LUXOMAT® DALI/KNX Gateway IP-N
Contents
1. Please follow country specific safety and accident prevention rules as well as all current KNX guidelines e Please follow country specific rules and regulations for the planning and construction of installations especially with regard to emergency lighting systems e For the installation the device must be switched to zero potential Do not open the device Faulty devices must be returned to the manufacturer 6 Technical data Power supplies e Mains connector for 100 to 240V 50 to 60Hz AC or DC e Maximum power consumption 7 W e In addition via KNX bus SELV 24V Connectors e Mains connector L N PE Screw connector 3x 1 2 5 mm single or threaded core e DALI Bus D D Screw connector 2x 1 2 5 mm single or threaded core Bus connector KNX bus connector Ethernet Eth RJ 45 plug connector for standard patch cables Control elements Programming Button to toggle between normal and address ing mode e 3 buttons Move Prg Set ESC on display front to commission the device and set parameters Display elements e LED red Indicates normal addressing mode e LNK LED yellow Signals device Ethernet readiness e ERR LED red Signals fault status e LCDisplay 2x12 characters for the commissioning and configuration menu Inputs e Passive input for connecting pushbuttons with auxiliary voltage e 9 32VDC or 8 26 VAC cable length max 15m Output DALI Bus e Connection of up to 64 ECGs in accordance with
2. be selected The relevant menu position is indicated in the display To navigate within the menu press the relevant buttons briefly The Move button is used to select the next menu item within a level Pressing the Prg Set button briefly accesses the level below Pressing the ESC button exits the selected level and returns to the level above Main menu Level 1 The main menu level level 1 has the following structure The firmware version is indicated The display language can be set in the lower level menu DALI CONTROL In the lower level menu the IP address set in the ETS or assigned by the DHCP server is ADDRESS indicated m U I lt N In the lower level menu on a reinstallation of a DALI segment the connected DALI TALLATION 4 gt g devices are reset and an automatic search for electronic ballasts is started all previously available electronic ballasts are deleted INS In the lower level menu on a post installation of DALI electronic ballasts the automatic search is started and the contiguration is compared if necessary only new electronic ballasts are found and indicated old elec tronic ballasts remain POST INSTALLATION In the lower level menus the electronic ballasts that are found are assigned to the desired DALI groups GROUP ASSIGNMENT In the lower level menus the parameters of the individual groups can be set and modified GROUP PARAMETERS In the lower lev
3. exited The devices must then be assigned to the indi vidual DALI groups The assignment is performed in the GROUP ASSIGNMENT menu item see Operation and menu structure section The assignment of all electronic ballasts to the desired groups completes the basic installation In the GROUP TEST menu item see Operation and menu structure section the individual groups can be switched on and off for test purposes If buttons are connected to the device inputs the button function can be set in the FUNCTION INPUT B1 and B2 menu items and the inputs can be assigned to individual DALI groups This means that even when the KNxX is not yet available DALI func tions can already be executed development mode Of course the inputs can also be used in standard mode to integrate inexpensive standard buttons in the system Finally the last stage of DALI startup is to assign the groups to the individual scenes in the SCENE ASSIGNMENT menu item see Operation and menu structure section Once these steps have been completed the startup of the DALI segment is complete KNX can then be started immediately or later with the ETS and the relevant application program in the usual way 12b Functions of the web browser Once the network connection has been established a web browser e g Microsoft Internet Explorer or Mozilla Firefox can be used to call the startup web page For this option only the IP address URL set in the ETS or assigned autom
