Powerware 9125 Two-in-One UPS 2500/3000 VA User`s

image

Contents

1. REPO Port Battery Connector i dl Communication Port Network X Slot Communication Ba Transient le O Ede Y Protector O S a a T S hi T Circuit Protector TWO 5 20 REE RARES Two 5 15 Receptac Power Cord with aal m Receptacle Figure 25 2500 3000 VA 120V Rear Panel REPO Port Battery Connector Communication Port Network Oy gt L X Slot Communication Bay Transient les f ses Ee Protector ON GEGIET CEE e 9 Four 10A IEC 320 C13 Receptacles 16A IEC 320 Input Connector 16A IEC 320 019 Receptacle Figure 26 2500 3000 VA 208V Rear Panel Battery Connector with Cover REPO Por Circuit Breakers Communication Port Network x o E LY stot Communication Bay Transient res E Le Protector L N RO n Segel e 9 Four 10A IEC 320 C13 Receptacles 16A IEC 320 Input Connector 16A IEC 320 C19 Receptacle Figure 27 2500 3000 VA 230V Rear Panel EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 33 www powerware com INSTALLATION Network Transient Protector REPO Port Terminal Block Communication Port Network N 19 Transient Les 1 Q Q Protector 3 O e o e Battery Connector with Figure 29 2500 3000 VA 230V Har
2. Figure 6 Rack Mount UPS with EBMs If installing optional EBMs continue to Extended Battery Module Installation on page 22 Otherwise continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 to complete the installation Tower Setup The setup varies depending on the number of cabinets you are installing 1 18 For one cabinet the pedestals must be installed Continue to Step 2 For two cabinets the pedestals and the joining brackets must be installed Skip to Step 6 For three or more cabinets the joining brackets must be installed Skip to Step 9 Place the UPS cabinet horizontally so that the left end of the cabinet is accessible see Figure 7 Align the pedestals with the screw holes on the end of the UPS cabinet Secure the pedestals with the screws provided in the accessory kit EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION Figure 7 Installing UPS Pedestals for One Cabinet 4 Carefully position the cabinet upright with the air vents at the top see Figure 8 b Continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 to complete the installation e Air Vents
3. UPS Battery T UPS EBM Cable EBM EBM o EBM Battery Connectors Figure 14 Typical EBM Installation 120V UPS Model Shown 22 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION 4 E EH UPS models have a battery connector cover that must be removed before installing the EBM s Remove the cover from the rear panel as shown in Figure 15 NOTE Keep the battery connector cover and screws for future use If the UPS is stored or used without an EBM the battery connector cover must be installed as a safety precaution Battery Connector Cover Screws MANGLET lt 3 1 Malt Figure 15 Battery Connector Cover E EH UPS Models Only 5 Remove the cover from the EBM cable as shown in Figure 16 NOTE Keep the EBM cable cover and screws for future use If the EBM is stored or removed from the UPS the EBM cable cover must be installed as a safety precaution A 7 EBM Cable with Cover Figure 16 EBM Cable Cover E EH UPS Models Only EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 23 www pow
4. 53 How to Replace Extended Battery Modules 55 Testing New Batteries annabel oss us Reo bts da mese dee bae ear e Ue e eite 56 Recycling the Used Battery or UPS 57 SPOCIIGANONS a AA en 59 Troubleshooting s sa sata citys a a daa 63 Audible Alarms and UPS Conditions 63 Silencing an Audible Alarm A Mere dex al 63 Service ANU Support ud s dece ee Da PEU etiim PNE ear 66 Warranty mM 67 Two Year Limited Warranty US and Canada 67 Ten Year Pro Rated Limited Warranty US and Canada 69 Load Protection Guarantee US and Canada 71 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 1 Introduction The Powerwaree 9125 uninterruptible power system UPS protects your sensitive electronic eguipment from the most common power problems including power failures power sags power surges brownouts line noise high voltage spikes freguency variations switching transients and harmonic distortion Power outages can occur when you least expect it and power guality can be erratic These power problems have the potential to corrupt critical dat
5. Got Terminal Block Cover Screws Figure 21 Wiring Access and Terminal Block 4 Pull the input and output wires through separate conduit leaving approximately 0 5m 2 ft of exposed wi fitting to the end of each conduit re Attach a flexible metal 28 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION 5 Insert each conduit through a wiring access entry and attach the conduit fitting to the panel Strip 1 5 cm 0 5 of insulation from the end of each incoming wire 6 Connect the input and ground wires to the input terminal block according to Figure 22 and Table 1 7 Connect the output and ground wires to the output terminal block according to Figure 22 and Table 1 O O O O O O O O O O O 3 o a o o A red NPU OUTPUT 1 2 3 4 5 6 Figure 22 Terminal Block Table 1 UPS Wiring Specifications UPS Wire Function Wire Terminal Terminal Wire Tightening Function Position EUH Models EH and GH Models Size Rating Torque Input 1 L2 N 2 10 mm E 2 G G 14 8 AWG 4 38 Nm 35 Ib in 3 L1 L Output 4 L2 N 2 10 mm 5 G G 14 8 AWG 4 38 Nm 35 Ib in 6 L1 L Use 2 0 mm 14 AWG 75 C copper wire minimum 8 Reinstall the terminal block cover 9 If an emergency power
6. Figure 8 Pedestals with One Cabinet 6 Place the UPS cabinet horizontally so that the left end of the cabinet is accessible see Figure 9 RS a SH Figure 9 Installing UPS Pedestals for Two Cabinets EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 19 www powerware com INSTALLATION 7 Place the EBM cabinet upside down so that the right end of the cabinet is accessible see Figure 10 A jf SERRE MTU E Figure 10 Installing EBM Pedestals 8 Align the pedestals with the screw holes on the end of the EBM cabinet Secure the pedestals with the screws provided in the accessory kit 9 Carefully position the cabinets upright with the air vents at the top see Figure 11 or Figure 12 Air Vents Figure 11 Pedestals with Two Cabinets 20 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION NOTE Pedestals are required for installations with one or two cabinets Joining brackets are required for installations with two or more cabinets 3 Air Vents 890
7. Figure 12 Tower Setup with Three Cabinets 10 Align each joining bracket with the adjacent corner screw holes and secure with the supplied screws see Figure 13 RSA Joining Bracket Joining Bracket Figure 13 Installing the Joining Brackets Top View with Pedestals 11 If installing additional EBMs repeat Step 10 for each cabinet 12 If installing optional EBMs continue to the following section Extended Battery Module Installation Otherwise continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 to complete the installation EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 21 www powerware com INSTALLATION Extended Battery Module Installation CAUTION A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly To install the optional EBMs 1 If installing an EBM with an E EH UPS model skip to Step 4 otherwise continue to Step 2 2 Plug the EBM cable s into the battery connector s as shown in Figure 14 Up to four EBMs may be connected to the UPS 3 Continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27
8. ront panel indicators and controls Alarm Indicators see page 63 i Bar Graph Indicators Indicator Legend o Unlit e Lit EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D cators Figure 30 shows the UPS N ro y O so lao RNA gesto ee Tanin a 19 Ort OLO O Oeo ES Ay G EE oL 6 CD a i Off Button On Button Figure 30 UPS Front Panel NA e Flashing ZIN 37 www powerware com OPERATION 38 Normal Mode During Normal mode the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment see Figure 31 The UPS monitors and charges the batteries as needed and provides power protection to your equipment Vv o O O O O O lt 10 00000 10 25 00000 26 50 00000 51 75 o 0 0 76 100 NIVA o 0 gt 100 ZIN SSH Figure 31 Load Level Indicators When all of the bar graph indicators are illuminated and the indicator flashes power requirements exceed UPS capacity see page 65 for more information EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com OPERATION Battery Mode When the UPS is operating during a power outage the alarm beeps once per second and the indicator illuminates The front panel displays the approximate percentage of battery capacity remaining see Figure 3
9. 164201374 Rev D 35 www powerware com OPERATION Turning the UPS Off NOTE Pressing the Off b button while the UPS is in Battery mode causes the UPS to shut down immediately To turn off the UPS 1 Prepare your equipment for shutdown 2 Press and hold the Off 1 button for approximately three seconds The UPS transfers to Standby mode if utility power is available and removes power from your equipment 3 Unplug or remove utility power from the UPS the UPS shuts down in five seconds All front panel indicators flash briefly prior to shutdown If you do not unplug or remove utility power from the UPS it remains in Standby mode Initiating the Self Test NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the self test NOTE AC input power must be applied to the UPS for 24 hours before performing the self test Press and hold the 4 button for three seconds to initiate the self test During the five second test the bar graph indicators cycle through twice If the alarm beeps or a UPS alarm indicator stays on see Table 11 on page 64 36 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Operating Modes OPERATION Powerware 9125 s front panel indicates the UPS status through the UPS indi Normal Mode Indicator Battery Mode Indicator Bypass Mode Indicator Test Alarm Reset Button
10. E T N Powerware Powerware 9125 Two in One UPS 2500 3000 VA User s Guide Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense ICES 003 This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe A respecte toutes les exigences du Reglement sur le mat riel brouilleur du Canada EN 50091 2 Some configurations are classified under EN 50091 2 as Class A UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a domestic environment this product may cause radio interference in which case the user may be required to take additional measures Powerware ABM LanSafe and FERRUPS are registered trademar
11. slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den e For a redusere fare for brann eller elektriske st t b r denne UPS en installeres i et innendgrs miljg med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen m ikke overskride 40 C Den m ikke brukes i naerheten av vann eller ved meget hay luftfuktighet 95 maks Alt utstyr som er forbundet med utgangen av denne UPS en m ikke ha en sterkere total lekkasjestrgm enn 1 5 milliampere for v re i overensstemmelse med internasjonale standarder og forkablingsbestemmelser e For UPS systemer med fastkoplete uttak m overstramvern for vekselstramuttak ene stilles til r dighet av andre e For UPS systemer med fastkoplete uttak m passende utkoplingsbrytere for vekselstramuttaklene stilles til r dighet av andre FORSIKTIG e Batterier kan for rsake elektriske st t eller forbrenning p grunn av h y kortslutningsstrgm Folg instruksene e Batterier m fjernes p korrekt m te Se lokale forskrifter vedr rende krav om fjerning av batterier e Kast aldri batterier i flammer da de kan eksplodere hvis de utsettes for pen ild 10 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com SAFETY WARNINGS Regulamentos de Seguran a INSTRU ES DE SEGURAN A IMPORTANTES GUARDE ESTAS INSTRU ES _ ESTE MANU
