Home
        User manual
         Contents
1.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       bO   Unit of measure Periodical washing Drain SV in Alarm relay Alarm relay logic Reverse osmosis Wash due   Auto   of par  b1 EC   at the end of the standby AL  active alarms NO  norm  open  Off  wash due to inactivity to test  M   minutes production cycle SP  set point reached   NC  norm  closed at next start inactivity  H   hours IN   during the production On  wash due to inactivity  cycle when disabled  57 H Open SP C On O On  58 H Open SP     On On Ofi  59 H Open SP C On On On  60 H Closed AL O Ofi O Ofi  61 H Closed AL O Off O On  62 H Closed AL O Off On Of  63 H Closed AL O Off On On  64 H Closed AL O On O Of  65 H Closed AL O On O On  66 H Closed AL O On On Ofi  67 H Closed AL O On On On  68 H Closed AL E Off O Ofi  69 H Closed AL E Ofi O On  70 H Closed AL E Off On Of  71 H Closed AL C Off On On  72 H Closed AL C On O Ofi  73 H Closed AL E On O On  
2.                                                                                                                                                                                                                                                                                                                                                                                                                                bO   Unit of measure Periodical washing Drain SV in Alarm relay Alarm relay logic Reverse osmosis Wash due   Auto   of par  b1 EC   at the end of the standby AL  active alarms NO  norm  open  Off  wash due to inactivity to test  M  minutes production cycle SP  set point reached   NC norm  closed at next start inactivity  H   hours IN   during the production On  wash due to inactivity  cycle when disabled  78 M E Open AL C On On O  79 E Open AL C On On On  80 E Open SP O O Of O  81 M EC Open SP O O Of On  82 E Open SP O O On O  83 M E Open SP O O On On  84 EC Open SP O On Of O  85 EC Open SP O On Of On  86 M E Open SP O On On O  87 E Open SP O On On On  88 M EC Open SP C O Of O  89 E Open SP C O Ofi On  90 M E Open SP C O On O  91 M E Open SP C O On On  92 EC Open SP C On Of O  93 M E Open SP C On Ofi On  94 E Open SP C On On O  95 M EC Open SP C On On On  96 M E   Closed AL O O Of O  97 E Closed AL O O Of On  98 M E Closed AL O Off On Off  99 EC Closed AL O O On On  00 M E Closed AL O On Of O  01 M E Closed AL O On Of On  02 E Closed AL O On On O  03 M EC Closed AL O O
3.                                                                                                                                                                                                                                                                                                                      bO   Unit of measure Periodical washing Drain SV in Alarm relay Alarm relay logic Reverse osmosis Wash due   Auto   of par  b1 EC   at the end of the standby AL  active alarms NO  norm  open  Off  wash due to inactivity to test  M   minutes production cycle SP  set point reached   NC  norm  closed at next start inactivity  H   hours IN   during the production On  wash due to inactivity  cycle when disabled  0 Open AL O Off O O  1 Open AL O Off O On  2 Open AL O Off On Of  3 Open AL O Off On On  4 Open AL O On    Off  5 Open AL O On O On  6 Open AL O On On Of  7 Open AL O On On On  8 Open AL C Off O Ofi  9 Open AL C Of    On  0 Open AL C Off On Of    Open AL C Off On On  2 Open AL C On O Ofi  3 Open AL C On O On  4 Open AL C On On Of  5 Open AL C On On On  6 Open SP  O Off O Ofi  7 Open SP O Off O On  8 Open SP O Off On Of  9 Open SP  O Off On On  20 Open SP O On    Off  21 Open SP O On O On  22 Open SP  O On On Ofi  23 Open SP O On On On  24 Open SP  C Off O Ofi  25 Open SP C Off O On  26 Open SP  C Off On Of  27 Open SP  E Off On On  28 Open SP  C On O Ofi  29 Open SP C On O On  30 Open SP C On On Ofi  31 Open SP C On On On  32 Closed AL O Of O Of  33 Closed AL O Of O On 
4.                                                                                       13       18 tLAN terminal connection  optional  with 30 Vdc power supply   24 Vac rectified    M9          AUX serial connector   M10 0 1     Analogue proportional controller probe humid   02     GND signal reference   0 3    21Vdc for active probe supply   0 4   NU    0 5   NU    117   AUX input          zEzzzz                   The auxiliary card features the following connections    ON OFF CONTROLLER  humidostat or remote switch      jumper inputs M14 1 and M14 2  enable  on the main board      connect terminals M10 1 and M10 2 to a humidostat or a remote  switch  voltage free contact      set parameter A0   0 to enable On Off operation  see Chap  7     EXTERNAL PROPORTIONAL CONTROLLER  modulating      jumper inputs M14 1 and M14 2  enable  on the main board      connect terminals M10 1 and M10 2  production request  to an  external controller      set parameter AO 1 to enable modulating control  see Chap  7  and  parameter A2 depending on the chosen signal  0 to 10V  2 to 10V  O to  20 4 to 20 mA   see Chap  7      CONTROL WITH CAREL HUMIDITY PROBE     jumper inputs M14 1 and M14  enable  on the main board      connect the probe to terminals M10 1  M10 2  The power line M10 3  can be connected with cable of maximum lenght of 2 m  6 6 ft   for  greater lenghts use an external power supply with the signal earth  electrically connected to the signal earth of the controller      set paramete
5.                3  Atthe end of the third cycle that ends after a time less than A9  the  water refill time is increased further  150  higher than parameter  bb  and a washing cycle is performed  during which chattering    is  applied  as enabled in the previous step  Warning Ed is also generated              4  After the final step  a new production cycle will be activated  If the  problem persists  the controller will restart the procedure from the  first step  until completing a cycle in the expected time  In this case   any warnings will be reset            Chattering  a sequence in which the drain solenoid valve is opened   closed in rapid succession  with the aim of removing any residues  scale   dust  etc  that prevent it from closing correctly      Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL       Notes                                                                                                  Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014 30    CAREL    CAREL INDUSTRIES HQs   Via dell Industria  11   35020 Brugine   Padova  Italy   Tel    39  049 9716611   Fax   39  049 9716600  e mail  carel carel com   www carel com    N   rel  11 4   10 02 2014          Agenzia   Agency            Ultrasound humidifier for fan coils    0300056    
6.            E digital variables  Modbus    COILS  R W  2 Just started flag R  3 Humidifier ready to produce R  4 Humidity set point reached R  5 Green LED R  6 Red LED R  7 Yellow LED R  8 Remote On Off R  9 Low level R  10 High level R  11 Aux level R  12 Autotest completed R  14 BMS serial in tLAN mode R  15 TAM enabled R  16 TAM reading R  17 Terminal connected R  18 Production in progress R  19 Fill R  20 Drain R  21 Transducer 1 R  22 Transducer 2 R  23 Fan R  24 Alarm relay R  25 Auxiliary relay R  26 Manual drain R W  27 Disable from serial R W  28 Reset hour counter R W  29 Reset alarms R W  30 Washing due to inactivity activated R  31 Functional test performed R  33 Unit of measure R W  37 Serial control enable R W  38 Activate wash from serial R W   Tab  12 b          12 2 Production control via network    To control production via a he connection  configure the humidifier  using following parameters        Digital 27  Digital 37 and Integer 60  Modbus 188     When the D37 is at 1  the humidifier excludes the external command  signals  external regulator or probes  and uses the value of Integer 60   modbus 188  as like comand signal  The humidity production can be  managed in two modes     To manage the production level in percentual mode      SetD37 1      Set parameter AO   1  Carel 20  Modbus 148  Proportional Mode       Set integer variable 60 Carel  188 Modbus  to the desired level   0 1000   0 100 0       To manage the production with a humidity probe managed b
7.       Check  yes humidification   ESC   Digital 29  insufficient e water supply and fill interrupted    drain open valve     faulty float e blockage of filter on  fill solenoid valve     check drain solenoid  valve and drain  connection   5 fast flashes EP  lt  gt  No production Malfunction of piezoe    Carry out maintenance   yes humidification   ESC   Digital 29  CNS lectric transducers on tank interrupted  3 fast flashes EF CS No water Interruption to water Check  yes humidification   automatic  after  supply or fill solenoid e water supply and fill   inthe 10  interrupted 10 minute wait   L J valve malfunction valve  minute only per 10 see Chap  5 8   e blockage of filteron   waiting minutes  fill solenoid valve period   4 fast flashes Ed CN  Nodrain Drain solenoid valve  Check drain valve and  yes humidification   ESC   Digital 29  L J circuit malfunction drain connection interrupted         5 slow flashes CL Tank maintenance 1500 operating hours for   Carry out maintenance  no signal only Reset hour  CN request signal recommended mainte    on tank and transducers counter  See  Li J nance exceeded  cap  9  Chap 5 6 or 6 8   6 fast flashes PU   External control Cable interrupted  Check the reference yes humidification   AUTO  signal not connected   disconnected not con    signal  4 to 20 mA or 2 interrupted  correctly nected correctly  to 10V    2 slow flashes H  High humidity The signal from the Check humidity probe yes humidification   AUTO  probe indicates humidity   s
