Home
        VAMP 210 manual - Schneider Electric België
         Contents
1.                                                                          stages  IL1  IL2  IL3 Phase currents  lo1 Residual current input lo   lo2 Residual current input Ios  U12  U23  U31 Line to line voltages  UL1  UL2  UL3 Phase to ground voltages  Uo Zero sequence voltage  f Frequency  P Active power  Q Reactive power  S Apparent power  loCalc Phasor sum I    Io   I3  l1 Positive sequence current  12 Negative sequence current  12 11 Relative negative sequence current  I2 In Negative sequence current in pu  U1 Positive sequence voltage  U2 Negative sequence voltage  U2 U1 Relative negative sequence voltage  IL Average  l4   lL2   13 3  Uphase  Uun  Average  Ui1   Ute   Ur3 3  Uline  ULL  Average  U12   U23   U31  3  TanFii Tangent       tan arccos     Prms Active power rms value  Qrms Reactive power rms value  Srms Apparnet power rms value  THDIL1 Total harmonic distortion of       THDIL2 Total harmonic distortion of I 2  THDIL3 Total harmonic distortion of l3  THDUa Total harmonic distortion of input Ua  THDUc Total harmonic distortion of input Up  THDUb Total harmonic distortion of input U   IL1RMS IL1 RMS for average sampling  IL2RMS IL2 RMS for average sampling  IL8RMS IL3 RMS for average sampling             Eight independent stages    The relay has eight independent programmable stages  Each    programmable stage can be enabled or disabled to fit the intended    application     135    5 27 Programmable stages  99     5 Protection functions    Technical description   
2.                                                              vamp210appl3    Figure 4 1 Typical application of the VAMP 210 generator protection relay           45    4 1 Main features    4 Introduction Technical description       4 1  Main features  The main features of VAMP 210 are    46    Comprehensive set of protection functions  The protection  stages not needed in a particular application can be disabled   Versatile measuring functions including currents  voltages   frequency  power  energy  symmetric components  average  values etc    Control functions and status display for circuit breakers   disconnectors etc    Arc protection is available as option    Fully digital signal handling with a powerful 16 bit  microprocessor  and high measuring accuracy on all the setting  ranges due to an accurate 16 bit A D conversion technique and  up to 20 bit dynamic range    Easy adaptability of the relay to the power plant automation  system or SCADA systems using the wide range of available  communication protocols    Easy adaptation to traditional alarm systems using the  available signal relay outputs and the flexible signal grouping  matrix of the relay    Flexible control and blocking possibilities due to digital signal  control inputs  DI  and outputs  DO     Freely configurable mimic display with busbar  CB etc  symbols  and six selectable measurement values    Five freely configurable double character size measurement  displays    Freely programmable interlocking schemes w
3.                                                 RATED INPUT   Maximum secondary scaled setting  enabling inverse delay times up to 20x  setting   Order code IL lox loo l1  l2  IL3  amp  lo loo   locaic   VAMP 210 1_ 1 2 5A   VAMP 210 5 __ 5 12 5A   VAMP 210 _A 5 5 1 25A 1 25A   VAMP 210 _B 5 1 1 25A 0 25A   VAMP 210 _C 1 5 0 25 A 1 25 A   VAMP 210 _D 1 1 0 25 A 0 25 A  5 29 1  Standard inverse delays IEC  IEEE  IEEE2  RI    The available standard inverse delays are divided in four  categories IEC  IEEE  IEEE2 and RI called delay curve families   Each category of family contains a set of different delay types  according the following table     Inverse time setting error signal    The inverse time setting error signal will be activated  if the delay  category is changed and the old delay type doesn t exist in the  new category  See chapter 5 29 for more details     Limitations    The minimum definite time delay start latest  when the measured  value is twenty times the setting  However  there are limitations at  high setting values due to the measurement range  See chapter  5 29 for more details     Table 5 29 1 1  Available standard delay families and the  available delay types within each family                                                  Curve family  KE O W D      Delay type Oo i m u     DT Definite time X  NI1 Normal inverse X X  VI Very inverse X X X  El Extremely inverse X X X  LTI Long time inverse X X  LTEI   Long time extremely inverse X  LTVI   Long time very in
4.                             Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day   Type Fault type   1 N Ground fault   2 N Ground fault   3 N Ground fault   1 2 Two phase fault   2 3 Two phase fault   3 1 Two phase fault   1 2 3 Three phase fault  Fit xlgn   Maximum fault current  Load xlgn_   1 s average phase currents before the   fault  EDly   Elapsed time of the operating time  setting  100    trip  Angle    Fault angle in degrees  U1 xUn_   Positive sequence voltage during fault  SetGrp 1 Active setting group during fault  2          Voltage restrained controlled  overcurrent function ly gt   51V     The voltage restrained overcurrent stage ly gt  is used for generator  short circuit protection in applications  where the static excitation  system of the generator is fed only from the generator terminals     In these applications the operation of the high set overcurrent  function must be secured using a voltage restrained overcurrent  function  At close by short circuits the fault current rapidly  decreases  thus jeopardizing the operation of the high set short   circuit protection  The operation characteristic of a voltage  restrained overcurrent function is shown in Figure 5 6 1  The  under impedance protection  see chapter 5 20  can be used for  the same purpose     63    5 6 Voltage restrained controll  overcurrent function IV gt   51V     ed 5 Protection functions Technical description        gt  Usaa
5.              For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed   C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault voltage  elapsed delay and setting group     Recorded values of the 100   stator earth fault stage                      Uots lt   64F3   Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit     3 harmonic value relative to Un V3  during fault  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      108 V210 EN M A011    Technical description    5 Protection functions 5 18 Overfrequency and  underfrequency protection f gt   f lt    81H 81L        5 18     V210 EN M A011    Overfrequency and underfrequency  protection f gt   f lt   81H 81L     Frequency protection is used for load sharing  loss of mains  detection and as a backup protection for over speeding     The frequency function measures the frequency from the two first  voltage inputs  At least one of these two inputs must have a  voltage connected to be able to measure the frequency  Whenever  the frequency crosses the user s pick up setting of a particular  stage  this stage picks up and a start signal is issued  If the fault  situation remains on longer than the user s o
6.              f gt  lt   f gt  gt  lt  lt                 32  P lt   P lt  lt                        Ne       CBFP                      21 40 SONARC  I lt  x lt  ArCh gt   X lt  lt  AtCl  gt              N                                  N j    67NT 9 50ARC  Prg1   8 Arc                                                               5            Blocking and  output matrix                      N                                                              vamp210appL2    Figure 10 2 1 Generator connected directly to the distribution busbar   Unearthed generator neutral     The neutral point of the generator winding is unearthed  The  busbar system is earthed via a separate earthing transformer  In  this case the earth fault protection principle is straight forward  It is  simply based on the measurement of the earth fault current  Io1   between the generator and the distribution busbar     236 V210 EN M A011    Technical description 10 Applications 10 3 Generator transformer unit                                                                                                                                                                                                                                                                                                                                                                                                                      a  10 3  Generator transformer unit  L1  L2  L3  Lif    L2  L3  L1  X6  L2   2 Protection function  4
7.        is used instead of the  correct name    3l       Example 1  single phase injection  Ucn  100V  Voltage measurement mode is  2LL Uo      V210 EN M A011    Technical description    7 Measurement functions 7 9 Symmetric components       V210 EN M A011    Injection   Up   U23  0       a i alae P   5                      U   3 1  a  o0   3 100Z0     33  U   33   U gt   33     U2 U    100    When using a single phase test device  the relative unbalance  U2 U  will always be 100       Example 2  two phase injection with adjustable phase angle  Ucn  100V   Voltage measurement mode is  2LL Uo     Injection    Ua   U2   100 V 40     Ub   Uz   100 V3 V Z 150     57 7 V 2 150                  U  _1f1  a   10020    _100f120   1 434 90   _  U    3 1  a  100 432 150    3  120   1 432  30      _ 100  2 432  30     _ 38 5    30       3   1   32Z 30     19 22  30      Ui  38 5   U gt   19 2   Us U    50      Figure 7 9 1 shows a geometric solution  The input values have  been scaled with V3 100 to make the calculation easier     199    7 9 Symmetric components    7 Measurement functions Technical description       200    FortescueEx2    Positive sequence       Figure 7 9 1 Example of symmetric component calculation using line to line  voltages     Unscaling the geometric results gives  U4   100 V3 x 2 3   38 5     Us   100 48 x 1 3   19 2     U2 U    1 3 2 3  50     Example 3  two phase injection with adjustable phase angle  Ucn  100V   Voltage measurement mode is  3LN     Injection    
8.        ms       Pulse length of  reactive imported  energy          175    6 9 Energy pulse outputs    6 Supporting functions Technical description       176    Scaling examples    Example 1    Average active exported power is 250 MW    Peak active exported power is 400 MW    Pulse size is 250 kWh    The average pulse frequency will be 250 0 250   1000 pulses h   The peak pulse frequency will be 400 0 250   1600 pulses h   Set pulse length to 3600 1600     0 2   2 0 s or less     The lifetime of the mechanical output relay will be  50x10   1000 h   6 a     This is not a practical scaling example unless an output relay  lifetime of about six years is accepted     Example 2    Average active exported power is 100 MW    Peak active exported power is 800 MW    Pulse size is 400 kWh    The average pulse frequency will be 100 0 400   250 pulses h   The peak pulse frequency will be 800 0 400   2000 pulses h   Set pulse length to 3600 2000     0 2   1 6 s or less     The lifetime of the mechanical output relay will be  50x10   250 h   23 a     Example 3    Average active exported power is 20 MW    Peak active exported power is 70 MW    Pulse size is 60 kWh    The average pulse frequency will be 25 0 060   416 7 pulses h   The peak pulse frequency will be 70 0 060   1166 7 pulses h   Set pulse length to 3600 1167     0 2   2 8 s or less     The lifetime of the mechanical output relay will be  50x10   417 h   14a     Example 4    Average active exported power is 1900 kW    Peak active 
9.       100  80                                                                                                                                              10 10    8   84  oe Ss E   k 5   S 2 S 2 ket  08 08 kos  0 6 0 6  0 4 0 4  0 2 0 2  0 1 0 1  0 08 0 08  0 06 0 06  1 2 3 4 5678 10 20 1 2 3 4 5678 10 20  T Iset inverseDelayRI T Iset inverseDelayRXIDG  Figure 5 29 1 15 Inverse delay of type Figure 5 29 1 16 Inverse delay of type  RI  RXIDG     151    5 29 Inverse time operation    5 Protection functions Technical description       5 29 2     152    Free parametrisation using IEC  IEEE and  IEEE2 equations    This mode is activated by setting delay type to    Parameters     and  then editing the delay function constants  i e  the parameters A      E  The idea is to use the standard equations with one   s own  constants instead of the standardized constants as in the previous  chapter     Example for GE IAC51 delay type inverse     k   0 50   l   4pu  lpickup   2 pu   A   0 2078  B   0 8630  C   0 8000  D      0 4180  E   0 1947    1 0 5  0 2078   0 8630 i     0 4180 n 0 1947  0 37    ay fo Tee    The operation time in this example will be 0 37 seconds    The resulting time current characteristic of this example matches  quite well with the characteristic of the old electromechanical  IAC51 induction disc relay        Inverse time setting error signal   The inverse time setting error signal will become active  if  interpolation with the given parameters is not possible  See  
10.       CTS out  Internally connected to pin 7                 o    No connected       NOTE  DSR must be connected to DTR to activate the front panel connector and    disable the rear panel X4 RS232 port   The other port in the same X4  connector will not be disabled      253    11 4 Serial communication  connectors    11 Connections    Technical description       11 4 2     Rear panel connector X5  REMOTE     The X5 remote port communication connector options are shown  in Figure 11 4 2 1  The connector types are listed in Table    11 4 2 1     Without any internal options  X5 is a TTL port for external  converters  Some external converters  VSE  are attached directly  to the rear panel and X5  Some other types  VEA  VPA  need  various TTL RS 232 converter cables  The available accessories  are listed in chapter 15   Internal options for fibre optic  Figure 11 4 2 3   2 amp 4 wire  galvanically isolated RS 485  Figure 11 4 2 2  and Profibus   Figure 11 4 2 4  are available  See ordering code in chapter 15     Table 11 4 2 1 Physical interface and connector types of  remote port X5 with various options  Serial interface  A  is the                                        default   Order Communication interface   Connector Pin usage  Code type  A Serial interface for external   D9S 1   reserved  converters only  REMOTE 2   TX_out  TTL  port  3   RX_in TTL  4   RTS out  TTL  7   GND  9    8V out  B Plastic fibre interface HFBR 0500   REMOTE port   C Profibus interface D9S 3 RXD TXD
11.     12 11 Relative current unbalance        I2 Ign Current unbalance  xlen       U1 Positive sequence voltage      U2 Negative sequence voltage          U2 U1 Relative voltage unbalance          IL Average  IL1   IL2   IL3  3      Uphase Average  UL1   UL2   UL3  3        Uline Average  U12   U23   U31  3          DO Digital outputs Yes Yes  DI Digital inputs Yes Yes  TanFii tano        Prms Active power rms value          Qrms Reactive power rms value          Srms Apparent power rms value      THDIL1 Total harmonic distortion of IL1      THDIL2 Total harmonic distortion of IL2        THDIL3 Total harmonic distortion of IL3      THDUa Total harmonic distortion of input Ua      THDUb Total harmonic distortion of input Ub      THDUc Total harmonic distortion of input Uc       IL1RMS IL1 RMS for average sampling      IL2RMS IL2 RMS for average sampling        IL3RMS IL3 RMS for average sampling                          157    6 2 Disturbance recorder 6 Supporting functions Technical description       Disturbance recorder parameters                      Parameter   Value Unit   Description Note  Mode Behaviour in memory full Set  situation   Saturated No more recordings are  Overflow accepted  The oldest recorder will be  overwritten  SR Sample rate Set  32 cycle Waveform  16 cycle Waveform  8 cycle Waveform  1 10ms One cycle value      1 20ms One cycle value      1 200ms Average  1 1s Average  1 5s Average  1 10s Average  1 15s Average  1 30s Average  1 1min Average  Time s Rec
12.     136    Setting groups    There are two settings groups available  Switching between    setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     There are two identical stages available with independent setting                                                 parameters   Parameters of the programmable stages PrgN  99   Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  S None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   Link  See Name for the supervised signal Set  table  above    See table Value of the supervised signal  above   Cmp Mode of comparison Set   gt  Over protection   lt  Under protection  Pickup Pick up value scaled to primary  level  Pickup pu Pick up setting in pu Set  t s Definite operation time  Set  Hyster   Dead band setting Set  NoCmp pu Minimum value to start under Set  comparison   Mode   lt                            Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the 
13.     Objects are circuit breakers  disconnectors etc   Their position or status  can be displayed and controlled in the interactive mimic display     There are two extra menus  which are visible only if the access level   operator  or  configurator  has been opened with the corresponding  password     Detailed protocol configuration is done with VAMPSET     19    2 2 Local panel operations    2 Local panel user interface Operation and configuration  instructions       2 2 2     20    Menu structure of protection functions    The general structure of all protection function menus is similar  although the details do differ from stage to stage  As an example  the details of the second overcurrent stage I gt  gt  menus are shown  below     First menu of I gt  gt  50 51 stage    first menu    AV  gt   gt  gt  STATUS 50 51    ExDO   Status  SCntr  TCntr  SetGrp  SGrpDI  Force       Figure 2 2 2 1 First menu of I gt  gt  50 51 stage    This is the status  start and trip counter and setting group menu   The content is     e Status        The stage is not detecting any fault at the moment  The stage  can also be forced to pick up or trip if the operating level is   Configurator  and the force flag below is on  Operating levels  are explained in chapter 2 2 5     e SCntr5    The stage has picked up a fault five times since the last reset  of restart  This value can be cleared if the operating level is at  least  Operator      e TCnir 1  The stage has tripped two times since the last res
14.     THDUb   U HARM  DISTORTION   Total harmonic distortion of the voltage  input b      THDUc   U HARM  DISTORTION   Total harmonic distortion of the voltage  input c      Diagram   U HARMONICS of input   Harmonics of voltage input Ua      Ua  see Figure 2 3 2 1   Diagram   U HARMONICS of input   Harmonics of voltage input Ub      Ub  see Figure 2 3 2 1   Diagram   U HARMONICS of input   Harmonics of voltage input Uc      Uc  see Figure 2 3 2 1   Count U VOLT  INTERRUPTS   Voltage interrupt counter  Prev U VOLT  INTERRUPTS   Previous interruption  Total U VOLT  INTERRUPTS   Total duration of voltage interruptions   days  hours   Prev U VOLT  INTERRUPTS   Duration of previous interruption  Status U VOLT  INTERRUPTS   Voltage status  LOW  NORMAL              harm    HARMONICS of IL1       3579 11 13 15    Figure 2 3 2 1  Example of harmonics bar display    30    V210 EN M A011    Operation and configuration    2 Local panel user interface 2 3 Operating measures       2 3 3     V210 EN M A011    Reading event register  The event register can be read from the Evnt submenu     1  Push once     2  The EVENT LIST appears  The display contains a list of all the  events that have been configured to be included in the event  register     event_list    EVENT LIST 44v    Code  71E10  CB open timeout    2002 02 15  00 17 37 530       Figure 2 3 3 1  Example of an event register    3  Scroll through the event list with and v   4  Exit the event list by pushing  lt      It is possible to se
15.     The relay has three communication ports as standard  A fourth  port  Ethernet  is available as option  See Figure 9 1 1    There are three communication ports in the rear panel  The  Ethernet port is optional  The X4 connector includes two ports   local port and extension port  The front panel RS 232 port will shut  off the local port on the rear panel when a VX003 cable is inserted     COMMUNICATION PORTS  LOCAL EXTENSION REMOTE  PORT PORT DATA BUS PORT    Default     TTL  for external  adapters only                       l  Options       RS 485  isolated     Fibre optic    Profibus    Ethernet and TTL X5     TTL is for external  adapters only     panel in use        Not isolated            S  X4  LOCAL    FRONT PANEL    Figure 9 1 1 Communication ports and connectors  By default the X5 is a D9S  type connector with TTL interface  The DSR signal from the front panel port  selects the active connector for the RS232 local port     By default the remote port has a TTL interface  It can only be used  together with external converters or converting cables  Inbuilt  options for RS 485  fibre optic  plastic plastic  plastic glass   glass plastic or glass glass   Profibus and Ethernet are available   V210 EN M A011    Technical description 9 Communication 9 1 Communication ports       9 1 1  Local port X4    The local port has two connectors     e On the front panel  e X4 the rear panel  D9S pins 2  3 and 5   Only one can be used at a time     NOTE  The extension port is locatin
16.     d  q                   A5  WY                                        vamp210lohko    Figure 11 8 1 Block diagram of the generator protection relay VAMP 210       267    11 9 Block diagrams of option    modules    11 Connections Technical description       11 9   11 9 1     11 9 2     268    Block diagrams of option modules    Optional arc protection    X6 1 BI        BI O  X6 2 BO    4  X6 3 comm           X6 4 L1       X6 5 L1       X6 6 L2          X6 7 L2       EE NE E A E NT ARC_option_block_diagram  Figure 11 9 1 1 Block diagram of optional arc protection module                          Optional DI19 DI20  Options    X61 DI149          DI  X6 2 DI19     X6 3 DI 20  E   X6 4 DI 20     X6 5 NC   3   X6 6 L         gt   X6 7 L  a    EEE O EE EE     DI19D120_option_block_diagram                   Figure 11 9 2 1 Block diagram of optional DI19 DI20 module with one arc  channel     V210 EN M A011    Technical description 11 Connections 11 10 Connection examples       11 10  Connection examples    1O mM  x X Qors gpg e Yo on eF ry ereees   EET                                                                                                                                                                                                                                                                                                                                            o  Q  E  g  o  G  2  a 5  2  i   2 5      Q  S R   s     OG N    a     DE K2 3  a 25  8   a Teo  7     s  o
17.    10000 Hysteresis for alarm limits   21x107    er  214x107 Limit setting  A  A  E  S   lt x     Alarm Active state  w        z  21x107    ME       z 241x107 Limit setting  T A  z E  E S  z  lt   a    Alarm Active state  x lt   Active value  1   9999 Modbus register for the measurement  1   247 Modbus address of the I O device  On   Off Enabling for measurement                      Analog input alarms have also matrix signals     Ext  Aix Alarm1     and    Ext  Aix Alarm2        V210 EN M A011 263    11 7 External I O extension modules 11 Connections Technical description       External digital inputs configuration  VAMPSET only   Range Description          Communication read errors                      1   16 Bit number of Modbus register value  CoilS  InputS      InputR or HoldingR Modbus register type     3      2  a  E    1   9999 Modbus register for the measurement  z  1   247 Modbus address of the I O device  0 1 Active state  On   Off Enabling for measurement                   264 V210 EN M A011    Technical description    11 Connections    11 7 External I O extension modules       V210 EN M A011    EXTERNAL DIGITAL OUTPUTS       External digital outputs configuration  VAMPSET only                       Range Description  Communication errors  ll 1   9999 Modbus register for the measurement  om    1   247 Modbus address of the I O device  0 1 Output state  On   Off Enabling for measurement                265    11 7 External I O extension modules    11 Connections    
18.    Application layer Set  5000 default confirmation timeout  CnfMode Application layer Set  EvOnly  default  confirmation mode  All  DBISup Double bit input support Set  No  default   Yes  SyncMode 0     65535 S Clock synchronization Set  request interval   0   only at boot          Set   An editable parameter  password needed     External I O  Modbus RTU master     External Modbus I O devices can be connected to the relay using  this protocol   See chapter 11 7 2 External input   output module  for more information     229    9 2 Communication protocols 9 Communication Technical description       9 2 9  IEC 61850    The relay supports communication using IEC 61850 protocol with  native implementation  IEC 61850 protocol is available with the  optional inbuilt Ethernet port  The protocol can be used to read    write static data from the relay or to receive events and to receive    send GOOSE messages to other relays     IEC 61850 serve interface is capable of     e Configurable data model  selection of logical nodes  corresponding to active application functions    e Configurable pre defined data sets  e Supported dynamic data sets created by clients    e Supported reporting function with buffered and unbuffered  Report Control Blocks   e Supported control model  direct with normal security   e Supported horizontal communication with GOOSE   configurable GOOSE publisher data sets  configurable filters  for GOOSE subscriber inputs  GOOSE inputs available in the  application lo
19.    Inrush blocking is recommended to be used into time delayed overcurrent  stages while non blocked instant overcurrent stage is set to 20   higher  than expected inrush current  By this scheme fast reaction time in short  circuit faults during the energization can be achieved while time delayed  stages are blocked by inrush function     O          Pickup  e a a e e e ce  c ccc ccc cr ccc        Cold   l    load    Cold load and inrush       No activation because the current has not been under the set  lae Current        Current dropped under the laie current level but now it stays  between the lae current and the pick up current for over 80ms        No activation because the phase two lasted longer than 80ms        Now we have a cold load activation which lasts as long as the  operation time was set or as long as the current stays above  the pick up setting     Figure 6 3 1 Functionality of cold load   inrush current feature     V210 EN M A011    Technical description    6 Supporting functions    6 3 Cold load pick up and inrush  current detection       V210 EN M A011    Parameters of the cold load  amp  inrush detection function                                        Parameter   Value Unit Description Note  ColdLd   Status of cold load detection   Start Cold load situation is active  Trip Timeout  Inrush   Status of inrush detection   Start Inrush is detected  Trip Timeout  ILmax A The supervised value  Max  of  IL1  IL2 and IL3  Pickup A Primary scaled pick up value  Idle
20.    PF_L1 P POWER PHASE 2 Power factor of phase 1   PF_L2 P POWER PHASE 2 Power factor of phase 2   PF_L3 P POWER PHASE 2 Power factor of phase 3   cos P COS  amp  TAN Cosine phi   tan P COS  amp  TAN Tangent phi   cosL1 P COS  amp  TAN Cosine phi of phase L1   cosL2 P COS  amp  TAN Cosine phi of phase L2   cosL3 P COS  amp  TAN Cosine phi of phase L3   Iseq P PHASE Actual current phase sequency  OK   SEQUENCIES Reverse        Useq P PHASE Actual voltage phase sequency  OK   SEQUENCIES Reverse        log P PHASE lo Uo angle       SEQUENCIES   lo2  P PHASE lo2 Uo angle       SEQUENCIES   fAdop P PHASE Adapted network frequency  Hz   SEQUENCIES   E  E ENERGY Exported energy  MWh    Eq  E ENERGY Exported reactive energy  Mvar    E  E ENERGY Imported energy  MWh    Eq  E ENERGY Imported reactive energy  Mvar    E  nn E DECIMAL COUNT Decimals of exported energy             V210 EN M A011    Operation and configuration    2 Local panel user interface    2 3 Operating measures       V210 EN M A011                                                                                                          Value Menu Submenu Description  Eq nn E DECIMAL COUNT Decimals of reactive energy  E  nn E DECIMAL COUNT Decimals of imported energy  Ewrap E DECIMAL COUNT Maximum energy counter value  E  E E PULSE SIZES Pulse size of exported energy  kWh   Eq  E E PULSE SIZES Pulse size of exported reactive energy   kvar   E  E E PULSE SIZES Pulse size of imported energy  kWh   Eq  E E PULSE SIZES Puls
21.    The following equation can be used if the previous   AAlIntv  value has been zero     604 8    AAIntv    DriftInOneWeek       If the auto adjust interval  AAlntv  has not been zero  but further  trimming is still needed  the following equation can be used to  calculate a new auto adjust interval   1  1 3 DriftInOneWeek  AAINWV previous 604 8       AAINtV yew         The term DriftInOne Week 604 8 may be replaced with the  relative drift multiplied by 1000  if some other period than one  week has been used  For example if the drift has been 37 seconds  in 14 days  the relative drift is 37 1000  14 24 3600    0 0306  ms s     V210 EN M A011    Technical description 6 Supporting functions 6 10 System clock and  synchronization       Example 1    If there has been no external sync and the relay s clock is leading  sixty one seconds a week and the parameter AAlntv has been  zero  the parameters are set as   AvDrft   Lead    AAIntv   004 8  9 95  61    With these parameter values the system clock corrects itself with      1 ms every 9 9 seconds which equals    61 091 s week     Example 2     If there is no external sync and the relay s clock has been lagging  five seconds in nine days and the AAlIntv has been  9 9 s  leading  then the parameters are set as    1  AAY yew      or oe    99 9 24 3600  AvDrft   Lead    NOTE  When the internal time is roughly correct     deviation is less than four  seconds     any synchronizing or auto adjust will never turn the clock  backwards  Ins
22.    k   Overload factor  Maximum continuous current  i e   service factor   Setting value    k     Ambient temperature factor  Permitted current due to  tamb  Figure 5 8 1   lan   The rated current  In or Imor    C   Cooling time coefficient  cooling time constant    C X T     V210 EN M A011    Technical description 5 Protection functions 5 8 Thermal overload protection T gt      49        Time constant for cooling situation   If the generator s fan is stopped  the cooling will be slower than  with an active fan  Therefore there is a coefficient ct for thermal  constant available to be used as cooling time constant  when  current is less than 0 3xlen     Heat capacitance  service factor and ambient temperature    The trip level is determined by the maximum allowed continuous  current Imax corresponding to the 100   temperature rise Orr i e   the heat capacitance of the generator  Imax depends of the given  service factor k and ambient temperature   ame and settings Imaxao  and Imax70 according the following equation     Imax  k ke lon    The value of ambient temperature compensation factor kO  depends on the ambient temperature Oame and settings Imaxao and  Imax7o  See Error  Reference source not found   Ambient  temperature is not in use when kO   1  This is true when         MAX40 is 1 0  e Samb is    n a     no ambient temperature sensor   e TAMB is  40   C     k AmbientTemperatureCompensation                                                        10 20 30 40 50 60 70 80  O
23.   0    BASE ANGLE    180    Ipr gt  TRIP AREA     cap     ind      90   Idir_modeBiDir 15     Figure 5 5 3 Bi directional application with two stages Idir gt  and Idir gt  gt      When any of the three phase currents exceeds the setting value  and     in directional mode     the phase angle including the base  angle is within the active  88   wide sector  the stage picks up and  issues a start signal  If this fault situation remains on longer than  the delay setting  a trip signal is issued     Four independent stages    There are four separately adjustable stages available  lgir gt   lair gt  gt    lgir gt  gt  gt  and Igir gt  gt  gt  gt      59    5 5 Directional overcurrent  protection Idir gt   67     5 Protection functions Technical description       60    Inverse operation time    Stages lair gt  and Igi gt  gt  can be configured for definite time or inverse  time characteristic  See chapter 5 29 for details of the available  inverse delays  Stages Igi gt  gt  gt  and lair gt  gt  gt  gt  have definite time  DT   operation delay  The relay will show a scaleable graph of the  configured delay on the local panel display     Inverse time limitation    The maximum measured secondary current is 50xlyn  This limits  the scope of inverse curves with high pick up settings  See  chapter 5 29 for more information     Cold load and inrush current handling  See chapter 6 3     Setting groups    There are two settings groups available for each stage  Switching  between setting grou
24.   4 DI20 Digital input 20   5       6 S1 gt   Arc sensor 1  positive connector    7 S1 gt   Arc sensor 1  negative connector                        Arc sensor itself is polarity free    252    V210 EN M A011             Technical description    11 Connections 11 2 Auxiliary voltage       11 2     11 3     11 4     11 4 1     V210 EN M A011    Auxiliary voltage    The external auxiliary voltage Uaux  standard 40   265 V ac dc or  optional 18   36 Vdc  for the terminal is connected to the terminals  X3  17 18     NOTE  When optional 18   36 Vdc power module is used the polarity is as    follows     X3 17 negative  X3 18 positive     Output relays    The terminal is equipped with nine configurable output relays  and   a separate output relay for the self supervision system    e Trip relays T1 and T2  terminals X3  12 13 and 14 15    e Alarm relays A1   A5  terminals X3  9 11  X2  5 6  7 8  10 12   13 15    e Self supervision system output relay IF  terminals X2  16 18     Serial communication connectors    The pin assignments of communication connectors including  internal communication converters are presented in the following  figures and tables     Front panel connector          Figure 11 4 1 1 Pin numbering of the front panel D9S connector       Pin RS232 signal       Not connected       Rx in       Tx out       DTR out   8 V        GND       DSR in  activates this port and disables the X4 RS232 port        RTS in  Internally connected to pin 8        COIN   MD  Ory  RH  OP 
25.   Auxiliary voltage       Type A Type B    Voltage range Uaux 40   265 V ac dc 18   36 Vdc   Note  Polarity   X3 17  negative      X3 18  positive                 Start up peak  DC                    110V  Type A  15A with time constant of 1ms  220V  Type A  25A with time constant of ims  Power consumption  lt  7 W  normal conditions     lt  15 W  output relays activated   Max  permitted interruption time  lt  50 ms  110 V dc   Terminal block  Maximum wire dimension     Phoenix MVSTBW or equivalent 2 5 mm   13 14 AWG        270 V210 EN M A011    Technical description    12 Technical data    12 1 Connections       12 1 3     12 1 4     12 1 5     12 1 6     V210 EN M A011    Digital inputs    Internal operating voltage                Number of inputs 6   Internal operating voltage 48 Vdc  Current drain when active  max   approx  20 mA  Current drain  average value  lt 1mA       Terminal block     Phoenix MVSTBW or equivalent          Maximum wire dimension   2 5 mm   13 14 AWG        Trip contacts       Number of contacts    2 making contacts  relays T1 and T2        Rated voltage    250 Vac dc                Continuous carry 5A   Make and carry  0 5 s 30 A   Make and carry  3s 15A   DC breaking capacity  L R 40ms    at 48 VDC  5A   at 110 VDC  3A   at 220 VDC 1A  Contact material AgNi 90 10       Terminal block     Phoenix MVSTBW or equivalent          Maximum wire dimension   2 5 mm   13 14 AWG        Alarm contacts       Number of contacts    3 change over contacts  relays 
26.   L3 8  7 50 51 67 X4  _  x3 a Z    17 3p gt  3P gt   18 3P gt  gt  pe X5  50N 51N 3l gt  gt  gt  gt   X1  1 49   X3  9  He 11  3   10  12  4 T  5 13   gt  gt  gt   14  6  81H 81L  7   gt  lt  df at 15  8 f gt  gt  lt  lt  40      a X2  E T P lt  50BF 5  10 a CBFP 6  11 50NARC 7  ACh  gt   12 a AIChy gt  8  10  13   SOARC  Arcl gt  n  LN  13  L t7     a Blocking and 14  i 18 output matrix 15   f D 16  17   48 V oo  L K   18     Digital J DI  inputs 5j  6l  7                   vamp210appl_3  Figure 10 3 1 Generator transformer unit    Besides the typical generator protection functions the device  includes the transformer earth fault protection  Whatever phase  difference and voltage ratio of the transformer can be  compensated in the relay in case VTs and CTs are on different  sides of the unit transformer     The earth fault protection of the transformer is based on an OR   function between the current inputs lo  and loz    The stator earth fault protection  reach 95   is based on  measuring the fundamental frequency component of the zero  sequence voltage Up with the overvoltage stage  59GN     Via the digital inputs of the relay various signals can be transferred  into the relay  such as information about the operation of a MCB in  the measuring circuit or circuit breaker status information     V210 EN M A011 237    10 4 Trip circuit supervision    10 Applications Technical description       10 4     10 4 1     238    Trip circuit Supervision    Trip circuit supervision is 
27.   Load 0 95 xin   EDly 13         Figure 2 2 4 2  Example of selected fault log    24 V210 EN M A011    Operation and configuration    2 Local panel user interface    2 2 Local panel operations       2 2 5     V210 EN M A011    Operating levels    The relay has three operating levels  User level  Operator level  and Configurator level  The purpose of the access levels is to  prevent accidental change of relay configurations  parameters or             settings   USER level  Use  Possible to read e g  parameter values   measurements and events  Opening  Level permanently open  Closing  Closing not possible                OPERATOR level          Use  Possible to control objects and to change e g   the settings of the protection stages  Opening  Default password is 1       Setting state     Push Os       Closing           The level is automatically closed after 10  minutes idle time  Giving the password 9999 can  also close the level           CONFIGURATOR level          Use  The configurator level is needed during the  commissioning of the relay  E g  the scaling of  the voltage and current transformers can be set    Opening  Default password is 2       Setting state     Push Os       Closing           The level is automatically closed after 10  minutes idle time  Giving the password 9999 can  also close the level           25    2 2 Local panel operations    2 Local panel user interface Operation and configuration  instructions       26    Opening access    1  Push   and on the
28.   On the other hand  faults near the neutral point are rare   because the voltage stress is low     Uof3_ANSI64F3_b  11     Operation area for  Uo gt  and Io gt     Operation area for  Uof3 lt        Figure 5 17 1 The overlapping coverage of winding earth fault protection of  basic protection stages and the third harmonic undervoltage protection stage     V210 EN M A011 105    5 17 100  stator earth fault  protection U0f3 lt   64F3     5 Protection functions Technical description       106    100   coverage of the windings    The  one hundred per cent  in the title is slightly misleading   Actually the 100   coverage is achieved only when this stage is  used together with conventional earth fault protection     The operation range of fundamental frequency earth fault  functions 59N and 51N covers about 95   of the stator windings  starting from the HV end  but never 100   of the windings  The  coverage of the Uois lt  stage is about 10      30   of the windings  but starting from the LV end  i e  the neutral point  Thus the  ranges do overlap as in Figure 5 17 1 and 59N or 51N together  with this 64F3 does cover 100   of the stator windings     Natural 3 harmonic at the neutral point    The voltage a generator is not ideal pure sine wave  There will  exist some small amount of harmonics as well  At the neutral point  there will exists some amount of 3   6   9   12       i e  3n  harmonics  The base frequency and other than 3n harmonics in  phase voltages do cancel each other 
29.   Or loo    CT   50 1   Current injected to the relay s input is 30 mA      Per unit current is   Ipy   0 03 1   0 03 pu 3    Example 6  Per unit to secondary for residual current   Input is lo1 Or loo    CT   50 1   The relay setting is 0 03 pu   3        Secondary current is   Isec   0 03x1   30 mA   Example 7  Secondary to per unit for residual current   Input is locaic    CT   750 5   Currents injected to the relay s IL  input is 0 5 A    l2   IL3   0      Per unit current is   Ipu   0 5 5   0 1 pu   10    Example 8  Per unit to secondary for residual current   Input is locaic    CT   750 5   The relay setting is 0 1 pu   10        gt  If IL2   ILtg   0  then secondary current to l4 is  Isec  0 1x5 0 5A    V210 EN M A011    Technical description    7 Measurement functions 7 10 Primary  secondary and per    unit scaling       7 10 2     V210 EN M A011    Voltage scaling    Primary secondary scaling of line to line voltages                                  Line to line voltage scaling  Voltage measurement mode   Voltage measurement mode     2LL Uo   BLN   U    U VD rrr ine VT ret  secondary   gt  primary PRI SEC PRI SEC  Wsec VWI sec      VW snc   U pri VWI sec  primary   gt  secondary   U sic  U pp    U snc      VT pri V3 VT pri             Example 1  Secondary to primary  Voltage measurement mode is   2LL Uo      VT   12000 110    Voltage connected to the relay s input Ua or Up is 100 V     Primary voltage is Upri   100x12000 110   10909 V    Example 2  Secondary to prima
30.   P   REMOTE port  4 RTS  5  GND  6  5V  8  RXD TXD  N  D RS 485  isolated  REMOTE   screw terminal   1  Signal ground  port  2  Reciever    3  Reciever    4  Transmitter    5  Transmitter    E Glass fibre interface ST   62 5 125 um   REMOTE  port   F Plastic   glass  62 5 125 HFBR 0500 ST   Plastic Rx  um  fibre interface Glass Tx   REMOTE port   G Glass  62 5 125 um    ST HFBR 0500   Glass Rx  plastic fibre interface Plastic Tx   REMOTE port        254    V210 EN M A011       Technical description    11 Connections    11 4 Serial communication    connectors       V210 EN M A011    Order  Code    Connector  type    Communication interface    Pin usage       Ethernet interface and  Serial interface for external  converters only  REMOTE  port     D9S and RJ 45       D connector    1   reserved  2 TX_out TTL  3   RX_in TTL   4   RTS out  TTL  7   GND   9    8V out    RJ 45 connector    1 Transmit     2 Transmit   3 Receive   4 Reserved  5 Reserved  6 Receive    7 Reserved  8 Reserved       10Mbps Ethernet interface  with IEC 61850 and Serial  interface for external  converters only  REMOTE  port     D9S and RJ 45       D connector    1   reserved  2 TX_out TTL  3   RX_in TTL   4   RTS out  TTL  7   GND   9    8V out    RJ 45 connector    1 Transmit     2 Transmit   3 Receive   4 Reserved  5 Reserved  6 Receive    7 Reserved  8 Reserved             100 Mbps Ethernet fibre  interface with IEC 61850  and Serial interface for  external converters only   REMOTE port        D9S and L
31.   Parameter    Value    Unit    Description    Note       LINE FAULT       FItL1  FItL2  FItL3    Fault   trip  status for each  phase    O No fault since fault ClrDly  1 Fault is on       OCt    Combined overcurrent trip  status     FitL1  FItL2 FItL3 0  FitL1 1 orFltL2 1 or FItL3 1       LxTrip     On  Event enabling for  FItL1   3    Events are enabled  Events are disabled    Set       LxTripOff       Off    Event enabling for  FItL1   3    Events are enabled  Events are disabled    Set       OCTrip    On  Off     On  Event enabling for  combined o c trips    Events are enabled  Events are disabled    Set       OCTripOff       Off    Event enabling for  combined o c starts    Events are enabled  Events are disabled    Set       IncFltEvnt    Disabling several events of  the same fault   Several events are enabled      Several events of an    increasing fault is disabled           Set       ClrDly       0    65535             Duration for active alarm  status FitL1  Flt2  FltL3 and  OCt       Set          Set   An editable parameter  password needed      Used with IEC 60870 105 103 communication protocol  The alarm screen will  show the latest if it s the biggest registered fault current  too  Not used with  Spabus  because Spabus masters usually don t like to have unpaired On Off    events           Used with SPA bus protocol  because most SPA bus masters do need an  off event for each corresponding on event     V210 EN M A011    185    6 14 Self supervision    6 Supportin
32.   Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     Figure 5 12 1 shows the functional block diagram of the  overvoltage function stages U gt   U gt  gt  and U gt  gt  gt         Setting Hysteresis Release Delay Enable  U gt s delay events    Figure 5 12 1 Block diagram of the three phase overvoltage stages U gt   U gt  gt   and U gt  gt  gt      91    5 12 Overvoltage protection U gt   59     5 Protection functions    Technical description       Parameters of the overvoltage stages U gt   U gt  gt   U gt  gt  gt   59                                                        Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  s None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   Umax V The supervised value  Max  of  U12  U23 and U31  U gt   U gt  gt   V Pick up value scaled to primary  U gt  gt  gt  value  U gt   U gt  gt    Un Pick up setting relative to Uen Set  U gt  gt  gt   t gt   t gt  gt   t gt  gt  gt  s Definite operation time Set  RIsDly s Release d
