SDC-20C (FC20) Sedona Zone Controller User Manual

image

Contents

1. e Virtual Device FC20 Template FC 20 HVAC File Setting Help Project New Quit Open NS i ii Close Firmware Version Save Function Block Ve i When done the apps can then be downloaded to the SDC 20C FC 20 device Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 18 f 159955 SYXTHSENSE 7 FC Sedona Kits Each SDC 20C FC controller comes with a set of predefined kits These kits are not manageable No additional kits are allowed to install There are total of 5 kits are available to use The 5 kits are as below Kits Name Description easyioFC20 I O objects for SDC 20C FC 20 easyioFC20Control Control objects easyioFC20Regs Register Objects to export either Bacnet or Modbus points easyioFC20HVAC HVAC objects such as PID loop drive easyioFC20TempTable TempTable Object to configure temp table In order to engineer the SDC 20C FC 20 controller user will also need the below kits Kits below need to be at least 1 0 48 Kits Name Minimum version Inet kit 1 0 48 Sox kit 1 0 48 oys kit 1 0 48 7 1 easyioFC20 This kit contains all I Os objects These objects can only be use one time Any duplication of the object will be discard 4 Analogue Output AO objects Each represent respective 0 easyioFC20 channel AO1 196 E A02 196 E A03 196 E A04 196 E 12 Digita
2. Ver 0 2 SDC AN18 CPT Tool User Guide 8 099958 SYXTHSENSE 2 6 Analog Output Connection SDC 20C has four Analog Output connections Each Analog Output can be configured to drive voltage or current output via hardware jumper setting and internal register settings The working range for voltage is O 10V and for current either O 20mA or 4 20mA For current transmitter the circuit able to drive load impedance up to 800 ohm which is ideal for long wire connection up to 500 meter wire length Control Current pye 4 2074 ADi Current controlled WSD COM COM A03 COM 3 And Control voltage 0 10 ce Voltage controlled Actuator COM Equivalent Circuk Voltage Type Equivalent Circuit Current Type T Drive Impedance up to e000 hin Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 9 3 Buttons and indications A a SYXTHSENSE The controller will do a hardware reset when the Reset Button is pressed whenever manual restart is required The Service button is used to activate the built in bootloader program for software upgrade Each digital output has a correspondence LED to indicate its current state LED Conditions Description PWR PWR is used to indicate the presence of 24VAC power source and internal power 4 Software Prerequisite ERR is to indicate whenever t
3. i Connected Device FC 20 HWAC Serial No 11250009 Download Firmware Version 1 0 00 Register Version 1 0 00 Function Black Version 1 0 00 Getting device info completed Step 6 Make sure the virtual device program is running in the PC or the host The virtual device can be running ina remote host It is not necessary to run in the local host Step 7 Using the Sedona workbench or CPT tool connect to the SDC 20C FC 20 device via open Sedona Sedona workbench open device CPT tool In this case the virtual device is running in a local host fe EasyiO Ax Workbench DES Edit Search Bookmarks Tools Window Wire Sheet Help d Od FA New Window File 1 Mit New Tab Ey Directory L Query E Open Platform E Open Station i Open Sedona sox Alt 0 El Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 16 099955 SYXTHSENSE fet Open Sedona Address Credentials Protocol Username Host localhost T admin Password Port 1876 Data Folders Choose sedona data folder Default Sedona Data Folder Step 8 You will see the Sedona programming environment Remember SDC 20C FG 20 is not a Sedona controller it is just using the Sedona workbench or CPT tool to program it All objects programming can only be done in the FC20 folder Dropping components objects in to other f