12. 110 120 127V selectable 80 144V PW9125 3000U 3000 VA 2100W PW9125 2500EU 2500 VA 1750W PW9125 2500G 208V default 230 240V selectable 160 288V PW9125 3000EU 3000 VA 2100W PW9125 3000G PW9125 2500E 2500 VA 1750W 230V default 220 240V selectable 160 288V PW9125 3000E 3000 VA 2100W PW9125 2500EUH 2500 VA 1750W PW9125 2500GH 208V default 230 240V selectable 160 288V PW9125 3000EUH 3000 VA 2100W PW9125 3000GH PW9125 2500EH 2500 VA 1750W 230V default 220 240V selectable 160 288V PW9125 3000EH 3000 VA 2100W EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 59 www powerware com SPECIFICATIONS Table 5 Power Connections Model Input Connection Output Connections Load Segment 1 Load Segment 2 PW9125 2500U PW9125 3000U 6 ft 5 30P attached power cord 2 5 15R and 2 5 20R 1 5 30R output cord PW9125 2500EU PW9125 3000EU PW9125 2500E PW9125 3000E PW9125 2500G PW9125 3000G 16A IEC 320 C20 input connector Country specific detachable power cord 4 10A IEC 320 C13 1 16A IEC 320 C19 PW9125 2500EUH PW9125 3000EUH PW9125 2500EH PW9125 3000EH PW9125 2500GH PW9125 3000GH Terminal block Terminal block N A Table 6 Technical Specifications Nominal Frequency 45 65 Hz 50 60 Hz auto sensing Noise Filtering MOVs and line filter for normal and common mode noise Regulation Normal Mode Nominal out
13. 3000 VA User s Guide 164201374 Rev D www powerware com Table 2 Configuration Mode LEDs and Options Configuration Mode CONFIGURATION LEDs Option LED Status Explanation 252 120 208 or 230V On default Nominal input voltage is one of the following 00006 Nominal Input e 120V for U models Voltage e 208V for EU EUH and G GH models q e 230V for E EH models All other nominal input voltages are disabled Flashing Disabled one of the other input voltage options is selected 110 220 or 230V On Selecting this option changes the nominal input voltage 6 6 8 N o Nominal Input to one of the following AN Voltage e 110V for U models e 220V for E EH models 230V for EU EUH and G GH models Flashing Disabled one of the other input voltage options is selected E 127 or 240V Nominal On Selecting this option changes the nominal input voltage ae NZ SO Input Voltage to one of the following AN e 127V for U models e m e 240V for EU EUH E EH and G GH models Flashing Disabled one of the other input voltage options is selected Site Wiring Fault On default Alarm sounds when the polarity of the outlet is reversed Alarm or the ground connection is missing have a qualified oe oo electrician repair the outlet wiring _ Wo Flashing Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground connection is missing For 208V or 230V models flashing is the default contact yo
14. Check the bar graph indicators for available battery capacity and prepare your equipment for shutdown NUA Hee wooo ZIN qq Warning Low Battery Three minute battery warning Three minutes or less of battery power remains depending on load configuration and battery charge Save your work and turn off your equipment 64 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Alarm or Condition Possible Cause TROUBLESHOOTING Action MY e 00000 ZIN mm Shutdown Low Battery Shutdown imminent Prepare equipment for shutdown gt e Bypass The UPS is in Bypass mode The equipment is transferred to utility power however the utility power continues to be passively filtered by the UPS Check for one of the following alarms Overtemperature Overload UPS Failure or Battery Service NU gt e Bypass ZIN Bypass is not available Input voltage is not within 12 of nominal or input frequency is not within 3 of nominal The UPS is receiving utility power that may be unstable or in brownout conditions The UPS continues to supply power to your equipment lf conditions worsen the UPS may switch to battery power wi Battery Service o AN The batteries may be fully discharged Plug the UPS into a power outlet apply utility power on hardwired models for 24 hours to charge the batteries After charging the bat
15. Figure 18 shows a typical installation only See UPS Rear Panels on page 33 for the rear panel of each model To install a plug receptacle UPS 1 If you are installing power management software connect your computer to the UPS communication port using the supplied communication cable Dutput Receptacles Communication Port Power ii DD UPS Sal TN O Li EBM EBM Figure 18 Typical Installation 120V UPS Model Shown 2 Plug the equipment to be protected into the appropriate UPS output receptacles see page 50 for more information on load segments NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements 3 If an emergency power off disconnect switch is required by local codes see Remote Emergency Power off Installation on page 31 to install the REPO switch before powering on the UPS EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 25 www powerware com INSTALLATION oa For 208 230V models only Plug the detachable UPS power cord into the input connector on the UPS rear panel Plug the UPS power cord into a power outlet All front panel indicators flash briefly and the UPS conducts a self test When the self test is complete the indicator flashes indicating the
16. One UPS 2500 3000 VA User s Guide 164201374 Rev D w www powerware com SAFETY WARNINGS CAUTION e Batteries can present a risk of electrical shock or burn from high short circuit current Observe proper precautions Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements e Never dispose of batteries in a fire Batteries may explode when exposed to flame Sikkerhedsanvisninger VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER A Denne UPS indeholder LIVSFARLIG H JSP NDING Alle reparationer og vedligeholdelse b r kun udfgres af en AUTORISERET SERVICETEKNIKER Ingen af UPS ens indvendige dele kan repareres af brugeren ADVARSEL A e Denne UPS indeholder egen energiforsyning batterier Udgangsnetstikkene kan lede strgm selv n r UPS en ikke er tilsat en AC energikilde e Netledningen ma ikke fjernes og stikket m ikke tr kkes ud mens UPS en er t ndt Dette fjerner sikkerhedsjorden fra UPS en og fra det udstyr der er sat til Installer denne UPS i et temperatur og fugtighedskontrolleret indend rsmilj frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stad Rumtemperaturen ma ikke overstige 40 C UP
17. Product s operation and maintenance manual and protect against further damage to the Product if there is a covered defect 70 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com WARRANTY OTHER LIMITATIONS Company s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it including interest charges if any During such time as Company has not received payment of any amount due to it for the Product in accordance with the contract terms under which the Product is sold Company shall have no obligation under this Warranty Also during such time the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts COSTS NOT RELATED TO WARRANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Warranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipment installation materials freight charges travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End User OBTAINING WARRANTY SERVICE In the USA call the Customer Reliability Center 7x24 at 800 356 5737 Outside of the USA contact your local Powerware product sales or service representative
18. REPARAR dentro del SIE ADVERTENCIA Este SIE contiene su propia fuente de energia las baterfas Los recept culos de salida pueden transmitir corriente el ctrica aun cuando el SIE no este conectado a un suministro de corriente alterna c a No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE Para reducir el riesgo de incendio o de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cerca del agua o con humedad excesiva 95 m ximo Para cumplir con los est ndares internacionales y las normas de instalaci n la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de p rdida a tierra superior a los 1 5 miliamperios Para los sistemas UPS con salidas cableadas permanentamente la protecci n contra exceso de corriente para el los circuito s de CA de salida ser suministrada por terceros Para los sistemas UPS con salidas cableadas permanentemente los interruptores de desconexi n debidamente clasificados para el los circuito s de CA de salida ser n suministrados por terceros PRECAUCI N e Las baterfas pueden presentar un riesgo de descargas el ctricas o de guemaduras debido a la alta corriente de cortocircui
19. This Guaranty applies only if all of the following circumstances arise 1 The UPS is plugged into properly grounded and wired outlets using no extension cords adapters other ground wires or other electrical connectors 2 The installation of the UPS complies with all applicable electrical and safety codes described by the National Electric Code NEC 3 The UPS was used under normal operating conditions and in accordance with all labels and instructions and 4 The UPS was not damaged by accident other than AC power line transient misuse or abuse Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty e 25 000 for Powerware UPS Models 3105 3110 and 3115 150 000 for Powerware UPS Models 5110 5115 and 5125 e 250 000 for Powerware UPS Models 9120 9125 9150 9155 9170 and FERRUPS products EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 71 www powerware com WARRANTY WHAT THIS GUARANTY DOES NOT COVER Any reimbursement or repair to End User s equipment does not include reimbursement for or restoration of any data loss This Guaranty does not cover any defects or damages caused by a failure to properly store the Product before installation including the charge of batteries no later than the date indicated on the packaging b shipping and delivery of the Product if shipping is FOB Factory c neglect accident abuse misuse misapplication or incorre
20. UPS output from a customer supplied switch in a remote location The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software Any devices that are operating on battery power are also shut down immediately When the REPO switch is reset the equipment will not return to battery power until the UPS is manually restarted If the Off J button is pressed after the REPO is activated the UPS remains in Standby mode when restarted until the On button is pressed The REPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation CAUTION To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated NOTE The REPO function activates when the REPO contacts open NOTE f the REPO function is not needed the REPO connector must remain installed in the REPO port on the UPS rear panel NOTE For Europe the emergency switch requirements are detailed in Harmonized document HD 384 48 S1 Electrical Installation of the Buildings Part 4 Protection for Safety Chapter 46 Isolation and Switching To install the REPO switch 1 Verify that the UPS is off and and disconnected from utility power 2 Remove the REPO
