1. Buxton Derbyshire SK17 IRZ United Kingdom ATEX Notified Body for Quality Assurance Det Norske Veritas DNV Notified Body Number 0575 Veritasvelea 1 N 1322 Hovik Norway 27 Rosemount 8800D Quick Installation Guide 00825 0100 4004 Rev DB December 201 1 28
2. STEP 3 SET JUMPERS Adjust jumpers to desired settings HART If alarm and security jumpers are not installed the flowmeter will operate normally with the default alarm condition alarm high and the security off Figure 9 HART Jumpers and LCD FOUNDATION fieldbus If security and simulate enable jumpers are not installed the flowmeter will operate normally with the default security off and simulate enable off Figure 10 FOUNDATION fieldbus Jumpers and LCD VORTEX BEE FOUNDATION ON oF FIELDBUS Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D STEP 4 CONNECT WiRING AND POWER UP Power Supply HART The dc power supply should provide power with less than two percent ripple The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller indicator and related pieces Note that the resistance of intrinsic safety barriers if used must be included Figure 11 Load Limitation Maximum Loop Resistance 41 7 Power Supply Voltage 10 8 Operating Region i A E o v S 24 10 8 42 Power Supply Volts The Field Communicator requires a minimum loop resistance of 2500 FOUNDATION Fieldbus The flowmeter requires 9 32 Vdc at the power terminals Each fieldbus power supply requires a power conditioner to decouple the power supply output from
3. 1 4 4 5 Revision Numbers 1 4 4 7 Descriptor 1 4 4 3 Scaled D A Trim 1 2 6 Density Ratio 1 3 2 4 1 1 Self Test 1 2 1 5 Device ID 1 4 4 7 6 Signal to Trigger Ratio 1 4 3 2 2 Electronics Temp 1 1 4 7 1 STD Nor Flow Units 1 1 4 1 2 Electronics Temp Units 1 1 4 7 2 Special Units 1 1 4 1 3 Filter Restore 1 4 3 3 Status 1 2 1 1 Final Assembly Number 1 4 4 7 5 SV Mapping 1 3 6 2 Fixed Process Density 1 3 2 4 2 Tag 1 3 1 Fixed Process Temperature 11585 23 Total 1 1 4 4 1 Flange Type 1 3 4 Totalizer Control 1 1 4 4 Flow Simulation 1 2 4 Transmitter Mode 15522 1 Installation Effects 1 4 1 6 TV Mapping 1 3 6 3 K factor Reference ISIS Trigger Level 1 4 3 2 5 Local Display 1 4 2 4 URV 1 3 8 1 Loop Test 1292 User Defined Units 1 1 4 1 3 3 Low Flow Cutoff 1 4 3 2 3 USL 1 3 8 4 Low Pass Filter 1 4 3 2 4 Shedding Frequency 1 1 4 6 LRV 1 3 8 2 Variable Mapping 1 3 6 LSL DIS ce Velocity Flow 1 1 4 3 Manufacturer 1 4 4 1 Velocity Flow Base 1 1 4 3 3 Mass Flow 1 1 4 2 1 Volumetric Flow 1 1 4 1 Mass Flow Units 1 1 4 2 2 Wetted Material 1 4 1 4 Mating Pipe ID Inside Diameter 1 3 5 Write Protect 1 4 4 6 Message 1 4 4 4 NOTE For detailed configuration information see the Rosemount 8800D Vortex Flowmeter manual 00809 0100 4004 14 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Table 2 Fast Keys for Rosemount 8800D Device Revision 2 DD Revision 3 Function HART Fast Key Function HART Fast Key Alarm Direction 1
4. 93 180 82 160 71 ln c 140 60 185 F Housing Temperature 120 49 Limit 100 38 80 27 60 16 eo u g 3 f o 2 5 E c 2 2 E lt 1000 538 Process Temperature F C Meter and pipe insulated with 3 inches of ceramic fiber insulation Horizontal Pipe and Vertical meter position The following orientations are recommended for applications with high process temperatures Install with electronics head beside or below process pipe Insulation around pipe may be necessary to maintain ambient temperature below 185 F 85 C NOTE Insulate pipe and meter body only Do not insulate support tube bracket so heat can be dissipated Steam Installations Avoid installation shown Figure 4 Such conditions may cause a water hammer condition at start up due to trapped condensation Figure 4 Improper Installation Upstream Downstream Requirements The Rosemount 8800D Flowmeter may be installed with a minimum of ten straight pipe diameters D upstream and five straight pipe diameters D downstream by following the K factor corrections as described in the 8800 Installation Effects Technical Data Sheet 0081 6 0100 3250 No K factor correction is required if 35 straight pipe diameters upstream 35D and 10 straight pipe diameters downstream 10D are available Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D External Pressure Tem
