Home

User Manual - Instrumart

image

Contents

1. mm O DC Ground 11 28 VDC DC Ground 9 11 28 VDC Figure 8 DC power connections 3 Connect an 12 28V DC Class 2 power source as illustrated in Figure 8 TFXL Meter terminal blocks can accommodate wire up to 14 AWG 4 Connect a switch or circuit breaker in close proximity of the TFXL Meter and within easy reach of the operator 5 Markthe switch or circuit breaker as the disconnect device for the TFXL Meter April 2015 TTM UM 00369 EN 02 Page 13 Transducer Installation TRANSDUCER INSTALLATION The transducers for the TFXL Meter contain piezoelectric crystals that transmit and receive ultrasonic signals through the walls of liquid piping systems DTTR DTTN and DTTH transducers are relatively simple and straightforward to install but spacing and alignment of the transducers is critical to the system s accuracy and performance CAREFULLY EXECUTE THESE INSTRUCTIONS DTTS and DTTC small pipe transducers have integrated transmitter and receiver elements that eliminate the requirement for spacing measurement and alignment Mounting the DTTR DTTN and DTTH clamp on ultrasonic transit time transducers takes four steps 1 Select the optimum location on a piping system 2 Select a mounting configuration 3 Enter the pipe and liquid parameters into the UltraLink software utility or key them into the transmitter The UltraLink software utility or the transmitter s firmware calculates prop
2. s aaW COE 066 WRO WANWW NOLLWTIVISNI 3svauo 3NOOTIIS HO ALY did 1300 OL314n02 32 V4iiis ONISNAS SUIDNGSNVEL 530435 LLG SDINOSYNAG Me DAV 5139 Sh OQNNZVH NON WIIWIXVW SNOUIV2O1 G3HISSVTD SnOQNVZVH SWaLSAS 3445 ATIWOISNIM NOUNTYVILSNI 972148 YSI 505 ANY 05 SNOLL3S 0 ISNV 3002 1V2IL2313 1VNOLLVN 3HLHLIM3ONYQNODOV NI 38 TI VHS NOLL TIVISNI Z 1 1220 VSD 3000 IVILI NVIGVNV9 JHL HLIM 32NVONODOV NI 38 5 VOWNV NI NOUN TIVISNI 9 IN3WdIQIO3 SIHLONITIVISNI N3HM 38 15 1 5 Slvivd v QalvIDOSS V s TWAOW dd IVNOLIVNHLINI S2 LNOHLIM OL NOISUG ON ALYS AVW SIN3NOdWOD 30 115805 DNIDIAWAS 380438 193NNODSIG S383HdSOWJV 318 VWWY 14 JO NOLLINDI IN3A3Md OL ONINSVM Z 15 ONLLNNOW NOLIV2O T2 QSNYM1 TWANYW NOLIV TIVILSNI 5 IWSNVULOLY33Y 1 2 58 OL Ob 3M Ld W LINGUA WAWIKYW 2 5 1 NOISWQ 155915 Figure 43 Control drawing IS barrier transducers Page 51 TTM UM 00369 EN 02 April 2015 Control Drawings CLASS DIVISION 1 GROUPS C AND D MAXIMUM AMBIENT TEMPERATURE 40 85 C 1 REF
3. Figure 35 Output tab Parameter Meaning Description Min Flow Controls how the 4 20 mA output is spanned Max Flow Controls how the 20 mA output is spanned The 4 20 mA Output menu applies to all transmitters and is the only output choice for Channel 1 The Flow at 4 mA 0 Hz and Flow at 20 mA 1000 Hz entries set the span for both the 4 20 mA output and the 0 1000 Hz frequency output The 4 20 mA output is internally powered current sourcing and can span negative to positive flow rates This output interfaces with virtually all recording and logging systems by transmitting an analog current that is proportional to system flow rate Independent 4 mA and 20 mA span settings are established in firmware using the flow measuring range entries These entries can be set anywhere in the 40 40 fps 12 12 mps range Resolution of the output is 12 bits 4096 discrete points and can drive up to a 900 Ohm load When powered by a DC supply the load is limited by the input voltage supplied to the instrument See Figure 24 on page 25 for allowable loop loads Flow at 4 mA 0 Hz Flow at 20 mA 1000 Hz The Flow at 4 mA 0 Hz and Flow at 20 mA 1000 Hz entries set the span of the 4 20 mA analog output and the frequency output These entries are volumetric rate units that are equal to the volumetric units configured as rate units and rate interval Example 1 To span the 4 20 mA output from 100 100 gpm with 12 m
4. d he ao des 9 Temperature Ratings for Transducers 9 05 5 CT MUT T Oa eee 9 Data Integrity cs ra RR DARE EE PRR n 9 Product Identification 24 0 84 e Qd s o qoe x Ae ee RU Bor Queda e eus 9 Transmitter Installation ace a Pack ORG Uu ARE ac wy XR NUR e sn 10 Transmitter Location 6 640 9046 ARR a IIIA Qe 10 ii AINEA ETE 10 Transducer Connectlons 23 sme does nus or da odo d 12 DC Power Connections raro ataga na R acq e Reb s qaot ard acu ioa edes do dor CAR ed dae d d 13 Transducer Installations s ae us aori OUR DR IR HEU 14 Mounting Location 22 3 Rr Rp eR ER ER ERR EORR EORR REOR EORR REOR 14 Select a Mounting Location lee eee ue ure 14 Selecta Mounting Configuration isa cR RR XR ce cea Le RR whS KWEA 16 Enter the Pipe and Liquid Parameters has 18 Mountthe Transducer suae b kaka OX FUA OE NUN OS RA E HE NEC EUR 18 Transducer Mounting Configurations seer sasarane a erT ENER EEEREN EAA
5. GDynasonics Time Ultrasonic Flow Meters Ultrasonic yr Meters TFXL Meter gt Badger Meter GUERRA User Manual Transit Time Ultrasonic Flow Meters TFXL Meter Page ii TTM UM 00369 EN 02 April 2015 User Manual CONTENTS ScopeofThis Mant al 452 te 24a bude rod on qoid 5 Unpacking and ROC _ 5 sc TTD TT 5 Terminology and Symbols RU RR RU RR 5 Consideration So oos 5 Quick Start Operating Overview ss cd ak e xh RR eh Us RR Ue Rn 6 Transducer e dU os Tus d ety d Ae qe 6 Power Connections xb dua qo d 6 Transducer Connections for Remote Mount Transducers 6 Initial Settings and Power p xs ROGA UR SOURCE OR X EG OR OE OX Ra e Ry 7 Pipe Preparation and Transducer Mounting 7 IntrOd ctiol suu ah NE KA Na P 9 Application Versatility 2 ngo e ey efe
6. 3 Place a single bead couplant approximately 1 2 inch 12 mm thick on the flat face of the transducer See Figure 12 on page 19 4 Placethe first transducer in between the mounting rails near the zero point on the scale Slide the clamp over the transducer Adjust the clamp and transducer so the notch in the clamp aligns with the zero on the scale See Figure 23 5 Secure with the thumb screw Check that the screw rests in the counter bore on the top of the transducer Excessive pressure is not required Apply just enough pressure so that the couplant fills the gap between the pipe and transducer 6 Placethe second transducer in between the mounting rails near the dimension derived in the transducer spacing section Read the dimension on the mounting rail scale Slide the transducer clamp over the transducer and secure with the thumb screw Figure 22 Mounting rail system for DTTR Mounting Track Installation for DTTN DTTH A convenient transducer mounting track can be used for pipes that have outside diameters between 2 10 inches 50 250 mm and for DTTN DTTH transducers If the pipe is outside of that range mount the transducers separately 1 Install the single mounting rail on the side of the pipe with the stainless steel bands provided Do not mount it on the top or bottom of the pipe On vertical pipe orientation is not critical Check that the track is parallel to the pipe and that all four mounting feet are touching th
7. 3001 Invalid hardware configuration Upload corrected file 3002 Invalid system configuration Upload corrected file ClassB 3003 Invalid strategy file Upload corrected file Errors 3004 Invalid calibration data Re calibrate the system 3005 Invalid speed of sound calibration data Upload new data 3006 Bad system tables Upload new table data ral 4001 Flash memory full Return transmitter to factory for evaluation Table 6 TFXL error codes Page 40 TTM UM 00369 EN 02 April 2015 K Factors K FACTORS Description The K factor with regards to flow is the number of pulses that must be accumulated to equal a particular volume of fluid You can think of each pulse as representing a small fraction of the totalizing unit An example might be a K factor of 1000 pulses per gallon This means that if you were counting pulses when the count total reached 1000 you would have accumulated one gallon of liquid Using the same reasoning each individual pulse represents an accumulation of 1 1000 of a gallon This relationship is independent of the time it takes to accumulate the counts The frequency aspect of K factors is a little more confusing because it also involves the flow rate The same K factor number with a time frame added can be converted into a flow rate If you accumulated 1000 counts one gallon in one minute then your flow rate would one gpm The output frequency in Hz is found simply by dividing the number of count
8. i o urbine Outpu Sz Turbine Output YA Figure 27 Freguency output switch settings The freguency outputis proportional to the makimum flow rate entered into the meter The makimum output freguency is 1000 Hz If for example the MAX RATE parameter was set to 400 GPM then an output frequency of 500 Hz half of the full scale frequency of 1 000 Hz would represent 200 GPM In addition to the control outputs the frequency output can be used to provide total information by use of K factor K factor simply relates the number of pulses from the frequency output to the number of accumulated pulses that equates to a specific volume Page 26 TTM UM 00369 EN 02 April 2015 Inputs Outputs For this transmitter the relationship is described by the following equation The 60 000 relates to measurement units in volume min Measurement units in seconds hours or days would require a different numerator 60 000 Full Scale Units A practical example would be if the MAX RATE for the application were 400 gpm the K factor representing the number of pulses accumulated needed to equal one gallon would be Kfactor 60 000 00 gpm If the frequency output is to be used as a totalizing output the transmitter and the receiving instrument must have identical K factor values programmed into them to ensure that accurate readings are being recorded by the receiving instrument Unlike standard mechanical transmitter
9. rh 19 Inputs Outputs i sek EE RON GUERRE OR OR eae ad Gade ae 25 Standard 420 mA umo Rd ee ao qup OO chos ose uo dup au on BR 25 Totalizer Output sine EG _ 26 Freguency OUTPUT E RR Rd 26 April 2015 TTM UM 00369 EN 02 Page iii Transit Time Ultrasonic Flow Meters TFXL Meter Parameter Configuration Using UltraLinkSoftware eee eh 28 System Requirements si a due ee AUN hate de UR RR ERR 28 14 28 InitializatiOn Roa RUE RAE 28 Configuration a dn 30 30 alinm ORTU 35 Calibration Ment Seca RIS GREG UE US EUR ee 37 Remove the Zero Offset c cues soma RON RON oe eps doo eda UR Len te e e dea dcr a NC ald 37 Select Flow Rate UNNS E RN 37 Set Multiple Flow Rates 2 5 oret eR ub o en ro Rx Redi ao des 38 Target Dog Data Screen Definitions sac sce kp xp CS XR ROG XR XU MR ONG Xue XC 39 Saving the Configura
10. Double click the UltraLink icon to start the software The UltraLink software will attempt to connect to the transmitter If communications cannot be established you will be prompted to select a Com Port and Com Port Type Page 28 TTM UM 00369 EN 02 April 2015 Parameter Configuration Using UltraLink Software The first screen is the RUN mode screen which contains real time information regarding flow rate totals signal strength communications status and the transmitter s serial number The COMM indicator in the lower right corner indicates that the serial connection is active If the COMM box contains a red ERROR indication select Communications on the Menu bar and select Initialize Choose the appropriate COM port and the RS232 USB Com Port Type Proper communication is verified when a green OK is indicated in the lower right corner of the PC display and the Last Update indicator in the text area on the left side of the screen changes from red to an active clock indication Device Addr 127 eel faa Time Emin Historical Data Flow 84 48 Gal M Totalizer 2496 Pos 2496 Gal Neg 0 Gal Sig Strength 15 2 Margin 100 0 60 19 ns Last Update 11 41 05 Reset Tolalizers April 2015 Figure 31 Data display screen TTM UM 00369 EN 02 Page 29 Configuration Menu CONFIGURATION MENU Configuration Basic Tab The Configuration menu has
11. Meters mul l L LL I LI TFXL Transit Time Model Transit Time Ultrasonic Flow Transmitter Display Options ABS Enclosure Blind No Display C US 1 ABS Enclosure With Rate and Total Display C US 2 Pipe Size Measurement Range 1 2 Inch ANSI Pipe 3 4 Inch ANSI Pipe 1 Inch ANSI Pipe 1 1 4 Inch ANSI Pipe 1 1 2 Inch ANSI Pipe 2 Inch ANSI Pipe 1 2 Inch Copper Tube 3 4 Inch Copper Tube 1 Inch Copper Tube 1 1 4 Inch Copper Tube 1 1 2 Inch Copper Tube 2 Inch Copper Tube 1 2 Inch O D Std Tube 3 4 Inch O D Std Tube 1 Inch O D Std Tube 1 1 4 Inch O D Std Tube 1 1 2 Inch O D Std Tube 2 Inch O D Std Tube Remote Mount Use with DTTR N H Remote Mount Use with DTTS C Connector Options None Two 1 2 inch Conduit Holes N Two Water Tight Cable Clamps A Two 1 2 Inch Flexible Conduit Connectors D Output Options 4 20 mA and TTL Pulse 1 Totalizer Pulse 3 gt lt OvD Z Reserved None Reserved N Options None N CPVC Transducer Material Integral Mount Options Only I S DTTN Transducer Remote Option X Only April 2015 TTM UM 00369 EN 02 Page 55 Transit Time Ultrasonic Flow Meters TFXL Meter Control Manage Optimize Dynasonics and UltraLink are registered trademarks of Badger Meter Inc Other trademarks appearing in this document are the property of their respective entities Due to con
