value of 1 sets the relay to active an output value of 0 sets the relay to inactive 1 an output value of 0 sets the relay to active an output value of 1 sets the relay to inactive Bit 1 Specifies the active state of the Digital Output signal 0 an input value of 1 sets the signal to none or the voltage to low an input value of 0 sets the voltage to high 1 an input value of 0 sets the signal to none or the voltage to low an input value of 1 sets the voltage to high Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D01 Response 103 Sets the miscellaneous settings for module 03 to 01 meaning that the Digital Output channels are in inactive mode and returns a response indicating that the command was successful Command 03D Response 10301 Reads the m
17. 1 1 Introduction to ZigBee ZigBee is a specification for a suite of high level communication protocols using small low power digital radios based on the IEEE 802 15 4 standard for personal area networks ZigBee devices are often used in mesh network form to transmit data over longer distances passing data through intermediate devices to reach more distant ones This allows ZigBee networks to be formed ad hoc with no centralized control or high power transmitter receiver required in order to reach all of the devices Any ZigBee device can be tasked with running the network ZigBee is targeted at applications that require a low data rate long battery life and secure networking ZigBee has a def ined rate of 250 kbit s best suited for periodic or intermittent transmission of data or for a single signal transmission from a sensor or input device Applications include wireless light switches electrical meters with in home displays traffic management systems and other consumer and industrial equipment that requires short range wireless transfer of data at relatively low rates The technology defined by the ZigBee specification is intended to be simpler and less expensive than other WPANs ICP DAS ZT 2026 User Manual Version 1 0 1 Page 7 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 1 2 Introduction to the ZT 2000 I O Series The ZT 2000 1 0 series of devices are small wireless ZigBee 0 modules based on the IEEE802 15 4
18. 2013 by ICP DAS Co Ltd ALL Rights Reserved gt Analog Input Over Under Range Readings Over Range Under Range Engineering Units 9999 9 9999 9 of FSR 999 99 999 99 2 s Complement Hex 1FFF 8000 gt Analog Input Over Under Range Readings when using the Modbus RTU protocol Over Range Under Range 7FFFh 8000h gt Data Format Settings FF 7 6 5 4 3 2 1 0 FS Reserved DF Key Description DF Data Format 00 Engineering Units 01 of FSR 10 2 s Complement Hexadecimal FS Filter Settings 0 60 Hz Rejection 1 50 Hz Rejection ICP DAS ZT 2026 User Manual Version 1 0 1 Page 21 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Analog Output Type and Slew Rate Type Code Input Type Data Format F S F S sits 210 Engineer ing A 10 000 0 000 2 y of FSR 100 00 000 00 2 s Comp Hex FFFF 0000 7 Engineering Units 10 000 10 000 3 w ae of FSR 100 00 100 00 2 s Comp Hex TEFE 8000 0 to 5 Engineer ing nine 05 000 00 000 4 y of FSR 100 00 000 00 2 s Comp Hex FFFF 0000 Engineering Units 05 000 05 000 fo 5 i zi 5 y of FSR 100 00 100 00 2 s Comp Hex iFFF 8000 1 FSR Full Scale Range gt Slew Rate Control e gt Immediate Change 0 0625 V Second 0 125 V Second 0 25 V Second
19. Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03CHC9 Response 203 Attempts to clear the status of the high alarm for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 55 AADHCi Section 7 4 58 AAHI Data CiTOj Section 7 4 61 AARAOj Section 7 4 63 AARH Section 7 4 64 AARHC i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 104 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 52 AACL Description This command is used to clear the low latch values for all Analog Input channels of a specified module Syntax AACL CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CL The command to clear the low latch values for all Analog Input channels Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RLO Response 103 05 000 Read
20. IAA i rei 74 42 Specific Channel Sets the Analog Output Safe Value for a AA6SN Data IAA X 7 4 43 Specific Channel ICP DAS ZT 2026 User Manual Version 1 0 1 Page 30 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 1 AANNTTCCFF Description This command is used to set the configuration of a specific module Syntax AANNTTCCFF CHECKSUM CR Delimiter character AA The address of the module to be configured in hexadecimal format 00 to FF NN The new address of the module in hexadecimal format 00 to FF TT 00 Reserved cC OA Reserved FF The command used to set the data format checksum and filter settings See Section 4 for details of the data format Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0320000A80 Response 103 In Normal mode the address 0x20 is saved to the EEPROM and the data format for module 03 is set to 80 50 Hz rejection The module returns a response indicating that the command was successful Command 032
21. Ltd ALL Rights Reserved 2 2 Pin Assignments DEMAN pwr ZigBee Antenna Protocol Address MSB F G GND Power Supply s Vem m mi E E 0 nmi vom vm Pin Assignments ICP DAS ZT 2026 User Manual Version 1 0 1 Page 11 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 2 3 Wire Connections ma Foal ime Requires Optional External 125 Q Resistor tS loo Sa BD VDC OS DGND ICP DAS ZT 2026 User Manual Version 1 0 1 Page 12 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Setting up the ZT 2000 I O Device 3 1 Introduction to the Configuration Parameters A The ZB PID parameter is the group identity for a ZigBee network and must be the same for all devices in the same ZigBee network B The Node ID parameter is the individual identity of the specific ZigBee module and must be unique for each device connected to the same ZigBee network C The ZB Channel parameter indicates the radio frequency channel and must be set to the same value as other modules on the same ZigBee network ZB Channel 0x00 OxO1 eee 0x0F Frequency MHz 2405 2410 eses 2480 X ZB channels 0x04 0x09 OxOE or 0x0F are recommended because they do not over lap with the Wi Fi frequency band 802 11b g ZB Channel 11 802 11b g ZB Channel 6 802 11b g ZB Channel 1 MHz MHz Ah 802 11
22. Related Commands Section 7 4 7 AA1 Section 7 4 46 AAEV Related Topics Section 6 Calibration Note The Enable Calibration command AAEV and the Zero Calibration command AA1 must be sent before this command is used See Sections 7 4 46 and 7 4 7 for details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 38 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 7 AA1 Description This command is used to perform an Analog Input zero calibration on a specified module Syntax AA1 CHECKSUM CR Delimiter character AA The address of the module to be calibrated in hexadecimal format 00 to FF 1 The command to perform the Analog Input zero calibration Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 031 Response 203 Attempts to perform an Analog Input zero calibration on module 03 but a response indicating that the command was unsuccessful is returned because the Enable Calibration command AAEV see Section 7 4 46 was not s
23. When the bit is 0 it denotes that the counter edge for the Digital Input channel will be set to falling and 1 denotes that the counter edge for the Digital Input channel will be set to rising Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03E03 Response 103 Sets the counter edges for Digital Input channels O and 1 of module 03 to rising and sets the counter edges for all other Digital Input channels to falling The module returns a response indicating that the command was successful Command 03E Response 10303 Reads the status of the counter edges for all Digital Input channels on module 03 and returns a response indicating that the command was successful with a value of 03 which denotes that the counter edges for Digital Input channels O and 1 are rising and the counter edges for all other Digital Input channels are fal ing Related Commands Section 7 4 27 AAE ICP DAS ZT 2026 User Manual Version 1 0 1 Page 69 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 29 AAF
24. the current Digital Input counter values Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x03 02 03 Starting Channel 2 See Section 7 5 1 for details Number or Address Mapping 04 05 Input Channel 2 0x0001 to 0x0020 Number or Bit Count Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x03 02 Byte Count 1 Byte Count of the Response B 2 Word Count O3 Register Values B 2 Register Values Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x83 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 144 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 6 Q4 0x04 Reading Multiple Input Registers Description This function code is used to read the current Analog Input values from the ZT 2000 1 0 module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x04 02 03 Starting Channel 2 See Section 7 5 1 for details Number or Address Mapping 04 05 Input Channel 2 0x0001 to 0x0020 Number or Bit Count Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x04 02 Byte Count 1 Byte Count of the Response
25. 2026 User Manual Version 1 0 1 Page 82 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 39 AA4N Description This command is used to read the safe value for Analog Output channel N of a specified module Syntax AA4N CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 4 The command to read the Analog Output safe value N The Analog Output channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The Analog Output safe value See Section 5 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030 06 000 Response gt Sets the Analog Output value for Analog Output channel 0 of module 03 to 06 000 6 0 V and returns a response indicating that the command was successful Command 0350 Response 103 Sets the current Analog Output value for Analog Output channel O as the Analog Output safe value and returns a response indicating that the command was successful
26. 203 Attempts to send a command to perform a span calibration on module 03 but returns a response indicating that the command was unsuccessful because the Enable Calibration command AAEV has not yet been sent Command 03E1 Response 103 Enables calibration on module 03 and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 95 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 030 Response 103 Sends a command to perform a span calibration on module 03 and returns a response indicating that the command was successful Related Commands Section 7 4 6 AAO Section 7 4 7 AA1 Section 7 4 8 AAON Section 7 4 9 AAIN Section 7 4 32 AAS1 Related Topics Section 6 Calibration Note This command must be sent before any other calibration commands can be used ICP DAS ZT 2026 User Manual Version 1 0 1 Page 96 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 47 AAO Name This command is used to set the name of a specified module Syntax AAO Name CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 0 The command to set the name of the module Name The new name of the module Max 8 characters Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR De
27. 7 4 51 AACHCi Section 7 4 58 AAHI Data CiTOj Section 7 4 61 AARAOj Section 7 4 64 AARHCi Section 7 4 69 AAROO j ICP DAS ZT 2026 User Manual Version 1 0 1 Page 111 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 56 AADI Description This command is used to read the status of all Digital Input and Digital Output channels of a specified module Syntax AAD CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF DI The command to read the status of all Digital Input and Digital Output channels Response Valid Command AAOOO CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF 0 Reserved 00 A two digit hexadecimal value representing the status of the Digital Output where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output is inactive and 1 denotes that the Digital Output is active A two digit hexadecimal value representing the status of the Digital Input where bit 0 corresponds to Digital Input channel 0 and bit 1 corresponds to Digital Input channel 1 etc When the bit is 0 it denotes
28. 8 9 A B C D E F Address 18 19 1A 0B 0C 1D 1E 1F Node ID 0x018 0x0019 Ox001A 0x001B 0x001C Ox001D 0x001E 0x001F Note 1 The Address and Node ID values are defined via the AANNTTCCFF command In software configuration mode the DIP switches for Address Data Format and Type Code are ignored and can also be set via the AANNTTCCFF and AACiRrr commands ICP DAS ZT 2026 User Manual Version 1 0 1 Page 14 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Address LSB ZB Channel Type Code Address MSB ZB PID Data Format Protocol Checksum gt DIP Switches Number Item Status Description I Address MSB OFF Valid Address Node ID from 0x01 to 0x0F ON Valid Address Node ID from 0x10 0x01 to Ox1F 9 Pratacal OFF DCON Protocol ON Modbus RTU Protocol 3 eiee OFF Disabled DCON Protocol ON Enabled DCON Protocol OFF ZigBee Pan ID 0x0000 i eae ON ZigBee Pan ID 0x0001 5 OFF ON 0x08 6 OFF ON 0x04 ZB Channel OFF oon ON 0x02 8 OFF ON 0x01 OFF Engineering Units Format 3 Data Parnas ON Hexadecimal Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 15 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Address LSB Address MSB Protocol Checksum gt Type Code DIP switches 10 12 are used to define t
29. B 2 Word Count O3 Register Values B 2 Register Values Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x84 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2 26 User Manual Version 1 0 1 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Page 145 Fatal 5 0x05 Writing a Single Coil Description This function code is used to write the Digital Output value for the ZT 2000 1 0 module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x05 02 03 Starting 2 See Section 7 5 1 for details Channel Number or Address Mapping 04 05 Output Value 2 A value of OxFFOO sets the output to ON A value of 0x0000 sets the output to OFF Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x05 02 03 Output Channel 2 This value is the same as bytes 02 and 03 Number of the Request 04 05 Output Value 2 This value is the same as bytes 04 and 05 of the Request Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x85 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 146 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 8 06 0x06 Writing Multipl
30. Data C110 446he454h45b05b40 roo odo DEORE 116 BASS WARGO Dabs 100 Errr EAEEREN EEEE 118 7 43 60 QAADODD 3 506 e5s ese vee ee ee eee eee eo oe ree ee eee oes 120 7 4 61 DRARAO osscceaccesecescanesonecossrouseoeeaneoes 122 Tool AARECI ss sosi eo oe i i i eee li i ee ee ee oe ee eo ee a 124 72h 68 QAARH ccc see aRRAeSeERRRRSRERERRRARSR ERS RRR RRR EE 126 Pes 60 AARHC 24 42 4 45 S4 44454 44 45 995 44 55 94 127 7 465 AARH Regge aren erererarerararerererarerar serene ararererarererarerer a greed erarer ee 129 7 466 wees eee ee ee ee eee ee eee ee eee ee ee eee ee 130 TAG ORARL Ci icace ace paca areca aan ae RR RRR RRR Ra ROR RRR RRR RCRCRCR e 131 74 68 QWARR 4 9 595554545559 995445559994 9F 5959 EEE EEE 133 y ee 2 a 2160 ee he 134 7 5 Modbus RTU Protocol Command Set cececcecccceccesces 136 7 5 1 Modbus Address Mapping 0sccceseeeesere0es 137 7 5 2 PLC Address MapDING s lt s seeceeeeeeeeaeeeawee aa a s 141 7 5 3 1 0x01 Reading the Coils cece ee wees 142 7 5 4 2 0x02 Reading the Discrete Inputs 143 7 5 5 03 0x03 Reading Multiple Registers 144 7 5 6 04 0x04 Reading Multiple Input Registers 145 7 5 7 05 0x05 Writing a Single Coil 146 7 5 8 06 0x06 Writing Multiple Registers 147 7 5 9 15 x F Writing Multiple Coils 148 7 5 10 70 0x46 Reading Writing the Module Settings 149 etc cht eer ee eer ee ee Tee ee ee er re 15
31. Description This command is used to read the firmware version of a specified module Syntax AAF CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF F The command to read the firmware version information Response Valid Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The firmware version of the module as a string value There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03F Response 103A1 0 Reads the firmware version of module 03 and returns a response indicating that the command was successful and showing that the firmware is version A1 0 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 70 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 30 AAM Description This command is used to read the name of a specified module Syntax AAM CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF M The command to read the name of the module Response Valid
32. Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 86 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 41 AA5PPSS Description This command is used to set the Digital Output power on value and the Digital Output safe value for a specified module Syntax AAD5PPSS CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 5 The command to set the Digital Output power on value and the Digital Output safe value PP A two digit hexadecimal value representing the Digital Output power on value where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output power on is inactive and 1 denotes that the Digital Output power on is active SS A two digit hexadecimal value representing the Digital Output safe value where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output safe value is inactive and 1 denotes that the Digital Output safe value is active Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal for
33. V and returns a response indicating that the command was successful Command 0361 Response 103 10 000 Reads the Analog Output requisition value for Analog Output channel 1 of module 03 and returns a response indicating that the command was successful with a value of 10 000 10 0 V ICP DAS ZT 2026 User Manual Version 1 0 1 Page 53 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0369 Response 203 Attempts to read the Analog Output value from the last command received by Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 5 AAN Data Section 7 4 20 AA8N Section 7 4 23 AA9NTS Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 54 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 18 AA7N Description This command is used to read the Analog Output power on value for channel N of a specified module Syntax AA7N CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 7 The command to read the Analog Output power on value N The Analog Output channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR
34. W 0 Hexadecimal 1 Engineering Units 00270 The status of the Host Watchdog timeout Write 1 Wo W W W W W W W W S S S S D ot a 2 2 2 2 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 137 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved to clear 00272 The factory calibration parameters Write 1 to load 00273 The Reset status 0 This is NOT the first time the module has been read after being powered on 1 This is the first time the module has been read after being powered on The Digital Input active mode 0 Normal 1 Inverse The Digital Output active mode 0 Normal 1 Inverse 00280 The high latch values for all Analog Input channels Write 1 to clear 00281 The low latch values for al Analog Input channels Write 1 to clear 00284 Enables or disables calibration R W 0 Disable 1 Enable 00516 to 3 Write 1 to clear 00545 The low latch values for Analog Input channels 0 00548 to 3 Write 1 to clear 00577 Enables or disables the high alarm for Analog Input 00580 channels 0 to 3 0 Disable 1 Enable Enables or disables the low alarm for Analog Input channels 0 to 3 0 Disable 1 Enable The high Alarm Type for Analog Input channels 0 to 3 0 Momentary 1 Latch The low Alarm Type for Analog Input channels 0 to 3 0 Momentary gt Latch 00705 The status of the high alarm for Analog Input 00708 channels 0 to 3
35. channel There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RECO Response 10300000008 Reads data from Digital Input channel O of module 03 and returns a response indicating that the command was successful with a counter value of 00000008 Command 03CECO Response 103 Resets the counter for Digital Input channel 0 of module 03 to the preset value and returns a response indicating that the command was successful Command 03RECO Response 10300000000 Reads data from Digital Input channel O of module 03 and returns a response indicating that the command was successful with a counter value of 00000000 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 124 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03REC9 Response 203 Attempts to read data from Digital Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because the Digital Input channel 9 does not exist Related Commands Section 7 4 25 AAD Section 7 4 26 AADnn Section 7 4 48 AACEC i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 125 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 63 AARH Description This command is used to read the high latch values for all Analog Input chann
36. communication error or there is no module with the specified address Examples Command 032 00 000 Response gt Sets the Analog Output value for channel 2 of module 03 to 00 000 0 0 V and returns a response indicating that the command was successful Command 0342 Response 103 Stores the current Analog Output as the Analog Output power on value for Analog Output channel 2 of module 03 and returns a response indicating that the command was successful Command 0349 Response 203 Attempts to store the current Analog Output as the Analog Output power on value for Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 18 AA7N Section 7 4 42 AAGPN Data ICP DAS ZT 2026 User Manual Version 1 0 1 Page 49 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 14 AA5 Description This command is used to read the reset status of a specified module Syntax AA5 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 5 The command to read the reset status of the module Response Valid Command 1 AAS CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a
37. joined the ZigBee network the signal qual ity can be confirmed by monitoring the status of the ZigBee Net LED indicators If the LED indicator shows a steady light communication with the ZI 2000 0 device has been successfully established for data acquisition and control ICP DAS provides the DCON Utility which can be used to simulate DCON Modbus communication This software can also be used to verify the device settings and the ZigBee 1 0 functions The DCON Utility can be downloaded from http ftp icodas com pub cd 8000cd napdos dr iver dcon_util ity ICP DAS ZT 2026 User Manual Version 1 0 1 Page 17 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 3 5 Examples gt Architecture Diagram RF Power Ag RS 232 RS 4 cerca gt Configuring the ZT 2000 I O device Oi 3 4 5 6 iO 4 Number Item Status Description 1 Address MSB OFF Address Node ID is 01 Rotary Switch 1 2 Protocol ON Use the Modbus RTU Protocol 3 Checksum OFF Disabled 4 ZB PID OFF ZigBee Pan ID 0x0000 5 ON 0x08 6 ON 0x04 _ 7 ZB Channel ON 0x02 ZigBee RF Channel Ox0E 8 OFF ICP DAS ZT 2026 User Manual Version 1 0 1 Page 18 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved gt Simulating I O channel operation via the DCON Utility 1 Launch the DCON Utility and select the appropriate COM Port settings to connect to the ZigBee Coordinato
38. module 03 to 8 10 10V and the module returns a response indicating that the command was successful Command 037C1R80 Response 203 Attempts to set the Type Code for Analog Input channel 1 of module 03 to 80 The module returns a response indicating that the command was unsuccessful because the Type Code is incorrect Related Commands Section 7 4 3 AA Section 7 4 4 AAN Section 7 4 21 AA8Ci Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 57 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 20 AA8N Description This command is used to read the current Analog Output value for Analog Output channel N of a specified module Syntax AA8N CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 8 The command to read the current Analog Output value N The Analog Output channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The current Analog Output value for the specified Analog Output channel See Section 5 for details of the data format There will b
39. of the low latched Digital Output and Digital Input channels 1 Reads the status of the high latched Digital Output and Digital Input channels Response Valid Command Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The status of the latched Digital Output and Digital Input channels represented by a four digit hexadecimal value followed by 00 There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03L0 Response 1010200 Reads the status of the low latched Digital Output and Digital Input channels of module 03 and returns a response indicating that the command was successful with a value of 010200 showing that Digital Output channel 0 and Digital Input channel 1 are latched low Command 03C Response 103 Clears the status of the latched Digital Output and Digital Input channels of module 03 and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 72 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03L0 Response 1000000 Reads the status of the low latched
40. or there is no module with the specified address Examples Command 03301F Response 103 Increases the voltage of the Analog Output for channel 0 of module 03 by an increment of 31 and returns a response indicating that the command was successful Command 033060 Response 203 Attempts to increase the voltage of the Analog output for channel 0 of module 03 by an increment 96 but returns a response indicating that the command was unsuccessful because the increment value is not within the valid range Related Commands Section 7 4 8 AAON Section 7 4 9 AAIN Section 7 4 46 AAEV Related Topics Section 6 Calibration ICP DAS ZT 2026 User Manual Version 1 0 1 Page 46 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 12 AA4 Description This command is used to read the synchronized sampling data that was stored of a specified module when the last command was issued Syntax AA4 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 4 The command to read the synchronized sampling data Response Valid Command AAS Data CHECKSUM CR Invalid Command AA CHECKSUM CR I Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF
41. standard that allow data acqusition and control via personal area ZigBee networks See Section 3 1 for more detailed information The ZT 2000 1 0 series is a wireless data acquisition based client server system Accordingly a Net Server for the ZigBee ZT 2570 ZT 2550 is essential in such systems For more information regarding any configuration issues related to the ZigBee Coordinator refer to the ZT 25XX ZigBee Converter Quick Start document which can be found at http ftp icpdas com pub cd usbcd napdos z i gbee zt_ser ies document ICP DAS ZT 2026 User Manual Version 1 0 1 Page 8 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Hardware Information 2 1 Specifications Analog I nput Input Channels 4 Differential 10 V 4 5 V 47 1 V 4 500 MV 150 mV 20 mA 20 mA Input type 20 mA 20mA requires an Optional External 125 Q Resistor Resolution 16 bit Sampling Rate 16 bit 10 Samples Sec Total Accuracy 0 1 FSR 3dB Bandwidth 15 7 Fiz Zero Drift 20 uV C Span Drift 25 ppm C Common Mode Rejection 86 dB Normal Mode Rejection 100 dB Input Impedance gt 2 MQ Overvoltage Protection 240 Vrms Individual Channel Yes Configuration Intra module Isolation Field to Logic AD Vok ESD Protection 4 kV Contact for each Channel Analog Output Output Channels 2 Output Type
42. status of the low alarms for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful and that the alarm limit is 03 000 3 0 V the Alarm Type is latched and Digital Output channel 1 is set as the low alarm output ICP DAS ZT 2026 User Manual Version 1 0 1 Page 131 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03RLC9 Response 203 Attempts to read the status of the low alarms for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 54 AACLCi Section 7 4 57 AADLCi Section 7 4 59 AALO Data CiTOj Section 7 4 61 AARAOj Section 7 4 69 AAROO j Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 132 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 68 AARLi Description This command is used to read the low latch value for a specific Analog Input channel of a specified module Syntax AARL i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RL The command to read the low latch value for the Analog Input channel i The Analog Input channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR Inva
43. to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The data from all the Analog Input channels See Section 4 for details of the data format Data from disabled channels is filled with space characters There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03 Response gt 025 12 020 45 012 78 018 97 003 24 015 35 Reads data from the Analog Input channels of module 03 and returns a response indicating that the command was successful with the data from all Analog Input channels in engineering units format Command 03 Response gt 4C0532628E2D683A20F 2ADBA1 Reads the Analog Input channels of module 03 and returns a response indicating that the command was successful with the data from all Analog Input channels in hexadecimal format Command 03 Response gt 9999 9 9999 9 9999 9 9999 9 9999 9 9999 9 Reads the Analog Input channels of module 03 and returns a response indicating that the command was successful but that the data is under range XRelated Commands Section 7 4 1 AANNTTCCFF Section 7 4 4 AAN Section 7 4 10 AA2 Section 7 4 19 AA7CiRrr XRelated Topics Section 4 Analog Input Type and Data Format Section 8 1 Software Configuration Mode ICP DAS ZT 2026 User Man
44. valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF S The reset status of the module 0 This is NOT the first time the command has been sent since the module was powered on which denotes that there has been no module reset since the last AA5 command was sent 1 This is the first time the command has been sent since the module was powered on There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 035 Response 1031 Reads the reset status of module 03 The module returns a response indicating that the command was successful and that it is the first time the AA5 command has been sent since the module was powered on Command 035 Response 1030 Reads the reset status of module 03 The module returns a response indicating that the command was successful and that there has been no module reset since the last AA5 command was sent ICP DAS ZT 2026 User Manual Version 1 0 1 Page 50 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 15 AA5VV Description This command is used to specify the Analog Input channels to be enabled on a specified module Syntax AADVV CHECKSUM CR Delimiter character AA The address of
45. value of 030100 showing that Digital Output channels 0 and 1 and Digital Input channel 0 are latched low Command 03C Response 103 Clears the latch values for all channels of module 03 and returns a response indicating that the command was successful Command 03L1 Response 1000000 Reads the low latch data for module 03 and returns a response indicating that the command was successful with a value of 000000 showing that all latched Digital Output and Digital Input channels have been cleared Related Commands Section 7 4 31 AALS ICP DAS ZT 2026 User Manual Version 1 0 1 Page 65 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 25 AAD Description This command is used to read whether the counter for each Digital Input channel of a specified module is enabled or disabled Syntax AAD CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF D The command to read the status of the counter for each Digital Input channe l Response Valid Command AAnn CHECKSUM CR Invalid Command AA CHECKSUM CR l Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF nn A two digit hexadecimal value representing the Digital Input channel whe
46. 0000A80 Response 120 In Software Configuration mode the address 0x20 is saved to the EEPROM and the data format for module 03 is set to 80 50 Hz rejection The module returns a response indicating that the command was successful Command 0303000000 Response 203 Attempts to set the configuration for module 03 but returns a response indicating that an error occurred because the CC parameter must be OA Related Commands Section 7 4 10 AA2 Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 31 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 2 Description This command instructs every Analog Input module to read data from every Analog Input channel and store the data for later retrieval Syntax Hk CHECKSUM CR Delimiter character The synchronized sampling command Response There is no response to this command Examples Command Hx Response No response Sends the synchronized sampling command to all Analog Input modules Command 034 Response gt 031 025 12 020 45 012 78 018 97 003 24 015 35 008 07 014 79 Sends the command to read the synchronized sampl ing data from module 03 The module returns a response indicating that the command was successful containing the data in Engineering Units format that w
47. 03 09 000100 Reads the status of the high alarms for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful and that the high alarm limit is 09 000 9 0 V the Alarm Type is momentary and Digital Output channel 0 is set as the high alarm output ICP DAS ZT 2026 User Manual Version 1 0 1 Page 127 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command O3RHC9 Response 203 Attempts to read the status of the high alarms for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 51 AACHCi Section 7 4 55 AADHCi Section 7 4 58 AAHI Data CiTOj Section 7 4 61 AARAOj Section 7 4 69 AAROO j Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 128 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 65 AARHi Description This command is used to read the high latch value for a specific Analog Input channel of a specified module Syntax AARHC i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RH The command to read the high latch value for the Analog Input channel i The Analog Input channel to be read zero based Response Valid C