4. individually or together ALL CHANNELS Broadcast and the system can therefore be tested GROUP PARAMETERS submenu Level 2 and 3 From the main GROUP PARAMETERS menu the submenu is accessed by briefly pressing the Prg Set button In this menu the indi vidual parameters can be set for each group In general the group parameters should be set in the ETS during KNX startup Direct set tings on the device are only used to quickly change individual parameters GROUP 6 Please note that each ETS download over TEST writes any settings made on the device GROUP TEST FUNCTION INPUT B1 GROUP PARAMETERS In the submenu scroll through the individual DIM CH functions by briefly pressing the Move button In the submenu scroll through the individual INPUT B1 channels by briefly pressing the Move button The first display line indicates the selected The first display line indicates the number of function The following functions can be set the selected channel DIM CH ON CHANNEL ALL gt Switch on when button is pressed In the submenu scroll through the individual See groups by briefly pressing the Move button GROUP 6 ia ee ee OFF Switch off when pute is pressed The first display line indicates the number of OFF gt butor to ccleckwhelherihecalacicd channel DIM CH CH Change when button is pressed the selected group should be switched on or off Briefly press CHANNEL 07 gt ON DIM Press briefly to switch on
5. pressing the Prg Set button In this menu the individual electronic ballasts found by the search can be assigned to the 16 DALI groups and existing assignments can be changed GROUP ASSIGNMENT In the submenu scroll through the various elec ie a tronic ballasts found by briefly pressing the ae Move button The first display line indicates the number of the selected electronic ballast EB No 12 EB When an electronic ballast is selected GROUP 1 gt the connected lamp flashes This enables the programmer to determine which lamp is assigned to the relevant number Hold down the Prg Set button to change to programming mode Briefly press the Move button to set the group to which the electronic ballast should be assigned Once the desired group is selected confirm and save the setting by briefly pressing the Prg Set button On a reinstallation perform this process once for all the electronic ballasts found Pressing the ESC button returns to the level above or the system returns there automatically after approx 30 sec FUNCTION INPUT B1 submenu Level 2 and 3 From the main FUNCTION INPUT B1 menu the submenu is accessed by briefly pressing the Prg Set button In this menu the function of the floating button connected at input B1 can be set GROUP TEST submenu Level 2 and 3 From the main GROUP TEST menu the submenu is accessed by briefly pressing the Prg Set button In this menu all groups can be switched
6. the EB number SIOP teggan SCENEO3 symbol indicates which of the 1 to 16 groups No KNX bus CH DIM Press briefly to change hold XXXX XX P is assigned to the relevant scene An X in SYSTEM gt In the event of a DALI short circuit no other down button for single button the relevant position means that the relevant EB ERROR 34 errors can be detected For all other error dimming group is assigned to the scene A means types several errors can be detected at the SCENE Calleetas whan baion that the group is not assigned The four SYSTEM gt same time Briefly press the Move button pressed characters after the scene number in the first KNX ERROR to switch between the various existing Hold down the Prg Set button to change to display line correspond to groups 1 to 4 from left to right The 12 characters in the second display line correspond to groups 5 to 16 in ascending order from the left Hold down the Prg Set button to change to programming mode A flashing cursor on the first X indicates that group 1 is selected errors within this menu item For lamp and electronic ballast errors the number of the relevant electronic ballast is indicated so that the error can also be located directly within a group Pressing the ESC button returns to the level above or the system returns there automatically after approx 30 sec programming mode Briefly press the Move button to select the channel or scene to which the selec
7. the startup page via the O Change Button The page has the following layout Groups To set a scene first select it on the right hand side e g Scene 1 When selected the scene if already programmed is called in the DALI segment The set light values are displayed in the relevant group windows Use the buttons to individually modif the light values Select the relevant button A AEK AEE BEES ON OFF Dim up Dim down With the mouse click briefly to switch or hold down to dim on the n field to modify the light value for the group The button can be to save the modified value in the selected used to set the assignment of groups for the individual scenes Press the button o scene Press the button to return to the previous page MAN 8229 080514 1