8.    Keepthe humidifier out of the reach of children and animals      Do not install and use the product near objects that may be damaged  when in contact with water  or condensate   CAREL declines all liability for  direct or indirect damage following water leaks from the humidifier      Do not use corrosive chemicals  solvents or aggressive detergents to clean  the inside and outside parts of the humidifier  unless specifically indicated  in the user manual      Do not drop  hit or shake the humidifier  as the inside parts and the linings  may be irreparably damaged              LEGGI E CONSERVA   gt  QUESTE ISTRUZIONI 4    READ AND SAVE  THESE INSTRUCTIONS    CAREL adopts a policy of continual development  Consequently  CAREL  reserves the right to make changes and improvements to any produc  described in this document without prior warning  The technical specifications  shown in the manual may be changed without prior warning    The liability of CAREL in relation to its products is specified in the CAREL genera  contract conditions  available on the website www carel com and or by  specific agreements with customers  specifically  to the extent where allowed  by applicable legislation  in no case will CAREL  its employees or subsidiaries  be liable for any lost earnings or sales  losses of data and information  costs o  replacement goods or services  damage to things or people  downtime or any  direct  indirect  incidental  actual  punitive  exemplary  special or consequent
9.   Fig  1 f    1  Connect the piezoelectric element power cable    2  grip the tank A with two hands    3  place the tank vertically on the fastening structure  first aligning the  connector on the tank with the electronic board  and then the fill  and drain hoses with the corresponding valves    4  apply pressure vertically until the tank is in position  i e  the tabs are  aligned        Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014           iH  a       y 1  mi 7                      du L3       v       INI       DI   nj   M       CAREL    2  WATER CONNECTIONS    2 1 Supply water    The ultrasound humidifier works on demineralised water  Using normal  water will shorten transducer life  specifically  maintenance intervals for             A Important  before proceeding with the water connections   make sure that the humidifier is not connected to the mains                                                                                                                                                                power supply  cleaning or replacing transducers depend on to what extent the supply  Drai Fill water mineral content exceeds the values recommended in Table 11 b  rain I      i s  i 90 T  pg 21  In the case of use of mains water  it is possible a reduction in the  production of moisture declared in Table 11 a due to salts and impurities      present   as Operating conditions   P   demineralised water with the characteristics indicated in Tabl
10.   The humidifier detects if the water supply is interrupted  or insufficient   by monitoring the status of the level sensor after opening the fill solenoid  valve  If the sensor is not activated within the time set for parameter bA   default 15 minutes   humidification is interrupted  the drain is activated  and the appliance waits a set number of minutes  parameter AA  default  10   during which the display shows    Rty     Retry   before attempting to  fill with water again   If this attempt succeeds  production will resume   otherwise the appliance waits a further AA minutes  The process is  repeated until the water supply returns  as measured by the sensor   For the first two attempts  no alarm is generated  while if on the third  attempt the procedure is not successful  alarm EF is generated  which is  reset automatically when the humidifier verifies that the water supply is  available again        13 6 Automatic control of atomised water  production    The humidifier monitors the water level inside the tank during production  of atomised water  If the level does not fall  it means one of the following  faults may have occurred          Malfunction of the piezoelectric transducers    Leaky fill solenoid valve    Fan malfunction    If after the set time for variable A8  in minutes  default 30  the water level  does not fall below the low level threshold  atomised water production  stops and the appliance waits a set number of minutes  parameter  AA  default 10   during wh
11.  34 Closed AL O Of On Of  35 Closed AL O Of On On  36 Closed AL O On O Of  37 Closed AL O On O On  38 Closed AL O On On Of  39 Closed AL O On On On  40 Closed AL C Of O O  41 Closed AL E Of O On  42 Closed AL C Of On Of  43 Closed AL C Of On On  44 Closed AL C On O Of  45 Closed AL C On O On  46 Closed AL E On On Ofi  47 Closed AL E On On On  48 Closed SP O Of O Of  49 Closed SP O Of O On  50 Closed SP O Of On Of  51 Closed SP O Of On On  52 Closed SP O On O Of  53 Closed SP O On O On  54 Closed SP O On On Of  55 Closed SP O On On On  56 Closed SP E Of O Of  57 Closed SP C Of O On  58 Closed SP C Of On Of  59 Closed SP C Of On On  60 Closed SP C On O Of  61 Closed SP E On O On  62 Closed SP C On On Of  63 Closed SP C On On On  64 EC Open AL O Off O Ofi  65 EC Open AL O Off O On  66 EC Open AL O Off On Of  67 EC Open AL O Off On On  68 EC Open AL O On O Ofi  69 EC Open AL O On O On  70 EC Open AL O On On Of  71 EC Open AL O On On On  72 EC Open AL C Off O Of  73 EC Open AL C Off O On  74 EC Open AL C Ofi On Ofi  75 EC Open AL E Off On On  76 EC Open AL E On O Ofi  77 EC Open AL C On O On                                                        Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014 18    CAREL                                                                                                                                                                                                                                                                  
12.  9a  Water circuit   2 transducers  UUOTF   Tank complete with transducers UUKC200000 B 9a  Cover with fan and level sensor UUKCO00000 L 9a  Water circuit   4 transducers  UUO1G   Tank complete with transducers UUKC400000 B 9a  Cover with fan and level sensor UUKCD00000 L 9a  Electrical and electronic parts  Main electronic board UUFO2S0000 D 9a  Main board   auxiliary card UUFO2M0000 D H  9    Pair of transducers with fastening UUKPZ00000  plate  Electrical and electronic parts   2 transducers  UU01F   Power transformer  UUKTFD0000 A 9a  230 24 36V  Power transformer  UUKTF10000 A 9a  115 24 30V  Cable kit UURWR00000 G 2a  Electrical and electronic parts   4 transducers  UU01G   Power transformer  UUKTF20000 A 9a  230 24 36V  Spare fuse 1A for transf  0605640AXX      230 24 36V  Spare fuse 4A for transf  0605621AXX      230 24 36V  Power transformer  UUKTF30000 A 9a  115 24 30V  Cable kit UUKWRO00000 G 9a  115V  230V UUKWR10000 G 9a  Transducer cable extension UUKPP00000 C 9a  Tab  9 a                      23       Replacement    Important  replacement must only be carried out by qualified  personnel  with the humidifier disconnected from the power  supply   In normal conditions  the tank requires maintenance after one year   or 1500 operating hours  if cleaned periodically   or if not used for an  extended period  Replacement is required immediately     even before  the scheduled period    should problems occur    For example  when scale inside the tank prevents correct ope
13.  be installed on the top of the fan  removing  the protection grill  so as to take in air from a different place to where  humiSonic is installed      Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    10    3 3 Elbow connector       The elbow connector can be installed on the cover and or the fan conveyor   so as to reduce the overall height occupied by the product     3 4 Diffuser          Fig  3 6    The diffuser can be installed on the cover  so as to deliver atomised water  directly into the room     3 5 Filter  50 micron          T       Fig  3 f    A filter is available to be installed on the fan  using the conveyor  with or  without the elbow   The filter is  delivered disassembled  cap not fixed   because on one side it is possible to mount it on the conveyor  on the other  side on the elbow  to mount with a slight interference   Once mounted   insert the cap  It s necessary to clean the filter  with compressed air or  running water  periodically  frequency depends on the environment in  which the system is installed  Features filter  50 micron  H   13 cm  D   5 cm    CAREL    3 6 Installation example in fan coil       Fan coil installation example          Fig  3 9    3 7 Ductinstallation example  UUO1G        Duct installation example        Connect the humiSonic fan inlet to the duct  in a position between the  main fan and the connection created for delivering atomised water into  the duct    Carel can supply the fan conveyor  P N UUKCY000