48. 030102 Reads the status of the alarms associated with Digital Output channel 1 of module 03 and returns a response indicating that the command was successful with a value of 1122 meaning that the high alarm on Analog Input channel O and the low alarm on Analog Input channel 1 are associated with the Digital Output channel 1 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 134 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03R009 Response 203 Attempts to read the status of the alarms associated with the Digital Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Digital Output channel 9 does not exist Related Commands Section 7 4 51 AACHCi Section 7 4 54 AACLCi Section 7 4 55 AADHCi Section 7 4 57 AADLCi Section 7 4 58 AAHI Data CiTOj Section 7 4 59 AALO Data CiTOj Section 7 4 61 AARAOJ Section 7 4 64 AARHCi Section 7 4 67 AARLCi ICP DAS ZT 2026 User Manual Version 1 0 1 Page 135 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 Modbus RTU Protocol Command set The Modbus Protocol was developed by Modicon Inc and was originally designed for Modicon controllers Detailed information regarding the Modbus RTU Protocol can be found at http www modicon com and http www modbus org gt Modbus RTU Command Format Fie
49. 0737 The status of the low alarm for Analog Input R R W W ICP DAS ZT 2026 User Manual Version 1 0 1 Page 138 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved a a E A 10034 channels 0 to 1 pot A 30004 0 to 3 pos en ne ee 30066 ae ae Digital Input counter for Digital i 30132 channels 0 to 1 poste fog ne ee 1 Ms mt eee 30516 to 3 pee free ae ieee 30548 3 pros utm port for Digital Outs chamele Oto 30706 Output port for Digital Output channels 0 to 1 porte for Digital int chamele o tot 30738 for Digital Output channels 0 to 1 40034 0 to 1 40098 channels 0 to 1 40194 channels 0 to 1 40260 40290 40324 Input channels 0 to 3 40332 Analog Input channels 0 to 3 40418 jou me 40482 er a 40484 40485 The Module Address The valid range is 1 247 R 40486 The Baud Rate Bit 5 0 Baud Rate Always set to Ox0A Bit 7 6 Reserved ee Host Watchdog timeout value The valid a ae is 0 255 in 0 1 second intervals ICP DAS ZT 2026 User Manual Version 1 0 1 Page 139 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 40490 Enables or disables each Analog Input channel R W 40492 The Host Watchdog timeout counter value Write 0 R W to clear 40580 to 3 i 40612 3 jot Pet ee 40674 0 to 1 40769 The Analog Input calibration type 40772 Ox5A45 Zro Calibration 0x5350 San Calibration 40801 The Analog Output calibration type 40802 Ox5A45 Zro Calibration 0x53
50. 46 02 Sub function 1 0x25 Code 03 Enabled Disabled 1 0x00 to OxFF The enabled disabled status Status of each Analog Input channel where bit 0 corresponds to Analog Input channel 0 and bit 1 corresponds to Analog Input channel 1 etc When the bit is 0 it denotes that the Analog Input channel is disabled and 1 denotes that the Analog Input channel is enabled Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 25 D3 BB Response 01 46 25 07 BB 5F ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 155 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 7 38 0x26 Enabling or Disabling a Analog Input Channel Description This sub function code is used to specify which Analog Input channels of a module are to be enabled Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x26 Code 03 Enabled Disabled 1 0x00 to OxFF The enabled disabled Settings settings for each Analog Input channel where bit 0 corresponds to Analog Input channel 0 and bit 1 corresponds to Analog Input channel 1 etc When the bit is 0 it denotes that the Analog Input channel is disabled and 1 denotes that the Analog Input channel is en
51. 50 San Calibration ICP DAS ZT 2026 User Manual Version 1 0 1 Page 140 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 2 PLC Address Mapping Description Reads the Coils Reads the Discrete Inputs Reads Multiple Registers Reads Multiple Input Registers Writes a Single Coil Writes Multiple Registers Writes Multiple Coils Reads Writes the Module Settings If the function specified in the message is not supported then the module will respond with an error code as per the tablk below Note that the address mapping for the Modbus protocol is Base 0 Error Response Length Value __ i to 247 1 i 00 BEE a1 J Funtion oe O 1 Function code 0780 Note If a CRC mismatch occurs the module will not respond ICP DAS ZT 2026 User Manual Version 1 0 1 Page 141 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved leasa 01 0x01 Reading the Coils Description This function code is used to read the current Digital Output values from the ZT 2000 1 0 module Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x01 02 03 Starting Channel 2 See Section 7 5 1 for details Number or Address Mapping 03 05 Output Channel 2 0x0001 to 0x0020 Number or Bit Count Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x01 02 Byte Count 1 Byte
52. 6 000 Reads the high latch value for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful with a value of 06 000 6 0 V Command 03CH1 Response 103 Clears the high latch value for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful Command 03RH1 Response 103 00 000 Reads the high latch value for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful with a value of 00 000 0 0 V signifying that the high latch value has been cleared ICP DAS ZT 2026 User Manual Version 1 0 1 Page 101 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03CH9 Response 203 Attempts to clear the high latch value for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 1 SAANNTTCCFF Section 7 4 49 AACH Section 7 4 63 AARH Section 7 4 65 AARHi ICP DAS ZT 2026 User Manual Version 1 0 1 Page 102 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 51 AACHC1 Description This command is used to clear the status of the high alarm for a specific Analog Input channel of a specified module Syntax AACHC i CHECKSU
53. 69 AAROOj Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 117 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 59 AALO Data CiTOj Description This command is used to enable the low alarm and set the low alarm limit and Alarm Type for a specific Analog Input channel of a specified module Syntax AALO Data Ci TO j CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF LO The command to enable the low alarm for the Analog Input channel Data The low alarm limit which should be consistent with the engineer ing units format Refer to Section 4 for details of the data format Ci The Analog Input channel where the low alarm is to be enabled zero based T The Alarm Type M Momentary Alarm L Latched Alarm 0j j specifies the Digital Output port to be used for the alarm ouput Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03L0 03 000C1L00 Respon
54. 9 8 1 Software Configuration Mode cece ceeccrccccvcesece 159 8 2 Dual Watchdog Operation 6464444445 5444454SSSS4S4 SSG SSG 160 Bo ESCO STATUS ow se eee au see ee aa E aa EEEE aia EE OE O O EUSES 161 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 4 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 9 Troubleshooting s4 4046006666066600066660806006660006665006665 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 5 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved What s tn the Shipping Package The shipping package contains the following items fice ZT 2026 Module ANT 124 05 Quick Start If any of these items are missing or damaged please contact your local distributor for more information Save the shipping materials and cartons in case you need to ship the module in the future More Information gt Documentation All documentation related to the ZT Series of devices can be found on the companion CD at CD Napdos ZigBee ZT_Series Document Or can be downloaded from http ftp icpdas com pub cd usbcd napdos zigbee zt_series document Software Utility software for the ZT Series of devices can be found on the companion CD at CD Napdos ZigBee ZT_Series Utility Or can be download from http ftp icpdas com pub cd usbcd napdos zigbee zt_series uti lity ICP DAS ZT 2026 User Manual Version 1 0 1 Page 6 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Introduction
55. A4N IAA 74 13 Output Channel AA5 Reads the Reset Status of the Module 7 4 14 Enables or Disables Specific Analog Input AA5VV IAA 7 4 15 Channels Reads whether each Analog Input Channel is AA6 IAAVV 7 4 16 Enabled or Disabled Reads the last Value received by a Specific SAAGN IAA Data d a al 7 4 17 Analog Output Channel Reads the Power on Value for a Specific SAA7N IAA Data 7 4 18 Analog Output Channel Sets the Type Code for a Specific Analog Input SAATCIRIT IAA m PAE TRASE hae Channel Reads the Current Value for a Specific Analo AABN IAA Data pecte Anaog 7 4 20 Output Channel ICP DAS ZT 2026 User Manual Version 1 0 1 Page 27 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Reads the Type Code for a Specific Anal SAABCI IAACIRrr yP anii 7 4 21 Input Channel Reads the Configuration for a Specific Anal SAAQN IAATTS e Configuration for a Specific Analog T Output Channel Sets the Configuration for a Specific Analo SAAQNTS IAA 9 PEE alae Output Channel Clears the Status of the Latched Digital Input SAAC IAA boaa CRETE N wea and Digital Output Channels Reads the Status of the Counter for each AAD AAnn a 7 4 25 Digital Input Channel Enables or Disables the Counter for each SAADnn IAA hi j 7 4 26 Digital Input Channel SAAE ee Reads the Status of the Counter Edge for each Sia Digital Input Channel Sets the Status of the Counter Edges for each SAAEnn sla 7 4 28 Digital Input Channel
56. ALL Rights Reserved 7 4 21 AA8Ci Description This command is used to read the Type Code information for a specific Analog Input channel on a specified module Syntax AA8C i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 8 The command to read the Type Code information for the Analog Input channel Ci i Specifies which Analog Input channel to access for the Type Code information 0 7 Response Valid Command AACiRrr CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Ci i specifies which Analog Input channel the Type Code information relates to Rrr rr represents the Type Code used for the specified Analog Input channel See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 038C0 Response 103COR08 Reads the Analog Input Type Code information for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with a value of 08 denoting that the input range is 10 10V Command 038C9 Respons
57. ARECi IAA Data ery E E I ela Channel Reads the High Latch Values for all Analo AARH AA data 9 i 7 4 63 Input Channels Reads the High Alarm Value for a Specific AARHCI IAA data S 4 7 4 64 Analog Input Channel Reads the High Latch Value for a Specifi AARH IAA data diae iti 7 4 65 Analog Input Channel Reads the Low Latch Values for all Analo AARL IAA data i j 7 4 66 Input Channels Reads the Low Alarm Value for a Specifi AARLCi IAA data S iii 7 4 67 Analog Input Channel Reads the Low Latch Value f ifi AARLI IAA data Sele tl ace nene ee 7 4 68 Analog Input Channel ICP DAS ZT 2026 User Manual Version 1 0 1 Page 29 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Reads whether the Alarms associated with a AAROO AAHHLL specific Digital Output Port are Enabled or Disabled Host Watchdog Command Sets The command to inform all modules that the No Response 7 4 33 Host is OK IAASS Reads the Status of the Host Watchdog 7 4 34 Resets the Status of the Host Watchdog IAA 7 4 35 Timeout Reads the Timeout Settings for the Host zi Watchdog E IAA Enables or Disables the Haa Watchdog and 7437 Sets the Host Watchdog Timeout Value AA Reads the Digital Output Power on Value and o 7 4 38 the Digital Output Safe Value for the module Sets the Digital Output Power on Value and the AA5PPSS IAA eee 7 4 41 Digital Output Safe Value for the module Sets the Analog Output Power on Value for a AAGPN Data
58. AS Co Ltd ALL Rights Reserved The DCON Modbus RTU Command Sets 7 1 Communicating with the ZT 2000 I O Device ICP DAS ZT 2000 0 devices can be operated using either the DCON or the Modbus RTU protocol which can be selected by adjusting the position of DIP Switch 2 to OFF DCON or ON Modbus RTU and then rebooting the ZT 2000 0 device to use the new protocol 7 2 The DCON Protocol Command Set All ZT 2000 1 0 series devices are control led via wireless broadcast commands so each device must have a unique address that is saved in the EEPROM of the device Consequently all command and response formats contain the address of the destination module When an 0 device receives a command it will determine whether or not to respond based on the address contained in the command However there are two exceptions to this the and commands gt DCON Command Format Delimiter Module Character Address Command CHECKSUM CR gt DCON Response Format Delimiter Module Character Address Data CHECKSUM CR xX Note CR is the end of command carriage return character used to end a frame X Note All characters should be expressed in capital letters ICP DAS ZT 2026 User Manual Version 1 0 1 Page 25 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 3 Checksum gt Calculating the Checksum Sum the ASCI codes of al the characters contained in the comm
59. Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR l Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The name of the module as a string value There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030ZT 2026 Response 103 Sets the name of module 03 to ZT 2026 and returns a response indicating that the command was successful Command 03M Response 103ZT 2026 Reads the name of module 03 and returns a response indicating that the command was successful and that the name of the module is ZT 2026 Related Commands Section 7 4 27 AAO Name ICP DAS ZT 2026 User Manual Version 1 0 1 Page 71 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 31 AALS Description This command is used to read the status of the latched Digital Output and Digital Input channels of a specified module Syntax AALS CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF L The command to read the status of the latched Digital Output and Digital Input channels S The status to be read 0 Reads the status
60. Count of the Response B Bit Count 7 8 03 Bit Values B Bit Values Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x81 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2 26 User Manual Version 1 0 1 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Page 142 7 5 4 2 0x02 Reading the Discrete Inputs Description This function code is used to read the current Digital Input values from the ZT 2000 0 module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x02 02 03 Starting Channel 2 See Section 7 5 1 for details Number or Address Mapping 04 05 Input Channel 2 0x0001 to 0x0020 Number or Bit Count Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x02 02 Byte Count 1 Byte Count of the Response B Bit Count 7 8 03 Bit Values B Bit Values Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x82 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 143 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved feda 03 0x03 Reading Multiple Registers Description This function code is used to read from the ZT 2000 1 0 module
61. DAS Co Ltd ALL Rights Reserved NNN NNN NNN NN NN NN NN NN NN NNN NN N N N N NN N N N N N N N N RARRRRRRARA RRR RRR RRR RRR RRR RRR RR RRR RRR AA Ce ee ae 41 SCARING SES oe ee OKRA EERE CER E REED ESRD Oe ees es 43 SAA2 so ec eanndoee hose bbe 445445644 544564654454 4405 45 EVEI Vs age a arena eee ae aera er er ere er er rer eer er a er eer ee ee ee 46 I ek ee NN aha as aha aha aha a aa a ata aa ea aaa 47 BIA Noss corsa ast aw oe EEE EEE E E EEE ENO 49 CARS cee sdes aceasta teehee e eee Ue Ne ee wee eee ees 50 CARS ieee EEEE E E E A EEEE 51 SAN O RE E E RE ARAARA RAAR ee 52 AAGN 36 oo oe en E E E E E wees 53 o snene uad ee eee ee ee ee ee ee eeek 55 SAAT GCIRG eee eee ee eee eReE ER E Aga aE 57 DARGN titans ahs epee ae eae eee ee ae ee we eee eae 58 SANGO Mio i oe a a aa eae aL SiN ALN ainaaS 60 TALON ASA dese eee Cet S Oe CLES SOS eA 61 DON Sica coca 000 oo 22 20 oes arn raranenscaravananecauatananenacatananerecaiararass 63 SAAC ee ee ee ee eee 65 SHAD LLG he eek ae eee R ea LERCEREREE REESE OREN 66 SAAD ecco ei 46 b644446446446444644644646444644644584 6 67 cg EE earner a rere rr err er re Gr Gr ere ar er Gr E Grr eer gar ar 68 CARCI Meee eket cesses eee eee eae week 69 SAAP oe eg ro ae OE a EE ES 70 SAAM hh 1 1 8 hy a Narada thes taygtg te ew Gy tw G7 eG 71 gt LUN ES Ree aR OR Onc ROO OPO RO OR 72 PNAS career ee T O T A T T A E A eee eeeeses 74 E E A E E a E vs E EEEN 75 PPI ee E E E sae a Ce Gs de So Soe Ge SG do de Se eS Gt
