        XTREME VALUE TOWER SERIES (XVT) USER`S MANUAL
         Contents
1.                     Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 14    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Please handle the UPS and associated equipment with extreme caution since a high amount of energy is  contained in the batteries  Always keep the unit in an upright position as marked on the packaging  and  never drop the unit     Please adhere to the following instructions if the UPS is not installed immediately     e Store the equipment as is in its original packing and shipping carton      Do not store in temperatures outside the range of  15  C to  25      e Ensure that the equipment is fully protected from wet or damp areas and from moist air     In order to maintain the batteries  the UPS should be recharged every 6 months for at least 8 hours     If flammable substances such as gases or fumes are present  or if the room is airtight  a hazardous  situation may exist in which no electrical equipment should be operated     The instructions in this manual explain how to install the UPS safely  Not acknowledging such electrical  hazards may be fatal     keep this manual for future reference     WARNING     It is strongly recommended that the UPS cabinet not be opened as components have very  high voltage and touching those components may be fatal  Only a qualified technician or  authorized agent may service the unit     The UPS unit s output receptacles carry live voltage even when not connect
2.                s            ST  EXE  WT  NEC  suc M                   4       NXRT EBP FRONT PANEL    Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 45    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        LED Description    The Charging LED GREEN indicates that the battery charger in the Extended Battery Pack is charging  normally with the AC power cord attached to the Battery pack     The Battery Test LED GREEN indicates that the DC output of the Extended Battery Pack  EBP  is normal   To perform the Battery Test     e switch the breaker on the rear of the        to ON position  e press the Battery Test Button on the front panel of the         e the DC output from the        is normal when the Battery Test LED is illuminated    Prior to connecting EBP s  test each EBP to assure proper operation     Extended Battery Pack Operation    The NXRT UPS System can be connected to multiple extended battery packs to increase the runtime  when connected to the UPS supporting the load  Most UPS Systems are limited to one or two external  battery packs because the UPS is responsible for the recharging and does not have the recharge capacity  to handle the additional batteries to a full recharge  The NXRT UPS System overcomes this limitation by  equipping each extended battery pack  EBP  with its own charger  providing the user a way to achieve  significantly more battery backup time  Not all of the AC input power cords for the 
3.             ______ __________ _ 18  Wall mounted Installation Steps                                                                   19   19    Rack mount using 5 in 1 bracket          20  RACK MOUNT INSTALLATION STEPS                                           21  UPS Rail Installation Instructions to 19                                           12 2 2 2 2                                                       nnns 21  INITIAL CONNECTION AND STARTUP                 J                24                                      Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 2    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     USER S OPERATIONS uq nat          DI RUE              ENIM Ne REV AP UN URS 26  Turning Off the UPS when connected to an AC source          26  Starting the UPS from a DC source  cold start     tenente 26  Turning Off the UPS when in DC          ert td ettet cr tacita cr ertt 26  STEMS BIS dr HIS INN E T TT 27  Audible Alarm silence in DC Mode or Fault Mode    27                     e                         28  REPLACING THE BATTERY      EE 28   TROUBLESHOOTING            31                     32   SPECIFICATIONS                   tum s                 33   SHIPPING LIS                      id      esee Ex                     36   OBTAINING  SERV ICE                                                   Fa do 37   XTREME POWER CONVERSIONS  XPC  CORPORATION LIMITED   WARRANTY e                  38   XTREM
4.   fire  flood  and wind    Damage caused by abuse  misuse  alteration  modification  or negligence    Any labor costs or travel  room and board expenses associated with the repair and or restoration of lost or damaged  hardware  software or data     EXCEPT AS EXPRESSLY PROVIDED IN THIS POLICY  XPC SHALL NOT BE LIABLE FOR ANY  DAMAGES WHATSOEVER  INCLUDING  BUT NOT LIMITED TO  DIRECT  INDIRECT  SPECIAL   INCIDENTAL  CONSEQUENTIAL  OR MULTIPLE DAMAGES ARISING OUT OF THE USE OF THE  PRODUCT OR DAMAGE TO THE CONNECTED EQUIPMENT  REGARDLESS OF THE LEGAL  THEORY ON WHICH SUCH CLAIM IS BASED  EVEN IF ADVISED OF THE POSSIBILITY OF SUCH  DAMAGE  SUCH DAMAGES INCLUDE  BUT ARE NOT LIMITED TO  LOSS OF PROFITS  LOSS OF  SAVINGS OR REVENUE  LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR  ANY ASSOCIATED EQUIPMENT  LOSS OF SOFTWARE  COST OF CAPITAL  COST OF ANY  SUBSTITUTE EQUIPMENT  FACILITIES OR SERVICES  DOWNTIME  THE CLAIMS OF THIRD  PARTIES  INCLUDING CUSTOMERS  AND INJURY TO PROPERTY     Submitting a Load Protection Policy Claim     e    ool    1  Any claim under the Load Protection Policy must be made within 10 days of the date of alleged damage to the  Connected Equipment    2  Call the XPC technical support department at 1 800  582 4524 and obtain a Load Protection Policy Returned Material  Authorization  RMA  number  Have information on all applicable insurance or other resources of recovery payment that is  available to the Purchaser and the name of the power utility sup
5.  7 13  Page 40    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        to make any representations beyond those made in this agreement concerning the Load Protection Policy     XPC Corporation  230 Yuma Street  Denver  CO 80223  1 800 582 4524                             RS             Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 41    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        APPENDIX A  EXTENDED BATTERY PACK USER GUIDE    Estimated Run Time for UPS with Extended Battery Packs  RUNTIME FOR        OF EXTENDED BATTERY PACKS IN MIN          VA  WA   ues               2                        4           5           NXRT   1000    1500 1050 18 67 123 184 315  NXRT   3000  2100 120 152    Note  for estimated run times using more than 5 EBP s  contact Xtreme Power Conversion at    support xpcc  com        ee ee  Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 42    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        CAUTION  It is very critical to connect the correct voltage        with the UPS intended     EBP1 is for NXRT 1000  EBP2 is for NXRT 1500  EBP3 is for NXRT 2000 3000    CONNECTING THE INCORRECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE  UPS AND OR BATTERY PACK WILL VOID THE WARRANTY     All EBP s have a different DC voltage configuration intended only for the UPS s listed above   PLEASE D
6.  LED will no longer be illuminated  This is normal  operation for the EBP  The EBP is working properly     SS  Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 49    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        5  Why don t the LED s on each EBP connected to an AC input source turn ON and OFF at the same  time     e The charger on each        functions independently from the others  One        charger  may be charging while another one might be at 10096 and the charger turned off  This is  normal operation of the EBP                                                                    Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 50    