14.  from 1096 to 10096 of the rated  value of the humidifier  parameter PO     Minimum production has an activation hysteresis  equal to the value of P1    default 5  of the proportional band of external signal  Y      Produzione di vapore  Steam production    A         5                                                  P1  10   _____  OFF ON  Y gt              Fig  13 a     Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014    28    CAREL    13  OPERATING PRINCIPLES    Automatic control with humidity probe  Humidity production is controlled based on the reading of the relative  humidity probe  TH or connection via optional card    The humidifier will produce until reaching the set point  St  default 50   rH   with a settable activation hysteresis  P1 default 5    see the figure   to maintain the set point    Produzione di vapore    Steam production    A  PO             St   rH  Fig  12a    13 3 Flow rate modulation    Atomised water flow rate can be varied from 5  to 100   parameters  Pm and PO  by alternating on off cycles of the transducers over a set  period  parameter b7  default 1 second     Flow rate is set based on parameter PO  default 100   and the request  from the external signal  with optional card and proportional control                                 Trasduttore  Transducer  ON Portata 10   OFF nae  Periodo  b7                    t  Fig  13 b  Trasduttore  Transducer  A  ON Portata 50   OFF ee   lt  Periodo  07   gt l t  Fig  13 c  Trasdutto
15.  using UP or DOWN    TER to confirm and access the list of parameters      UP or DOWN to scroll the list    ITER to select a parameter  display     set       P to modify  increase  the value of the parameter  To scroll faster  ess DOWN together    OWN to modify  decrease  the value of the parameter  To scroll faster  ess UP together    ITER to save the new value and return to the list of parameters  or  ESC to return to the list without saving the value    Press ESC to return to the main screen        mon              mo OS cium        6 7 Parameters  Recall default values    The default values of the parameters can be recalled at any time from  the main screen        From the main screen press      ENTER for 2 seconds      enter the password 50 using UP or DOWN and press ENTER      The message dEF flashes  to recall the default values press ENTER  or  ESC to exit     If no button is pressed for 30 seconds  the display returns to the main  screen without recalling the default values     6 8 Reset hour counter from display      Access parameter d3   see Chap  7     press UP and DOWN for 5 seconds  When reset is complete     res is shown on the display         Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014    16    CAREL    CAREL    7  CONFIGURATION PARAMETERS    To access and set the following parameters  see chapters 6 and 12           7 1 Basic parameters       Parameter UOM   range   def note  AO Operating mode   0 3 3  0 2 On Off mode from auxiliar
16. 00  to create the  connections between the fan  duct and hose  P N 1312955AXX   The  hoses should be as short and as straight as possible  max 1 2m each part    so as to reduce pressure drop     If using the UUKDPO  00 distribution system in the installation  turn the  hose so that the holes are in the direction of air flow  see the figure        Fig  3 i            Important  the connections of the hoses for humiSonic air intake  and atomised water delivery into the duct must be positioned so as to  avoid pressure differences  Excessive unbalances in pressure may cause  the system to malfunction  preventing atomised water production  It is  preferable to install the system  humiSonic   distribution  on the intake   making sure to leave enough space for absorption  Alternatively  if this is  not possible  suggested installation is near the end of the duct  close to  the outlet grill  away from the fan  so as to avoid too high pressure          No sifone   No siphon    Fig  3      Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL    4  ELECTRICAL CONNECTIONS    4 1 Electrical installation 4 2 Power cable connection    Correct wiring of the ultrasound humidifier is the responsibility of the  final appliance manufacturer  as required by IEC EN 60335 1    Before performing the electrical connections  make sure that the unit is  disconnected from the mains power supply    Check that the power supply voltage of the appliance corresponds to  the value 
17. 31        ambient operating humidity    rH     10  60       storage temperature   C    F      10   60  14   140        storage humidity    rH     5 to 95  41 to 203                 index of protection IP20  electronic controller   auxiliary voltage frequency  V  Hz  24V   50 60 Hz  maximum auxiliary power  VA  3       control signal inputs  general features     can be selected for the following signals  0 to 10 Vdc  2 to 10 Vdc  0 to 20 mA  4 to 20 mA   input impedance  20 kO with signals  O to 10 Vdc  2 to 10 Vdc  100 O with signals  0 to 20 mA  4 to 20 mA       alarm relay outputs  general features     24V  max 3 W        remote enabling signal input  general features     voltage free contact  max  resistance 100 O  Vmax  5 Vdc  Imax  5 mA                power  instant water vapour production  kg h  Ib h  see Tab  11 a  power consumption at rated voltage  W  see Tab  11 a       Tab  11 b       Maj ds   Bo  0093     in general C    0 65 onc  R  so 50 93 Op 20     c    average water vapour production is affected by factors such as  room temperature  water quality  water vapour distribution system    25    Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014    CAREL    12  HUMIDIFIER CONTROL VIA NETWORK    The variables shown in the list are a set of all the internal variables  DO  NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE  TABLE  OTHERWISE HUMIDIFIER OPERATION MAY BE AFFECTED              The serial connection  M11  is configured by default wit
18. 5    10         recommended values  referring to PVC or rubber cab    e in a closed conduit  20 m  65 6 ft  long  compliance with standards in force is always required   max instant rated water vapour production  average water vapour production may depend on external factors  such as  room temperature  water quality  water vapour distribution       Important  to avoid interference  keep power cables separate from probe cables     11 2 Technical specifications       Technical specifications    UU models       UU01        humidity outlet       connection dia  mm    40  ensure an outlet area of 1100 mm2  e g  22 x 8 mm holes        supply water       connection    G 1 8 F       temperature limits   C    F     1 to 40  33 8  to 104        pressure limits  MPa     0 1 to 0 6  1 to 6 bar        specific conductivity at 20  C    0 to 50 uS cm       total hardness    0 to 25 mg l CaCO3       temporary hardness    0 to 15 mg l CaCO3       total quantity of dissolved solids  cR     depending on specific conductivity       dry residue at 180  C    depending on specific conductivity                                      iron   manganese 0 mg l Fe Mn  chlorides 0 to 10 ppm Cl  silicon dioxide Oto 1 mg l SiO2  chlorine ions 0 mg l Cl   calcium sulphate mg l CaSO4  instant flow rate  l min  06   drain water   connection dia  mm     10mm  typical temperature   C    F    instant flow rate  l min  ri       environmental conditions       ambient operating temperature   C    F     1  55  33 8   1
19. 74 H Closed AL C On On Of  75 H Closed AL C On On On  76 H Closed SP  O Off    Of  77 H Closed SP  O Off Off On  78 H Closed SP  O Off On Of  79 H Closed SP  O Off On On  80 H Closed SP  O On O Of  81 H Closed SP  O On O On  82 H Closed SP O On On Ofi  83 H Closed SP O On On On  84 H Closed SP C Off O Ofi  85 H Closed SP C Off O On  86 H Closed SP  C Off On Of  87 H Closed SP  C Off On On  88 H Closed SP  E On O Of  89 H Closed SP  C On O On  90 H Closed SP C On On Of  91 H Closed SP  C On On On  92 H EC Open AL O Of O Of  93 H EC Open AL O Off O On  94 H EC Open AL O Off On Of  95 H EC Open AL O Off On On  96 H EC Open AL O On O Ofi  97 H EC Open AL O On O On  98 H EC Open AL O On On Ofi  99 H EC Open AL O On On On  200 H EC Open AL C Off O Ofi  201 H EC Open AL C Of    On  202 H EC Open AL E Off On Of  203 H EC Open AL  8 Off On On  204 H EC Open AL C On O Ofi  205 H EC Open AL C On O On  206 H EC Open AL C On On Off  207 H EC Open AL C On On On  208 H EC Open SP O Of O Of  209 H EC Open SP  O Off O On  210 H EC Open SP  O Off On Of  211 H EC Open SP O Of On On  212 H EC Open SP  O On O Ofi  213 H EC Open SP O On O On  214 H EC Open SP O On On Ofi  215 H EC Open SP O On On On  216 H EC Open SP C Of O Of  217 H EC Open SP  C Off O On  218 H EC Open SP    Off On Of  219 H EC Open SP  e Off On On  220 H EC Open SP  C On O Ofi  221 H EC Open SP C On O On  222 H EC Open SP C On On Off  223 H EC Open SP C On On On  224 H EC Closed AL O Of O Of  225 H EC Closed AL O Off O On  226 
20. 9       control hysteresis  parameter P1         Humidity Setpoint  parameter St        To return to the main display press ESC   Parameter CO  see Chap  7  can be used to change the value shown on  the main display  default  display input signal      If the humidifier is disabled  contact ON OFF open  see Fig  4 d   the  display shows          alternatively to the main screen  LED signal  Standby    If the display shows      it means a communication error between  display and humidifier  control connection cable  If the problem persists   call for service         To modify the parameter displayed press      ENTER  display  Set      UPor DOWN to set the value     ENTER to confirm the new value    Press ESC to return to the main screen  The parameters can also be  accessed from the list of parameters  see Chap  7          Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014       6 5 Display software release       1  on power up the display shows  rel  x y     e g  rel  1 2    2  during operation   a  on the display  from the main screen press ESC and UP together   the following are shown in sequence  humidifier size  supply  number  of phases and software release   b  via network on integer variable 81  Format Ht          e g  12   release 1 2      6 6 Accessing and setting parameters    The configuration parameters can be used to set and control humidifier  functions and status        From the main screen press    ENTER for 2 seconds    ter the password 77