5. bracket and insert temperature sensor into into the hole at the bottom of the meter body There is no need to remove the opposite end from the electronics Tighten with 1 2 inch open end wrench approximately 1 1 4 turns past finger tight Remote Electronics If you order one of the remote electronics options options R10 R20 R30 R33 R50 or RXX the flowmeter assembly ships in two parts 1 The meter body with an adapter installed in the support tube and an interconnecting coaxial cable attached to it 2 The electronics housing installed on a mounting bracket Mounting Mount the meter body in the process flow line as described earlier in this section Mount the bracket and electronics housing in the desired location The housing can be repositioned on the bracket to facilitate field wiring and conduit routing Cable Connections Refer to Figure 8 and the instructions on page 7 to connect the loose end of the coaxial cable to the electronics housing Figure 8 Remote Electronics Installation 2 NPT Conduit Adapter or Cable Electronics Gland Supplied by Customer Housing Coaxial Cable eter Adapter Union Washer Ground Connection Nut Sensor Cable Nut Housing Base Screw Ne Coaxial Housing Cable Nut P f SUpport Adapter N ril oon ube Housing Adapter Meter Body Screws I re il Conduit Ad
6. could damage the test diode in the test connection Twisted pairs are required to minimize noise pick up in the 4 20 mA signal and digital communication signal For high EMI RFI environments shielded signal wire is required and preferred in all other installations Use 24 AWG or larger wire and do not exceed 5 000 feet 1 500 meters For FOUNDATION fieldbus use wire specifically designed for fieldbus installations for maximum performance For ambient temperatures above 140 F 60 C use wire rated to 176 F 90 C Figure 13 shows wiring connections necessary to power a Rosemount 8800D and enable communications with a hand held Field Communicator Figure 14 shows wiring connections necessary to power the 8800D with FOUNDATION fieldbus 4 Plug and seal unused conduit connections Use pipe sealing tape or paste on threads AN to ensure a moisture tight seal Housing conduit entries marked with M20 will require M 20 x 1 5 blanking plug thread Unmarked conduit entries will require a 1 2 14 NPT blanking plug thread NOTE Straight threads require a minimum of three 3 wraps of tape to obtain a tight seal 5 If applicable install wiring with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the flowmeter housing Rosemount 8800D Vortex units ordered with painted meter body may be subject to electrostatic discharge To avoid electrostatic charge build up do not rub the meter body with a dry c
7. the fieldbus wiring segment Conduit Installation Prevent condensation in any conduit from flowing into the housing by mounting the flowmeter at a high point in the conduit run If the flowmeter is mounted at a low point in the conduit run the terminal compartment could fill with fluid If the conduit originates above the flowmeter route conduit below the flowmeter before entry In some cases a drain seal may need to be installed Figure 12 Proper Conduit Installation with Rosemount 8800D Conduit Line Conduit Line Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 Use the following steps to wire the flowmeter 1 Remove the housing cover on the side marked FIELD TERMINALS 2 Connect the positive lead to the terminal and the negative lead to the terminal as shown in Figure 13 for HART installations and Figure 14 for FOUNDATION fieldbus installations NOTE FOUNDATION fieldbus terminals are not polarity sensitive 3 For HART installations utilizing the pulse output connect the positive lead to the terminal of the pulse output and the negative lead to the terminal of the pulse output as shown in Figure 13 A separate 5 to 30 Vdc power supply is required for the pulse output Maximum switching current for the pulse output is 120 mA CAUTION Do not connect the powered signal wiring to the test terminals Power
8. to the Rosemount 8800D reference manual document number 00809 0100 4004 for more instruction The manuals and this QIG are also available electronically on www rosemount com A WARNING Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Please review the approvals section of the Rosemount 8800D reference manual for any restrictions associated with a safe installation Before connecting a handheld communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Verify the operating atmosphere of the flowmeter is consistent with the appropriate product certifications In an Explosion proof Flameproof installation do not remove the flowmeter covers when power is applied to the unit Electrical shock can result in death or serious injury Avoid contact with the leads and terminals High voltage that may be present on leads can cause electrical shock Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D STEP 1 MOUNT THE FLOWMETER Design process piping so the meter body will remain full with no entrapped air The vortex flowmeter can be installed in any orientation without affecting accuracy However the followin