62. Digital Output and Digital Input channels of module 03 and returns a response indicating that the command was successful with a value of 000000 showing that all low latched Digital Output and Digital Input channels have been cleared Command 03L2 Response 203 Attempts to read the status of the latched Digital Output and Digital Input channels of module 03 but returns a response indicating that the command was unsuccessful because the status byte parameter was incorrect Related Commands Section 7 4 24 AAC ICP DAS ZT 2026 User Manual Version 1 0 1 Page 73 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 32 AAS1 Description This command is used to reload the factory default calibration parameters for a specified module including the internal calibration parameters Syntax AAS1 CHECKSUM CR Delimiter character AA The address of the module where the default parameters are to be reloaded in hexadecimal format 00 to FF S1 The command to reload the factory default calibration parameters Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a comm
63. Host Watchdog is disabled 1 The Host Watchdog is enabled TT Two hexadecimal digits to represent the timeout value in tenths of a second For example 01 denotes 0 1 seconds and FF denotes 25 5 seconds There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 033164 Response 103 Enables the Host Watchdog for module 03 and sets the Host Watchdog timeout value to 64 10 0 seconds The module returns a response indicating that the command was successful Command 032 Response 103164 Reads the Host Watchdog timeout value for module 03 and returns a response indicating that the command was successful with a value of 164 which denotes that the Host Watchdog is enabled and the Host Watchdog timeout value is 10 0 seconds Related Commands Section 7 4 33 Section 7 4 34 AAO Section 7 4 35 AAI Section 7 4 37 AA3ETT Related Topics Section 8 2 Dual Watchdog Operation ICP DAS ZT 2026 User Manual Version 1 0 1 Page 78 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 37 AA3ZETT Description This command is used to enable or disable the Host Watchdog for a specified module and sets the Host Watchdog timeout value Syntax AA3ETT CHECKSUM CR Delimiter character AA The address of the module to be configured in hexad
64. Input channel where the counter is to be reset zero based Response Valid Command AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RECO Response 10300000008 Reads data from Digital Input channel 0 of module 03 and returns a response indicating that the command was successful with a counter value of 00000008 Command 03CECO Response 103 Resets the counter for Digital Input channel 0 of module 03 to the preset value and returns a response indicating that the command was successful Command 03RECO Response 10300000000 Reads data from Digital Input channel O of module 03 and returns a response indicating that the command was successful with a counter value of 000000000 Command 03CEC9 Response 103 Attempts to reset the counter for Digital Input channel 9 of module 03 to the preset value but returns a response indicating that the command was unsuccessful because ICP DAS ZT 2026 User Manual Version 1 0 1 Page 98 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved
65. M CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CHC The command to clear the status of the high alarm for the Analog Input channe i The Analog Input channel to be cleared zero based Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RA00 Response 1038000 Reads the current status of the alarms associated with Digital Output chanel 0 of module 03 and returns a response indicating that the command was successful and that a high alarm has occurred on Analog Input channel 7 Command 03CHC7 Response 103 Clears the status of the high alarm for Analog Input channel 7 of module 03 and returns a response indicating that the command was successful Command 03RA00 Response 1030000 Reads the current status of the alarms associated with Digital Output chanel 0 of module 03 and returns a response indicating that the command was successful and that no alarms have occurred ICP DAS ZT 2026 User Manual Version 1 0 1 Page 103
66. S Co Ltd ALL Rights Reserved 7 4 16 AA6 Description This command is used to read whether each Analog Input channel of a specified module is either enabled or disabled Syntax AA6 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 6 The command to read the status of the Analog Input channels Response Valid Command 1 AAVV CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF VV A two digit hexadecimal value representing the Analog Input channel where bit 0 corresponds to Analog Input channel 0 and bit 1 corresponds to Analog Input channel 1 etc When the bit is 0 it denotes that the Analog Input channel is disabled and 1 denotes that the Analog Input channel is enabled There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0350A Response 103 Enables Analog Input channels 1 and 3 on module 03 and disables all other Analog Input channels The module returns a response indicating that the command was successful Command 036 Response 1030A Reads the status of the Analog Input cha
67. S The status of the synchronized sampling data 1 This is the first time the data has been read 0 This is NOT the first time the data has been read Data The synchronized sampling data See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command Hx Response There is no response to this command Sends the synchronized sampl ing command instructing every Analog Input module to read data from every input channel and store the data for later retrieval Command 034 Response gt 031 025 12 020 45 012 78 018 97 003 24 015 35 008 07 014 79 Sends the command to read the synchronized sampl ing data from module 03 The module returns a response indicating that the command was successful and containing the data in Engineering Units format that was stored when the synchronized sampl ing command was last issued The status byte of the response is 1 which means that it is the first time the synchronized sampl ing data has been read since the previous command was receieved Command 034 Response gt 030 025 12 020 45 012 78 018 974003 24 015 35 008 07 014 79 Sends the command to read the synchronized sampl ing data from module 03 The module ICP DAS ZT 2026 User Manual Version 1 0 1 Page 47 Copyri
68. ZT 2026 User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year beginning from the date of delivery to the original purchaser Warning ICP DAS assumes no liability for any damage resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for its use nor for any Infringements of patents or other rights of third parties resulting from its use Copyright Copyright 2013 by ICP DAS AIl rights are reserved Trademarks Names are used for identification purposes only and may be registered trademarks of their respective companies Technical Support If you have any problems please feel free to contact us via email at service icpdas com ICP DAS ZT 2026 User Manual Version 1 0 1 Page 1 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Table of Contents 1 InNEroduUCtCiON er ee ee S 7 1 1 Introduction to ZigBee wesc e sc ced iced eee E KEKE R KREMER EOS 7 1 2 Introduction to the ZT 2000 I O Series ccceeeceees 8 2 Hardware Information 4444420404046500402000028888828488800888 9 2 1 Specifications wemir erie eet ere aai 9 2 2 Pin ASSiQuiencs teers eee eee VEE ESA EER 11 2 3 Wire Connections lt s0 5040 seee ea eee ee eee EEE E EEEE EEEE 12 3 Se
69. abled Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x26 Code 03 Enabled Disabled 1 0 OK Settings Others Error Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 26 01 3B AD Response 01 46 26 00 FA 6D ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 156 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 8 41 0x29 Reading the Miscellaneous Settings Description This sub function code is used to read the miscellaneous settings for a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x29 Code Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x29 Code 03 Miscellaneous 1 The data format See Section 4 for details Settings of the format Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 29 D3 BE Response 01 46 29 02 7E 5C ICP DAS ZT 2026 User Manual Version 1 0 1 Page 157 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved
70. active and 1 denotes that the Digital Output power on is active SS A two digit hexadecimal value representing the Digital Output safe value where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output safe value is inactive and 1 denotes that the Digital Output safe value is active There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0350102 Response 103 Sets the Digital Output power on value for module 03 to 01 and the Digital Output safe value to 02 and returns a response indicating that the command was successful Command 034 Response 1030102 Reads the Digital Output power on value and the Digital Output safe value for module 03 and returns a response indicating that the command was successful with a value of 0102 which denotes that the Digital Output power on value is 01 and the Digital Output safe value is 02 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 81 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Related Commands Section 7 4 37 AA3ETT Section 7 4 41 AADPPSS Note Neither the Digital Output power on value nor the Digital Output safe value have any effect on Digital Output channels that are associated with alarm outputs ICP DAS ZT
71. and in addition to the CR terminator The Checksum is the sum value expressed in Hexadecimal format gt Example Command 12 CR Sm O T F 24h 30h 31h 32h Bh Checksum B7 DCON Command with Checksum 012B7 CR gt Example Response 01200600 CR Sum P O TT ca Pe EY a Oe OR Oe OO Oe 21h 30h 31h 32h 30h 30h 36h 30h 30h 1AAh Checksum AA DCON Response with Checksum 01200600AA CR X Note The Checksum is the sum value expressed in capital letters ICP DAS ZT 2026 User Manual Version 1 0 1 Page 26 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 Overview of the DCON Command Set General Command Set R the Analog Input Data f ifi ere gt Data ie nalog Input Data from a Specific H AAN Data Sets the Analog Output for a Specific Channel Performs an Analog Input Span Calibration on SAAO IAA ok 74 6 the Module Performs an Analog Input Zero Calibration on AA1 IAA 7 4 7 the Module Performs a Zero Calibration on a Specific SAAON IAA 7 4 8 Analog Output Channel Performs a Span Calibration on a Specific SAAIN IAA 4 P 74 9 Analog output Channel AA2 IAANNTTCCFF Reads the Configuration of the Module 7 4 10 Trims the Calibration for a Specific Analo SAA3NVV IAA H i 7 4 11 Output Channel Reads the previously stored Synchronized SAM IAAS Data ie ae 74 12 Sampling Data Sets the Power on Value for a Specific Analog SA
72. annel 9 of module 03 to an output range of 5 to 5 V and a slew rate of 0 0625 V Second but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 22 AA9N Section 7 4 42 AAGPN Data Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 64 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 24 AAC Description This command is used to clear the Digital Input and Digital Output latche values for a specified module Syntax AAC CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF C The command to clear the Digital Input and Digital Output latch values Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03L1 Response 1030100 Reads the low latch data for module 03 and returns a response indicating that the command was successful with a
73. as stored when the synchronized sampl ing command was last issued The status byte of the response is 1 which means that it is the first time the synchronized sampl ing data has been read since the previous command was received Command 034 Response gt 030 025 12 020 45 012 78 018 974 003 24 015 35 008 07 014 79 Sends the command to read the synchronized sampl ing data from module 03 The module returns a response indicating that the command was successful containing the data in Engineering Units format that was stored when the synchronized sampl ing command was last issued The status byte of the response is 0 which means that it is NOT the first time the synchronized sampling data has been read since the previous command was received Related Commands Section 7 4 12 AA4 Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 32 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 3 AA Description This command is used to read data from all the Analog Input channels of a specified module Syntax HAA CHECKSUM CR H Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF Response Valid Command gt Data CHECKSUM CR Invalid Command AA CHECKSUM CR gt Delimiter character to indicate a valid command 7 Delimiter character
74. at 00 to FF 9 The command to set the Analog Output configuration N The Analog Output channel to be set zero based T The Analog Output type See Section 5 for details of the data format S The Analog Output slew rate See Section 5 for details of the data format Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR I Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 039051 Response 103 Sets the configuration for Analog Output channel 0 of module 03 to an output range of 5 to 5 V and a slew rate of 0 0625 V Second and returns a response indicating that the command was successful Command 0390 Response 10351 Reads the configuration for Analog Output channel 0 of module 03 and returns a response indicating that the command was successful with a value of 51 meaning that the output range is 5 to 5 V and the slew rate is 0 0625 V Second ICP DAS ZT 2026 User Manual Version 1 0 1 Page 63 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 039951 Response 203 Attempts to set the configuration for Analog Output ch
75. ation has been successful ly saved the fol lowing message wi be displayed pr The configuration file for the Z module has been saved successfu ICP DAS ZT 2026 User Manual Version 1 0 1 Page 162 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved
76. atus of the Digital Input and Digital Output for all channels of module 03 and returns a response indicating that the command was successful and showing that the Digital Output is active on channel 0 and that the Digital Input is active on channel 1 Related Commands Section 7 4 45 AADTT Section 7 4 56 AADI Notes 1 If the Digital Output port is already set as an alarm output port then the value written to the port is ignored 2 If aHost Watchdog timeout occurs the module will return a response indicating that the command was invalid and the Digital Output value that was sent will be ignored ICP DAS ZT 2026 User Manual Version 1 0 1 Page 121 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 61 AARAOJ Description This command is used to read the currently activated alarm associated with a specific Digital Output channel of a specified module Syntax AARAO j CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RA The command to read the currently activated alarms associated with the Digital Output channel 0j j specifies the Digital Output port to be read zero based Response Valid Command 1 AAHHLL CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address o
77. b g ZB Channel North America l 802 15 4 ZB Channel D Protocol Application Mode When implementing custom programs based on different protocols the following application mode s are recommended in order to ensure optimal performance User Program Protocol ZT 2000 ZT 2550 ZT 2570 DCON DCON Transparent Transparent Transparent Transparent Koani RIU soaua REU Modbus Gateway Modbus Gateway Modbus TCP Modbus RTU Modbus Gateway ICP DAS ZT 2026 User Manual Version 1 0 1 Page 13 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 3 2 Introduction to the Rotary and DIP Switches The configuration of the ZT 2026 can be adjusted using a combination of the external rotary switch and the DIP switches The ZT 2000 device should only be rebooted once the configuration is complete ON U2 AS HO a a Address LSB ZB Channel Type Code Address MSB ZB PID Data Format Protocol Checksum gt Rotary Switch Case 1 Address MSB 0 0 1 2 3 4 5 6 1 Address Note 1 01 02 03 04 05 06 07 Node ID Note 1 0x0001 0x0002 0x003 0x0004 0x0005 0x0006 0x0007 8 9 A B C D E F Address 08 09 OA OB 0C OD OE OF Node ID 0x008 0x0009 Ox000A Ox000B Ox000C Ox000D 0x000E Ox000F Case 2 Address MSB 1 0 1 2 3 4 5 6 7 Address 10 11 12 13 14 15 16 17 Node ID 0x0010 0x0011 0x0012 0x013 0x0014 0x0015 0x0016 0x0017