33.   The operation time in this example will be 5 seconds  The same  result can be read from Figure 5 29 1 1        500 IEC NI Bon IEC EI  400 400  200 200  100 100  80 80  60 60  40 40  20 20  10 10  m  8   8  Z 6 Z 6   gt  4  gt  4    a     2    2                                                                                                                                                                         0 8 0 8  0 6 0 6  04 04 k 2  k 1  0 2 0 2  0 1 RAI k o5  0 08 A S  9 1s ka  006 0 06  0 05    k 0 1 k 0 2  1 2 3 45678 10 20 1 2 3 45678 10 20  TIset inverseDelayIEC_NI T Iset inverseDelayIEC_EI  Figure 5 29 1 1 IEC normal inverse Figure 5 29 1 2 IEC extremely inverse  delay  delay   sa IEC VI ae IEC LTI  400 400  200 200  k 20  100 100  80 80 k 10  60 60  40 40 k 5  20 20  k   3 3     2 8 2  k 0 2  4 1  0 8 0 8 k1  0 6 0 6  0 4 0 4 k 0 05  0 2 0 2  0 1 0 1  0 08 0 08  0 06 0 06  1 2 3 4 5678 10 20 1 2 3 4 5678 10 20  T Iset inverseDelayIEC_VI V Iset inverseDelayIEC_LTI  Figure 5 29 1 3 IEC very inverse delay  Figure 5 29 1 4 IEC long time inverse  delay     144 V210 EN M A011    Technical description 5 Protection functions 5 29 Inverse time operation       IEEE ANSI inverse time operation    There are three different delay types according IEEE Std C37 112   1996  MI  VI  El  and many de facto versions according Table  5 29 1 3  The IEEE standard defines inverse delay for both trip  and release operations  However  in the device only the trip time  is inverse according
34.   This can be used to verify that the  device is receiving messages    e Communication error counter  Errors    e Communication time out error counter  Tout     e Same information as in the previous menu     V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       V210 EN M A011    EXTENSION PORT X4  pins 7  8 and 5     e Communication protocol for extension port X4  Protocol     e Message counter  Msg    This can be used to verify that the  device is receiving messages    e Communication error counter  Errors     e Communication time out error counter  Tout     e Information of bit rate data bits parity stop bits   This value is not directly editable  Editing is done in the  appropriate protocol setting menus    Ethernet port   These parameters are used by the ethernet interface  For   changing the nnn nnn nnn nnn style parameter values  VAMPSET   is recommended     Ethernet port protocol  Protoc     IP Port for protocol  Port    IP address  IpAdadr     Net mask  NetMsk     Gateway  Gatew     Name server  NameSw     Network time protocol  NTP  server  NTPSvr    TCP Keep alive interval  KeepAlive   MAC address  MAC    IP Port for Vampset  VS Port   Message counter  Msg     Error counter  Errors    Timeout counter  Tout     MODBUS   e Modbus addres for this slave device  Addr   This address has  to be unique within the system    e Modbus bit rate  bit s   Default is  9600     e Parity  Parity   Default is  Eve
35.   VIX Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   lo pu The supervised value according  lo2 the parameter  Input  below   loCalc  lo gt  gt  A Pick up value scaled to primary  lo gt  gt  gt  value  lo gt  gt  gt  gt   lo gt  gt  pu Pick up setting relative to the Set  lo gt  gt  gt  parameter  Input  and the  ass corresponding CT value  t gt  s Definite operation time  for Set  definite time only   Input lo1 X1 7 amp 8  See chapter 11  lo2 X1 9 amp 10  loCalc IL1   IL2   IL3 Set             For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults    There is detailed information available of the eight latest earth  faults  Time stamp  fault current  elapsed delay and setting group     78    V210 EN M A011    Technical description 5 Protection functions 5 10 Directional earth fault  protection l0  gt   67N        Recorded values of the undirectional earth fault stages  8  latest faults  lo gt   lo gt  gt   lo gt  gt  gt   lo gt  gt  gt  gt   50N 51N                                         Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit pu Maximum earth fault curren
36.   Weight  Terminal  Package and Manual  5 2 kg  12 3  Protection functions    For setting values the step size is mentioned if it differs from the  given resolution                       12 3 1  Current protection  Overcurrent stage I gt   50 51   Pick up current 0 10     5 00 x len  Definite time function  DT    Operating time 0 08       300 00 s  step 0 02 s   IDMT function     Delay curve family  DT   IEC  IEEE  RI Prg    Curve type EI  VI  NI  LTI  MI   depends on the family       Time multiplier k 0 05     20 0  except  0 50     20 0 for RXIDG  IEEE and IEEE2  Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms  Reset ratio 0 97  Transient over reach  any t  lt 10   Inaccuracy     Starting  3  of the set value or 5 mA secondary    Operating time at definite time function  1  or  30 ms    Operating time at IDMT function  5  or at least  30 ms                       El   Extremely Inverse  NI   Normal Inverse  VI   Very Inverse  LTI   Long Time Inverse  Ml  Moderately Inverse      The measuring range may limit the scope of inverse delays  See chapter 5 29 for details     Overcurrent stages I gt  gt  and I gt  gt  gt   50 51                             Pick up current 0 10     20 00 x Ian  I gt  gt     0 10     40 00 x lan  I gt  gt  gt    Definite time function     Operating time DT    I gt  gt  0 04      1800 00 s  step 0 01 s     I gt  gt  gt  0 04        300 00 s  step 0 01 s   Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  l
37.   for  example passwords  blockings and mimic configuration  are  normally set only during commissioning     Some of the parameters require the restarting of the relay  This  restarting is done automatically when necessary  If a parameter  change requires restarting  the display will show as Figure 2 4 1     autoboot    Pick PROTOCOL    Change will  cause autoboot    Press  CANCEL       Figure 2 4 1 Example of auto reset display    Press to return to the setting view  If a parameter must be  changed  press again  The parameter can now be set  When    the parameter change is confirmed with ox  a  RESTART   text  appears to the top right corner of the display  This means that  auto resetting is pending  If no key is pressed  the auto reset will  be executed within few seconds     33    2 4 Configuration and parameter 2 Local panel user interface Operation and configuration    setting    instructions       2 4 1     34    Parameter setting  1  Move to the setting state of the desired menu  for example    CONF CURRENT SCALING  by pushing ox  The Pick text  appears in the upper left part of the display   2  Enter the password associated with the configuration level by    pushing   and then using the arrow keys and a  default  value is 0002   For more information about the access levels   please refer to Chapter 2 2 5     3  Scroll through the parameters using and v  A parameter  can be set if the background color of the line is black  If the  parameter cannot be set the parameter 
38.   gt   lp gt  gt  A Pick up value scaled to primary  value  lp gt   lo gt  gt  xIgn Pick up setting Set  Curve Delay curve family   DT Definite time  IEC Inverse time  See chapter 5 29   IEEE Set  IEEE2  RI  PrgN  Type Delay type   DT Definite time  NI Inverse time  See chapter 5 29   VI Set  El  LTI  Paramet  ers  t gt  s Definite operation time  for Set  definite time only   k gt  Inverse delay multiplier  for Set  inverse time only   Dly20x s Delay at 20xlset  Dly4x s Delay at 4xlset  Dly2x s Delay at 2xlset  Dly1x S Delay at 1xlset  Mode Dir Directional mode  67  Set  Undir Undirectional  50 51   Offset 2 Angle offset in degrees Set     9 Measured power angle  U1  Un Measured positive sequence  voltage  A  B  C  D  User s constants for standard Set  E equations  Type Parameters   See chapter 5 29           For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    61    5 5 Directional overcurrent  protection Idir gt   67     5 Protection functions    Technical description       Parameters of the directional overcurrent stages  lgir gt  gt  gt   lgir gt  gt  gt  gt   67                                                              Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select 
39.   i  amp  a  a f2 f1 w  te  a cae poss eg ee   50     8  El INES   F  2   SSheapanen  E 0 Zsuauavauasuraratararar 7 7  0 E  fo         1  Nn  1                     0 05 O10 O15 020 025 030  Time  s  InrushCurrentLoad0    Figure 7 1 Example of various current values of a transformer inrush current     V210 EN M A011 187    7 1 Measurement accuracy    7 Measurement functions Technical description       7 1     188    Measurement accuracy    The specified frequency range for all measurements except  frequency is 45 Hz     65 Hz     Phase current inputs Ic  IL2  Ins                   Measuring range 25mA     250 A  5A   5mA     50 A  1A   Inaccuracy 1 lt 7 5A  0 5   of value or  0 3   of In  I gt 7 5A  3   of value  Squelch level 0 001 x In             The rated input In is 5 Aor 1 A  It is specified in the order code of  the relay     Voltage inputs Ua  Up  Uc   The usage of voltage inputs depends on the configuration  parameter voltage measurement mode  chapter 7 6   For  example  U  is the input for zero sequence voltage Uo if the mode   2LL   Uo  is selected but in mode  3LN  the same input is used  for phase to neutral voltage U s                                         Measuring range 0 160 V   Inaccuracy  0 5   or  0 3 V   Squelch level 0 1 V   Residual current inputs lo1  loz   Measuring range 0 5 xlon   Inaccuracy   lt  1 5 xXlon  0 5   of value or  0 3   of lon  I gt  1 5 Xlon  3   of value   Squelch level 0 0002 x lon             The rated input lon is 5A  1 Aor 0 2 A 
40.   the right direction for earth faults  too   For networks having the maximum  possible earth fault current less than the over current setting  use 67N  the  directional earth fault stages      Im     90            2       ind     cap        res     BASE ANGLE    30      Teaver       cap     ind           90   Idir_angle2  Figure 5 5 1 Example of protection area of the directional overcurrent function     V210 EN M A011    Technical description    5 5 Directional overcurrent  protection Idir gt   67     5 Protection functions       V210 EN M A011    Two modes are available  directional and non directional  Figure  5 5 2   In the non directional mode the stage is acting just like an  ordinary overcurrent 50 51 stage                  90      90       ind   cap   ind   cap   2  _   aaa   i DIRECTIONAL NON DIRECTIONAL  SET SET  VALUE o   VALUE o     gt   gt      res  ee ses  zres   BASE ANGLE   0    TRIP AREA TRIP AREA     cap    tind     cap    tind    90      90   Idir_modeA 15     Figure 5 5 2  Difference between directional mode and non directional mode   The grey area is the trip region     An example of bi directional operation characteristic is shown in  Figure 5 5 3  The right side stage in this example is the stage Idir gt   and the left side is Idir gt  gt   The base angle setting of the Idir gt  is 0    and the base angle of Idir gt  gt  is set to  180       nN        90     ind   cap      pfe  Iyp gt  gt  TRIP AREA  SET SET 3  VALUE VALUE 0     res  tres   BASE ANGLE 
41.   transient reactance for the synchronous machine     x x  a    a    The settings for loss of excitation stages can be derived from  these machine parameters  but there are many practices to do it   Here is one     Radius of the circle  Resistive offset Ros   0 14  X q   X4 2   Reactive offset Xos       X g   Xq 2    All the settings are in per unit     X lt    X 2    123    5 22 Under reactance and loss of 5 Protection functions Technical description    excitation protection X lt   40        124    X w   E where  Zy    Xpu   Reactance  or resistance  per unit    X   Reactance  or resistance  in ohms  Zn   Nominal impedance of the machine  2   fe   ag   where   Sy  Zn   Nominal impedance of the machine  Un   Nominal voltage of the machine  Sn   Nominal power of the machine    Characteristic on power plane    In Figure 5 22 2 the same characteristics as in the previous figure  is drawn on a PQ power plane assuming a constant voltage of 1  PU  The transformation is S   U  Z   where U is the voltage and Z  is the complex conjugate of impedance Z     I UnderReactancePQplane   J 15    NORMAL  OPERATION   AREA OF THE                 Cca    p  ind  v  a     m     fo    lt   H    P     4  r  a   ASI   ind    SFA    Figure 5 22 2 The loss of excitation characteristics drawn on a power plane     Two independent under reactance stages  There are two separately adjustable stages available  X lt  and X lt  lt      V210 EN M A011    Technical description    5 Protection functions    5 22 U
42.  20 1    V210 EN M A011    Technical description    5 Protection functions 5 20 Under impedance protection Z lt      21        V210 EN M A011    Whenever the positive sequence impedance goes inside the  circle  the stage will pick up  The radius Z lt  of the circle and the  definite delay time are the setting parameters     Yj          NORMAL    OPERATION  AREA OF THE            YAMOd ASYAAaY  YAMOd GYVMYOs    7  ind  PELLEN    Figure 5 20 2 Underimpedance characteristics drawn in power plane assuming   that voltage is constant  The trip area is now outside of the circle having radius  U   Z lt   where Z lt  is the pick up setting     Undercurrent blocking    When for some reason voltage collapses but currents remain at  normal load levels  the calculated impedance may fall into the trip  area  Inverted start signal from the most sensitive overcurrent  stage can be used to block the under impedance stages during  abnormal voltages not caused be short circuit faults     Characteristic on a PQ power plane    In Figure 5 20 2 the same characteristics as in the previous figure  is drawn on a PQ power plane assuming a constant voltage of 1  PU  The transformation is S   U  Z     where U is the voltage and Z  is the complex conjugate of impedance Z     The borderline of under impedance trip area in the power plane is  still a circle in origin  but now the trip area is the outside of the  circle  The shape of the normal operation area is totally different   For example the maximum a
43.  3     220    Extension port X4    This is a non isolated RS 485 port for external I O devices  The  port is located in the same rear panel D9S connector X4 as the  local port  but pins  7  8  5  are used instead of the standard RS   232 pins  2  3  5  used by the local port  See Figure 9 1 1                       Parameters  Parameter   Value Unit   Description Note  Protocol Protocol selection for the Set  extension port   None Command line interface for  VAMPSET  SPA bus SPA bus  slave   ProfibusDP Profibus DB  slave   ModbusSla Modbus RTU slave  ModbusTCPs Modbus TCP slave  IEC 103 IEC 60870 5 103  slave   ExternallO Modbus RTU master for  external I O modules  DNP3 DNP 3 0  Msg  0    2   1 Message counter since the   Clr  device has restarted or  since last clearing  Errors 0    2 541 Protocol errors since the Clr  device has restarted or  since last clearing  Tout 0    2 61 Timeout errors since the Clr  device has restarted or  since last clearing  Display of actual 1   communication parameters   speed   bit s  speed DPS D   number of data bits  P   parity  none  even  odd  Default   S   number of stop bits  38400 8N1 for  VAMPSET                         Set   An editable parameter  password needed     Clr   Clearing to zero is possible    1  The communication parameters are set in the protocol specific menus  For  the local port command line interface the parameters are set in configuration    menu     V210 EN M A011    Technical description    9 Communication    9 1 C
44.  3  Block diagram of the directional intermittent transient earth fault  stage lomT gt      Parameters of the directional intermittent transient earth fault  stage loint gt   67NI                          Parameter Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  SCnir Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active   setting group     None   Dix Digital input Set   Vix Virtual input   LEDx LED indicator signal   VOx Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset after a five minute timeout                 lot pu The detected Ip value according  lo2 the parameter  Input  below   Uo A The measured U  value   Uon   100    Uo gt    Uo pick up level  Uon   100   Set  t gt  s Operation time  Actually the Set    number of cycles including faults  x 20 ms  When the time  between faults exceeds 20 ms   the actual operation time will be          longer   lo input lo1Peak lox Connectors X1 7 amp 8 Set  lo2Peak loo Connectors X1 9 amp 10  Intrmt s Intermittent time  When the next Set    fault occurs within this time  the  delay counting continues from                   the previous value        For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     89       5 12 Overvoltage protect
45.  4l      5       0   NEDI  X4 2 Ow  oO oY                X4       RS485    Figure 11 4 2 1 Pin numbering of the Figure 11 4 2 2 Pin numbering of the                               rear communication ports  REMOTE rear communication ports  REMOTE  TTL RS 485   Fibre RX  ee  a A  Q  N  LU J  k a 2  Oop O  a     LL  X         Fibre TX  JA  LN  QN  On  JY  ProfibusDP  Remote fibre  Figure 11 4 2 3 Picture of rear Figure 11 4 2 4 Pin numbering of the  communication port  REMOTE FIBRE  rear communication ports  Profibus    DP     257    11 4 Serial communication 11 Connections Technical description  connectors            E  N E  Col             Figure 11 4 2 5 Dip switches in RS 485 and optic fibre options                                               Dip switch Switch Function Function   number position RS 485 Fibre optics   1 Left 2 wire connection   Echo off   1 Right   4 wire connection   Echo on   2 Left 2 wire connection   Light on in idle state  2 Right   4 wire connection   Light off in idle state  3 Left Termination On Not applicable   3 Right   Termination Off Not applicable   4 Left Termination On Not applicable   4 Right   Termination Off Not applicable       258 V210 EN M A011    Technical description 11 Connections 11 5 Optional two channel arc  protection card                                     11 4 3  X4 rear panel connector  local RS232 and  extension RS485 ports   Rear panel port Pin   Signal   LOCAL   X4 1 No connection  X4 2 Rx in  RS232 local  X4 3 Tx out  RS23
46.  60 ms   Reset time  lt 95 ms   Reset ratio 0 95   Inaccuracy      Starting  2  of the set value or  0 3  of the rated value     Starting  Peak mode   5  of the set value or  2  of the rated value   Sine wave  lt 65 Hz      Operate time  1  or  30 ms             This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts     Directional intermittent transient earth fault stage lont gt   67NI                    Input selection for l    peak signal lo  Connectors X1 7 amp 8  loo Connectors X1 9 amp 10   lo peak pick up level  fixed  0 1 x lon   50 Hz   Uo pickup level 10     100   Uon   Definite operating time 0 12     300 00 s  step 0 02    Intermittent time 0 00     300 00 s  step 0 02    Start time  lt 60 ms   Reset time  lt 60 ms   Reset ratio  hysteresis  for Uo 0 97   Inaccuracy      starting  3  for Up  No inaccuracy defined for l    transients     time  1  or  30 ms         The actual operation time depends of the intermittent behaviour of the fault and the intermittent  time setting     276 V210 EN M A011    Technical description    12 Technical data    12 3 Protection functions       V210 EN M A011    Directional earth fault stages lo    gt   Ibp gt  gt   67N        Pick up current    0 005   8 00 x lon  0 05     20 0 When locaic             Start voltage 1     50  Uon  Input signal lo  input X1 7  amp  8   lo2   input X1 9  amp  10   locate     IitlLo lis   Mode Non directional Sec
47.  9 1 shows a functional block diagram of the Ip gt  earth  overcurrent stage with definite time and inverse time operation  time  Figure 5 9 2 shows a functional block diagram of the lo gt  gt    lo gt  gt  gt  and lo gt  gt  gt  gt  earth fault stages with definite time operation  delay     V210 EN M A011    Technical description    5 Protection functions 5 9 Earth fault protection 10 gt    50N 51N        V210 EN M A011    Input signal selection    Each stage can be connected to supervise any of the following  inputs and signals     e Input Io  for all networks other than rigidly earthed    e Input loz for all networks other than rigidly earthed    e Calculated signal locaic for rigidly and low impedance earthed  networks  locale   l1   lL2   IL3     Additionally the stage lo gt  have two more input signal alternatives  to measure current peaks to detect a restriking intermittent earth  fault     e lo1Peak to Measure the peak value of input lo1   e lo2Peak to Measure the peak value of input loz     Intermittent earth fault detection    Short earth faults make the protection to start  to pick up   but will  not cause a trip   Here a short fault means one cycle or more  For  shorter than 1 ms transient type of intermittent earth faults in  compensated networks there is a dedicated stage lot gt  67NT      When starting happens often enough  such intermittent faults can  be cleared using the intermittent time setting  When a new start  happens within the set intermittent time  t
48.  A Primary scaled upper limit for  idle current  MaxTime s Set  Idle xXIGN   Current limit setting for idle Set  situation  Pickup xIGN Pick up setting for minimum Set  start current  80 ms Maximum transition time for  start recognition  Pickupf2   Pick up value for relative Set  amount of 2    harmonic  liz l                        Set   An editable parameter  password needed   For details of setting ranges see chapter 12 4     163    6 4 Voltage sags and swells    6 Supporting functions Technical description       6 4     164    Voltage sags and swells    The power quality of electrical networks has become increasingly  important  The sophisticated loads  e g  computers etc   require  uninterruptible supply of    clean    electricity  VAMP protection  platform provides many power quality functions that can be used  to evaluate  monitor and alarm on the basis of the quality  One of  the most important power quality functions are voltage sag and  swell monitoring     VAMP provides separate monitoring logs for sags and swells  The  voltage log is trigged  if any voltage input either goes under the  sag limit  U lt   or exceeds the swell limit  U gt    There are four  registers for both sags and swells in the fault log  Each register will  have start time  phase information  duration  minimum  average   maximum voltage values of each sag and swell event   Furthermore  there are total number of sags and swells counters  as well as total timers for sags and swells     The voltage
49.  CT supervisor CTSV       Parameter Value Unit   Description  Measured   ILmax A Maximum of phase currents  value ILmin A Minimum of phase currents  Display Imax gt   A Setting values as primary  Imin lt  values  Recorded   Date   Date of CT supervision  values alarm  Time Time of CT supervision  alarm  Imax A Maximum phase current  Imin A Minimum phase current                   For details of setting ranges see chapter 12 4     V210 EN M A011       Technical description    6 Supporting functions 6 7 Voltage transformer supervision       6 7     V210 EN M A011    Voltage transformer supervision    The device supervises the VTs and VT wiring between the relay  terminals and the VTs  If there is a fuse in the voltage transformer  circuitry  the blown fuse prevents or distorts the voltage  measurement  Therefore  an alarm should be issued   Furthermore  in some applications  protection functions using  voltage signals  should be blocked to avoid false tripping     The VT supervisor function measures the three phase voltages  and currents  The negative sequence voltage U2 and the negative  sequence currentls are calculated  If U2 exceed the Us gt  setting  and at the same time  l2 is less than the lo lt  setting  the function  will issue an alarm after the operation delay has elapsed     Setting parameters of VT supervisor VTSV                                                                  Parameter   Value Unit Default   Description  U2 gt  0 0     200 0  Un 34 6 Upper setting
50.  Curve Delay curve family   DT Definite time  IEC Inverse time  See chapter 5 29   IEEE Set  IEEE2  RI  PrgN  Type Delay type   DT Definite time  NI Inverse time  See chapter 5 29   VI Set  El  LTI  Paramet  ers  t gt  s Definite operation time  for Set  definite time only   k gt  Inverse delay multiplier  for Set  inverse time only   Input lot X1 7 amp 8  See chapter 11  lo2 X1 9 amp 10  loCalc IL1   IL2   IL3 Set  lo1 Peak X1 7 amp 8 peak mode  lo2Peak X1 9 amp 10 peak mode  Intrmt s Intermittent time Set  Dly20x s Delay at 20xlset  Dly4x s Delay at 4xlset  Dly2x S Delay at 2xlset  Dly1x S Delay at 1xlset  A  B  C  D  User s constants for standard Set  E equations  Type Parameters   See chapter 5 29           For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    77    5 9 Earth fault protection 10 gt    50N 51N     5 Protection functions    Technical description       Parameters of the undirectional earth fault stages    lo gt  gt   lo gt  gt  gt   lo gt  gt  gt  gt   50N 51N                                                           Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active  setting group  s None  Dix Digital input Set
51.  DI1     DI6 must be dry   potential free   These inputs use the common internal 48 Vdc  wetting voltage from terminal X3 1  only     NOTE  These digital inputs must not be connected parallel with inputs of an  another device     Label and description texts can be edited with VAMPSET  according the application  Labels are the short parameter names  used on the local panel and descriptions are the longer names  used by VAMPSET     Parameters of digital inputs                Parameter Value Unit   Description Set  DI1     DIG 0 Status of digital input  1  DI COUNTERS  DI1     DIG 0    65535 Cumulative active edge  Set   counter       DELAYS FOR DIGITAL INPUTS    DI1     DIG 0 00     60 00 s Definite delay for both on Set  and off transitions          CONFIGURATION DI1     DI6       Inverted no For normal open contacts Set   NO   Active edge is 0 gt 1  yes For normal closed    contacts  NC   Active edge is 1 gt 0             Alarm display   no No pop up display Set  yes Alarm pop up display is  activated at active DI edge  On event On Active edge event enabled   Set  Off Active edge event disabled  Off event On Inactive edge event Set  Off enabled  Inactive edge event  disabled                         V210 EN M A011 209    8 3 Virtual inputs and outputs    8 Control functions    Technical description       8 3     210                         Parameter Value Unit   Description Set  NAMES for DIGITAL INPUTS  editable with VAMPSET only   Label String of max  Short name for Dis on t
52.  Each controllable object has 2 control signals in matrix                       Output signal Description  Object x Open Open control signal for the object  Object x Close Close control signal for the object       213    8 6 Controllable objects    8 Control functions Technical description       214    These signals send control pulse when an object is controlled by  digital input  remote bus  auto reclose etc     Settings for read only objects  Each read only object has the following settings     Setting Value Description    DI for    obj open    None  any digital Open information  input  virtual input or  virtual output                DI for    obj close    Close information          Timeout for state  changes   If changing states takes longer than the time defined by    Object  timeout    setting  object fails and    Object failure    matrix signal is  set  Also undefined event is generated     Object timeout 0 02     600s                   Controlling with DI  firmware version  gt   5 53     Objects can be controlled with digital input  virtual input or virtual  output  There are four settings for each controllable object   Seiting Active  DI for remote open control  DI for remote close control  DI for local open control  DI for local close control             In remote state          In local state                If the device is in local control state  the remote control inputs are  ignored and vice versa  Object is controlled when a rising edge is  detected from the se
53.  It is specified in the order  code of the relay              Frequency  Measuring range 16 Hz  75 Hz  Inaccuracy  10 mHz             The frequency is measured from voltage inputs Ua and or Up     Power measurements P  Q  S       Inaccuracy  PF  gt  0 5  1   of value or  3 VAsec       Power factor  cos     tano          Inaccuracy  PF  gt 0 5  2   or  0 02       Energy counters E   Eq   E   Eq                 Inaccuracy  PF   gt  0 5  1   of value or  3 Whsecondary  1 h       THD and harmonics       Inaccuracy I  U  gt  0 1 PU  2   units                Update rate At least once a second       V210 EN M A011    Technical description    7 Measurement functions 7 2 Harmonics and Total Harmonic  Distortion  THD        7 2     V210 EN M A011    Harmonics and Total Harmonic  Distortion  THD     The device calculates the THDs as percentage of the base  frequency for currents and voltages    The device calculates the harmonics from the 2    to the 15  of  phase currents and voltages   The 17  harmonic component will  also be shown partly in the value of the 15  harmonic component   This is due to the nature of digital sampling      The harmonic distortion is calculated using equation  15  yn   THD   a   where    1  hy   Fundamental value  h gt  15   Harmonics       Example   hy  100A   hs   10A   h7  3A   h    8A   rup   3  8  _ 13 0        100    For reference the RMS value is   RMS   V100   102  3   8   100 9A       Another way to calculate THD is to use the RMS value as  reference
54.  Negative sequence current I         Figure 5 7 1 Inverse operation delay of current unbalance stage l gt   The    100    longest delay is limited to 1000 seconds   16min 40s      Parameters of the current unbalance stage l2 gt   46                                                     Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group    None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   I2 Ign  lgn   The supervised value   12 gt   lgn   Pick up setting Set  t gt  s Definite operation time Set   Type DT   Type DT Definite time Set  INV Inverse time  Equation 5 7 1   K1 s Delay multiplier  Type  INV  Set             For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults    There is detailed information available of the eight latest faults   Time stamp  unbalance current  elapsed delay and setting group     V210 EN M A011    Technical description    5 Protection functions    5 7 Current unbalance 
55.  Protection functions 5 19 Rate of change of frequency   ROCOF  protection df dt  81R        V210 EN M A011       0 6    ROCOFS_v3       0 5    0 4       0 3          0 2       0 14    Fastest possible operation time setting  s        0 1                                  0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8    Slope setting df dt  Hz s  0 714  Figure 5 19 2 At very sensitive slope settings the fastest possible operation time  is limited according the figure     Inverse operation time characteristics    By setting the second delay parameter tmin smaller than the  operational delay t  an inverse type of operation time  characteristics is achieved    Figure 5 19 3 shows three examples  where the frequency  behaviour is the same as in the first example  but the tmin setting is  0 15 s instead of being equal with t  The operation time depends  of the measured average slope according the following equation    t    np   w where    trrip   Resulting operation time  seconds     SsET   df dt i e  slope setting  hertz seconds     tser   Operation time setting t  Seconds     S   Measured average frequency slope  hertz seconds      The minimum operation time is always limited by the setting  parameter tmin  In the example of the fastest operation time  0 15  s  is achieved when the slope is 2 Hz s or more  The leftmost  curve in Figure 5 19 3 shows the inverse characteristics with the  same settings as in Figure 5 19 4     113    5 19 Rate of change of frequency 5 Protection functions       Te
56.  Un v3  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      104 V210 EN M A011    Technical description 5 Protection functions 5 17 100  stator earth fault  protection U0f3 lt   64F3        5 17  100  stator earth fault protection Uof3 lt    64F3     NOTE  This protection stage is available only in voltage measurement mode   2LL Uo   see chapter 7 6      NOTE  For this function the zero sequence voltage must be measured from the  generator s neutral point and the earth     NOTE  A unit transformer is usually needed between the generator and the  busbar for selective operation of this function     The third harmonic undervoltage stage can be used to detect  earth faults near a high impedance earthed generator s neutral  point or even at the neutral point  These kind of faults are rare   but if a second earth fault would occur in one of the phases the  consequences would be severe  because the first earth fault had  made the network solidly earthed  By using the Uor3 lt  stage such  situation can be avoided     Neutral point is a blind point for conventional earth fault  function    In case there is an earth fault near the neutral point or even at the  neutral point   the residual current and zero sequence voltage  caused by such fault are negligible or even zero  Thus a  conventional earth fault protection based on fundamental  frequency l    and or Up measurement is not able to detect such  faults
57.  and U31  f Hz The supervised frequency value  U f   Calculated Umax f  Uf gt    Pick up setting Set  t gt  s Definite operation time Set                      For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero  F   Editable when force flag is on    V210 EN M A011    Technical description    5 Protection functions    5 13 Volts hertz over excitation  protection Uf gt   24        V210 EN M A011    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults     Time stamp  fault voltage  fault frequency  elapsed delay and  setting group     Recorded values of the volts hertz over excitation stage  U  gt   8 latest faults  U  gt   24                                         Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit   Fault value V Hz  U  Un   Fault voltage  f Hz Fault frequency  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2          95    5 14 Undervoltage protection U1 lt  5 Protection functions Technical description     27P           14     96    Undervoltage protection U  lt   27P     This a special undervoltage protection for generator applications   where the voltage is measured at the generator side of the  generator circuit breaker  There are special self blocking features  for starting up and shutting do
58.  communication delays  A  negative value will compensate  any leading offset of the external  synch source   AAlntv  10000 s   Adapted auto adjust interval for 1   Set     ms correction  AvDrft Lead Adapted average clock drift sign Set  Lag     FilDev  125 ms   Filtered synchronisation                deviation          Set   An editable parameter  password needed       Astronomically a range    11      12 h would be enough  but for political and  geographical reasons a larger range is needed       If external synchoronization is used this parameter will be set automatically        Set the DI delay to its minimum and the polarity such that the leading edge  is the synchronizing edge     V210 EN M A011       Technical description 6 Supporting functions 6 11 Running hour counter       6 11  Running hour counter    This function calculates the total active time of the selected digital  input  virtual I O or output matrix output signal  The resolution is  ten seconds     Running hour counter parameters                               Parameter   Value Unit   Description Note  Runh 0     876000 h Total active time  hours  Set   Note  The label text  Runh  can  be edited with VAMPSET   0    3599 s Total active time  seconds  Set   Starts 0    65535 Activation counter  Set   Status Stop Current status of the selected  Run digital signal  DI Select the supervised signal Set    None  DI1    DI6  Physical inputs  VI1   V14  Virtual inputs  LedAl  Output matrix out signal Al  LedTr  Output
59.  data format   normalized value or scaled  value   DbandEna No Dead band calculation Set  Yes enable flag  DbandCy 100   10000 ms Dead band calculation Set  interval          Set   An editable parameter  password needed     226 V210 EN M A011    Technical description    9 Communication 9 2 Communication protocols       9 2 6     V210 EN M A011    IEC 60870 5 103    The IEC standard 60870 5 103  Companion standard for the  informative interface of protection equipment    provides  standardized communication interface to a primary system  master  system     The unbalanced transmission mode of the protocol is used  and  the device functions as a secondary station  slave  in the  communication  Data is transferred to the primary system using   data acquisition by polling  principle  The IEC functionality  includes the following application functions    e station initialization   e general interrogation   e clock synchronization and   e command transmission    It is not possible to transfer parameter data or disturbance  recordings via the IEC 103 protocol interface     The following ASDU  Application Service Data Unit  types will be  used in communication from the device    ASDU 1  time tagged message   ASDU 3  Measurands     ASDU 5  Identification message   ASDU 6  Time synchronization and   ASDU 8  Termination of general interrogation     The device will accept     e ASDU 6  Time synchronization  e ASDU 7  Initiation of general interrogation and  e ASDU 20  General command     
60.  definite time delay start latest  wnen the measured  value is twenty times the setting  However  there are limitations at  high setting values due to the measurement range  See chapter  5 29 for more details     153    6 1 Event log    6 Supporting functions Technical description       6     6 1     154    Supporting functions    Event log    Event log is a buffer of event codes and time stamps including  date and time  For example each start on  start off  trip on or trip   off of any protection stage has a unique event number code  Such  a code and the corresponding time stamp is called an event  The  event codes are listed in a separate document  Modbus_Profibus_Spabus_event pdf    As an example of information included with a typical event an  overvoltage trip event of the first 59 stage U gt  is shown in the  following table                                         EVENT Description Local   Communication  panel protocols  Code  30E2 Channel 30  Yes Yes  event 2  U gt  trip on Event text Yes No  112 0  Ugn Fault value Yes No  2007 01 31 Date Yes Yes  08 35 13 413 Time Yes Yes  Type  U12 23 31 Fault type Yes No       Events are the major data fora SCADA system  SCADA systems  are reading events using any of the available communication  protocols  Event log can also be scanned using the front panel or  using VAMPSET  With VAMSET the events can be stored to a file  especially in case the relay is not connected to any SCADA  system     Only the latest event can be read when us
61.  firmware    See Chapter 16 Firmware revision history  c None  version 6 firmware      D   4pcs  version 6 firmware      E   None  standard firmware   F   4pcs  standard firmware    Ingress protection rating      IP30  default   l   IP54  option     289    15 Order information    Operation and configuration  instructions       Accessories      Order Code    VEA3CGi  VPA3CG  VSE001PP  VSE002  VSE003  VSE009  VIO 12 AB  VIO 12 AC    VIO 12 AD    VX003 3  VX004 M3  VX007 F3  VA 1 DA 6  VAM 16D    VYX076  VYX077  VYX233  V200WAF    VM690 230    290    Explanation    External ethernet interface module   Profibus interface module   Fiber optic Interface Module  plastic   plastic    RS485 Interface Module   RS485 Interface Module  Ext I O interface   External DeviceNet interface module   RTD Module  12pcs RTD inputs  RS 485 Communication  24 230 Vac dc   RTD mA Module  12pcs RTD inputs  PTC  mA inputs outputs   RS232  RS485 and Optical Tx Rx Communication  24 Vdc   RTD mA Module  12pcs RTD inputs  PTC  mA inputs outputs   RS232  RS485 and Optical Tx Rx Communication  48 230 Vac dc        RS232 programming cable  Vampset  VEA 3CGi   TTL RS232 converter cable  PLC  VEA 3CGi   TTL RS232 converter cable  VPA 3CG    Arc Sensor    External LED module    Raising Frame for 200 serie  Raising Frame for 200 serie  Raising Frame for 200 serie  V200 wall aseembly frame    3 Phase Nominal Voltage Matching Transformer    Note    Cable length 3m  Cable length 3m  Cable length 3m  Cable length 6m  
62.  for VT  supervisor  I2 lt  0 0     200 0  ln 100 0   Lower setting for VT  supervisor  t gt  0 02     600 0 s 0 10 Operation delay  VT on On  Off   On VT supervisor on event  VT off On  Off   On VT supervisor off event  Measured and recorded values of VT supervisor VTSV      Parameter Value Unit   Description  Measured   U2  Un   Measured negative  value sequence voltage  12  ln Measured negative  sequence current  Recorded   Date   Date of VT supervision  values alarm  Time   Time of VT supervision  alarm  U2  Un   Recorded negative  sequence voltage  12  ln Recorded negative  sequence current                For details of setting ranges see chapter 12 4     169    6 8 Circuit breaker condition  monitoring    6 Supporting functions Technical description       6 8     170    Circuit breaker condition monitoring    The relay has a condition monitoring function that supervises the  wearing of the circuit breaker  The condition monitoring can give  alarm for the need of CB maintenance well before the CB  condition is critical     The CB wear function measures the breaking current of each CB  pole separately and then estimates the wearing of the CB  accordingly the permissible cycle diagram  The breaking current is  registered when the trip relay supervised by the circuit breaker  failure protection  CBFP  is activated   See    chapter 5 25 for CBFP and the setting parameter  CBrelay       Breaker curve and its approximation    The permissible cycle diagram is usually available 
63.  front panel   ENTER PASSWORD    a   kk0  v       Figure 2 2 5 1  Opening the access level    2  Enter the password needed for the desired level  the password  can contain four digits  The digits are supplied one by one by    first moving to the position of the digit using and then  setting the desired digit value using A    3  Push Oa     Password handling    The passwords can only be changed using VAMPSET software  connected to the local RS 232 port on the relay     It is possible to restore the password s  in case the password is  lost or forgotten  In order to restore the password s   a relay  program is needed  The serial port settings are 38400 bps  8 data  bits  no parity and one stop bit  The bit rate is configurable via the  front panel                 Command Description   get pwd_break Get the break code  Example  6569403    get serno Get the serial number of the relay  Example   12345              Send both the numbers to your nearest Schneider Electric  Customer Care Centre and ask for a password break  A device  specific break code is sent back to you  That code will be valid for  the next two weeks        Command Description       set pwd_break 4435876 Restore the factory default passwords      4435876    is just an example  The actual  code should be asked from your nearest             Schneider Electric Customer Care Centre         Now the passwords are restored to the default values  See  chapter 2 2 5      V210 EN M A011    Operation and configuration    2 
64.  functions             sesssssssereereeseserrrrrnrreeeee 49  5 3  General features of protection stages                ccceeeeee 50  5 4  Overcurrent protection l gt   50 51            eeeeeeeeeeeeeeeeeeeeeeeeee 53  5 5  Directional overcurrent protection lair gt   67        cccceeeeeeeees 58    V210 EN M A011    Table of Contents       5 6  Voltage restrained controlled overcurrent function ly gt   51V     63   5 7  Current unbalance protection l2 gt   46               cceeeeeeeeeees 67  5 8  Thermal overload protection T gt   49                  ceeeeeeeeeeeeees 70  5 9  Earth fault protection lo gt   5ON 51N              ceeeeeeeeeeeeeeeeeee 74  5 10  Directional earth fault protection log gt   67N         eeeeeeee 79  5 11  Intermittent transient earth fault protection lont gt   67NI    85  5 12  Overvoltage protection U gt   59           eeeeeeteeeeeeeeeeeeeee 90  5 13  Volts hertz over excitation protection U    24  s e    93  5 14  Undervoltage protection U4 lt   27P    0 2    eeeeeeeeeeeeeeeeeeeeeeeeeee 96  5 15  Undervoltage protection U lt   27         ceeeecieeeeteeeeeeeeeeteeee 99  5 16  Zero sequence voltage protection Uo gt   59N           2 102  5 17  100  stator earth fault protection Upis lt   64F3               105  5 18  Overfrequency and underfrequency protection f gt   f lt    COVEN OL  ccdohiseainanschen tenia Adenia RAA 109    5 19  Rate of change of frequency  ROCOF  protection df dt   81R  111    5 20  Under impedance protection Z lt   21            e