21. CAREL    MUMISONIC    Ultrasound humidifier                iS  A                ZY    i2              Bye        SS                                    User manual    e    LEGGI E CONSERVA  QUESTE ISTRUZIONI  READ AND SAVE  THESE INSTRUCTIONS      gt     Efficiency Solutions    High    CAREL    WARNINGS    CAREL humidifiers are advanced products  whose operation is specified in the  technical documentation supplied with the product or can be downloaded   even priorto purchase  from the website www carel com  Each CAREL product   in relation to its advanced level of technology  requires setup configuration   programming commissioning to be able to operate in the best possible way  for the specific application  The failure to complete such operations  which  are required indicated in the user manual  may cause the final product to  malfunction  CAREL accepts no liability in such cases    The customer  manufacturer  developer or installer of the final equipment   accepts all liability and risk relating to the configuration of the product in  order to reach the expected results in relation to the specific final installation  and or equipment  CAREL may  based on specific agreements  act as a  consultant for the installation commissioning use of the unit  however in no  case does it accept liability for the correct operation of the humidifier and the  final installation if the warnings or suggestions provided in this manual or in  other product technical documents are not heeded  I
22. H EC Closed AL O Ofi On Ofi  227 H EC Closed AL O Off On On  228 H EC Closed AL O On O Of  229 H EC Closed AL O On O On  230 H EC Closed AL O On On Ofi  231 H EC Closed AL O On On On  232 H EC Closed AL C Off O Ofi  233 H EC Closed AL C Off O On  234 H EC Closed AL C Off On Of  235 H EC Closed AL C Off On On   Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014 20       CAREL                                                                                                                                                                                                                                                                         bO   Unit of measure Periodical washing Drain SV in Alarm relay Alarm relay logic Reverse osmosis Wash due   Auto   of par  b1 EC   at the end of the standby AL  active alarms NO  norm  open  Off  wash due to inactivity to test  M  minutes production cycle SP  set point reached   NC  norm  closed at next start inactivity  H   hours IN   during the production On  wash due to inactivity  cycle when disabled  236 H E Closed AL C On Of O  237 H E Closed AL C On Of On  238 H E Closed AL E On On O  239 H EC Closed AL C On On On  240 H E Closed SP O O Ofi O  241 H E Closed SP O O Ofi On  242 H EC Closed SP O O On O  243 H EC Closed SP O O On On  244 H E Closed SP O On Ofi O  245 H E Closed SP O On Of On  246 H EC Closed SP O On On O  247 H E Closed SP O On On On  248 H E Closed SP G O Ofi O  249 H E Closed SP E O Ofi On  250 H EC Cl
23. REL products are guaranteed by the  m on  ISO 9001 certified design and production system  as well as by the C     mark        Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL       Content                                                                                                         1  INTRODUCTION AND ASSEMBLY 7 10  WIRING DIAGRAMS 24  11 Ultrasound humidi E e 7 iL EAGAN    A               24  te DIMENSIONS ana WENSE  11 GENERAL FEATURES AND MODELS 25  13 Opening the packaging      a seo C     14 Positioning 1 1  Ultrasound humidifier models for fan coils and electrical  15 Fastening Specifications    ausus naos amie       adea dO dad S 25  16 Humidifier assembly    8 1 2 Technical specifications    tts 25   2  WATER CONNECTIONS 9 12 HUMIDIFIER CONTROLVIA NETWORK 26  21 Supply water 9 2 1 Supervisor variable list    eatenus 26  23 Drain water 9 2 2 Production control via network iu    27   2 3 Washing cycle activation via network    27   3  ATOMISED WATER DISTRIBUTION 10                    13 OPERATING PRINCIPLES 28  3 1 Atomised water distributor    10  32 Fan conveyor 0 3 1 Ultrasound atomisation     33 Elbow connector  0 32 Control principles  34 Diffuser    10 3 3 Flow rate m  dUlatON asesinan  35 Filter 50 micron 0 34 Series flow rate modulation  4 transducer ver  only   36 Installation example in                     e 1 le   s ee Mn   i   35       5 Automatic insufficient supply water management                        37 D tall
24. alternately  Tab  4 c  RS 485  GND     x  RX  Fig  4 e     Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014 12    CAREL    Important  for RS485 connections in household  IEC EN 55014 1    and residential  IEC EN 61000 6 3  environments  use shielded  cable  with shield connected to PE both on the terminal and controller  ends   maximum length specified by the EIA RS485 protocol  equivalent  to European standard CCITT V11  using AWG26 twisted pair cable   the input impedance of the 485 stage is 1 8 unit load  96 kOhm   This  configuration allows a maximum of 256 devices to be connected  with  cables in separate conduits from the power cable     ALARM RELAY    This is used to signal one or more alarms via a remote connection     QD    HBBHHHHHH          Fig  4 f    ALARM RELAY POWER SUPPLY   The connections shown in Fig 4 g can be used to directly control a light  or an auxiliary relay coil   30 Vdc  24 Vac rectified   3 W max           Alarm signal   max 3W        GND    Fig  4 g    Note  in industrial environments  IEC EN61000 6 2  the signal cables   leaving the unit must not exceed 10 m  33 ft  in length  remote  on off digital input  terminals M14 1  M14 2  and shielded cable for  RS485 communication     4 4 Auxiliary card connections  optional                                                                                                     J8 MI    GND 21Vdc  ila d    3 4 5     MN UN I       8    3    3    3  o      SD                             
25. at le   UUOTG  iet i  lla 3 6 Automatic control of atomised water production                          29  4  ELECTRICAL CONNECTIONS 12 37 Automatic control of leaking drain solenoid valve   i      and fill solenoid valve flow rate              29  42 Power cable connection      2  43  Main board connections    sescenti eadein 2  44 Auxiliary card connections  optional     13   5  STARTING  USER INTERFACE AND BASIC   FUNCTIONS 14  5   Starting    4  52  Shutdown Standby 4  5 3 Autotest 4  54 LED signals 4  55  Disabling 4  56  Resettank hour counter 4  5 7 Automatic washing 4  5 8 Washing due to inactivity    4   6  LCD TERMINAL  OPTIONAL  15  6 1 Remote display terminal                                                              15  62 Meaning of the SyMb0lS                        15  6 3 Keypad 5  64 Main display 5  6 5 Display software release  6  6 6 Accessing and setting parameters    16  6 7 Parameters  Recall default values                s 6  6 8 Reset hour counter from display    6   7  CONFIGURATION PARAMETERS 17  71  Basic parameters cease sesion oe ela 7  7 3 Advanced PALAMteLS    ccessscssssssssssssssssssessssssssussssssssssssesessssssssssseusessssee  73 Serial connection parameters      74  Read only parameters    tte   8  ALARMS 22   9  MAINTENANCE AND SPARE PARTS 23  9 1 Spare parts    223  92 Tank cleaning and MAINTENANCE  23    93 Cleaning and maintenance of other COMPONENTS                         23    5  Ultrasound humidifier for fan coils   0300056EN   r
26. avoid malfunctions  BO  see Table  7 c  reverse osmosis  can be set so that the washing cycle is performed  when first restarting after a period of continuous inactivity set by b2           CAREL    6  LCD TERMINAL  OPTIONAL     6 1 Remote display terminal  VUKDI00000     The LCD terminal is an option and can only be used if the auxiliary card  is fitted  this too an option                    Fig  6 a    The terminal displays humidifier status and can be used to customise  operation by setting the parameters     CONNECTION                       1 6 wire telephone cable P N S90CONNOOO or equivalent  maximum  length 2 m  6 6 ft         remote display terminal        WIN       optional card       For lengths exceeding 2 m  6 6 ft   use shielded cable with the shield  connected to the PE both at the terminal and controller end     6 2 Meaning of the symbols          ue Power supply  Green LED        DI Humidifier operating  yellow LED   Steady  humidity production not yet at the set point  Flashing  humidity production at the set point       A Alarm  red LED   On activation of an alarm  LED flashing and buzzer active    When an alarm is active  pressing ESC mutes the buzzer and  he LED comes on steady  pressing ESC again resets the alarms   see Chap  8        sec Time in seconds                h Hour counter        Humidity production as a percentage of rated capacity  set Parameter setup   9 aintenance request  active alarm        On steady  humidifier fan operating   Flashing  