78. character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0301 Response 203 Attempts to perform an Analog Output zero calibration on Analog Output channel 1 of module 03 but a response indicating that the command was unsuccessful is returned because the Enable Calibration command AAEV see Section 7 4 46 was not sent in advance Command 03E1 Response 103 Enables calibration on module 03 and returns a response indicating that the command was successful Command 0301 Response 103 Performs an Analog Output zero calibration on Analog Output channel 1 of module 03 and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 41 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0309 Response 203 Attempts to perform an Analog Output zero calibration on Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 9 AAIN Section 7 4 11 AA3NVV Section 7 4 46
79. chdog is enabled and no Host Watchdog timeout has occurred Command 030 Response 10304 Reads the status of the Host Watchdog for module 03 and returns a response indicating that the command was successful with a value of 04 meaning that a Host Watchdog timeout has occurred Related Commands Section 7 4 33 Section 7 4 35 AA1 Section 7 4 36 AA2 Section 7 4 37 AA3ETT Related Topics Section 8 2 Dual Watchdog Operation ICP DAS ZT 2026 User Manual Version 1 0 1 Page 76 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 35 AA1 Description This command is used to reset the status of the Host Watchdog timeout for a specified module Syntax AA1 CHECKSUM CR Delimiter character AA The address of the module to be reset in hexadecimal format 00 to FF 1 The command to reset the status of the Host Watchdog timeout Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030 Response 10304 Reads the status of the Host Watchdog fo
80. command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030 06 000 Response gt Sets the Analog Output value for Analog Output channel 0 of module 03 to 06 000 6 0 V and returns a response indicating that the command was successful Command 0350 Response 103 Sets the current Analog Output value for Analog Output channel 0 of module 03 as the Analog Output safe value and returns a response indicating that the command was successful Command 0340 Response 103 06 000 Reads the Analog Output safe value for channel 0 of module 03 and returns a response indicating that the command was successful with a value of 06 000 6 0 V Command 0359 Response 203 Attempts to set the current Analog Output value for Analog Output channel 9 of module 03 as the Analog Output safe value but returns a response indicating that ICP DAS ZT 2026 User Manual Version 1 0 1 Page 85 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 37 AA3ETT Section 7 4 39 AAA4N Related Topics Section 5 Analog Output Type and
81. d Power On Value Output range es o 5Y Time p me Set Safe Value Miz n Apply Slew rate Host Watchdog Settings Timeout 0 1 25 5 sec Enable WDT Apply ICP DAS ZT 2026 User Manual immediate change v I Send Host OK Read Safe Value Safe Value Version 1 0 1 Page 19 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Analog Input Type and Data Format Type Code Input Type Data Format F S F S METERT Engineering lls 20 000 04 000 07 nih of FSR 100 00 000 00 2 s Comp Hex FFFF 0000 7 Engineering Units 10 000 10 000 08 w on of FSR 100 00 100 00 2 s Comp Hex 1FFF 8000 Engineering Units 5 0000 5 0000 5 to 5 i A 0 y of FSR 100 00 100 00 2 s Comp Hex TFFF 8000 or Engineering Units 1 0000 1 0000 0 y of FSR 100 00 100 00 2 s Comp Hex 1FFF 8000 B Engineering Units 500 00 500 00 0 am ie of FSR 100 00 100 00 2 s Comp Hex TFFF 8000 7 Engineering Units 150 000 150 00 0 ie be vat of FSR 100 00 100 00 2 s Comp Hex JEFF 8000 R Engineering Units 20 000 20 000 oD s B i of FSR 100 00 100 00 2 s Comp Hex 1FFF 8000 Engineering Units 20 000 00 000 1A pe of FSR 100 00 000 00 2 s Comp Hex FFFF 0000 1 FSR Full Scale Range ICP DAS ZT 2026 User Manual Version 1 0 1 Page 20 Copyright
82. de are loaded from the EEPROM The settings can then be changed using the AANNTTCCFF and AA7CiRrr commands When the ZT 2000 1 0 device is set to software configuration mode the switch settings are ignored ICP DAS ZT 2026 User Manual Version 1 0 1 Page 159 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 8 2 Dual Watchdog Operation Dual Watchdog Module Watchdog Host Watchdog The Module Watchdog is a hardware reset circuit that monitors the operating status of the module While working in harsh or noisy environments the module may be shut down by external signals The Watchdog circuit allows the module to operate continuously without disruption The Host Watchdog is a software function that monitors the operating status of the host Its purpose is to prevent problems due to network communication errors or host malfunctions When a Host Watchdog timeout occurs the module will reset all outputs to a safe state in order to prevent any erroneous operations of the controlled target ZT 2000 series devices include an internal Dual Watchdog making the control system more reliable and stable ICP DAS ZT 2026 User Manual Version 1 0 1 Page 160 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 8 3 Reset Status The reset status of a module is set when the module is powered on or when the module is reset by the Module Watchdog and is cleared after responding to the first AA5 command This can be used to chec
83. do eS Sas 0G do ie oe eG 76 SAAT GaGa tg vcasdasten antes tes es testes lactated is tes estates actactas dete tetera 77 I aV a OR AEE A oh oe teat ae at at geo ge ge ge gelesen ec gndgcceccgccgc ec gcgcgcac ec ecenecacanenecevecers 78 ae 2 3 i ol Mee eee ee re ee ere re A 79 OPA ees eee ee Pee CSE CEIIEECESESEL SSE SSR SEES eek Regs 81 PME CaN Side vse causa casts ch Teer 0 A Sy Sy Sy Se By Sy Sy ye I fe So So So fy SS ee a Sas a ye se 83 SAASN eek e ae Seat cee eee EEE EEE EEE EEE ERE ERE EES 85 SAASPPS Settattdsd eles eee iain aay 87 SAAGPN Data a4 446444 4446cs vb bee eevvnendnsade mm 89 SANOSN CDA A anion er ered ee RRR eC RRR OSCR eS Ress 90 SAAD aoe aos oo een OEE EEEE E E E E E E E sy 91 SAADI Tee eee aiana eee eS 93 AA ht Ce a a a a a a S 95 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 3 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Z447 RRAO NGNE peo eee cee eee t eee nee ee eee ee eee e ee ees 97 TAS RACE 22 cau pws weer eee ow eee ewer eres eer ee eee eee 98 PAA GACH ies casces 100 74 50 AACHi eer eee eee ee ee eee ee a ee 101 peed Uae 1 0 eg Pr E eee 103 TAB CARL ersi 55999555999 F FES EEEE EEEE EEEE EEES 105 7 4 53 QRACLIL 6 ceec een n ee eee kee ae ee eee ee ee Re eee ees 106 oro wn ee ee ee ee eee ee k 108 7 455 AADHCl ccc create eeeseeeeesseeee reassess aeaeeeee 110 Te amp 56 AADL 665 246s 42S SESS 9S SSS S9SSSR2SESS955 442428846 112 Taco AADLCi ia teriieen cere eee eee eee 114 7 4 58 GAAHT
84. e 203 Attempts to read the Type Code information for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 3 AA Section 7 4 4 AAN Section 7 4 19 AA7CiRrr Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 60 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 22 AA9N Description This command is used to read the Analog Output configuration for Analog Output channel N of a specified module Syntax AAQN CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 9 The command to read the Analog Output configuration N The Analog Output channel to be read zero based Response Valid Command 1 AATS CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF T The Analog Output type See Section 5 for details of the data format S The Analog Output slew rate See Section 5 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the s
85. e Registers Description This function code is used to configurethe settings for the ZT 2000 1 0 module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x06 02 03 Address Mapping 2 See Section 7 5 1 for details 04 05 Register Value 2 Register Value Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x06 02 03 Address Mapping 2 The value is the same as bytes 02 and 03 of the Request 04 05 Register Value 2 Register value Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x86 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 147 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Ves res 15 x F Writing Multiple Coils Description This function code is used to write the Digital Output values for the ZT 2000 1 0 module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x0F 02 03 Starting 2 See Section 7 5 1 for details Cchannel Number 04 05 Output Channel 2 0x0001 to 0x0020 Number 06 Byte Count 1 B Bit Count 7 8 07 Output Value 2 A bit corresponds to a channel When the bit is 0 it de
86. e command was successful Command 03RHO Response 103 00 000 Reads the high latch value for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with a value of 00 000 0 0 V signifying that the high latch has been cleared Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 50 AACHi Section 7 4 63 AARH Section 7 4 65 AARHi ICP DAS ZT 2026 User Manual Version 1 0 1 Page 100 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 50 AACHi Description This command is used to clear the high latch value for a specific Analog Input channel of a specified module Syntax AACHi CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CH The command to clear the high latch value for the Analog Input channel i The Analog Input channel to be cleared zero based Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command 7 Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RH1 Response 103 0
87. e indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 5 AAN Data Section 7 4 13 AA4N Section 7 4 42 AA6PN Data Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 56 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 19 AA7CiRrr Description This command is used to set the Type Code for a specific Analog Input channel on a specified module Syntax AA7CiRrr CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 7 The command to set the Type Code Ci i specifies the Analog Input channel to be set 0 7 Rrr rr represents the Type Code to be set for the Analog Inpit channel See Section 4 for details of the data format Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR I Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 037C0R08 Response 103 Sets the Type Code for Analog Input channel 0 of
88. e no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 039051 Response 103 Sets the configuration for Analog Output channel 0 of module 03 to an output range of 5 to 5 V and a slew rate of 0 0625 V Second and returns a response indicating that the command was successful Command 030 05 000 Response gt Sets the Analog Output value for Analog Output channel 0 of module 03 to 05 000 5 0 V and returns a response indicating that the command was successful Command 0380 Response 103 02 500 Reads the current Analog Output value for Analog Output channel 0 of module 03 and returns a response indicating that the command was successful with a value of 02 500 2 5 V ICP DAS ZT 2026 User Manual Version 1 0 1 Page 58 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0389 Response 203 Attempts to read the current Analog Output value for Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 17 AA6N Section 7 4 23 AAQNTS Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 59 Copyright 2013 by ICP DAS Co Ltd
89. ecimal format 00 to FF 3 The command to enable or disable the Host Watchdog E The command to set the Host Watchdog 0 Disables the Host Watchdog 1 Enables the Host Watchdog TT Two hexadecimal digits to represent the Host Watchdog timeout value in tenths of a second For example 01 denotes 0 1 seconds and FF denotes 25 5 seconds Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 033164 Response 103 Enables the Host Watchdog for module 03 and sets the Host Watchdog timeout value to 64 10 0 seconds The module returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 79 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 032 Response 103164 Reads the Host Watchdog timeout value for module 03 The module returns a response indicating that the command was successful with a value of 164 which denotes that the Host Watchdog is enabled and that the Host Watchdog timeout value is 10 0 seconds Related Co
90. ecimal format 00 to FF 6P The command to set the Analog Output power on value N The Analog Output channel to be set zero based Data The Analog Output value See the Section 5 for details of the data format Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 036P0 05 000 Response 103 Sets the Analog Output power on value for Analog Output channel 0 of module 03 to 05 000 5 0 V and returns a response indicating that the command was successful Command 036P0 25 000 Response 203 Attempts to set the Analog Output power on value for Analog Output channel 0 of module 03 to 25 000 25 0 V but returns a response indicating that the command was unsuccessful because the value is not within the valid output range Related Commands Section 7 4 5 AAN Data Section 7 4 13 AA4N Section 7 4 18 AA7N Section 7 4 23 AA9NTS Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 89 Copyright 2013 by ICP DAS Co Ltd ALL Right
91. els of a specified module Syntax AARH CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RH The command to read the high latch values for all Analog Input channels Response Valid Command AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The high latch values for all Analog Input channels See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RH Response 03 08 000 00 000 00 000 00 000 00 000 00 000 00 000 00 000 Reads the high latch values for all Analog Input channels on module 03 and returns a response indicating that the command was successful with the data in engineer ing units format Related Commands Section 7 4 1 AANNTTCCFF Section 74 49 AACH Section 7 4 50 AACHi Section 7 4 65 AARHi Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 126 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 64 AARHC1i Description This command is
92. ent in advance Command 03E1 Response 103 Enables calibration on module 03 and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 39 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 031 Response 103 Performs an Analog Input zero calibration on module 03 and returns a response indicating that the command was successful Related Commands Section 7 4 6 AA0 Section 7 4 46 AAEV Related Topics Section 6 Calibration Notes 1 The Enable Calibration command AAEV must be sent before this command is used See Section 7 4 46 for details 2 This command must be sent before the Span Calibration command AA0 is used See Section 7 4 6 for details ICP DAS ZT 2026 User Manual Version 1 0 1 Page 40 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 8 AAON Description The command is used to performan an Analog Output zero calibration on Analog Output channel N of a specified module Syntax AAON CHECKSUM CR Delimiter character AA The address of the module to be calibrated in hexadecimal format 00 to FF 0 The command to perform the Analog Output zero calibration N The Analog Output channel to be calibrated zero based Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter
93. ere the alarm is to be disabled zero based Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03R000 Response 1030001 Reads whether the alarms associated with Digital Output channel 0 of module 03 are enabled or disabled and returns a response indicating that the command was successful and that the high alarm for Analog Input channel 7 is enabled Command 03DLC0 Response 103 Disables the low alarm for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful Command 03R000 Response 1030000 Reads whether the alarms associated with Digital Output channel 0 of module 03 are enabled or disabled and returns a response indicating that the command was successful and that the low alarms for all Analog Input channels have not been enabled ICP DAS ZT 2026 User Manual Version 1 0 1 Page 114 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03DLC9 Response 203 Attempts to disable the low alarm for Analog Input c
94. ersion Information Description This sub function code is used to read the firmware version information for a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x20 Code Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x20 Code 03 Major Version 1 0x00 to OxFF 04 Minor Version 1 0x00 to OxFF 05 Reserved 1 0x00 06 Build Version 1 0x00 to OxFF Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 20 13 B8 Response 01 46 20 OA 01 00 00 D6 B9 J ICP DAS ZT 2026 User Manual Version 1 0 1 Page 154 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 6 37 0x25 Reading whether a Analog Input Channel is Enabled or Disabled Description This sub function code is used to read whether each Analog Input channel of a module is enabled or disabled Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x25 Code Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x