4. SDC 20C FC20 Sedona Zone Controller 155 SYXTHSENSE User Manual SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter Devon EX3 OQH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 www syxthsense com SYXTHSENSE Copyright Notice This document has been prepared by SyxthSense Limited using i its own proprietary information and ii proprietary information owned and controlled by other third parties for which SyxthSense Limited has a right to use The contents are copyrighted and must not be communicated in whole or in part to any other party without the prior written approval of SyxthSense Limited The following notice applies to this document and shall be reproduced on any permitted copies 2014 SyxthSense Limited All rights reserved Any request for further information concerning this document should be addressed to SyxthSense Limited 3 Topsham Units Dart Business Park Topsham Exeter EX3 0QH United Kingdom Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 2 SYXTHSENSE CONTENTS L INTRODUCTION iras 4 2 PREREQUISTER ae ie 10 Zl BASYIORO SEDONA RITS serrat 11 2 2 EASYIORC SEDONA PLATFORM FILES a 11 3 VIRTUALDEVICERCO aia 12 3l e AA o e ee en EEst 13 4 PROGRAMMING SDC 20C FC 20 DEVICE wisssccsscncsessnzccensvcconsespnnscsvadzstentevescessvinecseaeverscssevecsesenceens 15 Ss ECSE
5. Teminal Communication Setting Serial COM Port Setting This window is to define the Modbus or BACnet serial comm settings to be edited for all connected device in the bus When set button is hit it will set the serial comm settings to the entire scanned device in the device window below Setting r Modbus Baudrate 19200 Modbus Parity Even Modbus Stop Bit One Bacnet Baudrate 19200 Set Device Window This window shows the total number of available device in the bus Scanning address range is 1 127 Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 27 995555 SYXTHSENSE Devices Scan 9 3 Upgrade Firmware Steps Step 1 Get the required files from SyxthSense technical support at support syxthsense com The firmware file is a bin file Name j 10 20P HVAC B1 0 00 bin Step 2 Launch FC FwTool exe and connect USB to RS 485 to the port 1 Step 3 Under the firmware upgrade tab locate the bin file Select the COM port A a Lo moe RE Serial COM Port co M3 Y r Firmware Firmware Bin C Users dell Desktop FC 20 HVAC FC 20 HVAC v210 20P 2013 06 20 bin Model FE 240 Version 1 0 00 Release Date 17 32 40 Jun 20 2013 Step 4 While the controller is in ON mode hold down both buttons for 1 second and release the reset button left side wait for the STS Le
6. 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 29 SYXTHSENSE Connect a USB to RS 485 to the port 1 Step 2 Launch FC FwTool exe Step 3 Under the Terminal tab select the COM port and Connect Connect Serial COM Port STE Step 4 Press and hold down space bar on the keyboard While holding down the Space Bar key note that the comm LED will blink fast stating that communication is under progress Step 5 If the protocol is set to run BACnet MSTP follow this step Power off the controller press and hold down space bar on the keyboard While holding down the Space Bar key power ON the controller Hold down for approx 5 seconds Step 6 When the STS LED blinks at approx 5Hz release the space bar button The terminal window should show the login page Step 7 Login to the terminal mode with the below credentials Username admin Password 1234 Step 8 After successful login window will show the options as below Select one of the menu to proceed Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 30 SYXTHSENSE l Serial Port Read only shows the protocol selection done which done by setting the DIP switch 1 Il Modbus Menu to change the Modbus serial settings IlI Bacnet Menu to change the Bacnet serial settings To change the BACnet ID is
7. See next chapter for details EES TempTable 40 E 8 Temperature table SDC FC 20 comes with 16 temperature table These temperature table settings only available in Sedona workbench at the moment It cannot be done in CPT tool 8 temperature tables are user defines and 8 temperature tables are read only Below are the 16 tables that by default come with the controller Table number Sensor Type Remarks Table 01 NTC 10K Type 2 Editable Table 02 NTC 10K Type 2 Shunt 11K Editable Table 03 NTC 10K Type 3 Editable Table 04 NTC 10K Type 3 Shunt 11K Editable Table 05 NTC 3K Editable Table 06 NTC 20K Editable Table 07 RTD 1K Platinum Editable Table 08 RTD 1K Balco Editable Table 09 