27. de the packaging  fig 1       A  fastening bracket      B  tank    e C fill solenoid valve      D drain solenoid valve      E  transformer  make sure voltage is correct    e F  cable kit    e G  terminal kit           1 4 Positioning      The humidifier may only be accessed by specialist personnel      make sure the humidifier is level horizontally  observing the minimum  Clearance of 20 mm on the sides to leave room for maintenance      position the humidifier so as to allow the atomised water to be freely  delivered      position the transformer in a place that s protected against possible  water leaks and in any case not underneath the humidifier     1 5 Fastening    Fastening instructions    1  make two holes as shown in Fig  1 b    2  fixthefasteningbracketusingtwo M4x12 screws supplied  see Fig  1 c    using a spirit level to make sure installation is horizontal           2200 mm                       110       92                Fig 1 b                Fig  1 c     Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014       1 6 Humidifier assembly    Connect the valves as shown in Figure 1 d and 1 e            Important  insert an o ring before the drain valve       Fig  1 e         correct wiring of the ultrasound humidifier is the  responsibility of the final appliance manufacturer  as required by IEC EN  60335 1     e Connect the valve power cable     Connect the transformer power cable     24Vac 30 36Vac    Drain Fill Piezo     a  9   oga           
28. drain  R W  33 161 Parameter b4  Start delay time R W  34 162 Parameter b5  Operating hours for CL alarm R W  35 163 Parameter b6  Time to display new CL alarm in minutes R W  36 164 Parameter b7  Transducer On Off control interval R W  37 165 Parameter b8  Probe delay disconnected R W  38 166 Parameter b9 TAM OFF delay R W  39 167 Parameter bA  Maximum fill time R W  40 168 Parameter bb  Refill time in evaporation R W  41 169 Parameter bC  Maximum drain time R W  42 170 Parameter bd  Drain opening time to completely empty tank R W  43 171 Parameter bE  Delay time after measuring low level for refilling RAN  44 172 Parameter C0  Default display  Terminal  R W  45 173 Parameter C1  Parameter A0  Baud rate R W  46 174 Parameter C2  tLAN address  If O Master controller  R W  47 175 Parameter C3  Serial address R W  48 176 Parameter PO  Maximum flow rate R W  49 177 Parameter P1  Humidity control hysteresis R W  50 178 Parameter P2  Low humidity alarm threshold R W  51 179 Parameter P3  High humidity alarm threshold R W  52 180 Parameter SP  Humidity set point R W  53 181 Parameter d3  Operating hour counter R  54 182 Parameter d4  Unit hour counter  not resettable  R W  60 188 Serial request  If digital 37 is setted  R W  65 192 Parameter C4  Timeout for offline master serial R W  Tab  12 a        Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014 26    CAREL                                                                                                     
29. e 11 b     supply water  p  21    x   pressure between 0 1 and 0 6 MPa  14 5 and 116 PSI   temperature    EN c between 1 and 40   C  33 8 and 104   F   G1 8 F connection  see par   11 2    Technical specifications             noorganic compounds   g        Important   x   do not add disinfectants or anticorrosive compounds to the water  as  these are potential irritants                                                                                  the use of well water  industrial water or water from cooling circuits  and  in general  any potentially chemically or bacteriologically  Fig  2 j contaminated water is prohibited    bottom view     2 2 Drain water       This is not toxic and can be drained into the sewerage system    Council Directive 91 271 EEC on Urban Waste Treatmen                           water inlet      a                water drain    ap          Fig  2 k    Water connections  parts not included      r4 1  Install a manual shut off valve upstream of the installation  so as to  shut off the water supply      r4 2  use a hose to connect the humidifier to the water supply  the  product is supplied with a slide on elbow connector      r4 3  install a mechanical filter  60   5  to trap any solid impurities   connected downstream of the water tap         4 connect a section of drain hose  minimum inside diameter 6 mm     prepare a funnel to interrupt continuity in the drain line           6 connect a drain trap to prevent bad odours          Important  When ins
30. el  1 4   10 02 2014    CAREL          Fig 1   Packaging    Note  before proceeding with the installation   remove the tank from the stand  pushing the  fins black as shown         Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014 6    CAREL    1  INTRODUCTION AND ASSEMBLY    1 1 Ultrasound humidifier    Ultrasound humidifiers can be used for vast variety of applications  e g   data centers  climate rooms  close control units and food preservation  for  the RH  control  The 2 transducer version  UU01F  has been specifically  developed for integration into fan coils  Atomised water production is  0 5 I h  UU01F  and 1 I h  UU01G   delivered directly into the air stream     1 2 Dimensions and weights       4 transducer version   UU01G     2 transducer version   UU01F         E 1 1                                        Fig  1 4  UUO1F UU01G  dim  mm     A 121  4 76  185  7 28   B 125  4 92  125  4 92   C 221  8 70  216  8 50   weights kg  Ib    packaged 3 9  8 60  5 5  12 13   empty 2 8  6 17  4A  9 7   Tab  1 a    1 3 Opening the packaging       a Make sure the humidifier is intact upon delivery and immediately  notify the transporter  in writing  of any damage that may be due to  careless or improper transport    O move the humidifier to the site of installation before removing from  the packaging  grasping the neck from underneath    D open the cardboard box  remove the protective material and remove  the humidifier    n The following are contained insi
31. face  with the smaller ones being  carried air by the forced air flow  The quantity of atomised water depends  on water level  water temperature and distribution in the air    Water level is kept constant using fill and drain valves  and a level sensor   Demineralised water is recommended  if using mains water  the scale  that accumulates over time will foul the piezoelectric transducer   affecting atomisation  To avoid excessive scaling  humidifier periodically  drains and automatically refills the water  see par  12 5     13 2 Control principles       The humidifier can be controlled using the following signals     remote ON OFF      TAM  set by dipswitch       Humidity probe  set by dipswitch       Serial     ON OFF control    The action is all or nothing  activated by an external contact that   consequently determines the control set point and differential  The   external contact may be a humidistat  whose status determines the   operation of the humidifier      contact closed  the humidifier produces water vapour if the remote  ON OFF contact is also closed      contact open  water vapour production ends     Proportional control  only with optional card      Water vapour production is proportional to the value of a signal  Y   from an external device  The type of signal can be selected between  the following standards  0 to 10 Vdc  2 to 10 Vdc  0 to 20 mA  4 to 20 mA     Maximum humidifier production  corresponding to the maximum  value of the external signal  can be set
32. fan on during deactivation phase       gog 3 digits  after 999 the display shows to indicated the 1000s  the    hree digits are displayed with a dot at the top between the first  and second digit                  Tank filling    ad N Water in the tank    I Water draining from the tank       c gt  Humidity production in progress                         IN  Tab  6 a  6 3 Keypad  button function  Esc return to the previous display    UP from the main screen  display the humidification values  see    he following paragraph       from the list of parameters  scroll the parameters and set the  values       v DOWN   from the main screen  display the humidification values       from the list of parameters  scroll the parameters and set the  values                 ENTER   for 2 seconds  access the list of parameters   PRG    inside the list of parameters  select and confirm  like  Enter   on a computer keyboard           Tab  6 b    6 4 Main display       The humidifier display normally shows control signal status     For ON OFF or proportional input signal  A0 0  AO 1  AO 3 and Th  probe disconnected       display input signal      tank hour counter  h       maximum water vapour production control  parameter PO           control hysteresis  parameter P1          For humidity probe input signal  A0 2  A0 3 and Th probe connected      display humidity probe reading      display temperature  Th only      tank hour counter  h       maximum water vapour production control  parameter PO   
33. h the following  parameters      Address 1     Baud rate 19200 bps     Frame 8 N 2    12 1 Supervisor variable list                                                                                                                                                                                                       CAREL      analogue variables   Modbus    REGISTERS          1 param  d0  Th probe temperature reading R  2 param  d1  Th probe humidity reading R  3 param  d2  Probe reading R  4 param  d5  Set point trimmer reading R  CAREL S integer variables  Modbus    REGISTERS  R W  1 129 Level access password R W  2 130 Firmware release R  15 143 Alarms  see Cap 8 ALARMS  R W    bit0  EO Alarm  bit1  Et Alarm  bit2  EF Alarm  bit3  Ed Alarm  bit4  EP Alarm  bit5  PU Alarm  bit6  H Alarm  bit7  H_ Alarm  bit8  EE Alarm    bit9  CL Alarm  20 148 Parameter A0  Operating mode R W  21 149 Parameter A2  Type of external sensor R W  22 150 Parameter A3  Probe minimum R W  23 151 Parameter A4  Probe maximum R W  24 152 Parameter A5  Probe offset R W  25 153 Parameter A6  Fan off delay time R W  26 154 Parameter A7  Fan speed R W  27 155 Parameter A8  Maximum evaporation time for no production alarm R W  28 156 Parameter A9  Minimum evaporation time for no production alarm R W  29 157 Parameter b0  Operating options R W  30 158 Parameter b1  Time between two washing cycles R W  31 159 Parameter 02  Inactivity time for washing on next start R W  32 160 Parameter b3  Washing time  fill   
