1. 28 AAY2000IKI04 Installation manual 5 3 1 Description of cable inlets Ingeteam Power Technology S A Ingecon uWind units have cable inlets through the bottom of the housing Each type is described below Quick connectors for DC connection The cables from the wind generator may be connected using the following quick connectors The packaging includes two cables fitted with aerial connectors at one end for connecting directly to the inverter Note that these are marked and Respect the polarity Quick connector for AC connection This is a Wieland quick two pole connector plus ground Quick connector for communications This is a female quick connector A cable with a compatible connector must be connected Multi purpose glands Multi purpose cable glands can be requested as an option If these are not requested the plate will be supplied with its hole pre cut to be able to open it If the hole is opened and a cable gland is not fitted for correctly installed units the unit will lose its IP65 protection rating Two to six M12 cable glands and or one M20 cable gland are suitable for one or more cables This entrance can be used for Access to the DC connection by cable Access to the insulation fault con
2. Connectors to be joined 5 3 2 Order of connecting the unit The basic connections to be made with the inverter are as follows in this order Connecting auxiliary equipment optional Communication line optional Connecting the inverter and the transformer in units which include one Connecting the Ingecon Wind Interface communications cable optional 1 2 3 4 Connecting the inverter to the grid 5 6 Connecting the DC cables from the wind generator or the Ingecon uWind Interface depending on the configuration selected The following sections describe how to make these connections 5 3 3 System wiring diagram The layout will correspond to those in the figures in the majority of installations The regulations applicable to each installation and to each country in which the inverter is located must always be observed 30 AAY2000IKI04 Installation manual Ingeteam Power Technology S A TL unit electrical diagram For Ingecon Wind 2 5TL 3TL 3 3TL 3 68TL 4 6TL 5TL and 6TL Electricity company panel thermomagnetic counter rid circuit breaker kWh gr gt wind generator inverter Electrical diagram for units with transformers For Ingecon uWind 2 5 3 3 and 5 Electricity company panel E thermomagnetic counter id circuit breaker kWh gri gt wind generator inverter
3. Guidelines are provided in this section for choosing a suitable environment and adapting the unit to it properly 2 1 1 Environment Place the units in a place which is accessible for installation and maintenance work and which permits use of the keyboard and the reading of the front indicator LEDs Never place any object on top of the unit The radiator can reach 85 C Do not place any material sensitive to the high surrounding air tempera tures close to the inverter 2 1 2 IP rating Ingecon uWind units have an IP65 level of protection against external agents which enables them to be installed outdoors IP65 means that the unit is fully protected against the ingress of dust and also against water jets from any direction as defined for this level of protection in standard EC60529 However excessive moisture can cause a safety shutdown of the unit to protect it Hence the following is recommended Locate the units in a place protected from rain and avoiding corrosive atmospheres 2 1 3 Ambient temperature Ingecon uWind units are designed to operate at between 20 C and 70 C To operate in HT mode the maximum ambient temperature must not exceed 45 C To operate in HP mode the maximum ambient temperature must not exceed 40 C 2 1 4 Atmospheric conditions The ambient air must be clean and relative humidity must not exceed 50 at over 40 C Higher levels of relative humidity up to 95 can be tolerat
4. must be made when the unit is suspended as explained in Section 5 2 Fixing the unit to the wall The figure shows the approximate distances between the horizontal line formed by the three upper drilled holes and where the bottom hole will be It also shows the approximate vertical distance to the level of the top edge of the inverter which will subsequently be attached to the transformer fixed to the wall D z F R O y 100_ _ 100 il LO N _ 2 2 Environmental characteristics The environmental conditions for operation are Ambient conditions Minimum temperature 20 C Minimum surrounding air temperature 20 C Minimum surrounding air temperature ORC Maximum relative humidity without 95 condensation For further information see Chapter 3 Operating conservation and transport conditions 2 3 EMC requirements The Ingecon uWind units are equipped with the necessary filtering elements to comply with EMC requirements for industrial applications in order to prevent disturbances in other equipment outside the installation 16 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 3 Operating conservation and transport conditions Failure to follow the instructions provided in thi
5. 7 clock automatically changes the time from summer to winter and z vice versa MAIN MENU Each time LOK is pressed the data blinks in the top part of the Monitoring display where it is shown to be operating in the following order Configuration hours minutes day month and year Language Selection Cae n a The part of the date or time which it is desired to modify is changed using the L N and LX keys The new date and L time are stored by pressing LOK while the year is blinking The p z following message is shown on the screen CHANGE DATE Pressing LOK again confirms the selection Save OK Cancel ESC 8 8 Start Stop The operation of the inverter can be stopped and started P 11 23 11 01 120 manually using this menu i f MAIN MENU The Start or Stop status remains unchanged even if the unit loses its power supply Change date Start Stop Partial Data Reset Change inv number 48 AAY2000IKI04 Installation manual Ingeteam Power Technology S A Press OK to toggle from one status to the other The following i 11 23 11 01 12 1 message is shown on the screen START STOP Change to Stop 0K Cancel ESC Select the desired option and press LOK again The stopped status is maintained until the menu is accessed again 8 9 Reset partial data The partial counters Part E Tp con and Npcon are set to zero from this menu P
6. Inverter number 0001 Process finished OK Save 0K Cancel ESC b e d d 8 11 Autotest In some of the unit configurations there is an additional Autotest P 11 23 11 01 12 7 submenu In these configurations this additional submenu will 3 appear at the end of the main menu MAIN MENU Press LOK on Autotest to access the menu Sta rt Stop Partial Data Reset Change inv number Autotest d Once in the menu you can carry out tests on the voltage and P 11 23 11 01 12 frequency protections by varying their limits and checking that p they disconnect correctly To do this use the L N and D AUTOTEST keys to access the Start Autotest and Results functions The Start Autotest status of the process is displayed at the bottom of the screen at Results the same time The memory has capacity only for the data of one complete Autotest which means that any previous Autotest data Status Start is automatically deleted E S The statuses through which the Autotest algorithm passes and which are shown at the bottom of the screen are Start An Autotest process is starting Not Done There is no Autotest in progress Vmax When it is evaluating the upper limit for voltage protection This shows the voltage protection value as the algorithm varies it until disconnection is confirmed Reconnection Each time a Vmax Vmin Fmax or Fmin status is completed the connection status appears to indicate that it is starting the
7. gt ESPANA gt gt gt DEUTSCHLAND VDE0126 1 1 ENGLAND CONTINUE 31F0 gt DEUTSCHLAND Confirm OK ITALIA a P a a 42 AAY2000IKI04 Installation manual Ingeteam Power Technology S A When ESPA A is changed to any other Country you will be asked a for Password 2 Password 2 is specific and non transferable for Lo 11401412 each unit and will appear on the following screen in which the COUNTRY REGULATIONS assword will be input p il Password 2 K UR R E A On pressing LOK a screen will appear showing the waiting i 11 23 11 01 12 1 oe e configuration is taking place Its appearance is COUNTRY REGULATIONS While this screen is displayed various internal actions take ESPANA RD1663 gt gt gt place gt gt gt DEUTSCHLAND VDE0126 1 1 Sending of a configuration change command to the N ae Request for reading of configuration Awaiting response Configuration Once configuration has been 100 completed the following P 11 23 11 01 120 screen will appear COUNTRY REGULATIONS ESPA A RD1663 gt gt gt gt gt gt DEUTSCHLAND VDE0126 1 1 Prozess beendet OK E To complete the configuration change the unit must be marked appropriately There is a space on the ratings plate on which to mark some of the standards with which the unit complies because this is the way the authorities having jurisdiction require it The standards which it is obligatory to mark are VDE0126 1 1 for changes to configur
8. power to the grid 6 2 2 Settings Change date Go to the Change date menu Adjust the date and time of the unit s internal clock Section 8 6 Language selection explains how to do this Check that the monitored variables have coherent values using the keyboard and flat screen AAY2000IKI04 37 Ingeteam Power Technology S A Installation manual 7 Preventive maintenance The recommended preventive maintenance tasks must be carried out at least ANUALLY except where otherwise stated 7 1 Maintenance tasks The various maintenance tasks must be performed by qualified personnel Danger of electric shock To access the inside of the unit the safety recommendations of Chapter 4 Safety instructions must be taken into account All the maintenance checks included here must be carried out with the machine stopped under safe conditions for handling including those specified by the client for these types of operation Status of the enclosure A visual check of the condition of the housing must be carried out confirming the condition of the seals and the cover as well as the fixing of the units to their anchor points both at the wall and on the transformer if these exist In addition the condition of the enclosure must be checked for dents or scratches that might degrade the cabinet or cause it to lose its protection classification If these types of defect are noticed the affected parts must be repaired or rep
9. secured firmly and is not at risk of falling Isolating switch Check that the isolating switch is in the ON position 6 1 2 Hermetic sealing of the unit It must be ensured during installation operations that the unit s level of sealing has not been altered during connec tion of the unit Check that the connectors are tight and the cable glands are properly sealed Auxiliary connections In these connections through cable glands give cable pipes sufficient length so that they do not pull on the internal electrical connection terminals Make sure that the unused knock outs have not been opened Firmly tighten the cable glands to guarantee sealing Display cable If the front cover has been opened at any time ensure that the cable to the display remains firmly connected Cover If the front cover has been opened at any time attach it to the unit using its four screws as follows 1 Lubricate the screws 2 Ensure that the cover is correctly aligned with the housing This can be confirmed easily by checking that the holes in the cover and the housing mate 3 Manually insert the four screws into their threaded holes starting at the top right followed by the bottom left and finally the other two 4 Tighten the screws until a maximum torque of 5 Nm is applied to each with a calibrated tool 5 Check that sealing is conserved AAY2000IKI04 35 Ingeteam Power Technology S A Installation manual The guarantee does not cover dama
10. their meaning can be seen below DANGER Electric shock Dangerous voltage warning Warns of high voltage which can cause injury or even death and or damage to the equipment General warning Warns of conditions which might cause injury and or damage to the equipment Caution hot surface Warns of the existence of hot parts which may cause serious burns gt gt e The specific safety warnings and notes which affect specific tasks are included in each affected chapter and are repeated and completed in the corresponding critical points Please read this information carefully as it is written for your personal safety and to ensure the longest possible service life for the unit and the devices to which it is connected Y A 3 Definition of tasks to be carried out Installation start up inspection and maintenance operations may only be carried out by personnel appropriately qualified and trained in electrical subjects hereinafter qualified personnel You are reminded of the obligation to comply with the legislation applicable to electrical work An open enclosure never implies an absence of voltage in the unit so only qualified personnel may access the unit following the safe operation guidelines stipulated in this document at all times The set of conditions listed below should be considered as minimum requirements It is always prefer able to shut off the general power Installation defects may result in unwanted feedb
11. 1 DEMO 100010060001 DEMO 100010060001 TRANSFORMER 2011 2011 Unit packaging will be of the following size AAY2000IKI04 Label for Ingecon uWind 5 and transformer 17 Ingeteam Power Technology S A Installation manual Model O Packaging type Weight kg Length x Depth x Height mm 23M SL End 203 with no transformer ale Sri Sana SS 217 with no transformer SSL LET SL SUL ane 5 Cardboard box with foam 253 600 x 400 x 250 with no transformer Transformer 2 5 and 27 transformer 3 3 Transformer 5 43 7 Unpacking The serial number S N of the equipment is its unique identifier This number must be quoted in any communication with Ingeteam INGETEAM POWER TECHNOLOGY S A Ingeteam Avenida Ciudad de la Innovaci n 13 31621 Sarriguren Spain www ingeteam com Ingecon Wind Ingecon Wind 2 5 TL 2500 W 230 Vie 50 Hz 1 125 550 Vo 100110070001 2011 NUV g s o E oroso DEMO 100010060001 A A O Never stack more than 20 TL units or more than 10 units with their transformers on a Europallet In the case of units with transformers the transformers must be laid on the first two layers and half the third Transport damage If the equipment has been damaged during transport 1 Do not proceed with the installation 2 Notify the distributor imm
12. 4 kg depending on its power 3 Do not release the unit until it is perfectly secured or placed 4 Ask someone else to guide the movements to be made AAY2000IKI04 19 Ingeteam Power Technology S A Installation manual 3 4 Storage If the unit is not installed immediately after receipt the following points should be taken into account in order to prevent damage The package must be stored in the position in which the box arrived Keep the unit free of dirt dust shavings grease etc and away from rodents Keep away from water splashes welding sparks etc Cover the unit with a breathable protective material in order to prevent condensation due to ambient humidity Units in storage must not be subjected to climate conditions other than those indicated in Section 2 2 Environmental characteristics It is very important to protect the unit from chemical products which can cause corrosion as well as from salty atmospheres 3 5 Conservation In order to permit correct conservation of the units they must not be removed from their original packaging until it is time to install them In case of prolonged storage the use of dry places avoiding as far as possible sharp changes in temperature is recommended Deterioration of the packaging tears holes etc prevents the units from being kept in optimum conditions before installation Ingeteam Energy S A accepts no liability for damage in the case o
13. AIN MENU CONFIGURATION Monitoring COUNTRY REGULATIONS Configuration GRID VOLTAGE Language Selection GROUNDING Change date V F ADJUSTMENTS AUXILIARY RELAY a d E a The following passwords are necessary for some configuration changes Password Password 2 Password 3 Given that configuration changes occur in extraordinary installation situations the passwords are not supplied with the unit but rather need to be requested from Ingeteam s Sales Department The menu will display only the configurations corresponding to the device hardware The various available configuration changes are described below 8 5 1 Country Regulations Press LOK on option COUNTRY REGULATIONS in the submenu Configuration sr Mis 11 01 12 CONFIGURATION COUNTRY REGULATIONS COUNTRY REGULATIONS Country ESPA A GRID VOLTAGE Standard RD1663 GROUNDING Code 1 31F0 V F ADJUSTMENTS AUXILIARY RELAY b A a To make a change to COUNTRY REGULATIONS first press the LN key followed by LESC and then keep them both pressed for 4 seconds A list of COUNTRY REGULATIONS will appear on the screen The gt sign shows the current selection Select the COUNTRY REGULATIONS you wish to change using the LA and gt keys then press OK The following screen will be shown Press to confirm MERA 11 01 120 11 23 11 01 120 COUNTRY REGULATIONS COUNTRY REGULATIONS DANMARK ESPANA RD1663 gt gt
14. Change date Start Stop Partial Data Reset Change inv number menu 8 4 Monitoring This is accessed by pressing LOK once the Monitoring menu has been selected Six screens will appear showing the main variables being moni tored The right hand screen shows the first one You can move through them using the LA and LX keys 11 23 11 01 12 MAIN MENU Monitoring Configuration Installation manual 11 23 11 01 12 MAIN MENU Change date Start Stop Partial Data Reset Change inv number E ai This displays the main internal parameters and variables that indicate the operation status Certain firmware parameters can be changed in this menu to adapt it to different operating The display language can be selected in this menu The inverter time can be adjusted in this menu Inverter operation can be started and stopped manually from this menu Sets the partial data for Part E Tp con and Npcon to zero The inverter is allocated an identifying number within the wind farm installation from this Language Selection Change date 11 23 11 01 12 MONITORING Pout 5000 W Vac 239 V lac Alas A Fac 49 89 Hz PhiCos 0 998 b d See below for the structure and interpretation of the variables in this menu Screen 1 Pout Power W which the inverter is delivering to the grid Vsal Inverter output voltage V in the electricity grid connection lac Inverter output curre
15. Ingeteam Ingecon pWind Installation manual AAY2000IKI04_ Ingeteam Power Technology S A 02 2012 Energy Avda Ciudad de la Innovaci n 13 31621 SARRIGUREN Navarra Spain Tel 34 948 28 80 00 Fax 34 948 28 80 01 e mail solar energy ingeteam com Service Call Center 34 948 698 715 The copy distribution or use of this document or of its content requires written authorisation Any breach thereof will be reported for damages All rights reserved including those of patent rights or design registration The conformity of the document content with the hardware described has been checked However discrepancies may exist Liability will not be assumed for total concordance The information contained in this document is regularly reviewed and it is possible that there may be changes in subsequent editions Other functions may be available which are not covered by this document This document may be changed Installation manual Ingeteam Power Technology S A Important safety precautions This manual contains important instructions for the installation handling and use of the following models Ingecon uWind 2 5 TL Ingecon uWind 2 5 Ingecon Wind 3 TL Ingecon Wind 3 3 Ingecon uWind 3 3 TL Ingecon uWind 5 Ingecon uWind 3 68 TL Ingecon uWind 3 8 TL Ingecon uWind 4 6 TL Ingecon uWind 5 TL Ingecon uWind 6 TL and any models derived from these This manual should be read carefully and kept in
16. Le INSPECTION task ii ada NES 22 A322 Control tas KSinR EEEE RE Ea T EO a 22 4 3 3 Handling TASKS reiri Sinaia sicda cians a ico 22 AA ii a aaa n ap E E A A a E O a a E A 22 4 4 1 General risks existing and preventive MeasSuresS occccooncccccnncocnncnonnonnnnononnnoncnnnnnnnnnnnnonnnnnnnnnnonaninnn 23 4 4 2 Additional risks and measures in handling tasks ccccceecccseccceeececeeeeseeeeseeeeeeeeceseeeeseeeessueeeanes 23 4 4 3 Personal Protection Equipment PPE cccccccsseeeeeeeeeeeeecaeeeeceecaeeeeeeeeeeeeeeaeceeeessaeeeeeesaaeees 23 A 5 lnspection Control amd handling tasks a csicesiceevceusuadenastiguastitaiteaw ai Ras 24 4 51 o ole ccsosencdutad ad nOrecin doanceundaaguees E E EE N EEG 24 A522 COntrOl TASKS cimen EAEE A EEE E A OE E AEA EA 24 4 5 3 Handling taS Sit a a r ei ae ne aa ian iiaea aoai 24 5 Installation a AAA A a a a a 25 5 1 General requirements for installation cocido reco dc cena naria Daris Aa E 25 5 2 Fixin the Unit to the Wall serer aad aE ARP A as aa an E A E A EA 25 A eean aaa a aaa aeaiia a a DRE a ana iE e E E A A 25 Umitswith a transtera a E EEE ESA Ea a an a E eE 26 5 3 Electrical COMMON srecen aain E dad i i 28 5 31 Description of cable Inlet syrene aN EA NRE E AEAEE ANE RENAR 29 Quick connectors for DC connection ccccceeeceeeeceeaeeeeeeeceeeeeeecaeeeeceeaaeeeeeesaeneeeessaeeeeessaneeeeesaenees 29 AAY2000IKI04 vil Ingeteam Power Technology S A Installation man
17. a safe place General warnings The operations described in the manual may be performed only by qualified personnel The status of qualified personnel referred to in this manual will be as a minimum that which meets all the standards regulations and laws regarding safety applicable to the tasks of installing and oper ating this unit The responsibility for designating qualified personnel will always fall to the company to which the personnel belong It is necessary to decide which workers are suitable or not for carrying out specific work to preserve their safety at the same time as complying with occupational safety legislation These companies are responsible for providing appropriate training in electrical equipment to their personnel and for familiarising them with the contents of this manual All applicable safety related legislation for electrical work must be complied with Danger of electric shock Compliance with the safety instructions set out in this manual or in the suggested legislation does not imply exemption from other specific standards for the installation place country or other circum stances that affect the inverter Opening the door of the housing does not imply there is no voltage inside The risk of electric shock exists even after disconnecting from the grid the wind generator and the auxiliary supplies Only qualified personnel may open it following the instructions in this manual In units which inclu
18. ack Danger of electric shock gt gt bp AAY2000IKI04 21 Ingeteam Power Technology S A Installation manual In addition to the safety measures indicated in this manual the general measures that apply in this area specific to the installation country etc must be taken into account The electrical installation must not involve a risk of fire or explosion Workers must be duly protected against accident risks from direct or indirect contact The electrical installation and protection devices must take the voltage the external determining factors and the competence of the people who have access to parts of the installation into account All equipment must be appropriate to protect exposed workers against the risk of direct or indirect contacts In any case the electrical parts of the work equipment must comply with that laid down in the corresponding specific regulations All workers who carry out work outdoors must suspend their work in the case of storms rain or strong winds snow or any other unfavourable environmental condition which makes visibility or handling tools difficult Work on installations directly connected to overhead electricity lines must be inter rupted in the case of storms Ingeteam accepts no liability for any damages caused by improper use of the equipment Any work carried out on any equipment which implies a modification of the original electrical arrangements must be proposed in advance to Ingeteam T
19. ation for GERMANY and FRANCE RTC alle rete BT Enel Distribuzione CEl 11 20 2000 CEI 11 20 V1 2004 CEI 0 20 CEI 0 16 for changes to configuration for ITALY Two labels will be included together with the unit documentation to stick under the ratings plate in these cases The following illustration shows where these are to be located AAY2000IKI04 43 Ingeteam Power Technology S A INGETEAM POWER TECHNOLOGY S A Ingeteam Avenida Ciudad de la Innovaci n 13 31621 Sarriguren Spain www ingeteam com INGECON Wind Ingecon Wind 2 5 TL 2500 W 230 V 50 Hz 1 125 550 Vo 100110070001 2011 gn TU o o o O tly e 9705009 DEMO 100010060001 A O Installation manual INGETEAM POWER TECHNOLOGY S A Ingeteam Avenida Ciudad de la Innovaci n 13 31621 Sarriguren Spain www ingeteam com INGECON Wind Ingecon Wind 2 5 TL 2500 W 230 Va 50 Hz 1 125 550 Vo 100110070001 2011 s 9105009 DEMO 100010060001 A A Q RTC alle rete Enel Distribuzione CEI 11 20 CEI 11 20 V1 CEI 0 20 CEI 0 16 Never place the label unless the inverter fulfils the identified configuration Incorrectly marking a unit can constitute a breach of laws or regulations Ingeteam accepts no liability for the consequences which can result from erroneous or fraudulent marking of its units due to failure t
20. ccompanied by this message on the display the problem is that the external fan is not working correctly Check that no foreign bodies have entered the fan preventing it turning Ensure that an adequate flow of air arrives 1 second flash The internal fan is not working correctly Contact Ingeteam 3 second flash The inverter is in self limiting mode because it has reached the maximum permissible temperature In this situation check that the fans are running that the air inlets and vents are free from obstacles and that there are no sources of intense heat near the inverter If the problem persists contact Ingeteam 52 AAY2000IKI04 Installation manual Ingeteam Power Technology S A Steady light This LED indicates that an alarm has occurred in the inverter Shown below are some of the alarms which can indicate problems in the inverter which can be checked and or resolved 0400H Manual shutdown The unit has been stopped manually Check that the manual stop is not activated If it is release it from the display 0001H Vin out of range 0002H Grid frequency out of range 0004H Grid voltage out of range The most probably cause is a network power failure lt must be borne in mind that the alarms are additive hence when this fault occurs the alarm shown will be 0006h which is the sum of 0002H 0004H When power returns the inverter will restart If not check the connections to the grid If the grid has the appropriate gri
21. con pWind 3 3 Ingecon uWind 3 3 TL Ingecon uWind 3 68 TL 14 AAY2000IKI04 Installation manual Ingeteam Power Technology S A Forced convection 2 fans Te POOOOO F 0900 O Ingecon Wind 3 8 TL Ingecon Wind 4 6 TL Ingecon uWind 5 Ingecon uWind 5 TL Ingecon uWind 6 TL 2 1 8 Support surface and fastening To guarantee good heat evacuation and promote sealing the units must be placed on a perfectly vertical wall or failing this with a slight slope of a maximum of 10 or 10 with respect to the vertical A solid wall must be reserved for fixing the inverter It must be possible to drill the wall and fit suitable wall plugs and bolts to support the unit s weight In the Ingecon Wind TL packaging you will find a full scale template of the equipment to help you to mark the fixing holes in the wall AAY2000IKI04 15 Ingeteam Power Technology S A Installation manual For TL models the distance between drilled holes will be as follows 80 200 80 160 324 In models with transformers it is the transformer which will be secured to the wall The inverter will subsequently be fixed to the transformer The three upper drilled holes are made first The measurements to be used are shown in the figure The bottom hole
22. d quality parameters check the grid connections If the problem persists contact the installer 0020H Insulation fault in DC circuit There are three possible causes There is an insulation fault on wind generator grounding circuit The varistor thermal fuse protection has tripped The fault current or differential current protection has tripped An insulation fault can pose a hazard to personnel The repair of an insulation fault must be carried out by qualified personnel Procedure to determine the cause of the insulation fault 1 Disconnect the wind generator from the inverter 2 Open the inverter taking the safety warnings in this section into account and treating the operation as handling with which that laid down for handling operations in Section 4 will apply 3 Remove the varistors 4 Check with a multimeter that there is high impedance in the varistor terminals and continuity in the thermal fuse terminals If this is not the case the varistor thermal fuse which does not pass the check above will need to be replaced 5 Ifthe problem persists and the check is correct contact Ingeteam 6 Correctly insert the three varistors before closing the unit 9 1 3 Red LED This is the continuously lit LED indicating that the inverter is manually stopped To start it up this must be done manually as the Start or Stop status does not change even when the unit loses power In the main menu highl
23. de an isolating switch never switch from OFF to ON without first ensuring there is no DC voltage entering the equipment As long as the wind generator receives wind the DC cables will be live The entire manual must be read and understood in full prior to manipulating installing or operating the unit UP PP bp AAY2000IKI04 ill Ingeteam Power Technology S A Installation manual Following is a list of the basic obligatory safety standards for each country RD 614 2001 and RD 1699 2011 in Spain CEI 11 27 in Italy DIN VDE 0105 100 and DIN VDE 1000 10 in Germany UTE C15 400 in France Carry out all control and handling without voltage As a minimum security measure in this operation the so called five golden rules should always be followed Disconnect Prevent any possible resupply 1 2 3 Check there is no voltage 4 Ground and short circuit the equipment 5 Protect from live elements if any and put up safety signs around the work zone Until these five steps are completed the work area cannot be considered voltage free and any work performed will be considered to be work on live equipment Category III 1000 Volt measuring instruments must be used for checking for the absence of voltage Ingeteam accepts no liability for any damages caused by improper use of the equipment iv AAY2000IKI04 Installation manual Ingeteam Power Technology S A Potential hazards for people Bear in mind the followin
24. ed at below 30 C lt should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature vari ations and apart from the unit s own protection vigilance of these units is necessary once they have been started up on sites where it is suspected that the conditions described above will not be present 2 1 5 Contamination class The pollution degree for which the units have been designed is level 3 AAY2000IKI04 13 Ingeteam Power Technology S A Installation manual 2 1 6 Acoustic contamination When on the inverter generates a slight buzzing sound Do not place it in an occupied room or on light supports which might amplify this buzz The mounting surface must be firm and appropriate for the weight of the unit 2 1 7 Ventilation Ingecon pWind TL Ingecon uWind A zone of 30 cm above the unit and 20 cm below and at the sides must be left free of obstacles Only in this way will the unit s cooling system operate correctly The cooling system designed for the unit varies from one unit to another as greater heating occurs at higher power and this requires greater air flow to cool it This is why some models are cooled by means of natural convection and others use forced convection with one or two fans Natural convection Ingecon uWind 2 5 Ingecon Wind 2 5 TL Ingecon uWind 3 TL Forced convection 1 fan Inge
25. ediately within 5 days of receipt of the equipment If ultimately the unit has to be returned to the manufacturer you must use the same original packaging Separating the packaging All the packaging can be delivered to a non hazardous waste management company 18 AAY2000IKI04 Installation manual Ingeteam Power Technology S A In any event each part of the packaging may be recycled as follows Plastic polystyrene bag and bubble wrap Appropriate container plastic and bottles Cardboard Appropriate container paper and cardboard 3 2 Handling Correct handling of the units is vitally important in order to Prevent damage to the packaging which enables them to be kept in optimum condition from shipping until they are unpacked Avoid knocks and or falls which may harm their mechanical characteristics e g cause incorrect closure of the housing loss of IP rating etc Avoid as far as possible vibrations which may cause subsequent malfunction If you observe any anomaly please contact Ingeteam immediately 3 3 Transport Appropriate transport and storage of the unit are the necessary first steps for correct use and operation Taking Section 3 2 Handling into account and as a preventive measure Ingeteam recommends the use of transport companies specialised in the transport of special and or fragile equipment All units packaged according to Section 3 2 Handling must be handled with tools to pr
26. er is made by means of a three terminal connector The maximum diameter of the cable pipe permissible for the connector is 14 mm If the inverter and the grid connection point are far enough apart to require the use of cables of a greater section an external junction box close to the inverter to make this section change is recommended Protection of the connection to the electricity grid It is necessary to install protection elements in the connection between the inverter and the electricity grid Thermomagnetic circuit breaker A thermomagnetic circuit breaker and or fuse must be installed in the connection from the inverter to the electricity grid The following table provides the necessary data for the selection of these devices by the installer All data in Amperes 7 y Rated current for the Rated current for the type Ingecon pWind Maximum inverter current gL type fuse B MCB lS 20 20 23 ML s TL 17 25 20 Sms 17 25 20 Sieve IL 17 25 25 SS IL 18 8 25 25 4 6 TL 24 4 32 23 S TL 259 32 32 6 TL 26 2 32 32 When selecting the protection in an installation it must be borne in mind that its circuit breaking capacity needs to be higher than the grid connection point s short circuit current It must be taken into account for correct selection of the protection that the ambient working temperature influences the maximum current permitted by these protections as indicated by the manufacturer 32 AAY2000IKI04 Installation manual I
27. event damage to the packaging The unit must be protected during transport and storage from mechanical knocks vibrations water splashes rain and any other product or situation which may damage it or alter its behaviour Transport over distances of greater than 5 metres must be carried out using a pallet truck or forklift truck whenever possible Transport using a pallet truck At least the following requirements should be observed 1 Place the packaged units centred with respect to the forks 2 Try to locate them as close as possible to the connection between the forks and the steering unit 3 Inall cases observe the instructions in the pallet truck s user manual Transport using a forklift truck At least the following requirements should be observed 1 Place the packaged units centred with respect to the forks 2 Try to locate them as close as possible to the connection between the forks and the steering unit 3 Ensure that the forks are perfectly level to avoid overturning the unit 4 In any case observe the instructions in the forklift truck s user manual Once the unit has been transported to the place where it is to be located and only when it is to be installed unpack the unit Transport of the unpackaged unit At least the following requirements should be observed 1 Use the two side holes to grasp the unit with both hands 2 Follow the necessary ergonomic advice for lifting weights The unit weighs between 21 and 2
28. f failing to observe this condition 3 6 Waste handling During the various processes for installation start up and maintenance waste is generated which must be handled appropriately according to the regulations in the corresponding country At the end of the unit s life the waste must be processed by an authorised waste management company Ingeteam in accordance with its policy of respect for the environment will inform the authorised manager via this Section of the location of components to be decontaminated The elements within the unit that must be handled individually are 1 Electrolytic condensers or condensers containing PCB Batteries and accumulators 2 3 Printed circuit cards 4 Liquid crystal displays 20 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 4 Safety instructions 4 1 Contents This section contains safety instructions which must be followed when installing operating and accessing the unit Failure to comply with these instructions may cause injury or even death or cause damage to the unit Read this section carefully before working on the unit 4 2 Symbols The warnings advise of conditions which may cause serious injury or death and or damage to the equipment The means of avoiding the hazard to both people and the unit is indicated along with the warning The symbols and an explanation of
29. g warnings concerning personal safety gt Pe gt AAY2000IKI04 DANGER Electric shock The equipment may remain charged after disconnecting the wind generator and mains power Carefully follow the mandatory steps in the manual for removing the voltage DANGER Explosion There is a very low risk of explosion in very specific cases of malfunction The casing will protect people and property from the explosion only if it is correctly closed DANGER Crushing and joint injuries Always follow the indications in the manual on moving and placing the unit The weight of this unit can cause lesions serious injury and even death if not handled correctly DANGER High temperature The flow of air from the side and top outlets can reach high temperatures which can cause injury to people exposed The back and side of the unit act as a radiator Do not touch danger of severe burns Ingeteam Power Technology S A Installation manual Potential hazards for the equipment Bear in mind the following warnings concerning protection of the equipment OOP PP Should the grid or the invertor fail on power will be extracted from the wind turbine and so the wind generator must have a braking system or additional speed limiting to guarantee it never exceeds the equipment s maximum operating limits Vdc 550 V CAUTION Ventilation The unit requires quality air flow while it is operating Keeping the unit in the upright posit
30. ge caused by inadequate sealing of the unit Whenever the unit is opened it is mandatory to lubricate the screws before closing it again to prevent them seizing 6 2 Start up Once a general visual inspection wiring check and sealing check has been carried out proceed to connect power to the unit while keeping it switched off The tasks outlined for this step must be carried out with the unit door always closed thus avoiding possible contact with live parts 6 2 1 Configuration of the MPP curve The Ingecon uWind unit will impose the MPP working curve on the wind generator this relates the DC input to the power captured by the turbine optimising its energy capturing conditions over a wide range of wind speeds 6000 5000 4000 3000 Power W 2000 1000 0 T T T 1 100 200 300 400 500 Vdc The curve may be configured with up to 15 characteristic points The ranges of power and DC voltage values are as follows Range of values DC voltage O 450 V Power O 6100 W The output power will be limited by the unit s rated power 36 AAY2000IKI04 Installation manual Ingeteam Power Technology S A Other settable parameters Parameter Definition Default Range of value values Start up voltage DC input voltage at or above which the inverter will be 50 V 50 250 V connected to the grid T_potencia baja Maximum time the inverter may remain without providing 120 s 30 600s
31. hese must be studied and approved by Ingeteam The necessary means must be arranged to prevent people from outside the installation approaching or handling the equipment gt gt oo Warning signs cautioning that there are people working Elements for setting or mechanical locking These instructions must be easily accessible close to the unit and located within reach of all users Before installation and start up read these safety instructions and warnings carefully as well as all the notices located on the unit Ensure that all the notices are perfectly legible and that those which are damaged or have disappeared are restored 4 3 1 Inspection tasks May involve opening the housing for visual inspection tasks 4 3 2 Control tasks Tasks to load software from the communications connector 4 3 3 Handling tasks Tasks for the mounting and or replacement of parts fuses switchgear in general etc tasks for disconnecting and reconnecting voltage connecting the inverters to equipment and connecting communications cabling to the equip ment All those tasks which are neither Inspection or Control will be considered to be Handling 4 4 General This section defines the preventive measures to take to carry out all types of tasks on the unit working safely and controlling risks which cannot be avoided Protection against direct contact is by means of the housing which has IP65 protection class The unit has been te
32. ight the Start Stop option and press 1 23 11 01 12 OK to toggle the status MAIN MENU Change date D Partial Data Reset Change inv number AAY2000IKI04 53 Ingeteam Power Technology S A The following message is shown on the screen Highlight the desired option again and press 54 OK Installation manual 11 23 11 01 12 START STOP Change to Stop 0K Cancel ESC AAY2000IKI04 Notes Ingeteam Power Technology S A Energy Avda Ciudad de la Innovaci n 13 31621 SARRIGUREN Navarra Spain Tel 34 948 28 80 00 Fax 34 948 28 80 01 e mail solar energy ingeteam com AAY2000IKI04_ Ingeteam S r l 02 2012 Via Emilia Ponente 232 48014 CASTEL BOLOGNESE RA Italy Tel 39 0546 651 490 Fax 39 054 665 5391 e mail italia energy ingeteam com Ingeteam GmbH DE 153762639 Herzog Heinrich Str 10 80336 MUNICH Germany Tel 49 89 99 65 38 0 Fax 49 89 99 65 38 99 e mail solar de ingeteam com Ingeteam SAS Parc Innopole BP 87635 3 rue Carmin Le Naurouze B5 F 31676 Toulouse Lab ge cedex France Tel 33 0 5 61 25 00 00 Fax 33 0 5 61 25 00 11 e mail solar energie ingeteam com Ingeteam INC 5201 Great American Parkway Suite 320 SANTA CLARA CA 95054 USA Tel 1 415 450 1869 1 415 450 1870 Fax 1 408 824 1327 e mail solar us ingeteam com Inge
33. ion and the inlets free of obstacles is essential for this air flow to reach the inside CAUTION Connections After all duly authorised handling check that the inverter is ready to start operation Only after this can it be connected following the instructions in the manual Do not touch boards or electronic components The most sensitive components can be damaged or destroyed by static electricity Do not disconnect or connect any terminal while the unit is operating Disconnect and check for absence of voltage first Personal protection equipment PPE Use all items comprising the protection equipment Chapter 4 Safety instructions contains references to the use of this equipment depending on the situation gt vi The standard personal protective equipment is Safety goggles for mechanical hazards Safety goggles for electrical hazards Safety footwear Helmet AAY2000IKI04 Installation manual Ingeteam Power Technology S A Table of Contents T OVA Wa a 9 LL Introduction iii ada 9 1 2 E uipment descriptio Mes id 9 2 Model Seann ea A ade til a o 9 1 2 2 OPUS ia daa a sabuaes uedthanedede 9 1 23 System descriptor a metus atelnassiedacses 9 1 2 4 Ingecon y Wind Interface IWI renar N naaa iaa circa 11 12D COMPOSITION Sat da 11 1 3 Compliance With KESUlATIONS a aa 12 TIA CE Markie cie 12 LOW Voltage Directa a 12 Electromagnetic Compatibility Directive oocococcnccocnccocnnnonnnn
34. is voltage to the inverter even under the most adverse conditions e g an ambient temperature of 10 C In the case of damage due to the DC voltage exceeding 550 V Ingeteam accepts no liability for such damage Connect the positive pole of the wind generator to the terminal marked and the negative pole to the one marked The inverter s factory fitted terminals support a maximum current of 20 amperes In units which include an isolating switch never switch from OFF to ON without first ensuring there is no DC voltage at the input to the unit Whenever the wind generator receives wind there will be a voltage in the DC cables 5 4 Electrical disconnection To disconnect the unit follow the steps presented in Section 3 Operating conservation and transport conditions of this manual in reverse order Take careful note of the following warning There are electrical capacitances in the unit which can maintain high voltages even after having disconnected the inverter from the wind generator and the grid Ingecon uWind units may only be opened by authorised personnel AAY2000IKI04 33 Ingeteam Power Technology S A Installation manual During installation and maintenance operations on the units the use of personal protective equipment hard hat gloves and safety footwear is mandatory Do not touch the side or rear of the inverter these can reach high temperatures Installation wo
35. laced Check that there is no moisture inside the unit If moisture exists dry before making electrical connections Check the correct fixing of the housing components to their corresponding anchoring points Status of cables and terminals Check the correct path of the cables so they do not come into contact with live parts Check the insulation deficiencies and hot spots by checking the colour of the insulation and terminals Visually check that the connections are properly adjusted Ventilation Checking the status of exhaust fans cleaning and replacing them if necessary Clean the radiator fins and the ventilation grids Environment Check the environment to avoid amplifying or transmitting the buzz 38 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 8 Display control Ingecon uWind inverters incorporate a display and keypad unit to interface with the installer and the user This interface allows the display of the main internal parameters and the configuration of the entire system during installation Parameters variables and commands are organised as menus and submenus 8 1 Keypad and LEDs The keypad has four keys ESC To exit a parameter leave a menu and returning to the next level up in the structure to not confirm a change or not accept a proposal A With this key you can scroll up the list of parameters or folders within the same level or increase the value of an editab
36. le parameter by one base unit EX With this key you can scroll down the list of parameters or folders within the same level or decrease the value of an editable parameter by one base unit OK Serves to accept a parameter as valid to enter a lower level menu in the structure to confirm a change or accept a suggestion The front panel has three LEDs amp Green LED 1 second flash start up procedure 3 second flash standby due to low wind level e Steady inverter connected to the grid Orange LED 0 5 second flash the external fan is not working correctly 1 second flash the internal fan is not working correctly 3 second flash inverter limiting power due to high temperature Steady presence of alarm O Red LED Steady manual shutdown 8 2 Display The current date and time on the top line The internal clock PERE 11 01 12 automatically changes the time from summer to winter and vice versa INGECON pWind 5 0 TL The central section provides real time wind generator voltage power fed in by the inverter and grid voltage and frequency i 4567W 302V 229V 49 96Hz A AAY2000IKI04 39 Ingeteam Power Technology S A 8 3 Main menu The main menu contains the following submenus m 11 23 MAIN MENU 11 01 12 Monitoring Configuration Language Selection Change date b n d Monitoring of the unit Configuration conditions Language Selection
37. les in the wall with a bit recommended for the screws to be used to secure the plate to the wall later 3 Fix the plate using wall plugs and stainless steel screws to prevent corrosion Use fittings appropriate for the weight of the unit i i g a AAY2000IKI04 25 Ingeteam Power Technology S A Installation manual 4 Suspend the unit from the plate 5 6 Check that the unit is properly secured Units with a transformer The top attachment plate for the unit supports the weight The bottom point fixes the transformer to the wall and prevents vibrations Fix the transformer to the wall before coupling the equipment to it Fixing the transformer to the wall 1 Mark the attachment points for the plate on the wall 2 Drill holes in the wall with a bit recommended for the screws to be used to secure the plate to the wall later 3 Fix the plate using wall plugs and stainless steel screws to prevent corrosion It is important to choose screws washers and plugs which are suitable for the bolts which will fix the plate depending on the specific condi tions of each installation 26 AAY2000IKI04 Ingeteam Power Technology S A Installation manual 4 Suspend the
38. m Inv 0006H means the grid frequency and voltage are out of range 0002H 0004H Number allocated to the inverter through the menu accessible in the display for identifying communications Unit operating code This can be requested from Ingeteam s customer services Unit operating code This can be requested from Ingeteam s customer services Serial Number Total energy kWh delivered by the inverter to the grid from the date it was manufactured Recording the serial number of the equipment marks the start of this power log Number of hours the inverter has been connected to the grid Number of grid connections made during all hours of operation Total energy kWh delivered by the inverter to the grid since the last time the counter was reset Number of hours the inverter has been connected to the grid since the counter was last reset Number of grid connections since counter was last reset Unit firmware version Unit display firmware version Version of the display program enabling firmware housing 41 Ingeteam Power Technology S A Installation manual 8 5 Configuration Access restricted to installer Do not change any of these parameters if you are not the installer and you are not completely sure Ingeteam accepts no liability for damage to the unit or the installation due to configuration changes Press LOK on the Configuration option in the MAIN MENU W11 23 11 01 12 11 23 11 01 120 M
39. next Autotest measurement Vmin When it is evaluating the lower limit for voltage protection Fmax When it is evaluating the upper limit for frequency protection Fmin When it is evaluating the lower limit for frequency protection Completed When the Autotest is complete 50 AAY2000IKI04 Installation manual Ingeteam Power Technology S A The Autotest process can be interrupted at any time by selecting Mi 23 e 11 01 12M the Stop Autotest option which appears in place of Start Autotest Lia LLUIS while it is being carried out AUTOTEST Once an Autotest has been completed the results can be Stop Autotest displayed by selecting Results The results are accessed by Results pressing LOK and moving between the four available screens Status Vmax of results Here for example are the results screens for Vmax j and Fmax b d F z p p 11 23 11 01 12 11 23 11 01 12 AUTOTEST AUTOTEST Test result Vmax Test result Fmax Vmax 238 V Fmax 50 02 Hz Vac 236 V Fac 49 99 Hz Time 070 ms Time 060 ms A b A AAY2000IKI04 51 Ingeteam Power Technology S A Installation manual 9 Troubleshooting This is a guide for troubleshooting problems that may arise in the installation and operation of Ingecon Wind units It also explains how to perform simple operations such as component replacement and unit configuration Troubleshooting for the Ingecon Wind unit must be performed by qualified personnel in compliance
40. nfiguration of the MPP Curve ict cai dawssicancvnsenaisvece ala 36 6 22 A ccs samsung yankee achat aecumedtagundatchen dea e eG 31 Preventive MaidtenanCe oooccccccnncccnnnnnncnnnnn cnn RR RR RRE R RR RR nara rrnmnrnnnnns 38 Zl Maintenance taSKS uranio ai ela fala 38 Display control ae leida 39 8 1 Keypad and LEDS a a caes 39 Se DIS Mat collado 39 So Mame tic iaa 40 S4 MOMITONING id 40 SO ICONO oia 42 8 5 1 COUNTY Regula da atada tada 42 9 5 2 Nominal Srid voltage mierea a a tdi 44 3523 GrOUNdINE iia a oia aid 45 Sd VAP AG JUSTIMENUS a ai 45 SO AMA li def 46 AE NN 46 Grid COMEN iria a nai 47 VIBALIMIS nana eran nd ai dacs EAU acaagasacaamadacaansvarecndeiaeateesaataaes 47 Limiting POWE pisito 47 6 Language Selection iene nna a a a aa aaa a a a a 48 RO dates ssi cien iteassins aca O 48 qe OD a ON 48 8 9 Reset partial dalak rrenen ineeiieo laa 49 8 10 Change Inverter nube thes a a a a a aa aaa 49 Bid Le Oo E I A E E TE A T 50 TROUBIGSHOOUING sissioni a as decirse 52 Ol MLE D IMGSSASES dad llos 52 OV Ak Gre LED wiesss cccdseaessntversnnagecewa A A A AEN 52 912 Ova OO ED e a a r e a a ea aE E E a A A E 52 9 1 3 Red LED A a ado rats 53 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 1 Overview 1 1 Introduction The purpose of this manual is to describe the Ingecon uWind unit and to give appropriate information for its correct receipt installation start up operation and maintenance 1 2 E
41. ngeteam Power Technology S A Differential circuit breaker Never install in the grid connection for TL units with no transformer a differential switch with a limit current below the maximum fault current which may occur in the wind farm installation under all its operating conditions While feeding to the grid a shunt current is produced from the metallic housings to ground the value of which depends on the type of generator as well as atmospheric conditions rain snow etc This service conditioned shunt current must not exceed the breaking current value of the differential switch If it does so the connection of the inverter to the grid may trip the differential switch external to the inverter The unit will need to be started up manually as the Start Stop status is conserved even if the inverter has been switched off Section 8 Display control provides connection details 5 3 8 Wind generator connection The inverter is connected to the wind generator by means of quick connect terminals specifically designed for the purpose This type of quick connect terminal requires the use of specific tools Bear in mind at all times that whenever the wind generator is in movement there will be a voltage at its terminals The inverter can therefore have voltages of up to 550 V inside even when not connected to the grid The inverter needs a maximum system voltage of 550 V Check that the wind generator configuration cannot supply th
42. nnnnononnnnncnonnnnonnnnnnnnnnnnnnncnnononnannnnnnnnnns 12 13 2 VWDEOI26 1 1 and VDESAR N 4 Ossa arias 12 1 3 3 Regulations for connection to the ENEL Distribuzione grid oocccoccccoccncoonccnocnonnnnnnnnnnnnncnonannnonons 12 1 3 4 Engineering Recommendations G83 1 1 oonccccnncncccnccccnncocnnnonnnonnnnonnononnnnnnnnnnonnnnnncnnonacnnnnnnnnnns 12 Ze System GESCHPTOM A 6eaaasnitaanvewnscudaveaesneGadentdabadacnenadeneteteunes 13 QA LOCATON NR 13 2 Lely ENVIO Mei aana i Na A A E saved E 13 2 A OS 13 ZL Ambient EMP ile da 13 2 LA ATMOSPMENC CONGITIONS tds iia 13 2 15 Contamination Cls S icon ci a AA Ea OR EA EET AEU 13 2 126 Acoustic contaminato Massee in RE E E EAA EEA E R aA ERa 14 21 7 Ventil ati One ea oraes nan E EE E a EA EA aaa R RO E EEREN 14 2 1 9 Support surtace and fastening aia dd a 15 2 2 Environmental characteristics e A iia dai 16 2 9 EMG TEQUES MENS laa 16 3 Operating conservation and transport CONdItIONS cccoccccoconccoonoconnnononnononnnnnnnnnnnnnnnonnnnnnnnnnnnonnnncnnannnnnnnnnns 17 31 EQUIPMENT r ception A A aa 17 A asta casematuctuncat e a a a war aduetanesusraadlaleesueameuseediesadaduarefalacs austin demotdainas sambomee 19 3 3 MO ii 19 A A 20 3 5 CONS Mr it a a r aaan Ranana 20 3 6 Waste handle baladas 20 A Safety INSTUCHON Sii ie A O ea 21 da Contents at a A E AI 21 MA MO e E seven eeachesans cs E E E A adnacde os ncubagse AE E E 21 4 3 Definitonmof tasks to becada N AE EE Eaa 21
43. nt A Fac Output current frequency to the electricity grid Hz PhiCos Cosine of Phi Cosine of the phase shift angle between grid voltage and current supplied by the inverter If the phase shift is zero 0 the cosine of phi is 1 cos O 1 40 AAY2000IKIO4 Installation manual Ingeteam Power Technology S A Screen 2 Vdc Idc Screen 3 Alarm Numinv Code1 Code2 SN Screen 4 TotE T con NumCon Screen 5 ETotal T con NumCon Screen 6 FW Ver DFW Ver D Boot AAY2000IKI04 Voltage supplied by the wind generator to the inverter V Current supplied by the wind generator to the inverter A Status of inverter alarms The installer has instructions for the proper response to each alarm Only the ones mentioned in this manual may be of use to the user 0000H No alarms 0001H Insufficient input voltage 0002H Grid frequency out of range 0004H Grid voltage out of range 0008H Overcurrent in the inverter bridge 0010H Overcurrent in the AC DC converter 0020H Insulation fault 0040H Grid overcurrent 0080H Overtemperature O100H Bus overvoltage 0200H Configuration change 0400H Manual shutdown O800H HW error 1000H Instantaneous grid overcurrent 2000H Detection of island mode operation 4000H Relay impedance out of range 8000H Hardware fault alert The value displayed in Alarm Inv can be the result of the hexadecimal sum of two or more of the values listed above For example Alar
44. o comply with these instructions 8 5 2 Nominal grid voltage This menu serves to modify the configuration of the voltage output to the terminal strips An insulation fault can pose a hazard to personnel The repair of an insulation fault must be carried out by qualified personnel 44 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 8 5 3 Grounding In the case of Ingecon uWind the equipment will always be configured with no grounding so this menu option must not be changed The display should look like this p 11 23 11 01 12 GROUNDING gt Ungrounded PV Ground PV Ground 8 5 4 V f Adjustments Press LOK on option VF ADJUSTMENTS in the submenu Configuration Press OK to display the upper and lower limit values for the voltage and frequency protections You can browse through the four magnitudes for the value by means of the LA and IMA keys W11 23 11 01 120 11 23 11 01 12 CONFIGURATION V F ADJUSTMENTS COUNTRY REGULATIONS Fac MAX GRID VOLTAGE GROUNDING 50 20 Hz V F ADJUSTMENTS AUXILIARY RELAY se A E a To change the values of these magnitudes hold the key down J 11 23 11 01 12 for 4 seconds The following screen will appear requesting a password in this case Password 3 As for the other options in V F ADJUSTMENTS the Configuration submenu enter Password 3 specific and non transferable for each inverter and press LOK Pas
45. parts inside the unit internal radiator to cool 4 4 3 Personal Protection Equipment PPE The preventive maintenance tasks involve Inspection Control and or Handling actions depending on each case Inspection The use of safety footwear to standard EN 345 1 1992 is mandatory The use of kid leather type gloves is also mandatory Control The use of safety footwear to standard EN 345 1 1992 is mandatory The use of kid leather type gloves is also mandatory Handling The use of safety footwear to standard EN 345 1 1992 is mandatory The use of kid leather type gloves is also mandatory It is also mandatory to use dielectric gloves meeting standard EN 60903 1992 and protective face mask against AAY2000IKI04 23 Ingeteam Power Technology S A Installation manual electric shock complying with EN 168 1994 for voltage testing tasks and opening or closing automatic switches under load 4 5 Inspection control and handling tasks The mandatory safety measures necessary in carrying out inspection control and or handling tasks on this unit are defined below Opening method The cover is opened and closed using a system requiring tools to remove it nuts and bolts It is strictly forbidden to gain access to the inside of the equipment through any other point than the access cover provided for the purpose 4 5 1 Inspection tasks Access inside of the unit for inspection only via the front cover After completing
46. pliance with limits and procedures in other standards of the same series 1 3 2 VDE0126 1 1 and VDE AR N 4105 In countries such as Germany Portugal and France incorporating a device of this type facilitates compliance with the regulations in force for wind power and microgeneration facilities As such our units comply with the standards VDE 0126 1 1 Automatic disconnection for generating installations connected in parallel with the low voltage grid VDE AR N 4105 Generators connected to the low voltage distribution network Compliance with this standard must be requested on ordering the unit 1 3 3 Regulations for connection to the ENEL Distribuzione grid In Italy to connect to the company ENEU s grid it is necessary to comply with the regulations the company demands Hence our units comply with the applicable part of standard RTC alle rete BT di Enel Distribuzione Compliance with this standard must be requested on ordering the unit 1 3 4 Engineering Recommendations G83 1 1 In the United Kingdom there is document G83 1 1 which recommends the characteristics a microproduction gener ator needs to have Recommendations for the connection of small scale embedded generators in parallel with public low voltage distribution networks Compliance with this standard must be requested on ordering the unit 12 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 2 System description 2 1 Location
47. pment is limiting it power AUXILIARY RELAY Insulation fault Grid Connection V f Limits gt WAS When you access the menu select the required limiting power 11 23 11 01 120 using the L4Nland A keys To select this power more quickly i the following key stroke combinations may be used AUXILIARY RELAY N or D LOK increase or decrease the POWER LIMIT numbering in blocks of 10 Change gt 0000 W N or D ESC increase or decrease the Conii O9 numbering in blocks of 100 Cancel Esc a a Press LOK to confirm or LESC exit AAY2000IKI04 47 Ingeteam Power Technology S A Installation manual 8 6 Language selection Press LOK in the Language Selection menu to access the menu F 11 23 11 01 12 j for changing the language MAIN MENU The L N and LX keys allow you to scroll through the menu i i with the available languages Press LOK once when the language Monitoring Configuration you wish to display is highlighted and the system will switch to the confirmation screen Language Selection Change date Pressing LOK again confirms the selection 11 23 11 01 12 11 23 11 01 120 LANGUAGE SELECTION LANGUAGE SELECTION Spanish Language English Engish Continue German OK Italian 8 7 Change date From this menu you can change the date and time The internal P 11 23 11 01 12
48. quipment description An inverter is a circuit used to convert direct current to alternating current The function of the Ingecon Wind units is to convert the direct current generated by wind generators to alternating current and so enable it to be fed to the electricity grid 1 2 1 Models The main models in the Ingecon Wind range are Ingecon uWind 2 5 TL Ingecon uWind 2 5 Ingecon uWind 3 TL Ingecon Wind 3 3 Ingecon uWind 3 3 TL Ingecon Wind 5 Ingecon uWind 3 68 TL Ingecon uWind 3 8 TL Ingecon uWind 4 6 TL Ingecon uWind 5 TL Ingecon uWind 6 TL 1 2 2 Options All these models in the Ingecon uWind range may incorporate the following options DC circuit breaker MC3 type quick connectors Ingecon uWind Interface IWI connection kit AAYOO89 1 2 3 System description There are several configurations available depending on the features of the equipment being used These possibilities are discussed below A microgeneration wind power system must have a braking and stopping system in order to ensure the safety of people and the equipment If the braking and stopping system is supplied by others Ingeteam accepts no responsibility for any malfunction or the consequences thereof Wind generator with DC output and built in braking system wind generator grid a N Ingecon Wind n N AAY2000IKI04 9 Ingeteam Power Technology S A Installation manual Wind gene
49. rator with AC output and built in braking system In this case an AC DC conversion system will be required to change the generator output voltage to DC wind generator Part G N conversion system Ingecon Wind NE Z Wind generator with DC output with no built in braking system An external braking system is needed to be able to stop the wind generator or reduce the angular velocity heating resistor wind generator O e e T A braking system Ingecon yWind grid a l ue Wind generator with AC output with no built in braking system An external braking system is needed to be able to stop the wind generator or reduce itsangular velocity as well as another system to convert from AC to DC before the current reaches the Ingecon yWind unit heating resistor wind generator Ingecon Wind a N braking and conversion system AC 10 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 1 2 4 Ingecon pWind Interface IWI As explained in the previous point it is necessary in some circumstances to provide an external braking system and or an AC DC conversion system To fulfill this need Ingeteam has included the Ingecon uWind Interface unit in its range of products The Ingecon Wind Interface unit was designed to work in conjunction with Ingecon uWind converters in the control and conversion of energy generated by the wind
50. rd unit comes with the nsulation fault option selected P 11 23 11 01 12 The gt symbol points to the option selected 5 AUXILIARY RELAY Use the A and A keys to select the desired configuration and press LOK gt ESE ao eae Grid Connection V f Limits Power Limit Insulation fault Select nsulation fault if you wish the auxiliary relay to switch when the equipment detects a fault of this type 11 23 11 01 120 11 23 11 01 12 AUXILIARY RELAY AUXILIARY RELAY gt BERS ha OIU INSULATION FAULT Grid Connection V f Limits Continue Power Limit Confirm OK Cancel Esc 46 AAY2000IKI04 Installation manual Ingeteam Power Technology S A Grid connection Select Grid Connection if you wish the auxiliary relay to switch when the equipment detects that it is not connected to the grid 11 23 11 01 12M EZ 11 01 12 AUXILIARY RELAY AUXILIARY RELAY Insulation fault GRID CONNECTION gt CACA V f Limits Continue Power Limit Confirm 0K Cancel Esc V f Limits Select V f Limits if you wish the auxiliary relay to switch when the equipment detects that the voltage and or frequency values are not within limits W11 23 11 01 120 11 23 11 01 12 AUXILIARY RELAY AUXILIARY RELAY Insulation fault V F LIMITS Grid Connection gt ame ees Continue Power Limit Confirm OK Cancel Esc Limiting power Select Power Limit if you wish the auxiliary relay to invert when P 11 23 11 01 12 7 the equi
51. ress LOK to set the counters to zero The following message is i 11 23 11 01 12 1 shown on the screen MAIN MENU Change date Start Stop Partial Data Reset Change inv number E a Pressing LOK again confirms the selection 11 23 11 01 120 PARTIAL DATA RESET Save 0K Cancel ESC h 8 10 Change inverter number From this menu the inverter number is set by which it will be Wi E 11 01 12M identified by the Ingecon Manager software for carrying out aLi ULLA communication between them The operation is necessary when MAIN MENU several units are connected together Change date Press LOK on option Change inv number in the main menu A Start Stop Partial Data Reset Change inv number screen is accessed in which the LA and LX keys may be used to select the required number Assign unique numbers to the inverters Failure to do so will produce communications errors It is advisable to use sequential numbering 1 2 3 4 etc AAY2000IKI04 49 Ingeteam Power Technology S A Installation manual After selecting the required number press LOK to confirm your i 11 23 11 01 12 1 selection A change confirmation screen will inform you the oper ation has been successfully carried out CHANGE INV NUMBER Inverter number 101 Save OK Cancel ESC E 11 23 11 01 120 11 23 11 01 12 CHANGE INV NUMBER CHANGE INV NUMBER Inverter number 0003
52. rk requiring opening the unit should be done in a dry environment so that no moisture left inside could condense and damage the electronics Ingeteam accepts no liability for any damages caused by improper use of the equipment 34 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 6 Commissioning 6 1 Equipment inspection This section contains instructions on how to make the unit work once correctly wired and closed Ingecon Wind units manage a generating installation or part of one The correct condition of this installation must be checked before start up Each installation is different depending on its characteristics the country in which it is located or other special condi tions which may apply In all cases before starting up it is necessary to ensure that the installation complies with the applicable legislation and regulations and that at least the part to be started up is complete 6 1 1 Inspection Before inverter start up a general inspection of the units must be carried out involving mainly Wiring check Check that the cables are correctly connected to their connectors at the bottom of the housing Check that these cables are in a good condition and that there are no hazards in their environment which damage them such as sources of intense heat objects which could cut them or arrangements which put them at risk of impacts or pulls Check the the unit is properly secured Check that the unit is
53. s section may lead to damage to the equipment Ingeteam accepts no liability for damage resulting from the failure to follow these instructions 3 1 Equipment reception Reception Upon receipt of the shipment check the terms specified in the Delivery Note sign the Signature Receiver Goods field and return the copy to the return address Keep the unit in its packaging until immediately before installation Maintain the unit upright at all times If you have purchased inverters with transformers the transformer and inverter will be received in separate boxes It will be possible to identify which transformer corresponds to each unit by means of the serial number shown on the shipping label INGETEAM POWER TECHNOLOGY S A Avda Ciudad de la Innovaci n 13 31621 Sarriguren Navarra SPAIN www ingeteam com INGECON WIND Model Ingecon uWind 5 TL Code I D AAYXXX S N 100010060001 DEMO 100010060001 Ingeteam 2011 Ingecon uWind 5TL label INGETEAM POWER TECHNOLOGY S A Avda Ciudad de la Innovaci n 13 31621 Sarriguren Navarra SPAIN www ingeteam com INGECON WIND Ingeteam Ingeteam INGETEAM POWER TECHNOLOGY S A Avda Ciudad de la Innovaci n 13 31621 Sarriguren Navarra SPAIN www ingeteam com INGECON WIND Model Ingecon uWind 5 Model Ingecon uWind 5 Code I D AAYXXX Code I D AAYXXX S N 100010060001 S N 10001006000
54. sted according to the applicable regulations to comply with the safety requirements the values 22 AAY2000IKI04 Installation manual Ingeteam Power Technology S A for insulation distances and leakage paths for the voltages used The tools and or equipment used in handling tasks must have double reinforced insulation Class II 4 4 1 General risks existing and preventive measures Impact against immovable objects Inform workers of the risk Adequate lighting Work with care Keep sufficient distance to prevent contact with the part causing the risk Knocks punctures and cuts from objects and or tools Keep the lid closed if not working on the inside Adequate lighting Order and cleanliness Mandatory use of hard hat safety footwear and gloves when necessary Flying particles fan Recommended use of anti impact glasses when accessing the fan inlet and outlet zones Electrical danger Comply with that laid down in the Sections 4 4 3 Personal Protection Equipment PPE and Important safety precautions Inform the worker of the risk Comply with the legislation applicable to the installation in which the unit is located both that for the type of installation and the country where it is located 4 4 2 Additional risks and measures in handling tasks Thermal contact Inform workers of the risk Recommended use of gloves Disconnect the power and wait 10 minutes for the hot
55. sword 3 AIR Each time L N and X are pressed four screens will appear i 11 23 11 01 12 l offering the option to change the upper and lower voltage and V F ADJUSTMENTS frequency protection limits Shown as an example is the screen for changing the upper frequency limit Fac MAX Press LOK The value for the maximum frequency limit can be varied using the keys Once you have selected the desired Change OK 90 20 Hz value press LOK AAY2000IKI04 45 Ingeteam Power Technology S A Installation manual The following screen will appear requesting confirmation or ai 23 OL 12m cancellation of the modified value using the OK or ESC is LOMA VA respectively V F ADJUSTMENTS Fac MAX Change gt 50 20 Hz Change 0K Cancel Esc Changing the protection limits for voltage and frequency may result in failure to comply with the standards to which the original unit was certified In this case the certificates prior to the change will be invalid Ingeteam accepts no liability for any type of problem caused by changing these limits 8 5 5 Auxiliary relay Ingecon uWind units are fitted with an auxiliary relay which may be used for various functions Access the AUXILIARY RELAY submenu and press LOK to see 11 23 11 01 12 l the various options CONFIGURATION COUNTRY REGULATIONS GRID VOLTAGE GROUNDING V F ADJUSTMENTS AUXILIARY RELAY The standa
56. t all units can be configured to the options of every country Refer to the configuration section for further information AAY2000IKI04 11 Ingeteam Power Technology S A Installation manual 1 3 Compliance with regulations This unit can incorporate kits making it adaptable to the regulations for all European countries and countries in other continents 1 3 1 CE marking CE marking is mandatory for the sale of any pro duct within the European Union without prejudice to standards or laws Ingecon Wind units have CE marking by reason of their compliance with the following directives Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Low Voltage Directive Ingecon Wind units comply with this directive by means of compliance with the applicable parts of harmonised standard EN 50178 Electronic equipment for use in power installations and EN 50438 Requirements for the connec tion of micro generators in parallel with public low voltage distribution networks Electromagnetic Compatibility Directive Ingecon uWind units comply with this directive by means of compliance with the applicable parts of harmonised standards EN 61000 6 2 Electromagnetic Compatibility Part 6 2 Generic standards Immunity for industrial environments EN 61000 6 3 Electromagnetic Compatibility Part 6 3 Generic standards Emission for domestic environments Compliance with these standards calls for com
57. t to damage the housing The inside of the box must be checked to ensure there is no moisture If there are signs of moisture the unit must not be installed until it is completely dry All installation operations must obey the regulations in force Before starting the actions described under this point it is important to identify each of the parts described in it and to have gathered the necessary tools to carry them out 5 1 General requirements for installation The unit s environment must be appropriate and meet the guidelines described in Chapter 2 System description Additionally the parts used in the rest of the installation must be compatible with the unit and comply with the applicable legislation Ventilation and the space for work which must be suitable for maintenance tasks according to the applicable regulations in force The external connection devices which must be suitable and sufficiently close as set forth in current regulations The connecting cables must be of the appropriate section for the maximum current Special care must be taken to ensure that there are no external elements near the air inlets and outlets to obstruct proper ventilation of the unit 5 2 Fixing the unit to the wall Ingecon Wind units have a system for anchoring to the wall using a fixing plate TL units 1 Mark the attachment points for the plate on the wall Use the template provided with the unit 2 Drill ho
58. tact Access for other accessories AAY2000IKI04 Quick DC connectors Quick AC connectors Quick connectors for communications Knock out holes 29 Ingeteam Power Technology S A Installation manual DC circuit breaker Ingecon Wind units with or without transformers may have an optional DC isolating switch There are several different models although they all have the same electrical properties The advantage provided by this isolator is that it can isolate under load in case of emergency In any case we recommend that other than in the case of an emergency the unit be shut down by means of the display before isolating DC circuit breaker As long as the wind generator receives wind the DC cables will carry potentially dangerous voltage levels Never handle the connections before disconnecting the inverter from the grid and the wind generator Ingecon pWind Interface IWI Connector You may optionally request the inverter to be fitted with a connector for connecting to the Ingecon Wind Interface IWI connector Transformer connectors Ingecon uWind units with transformer are supplied with the inverter and transformer in separate boxes They must be connected when installed using the cable supplied with the transformer The connectors to link are as shown in the figure
59. team INC 3550 W Canal St Milwaukee WI 53208 USA Tel 1 414 934 4100 Fax 1 414 342 0736 e mail solar us ingeteam com Ingeteam a s Technologick 371 1 70800 OSTRAVA PUSTKOVEC Ingeteam CE Renu Tel 420 59 732 6800 Fax 420 59 732 6899 e mail czech ingeteam com Ingeteam Shanghai Co Ltd Shanghai Trade Square 1105 188 Si Ping Road 200086 SHANGHAI P R China Tel 86 21 65 07 76 36 Fax 86 21 65 07 76 38 e mail shanghai ingeteam com Ingeteam Ltda Rua Luiz Carlos Brunello 286 Ch cara Sao Bento 13278 074 VALINHOS SP Brazil Tel 55 19 3037 3773 Fax 55 19 3037 3774 e mail brazil ingeteam com Ingeteam Power Technology S A www ingeteam com
60. the inspection replace the front cover and secure it with the bolts supplied 4 5 2 Control tasks The only control task which can be carried out on this unit is the loading of software from the quick communications connector located on the outside 4 5 3 Handling tasks All those tasks which are neither Inspection or Control will be considered to be Handling Before handling the equipment ensure there is no voltage present To achieve this use the following protocol 1 Shut down the unit Block the wind generator if a braking system is available Disconnect the inverter DC input cable isolate it mark it and protect it Disconnect the Vac cable oR WN Wait 10 minutes for the internal capacitances to discharge the hot parts to cool and the inverter s fan blades to stop turning 6 Open the door and discharge the Vbus by means of a suitable discharge resistance between the VBUS and VBUS Check there is no voltage To carry out steps 2 3 4 5 and 6 it will be necessary to use the PPE indicated in Section 4 4 3 Personal Protection Equipment PPE in this document for work with live parts Any work carried out which implies a modification of the original electrical settings must be proposed to and accepted by Ingeteam 24 AAY2000IKI04 Installation manual Ingeteam Power Technology S A 5 Installation Before installing the Ingecon uWind unit the packaging must be removed taking special care no
61. transformer Electrical wiring diagram for TL equipment with a connection to Ingecon pWind Interface IWI For Ingecon Wind 2 5TL 3TL 3 3TL 3 68TL 4 6TL 5TL and 6TL with a connection to Ingecon Wind Interface IWI inverter Electricity company panel gt A thermomagnetic counter wind generator circuit breaker kWh grid Electrical wiring diagram for transformers with a connection to Ingecon pWind Interface IWI For Ingecon Wind 2 5 3 3 and 5 with a connection to Ingecon Wind Interface IWI Electricity company panel A GD a an thermomagnetic counter wind generator inverter transformer circuit breaker kWh grid 5 3 4 Multi purpose access The orifices provided for this function can be opened by breaking the knock out in the unit s base Once the orifices have been opened they must be fitted with M12 and or M20 metric cable glands which accept pipes of a diameter between 3 5 and 7 mm for M12 and between 7 and 13 mm for M20 Once the connection has been made check that the cable glands used have been properly fitted to guarantee sealing of the box A closure which is not sealed may allow moisture to enter and seriously damage the unit invalidating the manufac turer s warranty in addition If a knock out which is not to be used is opened accidentally or one which has been fi
62. transformer from the plate This operation must be carried out between two people 5 Screw on the bottom attachment 6 Check that the transformer is secured well Fixing the unit to the transformer 7 Suspend the inverter on the transformer by fitting the holes in the former onto the lugs at the top of the transformer 8 Adjust the two housings so that their edges coincide and are parallel so that the drilled plates at the rear bottom right of the inverter and the front bottom right part of the transformer are in contact and their drilled parts coincide 9 To join the inverter and transformer together the choice can be made between a nut and bolt or the use of a padlock Unit to transformer junction 27 AAY2000IKI04 Ingeteam Power Technology S A Installation manual 10 Check that the transformer is secured well 5 3 Electrical connection Once the unit has been mounted in its final position and has been solidly secured make the electrical connections to it quick connectors IWI connector fan communications transformer for DC optional fans connector connection radiator quick connector DC circuit breaker optional
63. tted with a cable gland is no AAY2000IKI04 31 Ingeteam Power Technology S A Installation manual longer used these open orifices must be closed with a sealing plug which maintains the unit s hermetic seal 5 3 5 Connection for communication via RS 485 serial port All Ingecon Wind units have communication facilities over an RS 485 serial line As the RS 485 communication board is already wired to the Harting HAN 4 A female connector simply plug in a male connector of the same type Refer to AAX2002IKI01 Installation Guide for Communications Devices for how to wire correctly the male connec tors which need to be plugged into the connector on the inverter This connector can be supplied by Ingeteam if requested together with the unit 5 3 6 Connection for communication by other means At the request of the installer inverters may optionally incorporate hardware for communicating via GSM GPRS telephone Ethernet In all these units the auxiliary signals connect directly to the corresponding communications card See the Communications Accessories Manual AAX2002IK101 5 3 7 Connection to ground and to the electricity grid The inverter s metal parts unit ground are electrically connected to the ground pin in the grid connection quick connector To ensure the safety of personnel this terminal must be connected to the installation s ground The connection of the grid Neutral and Phase to the invert
64. turbine The purpose of this unit is to perform the following functions Convert from AC to DC changing the AC voltage generated by the wind generator to DC for the Ingecon uWind unit Protect the system from excess rotational speed and overvoltage as well as limiting power capture when the generator is working in high wind speeds Shut down the wind generator Remotely control the installation and monitor additional variables of the wind power installation With its ability to convert AC to DC the Ingecon uWind Interface allows wind generators with a DC output to be connected too In this case the protection monitoring and remote control functions will still be utilised resistors wind generator 7 a N Ingecon Wind Interface Ingecon Wind grid communications The resistors are not included with the Ingecon yWind Interface The braking resistors must be dimensioned as explained in the Ingecon uWind Interface AAY2000IKI06 manual Should this point not be complied with Ingeteam will not guarantee the ability of the generator to brake and or stop For more information about Ingecon uWind Interface and its operation in conjunction with Ingecon Wind units see Installation and User Manual AAY2000IKI06 1 2 5 Compositions At the hardware level there are small variations between units for different countries However although these differences are small no
65. ual 6 7 8 9 viij Quick connector for AC CONMeCti ON criaron savastes vanced a aa AAE tao 29 Quick connector for COMMUNICATIONS ccccceceeeeeeceeeeeeeeeeceeeeeeeeaeeeececsueeeeeeeseeeeesaaneeeeeseeeeeesaeees 29 Multi purpose elandS sosusirias al idol 29 DG circuit Breaker ria toa Ia lA ea 30 Ingecon uWind Interface IWI Connector occccoooocooonocccnncnnnononononnnnonnnnnnnnonononnnnonannnnnnnnnnnnnonanannnnos 30 Transtormer COMES uta a ARIE en Aaaa 30 532 Order OF CONMECHNE the untsi nsn e a a a a a ea leaa 30 5 3 3 System Wiring diaga Missirien senise nen ie ea EE E AEE EEE EAEE E EEE ENEE NEE ERN 30 5 3 4 Milk purpose actes Shii aa a a a e a a e a aA ano 31 5 3 5 Connection for communication via RS 485 serial port ccccccccsecccseeceseeceeeeeeeaeeeseeceseeeesneeeees 32 5 3 6 Connection for communication by other MeanS csecsen aa a naa aa 32 5 3 7 Connection to ground and to the electricity grid ooocccoocccoonncnnnnnonnnncnnnnnnnoncnnnnnnnnnnnnncnonnnnnnnnnnns 32 Protection of the connection to the electricity grid oooccccoccccocnnconnncnocncnnnnonnnnnnonnnnnnnncnnnncnnonononcnnnns 32 5 3 8 Wind generator CONMECHOM ma do 33 54 Electrical CISCOMMECHOM o a ia e a aa aa aia a Ea 33 COMMISSIONING A o ESES 35 621 Equipment INSPECTION ada oia 35 E E MMS eO E A A E E E E E S 35 6 1 2 Hermetic sealing OF the UNIT osioiden e a a a a a aaa aa 35 6 2 Star O abbas cab beaaen 36 6 2 1 Co
66. with the general safety instructions in this manual 9 1 LED messages Some of the LEDs indicate some kind of problem in the wind farm installation 9 1 1 Green LED This is the LED that should light up in normal start up and operating conditions while the others remain off It has three modes 1 second flash This type of blinking indicates that the wind generator is feeding the right amount of voltage to the inverter and it is about to start up In this state the inverter checks the grid parameters to feed current into the grid at the latter s precise voltage and frequency This process takes about one minute 3 second flash Standby due to low wind level Flashing every 3 seconds This alarm is triggered when the wind generator does not receive enough wind to supply the minimum voltage required by the inverter to inject power If this situation occurs on a day when the wind is very light check the status of the generator and that it is correctly connected Steady light Inverter connected to the grid 9 1 2 Orange LED This is the LED which indicates that alarms have been set off in the inverter 0 5 second flash If accompanied by the message COMMS on the display means that communication has been lost This may be due to problems with the communications cable if the communications installation is fixed or because the inverter is resetting in which case the flashing will be momentary If the flashing is not a

Download Pdf Manuals

image

Related Search

Related Contents

Sun Microsystems iPlanet Web Server User's Manual  DA-661/662/663 Hardware User`s Manual v5  Kenwood X600F Stereo Amplifier User Manual  Sparky Group GUR 12S User's Manual  MALDI Biotyper CA System  Hog 3PC 140 Release Notes  Long elements - Mino Remote controlled Lange  Câmera Digital KODAK EASYSHARE DX4900 Zoom Guia do usuário  OPERATION & SERVICE MANUAL Model SMA7115  