NTC 10K Type 2 Read only Table 10 NTC 10K Type 2 Shunt 11K Read only Table 11 NTC 10K Type 3 Read only Table 12 NTC 10K Type 3 Shunt 11K Read only Table 13 NTC 3K Read only Table 14 NTC 20K Read only Table 15 RTD 1K Platinum Read only Table 16 RTD 1K Balco Read only How to configure Temp Table Step 1 Drop the TempTable object from the easyioFCTempTable into the FC20 folder Make sure to drop the object in to the FC20 folder and not the service folder Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 22 059555 SYXTHSENSE a Sedona feasvio FC 201 Tools H App C service B Fezo E TempTab Step 2 Double click on the obje
8. connection Make sure you are connecting the same wire for the same terminal position all H terminals connected to the same wire RS 485 RS 485 RS 485 RS 485 RS 485 RS 485 DEVICE DEVICE DEVICE DEVICE DEVICE DEVICE TERMINATE TERMINATE DAISY CHAIN Shielded Twisted Pair Wire Shielding With Lightning Vire Protection Circuit Max 32 Units vathOul repeater LT Terminating resistor 12002 Lightning Protection 2 2 1 1 RS485 Connection By default the Modbus serial comm settings is as below Baud Rate 19 2K Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 5 059555 SYXTHSENSE Parity even Data Bit 8 Not editable Stop Bit 1 By default BACnet serial settings as below Baud Rate 19 2K 2 3 Jumpers Setting Below image shows the jumper setting for Universal Input Analog Output BACnet Modbus Selection and the BACnet MSTP ID 1 127 or Modbus Serial ID 1 127 The controller comes with BACnet and Modbus protocols selection By default Modbus protocol is selected To switch to BACnet protocol toggle the 1 of the dip switch to ON The remaining DIP switch 2 8 are for BACnet MSTP ID or Modbus Serial ID address 0 is not available it will be set to 1 depending on DIP switch 1 selection Any changes to the DIP switch a power cycle is needed votage Current Analog
9. Output Jumpers Setting ue 1 H O a Fe fra lt x 14 28 4 Y s ow CA 19 E 3 ed n 1441444 m 7 u DOG AO COURT DIOSA 3ACnet Modbus ID Setting eg BACnet Modbus Selection ID b1110101 75H 115 Universal Input Jumpers Settin e jg m ON ON 5 4 4 EE 1 1 2345678 Resistance Senso Voltage Current j 9 4 Modbus BACnet Image below show the DIP switch settings details For serial addressing it uses binary bit The Least Significant Bit LSB isDIP 8 The Most Significant Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 6 099955 SYXTHSENSE Bit MSB is DIP 2 BACnet Modbus ID Setting eg Address 117 BACnet Modbus Selection Modbus Selected Modbus BACnet 2 4 Digital Output Wiring Connection SDC 20C has four general purpose isolated digital output connections relay output Each relay output able to drive up to 1A 30VDC 48VAC load It does not output voltage or current It is a dry relay contact A Direct Drive B Secondary Relay Contactor a lg tal IL o le Equivalent Circuit Lies vce Y gi Maximum Rating ji 14 30VDC 48VAC No Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 7 2 5 Universal Input Connection 195955
10. SYXTHSENSE SDC 20C has twelve non isolated universal inputs The universal input supports three type of analog signal e resistance voltage and current transmitter via hardware jumper and internal register settings a Resistance The working range of resistance is 0 30Kohms If the input is configured as Thermistor type the system provides 8 customizable temperature lookup tables for resistance to temperature translation The commonly used Thermistor like 10K 10K with Shunt 1K Balco and 1K Platinum are all supported b Voltage Two selection of working range 0 5V and 0 10V The minimum input impedance of voltage input is 1 Mega Ohm c Current Two selection of working ranges 0 20mA and 4 20mA The current input impedance is less than 25 Ohm Un COM U2 COM TE COM Ulag COM LUIS COM UIG COM uir COM UIs COM uig COM Uno COM 0111 COM Una CON Thennistor RTD or Potentiom eter Voltage 0 10 0 3 l Curent Tranamitter AAA 0 20m4 4 20m A a g ki T to Ce r E 3 amp ie if E 3 be 2 Online Store www syxthsense com Enquiries T 0844 840 3100 F 0844 840 3200 Equualert Circuit Resstance Temperature Sensor Type Equualert Circuit Voltage Type Ih i 0 1 005 Input Impedance gt 114 Ohm A c 3 Equualert Circust Current Type I 0 20m 44 20 4 i Input Imp dance 250hm 1 E Copyright O 2014 SyxthSense Ltd