34. h the humidifier on WITHOUT THE TANK  The yellow LED will flash     Close the On Off contact  the yellow LED will remain on steady     Switch the humidifier off     Reposition the piezoelectric element connector  replace the tank and  open the water supply tap     Switch the humidifier on                5 7 Automatic washing       The humidifier automatically runs a washing cycle at intervals in  operating time set by parameter b8  default 60 minutes  parameter bO  can be used to convert this value into hours  see Table 7 c     The washing cycle involves a complete drain cycle  a phase in which  fill and drain are activated together  default 1 minute  parameter b3  to  flush out any residues in the tank  a complete fill cycle and finally another  complete drain cycle    During this operation  water vapour production is stopped        5 8 Washing due to inactivity    If the humidifier remains inactive  on but in standby  for an extended  period  parameter b2  default 24 hours  a washing cycle is performed  as  described in the previous paragraph  This cleans the tank of any residues   e g  dust  that may have accumulated during the period of inactivity   Parameter bO can be used to set the time when this washing cycle is  performed  By default  the washing cycle is run after 24 hours  continuous   of no operation  i e  the humidifier is in standby  This is because the  humidifier is normally connected to a reverse osmosis system  which  needs to operate frequently in order to 
35. ia  damage of any kind whatsoever  whether contractual  extra contractual or  due to negligence  or any other liabilities deriving from the installation  use or  impossibility to use the product  even if CAREL or its subsidiaries are warned  of the possibility of such damage        DISPOSAL    The humidifier is made up of metal parts and plastic parts  In reference to  European Union directive 2002 96 EC issued on 27 January 2003 and the  related national legislation  please note that    1  WEEE cannot be disposed of as municipal waste and such waste must be   collected and disposed of separately    2  thepublicorprivatewastecollectionsystemsdefinedbylocallegislationmust   be used  In addition  the equipment can be returned to the distributor at   he end of its working life when buying new equipment    3  the equipment may contain hazardous substances  the improper use or   incorrect disposal of such may have negative effects on human health   and on the environment    4  the symbol  crossed out wheeled bin  shown on the product or on the  packaging and on the instruction sheet indicates that the equipment has  been introduced onto the market after 13 August 2005 and that it must  be disposed of separately    5  intheeventofillegal disposalofelectrical and electronic waste  the penalties  are specified by local waste disposal legislation              Warranty on materials  2 years  from the date of production  excluding  consumables      Approval  the quality and safety of CA
36. ich the display shows    Rty     Retry   before  attempting to resume production  If the situation is repeated  alarm EP is  activated  which shuts down the unit   If after a percentage of A8  set by parameter Ab  default 7096  the water  is above the high level threshold  atomised water production stops   warning EL is generated and the appliance waits AA minutes  default  10   during which the display shows  Rty   Retry   before attempting  to resume production  The warning signal EL is reset at the end of a  production cycle that is completed correctly           29       13 7 Automatic control of leaking drain  solenoid valve and fill solenoid valve  flow rate    Parameter A9 sets a minimum production time  default 1 minute   if the  production cycle lasts less than this time  it may mean that the drain  solenoid valve is leaking or that the fill solenoid valve flow rate is too low   In this case  the controller carries out the following operations     1  Atthe end of the first cycle that ends after a time less than A9  the  water refill time is increased  5096 higher than parameter bb  and  the reduced power supply voltage to the drain solenoid valve is  deactivated with the objective of increasing tightness     2  Atthe end of the second cycle that ends after a time less than A9   the water refill time is increased further  10096 higher than parameter  bb  and a chattering  cycle is activated on the drain solenoid valve   performed during the first automatic wash cycle  
37. ignal cable interrupted  above 8096rH  3 slow flashes H_ Low humidity The signal from the Check humidity probe yes humidification   AUTO  probe indicates humidity   signal cable interrupted  ess than 2096rH  4 slow flashes EE EEPROM alarm Problems in the EEPROM   If the problem persists    yes humidification   If this persists  contact the CAREL interrupted contact service  service centre  1 fast flash EO Functional test not   Functional test not If the problem persists    yes humidification   If this persists  performed performed by manufac    contact the CAREL interrupted contact service  urer EEPROM problems   service centre  7 slow flashes OFL Master Offline Loss of connection from   Check state of the yes humidification   AUTO  he serial master Master   Cable interrupted  If D37 1        To reset the alarms  press ESC once to mute the buzzer  press ESC a  second time to completely reset the alarm         Fast flash  0 2 seconds ON and 02 seconds OFF  Slow flash  1 second ON and 1 second OFF     Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014    22       CAREL    9  MAINTENANCE AND SPARE PARTS          9 2 Tankcleaning and maintenance                                                                                                                   9 1 Spare parts  Table of water circuit  electrical and electronic spare part numbers  part number pos    fig   Water circuit  Fill solenoid valve kit UUKFV00000 F 9a  Drain solenoid valve kit UUKDV00000 E
38. indicated on the rating plate affixed to the side of the product   Connect the transformer output cable to the electronic board  terminal  block A in Fig 4 8   Connect the transformer input cable to the mains   The humidifier power line must be fitted with a disconnect switch           Board connections                                                                                                                                                                                                                                                                                                                o Main Supply  Note  avoid unwanted  interference  the power cables P     should be kept separate from     In  the probe signal cables   Once the electrical and water  Key to Fig  4 a  connections have been    A board power supply input from transformer  24 36V for 230V transfor  completed  the humidifier is 0  136 30V     24V  mer or 24 30V for 115V transformer  ready for operation  Fig  4 c  B ransducer power cable   C valve power cables  L drain   R fill   D configuration dipswitch  E TAM  current transformer  input for measuring current on fan neutral  F rimmer connection to adjust set point  optional  4 3 M   b d    G TH humidity probe connection  IIC digital serial  part no     ain board connections   T        optional  vo Depending on the type of signal used  atomized water production can  remote  1 M14  in i    M11  RSA845 serial  M11  be enabled and or managed in differe
39. ked the water circuit  components  make sure the connections are restored correctly         Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL    un     et  cc         a             gt   e  e       10 1 Diagram                                              DENG    LL    DEN OEZ    DEN vC    77    DEN 9    0                               l      AJLA III ES  IEA IH TE             UleAq       Sf  ypms  MOL  9 91       ue4    LE SKK            A    oo  oo oo  oo oo  oo oo                   LOW LEV        H  LIMS  MO14 14 41    Fig  10 a    24     Ultrasound humidifier for fan coils  0300056EN   rel  1 4   10 02 2014    CAREL    11  GENERAL FEATURES AND MODELS          11 1 Ultrasound humidifier models for fan coils and electrical specifications                                           The table below summarises the electrical data  power supply voltages  of the various models  as well as their functional characteristics  Note that some  models can be powered at different voltages  obviously with different current and humidity production values   power supply  model humidity production 229  kg h    power  code voltage  current   A  cable  wiring diagram  Fig     W   V   type   mm     UUOTFD 05 40 D 230 1  0 5 15 10 a   UUOTF1 045 40 1 115 1  04 1 5 10 a   UU01GD 1 100 D 230 1  1 15 10 a   UU01G1 08 70 1 115 1  0 8 15 10 a   Tab  11 a    tolerance on rated values   5    10   EN 60335 1      SONS    system    tolerance allowed on rated mains voltage   1