12. OD 15 30 15 30 15 65 15 65 15 98 15 98 16 32 16 32 14 Wall 0 57 0 66 0 74 0 82 0 90 0 99 1 07 1 16 ID 14 16 13 98 14 17 14 01 14 18 14 00 14 18 14 00 OD 17 40 17 40 17 80 17 80 18 16 18 16 18 54 18 54 16 Wall 0 60 0 70 0 80 0 89 0 98 1 08 1 18 1 27 ID 16 20 16 00 16 20 16 02 16 20 16 00 16 18 16 00 OD 19 50 19 50 19 92 19 92 20 34 20 34 20 78 20 78 18 Wall 0 64 0 75 0 87 0 96 1 07 1 17 1 28 1 39 ID 18 22 18 00 18 18 18 00 18 20 18 00 18 22 18 00 OD 21 60 21 60 22 06 22 06 22 54 22 54 23 02 23 02 20 Wall 0 67 0 80 0 92 1 03 1 15 1 27 1 39 1 51 ID 20 26 20 00 20 22 20 00 20 24 20 00 20 24 20 00 Table 9 Cast iron pipe standard classes 3 20 inch Page 46 TTM UM 00369 EN 02 April 2015 North American Pipe Schedules Cast Iron Pipe Standard Classes 24 84 inch Class Size in in A B C D E F G H OD 25 80 25 80 26 32 26 32 26 90 26 90 27 76 27 76 24 Wall 0 76 0 98 1 05 1 16 1 31 1 45 1 75 1 88 ID 24 28 24 02 24 22 24 00 24 28 24 00 24 26 24 00 31 74 32 00 32 40 32 74 33 10 33 46 30 Wall 0 88 1 03 1 20 1 37 1 55 1 73 ID 29 98 29 94 30 00 30 00 30 00 30 00 OD 37 96 38 30 38 70 39 16 39 60 40 04 36 Wall 0 99 1 15 1 36 1 58 1 80 2 02 ID 35 98 36 00 35 98 36 00 36 00 36 00 OD 44 20 44 50 45 10 45 58 42 Wall 1 10 1 28 1 54 1 78 ID 42 00 41 94 42 02 42 02 OD 50 55 50 80 51 40 51 98 48 Wall 1 26 1 42 1 71 1 99 ID 47 98 4
13. avoided is estimated to be capable of causing minor or moderate personal injury or damage to property Considerations The installation of the TFXL Meter must comply with all applicable federal state and local rules regulations and codes EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 AVERTISSMENT RISQUE D EXPLOSION LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CEMAT RIEL INACCCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I DIVISION 2 DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO BE NON HAZARDOUS A AVERTISSMENT RISQUE D EXPLOSION NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST SOUSTENSION A MOINS QU LL NE S AGISSE D UN EMPLACEMENT NON DANGEREUX IMPORTANT Not following instructions properly may impair safety of equipment and or personnel IMPORTANT Must be operated by a Class 2 supply suitable for the location April 2015 TTM UM 00369 EN 02 5 Quick Start Operating Overview QUICK START OPERATING OVERVIEW Follow these instructions to get the system up and running quickly Refer to the detailed instructions if you require additional information NOTE The following steps require information supplied by the transmitter itself so it will be necessary to supply power to the transmitter at least temporarily and connect to a computer using the UltraLink software utility to obtain setup information Transducer Location 1 Se
14. conduit was ordered with the transducer The remote mount transducers use an add in connection board on the left side of the meter below the LCD TFXL Meter 2 version The terminals within the TFXL Meter are of a screw down barrier terminal type Connect the wires at the corresponding screw terminals in the transmitter Observe upstream and downstream orientation and wire polarity See Figure 2 on page 7 TTM UM 00369 EN 02 April 2015 Upstream Transducer 20000000000 U Downstream Transducer Figure 2 Remote mount connections Initial Settings and Powerup 1 Apply power to the transmitter 2 Enter the following data into the TFXL Meter via the UltraLink software utility 1 Transducer mounting method 7 Pipe liner thickness 2 Pipe O D Outside Diameter 8 Pipe liner material 3 Pipe wall thickness 9 Fluid type 4 Pipe material 10 Fluid sound speed 5 Pipe sound speed 11 Fluid viscosity 6 Pipe relative roughness 12 Fluid specific gravity NOTE Nominal values for these parameters are included within the transmitter operating system The nominal values may be used as they appear or may be modified if the exact system values are known 3 Record the value calculated and displayed as transducer spacing Pipe Preparation and Transducer Mounting DTTR DTTN and DTTH Transducers 1 Place the transmitter in si
15. on downward flowing pipes unless adequate downstream head pressure is present to overcome partial filling of or cavitation in the pipe Page 14 TTM UM 00369 EN 02 April 2015 Transducer Installation Pipin nfi ration Upstream Downstream g gu atio Pipe Pipe and Transducer Positioning Diameters Diameters Table 1 Piping configuration and transducer positioning The TFXL Meter will provide repeatable measurements on piping systems that do not meet these pipe diameter requirements but the accuracy of the readings may be influenced April 2015 TTM UM 00369 EN 02 Page 15 Transducer Installation Select a Mounting Configuration The transmitter can be used with five transducer types DTTR DTTN DTTH DTTS and DTTC Meters that use the DTTR DTTN or DTTH transducer sets consist of two separate sensors that function as both ultrasonic transmitters and receivers These transducers are clamped on the outside of a closed pipe at a specific distance from each other DTTS and DTTC transducers integrate both the transmitter and receiver into one assembly that fixes the separation of the piezoelectric crystals The DTTR DTTN and DTTH transducers can be mounted in W Mount where the sound traverses the pipe four times This mounting method produces the best relative travel time values but the weakest signal strength V Mount where the sound traverses the pipe twice V Mount is a compromise between travel time
16. overtighten Overtightening will not improve performance and may damage the transducer 5i Verify that signal strength is greater than 5 0 6 Inputthe units of measure and the data Page 8 TTM UM 00369 EN 02 April 2015 Introduction INTRODUCTION The TFXL Meter is designed to measure the fluid velocity of liquid within a closed conduit The transducers are a non contacting clamp on or clamp around type which provide the benefits of non fouling operation and ease of installation The TFXL Meter family of transit time transmitters uses two transducers that function as both ultrasonic transmitters and receivers The transducers are clamped on the outside of a closed pipe at a specific distance from each other The transducers can be mounted in V Mount where the sound transverses the pipe two times W Mount where the sound transverses the pipe four times or in Z Mount where the sound crosses the pipe once The selection of how transducers are mounted on opposite sides of the pipe and method is based on pipe and liquid characteristics which both have an effect on how much signal is generated The flow meter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers The difference in the time interval measured is directly related to the velocity of the liquid in the pipe Applicat
17. state high with pulses low April 2015 TTM UM 00369 EN 02 Page 53 Specifications Transducers PBT glass filled Ultem Nylon cord grip PER PVC cable jacket 40 250 F 40 1217 C CPVC Ultem Nylon cord grip DTTC OHIO Polyethylene cable jacket 40 185 F 40 85 C CPVC Ultem Nylon cord grip Transducer UTILES Polyethylene cable jacket 40 185 F 40 85 C Construction DTTH NEMA 6 IP67 PTFE Vespel Nickel plated brass cord grip PFA cable jacket 40 350 F 40 176 C DITS NEMA 6 IP67 PVC Ultem Nylon cord grip PVC cable jacket 40 140 F 40 60 NEMA 6 units to a depth of 3 ft 1 m for 30 days max NEMA 6P units to a depth of 100 ft 30 m seawater equivalent density indefinitely Cable Length 990 ft 300 meter max in 10 ft 3 m increments Submersible Conduit limited to 100 ft 30 m Pipe Tubing Sizes 1 2 in 12 mm and larger Pipe Tubing Materials Carbon steel stainless steel copper and plastic Software Utilities ULTRALINK Used to configure calibrate and troubleshoot flow and energy meters Connection via USB A B cable software is compatible with Windows 2000 Windows XP Windows Vista and Windows 7 Page 54 TTM UM 00369 EN 02 April 2015 Part Number Construction PART NUMBER CONSTRUCTION Dynasonics Ultrasonic Flow
18. the response time of the transmitter Conversely lowering this value will decrease the response time of the transmitter to changes in flow energy rate This filter is not adaptive it is operational to the value set at all times NOTE The transmitter completes a measurement in approximately 350 400 mS The exact time is pipe size dependent Flow Filter Damping Maximum adaptive filter value Enter a numeric value Flow Filter Damping establishes a maximum adaptive filter value Under stable flow conditions flow that varies less than the Flow Filter Hysteresis entry this adaptive filter will increase the number of successive flow readings that are averaged together up to this maximum value If flow changes outside of the flow filter hysteresis window the filter adapts by decreasing the number of averaged readings and allows the transmitter to react faster The damping value is increased to increase stability of the flow rate readings Damping values are decreased to allow the transmitter to react faster to changing flow rates The factory settings are suitable for most installations Increasing this value tends to provide smoother steady state flow readings and outputs Flow Filter Hysteresis Allows variations in flow Enter a numeric value Flow Filter Hysteresis creates a window around the average flow measurement reading allowing small variations in flow without changing the damping value If the flow varie
19. with most recording and logging systems by transmitting an analog current signal that is proportional to system flow rate The 4 20 mA outputis internally powered current sourcing and can span negative to positive flow energy rates Supply Voltage 7 VDC Maximum Loop Resistance 0 02 1100 1000 900 800 5 700 9 600 5 500 B Operate in the do Shaded Regions 200 100 10 12 14 16 18 20 22 24 26 28 Supply Voltage VDC Figure 24 Allowable loop resistance 10 4 20 mA Ground 4 20 mA Return 4 20 mA Output 4 20 mA Output a Ol Figure 25 4 20 mA output The 4 20 mA output signal is available between the 4 20 mA Output and Signal Ground terminals as shown in Figure 25 Batch Totalizer Output Totalizer mode configures the output to send a 100 mSec pulse each time the display totalizer increments divided by the TOT MULT The TOT MULT value must be a whole positive numerical value This output is limited to 1 Hz maximum For example if the totalizer exponent TOTL E is set to E0 x1 and the totalizer multiplier TOT MULT is set to 1 then the output will pulse each time the totalizer increments one count or each single whole measurement unit totalized If the totalizer exponent TOTL E is set to E2 x100 and the totalizer multiplier TOT MULT is set to 1 then the control output will pulse each time the display totalizer increments or once per 100 measur
20. 0 3559 7 1085 5 8 Butyrate Ethyl 3836 1 1170 Carbon dioxide 1 10 2752 6 839 7 7 0 137 0 151 Carbon tetrachloride 1 60 3038 1 926 2 5 0 607 0 968 Chloro benezene 1 11 4176 5 1273 3 6 0 722 0 799 Chloroform 1 49 3211 9 979 3 4 0 550 0 819 Diethyl ether 0 71 3231 6 985 4 9 0 3 11 0 222 Diethyl Ketone 4295 1 1310 Diethylene glycol 1 12 5203 4 1586 24 Ethanol 0 79 3960 0 1207 4 0 1 390 1 097 Ethyl alcohol 0 79 3960 0 1207 4 0 1 396 1 101 Ether 0 71 3231 6 985 4 9 0 311 0 222 Ethyl ether 0 71 3231 6 985 4 9 0 311 0 222 Ethylene glycol 1 11 5439 6 1658 2 1 17 208 19 153 Freon R12 2540 774 2 Gasoline 0 7 4098 4 1250 Glycerin 1 26 6246 7 1904 2 2 757 100 953 946 Glycol 1 11 5439 6 1658 2 1 Isobutanol 0 81 3976 4 1212 Iso Butane 4002 1219 8 Isopentane 0 62 32152 980 4 8 0 340 0 211 Isopropanol 0 79 3838 6 1170 2 18 2 134 Isopropyl Alcohol 0 79 3838 6 1170 2 718 2 134 Page 48 TTM UM 00369 EN 02 April 2015 Fluid Properties Fluid Specific Gravity Sound Speed delta v C Kinematic Absolute 20 C ft s m s m s C Viscosity cSt Viscosity Cp Kerosene 0 81 4343 8 1324 3 6 Linalool 4590 2 1400 Linseed Oil 0 925 0 939 5803 3 1770 Methanol 0 79 3530
21. 17 00 0 500 16 12 0 940 1568 1 160 1525 1375 1443 1 785 20 2000 18376 0 812 19 00 0 500 17 93 1 035 1743 1285 1700 1 500 16 06 1 970 24 2400 22 126 0 937 23 00 0 500 21 56 1 220 2093 1 535 2093 1 535 1931 2 345 30 30 00 29 00 0 500 36 36 00 35 00 0 500 42 42 00 41 00 0 500 48 4800 47 00 0 500 Table 7 Steel stainless steel PVC pipe standard classes April 2015 TTM UM 00369 EN 02 Page 43 North American Pipe Schedules Steel Stainless Steel PVC Pipe Standard Classes continued SCH 10 NES SCH5 SCH 20 SCH 30 STD SCH 40 in in ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall in in in 1 1315 1 185 0 065 1 097 0 109 1 049 1049 0 133 125 1 660 153 0065 1442 0109 1 380 1 380 0 140 15 1900 177 0065 1 682 0 109 1 610 1610 0 145 2 2 375 2245 0 065 2 157 0 109 B 2 067 2 067 0 154 25 2875 2709 0 083 2 635 0 120 2 469 2 469 0 203 3 3 500 3 334 0 083 3260 0 120 3 068 3 068 0 216 35 4000 3 834 0 083 3760 0 120 3 548 3 548 0 226 4 4 500 4 334 0 083 4260 0 120 4 026 0 237 4 026 0 237 5 5 563 5 345 0 109 5295 0 13
22. 2 2MHz DTTSnC Copper DTTSnT Stainless Steel DTTSnP ANSI 3 4 in 2MHz DTTSnC Copper DTTSnT Stainless Steel DTTSnP ANSI Tin 2MHz DTTSnC Copper DTTSnT Stainless Steel DTTSnP ANSI 1 1 4 in 2MHz DTTSnC Copper DTTSnT Stainless Steel DTTSnP ANSI 1 1 2 in 2MHz DTTSnC Copper DTTSnT Stainless Steel DTTSnP ANSI 2in DTTSnC Copper 2MHz DTTSnT Stainless Steel DTTS transducer designation refers to both DTTS and DTTC transducer types Table 3 Transducer mounting modes for DTTS DTTC April 2015 TTM UM 00369 EN 02 Page 17 Transducer Installation Enter the Pipe and Liquid Parameters The TFXL Meter calculates proper transducer spacing based on the piping and liquid information you enter into the transmitter via the UltraLink software utility See Parameter Configuration Using UltraLink Software on page 28 The most accuracy is achieved when the transducer spacing is exactly what the transmitter calculates so use the calculated spacing if the signal strength is satisfactory If the pipe is not round the wall thickness not correct or the actual liquid being measured has a different sound speed than the liquid programmed into the transmitter the spacing can vary from the calculated value In that case place the transducers at the highest signal level observed when moving the transducers slowly around the mount area NOTE Transducer spacing is calculated on ideal pipe Ideal pipe almost never exists so you may need to a