11. have the program in the flash memory until it is been overwrite by another program 2 Hardware Configurations 2 1 Power supply Connection Both AC and DC can be used for SDC 20C controller Refer to electrical specification for the working range In order to avoid damage on the controller input output devices and RS485 connection use individual power supply for each controller If a single power supply is used make sure controller power supplies are connected with the same polarity Stepdown Transformer 50 60Hz 17 VA O Primary AC Supply OR 24VDC 20 15 Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 4 099555 SYXTHSENSE Power Supply Connection Stepdown Transformer 50 60Hz Primary AC Supply 2 2 RS485 Connection RS485 connection must be terminated at both ends with termination resistor typically 1200hms lt is recommended to use shielded twisted pair wire STP for the wiring Lightning protection circuit is recommended to be installed at one end of the wiring The controller should be wired in daisy chain network topology as shown as image below If wire branch can be avoided keep it as short as possible and never connect more than one device to the wire branch Be careful if single power supply is used for all connected RS485 device make sure all devices are having the same ground
12. DC AN18 CPT Tool User Guide 33 4 SYXTHSENSE 11 Document Control Version Date Change History 0 1 18 Feb 2014 Original Release 0 2 04 Jun 2014 Hardware Configuration Details Added Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 34 199955 SYXTHSENSE 9455 SYXTHSENSE SyxthSense Limited 3 Topsham Units Dart Business Park Exeter EX3 0QH United Kingdom Enquiries T 0844 840 3100 F 0844 480 3200 Online store www syxthsense com Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 35
13. DONA RTE na aan nn a a ton nt noie 19 SI 4 OU AAA A A teh acs uted ame E AE 19 ds BAS MOE II CONTRO La ne 20 Sy PASTO OA AC ma EAE ETN 20 IA BASVIORC JORG ES tt 21 Do MAS VIO G ZO NIP TABLE arrose ee de EA ee a ee 22 0 TEVNIPERATURE TABLE msi 22 7 NAAA AAA nn de datant an eee atiaistie se ai 24 M PETA TOOL IP uo a tenet 24 TZ FIRMWARE UPGRADE TAB tartas 23 Ted UPGRADE FIRMWARE STEPS ti A 28 A TERMNALMODES IEPS apimi ieia ee ee ee ae too bo due 29 b3 COMMUNICATIONS SETTINGS TAB STEPS entraran ooo EAR TRA 32 S DBCLAIM Raparii E E E an dun not e 33 DOCUMENT CONTRO L masas 34 Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 3 SYXTHSENSE 1 Introduction SyxthSense SDC 20C FC 20 series controller is a competitive controller lt can serves as a dumb lO module or it can be program with limited standalone logic It is not a Sedona controller but it can be program via a Sedona workbench The virtual device will create a virtual Sedona running in the windows environment to replicate the Sedona VM No new software tool to learn No new programming concept to learn Reuse the Sedona workbench knowledge Same programming concept as SDC xG Series Limited resources up to 150 objects or 5MB memory which ever come first The virtual device can then be connected to a hardware and download the program into the controller The controller will
14. VAC vrl Project Name FooTest Model FC 20 Application Name FC 20 HVAC Version 1 0 00 cons Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 13 9955 SYXTHSENSE Step 3 The virtual machine Ul will looks as below ww Virtual Device FooTest FC 20 MVACY gt 2 is File Setting Help y pr gt Project FooTes Controller ae Disconnect Connected Dence FC 20 HVAC Senal No 11250009 Firmware Version 1000 Register Version 1 0 00 Download Funcion Block Version 1 0 00 Status cena dovice inf tod iblockSize 4 refize 4 Running SVM in Platform Mode MESSAGE sys App starting MESSAGE sox SoxService started ports 1876 MESSAGE sys App tunning an GREEN color input lo change value Debugging messages window SDC 20C FC 20 Hardware emulator The virtual device Digital Output indicator The Box will turn Yellow when the DO is ON state and Green when OFF state The virtual device Analog Output indicator The Analog box will show the output value of what is been commanded in the apps AO AO easyioF Z0 ADL Q Cut 6 00 In 76 00 Emergenc nan Manual Owerride nan Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 14 159955 SYXTHSENSE The virtu