21. a dedicated branch circuit that meets the following requirements 16A 2 pole circuit breaker for EH and GH models 20A 2 pole circuit breaker for EUH models to provide short circuit and overcurrent protection The protection device requires a two pole disconnection device between the UPS output and the load The breaker must be wall mounted and readily accessible to the operator For Europe the breaker must be approved by the appropriate safety agency such as TUV or VDE and have a contact air gap of at least 3mm 200 240 Vac Single phase 50 60 Hz Flexible metal conduit recommended for ease of service and maintenance EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 27 www powerware com INSTALLATION To hardwire the UPS 1 If you are installing power management software connect your computer to the UPS communication port using the supplied communication cable 2 Switch off utility power at the distribution point where the UPS will be connected Be absolutely sure there Terminal Block Cover is no power Communication Port s OO UPS EBM EBM Figure 20 Typical Hardwired UPS Installation 3 Remove the terminal block cover and the wiring knockouts see Figure 21 Retain the terminal block cover and screws Input Wiring Access Output Wiring Access
22. connector from the REPO port on the UPS rear panel EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 31 www powerware com INSTALLATION 3 Connect isolated normally closed dry contacts rated to handle 60 Vdc maximum 30 Vac RMS maximum and 20 mA maximum across the REPO device to Pin 1 and Pin 2 see Figure 24 Use stranded non shielded wiring size 0 75 mm2 0 5 mm 18 20 AWG o NOTE A separate contact must simultaneously cause UPS input AC power to be removed Pin 1 Pin 2 el Figure 24 REPO Connector Reconnect the REPO connector to the REPO port Verify that the externally connected REPO switch is not activated to enable power to the UPS output Plug in the UPS or switch the main utility breaker on for hardwired units and start the UPS by pressing the On button Activate the external REPO switch to test the REPO function De activate the external REPO switch and restart the UPS 32 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION UPS Rear Panels This section shows the rear panels of the Powerware 9125 models
23. for additional information such as important operating and maintenance instructions RJ 45 RECEPTACLE For 230V models only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Table of Contents T gt Introduction cir le sg wam a a qawa a len 1 2 Safety Warnings 3 3 Installation sasson 8 ee a ere wnd 15 Inspecting the Equipments tte uen eme ne mes hisser EO MSS 15 Gonnecting the UPS Internal Battery aksjen ege eR e Ne eee pe AA LOC t tex 16 UPSES coe p erbe ue EE EUSEB 16 Rack Mount Setupr ass simarin eee UL et A MEHR ME kia nk ah see 17 Tower Setup ota ee ete IS A A En neu CU ma 18 Extended Battery Module Installation 22 Plug Receptacle UPS Installation 25 Hardwired UPS Installation eo RENE Y SES TO aa a ead 2 Remote Emergency
24. models only network protection is available for 230V models 1 Connect the input connector of the equipment you are protecting to the jack labeled IN 2 Connect the network or telephone cable low voltage models only to the jack labeled OUT Jol Ja OUT Figure 38 Network Transient Protector EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 49 www powerware com ADDITIONAL UPS FEATURES Load Segments 50 Load segments are sets of receptacles that can be controlled by power management software providing an orderly shutdown and startup of your equipment For example during a power outage you can keep key pieces of equipment running while you turn off other equipment This feature allows you to save battery power See your power management software manual for details refer to the Software Suite CD or www powerware com for the latest information NOTE If power management software is not used the individual load segments cannot be controlled For hardwired UPSs there is only one load segment The terminal block serves as Load Segment 1 Each plug receptacle UPS has two load segments as shown in Figure 39 and Figure 40 Load Segment 2 e Figure 39 UPS Load Segments for 120V Models 0000 o Load Segment il fr Segment 2 Figure 40 UPS Load Segments for 208 230V Mod
25. polls the UPS for detailed information on the status of the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment The cable pins are identified in Figure 35 and the pin functions are described in Table 3 00000 00600 Figure 35 Communication Port 46 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com ADDITIONAL UPS FEATURES Table 3 Communication Port Pin Assignment Pin Number Signal Name Function Direction from the UPS 1 Low Batt Low Battery relay contact 20 mA 30 Vdc contact rating Out 2 TxD Transmit to external device Out 3 RxD Receive from external device In 4 DTR PnP Plug and Play from external device tied to Pin 6 In 5 GND Signal common tied to chassis 6 DSR To external device tied to Pin 4 Out 7 RTS PnP from external device default or On Bypass relay In Out contact jumper selectable 8 AC Fail AC Fail relay contact 20 mA 30 Vdc contact rating Out 9 Power Source V 8to 24 volts DC power Out The On Bypass Relay Contact You can enable the On Bypass relay using the jumper on the Single Port Card The jumper default is disabled To enable the On Bypass relay 1 Remove the Single Port Card on the UPS rear panel Retain the screws see Figure 36 Figure 36 Removing the S
26. temp rature e l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas utiliser proximit d eau ou dans une atmosph re excessivement humide 95 96 maximum e Afin d tre con fuite la terre d passer 1 5 mA Pour les model forme aux normes et r glements internationaux de c blage le courant de de la totalit du mat riel branch sur la sortie de l onduleur ne doit pas s UPS ayant des sorties c bl es la protection contre une surintensit pour le s circuits de sortie de courant alternatif doit tre fournie par un autre fournisseur e Pour les model s UPS ayant des sorties c bl es les interrupteurs de d connexion convenables pour le s circuit s de sortie de courant alternatif doivent tre fournie par un autre fournisseur ATTENTION e Les batteries peuvent pr senter un risque de d charge lectrique ou de br lure par des courts circuits de haute intensit Prendre les pr cautions n cessaires Une mise au rebut r glementaire des batteries est obligatoire Consulter les r glements en vigueur dans votre localit e Ne jamais jete exploser r les batteries au feu L exposition aux flammes risque de les faire EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D N www powerware com SAFETY WARNINGS Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAREN Dieses Handbuch enth lt
27. 2 When utility power returns the UPS transfers to Normal mode operation while the battery recharges Vv amp eo 00000 gt 7 0 O O gt 0 00000 gt 25 NU e 0 O O O 3 Minute Warning ZIN VI 00000 Shutdown Imminent ZIN SEI Figure 32 Battery Capacity Indicators If battery capacity becomes low while in Battery mode the 2 indicator starts flashing and the alarm becomes continuous indicating approximately three minutes of battery time remaining When shutdown is imminent the Y indicator flashes NOTE Depending on the UPS load the 3 minute warning may occur before the batteries reach 25 capacity the front panel immediately displays the 3 minute warning For UPS and Extended Battery Module EBM runtimes see Table 10 on page 62 These warnings are approximate and the actual time to shutdown may vary significantly Once these warnings are indicated immediately complete and save your work to prevent data loss and similar difficulties When utility power is restored after the UPS shuts down the UPS automatically restarts EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 39 www powerware com OPERATION 40 Bypass Mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available however the utility power continues to be passively filtered by the UPS The indicator
28. 5 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative NOTE Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 15 www powerware com INSTALLATION Connecting the UPS Internal Battery To ensure proper battery operation before installing the UPS 1 Verify that the UPS is off and unplugged 2 Remove the UPS front cover by pulling on both ends see Figure 2 Figure 2 Removing the UPS Front Cover 3 Connect the internal battery connector see Figure 3 Figure 3 Connecting the Internal Battery Connector 4 Replace the UPS front cover see Figure 4 Figure 4 Replacing the UPS Front Cover 5 Continue to the following section UPS Setup UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet If you are installing the UPS in a rack continue to the following section Rack Mount Setup otherwise continue to Tower Setup on page 18 16 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION Rack Mount Setup The UPS can be installed
29. AL CONTEMI INSTRU OES DE SEGURANCA IMPORTANTES CUIDADO executados SOMENTE POR PESSOAL DA ASSIST NCIA T CNICA AUTORIZADO N o h A A UPS cont m VOLTAGEM MORTAL Todos os reparos e assist ncia t cnica devem ser nenhuma PE A QUE POSSA SER REPARADA PELO USUARIO dentro da UPS ADVERTENCIA Esta UPS cont m sua pr pria fonte de energia baterias Os recept culos de sa da podem conter voltagem ativa quando a UPS n o se encontra conectada a uma fonte de alimentac o de corrente alternada N o remova ou desconecte o cabo de entrada quando a UPS estiver ligada Isto remover o aterramento de seguran a da UPS e do equipamento conectado Para reduzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condut veis A temperatura ambiente n o deve exceder 40 C N o opere pr ximo a gua ou em umidade excessiva m x 95 Para estar de acordo com os padr es internacionais e os regulamentos de fia o o equipamento total conectado sa da desta UPS n o deve ter uma corrente de fuga terra maior que 1 5 miliamp res Para sistemas UPS com sa das conectadas a prote o de sobrecarga para circuitos de sa da de corrente alternada deve ser fornecida por outros Para sistemas UPS com sa das conectadas interruptores de desconex o devidamente qualificados para circuitos de sa da de corrente alternada devem ser fornec
30. ATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 65 www powerware com TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative United States 1 800 356 5737 or 1 919 870 3149 Canada 1 800 461 9166 ext 260 All other countries Call your local service representative Please have the following information ready when you call the Help Desk e Model number e Serial number e Version number if available e Date of failure or problem e Symptoms of failure or problem e Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units NOTE For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you 66 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 10 Warranty Two Year Limited W
31. E PARTS inside the UPS This UPS contains its own energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply For 220 240V models the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the voltage to the output receptacles is OV With line to line input wiring the voltage to the output receptacles is 110 120V measured from line to ground or line to neutral depending on the UPS wiring Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum To comply with international standards and wiring regulations the total equipment connected to the output of this UPS must not have an earth leakage current greater than 1 5 milliamperes For UPS models with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others For UPS models with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others EATON Powerware 9125 Two in