23. 2 1076 2 92 0 695 0 550 Methyl Alcohol 0 79 35302 1076 2 92 0 695 0 550 Methylene Chloride 1 33 3510 5 1070 3 94 0 310 0 411 Methylethyl Ketone 3967 2 1210 Motor Oil SAE 20 30 0 88 0 935 4875 4 1487 Octane 0 70 3845 1 1172 4 14 0 730 0 513 Oil Castor 0 97 4845 8 1477 3 6 0 670 0 649 Oil Diesel 0 80 4101 1250 Oil Lubricating X200 5019 9 1530 Cil Olive 0 91 4694 9 1431 2 75 100 000 91 200 Oil Peanut 0 94 4783 5 1458 Paraffin Oil 4655 7 1420 Pentane 0 626 3346 5 1020 0 363 0 227 Petroleum 0 876 4229 5 1290 1 Propanol 0 78 4009 2 1222 Refrigerant 11 1 49 2717 5 828 3 3 56 Refrigerant 12 1 52 2539 7 774 1 4 24 Refrigerant 14 1 75 2871 5 875 24 6 61 Refrigerant 21 1 43 29232 891 3 97 Refrigerant 22 1 49 2932 7 893 9 4 79 Refrigerant 113 1 56 2571 2 783 7 3 44 Refrigerant 114 1 46 2182 7 665 3 3 73 Refrigerant 115 2153 5 656 4 4 42 Refrigerant C318 1 62 1883 2 574 3 88 Silicone 30 cp 0 99 3248 990 30 000 29 790 Toluene 0 87 4357 1328 4 27 0 644 0 558 Transformer Oil 4557 4 1390 Trichlorethylene 3442 6 1050 1 1 1 Trichloroethane 1 33 3231 6 985 0 902 1 200 Turpentine 0 88 4117 5 1255 1 400 1 232 Water distilled 0 996 4914 7 1498 24 1 000 0 996 Water heavy 1 4593 1400 Water sea 1 025 5023 1531 2
24. 4 5047 0258 5047 0258 6 6625 6407 0109 6357 0134 6065 0280 6 065 0280 8 8 625 8407 0 109 8329 0 148 8125 0250 8071 0277 7981 0322 7981 0 322 10 1075 10482 0 134 1042 0 165 1025 0 250 10 13 0310 10 02 0 365 10 02 0 365 13 1275 1242 0 165 12 39 0 180 1225 0 250 12 09 0 330 12 00 0 375 11 938 0 406 14 14 00 13 50 0 250 1337 0315 1325 0375 1325 0375 13 124 0 438 16 16 00 15 50 0 250 1537 0 315 1525 0375 1525 0 375 15 000 0 500 18 18 00 17 50 0250 1737 0315 17 12 0440 1725 0 375 16 876 0 562 20 20 00 19 50 0250 1925 0375 1925 0375 1925 0 375 18814 0 593 24 2400 23 50 0 250 2325 0375 2325 0375 2325 0375 22 626 0 687 30 30 00 2937 0315 2900 0 500 2900 0 500 2925 0375 2925 0 375 36 36 00 3537 0315 35 00 0 500 3500 0 500 3525 0375 3525 0 375 42 42 00 4125 0 375 4125 0 375 48 48 00 v 4725 0375 4725 0375 Figure 18 Steel stainless steel PVC pipe standard classes continued Page 44 TTM UM 00369 EN 02 April 2015 North American Pipe Schedules Copper Tubing Copper and Brass Pipe Aluminum Nominal is Copper Nominal iii amp Brass Alum amp B
25. 4 1 000 1 025 Wood Alcohol 0 791 35302 1076 2 92 0 695 0 550 m Xylene 0 868 4406 2 1343 0 749 0 650 o Xylene 0 897 4368 4 1331 5 4 1 0 903 0 810 4376 8 1334 0 662 Figure 41 Fluid properties April 2015 TTM UM 00369 EN 02 Page 49 Brad Harrison Connector Option BRAD HARRISON CONNECTOR OPTION ds 5 3 gt 2 5 DGA87 LL Cable D005 0956 001 Straight Connector D005 0956 002 90 Connector Bulkhead Connector D005 0954 001 Figure 42 Brad Harrison connection Page 50 TTM UM 00369 EN 02 April 2015 Control Drawings CONTROL DRAWINGS 5 Warivsno 3NON S00 ESOL L60G 5 a onmo 325 355 YSINGSNVYL 51 SNIMVUG wani E VE od ABAWON uva KINO HO N3q 8 E9v6 XvOD 6 0 500 SVa 2 60 NIW 7 100 0101 0200 ON 31n00W 51 SIOH 00 0101 000 BOW S1S2INOSVNAG amedai NOI LSNI BLLIWSNVHL OLID3NNOO 2 05 012 0380 188343 LINISWY WWIXVW NOIIV2OTSTIOGBVZVF NON Laco ti 5
26. 50 10 Wall 0 338 0 250 0 212 0 094 ID 2 435 2 465 2 495 2 500 2 400 ID 9 449 9 625 9 701 9 812 OD 3 125 3 125 3 125 3 500 3 000 OD 12 125 12 125 12 125 3 Wall 0 109 0 090 0 072 0 219 0 050 12 in Wall 0 405 0 280 0 254 ID 2 907 2 945 2 981 3 062 2 900 ID 11 315 11 565 11 617 Table 8 Copper tubing copper and brass pipe aluminum April 2015 TTM UM 00369 EN 02 Page 45 North American Pipe Schedules Cast Iron Pipe Standard Classes 3 20 inch Class Size in in A B G H OD 3 80 3 96 3 96 3 96 3 Wall 0 39 0 42 0 45 0 48 ID 3 02 3 12 3 06 3 00 OD 4 80 5 00 5 00 5 00 4 Wall 0 42 0 45 0 48 0 52 ID 3 96 4 10 4 04 3 96 OD 6 90 7 10 7 10 7 10 7 22 7 22 7 38 7 38 6 Wall 0 44 0 48 0 51 0 55 0 58 0 61 0 65 0 69 ID 6 02 6 14 6 08 6 00 6 06 6 00 6 08 6 00 OD 9 05 9 05 9 30 9 30 9 42 9 42 9 60 9 60 8 Wall 0 46 0 51 0 56 0 60 0 66 0 66 0 75 0 80 ID 8 13 8 03 8 18 8 10 8 10 8 10 8 10 8 00 OD 11 10 11 10 11 40 11 40 11 60 11 60 11 84 11 84 10 Wail 0 50 0 57 0 62 0 68 0 74 0 80 0 86 0 92 ID 10 10 9 96 10 16 10 04 10 12 10 00 10 12 10 00 OD 13 20 13 20 13 50 13 50 13 78 13 78 14 08 14 08 12 Wall 0 54 0 62 0 68 0 75 0 82 0 89 0 97 1 04 ID 12 12 11 96 12 14 12 00 12 14 12 00 12 14 12 00
27. 7 96 47 98 48 00 OD 56 66 57 10 57 80 58 40 54 Wall 1 35 1 55 1 90 2 23 ID 53 96 54 00 54 00 53 94 OD 62 80 63 40 64 20 64 28 60 Wall 1 39 1 67 2 00 2 38 ID 60 02 60 06 60 20 60 06 OD 75 34 76 00 76 88 72 Wall 1 62 1 95 2 39 ID 72 10 72 10 72 10 OD 87 54 88 54 84 Wall 1 72 2 22 ID 84 10 84 10 Table 10 Cast iron pipe standard classes 24 84 inch April 2015 TTM UM 00369 EN 02 Page 47 Fluid Properties FLUID PROPERTIES Fluid Specific Gravity Sound Speed delta v C Kinematic Absolute 20 C ft s m s m s C Viscosity cSt Viscosity Cp Acetate Butyl 4163 9 1270 Acetate Ethyl 0 901 3559 7 1085 44 0 489 0 441 Acetate Methyl 0 934 3973 1 1211 0 407 0 380 Acetate Propyl 4196 7 1280 Acetone 0 79 3851 7 1174 4 5 0 399 0 316 Alcohol 0 79 3960 0 1207 4 0 1 396 1 101 Alcohol Butyl 0 83 4163 9 1270 33 3 239 2 688 Alcohol Ethyl 0 83 3868 9 1180 4 1 396 1 159 Alcohol Methyl 0 791 3672 1 1120 2 92 0 695 0 550 Alcohol Propyl 3836 1 1170 Alcohol Propyl 0 78 4009 2 1222 2 549 1 988 Ammonia 0 77 5672 6 1729 6 7 0 292 0 225 Aniline 1 02 5377 3 1639 4 0 3 630 3 710 Benzene 0 88 4284 8 1306 4 7 0 7 11 0 625 Benzol Ethyl 0 867 4389 8 1338 0 797 0 691 Bromine 2 93 2916 7 889 3 0 0 323 0 946 n Butane 0 6
28. 9 Transducer Installation DTTS DTTC Small Pipe Transducer Installation The small pipe transducers are designed for specific pipe outside diameters Do not attempt to mount a DTTS DTTC transducer onto a pipe that is either too large or too small for the transducer Instead contact the manufacturer to arrange for areplacement transducer that is the correct size 1 Apply a thin coating of acoustic coupling grease to both halves of the transducer housing where the housing will contact the pipe See Figure 14 2 On horizontal pipes mount the transducer in an orientation so the cable exits at 45 degrees from the side of the pipe Do not mount with the cable exiting on either the top or bottom of the pipe On vertical pipes the orientation does not matter 3 Tighten the wing nuts or U bolts so the acoustic coupling grease begins to flow out from the edges of the transducer or from the gap between the transducer halves IMPORTANT Do not overtighten Overtightening will not improve performance and may damage the transducer 4 If signal strength is less than five remount the transducer at another location on the piping system MW 1 16 in 1 5 mm Acoustic Couplant Grease Figure 14 Application of acoustic couplant DTTS DTTC transducers NOTE If aDTTS DTTC small pipe transducer was purchased separately from the transmitter the following configuration procedure is required Page 20 TTM UM 00369 EN 02 April 2015 Transduc
29. A being 0 gpm enter these values Flow at 4 mA 0 Hz 100 0 Flow at 20 mA 1000 Hz 100 0 This setting also sets the span for the frequency output At 100 gpm the output frequency is 0 Hz At the maximum flow of 100 gpm the output frequency is 1000 Hz and in this instance a flow of zero is represented by an output frequency of 500 Hz Example 2 To span the 4 20 mA output from 0 100 gpm with 12 mA being 50 gpm enter these values Flow at 4 mA 0 Hz 0 0 Flow at 20 mA 1000 Hz 100 0 In this instance zero flow is represented by 0 Hz and 4 mA The full scale flow or 100 gpm is 1000 Hz and 20 mA and a midrange flow of 50 gpm is 500 Hz and 12 mA Test Enables calibration adjustments Allows a simulated flow value to be sent from the 4 20 mA output By incrementing this value the 4 20 mA output will transmit the indicated current value Click Test to enable the Calibration and Test options Page 36 TTM UM 00369 EN 02 April 2015 Calibration Menu CALIBRATION MENU Calibration The Calibration menu contains a powerful multi point routine for calibrating the transmitter to a primary measuring standard in a particular installation To initialize the three step calibration routine click Calibration 1 Make sure flow is at zero 2 Wait for flow to stabilize 3 Press Set to calibrate the zero offset Current Delta T 0 84 Set 0 File Open File Save Figure 36 Calibra
30. ERTO TRANSMITTER S INSTALLATION MANUAL FOR TRANSDUCER LOCATION AND MOUNTING INSTRUCTIONS 2 WARNING TO PREVENT IGNITION OF FLAMMABLE ATMOSPHERES DISCONNECT POWER BEFORE SERVICING 3 WARNING SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY 4 NO REVISION TO DRAWING WITHOUT PRIOR CSA INTERNATIONAL APPROVAL 5 ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT 6 INSTALLATION IN CANADA SHOULD BE IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE CSA C22 1 PART 1 APPENDIX 7 INSTALLATION SHALL BE IN ACCORDANCE WITH THE amp THE MAXIMUM NON HAZARDOUS LOCATION VOLTAGE IS 250V AC DC TEE FITTING 0002 1201 002 FLEXIBLE ARMORED CONDUIT SUITABLE FOR INCIDENTAL AND TEMPORARY SUBMERSION D002 1401 003 SENSING SURFACE COUPLE TO EMEN REVISIONS DETON Tumo Paa Baoen saes a sasoe NON HAZARDQUS LOCATION MAXIMUM AMBIENTTEMPERATURE 40 C TO 50 C CONNECTTO TRANSMITTER PER RED BLUE 10 MAX INSTALLATION MANUAL BLACK CLEAR RED BLUE DYNASONICS LS BARRIER MODEL D070 1010 002 PIPEWITHRTV OR SILICONE TUN GREASE SUPPLIED PER INSTALLATION MODEL NS DT OE ART MANUAL TFXD O amp M 990 MAX 3 60 MTG HOLES MTG HOLES 15 MODULE PART 0070 1010 001 02 METERS RG 59 U COAX BELDEN 9463 BELDEN 9463DB OR EQUAL ONLY SEALOF
31. ETRIC IMPORTANT If the UNITS entry has been changed from ENGLISH to METRIC or from METRIC to ENGLISH the entry must be saved and the instrument reset power cycled in order for the transmitter to initiate the change in operating units Failure to save and reset the instrument will lead to improper transducer spacing calculations and an instrument that may not measure properly Measurement standard Millimeters General Standard Configuration When using the Standard Configurations drop down menu alternate menu choices can be made by using the following guidelines 1 Select the transducer type and pipe size for the transducer to be used The firmware will automatically enter the appropriate values for that pipe size and type Every entry parameter except for Units Standard Configurations and Pre programmed e Specific Heat Capacity are unavailable grayed out pipe Menu selection configurations 2 From the Standard Configurations drop down menu select Custom The previously unavailable selections are now available for editing Make any necessary changes to the basic configuration and click Download 4 Cycle the transmitter power off and then back on again for the changes to take effect Page 30 TTM UM 00369 EN 02 April 2015 Configuration Menu Category Parameter Meaning Option Description Transducer Type Transducer type Menu selection Selects the
32. F CONDUIT PER INSTALLATION NOTES 6 amp 7 3 MIN 0 93 METERS PLACES 3 8ADITO 005010 PFNSHTOM GR REMOVE ALL BURRS AND BREAK SHARP EDGES 005 010 NOTES UNLESS OTHERWISE SPECIFIED PART NUMBER ACNE WSCONGIL USA Lor FAL 2020199857 CONTROL DRAWING 1 5 BARRIER amp DTT TRANSDUCER MATS D091 1053 005 SEEABOVE TODO PART NUMBER 59380 D091 1053 005 IS barrier DTT transducers flexible conduit Figure 44 Control drawing April 2015 TTM UM 00369 EN 02 Page 52 SPECIFICATIONS System Specifications Liquid Types Most clean liquids or liquids containing small amounts of suspended solids or gas bubbles Velocity Range 0 1 40 FPS 0 03 012 MPS Flow Accuracy DTTR DTTN DTTH DTTS DTTC 1 of reading at rates gt 1 FPS 0 3 MPS 0 01 FPS 0 003 MPS at rates lower than 1 FPS 1 in 25 mm and larger 1 of reading from 10 100 of measuring range 0 01 FPS 0 003 MPS at rates lower than 10 of measuring range 3 4 in 19 mm and smaller 1 full scale Ambient Temperature General purpose Hazardous locations integral mount Hazardous locations DTTN 40 185 F 40 85 0 105 F 17 40 C 40 185 F 40 85 Repeatability 0 5 of reading Transducer Type Clamp on uses time of flight ultrasonics Protection Reverse polarity surge suppression Certif
33. RES aoa awa AD E GUEST A E CP Rd 55 Page iv TTM UM 00369 EN 02 April 2015 Scope of This Manual SCOPE OF THIS MANUAL This manual is divided into two main sections Quick Start Operating Overview on 6 is intended to help you get the TFXL Meter up and running quickly Refer to the detailed instructions if you require additional information The remaining chapters provide a detailed description of all software settings and hardware installation guidance Read this manual carefully before attempting any installation or operation Keep the manual accessible for future reference UNPACKING AND INSPECTION Upon opening the shipping container visually inspect the product and applicable accessories for any physical damage such as scratches loose or broken parts or any other sign of damage that may have occurred during shipment NOTE If damage is found request an inspection by the carrier s agent within 48 hours of delivery and file a claim with the carrier A claim for equipment damage in transit is the sole responsibility of the purchaser SAFETY Terminology and Symbols Indicates a hazard ituation which if not avoided is estimated to b ble of ing death i A DANGER ous situation Which if not avoided is estimated to be capable of causing death or serious Indicates a hazardous situation which if not avoided could result in severe personal injury or death Indicates a hazardous situation which if not