65.  indicators   4  RS 232 serial communication port for PC    10 V210 EN M A011    Operation and configuration    2 Local panel user interface 2 1 Relay front panel       2 1 1     V210 EN M A011    Display    The relay is provided with a backlightedt 128x64 LCD dot matrix  display  The display enables showing 21 characters in one row  and eight rows at the same time  The display has two different  purposes  one is to show the single line diagram of the relay with  the object status  measurement values  identification etc   Figure  2 1 1 1   The other purpose is to show the configuration and  parameterization values of the relay  Figure 2 1 1 2               Figure 2 1 1 1 Sections of the LCD dot matrix display    Freely configurable single line diagram   Five controllable objects   Six object statuses   Bay identification   Local Remote selection   Auto reclose on off selection  if applicable    Freely selectable measurement values  max  six values     SO  OU ee N    ked2            Et  5  aM I   hen d TA PAN I  Est Barth  E    E   E    raki i   EAT         ah R  L   H MENG     Figure 2 1 1 2 Sections of the LCD dot matrix display       Main menu column   The heading of the active menu   The cursor of the main menu   Possible navigating directions  push buttons   Measured setting parameter   Measured set value    DOr ee    11    2 1 Relay front panel    2 Local panel user interface Operation and configuration  instructions       Backlight control    Display backlight can be sw
66.  instead of the fundamental frequency value  In the  example above the result would then be 13 0       189    7 3 Demand values    7 Measurement functions    Technical description       7 3     190    Demand values    The relay calculates average i e  demand values of phase currents  IL1  IL2  ILg and power values S  P and Q  The demand time is  configurable from 10 minutes to 30 minutes with parameter   Demand time      Demand value parameters       Parameter    Value    Description    Set       Time    10    30    Unit  min    Demand time  averaging time  Set       Fundamental frequency values                                        ILida A Demand of phase current IL1  IL2da A Demand of phase current IL2  IL3da A Demand of phase current IL3  Pda kW   Demand of active power P  PFda Demand of power factor PF  Qda kvar   Demand of reactive power Q  Sda kVA   Demand of apparent power S  RMS values   ILida A Demand of phase current IL1  IL2da A Demand of phase current IL2  IL3da A Demand of phase current IL3                   V210 EN M A011       Technical description    7 Measurement functions 7 4 Minimum and maximum values       7 4     V210 EN M A011    Minimum and maximum values    Minimum and maximum values are registered with time stamps  since the latest manual clearing or since the device has been  restarted  The available registered min  amp  max values are listed in  the following table                                            Min  amp  Max Description  measurement  I
67.  is less than 40 ms  a trip signal is  issued when the operation time is full     When the time between successive faults is more than 40 ms  the  stage will release between the faults and the delay counting is  restarted from zero for every single fault and no trip will be issued   For such cases the intermittent setting can be used  Figure 5 11 2  shows an example of how the intermittent setting works  The  upper start and trip signals are a case with zero intermittent  setting  The lower signals are another case with intermittent  setting 0 12 s  The operation time setting is 0 14 s in both cases  corresponding to seven 20 ms time slots with faults    87    5 11 Intermittent transient earth fault 5 Protection functions Technical description  protection IOINT gt   67NI        The time between the second and the third fault exceeds the  release time   intermittent time  Thus the operation delay counter  is cleared in both cases  with zero intermittent time and with 0 12  s intermittent time     The fourth and the next faults do occur after release time but  within release time   intermittent time  Thus the operation delay  counter is advanced at every fault in the case the intermittent time  setting is more than 100 ms  the lower status lines in the figure   and finally a trip signal is issued at t 0 87 s     When faults do occur more than 20 ms apart each other  every  single fault will increment the operation delay counter by 20 ms  In  this example the actual operation ti
68.  is used  for sampling rate synchronization when no voltage is present  The  local network frequency can also be manually given for the relay     Apart from the FFT calculations  some protection functions also  require the symmetrical components to be calculated for obtaining  the positive  negative and zero phase sequence components of  the measured quantity  For example  the function of the  unbalanced load protection stage is based on the use of the  negative phase sequence component of the current     Figure 4 2 1 shows a hardware block diagram of the relay  The  main components are the current and voltage inputs  digital input  elements  output relays  A D converters and the microcomputer  and a power supply unit     Figure 4 2 2 shows the inputs and outputs of a general protection  function  The FFT block is calculating the fundamental frequency  phasors and also harmonics used by some protection functions   The block matrix is used for simple interlocking   More complex  interlocking is done with the user s programmable logic   The  output matrix is used to connect the pick up and trip signals from  protection blocks to the output relays and indicators     Figure 4 2 3 shows a block diagram of a basic overcurrent or  overvoltage function with definite and inverse operation time     V210 EN M A011 47    4 2 Principles of numerical 4 Introduction Technical description  protection techniques       Display and  keyboard    Antialiasing 16 bit   filter A D converter   Trip 
69.  k 2    0 06 k 0 5 k 1  1 2 3 4 5678 10 20  T Iset inverse  DelayIEEE2_EI    Figure 5 29  1 14 IEEE2 extremely  inverse delay       RI and RXIDG type inverse time operation    These two inverse delay types have their origin in old ASEA   nowadays ABB  earth fault relays     The operation delay of types RI and RXIDG depends on the  measured value and other parameters according Equation  5 29 1 4 and Equation 5 29 1 5  Actually these equations can only  be used to draw graphs or when the measured value   is constant  during the fault  Modified versions are implemented in the relay    for real time usage   Equation 5 29 1 4  RI    k  0 236    T pickup    Equation 5 29 1 5 RXIDG    0 339             ri       temg  5 8    1 35In     pickup  t   Operation delay in seconds  k   Users multiplier      Measured value  lnickup   User   s pick up setting    V210 EN M A011    Technical description    5 Protection functions 5 29 Inverse time operation       V210 EN M A011    Example for Delay type RI       4       The operation time in this example will be 2 3 seconds  The same  result can be read from Figure 5 29 1 15    Example for Delay type RXIDG    k   0 50       4pu   lhickup   2 PU    k   0 50      4pu  lbickup   2 PU  0 5  tee                  gt  a   2 3  0 339     0 236    tang   5 8 1 35In   5239       The operation time in this example will be 3 9 seconds  The same  result can be read from Figure 5 29 1 16        eG RI ant RXIDG  400          400          200 200       100  80 
70.  matrix configuration for trip circuit  supervision with one wet digital input     V210 EN M A011 243    10 4 Trip circuit supervision    10 Applications Technical description       244    Example of dimensioning the external resistor R   Uaux   110Vdc 5  10     Auxiliary voltage with tolerance  Short time voltage dips  more than 5   are not critical from the trip circuit  supervision point of view     Relay type for the K1 auxiliary relay     Phoenix Contact 2941455   EMG 17 REL KSR 120 21 21 LC Au  Ux   120 Vac dc  20     10    Coil voltage of the auxiliary relay K1  lk   6mA    Nominal coil current of the auxiliary relay K1  Pcpcol   SOW  Rated power of the open coil of the circuit breaker     Umin   Uaux 5    104 5 V  Umax   Uaux   10  121V  Uximin   Uk  10     96 V  Rk1coil   Uxi Ik4   20 kQ    IkiMIN   Ukimin Rxtcoi   4 8 MA    K1MAX   Uk  max Rk1Coil   6 1 mA  Rcscoil   U  aux P   242 Q     The external resistance value is calculated using Equation  10 4 1 4     Equation 10 4 1 4    U   U kimin    R   MIN   I kimin  R    104 5     96  0 0048   242   1529 Q  By selecting the next smaller standard size we get 1 5 KQ        R    Coil    The power rating for the external resistor is calculated using  Equation 10 4 1 5  This equation includes a 100   safety margin  to limit the maximum temperature of the resistor  because modern  resistors are extremely hot at their rated maximum power     Equation 10 4 1 5   P  i a  R   P   2 0 0061 2x1500   0 11 W   Select the next bigger
71.  matrix out signal Tr  LedA  Output matrix out signal LA  LedB  Output matrix out signal LB  LedC  Output matrix out signal LC  LedDR Output matrix out signal DR  VO1   VO6 Virtual outputs  Started at Date and time of the last  activation  Stopped at Date and time of the last  inactivation                      Set   An editable parameter  password needed     Set    An informative value which can be edited as well     V210 EN M A011 181    6 12 Timers    6 Supporting functions Technical description       6 12     182    Timers    The VAMP protection platform includes four settable timers that  can be used together with the user s programmable logic or to  control setting groups and other applications that require actions  based on calendar time  Each timer has its own settings  The  selected on time and off time is set and then the activation of the  timer can be set to be as daily or according the day of week  See  the setting parameters for details   The timer outputs are available  for logic functions and for the block and output matrix          not in use    Day sh     en  ty  dl  Mody               Tuesday U  Wednesday a E Ln aaa  Thusdy aaa a a U S  Fiddy S U aaa  Saturday aaa a a a a  Sudy aaa aaa a a a a a  Mints    a G ake  Le G Ss  MIWES Lf L ee ia    SatSun  U  U  Figure 6 12 1 Timer output sequence in different modes                                The user can force any timer  which is in use  on or off  The  forcing is done by writing a new status value  No forcin
72.  menu selection with parameter  Protocol   See chapter  9 1     V210 EN M A011 223    9 2 Communication protocols 9 Communication Technical description       Parameters    Parameter   Value Unit   Description Note  Mode Profile selection Set  Cont Continuous mode  Reqst Request mode  bit s 2400 bps   Communication speed from  the main CPU to the  Profibus converter   The  actual Profibus bit rate is  automatically set by the  Profibus master and can be  up to 12 Mbit s    Emode Event numbering style   Set   Channel Use this for new  installations    Limit60   The other modes are for   NoLimit  compatibility with old  systems    InBuf bytes   Size of Profibus master s 1  3   Rx buffer   data to the  master   OutBuf bytes   Size of Profibus master s 2  3   Tx buffer   data from the  master   Addr 1     247 This address has to be Set  unique within the Profibus  network system   Conv Converter type     No converter recognized 4   VE Converter type  VE  is  recognized  Set   An editable parameter  password needed   Clr   Clearing to zero is possible  1  In continuous mode the size depends of the biggest configured data offset of  a data item to be send to the master  In request mode the size is 8 bytes   2  In continuous mode the size depends of the biggest configured data offset of  a data to be read from the master  In request mode the size is 8 bytes   3  When configuring the Profibus master system  the length of these buffers are  needed  The device calculates the lengths acc
73.  min    demand    Parameter to select the type of the S  registered values    Collect min  amp  max of one cycle values    Collect min  amp  max of 200 ms average values  Collect min  amp  max of 1 s average values  Collect min  amp  max of 1 minute average  values   Collect min  amp  max of demand values  see  chapter 7 3             ResetDays    Reset the 31 day registers 5          ResetMon          Reset the 12 month registers S                This is the fundamental frequency rms value of one cycle updated every 20    ms     192    V210 EN M A011       Technical description    7 Measurement functions 7 6 Voltage measurement mode       7 6     V210 EN M A011    Voltage measurement mode    Depending on the application and available voltage transformers   the relay can be connected either to line to line voltages or phase   to ground voltages  The configuration parameter  Voltage  measurement mode  must be set according the used connection     The available modes are     e  2LL Uo   The device is connected to line to line voltages U12 and U23  and to zero sequence voltage Up  The phase to ground  voltages are calculated  See Figure 7 6 1 and Figure 7 6 2   The network must use only three wires  Any neutral wire must  not exist    e   3LN   The device is connected to phase to ground voltages U_1  U2  and U 3  The zero sequence voltage is calculated  See Figure  7 6 3  There may exist a neutral wire     The overvoltage protection is always based on the line to line  voltage r
74.  mo  oa  e N     oo 1      O   TIIT  g euowoon 2 THON  Q  A   gt   o   Fi     N  a  g  a  4                            Figure 11 10 1 Connection example of VAMP 210     V210 EN M A011 269    12 1 Connections 12 Technical data Technical description       12  Technical data                         12 1  Connections  12 1 1  Measuring circuitry  Rated phase current 5 A  configurable for CT secondaries 1     10 A     Current measuring range 0   250 A    Thermal withstand 20 A  continuously   100 A  for 10 s   500 A  for 1 s     Burden  lt 0 2VA  Rated phase current  optional  1 A  configurable for CT secondaries 1     10 A     Current measuring range 0   50 A    Thermal withstand 20 A  continuously   100 A  for 10 s   500 A  for 1 s     Burden  lt  0 1 VA  Rated residual current  optional  5 A  configurable for CT secondaries 1     10 A     Current measuring range 0   25 A    Thermal withstand 4A  continuously   20 A  for 10 s   100 A  for 1 s     Burden  lt 0 2VA  Rated residual current 1 A  configurable for CT secondaries 0 1     10 0 A     Current measuring range 0   5A    Thermal withstand 4 A  continuously   20 A  for 10 s   100 A  for 1 s     Burden  lt 0 1 VA  Rated voltage Un 100 V  configurable for VT secondaries 50     120 V     Voltage measuring range 0     160 V  100 V 110 V     Continuous voltage withstand 250 V    Burden  lt 0 5VA  Rated frequency fn 45   65 Hz  Terminal block  Maximum wire dimension     Solid or stranded wire 4 mm   10 12 AWG                 12 1 2
75.  ms Time stamp  time of day  Fit  Ug   Minimum fault voltage  n  EDly   Elapsed time of the operating time  setting  100    trip  PreFlt  Ug   Supervised value before fault  1 s  n average value   SetGrp 1 Active setting group during fault  2                      Zero sequence voltage protection Up gt    59N     The zero sequence voltage protection is used as unselective  backup for earth faults and also for selective earth fault protections  for generators having a unit transformer between the generator  and the busbar     This function is sensitive to the fundamental frequency component  of the zero sequence voltage  The attenuation of the third  harmonic is more than 60 dB  This is essential  because 3n  harmonics exist between the neutral point and earth also when  there is no earth fault     Whenever the measured value exceeds the user s pick up setting  of a particular stage  this stage picks up and a start signal is  issued  If the fault situation remains on longer than the user s  operation time delay setting  a trip signal is issued     Measuring the zero sequence voltage    The zero sequence voltage is either measured with three voltage  transformers  e g  broken delta connection   one voltage  transformer between the generator s neutral point and earth or  calculated from the measured phase to earth voltages according  to the selected voltage measurement mode  see chapter 7 6      e Phase  the zero sequence voltage is calculated from the phase  voltages and therefo
76.  panel user interface    Operation and configuration       18                                                                                                                                           instructions  Main Number Description ANSI Note  menu of code  menus   lop gt  6 1st directional earth fault stage 67N 4  lop gt  gt  6 2nd directional earth fault stage 67N 4  loint gt  4 Transient intermittent E F 67NI 4  U gt  4 1st overvoltage stage 59 4  U gt  gt  3 2nd overvoltage stage 59 4  U gt  gt  gt  3 3rd overvoltage stage 59 4  Uf gt  3 Overexcitation stage volt hertz 24 4  U lt  4 1st undervoltage stage 27 4  U lt  lt  3 2nd undervoltage stage 27 4  U lt  lt  lt  3 3rd undervoltage stage 27 4  U1 lt  4 1st positive sequence undervoltage stage 27P 4  U1 lt  lt  4 2nd positive sequence undervoltage stage 27P 4  Uo gt  3 1st residual overvoltage stage 59N 4  Uo gt  gt  3 2nd residual overvoltage stage 59N 4  Uof3 lt  3 100  stator earth fault stage 64F3 4  P lt  3 1st reverse and underpower stage 32 4  P lt  lt  3 2nd reverse and underpower stage 32 4  Q lt  5 Under excitation stage 40 4  Z lt  3 1st underimpedance stage 21 4  Z lt  lt  3 2nd underimpedance stage 21 4  X lt  3 1st loss of excitation stage 40 21 4  X lt  lt  3 2nd loss of excitation stage 40 21 4  f gt  lt  4 1st over under frequency stage 81 4  f gt  gt  lt  lt  4 2nd over under frequency stage 81 4  f lt  4 1st underfrequency stage 81L 4  f lt  lt  4 2nd underfrequency stage 81L 4  dfdt 3 Rate of cha
77.  possible by the following ways    o through the local HMI   o through a remote communication   o through a digital input   The connection of an object to specific output relays is done via an  output matrix  object 1 6 open output  object 1 65 close output    There is also an output signal    Object failed     which is activated if  the control of an object fails     Object states  Each object has the following states                                Setting Value Description  Undefined  00   Object state bel Actual state of the object  Close  Undefined  11        Basic settings for controllable objects  Each controllable object has the following settings                                                  Setting Value Description  DI for    obj open    None  any digital Open information  DI for    obj close    input  virtual input or   Close information  DI for    obj ready    virtual output Ready information  Max ctrl pulse length 0 02     600 5 Pulse length for open and  ca close commands  Completion timeout Timeout of ready  0 02     600 s indication  Object control Open Close Direct object control       If changing states takes longer than the time defined by    Max ctrl   pulse length    setting  object fails and    Object failure    matrix signal  is set  Also undefined event is generated     Completion timeout    is  only used for the ready indication  If    DI for    obj ready    is not set    completion timeout has no meaning     Output signals of controllable objects 
78.  power quality functions are located under the  submenu    U        Setting parameters of sags and swells monitoring                                      Parameter   Value Unit Default   Description   U gt  20    150   110 Setting value of swell limit   U lt  10    120   90 Setting value of sag limit   Delay 0 04     1 00 s 0 06 Delay for sag and swell  detection   SagOn On  Off   On Sag on event   SagOff On  Off   On Sag off event   SwelOn On  Off   On Swell on event   SwelOf On  Off   On Swell off event                V210 EN M A011    Technical description    6 Supporting functions    6 4 Voltage sags and swells       V210 EN M A011    Recorded values of sags and swells monitoring                          Parameter   Value Unit Description  Recorded   Count   Cumulative sag counter  values Total   Cumulative sag time counter  Count   Cumulative swell counter  Total   Cumulative swell time  counter  Sag  swell   Date   Date of the sag swell  logs 1   4   Time   Time stamp of the sag swell  Type   Voltage inputs that had the  sag swell  Time s Duration of the sag swell  Min1  Un Minimum voltage value  during the sag swell in the  input 1  Min2  Un Minimum voltage value  during the sag swell in the  input 2  Min3  Un Minimum voltage value  during the sag swell in the  input 3  Avet  Un Average voltage value  during the sag swell in the  input 1  Ave2  Un Average voltage value  during the sag swell in the  input 2  Ave3  Un Average voltage value  during the sag swell in the  i
79.  relays  current and    voltage inputs hese    relays    SPAbus  Modbus     Profibus DP   fibre connectors       X Protection  Calculation of functions Block matrix Output matrix  symmetric  components  Output relay  FFT calculation control    Amplitude and  phase shift of  base freqency  component    32 samples   cycle    Digital 6 18   inputs       Settings  Figure 4 2 2 Block diagram of signal processing and protection software     1VISblock2    Start    Register  event       Setting Delay Definite inverse Inverse time Multiplier Enable  Ps time characteristic events    Figure 4 2 3 Block diagram of a basic protection function     48 V210 EN M A011    Technical description    5 Protection functions 5 1 Maximum number of protection    stages in one application       5     Deli    Protection functions    Each protection stage can independently be enabled or disabled  according to the requirements of the intended application     Maximum number of protection stages  in one application       2     The device limits the maximum number of enabled stages to about  30  depending of the type of the stages  For more information   please see the configuration instructions in chapter 2 4     List of protection functions                                                                                           IEEE  IEC symbol Function name  ANSI code   50 51 3I gt   3l gt  gt   3l gt  gt  gt  Overcurrent protection  67 lair gt s lair gt  gt   lar gt  gt  gt   lair gt  gt  gt  gt  Direct
80.  self  blocking can not be disabled     Initial self blocking    When the voltage U  has been below the block limit  the stages  will be blocked until the pick up setting has been reached     V210 EN M A011    Technical description    5 Protection functions 5 14 Undervoltage protection U1 lt    27P        V210 EN M A011    Figure 5 14 1 shows an example of low voltage self blocking     A _ The positive sequence voltage U  is below the block limit   This is not regarded as an under voltage situation     B The positive sequence voltage U  is above the block limit  but below the pick up level  However  this is not regarded  as an under voltage situation  because the voltage has  never been above the pick up level since being below the  block limit                            C Voltage is OK  because it is above the pick up limit   D This is an under voltage situation   E Voltage is OK   F This is an under voltage situation   G Voltage is under block limit and this is not regarded as an  under voltage situation   H SameasB     Voltage is OK   J  SameasG  K     Voltage is OK   U  UlunderSelfBlocking  A    E I K  dead band          a ERE EPE  AE AOT Ee ES  U  lt  setting  block limit  time  U  lt  under voltage state             Figure 5 14 1 Positive sequence under voltage state and block limit     Temporary self blocking at very low currents    Further the pick up can be delayed by using setting I lt BIk  When  the maximum of the three measured phase currents is less than 1    of 
81.  stages Up gt  and Up gt  gt   59N        Zero sequence voltage setting range    1     60  Uon       Definite time function     Operating time    0 3     300 0 s  step 0 1 s             Starting UoCalc  83LN mode     Operate time    Start time Typically 200 ms   Reset time  lt 450 ms   Reset ratio 0 97   Inaccuracy      Starting  2  of the set value or  0 3  of the rated value     1 V   1  or  150 ms       100   stator earth fault protection Upis lt   64F3        Pick up setting range    1    50         Definite time function     Operating time    0 5     30 0 minutes       Start time  Reset time  Reset ratio     lt 2s   lt 4s  1 05          Fundamental low voltage block limit   U12 and U23     Blocked when U42 and Uz   lt  65   of nominal       Inaccuracy     Starting    Operating time at definite time function           1   units   1  or  2 s             When pick up setting is below 5   reset value is less than set value  0 5   unit    stage is used     NOTE  The voltage measurement mode must be  2LL U   when this protection    279    12 3 Protection functions 12 Technical data Technical description          12 3 3  Frequency protection  Overfrequency and underfrequency protection stages f gt  lt  and  f gt  gt  lt  lt   Frequency measuring area 16 0   75 0 Hz  Current and voltage meas  range 45 0     65 0 Hz  Frequency stage setting range 40 0     70 0 Hz  Low voltage blocking 10     100  Un     Definite time function    operating time 0 10        300 0 s  step 0 02 s   S
82.  stages have two setting groups  Changing between setting  groups can be controlled manually or using any of the digital  inputs  virtual inputs  virtual outputs or LED indicator signals  By  using virtual I O the active setting group can be controlled using  the local panel mimic display  any communication protocol or  using the inbuilt programmable logic functions     Forcing start or trip condition for testing  The status of a protection stage can be one of the followings   e Ok        The stage is not detecting any fault     e Blocked The stage is detecting a fault but blocked by  some reason     e Start The stage is counting the operation delay   e Trip The stage has tripped and the fault is still on     The blocking reason may be an active signal via the block matrix  from other stages  the programmable logic or any digital input   Some stages also have inbuilt blocking logic  For example an  under frequency stage is blocked if voltage is too low  For more  details about block matrix  see chapter 8 5     Forcing start or trip condition for testing purposes    There is a  Force flag  parameter which  when activated  allows  forcing the status of any protection stage to be  start  or  trip  for a  half second  By using this forcing feature any current or voltage  injection to the relay is not necessary to check the output matrix  configuration  to check the wiring from the output relays to the  circuit breaker and also to check that communication protocols are  correctly 
83.  standard size  for example 0 5 W     When the trip contacts are still closed and the CB is already open   the resistor has to withstand much higher power  Equation  10 4 1 3  for this short time     P   121 2 1500   9 8 W    V210 EN M A011    Technical description 10 Applications 10 4 Trip circuit supervision       A 1 W resistor should be selected to withstand this short time peak  power  However  if the trip relay can be closed for longer time than  a few seconds  a 20 W resistor should be used     10 4 2  Trip circuit supervision with DI19 and DI20    The benefits of this scheme is that no external resistor is needed     The drawbacks are  that two digital inputs from two separate  groups are needed and two extra wires from the relay to the CB  compartment is needed  Additionally the minimum allowed  auxiliary voltage is 48 Vdc  which is more than twice the threshold  voltage of the dry digital input  because when the CB is in open  position  the two digital inputs are in series     e The first digital input is connected parallel with the auxiliary  contact of the open coil of the circuit breaker    e Another auxiliary contact is connected in series with the  circuitry of the first digital input  This makes it possible to  supervise also the auxiliary contact in the trip circuit    e The second digital input is connected in parallel with the trip  contacts    e Both inputs are configured as normal closed  NC     e The user s programmable logic is used to combine the digit
84.  the alarm limit current 6  kA  For such currents the decrement is one     A   1    V210 EN M A011 173    6 8 Circuit breaker condition 6 Supporting functions Technical description  monitoring       Local panel parameters of CBWEAR function                                                                                  Parameter Value Unit   Description Set  CBWEAR STATUS  Operations left for  Al1L1   Alarm 1  phase L1  Al1L2   Alarm 1  phase L2  AliL3   Alarm 1  phase L3  Al2L1   Alarm 2  phase L1  Al2L2   Alarm 2  phase L2  Al2L3   Alarm 2  phase L3  Latest trip  Date Time stamp of the latest trip  time operation  IL1 A Broken current of phase L1  IL2 A Broken current of phase L2  IL3 A Broken current of phase L3  CBWEAR SET  Alarm1  Current 0 00     100 00 kA   Alarmi current level Set  Cycles 100000   1 Alarm1 limit for operations   Set  left  Alarm2  Current 0 00     100 00 kA   Alarm2 current level Set  Cycles 100000   1 Alarm2 limit for operations   Set  left  CBWEAR SET2  Al1On On    Alarm1 on  event enabling   Set  Off  Al1 Off On    Alarm1 off  event enabling   Set  Off  Al2On On    Alarm2 on  event enabling   Set  Off  Al2Off On    Alarm2 off  event enabling   Set  Off  Clear a Clearing of cycle counters Set  Clear             Set   An editable parameter  password needed     The breaker curve table is edited with VAMPSET     174 V210 EN M A011    Technical description    6 Supporting functions    6 9 Energy pulse outputs       6 9     V210 EN M A011    Energy puls
85.  the fault detection  time and operation time of the trip contacts     Under excitation stage Q lt   40                 Settings      Q P0   Reactive power limit at P 0    100     0  xSen     Q P80   Reactive power limit at P 80    100     0  xSen   Definite time function      Operating time 0 08       300 00 s  step 0 02 s   Start time Typically 60 ms   Reset time 0 06     300 00 s  step 0 02 s   Retardation time  lt 50 ms   Reset ratio 0 98  x Sen    Inaccuracy      Starting  3  of set value or  0 5  of Sen    Operating time  1  or  30 ms                   This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts     V210 EN M A011 281    12 3 Protection functions 12 Technical data Technical description       Under reactance and loss of excitation stages X lt   X lt  lt   40                                Trip area radius setting range 0 05     2 00 xZn   Resistive offset Ros    2 00      2 00 xZn   Reactive offset Xos    2 00      2 00 xZn   Definite time function      Operating time 0 08        300 00 s  step 0 02 s   Start time  lt 80 ms   Reset time 0 08     300 00 s  step 0 02 s   Reset ratio 1 05   Inaccuracy      Starting  4   of set value or  0 01 x Zn    Operating time at definite time function  1   or  30 ms          This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts     Reverse pow
86.  the standard but the release time is constant   The operation delay depends on the measured value and other  parameters according Equation 5 29 1 2  Actually this equation  can only be used to draw graphs or when the measured value   is  constant during the fault  A modified version is implemented in the  relay for real time usage     Equation 5 29  1 2    t k  4 __ 3    I C    ese                                  t   Operation delay in seconds  k   Users multiplier      Measured value  pickup   Users pick up setting  A B C   Constant parameter according Table 5 29 1 3   Table 5 29 1 3 Constants for IEEE ANSI inverse delay  equation  Dalay wos Parameter  LTI Long time inverse 0 086 0 185 0 02  LTVI Long time very inverse 28 55 0 712 2  Long time extremely  LTEI inverse 64 07 0 250 2  MI Moderately inverse 0 0515 0 1140 0 02  VI Very inverse 19 61 0 491 2  El Extremely inverse 28 2 0 1217 2  STI Short time inverse 0 16758 0 11858 0 02  Short time extremely  STEI   Pverse 1 281 0 005 2                         V210 EN M A011 145    5 29 Inverse time operation 5 Protection functions Technical description       Example for Delay type  Moderately inverse  Ml       k   0 50      4pu  lpickup   2 pu  A   0 0515  B   0 114  C   0 02  t  0 50  E Hos  1 9  4y     1  2    The operation time in this example will be 1 9 seconds  The same  result can be read from Figure 5 29 1 8     aaa IEEELTI gu  IEEE LTVI  400 400  200  100  80  60  40    20    delay  s   delay  s     0 2 0 2    0 1  0 
87.  timeout Set  Fault Fault identifier number for  IEC 103  Starts   trips of all  stages   TagPos Position of read pointer  Chn Active channel  ChnPos Channel read position  Fault numbering  Faults Total number of faults  GridFlts Fault burst identifier  number  Grid Time window to classify Set                faults together to the same  burst           Set   An editable parameter  password needed     V210 EN M A011          Technical description    9 Communication 9 2 Communication protocols       9 2 7     9 2 8     V210 EN M A011    DNP 3 0    The relay supports communication using DNP 3 0 protocol    The following DNP 3 0 data types are supported    binary input   binary input change   double bit input   binary output   analog input   e counters   Additional information can be obtained from the    DNP 3 0 Device  Profile Document    for VAMP 2xx    DNP 3 0 communication is activated via menu selection  RS 485  interface is often used but also RS 232 and fibre optic interfaces  are possible                                                     Parameters  Parameter   Value Unit   Description Set  bit s bps   Communication speed Set  4800  9600  default   19200  38400  Parity Parity Set  None  default   Even  Odd  SlvAddr 1  65519 An unique address for the   Set  device within the system  MstrAddr 1  65519 Address of master Set  255 default  LLTout 0     65535 ms   Link layer confirmation Set  timeout  LLRetry 1 255 Link layer retry count Set  1 default  APLTout 0     65535 ms
88.  to activate the virtual input or select    Vloff    to  deactivate the virtual input    27    2 3 Operating measures    2 Local panel user interface    Operation and configuration  instructions       2 3 2     28    Measured data    The measured values can be read from the P  E    and U menus  and their submenus  Furthermore  any measurement value in the  following table can be displayed on the main view next to the  single line diagram  Up to six measurements can be shown                                                                                                                                Value Menu Submenu Description   P P POWER Active power  kW    Q P POWER Reactive power  kvar    S P POWER Apparent power  kVA       P POWER Active power angle        P F  P POWER Power factor   f P POWER Frequency  Hz    Pda P 15 MIN POWER Active power  kW    Qda P 15 MIN POWER Reactive power  kvar    Sda P 15 MIN POWER Apparent power  kVA    Pfda P 15 MIN POWER Power factor   fda P 15 MIN POWER Frequency  Hz    PL1 P POWER PHASE 1 Active power of phase 1  kW    PL2 P POWER PHASE 1 Active power of phase 2  kW    PL3 P POWER PHASE 1 Active power of phase 3  kW    QL1 P POWER PHASE 1 Reactive power of phase 1  kvar    QL2 P POWER PHASE 1 Reactive power of phase 2  kvar    QL3 P POWER PHASE 1 Reactive power of phase 3  kvar    SL1 P POWER PHASE 2 Apparent power of phase 1  kVA    SL2 P POWER PHASE 2 Apparent power of phase 2  kVA    SL3 P POWER PHASE 2 Apparent power of phase 3  kVA 
89.  to exit the Force function     11  Push to return to the main menu     NOTE  All the interlockings and blockings are bypassed when the force control    32    is used     V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       2 4     V210 EN M A011    Configuration and parameter setting    The minimum procedure to configure a relay is    1  Open the access level  Configurator   The default password  for configurator access level is 2    2  Set the rated values in menu  CONF  including at least current  transformers  voltage transformers and generator ratings  Also  the date and time settings are in this same main menu    3  Enable the needed protection functions and disable the rest of  the protection functions in main menu  Prot     4  Set the setting parameter of the enable protection stages  according the application    5  Connect the output relays to the start and trip signals of the   enabled protection stages using the output matrix  This can be   done in main menu  DO   although the VAMPSET program is  recommended for output matrix editing    Configure the needed digital inputs in main menu  DI     7  Configure blocking and interlockings for protection stages  using the block matrix  This can be done in main menu  Prot    although VAMPSET is recommended for block matrix editing     D    Some of the parameters can only be changed via the RS 232  serial port using the VAMPSET software  Such parameters 
90.  up value scaled to primary  value  I gt  xIgn Pick up setting Set  Curve Delay curve family   DT Definite time  IEC Inverse time  See chapter 5 29   IEEE Set  IEEE2 Pre 1996  RI  PrgN  Type Delay type   DT Definite time  NI Inverse time  See chapter 5 29   Vi Set  El  LTI  Paramet  ers  t gt  s Definite operation time  for Set  definite time only   k gt  Inverse delay multiplier  for Set  inverse time only   Dly20x s Delay at 20xlset  Dly4x s Delay at 4xlset  Dly2x s Delay at 2xlset  Dly1x s Delay at 1xlset  A  B  C  D  User s constants for standard Set  E equations  Type Parameters   See chapter 5 29                       For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    55    5 4 Overcurrent protection I gt   50 51     5 Protection functions    Technical description       56    Parameters of the overcurrent stages I gt  gt   I gt  gt  gt   50 51                                                     Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active Set  setting group  i None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  vox Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages an
91.  value      Activation  block limit     Operating time at definite time function        5  of the set value   1  or  30 ms          If one of the phase voltages is below sag limit and above block limit but another phase voltage    drops below block limit  blocking is disabled     Voltage interruptions                   Voltage low limit  U1  10  120   Definite time function  DT     Operating time  lt 60 ms  Fixed   Reset time  lt 60 ms   Reset ratio  1 03   Inaccuracy      Activation 3  of the set value             285    13 Abbreviations and symbols Operation and configuration    instructions       13     286    ANSI  CB  CBFP    cos     CT   CTperi  CTsec  Dead band  DI   DO   DSR    DST    DTR    FFT    Hysteresis    lseT  loset  loin    loon    IEEE  IEC 103    LAN    Abbreviations and symbols    American National Standards Institute  A standardization organisation   Circuit breaker   Circuit breaker failure protection   Active power divided by apparent power   P S   See power factor PF    Negative sign indicates reverse power    Current transformer   Nominal primary value of current transformer   Nominal secondary value of current transformer   See hysteresis    Digital input   Digital output  output relay   Data set ready  An RS232 signal  Input in front panel port of VAMP relays    to disable rear panel local port     Daylight saving time  Adjusting the official local time forward by one hour    for summer time     Data terminal ready  An RS232 signal  Output and alway
92.  voltage blocking is checking  the maximum of line to line voltages        This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts     280 V210 EN M A011    Technical description 12 Technical data 12 3 Protection functions       Rate of change of frequency  ROCOF  stage df dt gt   81R        Setting range 0 2   10 0 Hz s  Definite time function     operating time 0 14      10 00 s  Minimum delay  for inverse time delay 0 14     10 00 s  Start time Typically 140 ms  Reset time  lt  operating time   150 ms  Retardation time  lt 90 ms   Reset ratio 1   Inaccuracy      starting  0 05 Hz s     operating time  1  or  30 ms                   The fastest operation time is more than specified  if the setting is less than 0 7 Hz s  This is the  instantaneous time i e  the minimum total operational time including the fault detection time and  operation time of the trip contacts                 12 3 4  Impedance and power protection  Under impedance stages Z lt   Z lt  lt   21   Pick up setting range 0 05     2 00 xZn  Definite time function     Operating time 0 08       300 00 s  step 0 02 s   Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms  Reset ratio 1 05  Inaccuracy     Starting  4   of set value or  0 01 x Zn    Operating time at definite time function  1   or  30 ms                   This is the instantaneous time i e  the minimum total operational time including
93.  when the operation delay time  has elapsed  a trip signal is issued  In this definite time mode the  second delay    parameter  minimum delay  tmin  must be equal to the operation  delay parameter  t      If the frequency is stable for about 80 ms and the time t has  already elapsed without a trip  the stage will release     ROCOF and over under frequency stages    One difference between over  under frequency and df dt function  is the speed  In many cases a df dt function can predict an  overfrequency or underfrequency situation and is thus faster than  a simple overfrequency or underfrequency function  However  in  most cases a standard overfrequency and underfrequency stages  must be used together with ROCOF to ensure tripping also in case  the frequency drift is slower than the slope setting of ROCOF     Definite operation time characteristics    Figure 5 19 1 shows an example where the df dt pick up value is  0 5 Hz s and the delay settings are t 0 60 s and tyin 0 60 s   Equal times t    tmin will give a definite time delay characteristics   Although the frequency slope fluctuates the stage will not release  but continues to calculate the average slope since the initial pick   up  At the defined operation time  t   0 6 s  the average slope is  0 75 Hz s  This exceeds the setting  and the stage will trip     At slope settings less than 0 7 Hz s the fastest possible operation  time is limited according the Figure 5 19 2     112 V210 EN M A011    Technical description    5
94. 0 08       300 00 s  step 0 02 s           Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms   Reset ratio 0 97   Transient over reach  any t  lt 10        Inaccuracy     Starting         Operate time     3  of set value   1  or  30 ms                This is the instantaneous time i e  the minimum total operational time including the fault detection    time and operation time of the trip contacts     Current unbalance stage I2 gt   46        Setting range    Definite time characteristic     operating time   Inverse time characteristic     1 characteristic curve     time multiplier K      upper limit for inverse time  Start time   Reset time   Reset ratio   Inaccuracy      Starting     Operate time          2     70   step 1    1 0     600 0s s  step 0 1     Inv   1 50 s  step 1   1000s  Typically 200 ms   lt 450 ms   0 95     1    unit   5  or  200 ms          Stage is operational when all secondary currents are above 250 mA     Thermal overload stage T gt   49        Overload factor    Alarm setting range    Time constant Tau   Cooling time coefficient   Max  overload at  40   C  Max  overload at  70   C  Ambient temperature  Resetting ratio  Start  amp  trip   Inaccuracy      operating time       0 1     2 40 x len  Step 0 01   60     99    step 1     2     180 min  step 1    1 0     10 0 xTau  step 0 1   70     120  len  Step 1   50 100  len  step 1    55     125   C  step 1     0 95     5  or  15             275    12 3 Protection functions 12 T
95. 08  0 06    0 1  0 08  0 06       1 2 3 4 5678 10 20 1 2 3 4 5678 10 20  T Iset inverseDelayIEEE1_LTI V Iset    inverseDelayIEEE1_LTVI    Figure 5 29 1 5 ANSI IEEE long time Figure 5 29 1 6 ANSI IEEE long time  inverse delay very inverse delay    146 V210 EN M A011    Technical description    5 Protection functions    5 29 Inverse time operation       V210 EN M A011    600  400    200  100  80  60    40    20    Doo    delay  s     0 8  0 6    0 4    0 2    0 1  0 08  0 06    1 2 3 4 5678 10 20    T Iset inverseDelayIEEE1_LTEI    Figure 5 29  1 7 ANSIJEEE long time  extremely inverse delay    600  400    200    100    60  40    20    delay  s     0 2    0 1  0 08  0 06    1 2 3 4 5678 10 20  T Iset inverseDelayIEEE1_STI    Figure 5 29 1 9 ANSI IEEE short time  inverse delay    IEEE LTEI       IEEE STI          a IEEE MI    400                200       100                            20 k 20       k 10                   k 5             delay  s     2 k 2                      k 0 5             0 2       0 1  0 08  0 06                                                             1 2 3 4 5678 10 20  T Iset inverseDelayIEEE1_MI    Figure 5 29  1 8 ANSI IEEE moderately  inverse delay       IEEE STEI    600  400                   100                                                       delay  s                                   0 2 k 20       0 1 k 10    0 08 SRD RET ke    0 06 k 0 5  k 1   _ k 2 k 5                                                             1 2 3 4 5678 10 20  TIs