32. KOHTPOJIHPYEMbIMH TeMIIepaTypoit H BJIAXXHOCTbIO B KOTOPOM OTCYTCTBYIOT HPOBOJAIHE 3aTPA3HAIOIHE BELIECTBA Temnepatypa OKpy gt xKalOIIIero B03yryxa HE HOJDKHa npesbinrarb 40 C He aKcnnyarupy re YCTPO CTBO OKO IO BO IbI WIM B MECTAX C IIOBBIIIIeHHOII BJIAKHOCTBbIO Marc 95 INA o6ecneuerna CO6MOMEHUA rpe6oBauuit MEXHYHAPONHBIX CTAHHAPTOB H TPe60BaHHI K PA3BOJKE SIEKTPHIECKAX IIEITEH cyMMapHas BeJIHuuHa TOKA YTEUKH Ha 3 MJIIO BCETO 060Py1OBAHUA IIOJIKJIIOHeHHOTO K BBIXOIY UBIL He nom Ha npesbinrare 1 5 MUJUINAMITEPa OCTOPOXHO AKKYMY IATOPHI MOTYT BbI3BaTb OIIaCHOCTb MOPAKEHMA 3 IeKTDHuecKHM TOKOM HJIH OXKOTA OT TOKA KOPOTKOTO 3AMBIKAHUA CoomonaniTe COOTBETCTBYIOIIIHE MEPBI HPEHOCTOPOXKHOCTH Heo xonuwMo co monarb HPaBHJIA YTMJIM3ALMM AKKYMYAATOPOB O6parHrecb K MECTHBIM HOPMATMBHBIM AKTAM 3a MHPOPManne o TPe60BaHHSX K yTHJIM3a0 HH Hukorna He poca Te aKKYMYJIATOPBI B OTOHb AKKYMYJIATOPbI MOTYT B3OPBATbCA MON BO3 CTBMEM OTHA 12 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES Este SIE contiene VOLTAJES MORTALES Todas las reparaciones y el servicio t cnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TECNICO AUTORIZADO No hay NINGUNA PARTE QUE EL USUARIO PUEDA
33. Modbuse Card allows you to continuously and reliably monitor the UPSs in your Building Management System BMS e Multi Server Card has six serial communication ports that can communicate simultaneously with other computers using Powerware LanSafee Power Management Software provided on the Software Suite CD e USB Card connects to a USB port on your computer EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 45 www powerware com ADDITIONAL UPS FEATURES X Slot Communication Bay ome Single Port Card shown o po Mh ConnectUPS X Web SNMP Card bo i cw i 10 Relay Interface Card mp O i Bet Eo Modbus Card T FARER Be Zale Zal o 19 o Ge Ne Ee o Multi Server Card USB Card Figure 34 Optional X Slot Cards Single Port Card The Powerware 9125 is factory installed with a Single Port Card enabling connection to a PC for power management control or to the Powerware Expansion Chassis for multiple communication options To establish communication between the UPS and a computer connect your computer to the UPS communication port using the supplied communication cable When the communication cable is installed power management software can exchange data with the UPS The software
34. Power off Installation 31 UPS Rear Panels emmma nende dt bte pete Een SV meto tant mh etu Mos Qa ta 33 AA de own asl Nae ne DE RENEE eR 35 Torning the IPSI nc a e o aet oe Le ad NA e P DE Selb ave ahi t 35 Starting the UPS On Batte sas angen EA A ge mon an RIP TUER paqaq qana AE 35 Turning the UPS OM i ra eeeh 36 Initiating the Selfl esti orte O Sn osat A ia 36 Operating Modes te arten Pe RR Pe abade naa LS da GEA me cre E 37 Normal Mode ter Stettin a 38 Battery Modes rte ett tete Li Gk dan PE A Step eom Ba tot lk nen 39 Bypass Mode zc ette eed m eec agii es dte us 40 Standby Modesty mao Lasso ta See s e M sS ae ceu 40 5 Configuration ss zoen ao ber en a QR Ka o S EGER A 41 6 Additional UPS Features 45 JCS Bb Es iena iaa mis Sara 45 SinglePort Cad en SR 46 Network Transient Protector a Fo AR De Ces 49 Load Segmen S oss A EDUC A E NIME 50 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D i www powerware com TABLE OF CONTENTS 1 10 UPS Maintenance 4 444 I oiseau 51 UPS and Battery Cale 3005 0006 Eee Rn Se ee ee SENG 51 Storing the UPS and Batteries eet s I SA t EE DOE TS y k 51 When to Replace Batteries s once co cent t d eel ben Ree died 52 Replacing Batteries faee Lande Sos se OEC i Meier prat 52 How to Replace UPS Internal Batteries
35. R THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT INCLUDING INDEMNITY IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE SHALL NOT EXCEED THOSE SET FORTH ABOVE Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Guaranty the End User must use the Product in a normal way follow the Product s operation and maintenance manual and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Company s obligations under this Guaranty are expressly conditioned upon receipt by Company of all payments due to it including interest charges if any During such time as Company has not received payment of any amount due to it for the Product in accordance with the contract terms under which the Product is sold Company shall have no obligation under this Guaranty COSTS NOT RELATED TO GUARANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Guaranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipment installation materials freight charges travel expenses or labor of Company representatives outside the terms of this Guaranty will b
36. R kunnen worden GEREPAREERD Deze UPS bevat zijn eigen energiebron batterijen De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten Verwijder de ingangsnoer niet of haal de ste ker van de ingangsnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur en vochtigheidreg geleidende verontreinigingen aanwezig zijn overschrijden Niet gebruiken in de buurt van 95 Om aan de internationa e normen en bedrad eling te worden ge nstalleerd waar geen De omgevingstemperatuur mag 40 C niet water of bij zeer hoge vochtigheid max ingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten geen aardlekstroom van meer dan 1 5 milliamp re hebben Voor UPS systemen met vast bedrade uitgan gen moet de overstroombeveiliging voor wisselstroom uitvoercircuit s door anderen worden geleverd Voor UPS systemen met vast bedrade uitgan gen moeten de juiste hoofdschakelaars voor wisselstroom uitvoercircuit s door anderen worden geleverd EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D m www powerware com SAFETY WARNINGS OPGELET e Batterijen kunnen gevaar voor elektrische schok of brandw
37. S 003 EN 50091 2 IEC 62040 2 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 61 www powerware com SPECIFICATIONS Table 9 Battery UPS Configuration 6 12V 9 Ah internal batteries EBM Configuration PW9125 72 EBM 12 12V 9 Ah 2 strings of 6 batteries in parallel Type Sealed maintenance free valve regulated lead acid Charging Internal battery approximately 3 hours to 90 usable capacity at nominal line voltage after full load discharge External battery no more than 20x discharge time to 90 usable capacity at nominal line voltage after full load discharge Monitoring Advanced monitoring for earlier failure detection and warning auto detection of additional EBMs Table 10 Battery Runtimes in Minutes at Full Half Load Model UPS Internal Batteries 1EBM 2 EBMs 3 EBMs 4 EBMs 2500 VA 1750W 7 16 28 57 48 90 68 150 88 200 3000 VA 2100W 5 13 25 55 38 72 54 120 70 160 NOTE Battery times are approximate and vary depending on the load configuration and battery charge 62 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 9 Troubleshooting This section explains e UPS alarms and conditions How to silence an alarm e Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 11 to determine and resolve the UPS alar
38. S en b r ikke betjenes n r vand eller h j fugtighed maksimalt 95 e overensstemmelse med internationale normer og bestemmelser for el installation m det udstyr der er forbundet til udgangen af denne UPS tilsammen ikke overskride en jordafdelingssp nding pa mere end 1 5 milliampere e For UPS systemer med hardledningsudgange skal overstramsbeskyttelse for vekslestrammens udgangskredslab forsynes af andre e For UPS systemer med h rdledningsudgange skal egnede nominelle afbryderkontakter for vekslestrammens udgangskredslab forsynes af andre 4 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com SAFETY WARNINGS ADVARSEL Batterier kan udggre en fare for elektrisk stad eller forbr ndinger for rsaget af hgj kortslutningssp nding De korrekte forholdsregler bgr overholdes Korrekt bortskaffelse af batterier er p kraevet Overhold gaeldende lokale regler for e bortskaffelsesprocedurer Skaf dig aldrig af med batterierne ved at br ben ild nde dem Batterierne kan eksplodere ved Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKE
39. TLE NON INFRINGEMENT AND FITNESS FOR A PARTICULAR PURPOSE CORRECTION OF NON CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY S SOLE LIABILITY AND END USER S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS WHETHER CLAIMS OF THE END USER ARE BASED IN CONTRACT IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE LIMITATION OF LIABILITY The remedies of the End User set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder In no event shall Company be liable in contract in tort including negligence or strict liability or otherwise for damage to property or equipment other than the Products including loss of profits or revenue loss of use of Products loss of data cost of capital claims of customers of the End User or any special indirect incidental or consequential damages whatsoever The total cumulative liability of Company hereunder whether the claims are based in contract including indemnity in tort including negligence or strict liability or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must use the Product in a normal way follow the
40. UPS is in Standby mode with the equipment offline If the amp or 2 indicator flashes see page 65 LAND GIGA v 8 0 e OIQIQIO O Battery Service j Site Wiring Fault Indicator Indicator Figure 19 Fault Indicators Press the On button The indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment To change the factory set defaults see Configuration on page 41 NOTE The batteries charge to 90 capacity in approximately 3 hours However it is recommended that the batteries charge for 24 hours after installation or long term storage 26 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION Hardwired UPS Installation installation Risk of electrical shock Only qualified service personnel such as a licensed electrician shall perform the electrical CAUTION For UPS models with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others For UPS models with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others NOTE Do not make unauthorized changes to the UPS or accessories otherwise damage may occur to your equipment and void your warranty The Powerware 9125 hardwired models require
41. a destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Powerware 9125 you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Figure 1 shows the Powerware 9125 UPS with an optional Extended Battery Module EBM 000000 amp 0 0 NN AAN mme Figure 1 The Powerware 9125 UPS with Optional EBM ity the Powerware 9125 s Providing outstanding performance and reliab unique benefits include the following Online UPS design with pure sine wave output The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery e 2U rack height that conserves valuable rack space Two in one form factor for using the UPS in a rack mount configuration or as a standalone cabinet e ABMe technology that uses advanced battery management to increase battery service life optimize recharge time and provide a warning before the end of useful battery life Hours of extended runtime with up to four EBMs EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 1 www powerware com INTRODUCTION Start on battery capability for powering up the UPS even i
42. ant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof Company shall not be responsible for any charges for testing checking removal or installation of Warranted Items COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY IF PERMITTED BY THE APPLICABLE MANUFACTURER COMPANY SHALL PASS THROUGH SUCH MANUFACTURER S WARRANTIES TO END USER COMPANY DOES NOT WARRANT SOFTWARE INCLUDING SOFTWARE EMBEDDED IN PRODUCTS THAT IS NOT CREATED BY COMPANY WITHOUT LIMITING THE FOREGOING COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE SUCH AS LINUX THAT WAS CREATED USING AN OPEN SOURCE MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY TITLE NON INFRINGEMENT AND FITNESS FOR A PARTICULAR PURPOSE CORRECTION OF NON CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY S SOLE LIABILITY AND END USER S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS WHETHER CLAIMS OF THE END USER ARE BASED IN CONTRACT IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE LIMITATION OF LIABILITY The remedies of the End User set forth herein are exclu