34. TABLE FOR THE LOCATION DONOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO BENONHAZARDOUS DONOT CONNECT THE INTERFACE CABLE BETWEEN A TFXL Meter AND A PERSONAL COMPUTER UNLESS THE AREA IS KNOWN TO BE NONHAZARDOUS April 2015 TTM UM 00369 EN 02 11 Transducer Connections TRANSDUCER CONNECTIONS TRANSDUCER CONNECTIONS UPSTREAM BLUE UPSTREAM WHITE DOWNSTREAM WHITE DOWNSTREAM BLUE FIELD WIRING TERMINALS Figure 7 Transducer connections To access terminal strips for wiring first loosen the four screws holding the top of the case to the bottom NOTE The four screws captive screws and cannot be removed from the top of the case If the unit has a display remove the four Phillips head screws that hold the display to the main circuit board and carefully move it out of the way Do not over stress the ribbon cable located between the display and the microprocessor circuit boards Guide the transducer terminations through the transmitter conduit hole located in the bottom left of the enclosure Secure the transducer cable with the supplied conduit nut if flexible conduit was ordered with the transducer NOTE TFXL Meters with integral transducers have the transducers connected at the factory and the transducer connections section can be skipped The terminals within TFXL Meter are of a screw down barrier terminal type Depending on the type of transducers being us
35. To calculate where to set the substitute flow value in a bidirectional system perform the following calculation 100 x Maximum Flow Maximum Flow Minimum Flow Substitute Flow 100 Some typical settings to achieve zero with respect to MIN RATE and MAX RATE settings are listed below NOTE The UltraLink software utility is required to set values outside of 0 0 100 0 Page 34 TTM UM 00369 EN 02 April 2015 Filtering Tab The Filtering tab contains several filter settings for the transmitter These filters can be adjusted to match response times and data smoothing performance to a particular application Configuration Menu System Configuration Basic Fow Advanced Fitter Settings Time Domain Fiter Fitering Output Security Display NN kk Flow Fiter Damping 80 x Fow Fiter Hysteresis Flow Filter MinHysteresis 303 3 Flow Filter Sensitivity 3 Bad Data Rejection 3 Factory Defaults File Open Save Download Cancel Figure 34 Filtering tab Parameter Meaning Option Description Time Domain Filter Number of raw data sets averaged together 1 256 Time Domain Filter range 1 256 adjusts the number of raw data sets the wave forms viewed on the software Diagnostics Screen that are averaged together Increasing this value will provide greater damping of the data and slow
36. ances that may be in effect Consult the local electrical inspector for information regarding wiring regulations When making connections to the field wiring terminals inside the flow meter strip backthe wire insulation approximately 0 25 inch 6 mm Stripping back too little may cause the terminals to clamp on the insulation and not make good contact Stripping back too much insulation may lead to a situation where the wires could short together between adjacent terminals Wires should be secured in the field wiring terminals using a screw torque of 0 5 0 6 Nm If using the DC ground terminal as a protective conductor terminal apply the protective conductor first and secure it independently of other connections Connect the protective conductor so it is unlikely to be removed by servicing that does not involve the protective conductor or post a warning requiring the replacement of the protective conductor after removal Power the TFXL Meter flow meter with a Class 2 direct current DC power source The power source should be capable of supplying 12 28V DC at a minimum of 250 milliamps With the power from the DC power source disabled or disconnected connect the positive supply wire and ground to the field wiring terminals in the flow meter See Figure 8 on page 13 A wiring diagram is on the inside cover of the meter enclosure IMPORTANT e FOLLOW INSTRUCTIONS TO PROVIDE SAFETY OF EQUIPMENT AND OR PERSONNEL e MUST BE OPERATED BY A POWER SUPPLY SUI
37. and signal strength Z Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once Z Mount will yield the best signal strength but the smallest relative travel time Transducer Mounting Configuration Pipe Material Pipe Size Liquid Composition Plastic all types Carbon Steel Stainless Steel 2 4 in 50 100 mm W Mount Copper Ductile Iron Not recommended Cast Iron Plastic all types Carbon Steel 4 12 in 100 300 mm Stainless Steel Low TSS Total Suspended VMount Copper 4 30 in 100 750 mm Solids non aerated Ductile Iron Cast Iron 2 12 in 50 300 mm Plastic all types gt 30 in gt 750 mm Carbon Steel Stainless Steel Copper gt 30 in gt 750 mm Ductile Iron Cast Iron Table 2 Transducer mounting modes for and DTTH gt 121 gt 300 mm Z Mount gt 12 in gt 300 mm The transducers can be mounted in V Mount where the sound transverses the pipe two times W Mount where the sound transverses the pipe four times or in Z Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once The selection of mounting method is based on pipe and liquid characteristics which both have an effect on how much signal is generated The transmitter operates by alternately transmitting and receiving a frequency
38. another measurement cycle Flow Filter The current value of the adaptive filter SS Min Max The minimum and maximum signal strength levels encountered by the transmitter beginning at the time the power to the transmitter was last turned off and then on again Signal Strength State indicates if the present signal strength minimum and maximum are within a pre programmed signal strength window Sound Speed The actual sound speed being measured by the transducers at that moment Reynolds is a number indicating how turbulent a fluid is Reynolds numbers between 0 and 2000 are considered laminar flow Numbers between 2000 4000 are in transition between laminar and turbulent flows and numbers greater than 4000 indicate turbulent flow Reynolds Factor The value applied to the flow calculation to correct for variations in Reynolds numbers Target Data x Device Type TFXL Calc Count 54247 1 22 5 2 Delta T ns 1073 4 Gain 430 5 66 8 6 Tx Delay 43 7 Flow Filter 3 8 SS Min Max 8 01924 10 Sound Speed 4900 11 Reynolds 20 15 12 07500 13 Serial No TFXD Reset Target Dbg data screen Figure 40 Saving the Configuration on a PC The complete configuration of the transmitter can be saved from the Configuration screen Select File Save button located in the lower left hand corner of the screen and name the file Files are saved
39. as a dcf extension This file may be transferred to other transmitters or may be recalled should the same pipe be surveyed again or multiple transmitters programmed with the same information Printing a Configuration Report Select File Print to print a calibration configuration information sheet for the installation April 2015 TTM UM 00369 EN 02 Page 39 Calibration Menu UltraLink Error Codes Revised 04 06 2015 Code Description Correction 0001 Serial number not present Hardware serial number has become inoperative System performance will not be influenced Low signal strength is typically caused by one of the following Empty pipe Warnings 519181 Strength is below Signal Strength Cutoff Improper programming incorrect values entry Improper transducer spacing Non homogeneous pipe wall Removing the resistors from the transducer terminal block can boost the signal Measured speed of sound in the liquid is greater Verify that the correct liquid was selected in the BASIC menu 0011 than 10 of the value entered during transmitter setup Verify that pipe size parameters are correct Initiate a transmitter RESET by cycling power or by selecting Pisas 1001 System tables have changed SYSTEM RESET in the SEC MENU Errors x Initiate a transmitter RESET by cycling power or by selecting 1002 System configuration has changed SYSTEM RESET in the SEC MENU
40. bration Errors Print Print Previe Device Figure 16 Calibration page 3 of 3 Time 60 Min Scale 200 Edit Calibration Points x Model DTTSJP 050 NO00 N S N 39647 Delta T 391 53nS Uncal Flow 81 682 GPM CESSIT Delta T 391 53 ns Cal Flow 80 GPM Uncalibrated Flow 81 682 Gal Min Calibrated Flow 80 000 Gal Min Cancel Flow 1350 Gal Min Totalizer Net 0 OB Pos Sig Strength 15 6 Margin 10096 Delta T 2 50 ns Last Update 09 53 39 Figure 17 Data display screen Figure 18 Edit calibration points April 2015 TTM UM 00369 EN 02 Page 21 Transducer Installation Z Mount Configuration Installation on larger pipes requires careful measurements of the linear and radial placement of the DTTR DTTN and DTTH transducers Failure to properly orient and place the transducers on the pipe may lead to weak signal strength and or inaccurate readings This section details a method for properly locating the transducers on larger pipes This method requires aroll of paper such as freezer paper or wrapping paper masking tape and a marking device 1 2 Wrap the paper around the pipe in the manner shown in Figure 19 Align the paper ends to within 1 4 inch 6 mm Mark the intersection of the two ends of the paper to indicate the circumference Remove the template and spread it out on a flat surface Fold the template in half bisecting the circumference See Figure 20 Creas
41. ce of the transducer See Figure 12 Generally a silicone based grease is used as an acoustic couplant but any good quality grease like substance that is rated to not flow at the operating temperature of the pipe is acceptable Place the upstream transducer in position and secure with a stainless steel strap or other fastening device Straps should be placed in the arched groove on the end of the transducer A screw is provided to help hold the transducer onto the strap Verify that the transducer is true to the pipe adjust as necessary Tighten transducer strap securely Larger pipes may require more than one strap to reach the circumference of the pipe Figure 21 Z Mount transducer placement Page 22 TTM UM 00369 EN 02 April 2015 Transducer Installation 7 Place the downstream transducer on the pipe at the calculated transducer spacing See Figure 21 Using firm hand pressure slowly move the transducer both towards and away from the upstream transducer while observing signal strength Clamp the transducer at the position where the highest signal strength is observed A signal strength between 5 98 is acceptable The factory default signal strength setting is five However there are many application specific conditions that may prevent the signal strength from attaining this level A minimum signal strength of five is acceptable as long as this signal level is maintained under all flow conditions On certain pipes a slight twist t
42. e pipe 2 Slide the two transducer clamp brackets toward the center mark on the mounting rail 3 Place a single bead of couplant approximately 1 2 inch 12 mm thick on the flat face of the transducer See Figure 12 on page 19 4 Placethe first transducer in between the mounting rails near the zero point on the scale Slide the clamp over the transducer Adjust the clamp and transducer so the notch in the clamp aligns with the zero on the scale See Figure 23 April 2015 TTM UM 00369 EN 02 Page 23 Transducer Installation 5 Secure with the thumb screw Check that the screw rests in the counter bore on the top of the transducer Excessive pressure is not required Apply just enough pressure so that the couplant fills the gap between the pipe and transducer 6 Place the second transducer in between the mounting rails near the dimension derived in the transducer spacing section Read the dimension on the mounting rail scale Slide the transducer clamp over the transducer and secure with the thumb screw Top View of Pipe Figure 23 Mounting track installation Page 24 TTM UM 00369 EN 02 April 2015 Inputs Outputs INPUTS OUTPUTS The TFXL Meter is available in two general configurations The standard TFXL Meter is equipped with a 4 20 mA output and a rate frequency output The Meter is also available with a totalizing pulse output option Standard 4 20 mA Output The 4 20 mA output interfaces
43. e the paper at the fold line Mark the crease Place a mark on the pipe where one of the transducers will be located See Figure 10 for acceptable radial orientations Wrap the template back around the pipe placing the beginning of the paper and one corner in the location of the mark Move to the other side of the pipe and mark the pipe at the ends of the crease Measure from the end of the crease directly across the pipe from the first transducer location the dimension derived in Select a Mounting Configuration on page 16 Mark this location on the pipe The two marks on the pipe are now properly aligned and measured If access to the bottom of the pipe prohibits the wrapping of the paper around the circumference cut a piece of paper 1 2 the circumference of the pipe and lay it over the top of the pipe The equation for the length of 1 2 the circumference is 1 2 Circumference Pipe O D x 1 57 The transducer spacing is the same as found in Position and Secure the Transducer on page 19 Mark opposite corners of the paper on the pipe Apply transducers to these two marks 5 For DTTR DTTN and DTTH transducers place a single bead of couplant Zo Edge of Paper Line Marking Circumference Fold Pipe Circumference Transducer Spacing 1 gt lt LESS THAN 6 mm iine ipd Figure 19 Paper template alignment Figure 20 Bisecting the pipe circumference approximately 1 2 inch 12 mm thick on the flat fa