15. al device Universal Input as Digital Input Status Toggle switch to activate the Digital Input When DI is toggle the Universal Input will show value 51 00 when true and value 44 00 when value is false DI 101 20f 30M 40M 501 GO 7ON SOM 90M 10 01 11 08 1208 GREEN color inputto change value Virtual Device Universal Input Indicator Simulator Enter a value in here and it will show in the Sedona workbench liniers input 1 Current Value 51 00 40 Hew Value ILLES OR Cancel 6 Programming SDC 20C FC 20 device Step 1 Connect a USB to Rs 485 converter to the PC te Launch the Virtual Device FC 20 exe Some anti virus might block it to run E te Configure the COM port settings use To check the COM port please go to My Computer gt Properties gt Device Manager Windows 7 Step 4 In order to program the SDC 20C FC 20 the protocol has to set to Modbus DIP switch 1 Off Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 15 099955 SYXTHSENSE BACnet Modbus Selection ID b1110101 75H 115 Modbus BACnet Step 5 To test the connection between the Virtual Device and also the SDC 20C FC 20 hardware hit connect at the virtual device program A successful connection will show the SDC 20C FC 20 hardware details Fes Virtual Device FC 2D Lo eel File Setting Help Project
16. ct to bring up the temperature user interface Temprr ahias Tale Pana ati CT Only Table 1 to Table 8 is editable Table 9 to Table 16 is pre defined Default Applicable to Table 1 to Table 8 It will restore the default value according to the type stated above Add To add a row Max of 30 rows If 30 rows are in the table this button will be disable Delete To delete a row Edit To edit the row value Save Save the changes made to the flash memory Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 23 1599955 SYXTHSENSE 9 Firmware Flashing All FC series comes with build in bootloader Build in bootloader comes handy for firmware flashing or updating e The Build bootloader can only be carried out directly It does not support remote bootloader mode Firmware upgrading is via software package FC FwTools exe The FC FwTool exe comes in a bundle with the bootloader mode terminal mode and also serial settings mode It is a 3 in 1 tool bundle 9 1 FC FwTool Below is how the FC FwTool user interface 7 ewe FC Fw Tool Firmware Upgrade Terminal Communication Setting Serial COM Port E amp E Fimware Firmware Bin Browse Model Version Release Date Options Device Firmware Upgrade Device Firmware Detail Device Firmware Run Message Ready Selection Tab Three select
17. d to flash fast and release the service button right button Step 5 Make sure the controller is in bootloader mode The status LED will flash approx 5Hz when the device is in bootloader mode Device Firmware Upgrade Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 28 195955 SYXTHSENSE Hit the firmware upgrade button Message window will show as below Firmware Upgrade imware Size 110212 bytes Fimware Upgrading Status bar at bottom of the FC FwTool exe will show the progress Upgrading 49 983047 110212 bytes A successful firmware upgrade will show as below Message Fimware Upgrade Firmware Size 110212 bytes Firmware Upgrading Firmware CRC Checking Firmware CRC OK Firmware Upgrade Completed Step 6 To verify the firmware version hit the Device Firmware Detail button to retrieve the firmware information This step can be skip if you are sure about the firmware version Device Firmware Detail Device s Finnware Detail Model FC 20 Version 1 0 00 Compile Date Jun 20 2013 Compile Time 17 32 40 Step 7 Hit the Device Run Firmware button to kick the SDC 20C FC device out of bootloader mode into running mode Device Firmware Run 9 4 Terminal Mode Steps Step 1 Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T