43. arranty US and Canada Powerware UPS Models 3105 3110 3115 9104 9120 9125 and FERRUPS up to 3 1 kVA WARRANTOR The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation a Delaware Corporation company Company LIMITED WARRANTY This limited warranty this Warranty applies only to the original End User the End User of any Powerware 3105 3110 3115 9104 9120 9125 and FERRUPS up to 3 1 kVA Products individually and collectively the Product purchased on or after June 1 2004 and cannot be transferred This Warranty applies even in the event that the Product is initially sold by Company for resale to an End User LIMITED WARRANTY PERIOD The period covered by this Warranty for Product installed and currently located in the fifty 50 United States the District of Columbia and Canada is twenty four 24 months from the date of purchase WHAT THIS LIMITED WARRANTY COVERS The warrantor warrants that the Product and battery individually and collectively the Warranted Items are free from defects in material and workmanship If in the opinion of Company a Warranted Item is defective and the defect is within the terms of this Warranty Company s sole obligation will be to repair or replace such defective Warranted Item including by providing service parts and labor as applicable at the option of Company PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS The War
44. ct installation of Product d repair or alteration of Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent e improper testing operation maintenance adjustment or modification of any kind to the Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Guaranty is not valid a unless the End User returns to Company the Warranty Registration Card within thirty 30 days of purchase or b if the Product s serial numbers have been removed or are illegible Company shall not be responsible for any charges for testing checking removal or installation of any items LIMITATION OF LIABILITY THE REMEDIES OF THE END USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER EXCEPT AS OTHERWISE PROVIDED FOR IN THIS GUARANTY IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS INCLUDING LOSS OF PROFITS OR REVENUE LOSS OF USE OF PRODUCTS LOSS OF DATA COST OF CAPITAL CLAIMS OF CUSTOMERS OF THE END USER OR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES WHATSOEVE
45. der this Warranty Also during such time the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts 68 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide e 164201374 Rev D www powerware com WARRANTY COSTS NOT RELATED TO WARRANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Warranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipment installation materials freight charges travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End User OBTAINING WARRANTY SERVICE In the USA call the Customer Reliability Center 7x24 at 800 356 5737 Outside of the USA call your local Powerware product sales or service representative or call the Customer Reliability Center in the USA at 919 870 3149 For comments or questions about this Warranty write to the Customer Quality Representative 3301 Spring Forest Road Raleigh North Carolina 27616 USA Ten Year Pro Rated Limited Warranty US and Canada Powerware UPS Models 5115 5125 5140 9104 9120 9125 9155 9170 and FERRUPS WARRANTOR The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation a Delaware Corporation company Compa
46. dwired Rear Panel 34 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D Terminal Block Communication Port O s Do gele OO I D Q D L 9 Battery Connecto Figure 28 2500 3000 VA 208 240V Hardwired Rear Panel www powerware com e ok X Slot Communication Bay eig pes Communication Bay Chapter 4 Operation This section describes e Turning the UPS on and off e Starting the UPS on battery Initiating the self test e Operating modes Turning the UPS On After the UPS is connected to utility power it conducts a self test and enters Standby mode To turn on the UPS press the On button on the front panel The indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS Starting the UPS on Battery To turn on the UPS without using utility power press and hold the On button for at least four seconds The UPS starts up in Battery mode and supplies battery power to your eguipment When the UPS starts on battery it does not conduct a self test to conserve battery power EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide
47. e borne by the End User TO MAKE A CLAIM In the USA call the Customer Reliability Center 7x24 at 800 356 5737 Outside of the USA contact your local Powerware product sales or service representative or call the Customer Reliability Center in the USA at 919 870 3149 For comments or questions about this Load Protection Guaranty write to the Customer Quality Representative 3301 Spring Forest Road Raleigh North Carolina 27616 USA 72 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com
48. els Beco Do amp EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 7 UPS Maintenance This section explains how to e Care for the UPS and batteries Replace the batteries e Test new batteries e Recycle used batteries or UPS UPS and Battery Care O For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the UPS at an ambient temperature of 25 C 77 F NOTE If the UPS requires any type of transportation verify that the UPS is unplugged and turned off and then disconnect the UPS internal battery connector using the steps in Connecting the UPS Internal Battery on page 16 in reverse order NOTE The batteries in the UPS are rated for a 3 5 year service life The length of service life varies depending on the freguency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 5 years to keep units running at peak efficiency Storing the UPS and Batteries If you store the UPS for a long period recharge the batteries every 12 months by plugaing the UPS into a power outle
49. ennuksella kuormana olevien laitteiden ylivirtasuojaus ja erotuskytkimet tulee toteuttaa kuormapiireissa e Akusto saattaa aiheuttaa s hk iskun tai sytty tuleen jos akusto kytket n oikosulkuun Noudata asianmukaisia ohjeita e Akusto t ytyy h vitt s d sten mukaisella tavalla Noudata paikallisia m r yksi e l koskaan heit akkuja tuleen Ne voivat r j ht 6 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D Www powerware com Consignes de s curit CONSIGNES SAFETY WARNINGS DE S CURIT IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL IMPORTANT CONTIENT DES CONSIGNES DE S CURIT ES A Cet onduleur contient des TENSIONS MORTELLES Toute op ration d entretien et de r paration doit tre EXCLUSIVEMENT CONFI E A UN PERSONNEL QUALIFI AGR AUCUNE PI CE R PARABLE PAR L UTILISATEUR ne se trouve dans l onduleur AVERTISSEMENT e Cet onduleur renferme sa propre source d nergie batteries Les prises de sortie peuvent tre sous tension m me lorsque l onduleur n est pas branch sur le secteur e Ne pas retirer le cordon d alimentation lorsque l onduleur est sous tension sous peine de supprimer la m ise la terre de l onduleur et du mat riel connect Pour r duire les risques d incendie et de d charge lectrique installer l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la
50. ervice Life remaining at the time of return of the Product to Company In calculating the available credit the remaining portion of the Ten Year Service Life will be rounded up or down to the nearest whole year The End User will assume responsibility to pay the balance of the list price and Company reserves the right to require payment prior to delivery of the repaired or replacement equipment For the avoidance of doubt Company s responsibilities under this Warranty are as follows Years 1 2 Product repaired or replaced pursuant to terms of Limited Warranty Years 3 10 Unit Credit Current List Price X Years of Unexpired Life 10 Years of Warranted Life EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 69 www powerware com WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER This Warranty does not cover any defects or damages caused by a failure to properly store the Product before installation including the charge of batteries no later than the date indicated on the packaging b shipping and delivery of the Product if shipping is FOB Factory c neglect accident abuse misuse misapplication or incorrect installation d repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent e improper testing operation maintenance adjustment or modification of any kind not authorized in writing by Company pe
51. erware com INSTALLATION 6 Plug the EBM cable into the UPS battery connector see Figure 17 7 Attach the fixed cover plate supplied in the accessory kit to the EBM cable as shown in Figure 17 UPS Battery Connector Ej zx MODO H UPS EBM Cable EBM Cable with Fixed Cover Plate p q EBM e EBM Battery Connector with D EBM Cover e E Fixed Cover Plate Figure 17 EBM Installation for E EH UPS Models Only 8 If additional EBMs are to be installed remove the EBM battery connector cover Remove the cover from the EBM cable of the second cabinet and plug the EBM cable into the battery connector on the first EBM Attach the fixed cover plate to the EBM cable Repeat for each additional EBM Up to four EBMs may be connected to the UPS 9 Continue to the following section Plug Receptacle UPS Installation or Hardwired UPS Installation on page 27 24 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D Www powerware com INSTALLATION Plug Receptacle UPS Installation NOTE Do not make unauthorized changes to the UPS or accessories otherwise damage may occur to your equipment and void your warranty
52. ery connectors as shown in Figure 45 For E EH UPS models remove the cover from the EBM cable and plug the EBM cable into the UPS Attach the fixed cover plate to the EBM cable For additional EBMs plug the EBM cable into the battery connector on the adjacent EBM For E EH UPS models remove the EBM battery connector cover Remove the cover from the EBM cable of the second cabinet and plug the EBM cable into the battery connector on the first EBM Attach the fixed cover plate to the EBM cable EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 55 www powerware com UPS MAINTENANCE Joining Brackets Rea EBM Battery Connectors e e SOE UPS Battery Connector EBM Cables I Al 5 8 D o o eje olo o Figure 45 EBM Connections 120V UPS Model Shown Testing New Batteries Press and hold the button for three seconds to initiate a self test After the five second test is complete the indicator should turn off it may take a few seconds to turn off If the 2 indicator stays on check the battery connections Call your service representative if the problem persists EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D Www powerware com 56 UPS MAINTENANCE Recycling the Used Battery or UPS Contact your local