44. ed there are two terminal strip arrangements possible Remote mount small pipe transducers are connected to the terminals on the main circuit board Remote mount transducers are connected to a daughter board on the left side of the meter Connect the appropriate wires at the corresponding screw terminals in the transmitter Observe upstream and downstream orientation and wire polarity See Figure 7 NOTE High temperature transducer cables come with red and black wire colors For the red and black combination the red wire is positive and the black wire is negative NOTE The transducer cable carries low level high frequency signals In general it is not recommended to add additional length to the cable supplied with the transducers If additional cable is required contact the factory to arrange an exchange for a transducer with the appropriate length of cable Cables 100 990 feet 30 300 meters are available with RG59 75 Ohm coaxial cable Page 12 TTM UM 00369 EN 02 April 2015 DC Power Connections DC POWER CONNECTIONS The TFXL Meter should be operated from an 12 28V DC Class 2 power source capable of supplying a minimum of 250 mA of current 1 Feed the power source through the conduit hole on the right side of the enclosure Connect power to the screw terminal block in the TFXL Meter Use wiring practices that conform to local and national codes 2 Connect the DC power to 12 28V DC In and DC Gnd as in Figure 8
45. ed above the transmitter will calculate proper transducer spacing for the particular data set The distance will be in inches if the transmitter is configured in English units or millimeters if configured in metric units Mount the Transducer After selecting an optimal mounting location and determining the proper transducer spacing mount the transducers onto the pipe 1 Clean the surface of the pipe If the pipe has external corrosion or dirt wire brush sand or grind the mounting location until it is smooth and clean Paint and other coatings if not flaked or bubbled need not be removed Plastic pipes typically do not require surface preparation other than soap and water cleaning 2 Orient and space the DTTR DTTN and DTTH transducers on the pipe to provide optimum reliability and performance On horizontal pipes when Z Mount is required mount the transducers 180 radial degrees from one another and at least 45 degrees from the top dead center and bottom dead center of the pipe See Figure 10 on page 17 On vertical pipes the orientation is not critical The spacing between the transducers is measured between the two spacing marks on the sides of the transducers These marks are approximately 0 75 inches 19 mm back from the nose of the DTTR DTTN and DTTH transducers See Figure 11 Mount DTTS and DTTC transducers with the cable exiting within 45 degrees of the side of a horizontal pipe On vertical pipes the orientation does not appl
46. ement units totalized If the totalizer exponent E is set to E0 x1 and the totalizer multiplier TOT MULT is set to 2 the control output will pulse once for every two counts that the totalizer increments April 2015 TTM UM 00369 EN 02 Page 25 Inputs Outputs Totalizer Output Option TFXL Meters can be ordered with a totalizer pulse output option This option is installed in the position where the rate pulse would normally be installed Totalizing Pulse Specifications Parameter Specification Signal One pulse for each increment of the totalizer s least significant digit Operation Normal state is high pulses low with display total increments Pulse Duration 30 mSec minute Source Sink 2 mA maximum Logic 5V DC Table 5 Optional totalizing pulse output Wiring and configuration of this option is similar to the totalizing pulse output for the TFXL Meter variation This option must use an external current limiting resistor o TTL Pluse TTL Pluse 1 TTL Pluse TTL Pluse s Figure 26 Totalizer output option Frequency Output The frequency output is a TTL circuit that outputs a pulse waveform that varies proportionally with flow rate This type of frequency output is also known as a Rate Pulse output The output spans from 0 Hz normally at zero flow rate to 1000 Hz at full flow rate see Flow Tab on page 34 Turbine Output
47. empted the following error message displays UitraLINI um Value can not be 0 This value was already set in a previous screen 1 of 3 Figure 39 Zero value error Page 38 TTM UM 00369 EN 02 April 2015 Calibration Menu Target Dbg Data Screen Definitions Field Description Device Type The flow meter type Calc Count The number of flow calculations performed by the transmitter beginning at the time the power to the transmitter was last turned off and then on again Sample Count The number of samples currently being taken in one second Raw Delta T ns The actual amount of time it takes for an ultrasonic pulse to cross the pipe Course Delta T The transmitter series that uses two wave forms The coarse to find the best delay and other timing measurements and a fine to do the flow measurement Gain The amount of signal amplification applied to the reflected ultrasound pulse to make it readable by the digital signal processor Gain Setting Waveform Power The first number The gain setting on the digital pot automatically controlled by the AGC circuit Valid numbers are from 1 100 The second number The power factor of the current waveform being used For example 8 indicates that a 1 8 power wave form is being used Tx Delay The amount of time the transmitting transducer waits for the receiving transducer to recognize an ultrasound signal before the transmitter initiates
48. en a FLUID ABSOLUTE VISCOSITY must also be entered See Fluid Properties on page 48 for a list of alternate fluids and their associated viscosities Specific Heat Capacity Fluid specific heat capacity BTU Ib Allows adjustments to be made to the specific heat capacity of the liquid If a fluid was chosen from the FLUID TYPE list a default specific heat will be automatically loaded This default value is displayed as SPECIFIC HEAT If the actual specific heat of the liquid is known or it differs from the default value the value can be revised See Table 5 Table 6 and Table 7 for specific values Enter a value that is the mean of both pipes April 2015 TTM UM 00369 EN 02 Page 33 Configuration Menu Flow Tab Basic Flow Riteing Output Security Display Fow Rate Uns SEE Tetalizer Units Gallons hd Low Flow Cutoff Min Flow 400 0 Gal M Low Signal Cutoff Max Flow 400 0 Substitute Flow Open Save Cancel Figure 33 Flow tab Parameter Meaning Option Description Flow Rate Engineering units Select an appropriate rate unit and time from the two lists This entry also includes the selection Menu selection Units for flow rate of Flow Rate Interval after the virgule sign Totalizer Units Engineering units for totalizer Menu selection Select an appropriate totalizer unit and totalizer exponent The totaliz
49. er Installation DTTS DTTC Small Pipe Transducer Calibration Procedure 1 Establish communications with the transit time transmitter 2 From the tool bar select Calibration See Figure 17 3 Onthe pop up screen click Next twice to get to Page 3 of 3 See Figure 15 4 Click Edit 5 Ifa calibration point is displayed in Calibration Points Editor record the information then highlight and click Remove Calibration 3 of 3 Linearization xi 1 Please establish reference flow rate 1FPS 0 3MPS Minimum 2 Enter the reference flow rate below Do not enter 0 3 Wait for flow to stabilize 4 Press the Set button See Figure 16 E __ 6 Click ADD 7 Enter Delta T Un calibrated Flow and Calibrated Flow values from the DTTS DTTC calibration label then click OK cc See Figure 18 File Open File Save lt Back Cancel 8 Click OK in the Edit Calibration Points screen 9 The display will return to Page 3 of 3 Click Finish See Figure 15 10 After Writing Configuration File is complete turn off the Figure 15 Calibration points editor power Turn on the power again to activate the new Calibration Points Editor xj setti n g s Select point s to edit or remove Add Edit Remove Select All vitraLINK Device Addr 127 File Edit View Communications Window Help Eel Cancel SNC A Configuration Strategy Cali
50. er exponents are in scientific notation and permit the eight digit totalizer to accumulate very large values before the totalizer rolls over and starts again at zero Min Flow Minimum volumetric flow rate Enter a numeric value Enter the minimum volumetric flow rate setting to establish filtering parameters Volumetric entries are in the flow rate units For unidirectional measurements set Min Flow to zero For bidirectional measurements set Min Flow to the highest negative reverse flow rate expected in the piping system Max Flow Maximum volumetric flow rate Enter a numeric value Enter the maximum volumetric flow rate setting to establish filtering parameters Volumetric entries are in the flow rate units For unidirectional measurements set Max Flow to the highest positive flow rate expected in the piping system For bidirectional measurements set Max Flow to the highest positive flow rate expected in the piping system Low Flow Cutoff Flow cutoff value Enter a numeric value Allows very low flow rates that can be present when pumps are off and valves are closed to be displayed as zero flow Enter values between 1 0 5 096 of the flow range between Min Flow and Max Flow Low Signal Cutoff Low signal cutoff value Enter a numeric value Drives the transmitter and its outputs to the value specified in the Substitute Flow field when conditions occur that cause low signal streng
51. er mounting configurations FLOW METER FLOW METER MOUNTING ORIENTATION MOUNTING ORIENTATION DTTS and DTTC TRANSDUCERS 2 DTTS and DTTC TRANSDUCERS FLOW METER MOUNTING ORIENTATION DTTR DTTN and DTTH TRANSDUCERS Figure 5 Transducer mounting orientations DTTS and DTTC Transducers 1 Place the transmitter in signal strength measuring mode This value is available on the transmitter s display Service Menu or in the data display of the UltraLink software utility The pipe surface where the transducers are to be mounted must be clean and dry Remove scale rust or loose paint to provide satisfactory acoustic conduction Wire brushing the rough surfaces of pipes to smooth bare metal may also be useful Plastic pipes do not require preparation other than cleaning On horizontal pipe choose a mounting location within approximately 45 degrees of the side of the pipe See Figure 5 on page 8 Locate the flow meter so that the pipe will be completely full of liquid when flow is occurring in the pipe Avoid mounting on vertical pipes where the flow is moving in a downward direction Apply a single 1 2 inch 12 mm bead of acoustic couplant grease to the top half of the transducer and secure it to the pipe with the bottom half or with U bolts Tighten the nuts so the acoustic coupling grease begins to flow out from the edges of the transducer and from the gap between the transducer and the pipe IMPORTANT Do not
52. er transducer spacing based on these entries 4 Prepare the pipe and mount the transducers Mounting Location Select a Mounting Location The first step in the installation process is the selection of an optimum location for the flow measurement to be made For this to be done effectively a basic knowledge of the piping system and its plumbing are required An optimum location is defined as A piping system that is completely full of liquid when measurements are being taken If the pipe may become completely empty during a process cycle an error code 0010 Low Signal Strength will be displayed on the transmitter while the pipe is empty This error code will clear automatically once the pipe refills with liquid Do not mount the transducers in an area where the pipe may become partially filled such as the highest point in a flow loop Partially filled pipes will cause erroneous and unpredictable operation of the transmitter A piping system that contains lengths of straight pipe such as those described in Table 1 on page 15 The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation The straight runs in Table 1 apply to liquid velocities that are nominally 7 fps 2 2 mps As liquid velocity increases above this nominal rate the requirement for straight pipe increases proportionally An area where the transducers will not be inadvertently bumped or disturbed during normal operation NOT
53. etains all user entered configuration values in memory indefinitely even if power is lost or turned off Product Identification The serial number and complete model number of the transmitter are located on the top outside surface of the transmitter body Should technical assistance be required please provide our customer service department with this information April 2015 TTM UM 00369 EN 02 Page 9 Transmitter Installation TRANSMITTER INSTALLATION Transmitter Location Mount the enclosure in an area that is convenient for servicing calibration and observation of the LCD readout if equipped 1 Locate the transmitter within the length of transducer cables supplied If this is not possible exchange the cable for one that is of proper length 2 Mount the TFXL Meter transmitter in a location Where little vibration exists That is protected from corrosive fluids That is within the transmitters ambient temperature limits 40 185 F 40 85 C That is out of direct sunlight Direct sunlight may increase transmitter temperature to above the maximum limit 3 See Figure 6 for enclosure and mounting dimension details Allow enough room for door swing maintenance and conduit entrances 4 Secure the enclosure to a flat surface with two fasteners 5 Feed the cables through the conduit holes in the enclosure Use plugs to seal any unused holes NOTE Use NEMA 4 IP 65 rated fittings plugs to maintain the watertight i
54. f sound in that media will be automatically loaded If the actual sound speed rate is known for the pipe liner and that value varies from the automatically loaded value the value can be revised Thickness Pipe liner Inches If the pipe has a liner enter the pipe liner thickness Enter this value in inches if Liner thickness ENGLISH was selected as UNITS in millimeters if METRIC was selected Millimeters The transmitter provides flow profile compensation in its flow measurement calculation The ratio of average surface imperfection as it relates to the pipe internal diameter is used in this compensation and is found by using the following formula Uher material Enter a numeric iiher R Linear RMS Measurement of the Liners Internal Wall Surface Roughness relative roughness value Inside Diameter of the Liner 9 If a liner material was chosen from the LINER MATERIAL list nominal value for relative roughness in that material will be automatically loaded If the actual roughness is known for the application liner and that value varies from the automatically loaded value the value can be revised See Liner material relative roughness on page 38 for pipe liner relative roughness calculations Page 32 TTM UM 00369 EN 02 April 2015 Configuration Menu Category Parameter Meaning Option Description Fluid Type Fluid media type Select a fluid type selected from a pull down list If the liquid is not found in t
55. gnal strength measuring mode This value is available on the data display of the UltraLink software utility ey Downstream The pipe surface where the transducers are to be mounted Downstream must be clean and dry Remove scale rust or loose paint to Upstream ensure satisfactory acoustic conduction Wire brushing the rough surfaces of pipes to smooth bare metal may also be useful Plastic pipes do not require preparation other than cleaning On horizontal pipe choose a mounting location within approximately 45 degrees of the side of the pipe See Figure 5 on page 8 Locate the flow meter so that the pipe will be completely full of liquid when flow is occurring in the pipe Avoid mounting on vertical pipes where the flow is moving in a downward direction Apply a single 1 2 inch 12 mm bead of acoustic couplant grease to the upstream transducer and secure it to the pipe with a mounting strap Apply acoustic couplant grease to the downstream transducer and press it onto the pipe using hand pressure at the lineal distance calculated in Transducer Location on page 6 Upstream Figure 3 Transducer connections Quick Start Operating Overview 5 Space the transducers according to the recommended values from the UltraLink software utility Secure the transducers with the mounting straps at these locations TOP VIEW TOP VIEW VIEW OF PIPE 2 OF OF PIPE W Mount V Mount Figure 4 Transduc
56. he list select Other and enter the liquid Sound Speed and Absolute Viscosity into the appropriate boxes The liquid s specific gravity is required if mass measurements are to be made and the specific heat capacity is required for energy measurements Sound Speed Speed of sound in the fluid ENGLISH fps METRIC mps Allows adjustments to be made to the speed of sound entry for the liquid If the UNITS value was set to ENGLISH the entry is in fps feet per second METRIC entries are made in mps meters per second If a fluid was chosen from the FLUID TYPE list a nominal value for speed of sound in that media will be automatically loaded If the actual sound speed is known for the application fluid and that value varies from the automatically loaded value the value can be revised If OTHER was chosen as FLUID TYPE a FLUID SOUND SPEED will need to be entered A list of alternate fluids and their associated sound speeds is located in the Appendix located at the back of this manual Fluid sound speed may also be found using the Target DBg Data screen available in the UltraLink software utility See Target Dbg Data Screen Definitions on page 39 Specific Gravity Fluid specific gravity Enter a numeric value Allows adjustments to be made to the specific gravity density relative to water of the liquid As stated previously in the FLUID ABSOLUTE VISCOSITY section specific gravity is used in the Reynolds correctio
57. ications Remote mount transmitter and integral mount transmitter with transducers General purpose standards UL 61010 1 and CSA C22 2 No 61010 1 Hazardous location designation and standards Class Division 2 Groups C and D UL1604 CSA C22 2 No 213 Hazardous location transducers DTTN with 1 5 option Hazardous location designation and standards Class Division 1 Groups C and D T5 UL913 2002 UL916 CAN CSA C22 2 No 0 10 C22 2 No 142 M1987 C22 2 No 157 92 Install with I S barrier D070 1010 002 Transmitter Power 12 28V DC 0 25A Requirements UO i Type 2 line x 8 character LCD Display Rate 8 maximum digits with lead zero blanking Total 8 maximum digits with exponential multipliers from 1 6 NEMA Type 3 Type 3 ABS PVC and Ultem integral system brass or SS hardware Units of Engineering units Feet US gallons cubic feet million gallons barrels liquid and oil acre feet meters cubic meters liters million liters kilograms Rate Second minute hour day 4 20 mA 900 ohms max internally powered 12 bit resolution Analog and TTL Selectable turbine meter simulation or square wave Frequency 0 1000 Hz duty cycle 5096 1096 Outputs Output option 1 Square wave 5V DC Turbine meter simulation 500 mVpp minimum Totalizer pulse Source or sink 5V DC 2 mA maximum pulse duration 30 ms external resistor Output option 3 Normal
58. ion Versatility The TFXL Meter can be successfully applied on a wide range of metering applications The simple to program transmitter allows the standard product to be used on pipe sizes ranging from 1 2 100 inches 12 2540 mm A variety of liquid applications can be accommodated ultrapure liquids cooling water potable water river water chemicals plant effluent sewage reclaimed water others Because the transducers are non contacting and have no moving parts the transmitter is not affected by system pressure fouling or wear Temperature Ratings for Transducers Because the transducers are non contacting and have no moving parts the flow meter is not affected by system pressure fouling or wear Temperature ratings for each transducer are listed below Transducer Temperature Rating DTTR 40 250 F 40 1217 DTTC 40 194 F 40 90 C DTTN 40 194 F 40 90 C DTTH 40 350 F 40 177 DTTS 40 140 F 40 60 C User Safety The TFXL Meter uses a low voltage DC power source that provides electrical safety for the user Remove the cover to access to the meter connections and the computer interface connection THE POWER SUPPLY BOARD CAN HAVE LINE VOLTAGES APPLIED TOIT SO DISCONNECT ELECTRICAL POWER BEFORE OPENING THE INSTRUMENT ENCLOSURE WIRING SHOULD ALWAYS CONFORM TO LOCAL CODES AND THE NATIONAL ELECTRICAL CODE Data Integrity Non volatile flash memory r
59. lect a mounting location on the piping system with a minimum of ten pipe diameters 10 x the pipe inside diameter of straight pipe upstream and five straight diameters downstream See Table 1 on page 15 for additional configurations If the application requires DTTR DTTN or DTTH transducers select a mounting method for the transducers based on pipe size and liquid characteristics See Table 2 on page 16 The three transducer mounting configurations are shown in Figure 4 See Transducer Mounting Configurations on page 19 for mounting procedures NOTE AII DTTS and DTTC transducers use V Mount configuration Power Connections Power for the TFXL Meter flow meter is obtained from a direct current DC power source 1 2 Verify that the power source is capable of supplying 12 28V DC at a minimum of 250 milliamps With the power from the DC power source disabled or disconnected connect the positive supply wire and ground to the appropriate field wiring terminals in the flow meter See Figure 1 A wiring diagram decal is on the inside cover of the flow meter enclosure DC Ground 12 28V DC Figure 1 Power connections Transducer Connections for Remote Mount Transducers 1 2 Guide the transducer terminations through the transmitter conduit hole on the bottom left of the enclosure using a sealed cord grip or NEMA 4 conduit connection Secure the transducer cable with the supplied conduit nut if flexible
60. lter the transducer spacing An effective way to maximize signal strength is to configure the display to show signal strength fix one transducer on the pipe and then starting at the calculated spacing move the remaining transducer small distances forward and back to find the maximum signal strength point IMPORTANT Enter all of the data on this list save the data and reset the transmitter before mounting the transducers The following information is required before programming the instrument Transducer mounting configuration Pipe liner thickness if present Pipe outside diameter Pipe liner material if present Pipe wall thickness Fluid type Pipe material Fluid sound speed Pipe sound speed Fluid viscosity Pipe relative roughness Fluid specific gravity Table 4 Parameters required Nominal values for these parameters are included within the transmitter s operating system The nominal values may be used as they appear or may be modified if exact system values are known NOTE Much ofthe data relating to material sound speed viscosity and specific gravity is pre programmed into the transmitter You need to modify this data only if you know that a particular application s data varies from the reference values See Parameter Configuration Using UltraLink Software on page 28 for instructions on entering configuration data into the transmitter via the software utility After entering the data list
61. modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers The difference in the time interval measured is directly related to the velocity of the liquid in the pipe The appropriate mounting configuration is based on pipe and liquid characteristics Selecting the proper transducer mounting method is an iterative process Table 2 contains recommended mounting configurations for common applications These recommended configurations may need to be modified for specific applications if such things as aeration suspended solids out of round piping or poor piping conditions are present TOP VIEW E TOP VIEW E OF PIPE El OF PIPE E B OF PIPE E W Mount V Mount Figure 9 Transducer mounting modes for DTTR and DTTH Z Mount Page 16 TTM UM 00369 EN 02 April 2015 Transducer Installation Flow Meter Mounting Orientation DTTR DTTN and DTTH Transducers Top of Top of Flow Meter Flow Meter Mounting Orientation Mounting Orientation 2 DTTS and DTTC Transducers DTTS and DTTC Transducers Figure 10 Transducer orientation for horizontal pipes For DTTS and DTTC transducers the transducers are V mount The frequency setting depends on the pipe material Pipe Size b red Transducer Pipe DTTSnP ANSI 1
62. n algorithm It is also used if mass flow measurement units are selected for rate or total If a fluid was chosen from the FLUID TYPE list a nominal value for specific gravity in that media will be automatically loaded If the actual specific gravity is known for the application fluid and that value varies from the automatically loaded value the value can be revised If OTHER was chosen as FLUID TYPE a SPECIFIC GRAVITY may need to be entered if mass flows are to be calculated See Specifications on page 53 for list of alternate fluids and their specific gravities Fluid Absolute Viscosity Absolute viscosity of the fluid Enter a numeric value in centipoise Allows adjustments to be made to the absolute viscosity of the liquid in centipoise Ultrasonic transmitters use pipe size viscosity and specific gravity to calculate Reynolds numbers Since the Reynolds number influences flow profile the transmitter has to compensate for the relatively high velocities at the pipe center during transitional or laminar flow conditions The entry of FLUID VI is used in the calculation of Reynolds and the resultant compensation values If a fluid was chosen from the FLUID TYPE list a nominal value for viscosity in that media will be automatically loaded If the actual viscosity is known for the application fluid and that value varies from the automatically loaded value the value can be revised If OTHER was chosen as FLUID TYPE th
63. nt of the Pipes Internal Wall Surface relative roughness value Inside Diameter of the Pipe If a pipe material was chosen from the MATERIAL list a nominal value for relative roughness in that material will be automatically loaded If the actual roughness is known for the application piping system and that value varies from the automatically loaded value the value can be revised Enter the pipe wall thickness in inches if ENGLISH was selected as UNITS in 3 ENGLISH Inches millimeters if METRIC was selected Pipe wall Wall Thickness thickness METRIC See North American Pipe Schedules on page 43 for charts listing popular pipe Millimeters sizes Correct entries for pipe O D and pipe wall thickness are critical to obtaining accurate flow measurement readings Select a liner material If the pipe liner material used is not included in the list select Other and enter Material Pipe liner material liner material Sound Speed and Roughness much of this information is available at web sites such as www ondacorp com tecref acoustictable html Allows adjustments to be made to the speed of sound value shear or transverse wave for the pipe wall If the UNITS value was set to ENGLISH the entry is in fps feet per second METRIC entries are made in mps meters per second Speed of sound in ENGLISH fps Sound Speed the liner METRIC mps If a liner was chosen from the LINER MATERIAL list a nominal value for speed o