95. erved 7 4 34 AAQ Description This command is used to read the status of the Host Watchdog for a specified module Syntax m AAO CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 0 The command to read the status of the Host Watchdog Response Valid Command 1 AASS CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF SS Two hexadecimal digits that represent the status of the Host Watchdog where Bit 2 0 indicates that no Host Watchdog timeout has occurred and 1 indicates that a Host Watchdog timeout has occurred Bit 7 0 indicates that the Host Watchdog is disabled and 1 indicates that the Host Watchdog is enabled The status of the Host Watchdog is stored in the EEPROM and can only be reset by using the AA1 command See Section 7 4 35 for more detai Is There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030 Response 10380 Reads the status of the Host Watchdog for module 03 and returns a response indicating that the command was successful with a value of 00 meaning that the Host Wat
96. f the responding module in hexadecimal format 00 to FF HH A two digital hexadecimal value representing the currently activated high alarms associated with the Digital Output port where bit 0 corresponds to channel 0 and bit 1 corresponds to channel 1 etc When the bit is 0 it denotes that there are no activated high alarm associated with the channel and 1 denotes that there is an activated high alarms associated with the channel LL A two digital hexadecimal value respresenting the currently activated low alarms associated with the Digital Output port where bit 0 corresponds to channel 0 and bit 1 corresponds to channel 1 etc When the bit is 0 it denotes that there are no activated low alarm associated with the channel and 1 denotes that there is an activated low alarms associated with the channel There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RA01 Response 1031122 Reads the currently activated alarms associated with the Digital Output channel 1 of module 03 and returns a response indicating that command was successful with a value of 1122 which denotes that there is an activated high alarm associated with channels 0 and 4 and an activated low alarm associated with channels 1 and 5 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 122 Copyright 2013 by ICP DAS C
97. ght 2013 by ICP DAS Co Ltd ALL Rights Reserved returns a response indicating that the command was successful and containing the data in Engineering Units format that was stored when the synchronized sampl ing command was last issued The status byte of the response is 0 which means that it is NOT the first time the synchronized sampling data has been read since the previous command was received Related Commands Section 7 4 2 Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 48 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 13 AA4N Description This command is used to store the current Analog Output value as the Analog Output power on value for Analog Output channel N of a specific module Syntax AA4N CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 4 The command to store the current Analog Output value as the power on value N The Analog Output channel to be set zero based Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command 2 Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a
98. ght 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 10 AA2 Description This command is used to read the configuration of a specified module Syntax AA2 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 2 The command to read the configuration of the module Response Valid Command NNTTCCFF CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command NN The address of the module that is saved in the EEPROM in hexadecimal format 00 to FF TT 00 Reserved CC OA Reserved FF The data format checksum settings and filter settings for the module See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 032 Response FFOOOA00 In Normal mode reads the configuration of module 03 The response indicates that the command was successful and shows that the address stored in the EEPROM is OxFF that the filter is set to 60 Hz rejection and that the data format is Engineer ing Units Command FF2 Response FFOOOA00 In Software Configuration mode reads the configuration of module FF The response indicates that
99. hannel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 54 AACLCi Section 7 4 59 AALO Data CiTOj Section 7 4 61 AARAOj Section 7 4 67 AARLCi Section 7 4 69 AAROO j ICP DAS ZT 2026 User Manual Version 1 0 1 Page 115 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 58 AAHI Data CiTOj Description This command is used to enable the high alarm and set the high alarm limit and Alarm Type for a specific Analog Input channel of a specified module Syntax AAHI Data Ci TOj CHECKSUM CR Delimiter character AA The address of the module to be enabled in hexadecimal format 00 to FF HI The command to enable the high alarm for the Analog Input channel Data The high alarm limit which should be consistent with the engineering units format Refer to Section 4 for details of the data format Ci The Analog Input channel where the high alarm is to be enabled zero based T The Alarm Type M Momentary Alarm L Latched Alarm 0j j specifies the Digital Output port to be used for the alarm ouput Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the respond
100. he input type code for the ZT 2026 as shown below ZB Channel ZB PID Type Code Data Format Switch Switch Switch sess Type Code as Type Code ie Type Code Position Position Position ON ON ERR 0x08 0x09 Ox0A if tas be F io a E TZ ON ON ON LL 0x0B aT 0x0C 7 Ox0D 10 1 12 ete 12 10 11 12 ON ON hed 0x07 EEE 0x1A 10 11 12 10 11 12 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 16 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 3 3 Starting the ZT 2000 I O Device As the ZigBee network is controlled by the ZigBee Coordinator the ZT 2550 ZT 2570 ZigBee Coordinator must be configured first Refer to the documents section below for full details of how to configure these devices Once configuration of the ZigBee Coordinator has been completed set the ZB PID and ZB Channel values for the ZT 2000 0 device to the same values as the network and then reboot the device The module will automatically start to function on the ZigBee network using the default protocol xX Documents http ftp icpdas com tw pub cd usbcd napdos zigbee zt_ser ies document zt 255x http ftp icodas com tw pub cd usbcd napdos zi gbee zt_ser ies document zt 25 x X Configuration Utility Used to configure the ZT 2000 0 device Coordinator http ftp icodas com tw pub cd usbcd napdos zigbee zt_series utility 3 4 Communications Testing Once the ZT 2000 1 0 device has
101. her the Digital Output channels for a specified module are set to active or inactive Syntax AADODD CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF DO The command to set the Digital Output ports to active or inactive DD A two digit hexadecimal value representing the Digital Output port where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output port will be inactive and 1 denotes that the Digital Output port will be active Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D001 Response 103 Sets Digital Output channel 0 of module 03 to active and sets Digital Output channel 1 to inactive and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 120 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03D Response 1030102 Reads the st
102. ing module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03H1 09 OOOCOMO Response 103 Sets the high alarm limit for Analog Input channel 0 of module 03 to 09 000 9 0 V sets the Alarm Type to momentary and sets Digital Output channel 1 as the high alarm output and returns a response indicating that the command was successful Command 03RHCO Response 103 09 000101 Reads the status of the high alarms for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful and that the high alarm limit is 09 000 9 0 V the Alarm Type is momentary and Digital Output channel 1 is set as the high alarm output ICP DAS ZT 2026 User Manual Version 1 0 1 Page 116 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03H1 09 OOOCOMO Response 103 Attempts to set the high alarm limit for Analog Input channel 9 of module 03 to 09 000 9 0 V the Alarm Type to momentary and Digital Output channel 1 as the high alarm output but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 51 AACHCi Section 7 4 55 AADHCi Section 7 4 61 AARAOj Section 74 64 AARHCi Section 7 4
103. invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RL1 Response 103 06 000 Reads the low latch value for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful with a value of 06 000 6 0 V Command 03CL1 Response 103 Clears the low latch value for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful Command 03RL1 Response 103 00 000 Reads the low latch value for Analog Input channel 1 of module 03 and returns a response indication that the command was successful with a value of 00 000 0 0 V signifying that the low latch value has been cleared Command 03CL9 Response 203 Attempts to clear the low latch value for Analog Input channel 9 of module 03 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 106 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 52 AACL Section 7 4 66 AARL Section 7 4 68 AARL i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 107 Cop
104. iscellaneous settings for module 03 and returns a response indicating that the command was successful with a value of 01 which denotes that the Digital ICP DAS ZT 2026 User Manual Version 1 0 1 Page 93 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Output channels are in inactive mode Related Commands Section 7 4 44 AAD Section 7 4 56 AADI Section 7 4 60 AADODD ICP DAS ZT 2026 User Manual Version 1 0 1 Page 94 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 46 AAEV Description This command is used to enable or disable calibration for a specified module Syntax AAEV CHECKSUM CR Delimiter character AA The address of the module where calibration is to be enabled or disabled in hexadecimal format 00 to FF E The command to enable or disable calibration V The command to enable or disable calibration 0 Disables calibration 1 Enables calibration Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030 Response
105. k whether the module has been previously reset When the response to the AA5 command indicates that the reset status has been cleared it means that the module has not been reset since the last AA5 command was sent When the response to the AA5 command indicates that the reset status has been set and it is not the first time the AA5 command has been sent it means that the module has been reset and the Digital Output value has been changed to the power on value ICP DAS ZT 2026 User Manual Version 1 0 1 Page 161 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Troubleshooting A Technical Support If you have any difficulties using your ZT 2000 series 1 0 device please send a description of the problem to service icpdas com Include the following items in your email A description or diagram of the current DIP switch positions A copy of the configuration file for the ZI 2000 coordinator This file can be obtained using the procedure out ined below and should be attached to your email B Set the DIP switch for the ZT 255x device to the ZBSET position then reboot the device Launch the ZT Configuration Utility and select the Save Log icon to save the configuration of the ZI 255x as a file E zerowy on 4 Please select the setting mode nk vie C After clicking the Save Log icon enter the File Name and the File Path in the Windows Save dialog box Once the configur
106. ld Field Field Field Field 1 2 3 4nn n 1 n 2 Module Function Sub Conf i guration CRC16 Address Code Function Field Function Code Description 0x04 Reads the input channels 0x46 Reads writes the module settings Examples A To read the Analog Input value for module 01 the following command should be sent 01 04 00 00 00 08 F1 CC B To read the name of the module the fol lowing command should be sent 01 46 00 12 60 ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 136 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 1 Modbus Address Mapping Address Mapping Address 00002 00066 00074 00098 00106 00130 E R 00161 The Digital Output power on value 00162 00193 The status of the Digital Input counter edge R 00194 0 Falling Edge 1 Rising Edge 00225 The status of the Digital Input counter R W 00226 0 Disabled 1 Enabled 00259 The Filter settings R W 0 60Hz rejection 1 50Hz rejection 00260 The Modbus Host Watchdog mode R W 0 The same as the l 7000 series modules 1 The Analog Output and Digital Output commands can be used to clear the status of the Host Watchdog timeout 00261 Enables or disables the Host Watchdog R W 0 Disable 1 Enable 00264 The Digital Input Digital Output high latch and low latch values Write 1 to clear channels 0 to 1 00266 The status of the Digital Input counter Write 1 to clear channels 0 to 1 00269 The Modbus Data Format R
107. lid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The low latch value for the specified Analog Input channel See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RLO Response 103 02 000 Reads the low latch value for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with the data in engineer ing units format Command 03RL9 Response 203 Attempts to read the low latch value for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 52 AACL Section 7 4 53 AACLi Section 7 4 66 AARL Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 133 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 69 AAROOj Description This command is used to read whether the alarms associated with a specific Digital Output channel of a specified module are enabled or disabled
108. limiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 030ZT 2026 Response 103 Sets the name of module 03 to ZT 2026 and returns a response indicating that the command was successful Command 03M Response 103ZT 2026 Reads the name of module 03 and returns a response indicating that the command was successful with the name ZT 2026 Command 030123456789ABCDEF Response 203 Attempts to set the name of module 03 to 123456789ABCDEF but returns a response indicating that the command was unsuccessful because the name is longer than 8 characters Related Commands Section 7 4 30 AAM ICP DAS ZT 2026 User Manual Version 1 0 1 Page 97 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 48 AACEC1 Description This command is used to reset the counter for a specific Digital Input channel of a specified module Syntax AACEC i CHECKSUM CR Delimiter character AA The address of the module to be reset in hexadecimal format 00 to FF CE The command to reset the counter Ci i specifies the Digital
109. mat 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0350102 Response 103 Sets the Digital Output power on value for module 03 to 01 and the Digital Output safe value to 02 and returns a response indicating that the command was successful Command 034 Response 1030102 Reads the Digital Output power on value and the Digital Output safe value for module 03 and returns a response indicating that the command as successful with a value of 0102 which denotes that the Digital Output power on value is 01 and the Digital Output safe value is 02 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 87 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Related Commands Section 7 4 37 AA3ETT Section 7 4 38 AA4 Note Neither the Digital Output power on value nor the Digital Output safe value have any effect on the Digital Output channels that are associated with alarm outputs ICP DAS ZT 2026 User Manual Version 1 0 1 Page 88 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 42 AA6PN Data Description This command is used to set the power on value for Analog Output channel N of a specified module Syntax AAG6PN Data CHECKSUM CR Delimiter character AA The address of the module to be set in hexad
110. mmand Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03R000 Response 1038000 Reads whether the alarms associated with Digital Output channel O of module 03 are enabled or disabled and returns a response indicating that the command was successful and that the high alarm for Analog Input channel 7 is enabled Command 03DHC7 Response 103 Disables the high alarm for Analog Input channel 7 of module 03 and returns a response indicating that the command was successful Command 03R000 Response 1030000 Reads whether the alarms associated with Digital Output channel 0 of module 03 are enabled or disabled and returns a response indicating that the command was successful and that the alarms for all Analog Input channels have not been enabled Command 03DHC9 Response 203 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 110 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Attempts to disable the high alarm for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section