8. IEC 60926 DALIVoltage 16 20 VDC short circuit proof max 250 mA e Category 1 device in accordance with EN 62386 103 No other control devices DALI Master must be used e Additional DALI power supply is not required or permitted Ethernet P connection via Ethernet speed 100 Mbit second e IP address allocation via DHCP service or fixed IP address Connections Bus line KNX bus terminal e Mains supply Screw terminal for individual wires up to 2 5mm or 2 x 1 5mm e DALI bus Screw terminal for individual wires up to 2 5mm or 2 x 1 5mm e Input for connecting pushbuttons each contact Screw terminal for individual wires up to 2 5mm or 2 x 1 5 mm Ethernet RJ45 connector for standard patch cable Mechanical data DALI KNX Gateway IP N casing Plastic ABS VO e Dimensions REG casing 4TE Width 72mm Height 55 mm Length 86mm e Weight 200g e Mounting 35mm DIN rail Electrical safety Pollution class in accordance with EN60664 1 2 Protection type in accordance with EN 60529 IP20 Protection class according to IEC 1140 Overvoltage category Ill KNX Bus eparated extra low voltage SELV DC 24 V DALI Bus Functional extra low voltage FELV DC 18 V base isolation EMC requirements Complies with EN 50090 2 2 Environmental conditions e Weather resistence EN 50090 2 2 Environmental conditions during operation 5 C to 45 C Storage temperature 25 C to 70 C e Rel humidi
9. ae LUXOMAT DALI KNX Installation and operating instructions 1 General use B E G DALI Gateways bring together the crossfunctional KNX installa tion bus and the lighting control specific DALI Bus IEC 60929 Lights with cost effective digital DALI ECGs can therefore be integrated into an overall KNX architecture and operated via the multitude of existing KNX devices The B E G DALI KNX Gateway IP N is a device used to control ECGs with a DALI interface via KNX The device transforms switch and dim commands from the connected KNX system into DALI telegrams and status information from the DALI bus into KNX telegrams The DALI KNX Gateway IP N is a Category 1 device in accordance with EN 62386 103 This means the device must only be used in DALI segments with connected ECGs and not with other DALI control devices within the segment No multi master function Power supply for the up to 64 connected ECGs comes directly from the DALI KNX Gateway IP N An additional DALI power supply is not required and not permitted The device comes in a 4TE wide DIN Rail casing so it can be directly integrated into the mains distribution box Connection to the bus is via a bus connector Network and DALI lines are connected via screw connectors on the device ECGs can be switched dimmed and set to a defined value in 16 groups per gateway In addition to group control the DALI KNX Gateway IP N offers the possibility to individually control up t
10. atically by the DHCP server is called in the browser Please ensure that the full URL from the IP address and the prefix http is specified For example enter http 192 168 1 07 in the browser to launch the page When it is called the web page shown below is displayed in the browser On the web page the higher level startup functions can be executed via the header The header icons have the following meanings and functions O Update This function can be used to update the displayed electronic bal last assignments It is designed for use when additional changes have been made to assignments manually on the device or using the software tool 08 Reinstallation This button starts a reinstallation of the connected DALI seg ment Attention On a reinstallation the entire existing configu ration of the DALI segment is deleted 11 DALI startup via software tool The DALI segment can also be started using the free DALI programming tool For this option the device must already be connected to the KNX bus and a physical address assigned Communication with the device is then via an interface con nected to the KNX yi CCD aeh of L ii oj fe o eo x DALI EB DALI EB DALI EB DALI EB DALI EB OD j ifiloo fess o S KNX Ei For a precise description of the procedure for startup using the tool please refer to the DALI programming tool user manual Post installation T
11. commissioning allocation of DALI ECGs to individual groups and changes in configuration 1 Commissioning on the device 2 Commissioning via integrated web server The ETS Engineering Tool Software with the data base entry of the current application program is also required for the final commission ing of the KNX communication For more details regarding the commissioning of a DALI segment please see the current application program description Gateway IP N R 2 Device types and accessories At present the following device types are available from the DaliControl product group DALI KNX Gateway IP N Part number 90134 3 Scope of delivery The following individual components are included in the delive ry of the DALI KNX Gateway IP N device e Complete device with connected bus connector e 1x heat shrinkable tubing 1 2 x 2 cm for additional insula tion of the bus cable e Operating and mounting instructions e Delivered in break proof individual packaging 4 Application programs The following application programs are currently available for the DALI KNX Gateway IP N device DALI KNX Gateway IP N For application program functions please see the application program description 5 Installation advice e Risk of death by electric shock e The device is intended for interior installation in dry rooms e The device must only be installed and commissioned by an accredited electrical engineer e