53. f utility power is not available Hot swappable batteries that simplify maintenance by allowing you to replace batteries safely without powering down the critical load Emergency shutdown control through the remote emergency power off REPO port Optional X Slot cards with enhanced communication capabilities for increased power protection and control Network transient protector that guards your network communications equipment from surges Low voltage models can also protect modems fax machines or other telecommunications equipment Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring Sequential shutdown and load management through separate receptacle groups called load segments Flash memory provides easy upgrades or reconfiguration capability without requiring a service call Backed by worldwide agency approvals EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference This UPS contains LETHAL VOLTAGES Al repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABL
54. gata con l uscita del gruppo statico di continuit non deve avere una corrente di dispersione di terra superiore a 1 5 milliampere e Nei sistemi UPS provvisti di uscite cablate i dispositivi di protezione da sovracorrente per il i circuito i a corrente alternata in uscita devono essere forniti da terzi e Nei sistemi UPS prowvisti di uscite cablate i sezionatori di corrente nominale adeguata per il i circuito i a corrente alternata in uscita devono essere forniti da terzi EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com SAFETY WARNINGS ATTENZIONE e Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da alta corrente dovuta a corto circuito Osservare le apposite istruzioni e Le batterie devono essere smaltite in modo corretto Per i requisiti di smaltimento fare riferimento alle disposizioni locali Non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle fiamme Viktig Sikkerhetsinformasion Denne UPS en inneholder LIVSFARLIGE SPENNINGER All reparasjon og service m kun utfgres av AUTORISERT SERVICEPERSONALE BRUKERE KAN IKKE UTFORE SERVICE PA NOEN AV DELENE i UPS en e Denne UPS en har en egen energikilde batterier Stikkontaktene kan v re str mf rende selv om UPS en ikke er tilsluttet en vekselstramforsyning e Strgmforsyningskabelen m ikke fjernes eller trekkes ut nar UPS en er p
55. guration mode The LEDs flash briefly and then display the enabled options Press the On button to scroll through the options Each time you press the button the UPS beeps The LED for the selected option indicates the current setting flashing represents disabled options see Figure 33 and Table 2 Scrolling past the last LED returns to the first configuration option If you press the On button and nothing happens the UPS is still in Operation mode Repeat Step 1 to enter Configuration mode and then perform Step 2 Press the 4 button for approximately one second to select the Voltage option or to toggle the Site Wiring Fault Alarm or AC Input Failure Alarm on or off O NOTE The UPS exits Configuration mode automatically after two minutes of inactivity 4 Press and hold the On button and the button simultaneously to exit Configuration mode at any time EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 41 www powerware com CONFIGURATION O O O O O16 Configuration Mode Indicators e 0 0 Press the Test Alarm Reset 1 Press and hold the On and Test Alarm Reset q 7 button to select an option buttons simultaneously to toggle between Configuration and Operation modes Test Alarm On Button Reset Button o Press the On button to scroll to the next option Figure 33 Using Configuration Mode 42 EATON Powerware 9125 Two in One UPS 2500
56. he new battery trays into the UPS The battery trays are keyed to prevent improper connection The battery tray with the battery cable goes in the bay to the right 7 Reinstall the battery retaining bracket removed in Step 4 8 Reconnect the battery cable Secure the cable to the battery retaining bracket with a tie wrap 9 Snap the LED panel into place 10 Replace the UPS front cover 54 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com O UPS MAINTENANCE How to Replace Extended Battery Modules CAUTION The Extended Battery Module EBM is heavy see page 61 A minimum of two people are required to lift the EBM when it is replaced To replace the Extended Battery Modules EBMs Unplug the EBM cable from the UPS NOTE For 230V models remove the fixed cover plate and then unplug the EBM cable from the UPS If additional EBMs are installed unplug the EBM cable from the battery connector on each EBM If the EBM is in a tower configuration remove the joining brackets If the EBM has pedestals installed remove the pedestals and retain If the EBM is in a rack install the mounting handles and brackets on the new EBM Replace the EBM See Recycling the Used Battery or UPS on page 57 for proper disposal Reinstall the pedestals if removed in Step 3 Reinstall the joining brackets if removed in Step 2 Plug the EBM cable s into the batt
57. idos por outros As baterias podem apresentar o risco de choque el trico ou queimaduras provenientes de alta corrente de curto circuito Observe as instru es adequadas Siga as instru es apropriadas ao desfazer se das baterias Consulte os c digos do local para maiores informa es sobre os regulamentos de descarte de produtos Nunca jogue as baterias no fogo porque h risco de explos o EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 11 www powerware com SAFETY WARNINGS MpeaynpexaeHua no mepam 6esonacHocTM BAXHbIE YKA3AHMA MO MEPAM BE3ONACHOCTU COXPAHMTE ITU YKA3AHUA DAHHOE PYKOBOLCTBO COAEPXUT BAXHbIE YKA3AHMA NO MEPAM BE3ONACHOCTN B gannom MBII umeiotca CMEPTEJIBHO OIIACHPBIE HATIPSDKEHMA Bce pa6orBi rro peMOHTY H o6cryxauraHulo HOJDKHBI BbIHOJIHATBCA TOJIBKO YIOJIHOMOHEHHPIM OBC IV7KHBAIOTIIHM IIEPCOHAJIOM Buyrpu MBII Her y3108 OBCJIYXMBAEMDIX IIOJIBSOBATEJIEM NPEAYNPEXAEHVE annem HBII conepxur co6crBeHHble ucrounuku IHEprun AKKYMYNATOPEI Ha BbIXO IHbIX PO3ETKAX MOXKET HMETbCS HATIPSDKEHHe zaxe korna MbII He NOAKMIOYEH K cera HEPEMEHHOTO TOKA He oTcoeIMHAliTe cereBoli IIHYp H He H3BJIEKAKTE ero BH IKY H3 poserku ripu BK1O4eHHOM MBII IIpu stom 3anmuTHoe 333eMJICHHe OTKJIOYAETCA or MBII n or o6opynosauus HONKJIOYEHHOTO K HIIb la CHHXKEHHA OHACHOCTH HOXKAPA WIM HOPAXEHUA 91EKTPHIECKAM TOKOM ycTaHaB1nBa Te HBII B sakpbITOM HOMELIEHUM c
58. ill pay its designated carrier for all shipping charges for return of defective equipment and replacement of Warranted Items Any returned Warranted Item or parts that are replaced may be new or reconditioned All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 67 www powerware com WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER This Warranty does not cover any defects or damages caused by a failure to properly store the Product before installation including the charge of batteries no later than the date indicated on the packaging b shipping and delivery of the Product if shipping is FOB Factory c neglect accident abuse misuse misapplication or incorrect installation d repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent e improper testing operation maintenance adjustment or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Warranty is not valid if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursu
59. illuminates The UPS transfers to Bypass mode when The UPS has an overtemperature condition The UPS has an overload condition of 101 to 150 for 30 seconds The UPS detects a fault in the battery or UPS electronics Standby Mode When the UPS is turned off and remains connected to utility power the UPS is in Standby mode The indicator flashes and the bar graph indicators are off indicating that power is not available to your equipment The battery recharges when necessary NOTE For 220 240V models the output receptacles may remain electrically live up to 110 120V Unplug the UPS to ensure power is not available to the output receptacles EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 5 Configuration When the UPS is in Configuration mode the bar graph indicators represent the configuration options Use the control buttons On button and button to modify the UPS configuration Figure 33 shows the LEDs and Table 2 explains the corresponding options NOTE The UPS can be configured while in Battery mode If the UPS transfers to battery power while in Configuration mode the UPS remains in Configuration mode and indicates Battery mode on the front panel after exiting Configuration mode To reconfigure the UPS default settings 1 Press and hold the On button and the button simultaneously for one beep The UPS transfers to Confi
60. in 19 inch racks and needs only 2U of valuable rack space CAUTION NOTE Mounting rails are required for each UPS and EBM cabinet If rails are not already The UPS and EBM are heavy see page 61 A minimum of two people are required to lift the cabinets into the rack installed in your rack contact your local distributor to order rail kits To install the UPS and optional EBMs in a rack 1 Place the UPS on a flat stable surface with the front of the UPS facing toward you 2 Attach the supplied mounting handles to the mounting brackets and secure with the supplied screws see Figure 5 3 Align the mounting brackets with the screw holes on the side of the UPS and secure with the supplied screws see Figure 5 4 If installing optional EBMs repeat Steps 1 through 3 for each cabinet Mounting Bracket Mounting Handle Figure 5 Installing the Mounting Handles and Brackets EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 17 www powerware com INSTALLATION o NOTE The EBMs must be installed below the UPS as shown in Figure 6 5 Slide the UPS and any optional EBMs into the rack 6 Secure the cabinets to the rack according to the rail kit instructions i pem Il Optional On EBMs 2 Lo UUUUUU J 7
61. in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 96 betreiben Uminternationale Normen und Verdrahtungsvorschriften zu erf llen d rfen die an den Ausgang dieser USV angeschlossenen Ger te zusammen einen Erdableitstrom von insgesamt 1 5 Milliampere nicht berschreiten e F r UPS Systeme mit festverdrahteten Eing ngen mu der berstromschutz f r die Ausgangswechselstromkreise anderweitig bereitgestellt werden e F r UPS Systeme mit festverdrahteten Ausg ngen m ssen Trennschalter f r die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden 8 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com SAFETY WARNINGS VORSICHT e Batterien k nnen aufgrund des hohen KurzschluRstroms Elektroschocks oder Verbrennungen verursachen Die entsprechenden Vorsichtsma nahmen sind unbedingt zu beachten Wartungsarbeiten sollten nur von qualifiziertem Fachpersonal welches sich mit dieser Art von Batterien und den entsprechenden Sicherheitsvorkehrungen auskennt durchgef hrt werden Bitte halten Sie unqualifiziertes Personal von den Batterien fern e Die Batterien m ssen ordnungsgem entsorgt werden Hierbei sind die rtlichen Bestimmungen zu beachten Batterien niemals verbrennen da sie explodieren k n
62. ingle Port Card 2 Move the J3 jumper to the AS 400 position to enable the On Bypass relay as shown in Figure 37 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 47 www powerware com ADDITIONAL UPS FEATURES On Bypass Disabled On Bypass Enabled po NO AS 40 On Bypass Relay Jumper i H 43 Figure 37 On Bypass Relay Jumper 3 To prevent electrostatic discharge ESD place one hand on a metal surface such as the UPS rear panel Align the Single Port Card with the slot guides and slide the card into the slot until it is firmly seated 4 Secure the Single Port Card with the screws removed in Step 1 48 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com ADDITIONAL UPS FEATURES Network Transient Protector The network transient protector shown in Figure 38 is located on the rear panel and has jacks labeled IN and OUT This feature accommodates a single RJ 45 10BaseT network connector Low voltage models can also accommodate an RJ 11 telephone connector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange environments NOTE DO NOT connect any telephone or fax modem equipment to the 230V