9. 3 1 3 2 Percent of Range 3 4 3 2 Analog Output 3 4 3 1 Polling Address 2g mr Analog Trim 3 4 3 6 Primary Variable Damping 2 1 4 1 Base Time Unit 2128212382 Primary Variable as lh Base Volume Unit 2 2 2 3 1 Process Density Units 2 2 2 2 6 Burst Mode DETA Process Fluid Type Oe We le 2 Burst Option 2 2 7 3 Process Temp Units 2 2 3 1 2 Burst Slot 0 2 2 7 4 1 Process Variables 3 2 1 Burst Slot 1 2 2 7 4 2 Pulse Output 3 2 4 4 Burst Slot 2 2 2 7 4 3 Pulse Output Test 3 5 3 4 Burst Slot 3 2 2 7 4 4 Recall Factory Calibration 3 4 3 8 Burst Variable Mapping 2 2 7 4 5 Reference K Factor yey bi Compensated K Factor 2 2 1 2 2 Reset Transmitter 3 4 1 2 Conversion Number 2 2 2 3 4 Restore Default Filters 2 1 4 6 Date 2 2 8 2 1 Revision Numbers 2 2 8 3 Descriptor 2 2 8 2 2 Scaled Analog Trim 3 4 3 7 Density Ratio 2 2 3 3 2 2nd Variable 2 2 2 1 2 Device ID 2 2 8 1 5 Self Test 3 4 1 1 Display 2 1 1 2 Set Variable Mapping 2 2 2 1 5 Electronics Temp 3 2 5 4 Shedding Frequency 3 2 4 2 Electronics Temp Units 2 2 2 2 5 Signal Strength 3 2 5 2 Final Assembly Number 2 2 8 1 4 Special Flow Unit Oy PP Sys Fixed Process Density 2 2 1 1 5 Special Volume Unit 2 2 2 3 3 Fixed Process Temperature 2 2 1 1 4 Status Ups i Flange Type 2 2 1 4 2 Tag 2 2 8 1 1 Flow Simulation Su 3rd Variable 2223 4th Variable 2 2 2 1 4 Total 1 3 6 1 Installation Effects 22 Ne Ws 7 Totalizer Configuration TEO Lower Range Value 2 2 4 1 4 Totalizer Control 1 3 6 2 Lower Sensor Limit 2
10. 52745185412 Transmitter Mode ZA abs tal Loop Test 3 5 2 6 Trigger Level 2 1 4 5 Low Flow Cutoff 2 1 4 3 Upper Range Value 2 2 4 1 3 Low pass Corner Frequency 2 1 4 4 Upper Sensor Limit 2 2 4 1 5 1 Manufacturer 2 2 8 1 2 Velocity Flow 3 2 3 4 Mass Flow 3 2 3 6 Velocity Flow Units 2 2 2 2 2 Mass Flow Units 2 2 2 2 4 Velocity Measurement Base 2 2 2 2 3 Mating Pipe ID Inside Diameter 2 2 1 1 6 Volume Flow 3 2 3 2 Message 2 2 8 2 3 Volume Flow Units OPP Meter Body Number 2 2 1 4 5 Wetted Material 2 2 1 4 1 Minimum Span 2 2 4 1 6 Write Protect 22 0 15 Optimize DSP 2 3 3 15 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 PRODUCT CERTIFICATIONS Approved Manufacturing Locations Rosemount Inc Eden Prairie Minnesota USA Emerson Process Management BV Ede The Netherlands Emerson Process Management Flow Technologies Company Ltd Nanjing Jiangsu Province P R China Flameproof enclosure Ex d protection type in accordance with IEC 60079 1 EN 60079 1 Transmitters with Flameproof enclosure type protection shall only be opened when power is removed Closing of entries in the device must be carried out using the appropriate Ex d cable gland or blanking plug Unless otherwise marked on housing the standard conduit entry thread forms are 1 2 14 NPT Type n protection type in accordance with IEC 60079 15 EN 60079 15 Closing of entries in the device must be carried out using the a
11. For information regarding the dimensions of the flameproof joints the manufacturer shall be contacted The Flowmeter shall be provided with special fasteners of property class A2 70 or A4 70 Care must be taken when installing the equipment with process fluid in the range of 202 C to 427 C as the ambient temperature for the electronics and electronics housing must stay in the temperature range of 50 C to 70 C The remote mounted sensor shall only be connected to the transmitter with the associated cable supplied by the manufacturer Chinese Certifications NEPSI Flameproof Certification E3 Certification No GYJ071327X Ex d ia IIC T6 50 C to 70 C Intrinsic Safety I3 Certification No GYJO71171X Ex ia IIC T4 T5 T4 60 C to 70 C T5 60 C to 40 C Input Parameters U 30 Vdc l 185 mA P 1 0 W Ci 0 uF Li 0 97 mH Type N Certification N3 Certification No GYJ071193X Ex nAnL IIC T5 40 C to 70 C 42 Vdc Max K3 E3 13 and N3 Combination 23 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 Japanese Certifications TIIS Flameproof Certification E4 Transmitter Ex d ia T6 Remote Sensor Ex ia IIC T6 Certificate Description TC17816 8800D with display without MTA option TC17817 8800D without display without MTA option TC17905 8800D with display with MTA option TC17906 8800D without display with MTA option 24 Quick Installation Gu
12. Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Rosemount 8800D Series Vortex Flowmeter Start Step 1 Mount the Flowmeter Step 2 Consider Housing Rotation Step 3 Set Jumpers Step 4 Connect Wiring and Power Up Step 5 Verify Configuration Product Certifications nant Ce FOUNDATION ROSEMOUNT MM EMERSON Process Management WWW rosemount com Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 2011Rosemount Inc All rights reserved All marks property of owner Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc The Emerson logo is a trademark and servicemark of Emerson Electric Co Rosemount Inc Emerson Process Management Emerson Process 8200 Market Boulevard Neonstraat 1 Management Asia Pacific Chanhassen MN USA 55317 6718 WX Ede Private Limited T US 800 522 6277 The Netherlands 1 Pandan Crescent T Intnl 303 527 5200 T 31 0 318 495555 Singapore 128461 F 952 906 8889 F 31 0 318 495556 T 65 6777 8211 F 65 6777 0947 65 6777 0743 A IMPORTANT NOTICE This installation guide provides basic guidelines for the Rosemount 8800D Vortex Flowmeter It does not provide instructions for detailed configuration diagnostics maintenance service troubleshooting Explosion proof Flameproof or Intrinsically Safe 1 S installations Refer
13. ansmitter with the associated cable supplied by the manufacturer Special conditions for safe use x For information regarding the dimensions of the flameproof joints the manufacturer shall be contacted The Flowmeter shall be provided with special fasteners of property class A2 70 or A4 70 ATEX Dust Certification EN 60241 0 2006 EN 60241 1 2004 ND Certification No Baseefa05ATEX0086 3 II 1D Ex tD A20 IP66 T90 C 20 C lt Ta lt 70 C 42 VDC Max 4 20 mA HART 32 VDC Max Fieldbus K1 E1 11 N1 and ND Combination 20 Quick Installation Guide 00825 0100 4004 Rev DB December 201 1 Rosemount 8800D International IECEx Certifications Intrinsic Safety IEC 60079 0 2007 IEC 60079 11 2006 I7 Certification No IECEx BAS05 0028X Ex ia IIC T4 Ga 60 C lt T lt 70 C 4 20 mA HART 60 C lt Ta lt 60 C Fieldbus SUIDA ENI Fieldbus Entity Parameters Parameters U 30 VDC U 30 VDC Ii 185 mA lj 300 mA P 1 0W P 1 3W Ci 20 uF Ci 0 uF Li lt 0 97 mH Li lt 10 uH 1 Total for transmitter FISCO FNICO IG Certification No IECEx BAS 05 0028X Ex ia IIC T4 Ga 60 C x T4 lt 60 C Input Parameters Uj 17 5 Vdc l 380 mA P 5 32 W Ci 0 uF Lj 10 pH Special conditions for safe use x When fitted with 90V transient suppressors T1 Option the equipment is not capable of passing the 500V isolation test This must be taken into account upon i
14. apter optional supplie NOTE by customer Consult factory for SST installation Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D 1 If you plan to run the coaxial cable in conduit carefully cut the conduit to the desired length to provide for proper assembly at the housing A junction box may be placed in the conduit run to provide a space for extra coaxial cable length CAUTION The coaxial remote cable cannot be field terminated or cut to length Coil any extra coaxial cable with no less than a 2 in 51 mm radius 2 Slide the conduit adapter or cable gland over the loose end of the coaxial cable and fasten it to the adapter on the meter body support tube If using conduit route the coaxial cable through the conduit Place a conduit adapter or cable gland over the end of the coaxial cable Remove the housing adapter from the electronics housing Slide the housing adapter over the coaxial cable Remove one of the four housing base screws Attach and securely tighten the coaxial cable nut to the connection on the electronics housing 9 Attach the coaxial cable ground wire to the housing via the housing base ground screw 10 Align the housing adapter with the housing and attach with three screws 11 Tighten the conduit adapter or cable gland to the housing adapter CAUTION To prevent moisture from entering the coaxial cable connections install the interconnecting c
15. cleaned with a damp cloth When the equipment is installed particular precautions must be taken to ensure taking into account the effect of process fluid temperature that the ambient temperature of the electrical housing of the equipment meets the marked protection type temperature range ATEX Flameproof Certification EN 60079 0 2009 EN 60079 1 2007 EN 60079 11 2007 19 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 E1 Certification No KEMA99ATEX3852X Integral Flowmeter marked 9 Il 1 2 G Ex d ia IIC T6 Ga Gb 50 C lt Ta lt 70 C Remote Transmitter marked 9 11 2 1 G Ex d ia IIC T6 Ga Gb 50 C lt T4 x 70 C with meter body marked 9 II 1 G Exia IIC T6 Ga 42 VDC Max 4 20 mA HART 32 VDC Max Fieldbus Um 250V Installation instructions The cable and conduit entry devices shall be of a certified flameproof type Ex d suitable for the conditions of use and correctly installed Unused apertures shall be closed with suitable blanking elements When the ambient temperature at the cable or conduit entries exceed 60 C cables suitable for at least 90 C shall be used Care must be taken when installing the equipment with process fluid in the range of 202 C to 427 C as the ambient temperature for the electronics and electronics housing must stay in the temperature range of 50 C to 70 C The remote mounted sensor may only be connected to the tr
16. e taken to ensure taking into account the effect of process fluid temperature that the ambient temperature of the electrical housing of the equipment meets the marked protection type temperature range Flameproof Certification IEC 60079 0 2007 10 IEC 60079 1 2007 04 IEC 60079 11 2006 IEC 60079 26 2006 E7 Certification No IECEx KEM05 0017X Integral Flowmeter marked Ex d ia IIC T6 Ga Gb 50 C lt Ta lt 70 C Remote Transmitter marked Ex d ia IIC T6 Ga Gb 50 C x T4 x 70 C with meter body marked Ex ia IIC T6 Ga 42 VDC Max 4 20 mA HART 32 VDC Max Fieldbus Um 250V Installation instructions The cable and conduit entry devices shall be of a certified flameproof type Ex d suitable for the conditions of use and correctly installed Unused apertures shall be closed with suitable blanking elements When the ambient temperature at the cable or conduit entries exceed 60 C cables suitable for at least 90 C shall be used 22 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Care must be taken when installing the equipment with process fluid in the range of 202 C to 427 C as the ambient temperature for the electronics and electronics housing must stay in the temperature range of 50 C to 70 C The remote mounted sensor may only be connected to the transmitter with the associated cable supplied by the manufacturer Special conditions for safe use x
17. ering ASME B31 3 2008 ATEX Directive 94 9 EC Model 8800D Vortex Flowmeter BasecfatSATEX0084 X Intrinsic Safety Certificate Equipment Group Il Category G Ex ia IIC T4 Ga EN 60079 0 2009 EN 60079 11 2007 Bascefa05ATEX008S X Type n Certificate Equipment Group Il Category 3 G Ex mA ic IIC TS Ge EN 60079 0 2009 EN 60079 11 2007 EN 60079 15 2010 Baseefs SATEX0086 Dust Certificate Equipment Group Il Category 1 D Ex tD A20 IP66 TW EN 61241 0 2006 EN 61241 1 2004 26 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D www CE Schedule EC Declaration of Conformity RFD 1029 Rev K ATEX Directive 94 9 EC continued KEMA99ATEX38S2X Flameproof with Intrinsically Safe Connection s Equipment Group IL Category 1 2 G Ex d ia IIC T6 Ga Gb Integral Transmitter Equipment Groep Il Category 2 1 G Ex d ia Ga IIC T6 Gb Remote Transminer Equipment Group IL Category 1 G Ex ia LIC T6 Ga Remote Sensor EN 60079 0 2009 EN 60079 1 2007 EN 60079 11 2007 EN 60079 26 2007 PED Notified Body Det Norske Veritas DNV Notified Body Number 0575 Veritasveien 1 N 1322 Hovik Norway ATEX Notified Bodies for EC Type Examination Certificate DEKRA Notified Body Number 0344 Utrechtseweg 310 6812 AR Amhem P O Box 5185 6802 ED Amber The Nethertands Postbank 6794587 Baseefa Notified Body Number 1180 Rockhead Business Park Staden Lane
18. g are guidelines for certain installations Vertical Mounting If the vortex flowmeter will be installed in a vertical orientation Install upward or downward flow for gas or steam Install upward flow for liquids Figure 1 Vertical Installation Gas Flow ae a Liquid or Gas Flow Horizontal Mounting Figure 2 Horizontal Installation The meter body installed with the electronics to the side of the pipe jj The meter body installed with the electronics above the pipe Acceptable Preferred za For steam and fluids with small solids content it is recommended to have the flowmeter installed with the electronics to the side of the pipe This will minimize potential measurement errors by allowing the condensate or solids to flow under the shedder bar without interrupting the vortex shedding High Temperature Mounting The maximum temperature for integral electronics is dependent on the ambient temperature where the flowmeter is installed The electronics must not exceed 185 F 85 C Figure 3 shows combinations of ambient and process temperatures needed to maintain a housing temperature of less than 185 F 85 C Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 Figure 3 Rosemount 8800D Ambient Process Temperature Limits 200