18. dules folders Different Sedona version needs different jar file Rename the jar files provided to easyioFC jar or else it will not work 4 1 easyioFC Sedona kits SYXTHSENSE Mame easyloFC_1 1 jar easyioFC_1 2 jar These are the kits that need to be in the Sedona kits folder Copy these files and paste it into the Sedona kits folder Mame de easyioFC di easyioFC20 Je easyloFC2DRegs di easyioFCControl Je easyloFCHVAC de easyioFCTempTable di inet Je SOX de sys 4 2 easyioFC Sedona platform files These sedona platform files that need to be in the Sedona platform folder Copy these files and paste it into the Sedona platform db folder Online Store www syxthsense com Enquiries T 0844 840 3100 F 0844 840 3200 Copyright 2014 SyxthSense Ltd Ver 0 2 SDC AN18 CPT Tool User Guide 11 199955 SYXTHSENSE Marne Je easyios0p d FC20 de fg 5 VirtualDeviceFC20 The virtual device Ul is as below The virtual device is able to show the firmware version serial number and also register version if an SDC 20C FC 20 device is connected If the virtual device is not connected to any hardware it will as below exw Virtual Device FC 20 File Setting Help ort Pro Tempearature Table Virtual Device FC 20 File Setting Help Connected Device Mone Serial Mo Prl Firmware Wersion Register Wersion Function Block Version Status The port d
19. here is communication errors STS is used to indicate the heartbeat of the Microcontroller The STS LED will blink at 1 second interval in normal operation condition TXRX is used to indicate when there are communication activities Transmitting or Receiving on the communication port It is good to refer also to the Firmware Flashing section Below are files needed to be copied into the host PC Apart from the below files a USB to RS 485 converter is needed in order to proceed for program downloading Any equivalent USB to RS 485 converter can be use No Item 1 VirtualDeviceFC20 2 easyioFC Niagara module 3 Sedona kits for FC 20 4 Sedona platform files for FC 20 VirtualDeviceFC20 Description This is the controller Emulator This module is for FC controller temp table settings Sedona kits These kits are fixed sedona platform files This is a program to emulate the FC device in the windows environment Online Store www syxthsense com Enquiries T 0844 840 3100 F 0844 840 3200 Copyright 2014 SyxthSense Ltd Ver 0 2 SDC AN18 CPT Tool User Guide 10 Name db FB de Miagara modules de Projects de Sedona E FC20Ctrl dll 10 20P 2013 07 18 bin VirtualDeviceFC20 2013 07 19 exe Remarks All the files above have to be in a same root folder easyioFC jar Java module for Niagara workbench to be able to view the temp table UI It has to be drop into the Niagara installation mo
20. in this menu IV Username This is to change the terminal mode username V Password This is to change the terminal mode password VI Reset Setting to Default Value This is to reset all the settings done for I Os VII Device information Shows the device firmware information VIII Exit To kick the controller out of terminal mode to normal running mode Step 9 When settings are done hit ESC keyboard button to return to previous menu Choose selection 8 to exit the terminal mode or else press the onboard reset button Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 31 CCG LAR D SYXTHSENSE 9 5 Communications Settings Tab Steps Step 1 Connect a USB to RS 485 to the port 1 Step 2 Launch FC FwTool exe Step 3 Under the Communications Settings tab select the COM port and Connect In this case the COM port use is COM 3 Serial COM Port com3 La This tab can only work if the hardware protocol DIP switch is set to Modbus It will not work if the protocol DIP switch set to BAcnet Step 4 Choose the desire Modbus Baud Rate Parity Stop Bit for Modbus protocol or and BACnet baud rate for BACnet protocol Auto Baud Rate is supported for BACnet MS TP Setting Modbus Baudrate 19200 X Modbus Parity Even Modbus Stop Bt One Bacnet Baudrate 19200 These sett