12. dicaiasahe number ol ike cekaed lt cene which the selected function is linked Pressing In programming mode the selected param TE E E EE aos the ESC button returns to the level above or eter can be modified by briefly pressing SCENE 2 old down the o re to tall to the system returns there automatically after the Move button Briefly press the Prg Set Call gt programming Moge aney press Ine moye approx 30 sec button to switch between the Call scene button t th t value P i ee A N E and Save scene functions Briefly press the FUNCTION INPUT B2 submenu Level 2 and 3 mode is automatically activated for the next parameter in this group at the same time This means that if for example only the parameter for maximum dimmer value is to be modified the user must first scroll through the switch on value and minimum dimmer Prg Set button again to execute the selected operation and to call or save the set scene Pressing the ESC button returns to the level above or the system returns there automati cally after approx 30 sec From the main FUNCTION INPUT B2 menu the submenu is accessed by briefly pressing the Prg Set button In this menu the function of the floating button connected at input B2 can be set vae parameters nenti eve 2 Pressmg In the submenu scroll through the individual SYSTEM NO ERROR SCENE ASSIGNMENT the submenu is accessed by briefly pressing the Prg Set button In this menu t
13. e Prg Set button to change to rogramming mode Pressing the Prg Set a FROG MIDE button e a starts the vatifieation and search process A search is performed for the connected electronic ballasts using their long address and they are automatically compared with the previous configuration If NEW electronic ballasts have been removed from BALLASTS 1 gt the DALI segment the relevant entries in the device are deleted automatically During the POST INSTALLATION SEARCH V1 DEL ELEC BALLASTS 3 gt DEL NEW verification process the number of deleted BALLASTS devices is indicated 3 1 gt Then a search is performed for new installed devices in the DALI segment Newly added electronic ballasts are reset automatically and any previously set parameters and group assignments are deleted Depending on the number of connected electronic ballasts the search may take a few minutes During the search the number of new devices found is indicated in the display Once the entire process is complete verifica tion and search the number of deleted devices and the number of new devices found are indicated in the display deleted devices new devices from left to right see image on the left Pressing the ESC button returns to the level above or the system returns there automati cally after approx 30sec GROUP ASSIGNMENT submenu Level 2 and 3 From the main GROUP ASSIGNMENT menu the submenu is accessed by briefly
14. el menus the desired and relevant groups can be assigned to the DALI scenes SCENE ASSIGNMENT In the lower level menu the entire system broadcast and the individual groups can be switched on and off for test purposes GROUP TEST In the lower level menu the individual programmed scenes can be called for test purposes SCENE TEST In the lower level menu existing system errors SYSTEM can be called individually TEST In the lower level menus the function of floating button input B1 can be set A as above FUNCTION INPUT B1 FUNCTION INPUT B2 Once all the connections have been made and the supply voltage has been switched on the firmware version is indicated in the display The flashing green PWR LED indicates that the device is ready to operate If the device is started up without KNX the red ERR LED lights up If the ERR LED remains lit even when the KNX voltage is connected this indicates a short circuit within the DALI segment see also SYSTEM TEST submenu below In this case please check the wiring of the DALI segment For the DALI KNX Gateway IP N the DALI segment can also be started up easily via the integrated web server The device has an RJ45 socket on the bottom right hand side above the bus terminal A standard patch cable can be used to connect the device with a switch or router for the IP network Ethernet The connection is usually only required during startup and can be tem