111. mmands Section 7 4 33 Section 7 4 34 AAO Section 7 4 35 AA1 Section 7 4 36 AA2 Section 7 4 38 AA4 Section 7 4 39 AAA4N Section 7 4 40 AADN Section 7 4 41 AA5PPSS Related Topics Section 8 2 Dual Watchdog Operation Note When a Host Watchdog timeout occurs the Host Watchdog is disabled In this case the AA3ETT command should be sent again to re enable the Host Watchdog ICP DAS ZT 2026 User Manual Version 1 0 1 Page 8 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 38 AA4 Description This command is used to read the Digital Output power on value and the Digital Output safe value for a specified module Syntax AA4 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 4 The command to read the Digital Output power on value and the Digital Output safe value Response Valid Command AAPPSS CHECKSUM CR Invalid Command AA CHECKSUM CR l Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF PP A two digit hexadecimal value representing the Digital Output power on value where bit 0 corresponds to Digital Output channel 0 and bit 1 corresponds to Digital Output channel 1 etc When the bit is 0 it denotes that the Digital Output power on is in
112. nalog Input channel of a specified module Syntax AARLC i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RL The command to read the status of the low alarm for the Analog Input channe Ci The Analog Input channel to be read zero based Response Valid Command 1AA Data SO j CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The status of the low alarm for the specified Analog Input channel in engineering units See Section 4 for details of the data format S The Alarm Type 0 Alarm Disabled 1 Momentary Alarm 2 Latched Alarm 0j J specifies the Digital Output channel that was read zero based There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03L0 03 000C1L01 Response 103 Sets the low alarm limit for Analog Input channel 1 of module 03 to 03 000 3 0 V sets the Alarm Type to latched and sets Digital Output channel 1 as the low alarm output and returns a response indicating that the command was successful Command 03RLC1 Response 103 03 000201 Reads the
113. nnels on module 03 and returns a response indicating that the command was successful with a value of 0A which denotes that Analog Input channels 1 and 3 are enabled and al other Analog Input channels are disabled Related Commands Section 7 4 15 AA5VV ICP DAS ZT 2026 User Manual Version 1 0 1 Page 52 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 17 AA6N Description This command is used to read the Analog Output requisition for channel N of a specified module Syntax AA6N CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 6 The command to read the output value requisition N The Analog Output channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The output requistion value See Section 5 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 031 10 000 Response 103 Sets the Analog Output requisition value for Analog Output channel 1 of module 03 to 10 000 10
114. notes that the channel that was set is OFF or Disabled If the bit is 1 it denotes that the channel that was set is ON or Enabled Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 Ox0F 02 03 Starting Channel 2 The value is the same as bytes 02 and 03 Number of the Request 04 05 Output Channel 2 0x0001 0x0020 Number Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 Ox8F 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 148 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 5 10 70 0x46 Reading Writing the Module Settings Description This function code is used to read the configuration settings from the module or to change the settings for the module The following sub function codes are supported Oe anaes 2 Description Section 00 0x00 Reads the Name of the Module A 1 04 0x04 Sets the Address of the Module A 2 07 0x07 Reads the Type Code A 3 08 0x08 Sets the Type Code A 4 32 0x20 Reads the Firmware Version A 5 37 0x25 Reads whether a Specific Channel is A 6 Enabled or Disabled 38 0x26 Sets a Specific Channel to Enabled A 7 or Disabled 41 0x29 Reads the Miscellaneous Settings A 8 42 0x2A Writes the Miscellaneous Settings A 9 If the sub function code specified in the message is not su
115. o Ltd ALL Rights Reserved Command O3RA09 Response 203 Attempts to read the currently activated alarms associated with the Digital Output channel 9 of module 03 but returns a response indicating that command was unsuccessful because Digital Output channel 9 does not exist Related Commands Section 7 4 51 AACHCi Section 7 4 54 AACLCi Section 7 4 55 AADHCi Section 7 4 57 AADLCi Section 7 4 58 AAHI Data CiTOj Section 7 4 59 AALO Data CiTOj Section 7 4 64 AARHCi Section 7 4 67 AARLCi Section 7 4 69 AAROO j ICP DAS ZT 2026 User Manual Version 1 0 1 Page 123 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 62 AAREC1i Description This command is used to read the counter value for a specific Digital Input channel of a specified module Syntax AAREC i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RE The command to read the counter value for the Digital Input channel Ci The Digital Input channel to be read zero based Response Valid Command 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The counter value for the specified Digital Input
116. oltage is low an input value of 0 indicates that the voltage is high 1 an input value of 0 indicates that there is no signal or the voltage is low an input value of 1 indicates that the voltage is high There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D01 Response 103 Sets the miscellaneous settings for module 03 to 01 meaning that the Digital Output channels are in inactive mode and returns a response indicating that the command was successful Command 03D Response 10301 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 91 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Reads the miscellaneous settings for module 03 and returns a response indicating that the command was successful with a value of 01 which denotes that the Digital Output channels are in inactive mode Related Commands Section 7 4 45 AADTT Section 7 4 56 AADI Section 7 4 60 AADODD ICP DAS ZT 2026 User Manual Version 1 0 1 Page 92 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 45 AADTT Description This command is used to set the Digital Input and Digital Output configuration for a specified module Syntax AADTT CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format
117. ommand 1AA Data CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The high latch value for the specified Analog Input channel See Section 4 for details of the data format There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RHO Response 103 08 000 Reads the high latch value for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with the data in engineer ing units format Command 03RH9 Response 203 Attempts to read the high latch value for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 49 AACH Section 7 4 50 AACHi Section 7 4 63 AARH Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 129 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 66 AARL Description This command is used to read the low latch values for all Analog Input channels of a specified module
118. or Digital Input channels 0 and 1 are enabled and the counters for all other Digital Input channels are disabled Related Commands Section 7 4 25 AAD Section 7 4 48 AACECi Section 7 4 62 AAREC i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 67 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 27 AAE Description This command is used to read whether the counter edges for each Digital Input channel of a specified module are rising or falling Syntax AAE CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF E The command to read the status of the counter edges for the Digital Input channels Response Valid Command AAnn CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF nn A two digit hexadecimal value representing the Digital Input channel where bit 0 corresponds to Digital Input channel 0 and bit 1 corresponds to Digital Input channel 1 etc When the bit is 0 it denotes that the counter edge for the Digital Input channel is falling and 1 denotes that the counter edge for the Digital Input channel is rising There will be no response if the command syntax is incorrect there is a communication e
119. pecified address Examples Command 039051 Response 103 Sets the configuration for Analog Output channel 0 of module 03 to an output range of 5 to 5 V and a slew rate of 0 0625 V Second and returns a response indicating that the command was successful Command 0390 Response 10351 Reads the configuration for Analog Output channel 0 of module 03 and returns a response indicating that the command was successful with a value of 51 meaning that the output range is 5 to 5 V and the slew rate is 0 0625 V Second ICP DAS ZT 2026 User Manual Version 1 0 1 Page 61 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0399 Response 203 Attempts to read the configuration for Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Output channel 9 does not exist Related Commands Section 7 4 5 AAN Data Section 7 4 23 AAQNTS Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 62 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 23 AA9NTS Description This command is used to set the configuration for Analog Output channel N of a specified module Syntax AAQNTS CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal form
120. pported then the module will respond with an error code as per the table below Error Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details ICP DAS ZT 2 26 User Manual Version 1 0 1 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Page 149 A 1 00 0x00 Reading the Name of a Module Description This sub function code is used to read the name of a module Request Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x00 Code Response Byte Description Length Value 00 Address 1 1 to 247 01 Function Code 1 0x46 02 Sub function 1 0x00 Code 03 06 Module Name 4 0x54 0x20 0x26 0x00 Error Response Byte Description Length Value 00 Address 1 1 to 241 01 Function Code 1 0xC6 02 Exception Code 1 Refer to the Modbus standard for more details Example Command 01 46 00 12 60 Response 01 46 00 54 20 26 00 OE FC ICP DAS ZT 2 26 User Manual Version 1 0 1 Page 150 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved A 2 04 0x04 Setting the Address of the Module Description This sub function code is used to set the address fo the module
121. r ZT 2550 ZT 2570 2 Click the Search button to start searching for ZT 2000 1 0 devices connected to the same ZigBee network 3 If any ZT 2000 0 devices are found they will be displayed in the device list window Double click the name of the module to start the operation Timeout Settings lity_version 525 beta 1 result of fin oO Select the COM Port and Baud Rate Ej pecz rs Select COM to search comt 300 ms pea Bal Checksum paa nem EN N Bi v 115200 M 57600 f 38400 19200 mM 9600 M 4800 m 2400 mM 1200 O DCONW_Utility versio 525 beta 1 result of find Sr ae pbs PDE MO File COM Port Search Terminal Language Help Protocol Options M DCON i ModbusRTU Modbus ASCII pio Atess Baud ate Checks IF 21 2026 115200 Disable m for Z1 2026 Module ersion 401 Checksum Options Disabled Enabled Parity V None N 8 1 Even E 8 1 Configurations amp AO Al amp DO Alarm Configuration Settings Channel Output fi None N 8 2 mn Odd 0 3 1 software hardware Channet 0 99 000 v PNE eae Caer configuration configuration 2 Pr Modbus ATU 10 0 10 Set Power On Value Read Power On Value PUEA Dutput range fa v y 10 RTS Apply __ Set Safe Value a Slew rate immediate change Read Safe Value eae wane he Channel Output 7 p Output value Read back Channel 1 00 000 v Apply 5 0 5 Set Power On Value Command Response Delay Time Rea
122. r module 03 and returns a response indicating that the command was successful and that a Host Watchdog timeout has occurred Command 031 Response 103 Resets the status of the Host Watchdog timeout for module 03 and returns a response indicating that the command was successful Command 030 Response 10300 Reads the status of the Host Watchdog for module 03 and returns a response indicating that the command was successful and showing that no Host Watchdog timeout has occurred Related Commands Section 7 4 33 Section 7 4 34 AAO Section 7 4 36 AA2 Section 7 4 37 AA3ETT Related Topics Section 8 2 Dual Watchdog Operation ICP DAS ZT 2026 User Manual Version 1 0 1 Page 77 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 36 AA2 Description This command is used to read the Host Watchdog timeout value for a specified module Syntax AA2 CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF 2 The command to read the Host Watchdog timeout value Response Valid Command 1 AAETT CHECKSUM CR Invalid Command AA CHECKSUM CR I Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF E The status of the Host Watchdog 0 The
123. re bit 0 corresponds to Digital Input channel 0 and bit 1 corresponds to Digital Input channel 1 etc When the bit is 0 it denotes that the counter for the Digital Input channel is disabled and 1 denotes that the counter for the Digital Input channel is enabled There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D03 Response 103 Enables the counters for Digital Input channels 0 and 1 on module 03 and disables the counters for all other Digital Input channels The module returns a response indicating that the command was successful Command 03D Response 10303 Reads the status of the counters for each Digital Input channel on module 03 and returns a response indicating that the command was successful with a value of 03 which denotes that the counters for Digital Input channels 0 and 1 are enabled and that the counters for all other Digital Input channels are disabled Related Commands Section 7 4 26 AADnn Section 7 4 48 AACECi Section 7 4 62 AAREC i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 66 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 26 AADnn Description This command is used to enable or disable the counter for each Digital Input channel of a specified module Syntax AADnn CHECKSUM CR
124. response if the command syntax is incorrect there is a communication error or there is no module with the specified address ICP DAS ZT 2026 User Manual Version 1 0 1 Page 35 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Examples Command 039050 Response 103 Sets the output range for Analog Output channel O of module 03 to 5 to 5 V and sets the slew rate to change immediately and returns a response indicating that the command was successful Command 030 05 000 Response gt Sets the output value for Analog Output channel 0 of module 03 to 05 000 5 0 V and returns a response indicating that the command was successful Command 030 25 000 Response Attempts to set the output value for Analog Output channel 0 of module 03 to 25 000 25 V but returns a response indicating that the command was unsuccessful because the output value of 25 000 25 V is not within the valid range The Analog Output value will be restored to the closest value of 05 000 5V defined in the range settings for the module Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 22 AA9N Section 7 4 23 AAQNTS Related Topics Section 5 Analog Output Type and Slew Rate ICP DAS ZT 2026 User Manual Version 1 0 1 Page 36 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 6 AAO Description This command is used to perfo
125. rm an Analog Input span calibration on a specified module Syntax AA0 CHECKSUM CR Delimiter character AA The address of the module to be calibrated in hexadecimal format 00 to FF 0 The command to perform the Analog Input span calibration Response Valid Command Invalid Command AA CHECKSUM CR AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address ICP DAS ZT 2026 User Manual Version 1 0 1 Page 37 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Examples Command 030 Response 203 Attempts to perform an Analog Input span calibration on module 03 but a response indicating that the command was unsuccessful is returned because the Enable Calibration command AAEV see Section 7 4 46 was not sent in advance Command 03E1 Response 103 Enables calibration on module 03 and returns a response indicating that the command was successful Command 030 Response 103 Performs an Analog Input span calibration on module 03 and returns a response indicating that the command was successful
126. rm an Analog Output span calibration on Analog Output channel 1 of module 03 but a response indicating that the command was unsuccessful is returned because the Enable Calibration command AAEV see Section 7 4 46 was not sent in advance Command 03E1 Response 103 Enables calibration on module 03 and returns a response indicating that the command was successful Command 0311 Response 103 Performs an Analog Output span calibration on Analog Output channel 1 of module 03 and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 43 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 0319 Response 203 Attempts to perform an Analog Output span calibration on Analog Output channel 9 of module 03 but returns a response indicating that the command was unsuccessful because the Analog Output channel 9 does not exist Related Commands Section 7 4 8 AAON Section 7 4 11 AA3NVV Section 7 4 46 AAEV Related Topics Section 6 Calibration Notes 1 The Enable Calibration command AAEV and the Analog Output Zero Calibration command AAON must be sent before this command is used See Sections 7 4 46 and 7 4 8 for details 2 For Analog Output channels calibration must be performed for each channel individual ly ICP DAS ZT 2026 User Manual Version 1 0 1 Page 44 Copyri