21. ings are to configure only the Port 1 RS 485 Port 2 is only for Modbus protocol and the baud rate is preset at Baud Rate Parity Stop Bit Step 5 Hit Scan and the program will scan the bus for all the Modbus devices It will scan from address 1 to 127 The window below will show the total number of Modbus devices Step 6 The window below will show the total number of Modbus devices If there is an duplicate Modbus address in the bus it will prompt an error and the scan will be stop Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 32 099955 SYXTHSENSE O 00000001 000000000 F Esmi 000000017 O DODDOO00 Step 7 Hit Set button and the program will set the selected serial settings to all the device listed in the window Serial COM Port com3 Setting Modbus Baudrate 13200 Modbus Parity Even Modbus Stop Bt One Bacnet Baudrate 19200 z se The device do not need a power cycle or reboot for the serial settings to take effect Try rescanning again to confirm the serial settings 10 Disclaimer The SDC 30 SDC 20C SDC 20G and SDC 32G controllers are was built on the Sedona Framework 6 Sedona Framework is a trademark of Tridium Inc CPT Tool is by Online Tools Inc Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 S
22. ion tab available Bootloader mode Terminal mode and also Communication settings mode ea FC Fw Tool Firmware Upgrade Terminal Communication Setting benne eee Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 24 h 1 i g E 133 SYXTHSENSE Tab Selection Function Firmware Upgrade To upgrade the firmware of the FC controller Terminal Terminal mode to change the Bacnet device ID bacnet mstp serial comm settings To change Modbus serial comm settings To reset settings to default value Communication Setting To change serial comm setting in a batch Apply for both Modbus and Bacnet 9 2 Firmware Upgrade Tab Com port selection This field to select the COM port to be use for the FC FwTool exe at the PC In this case it COM3 ames FC Fw Too Firmware Upgrade Terminal Communicatic Serial COM Port mae Firmware selection This field is to select locate the firmware file bin in the local computer Firmware Firmware Bin Options There are 3 options All the options are only useable when the EasylO FC device is in bootloader mode Out of bootloader mode it does not serve any function If option button is click when the device is not in bootloader mode it will pop up an error message saying that device is not in bootloader mode FC Fw Tool Please check device Make sure device is running i
23. l Input DI objects Each represent respective channel Note f DI1 is use then Ul1 is no longer use as an analogue input Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 19 SYXTHSENSE easyioFC20 011 148 6 0110 148 E 0111 14 E 0112 14 E D12 148 E O13 148 E 014 14 El 015 14 E DIS 148 El CI7 148 E Drs 148 E Dia 148 E 4 Digital Output DO objects Each represent respective channel B easyioFC20 M Doi 148 E DO2 148 E 0o03 148 E 004 148 E 12 Universal Input objects Each represent respective channel Note if UN is use then Df is no longer use as a digital input B easyioFC20 Uli 2448 UI10 2448 uni 2448 UI12 2448 UI2 244E UI3 2446 UI4 2448 Us 2448 3 Uls 2448 UI7 2448 UIS 2446 SUIS 2448 7 2 easyioFC20Control This kit contains all the control objects The control objects are from Sedona control kit All source code are available from Sedona 7 3 easyioFC20HVAC This kit contains all the control objects for HVAC applications The control objects are from Sedona control kit All source codes are available from Sedona Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User G
24. n bootloader mode Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 25 199955 SYXTHSENSE Options Device Firmware Upgrade Device Firmware Detail Device Firmware Run Options Function Device Firmware Upgrade To upgrade the firmware of the SDC 20 FC device according to the firmware selected at the firmware selection field Device Firmware Detail To retrieve the firmware information when SDC 20C FC device in bootloader mode Device firmware Run To kick the bootloader mode into running mode Output messages window This window shows the debugging messages of each option above Message Device is running in normal mode Terminal Tab Com port selection This field to select the COM port to be use for the FC FwTool exe atthe PC In this case it COM3 cs EA Fimware Upgrade Terminal Communication Setting Serial COM Port coma i Working window This window here shows the selection when the program successfully connected to the SDC 20C FC device Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 26 SYXTHSENSE Communication Setting Tab Com port selection This field to select the COM port to be use for the FC FwTool exe at the PC In this case it COM3 FC Fw Too Me e i Firmware Upgrade