63. ks and X Slot and ConnectUPS are trademarks of Eaton Power Quality Corporation Modbus is a registered trademark of Modicon AS 400 is a registered trademark of International Business Machines Corp OCopyright 2004 2005 Eaton Corporation Raleigh NC USA All rights reserved No part of this document may be reproduced in any way without the express written approval of Eaton Corporation Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives e Harmonized Standards EN 50091 1 1 and EN 50091 2 IEC 60950 Third Edition EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Power Quality Oy Koskelontie 13 FIN 02920 Espoo Finland Phone 358 9 452 661 Fax 358 9 452 665 68 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Indicates that a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual
64. l standard och installationsf reskrifter f r inte den totala utrustning som anslutits till uttagen p denna UPS enhet ha l cksstr m som verstiger 1 5 milliampere e verstr msskydd f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r UPS system med fasta utg ngar e Bortkopplingsswitchar med passande dimensionering f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r UPS system med fasta utg ngar VIKTIGT e Batterierna kan ge elektriska st tar eller br nnskador fr n h g kortslutningsstr m F lj till mpliga anvisningar e Batterierna m ste avyttras enligt anvisningarna lokal lagstiftning e Anv nda batterier f r aldrig br nnas upp De kan explodera 14 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 3 Installation This section explains Equipment inspection UPS internal battery connection UPS setup and installation Extended Battery Module EBM installation Remote emergency power off REPO installation UPS rear panels Inspecting the Equipment If any equipment has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 1
65. ms and O Battery Service Test Alarm Reset Button conditions NOTE Some alarms such as the Overtemperature and Overload alarms must be cleared by shutting down and restarting the UPS see page 65 for more information Site Wiring Fault Self Test i Li oiy Lao 6 D N S Figure 46 Alarm Indicators Silencing an Audible Alarm Overtemperature Overload Indicator Legend o Unlit o Lit M o Flashing ZIN Before silencing an alarm check the alarm condition and perform the applicable action to resolve the condition see Table 11 To silence the alarm for an existing fault press the button If UPS status changes the alarm beeps overriding the previous alarm silencing EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 63 www powerware com TROUBLESHOOTING Table 11 Troubleshooting Guide Alarm or Condition Possible Cause Action The indicator is not on the UPS does not start The power cord is not connected correctly Check the power cord connections The wall outlet is faulty Have a qualified electrician test and repair the outlet The main utility breaker is off Verify that the main utility breaker is on The remote emergency power off REPO switch is active Reset the REPO switch and restart the UPS The REPO connector is missing Verify that
66. nen Avvisi di sicurezza IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA PERICOLO A La TENSIONE contenuta in questo gruppo statico di continuit LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO All interno del gruppo statico di continuit NON vi sono PARTI RIPARABILI DALL UTENTE AVVERTENZA Questo gruppo statico di continuit contiene una fonte di energia autonoma le batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuit non collegato con una fonte di alimentazione a corrente alternata e Non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Perridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo di agenti contaminanti conduttivi La temperatura ambiente non deve superare i 40 C Non utilizzare l unit in prossimit di acqua o in presenza di umidit eccessiva 8596 max e Per conformit con gli standard internazionali e con le norme in merito al cablaggio tutta l apparecchiatura colle
67. ny LIMITED WARRANTY This pro rated limited warranty this Warranty applies only to the original End User the End User of any Powerware 5115 5125 5140 9104 9120 9125 9155 9170 and FERRUPS Products individually and collectively the Product and cannot be transferred This Warranty applies even in the event that the Product is initially sold by Company for resale to an End User WHAT THIS WARRANTY COVERS In addition to the standard Two Year Limited Warranty covering the applicable Product the warrantor warrants that the Product will have a service life defined below of ten years from the date of purchase the Ten Year Service Life when used in accordance with the storage handling installation operation and maintenance procedures prescribed in the Product s user s guide Service life means the Product s ability to deliver at least 80 of its original rated backup time If Company finds in its sole discretion that any Product has not provided the Ten Year Service Life Company will as its sole obligation and the End User s sole remedy for Company s breach of this warranty repair or replace the Product at its option F O B Company s factory for a charge payable by the End User to Company pro rated on the following basis The End User will be allowed a credit against Company s list price of equivalent equipment at the time of return of the Product to Company in proportion to the percentage of Ten Year S
68. off disconnect switch is required by local codes see Remote Emergency Power off Installation on page 31 to install the REPO switch before powering on the UPS EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 29 www powerware com INSTALLATION 10 11 Switch the main utility breaker on All front panel indicators flash briefly and the UPS conducts a self test When the self test is complete the indicator flashes indicating the UPS is in Standby mode with the equipment offline If the amp or amp indicator flashes see page 65 get gue JE v GO QIQICIO 0 Battery Service j Site Wiring Fault Indicator Indicator Figure 23 Fault Indicators Press the On button The indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment To change the factory set defaults see Configuration on page 41 NOTE The batteries charge to 90 capacity in approximately 3 hours However it is 30 1 recommended that the batteries charge for 24 hours after installation or long term storage EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com INSTALLATION Remote Emergency Power off Installation gt P The Powerware 9125 includes a REPO port that allows power to be switched off at the
69. onden veroorzaken als gevolg van un hoge kortsluitstroom Volg de desbetreffende aanwijzingen op e De batterijen moeten op de juiste wijze worden opgeruimd Raadpleeg hiervoor uw plaatselijke voorschriften e Nooit batterijen in het vuur gooien De batterijen kunnen ontploffen Tarkeita Turvaohjeita T RKEIT TURVAOHJEITA SUOMI S ILYT N M OHJEET N T M OPAS SIS LT T RKEIT TURVAOHJEITA VAARA T m UPS sis lt HENGENVAARALLISIA J NNITTEIT Kaikki korjaukset ja huollot on j tett v VAIN VALTUUTETUN HUOLTOHENKIL N TOIMEKSI UPS ei sis ll MIT N K YTT J N HUOLLETTAVIA OSIA VAROITUS e T m UPS sis lt oman energial hteen akuston Ulostuloliittimiss voi olla j nnite kun UPS ei ole liitettyn verkkoj nnitteeseen e l poista tai irrota sis ntulojohtoa kun UPS on kytkettyn T m poistaa turvamaadoituksen UPS laitteesta ja siihen liitetyst laitteistosta e V hent ksesi tulipalon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell vett ja v lt kosteita tiloja 95 maksimi e Kansainv liset normit ja johdotusm r ykset vaativat ett kaikkien t m n UPS laitteen ulostulokytkent jen yhteinen maavuotovirta ei ylit 1 5 milliampeeria mA e UPS j rjestelmiss kiintealla as
70. or call the Customer Reliability Center in the USA at 919 870 3149 Company will not accept any Product for return credit or exchange unless expressly authorized by Company in writing and delivered FOB Company factory For comments or questions about this Warranty write to the Customer Quality Representative 3301 Spring Forest Road Raleigh North Carolina 27616 USA Load Protection Guarantee US and Canada Powerware UPS Models 3105 3110 3115 5110 5115 5125 9120 9125 9150 9155 9170 and FERRUPS GUARANTOR The Guarantor for the load protection guaranty set forth herein is Eaton Power Quality Corporation a Delaware Corporation company Company LIMITED GUARANTY This load protection guaranty this Guaranty applies only to the original End User the End User of any Powerware 3105 3110 3115 5110 5115 5125 9120 9125 9150 9155 9170 and FERRUPS Products individually and collectively the Product and cannot be transferred This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End User WHAT THIS GUARANTY COVERS For the lifetime of the Product Guarantor promises to repair or replace at Guarantor s option the equipment valued up to the limits shown below that is damaged by an AC power line surge spike or other transient when properly connected to Guarantor s uninterruptible power system UPS Reimbursement for or restoration of data loss excluded
71. put voltage 3 Regulation Battery Mode Voltage Waveform Nominal output voltage 3 Normal mode Sine wave lt 5 THD with full PFC and nonlinear load 60 www powerware com EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D SPECIFICATIONS Table 7 Weights and Dimensions UPS Extended Battery Module Dimensions 43 2 X 60 7 X 8 9 cm 43 2 X 60 7 X 8 9 cm WxDxH 17 0 x 23 9 x 3 5 2U 17 0 x 23 9 x 3 5 2U Weights 37 kg 81 5 Ib 42 5 kg 93 Ib Table 8 Environmental and Safety 120V Models 208V Models 230V Models Operating Temperature 0 C to 40 C 32 F to 104 F Optimal battery performance 25 C 77 F Storage Temperature 0 C to 25 C 32 F to 77 F Transit Temperature 25 C to 55 C 13 F to 131 F Relative Humidity 5 95 noncondensing Operating Altitude Up to 3 000 meters above sea level Transit Altitude Up to 10 000 meters above sea level Audible Noise Less than 45 dBA Normal mode typical load Less than 50 dBA Battery mode Surge Suppression IEEE C62 41 Category B IEEE C62 41 Category B IEC 61000 4 5 IEC 61000 4 5 Safety Conformance UL 1778 UL 497A UL 1778 UL 497A IEC 60950 1 EN 62040 1 1 CSA C22 2 No 107 1 107 2 NOM 019 SCFI NOM 019 SCFI IEC 60950 1 EN 62040 1 1 Agency Markings cULus NOM NYCE cULus NOM NYCE CE CE T V GS T V GS G models only EMC Class A FCC Part 15 ICES 003 FCC Part 15 ICE
72. ranted Item will be repaired or replaced at a Company site or such other location as determined by Company If the Warranted Item is to be replaced by Company and the End User supplies a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the End User within one 1 business day after Company receives notice of the warranty claim In such case the End User must return at Company s expense the defective Warranted Item to Company in the same packaging as the replacement Warranted Item received by the End User or as otherwise instructed by Company If Company does not receive the defective Warranted Item Company will either charge the End User s credit card or send the End User an invoice which the End User agrees to pay for the value of the replacement Product If the Warranted Item is to be replaced by Company but the End User is unwilling or unable to supply a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the End User within one 1 business day after Company receives the defective Product from the End User In any case Company will provide shipping instructions and w