96. 2 Dielectric test voltages               ccccceeeeeeeeeeeeeeeeeeeeeees 272  12 2 3 Mechanical tests xa  r aie as wes 272  12 2 4 Environmental COnditionS                cceeeceeeeeeeeeeeeeeees 272  T 22S  CASING eoit eea ra a re EE 272  27 6 PACK AGG  nein a a ONA 273   12 3  Protection fUNCTIONS                   cccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 273  12 3 1 Current DrOtS COM  cecca cansg3cuee casdueestavGegecces eerste 273  12 3 2  Voltage protection                    ccccceeeeeeeeeeeeeeeeeeeeeeeees 278  12 3 3 Frequency protection                 ccccceeeeeeesseeeeeeeeeeeeees 280  12 3 4 lmpedance and power protection                   eeeeeee 281  12 3 5 Second harmonic function           eee eeeeeeteeeeeeeeees 282  12 3 6 Fifth harmonic fUNCTION              cceeeeeeeeeeeeeeetteeeeeeeees 282  12 3 7 Circuit breaker failure protection                  ceeeee 283  12 3 8 Arc fault protection stages  Option                 ceeee 283   12 4  Supporting functions site  eh cieceticteteteininie ictal etigteledtsase 284  12 4 1 Disturbance recorder  DR            cccceeeeeeeeteeeeeeeees 284  12 4 2 Inrush current detection  68             eeeeeeeeeseeeeeeeeees 284  12 4 3  Transformer supervision               cceeeeeeeeeeeeeeeeeeeeees 284    6 V210 EN M A011    Table of Contents       V210 EN M A011    12 4 4 Voltage sags  amp  swells             ccccceeeeeeeeeeeeeeeeeeeeeeees 285  12 4 5 Voltage interruptions                ccccceeeeeeeeeeeeeeeeeeeeeeeees 285  13  Abbrev
97. 2 local  X4 4 DTR out   8 V   X4 5 GND  X4 6 No connection  X4 7 B  RS485 extension port  X4 8 A  RS485 extension port  X4 9 No connection                   NOTE  In the VAMP relays a positive RS485 voltage from A  to B  corresponds  to bit value    1     In X4 connector the RS485 extension port is not  galvanically isolated     11 5  Optional two channel arc protection  card    NOTE  When this option card is installed  the parameter  Arc card type  has  value  2Arc Bl O   Please check the ordering code in chapter 15     NOTE  If the slot X6 is already occupied with the DI19 DI20 digital input card  this  option is not available  but there is still one arc sensor channel available   See chapter 11 6  The optional arc protection card includes two arc sensor channels   The arc sensors are connected to terminals X6  4 5 and 6 7   The arc information can be transmitted and or received through  digital input and output channels  This is a 48 V dc signal     Connections     X6  1 Binary input  BI    X6  2 Binary output  BO    X6  3 Common for BI and BO   X6  4 5 Sensor 1   X6  6 7 Sensor 2    The binary output of the arc option card may be activated by the  arc sensors or by any available signal in the output matrix  The   binary output can be connected to an arc binary input of another  VAMP protection relay or manager     V210 EN M A011 259    11 6 Optional digital I O card 11 Connections Technical description     DI19 D120        11 6     260    Optional digital I O card  DI19 D
98. 29in 2x VYX199 needed       21  0 83    Semi flush          B 7S Panel mounting    288 V210 EN M A011    Technical description    15 Order information    12 4 Supporting functions       15  Order information    When ordering  please  state the ordering code     VAMP 210 ORDERING CODE    V 210  CILITICILIC I                                       Note      Optional hardware  A H available     Optional hardware  A G available    V210 EN M A011             Nominal current  A     1   1A   5   5A   Nominal earth fault currents loi  amp  lo2  A   A   5A amp 5A   B   5A amp 1A   C   1A amp 5A   D 1A amp 1A    Frequency  Hz   7   Standard relay    Supply voltage  V     40   265Vac de    18   36Vdc    40   265Vac dce   ARC Protection     36Vdc   ARC Protection    40   265Vac dc   DI19  DI20 Optional    18   36Vdc   DI19  DI20 Optional    moov    1        Optional hardware   A   None   B    Plastic Plastic serial fibre interface   C   Profibus interface   D   _ RS 485 interface  4 wire    E   Glass Glass serial fibre interface   F   _ Rx Plastic Tx Glass serial fibre interface   G   Rx Glass Tx Plastic serial fibre interface   H   _ RJ 45 10Mbps ethernet interface   M   RJ 45 10Mbps ethernet inc  IEC 61850   O   LC 100 Mbps ethernet fibre interface inc  IEC 61850    RJ 45 100Mbps ethernet interface inc  IEC 61850     2xLC 100 Mbps ethernet fibre interface inc  IEC 61850    2x RJ 45 100 Mbps ethernet interface inc  IEC 61850    P  R  S  Analog Outputs  amp  firmware   A   Nore  version 3
99. 4 1 5   The rated coil  voltage of the auxiliary relay is selected according the rated  auxiliary voltage used in the trip circuit  The operating voltage  range of the relay should be as wide as possible to cover the  tolerance of the auxiliary voltage     In this application using the other wet inputs for other purposes is  not limited unlike  when using the dry inputs     V210 EN M A011    Technical description 10 Applications 10 4 Trip circuit supervision        V x   110 Vdc         Alarm relay  for trip  circuit failure    Trip Circuit  failure alarm        relay compartment       circuit breaker compartment       close control    Relay K1  Phoenix Contact   EMG 17 REL KSR 120 21 21 LC Au  Coil  96     127 V  20 kQ   Width  17 5 mm   Assembly  EN 50022 mounting rail     V aux  CLOSE COIL       TCS1Dl  closed         Figure 10 4 1 5 Trip circuit supervision using one of the VAMP 200 series  internally wetted digital input  DI1   DI6  and auxiliary relay K1 and an external  resistor R  The circuit breaker is in the closed position  The supervised circuitry  in this CB position is double lined  The digital input is in active state when the  trip circuit is complete     DIGITAL INPUTS    DIGITAL INPUTS  1 0 HC 0 5 s off off On 0    Figure 10 4 1 6 An example of digital input DI1 configuration for trip circuit  supervision with one wet digital input        OUTPUT MATRIX       connected     connected and latched    T1 T2 T3 T4 A1 A2    D    Figure 10 4 1 7 An example of output
100. 5 POlts    c cnssscebecteeedsesdpneessacthentennsseetesdeesdseeteeeteeenneets 259  11 5  Optional two channel arc protection Card            eee 259  11 6  Optional digital I O card  DI19 DI20                eeeeeee 260  11 7  External I O extension modules                     eeeeeeeeeeeeeeees 261  11 7 1 External LED module VAM 16D                     eeeeeee 261  11 7 2 External input   output module                   ceeeeeeeees 261  11 8  Block diagrams  1  5 detectois paste doe tenesdeheeanedadabededeneenssbde 267  11 9  Block diagrams of option modules                    ceeeeeeeeee 268  11 9 1 Optional arc protection                ccccceeeeeeeeeeeeeteeeeeeeees 268  11 9 2 Optional DI19 DI20               eeeeeccceeeeeeeeeeseseeeeeeeeeeeees 268  11 10  Connection examples            cccccceeeeeeeeeeeeeeeeeeeeeeeees 269   12  Technical data wiicciissscncecivenininnicnnaeericinieinennnienwevucinanewenss 270   12 COMMOGU GINS nsin e aaa 270  12 1 1 Measuring circuitry ce cco coca cect eines ener Cocesvetieiicuctimecendss 270  12 1 2  Auxiliary VOItAQC             ceeeeeeeeeeeceeeeeeeeeeeeeeeeeeeeeeeees 270   2  PSS  Digital INPUTS  manene perenne ener 271  Te TA Enp contact Sann ETA 271  12 1 5 Alarm COMaCe cnc eines edi eeaiie eh ededalds 271  12 1 6 Arc protection interface  Option                  ceeeeee 271   12 2  Tests and environmental ConditionS                ccccceeee 272  12 2 1  Disturbance tests               cccccseccceeeeeeeeeeeeeeeeeeeeeeeeees 272  12 2 
101. 99xlgn  The average load current before the fault has been 0 99 pu    e EDly 81   The elapsed operation delay has been 81  of the setting 0 60  s   0 49 s  Any registered elapsed delay less than 100    means that the stage has not tripped  because the fault  duration has been shorter than the delay setting    e SetGrp 1    The setting group has been 1  This line can be reached by       K    pressing Mid and several times      V210 EN M A011    Operation and configuration    2 Local panel user interface 2 2 Local panel operations       2 2 3     V210 EN M A011    Setting groups    Most of the protection functions of the relay have two setting  groups  These groups are useful for example when the network  topology is changed frequently  The active group can be changed  by a digital input  through remote communication or locally by  using the local panel     The active setting group of each protection function can be  selected separately  Figure 2 2 3 1 shows an example where the  changing of the I gt  setting group is handled with digital input one   SGrpDI   If the digital input is TRUE  the active setting group is  group two and correspondingly  the active group is group one  if  the digital input is FALSE  If no digital input is selected  SGrpDI         the active group can be selected by changing the value of the  parameter SetGrp     group     AV P I gt  STATUS    Status  SCntr  TCntr  SetGrp  SGrpDI  Force    Figure 2 2 3 1  Example of protection submenu with setting grou
102. A1  A2 and A3   2 making contacts  relays A4 and A5   1 change over contact  IF relay              Rated voltage 250 V ac dc  Continuous carry 5A   DC breaking capacity  L R 40ms    at 48 VDC  1 3 A   at 110 VDC  0 4 A   at 220 VDC 0 2 A       Contact material    AgNi 0 15 gold plated       Terminal block    Phoenix MVSTBW or equivalent          Maximum wire dimension  2 5 mm   13 14 AWG        Arc protection interfac    e  option        Number of arc sensor inputs  Sensor type to be connected  Operating voltage level  Current drain  when active  Current drain range    2  VA1DA  12 Vdc   gt 11 9mA    1 3   31 mA  NOTE  If the drain is outside the  range  either sensor or the wiring is defected        Number of binary inputs    1  optically isolated              Operating voltage level  48 Vdc  Number of binary outputs 1  open collector   Operating voltage level  48 Vdc       output without an external amplifier     NOTE  Maximally three arc binary inputs can be connected to one arc binary    271                12 2 Tests and environmental 12 Technical data Technical description  conditions             12 2  Tests and environmental conditions  12 2 1  Disturbance tests   Emission  EN 50081 1      Conducted  EN 55022B  0 15   30 MHz     Emitted  CISPR 11  30     1 000 MHz   Immunity  EN 50082 2      Static discharge  ESD  EN 61000 4 2  class III    6 kV contact discharge  8 kV air discharge      Fast transients  EFT  EN 61000 4 4  class III  2 kV  5 50 ns  5 kHz         Surge E
103. C          D connector    1   reserved   2   TX_out TTL  3   RX_in TTL  4   RTS out  TTL  7 GND   9    8V out    Fiber connector   TX Upper LC   connector  RX Lower LC   connector          255    11 4 Serial communication    connectors    11 Connections    Technical description       256    Order  Code    Communication interface    Connector  type    Pin usage       100Mbps Ethernet interface  with IEC 61850 and Serial  interface for external  converters only  REMOTE  port     D9S and RJ 45    D connector    1   reserved   2   TX_out  TTL  3   RX_in TTL   4   RTS out  TTL  7   GND   9    8V out    RJ 45 connector    1 Transmit     2 Transmit   3 Receive   4 Reserved  5 Reserved  6 Receive    7 Reserved  8 Reserved       100 Mbps Ethernet fibre  interface with IEC 61850    LC connector from  top     Port 2 Tx    Port 2 Rx    Port 1 Tx    Port 1 Rx             100Mbps Ethernet interface  with IEC 61850          1 Transmit   2 Transmit   3 Receive   4 Reserved  5 Reserved  6 Receive   7 Reserved  8 Reserved          NOTE  In the VAMP relays RS485 interfaces a positive voltage from Tx  to Tx  or  Rx  to Rx  does correspond to the bit value    1     In X5 connector the  optional RS485 is galvanically isolated     NOTE  In 2 wire mode the receiver and transmitter are internally connected in  parallel  See a table below     V210 EN M A011       Technical description    11 Connections 11 4 Serial communication  connectors       V210 EN M A011                     111     on 211      X
104. COM _   Internal fault relay  common connector  17 a 17  IFNC Internal fault relay  normal closed connector  ig O 18  IFNO Internal fault relay  normal open connector   NXS    251    11 1 Rear panel view    11 Connections    Technical description                                                                                                                                                                         Terminal X3  No  Symbol Description  1 1  48V Internal wetting voltage for digital inputs 1     6  2 2 DIt Digital input 1  3 3 DI2 Digital input 2  4 4 DIS Digital input 3  5 5 DI4 Digital input 4  6 6 DI5 Digital input 5  7 7 DI6 Digital input 6  8 aie      9 9 A1 COM  Alarm relay 1  common connector  40 10  A1NO Alarm relay 1  normal open connector  11  A1NC Alarm relay 1  normal closed connector  m 12  T2 Trip relay 2  14 13   T2 Trip relay 2  3 14 iTi Trip relay 1  14 15  T1 Trip relay 1  15 16      16 17  Uaux Auxiliary voltage  17 18  Uaux Auxiliary voltage  18  Symbol Description  Bl External arc light input  BO Arc output  COM Common for BI and BO  S1 gt   Arc sensor 1  positive connector    S1 gt   Arc sensor 1  negative connector    S2 gt   Arc sensor 2  positive connector    S2 gt   Arc sensor 2  negative connector                                    Arc sensor itself is polarity free    Terminal X6 with DI19 DI20 option                                     No    Symbol Description   1 DI19 Digital input 19   2 DI19 Digital input 19   3 DI20 Digital input 20 
105. D2 Be SEA DUS iis eeo Sa Magica e a 225  9 2 5  IEC 60870 5 101 is csscccsnpastednnptatetodvasieaetyeabeianaanebers 226  9 2 6  IEC 60870 5 103 di cosscustnotavsicesintigtiamiecnastiniantis 227  927 DNP 3 Oir E E E 229  9 2 8  External I O  Modbus RTU master                0 00 229  PoE Ol OOO ree aneti ieii pei aaeain 230  AOA EEN E e ce tad EE 232   TO AD PliGatlO nS iisisiccctiiscsieducncidnad  stuisatianwecad  stcevadeaanasadictcdanteates 234  10 1  Directly connected generator                eeeeeeeeeeeeeeeeeeeeeeeeee 235  10 2  Directly connected generator with unearthed generator  MEU alas enaar E A A ied ANAA 236  10 3  Generator transformer unit           sssssseeessesseserrrrrrreeseerrree 237  10 4  Trip circuit supervision    csseseeeieteae are Oeste 238   10 4 1  Trip circuit supervision with one digital input           238  10 4 2  Trip circuit supervision with DI19 and DI20             245    Table of Contents       11  CONC CIOS vais sian tvawecandetwecenteavereududeenauccdseievindnanendudceteuiiansuat 249  11 1  Rear panel view tiene cote owiehe a cane eee oe 249  11 2  Auxiliary voltage   0    e cece eeeeeenee teeter ee eeeeeeeeeeeeeeeeeeeeeeees 253  DIS POUIDULTSlAY Sy  nnise a 253  11 4  Serial communication Connectors                  ceeeeeeeeeeeeeees 253   11 4 1  Front panel CONNECHOTM                ccceeeeeeeeeeeeeeeeeeeeeees 253  11 4 2 Rear panel connector X5  REMOTE              e 254  11 4 3 X4 rear panel connector  local RS232 and extension  RS48
106. DST  rules added for system clock   HMI changes     Order of the first displays changed   1 measurement  2  mimic  3  title    timeout does not apply if the first 3 displays are  active           293    16 Revision history Operation and configuration  instructions       294 V210 EN M A011         Customers Care Center  http   www schneider electric com ccc    Schneider Electric   35 rue Joseph Monier   92506 Rueil Malmaison  FRANCE   Phone   33  0  1 41 29 70 00  Fax   33  0  1 41 29 71 00    www schneider electric com  Publication version  V210 EN M A011       Publishing  Schneider Electric  12 2012       2012 Schneider Electric  All rights reserved    
107. Disables rear local communication    Height 40mm  Height 60mm  Height 100mm    690V  gt 230V   400V  gt 110V    V210 EN M A011    Technical description    16 Revision history 12 4 Supporting functions       16     V210 EN M A011    Revision history    Manual revision history    Manual version    Description          V210 EN M A011       The first version          Firmware revision history       Firmware  version    Description       3 66    Non volatile value storage  E  PROM  updated        3 68    Info display v  spontaneous alarm display conflict  updated        6 13    A major update  Older versions of VAMPSET parameter  files are not compatible and must NOT be used   Numerous new features has been added     e several new protection stages  e two setting groups for protection stages    e temperature measurement and supervising using  external Modbus modules    e digital I O extension using external Modbus modules   e user s programmable logic   e user configurable interactive mimic display   e language support   Latin alphabet    e EC 60870 5 103  DNP 3 0 communication protocols    e Supported for internal Ethernet adaptor  See  Communication interface    H    in Chapter 15  Order  information         6 21    lO   gt  sector mode characteristics improved   IEC 60870 5 101 added           6 62       Uof8 lt  correction    Unit transformer correction    Transient Intermittent  67NI  protection function added   RMS mode to I gt  added    Programmable curve  Operation delay  
108. FANG 2  VOWAGS scaling nann teehee een 205   8  Control TUncCion cicccccciciccccceciecccccctescscceescscccceicscccecccsccceeces 208  8 1  Output HOLA Sesh ecisat Posie blicesdiceadeited detested atuted deeMeted Mercedes 208  6 2   Digita MPU S  lt intictecstaceisisicie a tical ete el cee et tere al tues  209  8 3  Virtual inputs and CUTOUTS  icsccc sees coce ccerceen dace cen ccencevndeeten 210  8 4  COUTTS etc set wa cae cari ne aviv ania a darie aecesic ee 211  8 9  Blocking Malik nc2sceseteic eesti eae cscs eie cael ase 212  8 6  Controllable ODjCCtS ic   cesccc cc ccceceeecccendeannecocecnceseeinacties 213   8 6 1  Local Remote Selection                  cceceeeeeeeeeeeeeeeeteees 215  6 7  gt  LOGIC TUMCHONS Siicict tticcecetttatee E saete olteate 215   9  Communication cicecccecieccicecteccicectececceedecedcaedececenetecedenedencecees 216   9 1  Communication ports               cccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeteeee 216  9 1 1  Local port X4       sssssesesssennnnnessesssrrrrrnrnssserrrrennnnneeee 217  9 1 2  Remote port X5     sssssssssssenrressserrrrrrnrnnnsserrrrrnnrrnnset 219  9 1 3  Extension port X4       ccccccceeeeeeeeeceeeceeeeeeeeeeeeeeseeees 220  9 1 4  Ethernet port            cccccccceeeeeeesssseseeeceeeeeeeeeeeeseeeeeees 221   9 2  Communication PFOLOCOISicx cee eessceee cout cetera ceendae 222  9 2 1  PC communication iss acsssa cincinnati sia ri itn 222  9 2 2  Modbus TCP and Modbus RTU                  eeeeee 222  Fee PrOD S DIP a E Raat cette eae 223  
109. FtransientFig3   WAV ao AAV VAVAVAVA Seta     UL                            0 50 100 150 200  Time  ms     Figure 5 11 1 Typical phase to earth voltages  residual current of the faulty  feeder and the zero sequence voltage Up during two transient earth faults in  phase L1  In this case the network is compensated     Direction algorithm    The function is sensitive to the instantaneous sampled values of  the residual current and zero sequence voltage  The selected  voltage measurement mode has to include a direct  Uo  measurement     lo pick up sensitivity   The sampling time interval of the relay is 625 us at 50 Hz  32  samples cycle   The l    current spikes can be quite short compared  to this sampling interval  Fortunately the current spikes in cable  networks are high and while the anti alias filter of the relay is  attenuates the amplitude  the filter also makes the pulses wider   Thus  when the current pulses are high enough  it is possible to  detect pulses  which have duration of less than twenty per cent of  the sampling interval  Although the measured amplitude can be  only a fraction of the actual peak amplitude it doesn t disturb the  direction detection  because the algorithm is more sensitive to the  sign and timing of the lo transient than sensitive to the absolute  amplitude of the transient  Thus a fixed value is used as a pick up  level for the lo     Co ordination with Up gt  back up protection    Especially in a fully compensated situation  the zero sequen
110. I20     NOTE  When this option card is installed  the parameter  Arc card type  has  value  Arc 2DI   With DI19 DI20 option only one arc sensor channel is  available  Please check the ordering code in chapter 15     NOTE  If the slot X6 is already occupied with the two channel arc sensor card   chapter 11 5   this option is not available     The DI19 DI20 option enables two more digital inputs  These  inputs are useful in applications where the contact signals are not  potential free  For example trip circuit supervision is such  application  The inputs are connected to terminals X6 1     X6 2 and    X6 3     X6 4    Connections   X6 1 DI19   X6 2 DI19   X6 3 DI20   X6 4 DI20   X6 5 NC  X6 6 L   X6 7 L     V210 EN M A011    Technical description 11 Connections 11 7 External I O extension modules       11 7  External I O extension modules  11 7 1  External LED module VAM 16D    The optional external VAM 16D led module provides 16 extra led   indicators in external casing  Module is connected to the serial port  of the relays front panel  Please refer the User manual VAM 16 D   VM16D ENxxx for details     11 7 2  External input   output module    The relay supports an optional external input output modules used  to extend the number of digital inputs and outputs  Also modules  for analogue inputs and outputs are available  The following types  of devices are supported     e Analog input modules  RTD   e Analog output modules  mA output   e Binary input output modules    EXTENSI
111. L1  IL2  IL3 Phase current  fundamental frequency value   IL1RMS  IL2RMS  Phase current  rms value  IL3RMS  lo1  lo2 Residual current  U12  U23  U31 Line to line voltage  Uo Zero sequence voltage  f Frequency  P Q  S Active  reactive  apparent power  ILida  IL2da  IL8da Demand values of phase currents  ILida  IL2da  IL8da Demand values of phase currents  rms values   rms value   PFda Power factor demand value          The clearing parameter  ClrMax  is common for all these values           Parameters  Parameter   Value Description Set  ClrMax Reset all minimum and maximum values S  Clear                      191    7 5 Maximum values of the last 31  days and twelve months    7 Measurement functions    Technical description       7 5     Maximum values of the last 31 days    and twelve months    Some maximum and minimum values of the last 31 days and the  last twelve months are stored in the non volatile memory of the  relay  Corresponding time stamps are stored for the last 31 days   The registered values are listed in the following table                                   Measurement   Max   Min Description   IL1  IL2  IL3 X Phase current  fundamental frequency value   lo1  lo2 X Residual current   S xX Apparent power   P X X Active power   Q X X Reactive power       The value can be a one cycle value or an average according  parameter  Timebase      Parameters of the day and month registers       Parameter    Value    Description    Set       Timebase    20 ms  200 ms  1s  1
112. Leki  27  2 3 2  Measured Calas xascic  cazcucscsavceaseeet canes taceeesesesceeekaseass 28  2 3 3  Reading event register                 cccccceeeeeeeseseeeeeeeeeees 31  2 3 4  Forced control  Force                   cccceeeeeeeesseeeeeeeeeeeees 32  2 4  Configuration and parameter setting                  ccceeeeeeee 33  2 4 1  Parameter Sein ese  sacs ceceewel cock eves swesewatcediavadameenetins 34  2 4 2  Setting range limits                ceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 35  2 4 3  Disturbance recorder menu DR                   eeeeeeeeeeees 35  2 4 4  Configuring digital inputs DI    eeeeeeeeeeees 36  2 4 5  Configuring digital outputs DO              eeeeeeeeees 36  2 4 6  Protection Menu Prot              c  ccccceeeeeeeeeeeeseeeeeeeeeees 37  2 4 7  Configuration menu CONF   ssssssssssssssssesssssssrrnnneeseee 37  2 4 8  Protocol menu BUS              eeceeeeecceeeeeeeeeeeeeeeeeeeeeeeeees 40  2 4 9  Single line diagram editing               ccceeeeeeeeeeeeeees 43  2 4 10 Blocking and interlocking configuration                43   3  VAMPSET PC software            cccccccsssseseeeeeeeeeeeeeeeeeeeseeeeeeeeeees 44   4  INMFOAUCUON ssn eaa a aaia raias 45  4 1  Main IGQLUING Siete scans anya rei sits alot neath ot 46  4 2  Principles of numerical protection techniques                    47   5  Protection functions ss civiciscscsiscdescesadassdiniunssatiedleitieasanrazarcaaess 49  5 1  Maximum number of protection stages in one application49  5 2  List of protection
113. Local panel user interface 2 3 Operating measures       2 3   2 3 1     V210 EN M A011    Operating measures    Control functions    The default display of the local panel is a single line diagram  including relay identification  Local Remote indication  Auto   reclose on off selection and selected analogue measurement  values     Please note that the operator password must be active in order to  be able to control the objects  Please refer to page 26 Opening  access     Toggling Local Remote control    1  Push ox  The previously activated object starts to blink   2  Select the Local Remote object     L    or    R    squared  by using  the arrow keys     3  Push ox  The L R dialog opens  Select    REMOTE    to enable  remote control and disable local control  Select    LOCAL    to  enable local control and disable remote control     4  Confirm the setting by pushing ox  The Local Remote state  will change     Object control    1  Push ox  The previously activated object starts to blink     2  Select the object to control by using the arrow keys  Please  note that only controllable objects can be selected     3  Push ox  A control dialog opens   4  Select the    Open    or    Close    command by using and v     5  Confirm the operation by pushing ox  The state of the object  changes     Toggling virtual inputs    1  Push ox  The previously activated object starts to blink    2  Select the virtual input object  empty or black square    3  The dialog opens   4  Select    Vlon   
114. N 61000 4 5  class III    2 KV  1 2 50 us  common mode  1 kV  1 2 50 us  differential mode      Conducted HF field EN 61000 4 6   0 15   80 MHz  10 V    Emitted HF field EN 61000 4 3   80   1000 MHz  10 V m    GSM test ENV 50204    900 MHz  10 V m  pulse modulated                                                                                        12 2 2  Dielectric test voltages  Insulation test voltage  IEC 60255 5  2 kV  50 Hz  1 min  Class III  Surge voltage  IEC 60255 5  5 kV  1 2 50 us  0 5 J  Class III  12 2 3  Mechanical tests  Vibration  IEC 60255 21 1  10     60 Hz  amplitude  0 035 mm  Class   60     150 Hz  acceleration 0 5g  sweep rate 1 octave min  20 periods in X   Y  and Z axis direction  Shock  IEC 60255 21 1  half sine  acceleration 5 g  duration 11 ms  Class   3 shocks in X   Y  and Z axis direction  12 2 4  Environmental conditions  Operating temperature  10 to  55   C  Transport and storage temperature  40 to  70   C  Relative humidity  lt  75   1 year  average value    lt  90   30 days per year  no condensation  permitted   12 2 5  Casing  Degree of protection  IEC 60529  IP20  Dimensions  W x H x D  208 x 155 x 225 mm  8 19 x 6 10 x 8 86 inches  Material 1 mm steel plate  Weight 4 2 kg  Colour code RAL 7032  Casing    RAL 7035  Back plate                 2 2 V210 EN M A011    Technical description 12 Technical data 12 3 Protection functions       12 2 6  Package                      Dimensions  W x H x D  215 x 160 x 275 mm  8 46 x 6 30 x 10 82 inches
115. Ni    eE  aI O     T eE ri rin             N                                                                                                                                              va                                                 xe  i    l  le  ll  I   loz  U   U  U                             LL         SLOWS                                      F 1919199 S12 sFe1     od OV  AG9C   OV                                                                             NTO  SLO  Oo  No  elie feieliei elie                             lnjol   mlolnlaja Si                                                  Figure 11 1 1 Connections on the rear panel of the VAMP 210    The generator protection relay is connected to the protected object  through the following measuring and control connections    Phase currents IL1  IL2 and IL3  terminals X1  1 6    Residual currents 101 and 102  terminals X1  7 10   Phase to phase voltages U12 and U23  terminals X1  11 14   Zero sequence voltage UO  terminals X1  17 18     V210 EN M A011 249    11 1 Rear panel view    11 Connections Technical description       Terminal X1 left side                                                                                                                                                                                                                        No  Symbol Description  1 IL1  S1  Phase current L1  S1   1 3 IL2  S1  Phase current L2  S1   3 5 5 IL3  S1  Phase current L3  S1   5 G 7 lo1  S1  Residual curr
116. ON port is primarily designed for IO modules  This port is  found in the LOCAL connector of the relay backplane and IO  devices should be connected to the port with VSE003 adapter   NOTE  If ExternallO protocol is not selected to any communication port   VAMPSET doesn   t display the menus required for configuring the IO    devices  After changing EXTENSION port protocol to ExternallO  restart  the relay and read all settings with VAMPSET     V210 EN M A011 261    11 7 External I O extension modules    11 Connections    Technical description       262    an          a     oO            lt   z   lt        a         UJ   a  x lt          External analog inputs configuration  VAMPSET only     HoldingR    HoldingR          Range    Description       Communication read errors       X   32000   32000    Y2   Scaled value                   Y   1000   1000 Point 2  X2   Modbus value  Y1   Scaled value  Point 1  D X1   Modbus value on   32000   32000 E Subtracted from Modbus  2  value  before running XY  Off scaling  set             InputR or HoldingR    Modbus register type       1   9999    Modbus register for the measurement       1   247    Modbus address of the I O device       C  F  K  mA  Ohm or  V A    Unit selection       Active value          On   Off       Enabling for measurement          V210 EN M A011    Technical description 11 Connections 11 7 External I O extension modules       Alarms for external analog inputs                                     Range Description  0
117. PDT      Parameters of output relays       Parameter    Value    Unit    Description    Note       T1  T2    0    Status of trip output relay       Al    A5    1  0  1    Status of alarm output relay       IF    Status of the internal fault  indication relay       Force    On  Off    Force flag for output relay  forcing for test purposes  This  is a common flag for all output  relays and protection stage  status  too  Any forced  relay s  and this flag are  automatically reset by a 5   minute timeout     Set       REMOTE PULSES       Al     A5    0 00     99 98  or  99 99    Pulse length for direct output  relay control via  communications protocols   99 99 s   Infinite  Release by  writing  0  to the direct control  parameter    Set       NAMES for OUTPUT RELAYS  edita    ble with VAMPSET only        Description          String of  max  32  characters       Names for DO on VAMPSET  screens  Default is   Trip relay n   n 1  2 or        Alarm relay n   n 1   5       Set          Set   An editable parameter  password needed   F   Editable when force flag is on    V210 EN M A011    Technical description 8 Control functions 8 2 Digital inputs       8 2  Digital inputs    There are 6 digital inputs available for control purposes  The  polarity     normal open  NO    normal closed  NC     and a delay  can be configured according the application  The signals are  available for the output matrix  block matrix  user s programmable  logic etc    The contacts connected to digital inputs
118. Pick up setting Xloin  Arclo2 gt  pu Pick up setting Xloon  Arclin Light indication source selection Set    No sensor selected  S1 Sensor 1 at terminals X6 4 5  S2 Sensor 2 at terminals X6 6 7   1 S2  Bl Terminals X6 1 3   1 Bl  S2 Bl   1 S2 Bl  Delayed light signal output  Ldly s Delay for delayed light output Set  signal  LdlyCn Light indication source selection Set    No sensor selected  S1 Sensor 1 at terminals X6 4 5  S2 Sensor 2 at terminals X6 6 7   1 S2  Bl Terminals X6 1 3   1 Bl  S 2 Bl   1 S2 Bl       For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed   C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault type  fault value  load current before the fault  and elapsed delay     139    5 29 Inverse time operation    5 Protection functions Technical description       5 29     140    Recorded values of the arc protection stages  Arcl gt   ArcloiA  Arclo2 gt   50ARC 50NARC                             Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Type pu Fault type value  Only for Arcl gt  stage   Fit pu Fault value  Load pu Pre fault current  Only for Arcl gt  stage   EDly   Elapsed time of the operating time  setting  100    trip                   Inverse time operation    The inverse time operation   i e  inve
119. Pulse counter input 1    Pulse counter input 2    Pulse counter input 3    Pulse counter input 4    e pulseconf2    Pulse counter input 1    Pulse counter input 2    Pulse counter input 3    Pulse counter input 4    e pulsecont3    having common minus and an internal wetting voltage     V210 EN M A011    6 10 System clock and  synchronization    6 Supporting functions Technical description       6 10     178    System clock and synchronization    The internal clock of the relay is used to time stamp events and  disturbance recordings     The system clock should be externally synchronised to get  comparable event time stamps for all the relays in the system     The synchronizing is based on the difference of the internal time  and the synchronising message or pulse  This deviation is filtered  and the internal time is corrected softly towards a zero deviation     Adapting auto adjust    During tens of hours of synchronizing the device will learn its  average error and starts to make small corrections by itself  The  target is that when the next synchronizing message is received   the deviation is already near zero  Parameters  AAIntv  and   AvDrit  will show the adapted correction time interval of this  1  ms auto adjust function     Time drift correction without external sync    If any external synchronizing source is not available and the  system clock has a known steady drift  it is possible to roughly  correct the clock error by editing the parameters  AAlntv  and   AvDrit
120. Secondary to per unit  Voltage measurement mode is   BLN      VT   12000 110   Uan   11000 V   Three symmetric phase to neutral voltages connected to the  relay s inputs Uz Up and Us are 58 2 V      Per unit voltage is   Upu   V3x58 2 110x12000 11000   1 00 pu   1 00xUen   100      Example 3  Per unit to secondary  Voltage measurement mode is   2LL Uo      VT   12000 110  Uan   11000 V    The relay displays 1 00 pu   100       Secondary voltage is    Usec   1 00x110x11000 12000   100 8 V    Example 4  Per unit to secondary  Voltage measurement mode is   3LN      VT   12000 110   Uan   11000 V   The relay displays 1 00 pu   100        Three symmetric phase to neutral voltages connected to the  relay s inputs Ua  Ub and U  are    Usec   1 00x110 V3x11000 12000   58 2 V    V210 EN M A011       Technical description    7 Measurement functions 7 10 Primary  secondary and per  unit scaling       V210 EN M A011    Per unit  pu  scaling of zero sequence voltage       Zero sequence voltage  Uo  scaling                               Voltage measurement mode Voltage measurement mode    3LN      2LL Uo    1LL Uo LLy    U              secondary   gt  a i 1 UatUy tue ac  per unit iste pu       VT grc V3  per unit  gt  U  U   U   ae _  secondary ae al wen UatUo Ue SEC V3 U py Wc          Example 1  Secondary to per unit  Voltage measurement mode is   2LL Uo     Uosec   110 V  This is a configuration value corresponding to Up at  full earth fault     Voltage connected to the device s input U
121. Set   An editable parameter  password needed    C   Can be cleared to zero   F   Editable when force flag is on       Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault type  fault current  load current before the fault   elapsed delay and setting group     65    5 6 Voltage restrained controlled  overcurrent function IV gt   51V     5 Protection functions    Technical description       66    Recorded values of the voltage restrained controlled  overcurrent stages  8 latest faults  iv gt   51V                                      Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Type Fault type  1 N Ground fault  2 N Ground fault  3 N Ground fault  1 2 Two phase fault  2 3 Two phase fault  3 1 Two phase fault  1 2 3 Three phase fault  Flt xlgn_   Maximum fault current  Load xlgn_   1s average phase currents before the  fault  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp Active setting group during the fault             V210 EN M A011    Technical description    5 Protection functions 5 7 Current unbalance protection 12 gt        46        5 7     V210 EN M A011    Current unbalance protection l2 gt   46     Current unbalance in a generator causes double frequency  currents in the rotor  This warms up the surface of the rotor and  the available thermal capacity of the rotor is much less than the  ther
122. SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  None  Dix Digital input  VIX Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   f Hz Measured frequency  df dt Hz s The supervised value  df dt gt  Hz s Pick up value Set  t gt  s Definite operation time Set  tMin gt  S Minimum operating time for  inverse delay  For definite time Set  set tMin  t  LVbIk  Un Low limit for self blocking  This  is acommon setting for all four Set  stages and with the  undervoltage stages                          For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults  There are detailed information available of the eight latest faults     Time stamp  frequency drift  elapsed delay and setting group     V210 EN M A011    115    5 20 Under impedance protection Z lt  5 Protection functions Technical description     21        5 20     116    Recorded values of the rate of change of frequency stage  8  latest faults  df dt gt   81R                       Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit Hz s   Faulty frequency drift  EDly   Elap
123. T program  The recording is in COMTRADE format  This  means that also other programs can be used to view and analyse  the recordings made by the relay     For more details  please see a separate VAMPSET manual     Number of channels    At the maximum  there can be 12 recordings  and the maximum  selection of channels in one recording is also 12  limited in  waveform recording   The digital inputs reserve one channel   includes all the inputs   Also the digital outputs reserve one  channel  includes all the outputs   If digital inputs and outputs are  recorded  there will be still 10 channels left for analogue  waveforms     V210 EN M A011    Technical description    6 Supporting functions    6 2 Disturbance recorder       V210 EN M A011    Available channels  The following channels i e  signals can be linked to a disturbance                                                                                                                         recorder   Available for waveform  ae Voltage measurement  Channel Description mode   2LL Uo   3LN   IL1  IL2  IL3 Phase current Yes Yes  lo1  lo2 Measured residual current Yes Yes  U12  U23 Line to line voltage Yes     U31 Line to line voltage        UL1  UL2  UL3 Phase to neutral voltage   Yes  Uo Zero sequence voltage Yes    f Frequency      P Q S Active  reactive  apparent power      P F  Power factor      CosFii coso      loCalc Phasor sum lo    IL1 IL2 IL3  3      l1 Positive sequence current      12 Negative sequence current      
124. Tamb Set  ExtAl1    External Analogue input 1   16  16                         For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    73    5 9 Earth fault protection 10 gt    50N 51N     5 Protection functions Technical description       5 9     74    Earth fault protection lo gt   50N 51N     Undirectional earth fault protection is used for generator s stator  earth faults in low impedance earthed networks  In high  impedance earthed networks  compensated networks and isolated  networks undirectional earth fault can be used as back up  protection    The undirectional earth fault function is sensitive to the  fundamental frequency component of the residual current 3lo  The  attenuation of the third harmonic is more than 60 dB  Whenever  this fundamental value exceeds the user s pick up setting of a  particular stage  this stage picks up and a start signal is issued  If  the fault situation remains on longer than the user s operation time  delay setting  a trip signal is issued     i0s1       Setting Io gt s Delay Definite  inverse Inverse time Multiplier Enable events  time characteristics    Figure 5 9 1 Block diagram of the earth fault stage l    gt     0ssblock    Start  Register  event  Register  event       Setting Io gt  gt s Delay Enable events    Figure 5 9 2 Block diagram of the earth fault stages Ip gt  gt   l gt  gt  gt  and Ip gt  gt  gt  gt     Figure 5
125. Technical description       266       EXTERNAL ANALOG OUTPUTS    External analog outputs configuration  VAMPSET only     c4      S  2           HoldingR          Range    Description       Communication errors        32768    32767   0   65535     Modbus value corresponding Linked  Val  Max       Modbus value corresponding Linked  Val  Min       InputR or HoldingR    Modbus register type                               1   9999 Modbus register for the output   1   247 Modbus address of the I O device  Maximum limit for lined value   corresponding to    Modbus Max      0   42x108     21    21x108  Minimum limit for lined value   corresponding to    Modbus Min     Link selection    21x107    oo     4214x107 Minimum  amp  maximum output values  Active value   On   Off Enabling for measurement          V210 EN M A011       Technical description    11 Connections    11 8 Block diagrams       11 8     V210 EN M A011    Block diagrams    10  11  12  13  14  17    18    X3    NoJAUON     Protection function          50 51       3 gt     3l gt  gt     3l gt  gt  gt                       5ON 51N                                           59       u gt   U gt  gt     U gt  gt  gt                    81H 81L       f  gt  lt   f  gt  gt  lt  lt                    32             P lt        SOBF    CBFP                SONARC                ACh  gt   Arcly gt           99    50ARC                Prg1   8          Arcl gt                             BEEBE BSS    Blocking and  output matrix      
126. The data in a message frame is identified by     e type identification  e function type and  e information number     These are fixed for data items in the compatible range of the  protocol  for example  the trip of I gt  function is identified by  type  identification   1  function type   160 and information number    90   Private range  function types are used for such data items   which are not defined by the standard  e g  the status of the digital  inputs and the control of the objects      The function type and information number used in private range  messages is configurable  This enables flexible interfacing to  different master systems    For more information on IEC 60870 5 103 in Vamp devices refer  to the    IEC103 Interoperability List    document     227    9 2 Communication protocols    9 Communication    Technical description       228                                                                         Parameters  Parameter   Value Unit   Description Note  Addr 1  254 An unique address within Set  the system  bit s bps   Communication speed Set  9600  19200  Measlint 200     10000 ms Minimum measurement Set  response interval  SyncRe ASDU6 response time Set  Sync mode  Sync Proc  Msg  Msg Proc  Set   An editable parameter  password needed   Parameters for disturbance record reading  Parameter   Value Unit   Description Note  ASDU23 On Enable record info Set  Off message  Smpls msg   1 25 Record samples in one Set  message  Timeout 10 10000 S Record reading
127. Ua  U  100 V3 V 20   57 7V 20     Up  U  100 V3 V 2 120    57 7 V 2 120     Us  U   0V    This is actually identical case with example 2 because the  resulting line to line voltages U12   UL      Utz   100 V 730   and  Uz   Ute     Uls   Ure   100 V3 V7   120   are the same as in  example 2  The only difference is a  30   phase angle difference   but without any absolute angle reference this phase angle  difference is not seen by the device           100      70     U    1 1 1 ane 100 20     1002     120    U    a a T ET 100 20     100 20      U  la a  gt  0 373   10940    1002  120     1002  60     19 22  60           20020        38 5 20     33    100 60   19 27   60      V210 EN M A011       Technical description 7 Measurement functions 7 9 Symmetric components  Uo   19 2    U    38 5    U2   19 2      V210 EN M A011    U2 U    50      Figure 7 9 2 shows a graphical solution  The input values have  been scaled with V3 100 to make the calculation easier               Positive sequence FortescueEx3  U    2 3  2   2  aU     U   aU    Injected line to neutral voltages  U   0 cee  l Un Un egative sequence  x  UL UL    U    1 3    Figure 7 9 2 Example of symmetric component calculation using line to neutral  voltages    Unscaling the geometric results gives   U    100 V3 x 2 3   38 5    U gt    100V3x1 3 19 2    U gt  U    1 3 2 3   50     201    7 10 Primary  secondary and per unit 7 Measurement functions Technical description  scaling       7 10  Primary  secondary and per uni