25. older might cause issues later Sedona easyio FC 20 oS Tools Et Ef App EES service gt Hw aot E E Doi HW po2 E 8 TickToc E pit E p12 Step 9 The program right now will reflect the virtual device The virtual device will run as it is an SDC xG Virtual Device The virtual device is running real time It will show real time values when engineering via Sedona workbench or CPT tool Online Store www syxthsense com Copyright O 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 17 099958 SYXTHSENSE DO soc Punto Tick Tock ET II gt Step 10 Once programming is done the program can then be downloaded to the SDC 20C FC 20 hardware via the virtual device Just hit download and the program will be downloaded into the hardware The program will run right after the download process is done The project will also download the temp table set via the workbench or CPT tool Every download will overwrite the program in the SDC 20C FC 20 Step 11 The program done in workbench or CPT tool can be backup as it is a project created as mention is the previous chapter To save the project just go to File gt Save Save As The saved file extension is vd F3 Marne __ FC20Sample vd _ FC20TickTock wd __ fooTest vd To reuse the backup just open the project via Virtual Device and then connect Sedona via workbench or CPT tool to modify
26. rop down menu is for use to set the serial comm settings that is use to connect to the SDC 20C FC 20 device In this case the settings are as below Serial Port Serial port use selection Serial settings SDC 20C FC 20 hardware pre define settings This settings are done using the FC FwTool exe Device ID SDC 20C FC 20 devices ID to be connect This is set via the SDC 20C FC 20 DIP switch Serial Port Setting Serial Port Baud Rate Parity Stop Bit Device ID OK Cancel Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 12 159955 SYXTHSENSE sw Virtual Device FC 20 File Setting Help Project Connected Device FC 20 HVAC Serial No 11250009 Download Firmware Version 1 0 00 Register Version 1 0 00 Function Block Version 1 0 00 Getting device info completed When connect button is press the virtual device will obtain the hardware information from the device 5 1 Create a project file Step 1 The virtual device is capable of creating and saving an apps for future use To do this go to drop menu File and hit Project gt New ewe Virtual Device FC 20 Setting Help Project y Hels step 2 Put in a project name and select the Project tyoe as SDC 20C FC 20 HVAC then hit OK iNew Project res Project Type FC 20H
27. uide 20 099955 SYXTHSENSE D essor E Drive 152 B Loop 216 E LSeg 152 6 Psychrometric 148 E ReheatSeg 144 E Reset 128 E RunTime 100 El Thermostat 120 B 7 4 easyioFC20Regs This kit contains register objects Each type comes with max 16 register addresses Type Register Type Total Number of Register Bool Boolean Read Only 16 BoolWr Boolean Writable 16 Float Float Read Only 16 combine share with Long FloatWr Float Writable 16 combine share with LongWr Long Long Read Only 16 combine share with Float LongWr Long Writable 16 combine share with FloatWr short Integer Read Only 16 shortWr Integer Writable 16 These register address will represents in Modbus or Bacnet automatically base on address and name created See example below The register Bool with address 2000 for Modbus and BACnet As for BACnet when doing points discovery the name of the object will appear AO 4 Reverse binaryValue 20 presentValue Inactive benaryyelue 2 elReg2 binaryValue 22 presentValue Inactive Modbus Register BACnet Object Address 2000 Object ID BV 21 Data Type Discrete Input Data Type Binary Value Address Base Zero Base Online Store www syxthsense com Copyright 2014 SyxthSense Ltd Ver 0 2 Enquiries T 0844 840 3100 F 0844 840 3200 SDC AN18 CPT Tool User Guide 21 099958 SYXTHSENSE 7 5 easyioFC20TempTable This kit contains an object for configuring the temp table for the FC device