15. he relevant the red error LED to light up can be detected SCENE 03 gt ON DIM DALI groups can be assigned to up to 16 by the system and indicated on the display individual scenes SYSTEM gt e DALI short circuit the ESC button returns to the level above or SYSTEM TEST submenu Level 2 and 3 SCENE fancione by brelly pressing the Move button the system returns there automatically after From the main SYSTEM TEST menu the INPUT B2 The tirdi res la A heselecied l approx 30sec STEN submenu is accessed by briefly pressing the linei pP BA ina functi besel TEST Pay Sale ine ae unction The following tunctions can be set rg et button In this menu any existing error SCENE SCENE ASSIGNMENT submenu Level 2 and 3 states can be called lt SCENE 03 D gt ON E From the main SCENE ASSIGNMENT menu oe If no errors exist this is indicated in the dis OFF Switch off when button is pressed Press briefly to switch on hold down button to dim up with stop er oe telegram In the submenu scroll through the individual A lamp error with indication of the lamp l j SCENEO1 XXXX by brief nale Mech or electronic ballast EB number OFF DIM Press briefly to switch off hold XXXXXXXXXKXX CENS Py Ornety Pressing ne Ove Duhon SYSTEM gt Electronic ballast error with indication of down button to dim down with The first display line indicates the number of the selected scene After the scene number a pe ERRORS 2
16. his button starts a post installation within the DALI segment On a post installation ballasts that no longer exist are deleted and new devices are added Gator Any processes that have been started are aborted by this function Broadcast ON Broadcast OFF These functions send a DALI broadcast telegram to switch all electronic ballasts lamps in the DALI segment on or off change to scene page This button changes to the scene setting page Under the header are the fields that can be used for the identi fication of electronic ballasts and for group assignment For the identification of electronic ballasts all lamps should first be set to a defined value e g OFF using a broadcast Atter the toggle button has been selected the electronic ballasts can be switched on and off individually using the mouse This enables the identification of electronic ballasts arranged in random order Following identification the individual electronic ballasts can be assigned to groups To do this select the assignment button Then use the mouse to select the group to which the bal lasts will be assigned Click on the electronic ballast to assign it to the selected group The group assignment is indicated by a small blue field with the group number in the electronic ballast list Electronic ballasts that are not yet assigned a group have a yellow field with a question mark In principle the position long address of the electr
17. hold Hold down the Prg Set button to change to the Prg Set button to execute the selected down button to dim up with stop CRO Ee gt programming mode In programming mode operation Pressing the ESC button returns to telegram ON VALUES 100 the parameter type and the set value are the level above or the system returns there OFF DIM Press briefly to switch off hold indicated in the second display line The fol automatically after approx 30 sec GROUP 12 lowing parameters can be modified directly MIN DIM P on the device down button to dim down with stop telegram CH DIM Press briefly to change hold down button for single button dimming SCENE Call scene when button is SCENE TEST submenu Level 2 and 3 From the main SCENE TEST menu the a O to 100 in 5 increments stats submenu is accessed by briefly pressing i TES the Prg Set button In this menu all scenes Switch on value Minimum dimmer value 0 15 40 tind A neremenis can be called for test purposes or newly set GROUP 12 gt Maz di lue lighting situations can be assigned to the pressed DIM TIME 10s Maximum i ia VUS relevant scene Hold down the Prg Set button to change to 50 to 100 in 5 increments E i de Brief hen N 3 o Briefly press the Move button to scroll through ai n Aaea a a Dimming time for dimming from 0 100 SCENE 2 the individual scenes The first display line button to select the channel or scene to 5 sec to 60sec TEST
18. ls Once the device has been mounted the connecting cable for the DALI bus should be led to the top left terminal Accord ing to familiy of standards EN 62386 DALI control lines can be led together with the power line in a 5 wire cable single basic insulation is sufficient However clear marking must be en sured For the entire DALI installation in a segment a maximum line length of 300m must not be exceeded recommended cross section 1 5 mm Once the DALI line is connected the two external pushbuttons can be connected according to the connection scheme if required The button inputs are passive which means that an auxiliary voltage of 8 26V AC or 9 32V DC is required The mains voltage is connected to the bottom right hand termi nal according to the instructions marked on the casing To connect the KNX line a standard bus terminal is inserted in the corresponding terminal slot on the device Ensure double basic insulation between the KNX installation and the mains voltage To do this provide additional insulation on the wires of the KNX line to the bus terminal using the shrink sleeve provided 9 Operation and menu structure It is possible to start up the connected DALI segment and set and modify the DALI parameters using just the three buttons Move Set Prg ESC and the 2 x 12 character display on the front of the device The operating concept is menu driven Depending on the menu position up to two sublevels can
19. o 64 ECGs Please remember that once ECGs have been assigned to a group they can no longer be controlled individually An ECG can only be allocated to one DALI group The DALI KNX Gateway IP N does not support multi group allocations If multi group allocation is required it must be performed via KNX communication objects Numerous communication objects are available for the visualisation of status and error information on an ECG as well as group and gateway level Current application 11 communication objects per ECG and 8 communication objects per group numerous individual objects In addition to all standard operating devices the DALI KNX Gate way IP N also allows the control of individual battery emergency lights EN 62386 202 For individual battery emergency lights a distinction is made between devices with switchable ECGs usually emergency lights with one ECG and devices with non switchable ECGs converters which are usually used in connection with another normal ECG 2 ECGs per light The DALI KNX Gateway IP N allows for the mixed control of different ECG types within a DALI segment Emergency lighting systems with a central battery are also supported A scene module for the extensive programming of up to 16 scenes from groups and individual ECGs as well as an effect module for the control of processes and light effects are also available on the device The DALI KNX Gateway IP N enables different forms of DALI
20. onic ballasts within the DALI segment is random On a reinstallation the system searches for addresses automatically and enters a short address from 0 63 in the electronic ballast list To enable electronic ballast positions to be moved to a specific location the positions of two electronic ballasts can be swapped using the Swap button First press the Swap button and then click on two electronic ballasts in the electronic ballast list to swap them over 12a DALI startup via web server In addition to startup via buttons or via the software tool DALI startup can be completed easily using the web server integrat ed in the device For this option the DALI KNX Gateway 2 IP can be connected directly to the IP network On the bottom left hand side of the casing above the KNX bus terminal there is an RJ45 socket A standard patch cable can be used to con nect the device with a switch hub or router for the IP network Since the network connection is only required during startup a temporary connection is usually sufficient Once the process is complete the network connection can be removed again Of course a WLAN access point can also be used as a network coupler In this case startup can also be completed via a port able notebook PDA or similar device i pe Il In addition to identification and the assignment of groups the scene values and scene assignments can be set on another web page The scene page is accessed from
21. porary Once startup is complete the Ethernet connection is no longer required for normal operation When connecting the network connection run the cable carefully to ensure sufficient distance between the IP cable and the mains supply To activate a process or change a parameter setting in a lower level change to programming mode at the selected point by holding the Prg Set button for gt 2sec When the relevant function is in programming mode a g symbol appears in the display If programming mode is active a parameter or setting can be modified by pressing the Move button Pressing the Prg Set button again briefly exits the process The set param eter is saved or the relevant process is activated DALI KNX Gateway submenu Level 2 From the main Dali Control menu the DALI CONTROL LANGUAGE submenu is accessed by briefly pressing the Prg Set button The submenu indicates the display language that is currently set Hold down the Prg Set button to change to programming mode Then use the Move button to select the language GERMAN ENGLISH FRENCH SPANISH SWEDISH Press the Prg Set button briefly to confirm the selection The set parameter is saved and the display now operates in the relevant language LANGUAGE ENGLISH lt N IP ADDRESS submenu Level 2 From the main IP ADDRESS menu the submenu is accessed by briefly pressing the Prg Set button IP ADDRESS In the submenu the IP address set in the ETS or a
22. ssigned by the DHCP server in the IP network is indicated The setting cannot be modified on the device It must be set via the ETS or via DHCP IP 192 168 004 101 REINSTALLATION submenu Level 2 ae From the main REINSTALLATION menu the SEARCH via PROG MODE submenu is ac INSTALLATION T sessed by briefly pressing the Prg Set button Hold down the Prg Set button to change to programming mode Pressing the Prg Set button again briefly starts the initialisation and search process First all electronic ballasts connected to the DALI segment are reset automatically and any previously set pa rameters and group assignments are deleted Then a search is performed for the connected electronic ballasts using their randomly gen erated long address and they are detected automatically in ascending order Depending on the number of connected electronic ballasts the search may take a few minutes When the search is complete the number of electronic ballasts found is indicated in the display Pressing the ESC button returns to the level above or the system returns there automatically after approx 30 sec SEARCH via PROG MODE ELECTRONIC BALLASTS 47 gt DALI EB DALI EB DALI EB l Iiz iii r m OS e E EKI Iifiles ws o KNX POST INSTALLATION submenu Level 2 From the main POST INSTALLATION menu the SEARCH via PROG MODE submenu is accessed by briefly pressing the Prg Set button Hold down th
23. ted function is linked Pressing the ESC button returns to the level above or the system returns there automatically after ap prox 30 sec Briefly press the Move button to select whether the relevant group should be assigned to the selected scene change between X and character Briefly press the Prg Set button to move the cursor to the next group so that it can be set Once all 16 groups have been processed the setting is saved and taken into account during the next scene programming When the Prg Set button is pressed for the last time the system returns automatically to the level above Pressing the ESC button returns to the level above without saving any changes made or the system returns there automatically after approx 30 sec when no button is pressed 10 DALI startup via the device buttons and the display Once the wiring is complete according to the above connec tion diagram the DALI line can be started up The installer can initiate startup independent of KNX startup If no KNX is connected the red ERR LED lights up to indicate an error However DALI startup can still be continued For initial startup first search the DALI line for connected electronic ballasts The search is started in the REINSTALLATION menu item see Operation and menu structure section Once all the connected devices have been found indicated by an ESC behind the number of found devices shown in the display this menu item can be
24. ty non condensing 5 to 93 Certification KNX certified CE Signage According to EMC Guidelines Residential and commercial build ings Low Voltage guidelines 7 Location and function of indication and control elements The device connectors as well as the programming button and programming LED that are required for commissioning are only accessible in the distribution box when the cover is removed The 3 buttons MOVE Prg Set ESC that are required to commission and configure the DALI and the 2 line display and control LEDs ERR und LNK are accessible when the cover is closed The following connectors can be found on the underside of the REG casing left to right Al RJ 45 plug for Ethernet connection A2 KNX bus connector A3 Power supply connector The following elements can be found on the upper side of the REG casing left to right A4 DALI output connector A5 Programming LED for normal addressing mode A6 Programming button normal addressing mode The following elements can be found on the device front A7 MOVE button A8 Prg Set button A9 ESC button A10 Error LED A11 Ethernet LNK LED A12 Display 2x12 characters for DALI configuration You must follow the terminal pin assignment as labelled on the casing AY A7 A8 Al Al 8 Installation and wiring The DALI KNX Gateway IP N is a REG device and is therefore suitable for direct mounting in consumer units on 35 mm DIN rai
Download Pdf Manuals
Related Search
Related Contents
Cables Direct USB 3.0 to HDMI Pdf 288.34 KB 5.本体のたたみ方 4.本体の組立て方 2.各部の名称 3.仕様 安全上 Bedienungsanleitung Operation Manual Mode d`emploi ATD Tools ATD-8031 User's Manual IDEA 2015 Inspiring the Next Generation Hynes Convention Center User Manual Lightweight Wheelchair +050004122-29_r_1-2 PJEZ DISTR_GB e SPA.indd Manuale di installazione e funzionamento Registratore videografico Copyright © All rights reserved.