73. recycling or hazardous waste center for information on proper disposal of the used battery or UPS e Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements e Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes lt may be toxic CAUTION Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your Pb local recycling reuse or hazardous waste center CAUTION Do not discard waste electrical or electronic eguipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 57 www powerware com UPS MAINTENANCE 58 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 8 Specifications This section provides the following specifications Model list Electrical input and output Weights and dimensions Environmental and safety e Battery Table 4 Model Specifications Power Levels Input Voltage Model Number Rated at Nominal Inputs Nominal Voltage Range PW9125 2500U 2500 VA 1750W 120V default
74. rsonnel or performed by an authorized Company Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Warranty is not valid a unless the End User returns to Company the Warranty Registration Card within thirty 30 days of purchase or b if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof Company shall not be responsible for any charges for testing checking removal or installation of Warranted Items COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY IF PERMITTED BY THE APPLICABLE MANUFACTURER COMPANY SHALL PASS THROUGH SUCH MANUFACTURER S WARRANTIES TO END USER COMPANY DOES NOT WARRANT SOFTWARE INCLUDING SOFTWARE EMBEDDED IN PRODUCTS THAT IS NOT CREATED BY COMPANY WITHOUT LIMITING THE FOREGOING COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE SUCH AS LINUX THAT WAS CREATED USING AN OPEN SOURCE MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY TI
75. sive and are the sole remedies for any failure of Company to comply with its obligations hereunder In no event shall Company be liable in contract in tort including negligence or strict liability or otherwise for damage to property or equipment other than the Products including loss of profits or revenue loss of use of Products loss of data cost of capital claims of customers of the End User or any special indirect incidental or consequential damages whatsoever The total cumulative liability of Company hereunder whether the claims are based in contract including indemnity in tort including negligence or strict liability or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must use the Product in a normal way follow the Product s user s guide and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Company s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it including interest charges if any During such time as Company has not received payment of any amount due to it for the Product in accordance with the contract terms under which the Product is sold Company shall have no obligation un
76. t The batteries charge to 90 capacity in approximately 3 hours However it is recommended that the batteries charge for 24 hours after long term storage Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 51 www powerware com UPS MAINTENANCE When to Replace Batteries When the indicator flashes the batteries may need replacing Conduct a self test by pressing and holding the 4 button for three seconds After the five second test is complete the 7 indicator should turn off it may take a few seconds to turn off If the 3 indicator continues flashing contact your service representative to order new batteries Replacing Batteries o NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode With the hot swappable battery feature UPS batteries can be replaced easily without turning the UPS off or disconnecting the load If you prefer to remove input power to change the batteries see Turning the UPS Off on page 36 Consider all warnings cautions and notes before replacing batteries Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools wi
77. teries press and hold the button for 3 seconds then check the A indicator If the amp indicator is still flashing see Replacing Batteries on page 52 The batteries are not connected correctly Check the battery connections Call your service representative ifthe problem persists amp Site Wiring Fault W 120V models only AIN Ground wire connection does not exist or the line and neutral wires are reversed in the wall outlet Have a gualified electrician correct the wiring To disable this alarm see Configuration Mode on page 41 ado w Overtemperature ZIN The UPS internal temperature is too high The UPS transfers to Bypass mode allowing the UPS to cool Turn off the UPS Unplug or remove utility power from the UPS Clear vents and remove any heat sources Ensure the airflow around the UPS is not restricted Wait at least 5 minutes and restart the UPS If the condition persists contact your service representative ES NZ e e o o o N SS Overload Continuous audible alarm Power requirements exceed UPS capacity 101 150 for 30 seconds or the load is defective Turn off the UPS Unplug or remove utility power from the UPS Remove some of the equipment from the UPS Wait at least 5 seconds until all indicators are off and restart the UPS Ifthe overload condition persists 101 110 for 2 minutes or 111 150 for 30 seconds the UPS automatically shuts down E
78. th insulated handles 3 Do not lay tools or metal parts on top of batteries e ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury 52 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com UPS MAINTENANCE How to Replace UPS Internal Batteries CAUTION Pull the battery out onto a flat stable surface The battery is unsupported when you pull it out of the UPS To replace the UPS internal batteries 1 Remove the UPS front cover by pulling on both ends see Figure 41 Figure 41 Removing the UPS Front Cover 2 Push down on and unsnap the LED panel see Figure 42 3 Disconnect the battery cable from the UPS and cut the battery cable wire tie Battery Cable Panel Figure 42 Disconnecting the Battery Cable EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 53 www powerware com UPS MAINTENANCE 4 Unscrew and set aside the battery retaining bracket see Figure 43 Figure 43 Removing the Battery Retaining Bracket b Pull the battery trays out onto a flat stable surface see Figure 44 See Recycling the Used Battery or UPS on page 57 for proper disposal Figure 44 Removing the Battery Trays 6 Slide t
79. the REPO connector is installed on the rear panel The indicator is flashing power is not available at the UPS output receptacles The UPS is in Standby mode Press the On button to supply power to the connected equipment The UPS operates normally but some or all of the protected equipment is not on The equipment is not connected to the UPS correctly Verify that the eguipment is plugged into the UPS receptacles For hardwired models contact a gualified electrician to check connections to the power source The output receptacle circuit breaker if applicable is open Check the load Disconnect faulty load eguipment Wait several minutes before resetting the UPS circuit breaker One of the load segments has been turned off through the power management software Reactivate the segment with the software The UPS does not provide the expected backup time Fe Battery Intermittent audible alarm The batteries need charging or service The UPS is on battery see Battery Mode on page 39 for more information Plug the UPS into a power outlet apply utility power on hardwired models for 24 hours to charge the batteries After charging the batteries press and hold the 4 button for 3 seconds then check the 5 indicator If the amp indicator is still flashing see Replacing Batteries on page 52 The UPS is powering the equipment with battery power
80. to Preste atenci n a las instrucciones correspondientes Es necesario desechar las baterias de un modo adecuado Consulte las normas locales para conocer los reguisitos pertinentes Nunca deseche las bater as en el fuego Las bater as pueden explotar si se las expone a la llama EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 13 www powerware com SAFETY WARNINGS S kerhetsforeskrifter VIKTIGA S KERHETSF RESKRIFTER SPARA DESSA FORESKRIFTER DENNA BRUKSANVISNING INNEH LLER VIKTIGA SAKERHETSFORESKRIFTER A Denna UPS enhet inneh ller LIVSFARLIG SPANNING ENDAST AUKTORISERAD SERVICEPERSONAL far utf ra reparationer eller service Det finns inga delar som ANVANDAREN KAN UTFORA SERVICE PA inuti UPS enheten e Denna UPS enhet har en egen energik lla batterier De utg ende kontakterna kan vara str mf rande n r UPS enheten inte r ansluten till en v xelstr mk lla Ta aldrig bort n tsladden n r UPS enheten r p slagen Detta tar bort skyddsjordningen fr n b de UPS enheten och den anslutna utrustningen e Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande temperatur f r ej verstiga 40 C Anv nd inte utrustningen n ra vatten eller vid h g luftfuktighet max 95 e F r att verensst mma med internationel
81. ur service representative to activate this alarm vV AC Input Failure On default Alarm sounds when there is an AC input failure Alarm 90000 Flashing Alarm DOES NOT sound when there is an AC input failure EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D 43 www powerware com CONFIGURATION 44 EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide 164201374 Rev D www powerware com Chapter 6 X Slot Cards Additional UPS Features This section describes e X Slot cards e Network transient protector e Load segments X Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices The Powerware 9125 is factory installed with a Single Port Card which can be replaced with one of the following X Slot cards e ConnectUPS X Web SNMP Card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to a twisted pair Ethernet 10 100BaseT network It has a built in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops In addition a Powerware Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information e Relay Interface Card has isolated dry contact Form C relay outputs for UPS status Utility failure Low battery UPS alarm OK or On bypass e
82. wichtige Hinweise welche Sie bei der Installation und Wartung die USV beachten sollten Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem Ger t arbeiten Bewaren Sie das Handbuch zum Nachlesen auf Die USV f hrt lebensgef hrliche Spannungen Alle Reparatur und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgef hrt werden Die USV enth lt keine vom Benutzer zu wartenden Komponenten ACHTUNG Diese USV ist mit einer eigenen Energiequelle Batterie ausgestattet An den Ausgangssteckdosen kann auch dann Spannung anliegen wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist Bei Modellen mit 220 240 Volt k nnen die Ausgangssteckverbinder stromf hrend bleiben Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist wie in den meisten europ ischen Anlagen betr gt die Spannung an den Ausgangssteckverbindern 0 Volt Bei einer Verkabelung mit Au enleitern betr gt die Spannung an den Ausgangssteckverbindern 110 120 Volt gemessen von Leitung zu Masse oder Leitung zu Masseleiter abh ngig von der UPS USV Verkabelung e Das Eingangskabel nicht entfernen oder abziehen w hrend die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Ger ten entfernt wird Um die Brand oder Elektroschockgefahr zu verringern diese USV nur in Geb uden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren