Engineer`s and User`s Manual

image

Contents

1. AUTO oee EXIT E Cet A1 at A l lt T N RS485 1 Control Room 2000 PT FIRE Auro ea Figure 1 3 A Centralized Dry Chemical Fire Extinguishing System 1 Hazardous Area 4 Light and Sound Alarms 2 S2000 PT CIE 5 82000 KPB Module 3 S2000M Control Console info bolid ru overseas bolid com 11 FIRE ALARM AND EXTINGUISHING CONTROL PANEL LJ Releasing Circuit A LJ LJ Releasing Circuit v Releasing Circuit A AN Primary Agent Ru um muy 1 4 4 4 12 EZ RS485 7 i FIRE Auro J Figure 1 4 A Centralized Gaseous Fire Extinguishing System 1 Hazardous Area 4 Light and Sound Alarms 2 S2000 PT CIE 5 S2000 KPB Module 3 S2000M Control Console 6 Gas Installation www bolid com l l L IS Secondary Agent Storage Cylinders Storage Cylinders SS rd y 4 S2000 ASPT Panel Design 2 PANEL DESIGN 2 1 Panel View and Basic Elements The basic panel elements are shown in Figure 2 1 8 1 2 9 c CONDITION ATA INPUTS O PREALARM Oo LJ 3 O FIRE
2. Figure 6 3 Smoke Detectors Wiring into Loop of Type 1 6 2 1 2 Combined Smoke and Heat Alarm Loop Bring the provided termination resistor 4 7 kQ into the alarm loop as shown in Figure 6 4 Here Riem is for the termination resistor mentioned above SD is for a smoke detector HD is for a heat detector R 0 510Q is a resistor brought in series with smoke detectors depends on the type of the detector Rs 8 2 KQ is a resistor brought in parallel across a heat detector HD bos E Rs Rsh SD Rterm loop Figure 6 4 Smoke and Heat Detectors Wiring into Loop of Type 2 info bolid ru overseas bolid com 65 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 6 2 1 3 Heat Double Response Recognizable Alarm Loop Bring the provided termination resistor 4 7 kQ into the alarm loop as shown in Figure 6 5 Here Rierm is for the termination resistor mentioned above HD is for a heat detector Rs 4 7 KQ is for a resistor brought in parallel across a heat detector HD HD ete ae sth C4 Ce Rsh Rsh Rterm loop lt Figure 6 5 Heat Detectors Wiring into Loop of Type 3 6 2 2 Connecting Circuits to the Contacts 4 6 7 Connect if necessary the door open sensor door contact or another detector the discharge monitoring circuit and the extinguishing equipment fault circuit to the panel PCB terminal blocks marked as 4 6 and 7 respectively Any contact
3. 45 3 8 12 Fire 72 ER 45 3 8 13 Pre discharge Delay Ee 46 3 8 14 Blocked ReleaSe nnnnnnnnnnnnnnnnnnnenrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrne 46 info bolid ru overseas bolid com 3 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 7 8 4 QUON COMEDIT m eS 47 3 8 16 muhel iim t X 47 3 8 17 ITI qu E 47 3 8 18 Emergency HOlBaSB useiciebesiutessadsetistusabakeba la baneta Mon sRE EUER HNa AU StEEUE 47 3 9 The Modes to Release the Fire Suppression System 48 3 MEME 0091 27 17 E 48 3 9 2 Automatic Release M 48 3 10 Panel Indication me 49 3 11 External INGICQHON 2c ee occ eee 53 3 12 Panel Co operation enn 55 3 12 1 Zones Monitored by the Network Controller 55 3 12 2 Outputs Monitored by the Network Controller 56 3 12 3 Implemented Network Controller Commanads s 56 3 12 4 Panel Messages Being Transmitted to the Network Controller 56 3 12 5 S2000 KPB Messages E Q 58 3 12 6 Control Commands Transmitted to S2000 KPB 58 KENELLCHUIBQ4U M E R X X X P 58 STANDARD DELIVERY MARKING AND PACKING 60 4 1 Standard Delivery oor acess eaten 60 S HE ug m 60 Bg POOR uiii A E 61 GENERAL INSTHUCTIONS au
4. Using a screwdriver tighten terminal screws if necessary Repair the connection if there is any wire broken Replace wires with broken covering Inspect operating the panel indicators push buttons internal and external audible alarms and visual alarms by switching the panel to the Test mode see clause 3 8 5 info bolid ru overseas bolid com 79 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 80 DISPATCH LIST 2 Inspect and clean the panel in accordance with the 1 1 1 8 steps of the Dispatch List 1 Check the panel operability Simulate detector actuating and ensure the indication messages and control commands are in agreement with the mode programmed Disconnect the mains power and check the panel operability similarly to the procedure mentioned above Measure the isolation resistance as follows Disconnect the mains and backup powers Couple the 220 V block terminals Using megaohm meter measure the isolation resistance between the Earth and the Live terminals The isolation resistance value should be no less than 20 MQ www bolid com S2000 ASPT BOLID Contact Information 9 BOLID CONTACT INFORMATION ZAO NVP BOLID 4 Pionerskaya Str Korolev Moscow Region Russia 141070 Tel fax 7 495 775 7155 E mail info bolid ru overseas bolid com Web site www bolid ru www bolid com info bolid ru overseas bolid com 81 ISTE FIRE ALARM AND EXTINGUISHING CONTROL PANEL Appendix A Calculating the
5. address unique The panel doesn t detect The interface line Find out and repair the connected S2000 KPB RS 485 2 failure modules The S2000 is inoperable KPB indicator flashes the panel sounder beeping Interface lines A2 and B2 are interchanged Check and correct if necessary The jumper XP2 connecting the EOL Terminator to the RS 485 2 line is set improperly Ensure the EOL resistor jumper is put on if the panel is the first or the last device in the RS 485 2 interface line or removed otherwise Some S2000 KPB modules have the same addresses Check and change if necessary S2000 KPB addresses being in use so that they have been unique info bolid ru overseas bolid com 77 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 8 MAINTENANCE The S2000 ASPT maintenance needs to be performed by trained personnel having learned closely this Manual and been aware of the panel design along with the operating rules All maintenance operations have to be carried out by a person knowledgeable in the electrical installation work codes It is necessary to comply with safety precautions exposed in clause 5 1 of this manual It is obligatory to keep up the periodicity and technological order and technique of accomplishment of maintenance routines Disconnect the panel from the mains and backup power before you begin the working To ensure that your system is fully operational perform the m
6. 2 82 www bolid com S2000 ASPT Thus if there are no external devices connected to the 24V panel output then backup battery of the capacity of 4 5 Ah supplies power to the panel for 24 hours provided that a visual alarm connected to the VAS panel output consumes no more than 80 mA 2 Evaluating maximum I for 3 hours of operating in the Fire mode Taking into account 25 reserved battery capacity the average current delivered by a battery during backup supplying can be evaluated as Law A a P lt 0 75xW 3 0 06 Ampl Since visual alarms VA1 and VA2 are turned on in a flashing mode and can be turned on simultaneously only in the Emergency Launch mode so the maximum value can be evaluated as I 20 5 1 0 5 I amp I 0 75 15 1 Amp 3 For a 4 5 Ah battery we obtain that lpackup 1 125 Amp I lt 1 065 Amp 4 VA1 VA2 VAS SA 24V det dI The values must comply with conditions and are defined depending on specific alarms The procedure of calculation is as follows 1 Based on the technical specifications for visual and sound alarms being in use find the values of current 1 1 47 V 1 je 2 Based on the panel wiring diagram for operating calculate the 3 Calculate the value based on the formula 1 and the conditions 2 for the quiescent mode 4 Calculate the value based on the formula 3 and the conditions 4 for the Fire mode info bolid ru overseas bolid c
7. 6 4 1 Changing Configuration Parameters by Means of UProg To change the configuration by means of a computer follow these steps 1 6 4 2 Connect the RS 485 1 port of the panel to the COM port of the PC which the UProg Configuration Tool is installed on through one of the Bolid manufactured interface converters PI GR S2000 PI 2000 USB USB RS485 or S2000M in programming mode Ensure the backup battery is connected to the panel Turn up mains power Wait until Pre operation mode is finished Run the UProg program of version no less than 4 0 0 905 Select the proper COM port and start the device finding procedure NOTE The program ORION PROG EXE can be downloaded from the sites of the Bolid Company hittp bolid ru and www bolid com The program having found the connected devices select the panel by scrolling the device list Set the proper configuration parameters and save changes by activating Write Configuration command If necessary change the panel network address by using the Network Address command Changing the Panel Network Address by Means of the S2000M To change the panel network address by means of the S2000 S2000M console follow these steps 1 Connect the panel to the S2000 S2000M console via RS 485 1 interface line 2 Wait until S2000 S2000M console has detected the S2000 ASPT panel 2 Press the PRG console key 3 Enter the password 4 Select th
8. Open Failure status Short Failure status The statuses of alarm loops are defined depending on their parameters accordingly with Table 3 2 Table 3 2 Alarm Loop Parameters in Various Statuses Alarm Loop Parameters dni Open Short Type Operating Responded 1 resistance Smoke 2 2 to 5 4 KQ resistance double response recognizable resistance resistance Smoke detectors 0 1 to 1 8kQ gt 6 6 kQ 100 Q consume current from 0 to 3 milliamp resistance 2 resistance Combined Ad 0 1to 1 8kQ resistance resistance smoke and Smoke detectors or gt 16kQ lt 100 0 heat consume current from 6 6 to 44 4 kQ 0 to 1 2 milliamp 3 Heat double resistance resistance resistance resistance response 2 2 to 5 4 kQ 6 6to25kQ gt 30kQ lt 1 8 kQ recognizable Alarm loop resistance can be estimated based on its measured ADC value by using the formula as follows info bolid ru overseas bolid com 27 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 280 8 Ro ADC A KO Where Rio is the actual resistance value of an alarm loop and ADC is the measured ADC value of the resistance Reading the ADC values can be requested by means of the network controller tools using the loop control menu The panel provides powering active two wire detectors through alarm loops The maximum number of detectors to be wired into any alarm loop can be estimated by formula N Imax i where N is the number of
9. 29 EERE FIRE ALARM AND EXTINGUISHING CONTROL PANEL The maximum commuting current for each output is 1 amp in permanent mode Up to 2 amp for 2 s in pulse mode The maximum circuit controlling current is 1 5 milliamps The panel recognizes the following statuses of the annunciator appliances as Normal Operating status Open Failure status Short Failure status These statuses are defined depending on a voltage of alarm output negative terminal relative to 12 V output one in agreement with Table 3 4 Table 3 4 Alarm Circuit States Operating Open failure Short failure Voltage anedon ON OFF on oF os V d V Less than More than More than Less than 0 05 V 4 1 V 4 5 V 0 3 V 3 6 2 Monitoring Releasing Circuit The panel monitors the releasing circuit for open and short failures both for quiescent condition and while agent releasing If the panel is used in a gaseous extinguishing system the release is considered to be successive after pressure detector having actuated If the release pulse has completed but the pressure detector doesn t respond or its circuit is in fault the release is considered to be failed In such a case duration of the release pulse must comply with the maximum time of the extinguishing agent releasing The release circuit parameters met the requirements listed in the Section 3 6 1 3 7 Panel Configuration Parameters To adjust the panel for particular application it
10. ALARM Oo SIREN RESET O VISUAL ALARMS FAULT WARNING O CALL POINTS 7 FIRE DISABLED DOOR CIRCUIT TROUBLE 10 FIRE SUPPRESSION O rpm e O w RELEASE CIRCUIT E DISCHARGE Q AUX EQUIPMENT 2 OL mone jJ MODE i MASS PRESSURE Q Som EXTERNAL FAULT S2000 AS PT 11 4 5 12 13 6 T Figure 2 1 Basic Panel Elements 1 Control Board 5 Power and Earth 9 Front Plate 2 Main PCB Terminals 10 Key Switch 3 Tamper Switch 6 Transformer 11 Mechanical Lock 4 F1 Fuse Holder 7 Panel Base 12 Battery Leads 8 Panel Top Cover 13 Backup Batteries info bolid ru overseas bolid com 13 EME 2 2 Panel Front Plate FIRE ALARM AND EXTINGUISHING CONTROL PANEL A number of light indicators and push buttons as well as a key switch are located on the panel front plate as follows 2 2 1 Front Plate Indicators There are 27 light indicators LEDs on the panel front plate as shown in Figure 2 2 Its destination and light modes are represented by Table 2 1 CONDITION INPUTS OUTPUTS O PREALARM O FIRE ALARM Z RESET FAULT WARNING DISABLED m O O wi O te suence O XX O w2 O SIREN O E LOOP 3 O VISUAL ALARMS O A O CALL POINTS O FIRE BOLID DOOR CIRCUIT O TROUBLE FIRE SUPPRESSION 6 4 O Aana O i O RELEASE CIRCUIT O DISCHARGE O AUX EQUIPMENT O amp M sns OQ MASS PRESSURE O s2000
11. Battery Operating Time and Average Consumed Current The capacity of a backup battery must provide powering the panel for 24 hours in the Quiescent mode and 3 hours in the Fire mode The panel is intended to be supplied by a battery with voltage rating of 24 V The backup battery operating time is defined by its capacity and by total load current consumed by the outputs VA1 VA2 VA3 SA and 24V This dependence is expressed by the formula Lm J Hr where Top the battery operating time in hours W the battery capacity in Ah I the total load current in Amp L VAI VA2 VA3 SA 24V I T T Td L Amp The relationship between the I current and the battery supplying current lar in the 0 0 5 A range can be considered as linear qo I gt 0 06 Amp The panel provides housing two assembled batteries 12 V 4 5 Ah each within the panel enclosure bat 1 Evaluating maximum I for 24 hours of quiescent operating Taking into account 25 reserved battery capacity the average current delivered by a battery during backup supplying can be evaluated as Poo 0 75 a Amp Because the current consumed from the battery han must not exceed the average current Ibackup SO W X I UTI 0 06 Amp Since all visual and sound alarms except the VAS are disabled in the Quiescent mode and don t consume current therefore X VA3 24V l Hl I A 1 For a 4 5 Ah battery Ipackup 0 14 Amp I 0 08 Amp
12. Loss of communications with any Turned on for 1 s once per two connected S2000 KPB module seconds Table 3 29 Power Indicator On Batteries Indicator Indicator Behavior lbid On Batteries mains power failed batteries in norm Turned on for 1 s once per two seconds Lit steady 52 www bolid com S2000 ASPT Technical Description T Indicator Behavior Panel Condition mm E t3 Battery fault Mains power in norm Lit steady Turned on for 1 s once the batteries failed per two seconds Full power fault both mains and backup power failed Power shutdown Turned on for 1 s once Turned on for 1 s once per two seconds per two seconds Table 3 30 Device Failure Indicator Device Failure Mode Turned on for 1 s once per two seconds 3 11 External Indication The tables below describe the behavior of external indicators connected to the panel Table 3 31 SIREN SA Output Turned on for 1 5 s once per every 2 seconds info bolid ru overseas bolid com 53 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Table 3 32 EXIT Sign VA1 Output Panel Condition Output Behavior Pre discharge Dela eee ee y Turned on for 0 5 s once per second Emergency Release Release Extinguishing Of Oh Of Table 3 33 KEEP OUT Sign VA2 Output Panel Condition Output Behavior Pre discharge Delay Fais Ac Turned on for 0 5 s once per second Release E
13. at least one related loop is disarmed the relay is O n Upon Disarming switched off Switch On If at least one related loop is armed the relay is Off Upon Arming switched on Switch Off If at least one related loop is armed the relay is O i n Upon Arming switched off NOTES 1 means that the relay condition is defined by the conditions of input outputs related with the relay 34 www bolid com S2000 ASPT Technical Description 2 Off relay conditions means the following conditions of the contacts NO C opened NC C closed 3 On relay conditions means the following conditions of the contacts NO C closed NC C opened The Activation Time parameter defines the time the relay is activated for if the program is supposed to be time limited The maximum time the relay can be activated for is 65 535 periods of 0 125s 8192s total The relay can be linked with the following panel input zones Zone 1 Detection Loop 1 Zone 2 Detection Loop 2 Zone 3 Detection Loop 3 Zone 4 Door Sensor Circuit Zone 5 Manual Call Points Zone 6 Pressure Detector Zone 11 Remote Release Zone 12 Fire Protection Equipment Fault The relay can be linked with the following panel outputs Output 1 Visual Alarm 1 EXIT caution sign Output 2 Visual Alarm 2 KEEP OUT caution sign Output 3 Visual Alarm 3 AUTOMATICS OFF sign Output 4 Siren Output 5 Releasing Circuit The rel
14. in Sections 3 9 1 and 3 9 2 has occurred In such cases the panel enters the Blocked Release mode For a remote release the panel restores the Pre discharge Delay mode when the door sensor circuit has been restored For an automatic release the panel restores the Pre discharge Delay mode when The manual call points circuit has been broken or a Release Extinguishing Agent command has been received from the network controller or 46 www bolid com S2000 ASPT Technical Description The automatic release mode is repeatedly turned on if the Automatic Release Recovery configuration parameter is set on 3 8 15 Release Having entered the Release mode the panel generates the release pulse of given duration at the output of the releasing circuit R and gives release commands to the connected S2000 KPB modules The VA1 output usually assigned with an EXIT light sign is turned off while the VA2 output 2 usually assigned with a KEEP OUT light sign flashes To cancel the Release mode press the Extinguishing Reset button or give the relevant command by means of the network controller 3 8 16 Extinguishing If response of the pressure detector has been detected during the release pulse then the panel switches from the Release to the Extinguishing mode If the Pressure Detector Disabled parameter is set on then the panel transits to the Extinguishing mode just after the Release mode finishing To cancel the Extinguishing mode pres
15. of the Fire output are closed To cancel the Fire Alarm mode press the Fire Reset button or give the relevant command by means of the network controller 3 8 13 Pre discharge Delay The panel enters the Pre discharge Delay mode in cases of Manual call point circuit breaking a remote release or Receiving a release extinguishing agent command from a network controller a remote release or Actuating of two or more fire detectors connected to the panel an automatic release If the panel has entered the Pre discharge Delay mode then The SA sound alarm and the VA1 visual alarm 1 outputs are switching on and The FR output contacts are closed In this mode the Pre discharge Delay begins to be counted if programmed The value of the Pre discharge Delay is programmed individually for automatic and remote release While the Pre discharge Delay is being counted the panel internal sounder beeps Before 15 s remaining until the Pre discharge Delay has been expired the sounding frequency is duplicated and before 5 s sounding frequency is quadrupled The Pre discharge Delay having expired the panel transits into the Release mode To cancel the Pre discharge Delay mode press the Extinguishing Reset button or give the relevant command by means of the network controller 3 8 14 Blocked Release In automatic and remote launch modes counting of a launch Delay can be terminated if one of the conditions described
16. than the Seller In case of defect contact the security professional who installed and maintains your security equipment or the Seller for product repair This one year Limited Warranty is in lieu of all other express warranties obligations or liabilities THERE ARE NO EXPRESS WARRANTIES WHICH EXTEND BEYOND THE FACE HEREOF ANY IMPLIED WARRANTIES OBLIGATIONS OR LIABILITIES MADE BY SELLER IN CONNECTION WITH THIS PRODUCT INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE ARE LIMITED IN DURATION TO A PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE ANY ACTION FOR BREACH OF ANY WARRANTY INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY MUST BE BROUGHT WITHIN 12 MONTHS FROM DATE OF ORIGINAL PURCHASE IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Some countries do not allow limitation on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you Seller does not represent that the product may not be compromised or circumvented that the product will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the prod
17. 10 Close shortly the door sensor terminals 4 The panel shall enter the Blocked Release mode The S2000M console shall display the messages LOOP TRBL SHORT 127 004 LAUNCH BLOCKED 127 010 and EX MODE MANUAL 127 009 sequentially Both the H2 and H8 indicators shall be off 11 Open the door sensor terminals 4 The S2000M shall display AUX ZONE RESTORE 127 004 the H2 indicator starting light in 2 s 12 Switch on the automatic mode again and repeat all the actions described in the item 9 The panel shall enter the Pre discharge Delay mode again The S2000M shall display the EX MODE AUTO 127 009 followed by LAUNCH DELAY 127 010 In 30 s the panel shall enter the Release mode the H5 indicator turning on Then the automatic release mode shall be turned off the S2000M shall displaying LAUNCH 127 010 followed by EX MODE MANUAL 127 009 The H6 indicator shall turn off while the H7 indicator shall start flashing 13 In 15 s the H5 indicator shall turn off the S2000M displaying the LAUNCH FAULT 127 010 NOTE The release fault message was generated because no response of the pressure detector has been detected during the release pulse 14 Press the Extinguishing RESET button followed by pressing the Fire RESET button The panel shall enter the Quiescent mode The S2000M console will sequentially display the messages LAUNCH CANCEL 127 010 ALARM RESET LP 127 002 ALARM RE
18. 5 1 End Of Line RS 485 2 End Of Line resistor connector X XP1 XP2 resistor connector IL Ll N y redd a FEEPFIBBBBEEBELE WEE FLT FR NO NC C 24V RE OV A1 B1 A2 B2 br e to the S2000M RS485 1 T1 XT1 o F1 0 5A frame ground Ao Resistors TLF R1 3 3 kOhm 0 25W R2 4 7 kOhm 0 25W gt Diode 1N4148 p LED 220V Live 4 o o T E 3 o z gt e N N 1 12V 4Ah Figure 6 9 Wiring the Panel for Testing 7 Open the S1 contact and close the S2 contact The H2 indicator shall flash with red the S2000M console displaying the FIRE SIGNAL 127 003 followed by the FIRE PREALARM 127 003 Open the S2 contact 72 www bolid com S2000 ASPT Getting Started 8 After 2 s since opening the S2 the panel shall enter the Fire Alarm mode the S2000M console displaying the FIRE ALARM 127 010 The H3 shall light steady and the H9 shall flash 9 Press the AUTOMATIC MODE button on the panel front plate The automatic release mode shall be turned on and the panel shall enter the Pre discharge Delay mode The S2000 M console shall display the message AUTOMATICS ON 127 009 followed by the message LAUNCH DELAY 127 010 The H8 indicator shall turn off while the H6 indicator shall flash
19. ARE NOT CONNECTED THE LOAD CONNECTION MODULES ALLOWING THE PANEL TO CONTROL THE CIRCUIT CONDITIONS SHALL BE INSTALLED CLOSELY TO A LIGHT OR SOUND ALARM WHILE COMMISSIONING AS WELL AS WHEN ANY OUTPUT IS NOT IN USE CONNECT A 1Ko 1W RESISTOR ACROSS THE RELEVANT TERMINALS info bolid ru overseas bolid com 67 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL load load connection connection black module black module load connection module white pers 2 3 black oO Figure 6 8 How to Connect Several Alarms to the Same Output The schematic can require some additional resistors in case if the total current exceeds the normal value 6 2 5 Connecting Releasing Circuit The releasing circuit is connected to the R panel terminals All required parameters are described in Table 3 1 If a releasing device imposes any additional limitation on the value of current then DO BRING a suitable resistor in series with the releasing device 6 2 6 Connecting Message Transmission Circuit If the S2000 ASPT is intended to transmit FIRE and FAULT messages to a fire department or a central monitoring station connect the appropriate circuits to the terminals marked as FR and FLT on the panel PCB correspondently A FIRE message is generated as a result of closing the FR output relay contacts while a FAULT message is formed as a result of opening the FLT relay contact 6 2 7 Connecting Auxiliary Equipment The engineeri
20. EME S2000 ASPT Fire Alarm and Extinguishing Control Panel Engineer s and User s Manual BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL ATTENTION To modify the panel configuration parameters use the program UProg exe of version 4 0 0 905 or higher 2 www bolid com S2000 ASPT Table of Contents T GENERAL cT 7 2 PANEL DESIGN iei ere eer en ee eee mitis easi oa eee emer eee ee 13 2 1 Panel View and Basic Elements ccccccccccccecrsnsssnennnnnnnnnnnnnneneenenennneneees 13 22 Panel Front Plate 14 o C HMENI C qu i Terme er 14 2 2 2 Push Buttons 17 23 Panel Internal PC Board ortae ao tta cete ase tiran inde 19 2 3 1 PCB Terminal rect E Rm 20 2 3 2 PCB XP1 and XP2 Jumpers ssssssssssssssssssseeeee nnne 21 2 3 3 Voltage Test Points T 21 24 Panel Tamper SWUNG sist ee eee 21 2 95 External OQ 22 4 TECHNICAL DESCRIPTION sgscsvesscccecescestccwecesacenccactscssseneevessctesstreseescesis 23 3 1 Access Levels for the Indications and Controls 23 3 2 External Circuit Control Outputs eere erre ee nenas 24 3 8 Transmitting Fault Conditions to a Central Monitoring Station 25 3 4 Transmitting Fire Conditions to a Central Monitoring Station 26 3 5 Zone Monitoring iia te ete oi em dm MEE EE 26 3 5 1 Monitoring Alarm EOUD
21. Failed or Disarmed status the relay is switched off Otherwise the relay is switched on In case of a Fire Alarm the relay is switched on off twice per second in mode On for 25s and Off for 25s In case of a Fire Prealarm the relay is switched on off once per second in mode On for 25s and Off for 75s Fire Lamp In case of a Trouble the relay is switched on off once per 2 seconds in mode On for 25s and Off for 1 75s If all the alarm loops related with the relay are armed the relay is switched on Otherwise the relay is switched off Switch On For a Time If any related alarm loop has just been armed the relay Off Upon Arming is switched on for a given time Switch Off For a Time If any related alarm loop has just been armed the relay On Upon Arming is switched off for a given time Switch On For a Time If any related alarm loop has just been disarmed the Off Upon Disarming relay is switched on for a given time Switch Off For a Time If any related alarm loop has just been disarmed the On Upon Disarming relay is switched off for a given time Switch On For a Time If arming of any related alarm loop has just failed the O When Arming Failed relay is switched on for a given time ff Switch Off For a Time If arming of any related alarm loop has just failed the On When Arming Failed relay is switched off for a given time Switch On If at least one related loop is disarmed the relay is 27 Off Upon Disarming switched on Switch Off If
22. KPB O TEST Q EXTERNAL FAULT S2000 ASPT Figure 2 2 The Panel LEDs Table 2 1 Panel Faceplate Indicators Indicator Color Destination PREALARM Red The generalized indicator for prealarm fire conditions FIRE ALARM Red The generalized indicator for fire conditions The generalized indicator for fault FAULT WARNING Yellow condone DISABLED Vallow The generalized indicator for disabled conditions 14 www bolid com S2000 ASPT Panel Design Indicator Color Destination The generalized indicator for the EXTINGUISHING neo Extinguishing operating mode of the panel Indicates whether the automatic mode to AUTOMATIC Red release extinguishing agent is set on of off MODE also indicates the current status of the VA3 output TEST Yellow Indicates the panel Test mode LOOP 1 Red Indicates prealarm fire alarm and fire LOOP 2 SPONTE GOP CSL o LOOP 3 Yellow Indicates fault and disabled loop conditions Indicates one or more manual call points Red wired to the MCP panel terminals being activated CALL POINTS E ede pee ML E Indicates the MCP circuit failure or Yellow disablement as a result of pressing the same name button Indicates the circuit with door open HORSE Ow detector included being broken or failed Indicates remote release command having Red been received over the RS 485 1 interface REMOTE line COMMAND eee uc IEEE pies Indicates remote relea
23. KPB relay modules allowing increasing the number of release circuits info bolid ru overseas bolid com 7 Erme FIRE ALARM AND EXTINGUISHING CONTROL PANEL The panel can be powered by mains power supply 220 V ac 50 Hz or backup power supply two connected in series batteries 12 V d c DO NOT operate the panel without connecting batteries to it The panel provides round the clock operation The panel must not be used under aggressive or dust ambient conditions or in explosion hazardous premises The panel construction design provides the ingress protection rating in accordance with IP30 IEC 529 89 The panel has been ready to operate after no more than 30 s since powering on The average operating life is 10 years panel s both backup batteries needing to be replaced once every 5 years Do not replace only one battery but rather both batteries must be replaced The panel weight is no more than 6 kg without backup batteries Overall dimensions are equal to 305x255x95 mm The panel is intended to be used under the following ambient conditions operating temperatures from 0 C to 50 C provided that backup batteries are housed within the panel and from 30 C to 50 C provided that backup batteries are stored separately relative humidity up to 98 for 25 C non condensing vibration load from 1 to 35 Hz with maximum acceleration 0 5 g Following are the schemes that show some ways to use the pa
24. M ME Indicates fault or disabled condition of the Yellow e releasing circuit Red Indicates that the relay is activated AUX EQUIPMENT 302s ee Yellow Indicates that the output is disabled Indicates that one or more of the S2000 2000 KPB Yellow KPB modules connected to the panel failed or are isolated Pewee Green Indicates that the panel power is turned on Indicates faults of mains power backup On Batteries Yellow batteries and the battery charger A Device Failure Yellow Indicates the Device Failure panel mode 16 www bolid com S2000 ASPT Panel Design Note For the VISUAL ALARM indicator activating one of the VA outputs by the panel is more priority condition to display than circuit failure condition of the other VA output The behavior of all the indicators in particular conditions while panel operating is described below in the Section 3 10 2 2 2 Push Buttons There are 17 operating push buttons and a key switch on the panel front plate Locating the push buttons on the panel front plate is shown in Figure 2 3 The push button and key switch functions are demonstrated by Table 2 2 CONDITION INPUTS OUTPUTS PREALARM LOOP 1 C SILENCE XE FIRE ALARM LOOP 2 O C SIREN RESET C LOOP 3 C VISUAL ALARMS IN FAULT WARNING C C CALL POINTS FIRE BOLD DISABLED DOOR CIRCUIT TROUBLE FIRE SUPPRESSI
25. ON amp B prey C onl RELEASE CIRCUIT DISCHARGE C AUX EQUIPMENT AUTOMATIC NOME MASS PRESSURE S2000 KPB TEST C EXTERNAL FAULT S2000 ASPT Figure 2 3 Panel Push Buttons and Key Switch Table 2 2 Push Button Functions Fire RESET Cancels the Fire mode of the panel Extinguishing E ae RESET Aborts extinguishing AUTOMATIC r aes automatic discharge of extinguishing MODE equipment info bolid ru overseas bolid com BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL TEST Switches the panel to the Test mode LOOP 1 LOOP 2 visa i the input zones of automatic etection LOOP 3 CALL POINTS Disables Enables the Manual Call Point circuit REMOTE Disables Enables the remote release commands COMMAND received via the RS 485 1 interface DISCHARGE Disables Enables the Pressure Detector circuit SILENCE Silences the internal sounder Disables Enables the circuits controlled by the outputs EUREN VA1 and VA229 Disables Enables the circuits controlled by the outputs VISUAL ALARMS lere and VAS pre discharge and discharge alarms FIRE Disables Enables the FIRE output FAULT Disables Enables the FAULT output 2 3 2 3 RELEASE CIRCUIT Disables Enables the releasing circuit AUX EQUIPMENT Disables Enables the NO NC C output Locks Unlocks pressing the panel buttons by means of eye the key provided Note The digits 1 2 and 3 denote the access levels for which th
26. S eoo Eats ra RE xcu EE M DEd n EEnE 26 3 5 2 Monitoring Input Circuits 4 to 7 eeesssssssssssssssssee eene 28 3 6 Monitoring Panel Outputs eeeeeeee sees ee eese e eene enne a anat nana nna nnn 29 3 6 1 Monitoring Annunciator Appliance Circuits susss 29 3 6 2 Monitoring Releasing Circuit 30 3 7 Panel Configuration Parameters eee esee eese e eiiis 30 3 7 1 Parameters of Alarm Loops and Monitored Circuits 31 3 7 2 Parameters of the NO NC C Relay Control uusss 33 3 7 3 Panel Configuration Parameters ence p apres ES eee prd P a sine 36 3 7 4 System Configuration Parameters sse 38 O72 TRE Factory Default SOS se tevss ebrei ipae tee setis te pta eq Eep R2 epi ssa SE es 39 48 Panel Operating Modes entr ertt easet eA 41 VES NEN Loo Io MEER 42 3 8 2 Device FallUfe iiuss esae rk EE FE EREREEFRERERERKRERRREEREKERERERKERRERERRERREEREE 42 3 8 3 Quiescent MOUO oio Rx Dra eee ee 43 vir PI tc RnR REDE ep RE a a Ak NESE Tee eee 43 ine S co CC 43 voro 43 3 8 7 On BHlBlIOS ci ai PEU ee TUE UM 44 VE RECMEESTI CI II s 44 5 8 9 Master Key Programming ss eeu o eR FREE R M ERRARE 44 3 8 10 User Key Programming Liuius perpe ba Rok BER EEEREEEREEREEERFERRREREREKERERERE 45 3O11 Proalati RT
27. SET LP 127 003 ARMED LP 127 010 ARMED LP 127 002 and ARMED LP 127 003 15 Shut the panel power off by removing the F1 fuse from the fuse holder on the panel main PCB Within a minute the panel shall enter the On Batteries mode The H2 indicator shall turn off the S2000M console displaying AC POWER FAILED 127 007 info bolid ru overseas bolid com 73 Erm FIRE ALARM AND EXTINGUISHING CONTROL PANEL 16 Restore the panel power again The panel shall enter the Quiescent mode the S2000M displaying the AC POWER RESTORED 127 007 17 Detach the red wire from the relevant backup battery In 15 minutes the panel shall enter the Battery Failed mode the H2 indicator turning off The S2000M shall display BATTERY FAILED 127 008 18 Connect the red wire to the battery again Wait for 15 minutes and press the Fire RESET button The panel shall enter the Quiescent mode the S2000M displaying the BATTERY RESTORED 127 008 message 19 Detach the backup batteries Detach the panel mains power connection Close the panel top cover and turn the key switch o the Locked position 6 6 Performance The basic panel performance and operations are described by Sections 3 8 and 3 9 of this Manual The number of release outputs can be expanded up to 97 ones in case of using S2000 KPB up to 16 modules per a single panel The addresses of the S2000 KPB modules connected to the panel via the panel RS 485 2 port
28. T6 sounder BOL D i Gre o gt SECURITY SYSTEMS o 5 tel 775 71 55 tamper switch E HL1 http www bolid c em L3 internal indicator contacts control board e mail info bolid ru battery connection terminals RS 485 1 End Of Line RS 485 2 End Of Line E resistor connector N xp4 XP2 resistor connector EOCCATECH Geene Mhehe CEEE FR SA 1 3 4 5 6 7 FLT NO NC C 24V RE OV A1B1 A2 B2 R VA1 VA2 VA3 af H i 5 S TS 2 J l y l y JI z o oN a 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K 8 o o X c a b r b jr bjr b r o n Ww Seo 990 Pg ey Ya v 3 fe a xe 8 amp gt S52 A amp 33 2 1 2 1 f2 1 2 1 2 1 8 E E ou 9 fire detectors a amp 2 H3 x Hs ST ou iButton od SS 5 x 5 58 v ot 8s d Ec Oo 3 4 13 4 3 4 8 4 38 4 9 8 B Ba 595 reader T or 5 E o 9 gg 2 g w w b w b 5 8 3 of se reader LED 2 8 18 8 aed red LYI o os 8B B E Pan oo EZ g oO E Be 55 EQ c s so sg g Bx Bo fg 7 ft u Sz gt SY 26 gt Es E 5 E EB aot load connection module aA ES N 8 Ru Hi q Figure 2 4 Panel Printed Circuit Board Layout The panel PCB terminal blocks see Figure 2 4 are designed to 1 2 3 connect alarm loops 1 2 3 with fire detectors included 4 connect door open sensors 5 connect manual call points 6 co
29. age if its value has fallen below 12 V then replace or charge the battery The panel LEDs are not lit while the internal indicator HL1 on the main PCB flashes rapidly The cord to couple the main PCB and the indication PCB is disconnected or defective Connect the cable or check the proper connecting FAULT WARNING indicator flashes the panel making no sounds The tamper switch has been released or out of service Remove the panel cover and check the tamper switch When the panel cover is closed the plunger must be pushed within 15 s After panel having been turned on for more than 10 s the FAULT WARNING and the A indicators flash the panel sounder being silent Device is being in the Powering On mode Mains power voltage is below the normal range Check the value of the mains voltage at the panel power input and the same value at the control point 40 info bolid ru overseas bolid com 15 BOLD FIRE ALARM AND EXTINGUISHING CONTROL PANEL After powering up the panel the FAULT WARNING and the indicators flash the panel sounder sounds interruptedly and the HL1 internal indicator on the main PCB flashes rapidly A firmware error has been detected the panel is being in the Device Failed mode Update the microcontroller firmware see Section Device Failure After powering up the panel the indicators FAULT WARNING and A flash the panel s
30. aintenance according with dispatch lists as follows According to the dispatch list 1 monthly and According to the dispatch list 2 in case of receiving at least two nuisance alarms within a month Try out all the control and measuring equipment Check the panel isolation resistance annually in accordance with the step 4 of the dispatch list 2 Register all the maintenance operations in a special log 78 www bolid com S2000 ASPT Maintenance 1 1 1 2 1 3 1 4 1 5 1 7 1 8 1 9 DISPATCH LIST 1 Visual Checking and Cleaning the Panel Disconnect the panel from the mains power supply and remove dust dirt and other contaminations from the panel surface with the help of waste grainer brush Visually check the panel and remove of signs of corrosion if present using a waste grainer brush and an oil based solvent Remove the panel top cover and clean all the terminals from dirt dust and corrosion using a waste grainer brush and an oil based solvent Remove the dust dirt or humidity from the battery surface using waste and grainer brush Measure the voltage at each battery output If the voltage value has dropped below 12 V replace both backup batteries Check the fuse F1 rating 0 5 A and usability Check if the panel is grounded properly and the earth wire is operable Ensure connecting the external circuits matches with panel output terminals using the panel connecting diagram see Figure 2 4
31. anel without connecting batteries to it The panel generates an AC POWER FAILED message within 60 s since mains power has dropped below 13010 V or mains rectifier output voltage test point 40 on the main panel PCB has been below 30 0 5 V The panel generates an AC POWER RESTORED message when mains power has exceeded 180710 V or mains rectifier output voltage test point 40 on the main panel PCB has exceeded 4040 5 V If the mains power failed the panel automatically begins to consume power from backup batteries When mains power has been restored the panel returns to consume power from mains The panel generates a BATTERY FAILED message within 15 minutes since the battery voltage has dropped below 22 0 5 V under load current consumption 0 5 amp in the Quiescent mode When the battery voltage has exceeded 25 0 5 V the panel the panel generates a BATTERY RESTORED message If mains power failed and the backup battery voltage has dropped below 20 5 0 5 V the device power is shut down full discharge The wattage consumed from mains power doesn t exceed 30 W The method of calculating the value of current consumed in the quiescent mode from backup batteries is represented in Appendix A info bolid ru overseas bolid com 59 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 4 STANDARD DELIVERY MARKING AND PACKING 4 1 Standard Delivery Following is the list of the S2000 ASPT components provided v T
32. arge Delay Release Extinguishing Release Fault Emergency Release Blocked Release info bolid ru overseas bolid com 41 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 3 8 1 Pre operation The panel switches from the power off condition to the Pre operation mode after mains power having been turned on In this mode the panel has analyzed the voltage at the AC DC converter output for 3 s and then reads zone conditions the automatic release mode and the panel mode from the panel non volatile memory The only indicator on the panel faceplate which is lit is the Power indicator V If the voltage at the AC DC converter output the control point 40 on the panel PCB is below than 30 V or unstable the panel keeps being in the Pre Operation mode infinitely The panel leaves the Pre operation mode when the converter output voltage has a stable value higher than 30 V Having left the Pre operation mode the panel makes a sound and returns to a mode in which it was before turning the power off If before turning the power off the panel was in the Release mode see below extinguishing will be aborted automatically while turning the panel on to avoid second releasing of the fire protection system If the panel keeps the Pre operation mode and the TEST indicator flashes it means that the panel has not been completely tested upon manufacturing To switch the panel to the Quiescent mode see below press and hold th
33. ase of double detector response in a single loop while for loops of the type 2 this one can be discharge when two detector responses in two different alarm loops The loop of type 1 is intended to wire fire detectors with normally opened contacts powered by loop with actuated detector voltage rest of 4 5 to 8 V and minimum operating voltage no more than 12 V An additional resistor has to be brought in a loop in series with fire detectors The values of the additional resistors are represented in clause 6 2 1 The loop of type 2 is intended to wire both smoke normally opened detectors without any series resistors and heat normally closed detectors with shunt resistors connected across is contacts as shown in Figure 6 4 The loop of type 3 is intended to wire fire contact detectors with normally closed contacts A shunt resistor needs to be brought in parallel across the detector contacts See clause 6 2 1 for more information Loop Analysis Delay parameter defines the time period during which the panel doesn t consider loop resistance changes after power reset The value of this delay is defined by detector pre operating time its minimum value being equal to 3 s If necessary the function of repeated request of actuated detector can be disabled by setting the Loop Requery Prohibition parameter on This feature is suitable if for example normally opened four wire detectors with separate power supplying are in use The Recovery Time pa
34. ates Operating Open Failure Short Failure From 2 2 kQ to From 200 Q to 1 8 KQ More than Less than 5 4 kQ or from 6 6 kQ to 25 kQ 30 kQ 100 Q The resistance of a monitored circuit can be estimated based on its measured ADC value by using the formula as follows R ADC 126 4 0 53 ADC where Ry is the actual resistance of the monitored circuit and K9 ADC is the measured ADC value of the resistance Reading the ADC values can be requested by means of the network controller tools using the loop control menu The integration time that is needed the panel to detect circuit breaking is 1 s for manual call points circuit and 300 milliseconds for other monitored circuits 3 6 Monitoring Panel Outputs The panel provides monitoring for conditions of the following panel outputs output 1 visual alarm 1 EXIT light sign output 2 visual alarm 2 KEEP OUT light sigh output 3 visual alarm 3 AUTIMATICS OFF light sign output 4 audible alarm fire siren output 5 releasing circuit outputs 21 to 26 executive outputs of the first S2000 KPB outputs 31 to 36 executive outputs of the second S2000 KPB outputs 171 to 176 executive outputs of the 16 S2000 KPB 3 6 1 Monitoring Annunciator Appliance Circuits The panel monitors the VA1 VA2 VA and SA circuits for open and short failures both in activated and deactivated conditions info bolid ru overseas bolid com
35. ay should be linked to one or more outputs only for the executive program No 14 Trouble output If the relay is linked with a zone output the control commands from the network controller are ignored Local relay control is in priority to centralized relay control The relay to be able to be controlled remotely by network controller commands do the following Remove all links between the relay and panel inputs outputs in the panel configuration by UProg tools Select any executive program with the proper relay initial conditions On or Off in the panel configuration by UProg tools info bolid ru overseas bolid com 25 Erm FIRE ALARM AND EXTINGUISHING CONTROL PANEL n the configuration of the network controller link the relay with the proper partitions assign the relay to proper executive program and define the required delay and activation time If the relay is not linked to the panel inputs outputs in the panel configuration the Executive Program defines only the initial condition of the relay that is the condition of the relay just after powering on the panel If the relay is to be controlled centrally in most cases the program is given which supposes the Off initial condition for example the program No 1 Switch On After turning panel power on and till receiving the centralized command which is to switch the relay to the required condition some time can be needed So if the centralized program
36. can be necessary to change some configuration parameters stored in the panel non volatile memory The panel configuration parameters can be sorted into the following four groups Parameters of alarm loops and monitored circuits Parameters to control the NC NO C relay output Parameters of the panel System parameters 30 www bolid com S2000 ASPT Technical Description 3 7 1 Parameters of Alarm Loops and Monitored Circuits Table 3 5 Loop and Circuit Parameters 1 smoke with double Determines the control algorithm actuating recognition and available types of detectors to 2 combined smoke be connected normally opened or and heat without closed detectors recognition of two double actuating or more detectors actuating in one recognition loop 3 heat with double actuating recognition Loop Type The pause before alarm loop status Loop analysis having begun since power Analysis reset It is defined by the time 3 to 255s Delay period necessary for two wire detectors operating mode recovery Loop Requery Prohibition Gives the time from the moment of Recovery restoring a monitored circuit until Time the moment of considering the circuit as being in norm Blocks the repeated status request of the actuated detector On Off 0 to 255 s Loop Type parameter defines the panel a way to control the alarm loop and detectors included The Alarm Integration Time value for all loop types is 1s The pa
37. can coincide with the addresses of the devices connected to the panel RS 485 1 port The addresses of the S2000 KPB modules which are used to expand the number or releasing outputs MUST be enrolled in the panel configuration Not only an S2000M console but also a PC with ARM Orion installed can co operate with the panel as a network controller Some typical ways to use the S2000 ASPT panel are shown in Section 1 of this Manual Remote monitoring and controlling the panel can be implemented with the help of an S2000 PT control and indicating equipment To do this the network controller MUST be programmed properly by means of the PProg programming tool 74 www bolid com S2000 ASPT Troubleshooting 7 TROUBLESHOOTING Use the Table 7 1 to resolve minor S2000 ASPT installation and operating problems Table 7 1 Problem Resolving Problem Possible Cause Solution If connected to the mains power the panel is not turned on The panel indicators are not lit No utility voltage or F1 fuse is out of service Check the S2000 ASPT power supply connection Replace the fuse When mains power has been shuts down the panel shuts down too but in case of the mains power supplying the panel indicates the battery fault Contact impairment between battery leads and terminals The battery is inoperable or discharged Check the contacts between the panel and the battery and repair if necessary Measure the battery volt
38. ccess to panel operations Access Level 1 The access level 1 is expected to be used by operating personnel and safety officers responsible for safety supervision who might be expected to investigate and respond to a fire alarm or a fault warning The following operations are available for these users Monitoring indication of light emitting indicators of the panel front plate and Silencing the panel sounder if activated No special procedures for entry to access level 1 is needed this level is associated with the position of the Key Switch on the panel front plate see Figure 2 3 Access Level 2 The access level 2 is expected to be used by persons having a specific responsibility for operating fire protection equipment and who are trained and authorized to operate the panel in the following conditions Quiescent mode Fault mode Prealarm mode Fire Alarm mode Pre discharge Delay mode Release mode Extinguishing mode The access level 2 enables users to implement all the operations available for the access level 1 and additionally the following operations Resetting the Prealarm and Fire Alarm panel operating modes Resetting the Extinguishing Pre discharge Delay and Release panel operating modes Switching on off the mode of automatic release To entry for access level 2 switch the Key Switch on the panel front plate see Figure 2 3 to the B position by means of th
39. cun sonam ecu oaa a atu run n nae a na ck S raa pnu enn aee rare 62 CNMEE C Acn ceca ac es eee 62 Es WME 18 2 0 het E RESTA UI 62 GETTING S GAR TED i ccicascsescsnecacepssdescedacsncanvctsanavensesncnssiaccessaaceaeccasceerees 63 6 1 Mounting the Panel tea eats eee 63 6 2 Connecting the External Circuits ee eeeeeeeee eene nnne 64 6 2 1 Connecting the Alarm Loops cccssssccecceeeeeeeeeseeeesaaeeeeeeeeeesseeens 64 6 2 1 1 Smoke Double Response Recognizable Alarm Loop 65 6 2 1 2 Combined Smoke and Heat Alarm Loop eeuessssss 65 6 2 1 3 Heat Double Response Recognizable Alarm Loop 66 6 2 2 Connecting Circuits to the Contacts 4 6 7 uuueueeeueeussss 66 6 2 8 Connecting Manual Call Points 222 c ssccccceeeeeeeeeeeeteseeeeeeeeeeteeeeeeaaes 67 6 2 4 Connecting Light and Sound Alarms sess 67 6 2 5 Connecting Releasing Circuit eosessssssssssiiseeeeee 68 6 2 6 Connecting Message Transmission Circuit oossusss 68 6 2 7 Connecting Auxiliary Equipment esses 68 6 2 8 Connecting RS 485 Interface Lines suus 69 6 3 Connecting Power Supply eereeeee eene esee n nennen anam anna nnn nnn 69 6 4 Setting the Panel Configuration Parameters 70 6 4 1 Cha
40. d in the panel configuration 3 12 4 Panel Messages Being Transmitted to the Network Controller The panel can transmit to the network controller some event messages as follows EMERGENCY LAUNCH Fire extinguishing equipment has been launched that is the outflow of extinguishing agent has been detected without having received the launching pulse ARMED Detector status monitoring has been turned on 56 www bolid com S2000 ASPT Technical Description FIRE TRBL RST ARM FAILED FIRE SIGNAL FIRE PREALARM FIRE ALARM LAUNCHING LAUNCHING DELAY LAUNCH BLOCKED ILLEGAL CODE LOOP TRBL OPEN LOOP TRBL SHORT RELAY TRBL OPEN RELAY TRBL SHORT RELAY RESTORE AC POWER FAILED AC POWER RESTORE BATTERY FAILED BATTERY RESTORED TAMPER ALARM TAMPER RESTORE MANUAL TESTING ALARM RESET GAS PRESS SIGNAL EXTINGUISHING Extinguishing equipment operates normally Arming has failed due to the actuated status of detector Fire conditions have been detected Fire signal has been received and fire is probable Fire alarm The pulse for the fire extinguishing equipment launching has just been given out The condition for fire extinguishing equipment launching has been met and the launching delay is being counted Launching of the fire extinguishing equipment was block
41. detectors Imax is maximum load current Imax 3 milliamp for a loop type 1 Imax 1 2 milliamp for a loop type 2 is the current in milliamps consumed by each detector in the quiescent mode If an alarm loop of type 1 smoke double response recognizable is in use then the wired detectors have to retain their operability in case of loop voltage having fallen down to 12 V The integration time the time the panel needs to detect loop breaking is 300 milliseconds for all loop types 3 5 2 Monitoring Input Circuits 4 to 7 The panel provides monitoring for conditions of such input circuits as the door sensor circuit the manual call point circuit the pressure detector circuit and the fault circuit of fire protection equipment which have the characteristics as follows wire resistance without regard to termination resistors no more than 100 Q leakage impedance between two wires or between any wire and earth at least 50 kQ The termination resistor 0 5 W 4 7 kQ 5 has to be included into each monitored circuit said above The panel recognizes the following statuses of the door sensor and manual call point circuits Normal Operating status Activated Broken status Open Failure status Short Failure status 28 www bolid com S2000 ASPT Technical Description Table 3 3 gives the couples between the circuit parameter values and the relevant statuses Table 3 3 Monitored Circuits 4 and 5 in Various St
42. detectors or relay outputs of other devices can be used as status detectors or signal devices brought into the circuits connected to the 6 and 7 terminals Standard wiring of detectors along with termination series and shunt resistors is shown in Figure 6 6 Instead of door detectors or along with them other burglary alarm device output circuits can be wired into this circuit The number of door detectors not powered by circuit in question is unlimited If this circuit is not in use connect the supplied termination resistor of 4 7 kQ across the relevant terminals NC Detector Rseries 510 Ohm LI Rshunt 8 2 k I Rtermination 4 7 k NO Detector loop e Figure 6 6 Wiring Door Sensors or Pressure Annunciators 66 www bolid com S2000 ASPT Getting Started 6 2 3 Connecting Manual Call Points The circuit with manual call points included is connected to the 5 PCB terminals as shown in Figure 6 7 loop loop loop loop Figure 6 7 Wiring Manual Call Points You can include into circuit in question suitable manual devices designed for d c voltage If this circuit is not in use connect the termination resistor 4 7 kQ across the 5 terminals 6 2 4 Connecting Light and Sound Alarms Connect the light and sound alarms if used to the VA1 VA2 VA3 and SA terminals according to the Figure 2 4 and Table 3 1 DON T CONNECT ANY RATED LOAD TO OUTPUTS WHEN BACKUP BATTERIES
43. ditions include Short open failure of an alarm loop door sensor circuit audible or visual alarm circuit manual call points circuit pressure detector or fire protection equipment fault circuit Audible or visual alarm circuit overcurrent Mains or backup power supply failure Panel tampering Disablement of a zone circuit or output Receiving fault conditions from a connected S2000 KPB module Loss of communication with any S2000 KPB module info bolid ru overseas bolid com 25 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 3 4 Transmitting Fire Conditions to a Central Monitoring Station Transmitting fire conditions to a CMS is performed by closing of the contacts of the panel FIRE output in cases of as follows Panel entering the Fire Alarm mode Remote releasing the extinguishing system Emergency release when an extinguishing agent is being discharged without having received a release pulse 3 5 Zone Monitoring The panel provides monitoring for such physical and logic zones as zone 1 panel alarm loop 1 zone 2 panel alarm loop 2 zone 3 panel alarm loop 3 zone 4 panel door sensor circuit zone 5 panel manual call points circuit zone 6 pressure detector circuit zone 7 panel mains power control zone 8 panel battery power control zone 9 panel automatic release mode control zone 10 panel operating mode contro
44. e specified operations are enabled see Section 3 1 of this Manual Once the Fire RESET button has been pressed available for the access level 2 the panel resets all fire alarms and automatically arms all responded alarm loops Once the Extinguishing RESET button has been pressed available for the access level 2 the panel aborts the Extinguishing mode de energizes the releasing circuit R and switches the releasing outputs of the S2000 KPB modules if present to initial conditions Pressing the AUTOMATIC MODE button available for the access level 2 causes the panel to switch the mode of automatic release on and off If the automatic mode is enabled pressing the button will disable this one and otherwise if the automatic mode is disabled pressing the button will enable it If automatic mode is blocked for 18 www bolid com S2000 ASPT Panel Design example the door sensor detector circuit is broken pressing the button causes the internal sounder to make a long sound If the Test button is pressed available for the access levels 2 and 3 the panel enters the TEST mode see the Section 3 8 6 The LOOP1 LOOP3 and CALL POINTS buttons having been pressed the input zones of automatic detection and manual call points are armed disarmed The REMOTE COMMAND and the DISCHARGE buttons having been pressed the input of remote releasing commands and pressure detector monitoring are disabled enabled respectively Pressing
45. e 3 20 TEST Indicator Panel Mode Indicator Behavior Turned on for 0 25 s twice per second Table 3 21 DETECTOR LOOP 1 3 Indicators Zone Condition Indicator Behavior Nom 05 Detector response Double flashes once per two seconds Red O Predom Tumed on for 0 5 sonce per second Red FreNam Turned on for 0 25 s wice per second Red 50 www bolid com S2000 ASPT Technical Description Table 3 22 MANUAL CALL POINTS Indicator REMOTE COMMAND Indicator nom 0o Turned on for 0 25 s twice per second Red Short Open failure Turned on for 1 s once per two seconds Disabled Lit steady Table 3 23 DOOR CIRCUIT Indicator EXTERNAL FAULT Indicator Table 3 24 DISCHARGE Indicator nom o broken umed on tor 0 5 s once per second Red Table 3 25 MASS PRESSURE Indicator Breaking of the Mass or Turned on for 1 s once per two seconds Pressure input circuit of an S2000 KPB info bolid ru overseas bolid com 51 IeIMI FIRE ALARM AND EXTINGUISHING CONTROL PANEL Table 3 26 SIREN Indicator VISUAL ALARMS Indicator FIRE Output Indicator RELEASE CIRCUIT Indicator AUX EQUIPMENT Indicator Output Condition Indicator Behavior Deactivated O oo Adwaed SSC steady Red Short Open failure Turned on for 1 s once per two seconds Table 3 27 FAULT Output Indicator Output Condition Indicator Behavior l Off Table 3 28 S2000 KPB Indicator
46. e ADDRESSES command from the console menu by 70 1and ENT keys or press hot key 3 www bolid com S2000 ASPT Getting Started 5 Select RS485 DEVICES menu command by 4 and ENT keys or press hot key 1 6 Enter the current panel address or select its value by and press ENT 7 Enter the new panel address and press ENT Short double console sound acknowledges successfully performed assigning 8 For the new address to come into effect reset the panel power suppliers The outage duration has to take at least 3 seconds w w keys ATTENTION Connecting the panel into the Orion system or connecting S2000 KPB modules to the panel RS 485 2 terminals NEVER ASSIGN THE SAME ADDRESS TO DIFFERENT DEVICES Include the devices into given interface line one at a time assigning each of them the new unique address Although the addresses of devices brought to the RS 485 1 line can coincide with those of devices brought to the RS 485 2 line that is address spaces of different interface line are unrelated DISCONNECTING THE PANEL FROM THE RS 485 INTERFACE NEVER DETACH ONLY A SINGLE WIRE BUT BOTH WIRES AT ONCE 6 5 Testing the Panel Before operating the panel it is advisable to test panel operability by doing the following 1 Establish the test set up shown in Figure 6 9 2 Co
47. e key provided info bolid ru overseas bolid com 23 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Access Level 3 The access level 3 is expected to be used by persons who are trained and authorized to operate fire protection equipment and all panel functions including disabling panel input output circuits and switching the panel to the Test mode To entry for access level 3 touch the iButton reader connected to the panel with the Master Key If the Master Key Provided Access panel configuration parameter see Section 3 7 3 is set off off by default all operations said above are available for the access level 2 too Access Level 4 The access level 4 is expected to be used by persons who are trained and authorized to configure and re configure the panel as well as to maintain the panel to repair the panel or to alter its firmware A mechanical lock on the top panel cover and its key provided are used for entry to access level 4 Access Level 5 When the panel operates under controlling of an Orion network controller an additional access level 5 can be provided for a system operator operator of the S2000 S2000M console or ARM Orion which is enabled to control the panel remotely For entry to access level 5 the proper password enrolled in the Orion system database must be typed on the console keypad or PC keyboard 3 2 External Circuit Control Outputs The panel provides some outputs to connect and operate the ext
48. e tamper plunger for a long time or return the panel back to the manufacturer 3 8 2 Device Failure The panel enters the Device Failure mode if a checksum error has been detected during a microcontroller memory test or battery charger has failed In case of a checksum error both the Device Failure indicator A and the FAULT WARNING indicator on the panel front plate flash and the internal panel sounder beeps If after restarting the panel the checksum error is detected once more then update the microcontroller firmware by doing the following 1 Connect the panel to a PC via one of the interface connectors such as an S2000M in the programming mode PI GR S2000 USB or USB RS485 Use the A1 and B1 panel terminals 2 Turn the panel power on 3 With the help of the program ORION _PROG EXE update the firmware While the firmware is written to the panel the panel sounder keeps silent the HL1 indicator on the panel PCB being lit with short breakings 42 www bolid com S2000 ASPT Technical Description When writing has been completed the panel enters the Pre operating mode NOTE The program ORION _PROG EXE and the firmware file can be downloaded from the site of the Bolid Company http bolid ru If a charger failure has been detected during the evan self test procedure the indicators FAULT WARNING Ej and A flash the panel sounder sounds interruptedly In such case the panel should be sent to the manufacturer for repair wi
49. ed up e g due to the door opening to the protected area Access has denied due to the illegal entered code Open circuit failure in the alarm loop Short circuit failure in the alarm loop Open circuit failure of relay output load circuit Short circuit failure of relay output load circuit Relay output load circuit has been restored AC power has been lost AC power has been restored Battery supply has been out of range Battery supply has been restored Panel case is opened Panel case is closed Panel diagnostic mode has been started Fire alarm has been cancelled The detectors have been monitored again The pressure detector fixed pressure rising Fire extinguishing is in process the launching pulse was given out and outflow of fire extinguishing agent has been detected info bolid ru overseas bolid com 57 EERE FIRE ALARM AND EXTINGUISHING CONTROL PANEL LAUNCH FAULT Fire extinguishing equipment was not successfully launched the launching pulse was given out but outflow of fire extinguishing agent has not been detected EX MODE AUTO The auto launching mode of fire extinguishing is in effect EX MODE MANUAL The auto discharge mode is OFF PROGRAMMING Programming mode having been entered ALARM CANCEL The user has silenced the inner alert fire or trouble signal SELF TEST ERROR A trouble has been detected in the process of a panel self testi
50. ernal devices as shown in Table 3 1 Table 3 1 Panel Control Outputs Provided that To connect a pre discharge the backup alarm EXIT light sign VA2 Normally batteries are To connect a discharge opened connected alarm KEEP OUT sign contacts 24 2 V 1amp To connect the VAS monitored up to 2 amp for AUTOMATICS OFF sign for 2 seconds To connect an external shor open See App A sound alarm siren failures control circuit The release circuit to current connect exploders valves 0 0015 amp and so on 24 www bolid com S2000 ASPT Technical Description E iButton reader Voltage of current 5 0 5 V 700 micro amp maximum Connects the iButton reader current Transmits the FIRE message to the fire department Transmits the TROUBLE Maximum commuting voltage is Normally opened solid state relay 100V 0 1amp contacts do message to the fire department Maximum commuting Controls auxiliary equipment such as ventilation air voltage is ditioni darhoali 28V 2amp d c con itioning and air eating ne installations as well as air or ae damper controls and so on Change over relay contacts Supplies 24 V power to external devices consumed no more than 0 2 amp 24 2 V See page 82 3 3 Transmitting Fault Conditions to a Central Monitoring Station Transmitting fault conditions to a Central Monitoring Station CMS is performed by opening the contacts of the FAULT panel output The fault con
51. es ALWAYS TAKE AWAY BOTH WIRES 6 3 Connecting Power Supply Before connecting the panel to the mains power insert the supplied plastic bushing into the hole made in panel enclosure This bushing is used to isolate the power cable from panel metallic case The panel fuse being housed into a special voltage insolating holder is used as mains power on off switch ATTENTION IT IS FORBIDDEN TO EXPLOIT THE S2000 ASPT PANEL IN CASE OF DISCONNECTED BATTERY SWITCH THE MAINS POWER OFF AND PULL THE FUSE F1 OUT BEFORE YOU INSTALL OR REPLACE THE BATTERY How to start the panel Connect the ground wire to the ground terminal Then connect the backup batteries interconnected with the connector provided by coupling red panel wire to the terminal and the white one to the terminal Finally put the fuse F1 into the holder How to shut the panel down Remove the fuse F1 from the holder on the panel PCB Then disconnect the batteries Finally cut the mains power out de energizing the panel info bolid ru overseas bolid com 69 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 6 4 Setting the Panel Configuration Parameters S2000 ASPT panel is delivered by manufacturer with configuration parameters being set in accordance with the Table 3 10 Table 3 11 Table 3 12 and Table 3 13 In order to change default configuration the panel needs to be connected to the network controller via RS 485 1 line and to the both power suppliers
52. he Battery Fault mode when the backup power has been restored can be decreased down to 300 ms by pressing the Fire Reset button BA 3 8 9 Master Key Programming The panel can be switched to the Master Key Programming mode only from the Quiescent mode by opening the panel top cover and pressing the tamper switch with one long one short one long pressing Long pressing means keeping for at least 1 5 s while short pressing means keeping for 0 1 to 0 5 s The pauses between pressings last 0 1 to 0 5 s This mode is designed for writing the code of a special Master Key electronic device to the panel memory 44 www bolid com S2000 ASPT Technical Description The panel exits the Master Key Programming mode after repeated touching the reader with the Master Key device or automatically after 30 s timeout since last button pressing having expired The new Master Key being enrolled into the panel memory all already existed electronic identifiers are deleted 3 8 10 User Key Programming The panel enters the User Key Programming mode from the Quiescent mode if the iButton reader connected to the panel is touched with the Master Key This mode is designed to enroll to the panel memory the codes of User Keys up to 7 which are supposed to be used to switch the automatic release mode on and off Exit the User Key Programming mode is implemented Automatically after the last eighth User Key has been enrolled or By second touchi
53. he S2000 ASPT Fire Alarm and Extinguishing Control Panel itself Y This Engineer s and User s Manual v The component parts including 7 termination resistors MF 1 2W 4K7 596 5 load connection modules 1 AC fuse 0 5 amp 2 mechanical lock keys 2 electric contact lock keys 1 battery connector 3 woodscrews 3 wall plugs 8x35 2 plastic bushings Notes The S2000 ASPT panel is delivered by manufacturer WITHOUT backup batteries iButton readers and iButtons which are to be purchased separately The panel is delivered with XP1 and XP2 jumpers being put on the fuse being not housed 4 2 Marking Each panel is supplied with marking as follows v v v v Y Manufacturer logotype Symbolic notation The two last digits of the year and the quarter of the manufacturing Accordance mark Factory number The external panel terminal marking corresponds to the wiring diagram Near the mains operating socket there is the lettering denoting the supply mains rated voltage 60 www bolid com S2000 ASPT Standard Delivery Marking and packing The panel enclosure is supplied with the ground terminal designed to connect the protective earth 4 3 Packing The panel along with component parts and maintenance documentation is packed into the carton box It is assumed to pack the panel into the proper container The boxes or containers are placed along with accompanying documents into the transportation pickings Each transp
54. he door sensor circuit leads to disabling automatic release this mode being kept even after trouble having restored If the Automatic Release Recovery parameter is set on then the panel automatically restores the Pre discharge Delay release mode if upon an automatic release the door sensor circuit has been broken and repaired again or the door has been open and then closed again If this parameter is set off in case of automatic release breaking the door sensor circuit info bolid ru overseas bolid com 37 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL aborts releasing and the extinguishing system will not be discharged even after the door circuit is restored It is sensible to set this parameter if the Automatic Mode Recovering has been set on The Remote Release Priority parameter prioritizes the remote release mode above blocking release upon any fault or opening the door sensor circuit This parameter being set on the remote release can not be blocked up by door opening but only by reset The Pressure Detector Disabled parameter allows canceling monitoring the pressure detector circuit of the panel if there is no need for this for example if dry chemical or aerosol extinguishing equipment is in use The Blocking Two Prealarm Release parameter blocks panel entering the Fire Alarm mode in case of two different alarm loops entering the Fire Prealarm status This parameters provide implementing the tactics of automatic relea
55. ical Description Table 3 9 System Parameters Defines the panel address within the RS puis 485 interface line connected to the 1 to 127 network controller RS 485 1 1 5 ms to 500 ms with increments of 0 125 ms Defines the time required the panel to respond on the requests of the network controller Response Pause The Network Address is designed for unique identifying the S2000 ASPT panel by the network controller The panel transmits events to and receives commands from the network controller using this address This address must be unique for each the device Setting the Response Pause parameter provides using the panel within a system with a sophisticated network topology where long layover can exist for example while converting RS 485 data into other interfaces intended for transmission over local area networks fiber optic channels or radio channels The current values of the Network Address and Response Pause can be reset to factory default values by pressing the panel tamper switch with special way long long long short Long pressing means pressing and holding the tamper switch pressed for more than 1 5 s while short one means pressing and holding the tamper switch pressed for a time between 0 1 s and 0 5 s A pause between pressings must last from 0 1 s and 0 5 s 3 75 The Factory Default Settings The factory default values of parameters are represented by Table 3 10 Table 3 11 Table 3 11 a
56. ice is storied 62 www bolid com S2000 ASPT Getting Started 6 GETTING STARTED To provide the claimed features and functions the panel must be operated with connected and charged batteries After unpacking make visual inspection of the panel and ensure the panel is free from mechanical damages Check the panel completeness After transportation the panel shall be cured without packing under normal condition for at least 24 hours Master this manual for technical features display and control elements of S2000 ASPT before you put the panel into service If S2000 ASPT is co operated with other parts of fixed extinguishing or safety system namely S2000 S2000M and S2000 KPB study these devices manuals closely 6 1 Mounting the Panel Overall and mounting dimensions of the S2000 ASPT panel given in millimeters are shown in Figure 6 1 and Figure 6 2 The S2000 ASPT panel is wall mountable There are three holes on the panel base to mount it on the wall at any required place and one hole for fixing the panel with the screw 305 255 Figure 6 1 S2000 ASPT Overall Dimensions info bolid ru overseas bolid com 63 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL IOI O paca O Figure 6 2 S2000 ASPT Mounting Dimensions 6 2 Connecting the External Circuits The wiring of the external circuits to the panel is carried out in accordance with the connecting diagram shown in Figure 2 4 After all connection having been comp
57. l zone 11 panel remote release mode control zone 12 fire protection equipment fault monitoring zones 20 21 22 controlling the tamper switch and two zones of the first S2000 KPB zones 30 31 32 controlling the tamper switch and two zones of the second S2000 KPB zones 170 171 172 controlling the tamper switch and two zones of the 16 S2000 KPB 3 5 1 Monitoring Alarm Loops The panel provides connecting and monitoring for statuses of three alarm loops having the characteristics as follows alarm loop resistance without regard to termination resistor no more than 100 Q leakage impedance between the loop wires or between any wire and earth at least 50 kQ The termination 0 5 W 4 7 kQ 5 resistors provided have to be included into each alarm loop 26 www bolid com S2000 ASPT Technical Description In the quiescent mode the panel provides alarm loop inputs with power voltage ranging from 24 V down to 19 V depending on rated current from 0 to 3 milliamps correspondently In case of a short failure in any loop the panel supplies other loops with the same input voltage as mentioned above The panel provides limiting the loop current in case of a short circuit failure by the value of 27 milliamps The effective voltage ripples are not to exceed 20 mV The panel recognizes the following alarm loop statuses as follows Normal Operating status Responded Broken status
58. leted cover the panel top cover Then turn the key switch on the panel front plate to the Locked position 6 2 1 Connecting the Alarm Loops Connect alarm loops with automatic detection included to the PCB terminal blocks marked as 1 2 and 3 The detector wiring diagrams for specific loop types are demonstrated in Figure 6 3 Figure 6 4 and Figure 6 5 If any alarm loop is not in use connect the supplied termination resistor of 4 7 KQ across the relative terminal blocks The number of detectors included into a single loop can be calculated by formula being referred to in clause 3 5 1 The values of additional series and shunt resistors are selected in such a way so that a confirmed response of a single smoke detector or a response of a heat detector causes the loop to get the Fire Prealarm status while two detector responses causes the loop to get the Fire Alarm status 64 www bolid com S2000 ASPT Getting Started 6 2 1 1 Smoke Double Response Recognizable Alarm Loop Bring the provided termination resistor 4 7 kQ into the alarm loop as shown in Figure 6 3 Here Rierm is for the termination resistor mentioned above SD is for a smoke detector Rs is for a resistor brought in series with any smoke detector Its value varies from 1 5 KQ up to 3 kQ depending on specific smoke detector type and can be corrected during testing operability of the panel with specific detectors loop Rs Rs SD SD Rterm loop
59. lled in the panel memory or Send the relevant command from the network controller 48 www bolid com S2000 ASPT Technical Description Automatic release is cancelled by the door sensor circuit being broken or failed If the Automatic Mode Recovery parameter is set on the automatic release mode recovers when the door sensor circuit has been restored If the automatic release mode is disabled the panel turns on the visual alarm connected to the VA3 output usually the AUTOMATICS OFF light sign 3 10 Panel Indication All panel indication is described by the Tables following Table 3 14 PREALARM Indicator Panel Mode Indicator Behavior Turned on for 0 5 s once per second Table 3 15 FIRE Indicator Panel Mode Indicator Behavior Turned on for 0 25 s twice per second Table 3 16 FAULT WARNING Indicator Panel Mode Indicator Behavior Disabled excluding silencing the internal sounder Turned on for 1 s once per two seconds The panel enclosure is open Table 3 17 DISABLED and SILENCE Indicators Panel Mode Indicator Behavior Disabled including silencing info bolid ru overseas bolid com 49 BOLID J FIRE ALARM AND EXTINGUISHING CONTROL PANEL Table 3 18 EXTINGUISHING Indicator Launch Delay Turned on for 0 5 s once per second Emergency Launch Turned on for 0 25 s twice per second Launch Fault Extinguishing Table 3 19 AUTOMATICS ON OFF Indicator Panel Mode Indicator Behavior Tabl
60. nd Table 3 12 Table 3 10 The Factory Loop and Panel Configuration Loop Type for the loop 1 Loop Type for the loop 2 info bolid ru overseas bolid com 39 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Remote Pre discharge Delay s Off Off Off Table 3 11 Default Addresses of the Controlled S2000 KPB N 1i 2 s 4 5 ef7 s 9 10 11 12 13 14 15 16 e o ojojojojo ojo ojojojojo ojO 0 Table 3 12 The Factory System Parameters Network Address Table 3 13 Default NO NC C Relay Parameters Zone Number 1 2 s 4 s 7 s s poppe Link the Relay ll LLlLlLl lu ualulas With Executive 13 Fire Output Program Activation Time Unlimited The zone numbers means as follows 1 Detection Loop 1 2 Detection Loop 2 40 www bolid com S2000 ASPT Technical Description Detection Loop 3 Door Sensor Circuit Manual Call Points Pressure Detector Circuit Fire Protection Equipment Fault co Oo OF HR C Releasing Circuit 9 Visual Alarm 1 Circuit 10 Visual Alarm 1 Circuit 11 Visual Alarm 1 Circuit 12 Sound Alarm Circuit 13 Remote Release Commands 3 8 Panel Operating Modes The panel supports the following operating modes Pre operation Device Failure Quiescent Fault On Batteries Battery Fault Disabled Test User Key Programming Master Key Programming Prealarm Fire Alarm Pre disch
61. nel within a fire alarm and extinguishing system see Figure 1 1 to Figure 1 4 8 www bolid com S2000 ASPT General Y Call LE Loop 1 o Loop 2 iButton Reader S2000 ASPT RS485 2 LM Door 2 24V 2000 KPB Release Dry Chemical or Aerosol Modules a D I LZ eu Coo Eu neo Figure 1 1 A Standalone Dry Chemical Fire Extinguishing System 1 Light Alarms Caution Signs 6 S2000 ASPT Panel 2 Audible Alarm 7 Smoke Detectors 3 Manual Call Point 8 Heat Detectors 4 iButton Reader 9 Fire Protection Modules 5 Door Contact 10 S2000 KPB module info bolid ru overseas bolid com 9 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL y es ug P nel s A iButton O Reader e m 3 2 Door 9 7 Discharge Monitoring X E Release D Equipment Fault Pressure Monitoring Figure 1 2 A Standalone Gaseous Fire Extinguishing System 1 Light Alarms Caution Signs 7 Smoke Detectors 2 Audible Alarm 8 Heat Detectors 3 Manual Call Point 11 Output Pressure Detector 4 iButton Reader 12 Release Activator 5 Door Contact 13 Internal Pressure Detector 6 S2000 ASPT Panel 10 www bolid com S2000 ASPT General Area 10
62. nel provides recognizing of such loop statuses as Breaking Open Failure and Short Failure Having received a single response from a smoke normally opened detector the panel transmits the Fire Signal message to the network controller and requests the detector status again by shutting the loop power down and waiting the repeated actuation during one minute Unless after power reset the detector has returned to the initial status or the detector has actuated again within one minute the panel enters the Prealarm status Otherwise the panel retains the Quiescent mode Single heat normally closed detector response immediately causes the panel to enter the Prealarm mode Alarm loops of types 1 and 3 are capable of recognizing dual actuating that is the panel perceives each of two or more actuated detectors In such a case the loop switches from the Armed or Fire info bolid ru overseas bolid com 31 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Prealarm statuses to the Fire status only after another detector having actuated at the same loop For an alarm loop of type 2 only single detector actuating is recognized If so the panel switches to the Prealarm status The transition to the Fire Alarm status becomes possible if another loop has transited to the Fire Prealarm status Entering the Fire Alarm mode causes the panel to release extinguishing agent So for loops of types 1 and 3 the extinguishing system can be discharged in c
63. nes 20 21 22 controlling the tamper switch and loops of the first S2000 KPB zones 30 31 32 controlling the tamper switch and loops of second S2000 KPB zones 170 171 172 controlling the tamper switch and loops of the 6 S2000 KPB info bolid ru overseas bolid com 55 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 3 12 2 Outputs Monitored by the Network Controller The network controller is capable of monitoring the panel and S2000 KPB outputs as follows output 1 panel VA1 EXIT output 2 panel VA2 KEEP OUT output 3 panel VA3 AUTOMATICS OFF output 4 panel SA SIREN output 5 panel releasing circuit R outputs 21 26 first S2000 KPB s outputs outputs 31 4 36 second S2000 KPB s outputs Outputs 41 46 third S2000 KPB s outputs outputs 171 176 16 S2000 KPB s outputs 3 12 3 Implemented Network Controller Commands The panel is intended to receive through the RS 485 1 interface line and to implement the network controller commands such as Reading Configuration Writing Configuration Assigning the Network Address Resetting alarms Abort releasing Release extinguishing system Switch the release mode to automatic or remote Time synchronization Loop parameter request The panel provides transmitting of launching launch canceling commands through the RS 485 2 interface to any S2000 KPB module re gistere
64. ng and technical equipment which are to be controlled by the panel ventilation controls smoke management controls hot air heating and conditioning system controls fire control dampers air closers door closers and so on are connected to the NO NC C panel terminals The NO C terminals are normally opened the NC C terminals being normally closed The output parameters are shown in Table 3 1 68 www bolid com S2000 ASPT Getting Started 6 2 8 Connecting RS 485 Interface Lines If S2000 ASPT is to co operate with an S2000M console or S2000 KPB modules it needs to be connected to these devices via the RS 485 1 interface port and the RS 485 2 interface port respectively The typical wiring diagrams are shown in Figure 1 1 Figure 1 2 Figure 1 3 and Figure 1 4 Connect A and B lines of the network controller RS 485 bus to the A1 and B1 terminals of RS 485 1 panel port respectively If the S2000 ASPT panel is not the first or the last device in the RS 485 bus then remove the XP1 jumper that is RS 485 EOL terminator from the panel PC board otherwise let it put on Connect A and B lines of the S2000 KPB modules RS 485 bus to the A2 and B2 terminals of the panel RS 485 2 port correspondently If the S2000 ASPT panel is not the first or the last device in the RS 485 bus then remove the XP2 jumper that is RS 485 EOL terminator from the panel PC board otherwise let it put on Separating the panel from RS 485 1 or RS 485 2 lin
65. ng procedure 3 12 5 S2000 KPB Messages The panel receives events from the S2000 KPB modules connected via RS 485 2 interface line FIRE TROUBLE Extinguishing equipment fault FIRE TRBL RST Extinguishing equipment operates normally RELAY TRBL OPEN Open circuit failure of relay output load circuit RELAY TRBL SHORT Short circuit failure of relay output load circuit RELAY RESTORE Relay output load circuit has been restored POWER FAILED S2000 KPB power has been lost POWER RESTORE S2000 KPB power has been restored TAMPER ALARM 82000 KPB module case is opened TAMPER RESTORE S2000 KPB module case is closed While configuring S2000 KPB modules which are to operate under the S2000 ASPT panel of versions 2 01 set the Condition parameters of programmable alarm loops only to Fire Equipment Fault or Fire Equipment Restored values 3 12 6 Control Commands Transmitted to S2000 KPB The panel provides transmitting release abort commands over the RS 485 2 interface line to each of the S2000 KPB modules programmed in the configuration 3 13 Panel Powering The panel keeps it s operability upon mains power supply from 130 V to 250 V a c 50 1 Hz or upon backup battery supplying from 22 V to 58 www bolid com S2000 ASPT Technical Description 28 V d c Two backup batteries in series of 12 V and 4 to 4 5 Ah capacities each are to be used as a backup power supply DO NOT operate the p
66. ng the iButton reader with the master Key or Automatically after 30 s having been expired since the reading of a User Key touched to the reader 3 8 11 Prealarm The panel switches from the Quiescent mode to the Prealarm mode after response of a single fire detector wired to any alarm loop the duration of the response lasting at least 1 s If active smoke detectors are wired into the alarm loop this transition is implemented with the repeated query of the actuated detector status see the Section 3 7 1 To cancel the Prealarm mode press the Fire Reset button or give the relevant command by means of the network controller 3 8 12 Fire Alarm The panel switches from the Prealarm mode to the Fire Alarm mode after response of a second fire detector in the same or any other alarm loop depending on the configuration settings See the Section 3 7 1 The panel enters the Fire Alarm mode from the Quiescent mode in case of Response of two or mode detectors in the same alarm loop or different alarm loops depending on the current loop settings see the Section 3 7 1 or Response of a manual call point connected to the Manual Call Points input of the panel or Receiving a release command from the network controller info bolid ru overseas bolid com 45 EM FIRE ALARM AND EXTINGUISHING CONTROL PANEL The panel having entered the Fire Alarm mode its internal sounder is activated the SA output is activated and the contacts
67. nging Configuration Parameters by Means of UProg 70 6 4 Changing the Panel Network Address by Means of the S2000M 70 6 5 Testing the PallBl e ep ttu adii du iu ss eR 71 BB OLIN AICO rise irt Ei EE EM LE 74 THOUBLESHOOTINQL i cernunt ndn meen ener tl nnnp mete Rn rud Edu ERI Sin Mex Ix VE una ue 75 Li gp2d Dioec 78 www bolid com S2000 ASPT 9 BOLID CONTACT INFORMATION eeeee eere eee eee 81 Appendix A Calculating the Battery Operating Time and Average Consumed Current weiss T 82 Appendix B Personnel Action Plan in Case of Fixed Extinguishing System Discharge Me 84 info bolid ru overseas bolid com 5 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL This Engineers and User s Manual is intended to help for studying operability principles and maintenance of the S2000 ASPT Fire Alarm and Extinguishing Control Panel version 3 05 Please read these instructions completely before connecting operating or adjusting this product 6 www bolid com S2000 ASPT General 1 GENERAL The S2000 ASPT Fire Alarm and Extinguishing Control Panel hereinafter referred to as the panel is designed to be used in standalone or centralized fire alarm and protection systems The panel provides monitoring fire conditions controlling audible and visual alarms and operating a fire suppres
68. nnect pressure detector contacts 7 connect a fault circuit of fire protection equipment FLT transmit fault condition to a fire department FR transmit fire conditions to a fire department NO NC C connect auxiliary equipment to be controlled such as fans dampers and so on 20 www bolid com S2000 ASPT Panel Design 24V supply 24 V d c to external devices l connect the LED of the iButton reader RE connect the iButton reader OV this is the panel OV circuit output A1 B1 link the panel with the network controller RS 485 1 A2 B2 connect S2000 KPB modules to the panel RS 485 2 R connect the exploder releasing circuit VA1 connect a visual alarm 1 EXIT sign VA2 connect a visual alarm 2 KEEP OUT sign VA3 connect a visual alarm 3 AUTOMATION OFF table SA connect an audible alarm siren 2 3 2 PCB XP1 and XP2 Jumpers In order to help keep the network line at optimum level for communication the End of Line EOL terminators or resistors have to be connected to each end of the RS 485 1 and RS 485 2 interface lines For this purpose two jumpers marked as XP1 and XP2 on the panel PCB are destined If the S2000 ASPT panel is the first or the last device in the RS 485 1 and or RS 485 2 lines then the relative jumper s must be connected across the corresponding A and B lines Otherwise the jumpers must be removed 2 3 8 Voltage Test Points Following are the panel PCB voltage test p
69. nnect the panel A1 and B1 terminals with the S2000M operating as a network controller through the RS 485 interface line 3 Insert the backup batteries and connect the panel to the mains power 4 After expiring the Pre operation mode the panel shall enter the Quiescent mode the S2000M displaying the CONNECTED D127 message followed by the DEVICE RESTART D127 message 5 Turn the key switch on the panel front plate to the Unlocked position B If the panel has entered any alarm mode press the Fire RESET button or Extinguishing RESET button to switch the panel to the Quiescent mode If the AUTOMATIC MODE indicator is turned on reset it by pressing the relevant button The H8 indicator see Figure 6 9 shall start lighting info bolid ru overseas bolid com 71 Erm FIRE ALARM AND EXTINGUISHING CONTROL PANEL 6 Close the S1 contact see Figure 6 9 H1 indicator shall have being off for 3 s the LOOP 2 indicator on the panel front plate shall flash with red color and the S2000M console shall display FIRE SIGNAL 127 002 When the H1 indicator has turned on again the panel shall enter the Prealarm mode the S2000M console displaying FIRE PREALARM 127 002 Then the H4 indicator shall start lighting u BOLID mm 0 PES S tel 7 495 513 3235 HL1 tamper switch b internal light emitting contacts http www bolid com c indicator control board email info bolid ru connection battery terminals RS 48
70. oints 0 the panel OV circuit 5 the regulated 5 0 5 V voltage supply output 27 the regulated 27 1 V voltage supply output 40 mains rectifier output voltage 2 4 Panel Tamper Switch There is a tamper switch under the panel top cover see Figure 2 1 The tamper switch is connected to the XP3 terminal block of the panel main PCB by a double core cable When the panel top cover is closed the tamper switch contacts are closed too You must open the panel cover to switch the panel to the Master Key Programming mode info bolid ru overseas bolid com 21 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 2 5 External Reader The panel provides connecting the reader of Dallas Touch Memory electronic devices or iButtons The user authentication is performed by key code reading The reading and writing iButton codes are implemented when an iButton is touched to the reader The panel is supplied by a single input to connect a reader The distance between the panel and the reader cannot exceed 100 m provided the wire cross section area is not less than 0 1 square mm The panel provides storing up to eight iButton codes including the code of the Master Key in its non volatile memory 22 www bolid com S2000 ASPT Technical Description 3 TECHNICAL DESCRIPTION 3 1 Access Levels for the Indications and Controls The panel provides five different access levels for the indications and controls which are used to have user a
71. om 2 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Appendix B Personnel Action Plan in Case of Fixed Extinguishing System Discharge In order to prevent secondary actuating fire extinguishing installation in the event of its launch it is advisable to follow this sequence of operations 1 Visually inspect the protected zones to discover the reason the extinguishing system has actuated if it is the presence of combustion products or smoke filling or manual call point activation Take the necessary measures to protect occupants and premises against fire and extinguishing agent releasing 2 In cases of fire having been already suppressed or nuisance alarm suppress the audible alarm by means of SILENCE push button pressing 3 Check the conditions of panel faceplate indicators PREALARM FIRE ALARM AUTOMATICS ON OFF and EXTINGUISHING Define which zones are in fire conditions 4 Check the conditions of the indicators on responded fire detectors if applicable Inspect the conditions of manual call points 5 Abort the Extinguishing mode by pressing the RESET button at the left lower corner of the panel faceplate Abort the Fire mode by pressing the RESET button at the left upper corner of the panel faceplate 6 Cutoff both mains and backup power from the panel and the S2000 KPB modules if applicable 7 Register your activity and observations into the user log 8 After incident investigation having completed and before p
72. ontroller so called centralized control All available programs are described in Table 3 7 Table 3 7 Relay Executive Programs Initial Remote Control The relay is controlled only remotely Switch On The relay is switched on if there is an Intrusion Alarm or Fire Alarm Switch Off The relay is switched off if there is an Intrusion Alarm or Fire Alarm Switch On for a Time The relay is switched on for a specified time if there is an Intrusion Alarm or Fire Alarm Switch Off for a Time The relay i is switched off for a specified time if there is On an Intrusion Alarm or Fire Alarm Blink From Off The relay is switched on off once per second if there is Off Condition an Intrusion Alarm or Fire Alarm Blink From On The relay is switched on off once per second if there is Condition an Intrusion Alarm or Fire Alarm The relay is switched on off once per second for a specified time if there is an Intrusion Alarm or Fire Alarm Blink for a Time From Off Condition info bolid ru overseas bolid com 33 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL A Initial The relay is switched on off once per second for a specified time if there is an Intrusion Alarm or Fire Alarm Blink for a Time From On Condition If the related loop has Fire Alarm or Fire Prealarm Fire Output status then the relay is switched on else the relay is switched off open If there are related alarm loops having Trouble Arming Trouble Output
73. ortation packing should be furnished by packing list contained information as follows 1 Manufacturer logotype 2 The identification the designation and the number of products inside 3 The designation and the number of replacement components 4 Packager sign or stamp 5 The date of packaging info bolid ru overseas bolid com 61 EI FIRE ALARM AND EXTINGUISHING CONTROL PANEL 5 GENERAL INSTRUCTIONS Install test and maintain the S2000 ASPT panel according to instructions as follows Failure to follow these instructions may result in failure to the device to operate properly or personal injury 5 1 Safety Precautions Do FOLLOW the electrical installation operational and electrical safety code rules during the installation operation or maintenance of S2000 ASPT panel and communication lines and associated equipment Only certificated personnel trained in the requirements of safety codes have to be allowed to deal with this activity MAKE SURE that the protective ground is properly wired before operating the panel NEVER use the panel without system earth or in case of fuse mismatching with the rating requirements Do SHUT OFF mains and backup power before installing the panel or repairing any failure BEWARE of touching the 220 B terminals that can be alive and dangerous 5 2 Storage There must not be any acids or alkalis vapor aggressive gas or other noxious agent with corrosive effect on premises where the dev
74. ounder sounds interruptedly A charger failure has been detected the panel is being in the Device Failed mode Send the panel to the manufacturer After powering up the panel the TEST indicator flashes the panel making no sounds The panel is not completely factory tested 1 Press and hold the tamper plunger until the panel enters the Operating mode or 2 Send the panel to the manufacturer The panel doesn t display S2000 KPB faults A S2000 KPB module is not started along with starting the fire protection equipment The S2000 KPB address is not enrolled in the panel configuration Change the panel configuration having specified the addresses of the connected S2000 KPB modules Turn the panel power on and then off again The panel is not detected by the network controller The interface line RS 485 1 is inoperable Find out and repair the failure Interface lines A1 and B1 are interchanged Supervise and correct if necessary The jumper XP1 connecting the EOL Terminator to the RS 485 1 line is set improperly Ensure the EOL resistor jumper is put on if the panel is the first or the last device in the RS 485 1 interface line or removed otherwise 76 www bolid com S2000 ASPT Troubleshooting Some devices in the interface line RS 485 1 have the same network Check and change if necessary network addresses being in use so that they have been
75. ower returning separate automatic fire extinguishing modules from panel starting circuits and the S2000 KPB devices if applicable and replace them by simulators You can use a fuse with actuating current being equal to automatic module s one as a simulator 9 Carry out the pre commissioning routines to check the panel operability 10 Make sure the panel is not in an alarm mode and disable the mains and backup power supplies Replace the simulators by the effective fire extinguishing modules and restore the powering 84 www bolid com BOLID ONE YEAR LIMITED WARRANTY Bolid Company and its divisions and subsidiaries Seller 4 Pionerskaya Str Korolev 141070 Moscow Region Russia warrants its security equipment the product to be free from defects in materials and workmanship for one year from date of original purchase under normal use and service Seller s obligation is limited to repairing or replacing at its option free of charge for parts or labor any product proven to be defective in materials or workmanship under normal use and service Seller is not responsible for results where the product is used improperly where it is used for any application it is not intended for used under unacceptable environmental conditions and mishandled or stored under improperly Seller shall have no obligation under this warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other
76. rameter is related to such circuits as the door sensor circuit discharge monitoring circuit and fire protection equipment trouble circuit Varying the value of this parameter for the particular device or equipment provides increasing or decreasing the time the device or equipment needs to restore the circuit after breaking This provides avoiding unnecessary messages due to transient processes as well as people passing through the door 32 www bolid com S2000 ASPT Technical Description 3 7 2 Parameters of the NO NC C Relay Control Table 3 6 NO NC C Parameters The number of the executive program see Table 3 7 which defines both the way the 0 to 8 13 to 15 relay is controlled depending on the 19 to 24 condition of the related inputs outputs see and 27 to 30 below and the initial condition of the relay Executive Program From 0 to 8192 s 2 h 16 min 32 s with increments of 0 125 s The time the relay will be activated for only for those programs which suppose activation the relay for a time Activation Time Links the relay with the panel inputs and or outputs which statuses can impact on the activating the relay Link the Relay With The Executive Program parameter defines the tactic of relay control depending on the condition of the panel input output circuits so called ocal control or the initial relay condition just after panel power turning on until receiving the first command from the network c
77. rseas bolid com 43 IsI FIRE ALARM AND EXTINGUISHING CONTROL PANEL output can be activated for no more than 3 s The outputs VA1 and VA2 Visual Alarms are activated in interrupted mode To inspect operating of the electronic key for shutting down the alarm loop power press any button of the Device Loop 1 Device Loop 2 and Device Loop 3 In such case the power on the terminals 1 2 and 3 has turned on for 3 seconds To leave the Test mode press the Test button repeatedly or press the Reset button The panel has automatically left the Test mode since 30 seconds after last pressing a button 3 8 7 On Batteries The panel enters the On Batteries mode when the mains power has been off The panel enters the On Batteries mode within no more than 60 s since the mains power has failed The panel leaves the On Batteries mode within no more than 300 ms since the mains power has been restored 3 8 8 Battery Fault The panel enters the Battery Fault mode in the two following cases One or two of the batteries has have failed The battery charger has failed The panel enters the Battery Failed mode within no more than 15 minutes since the backup power has failed 300 ms since the battery charger has failed The panel leaves the Battery Failed mode within no more than 15 minutes since the backup power has been restored 300 ms since the battery charger has been restored The time to exit t
78. s the Extinguishing Reset button or give the relevant command by means of the network controller 3 8 17 Release Fault If no response of the pressure detector has been detected during the release pulse then the panel transits from the Release mode to the Release Fault mode The panel in this mode can enter the Extinguishing mode after pressure detector having actuated To cancel the Release Fault mode press the Extinguishing Reset button or give the relevant command by means of the network controller 3 8 18 Emergency Release The panel switches from the Quiescent mode to the Emergency Release mode in case of a response of the Pressure Detector having occurred In the Emergency Release mode The outputs VA1 VA2 and SA are turned on and The contacts of the FR output is closed In the Emergency Release mode the release pulse doesn t generate and doesn t give a command to launch the connected S2000 KPB modules info bolid ru overseas bolid com 47 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL To cancel the Emergency Release mode press the Extinguishing Reset button or give the relevant command by means of the network controller 3 9 The Modes to Release the Fire Suppression System The panel provides the following modes to release a fire extinguishing agent Remote mode and Automatic mode 3 9 1 Remote Release The remote releasing the extinguishing system is implemented in case of either activa
79. se commands being Yellow disabled Indicates the Extinguishing and med Unexpected Release panel modes DISCHARGE naaa EA pn eed ah d cel Indicates this circuit fault or being disabled Indicates that one or more Mass or Meets SHOW Pressure inputs of S2000 KPB have failed EXTERNAL FAULT Yellow Indicates this circuit fault or being broken Indicates internal panel sounder being SILENCE Yellow dianed info bolid ru overseas bolid com 15 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL Indicator Color Destination Red Indicates this output is activated causing SIREN the connected sound alarms to sound Vellaw Indicates that the output is disabled or the connected circuit failed Indicates the VA1 and VA2 outputs are Red activated and so are the connected caution signs the pre discharge and discharge VISUAL ALARMS alarms Indicates that the VA1 and VA2 outputs Yellow are disabled or the connected circuits failed See the note below the table Indicates that fire condition is being FIRE RER transmitted to a fire monitoring station veilow Indicates the VA1 and VA2 outputs being disabled Indicates that either a fault signal is being sent on the fire monitoring station or the FAUT TELON output is disabled by pressing the same name button Indicates that the panel releasing circuit is Red active under current RELEASE CIRCUIT jp 4 RE MO DEA ene ue OA
80. sing upon two detector responses in a single alarm loop The Master Key Provided Access parameter additionally restricts the user rights to disable enable including arm disarm panel inputs outputs If this parameter is set on a user authorized for the second access level can disable a zone or an output if only he or she has a Master key If the parameter is set off users authorized for the second access level are automatically enabled to make actions authorized for the third access level The S2000 KPB Addresses define the S2000 KPB modules which relate to this hazard extinguishing area and expand release output of the panel The S2000 KPB modules are connected to the S2000 ASPT panel through its RS 485 2 interface line Each module has to be assigned with unique network number ranged from 1 to 127 The maximum number of S2000 KPB modules to be connected to a single S2000 ASPT panel is 16 After release conditions having occurred see clause 3 8 13 and Pre discharge Delay period having been expired the panel gives the discharge command to each of the connected S2000 KPB modules The discharge pulse durations as well as pauses between S2000 KPB output activation are given by S2000 KPB module configurations 3 74 System Configuration Parameters The system configuration parameters define the panel operating in network mode as a part of Orion security system under S2000 S2000M or ARM Orion PC controlling 38 www bolid com S2000 ASPT Techn
81. sion system both releasing extinguishing agent and monitoring faults of the fire protection equipment The main S2000 ASPT functions are Protecting a single hazard area Releasing extinguishing agent in gaseous dry chemical or aerosol fire suppression system both automatically and remotely Receiving and processing signals from both manual call points and automatic fire detectors passive active two wire four wire normally open and normally closed Controlling one sound and three visual alarms Controlling technological equipment such as ventilation systems and so on Receiving commands from and transmitting alarm and fault messages over the RS 485 interface line to the network controller either a S2000M fire and alarm control console or a PC with the ARM Orion software package installed Monitoring for faults of fire protection equipment and audible and visual alarms Monitoring for faults of fire suppression installation ddr VRG signals from Door open sensors Pressure detectors Mass of Pressure outputs of the fire protection equipment Connected S2000 KPB release modules Manual call points Button reader Transmitting the Fire Alarm and Fault messages to a fire department or central monitoring station The panel can operate both stand alone and as an addressable part of an Orion security installation controlled by its network controller Also the panel can be co operated with S2000
82. supposes the On initial condition it is advisable to switch the relay to On condition just after power turning on To do this assign the relay to any executive program with On initial condition for example the program No 2 Switch Off 3 7 3 Panel Configuration Parameters The panel configuration parameters define the panel operating tactics and the parameters of releasing the fire suppression system These are shown in Table 3 8 Table 3 8 Panel Parameters Automatic Defines the pre discharge time interval Pre discharge between fire conditions occurring as a 0 to 255 s Dela result of fire detector responses and y generating release pulse Defines the pre discharge time interval Remote Pre between fire conditions occurring asa i result of manual call point activation or discharge A dvi 0 to 255s Delay receiving remote release command via the RS 485 interface and generating release pulse Release Pulse Defines the duration of release pulse 0 to 255 s Siren Defines the time to activate the sound erue alarm connected to the SA panel output MEDIS Automatic Allows auto restoring of automatic Mode discharge mode just after panel having Guo Recover entered the Quiescent mode after door y closing or door circuit fault repairing 36 www bolid com S2000 ASPT Technical Description Automatic Enables returning the Pre discharge Release Delay mode in case of automatic release On Off Recovery after door circ
83. th the relevant notification 3 8 3 Quiescent Mode The panel is considered to be in the Quiescent mode if all its monitored input and output circuits are in Norm conditions 3 8 4 Fault The panel enters the Fault mode when generating any message described in the section 3 3 After repairing all the faults the panel automatically leaves the Fault mode 3 8 5 Disabled The panel enters the Disabled mode if a zone is disabled disarmed or an output is disabled or the panel sounder is disabled Turning the automatic release mode off doesn t lead to the panel entering the Disabled mode 3 8 06 Test The Test mode provides inspecting operating of the Outputs controlling the visual and sound alarms VA1 VA2 VA3 SA Fire and Fault outputs NC NO C relay Aux Equipment Electronic key to shut the power of the alarm loops off To switch the panel to the Test mode you must be authorized to use the access level 3 If so use the Test push button to start the Test mode To test a panel output press the relevant output s push button The device condition will be displayed by the associated indicator if the output is active closed the indicator is turned on while otherwise if the output is not active open the indicator is turned off Switching over conditions of the outputs VA1 VA2 VAS Fire Fault and Aux Equipment is implemented by repeated pressings on the output push button The Siren info bolid ru ove
84. the SILENCE button available for all the access levels silences the internal panel sounder when it is activated The internal sounder is unblocked manually by repeated pressing the button or automatically after any event causing sounding having occurred The internal sounder CANNOT be silenced when the panel is in the Pre discharge Delay mode Pressing the buttons SIREN VISUAL ALARMS FIRE FAULT RELEASE CIRCUIT and AUX EQUIPMENT disables enables the output circuits SA VA1 and VA2 Fire Fault R and NO NC C respectively When the key switch is positioned to the n locked position the manual panel control by means of its push buttons is disabled This is available for the access level 1 Pressing any button causes the internal sounder to make a long sound indicating blocking the buttons When the key switch is positioned to the B unlocked position the manual panel control by means of its push buttons is enabled This is available for the access level 2 and above In such a mode if you press any faceplate button the internal sounder makes short sound acknowledging the pressing 2 3 Panel Internal PC Board The panel PCB layout can be shown in Figure 2 4 The main internal panel components are Terminal Blocks XP1 and XP2 jumpers HL1 internal light emitting indicator Voltage test points info bolid ru overseas bolid com 19 BOLID FIRE ALARM AND EXTINGUISHING CONTROL PANEL 2 3 1 PCB Terminal Blocks X
85. tion manual call points or receiving the relevant command from the network controller When one of the conditions said above is met the panel immediately enters the Fire Alarm and Pre discharge Delay modes If the Remote Release Priority parameter is set off then in the remote release mode the pre discharge delay is stopped when the door sensor circuit has been broken or failed As soon as the door sensor circuit has restored the pre discharge delay continues to be counted If the Remote Launch Priority parameter is set the pre discharge delay is counted without regard to opening or fault the door sensor circuit 3 9 2 Automatic Release In case of automatic releasing the panel enters the Pre discharge Delay mode just after having entered the Fire Alarm mode after having received two responses from automatic fire detectors If the automatic mode is disabled while the pre discharge delay is being counted the pre discharge delay is stopped In such case the panel can enter the Pre discharge Delay mode again only by Automatic release mode having restored having repeatedly activated or Remote releasing the extinguishing system resulting from manual call point activation or receiving the remote release command from the network controller To switch the automatic release mode on off Press the AUTOMATIC MODE button on the panel front plate or Touch the reader connected to the panel with an authorized User Key enro
86. uct will in all cases provide adequate warning or protection Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary robbery fire or other events occurring without providing an alarm but it is not insurance or guarantee that such will not occur or that there will be no personal injury or property loss as a result CONSEQUENTLY SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING HOWEVER IF SELLER IS HELD LIABLE WHETHER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE REGARDLESS OF CAUSE OR ORIGIN SELLER S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER This warranty gives you specific legal rights and you may also have other rights which vary from country to country No increase or alteration written or verbal to this warranty is authorized 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru www bolid com
87. uit having been repaired Remote Enables remote releasing even in case of Release AA On Off per door being open or a door circuit fault Priority Pressure i Detector Blocks up the pressure detector circuit On Off input Disabled Blocking Two Disables automatic release which is the Prealarm result of two alarm loops being in the Fire On Off Release Prealarm statuses Master Key Restricts access to disabling enabling the Provided panel inputs outputs see the Section On Off Access 3 1 Up to 16 addresses ranged from 1 to 127 Defines the addresses of the connected S2000 KPB modules controlled by the panel S2000 KPB Addresses The Automatic Remote Pre discharge Delay parameters defines the duration of delay in seconds between release conditions having occurred and generating a pulse to release the fire extinguishing system The panel provides individual delays for automatic release and remote release both by remote release command received via RS 485 interface and by activating a manual call point The Siren Sounding Time defines the time to activate an external audible alarm connected to the panel when the panel has entered the Fire Alarm or Pre discharge Delay mode If the Automatic Mode Recovery parameter is set on then the panel automatically restores the automatic release mode after a door having closed or any door circuit trouble having repaired If the parameter in question is set off then breaking t
88. xtinguishing Ohe Of Table 3 34 AUTO OFF Sign VA3 Output Panel Condition Output Behavior Automatic release enabled Automatic release disablec Table 3 35 Reader LED Table 3 36 FAULT Relay Panel Condition Relay Contacts Power shutoff faut mote _ mode Opened faut mote _ mode Enclosure tampering Enclosure tampering 54 www bolid com S2000 ASPT Technical Description Table 3 37 FIRE Relay Panel Condition Relay Contacts Fire Alarm mode Pre disch Del re discharge Delay Closed Release Emergency Release Extinguishing 3 12 Panel Co operation The panel can be connected to the network controller via RS 485 1 interface terminals and to the controlled S2000 KPB modules via RS 485 2 terminals 3 12 1 Zones Monitored by the Network Controller Following are the zones that can be monitored by the network controller through the S2000 ASPT panel zone 1 panel alarm loop 1 control zone 2 panel alarm loop 2 control zone 3 panel alarm loop 3 control zone 4 panel door sensor control zone 5 panel manual call point control zone 6 panel pressure detector control zone 7 panel mains power control zone 8 panel battery power control zone 9 panel automatic release mode control zone 10 panel operating mode control zone 11 panel remote release mode control zone 12 fire protection equipment fault monitoring zo