19. ide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Figure 15 European Declaration of Conformity EC Declaration of Conformity No RFD 1029 Rev K Rosemount Inc 12001 Technology Drive Eden Prairie MN 55344 3695 USA declare under our sole responsibility that the product s Model 8800D Vortex Flowmeters manufactured by Rosemount Inc 12001 Technology Drive and 8200 Market Boulevard Eden Prairie MN 55344 3695 Chanhassen MN 55317 9687 USA USA to which this declaration relates is in conformity with the provisions of the European Community Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of harmonized or applicable technical standards and when applicable or required a European Community notified body certification as shown in the attached schedule Mark Fleigie name printed Vice President Techaology and New Products function eame printed 25 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 ROSEMOUNT CE Schedule EC Declaration of Conformity RFD 1029 Rev K EMC Directive 2004 108 EC All Models EN 61326 1 2006 PED Directive 97 23 EC Model 88001 Vortex Flowmeter in Line Sizes 1 5 127 QS Certificate of Assessment EC No 9552 2009 CE HOU DNV Module H Conformity Assessment ASME B31 3 2008 Model 8800D Vortex Flowmeter in Line Sizes 5 1 Sound Engine
20. loth or clean with solvents 10 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Figure 13 Flowmeter Wiring Diagrams for HART protocol 4 20 mA Wiring R 22500 1 0 Power Supply Power Supply with Counter Sa du 11 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 NOTE Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 8800D case is properly grounded Figure 14 Flowmeter Wiring Diagram for FOUNDATION fieldbus protocol Field Wiring Diagram ds n 1900 m ma lepending upon cable Integrated characteristics Power Conditioner and Filter Terminators Fieldbus Segment The power supply filter first terminator and configuration tool are typically located in the control room Devices 1 through 16 Intrinsically safe installations may allow fewer devices per I S barrier Cover Jam Screw For transmitter housings shipped with a cover jam screw the screw should be properly installed once the transmitter has been wired and powered up The cover jam screw is intended to disallow the removal of the transmitter cover in flameproof environments without the use of tooling Follow the
21. n into account upon installation 18 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D The enclosure may be made from aluminium alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion when located in Zone 0 environment The polyurethane paint finish may constitute an electrostatic hazard and must only be cleaned with a damp cloth When the equipment is installed particular precautions must be taken to ensure taking into account the effect of process fluid temperature that the ambient temperature of the electrical housing of the equipment meets the marked protection type temperature range ATEX Type N Certification EN 60079 0 2009 EN 60079 11 2007 EN 60079 15 2010 N1 Certification No Baseefa05ATEX0085X ATEX Marking Il 3 G Ex nA ic IIC T5 Gc 50 C lt Ta lt 70 C 4 20 mA HART 50 C lt T4 lt 60 C Fieldbus Input Parameters Maximum Working Voltage 42 VDC Max 4 20 mA HART Maximum Working Voltage 32 VDC Max Fieldbus Special conditions for safe use x When fitted with 90V transient suppressors T1 Option the equipment is not capable of passing the 500V isolation test This must be taken into account upon installation The enclosure may be made from aluminium alloy with a protective polyurethane paint finish The polyurethane paint finish may constitute and electrostatic hazard and must only be
22. nstallation The enclosure may be made from aluminium alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion when located in Zone 0 environment The polyurethane paint finish may constitute an electrostatic hazard and must only be cleaned with a damp cloth When the equipment is installed particular precautions must be taken to ensure taking into account the effect of process fluid temperature that the ambient temperature of the electrical housing of the equipment meets the marked protection type temperature range 21 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 Type N Certification IEC 60079 0 2007 IEC 60079 11 2006 IEC 60079 15 2010 N7 Certification No IECEx BAS05 0029X Ex nA ic IIC T5 Gc 40 C x T x 70 C 4 20 mA HART 40 C lt T x 60 C Fieldbus Maximum Working Voltage 42 VDC 4 20 mA HART Maximum Working Voltage 32 VDC Fieldbus Special conditions for safe use x When fitted with 90V transient suppressors T1 Option the equipment is not capable of passing the 500V isolation test This must be taken into account upon installation The enclosure may be made from aluminium alloy with a protective polyurethane paint finish The polyurethane paint finish may constitute an electrostatic hazard and must only be cleaned with a damp cloth When the equipment is installed particular precautions must b