40. me for washing h 0 255 24  b3   Washing time  fill   drain  min 0 10     b4  Start delay time 5 0 240 10  b5                    hours for CL alarm h 0 3000      1500  b6   Time to display new CL alarm after reset from keypad  without resetting hour counter  m 0 240 60  b7   Iransducer modulating control period 5 0 10 2  b8  jProbe disconnected delay 5 0 200 10  b9   TAM reading delay S 0 60 2  bA   Maximum fill time min 0 30 15  bb   Water refill time in production 5 0 120 10  bC   Maximum drain time 5 0 240 60  bd   Drain opening time to completely empty tank 5 0 240 30  bE   Delay time after measuring low level for refilling 5 0 240 20  P1 Humidity control hysteresis  rH 2 20 2  P2   Low humidity alarm threshold 96rH 0 100 20  P3   High humidity alarm threshold 96rH 0 100 80  Tab  7 b        1  To change the value from the terminal it is necessary set all related dipswitch to Off  To again use the value given by the dipswitch it is necessary set one of the  dipswitch to On and power off  At the next reboot the control will use again the values set by the dipswitch        17  Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL       Parameter bO                                                                                                                                                                                                                                                                                                                   
41. n On On  04 EC Closed AL C O Of O  05 M EC Closed AL C O Of On  06 EC Closed AL c O On O  07 EC Closed AL C O On On  08 M EC Closed AL C On Of O  09 EC Closed AL C On Of On  0 M EC Closed AL C On On O  1 EC Closed AL E On On On  2 EC Closed SP O O Of O  3 M EC Closed SP O O Of On  4 EC Closed SP O O On O  5 M EC Closed SP O O On On  6 EC Closed SP O On Of O  7 EC Closed SP O On Of On  8 M EC Closed SP O On On O  9 EC Closed SP O On On On  20 M EC Closed SP C O Of O  21 EC Closed SP E O Of On  22 M EC Closed SP C O On O  23 M EC Closed SP C O On On  24 EC Closed SP C On Of O  25 M EC Closed SP E On Of On  26 EC Closed SP C On On O  27 M EC Closed SP C On On On  28 H Open AL O O Ofi O  29 H Open AL O O Ofi On  30 H Open AL O O On O  31 H Open AL O O On On  32 H Open AL O On Of     33    Open AL O On Of On  34 H Open AL O On On O  35 H Open AL O On On On  36 H Open AL E O Ofi O  37 H Open AL C O Ofi On  38 H Open AL C O On O  39 H Open AL C O On On  40 H Open AL E On Of O  41 H Open AL C On Of On  42 H Open AL C On On O  43 H Open AL C On On On  44 H Open SP O O Ofi O  45 H Open SP O O Ofi On  46 H Open SP O O On O  47 H Open SP O O On On  48 H Open SP O On Ofi O  49 H Open SP O On Ofi On  50 H Open SP O On On O  51 H Open SP O On On On  52 H Open SP C O Of O  53 H Open SP C O Ofi On  54 H Open SP C O On O  55 H Open SP C O On On  56 H Open SP C On Of O  19    Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014          CAREL                                  
42. n addition to observing  the above warnings and suggestions  the following warnings must be heeded  for the correct use of the product       DANGER OF ELECTRIC SHOCK  The humidifier contains live electrical components  Disconnect the  mains power supply before accessing inside parts or during maintenance  and installation      DANGER OF WATER LEAKS  The humidifier automatically and constantly fills drains certain quantities  of water  Malfunctions in the connections or in the humidifier may cause  leaks     Ap Important       Environmental and power supply conditions must conform to the values  specified on the product rating labels      The product is designed exclusively to humidify rooms directly      Only qualified personnel who are aware of the necessary precautions and  able to perform the required operations correctly may install  operate or  carry out technical service on the product      Only water with the characteristics indicated in this manual must be used  for water vapour production      All operations on the product must be carried out according to the  instructions provided in this manual and on the labels applied to the  product  Any uses or modifications that are not authorised by the  manufacturer are considered improper  CAREL declines all liability for any  such unauthorised use      Do not attempt to open the humidifier in ways other than those specified  in the manual    e Observe the standards in force in the place where the humidifier is installed   
43. nt ways  ON OFF or modulating    M15           alarm relay  M15 1 M15 2      30 Vdc output  24 Vac rectified   max  3W   M15 3 M15 4  HUMIDOSTAT OR REMOTE CONTACT  ON OFF action   N  auxiliary card connection Production is enabled by closing terminal M14   Tab  4 b M14 can be connected to a switch  a humidistat or a controller  voltage   free contact  max 5 Vdc open  max 7 mA closed    Dipswitch configuration  configuration must be performed TH HUMIDITY PROBE  Optional   before fitting the tank  If the TH humidity probe is connected to the G terminal  fig 4 a  atomized  ON water production starts ifi     The terminal M14 is closed     The humidity value measured by the probe is below the setpoint  H HH         AN  preset at 50 rH and modified via dipswitches 5 6  see Tab 4 a   1 2 3 4 5 6 7 8 The setpoint can be changed by connecting the trimmer  optional  to  Fig  4b F terminal  fig 4 a   1   Communication  OFF Serial 485 Carel Modbus  ON         2 3 tLAN address  if 1 is ON   OFF OFF     OFF O  oe    ON OFF address 2  ON ON address 3 ON OFF  4  Serial 485   tLAN baud rate  OFF 19200     9600  5 6  Humidity Setpoint Fig  4 d  OFF OFF 50  rH            30  rH  ON OFF   40 96rH  ON ON 6096rH 485 SERIAL CONNECTION  7  TAM  OFF disabled Carel Modbus protocol  0 enabled    fur  8  Production transducer management  only for 4 transducer version  A  OFF    gt  parallel management  modulation of all 4   ON    gt  if demand is less than 50   only one pair of transducers opera   tes  
44. osed SP C O On O  251 H E Closed SP C O On On  252 H E Closed SP C On Of O  253 H EC Closed SP C On Ofi On  254 H EC Closed SP C On On O  255 H E Closed SP C On On On  Tab  7 c  7 3 Serial connection parameters  Parameter UOM range def note  CO  Default display  Terminal    0 5 0  C1  Baud rate   0 3 2  0   4800 bps  1   9600 bps  2   19200 bps  3   38400 bps  C2        address  if 0   master   C3  Serial address   1 207 1  C4  Timeout for master offline alarm S 0 240 30 The alarm is only  generated if online  production control is  active  see chap  12 2   Tab  7 d  7 4 Read only parameters  Parameter UOM range def note  dO Th probe temperature reading   C   F 0 1000 0  di Th probe humidity reading 96rH 0 1000 0  d2 Configurable input reading  optional card  96   96rH 0 100 0  d3 Tank operating hour counter  resettable  see 6 10 and 12 8  h 0 9999    0  d4 Unit hour counter  read only  h 0 9999    0  d5 Set point trimmer reading 96rH 0 80 100 0  Tab  7 6                          after 999 the display shows ILL to indicate the 10005  the three digits are displayed with a dot at the top between the first and second digit         21     Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    CAREL    8  ALARMS                                                                         red LED signal       code and symbol meaning cause solution alarm relay action reset  on display activation   flashing   2 fast flashes Et a Autotest failed   Fill not connected or 
45. r A0 2 to enable probe control  see Chap  7  and  parameter A2 depending on the chosen signal  0 to 10V  2 to 10V  0 to  20  4 to 20 mA   see Chap  7         If non CAREL probes are used  check     voltage signal  0 to 10 Vdc  2 to 10 Vdc  terminal M10 1  GND  M10 2    e current signal  4 to 20  0 to 20 mA  terminal M10 1  GND  M10 2      Final checks  The following conditions represent correct electrical connection     mer    o mains power to the humidifier corresponds to the voltage shown on  the rating plate    o a mains disconnect switch has been installed so as to be able to  disconnect power to the humidifier    o terminals M14 1  M14 2 are jumpered or connected to a contact to  enable operation    n ifthe humidifier is controlled by an external controller  with auxiliary  card   the signal earth is electrically connected to the controller earth        Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014          Before starting the humidifier  check     o water connections  chap  2  in the event of water leaks  do not start  the humidifier before having restored the connections   o water vapour distribution  chap  3 and electrical connections chap  4     51 Starting    1 The humidifier  once powered and enabled for production  remote  on off humidistat  terminal M14  Fig 4 e   is ready for operation        2 If there are no other external connections  the humidifier will start  and  operation will only stop if the enabling signal  M14  is no longer p
46. ration of  the piezoelectric transducers     Replacement procedure    1  switch the humidifier off  switch  0   and open the mains disconnect  switch  safety procedure     2  disconnect the transducer power cable    3  releasethetank thetwotabsatthe rear  andliftitverticallyto removeit    4  clean or replace the transducers by removing the screws  see Fig  9 6   after replacement test water tightness by filling the tank manually    5  reconnect the transducer power cables    6  reposition the tank    7  switch the humidifier on           Periodical checks     Each year or after no more than 1500 operating hours     clean the piezoelectric transducers    make sure the level sensor slides freely    Important  in the event of water leaks  disconnect the humidifier  from the power supply and repair the leak    9 3 Cleaning and maintenance of other  components         when cleaning plastic parts do not use detergents solvents      descaling can be performed using a 2096 acetic acid solution  followed  by rinsing with water      to replace the transducers  loosen with the screwdriver the screws  shown in Fig  9 b  being careful not to pull or force  An improper  maintenance can cause future water losses from the tank     Maintenance checks on other components    o fill solenoid valve  After having disconnected the cables and hoses   remove the solenoid valve  check the inlet filter and clean if necessary   using water and a soft brush        Important  after having replaced or chec