64. ntegrity of the enclosure Generally the right side conduit hole viewed from front is used for power the bottom conduit hole s for transducer connections Enclosures Integral Enclosure Remote Enclosure lt A n 5 a m J Two mounting holes Conduit hole A B D DIA E F G H JDIA K mm in mm in mm in mm in mm in mm in mm in mm in mm in mm 6 72 170 7 3 17 80 5 2 57 65 3 0 87 22 2 1 33 33 8 0 85 21 6 0 77 19 6 1 78 45 2 3 74 95 0 22 5 6 7 01 178 Figure 6 Transmitter enclosure dimensions The remote mount transmitter has three conduit holes in the flow meter enclosure that should be suitable for most installations Use a sealed cord grip or NEMA 4 conduit connection to retain the NEMA 3 integrity of the flow meter enclosure Failure to do so will void the manufacturer s warranty and can lead to product failure The TFXL Meter is housed in an insulating plastic enclosure that does not provide continuity of bonding between field wiring conduit and the TFXL Meter chassis or other conduits connected to the enclosure Page 10 TTM UM 00369 EN 02 April 2015 Transmitter Installation Wiring methods and practices are to be made in accordance with the NEC National Electrical Code and or other local ordin
65. o the transducer may cause signal strength to rise to acceptable levels Certain pipe and liquid characteristics may cause signal strength to rise to greater than 98 The problem with operating this transmitter with very high signal strength is that the signals may saturate the input amplifiers and cause erratic readings Strategies for lowering signal strength would be changing the transducer mounting method to the next longest transmission path For example if there is excessive signal strength and the transducers are mounted in a Z Mount try changing to V Mount or W Mount Finally you can also move one transducer slightly off line with the other transducer to lower signal strength 8 Secure the transducer with a stainless steel strap or other fastener Mounting Rail System Installation for DTTR For remote flow DTTR transducers with outside diameters between 2 10 inches 50 250 mm the rail mounting kit aids in installation and positioning of the transducers Transducers slide on the rails which have measurement markings that are viewable through the sight opening 1 Install the single mounting rail on the side of the pipe with the stainless steel bands provided Do not mount it on the top or bottom of the pipe On vertical pipe orientation is not critical Check that the track is parallel to the pipe and that all four mounting feet are touching the pipe 2 Slide the two transducer clamp brackets toward the center mark on the mounting rail
66. orp com tecref acoustictable html for pipe relative roughness calculations Specifies the speed of sound value shear or transverse wave for the pipe wall If the UNITS value was set to ENGLISH the entry is in fps feet per second METRIC entries are made in mps meters per second ENGLISH fps If a pipe material was chosen from the PIPE MATERIAL list a nominal value for Sound Speed Pipe sound speed speed of sound in that material will be automatically loaded If the actual sound METRIC mps RT a speed is known for the application piping system and that value varies from the automatically loaded value the value can be revised If OTHER was chosen as PIPE MATERIAL then a PIPESOUND SPEED must also be entered Enter the pipe outside diameter in inches if ENGLISH was selected as UNITS in ENGLISH Inches millimeters if METRIC was selected Pipe outside n Pipe diameter METRIC See North American Pipe Schedules on page 43 for charts listing popular pipe Pipe Millimeters sizes Correct entries for pipe O D and pipe wall thickness are critical to obtaining accurate flow measurement readings The transmitter provides flow profile compensation in its flow measurement calculation The ratio of average surface imperfection as it relates to the pipe internal diameter is used in this compensation algorithm and is found by using the following formula Roughness Pipe material Enter a numeric Pipe R Linear RMS Measureme
67. orth American Pipe Schedules 5 SCH 60 X STG SCH 80 SCH 100 SCH 120 140 SCH 180 In In ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall in in 1 1 315 0 957 0179 0957 0179 0 815 0 250 125 1 660 1278 0 191 1278 0191 1160 0 250 15 1 900 1 500 0 200 1 500 0 200 1 338 0281 2 2 375 1939 0218 1 939 0218 1 687 0 344 25 2 875 2323 0276 2323 0276 2 125 0 375 3 3 500 2 900 0 300 2 900 0 300 2 624 0 438 35 4000 3 364 0 318 3 364 0 318 4 4 500 3 826 0 337 3 826 0 337 3 624 0 438 3438 0531 5 5 563 4813 0375 4813 0375 4563 0 500 4313 0 625 6 6 625 5 761 0 432 5 761 0432 5 50 0 562 5 187 0719 8 8 625 7 813 0406 7 625 0 500 7 625 0 500 7437 0 594 7178 0 719 6 183 1221 10 1075 9750 0 500 975 0 500 9 562 0 594 9312 0719 9 062 0 844 8 500 1 125 13 12 75 11 626 0 562 1175 0 500 11 37 0 690 11 06 0845 1075 1 000 10 12 1 315 14 14 00 12814 0 593 13 00 0 500 12 50 0 750 1231 0845 11 81 1095 11 18 1 410 16 16 00 14 688 0 656 15 00 0 500 1431 0 845 1393 1 035 13 56 1220 1281 1 595 18 18 00 16 564 0 718
68. ot user adjustable Bad Data Rejection is a value related to the number of successive readings that must be measured outside of the Flow Filter Hysteresis or Flow Filter MinHysteresis windows before the Sets the number Bad Data of readinas to Enter a numeric transmitter will use that flow value Larger values are entered into Bad Data Rejection when Rejection 9 value measuring liquids that contain gas bubbles as the gas bubbles tend to disturb the ultrasonic measure RUE signals and cause more extraneous flow readings to occur Larger Bad Data Rejection values tend to make the transmitter more sluggish to rapid changes in actual flow rate April 2015 TTM UM 00369 EN 02 Page 35 Configuration Menu Output Tab The entries made in the Output tab establish input and output parameters for the transmitter Select the appropriate function from the pull down menu and click Download When a function is changed from the factory setting a configuration error 1002 will result This error will be cleared by resetting the transmitter microprocessor from the Communications Commands Reset Target button or by cycling power to the transmitter Once the proper output is selected and the microprocessor is reset calibration and configuration of the modules can be completed Row Ou Depi Module 1 Pulse and 4 20mA z Module 2 None z Min Flow Gal M Flow 100 Gal M Drese
69. pecific to Transducer 2 in and Greater 1MHz Spacing Transducer spacing ENGLISH Inches METRIC Millimeters A value calculated by the transmitter s firmware that takes into account pipe liquid transducer and mounting information The spacing adapts as these parameters are modified The spacing is given in inches for English units or millimeters for metric This value is the lineal distance that must be between the transducer alignment marks Selection of the proper transducer mounting method is not entirely predictable and many times is an iterative process NOTE Thissetting only applies to DTTR DTTN and DTTH transducers Flow Direction Transducer flow direction FORWARD REVERSE Allows the change of the direction the transmitter assumes is forward When mounting transmitters with integral transducers use this feature to reverse upstream and downstream transducers making upside down mounting of the display unnecessary April 2015 TTM UM 00369 EN 02 Page 31 Configuration Menu Category Parameter Meaning Option Description Select a material from the pull down list If the pipe material used is not found in the list select Other Materi and enter the actual pipe material Sound Speed and Roughness much of this information is available aterial Pipe material at web sites such as www ondac
70. pm The calculation is a little more complex if velocity is used because you first must convert the velocity into a volumetric flow rate to be able to compute a K factor To convert a velocity into a volumetric flow the velocity measurement and an accurate measurement of the inside diameter of the pipe must be known Also needed is the fact that one US gallon of liquid is equal to 231 cubic inches Example 3 Known values are Velocity 4 3 ft sec Inside Diameter of Pipe 3 068 in April 2015 TTM UM 00369 EN 02 Page 41 Factors Find the area of the pipe cross section Area nr 2 8 Area James 7 39 in Find the volume in one foot of travel 88 71in 7 39 in x 12 in 1 ft What portion of a gallon does one foot of travel represent 88 71 ir 231 in 0 384 gallons So for every foot of fluid travel 0 384 gallons will pass What is the flow rate in gpm at 4 3 ft sec 0 384 gallons x 4 3 FPS x 60 sec 1 min 2 99 1 Now that the volumetric flow rate is known all that is needed is an output frequency to determine the K factor Known values are Frequency 700 Hz By measurement Flow Rate 99 1 gpm By calculation 700 Hz x 60 sec 42 000 pulses per gallon 42 000 pulses per min K factor 423 9 pulses per gallon 99 1 qpm Page 42 TTM UM 00369 EN 02 April 2015 NORTH AMERICAN PIPE SCHEDULES Steel Stainless Steel PVC Pipe Standard Classes N
71. rass Alum Diameter Type Pipe Diameter Type Pipe in in in K L M K L M OD 0 625 0 625 0 625 0 840 OD 3 625 3 625 3 625 4 000 0 5 Wall 0 049 0 040 0 028 0 108 Wall 0 120 0 100 0 083 0 250 ID 0 527 0 545 0 569 0 625 ID 3 385 3 425 3 459 3 500 OD 0 750 0 750 0 750 OD 4 125 4 125 4 125 4 500 4 000 0 6250 Wall 0 049 0 042 0 030 4 in Wall 0 134 0 110 0 095 0 095 0 250 ID 0 652 0 666 0 690 ID 3857 3 905 3 935 3 935 4 000 OD 0 875 0 875 0 875 1 050 OD 5 000 075 Wal 0065 0045 0032 17 wap 0250 ID 0 745 0 785 0 811 0 822 ID 4 500 OD 1 125 1 125 1 125 1 315 OD 5 125 5 125 5 125 5 563 5 000 1 Wall 0 065 0 050 0 035 0 127 5 in Wall 0 160 0 125 0 109 0 250 0 063 ID 0 995 1 025 1 055 1 062 ID 4 805 4 875 4 907 5 063 4 874 OD 1 375 1 375 1 375 1 660 OD 6 125 6 125 6 125 6 625 6 000 1 25 Wall 0 065 0 055 0 042 0 146 6in Wall 0 192 0 140 0 122 0 250 0 063 ID 1 245 1 265 1 291 1 368 ID 5 741 5 845 5 881 6 125 5 874 OD 1 625 1 625 1 625 1 900 OD 7 625 7 000 1 5 Wall 0 072 0 060 0 049 0 150 7 in Wall 0 282 0 078 ID 1 481 1 505 1 527 1 600 ID 7 062 6 844 OD 2 125 2 125 2 125 2 375 OD 8 125 8 125 8 125 8 625 8 000 2 Wall 0 083 0 070 0 058 0 157 8 in Wall 0 271 0 200 0 170 0 313 0 094 ID 1 959 1 985 2 009 2 062 ID 7 583 7 725 7 785 8 000 7 812 OD 2 625 2 625 2 625 2 875 2 500 OD 10 125 10 125 10 125 10000 2 5 Wall 0 095 0 080 0 065 0 188 0 0
72. s 1000 by the number of seconds in a minute 60 to get the output frequency 1000 60 16 6666 Hz If you were looking at the pulse output on a frequency counter an output frequency of 16 666 Hz would be equal to one gpm If the frequency counter registered 33 333 Hz 2 x 16 666 Hz then the flow rate would be two gpm Finally if the flow rate is two gpm then the accumulation of 1000 counts would take place in 30 seconds because the flow rate and hence the speed that the 1000 counts is accumulated is twice as great Calculating Factors Many styles of transmitters are capable of measuring flow in a wide range of pipe sizes Because the pipe size and volumetric units the transmitter will be used on vary it may not possible to provide a discrete K factor In the event that a discrete K factor is not supplied then the velocity range of the transmitter is usually provided along with a maximum frequency output The most basic K factor calculation requires that an accurate flow rate and the output frequency associated with that flow rate be known Example 1 Known values are Frequency 700 Hz Flow Rate 48 gpm 700 Hz x 60 sec 42 000 pulses per min 42 000 pulses per min K factor 875 pulses per gallon 48 gpm Example 2 Known values are Full Scale Flow Rate 85 gpm Full Scale Output Frequency 650 Hz 650 Hz x 60 sec 39 000 pulses per min 39 000 pulses per min K factor 458 82 pulses per gallon 85 g
73. s such as turbines gear or nutating disc meters the K factor can be changed by modifying the MAX RATE flow rate value See Calculating K Factors on page 107 Kfactor 150 Pulses Per Gallon There are two frequency output options available The Turbine Meter Simulation option is used when a receiving instrument is capable of interfacing directly with a turbine transmitter s magnetic pickup The output is a relatively low voltage AC signal whose amplitude swings above and below the signal ground reference The minimum AC amplitude is approximately 500 mV peak to peak To activate the turbine output circuit turn SW4 OFF 500 MVp p 0 ac Figure 28 Frequency output waveform simulated turbine The Square Wave Frequency option is used when a receiving instrument requires that the pulse voltage level be either of a higher potential and or referenced to DC ground The output is a square wave with a peak voltage equaling the instrument supply voltage when the SW3 is ON If desired an external pullup resistor and power source can be used by leaving SW3 OFF Set SW4 to ON for a square wave output V 1 Figure 29 Frequency output waveform square wave April 2015 TTM UM 00369 EN 02 Page 27 Parameter Configuration Using UltraLink Software PARAMETER CONFIGURATION USING ULTRALINK SOFTWARE The UltraLink software utility is used for configuring calibrating and communicating with transit time flow meters It has numerou
74. s troubleshooting tools to make diagnosing and correcting installation problems easier A PC can be hard wired to the transmitter through a standard RS232 connector System Requirements The software requires a PC type computer running Windows 98 Windows ME Windows 2000 Windows NT Windows XP Windows Vista or Windows 7 operating systems and 5232 9 pin communication port 0010 0204 001 Installation 1 From the Windows Start button choose the Run command From the Run dialog box use Browse to navigate to the UltraLink Setup exe file and double click 2 The UltraLink Setup will automatically extract and install on the hard disk The UltraLink icon can then be copied to the desktop NOTE If a previous version of this software is installed it must un installed before a new version of the software can be installed Newer versions will ask to remove the old version and perform the task automatically Older versions must be removed using the Microsoft Windows Add Remove Programs applet NOTE Most PCs will require a restart after a successful installation Initialization 1 Connect the 9 pin serial end to an available port on the PC Connect the other end to the TFXL Meter PCINTERFACE CABLE PC INTERFACE inte hl o Figure 30 PC connections NOTE Power upthe transmitter prior to running this software NOTE While the serial cable is connected the frequency outputs are disabled 2