23. oaxial cable in a single dedicated conduit run or use sealed cable glands at both ends of the cable NOTE Refer to the User Manual for details for the CPA option 0o T4 Qv de 0 STEP 2 CONSIDER HOUSING ROTATION The entire electronics housing may be rotated in 90 increments for easy viewing Use the following steps to change the housing orientation 1 Loosen the three housing rotation set screws at the base of the electronics housing with a 5 32 hex wrench by turning the screws clockwise inward until they clear the support tube 2 Slowly pull the electronics housing out of the support tube CAUTION Do not pull the housing more than 1 5 in 40 mm from the top of the support tube until the sensor cable is disconnected Damage to the sensor may occur if this sensor cable is stressed 3 Unscrew the sensor cable from the housing with a 5 16 in open end wrench 4 Rotate the housing to the desired orientation 5 Holdit in this orientation while you screw the sensor cable onto the base of the housing Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 CAUTION Do not rotate the housing while the sensor cable is attached to the base of the housing This will stress the cable and may damage the sensor 6 Place the electronics housing into the top of the support tube 7 Use a 5 32 hex wrench to turn the three housing rotation screws counter clockwise outward to engage the support tube
24. on 2 Groups A B C and D Temperature Code T4 50 C lt T lt 70 C 4 20 mA HART Temperature Code T4 50 C lt T lt 60 C Fieldbus Single Seal Enclosure Type 4X 17 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 IF FISCO for Class I Division 1 Groups A B C and D FNICO for Class 1 Division 2 Groups A B C and D Temperature Code T4 50 C x T lt 60 C When installed per Rosemount drawing 08800 0112 Enclosure Type 4X K6 E6 and I6 Combination Combination Certifications KB ES 15 E6 and l6 Combination European Certifications ATEX Intrinsic Safety EN 60079 0 2009 EN 60079 11 2007 n Certification No Baseefa05ATEX0084X ATEX Marking II 1 G Ex ia IIC T4 Ga 60 C lt Ta lt 70 C 4 20 HART 60 C lt Ta lt 60 C Fieldbus 4 20 mAHART Fieldbus Entity Entity Parameters Parameters U 30 VDC U 30 VDC I 185 mA lj 300 mA P 1 0Ww Pj213W C 0 uF C 0 uF Lj 0 97 mH Lj lt 10 uH 1 Total for transmitter ce 0575 ATEX FISCO FNICO IA Certification No Baseefa05ATEX0084X ATEX Marking II 1 G Ex ia IIC T4 Ga 60 C lt Ta x 60 C ce 0575 Input Parameters U 17 5 Vdc I 380 mA Pj 5 32 W C 0 uF Lj lt 10 uH Special conditions for safe use x When fitted with 90V transient suppressors T1 Option the equipment is not capable of passing the 500V isolation test This must be take
25. perature Transmitters When using pressure and temperature transmitters in conjunction with the 8800D for compensated mass flows install the transmitters downstream of the Rosemount 8800D flowmeter as shown in Figure 5 Figure 5 Upstream Downstream Piping Wafer Style Installation Figure 6 Wafer Style Installation G Installation Studs and Nuts Supplied by Customer Gaskets Supplied by Customer Flanged Style Installation Figure 7 Flanged Style Flowmeter Installation Installation Bolts and Nuts Supplied by Customer Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 NOTE The required bolt load for sealing the gasket joint is affected by several factors including operating pressure gasket material thickness and condition A number of factors also affect the actual bolt load resulting from a measured torque including condition of bolt threads friction between the nut head and the flange and parallelism of the flanges Due to these application dependent factors the required torque for each application may be different Follow the guidelines outlined in the ASME PCC 1 for proper bolt tightening Make sure the flowmeter is centered between flanges of the same nominal size as the flowmeter Insert Integral Temperature Sensor MTA Option Only The Temperature Sensor is coiled and attached to the electronics bracket Remove the plastic band holding the sensor to the electronics
26. ppropriate Ex e or Ex n cable gland and metal blanking plug or any appropriate ATEX or IECEx approved cable gland and blanking plug with IP66 rating certified by an EU approved certification body European Directive Information The CE Declaration of Conformity for all applicable European directives for this product can be found on our website at www rosemount com A hard copy may be obtained by contacting our local sales office ATEX Directive Rosemount Inc complies with the ATEX Directive European Pressure Equipment Directive PED Rosemount 8800D Vortex Flowmeter Line Size 40 mm to 300 mm Certificate Number 59552 2009 CE HOU DNV ce 0575 Module H Conformity Assessment Mandatory CE marking for flowmeters in accordance with Article 15 of the PED can be found on the flowtube body Flowmeter categories IIl use module H for conformity assessment procedures Rosemount 8800 Vortex Flowmeter Line Size 15 mm and 25 mm Sound Engineering Practice Flowmeters that are SEP are outside the scope of PED and cannot be marked for compliance with PED 16 Quick Installation Guide 00825 0100 4004 Rev DB December 2011 Rosemount 8800D Hazardous Location Certifications Rosemount 8800D North American Certifications Factory Mutual FM E5 Explosion Proof for Class I Division 1 Groups B C and D Dust ignition proof for Class II III Division 1 Groups E F and G Temperature Code T6 50 C lt Ta lt 70 C Facto