127. rror or there is no module with the specified address Examples Command 03E03 Response 103 Sets the counter edges for Digital Input channels 0 and 1 of module 03 to rising and sets the counter edges for all other Digital Input channels to falling The module returns a response indicating that the command was successful Command 03E Response 10303 Reads the status of the counter edges for all Digital Input channels on module 03 and returns a response indicating that the command was successful with a value of 03 which denotes that the counter edges for Digital Input channels O and 1 are rising and the counter edges for all other Digital Input channels are fal ing Related Commands Section 7 4 28 AAEnn ICP DAS ZT 2026 User Manual Version 1 0 1 Page 68 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 28 AAEnn Description This command is used to specify whether the counter edges for each Digital Input channel of a specified module are to be rising or falling Syntax AAEnn CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF E The command to set the counter edges for the Digital Input channels nn A two digit hexadecimal value representing the Digital Input channel where bit 0 corresponds to Digital Input channel 0 and bit 1 corresponds to Digital Input channel 1 etc
128. s Reserved 7 4 43 AA6SN Data Description This command is used to set the safe value for Analog Output channel N of a specified module Syntax AA6SN Data CHECKSUM CR Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF 6S The command to set the Analog Output safe value N The Analog Output channel to be set zero based Data The Analog Output value See Section 5 for details of the data format Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 036S0 05 000 Response 103 Sets the Analog Output safe value for Analog Output channel 0 of module 03 to 05 000 5 0 V and returns a response indicating that the command was successful Command 036S0 25 000 Response 203 Attempts to set the Analog Output safe value for Analog Output channel 0 of module 03 to 25 000 25 0 V but returns a response indicating that the command was unsuccessful because the value is not within the valid output range
129. s the low latch value for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with a value of 05 000 5 0 V Command 03CL Response 103 Clears the low latch values for all Analog Input channels of module 03 and returns a response indicating that the command was successful Command 03RLO Response 103 00 000 Reads the low latch value for Analog Input channel 0 of module 03 and returns a response indicating that the command was successful with a value of 00 000 0 0 V signifying that the low latch value has been cleared Related Commands Section 7 4 53 AACLi Section 7 4 66 AARL Section 7 4 68 AARL i ICP DAS ZT 2026 User Manual Version 1 0 1 Page 105 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 53 AACLi Description This command is used to clear the low latch value for a specific Analog Input channel of a specified module Syntax AACL i CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CL The command to clear the low latch value for the Analog Input channel i The Analog Input channel to be cleared zero based Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command 2 Delimiter character to indicate an
130. se 103 Sets the low alarm limit for Analog Input channel 1 of module 03 to 03 000 3 0 V sets the Alarm Type to latched and sets Digital Output channel 0 as the low alarm output and returns a response indicating that the command was successful Command 03RLC1 Response 103 03 000200 Reads the status of the low alarms for Analog Input channel 1 of module 03 and returns a response indicating that the command was successful and that the low alarm limit is 03 000 3 0 V the Alarm Type is latched and Digital Output channel 0 is set as the low alarm output ICP DAS ZT 2026 User Manual Version 1 0 1 Page 118 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03L0 03 000C9L00 Response 103 Attempts to set the low alarm limit for Analog Input channel 9 of module 03 to 03 000 3 0 V the Alarm Type to latched and Digital Output channel 0 as the low alarm output but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 54 AACLCi Section 7 4 57 AADLCi Section 7 4 61 AARAOj Section 7 4 67 AARLCi Section 7 4 69 AAROO j Related Topics Section 4 Analog Input Type and Data Format ICP DAS ZT 2026 User Manual Version 1 0 1 Page 119 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 60 AADODD Description This command is used to specify whet
131. sponse 1030000 Reads the current status of the alarms associated with Digital Output channel 0 for module 03 and returns a response indicating that the command was successful and that no alarms have occurred Command 03CLC9 Response 203 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 108 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Attempts to clear the status of the low alarm for Analog Input channel 9 of module 03 but returns a response indicating that the command was unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 57 AADLCi Section 7 4 59 AALO Data CiTOj Section 7 4 61 AARAOj Section 7 4 67 AARCi Section 7 4 69 AARAOO j ICP DAS ZT 2026 User Manual Version 1 0 1 Page 109 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 55 AADHCi Description This command is used to disable the high alarm for a specific Analog Input channel of a specified module Syntax AADHC i CHECKSUM CR Delimiter character AA The address of the module to be configured in hexadecimal format 00 to FF DH The command to disable the high alarm for the Analog Input channel Ci The Analog Input channel where the alarm is to be disabled zero based Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid co
132. that the Digital Input is inactive and 1 denotes that the Digital Input is active There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03D001 Response 103 Sets Digital Output channel 0 of module 03 to ON and sets Digital Output channel 1 to OFF and returns a response indicating that the command was successful ICP DAS ZT 2026 User Manual Version 1 0 1 Page 112 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved Command 03D Response 1030102 Reads the status of the Digital Input and Digital Output for all channels of module 03 and returns a response indicating that the command was successful and showing that the Digital Output is active on channel 0 and that the Digital Input is active on channel 1 Related Commands Section 7 4 45 AADTT Section 7 4 60 AADODD ICP DAS ZT 2026 User Manual Version 1 0 1 Page 113 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 57 AADLC1 Description This command is used to disable the low alarm for a specific Analog Input channel of a specified module Syntax AADLC i CHECKSUM CR Delimiter character AA The address of the module to be configured in hexadecimal format 00 to FF DL The command to disable the low alarm Ci The Analog Input channel wh
133. the command was successful and shows that the address stored in the EEPROM is OxFF that the filter is set to 60 Hz rejection and that the data format is Engineering Units Related Commands Section 7 4 1 AANNTTCCFF Related Topics Section 4 Analog Input Type and Data Format Section 5 Analog Output Type and Slew Rate Section 8 1 Software Configuration Mode ICP DAS ZT 2026 User Manual Version 1 0 1 Page 45 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 11 AA3NVV Description The command is used to trim the calibration for Analog Output channel N of a specified module Syntax AA3NVV CHECKSUM CR Delimiter character AA The address of the module to be trimmed in hexadecimal format 00 to FF 3 The command to trim the calibration N The Analog Ouptput channel to be trimmed zero based VV Two hexadecimal digits to represent the trim calibration value Use 00 to 5F to increase the voltage in increments from 0 to 95 and use FF to Al to decrease the voltage in increments from 1 to 95 Response Valid Command AALCHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error
134. the module to be set in hexadecimal format 00 to FF 5 The command to enable the Analog Input channels VV A two digit hexadecimal value representing the Analog Input channel where bit 0 corresponds to channel 0 and bit 1 corresponds to channel 1 etc When the bit is 0 it denotes that the channel is to be disabled and 1 denotes that the channel is to be enabled Response Valid Command 1AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 0350A Response 103 Enables Analog Input channels 1 and 3 on module 03 and disables all other Analog Input channels The module returns a response indicating that the command was successful Command 036 Response 1030A Reads the status of the Analog Input channels on module 03 and returns a response indicating that the command was successful with a value of 0A which denotes that Analog Input channels 1 and 3 are enabled and all other Analog Input channels are disabled Related Commands Section 7 4 16 AA6 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 51 Copyright 2013 by ICP DA
135. tting up the ZT 2000 I O Device ccc cece ec eee eee 13 3 1 Introduction to the Configuration Parameters 13 3 2 Introduction to the Rotary and DIP Switches 14 3 3 Starting the ZT 2000 I O Device 56524455555 HES EE SEE SEER SS 17 3 4 Communications Testing s sssessssessssessssesosoesoeo 17 325 EXMP LOS i e e r L ce eee eee ee eees 18 4 Analog Input Type and Data Format ccccccecccccceuceccsvavens 20 5 Analog Output Type and Slew Rate 444444444444444444444445844 22 6 Calibration sssiscsccccsscssescsssscescassssesanss ssena a TEET 23 Gel ANGLOG INPC ssceresesssorese en Erase ee Ee eS EE 23 6 2 ANGLOG OUTPUT aceneceereeee wees eee sees eee eee eee eeeees 24 7 The DCON Modbus RTU Command Sts 660 0006 de kee eees ace ecascne es 25 7 1 Communicating with the ZT 200 I O Device 25 7 2 The DCON Protocol Command Set ccscccccccccvccevcvccees 25 73 CHECRSUM 6 5 0 e u e 6 0 6 0 6 8 e ee SEEN R ELE S 26 7 4 Overview of the DCON Command Set cceecccceccccees 27 7 4 1 AANNTTCCFF hock i CEEE EEEE EEEE EES 31 IMD LEO RLS ERERERRRRERERERER ERE OREEEEEEEEEEE EERE EDS 32 7 4 3 HPN 5 66 S EE EEELEOCCOSEHEEGROHEG EEE GE 6OS4S EGGS GEESE ESS 33 7 4 4 HAAN 64 44 09 IRANDERAND RRND E 34 7 4 5 HAAN Data ccc ccc cece ec cee cee eee eee e ee eeees 35 7 4 6 DANO 6k KEKE GHA HEHE HHEEREHEA EE REHEEAE EEE EREEEA ROR EE 37 ICP DAS ZT 2026 User Manual Version 1 0 1 Page 2 Copyright 2013 by ICP
136. ual Version 1 0 1 Page 33 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 4 AAN Description This command is used to read data froma specific Analog Input channel of a specified module Syntax AAN CHECKSUM CR H Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF N The Analog Input channel to be read zero based Response Valid Command gt Data CHECKSUM CR Invalid Command AA CHECKSUM CR gt Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The data from the specified Analog Input channel See Section 4 for details of the data format If the specified channel is disabled then the data field will be filled with space characters There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 032 Response gt 025 13 Reads data from Analog Input channel 2 of module 03 and returns a response indicating that the command was successful and that the Analog Input value is 025 13 25 13 mV Command 039 Response 203 Attempts to read data from Analog Input channel 9 of module 03 but returns a response indicating that the command was
137. unication error or there is no module with the specified address Examples Command 03S1 Response 103 Sends a command to reload the factory default calibration parameters for module 03 and returns a response indicating that the command was successful Command 03S0 Response 203 Attempts to send a command to reload the factory default calibration parameters for module 03 but returns a response indicating that the command was unsuccessful because the command was incorrect Related Commands Section 7 4 6 AA0 Section 7 4 7 AA1 Section 7 4 8 AAON Section 7 4 9 AAAIN Section 7 4 46 AAEV Related Topics Section 6 Calibration ICP DAS ZT 2026 User Manual Version 1 0 1 Page 74 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 33 Descript ion This command is used to inform all modules that the Host is OK Syntax eve CHECKSUM CR N Delimiter character ek The Host OK command Response There is no response to this command Examples Command moe Response No response Sends a Host OK command to all modules Related Commands Section 7 4 34 AAO Section 7 4 35 AA1 Section 7 4 36 AA2 Section 7 4 37 AA3ETT Related Topics Section 8 2 Dual Watchdog Operation ICP DAS ZT 2026 User Manual Version 1 0 1 Page 75 Copyright 2013 by ICP DAS Co Ltd ALL Rights Res
138. unsuccessful because Analog Input channel 9 does not exist Related Commands Section 7 4 1 AANNTTCCFF Section 7 4 3 AA Section 7 4 10 AA2 Section 7 4 19 AA7CiRrr Related Topics Section 4 Analog Input Type and Data Format Section 8 1 Software Configuration Mode ICP DAS ZT 2026 User Manual Version 1 0 1 Page 34 Copyright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 5 AAN Data Description This command is used to set the Analog Output value for Analog Output channel N of a specified module Syntax HAAN Data CHECKSUM CR H Delimiter character AA The address of the module to be set in hexadecimal format 00 to FF N The Analog Output channel to be set zero based Data The Analog Output value See the Section 5 for details of the data format Response Valid Command gt CHECKSUM CR Invalid Command CHECKSUM CR Ignored Command 1 CHECKSUM CR gt Delimiter character to indicate a valid command Delimiter character to indicate an invalid command because the Analog Output value Data is out of range The Analog Output value will be restored to the closest value defined in the range settings for the module Delimiter character to indicate that the module s Host Watchdog flag is set The command will be ignored and the Analog Output value will be set to the configured Safe value There will be no
139. used to read the status of the high alarm for a specific Analog Input channel of a specified module Syntax AARHC i CHECKSUM CR Delimiter character AA The address of the module to be read in hexadecimal format 00 to FF RH The command to read the status of the high alarm for the Analog Input channe Ci The Analog Input channel to be read zero based Response Valid Command 1AA Data SO j CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF Data The highalarm value for the specified Analog Input channel in engineer ing units format See Section 4 for details of the data format S The Alarm Type 0 Alarm Disabled 1 Momentary Alarm 2 Latched Alarm 0j j specifies the Digital Output port There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03H1 09 000COM00 Response 103 Sets the high alarm limit for Analog Input channel 0 of module 03 to 09 000 9 0 V sets the Alarm Type to momentary and sets Digital Output channel 0 as the high alarm output and returns a response indicating that the command was successful Command 03RHCO Response 1
140. yright 2013 by ICP DAS Co Ltd ALL Rights Reserved 7 4 54 AACLC1 Description This command is used to clear the status of the low alarm for a specific Analog Input channel of a specified module Syntax AACLC i CHECKSUM CR Delimiter character AA The address of the module to be cleared in hexadecimal format 00 to FF CLC The command to clear the status of the low alarm for the Analog Input channe i The Analog Input channel to be cleared zero based Response Valid Command 1 AA CHECKSUM CR Invalid Command AA CHECKSUM CR Delimiter character to indicate a valid command Delimiter character to indicate an invalid command AA The address of the responding module in hexadecimal format 00 to FF There will be no response if the command syntax is incorrect there is a communication error or there is no module with the specified address Examples Command 03RA00 Response 1030080 Reads the current status of the alarms associated with Digital Output channel 0 for module 03 and returns a response indicating that the command was successful and that a low alarm has occurred on Analog Input channel 7 Command 03CLC7 Response 103 Clears the status of the low alarm for Analog Input channel 7 of module 03 and returns a response indicating that the command was successful Command 03RA00 Re