128. VAMP 210    Generator protection relay    Publication version  V210 EN M A011    User manual          Schneider       V210 EN M A011    Table of Contents       Table of Contents    Nis GSN SF Al sais cascntantahiaasahaaoeutienraasilakanantuavaned tananantienssemnTenneiaatanael 8  1 1  Relay features fxs tc eee i essaiatd Nate beaaked taint ead tat aah 8  k2  SWSEN WG ACC otic ecccster teed eatea aa Aa Aa AEEA EAA AANS 9  1 3  Operating Safety coed fei asians el A heehee aes eee bla ede 9   2  Local panel user interface            cccccceseeeseeeeeeeeeeeeeeeeeeeeneeees 10  2ko Relay front panels seei ai 10   DAT ADISplay eee a e e A 11  2 1 2  Menu navigation and pointers               eeeeeeeeeeeeeeeeeees 12  2l Keypads ics ob aeaea a a E actors aain 12  2 1 4  Operation INndicators               ccceeccceeeeeeeeeeseeeeeeeeeeeeees 13  2 1 5  Adjusting display Contrast               cccceeeeceeeeeeeeeeeeees 14  2 2  Local panel operations 2 cves ces cots ctat cocececcvocesecdcecceuectoeseesdee 15  2 2 1  Navigating in Menus                   cccceeeeeeeeeeeeeeeeeeeeeeees 15  2 2 2  Menu structure of protection functions                 20  PAPAE ARSI QUOUDS sievics ives adc coeliecssueatars ieee tacdevedancceneepaciee 23  224  AUN IOOS tcc inen a a aa a aads 24  2 2 5  Operating levels    ceeeeccsecceeeeeeeeeeeseeneeeeeeeeees 25  2 3  Operating MEASUIOS soi cece seek coccetud coneseniseceseudeiencaneedonnseedion 27  2 3 1  Control fUNCtIONS 4 2cc2 occ cet ietet esi eesree ete 
129. adband  calculation        10 51    SC fault distance added to IEC 103 map       10 56    Uo setting grange of loDir stages changed from 1   20  to  1   50         10 58    New features in IEC 61850 added   Outputs vef files with suomi  amp  russian language packets        10 65    100 Mbps option card support        10 67    Default font sizes changed    lo gt  gt  minimum delay setting changed to 0 05s with 0 01s  step    Popup window added for language packet init    EF items  EFDX  EFDFph  EFctr and EFDFItDist added to  IEC103        10 68    Ethernet IP and DeviceNet identity info changes        10 74    Lower 3 harmonic limit for Upf3 lt    I gt  and I gt    lo gt  gt  gt  gt   stages with faster operation time        10 85    Virtual output events added       10 106    GOOSE supervision signals added   Automatic LED latch release added  Disturbance recorder full event added       10 108    Use of recorder memory in percents added  Various additions to IEC 61850          10 113       U12y voltage measurement to IEC 60870 5 101 protocol  NOTE  Vampset version 2 2 59 required        V210 EN M A011       Technical description    16 Revision history 12 4 Supporting functions       V210 EN M A011    10 116    IP and other TCP parameters are able to change without  reboot    Logic output numbering is not changed when changes are  made in the logic    NOTE  Vampset version 2 2 97 required           10 118       Enable sending of analog data in GOOSE message  Day light saving  
130. after the event  code     Setting parameters for events                                              Parameter Value Description Note  Count Number of events  ClrEn Clear event buffer Set  Clear  Order Order of the event buffer for local display Set  Old   New  New   Old  FVSca Scaling of event fault value Set  PU Per unit scaling  Pri Primary scaling  Display On Alarm pop up display is enabled Set  Alarms Off No alarm display  FORMAT OF EVENTS ON THE LOCAL DISPLAY  Code  CHENN CH   event channel  NN event code  Event description Event channel and code in plain text  yyyy mm dd Date  for available date formats see chapter 6 10   hh mm ss nnn Time             V210 EN M A011 155    6 2 Disturbance recorder    6 Supporting functions Technical description       6 2     156    Disturbance recorder    The disturbance recorder can be used to record all the measured  signals  that is  currents  voltages and the status information of  digital inputs  DI  and digital outputs  DO   The digital inputs  include also the arc protection signals S1  S2  BI and BO  if the  optional arc protection is available     Triggering the recorder    The recorder can be triggered by any start or trip signal from any  protection stage or by a digital input  The triggering signal is  selected in the output matrix  vertical signal DR   The recording  can also be triggered manually  All recordings are time stamped     Reading recordings    The recordings can be uploaded  viewed and analysed with the  VAMPSE
131. age by means of the par meters  Q1 and Q2  The shaded area is the area of operation  In this example the  operation depends on both P and Q  because the operating line has an 8   slope   Q1   Q2   14       P P Q circle2       Figure 5 21 2 Setting of the under excitation stage by means of the parameters  Q1 and Q2  The shaded area constitutes the area of operation  In the above  example the operation solely depends on the reactive power  because the  operating line is vertical  Q1   Q2   0       V210 EN M A011    Technical description    5 Protection functions 5 21 Under excitation protection Q lt    4    0        V210 EN M A011    Power swing    A release time setting is available against prolonged power  swings  In a power swing situation the power phasor is swinging  back and forth between capacitive and inductive power  With a  long enough release time setting the stage accumulates the total  fault time and will eventually trip     Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     Parameters of the under excitation stage Q lt   40                             Parameter Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1 or2 Active setting group Set  SGrpDI Digital sign
132. ages                Operating time    Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms   Reset ratio 1 03   Inaccuracy      Starting  3  of set value           1  or  30 ms          This is the total operational time including the fault detection time and operation time of the trip    contacts     NOTE  To make the relay trip after low voltage blocking  the positive sequence  voltage has to go above the pick up setting     V210 EN M A011    Technical description    12 Technical data    12 3 Protection functions       V210 EN M A011    Undervoltage stage U lt   U lt  lt   U lt  lt  lt   27        Setting range    20     120 xUn       Definite time function     Operating time U lt     Operating time U lt  lt  and U lt  lt  lt     0 08         300 00 s  step 0 02 s   0 06         300 00 s  step 0 02 s        Undervoltage blocking    0     80  x Un       Start time    Typically 60 ms       Reset time for U lt    Reset time for U lt  lt  and U lt  lt  lt   Retardation time   Reset ratio  hysteresis   Reset ratio  Block limit     0 06     300 00 s  step 0 02 s     lt 95 ms    lt 50 ms   1 001     1 200  0 1     20 0    step 0 1     0 5 V or 1 03  3          Inaccuracy     starting    blocking         time        3  of set value   3  of set value or  0 5 V   1  or  30 ms              This is the instantaneous time i e  the minimum total operational time including the fault detection    time and operation time of the trip contacts     Zero sequence voltage
133. al  input signals with an AND port  The delay is configured longer  than maximum fault time to inhibit any superfluous trip circuit  fault alarm when the trip contact is closed    e The output from the logic is connected to a relay in the output  matrix giving out any trip circuit alarm    e The trip relay should be configured as non latched  Otherwise   a superfluous trip circuit fault alarm will follow after the trip  contact operates  and the relay remains closed because of  latching    e Both digital inputs must have their own common potential   Using the other digital inputs in the same group as the upper DI  in the Figure 10 4 2 1 is not possible in most applications   Using the other digital inputs in the same group as the lower DI  in the Figure 10 4 2 1 is limited  because the whole group will  be tied to the auxiliary voltage Vaux     Note  In many applications the optimum digital inputs for trip circuit supervision  are the optional inputs DI19 and DI20 because they don t share their  terminals with any other digital inputs     V210 EN M A011 245    10 4 Trip circuit supervision 10 Applications Technical description               V x   48 Vdc     240 Vdc  VAMP relay    Alarm relay  for trip    circuit failure trip circuit    failure alarm    relay compartment    circuit breaker compartment      Vaux  CLOSE COIL    TCS2Diclosed  Figure 10 4 2 1 Trip circuit supervision with two dry digital input  The CB is  closed  The supervised circuitry in this CB position is dou
134. al to select the active   Set   setting group     None   Dix Digital input   Vix Virtual input   LEDx LED indicator signal   VOx Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout                                         P  Sgn   The supervised active power  value   Q  Sgn_   The supervised reactive power  value   Q P0   Sgn   Setting 1  See Figure 5 21 1 Set  kvar  Q P80   Sgn   Setting 2  See Figure 5 21 2 Set  kvar  t lt  s Definite operation time Set  RIsDly s Release delay for power swing Set       For details of setting ranges see chapter 12 3   Set   An editable value  password needed    C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest earth  faults  Time stamp  fault power P and Q  elapsed delay and setting    group   121    5 22 Under reactance and loss of 5 Protection functions Technical description    excitation protection X lt   40           22     122    Recorded values of the under excitation stage Q lt   40                          Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  P  Sgn   Active fault power  Q  Sgn   Reactive fault power  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group 
135. and flexible protection functions are provided  for the generator earth fault protection  These features are  needed  when for instance  several generators are connected in  parallel to the same busbar but their earthing principles differ     The other energizing connections  except for the ones for the  earth fault protection  are independent of the generator size and  type  For large generator a higher accuracy of the protection  functions is needed  Being based on numerical signal processing  and high resolution A D conversion the device fulfils also these  requirements     The three generator protection applications on the following pages  illustrate how the flexibility of the device can be utilized     234 V210 EN M A011    Technical description 10 Applications 10 1 Directly connected generator       10 1  Directly connected generator    L1  L2  L3                            50 51    X3 3 gt     3b gt                    3P gt  gt  gt                          50N 51N 3Pp gt  gt  gt                 W gt     49    T gt                 37                                     U gt  gt  gt                 81H 81L  f gt  lt   f gt  gt  lt  lt                                   32  P lt   P  lt  lt                                         21 40  X lt   X lt  lt                                      9  b Prg1   8 Arce                                                          Blocking and  18 0 output matrix                      K4                         X3  MBV n       Digital  input
136. and the Equation 6 8 2 and Equation 6 8 3  the relay calculates    10000  In      80 _       37000 1 5038  In    1250  a  10000 1250      8   454 10      V210 EN M A011    Technical description 6 Supporting functions 6 8 Circuit breaker condition  monitoring       Using Equation 6 8 1 the relay gets the number of permitted  operations for current 6 kA     6  C  454 10    600015038    Thus the maximum number of current breaking at 6 kA is 945   This can be verified with the original breaker curve in Figure 6 8 1   Indeed  the figure shows that at 6 kA the operation count is  between 900 and 1000  A useful alarm level for operation left   could be in this case for example 50 being about five per cent of  the maximum     Example of operation counter decrementing when the CB is  breaking a current    Alarm2 is set to 6 kA  CBFP is supervising trip relay T1 and trip  signal of an overcurrent stage detecting a two phase fault is  connected to this trip relay T1  The interrupted phase currents are  12 5 KA  12 5 KA and 1 5 kA  How much are Alarm2 counters  decremented     Using Equation 6 8 1 and values n and a from the previous    example  the relay gets the number of permitted operation at 10  kA     454  10    10kA   12500      8 z 313  At alarm level 2  6 kA  the corresponding number of operations is  calculated according    Equation 6 8 4    A   ONTA  C  945  An  A   313  o    Thus Alarm2 counters for phases L1 and L2 are decremented by  3  In phase L1 the currents is less than
137. another output relay  which will remain  activated until the primary trip relay resets    The CBFP stage is supervising all the protection stages using the  same selected trip relay  since it supervises the control signal of  this relay  See chapter 8 4 for details about the output matrix and  the trip relays     132 V210 EN M A011    Technical description    5 Protection functions    5 26 Circuit breaker failure  protection CBFP  50BF        V210 EN M A011    Parameters of the circuit breaker failure stage CBFP  50BF                             Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   CBrelay 1 2 The supervised output relay     Set  Relay T1     T2  depending the  ordering code   t gt  s Definite operation time  Set                      For details of setting ranges see chapter 12 3    Set   An editable parameter  password needed   C   Can be cleared to zero  F   Editable when force flag is on     This setting is used by the circuit breaker condition monitoring  too  See    chapter 6 8     Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp and elapsed delay     Recorded values of the circuit breaker fa
138. arameter  Clear   Clear oper   left cntrs   After clearing the relay will show the maximum allowed  operations for the defined alarm current levels     Operation counters to monitor the wearing    The operations left can be read from the counters  AliLn   Alarm  1  and  Al2Ln   Alarm2   There are three values for both alarms   one for each phase  The smallest of three is supervised by the two  alarm functions     V210 EN M A011 171    6 8 Circuit breaker condition  monitoring    6 Supporting functions Technical description       172    Logarithmic interpolation    The permitted number of operations for currents in between the  defined points are logarithmically interpolated using equation    Equation 6 8 1    a  C       where    n    C   permitted operations       interrupted current   a   constant according Equation 6 8 2  n   constant according Equation 6 8 3  Equation 6 8 2       Equation 6 8 3    a  C I    In   natural logarithm function   Ck   permitted operations  k   row 2   7 in Table 6 8 1   Ik   Corresponding current  k   row 2   7 in Table 6 8 1   Ck   permitted operations  k   row 2   7 in Table 6 8 1   lk 1   corresponding current  k   row 2   7 in Table 6 8 1     Example of the logarithmic interpolation   Alarm 2 current is set to 6 kA  What is the maximum number of  operations according Table 6 8 1    The current 6 kA lies between points 2 and 3 in the table  That  gives value for the index k  Using    k  2   Ck   10000  Cyi1   80   ket   31kKA  Ik   1 25kA    
139. art of the manual     PROFIBUS   Only one instance of this protocol is possible    e  Mode    e Bit rate  bit s   Use 2400 bps  This parameter is the bit rate  between the main CPU and the Profibus ASIC  The actual  Profibus bit rate is automatically set by the Profibus master and  can be up to 12 Mbit s    e Event numbering style  Emode     e Size of the Profibus Tx buffer  InBufl    e Size of the Profibus Rx buffer  OutBuf     When configuring the Profibus master system  the length of  these buffers are needed  The size of the both buffers is set  indirectly when configuring the data items for Profibus    e Address for this slave device  Addr   This address has to be  unique within the system    e Profibus converter type  Conv   If the shown type is a dash           either Profibus protocol has not been selected or the device  has not restarted after protocol change or there is a  communication problem between the main CPU and the  Profibus ASIC    For details see the technical description part of the manual     V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       2 4 9     2 4 10     V210 EN M A011    DNP3  Only one instance of this protocol is possible     e Bit rate  bit s   Default is  9600     e  Parity     e Addres for this device  SlvAddr   This address has to be unique  within the system    e Master s addres  MstrAddr     For further details see the technical description part of the manual     S
140. at the neutral point  Figure  5 17 2 and Figure 5 17 3   The third harmonic residual  undervoltage stage Uois lt  is supervising the level of the 3    harmonic at the neutral point  If there is an earth fault near the  neutral point  this 150 Hz or 180 Hz voltage drops below setting  and the stage will pick up        Uof3_HARM3    20      Uo    Uti   Ur2   UL3  3             Figure 5 17 2 When symmetric phase to ground voltages containing third  harmonic are summed together  the result is not zero        Uof3_HARM5  ULI UL2 UL3 20     Uo    U11   Ur2   UL3  3   0             Figure 5 17 3 When the phase to ground voltages do contain fifth harmonic   they cancel each other when summed and the resulting zero sequence voltage  Up will be zero     V210 EN M A011    Technical description 5 Protection functions 5 17 100  stator earth fault  protection U0f3 lt   64F3        Finding out the correct pick up setting   A problem with this third harmonic undervoltage stage is to find a  proper pick up setting  In practice an empirical value is used   because the natural 3 harmonic at the neutral point is dependent  on    Construction of the generator   Loading and the power factor   Amount of excitation   Earthing circuitry   Transformers connected     The relay itself can be used to measure the actual level of 3 Uo  harmonic during various situations  Typically the generator is  producing its minimum amount of 3   harmonic when the load is  small and the excitation is low  The pick up s
141. ated power of the open coil of the circuit breaker  If this  value is not known  0 Q can be used for the Rooi     Umin   Uaux     20    88 V  Umax   Uaux 10  121V  Rcoi   U7aux P   242 Q     The external resistance value is calculated using Equation  10 4 1 1     Equation 10 4 1 1    U un  U  l  R  Ip    Coil    R        R    88     18     0 003 242  0 003   23 1 KQ   In practice the coil resistance has no effect    By selecting the next smaller standard size we get 22 KQ     The power rating for the external resistor is estimated using  Equation 10 4 1 2 and Equation 10 4 1 3  The Equation 10 4 1 2 is  for the CB open situation including a 100   safety margin to limit  the maximum temperature of the resistor     Equation 10 4 1 2  P 2 I   R    P   2 0 003 2x22000   0 40 W    241    10 4 Trip circuit supervision    10 Applications Technical description       242    Select the next bigger standard size  for example 0 5 W     When the trip contacts are still closed and the CB is already open   the resistor has to withstand much higher power  Equation  10 4 1 3  for this short time     Equation 10 4 1 3    P  Cae  R  P   12142 22000   0 67 W    A 0 5 W resistor will be enough for this short time peak power  too   However  if the trip relay is closed for longer time than a few  seconds  a 1 W resistor should be used     Using any of the non dry digital inputs DI1   DI6    In this scheme an auxiliary relay is needed to connect the wet  digital input to the trip circuit  Figure 10 
142. ation Technical description       9 2 5  IEC 60870 5 101    The IEC 60870 5 101 standard is derived from the IEC 60870 5  protocol standard definition  In Vamp devices  IEC 60870 5 101  communication protocol is available via menu selection  The Vamp  unit works as a controlled outstation  slave  unit in unbalanced  mode     Supported application functions include process data  transmission  event transmission  command transmission  general  interrogation  clock synchronization  transmission of integrated  totals  and acquisition of transmission delay     For more information on IEC 60870 5 101 in Vamp devices refer  to the    IEC 101 Profile checklist  amp  datalist    document                                                           Parameters  Parameter Value Unit   Description Note  bit s 1200 bps   Bitrate used for serial Set  2400 communication   4800  9600  Parity None Parity used for serial Set  Even communication  Odd  LLAddr 1   65534 Link layer address Set  LLAddrSize 1 2 bytes   Size of Link layer address Set  ALAddr 1     65534 ASDU address Set  ALAddrSize   1 2 Bytes   Size of ASDU address Set  lOAddrSize 2 3 Bytes   Information object address Set  size   8 octet addresses are  created from 2 octet  addresses by adding MSB  with value 0    COTsize 1 Bytes   Cause of transmission size  TTFormat Short The parameter determines Set  Full time tag format  3 octet  time tag or 7 octet time tag   MeasFormat   Scaled The parameter determines Set  Normalized measurement
143. ay 3  common connector  Fs S 11  A3 NC Alarm relay 3  normal closed connector  49 ea 12  A3NO Alarm relay 3  normal open connector     13  A2 COM   Alarm relay 2  common connector   13    14  A2NC Alarm relay 2  normal closed connector  14    15  A2 NO Alarm relay 2  normal open connector  15    16  IF COM _  Internal fault relay  common connector  16    17  IFNC Internal fault relay  normal closed connector  17    18  IFNO Internal fault relay  normal open connector  18        Terminal X2 with the analogue output                                                                                                                                                    V210 EN M A011    No  Symbol Description   1I    1 AQ1  Analogue output 1  common positive connector  2    2 AO1  Analogue output 1  negative connector  3      3 AQ2  Analogue output 2  common positive connector  4     4 AQ2  Analogue output 2  negative connector  5      5 AO3  Analogue output 3  common positive connector  6l   6 AO3  Analogue output 3  negative connector  71    7 AO4  Analogue output 4  common positive connector  8l   8 AO4  Analogue output 4  negative connector  o  S    2   i  10    10  A3 COM  Alarm relay 3  common connector  11    11  A3 NC Alarm relay 3  normal closed connector  12    12  A3NO Alarm relay 3  normal open connector  13    13  A2COM  Alarm relay 2  common connector  14    14  A2NC Alarm relay 2  normal closed connector  15    15  A2 NO Alarm relay 2  normal open connector  16    16  IF 
144. between phase and  neutral overvoltage protection may be needed for phase to ground  voltages  too  In such applications the programmable stages can  be used  See chapter 5 27     Three independent stages    There are three separately adjustable stages  U gt   U gt  gt  and U gt  gt  gt    All the stages can be configured for definite time  DT  operation  characteristic     Configurable release delay    The U gt  stage has a settable release delay  which enables  detecting intermittent faults  This means that the time counter of  the protection function does not reset immediately after the fault is  cleared  but resets after the release delay has elapsed  If the fault  appears again before the release delay time has elapsed  the  delay counter continues from the previous value  This means that  the function will eventually trip if faults are occurring often enough     V210 EN M A011    Technical description    5 Protection functions 5 12 Overvoltage protection U gt   59        V210 EN M A011    Configurable hysteresis    The dead band is 3   by default  It means that an overvoltage  fault is regarded as a fault until the voltage drops below 97   of  the pick up setting  In a sensitive alarm application a smaller  hysteresis is needed  For example if the pick up setting is about  only 2   above the normal voltage level  hysteresis must be less  than 2    Otherwise the stage will not release after fault     Setting groups   There are two settings groups available for each stage
145. bined overcurrent status    6 Supporting functions    Technical description       6 13     184    Line fault parameters    Combined overcurrent status    This function is collecting faults  fault types and registered fault  currents of all enabled overcurrent stages        Parameter    Value    Unit    Description    Note       IFitLas    Xlen    Current of the latest  overcurrent fault     Set        LINE ALARM       AlrL1  AlrL2  AlrL3    Start   alarm  status for each  phase    O No start since alarm ClrDly  1 Start is on       OCs    Combined overcurrent start  status     AlrL1 AlrL2 AlrL3 0  AlrL1 1 orAlrL2 1 or AlrL3 1       LxAlarm     On  Event enabling for  AlrL1   3    Events are enabled  Events are disabled    Set       LxAlarm Off       Off    Event enabling for  AlrL1   3    Events are enabled  Events are disabled    Set       OCAlarm    Off     On  Event enabling for  combined o c starts    Events are enabled  Events are disabled    Set       OCAlarmOff    On  Off       Off    Event enabling for  combined o c starts    Events are enabled  Events are disabled    Set       IncFltEvnt    Off    Disabling several start and  trip events of the same fault  Several events are enabled      Several events of an    increasing fault is disabled           Set          ClrDly       0    65535          Duration for active alarm  status AlrL1  Alr2  AlrL3 and  OCs       Set       V210 EN M A011       Technical description    6 Supporting functions    6 14 Self supervision     
146. ble lined  The digital  input is in active state when the trip circuit is complete  This is applicable for dry  inputs DI7   D20 only     246 V210 EN M A011    Technical description 10 Applications 10 4 Trip circuit supervision            V ux   48 Vdc     240 Vdc  VAMP relay      Trip Circuit    Failure alarm    Alarm relay  for trip  circuit failure    TCS2Dlopen    Figure 10 4 2 2 Trip circuit supervision with two dry digital inputs  The CB is in  the open position  The two digital inputs are now in series     Note  If for example DI13 and DI7 are used as the upper and lower digital inputs  in the Figure 10 4 2 2  the usage of DI8     DI14 is limited to the same  circuitry sharing the Vaux in the common terminal and the DI14    DI18  cannot be used  because they share the same common terminal with DI13     V210 EN M A011 247    10 4 Trip circuit supervision    10 Applications Technical description       248       Figure 10 4 2 3 An example of digital input configuration for trip circuit  supervision with two dry digital inputs DIZ and DI13        Figure 10 4 2 4 An example of logic configuration for trip circuit supervision with  two dry digital inputs DIZ and DI13        Figure 10 4 2 5 An example of output matrix configuration for trip circuit  supervision with two dry digital inputs     V210 EN M A011    Technical description 11 Connections 11 1 Rear panel view       11  Connections             11 1  Rear panel view  VO90XAA  Soe  NS oY peo BoD  gt    fe  nl tl olaol Si
147. c is 22 V      Per unit voltage is   Upu   22 110   0 20 pu   20     Example 2  Secondary to per unit  Voltage measurement mode is   BLN     VT   12000 110   Voltage connected to the device s input Ua is 38 1 V  while   Ua   Up   0      Per unit voltage is   Uru    38 1 0 0   V3x110    0 20 pu   20     Example 3  Per unit to secondary  Voltage measurement mode is   2LL Uo     Uosec   110 V  This is a configuration value corresponding to Uo at  full earth fault     The device displays Up   20        gt  Secondary voltage at input Uc is   Usec   0 20x110   22 V   Example 4  Per unit to secondary  Voltage measurement mode is   BLN     VT   12000 110   The device displays Uo   20       gt  If Up   Ue   0  then secondary voltages at U  is   Usec   V3x0 2x110   38 1 V    207    8 1 Output relays    8 Control functions    Technical description       8     8 1     208    Control functions    Output relays    The output relays are also called digital outputs  Any internal    signal can be connected to the output relays using output matrix   An output relay can be configured as latched or non latched  See  output matrix for more details     NOTE  If the device has the mA option  it is equipped with only three alarm    relays from A1 to A3     The difference between trip contacts and alarm contacts is the DC  breaking capacity  See chapters 12 1 4 and 12 1 5 for details  The  contacts are SPST normal open type  NO   except alarm relays   A1  A2 and A3  which have change over contacts  S
148. ce  voltage back up protection stage Uo gt  for the bus may not release  between consecutive faults and the Uo gt  might finally do an  unselective trip if the intermittent transient stage Ioint gt  doesn t  operate fast enough  The actual operation time of the loint gt  stage  is very dependent on the behaviour of the fault and the intermittent  time setting  To make the co ordination between Uo gt  and loint gt   more simple  the start signal of the transient stage loint gt  in an  outgoing feeder can be used to block the Up gt  backup protection     V210 EN M A011    Technical description    5 Protection functions 5 11 Intermittent transient earth fault  protection IOINT gt   67NI        V210 EN M A011    Co ordination with the normal directional earth fault  protection based on fundamental frequency signals    The intermittent transient earth fault protection stage loint gt  should  always be used together with the normal directional earth fault  protection stages l    gt   lp gt  gt   The transient stage loint gt  may in  worst case detect the start of a steady earth fault in wrong  direction  but will not trip because the peak value of a steady state  sine wave l    signal must also exceed the corresponding base  frequency component s peak value in order to make the Igint gt  to  trip    The operation time and Uo setting of the transient stage loint gt   should be higher than the settings of any l    gt  stage to avoid any  unnecessary and possible incorrect start signa
149. chapter 5 29 for more details     Limitations   The minimum definite time delay start latest  wnen the measured  value is twenty times the setting  However  there are limitations at  high setting values due to the measurement range  See chapter  5 29 for more details     V210 EN M A011    Technical description    5 Protection functions 5 29 Inverse time operation       5 29 3     V210 EN M A011    Programmable inverse time curves  Only with VAMPSET  requires rebooting     The  current  time  curve points are programmed using VAMPSET  PC program  There are some rules for defining the curve points     e configuration must begin from the topmost row   e row order must be as follows  the smallest current  longest  operation time  on the top and the largest current  shortest  operation time  on the bottom   e all unused rows  on the bottom  should be filled with  1 00  0 00s    Here is an example configuration of curve points                                                           Point Current I lpick up Operation delay  1 1 00 10 00s  2 2 00 6 50 s  3 5 00 4 00s  4 10 00 3 00s  5 20 00 2 00s  6 40 00 1 00s  7 1 00 0 00 s  8 1 00 0 00 s  9 1 00 0 00 s  10 1 00 0 00 s  11 1 00 0 00 s  12 1 00 0 00 s  13 1 00 0 00 s  14 1 00 0 00 s  15 1 00 0 00 s  16 1 00 0 00 s                Inverse time setting error signal   The inverse time setting error signal will be activated  if  interpolation with the given points fails  See chapter 5 29 for more  details     Limitations    The minimum
150. chnical description   ROCOF  protection df dt  81R   Slope and delay settings  0 5 Hz s 1Hz s 1 5 Hz s  0 6 0 6 s 05s 04s    ROCOF6_y3        0 8          0 5 0 7       a        gt   w          Operation time  s   o   gt        b       0 2          Setting for minimum delay  tyin  0 15 s    0 1                               2 3 4  Measured slope  df dt   Hz s     Figure 5 19 3 Three examples of possible inverse df dt operation time  characteristics  The slope and operation delay settings define the knee points  on the left  A common setting for tmin has been used in these three examples   This minimum delay parameter defines the knee point positions on the right                       FREQUENCY ROCOF3_v3   Hz   50 0    Settings   ARO df dt   0 5 Hz s  Vz  t 0 60s  A Ly tun   0 158  N EN  a SS  Se  i SE JME  0 00  0 15                START  TRIP    Figure 5 19 4 An example of inverse df dt operation time  The time to trip will be    0 3 s  although the setting is 0 6 s  because the average slope 1 Hz s is steeper  than the setting value 0 5 Hz s           114    V210 EN M A011    Technical description    5 Protection functions    5 19 Rate of change of frequency   ROCOF  protection df dt  81R        Parameters of the rate of change of frequency stage                                           df dt gt   81R   Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  
151. command line interface in ports X4 and the front  panel  The front panel is always using this setting  If SPABUS  is selected for the rear panel local port X4  the bit rate is  according SPABUS settings    e Access level  Acc     LANGUAGE  e List of available languages in the relay    CURRENT SCALING    e Rated phase CT primary current  Inom    e Rated phase CT secondary current  Isec    e Rated input of the relay  linput   5 A or 1 A  This is specified in  the order code of the device    e Rated value of 10 CT primary current  lonom    e Rated value of 10 CT secondary current  losec    e Rated 101 input of the relay  loinp   5 A or 1 A  This is specified  in the order code of the device    e Rated value of 102 CT primary current  lo2nom    e Rated value of 102 CT secondary current  lo2sec    e Rated 102 input of the relay  lo2inp   5A  1 Aor 0 2 A  This is  specified in the order code of the device     37    2 4 Configuration and parameter 2 Local panel user interface Operation and configuration    setting    instructions       38    The rated input values are usually equal to the rated secondary  value of the CT    The rated CT secondary may be greater than the rated input but  the continuous current must be less than four times the rated  input  In compensated  high impedance earthed and isolated  networks using cable transformer to measure residual current lo  it  is quite usual to use a relay with 1 A or 0 2 A input although the  CT is 5 Aor 1A  This increases the measur
152. counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active  setting group  z None  Dix Digital input Set  VIX Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   lo pu The supervised value according  lo2 the parameter  Input  below   loCalc  lop gt  only   loPeak  Iop gt  only   lo2Peak  loRes pu Resistive part of l     only when   InUse  Res   loCap pu Capacitive part of Ip  only when   InUse  Cap   loo gt  A Pick up value scaled to primary  value  log gt  pu Pick up setting relative to the Set  parameter  Input  and the  corresponding CT value  Uo gt    Pick up setting for Uo Set  Uo   Measured Uo  Curve Delay curve family   DT Definite time  IEC Inverse time  See chapter 5 29   IEEE Set  IEEE2  RI  PrgN  Type Delay type   DT Definite time  NI Inverse time  See chapter 5 29   Vi Set  El  LTI  Paramet  ers                      83    5 10 Directional earth fault  protection l0  gt   67N     5 Protection functions    Technical description       84                                              Parameter Value Unit Description Note  t gt  s Definite operation time  for Set  definite time only   k gt  Inverse delay multiplier  for Set  inverse time only   Mode ResCap High impedance earthed nets  Sector Low impedance earthed nets S
153. cted 10 signal  This mode is used with  unearthed networks  The trip area is a half plane as  drawn in Figure 5 10 2  The base angle is usually set to  zero degrees   e Sector  This mode is used with networks earthed with a small  resistance  In this context  small  means  that a fault current  may be more than the rated phase currents  The trip area has  a shape of a sector as drawn in Figure 5 10 3  The base angle  is usually set to zero degrees or slightly on the lagging  inductive side  i e  negative angle    e Undir  This mode makes the stage equal to the undirectional stage  lo gt   The phase angle and Uo amplitude setting are discarded   Only the amplitude of the selected lo input is supervised     Input signal selection   Each stage can be connected to supervise any of the following   inputs and signals    e Input lo  for all networks other than rigidly earthed    e Input loz for all networks other than rigidly earthed    e Calculated signal locar for rigidly and low impedance earthed  networks  locale   Iu   ILo   IL3   3lo     Additionally the stage lop gt  have two more input signal alternatives  to measure current peaks to detect short restriking intermittent  earth faults    e lo1Peak to Measure the peak value of input lo1    e lo2Peak to Measure the peak value of input loz     80 V210 EN M A011    Technical description    5 Protection functions 5 10 Directional earth fault  protection l0  gt   67N        V210 EN M A011    Intermittent earth fault detection    Sh
154. ctive power  prime mover limit  is just  a vertical line while in impedance plane  Figure 5 20 1  it is a circle  touching the jX axis     117    5 20 Under impedance protection Z lt  5 Protection functions Technical description   21        When current is zero the impedance calculation gives infinite as  result  Thus the stage will not pick up in a machine stand still  situation     Two independent under impedance stages  There are two separately adjustable stages available  Z lt  and Z lt  lt      Setting groups    There are two settings groups available for each stage  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     Parameters of the under impedance stages Z lt   Z lt  lt   21                             Parameter Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  TripTime Ss Estimated time to trip  SCnir Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   setting group   L None   Dix Digital input Set   Vix Virtual input   LEDx LED indicator signal   VOx Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout           Z ohm The supervised value scaled to  primary value   Inf    infinite  Z xZn The supervis
155. d  output relays  too  Automatically  reset by a 5 minute timeout   ILmax A The supervised value  Max  of  IL1  IL2 and IL3  I gt  gt    gt  gt  gt  A Pick up value scaled to primary  value  I gt  gt   I gt  gt  gt  xIgn Pick up setting Set  t gt  gt   t gt  gt  gt  s Definite operation time Set       For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults  There are detailed information available of the eight latest faults   Time stamp  fault type  fault current  load current before the fault   elapsed delay and setting group     V210 EN M A011       Technical description 5 Protection functions 5 4 Overcurrent protection I gt   50 51        Recorded values of the overcurrent stages  8 latest faults   I gt   I gt  gt   I gt  gt  gt   50 51                             Parameter   Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Type Fault type  1 N Ground fault  2 N Ground fault  3 N Ground fault  1 2 Two phase fault  2 3 Two phase fault  3 1 Two phase fault  1 2 3 Three phase fault  Fit xlgn   Maximum fault current  Load xlgn_   1 s average phase currents before the  fault  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      V210 EN M A011 57    5 5 Directional overcurrent  protection Idi
156. dress used for  sending IO messages   Multicast TTL   1 100 Time to live of the IO messages  sent to multicast address   Vendor ID 1 65535 Identification of a vendor by  number   Device Type   0 65535 Indication of general type of  product   Product Code   1 65535 Identification of a particular  product of an individual vendor   Major 1 127 Major revision of the item the   Revision Identity Object represents   Minor 1 255 Minor revision of the item the   Revision Identity Object represents   Serial 0 4294967295 Serial number of device   Number   Product 32 chars Human readable identification   Name   Producing 1 1278 Instance number of producing   Instance assembly   Include On Off Include or exlude Run Idle   Run Idle Header in an outgoing IO   Header messages    Producing    Consuming 1 1278 Instance number of consuming   Instance assembly   Include On Off Expect presence or absence of   Run Idle Run Idle Header in an incoming   Header IO messages     Consuming                 233    9 2 Communication protocols 10 Applications Technical description       10  Applications    The device comprises all the essential protection functions needed  for a generator  except the differential protection function    Thanks to the comprehensive range of protection functions the  generator protection relay can be used as the main protection for a  variety of generators from small diesel power plants to large hydro  power plants in the power range from 1 to 100 MW     Especially versatile 
157. during fault  2                      Under reactance and loss of excitation  protection X lt   40     Synchronous machines need some minimum level of excitation to  remain stable throughout their load range  If excitation is lost or is  too low  the machine may drop out of synchronism  The loss of  excitation stages X lt  and X lt  lt   are used to supervise that the  synchronous machine is working in the stable area   The protection is based on positive sequence impedance as  viewed from the machine terminals  This impedance is calculated  using the measured three phase voltages and phase currents  according the following equation    Ui  I  Z    positive sequence impedance   U    positive sequence voltage phasor  l     positive sequence current phasor     Z     where    If this impedance goes under the steady state stability limit  the  synchronous machine may loose its stability and drop out of  synchronism     Detecting power swinging    A release time setting is available against prolonged power  swings  In a power swing situation the power phasor is swinging  back and forth between capacitive and inductive power  With a  long enough release time setting the stage accumulates the total  fault time and will eventually trip     Undercurrent blocking    When for some reason voltage collapses but currents remain at  normal load levels  the calculated impedance may fall into the trip  area  Inverted start signal from the most sensitive overcurrent  stage can be used to block t
158. e   of inverse curves with high pick up settings  See chapter 5 29 for   more information     Setting groups    There are two settings groups available for each stage  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     Parameters of the undirectional earth fault stage  lo gt   50N 51N                             Parameter Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   setting group   k None   Dix Digital input Set   VIX Virtual input   LEDx LED indicator signal   VOx Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout              lo pu The supervised value according  lo2 the parameter  Input  below   loCalc  loPeak  lo2Peak  lo gt  A Pick up value scaled to primary  value  lo gt  pu Pick up setting relative to the Set    parameter  Input  and the  corresponding CT value                         V210 EN M A011    Technical description    5 Protection functions    5 9 Earth fault protection 10 gt        V210 EN M A011                                                     50N 51N   Parameter Value Unit Description Note 
159. e duration of imported reactive  energy  ms   E  E E PULSE DURATION   Pulse duration of exported energy  ms   Eq  E E PULSE DURATION   Pulse duration of exported reactive  energy  ms   E  E E PULSE DURATION   Pulse duration of imported energy  ms   Eq  E E PULSE DURATION   Pulse duration of imported reactive  energy  ms   E  E E pulse TEST Test the exported energy pulse  Eq  E E pulse TEST Test the exported reactive energy pulse  E  E E pulse TEST Test the imported energy pulse  Eq  E E pulse TEST Test the imported reactive energy pulse  IL1 I PHASE CURRENTS Phase current IL1  A   IL2 I PHASE CURRENTS Phase current IL2  A   IL3 I PHASE CURRENTS Phase current IL3  A   ILida I PHASE CURRENTS 15 min average for IL1  A   IL2da I PHASE CURRENTS 15 min average for IL2  A   IL8da I PHASE CURRENTS 15 min average for IL3  A   lo I SYMMETRIC Primary value of zerosequence  residual  CURRENTS current lo  A   lo2 SYMMETRIC Primary value of zero   CURRENTS sequence residual current lo2  A   loC I SYMMETRIC Calculated lo  A   CURRENTS  l1 I SYMMETRIC Positive sequence current  A   CURRENTS  12 I SYMMETRIC Negative sequence current  A   CURRENTS  12 11 I SYMMETRIC Negative sequence current related to  CURRENTS positive sequence current  for  unbalance protection       THDIL I HARM  DISTORTION   Total harmonic distortion of the mean  value of phase currents      THDIL1 I HARM  DISTORTION   Total harmonic distortion of phase  current IL1      THDIL2   I HARM  DISTORTION   Total harmonic distor
160. e in  frequency  A load drop will increase the frequency and increasing  load will decrease the frequency  at least for a while  The  frequency may oscillate after the initial change  After a while the  control system of the generator  s  will drive the frequency back to  the original value  However  in case of a heavy short circuit fault  or in case the new load exceeds the generating capacity  the  average frequency keeps on decreasing     FREQUENCY ROCOF1_v3   Hz            50 0 Settings   df dt   0 5 Hz s  t 0 60s    tMin   0 60 s       49 7    TRIP M    Figure 5 19 1 An example of definite time df dt operation time  At 0 6 s  which  is the delay setting  the average slope exceeds the setting 0 5 Hz s and a trip  signal is generated     V210 EN M A011 111    5 19 Rate of change of frequency 5 Protection functions Technical description   ROCOF  protection df dt  81R        Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     Description of ROCOF implementation    The ROCOF function is sensitive to the absolute average value of  the time derivate of the measured frequency  df dt   Whenever the  measured frequency slope  df dt  exceeds the setting value for 80  ms time  the ROCOF stage picks up and issues a start signal after  an additional 60 ms delay  If the average  df dt   since the pick up  moment  still exceeds the setting 