27. riable Mapping Range Values Pulse Output Configuration For units with a pulse output only Transmitter Mode Process Fluid Reference K Factor Flange Type Mating Pipe ID PV Units Configured in the Al block Flow Damping Process Temperature Damping Fixed Process Temperature Auto Adjust Filter LCD Display Configuration For units with a display only Density Ratio For Standard or Normal flow units only Process Density and Density Units For mass flow units only 13 Quick Installation Guide 00825 0100 4004 Rev DB Rosemount 8800D December 2011 Table 1 Fast Keys for Rosemount 8800D Device Revision 1 DD Revision 2 and Device Revision 2 DD Revision 1 Function HART Fast Key Function HART Fast Key Alarm Jumpers 1 3 Meter Body Number 1 4 2 1 4 1 5 Analog Output 1 4 2 1 Minimum Span TS Auto Adjust Filter 1 4 3 1 4 Num Req Preams 1 4 2 3 2 Base Time Unit Tey leh Poll Address 1 4 2 3 1 Base Volume Unit 1 1 4 1 3 1 Process Fluid Type 1 3 2 2 Burst Mode 1 4 2 3 4 Process Variables i Burst Option 1 4 2 3 5 Pulse Output 1 4 2 2 1 Burst Variable 1 1 4 2 3 6 1 Pulse Output Test 1 4 2 2 2 Burst Variable 2 1 4 2 3 6 2 PV Damping 1 3 9 Burst Variable 3 1 4 2 3 6 3 PV Mapping 1 3 6 1 Burst Variable 4 1 4 2 3 6 4 PV Percent Range 1 1 2 Burst Xmtr Variables 1 4 2 3 6 QV Mapping 1 3 6 4 Conversion Number 1 1 4 1 3 4 Range Values 1 3 8 D A Trim 25 Review 105 Date
28. ry Sealed Enclosure Type 4X I5 Intrinsically safe for use in Class Il III Division 1 Groups A B C D E F G Non incendive for Class I Division 2 Groups A B C and D NIFW Non incendive Field Wiring when installed per Rosemount Drawing 08800 0116 Temperature Code T4 50 C lt T lt 70 C 4 20 mA HART Temperature Code T4 50 C lt T lt 60 C Fieldbus IE FISCO for Class Division 1 Groups A B C and D FNICO for Class 1 Division 2 Groups A B C and D Temperature Code T4 50 C T lt 60 C when installed per Rosemount control drawing 08800 0116 Enclosure Type 4X K5 E5 and I5 Combination Special conditions for safe use x When fitted with 90V transient suppresors T1 Option the equipment is not capable of passing the 500V insulation test This must be taken into account upon installation The enclosure may be made of an aluminum alloy and given a protective polyurethane paint finish care should be taken to protect the housing from impact or abrasion Canadian Standards Association CSA E6 Explosion Proof for Class I Division 1 Groups B C and D Dust ignition proof for Class Il and Class III Division 1 Groups E F and G Class I Zone 1 Ex d ia IIC CSA 06 1674267 Temperature Code T6 50 C lt T lt 70 C Factory Sealed Single Seal Enclosure Type 4X l6 Intrinsically safe for use in Class Il III Division 1 Groups A B C D E F G Non incendive for Class I Divisi
29. se steps to install the cover jam screw 1 Verify that the cover jam screw is completely threaded into the housing Install the transmitter housing cover and verify that the cover is tight against the housing 2 3 Using an M4 hex wrench loosen the jam screw until it contacts the transmitter cover 4 Turn the jam screw an additional 1 2 turn counterclockwise to secure the cover NOTE Application of excessive torque may strip the threads 5 Verify that the cover cannot be removed 12 Quick Installation Guide 00825 0100 4004 Rev DB December 201 1 Rosemount 8800D STEP 5 VERIFY CONFIGURATION Before operating the Rosemount 8800D in an installation you should review the configuration data to ensure that it reflects the current application In most cases all of these variables are pre configured at the factory Configuration may be required if your 8800D is not configured or if the configuration variables need revision Rosemount recommends the following variables are reviewed before startup HART Configuration FOUNDATION fieldbus Configuration e Tag Tag Transmitter Mode Process Fluid Reference K Factor Flange Type Mating Pipe ID PV Units PV Damping Process Temperature Damping Fixed Process Temperature Auto Adjust Filter LCD Display Configuration For units with a display only Density Ratio For Standard or Normal flow units only Process Density and Density Units For mass flow units only Va