47. re  Transducer  Portata 7596  ON  OFF     lt  Periodo  b7   gt   t  Fig  13 d    If the flow rate is 100   the transducers are always on     CAREL    13 4 Series flow rate modulation   4 transducer ver  only  dipswitch 8 On     Atomised water flow rate can be modulated as a percentage of rated  production  from 1096 to 10096  Each pair of transducers generates  5096 of total production  If humidity demand from the external  signal  when using the optional card and proportional control  and  parameter PO are both 100   all four transducers will be activated   For lower demand  production will be split between the two pairs of  transducers as follows        5196   9996  one pair of transducers is always activated to generate 5096  of required production  while the other pair modulates   as described  in the previous paragraph   to generate the remaining percentage of  production     e g  7596 demand  one pair of transducers is always activated  the  other modulates at 5096  as shown in Fig  13 d     1096   5096  one pair of transducers is always off  the other modulates    as described in the previous paragraph   to generate the required  percentage of production     e g  2596 demand  one pair of transducers is always off  the other  modulates at 5096  as shown in Fig  13 d    Distribution of production between the two pairs of transducers  is rotated every hour of operation  to avoid uneven ageing of the  transducers     13 5 Automatic insufficient supply water    management  
48. resent   If TH humidity probe  optional  is connected to terminal G  Fig  4 a    the humidifier will operate until reaching the humidity set point   default 5096rH   See chap  12 9     4 Ifterminal E  Fig  4 a  is connected to the current transformer  TAM   optional  and is enabled  dipswitch 7  Fig  4 c  the humidifier will  only start if current is measured on the fan neutral wire on the prin   cipal system  This wire must run inside the TAM In this way  atomised  water will only be produced when the fan is on     UJ       5 2 Shutdown Standby    1 To switch the humidifier off  disconnect power   2 The humidifier goes into standby when     the remote on off contact is open    TH probe is fitted and the humidity set point has been reached    no current is measured by the TAM  if fitted and enabled     the on off contact is open and serial enabling is set to 0  see  Chap 12 2     a modulating signal is used  optional card  and there is no  request       When the humidifier is in standby  the unit is emptied  automatically  When in standby the fan stays on for 5 min        5 3 Autotest    Whenever the humidifier is first started  from off   if enabled and  humidity production is required  a test cycle is run  A complete fill and  drain cycle is performed  during which the level sensor is monitored  if  the test is successful  regular water vapour production will start  If the test  fails  production is disabled  see the alarm table         5 4 LED signals             A light i
49. s fitted on the top of the humidifier to indicate operating status   GREEN LED ORANGE LED   Steady Humidity production Retry procedure     Flashing slowly  Set point reached Standby   Flashing quickly  Fill or Autotest Washing              Flashing slowly  1s ON and 1s OFF  Flashing quickly  0 25 ON and 0 2s OFF      See paragraphs 13 5 and 13 6     The red LED means an alarm is active  See chapter 8 for information on  alarms      Ultrasound humidifier for fan coils   O300056EN   rel  1 4   10 02 2014    CAREL    5  STARTING  USER INTERFACE AND BASIC FUNCTIONS    5 5 Disabling    The humidifier can be disabled in three different ways      Opening contact M14 1 and M14 2  enabling signal      Ifthe current transformer  TAM  is fitted and enabled  dipswitch 7 ON   and no current is measured     There are active alarms  see Chap  8        5 6 Resettank hour counter    The humidifier is fitted with an hour counter that records operation   After a set number of hours  1500   a signal is activated to indicate  maintenance should be performed on the tank and operation of the  piezoelectric elements checked  see Chap 9  Maintenance and spare  parts  on p  19 and chap  8    Alarm table  on p  18        To reset the hour counter at any time  proceed as follows       Switch the humidifier off     Wait for the tank to empty completely     Close the water supply tap     Removethe tank  making sure to disconnect the piezoelectric element  power supply     Open the On Off contact     Switc
50. tallation is completed  flush the supply hose  for around 30 minutes by piping water directly into the drain  without  sending it into the humidifier  This will eliminate any scale or processing  residues that may block the fill valve     9  Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014    3  ATOMISED WATER DISTRIBUTION       3 1 Atomised water distributor         Important  the atomised water delivery hose  the distributor  the  fan conveyor  the elbow connection and the diffuser are not supplied with  the humidifier     Requirements      humidifier delivery hose OD 40 mm      make sure the atomised water outlet area is 1100 mm2  e g  22 holes  8mm in diameter       the hose running to the distributor should have a minimum upward  gradient of 2   so that any condensate flows back into the humidifier or  a special condensate drain system      make sure there are no condensate leaks from the water vapour  distributor      position the distributor in such a way that the air is not directed against  nearby objects  minimum distance 10 cm       bends or choking of the hose may cause condensate to form and  decrease humidity delivery      avoid loads that may cause mechanical stress on the humidifier outlet  connector           2 c6000999000000009999     A                                              Fig  3 4       o  99000000000000080   9                                                       Fig  3 b    3 2 Fan conveyor          The air flow conveyor can
51. y card probe input   1   Proportional mode from auxiliary probe input   2   Humidity probe mode from auxiliary card probe input   3   Auto mode  if fitted  humidity probe TH reading is used  otherwise On Off mode from contact on  main board  Parameter A2 is not used                   A1  Unit of measure 0   Celsius   1  Fahrenheit   0 1 0   A2  Type of external sensor  optional card   0   On Off  1   0 10V  2   2 10V  3   0 20 mA  4   4 20 mA    0 4 1   PO aximum production  96 10 100   100 only if terminal  connected  otherwise  values set by dipswitch   P1  Humidity control hysteresis 96rH 2 20 2          St  Humidity set point   rH 20 80 50 only if terminal  connected  otherwise    values set by dipswitch                                                                                                                                           CO Default display  Terminal    0 5 0  Tab  7 a  7 2 Advanced parameters  Parameter UOM   range   def note  A3   Probe minimum RH96 0 100 0  A4   Probe maximum RH96 0 100 100  A5  Probe offset RH96   99 100 0  A6   Fan off delay time min 0 240 5  A7   Fanspeed 96 40 100   100  A8   Maximum evaporation time for reduced production alarm min 0 200 30  A9   Minimum evaporation time for reduced production alarm min 0 200 1  AA  Retry waiting time min 1 60 10  Ab  jPercentage of A8 at which to run the level test 96 50  90 70  bO  Operating options  see Tab  7 c    0   63 Z  bl  Time between two washing cycles min 0 120 60  b2 _  Inactivity ti
52. y the   master      SetD37 1      Set parameter AO   2  Carel 20  Modbus 148  Humidity probe Mode       Set integer variable 60 Carel  188 Modbus  to the desired level   0 1000   0 100 0 rH        Set integer variable 52 Carel  180 Modbus  to the desired humidity  setpoin     When the D37 is at 1  if the communication is lost for the seconds settled  by parameter C4  is generated the    Master Offline  alarm  see alarms  table  and the production stops     Production is activated deactivated via digital parameter D27  see  parameter table     If D27   1 the humidifier is disabled and production stops   if D27 2 0 the humidifier is enabled and production is activated    D27 is independent from the state of D37     12 3 Washing cycle activation via network    A washing cycle can be performed at any time by managing digital  variable 38        Setting the variable to 1 will immediately activate a washing cycle  even  if the unit is in standby  and even if both automatic washing and washing  due to inactivity are disabled by their corresponding parameters     The variable will keep the value 1 throughout the duration of the washing  cycle  and will automatically be reset at the end of the cycle      Ultrasound humidifier for fan coils   0300056EN   rel  1 4   10 02 2014          13 1 Ultrasound atomisation    Ultrasound humidifiers atomise water through propagation of a wave  generated by a piezoelectric element to the surface of the water   Droplets of water thus form on the sur
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
ESTRELA    平成22年度 成果報告書〔PDF 529.5KB〕  VGN-AR710E/B  User Manual  HoMedics PerfectSteam PS-150 User's Manual  Manual de usuario de la aplicación de control  Manual de Usuario CCR - Maestro Virtual    Copyright © All rights reserved. 
   Failed to retrieve file