161. e is OK  because it is above the pick up limit   This is an under voltage situation    Voltage is OK    This is an under voltage situation     The voltage Uttmin is under block limit and this is not  regarded as an under voltage situation     This is an under voltage situation   Voltage is OK    Same as G   Voltage is OK     W    onmo    Ao TT    Un    max      max U    U    Uz     UunderSelfBlocking         dead band          ea ea sl ag PEREIRAS A fea PERR  U lt  setting          block limit    time                      U lt  under voltage state    Figure 5 15 1 Under voltage state and block limit     Three independent stages    There are three separately adjustable stages  U lt   U lt  lt  and U lt  lt  lt    All these stages can be configured for definite time  DT  operation  characteristic     Setting groups    There are two settings groups available for all stages  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     100 V210 EN M A011    Technical description    5 Protection functions    5 15 Undervoltage protection U lt   27        Parameters of the under voltage stages U lt   U lt  lt   U lt  lt  lt   27                                                           Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  Digital sig
162. e outputs    The device can be configured to send a pulse whenever certain  amount of energy has been imported or exported  The principle is  presented in Figure 6 9 1  Each time the energy level reaches the  pulse size  an output relay is activated and it will stay active as  long as defined by a pulse duration setting                Configurable   100 ms   5 000 ms     lt M   Configurable        10   10 000 kWh    kvarh    Figure 6 9 1 Principle of energy pulses    The device has four energy pulse outputs  The channels are     Active exported energy  Reactive exported energy  Active imported energy  Reactive imported energy    Each channel can be connected to any combination of the output    relays using output matrix  The parameters for the energy pulses    can be found in the E menu under the submenus E PULSE SIZES  and E PULSE DURATION     Energy pulse output parameters       Parameter    Value    Unit    Description       E PULSE  SIZES    10     10 000    kWh    Pulse size of active  exported energy       10     10 000    kvarh    Pulse size of  reactive exported  energy       10     10 000    kWh    Pulse size of active  imported energy       10     10 000    kvarh    Pulse size of  reactive imported  energy       E PULSE  DURATION       100     5000    ms    Pulse length of  active exported  energy       100     5000    ms    Pulse length of  reactive exported  energy       100     5000    ms    Pulse length of  active imported  energy       Eq           100     5000
163. e restrained or voltage controlled overcurrent   function  46 l gt  Current unbalance protection  49 T gt  Thermal overload protection  50N 51N l gt   lo gt  gt   lo gt  gt  gt   Ip gt  gt  gt  gt  Earth fault protection   67N Iog gt s Tog gt  gt  Directional earth fault protection   67NT lor Intermittent transient earth fault protection  59 U gt   U gt  gt   U gt  gt  gt  Overvoltage protection  27 U lt   U lt  lt   U lt  lt  lt  Undervoltage protection  24 U f gt  Volts hertz overexcitation protection   27P Ui lt   Ui lt  lt  Positive sequence undervoltage protection  59N Uo gt   Uo gt  gt  Residual voltage protection   64F3 Uot3 lt  100   stator earth fault protection   81H 81L f gt  lt   f gt  gt  lt  lt  Overfrequency and underfrequency protection   81L f lt   f lt  lt  Under frequency protection   81R df dt gt  Rate of change of frequency  ROCOF  protection  21 Z lt   Z lt  lt  Underimpedance protection  40 Q lt  Underexcitation protection   21 40 X lt   X lt  lt  Underreactance protection  Loss of excitation   32 P lt   P lt  lt  Reverse and underpower protection   51F2 l gt  Second harmonic O C stage   51F5 lis gt  Fifth harmonic O C stage   50BF CBFP Circuit breaker failure protection  99 Prg1   8 Programmable stages             V210 EN M A011       Operation and configuration 1 General 1 2 User interface                      IEEE  IEC symbol Function name   ANSI code  50ARC Arcl gt   Optional arc fault protection  50NARC Arclo  gt   Arclos gt        Further the rela
164. e voltage 5 Protection functions Technical description  protection U0 gt   59N        Parameters of the residual overvoltage stages  Uo gt   Uo gt  gt   59N                                                     Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCntr Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  None  Dix Digital input  VIX Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   Uo   The supervised value relative to  Un V3  Uo gt   Uo gt  gt    Pick up value relative to Un V3 Set  t gt   t gt  gt  s Definite operation time Set       For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed   C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault voltage  elapsed delay and setting group     Recorded values of the residual overvoltage stages  Uo gt   Uo gt  gt   59N                       Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit     Fault voltage relative to
165. each stage  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     l0fiisblock       Setting  Tcosp Res   Ip gt s  Ising  Cap        Figure 5 10 1 Block diagram of the directional earth fault stages lo    gt  and Iyp gt  gt     81    5 10 Directional earth fault 5 Protection functions    Technical description  protection l0  gt   67N        loDir_ResCap       Figure 5 10 2 Operation characteristic of the directional earth fault protection in  Res or Cap mode  Res mode can be used with compensated networks and  Cap mode is used with ungrounded networks      90    90    Angle offset    15    55   Angle offset    32    Sector    70   Sector    120             TRIP AREA    E gt        TRIP AREA     88     loDir_SectorAdj  Figure 5 10 3 Two examples of operation characteristics of the directional earth  fault stages in sector mode  The drawn Ip phasor in both figures is inside the trip  area  The angle offset and half sector size are user   s parameters     82 V210 EN M A011    Technical description    5 Protection functions    5 10 Directional earth fault  protection l0  gt   67N        V210 EN M A011    Parameters of the directional earth fault stages  lop gt   lop gt  gt   67N                                                           Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  TripTime s Estimated time to trip  SCntr Cumulative start 
166. echnical data Technical description       Earth fault stage Ip gt   50N 51N                             Input signal lo  input X1 7  amp  8   loz   input X1 9  amp  10   locaic     ILitlLotlis   Setting range lo gt  0 005     8 00 When loor lo2  0 05     20 0 When locaic  Definite time function  DT    Operating time 0 08        300 00 s  step 0 02 s   IDMT function     Delay curve family  DT   IEC  IEEE  RI Prg    Curve type EI  VI  NI  LTI  MI   depends on the family       Time multiplier k 0 05   20 0  except  0 50     20 0 for RXIDG  IEEE and IEEE2  Start time Typically 60 ms  Reset time  lt 95 ms  Reset ratio 0 95  Inaccuracy     Starting  2  of the set value or  0 3  of the rated value    Starting  Peak mode   5  of the set value or  2  of the rated value   Sine wave  lt 65 Hz     Operating time at definite time function  1  or  30 ms    Operating time at IDMT function   5  or at least  30 ms                 El   Extremely Inverse  NI   Normal Inverse  VI   Very Inverse  LTI   Long Time Inverse  Ml  Moderately Inverse      The measuring range may limit the scope of inverse delays  See chapter 5 29 for details     Earth fault stages Io gt  gt   lo2 gt   lo2 gt  gt   50N 51N    Input signal lo  input X1 7  amp  8    lo2   input X1 9  amp  10    locatc     ILitlLo lis    Setting range lo gt  gt  0 01     8 00 When Ip or loo  0 05     20 0 When locaic             Definite time function                   Operating time 0 08        300 00 s  step 0 02 s    Start time Typically
167. ed value scaled to    per unit  pu    1 pu   1xZ    Ugn  V3xlgn                   Inf    infinite  Z lt  ohm Pick up value scaled to primary  Z lt  lt  value  Z lt  xZn Pick up setting in per unit  pu   Set  Z lt  lt  1 pu   1XZ_   Ugn  V3Xlgn    t lt  s Definite operation time Set  U1 V Measured value of positive    sequence voltage U4       l1 A Measured value of positive  sequence current       For details of setting ranges see chapter 12 3   Set   An editable value  password needed    C   Can be cleared to zero   F   Editable when force flag is on                         118 V210 EN M A011    Technical description    5 Protection functions 5 21 Under excitation protection Q lt    4    0           21     V210 EN M A011    Recorded values of the latest eight faults    There are detailed information available of the eight latest earth  faults  Time stamp  fault impedance  elapsed delay and setting    group   Recorded values of the under impedance stages Z lt   Z lt  lt   21                       Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Flt Zn   Minimum fault impedance  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      Under excitation protection Q lt   40     Synchronous machines need some minimum level of excitation to  remain stable throughout their load range  If excitation is too low   the machine may drop out of 
168. eeeeeeeeeeeeees 116  5 21  Under excitation protection Q lt   40            eeeeeeeeeeeeeee 119  5 22  Under reactance and loss of excitation protection X lt   40   122   5 23  Reverse power and under power protection P lt   32       126  5 24  Second harmonic O C stage  je gt  51F 2  n se 130  5 25  Fifth harmonic O C stage lis gt  51F5               ceeeeeeeeteeeeees 131  5 26  Circuit breaker failure protection CBFP  50BPF                132  5 27  Programmable stages  99             cccceeceeeeessseeeeeeeeeeeeeeeeee 134  5 28  Arc fault protection  50ARC 50NARC   optional              137  5 29  Inverse time Operation                  ccccceeeeeeeeeseeeeeeeeeeeeeeeeeees 140    5 29 1 Standard inverse delays IEC  IEEE  IEEE2  RI      142  5 29 2 Free parametrisation using IEC  IEEE and IEEE2    COAL OINS vies vcs ireid anan ied edd anda teed aeaaaee inc aeeu le ined in ied ined 152  5 29 3 Programmable inverse time CurveS               000 153   6  Supporting functions iiiiiiciisiiisciiecuscdcincrcntnarewenccdsndincanateatve 154  Galle  Event NOG as capes cds ara i a Omticenstecncnide 154  6 2  Disturbance reCordet                  cccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 156  6 3  Cold load pick up and inrush current detection               161  6 4  Voltage sags and SWellS               cccceeeeeeeseeeeeeeeeeeeeeeeeeees 164  6 5  Voltage interruptions               ccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee 166  6 6  Current transformer SUperVISION                  eeeeeeeeeee
169. eeeeeees 168  6 7  Voltage transformer supervision                    cceeeeeeeeeeeeees 169  6 8  Circuit breaker condition mMonitoring                cccceeeeeee 170  6 9  Energy pulse outputs                  cccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 175  6 10  System clock and synchronization                  ccceeeeeeeeeees 178  6 11  Running hour COUNTEL                 cceeeeeeeeeeeeeeeeteeeeeeeeeeeeteees 181  G  T2 METS aea r eee  182  6 13  Combined overcurrent Status              eeeeeeeeeeeeeeeeeeeeeeeeeees 184  6 14  Self SUPEIVISION 00    eeeeeeeeeeeeeeeeeeeee eee eeeeeeeeeeeeeeeeeeeeeeeeees 186    V210 EN M A011    Table of Contents       V210 EN M A011    7  Measurement functions          ccceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeneeeeeees 187  7 1  Measurement accuracy           ccccceeeeeeeeeeeeteeeeeeeeeeeteeeeeaeees 188  7 2  Harmonics and Total Harmonic Distortion  THD             189  7 3  Demand vale Serinin 190  7 4  Minimum and maximum Values             cccccccccccceeeeeeeeeeees 191  7 5  Maximum values of the last 31 days and twelve months192  7 6  Voltage measurement Mode                    ccceeeeeeeeeeeeeeeeeees 193  7 7  Power calculation aire ce ernncesnencee atl eneee 195  7 8  Direction of power and CUITeNnt             ccccccccceeeeeeeeeeeeeeees 197  7 9  Symmetric COMPONEINS    tce a ctrecteistecetsoeteteliueteiettntes 198  7 10  Primary  secondary and per unit scaling                0000 202   ZOO GUN CNESCANING 22 2 Mec hs areca rtdechusdiven tena 202  
170. egardless of the measurement mode     NOTE  When the 100   stator earth fault stage U0f3 lt  is to be used  the mode     2LL Uo  must be used and the zero sequence voltage must be measured  from the generator s neutral point as in Error  Reference source not found      L1 L2 L3  2Line Uo            2Line_Uo_1 15     Figure 7 6 1 The device is connected to line to line voltages from V connected   open delta  voltage transformers  The zero sequence voltage is measured with  a voltage transformer between neutral point and ground  Voltage measurement  mode is set to  2LL U       193    7 6 Voltage measurement mode 7 Measurement functions Technical description       L1 L2 L3  2Line Uo         2Line_Uo_2 15     Figure 7 6 2 The device is connected to line to line voltages from three Y   connected voltage transformers  The zero sequence voltage is measured with  VT tertiaries in a broken delta connection  Voltage measurement mode is set to   2LL Up      LI L2 L3  3Phase  VAMP 210       3Phase 15     Figure 7 6 3 The device is connected to phase to ground voltages from three Y   connected voltage transformers  The zero sequence is calculated internally   Voltage measurement mode is set to  3LN      194 V210 EN M A011    Technical description 7 Measurement functions 7 7 Power calculation       7 7  Power calculation    The power calculation in VAMP relays are dependent on the  voltage measurement mode  see chapter 7 6  The equations used  for power calculations are described in this c
171. elay  U gt  stage only  Set  Hyster 3   Dead band size i e  hysteresis Set   default              For details of setting ranges see chapter 12 3    Set   An editable parameter  password needed   C   Can be cleared to zero  F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault voltage  elapsed delay and setting group     Recorded values of the overvoltage stages  8 latest faults   U gt   U gt  gt   U gt  gt  gt   59                                Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit  Un   Maximum fault voltage  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2             92    V210 EN M A011    Technical description    5 Protection functions 5 13 Volts hertz over excitation  protection Uf gt   24        5 13     Volts hertz over excitation protection  Ur  24     The saturation of any inductive network components like  transformers  inductors  motors and generators  depend on the  voltage and frequency  The lower the frequency  the lower is the  voltage at which the saturation begins     The volts hertz over excitation protection stage is sensitive to the  voltage frequency ratio instead of voltage only  Figure 5 13 1  shows the difference between volts hertz and a standard  overvoltage function  The maximum of the t
172. elay tybe Parameter  y  YP A B C D E  MI Moderately inverse 0 1735 0 6791 0 8  0 08 0 1271  NI Normally inverse 0 0274 2 2614 0 3   1899 9 1272  VI Very inverse 0 0615 0 7989 0 34  0 284 4 0505  El Extremely inverse 0 0399 0 2294 0 5 3 0094 0 7222       148    V210 EN M A011       Technical description 5 Protection functions 5 29 Inverse time operation       Example for Delay type  Moderately inverse  Ml       k   0 50       4pu  Ipickup   2pu   A   0 1735  B   0 6791  C   0 8   D    0 08  E   0 127    0 6791  0 08 0 127   4   4 2   4 3  6  08      0 8     0 8   2 2 2    The operation time in this example will be 0 38 seconds  The  same result can be read from Figure 5 29 1 11     M IEEE2 MI  400    t  0 5   0 1735           0 38       ei IEEE2 NI    400    200 200    100  80  60    40    100  80    20    delay  s   delay  s     0 2    0 1  0 08       0 08 k 0 5  0 06 0 06  T 2 3 4 5678 10 20 1 2 3 4 5678 10 20  TIset inverse DelayIEEE2_MI Tset inverse DelayIEEE2_NI  Figure 5 29 1 11 IEEE2 moderately Figure 5 29 1 12 IEEE2 normal inverse  inverse delay delay    V210 EN M A011 149    5 29 Inverse time operation    5 Protection functions    Technical description       150    ie IEEE2 VI  400    100    60  40    N  3    0  8  Ta   2 6  4  2  g 2 k 20  1 k 10  0 8  0 6 k 5  0 4  0 2 2  0 1    0 08    0 06 k 0 5  1 2 3 4 5678 10 20  set inverse  DelayIEEE2_VI    Figure 5 29 1 13 IEEE2 very inverse  delay       a IEEE2 EI  400    200    100    delay  s     k 20    06 k 10    k 5   
173. ement accuracy    The rated CT secondary may also be less than the rated input but  the measurement accuracy near zero current will decrease     VOLTAGE SCALING   Rated VT primary voltage  Uprim    Rated VT secondary voltage  Usec   Rated UO VT secondary voltage  Uosec   Voltage measuring mode  Umode     GENERATOR SETTING    Rated voltage of the generator or motor  Ugn     e Rated power of the generator or motor  Sgn     e Rated shaft power of the prime mover  Pm   If this value is not  known  set it equal to Sgn  The reverse power and underpower  stages do use this value as reference for 1 00 per unit    e Rated current of the generator calculated by the device  Ign     e Rated impedance of the generator or motor calculated by the  device  Zgn     e Existence of any unit transformer between VTs and CTs   Trafo   In case the VTs are on the bus side of the transformer  and CTs are on the generator side  this parameter is set equal  to  On   The generator may have a unit transformer  but if the  VTs and CTs are on the same side of this transformer  this  parameter is set equal to  Off     e Connection group of the unit transformer  if any  IEC marking  with capital letters Y and D for bus side and small case letters y  and d for generator side combined with the dial hour is used   For example Yd11 means a wye delta transformer where the  delta side phase to ground voltages are leading 30   the wye  side phase to ground voltages    e Rated busbar side voltage of the unit transfo
174. ends of the communication  letter in the order code  See Figure 9 1 1  chapter 11 and the table  below  The TTL interface is for external converters and converter  cables only  It is not suitable for direct connection to distances  more than one meter                          Parameters  Parameter   Value Unit   Description Note  Protocol Protocol selection for Set  remote port  None    SPA bus SPA bus  slave   ProfibusDP Profibus DB  slave   ModbusSla Modbus RTU slave  ModbusTCPs Modbus TCP slave  IEC 103 IEC 60870 5 103  slave   ExternallO Modbus RTU master for  external I O modules  DNP3 DNP 3 0  Msg  0    29 1 Message counter since the   Clr  device has restarted or  since last clearing  Errors 0    2 81 Protocol errors since the Cir  device has restarted or  since last clearing  Tout 0    2 81 Timeout errors since the Cir  device has restarted or  since last clearing  Display of current 1   communication parameters   speed   bit s  speed DPS D   number of data bits  P   parity  none  even  odd  S   number of stop bits  Debug Echo to local port Set  No No echo  Binary For binary protocols  ASCII For SPA bus protocol                         Set   An editable parameter  password needed     Clr   Clearing to zero is possible    1  The communication parameters are set in the protocol specific menus  For  the local port command line interface the parameters are set in configuration    menu     219    9 1 Communication ports    9 Communication    Technical description       9 1
175. ent   Nominal power of the prime mover   Used by reverse under power  protection     See VT    Per unit  Depending of the context the per unit refers to any nominal    value  For example for overcurrent setting 1 pu   1Xlen   Reactive power  Unit    var  acc  IEC   Root mean square   Apparent power  Unit    VA    Nominal power of the protected device   Simple Network Time Protocol for LAN and WWW   Trip circuit supervision   Total harmonic distortion    Voltage at input U  at zero ohm earth fault   Used in voltage  measurement mode  2LL Uo      Voltage input for U42 or U_  depending of the voltage measurement mode  Voltage input for U23 or UL2 depending of the voltage measurement mode  Voltage input for Us  or Uo depending of the voltage measurement mode  Nominal voltage of the protected device   Nominal voltage  Rating of VT primary or secondary   Coordinated Universal Time  used to be called GMT   Greenwich Mean  Time    Voltage transformer i e  potential transformer PT   Nominal primary value of voltage transformer   Nominal secondary value of voltage transformer    World wide web   internet    287    14 Construction Operation and configuration  instructions       14  Construction    PANEL MOUNTING VAMP 200 SERIES 190  7 48        mm             SEMI FLUSH VAMP 200 SERIES      _Raising trame   A Ta o   Fixngbracket    VYX076 40mm 1 57in 69mm 6 65in Standard for 200 series 5 20  VYX077 60mm  2 36in  149mm 5 87In Standard for 200 serles 0 79     VYX233 100 mm 3 94in 109mm 4 
176. ent lo1  S1   7 EY 9 lo2  S1  Residual current lo2  S1   9 g 11 Ua  a  Line to line voltage U12  a  or phase to neutral voltage UL1  a   11 13   Ub  a  Line to line voltage U23  a  or phase to neutral voltage UL2  a   ii  ey ite t     35 g 17   Uc  dn n  Zero sequence voltage Uo  dn  or phase to neutral voltage UL3  b     19         17  B  19   amp    o   Terminal X1 right side       No  Symbol Description  2 IL1  S2  Phase current L1  S2   G 2 f4 IL2  S2  Phase current L2  S2   E 41 6 IL3  S2  Phase current L3  S2   S 6  8 lo1  S2  Residual current lo1  S2   E  8 10  lo2  S2  Residual current lo2  S2     10112   Ua  b n  Line to line voltage U12  b  or phase to neutral voltage UL1  n     42  14   Ub  b n  Line to line voltage U23  b  or phase to neutral voltage UL2  n   Q Ilr te t       Q i 18  Uc  da a  Zero sequence voltage Uo  da  or phase to neutral voltage UL3  a   f 20         RI 18  A 20                                                             250    V210 EN M A011          Technical description    11 Connections    11 1 Rear panel view       Terminal X2 without the analogue output                                                                                                                                                                   No  Symbol Description  1l S J ics i  all      2l  a  ail    ees 2  4l      4 I  E  5    5 A5 Alarm relay 5  6    6 A5 Alarm relay 5  7 S 7 A4 Alarm relay 4  8    8 A4 Alarm relay 4  all    ee ale a  10 Ze 10  A3 COM   Alarm rel
177. er and under power stages P lt   P lt  lt   32                          Pick up setting range    200 0      200 0  Pm   Definite time function      Operating time 0 3     300 0 s   Start time Typically 200 ms   Reset time  lt 500 ms   Reset ratio 1 05   Inaccuracy      Starting  3   of set value or  0 5   of rated value    Operating time at definite time function  1   or  150 ms       NOTE  When pick up setting is  1      200  an internal block will be activated if  max  voltage of all phases drops below 5  of rated           12 3 5  Second harmonic function  2  Harmonic stage  51F2   Settings     Setting range 2 Harmonic 10 100     Operating time 0 05     300 00 s  step 0 01 s   Inaccuracy     Starting  1   unit                NOTE  The amplitude of second harmonic content has to be at least 2  of the  nominal of CT  If the moninal current is 5 A  the 100 Hz component needs  to exceed 100 mA     12 3 6  Fifth harmonic function    5  Harmonic stage Ij5 gt   51F5        Settings     Setting range 2 Harmonic 10 100     Operating time 0 05     300 00 s  step 0 01 s        Inaccuracy     Starting  2   unit                NOTE  The amplitude of second harmonic content has to be at least 2  of the  nominal of CT  If the moninal current is 5 A  the 250 Hz component needs  to exceed 100 mA    282 V210 EN M A011    Technical description    12 Technical data    12 3 Protection functions       12 3 7     12 3 8     V210 EN M A011    Circuit breaker failure protection    Circuit breaker 
178. et  Undir Undirectional mode  Offset o Angle offset for RecCap and Set  Sector modes  ChCtrl Res Cap control in mode  ResCap  Res Fixed to Resistive characteristic Set  Cap Fixed to Capacitive  DI1   6 characteristic  VIH   4 Controlled by digital input  Controlled by virtual input  InUse Selected submode in mode  ResCap   2 Mode is not ResCap  Res Submode   resistive  Cap Submode   capacitive  Input lot X1 7 amp 8  See chapter 11  lo2 X1 9 amp 10  loCalc IL1   IL2   IL3 Set  lo1 Peak X1 7 amp 8 peak mode  log gt  only   lo2Peak X1 9 amp 10 peak mode  Ig gt  only   Intrmt s Intermittent time Set  Dly20x s Delay at 20xlset  Dly4x S Delay at 4xlset  Dly2x s Delay at 2xlset  Dly1x s Delay at 1xlset  A  B  C  D  User s constants for standard Set  E equations  Type Parameters   See chapter 5 29                       For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults    There is detailed information available of the eight latest earth  faults  Time stamp  fault current  elapsed delay and setting group     V210 EN M A011    Technical description    5 Protection functions 5 11 Intermittent transient earth fault  protection IOINT gt   67NI        5 11     V210 EN M A011    Recorded values of the directional earth fault stages  8 latest  faults  lo    gt   lop gt  gt   67N                             Parameter Value Unit   Descrip
179. et inverseDelayIEEE1_STEI    Figure 5 29 1 10 ANSI IEEE short time  extremely inverse delay    147    5 29 Inverse time operation    5 Protection functions Technical description       IEEE2 inverse time operation    Before the year 1996 and ANSI standard C37 112 microprocessor  relays were using equations approximating the behaviour of  various induction disc type relays  A quite popular approximation  is Equation 5 29 1 3  which in the device is called IEEE2  Another  name could be IAC  because the old General Electric IAC relays  have been modeled using the same equation     There are four different delay types according Table 5 29 1 4  The  old electromechanical induction disc relays have inverse delay for  both trip and release operations  However  in the device only the  trip time is inverse the release time being constant    The operation delay depends on the measured value and other  parameters according Equation 5 29 1 3  Actually this equation  can only be used to draw graphs or when the measured value   is  constant during the fault  A modified version is implemented in the  relay for real time usage     Equation 5 29 1 3                                                             B D E  t k  A    z  i  I I I     Aa c   C  C  pickup Tiii Tiii A  t   Operation delay in seconds  k   Users multiplier      Measured value  lpickup   User s pick up setting  A B C D   Constant parameter according Table 5 29 1 4   Table 5 29 1 4 Constants for IEEE2 inverse delay equation  D
180. et of restart   This value can be cleared if the operating level is at least   Operator     e SetGrp 1  The active setting group is one  This value can be edited if the  operating level is at least  Operator   Setting groups are  explained in chapter 2 2 3    e SGrpDI      The setting group is not controlled by any digital input  This  value can be edited if the operating level is at least   Configurator      e Force Off    The status forcing and output relay forcing is disabled  This  force flag status can be set to  On  or back to  Off  if the  operating level is at least  Configurator   If no front panel    V210 EN M A011    Operation and configuration    2 Local panel user interface 2 2 Local panel operations       V210 EN M A011    button is pressed within five minutes and there is no  VAMPSET communication  the force flag will be set to  Off   position  The forcing is explained in chapter 2 3 4     Second menu of I gt  gt  50 51 stage    second menu    AV lt   gt    gt  gt  SET 50 51  Stage setting group 1  ExDI ILmax 403A   ExDO   Status      Prot I gt  gt  1013A   gt  gt  2 50xlgn  t gt  gt  0 60s       Figure 2 2 2 2  Second menu  next on the right  of l gt  gt  50 51 stage    This is the main setting menu  The content is    e Stage setting group 1  These are the group 1 setting values  The other setting group  can be seen by pressing push and then or  lt    Setting groups are explained in chapter 2 2 3    e ILmax 403A    The maximum of the three measured phase curre
181. etting must be below  this minimum value  A typical operation delay is one minute     Blocking the protection   The squelch of voltage measurement will block the stage when the  generator is stopped  Using the block matrix  blocking by under   voltage  under power  CB position and other blocking schemes are  possible     Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     V210 EN M A011 107    5 17 100  stator earth fault 5 Protection functions Technical description  protection U0f3 lt   64F3        Parameters of the 100   stator earth fault stage Upois lt   64F3                                   Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  i None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  vox Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   Uof8   The supervised value relative to  Uon  For Uon see chapter 7 2   Uof8 lt    Pick up value relative to Uon  Set  For Uon see chapter 7 2   t lt  min Definite operation time in Set  minutes            
182. exported power is 50 MW    Pulse size is 10 kWh    The average pulse frequency will be 1900 10   190 pulses h   The peak pulse frequency will be 50000 10   5000 pulses h   Set pulse length to 3600 5000     0 2   0 5 s or less     The lifetime of the mechanical output relay will be  50x10   190 h   30 a     V210 EN M A011    Technical description    6 Supporting functions    6 9 Energy pulse outputs       VAMP 210    Active exported 4  energy pulses    Reactive exported      energy pulses    Active imported _  energy pulses    Reactive imported _   energy pulses    Figure 6 9 2 Application example of wiring the energy pulse outputs to a PLC    q    q                               PLC    Pulse counter input 1    Pulse counter input 2    Pulse counter input 3    Pulse counter input 4       e pulseconfl    having common plus and using an external wetting voltage    VAMP 210    Active exported 4   energy pulses    Reactive exported 4  energy pulses    Active imported p      energy pulses    Reactive imported _   energy pulses    Figure 6 9 3 Application example of wiring the energy pulse outputs to a PLC  having common minus and using an external wetting voltage    VAMP 210    Active exported  energy pulses    Reactive exported  energy pulses    Active imported _   energy pulses    Reactive imported  E  energy pulses    Figure 6 9 4 Application example of wiring the energy pulse outputs to a PLC    q    q       q    q                                                                
183. face 2 2 Local panel operations       2 2     2 2 1     V210 EN M A011    Local panel operations    The front panel can be used to control objects  change the local   remote status  read the measured values  set parameters  and to  configure relay functions  Some parameters  however  can only be  set by means of a PC connected to one of the local  communication ports  Some parameters are factory set     Navigating in menus    All the menu functions are based on the main menu submenu  structure     1  Use the arrow keys and to move up and down in the  main menu     2  To move to a submenu  repeatedly push until the required    submenu is shown  Correspondingly  push to return to the  main menu     3  Push to confirm the selected submenu  If there are more  than six items in the selected submenu  a black line appears to  the right side of the display  Figure 2 2 1 1   It is then possible  to scroll down in the submenu     4  Push to cancel a selection     5  Pushing the or key in any position of a sub menu   when it is not selected  brings you directly one step up or down  in the main menu     The active main menu selection is indicated with black back   ground color  The possible navigating directions in the menu are  shown in the upper left corner by means of black triangular  symbols     scroll    ENABLED STAGES 3    U gt  On  U gt  gt  On    U gt  gt  gt  On  U lt  Off  U lt  lt  Off  U lt  lt  lt  Off       Figure 2 2 1 1  Example of scroll indication    15    2 2 Local pa
184. failure protection CBFP  50BF        Relay to be supervised    T1 or T2        Definite time function    Operating time    0 1     10 0 s  step 0 1 s              Reset time  lt 95 ms  Inaccuracy    Operating time  20 ms                This setting is used by CB condition monitoring function  too     Arc fault protection stages  option     Arc protection stage Arcl gt   50ARC   option       Setting range   Arc sensor connection     Operating time  Light only      Operating time  4xlset   light     Operating time  BIN      Operating time  Delayed Arc L gt      BO operating time   Reset time   Reset time  Delayed ARC L   Reset time  BO    Reset ratio   Inaccuracy      Starting     Operating time         Delayed ARC light       0 5   10 0 x In   1  S2  S1 S2  BI  S1 Bl  S2 Bl  S1 S2 BI  13 ms   17ms   10 ms  0 01 0 15s   lt 3 ms    lt 95 ms    lt 120 ms    lt 85 ms   0 90    10  of the set value   5 ms   10 ms          Arc protection stage Arclo gt   50NARC   option       Setting range   Arc sensor connection     Operating time  Light only      Operating time  4xlset   light     Operating time  BIN      Operating time  Delayed Arc L gt      BO operating time   Reset time   Reset time  Delayed ARC L   Reset time  BO    Reset ratio   Inaccuracy      Starting     Operating time     Delayed ARC light          0 5   10 0 x In   1  S2  S1 S2  BI  S1 Bl  S2 Bl  S 1 S2 BI  13 ms   17ms   10 ms  0 01 0 15s   lt 3 ms    lt 95 ms    lt 120 ms    lt 85 ms   0 90    10  of the set value   5 
185. g 16  current  time  points   The relay interpolates the values between given points with  2nd degree polynomials  This mode is activated by setting  curve family to    PrgN     There are maximum three different  programmable curves available at the same time  Each  programmed curve can be used by any number of protection  stages  See chapter 5 29 3     V210 EN M A011    Technical description    5 Protection functions 5 29 Inverse time operation       V210 EN M A011    Local panel graph    The relay will show a graph of the currently used inverse delay on  the local panel display  Up and down keys can be used for  zooming  Also the delays at 20xlser  4xlse7 and 2xlser are shown     Inverse time setting error signal    If there are any errors in the inverse delay configuration the  appropriate protection stage will use definite time delay     There is a signal    Setting Error    available in output matrix  which  indicates three different situations     1  Settings are currently changed with VAMPSET or local panel   and there is temporarily an illegal combination of  curve delay points  For example if previous settings were  IEC NI and then curve family is changed to IEEE  the setting  error will active  because there is no NI type available for IEEE  curves  After changing valid delay type for IEEE mode  for  example MI   the    Setting Error    signal will release    2  There are errors in formula parameters A   E  and the device is  not able to build the delay curve   3  T
186. g a digit in a numerical     lt A gt            oN    value       5  Additional information key  O    NOTE  The term  which is used for the buttons in this manual  is inside the    brackets     V210 EN M A011    Operation and configuration    2 Local panel user interface    2 1 Relay front panel       2 1 4     V210 EN M A011    Operation Indicators  The relay is provided with eight LED indicators        CO Power     C  Error     Com        Alarm      Trip  OA     B  DE             Figure 2 1 4 1  Operation indicators of the relay                            LED indicator Meaning Measure  Remarks   Power LED lit The auxiliary power has Normal operation state  been switched on   Error LED lit Internal fault  operates in The relay attempts to  parallel with the self reboot  REBOOT   If the  supervision output relay error LED remains lit  call   for maintenance    Com LED lit or The serial bus is in use and   Normal operation state   flashing transferring information   Alarm LED lit One or several signals of The LED is switched off  the output relay matrix have   when the signal that  been assigned to output LA   caused output Al to  and the output has been activate  e g  the START  activated by one of the signal  is reset  The  signals   For more resetting depends on the  information about output type of configuration   matrix  please see chapter connected or latched   2 4 5     Trip LED lit One or several signals of The LED is switched off  the output relay matrix have   when t
187. g flag is  needed as in forcing i e  the output relays     The forced time is valid until the next forcing or until the next  reversing timed act from the timer itself    The status of each timer is stored in non volatile memory when the  auxiliary power is switched off  At start up  the status of each timer  is recovered     V210 EN M A011    Technical description    6 Supporting functions    6 12 Timers       V210 EN M A011    Setting parameters of timers                   Parameter   Value Description  TimerN Timer status    Not in use  0 Output is inactive  1 Output is active  On hh mm ss Activation time of the timer  Off hh mm ss De activation time of the timer  Mode For each four timers there are 12 different  modes available      The timer is off and not running  The output is  off i e  O all the time   Daily The timer switches on and off once every day   Monday The timer switches on and off every Monday   Tuesday The timer switches on and off every Tuesday   Wednesday   The timer switches on and off every  Wednesday   Thursday The timer switches on and off every Thursday   Friday The timer switches on and off every Friday   Saturday The timer switches on and off every Saturday   Sunday The timer switches on and off every Sunday   MTWTF The timer switches on and off every day except  Saturdays and Sundays  MTWTFS The timer switches on and off every day except  Sundays   SatSun The timer switches on and off every Saturday             and Sunday           183    6 13 Com
188. g functions Technical description       6 14     186    Self supervision    The functions of the micro controller and the associated circuitry   as well as the program execution are supervised by means of a  separate watchdog circuit  Besides supervising the relay  the  watchdog circuit attempts to restart the micro controller in a fault  situation  If the restarting fails  the watchdog issues a self   supervision alarm indicating a permanent internal fault     When the watchdog circuit detects a permanent fault  it always  blocks any control of other output relays  except for the self   supervision output relay      In addition  the internal supply voltages are supervised  Should the  auxiliary supply of the relay disappear  an alarm is automatically  given because the internal fault  IF  output relay functions on a  working current principle  This means that the IF relay is energized  when the auxiliary supply is on and no internal fault is detected     V210 EN M A011    Technical description 7 Measurement functions 6 14 Self supervision       7  Measurement functions    All the direct measurements are based on fundamental frequency  values   The exceptions are frequency and instantaneous current  for arc protection   The figure shows a current waveform and the  corresponding fundamental frequency component  second  harmonic and rms value in a special case  when the current  deviates significantly from a pure sine wave                     es L oad   0    100        i i i   
189. g in the same X4 connector     NOTE  When the VX003 cable is inserted to the front panel connector it activates  the front panel port and disables the rear panel local port by connecting  the DTR pin 6 and DSR pin 4 together  See Figure 9 1 1     Protocol for the local port   The front panel port is always using the command line protocol for  VAMPSET regardless of the selected protocol for the rear panel  local port    If other than  None  protocol is selected for the rear panel local  port  the front panel connector  when activated  is still using the  plain command line interface with the original speed  parity etc   For example if the rear panel local port is used for remote  VAMPSET communication using SPA bus default 9600 7E1  it is  possible to temporarily connect a PC with VAMPSET to the front  panel connector with the default 38400 8N1  While the front panel  connector is in use  the rear panel local port is disabled  The  communication parameter display on the local display will show  the active parameter values for the local port     Physical interface  The physical interface of this port is RS 232     V210 EN M A011 217    9 1 Communication ports    9 Communication    Technical description                                                    Parameters  Parameter   Value Unit   Description Note  Protocol Protocol selection for the Set  rear panel local port   None Command line interface for  VAMPSET  SpaBus SPA bus  slave   ProfibusDP Profibus DB  slave   ModbusSla M
190. ge transformer  VT  voltage V3    e LL Uo  The zero sequence voltage is measured with voltage  transformer s  for example using a broken delta connection   The setting values are relative to the VTo secondary voltage  defined in configuration    NOTE  The Up signal must be connected according the connection diagram    Figure 10 2 1  in order to get a correct polarization  Please note that   actually the negative Uo     Up  is connected to the relay     V210 EN M A011 79    5 10 Directional earth fault 5 Protection functions Technical description  protection l0  gt   67N        Modes for different network types  The available modes are     e ResCap  This mode consists of two sub modes  Res and Cap  A digital  signal can be used to dynamically switch between these two  sub modes  This feature can be used with compensated  networks  when the Petersen coil is temporarily switched off   o Res  The stage is sensitive to the resistive component of the  selected lo signal  This mode is used with compensated  networks  resonant grounding  and networks earthed  with a high resistance  Compensation is usually done  with a Petersen coil between the neutral point of the  main transformer and earth  In this context  high  resistance  means  that the fault current is limited to be  less than the rated phase current  The trip area is a half  plane as drawn in Figure 5 10 2  The base angle is  usually set to zero degrees   o Cap  The stage is sensitive to the capacitive component of  the sele
191. gic matrix   Additional information can be obtained from the separate   documents    IEC 61850 conformance statement pdf        IEC 61850   Protocol data pdf    and    Configuration of IEC 61850 interface pdf      on our website     230 V210 EN M A011    Technical description    9 Communication    9 2 Communication protocols       V210 EN M A011    IEC 61850 main config parameters                                        Parameter   Value Unit   Description Set  Port 0   64000 IP protocol port Set  Check Yes   No If the checkbox  Check Set  upper upper addresses    is  addresses checked the below  parameters are also  checked and used for  addressing when the  client is communicating to  the device  by default this  is disabled   The below parameters  are ACSE association  parameters described in  the standard part 61850   8 1  AP ID nnn nnn nann nnn ACSE AP title value Set  AE 0     64000 ACSE AE qualifier  Qualifier  P Selector 0     4200000000 Presentation selector  S Selector 0     64000 Session selector  T Selector 0     64000 Transport selector  IED Name   String Identifcation of the device   Each device must have  unique name   Delete command Send command to clear  dynamic all dynamic datasets  datasets                      231    9 2 Communication protocols    9 Communication Technical description       9 2 10     232    EtherNet IP    The relay supports communication using EtherNet IP protocol  which is a part of CIP  Common Industrial Protocol  family   EtherNet IP pr
192. gt      U gt  gt  gt    Definite time characteristic     operating time U gt   U gt  gt      operating time U gt  gt  gt   Starting time   Resetting time U gt   Resetting time U gt  gt   U gt  gt  gt   Retardation time   Reset ratio   Inaccuracy      starting     operate time          50   150  Un      50   160   Un        0 08      300 00 s  step 0 02    0 06    300 00 s  step 0 02    Typically 60 ms   0 06   300 00 s  step 0 02     lt 95 ms    lt 50 ms   0 99     0 800  0 1     20 0    step 0 1        3  of the set value       1  or  30 ms             This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts       The measurement range is up to 175 V  This limits the maximum usable setting when rated VT    secondary is more than 100 V     Volts hertz over excitation protection U  gt   24                   Operating time at definite time function       Pick up setting range 100     200    Operating time 0 3     300 0 s  Start time Typically 200 ms  Reset time  lt 450 ms   Reset ratio 0 995  Inaccuracy      Starting U  lt  0 5   unit    f  lt  0 05 Hz   1   or  150 ms             Positive sequence undervoltage stages U  lt   U  lt  lt   27P        Setting range    20     120  x Uan       Definite time function     Operating time    0 08         300 00 s       Undervoltage blocking    Blocking time  when I lt  1  x Ign    2     100  x Uen  common for both stages   0 30s  common for both st