75. s within that hysteresis window greater display damping will occur up to the maximum values set by the flow filter entry The filter also establishes a flow rate window where measurements outside of the window are examined by the Bad Data Rejection filter The value is entered as a percentage of actual flow rate For example if the average flow rate is 100 gpm and the Flow Filter Hysteresis is set to 5 a filter window of 95 105 gpm is established Successive flow measurements that are measured within that window are recorded and averaged in accordance with the Flow Filter Damping setting Flow readings outside of the window are held up in accordance with the Bad Data Rejection filter Flow Filter MinHysteresis Minimum hysteresis window Enter a numeric value Flow Filter MinHysteresis sets a minimum hysteresis window that is invoked at sub 0 25 fps 0 08 mps flow rates where the of rate flow filter hysteresis is very small and ineffective This value is entered in pico seconds psec and is differential time If very small fluid velocities are to be measured increasing the flow filter minhysteresis value can increase reading stability Flow Filter Sensitivity allows configuration of how fast the Flow Filter Damping will adapt in the Muda SOUTH positive direction Increasing this value allows greater damping to occur faster than lower y values Adaptation in the negative direction is n
76. show what units were used during the existing calibration 1 If no data exists in the editor selection of Flow Rate Units will not influence measurements 2 If new calibration points are to be entered on Page 3 of 3 it is advisable to remove the existing calibration points using the Calibration Points Editor File Open File Save lt Back Cancel Figure 37 Calibration page 2 of 3 TTM UM 00369 EN 02 Page 37 Calibration Menu Set Multiple Flow Rates Use Page 3 of 3 to set multiple actual flow rates to be recorded by the transmitter To calibrate a point 1 Establish a stable known flow rate verified by a real time primary flow instrument 2 Enter the actual flow rate in the Flow window and click Set 3 Repeat for as many points as desired 4 Click Finish when you have entered all points If you are using only two points zero and span use the highest flow rate anticipated in normal operation as the calibration point If an erroneous data point is collected remove it click Edit select the bad point click Remove 1 Please establish reference flow rate 1FPS 0 3MPS Minimum 2 Enterthe reference flow rate below Do not enter 0 3 Wait for flow to stablize 4 Press Set button Flow File Open File Save Figure 38 Calibration page 3 of 3 Zero values are not valid for linearization entries Flow meter zero is entered on Page 1 of 3 If a zero calibration point is att
77. six tabs used to control how the transmitter is set up and responds to varying flow conditions The first screen that appears after clicking the Configuration button is the Basic tab Entry of data in the Basic and Flow tabs is all that is required to provide flow measurement functions to the transmitter If you are not going to use input output functions click Download to transfer the configuration to the transmitter When the configuration has been completely downloaded turn the power to the transmitter off and then on again to guarantee the changes take effect Row Fitering Output Display General Units Engish Standard Configurations TFXL 1 Schedule 40 Steel 7 Transducer Mount x Spacing DTTSnP Pipe SoundSpeed FPS Roughness 0 000150 _ Material Carbon Steel x Pipe OD 1 315 in Wall Thickness pi in Liner SoundSpeed 00 5 Roughness 00 None mime 0 Fluid SoundSpeed 491150 FPS Abs Viscosty 100 Type Water Tap z Spec Gravity 1 00 Spec Heat Capacity 1 Btu b F Fle Open Fie Save Cancel Figure 32 Basic tab Category Parameter Meaning Option Description Units The English metric selection will also configure the transmitter to display sound speeds in pipe materials and liquids as either feet per second fps or meters per second mps respectively ENGLISH Inches M
78. stream transducer while observing signal strength Signal strength can be displayed on the transmitter s display or on the main data screen in the UltraLink software utility See Parameter Configuration Using UltraLink Software on page 28 Clamp the transducer at the position where the highest signal strength is observed The factory default signal strength setting is five However there are many application specific conditions that may prevent the signal strength from attaining this level Signal levels less than five will probably not be acceptable for reliable readings NOTE Signal strength readings update only every few second Move the transducer 1 8 inch then wait to see if the signal is increasing or decreasing Repeat until the highest level is achieved If after adjusting the transducers the signal strength does not rise to above five use an alternate transducer mounting configuration If the mounting configuration was W Mount re configure the transmitter for V Mount move the downstream transducer to the new spacing distance and repeat the procedure Mount the Transducer on page 18 NOTE Mounting the high temperature transducers is similar to mounting the DTTR DTTN transducers High temperature installations require acoustic couplant that is rated not to flow at the operating temperature of the pipe surface Transducer Spacing Ti 1 mi Figure 13 Transducer positioning April 2015 TTM UM 00369 EN 02 Page 1
79. th A signal strength indication below 5 is generally inadequate for measuring flow reliably so generally the minimum setting for low signal cutoff is 5 A good practice is to set the low signal cutoff at approximately 60 70 of actual measured maximum signal strength The factory default low signal cutoff is 5 If the measured signal strength is lower than the low signal cutoff setting a Signal Strength too Low highlighted in red appears in the text area to the left in the Data Display screen until the measured signal strength becomes greater than the cutoff value Signal strength indication below 2 is considered to be no signal at all Verify that the pipe is full of liquid the pipe size and liquid parameters are entered correctly and that the transducers have been mounted accurately Highly aerated liquids also cause low signal strength conditions Substitute Flow Substitute flow value 0 0 100 0 A value that the analog outputs and the flow rate display to indicate when an error condition in the transmitter occurs The typical setting for this entry is a value that will make the instrument display zero flow during an error condition Substitute flow is set as a percentage between MIN RATE and MAX RATE In a unidirectional system this value is typically set to zero to indicate zero flow while in an error condition In a bidirectional system the percentage can be set such that zero is displayed in a error condition
80. tinuous research product improvements and enhancements Badger Meter reserves the right to change product or system specifications without notice except to the extent an outstanding contractual obligation exists O 2015 Badger Meter Inc All rights reserved www badgermeter com The Americas Badger Meter 4545 West Brown Deer Rd PO Box 245036 Milwaukee WI 53224 9536 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa GmbH Nurtinger Str 76 72639 Neuffen Germany 49 7025 9208 0 Europe Middle East Branch Office Badger Meter Europe PO Box 341442 Dubai Silicon Oasis Head Quarter Building Wing C Office 209 Dubai UAE 971 4 371 2503 Czech Republic Badger Meter Czech Republic s r o 2082 26 621 00 Brno Czech Republic 420 5 41420411 Slovakia Badger Meter Slovakia s r o Racianska 109 B 831 02 Bratislava Slovakia 421 2 44 63 83 01 Asia Pacific Badger Meter 80 Marine Parade Rd 21 06 Parkway Parade Singapore 449269 65 63464836 China Badger Meter 7 1202 99 Hangzhong Road Minhang District Shanghai China 201101 86 21 5763 5412 Legacy Document Number 06 TTM UM 00158
81. tion Page 1 of 3 The first screen Page 1 of 3 establishes a baseline zero flow rate measurement for the transmitter Remove the Zero Offset Because every transmitter installation is slightly different and sound waves can travel in slightly different ways through these installations it is important to remove the zero offset at zero flow to maintain the transmitter s accuracy The zeroing process is essential in systems using the DTTS and DTTC transducer sets for accuracy To establish zero flow and eliminate the offset 1 Establish zero flow in the pipe verify that the pipe is full of fluid turn off all pumps and close a dead heading valve Wait until the delta time interval shown in Current Delta T is stable and typically very close to zero 2 Click Set 3 Click Next when prompted then click Finish to advance to Page 2 of 3 Select Flow Rate Units Use Page 2 of 3 to select the engineering units for the calibration 1 Select an engineering unit from the Flow Rate Units drop down menu 2 Click Next to advance to Page 3 of 3 April 2015 Flow Rate Units EESTI Min kis advisable to File Save the existing calibration before modifying it If the Flow Rate Units selected on this page do not match the Flow Rate Units utilized for the existing data points collected on Page 3 of 3 flow measurement errors can occur To view existing measurement units go to Page 3 of 3 and press Edit The Calibration Points Editor will
82. tion on a PC BORE ROE boa 39 Printing a Config ration oe de du Sra OA PE teak A YE NOR ORA C S OE AURA AE XU RUE RON 39 Ultralink Error sat dk ead 40 KFactOrS s er Ge OE GRE RC E AUTE COR RC Cup de 41 DESChIDTOM P he ne 41 Calculating gt asais dea Up 41 North American Pipe ex IIR o duke ue Ao eder done a d dor Bos e idea 43 Fluid Properties 25 so RUE ey HORAE ROC aO ADS 48 Brad Harrison Connector Option obe x CE ux o 24 a oe 50 Control Drawings spatia ee y USAR qa pe PERG p E RUPES PE SN 51 SpecifiCatiOns c at autom t rere aye eed SR ed ba ewan ds 53 SYSTEM sco cc we RE 53 Re we eae AW Ok ad ew ee FEW we ee 53 Transduters 54 Software Utilities AA RU RR ew deed Vo RR eee Ae a 54 Part N mber Constr ctlon ceed eg ee A
83. transducer that will be connected to the transmitter Select the appropriate transducer type from the drop down list This selection influences transducer spacing and transmitter performance so it must be correct If you are unsure about the type of transducer to which the transmitter will be connected consult the shipment packing list or call the manufacturer for assistance A change of transducer type will cause a system configuration error 1002 Sys Config Changed to occur This error will clear when power to the transmitter is cycled Mount Transducer mounting method lt Selects the orientation of the transducers on the piping system See Transducer Installation on page 15 and Table 2 on page 17 for detailed information regarding transducer mounting modes for particular pipe and liquid characteristics Whenever the transducer mounting mode is changed power to the transmitter must be cycled Frequency Transducer transmission frequency 1MHZ 2MHZ Selects a transmission frequency for the various types of transducers In general the larger the pipe the slower the transmission frequency needs to be to attain a good signal Pipe Size and Transducers Type Frequency Mounting Modes All 1 2 1 1 2 in Small Pipe and Tube 2in Tubing Selected by Firmware Specific to 2 MHz Transducer 2 in ANSI Pipe and Copper Tube Standard and High Temp Selected by Firmware W V andZ S
84. y Alignment 3 Figure 11 Transducer alignment marks Page 18 TTM UM 00369 EN 02 April 2015 Transducer Installation Transducer Mounting Configurations V Mount and W Mount Configurations Apply the Couplant For DTTR DTTN and DTTH transducers place a single bead of couplant approximately 1 2 inch 12 mm thick on the flat face of the transducer See Figure 12 Generally a silicone based grease is used as an acoustic couplant but any good quality grease like substance that is rated to not flow at the operating temperature of the pipe is acceptable For pipe surface temperature over 150 F 65 C use Sonotemp D002 2011 011 2 Figure 12 Application of couplant Position and Secure the Transducer 1 Place the upstream transducer in position and secure with a mounting strap Place the straps in the arched groove on the end of the transducer Use the screw provided to help hold the transducer onto the strap Verify that the transducer is true to the pipe and adjust as necessary Tighten the transducer strap securely Place the downstream transducer on the pipe at the calculated transducer spacing See Figure 13 on page 19 Apply firm hand pressure If signal strength is greater than five secure the transducer at this location If the signal strength is not five or greater using firm hand pressure slowly move the transducer both towards and away from the up

Download Pdf Manuals

image

Related Search

Related Contents

Canon CXDI-55G User's Manual  

Copyright © All rights reserved.
Failed to retrieve file