7.  brackets    gy MV dcr         1  set of horizontal mounting brackets            lt       _________________ ___________________________  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 36    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        OBTAINING SERVICE    If the UPS requires Service     Use the TROUBLESHOOTING section in this manual to eliminate obvious causes   Verify there are no circuit breakers tripped   Call your dealer for assistance  If you cannot reach your dealer  or if they cannot resolve the  problem  call Xtreme Power Conversion Corp Technical Support at 800 582 4524  Technical  support inquires can also be made at support xpcc com  Please have the following information  available BEFORE calling the Technical Support Department   a  Your name and address   The serial number of the unit   Where and when the unit was purchased   All of the model information about your UPS   Any information on the failure  including LED s that may or may not be illuminated     560   Dem    A description of the protected equipment  including model numbers if possible     A technician will ask you for the above information and  if possible  help solve your problem  over the phone  In the event that the unit requires factory service  the technician will issue you a  Return Material Authorization number              If you are returning the UPS to Xtreme Power for service  please follow these procedures     1  Packthe UPS 
8.  power requirements      Backup time required will indicate the battery size needed  If the load is less than the UPS  nominal power rating  then actual backup time is longer   e The following options are available   o Extended Battery Packs     NXRT EBP1 for 1000     NXRT EBP2 for 1500     NXRT EBP3 for 2000 3000  o Connectivity Options  SNMP WEB card  o Xtreme Power Distribution Units  XPDU     See the Specification section of this manual for additional model information        _     E   Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 9    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        BATTERY INTERNAL COMMUNICATION  REPO SOCKET SNMP SLOT SWITCH            OUTPUT I NPUT INPUT                                                                                                                                                      COMMUNICATION  SOCKET BREAKER SOCKET INTERFACE  NXRT 1000 REAR VIEW  INPUT INTERNAL COMMUN ICATION  BREAKER SNMP SLOT T SWITCH              IL                 mo    o           B8 e              52 ba ID _ P lo                        OUTPUT BATTERY AC INPUT FAN COMMUNICATION  SOCKET SOCKET INTERFACE  NXRT 1500 REAR VIEW  OUTPUT INTERNAL COMMUNI CATION  SOCKET SNMP SLOT FAN            NTERFACE       COMMUNICATION QUTPUT HIGH CURRENT INPUT      INPUT BATTERY  SWITCH BREAKER OUTPUT SOCKET BREAKER SOCKET  NXRT 2000 REAR VIEW       Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 10    
9.  the event that the internal EBP  charger draws excessive current     Extended Battery Pack Installation    CAUTION  Extended Battery Pack  EBP  Installation should be performed by qualified service  personnel     1  Verify that the DC circuit breaker on the rear panel of the EBP is in the OFF position   2  Turn the UPS OFF and disconnect the UPS Input Cord from the AC wall outlet   3  Remove the EBP connector cover from the UPS rear panel     4  Connectthe external DC battery cable from the EBP to the appropriate connector on the UPS                                             Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 48    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        5  Secure the DC battery cable to both the rear of the UPS and the rear of the        by using         8  screws provided  2 each per connector end      6  Repeat the above procedure for testing and securing each additional EBP required     CAUTION  Do not use extension cords when connecting input AC power to UPS or EBP s    7  Move the DC circuit breaker on the rear of each        to the ON position  At this point the UPS  will need to be started     8  If the EBP s are plugged into an AC source and properly installed  the internal batteries will be  charged when acceptable voltage is present  EBP s must be charged for a minimum of 6 hours  for full battery time     NOTE  If the EBP is going to be out of service or stored for six months or 
10. 50dba at one meter    Altitude 11 500 ft  3500 m  above sea level    WARRANTY Three years electronics   Three years batteries  APPROVALS North America UL cUL FCC    INDICATORS  amp     ALARMS Input output voltage  amp  frequency  on line mode  back up mode  battery capacity     load level    Audible Alarm Beep every 4 sec  on battery     UPS Faut   Continuous beeping sound and LCD display    LCD Visual Display                                     Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 34    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS              seen                   50 60 Hz auto sensing                            Ree _    BATTERY  Battery Type sealed  non spillable  maintenance free  valve regulated  lead acid                                  _               ma          mem                             one                EXTENDED BATTERY  EE PACK MODELS NXRT EBP1 NXRT EBP2 NXRT EBP3    WARRANTY Warranty Three years electronics   Three years batteries  APPROVALS   North America UL cUL FCC    INDICATORS     amp  ALARMS LED Visual Display Charging LED  Battery test LED                                   Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 35    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        SHIPPING LIST  1   1 UPS   1  User s and Installation Manual   1  6 ft RS232 cable   1  UPSILON CD  monitoring software    2  sets of 5 in 1 mounting
11. BP2    Use      x 6 screws on places marked with letter A       NXRT 2000  NXRT 3000  NXRT EBP3    Use M4 x 6 screws on places marked with letter A    F  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 17    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     Vertical Installation Steps       NXRT 1000  NXRT 1500  NXRT EBP1  NXRT EBP2    Use M4 x 6 screws on places marked with letter          NXRT 2000  NXRT 3000  NXRT EBP3    Use M4 x 6 screws on places marked with letter A       Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 18    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Wall mounted Installation Steps       NXRT 1000  NXRT 1500  NXRT EBP1  NXRT EBP2    Use M5 x 12 screws on places marked with letter B       NXRT 2000  NXRT 3000  NXRT EBP3    Use M5 x 12 screws on places marked with letter B       Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 19    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        19  Rack mount using 5 in 1 bracket       NXRT 1000  NXRT 1500  NXRT EBP1  NXRT EBP2    Use M5 x 12 screws on places marked with letter B       NXRT 2000  NXRT 3000  NXRT EBP3    Use M5 x 12 screws on places marked with letter B                                        Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 20    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRU
12. E POWER CONVERSION  LOAD PROTECTION POLICY    eR Error  Bookmark not defined    APPENDIX A  EXTENDED BATTERY PACK USER GUIDE               39  Estimated Run Time for UPS with Extended Battery Packs    42                                  MM      46  Extended Battery Pack Opera Otivissssssiviassstsissiscaaeatecousacvbassiwtasselabso sdadeatosousactbusshwiassalabioisdagentbsorsnctbnashe 46  Extended Battery Pack Installation       scssssssssssssesssssessssssesssssessessecssssussessssessssucesssisessssecsessiesessseseesseeeten 48  Extended Battery Pack Q  amp  A    dicc      49               e  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 3    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Thank you for selecting this uninterruptible power supply  UPS   It provides you with protection for  connected equipment  Please read this manual before installing the NXRT Series UPS models NXRT   1000  NXRT 1500  NXRT 2000 and NXRT 3000 as it provides important information that should be  followed during installation and maintenance of the UPS and batteries  allowing you to correctly set up  your system for the maximum safety and performance  Included is information on customer support  and service  if it is required  If you experience a problem with the UPS  please refer to the  Troubleshooting section in this manual to correct the problem  If the problem is not corrected  please  collect information so that the Technical Sup
13. E POWER SUPPLY  UPS        Xtreme Power Conversion Load Protection Policy    THIS POLICY 15 NOT AWARRANTY  REFER TO THE XPC CORPORATION  INC  LIMITED WARRANTY FOR INFORMATION  CONCERNING THE WARRANTY FOR YOUR XPC PRODUCT  THE LIMITATIONS AND CONDITIONS CONTAINED IN THIS  POLICY DO NOT AFFECT THE TERMS OF THE XPC LIMITED WARRANTY     Definitions    1   Product  means a Standard 120  208  or 240 Volt power protection device that is used in the United States and  Canada  This policy does not include custom manufactured products    2   Power Disturbance  means an AC power line transient  telephone line or Local Area Network  if applicable    spike or surge    3   Connected Equipment  properly connected electronic equipment   4     Fair Market Value  of damaged Connected Equipment as determined by XPC shall be the lower of  a  the  average price the same or similar items are being sold for on eBay   b  the price list of Orion Blue Book  or if  such price list is no longer published  a published or announced price list reasonably selected by XPO    c  the  lowest price the same or similar items can be purchased for in the United States or  d  the total amount of all  payment s  you have or are entitled to receive from insurance  other warranties  extended warranties  a legal  liability claim or from other sources or persons for the damaged Connected Equipment    5   Purchaser  means the person or entity that originally purchased the Product from an authorized reseller or  distribut
14. EBP s need to be  connected to AC   the more you connect the faster the recharge of the batteries     1  The DC Circuit Breaker on the rear of the        connects and disconnects the DC bus voltage from  the EBP to the UPS  The DC Circuit Breaker will also trip to the OFF position in the event of an  over current condition in the EBP     BREAKER          125              ON           INPUT 110V 120V 60Hz Max3A mI                     The equipment must be BREAKER  50A 230Vac  connected to the power     socket with the grounding       EBP2 REAR VIEW                                        Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 46    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        2  The EBP s use a cable shipped with each EBP to  daisy chain  together additional EBP s to the  first EBP being connected to the UPS in the appropriately labeled connector  or for connecting  the first EBP to the UPS     UPS                       gt                5  daisy chain  to UPS or other                 3  The AC input cord is for connecting AC utility to operate the Charger contained in each EBP                           Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 47    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     MSN 5 Gre                               5  daisy chain  to UPS or other           4  The input AC Circuit Breaker will trip to the OFF position in
15. HE   SETTINGS SECTION FOR YOUR SPECIFIC INSTALLATION     8  After charging is complete  connect the loads to the UPS while monitoring the load levels  via the UPS LCD or via the software      Do not connect any devices that have the possibility of overloading the UPS     Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 25    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Refer to the Troubleshooting section and or Technical Support with any problems during setup     USER S OPERATIONS    The only operations that users are permitted to do are     e Turning the UPS unit ON or OFF  e Operating the user interfaces   e Connecting data interface cables  e Changing the batteries    All such operations are to be performed exactly as instructed in this manual  The greatest care possible  must be taken for any of these operations  and any change thereof may prove very hazardous to the  operator        On Off Button Function Button Inquiry Button    Turning Off the UPS when connected to an AC source    e Press and hold the ON OFF button for more than 3 seconds to turn off the UPS  This means the  internal inverter has been deactivated       The unit will run a self test prior to the deactivation of the inverter    e The green LED will be off and the yellow LED will be on  The LCD display will indicate    On BPS      which means the UPS in providing no output     Starting the UPS from a DC source  cold start     e Assure that t
16. IOT REME    Power Conversion       UNINTERRUPTIBLE POWER SUPPLY  UPS     NXRT Online Low Voltage    Models    USER  amp  INSTALLATION MANUAL    WWW Xpcc com      2013 Xtreme Power Conversion Corporation  All rights reserved     NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     Table of Contents          Statements   FCC Part 15                                                  ns D   IMPORTANT SAFETY INSTRUCTIONS                                                    6   INTRODUCTION sna annainn ananasa aaa                   8   PRODUCT DESCRIPTION l                                                8  Double Conversion On Line Technology                                8     uuu un                     9   SYSTEM CONFIGURATION    iu a ua                         9  BR            neu          gach iti uL UM Ren M OE NL EATUR E eR 11                     ON                 12            13  SNMP Communications Option                  cease 13  Remote Emergency Power Off  REPO  Port          nn treten        14    DETERMINING THE POWER REQUIREMENTS OF YOUR    EOUIPMEN u l li l  14  HARDWARE INSTALLATION GUIDE                  nnns 14               ordeo                                                     UD                      16   s Lida rae k   c umo                                               AI MM ML UA MM IM 16   19 Cabinet Ear IMStalll ation                                                            17  Vertical Installation Steps       
17. NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        OUTPUT INTERNAL COMMUNICATION  SOCKET SNMP SLOT    FAN REPO INTERFACE       COMMUNICATION OUTPUT HIGH CURRENT INPUT      INPUT BATTERY  SWITCH BREAKER   OUTPUT SOCKET BREAKER SOCKET    NXRT 3000 REAR VIEW    LED Green light  LED Yellow light  LED Red light                       A A A  9    e T 6 6 6    NXRT FRONT CONTROL PANEL    LED Description    The UPS has three LED s on the front control panel  These LED s allow the user to quickly understand if  any action is needed     Red LED    If this LED is illuminated it indicates a fault and the UPS will have no output  Faults that would indicate  this alarm condition include     e Overload  e Inverter fault  e  BUSfault    e Over temperature fault    Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 11    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Yellow LED    If this LED is illuminated it indicates the user needs to take some action  and included        UPSin Bypass Mode   e Batteries Overcharged   e Charger fault   e Fan fault   e Batteries discharged to low voltage level    Green LED    If this LED is illuminated it indicates that everything is normal and the UPS is being powered by incoming  AC utility or by the batteries     LCD Descriptions    There are four lines of information in the LCD display  Each line provides specific information related to  the unit stat
18. O NOT MIX EBP s AND MAKE SURE YOU ONLY CONNECT THE EBP TO LIKE EBP s OR  UPS INDICATED ABOVE  DC VOLTAGES ARE MARKED ON BOTH THE UPS AND THE            MAKE  SURE THEY MATCH              CAUTION          CAUTION LABEL             CABLE  CONNECTORS   PLEASE CHECK  VOLTAGES CAREFULLY         LS  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 43    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Extended Battery Pack Configuration                                   e INPUT   BATTERY     E   INPUT BREAKER socker FAN SOCKET BATTERY BREAKER  Fe                  or   9  e    P   2 4                       J   AN wy       dE      Er  O     j        0                            ur reme   y     S lt  Sd                           n        Ee  9 v       EXTENDED BATTERY PACK 1  EBP1  FOR NXRT 1000  TT     BATTERY BREAKER palio FAN INPUT BREAKER    oy        o               a  INPUT  SOCKET    EXTENDED BATTERY PACK 2  EBP2  FOR NXRT 1500    Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 44    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        BATTERY  BATTERY BREAKER SOCKET FAN INPUT BREAKER       INPUT  SOCKET    EXTENDED BATTERY PACK 3  EBP3  FOR NXRT 2000 3000    CHA    RGING LED             BATTERY      TEST LED                                                                 C  Serr                  nia ER c atl puc a 5                 m  UN         w    E uet S  4
19. PTIBLE POWER SUPPLY  UPS        RACK MOUNT INSTALLATION STEPS    UPS Rail Installation Instructions to 19  Cabinet  1        2U EAR FOR UPS             MOUNING IN  CABINET       EXPANDABLE RAIL FOR UPS OR EBP MOUNTING IN CABINET       MOVEABLE NUT  FOR MOUNTING  RAIL KIT IN  CABINET    w      vrw _   _     Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 21    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     4                ASSEMBLE THE RAIL ONTO THE CABINET U BAR WITH  SCREWS AT FRONT  amp  BACK USING MOVABLE NUTS      z                               Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 22    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        6     EU    PUSH THE UPS OR EBP INTO THE CABINET VIA THE RAIL  FROM THE FRONT         dii    j                           Z           mall um      a ma mt    T       3                     ATTACH UPS OR        EAR ONTO CABINET U BAR WITH  SCREWS ON BOTH LEFT  amp  RIGHT SIDES    Note  Any external Battery Packs must be installed next to or under the UPS  Please refer to Appendix  A  Battery Pack User Guide for more information when installing these                                               Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 23    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        INITIAL CONNECTION AND STARTUP     Ensure that the UPS and 
20. The short circuit current capability of the battery is  sufficient to burn wire or tools very rapidly  producing molten metal  Observe these precautions when  replacing the battery     Remove all watches  rings or other metal objects    Only use tools with insulated handles    Do not lay tools or metal parts on top of battery or any terminals    Wear protective eye wear  goggles   rubber gloves  and boots    Disconnect the charging source before connecting or disconnecting the battery terminals     Qu M6 d ind    Determine if the battery is inadvertently grounded  If inadvertently grounded  remove the  source of the ground  Contact with a grounded battery can result in electrical shock  The  likelihood of such shock will be reduced if such grounds are removed during installation and  maintenance  applicable to a UPS and a remote battery supply not having a grounded circuit                      7 ______________________  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 28    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Remove plastic front cover          Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 29    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     6029 0 0 0402 040 oO       O O O 0 0 20 O O    o          Q OO oo oo ooo dara D O O O  250505040    WS WS         CODO OO           O0                      o O D OU  ORC aon na noa e 5       0 0 0  OOO OO e
21. XPC Corporation or a XPC Corporation authorized representative before or after  delivery with regard to the use or application of Xtreme Power Conversion equipment is furnished on  the basis that it represents XPC Corporations best judgment under the situation and circumstances  but  it is used at the recipient s sole risk     EXCEPT AS STATED ABOVE  XPC Corporation DISCLAIMS ALL WARRANTIES  EXPRESSED OR IMPLIED   INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE     EXCEPT AS STATED ABOVE  IN NO EVENT WILL XPC Corporation BE LIABLE FOR DIRECT  INDIRECT   SPECIAL  INCIDENTAL  OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF Xtreme Power  Conversion EQUIPMENT  including but not limited to  any costs  lost profits or revenue  loss of  equipment  loss of use of equipment  loss of software  loss of data  cost of substitutes  or claims by third  parties  Purchaser s sole and exclusive remedy for breach of any warranty  expressed or implied   concerning Xtreme Power Conversion equipment  and the only obligation of XPC Corporation under this  warranty  shall be the repair or replacement of defective equipment  components  or parts  or  at XPC  Corporations sole discretion  refund of the purchase price or substitution of an equivalent replacement  product                                                          Ii  OII  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 38    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBL
22. ance     ICES 003    This Class B Interference Causing Equipment meets all requirements of the Canadian Interference  Causing Equipment Regulations ICES 003  Cet appareil numerique de la classe B respecte toutes les  exigencies du Reglement sur le materiel brouilleur du Canada     Declaration of Conformity Request  Units labeled with a UL mark comply with the following standards and directives     e   UL 1778    CAUTION     shielded type power cord is required in order to meet FCC emission limits and to    prevent interference to the nearby radio or TV reception  It is essential that only the supplied power  cord be used  Use only shielded cables to connect 1 0 devices to this equipment     WARNING  Any changes or modifications not expressly approved by the manufacturer of this    device could void the user s authority to operate the equipment                      Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 5    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        IMPORTANT SAFETY INSTRUCTIONS    SAVE THESE INSTRUCTIONS     CAUTION   UPS having Internal Batteries   Risk of electrical shock     Hazardous live    parts inside this unit are energized from the battery supply even when the input AC power is  disconnected     CAUTION   No User serviceable Parts   Risk of electrical shock  do not remove cover     No user serviceable parts inside  Refer servicing to qualified service personnel     CAUTION   Non isolated Bat
23. ding computers  workstations  process control systems  telecommunications systems   sales terminals  other critical instrumentation  etc  The purpose of the UPS is to protect these systems  from poor quality utility power  complete loss of power  or other associated problems     Electrical interference exists in many forms  causing problems in AC power  from lightning  power  company accidents and radio transmission motors  air conditioners  and vending machines  Protection  of sensitive electrical equipment is vital to protect against power outages  low or high voltage  conditions  slow voltage fluctuations  frequency variations  differential and common mode noise   transients  etc     To prevent power line problems from reaching critical systems causing damage to software  hardware   and equipment malfunctions  the UPS maintains constant voltage  isolating critical load output and  cleaning the utility AC power     Double Conversion On Line Technology    A double conversion on line technology UPS provides completely isolated  clean  uninterrupted single   phase power to your critical systems  while maintaining the batteries for their maximum potential  In  the event that the power failure lasts longer than the UPS backup time  the UPS will shut down avoiding  battery damage  When the input AC voltage returns  the UPS will automatically return online to  recharge the batteries     As shown in fig  1 block diagram     e An input filter reduces transients on the incoming utili
24. e OG                 O  D G           TOO OO O00                  o o0 6 0 9            OOO       IRI       O O O          CO OO O       Remove the battery tray from the UPS     ___ _  gt                    _      _     Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 30    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     TROUBLESHOOTING    Issue    The    Input     letters in the  second row  of the LCD  are flashing    The  Input   letters in the  second row  of the LCD  are flashing    Battery  Indicator  Flashing    Utility  Normal  UPS  has no AC  input    Insufficient  battery run   time    UPS will not  start after  pressing the     On Off     button    Major fault  detection by  the UPS    Audible  Alarm  Two Beeps  per second  at startup    for 8 total  seconds    One beep  per 2  minutes    One beep  per second    Once every  4 seconds  in DC mode    Constant  beep    Alarm Description    The Input Voltage or frequency  may be beyond the normal  acceptable range     Possible mis wiring AC line and  neutral line    Batteries are undercharged   disconnected or need to be  replaced     Possibility that circuit breaker  on UPS has tripped       On batt    displayed on LCD    1  Insufficient time for button  depression  2  UPS has no battery connected  3  Battery voltage is too low to  power the load  4  Fault has occurred inside the  UPS    Type of fault and fault code  displayed on LCD        Xtreme Power Convers
25. e for the correct  operating system     Follow the setup instructions  Enter the product key when prompted  The  software key is found on the CD cover  Click finish when prompted    e The UPSILON icon will appear in the system tray of the desktop near the system  clock  Double click this icon to enlarge the program window     Connect the RS232 cable  included in the UPS packaging  to the Computer and  UPS  Communication should start momentarily  If it does not  click on Settings up  on the UPSilon toolbar  then select a different Comport until communication is  established    Click on  Manual  in the UPSILON toolbar for further software configuration     e NOTE  PLEASE VERIFY AUTOMATIC SHUTDOWN TIME PARAMETERS IN THE  SETTINGS SECTION FOR YOUR SPECIFIC INSTALLATION     7  Configure the optional NetAgentll SNMP card if installed      Insert the NetAgent Utility CD  included with SNMP packaging  into a PC and  download the user manual    Install Netility from the AutoRun menu      Connect a network cable from the PC to the SNMP                Run Netility program and it will auto search and list available NetAgents  SNMP  card     Highlight and click  Configure  to change the network settings on the NetAgent   discovered    e Disconnect the cable      the PC and connect the SNMP          to your network    e Access the SNMP card via the network and make configuration changes using the  manual downloaded previously    e NOTE  PLEASE VERIFY AUTOMATIC SHUTDOWN TIME PARAMETERS IN T
26. ed to an input       voltage source  The UPS has its own internal energy source     Environment    Ensure that all environmental concerns and requirements are met according to specifications listed in  this document  otherwise the safety of installation personnel cannot be guaranteed  and the unit may    malfunction        Ensure that you remember the following when locating the UPS system and battery options        Avoid extremes of temperature and humidity  Maximum battery life can be attained with a  recommended temperature range of  15     to  25        e Provide protection for the equipment from moisture    e Space and ventilation requirements must be met  Ensure there is 100mm behind and 50mm on  the sides of the UPS for proper ventilation    e Ensure that the front of the UPS remains clear for user operation                   _           lt   lt                           Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 15    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Installation    Standard brackets          4 Fj  2U 5IN 1 BRACKET FOR    NXRT 1000  NXRT 1500   EBP1  amp  EBP2                     X      k       3U 5 IN1 BRACKET FOR    NXRT 2000  NXRT 3000   amp  EBP3    Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 16    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        19  Cabinet Ear Installation       NXRT 1000  NXRT 1500  NXRT EBP1  NXRT E
27. er for either the cost of repair of the  Connected Equipment or the Fair Market Value of the damaged Connected Equipment  up to the dollar limits  stated above  XPC reserves the right to require the Purchaser to transfer title and deliver the Connected  Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected  Equipment            maximum liability shall be reduced to reflect all such other payments or sources of  recovery  whether applied for or not    4   f XPC issues payment to the Purchaser to have the Connected Equipment repaired  the repair must be performed at a  service center that is authorized by the manufacturer of the Connected Equipment  XPC reserves the right to contact the  authorized service center directly to discuss repair costs and damage to the Connected Equipment to determine if it was  caused by a Power Disturbance and the right to request that the service center forward the Connected Equipment or  components of the Connected Equipment to XPC for inspection   5  Unless modified in writing signed by an officer of XPC and the Purchaser  the terms of this policy are the complete and  exclusive agreement between the parties  superseding all prior agreements  oral or written  and all other communications  between the parties relating to the subject matter of this agreement  No employee of XPC or any other party is authorized               iz                           Xtreme Power Conversion   XPC  Corporation  Rev 2
28. erly operated when a Power Disturbance passed through the  Product and  i  exhausts the protection capacity of the Product or  ii  damages the Product    6  The Load Protection Policy does not apply if the Product has been operated in a failure mode or not in compliance with  XPC operating instructions in the Product user s manual  or if the Connected Equipment has not been operated in  compliance with the instructions and manuals of its manufacturer vendor            III       Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 39    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        7  This policy is null and void if  XPC determines  in its sole discretion  that the Product has been tampered with or altered  in any way     What is Not Covered Under the Load Protection Policy   The following damage is not covered by this Policy     1  Restoration of lost data and reinstallation of software    2  Damage from a cause other than AC power line transients  except for damage due to telephone line  Local Area  Network  or CATV transients  which is covered only if the Product offers such protection    DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT FOR THE  PRODUCT  INCLUDING  BUT NOT LIMITED TO  LACK OF A PROPER SAFETY GROUND     Damage caused by the use of the Product for purposes other than those for which it was designed    Damage caused by accidents  or natural disasters  including but not limited to
29. follow up maintenance of the UPS and batteries                       Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 6    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS     CAUTION    The unit has a dangerous amount of voltage  If the UPS indicator is on  the unit s outlets may have a  dangerous amount of voltage even when not plugged into the wall outlet because the battery may  continue to supply power     Care should be taken to undertake installation indoors  free from electrically conductive particles  which are under temperature and humidity control  in order to reduce the risk of electric shock     It is best to disconnect the device using the power supply cord  Ensure that the equipment is placed in  a position near the outlet where easily accessible     Except for replacing the batteries  all servicing on this equipment must be carried out by qualified    service personnel     Before conducting any maintenance  repair  or shipment  first ensure that everything is turned off  completely and disconnected        For additional safety instructions  please use the Safety Manual as a reference     Special Symbols    The following symbols used on the UPS warn you of precautions     RISK OF ELECTRIC SHOCK   Please observe the warning that a risk of electric shock is present    CAUTION  REFER TO OPERATOR S MANUAL   Refer to the operator s manual for additional  information  such as important operating and maintenance ins
30. he UPS has fully charged batteries and the internal battery pack is connected    e Assure that there is no AC input power source and or the unit is not plugged into an outlet    e Press and hold the ON OFF button for three seconds    e          turned       the UPS will perform a self test function  when the yellow LED turns to green   LCD displays  On Batt      the UPS is now functioning in DC mode     Turning Off the UPS when in DC Mode    e Press and hold the ON OFF button for more than 3 seconds to turn off the UPS  This means the  internal inverter has been deactivated     rc SS SS  Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 26    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        e During the shutdown period  the UPS will run a self test  Once the self test has been completed   assuming there is still no AC input  the LCD will no longer display information  This indicates the  UPS has no output     Self Test Operation    Please refer to the three operating buttons on the front panel of the UPS     e Confirm the UPS is in  Utility Mode    e Press and hold the  Function  button for a minimum of two seconds   e The self test will last for 10 seconds  during this time the LED s will be lit in a sequential     repeating fashion     Audible Alarm silence in DC Mode or Fault Mode       When the UPS is in DC Mode  the audible alarm will sound every four  4  seconds  Press and  hold the  Function  Button for a mini
31. in its original packaging  If the original packaging is no longer available  as  the Technical Support Technician about obtaining a replacement set of packaging  material  It is important to pack the UPS properly in order to avoid damage in transit   Never use Styrofoam beads for a packing material    2  Include a letter with your name  address  daytime phone number  RMA number  a copy  of your original sales receipt  and a brief description of the problem    3  Markthe RMA number on the outside of all packages  Xtreme Power cannot accept any  package without the RMA number marked on the outside of the boxes    4  Return the UPS by insured  prepaid carrier to the address provided by the Technician     Refer to the Warranty statements in this manual for additional details on what is covered                          Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 37    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        XTREME POWER CONVERSIONS  XPC  CORPORATION LIMITED  WARRANTY    Xtreme Power Conversion  XPC  Corporation warrants Xtreme Power Conversion equipment  when  properly applied and operated within specified conditions  against faulty materials or workmanship   excluding batteries  for a period of three years for NXRT Series products from the date of purchase   XPC Corporation warrants internal batteries for a period of three years from the date of purchase  For  equipment sites within the United States and Ca
32. ion    XPC  Corporation  Rev 2 7 13        What You Should Do    Verify that utility voltage and  frequency is within acceptable  range  If so  contact support     Check wiring of input to UPS   reversed wiring  etc  Rewire  if  necessary    Check UPS batteries  If necessary  reconnect batteries  wait 12 hours  to charge or replace defective  batteries    Reset circuit breaker    1  If batteries are undercharged let  UPS charge batteries at least 12  hours  2  After charging  if runtime is still  insufficient  replace with new  batteries  3  Reduce output load to lengthen  runtime    1  Depress the    On Off    button for  at least three seconds  2  Make sure the batteries are  connected and the connector on  the battery cartridge is    mated     correctly   3  Plug the UPS in  remove all loads   and allow to charge for 12 hours   4  Contact dealer for service details    Review abnormal process  information table listed below in  this manual and take appropriate   action  If problem does not resolve  contact supplier for service and  provide error code s        Page 31    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        LCD FAULT CODES                     LNEMODE                    BATTEST MODE      BUS FAULT       ee 05  25 01  21 40  41    OVERHEAT   33 06   oB   B __     OPSHRT        6   02 14         OVERLOAD     B   060   45          FANFAUT   _ 36       28   38       46 __       E                       Xtreme Power Conver
33. longer  the    batteries must be recharged for at least 36 hours every six months     Extended Battery Pack Q  amp  A    1  Which EBP s do   connect to an AC input source         t is possible to plug in every        into      AC input source  The more connected the  faster the recharge time  It is recommended that every third EBP be connected to  incoming AC utility to properly charge the batteries in a complete system  Leaving too  many chargers connected may cause an over charge situation which could damage the  batteries     2  Which LED s are supposed to be lit on the front of each EBP        When             is connected to an AC input source and the unit is charging  a GREEN LED  on the front of the EBP will be illuminated     3  Are any LED s on the front of the EBP supposed to be lit if it is not connected to an AC input  source        No  The UPS and or the EBP s that are plugged into an AC input source are responsible  for charging the entire system  The EBP is still working and has the capability of  providing DC voltage when needed  No LED on the front bezel will be illuminated     4  The EBP is connected to an AC input source  why does the LED on the front of the EBP turn ON  and OFF intermittently  and does this mean this EBP is not working     e        GREEN LED on the front of each        indicates that the charger contained in the         is charging  Under certain conditions when the batteries are 10096 charged  the charger  in the EBP will shut off and the
34. mum of two  2  seconds to disable the audible alarm    e When the UPS is in Fault Mode  the audible alarm will continuously sound  Press and hold the   Function  Button for a minimum of two  2  seconds to disable the audible alarm                         Ila II  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 27    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        BATTERIES    The life of batteries used in these UPS products is estimated at 3 6 years depending on level of usage   Once the battery is no longer useful and must be replaced  please contact service personnel for  assistance     REPLACING THE BATTERY   QUALIFIED SERVICE PERSONNEL ONLY     CAUTION  nead and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery     Service the battery under the supervision of Qualified Service Personnel knowledgeable of batteries and  their precautions     CAUTION  use only the specified type of battery  See your dealer for replacement batteries     CAUTION  rne battery may present risk of electrical shock  Do not dispose of batteries in a fire as it    may explode  Follow all local ordinances regarding proper disposal of batteries     CAUTION  po not open or mutilate the batteries  Released electrolyte is harmful to skin and eyes    and may be toxic     CAUTION  Although the battery system voltage is only 12VDC and 24VDC  the battery can present       high risk of short circuit current and electrical shock  
35. n the Optional battery packs if installed   Connect the AC input cable to the UPS and connect the other end to an approved  grounded outlet  Once the UPS has been connected to an AC power source the internal  charger will start charging the UPS batteries  at this point the yellow LED is illuminated   and the LCD displays  UPS OFF     In this state the output voltage is zero  which means UPS  has no output  Please realize that although you may start using the UPS immediately   maximum back up time will still not be available  so it is recommended to charge the  batteries for a minimum of 6 hours before use    5  Start and configure the UPS       On Off Button Function Button Inquiry Button       Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 24    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        e Press and hold the ON OFF button for more than 3 seconds to turn on the UPS   The UPS should now start its inspection of the internal functions  main  synchronization  and inverter startup  Then power should start to be supplied via  the outlets  Once turned on  the UPS will perform a self test function  when the  yellow LED turns to green  LCD displays  on line   and means UPS is working in  utility mode    6  Configure the local monitoring software if desired    e Insert the UPSilon 2000 CD  included with UPS packaging  into the CD ROM of the  local computer    e Select    Install program  from the Autorun menu and choos
36. nada  this warranty covers repair or replacement  at the  sole discretion of XPC Corporation  The customer is responsible for the costs of shipping the defective  product to XPC Corporation  XPC Corporation will pay for ground shipment of the repaired or  replacement product  This warranty applies only to the original purchaser     If equipment provided by XPC Corporation is found to be Dead on Arrival  DOA   XPC Corporation will  be responsible for the costs of shipping product to and returning equipment from the customer in a  timely manner as agreed to with the customer  once the customer has requested and received a Return  Material Authorization  RMA  number  DOA equipment is defined as equipment that does not properly  function according to user documentation when initially received and connected in conjunction with  proper procedures as shown in the user documentation or via support provided by XPC Corporation  personnel or authorized agents     This warranty shall be void if  a  the equipment is repaired or modified by anyone other than XPC  Corporation or a XPC Corporation approved third party   b  the equipment is damaged by the customer   is improperly used or stored  is subjected to an adverse operating environment  or is operated outside  the limits of its electrical specifications  or  c  the equipment has been used or stored in a manner  contrary to the equipment s operating manual  intended use or other written instructions  Any technical  advice furnished by 
37. onnected equipment does not exceed  the maximum VA rating for the UPS  The maximum VA ratings are shown in the Specifications  section of this document    2  Ensure that the equipment plugged into the battery powered outlets does not exceed the UPS  rated capacity  If UPS rated capacities are exceeded  an overload condition may occur and cause  the UPS to shut down and trip the circuit breaker    3  If the power requirements of your equipment are listed in values other than Volt Amps          convert Watts  W  or Amps  A  into VA by doing the calculations below  Note  The equation  below only calculates the maximum amount of VA that the equipment can use  not what is  typically used by the equipment at any given time  Users should expect usage requirements to  be approximately 6096 of the value to estimate power requirements     Watts  W  x 1 43   VA or Amps  A  x 120   VA    Add the totals for all of the equipment and multiply this total by 0 65 to calculate actual power  requirements     Note  Many factors can affect the amount of power that your computer system will require  The  total load that you will be placing on the battery powered outlets should not exceed 8596 of the  UPS capacity     HARDWARE INSTALLATION GUIDE  Inspect the UPS upon receipt  The packaging is recyclable  keep it for reuse or dispose of properly     Safety Information    Information presented here is vital to all personnel  Please read all Safety information     Storage and Transportation           
38. operating  systems  It can support operating systems such as HP Open View  IBM Netview  SUN Netmanager  etc   This enables the UPS to provide instant UPS and power information over the network  Please contact  your reseller for additional details     Notes    The UPS can be monitored through the RS232 interface or the SNMP card  but only one way at a time   The user can choose RS232 or SNMP communications through the communications switch on the rear  panel of the UPS  RS232 is chosen if the switch is depressed to the RS232 position  and SNMP is chosen if  the switch is depressed to the SNMP position  When there are two or more monitored pieces of  equipment  the ground of each piece of equipment should be shared  The SNMP card is configured as  DHCP by default IP setting     cv rnn Yr  Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 13    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Remote Emergency Power Off            Port    A customer supplied switch located remotely can be used to close the REPO connection and allows the  UPS output receptacles to be switched off  Since the REPO shuts down the equipment immediately   orderly shutdown procedures are not followed by any power management software  The UPS will have  to be manually restarted in order to regain power to the outlets on the UPS     DETERMINING THE POWER REQUIREMENTS OF YOUR  EQUIPMENT    1  Make sure the total Volt Amp  VA  requirements of your c
39. optional battery packs are mounted correctly  and the UPS is disconnected  from input power before proceeding     1  Connect external battery packs  option   CAUTION  CONNECT ONLY BATTERY PACKS PROVIDING THE SAME DC VOLTAGE AS THE  UPS     PLEASE DOUBLE CHECK LABELING ON THE UPS AND BATTERY PACKS TO ASSURE  PROPER VOLTAGES ARE CONNECTED  CONNECTING THE INCORECT BATTERY PACK TO    THE UPS MAY RESULT IN DAMAGE TO THE UPS AND OR BATTERY PACK THAT WILL VOID  THE WARRANTY           Ensure that the UPS is disconnected from      input and is off while connecting the  External Battery Packs  Ensure all battery breakers are in the  OFF  position    e Remove the        covers on the UPS and         Connect the battery cable that comes with  the External Battery Pack between the External Battery Pack to the UPS    e Secure the DC battery cable to the rear of the UPS  and the rear of the        by using       x 8 screws provided  2 each per connector end         Connect the 5 15P from the        to      input AC utility source per specifications        Connect a second battery pack to the first        in the same fashion if more than one is to  be installed    e Refer to Appendix A  Battery Pack User Manual for more details   2  Connect SNMP card  option       Remove the two screws securing the SNMP cover plate on the rear of the UPS  and slide  the SNMP NetAgentll card into the slot  Secure the card into the slot with the two  screws previously removed    3  Close the battery breakers o
40. or of XPC  Products     The Purchaser of this Product is protected  for the term of the XPC Limited Warranty  against certain losses caused by a Power  Disturbance for properly connected electronic equipment  referred to as the  Connected Equipment   subject to certain terms and  conditions provided below     This policy applies only to the original purchaser of the Product  If the Product is transferred or sold to another person or entity   this policy is void     Load Protection Policy Dollar and Period Limits    For purchasers that meet the qualifications and conditions set forth in this policy  XPC will provide reimbursement  cost of repair or  fair market value as determined by         during the period limits and up to the dollar limits stated as follows     NXRT 50 000 Term of XPC Limited Warranty  P80 50 000 Term of XPC Limited Warranty  P90   50000 Term of XPC Limited Warranty    This Load Protection Policy is not deemed  first dollar  coverage  XPC s obligation is reduced by any amounts that the Purchaser is  entitled to recover  from other sources regarding the Connected Equipment  including  but not limited to  insurance  other warranty   extended warranty  or legal liability  regardless of whether or not the Purchaser makes a claim for recovery        Eligibility for Coverage Under the Load Protection Policy    1  The Product must be registered on the XPC website  www xpcc com  within 10 days of purchase  All required information  must be provided  and Purchaser 
41. plier for the location of the Connected Equipment  XPC  will forward to the Purchaser a Load Protection Policy claims form  which must be completed and filed with XPC within 30  days    a  Mark the Load Protection Policy        number on the Product the Purchaser is returning    b  Pack the Product in its original packaging or similar packing materials if the original packaging has been  discarded  Enclose the completed Load Protection Policy claim form and a copy of the Purchaser s original  sales receipt for the Product in the box    c  Mark the RMA number clearly on the outside of the box    d  Ship the Product  one way shipping charges paid by the Purchaser  to    XPC Corporation  230 Yuma Street  Denver  CO 80223  Attn  LPP RMA    3  XPC will evaluate the Product to determine its level of functionality  and will examine the Product for evidence of damage  from a Power Disturbance     a   f XPCs  evaluation provides no evidence of damage from a Power Disturbance  XPC will send to the Purchaser   i  a report summarizing the tests performed and  ii  a rejection of claim notice    b  If the Product shows evidence of damage from a Power Disturbance  XPC will request that all Connected  Equipment for which a Load Protection Policy claim has been submitted  be sent for evaluation to either XPC or  an authorized service center  If it is determined that the Connected Equipment has been damaged by a Power  Disturbance  XPC will  in its sole discretion  issue payment to the Purchas
42. port personnel can more effectively assist you                Cr        Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 4    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        EMC Statements   FCC Part 15    Notice  Pursuant to section 15 of the        rules  this product has been tested and thereby complies  to the conditions of a Class B  NXRT 1000  NXRT 1500  and Class A  NXRT 2000  NXRT 3000  digital  device  which have been established for offering sufficient protection against dangerous interference for  installation in a residential area  Installation and use of the equipment should comply with the  instructions provided in order to avoid such interference due to the amount of radio frequency energy  that is radiated and generated by the equipment  In spite of this  we cannot assure that a certain  amount of interference may not occur in some installations  If  by turning on and off  it can be deduced  that your radio or television reception is found to be influenced by harmful interference from the  equipment  it is recommended to use one of the following preventive measures     e Place the receiving antenna in a separate location or orientation    e   Ensure a greater distance is achieved between the receiver and the equipment       Ensure that your equipment is connected to an outlet on a separate circuit than the  receiver    e Contacta technician experienced with radio and TV or a dealer for further assist
43. should retain a copy for Purchaser   s records  When registering on the website   Purchaser must list all connected equipment that is directly connected to the product  Only those devices registered in  that manner will be covered    2  All Connected Equipment must be UL or CSA approved    3  The Product must be plugged into a properly wired and grounded outlet  Use of input surge devices  extension cords   adapters  ground wires  or electrical connections not manufactured by XPC voids the XPC Load Protection Policy  No  other surge protection device may be connected to the output sockets of the Product  The installation must comply with all  applicable electrical and safety codes set forth pursuant to the NEC    4  The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the  damage    5  The Connected Equipment must have been damaged by a Power Disturbance on a properly installed  grounded  and  National Electric Code              code compliant 120  208  240 Volt AC power line in the United States or Canada  by a  Power Disturbance on standard telephone land line or PBX telephone equipment line that is properly installed and  connected to an RJ11 port on the Product  or by a Power Disturbance on a standard Local Area Network connection that  is properly installed and connected to an RJ45 port on the Product and  d  is directly plugged into  and properly connected  to  the Product in its original condition which was prop
44. sion   XPC  Corporation  Rev 2 7 13  Page 32    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        SPECIFICATIONS     mmm                                  emm       120 VAC  80   138V at 100  load  60 138V at 40  load             Linear  lt  596  non Linear  lt  10   ULU  EL                   mese       mz oxm   w        Overload Capacity 110 150  for 30 sec   gt  150  for 200 msec    Crest Factor 3 1 at full load             Battery           UPS   3 12V 9        36      4  12V 7 2 AH   48V  8  12V 7 2AH   96V    Backup Time 7 11 min  internal batteries  to 18 hours using External Battery Packs  EBP     Battery Type  EBP  E us   da An d 2 strings of  8  12V 7 2 AH   96V    Recharge Time    8 hours to 9096       E  Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 33    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS                               waran          _  17 3  x 17 7  x 3 4  17 3  x 25 6  x 3 4  17 3  x 21 7  x 5 2                 usimerermrimenr      mexmexne                 orm   oem _             _       _____     s                       1  NEMA L5 20R    1  NEMA 15 308  Receptacles           v Tort    4           5 20R      4  NEMA 5 20R  Communication RS 232 or SNMP  optional card   Interface    Included in box UPSILON CD  horizontal brackets  5 1 brackets  manual  6ft DB9 cable    ENVIRONMENT Operating  0   40      32   10437   Temperature    Audible Noise  lt  
45. tery supply   Risk of electric shock  battery circuit 15 not    isolated from AC input  hazardous voltage may exist between battery terminals and ground  Test before  touching     WARNING   Fuses   To reduce the risk of fire  replace only with the same type and size of fuse    WARNING I unit intended for installation in a controlled environment    CAUTION  po not dispose of batteries in a fire  the battery may explode    CAUTION  po not open or mutilate the battery  released electrolyte is harmful to the skin and eyes   CAUTION  A battery can present a risk of electric shock and high short circuit current  The following    precaution should be observed when working on batteries        Remove watches  rings or other metal objects   e Use tools with insulated handles     To reduce the risk of electric shock  disconnect the UPS from the main supply before installing a  computer interface signal cable  Reconnect the power cord only after signaling interconnections have  been made     Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and  the required precautions  Keep unauthorized personnel away from batteries     These UPS units are extremely heavy  Do not install the UPS in a rack or enclosure by its front two ears  only  Adjustable rack rails are required for this type of installation     The instructions contained within this safety manual are deemed important and should be closely  followed at all times during installation and 
46. tructions     SAFE GROUNDING TERMINAL   Indicates primary safe ground    LOAD ON OFF   Pressing the button turns on off the output receptacles and the indicator  light    RJ45 RECEPTACLE   The receptacle provides network interface connections and telephone or  telecommunications equipment should not be plugged into it    Please do not discard of the UPS or the UPS batteries as the UPS may have valve regulated  lead acid batteries  Please recycle batteries appropriately                      4                                 Qe       Xtreme Power Conversion    XPC  Corporation  Rev 2 7 13  Page 7    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        INTRODUCTION    The information provided in this manual covers single phase 1000 3000 VA uninterruptible power  systems  their basic functions  operating procedures  options available and emergency situations  It also  includes information on how to ship  store  handle  and install the equipment  Only detailed  requirements of the UPS units are described herein  and installation must be carried out in accordance  with this manual  Electrical installation must also carefully follow local legislation and regulations  Only  qualified personnel should conduct these installations as failure to acknowledge electrical hazards could  prove to be fatal     PRODUCT DESCRIPTION    Many different kinds of sensitive electrical equipment can be protected by an Uninterruptible Power  Supply  UPS  inclu
47. ty            maintain full battery charge  the AC input power is rectified and regulated in the rectifier  feeding power to the battery converter and inverter       DC power is converted to AC in the inverter  passing it on to the load    e Power is maintained from the battery during a power failure    e The converter increases voltage appropriately for the inverter                   Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 8    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        By pass                           Filter   Rectifier Inverter      Filter  4          Monitoring    DC DC panel  Battery Converter    Control      8      75232 m  Charger amp  Monitoring  battery      Figure 1     Block Diagram    Diagnostic Tests    When the UPS is started  a diagnostic test is automatically executed  checking the electronics and  batteries  reporting any problems on the LCD display  A diagnostic test can also be performed manually  from the front panel at any time     SYSTEM CONFIGURATION    The UPS device and the internal batteries make up the system  Depending on the site and load  requirements of the installation  certain additional options are available for the solution     Planning a UPS system  the following should be taken into consideration        The total demand of the protected system shall dictate the output power rating  VA   Allow     margin for future expansion or calculation inaccuracies from measured
48. us and or operation  Line information will be described from top to bottom with the top  being line one     Line One    Provides data in to numeric sections  with the data corresponding to the applicable category in line one  and two    Line Two    Allows the user to identify which variable information is being displayed        Input  e Output  e Battery  e Load    e Temperature    Line Three    This is a graphics section with load graphics on the left and battery graphics on the right  The failure icon  will appear in this section when a failure occurs                           Xtreme Power Conversion   XPC  Corporation  Rev 2 7 13  Page 12    NXRT 1000  NXRT 1500  NXRT 2000  NXRT 3000 USER S MANUALUNINTERRUPTIBLE POWER SUPPLY  UPS        Line Four    This indicates the status of the UPS     e ONLINE   utility mode     ON BATT   battery mode     ON BPS   bypass mode     UPSOFF  standby mode    RS 232 Standard Interface    The RS 232 interface uses a 9 pin female D sub connector  Information provided includes data about  utility  load and the UPS  The interface port pins and their functions are identified in the following table     GOGO                PIN    FUNCTIONS  1 4 6 7 8 NOT USED    9 _______ REMOTEWAKEUP        CAUTION  MAX RATED VALUES 12VDC       SNMP Communications Option    The UPS provides an intelligent slot for internal or external network card  This special intelligent network  card can be compatible with popular software and hardware found on the web and in 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Manual do Utilizador  Samsung SGH-E808 用戶手冊  Panavision 3D System for NEC 2000C Projector Installation and  IPA TouchPoints Hub User Manual  intext:Installationsanleitung filetype:pdf  DT Research DT362  MANUEL D’INSTRUCTIONS  Franke 112.0188.649  Use and Care Manual  CTA Digital IP-CG mobile telephone part    Copyright © All rights reserved. 