193. hapter     The relay is connected to line to line voltages    When the relay is connected to line to line voltages  the voltage  measurement mode is set to equal to  2LL Uo   The following  Aron equation is used for power calculation     S U   Thy  U33 Ty   where    Three phase power phasor         Measured voltage phasor corresponding the  fundamental frequency voltage between phases L1 and  L2     I    Complex conjugate of the measured phase L1  fundamental frequency current phasor    U     Measured voltage phasor corresponding the  fundamental frequency voltage between phases L2 and  L3    I       Complex conjugate of the measured phase L3   fundamental frequency current phasor     Q    l        Apparent power  active power and reactive power are calculated  as follows    s   s   P   real S   Q  imag S     COs oe  f S    V210 EN M A011 195    7 7 Power calculation    7 Measurement functions Technical description       196    The relay is connected to line to neutral voltage    When the relay is connected to line to neutral voltages  the  voltage measurement mode is set to equal to  3LN   The following  equation is used for power calculation        S  U nla  U  lia  U  Iis  where    Three phase power phasor   Measured voltage phasor corresponding the  fundamental frequency voltage of phase L1   Complex conjugate of the measured phase L1  fundamental frequency current phasor   Measured voltage phasor corresponding the  fundamental frequency voltage of phase L2   Complex conj
194. he Set  10 characters local display  Default is  DIn   n 1   6  Description String of max  Long name for Dls  Default   Set  32 characters is   Digital input n   n 1   6                Set   An editable parameter  password needed     Virtual inputs and outputs    There are four virtual inputs and six virtual outputs  The four virtual  inputs acts like normal digital inputs  The state of the virtual input   can be changed from display  communication bus and from  VAMPSET  For example setting groups can be changed using    virtual inputs     Parameters of virtual inputs                               Parameter Value Unit   Description Set  Vit    VI4 0 Status of virtual input  1  Events On Event enabling Set  Off  NAMES for VIRTUAL INPUTS  editable with VAMPSET only   Label String of max  Short name for VIs on the Set  10 characters local display  Default is  VIn   n 1   4  Description String of max  Long name for Vis  Default   Set  32 characters is   Virtual input n   n 1   4                Set   An editable parameter  password needed     The six virtual outputs do act like output relays  but there are no  physical contacts  Virtual outputs are shown in the output matrix  and the block matrix  Virtual outputs can be used with the user s  programmable logic and to change the active setting group etc     V210 EN M A011    Technical description    8 Control functions 8 4 Output matrix       8 4     V210 EN M A011    Output matrix    By means of the output matrix  the output signa
195. he VAMPSET program can communicate using the  local RS 232 port or using ethernet interface  It is also possible to  select SPA bus protocol for the local port and configure the  VAMPSET to embed the command line interface inside SPA bus  messages  For ethernet interface configuration see chapter 9 1 4     Modbus TCP and Modbus RTU    These Modbus protocols are often used in power plants and in  industrial applications  The difference between these two protocols  is the media  Modbus TCP uses Ethernet and Modbus RTU uses  asynchronous communication  RS 485  optic fibre  RS 232    VAMPSET will show the list of all available data items for Modbus   A separate document    Modbus parameters pdf    is also available   The Modbus communication is activated usually for remote port  via a menu selection with parameter  Protocol   See chapter 9 1     For ethernet interface configuration see chapter 9 1 4                 Parameters  Parameter   Value Unit   Description Note  Addr 1     247 Modbus address for the Set  device   Broadcast address 0 can  be used for clock  synchronizing  Modbus  TCP uses also the TCP  port settings   bit s 1200 bps   Communication speed for Set  2400 Modbus RTU  4800  9600  19200  Parity None Parity for Modbus RTU Set  Even  Odd                         Set   An editable parameter  password needed     V210 EN M A011    Technical description 9 Communication 9 2 Communication protocols       9 2 3  Profibus DP    The Profibus DP protocol is widely used in ind
196. he operation delay  counter is not cleared between adjacent faults and finally the stage  will trip     Four or six independent undirectional earth fault overcurrent  stages    There are four separately adjustable earth fault stages  lo gt   lo gt  gt    Ip gt  gt  gt   and lo    gt  gt  gt  gt   The first stage lo gt  can be configured for definite  time  DT  or inverse time operation characteristic  IDMT   The  other stages have definite time operation characteristic  By using  the definite delay type and setting the delay to its minimum  an  instantaneous  ANSI 50N  operation is obtained     Using the directional earth fault stages  chapter 5 10  in  undirectional mode  two more stages with inverse operation time  delay are available for undirectional earth fault protection     75    5 9 Earth fault protection 10 gt    50N 51N     5 Protection functions Technical description       76    Inverse operation time  Ip gt  stage only     Inverse delay means that the operation time depends on the  amount the measured current exceeds the pick up setting  The  bigger the fault current is the faster will be the operation   Accomplished inverse delays are available for the Io gt  stage  The  inverse delay types are described in chapter 5 29  The relay will  show a scaleable graph of the configured delay on the local panel  display     Inverse time limitation    The maximum measured secondary residual current is 10xloy and  maximum measured phase current is 50xIn  This limits the scop
197. he signal that  been assigned to output Tr    caused output Tr to  and the output has been activate  e g  the TRIP  activated by one of the signal  is reset  The  signals   For more resetting depends on the  information about output type of configuration   relay configuration  please connected or latched   see chapter 2 4 5     A  C LED lit Application related status Configurable       indicators              13    2 1 Relay front panel    2 Local panel user interface Operation and configuration  instructions       Resetting latched indicators and output relays    All the indicators and output relays can be given a latching  function in the configuration     There are several ways to reset latched indicators and relays   e From the alarm list  move back to the initial display by pushing    a for approx  3 s  Then reset the latched indicators and    output relays by pushing ox   e Acknowledge each event in the alarm list one by one by    pushing equivalent times  Then  in the initial display  reset  the latched indicators and output relays by pushing SK  The latched indicators and relays can also be reset via a remote    communication bus or via a digital input configured for that  purpose     Adjusting display contrast    The readability of the LCD varies with the brightness and the  temperature of the environment  The contrast of the display can be  adjusted via the PC user interface  see chapter 3     V210 EN M A011    Operation and configuration    2 Local panel user inter
198. he under reactance stages during  abnormal voltages not caused be short circuit faults     Characteristic on an impedance plane    The characteristics on an impedance plane is a circle covering the  unstable area of the synchronous machine  Figure 5 22 1   The  V210 EN M A011    Technical description    5 Protection functions 5 22 Under reactance and loss of    excitation protection X lt   40        V210 EN M A011    radius X lt  and centre point  Roffset  Xoffset  of the circle are  editable  Whenever the positive sequence impedance goes inside  this circle  the stage will pick up  If the fault stays on longer than  the definite time delay setting  the stage will issue a trip signal   UnderReactanceZplane    jX A     cap                         Z    Va     sho  k  40    NORMAL  9                                             D                                                                               a n 4N  OPERATION 265  mig   AREA OF THE     m  S O    GENERATOR    4  a  gt  Roffset  lt     R  m o zw a  otg  gt   E     1s 7  be  m                D        cap    AN      A   3S         Figure 5 22 1 The trip region of loss of excitation stage is a circle is covering the  unstable area of the generator  The radius X lt   Roffset and Xoffset are the  setting parameters  Whenever the positive sequence impedance falls inside the  X lt  circle  the stage picks up     Calculating setting values   The machine manufacturer specifies      synchronous unsaturated reactance and the   
199. here are errors in the programmable curve configuration and  the device is not able to interpolate values between the given  points    Limitation   The maximum measured phase current is 50xln and the maximum   directly measured earth fault current is 5xlon  This limits the scope   of inverse curves when the setting is more than 2 5xly  overcurrent  stages and earth fault stages using localc input  or 0 25xloin  earth  fault stages using Io  input or Io2 input   The In and loin and Ipon  depend on the order code  See chapter 15   The table below gives  the limit values in secondary amperes     Example of limitation   CT  750 5   lan  5 77A   CT   100 1  a cable CT for lo   Secondary scaled Ignsec iS NOW 3 85 A    For 5 A CT secondaries and 1 A residual current inputs VAMP  relay VAMP 210 5D7AAA is used  It has 5 A phase current inputs  and 1 A residual inputs     For overcurrent stage I gt  the table below gives 12 5 A  Thus the  maximum setting for l gt  stage giving full inverse delay range is  12 5 A   3 85 A   3 25 xlen    For earth fault stage Io gt  and input Io  the table below gives 0 25 A   Thus the maximum setting for l    gt  stage giving full inverse delay  range is 0 25 A  1 A   0 25 pu  This equals a 25 A primary earth  fault current     141    5 29 Inverse time operation 5 Protection functions Technical description       When using input signal locaic the corresponding setting is 12 5 A    1 A  12 5 pu  This equals a 9375 A of primary earth fault current        
200. hree line to line  voltage is used regardless of the voltage measurement mode   chapter 7 6   By using line to line voltages any phase to ground  over voltages during earth faults have no effect   The earth fault  protection functions will take care of earth faults      The used net frequency is automatically adopted according the  local network frequency     Overexcitation protection is needed for generators  which are  excitated even during start up and shut down  If such a generator  is connected to a unit transformer  also the unit transformer needs  volts hertz over excitation protection  Another application is  sensitive overvoltage protection of modern transformers with no  flux density margin in networks with unstable frequency     Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually                                                  Measured voltage  PU                          V210 EN M A011                                                                         ole  Uf gt  setting Us setting          gt      2 0  5 18 5  A 16   amp   o  op 14     a af 5  S  w   10  o  3 08  wm      06  a  z 0 4 one   0 2  30 35 40 45 50 55 60 65 30 35 40 45 50 55 60 65  30 36 42 48 54 60 66 72 30 36 42 48 54 60 66 72  Frequency  Hz  OverVoltreqChar Frequency  Hz  VoltPerHorz    Figure 5 13 1 This figure shows the difference between volts hert
201. iations and SYMbOIS             ccccceeeseeseeeeeeeeeeeeeeeeeees 286  14  Construction mreresrrerererer errr rier rr rererererer eres rer rererererrrrrerrr terry 288  TS  Order information vicsessscisieciscccesssnseriweiencewersennnerocrecenscnes 289  16  REVISION RISTOMY    siciescccii cece cscicesseantscaceenscesseerdsancncetsincadnanenane 291    1 General Operation and configuration    instructions    1 1 Relay features       T  General    This first part  Operation and configuration  of the publication  contains general descriptions of the functions  of the generator  protection relay as well as operation instructions  It also includes  instructions for parameterization and configuration of the relay and  instructions for changing settings     The second part  Technical description  of the publication includes  detailed protection function descriptions as well as application  examples and technical data sheets     1 1  Relay features    The comprehensive protection functions of the relay make it ideal  for utility  industrial  marine and off shore power distribution  applications  The relay features the following protection functions     List of protection functions                                                                                     IEEE  IEC symbol Function name  ANSI code   50 51 3l gt   3l gt  gt   3l gt  gt  gt  Overcurrent protection  67 lgir gt s lair gt  gt   lgir gt   gt  gt   lair  gt  gt  gt  Directional overcurrent protection   51V Iv gt  Voltag
202. ill not work   e Si Light sensor S1    e S2 Light sensor S2    e S1 S2 Either one of the light sensors S1 or S2    e BI Binary input of the arc card  48 Vdc    e S1 Bl Light sensor S1 or the binary input    e S2 Bl Light sensor S2 or the binary input     e S1 S2 Bl Light sensor S1 or S2 or the binary input     137    5 28 Arc fault protection   50ARC 50NARC   optional     5 Protection functions Technical description       138    Binary input   The binary input  BI  on the arc option card  see chapter 11 5   can be used to get the light indication from another relay to build  selective arc protection systems  The BI signal can also be  connected to any of the output relays  BO  indicators etc  offered  by the output matrix  See chapter 8 4   BI is a dry input for 48 Vdc  signal from binary outputs of other VAMP relays or dedicated arc  protection devices by VAMP     Binary output   The binary output  BO  on the arc option card  see chapters 11 5  and 11 6  can be used to give the light indication signal or any  other signal or signals to another relay s binary input to build  selective arc protection systems  Selection of the BO connected  signal s  is done with the output matrix  See chapter 8 4   BO is  an internally wetted 48 Vdc signal for BI of other VAMP relays or  dedicated arc protection devices by VAMP     Delayed light indication signal    Relay output matrix has a delayed light indication output signal   Delayed Arc L gt   available for building selective arc protec
203. ilure stage  8 latest          faults  CBFP  50BF   Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date       hh mm ss ms    Time stamp  time of day       EDly                     setting  100    trip    Elapsed time of the operating time          133    5 27 Programmable stages  99  5 Protection functions Technical description          27     134    Programmable stages  99     For special applications the user can built his own protection  stages by selecting the supervised signal and the comparison  mode     The following parameters are available    e Priority  If operation times less than 60 milliseconds are needed select  10 ms  For operation times under one second 20 ms is  recommended  For longer operation times and THD signals  100 ms is recommended     e Link  The name of the supervised signal  see table below      e Cmp  Compare mode      gt     for over or     lt     for under comparison     e Pick up  Limit of the stage  The available setting range and the unit  depend on the selected signal     e t  Definite time operation delay    e Hyster  Dead band  hysteresis     e NoCmp    Only used with compare mode under      lt         This is the limit to  start the comparison  Signal values under NoCmp are not  regarded as fault     V210 EN M A011    Technical description    5 Protection functions    5 27 Programmable stages  99        V210 EN M A011    Available signals to be supervised by the programmable                                    
204. in the  documentation of the CB manufacturer  Figure 6 8 1   The  diagram specifies the permissible number of cycles for every level  of the breaking current  This diagram is parameterised to the  condition monitoring function with maximum eight  current  cycles   points  See Table 6 8 1  If less than eight points needed  the  unused points are set to  Ipic  1   where Isic is more than the  maximum breaking capacity     If the CB wearing characteristics or part of it is a straight line ona  log log graph  the two end points are enough to define that part of  the characteristics  This is because the relay is using logarithmic  interpolation for any current values falling in between the given  current points 2   8    The points 4   8 are not needed for the CB in Figure 6 8 1  Thus  they are set to 100 kA and one operation in the table to be  discarded by the algorithm                    100000 T a  eel eee Dest od  l l  l l  2    I  S Rees shes oS ase eo ge Poe ee eee    i i     10000     ila Ses errr ie ee  ro  T L  D   i i  Suis ere es lle  Fa l l     1000 r r     F 1 1  O     FESE priest a EA  4  l l  9 l i         S fe te fe we  a 1 1  E 100 i         1 I 1  I es aa areal i  f i i i  20 F     LISAR EF e T  l l 1  10  100 200 500 1000 10000 100000    Breaked current  A  CBWEARcharacteristics  Figure 6 8 1 An example of a circuit breaker wearing characteristic graph     Table 6 8 1 An example of circuit breaker wearing  characteristics in a table format  The value are taken f
205. ing communication  protocols or VAMPSET  Every reading increments the internal  read pointer to the event buffer   In case of communication error   the latest event can be reread any number of times using an other  parameter   On the local panel scanning the event buffer back  and forth is possible     Event enabling masking    In case of an uninteresting event  it can be masked  which  prevents the particular event s  to be written in the event buffer     As a default there is room for 200 latest events in the buffer  Event  buffer size can be modified from 50 to 2000 in all v 10 xx  softwares  Modification can be done in    Local panel conf       menu   Alarm screen  popup screen  can also be enabled in this same  menu when Vampset  setting tool is used  The oldest one will be  overwritten  when a new event does occur  The shown resolution  of a time stamp is one millisecond  but the actual resolution  depends of the particular function creating the event  For example  most protection stages create events with 10 ms or 20 ms  resolution  The absolute accuracy of all time stamps depends on    V210 EN M A011    Technical description 6 Supporting functions 6 1 Event log       the time synchronizing of the relay  See chapter 6 10 for system  clock synchronizing     Event buffer overflow    The normal procedure is to poll events from the device all the time   If this is not done  the event buffer will eventually overflow  On the  local screen this is indicated with string  OVF  
206. ingle line diagram editing    The single line diagram is drawn with the VAMPSET software  For  more information  please refer to the VAMPSET manual   VVAMPSET EN M xxxx      single line diagram    1 Bay    OA  0 000A  OkW  OKvar    IR    Figure 2 4 9 1  Single line diagram     Blocking and interlocking configuration    The configuration of the blockings and interlockings is done with  the VAMPSET software  Any start or trip signal can be used for  blocking the operation of any protection stage  Furthermore  the  interlocking between objects can be configured in the same  blocking matrix of the VAMPSET software  For more information   please refer to the VAMPSET manual  VVAMPSET EN M xxxx      43    2 4 Configuration and parameter 3 VAMPSET PC software Technical description    setting       3     44    VAMPSET PC software    The PC user interface can be used for     e On site parameterization of the relay   e Loading relay software from a computer   e Reading measured values  registered values and events to a  computer    e Continuous monitoring of all values and events     Two RS 232 serial ports are available for connecting a local PC  with VAMPSET to the relay  one on the front panel and one on the  rear panel of the relay  These two serial ports are connected in  parallel  However  if the connection cables are connected to both  ports  only the port on the front panel will be active  To connect a  PC to a serial port  use a connection cable of type VX 003 3    The VAMPSET 
207. inputs  virtual inputs   mimic display  communication  logic  and manually    There are two identical stages available with independent setting  parameters     128 V210 EN M A011    Technical description    5 Protection functions 5 23 Reverse power and under   power protection P lt   32        V210 EN M A011    Parameters of the reverse under power stages P lt   P lt  lt   32                                                     Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  s None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   P kW The supervised value   P lt   P lt  lt  kW Pick up value scaled to primary  value   P lt   P lt  lt   Pm   Pick up value scaled to pu  Set  t lt   t lt  lt  s Definite operation time Set          For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed   C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults     Time stamp  fault power  elapsed delay and 
208. ion U gt   59  5 Protection functions Technical description          12     90    C   Can be cleared to zero  F   Editable when force flag is on  Recorded values of the latest eight faults    There is detailed information available of the eight latest detected  faults  Time stamp  Uo voltage  elapsed delay and setting group     Recorded values of the directional intermittent transient earth  fault stage  8 latest faults  lont gt   67NI                          Parameter Value Unit   Description   yyyy mm dd Time stamp of the recording  date   hh mm ss ms Time stamp  time of day  Fit pu   Maximum detected earth fault current  EDly   Elapsed time of the operating time   setting  100    trip  Uo     Max  Up voltage during the fault  SetGrp 1 Active setting group during fault  2                      Overvoltage protection U gt   59     The overvoltage function measures the fundamental frequency  component of the line to line voltages regardless of the voltage  measurement mode  chapter 7 6   By using line to line voltages  any phase to ground over voltages during earth faults have no  effect   The earth fault protection functions will take care of earth  faults   Whenever any of these three line to line voltages exceeds  the user s pick up setting of a particular stage  this stage picks up  and a start signal is issued  If the fault situation remains on longer  than the user s operation time delay setting  a trip signal is issued     In rigidly earthed 4 wire networks with loads 
209. ional overcurrent protection   51V Iv gt  Voltage restrained or voltage controlled overcurrent   function  46 l2 gt  Current unbalance protection  49 T gt  Thermal overload protection  50N 51N l gt   lo gt  gt   lo gt  gt  gt   Ip gt  gt  gt  gt  Earth fault protection   67N Iog gt   Log gt  gt  Directional earth fault protection   67NT Ior Intermittent transient earth fault protection  59 U gt   U gt  gt   U gt  gt  gt  Overvoltage protection  27 U lt   U lt  lt   U lt  lt  lt  Undervoltage protection  24 U f gt  Volts hertz overexcitation protection   27P Ui lt   Ui lt  lt  Positive sequence undervoltage protection  59N Uo gt   Up gt  gt  Residual voltage protection   64F3 Uors lt  100   stator earth fault protection   81H 81L f gt  lt   f gt  gt  lt  lt  Overfrequency and underfrequency protection   81L f lt   f lt  lt  Under frequency protection   81R df dt gt  Rate of change of frequency  ROCOF  protection  21 Z lt   Z lt  lt  Underimpedance protection  40 Q lt  Underexcitation protection   21 40 X lt   X lt  lt  Underreactance protection  Loss of excitation   32 P lt   P lt  lt  Reverse and underpower protection   51F2 l gt  Second harmonic O C stage   51F5 lis gt  Fifth harmonic O C stage   50BF CBFP Circuit breaker failure protection  99 Prg1   8 Programmable stages          V210 EN M A011    49    5 3 General features of protection 5 Protection functions Technical description    stages       5 3     50    General features of protection stages    Setting groups   Most
210. irtual  inputs  mimic display  communication  logic  and manually     109    5 18 Overfrequency and 5 Protection functions Technical description  underfrequency protection f gt   f lt    81H 81L        Parameters of the over  amp  under frequency stages  f gt  lt   f gt  lt  gt  lt   f lt   f lt  lt   81H 81L                          Parameter   Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set   setting group   None   Dix Digital input   Vix Virtual input   LEDx LED indicator signal   vox Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout                                         f Hz The supervised value   Hz Pick up value  fX Over under stage f gt  lt   See  fXX Mode Set  f lt  Over under stage f gt  lt  gt  lt    f lt  lt  Under stage f lt   Under stage f lt  lt   s Definite operation time  tX f gt  lt  stage  tXX f gt  lt  gt  lt  stage Set  t lt  f lt  stage  t lt  lt  f lt  lt  stage  Mode Operation mode   only for f gt  lt   and f gt  lt  gt  lt   Set   gt  Overfrequency mode  2 Underfrequency mode  LVbIck  Un Low limit for self blocking  This  is acommon setting for all four Set  stages        For details of setting ranges see chapte
211. is configured longer than maximum fault  time to inhibit any superfluous trip circuit fault alarm when the  trip contact is closed    e The digital input is connected to a relay in the output matrix  giving out any trip circuit alarm    e The trip relay should be configured as non latched  Otherwise   a superfluous trip circuit fault alarm will follow after the trip  contact operates  and the relay remains closed because of  latching    e By utilizing an auxiliary contact of the CB for the external  resistor  also the auxiliary contact in the trip circuit can be  supervised    e When using the dry digital inputs DI7     using the other inputs  of the same group  sharing a common terminal  is limited    e When using the wet digital inputs DI1     DI6  an auxiliary relay  is needed     V210 EN M A011    Technical description 10 Applications 10 4 Trip circuit supervision       Using optional DI19  DI20    Note  In the device only the optional digital inputs DI19 and DI20 are dry  see the  ordering code for this option          V aux   24 Vdc     240 Vdc         VAMP relay        Trip relay by Pala    Alarm relay ted  for trip a    circuit failure         rip circul  Failure alarm    relay compartment    circuit breaker compartment      SS SS Se eS TCS1Diclosed  Figure 10 4 1 1 Trip circuit supervision using a single dry digital input and an  external resistor R  The circuit breaker is in the closed position  The supervised  circuitry in this CB position is double lined  The digi
212. is framed     4  Select the desired parameter  for example Inom  with l    5  Use the and to change a parameter value  If the value  contains more than one digit  use and to shift from  digit to digit  and the and to change the digits    6  Push to accept a new value  If you want to leave the    parameter value unchanged  exit the edit state by pushing a    VAMP 200 series changing parameters    CURRENT SCALING PICK CURRENT SCALING    CT prima  inom    Isec Isec  lonom lonom  losec d losec  loinp   loinp  lo2nom lo2nom    OK  OJ  Edit VALUE CHANGE    E enter CT pary     CANCEL ok PES  j    Figure 2 4 1 1 Changing parameters          V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       2 4 2     2 4 3     V210 EN M A011    Setting range limits    If the given parameter setting values are out of range values  a  fault message will be shown when the setting is confirmed with    mi  Adjust the setting to be within the allowed range     illegal    Edit VALUE CHANGE    Illegal value    Lim  0 10   5 00    Press  CANCEL       Figure 2 4 2 1 Example of a fault message    The allowed setting range is shown in the display in the setting    mode  To view the range  push 0 Push to return to the  setting mode     infoset_I    Info SET I gt   Setting for stage I gt   Type  i32 dd  Range  0 10      5 00    ENTER   password  CANCEL  back to menu    Figure 2 4 2 2  Allowed setting ranges show in the display       Disturba
213. isplay  communication  logic  and manually     Start  Register  event   Trip  Register  event   Setting I gt s Delay Definite inverse Inverse time Multiplier Enable events  i characteristics    Figure 5 4 1 Block diagram of the three phase overcurrent stage l gt      3visblock       3vIssblock    Register  event  Register  event       Setting I gt  gt s Delay Enable events    Figure 5 4 2 Block diagram of the three phase overcurrent stage I gt  gt  and I gt  gt  gt      Parameters of the overcurrent stage I gt   50 51                          Parameter   Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   setting group     None   Dix Digital input Set   Vix Virtual input   LEDx LED indicator signal   VOx Virtual output                         V210 EN M A011    Technical description    5 Protection functions    5 4 Overcurrent protection I gt   50 51        V210 EN M A011                                              Parameter   Value Unit Description Note  Force Off Force flag for status forcing for Set  On test purposes  This is a   common flag for all stages and  output relays  too  This flag is  automatically reset 5 minutes  after the last front panel push  button pressing   ILmax A The supervised value  Max  of  IL1  IL2 and IL3  I gt  A Pick
214. itched on with a digital input  virtual  input or virtual output  LOCALPANEL CONF Display backlight  ctrl setting is used for selecting trigger input for backlight control   When the selected input activates  rising edge   display backlight  is set on for 60 minutes     Menu navigation and pointers    1  Use and A to move up and down in the main menu  that  is  on the left hand side of the display  The active main menu  option is indicated with a cursor  The options in the main menu  items are abbreviations  e g  Evnt   events    2  After any selection  the arrow symbols in the upper left corner  of the display show the possible navigating directions   applicable navigation keys  in the menu    3  The name of the active submenu and a possible ANSI code of  the selected function are shown in the upper part of the  display  e g  CURRENTS    4  Further  each display holds the measured values and units of  one or more quantities or parameters  e g  ILmax 300A     Keypad    You can navigate in the menu and set the required parameter  values using the keypad and the guidance given in the display   Furthermore  the keypad is used to control objects and switches  on the single line diagram display  The keypad is composed of  four arrow keys  one cancel key  one enter key and one info key     o    Figure 2 1 3 1 Keys on the keypad       1  Enter and confirmation key  amp    Home   Cancel key E     Up Down  Increase Decrease  arrow keys  amp    Vj  Keys for selecting submenus  selectin
215. ith basic logic  functions and timers    Recording of time stamped events and fault values    Built in disturbance recorder for evaluating all the analogue  and digital signals    Disturbance recorder for evaluating all the analogue and digital  signals    Easy configuration  parameterisation and reading of  information via the local human man interface  HMI   or with  the free of charge VAMPSET PC program    Built in  self regulating AC DC converter for auxiliary power  supply from any source within the range from 40 to 265 VDC or  VAC   The alternative power supply is for 18 to 36 VDC     V210 EN M A011    Technical description 4 Introduction 4 2 Principles of numerical  protection techniques       4 2  Principles of numerical protection  techniques    The manager is using numerical technology  This means that all  the signal filtering  protection and control functions are  implemented through digital processing     The numerical technique used in the manager is primarily based  on an adapted Fast Fourier Transformation  FFT  algorithm   Synchronized sampling of the measured voltage and current  signals is used  The sample rate is 32 samples cycle within the  frequency range 45 Hz     65 Hz  The frequency is measured from  the voltage signals and used to synchronize the sampling rate   Therefore secondary testing of a brand new device should be  started with voltage protection functions and voltage injection to let  the relay learn the local frequency  The learned frequency
216. latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault value and elapsed delay     V210 EN M A011    Technical description    5 Protection functions 5 28 Arc fault protection   50ARC 50NARC   optional        5 28     V210 EN M A011    Recorded values of the programmable stages PrgN  99                       Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit pu Fault value  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      Arc fault protection  50ARC 50NARC    optional     NOTE  This protection function needs optional hardware in slot X6  More details    of the hardware can be found in chapters 11 5 and 12 1 6      Arc protection is used for fast arc protection  The function is based  on simultaneous light and current measurement  Special arc  sensors are used to measure the light of an arc     Three stages for arc faults  There are three separate stages for the various current inputs     e Arcl gt  for phase to phase arc faults  Current inputs  IL1  IL2  IL3 are used    e   Arcloi gt  for phase to earth arc faults  Current input lo  is  used    e   Arclos gt  for phase to earth arc faults  Current input loz is  used     Light channel selection    The light information source to the stages can be selected from  the following list     e     No sensor selected  The stage w
217. lected input  Length of digital input pulse  should be at least 60 ms     V210 EN M A011    Technical description    8 Control functions 8 7 Logic functions       8 6 1     8 7     V210 EN M A011    Local Remote selection    In Local mode  the output relays can be controlled via a local HMI   but they cannot be controlled via a remote serial communication  interface     In Remote mode  the output relays cannot be controlled via a local  HMI  but they can be controlled via a remote serial communication  interface     The selection of the Local Remote mode is done by using a local  HMI  or via one selectable digital input  The digital input is  normally used to change a whole station to a local or remote  mode  The selection of the L R digital input is done in the    Objects     menu of the VAMPSET software     NOTE  A password is not required for a remote control operation     Logic functions    The relay supports customer defined programmable logic for  boolean signals  The logic is designed by using the VAMPSET  setting tool and downloaded to the relay  Functions available are   AND   OR   XOR   NOT   COUNTERs   RS  amp  D flip flops    Maximum number of outputs is 20  Maximum number of input  gates is 31  An input gate can include any number of inputs     For detailed information  please refer to the VAMPSET manual   VVAMPSET EN M xxxx      215    9 1 Communication ports    9 Communication Technical description       9     7 1     216    Communication    Communication ports
218. ls from the loint gt   stage     Auto reclosing    The start signal of any I  gt  stage initiating auto reclosing  AR  can  be used to block the Ioint gt  stage to avoid the loint gt  stage with a  long intermittent setting to interfere with the AR cycle in the middle  of discrimination time     Usually the Ioint gt  stage itself is not used to initiate any AR  For  transient faults the AR will not help  because the fault phenomena  itself already includes repeating self extinguishing     Intermittent time    Single transient faults make the protection to pick up  but will not  cause trip if the stage has time to release between to successive  faults  When starting happens often enough  such intermittent  faults can be cleared using the intermittent time setting     When a new fault happens within the set intermittent time  the  operation delay counter is not cleared between adjacent faults and  finally the stage will trip  A single transient fault is enough to start  the stage and increase the delay counter by 20 ms  For example if  the operating time is 140 ms  and the time between two peaks  does not exceed the intermittent time setting  then the seventh  peak will cause a trip  Figure 5 11 3      Operation time setting and the actual operation time    When the algorithm detects the direction of the fault outwards from  the bus  the stage picks up and the operation delay counter is  incremented with 20 ms and a start signal is issued  If the time  between successive faults
219. ls of the various  protection stages  digital inputs  logic outputs and other internal  signals can be connected to the output relays  front panel  indicators  virtual outputs etc     There are two LED indicators named  Alarm  and  Trip  on the  front panel  Furthermore there are three general purpose LED  indicators      A    B  and  C      available for customer specific  indications  In addition  the triggering of the disturbance recorder   DR  and virtual outputs are configurable in the output matrix  See  an example in Figure 8 4 1     An output relay or indicator LED can be configured as latched or  non latched  A non latched relay follows the controlling signal  A  latched relay remains activated although the controlling signal  releases     There is a common  release latched  signal to release all the  latched relays  This release signal resets all the latched output  relays and indicators  The reset signal can be given via a digital  input  via a keypad or through communication  Any digital input  can be used for resetting  The selection of the input is done with  the VAMPSET software under the menu  Release output matrix  latches   Under the same menu  the  Release latches  parameter  can be used for resetting     OUTPUT MATRIX  T1 T2 A A2 A3 A4 A5 Alarm Trip A B C DR vOo1  e connected      connected and latched Z  Z Z  Z  Z T Z    b gt  start  I gt  trip      gt  gt  start   gt  gt  trip  lo gt  start  lo gt  trip    lo gt  gt  start    lo gt  gt  trip  OutputMatri
220. ly longer than in the figure  an unselective  trip might happen  the dashed 40 ms pulse in the figure   In VAMP  relays the retardation time is less than 50 ms     51    5 3 General features of protection 5 Protection functions Technical description    stages       52    Reset time  release time     Figure 5 3 2 shows an example of reset time i e  release delay   when the relay is clearing an overcurrent fault  When the relay s  trip contacts are closed the circuit breaker  CB  starts to open   After the CB contacts are open the fault current will still flow  through an arc between the opened contacts  The current is finally  cut off when the arc extinguishes at the next zero crossing of the  current  This is the start moment of the reset delay  After the reset  delay the trip contacts and start contact are opened unless  latching is configured  The reset time varies from fault to fault  depending on the fault size  After a big fault the time is longer  The  reset time also depends on the specific protection stage  The  maximum reset time for each stage is specified in chapter 12 3   For most stages it is less than 95 ms     ReleaseTime            treser    TRIP CONTACTS    Figure 5 3 2 Reset time is the time it takes the trip or start relay contacts to  open after the fault has been cleared     Hysteresis or dead band    When comparing a measured value against a pick up value  some  amount of hysteresis is needed to avoid oscillation near  equilibrium situation  With zero hy
221. mal capacity of the whole generator  Thus an rms current  based overload protection  see chapter 5 8  is not capable to  protect a generator against current unbalance     The current unbalance protection is based on the negative  sequence of the base frequency phase currents  Both definite  time and inverse time characteristics are available    Inverse delay   The inverse delay is based on the following equation    Equation 5 7 1    t     where   i   gn  t   Operation time  K     Delay multiplier  l gt    Measured and calculated negative sequence phase  current of fundamental frequency   ln   Rated current of the generator  K     Pick up setting l2 gt  in pu  The maximum allowed degree    of unbalance        Example   Ki   15s  lo   22 9    0 229 Xlgn  Ko   5     0 05 XIgn   t  13   300 4    2      0 05   1  The operation time in this example will be five minutes     More stages  definite time delay only     If more than one definite time delay stages are needed for current  unbalance protection  the freely programmable stages can be  used  chapter 5 27      Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     67    5 7 Current unbalance protection 12 gt      46     5 Protection functions    Technical description       68    CurrentUnbalanceChar       2000  1000         Operation time  s                                   20    60 
222. me starting from the third fault  will be 617 ms although  the setting was 140 ms  In case the  intermittent setting would have been 0 2 s or more  the two first  faults had been included and a trip would have issued at t 0 64 s     EFtransientFig7        1     Intermittent time   0 s i  Start T2 Lo H ppi CES pp SCEE payg BCH paa BA p ALe  Trip i      0 12 s     Intermittent time   0 12 s                                                 0 0 0 2 0 4 0 6 0 8 1 0  Time  s     Figure 5 11 2  Effect of the intermittent time parameter  The operation delay  setting is 0 14 s   7x20 ms  The upper start and trip status lines are for a case  with the intermittent time set to zero  No trip will happen  The lower start and trip  status lines show another case with intermittent time setting 0 12 s  In this case  a trip signal will be issued at t 0 87 s     Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     88 V210 EN M A011    Technical description    5 Protection functions 5 11 Intermittent transient earth fault  protection IOINT gt   67NI        V210 EN M A011    idtBlock          I  samples I  I  peak      TRANSIENT  ALGORITHM  I  fundamental     freq  amplitude   U  samples    o  U  fundamental E i  freq  amplitude                  Setting  Setting  Setting  Enable  U  pick up Delay Intermittent events  n   delay 20 ms time    Figure 5 11
223. ms   10 ms          283    12 4 Supporting functions    12 Technical data    Technical description       12 4   12 4 1     12 4 2     12 4 3     284    Arc protection stage Arclo2 gt   50NARC   option       Setting range   Arc sensor connection     Operating time  Light only      Operating time  4xlset   light     Operating time  BIN      Operating time  Delayed Arc L gt      BO operating time   Reset time   Reset time  Delayed ARC L   Reset time  BO    Reset ratio   Inaccuracy      Starting     Operating time     Delayed ARC light          0 5   10 0 x In   1  S2  S1 S2  BI  S1 Bl  S2 Bl  S1 S2 BI  13 ms   17ms   10 ms  0 01 0 15s   lt 3 ms    lt 95 ms    lt 120 ms    lt 85 ms   0 90    10  of the set value   5 ms   10 ms       Supporting functions    Disturbance recorder  DR     The operation of disturbance recorder depends on the following  settings  The recording time and the number of records depend on  the time setting and the number of selected channels     Disturbance recorder  DR        Mode of recording   Sample rate      Waveform recording     Trend curve recording    Recording time  one record     Pre trigger rate       Number of selected channels       Saturated   Overflow    32 cycle  16 cycle  8 cycle   10  20  200 ms   1 5  10  15  30s   1 min   0 1 s     12 000 min    must be shorter than MAX time   0     100    0 12          Inrush current detection  68        Settings     Setting range 2 Harmonic         Operating time       10 100    0 05       300 00 s  s
224. mum total operational time including the fault detection    time and operation time of the trip contacts         The measuring range may limit the scope of inverse delays  See chapter 5 29 for details     Directional overcurrent stages lair gt  gt  gt  and lair gt  gt  gt  gt   67        Pick up current    0 10     20 0 x len       Mode    Directional non directional       Minimum voltage for the direction solving    0 1 V secondary       Base angle setting range     180   to   179         Operation angle     88         Definite time function     Operating time    DT  0 06        300 00 s  step 0 02 s           Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms   Reset ratio 0 95   Reset ratio  angle  2     Transient over reach  any t  lt 10        Inaccuracy     Starting  rated value IN  1    5A     Angle         Operate time at definite time function        3  of the set value or  0 5  of the rated value   2   U gt 5 V    30   U gt 0 1 V    1  or  30 ms             This is the instantaneous time i e  the minimum total operational time including the fault detection    time and operation time of the trip contacts     274    V210 EN M A011    Technical description    12 Technical data    12 3 Protection functions       V210 EN M A011    Voltage restrained controlled overcurrent stage ly gt   51V        Settings     lyv gt       Ux    Ux2    Z Iv  Ivo    0 50     4 00 x len  0  150   0     200  ly gt        Definite time function     Operating time    
225. n     For details see the technical description part of the manual     EXTERNAL I O protocol   This is a Modbus master protocol to communicate with the  extension I O modules connected to the extension port  Only one  instance of this protocol is possible    e Bit rate  bit s   Default is  9600     e Parity  Parity   Default is  Even     For details see the technical description part of the manual     41    2 4 Configuration and parameter 2 Local panel user interface Operation and configuration    setting    instructions       42    SPA BUS   Several instances of this protocol are possible    e SPABUS addres for this device  Addr   This address has to be  unique within the system    e Bit rate  bit s   Default is  9600     e Event numbering style  Emode   Default is  Channel     For details see the technical description part of the manual    IEC 60870 5 101   e Bit rate  bit s   Default is    9600       e  Parity     e Link layer address for this device  LLAddr     e ASDU address  ALAdadr     For details see the technical description part of the manual     IEC 60870 5 103   Only one instance of this protocol is possible    e Address for this device  Addr   This address has to be unique  within the system    e Bit rate  bit s   Default is  9600     e Minimum measurement response interval  Measint     e ASDU6 response time mode  SyncRe     For details see the technical description part of the manual     IEC 103 DISTURBANCE RECORDINGS  For details see the technical description p
226. n delay  the delay counting is frozen until the blocking  goes off or the pick up reason  i e  the fault condition  disappears   If the stage is already tripping  the blocking has no effect     Retardation time    Retardation time is the time a protection relay needs to notice  that  a fault has been cleared during the operation time delay  This  parameter is important when grading the operation time delay  settings between relays                trauu    jer  lt 50 my    DELAY SETTING  gt  tmur   trer  ey    TRIPCONTACTS TE      Figure 5 3 1 Definition for retardation time  If the delay setting would be slightly  shorter  an unselective trip might occur  the dash line pulse               For example when there is a big fault in an outgoing feeder  it  might start i e  pick up both the incoming and outgoing feeder  relay  However the fault must be cleared by the outgoing feeder  relay and the incoming feeder relay must not trip  Although the  operating delay setting of the incoming feeder is more than at the  outgoing feeder  the incoming feeder might still trip  if the  operation time difference is not big enough  The difference must  be more than the retardation time of the incoming feeder relay plus  the operating time of the outgoing feeder circuit breaker     Figure 5 3 1 shows an overcurrent fault seen by the incoming  feeder  when the outgoing feeder does clear the fault  If the  operation delay setting would be slightly shorter or if the fault  duration would be slight
227. nabled Start on event  Disabled   S_Off Enabled    Enabled Start off event  Disabled   T_On Enabled    Enabled Trip on event  Disabled   T_Off Enabled    Enabled Trip off event  Disabled                      V210 EN M A011    Technical description    5 Protection functions 5 25 Fifth harmonic O C stage    1f5 gt  51F5           25     V210 EN M A011    Measured and recorded values of second harmonic blocking  2 Ha 51F2                        Parameter   Value Unit Description  Measured   IL1H2    2  harmonic of IL1   values proportional to the  fundamental value of  IL1  IL2H2    2  harmonic of IL2  IL3H2    2  harmonic of IL3  Recorded Flt A The max  fault value  values  EDly   Elapsed time as    compared to the set  operating time  100                         tripping       Fifth harmonic O C stage Ijs5 gt  51F5     Overexiting for example a transformer creates odd harmonics   This 5  harmonic overcurrent stage can be used detect  overexcitation  This stage can also be used to block some other  stages     The ratio between the fifth harmonic component and the  fundamental frequency component is measured on all the phase  currents  When the ratio in any phase exceeds the setting value   the stage gives a start signal  After a settable delay  the stage  gives a trip signal     The trip delay of the stages to be blocked must be more than 60  ms to ensure a proper blocking     Setting parameters of second harmonic blocking 5 Ha 51F5                           Parameter   Value U
228. nal to select the active   Set  SGrpDI setting group  s None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   MinU V The supervised minimum of line   to line voltages in primary volts  U lt   U lt  lt   V Pick up value scaled to primary  U lt  lt  lt  value  U lt   U lt  lt    Ugn   Pick up setting Set  U lt    lt  lt   t lt   t lt  lt   t lt  lt  lt  s Definite operation time Set  LVBIk  Ugn   Low limit for self blocking Set  RlsDly s Release delay  U lt  stage only  Set  Hyster Default   Dead band setting Set  3 0              For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults  There are detailed information available of the eight latest faults  for each of the stages  Time stamp  fault voltage  elapsed delay   voltage before the fault and setting group     V210 EN M A011    101    5 16 Zero sequence voltage  protection U0 gt   59N     5 Protection functions Technical description       5 16     102    Recorded values of the undervoltage stages  8 latest faults   U lt   U lt  lt   U lt  lt  lt   27                          Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss
229. nce recorder menu DR    Via the submenus of the disturbance recorder menu the following  functions and features can be read and set     DISTURBANCE RECORDER    Recording mode  Mode    Sample rate  Rate    Recording time  Time    Pre trig time  PreTrig    Manual trigger  MnITrig    Count of ready records  ReadyRe     REC  COUPLING    e Add a link to the recorder  AddLink   e Clear all links  ClrLnks     35    2 4 Configuration and parameter 2 Local panel user interface Operation and configuration  setting instructions       Available links     DO  DI   Uline  Uphase   IL   U2 U1  U2  U1   I2 In  12 11  12  11  loCalc  CosFii   PF  S Q  P   f   Uo   UL3  UL2  UL1   U31  U23  U12   l02  lo   IL3  IL2  IL1   Prms  Qrms  Srms   Tanfii   THDIL1  THDIL2  THDIL3  THDUa  THDUb  THDUc  fy  fz  U12y  U12z    2 4 4  Configuring digital inputs DI    The following functions can be read and set via the submenus of  the digital inputs menu    The status of digital inputs  DIGITAL INPUTS 1 6 18   Operation counters  DI COUNTERS    Operation delay  DELAYs for Digln    The polarity of the input signal  INPUT POLARITY   Either  normally open  NO  or normally closed  NC  circuit    e Event enabling EVENT MASK1    2 4 5  Configuring digital outputs DO    The following functions can be read and set via the submenus of  the digital outputs menu     e The status of the output relays  RELAY OUTPUTS1 and 2   e The forcing of the output relays  RELAY OUTPUTS1 and 2    only if Force   ON    o Forced cont
230. nce voltage of Un V3  U1 lt   U1 lt  lt  V Pick up value scaled to primary  value  U1 lt   U1 lt  lt    Pick up setting of Un V3 Set  t lt   t lt  lt  s Definite operation time Set  LVBIk  Un Low limit for self blocking  This Set  is acommon setting for both  stages   I lt Blk s Pick up delay  when current is Set                less than 1  len              For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault voltage  elapsed delay and setting group     V210 EN M A011    Technical description 5 Protection functions 5 15 Undervoltage protection U lt   27        Recorded values of the undervoltage stages  8 latest faults   Ui lt   U1 lt  lt   27P                                         Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit  Un   Minimum fault voltage  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2  5 15  Undervoltage protection U lt   27     This a basic undervoltage protection  The function measures the  three line to line voltages and whenever the smallest of them  drops below the user s pick up setting of a particular stage  this  stage picks up and a start signal is issued  If the faul
231. nder reactance and loss of  excitation protection X lt   40        Setting groups    There are two settings groups available  Switching between    setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     Parameters of the under reactance stages X lt   X lt  lt   40                                                                          Parameter   Value Unit   Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active  setting group  3 None  Dix Digital input Set  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is acommon  flag for all stages and output  relays  too  Automatically reset by  a 5 minute timeout   Z ohm   The supervised value scaled to  primary value   Inf    infinite  Z xZn   The supervised value scaled to  per unit  pu    1 pu   1xXZy   Ugn  V3xl gn     Inf    infinite  Zo 3 Angle of the supervised  impedance  X lt  ohm   Pick up value scaled to primary  X lt  lt  value  X lt  xZn Pick up setting in per unit  pu   Set  X lt  lt  1 pu   1xZn   Ugn  V3XI gn    t lt  s Definite operation time Set  RIsDly s Release delay Set  Ros xZn Resistive offset for trip area origin Set  in pu   Xos xZn Reactive off
232. nel operations    2 Local panel user interface Operation and configuration       16                                                                                              instructions  Main menu   Submenus   I  I  I  I     z  I   V  a   Prot k protection enabling a   a  I  I  i  ok   I  i y  I  I a  I  i  l l pick up setting        za  I a y  iene  l Yy  I  i moving in the menus_relay             Figure 2 2 1 2  Principles of the menu structure and navigation in the menus    6  Push O to obtain additional information about any menu  item     7  Push to revert to the normal display     Main menu   The general menu structure is shown in Figure 2 2 1 2  The menu  is dependent on the user s configuration and the options according  the order code  For example only the enabled protection stages  will appear in the menu     V210 EN M A011    Operation and configuration    2 Local panel user interface    2 2 Local panel operations       A list of the local main menu                                                                                                                                     Main Number Description ANSI Note  menu of code  menus  1 Interactive mimic display 1  5 Double size measurements defined by the user 1  1 Title screen with device name  time and firmware  version   P 14 Power measurements  E 4 Energy measurements    13 Current measurements  U 15 Voltage measurements  Dema 15 Demand values  Umax 5 Time stamped min  amp  max of voltages  Imax 9 Time stam
233. ng  For phase currents excluding Arcl gt  stage  1 pu   1xlen   100    where  Ign is the rated current of the generator   For residual currents and Arcl gt  stage  1 pu   1xCTsec for secondary side and  1 pu   1xCTpr   for primary side   Phase current scaling Residual current  3lo   excluding Arcl gt  stage scaling and phase  current scaling for Arcl gt   stage  f _ I SEC  CT ori   I SEC  secondary   gt  per unit   Lpy                             Ip    CT sxc gi GN CT sxc    nan Ion  amp   per unit   gt  secondary   I snc  I py    CT sp        1 sec    py   CT suc  CT prr                Example 1  Secondary to per unit for phase currents excluding  Arcl gt      CT   750 5  lan   525A  Current injected to the relay s inputs is 7 A       Per unit current is  Ipu   7X750  5x525    2 00 pu   2 00 xlen  200      Example 2  Secondary to per unit for Arcl gt     CT   750 5   Current injected to the relay s inputs is 7 A      Per unit current is   Ipu   7 5   1 4 pu   140    Example 3  Per unit to secondary for phase currents excluding  Arcl gt      CT   750 5   lan   525A   The relay setting is 2xlgn   2 pu   200       Secondary current is   Isec   2x5x525 750   7A   Example 4  Per unit to secondary for Arcl gt    CT   750 5   The relay setting is 2 pu   200         Secondary current is  Isec  2x5 10A    203    7 10 Primary  secondary and per unit 7 Measurement functions Technical description    scaling       204    Example 5  Secondary to per unit for residual current   Input is lo
234. nge of frequency  ROCOF  stage 81R 4  Prg1 3 1st programmable stage 4  Prg2 3 2nd programmable stage 4  Prg3 3 3rd programmable stage 4  Prg4 3 4th programmable stage 4  Prg5 3 5th programmable stage 4  Prg6 3 6th programmable stage 4  Prg7 3 7th programmable stage 4  Prg8 3 8th programmable stage 4  If2 gt  3 Second harmonic O C stage 51F2 4  CBFP 3 Circuit breaker failure protection 50BF 4  CBWE 4 Circuit breaker wearing supervision 4  CTSV 1 CT supervisor 4  VTSV 1 VT supervisor 4  Arcl gt  4 Optional arc protection stage for phase to phase 50ARC 4   faults and delayed light signal   Arclo gt  3 Optional arc protection stage for earth faults  Current   50NARC_   4   input   101  Arclo2 gt    3 Optional arc protection stage for earth faults  Current   50NARC_   4   input   102  OBJ 11 Object definitions 5                      V210 EN M A011                                        Operation and configuration 2 Local panel user interface 2 2 Local panel operations  Main Number Description ANSI Note  menu of code   menus  Lgic 2 Status and counters of user s logic 1  CONF 10 2 Device setup  scaling etc  6  Bus 13 Serial port and protocol configuration 7  Diag 6 Device selfdiagnosis  Notes    V210 EN M A011    1  2  3    Configuration is done with VAMPSET   Recording files are read with VAMPSET   The menu is visible only if protocol  ExternallO  is selected for one of  the serial ports  Serial ports are configured in menu  Bus     The menu is visible only if the stage is enabled
235. nit Default Description   If5 gt  10   100   10 Setting value If2 lfund   t_f5 0 05   300 0   s 0 05 Definite operating time   S_On Enabled    Enabled Start on event  Disabled   S_Off Enabled    Enabled Start off event  Disabled   T_On Enabled     Enabled Trip on event  Disabled   T_Off Enabled     Enabled Trip off event  Disabled                         131    5 26 Circuit breaker failure 5 Protection functions Technical description  protection CBFP  50BF        Measured and recorded values of fifth harmonic blocking                                           5 Ha 51F5    Parameter   Value Unit Description  Measured   IL1H5    5  harmonic of IL1   values proportional to the  fundamental value of  IL1  IL2H5  A 5  harmonic of IL2  IL3H5    5  harmonic of IL3  Recorded   Fit   The max  fault value  values  EDly   Elapsed time as  compared to the set  operating time  100     tripping  5 26  Circuit breaker failure protection CBFP     50BF     The circuit breaker failure protection can be used to trip any  upstream circuit breaker  CB   if the fault has not disappeared  within a given time after the initial trip command  A different output  contact of the relay must be used for this backup trip     The operation of the circuit breaker failure protection  CBFP  is  based on the supervision of the signal to the selected trip relay  and the time the fault remains on after the trip command    If this time is longer than the operating time of the CBFP stage  the  CBFP stage activates 
236. nput 3  Max1  Un Maximum voltage value  during the sag swell in the  input 1  Max2  Un Maximum voltage value  during the sag swell in the  input 2  Max3  Un Maximum voltage value                                                    during the sag swell in the  input 3          For details of setting ranges see chapter 12 4     165    6 5 Voltage interruptions    6 Supporting functions Technical description       6 5     166    Voltage interruptions    The device includes a simple function to detect voltage  interruptions  The function calculates the number of voltage  interruptions and the total time of the voltage off time within a  given calendar period  The period is based on the real time clock  of the device  The available periods are    8 hours  00 00     08 00  08 00     16 00  16 00     24 00   one day  00 00     24 00   one week  Monday 00 00     Sunday 24 00   one month  the first day 00 00     the last day 24 00   one year  1st January 00 00     31st December 24 00    After each period  the number of interruptions and the total  interruption time are stored as previous values  The interruption  counter and the total time are cleared for a new period  The old  previous values are overwritten     The voltage interruption is based on the value of the positive  sequence voltage U  and a user given limit value  Whenever the  measured U  goes below the limit  the interruption counter is  increased  and the total time counter starts increasing    Shortest recognized interru
237. nt    Number of voltage sags  during the current  observation period       Prev    Number of voltage sags  during the previous  observation period       Total    Total  summed  time of  voltage sags during the  current observation period          Prev             Total  summed  time of  voltage sags during the  previous observation period          For details of setting ranges see chapter 12 4     167    6 6 Current transformer supervision    6 Supporting functions    Technical description       6 6     168    Current transformer supervision    The relay supervise the external wiring between the relay  terminals and current transformers  CT  and the CT them selves   Furthermore  this is a safety function as well  since an open  secondary of a CT  causes dangerous voltages     The CT supervisor function measures phase currents  If one of the  three phase currents drops below Imin lt  setting  while another  phase current is exceeding the Imax gt  setting  the function will issue  an alarm after the operation delay has elapsed     Setting parameters of CT supervisor CTSV                                                                           Parameter   Value Unit   Default   Description  Imax gt  0 0    10 0 xIgn 2 0 Upper setting for CT  supervisor  Imin lt  0 0    10 0 xIgn 0 2 Lower setting for CT  supervisor  t gt  0 02     600 0 s 0 10 Operation delay  CT on On  Off   On CT supervisor on event  CT off On  Off   On CT supervisor off event  Measured and recorded values of
238. nts is at the  moment 403 A  This is the value the stage is supervising     e Status        Status of the stage  This is just a copy of the status value in  the first menu     e I gt  gt 1013A  The pick up limit is 1013 A in primary value   e  gt  gt  2 50xlgn    The pick up limit is 2 50 times the rated current of the  generator  This value can be edited if the operating level is at  least  Operator   Operating levels are explained in chapter  2 2 5    e t gt  gt 0 60s    The total operation delay is set to 600 ms  This value can be  edited if the operating level is at least  Operator      21    2 2 Local panel operations    2 Local panel user interface Operation and configuration  instructions       22    Third menu of I gt  gt  50 51 stage    third menu    AV lt  I gt  gt LOG  FAULT LOG 1   ExDI 2006 09 14  ExDO   12 25 10 288    Type 1 2    Fit 2 86xlgn  CBWE   Load 0 99xlgn    EDly 81        Figure 2 2 2 3  Third and last menu  next on the right  of l gt  gt  50 51 stage    This is the menu for registered values by the I gt  gt  stage  Fault logs  are explained in chapter 2 2 4     e FAULT LOG 1  This is the latest of the eight available logs  You may move    between the logs by pressing push and then or  lt      e 2006 09 14  Date of the log   e 12 25 10 288  Time of the log   e Type 1 2    The overcurrent fault has been detected in phases L1 and L2   A  amp  B  red  amp  yellow  R amp S  u amp v      e Fit 2 86xlgn  The fault current has been 2 86 per unit    e Load 0 
239. odbus RTU slave  ModbusT CPs Modbus TCP slave  IEC 103 IEC 60870 5 103  slave   ExternallO Modbus RTU master for  external I O modules  DNP3 DNP 3 0  Msg  Oa 2 Message counter since the   Clr  device has restarted or  since last clearing  Errors o    2 61 Protocol errors since the Clr  device has restarted or  since last clearing  Tout o    2 61 Timeout errors since the Cir  device has restarted or  since last clearing  Display of actual 1   communication parameters   speed   bit s  speed DPS D   number of data bits  P   parity  none  even  odd  Default   S   number of stop bits  38400 8N1 for  VAMPSET  VAMPSET communication  Direct or SPA bus embedded command line  interface   TX bytes size Unsent bytes in transmitter  buffer size of the buffer  Msg  0    29 1 Message counter since the   Clr  device has restarted or  since last clearing  Errors Oy 4 Errors since the device has   Clr  restarted or since last  clearing  Tout o    2 61 Timeout errors since the Cir  device has restarted or  since last clearing                         Set   An editable parameter  password needed     Clr   Clearing to zero is possible    1  The communication parameters are set in the protocol specific menus  For  the local port command line interface the parameters are set in configuration    menu     V210 EN M A011    Technical description    9 Communication    9 1 Communication ports       9 1 2     V210 EN M A011    Remote port X5    Physical interface    The physical interface of this port dep
240. olled  overcurrent function IV gt   51V        V210 EN M A011    Cold load and inrush current handling  See chapter 6 3     Setting groups    There are two settings groups available  Switching between  setting groups can be controlled by digital inputs  virtual inputs   mimic display  communication  logic  and manually     Parameters of the voltage restrained and voltage controlled  overcurrent stage ly gt   51V                          Parameter   Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set   setting group   s None   Dix Digital input   VIX Virtual input   LEDx LED indicator signal   VOx Virtual output  Force Off Force flag for status forcing for Set   On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout                             ILmax A The supervised value  Max  of  IL1  IL2 and IL3  Iv gt  A Pick up value scaled to primary  value  Iv gt  xIgn Pick up setting Set  t gt  s Definite operation time Set  X1  U1 Voltage for the 1st knee point  Set  X2  U1 Voltage for the 2  knee point Set  Y1  lv gt    Multiplier for pick up setting at Set  the 1st knee point  Y2  lv gt    Multiplier for pick up setting at Set                      the 2    knee point  For details of setting ranges see chapter 12 3    
241. ommunication ports       9 1 4     V210 EN M A011    Ethernet port    IEC61850 and Modbus TCP use ethernet communication  Also  VAMPSET  SPA bus and DNP 3 0 communication can be directed                                           via TCP IP   Parameters  Parameter Value Unit   Description Set  Protoc Protocol selection for the Set  extension port   None Command line interface  for VAMPSET  ModbusTCPs Modbus TCP slave  IEC 61850 IEC 61850 protocol  Ethernet IP Ethernet IP protocol  Port nnn lp port for protocol  Set  default 102  pAddr n n n n Internet protocol address Set   set with VAMPSET   NetMsk n n n n Net mask  set with Set  VAMPSET   Gatew default   0 0 0 0 Gateway IP address  set Set  with VAMPSET   NTPSvr n n n n Network time protocol Set  server  set with  VAMPSET   0 0 0 0   no SNTP  VS Port nn IP port for Vampset Set  KeepAlive nn TCP keepalive interval Set  MAC nnnnannnnnnnn MAC address  Msg  nnn Message counter  Errors nnn Error counter  Tout nnn Timeout counter                         Set   An editable parameter  password needed     221    9 2 Communication protocols    9 Communication Technical description       9 2     9 2 1     9 2 2     222    Communication protocols    This protocols enable the transfer of the following type of data     events   status information   measurements   control commands    clock synchronizing   Settings  SPA bus and embedded SPA bus only     PC communication    PC communication is using a VAMP specified command line  interface  T
242. onic ratio to  fundamental frequency  lt2 li1  of at least one phase exceeds the  given setting  the inrush detection signal is activated  This signal is  available for output matrix and blocking matrix  Using virtual  outputs of the output matrix setting group control is possible     By setting the Pickupf2 parameter for l l  to zero  the inrush  signal will behave equally with the cold load pick up signal     Application for inrush current detection    The inrush current of transformers usually exceeds the pick up  setting of sensitive overcurrent stages and contains a lot of even  harmonics  Right after closing a circuit breaker the pick up and  tripping of sensitive overcurrent stages can be avoided by  selecting a more coarse setting group for the appropriate over   current stage with inrush detect signal  It is also possible to use  the detection signal to block any set of protection stages for a  given time     161    6 3 Cold load pick up and inrush 6 Supporting functions Technical description    current detection       162    NOTE  Inrush detection is based on FFT   calculation which recuires full cycle    of data for analyzing the harmonic content  Therefore when using inrush  blocking function the cold load pick up starting conditions are used for  activating the inrush blocking when the current rise is noticed  If in the  signal is found second harmonic component after 1 st cycle the blocking  is continued  otherwise 2 nd harmonic based blocking signal is released
243. or definite time   DT  or inverse time operation characteristic  IDMT   The stages  I gt  gt  and I gt  gt  gt  have definite time operation characteristic  By using  the definite delay type and setting the delay to its minimum  an  instantaneous  ANSI 50  operation is obtained    Figure 5 4 1 shows a functional block diagram of the I gt   overcurrent stage with definite time and inverse time operation  time  Figure 5 4 2 shows a functional block diagram of the I gt  gt  and  l gt  gt  gt  overcurrent stages with definite time operation delay     Inverse operation time   Inverse delay means that the operation time depends on the  amount the measured current exceeds the pick up setting  The  bigger the fault current is the faster will be the operation   Accomplished inverse delays are available for the I gt  stage  The  inverse delay types are described in chapter 5 29  The relay will  show the currently used inverse delay curve graph on the local  panel display     Inverse time limitation    The maximum measured secondary current is 50xly  This limits  the scope of inverse curves with high pick up settings  See  chapter 5 29 for more information     53    5 4 Overcurrent protection I gt   50 51  5 Protection functions Technical description       54    Cold load and inrush current handling  See chapter 6 3     Setting groups    There are two settings groups available for each stage  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic d
244. ording length Set  PreTrig   Amount of recording data Set  before the trig moment  MaxLen S Maximum time setting     This value depends on  sample rate  number and  type of the selected  channels and the configured  recording length              Status Status of recording  3 Not active  Run Waiting a triggering  Trig Recording  FULL Memory is full in saturated  mode  ManTrig Manual triggering Set  Trig  ReadyRec   n m n   Available recordings  m   maximum number of  recordings    The value of  m  depends on  sample rate  number and  type of the selected  channels and the configured  recording length                          158 V210 EN M A011    Technical description    6 Supporting functions    6 2 Disturbance recorder       Parameter    Value    Unit    Description    Note       AddCh    IL1  IL2  IL3  lo1  lo2    U12  U23   U31    UL1  UL2   UL3   Uo   f   P Q S  P F   CosFii  loCalc   11  12  12 11  I2 Ign   U1  U2   U2 U1   IL    Uphase   Uline    DO  DI   TanFii   THDIL1  THDIL2  THDIL3  THDUa  THDUb  THDUc  IL1 RMS  IL2RMS  IL8RMS    Add one channel  Maximum  simultaneous number of  channels is 12     Set       ClrCh    Clear    Remove all channels    Set           Ch              List of selected channels             For details of setting ranges see chapter 12 4   Set   An editable parameter  password needed      This is the fundamental frequency rms value of one cycle updated every 10    ms         This is the fundamental frequency rms value of one cycle updated eve
245. ording the Profibus data and  profile configuration and the values define the in out module to be configured for  the Profibus master   4  If the value is  i0   Profibus protocol has not been selected or the device has  not restarted after protocol change or there is a communication problem  between the main CPU and the Profibus ASIC                                                  224 V210 EN M A011    Technical description    9 Communication    9 2 Communication protocols       9 2 4     V210 EN M A011    SPA bus    The manager has full support for the SPA bus protocol including  reading and writing the setting values  Also reading of multiple    consecutive status data bits  measurement values or setting    values with one message is supported     Several simultaneous instances of this protocol  using different  physical ports  are possible  but the events can be read by one  single instance only     There is a separate document    Spabus parameters pdf    of SPA     bus data items available                 Parameters  Parameter   Value Unit   Description Note  Addr 1  899 SPA bus address  Must be Set  unique in the system   bit s bps   Communication speed Set  1200  2400  4800  9600  default   19200  Emode Event numbering style   Set   Channel Use this for new  installations    Limit60   The other modes are for   NoLimit  compatibility with old  systems                           Set   An editable parameter  password needed     225    9 2 Communication protocols 9 Communic
246. ort earth faults make the protection to start  to pick up   but will  not cause a trip   Here a short fault means one cycle or more  For  shorter than 1 ms transient type of intermittent earth faults in  compensated networks there is a dedicated stage lot gt  67NT      When starting happens often enough  such intermittent faults can  be cleared using the intermittent time setting  When a new start  happens within the set intermittent time  the operation delay  counter is not cleared between adjacent faults and finally the stage  will trip     Two independent stages    There are two separately adjustable stages  lo gt  and l    gt  gt   Both  the stages can be configured for definite time delay  DT  or  inverse time delay operation time     Inverse operation time    Inverse delay means that the operation time depends on the  amount the measured current exceeds the pick up setting  The  bigger the fault current is the faster will be the operation   Accomplished inverse delays are available for both stages lo gt   and lp  gt  gt   The inverse delay types are described in chapter 5 29   The relay will show a scaleable graph of the configured delay on  the local panel display     Inverse time limitation    The maximum measured secondary residual current is 10xlon and  maximum measured phase current is 50xly  This limits the scope   of inverse curves with high pick up settings  See chapter 5 29 for   more information     Setting groups   There are two settings groups available for 
247. otocol is available with the optional inbuilt Ethernet  port  The protocol can be used to read   write data from the relay  using request   response communication or via cyclic messages  transporting data assigned to assemblies  sets of data      EtherNet IP main features     Static data model  2 standard objects  Overload and Control  Supervisor   2 private objects  one for digital data and one for  analog data  and 4 configuration objects for protection  functions configuration    Two configurable assemblies  one producing and one  consuming  with the maximum capacity of 128 bytes each EDS  file that can be fed to any client supporting EDS files  can be  generated at any time  all changes to EtherNet IP configuration   see configuration parameters in table below  or to assemblies     content require generating of the new EDS file     Three types of communications are supported  UCMM  one  time request   response   Class 3 connection  cyclic request    response  and Class 1 connection  cyclic IO messages  containing assemblies    data     EtherNet IP implementation on VAMP relay serves as a server  and is not capable of initiating communication    V210 EN M A011    Technical description    9 Communication    9 2 Communication protocols       V210 EN M A011    EtherNet IP main configuration parameters                                                     Parameter Range Description   IP address IP protocol address identifing  device in the network   Multicast IP Multicast IP ad
248. ower coso Power factor  quadrant related to direction PF  voltage    inductive Lagging Forward        capacitive Leading Forward   _      inductive Leading Reverse          capacitive Lagging Reverse   Z                      197    7 9 Symmetric components    7 Measurement functions Technical description       7 9     198    Symmetric components    In a three phase system  the voltage or current phasors may be  divided in symmetric components according C  L  Fortescue   1918   The symmetric components are    e Positive sequence 1   e Negative sequence 2   e Zero sequence 0    Symmetric components are calculated according the following  equations        So 1 1 1fU  S    gt  l a a  V   where  S  la aw   So   zero sequence component    S    positive sequence component  negative sequence component    TR  N       1 vad    a  12120     aa i   a phasor rotating constant    U   phasor of phase L1    phase current or line to neutral voltage   V   phasor of phase L2  W   phasor of phase L3    In case the voltage measurement mode is  2LL Uo  i e  two line   to line voltage are measured  the following equation is used  instead                re s     iosa   en   where  U    3 1 Ta   U z     Ui2   Voltage between phases L1 and L2   U23   Voltage between phases L2 and L3     When using line to line voltages  any zero sequence voltage can  not be calculated     NOTE  The zero sequence or residual measurement signals connected to the    relay are  Uo and 3l     However  usually the name    l
249. p parameters       The changing of the setting parameters can be done easily  When  the desired submenu has been found  with the arrow keys   press    to select the submenu  Now the selected setting group is  indicated in the down left corner of the display  See Figure  2 2 3 2   Seti is setting group one and Set2 is setting group two   When the needed changes  to the selected setting group  have    been done  press or to select another group  amp  is used    when the active setting group is 2 and is used when the active  setting group is 1      group2    SET I gt   Setting for stage I gt    ILmax   Status    I gt           Figure 2 2 3 2  Example of I gt  setting submenu    23    2 2 Local panel operations 2 Local panel user interface Operation and configuration  instructions       2 2 4  Fault logs    All the protection functions include fault logs  The fault log of a  function can register up to eight different faults with time stamp  information  fault values etc  Each function has its own logs  See  Figure 2 2 4 1      log     AV lt p I gt  log buffer   Log buffer 1  2003 04 28  11 11 52 251       Figure 2 2 4 1  Example of fault log    To see the values of  for example  log two  press to select the  current log  log one   The current log number is then indicated in  the down left corner of the display  See Figure 2 2 4 2  Log2   log    two   The log two is selected by pressing once     log2    I gt  log buffer  Date    03 08 21  342    Type 1 2  Log2 jFit 1 69 xin  I gt
250. ped min  amp  max of currents  Pmax 5 Time stamped min  amp  max of power and frequency  Mont 21 Maximum values of the last 31 days and the last  twelve months  Evnt 2 Events  DR 2 Disturbance recorder 2  Runh 2 Running hour counter  Active time of a selected  digital input and time stamps of the latest start and  stop   TIMR 6 Day and week timers  DI 5 Digital inputs including virtual inputs  DO 4 Digital outputs  relays  and output matrix  ExtAl 3 External analogue inputs 3  ExDI 3 External digital inputs 3  ExDO 3 External digital outputs 3  Prot 27 Protection counters  combined overcurrent status   protection status  protection enabling  cold load and  inrush detectionlf2 gt  and block matrix  I gt  5 1st overcurrent stage 50 51 4  I gt  gt  3 2nd overcurrent stage 50 51 4    gt  gt  gt  3 3rd overcurrent stage 50 51 4  Iv gt  4 Voltage restrained controlled overcurrent stage 51V 4  l    gt  6 1st directional overcurrent stage 67 4  lo gt  gt  6 2nd directional overcurrent stage 67 4  lo gt  gt  gt  4 3rd directional overcurrent stage 67 4  lp gt  gt  gt  gt  4 4th directional overcurrent stage 67 4  I lt  3 Undercurrent stage 37 4  12 gt  3 Current unbalance stage 46 4  T gt  3 Thermal overload stage 49 4  lo gt  5 1st earth fault stage 5ON 51N   4  lo gt  gt  3 2nd earth fault stage 50N 51N   4  lo gt  gt  gt  3 3rd earth fault stage 5ON 51N   4  lo gt  gt  gt  gt  3 4th earth fault stage 5ON 51N   4          V210 EN M A011    17    2 2 Local panel operations    2 Local
251. peration delay setting   a trip signal is issued  For situations  where no voltage is present  an adapted frequency is used  See chapter 4 2     Protection mode for f gt  lt  and f gt  lt  gt  lt  stages    These two stages can be configured either for overfrequency or for  underfrequency     Under voltage self blocking of underfrequency stages    The underfrequency stages are blocked when biggest of the three  line to line voltages is below the low voltage block limit setting   With this common setting  LVBIk  all stages in underfrequency  mode are blocked  when the voltage drops below the given limit   The idea is to avoid purposeless alarms  when the generator is not  running     Initial self blocking of underfrequency stages    When the biggest of the three line to line voltages has been below  the block limit  the under frequency stages will be blocked until the  pick up setting has been reached     Four independent frequency stages    There are four separately adjustable frequency stages  f gt  lt   f gt  lt  gt  lt    f lt   f lt  lt   The two first stages can be configured for either  overfrequency or underfrequency usage  So totally four  underfrequency stages can be in use simultaneously  Using the  programmable stages even more can be implemented  chapter  5 27   All the stages have definite operation time delay  DT      Setting groups    There are two settings groups available for each stage  Switching  between setting groups can be controlled by digital inputs  v
252. program can also use TCP IP LAN connection   Optional hardware is required    There is a free of charge PC program called VAMPSET available  for configuration and setting of VAMP relays  Please download  the latest VAMPSET exe from our web page www vamp fi  For  more information about the VAMPSET software  please refer to  the user   s manual with the code VVAMPSET EN M xxxx  Also the  VAMPSET user   s manual is available at our web site     V210 EN M A011    Technical description    4 Introduction 2 4 Configuration and parameter  setting       4     V210 EN M A011    Introduction    The numerical device includes all the essential protection    functions needed to protect generators in power plants  industry   offshore applications and embedded power generation                                               L1  L2  L3  Lif  ef e  A aml  B a L F  A ce   2 Lt Al Protection function    4      B b  50 51 67 SIV  p  3p Ea le                3p gt                 3P gt  gt                          SON SIN                    a 49             p gt                    37                                     u gt  gt              2    if   gt  gt  gt     ge  x  5  a I  i l a j lt  u gt    lt  lt         lt  lt     u gt  gt  gt                    81H 81L          t gt  lt                                                                                99          Prgl   8                                              Blocking and  output matrix                                                  
253. protection 12 gt        46        V210 EN M A011    Recorded values of the current unbalance stage  8 latest  faults  l2 gt   46                                   Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit  lgn   Maximum unbalance current  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during the fault          69    5 8 Thermal overload protection T gt  5 Protection functions Technical description     49        5 8     70    Thermal overload protection T gt   49     The thermal overload function protects the generator stator  windings against excessive temperatures     Thermal model    The temperature is calculated using rms values of phase currents  and a thermal model according IEC 60255 8  The rms values is  calculated using harmonic components up to the 15      rar  Trip time  Gore  Alarm  a k  ko  loy  valarm  Alarm 60    0 6   Trip  a k  ko  lon  I   Release time  t  T  C   In            a    I   Trip release  a V0 95 x ko x Igy    Start release  a V0 95 x ko x Igy xvalarm  Alarm 60    0 6     T   Operation time  T   Thermal time constant tau  Setting value   In   Natural logarithm function        Measured rms phase current  the max  value of three  phase currents     Ip    Preload current  1   VOxk  Icy  If temperature rise    is 120   gt    1 2   This parameter is the memory of  the algorithm and corresponds to the actual  temperature rise  
254. ps can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually    Figure 5 5 4 shows the functional block of the Idir gt  stage     Start  Register  event   Trip  Register  event    Figure 5 5 4 Block diagram of the three phase overcurrent stage lair gt     3vidirsblock       Dir  Base angle Setting Idir gt s Delay Definite   inverse Inverse time Multiplier Enable events  Not dir time characteristics    Parameters of the directional overcurrent stages  lair gt   lair gt  gt   67                                                  Parameter Value Unit Description Note  Status   Current status of the stage   Blocked   Start F   Trip F  TripTime s Estimated time to trip  SCntr Cumulative start counter Clr  TCntr Cumulative trip counter Clr  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active   setting group   2 None   Dix Digital input Set   VIX Virtual input   LEDx LED indicator signal   VOx Virtual output  Parameter   Value Unit   Description Note                         V210 EN M A011    Technical description    5 Protection functions    5 5 Directional overcurrent  protection Idir gt   67        V210 EN M A011                                                                   Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   ILmax A The supervised value  Max  of  IL1  IL2 and IL3  l  
255. ption time is 40 ms  If the voltage off  time is shorter it may be recognized depending on the relative  depth of the voltage dip    If the voltage has been significantly over the limit U  lt  and then  there is a small and short under swing  it will not be recognized   Figure 6 5 1     Voltage U1                      t              10 20 30 40 50 60 70 80 90  ms      gt  Time       Figure 6 5 1 A short voltage interruption which is probably not recognized    On the other hand  if the limit U  lt  is high and the voltage has been  near this limit  and then there is a short but very deep dip  it will be  recognized  Figure 6 5 2      V210 EN M A011    Technical description    6 Supporting functions    6 5 Voltage interruptions       V210 EN M A011    Voltage U1  A  U lt              gt  Time          10       20 30    40    50    60    70 80 90  ms     Figure 6 5 2 A short voltage interrupt that will be recognized    Setting parameters of the voltage sag measurement function                                Parameter   Value Unit   Default   Description   U1 lt  10 0     120 0   64 Setting value   Period 8h   Month   Length of the observation  Day period  Week  Month   Date     Date   Time   z Time             Measured and recorded values of voltage sag measurement    function        Parameter    Value    Unit    Description       Measured  value    Voltage    LOW   OK    Current voltage status       U1         Measured positive  sequence voltage       Recorded  values       Cou
256. r 12 3   Set   An editable parameter  password needed   C   Can be cleared to zero   F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  frequency during fault  elapsed delay and setting    group     Recorded values of the over  amp  under frequency stages  8  latest faults  f gt  lt   f gt  lt  gt  lt   f lt   f lt  lt   81H 81L     Parameter Value Unit   Description                         110 V210 EN M A011    Technical description 5 Protection functions 5 19 Rate of change of frequency   ROCOF  protection df dt  81R                                      yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day   Fit Hz Faulty frequency   EDly   Elapsed time of the operating time   setting  100    trip  SetGrp 1 Active setting group during fault  2  5 19  Rate of change of frequency  ROCOF     protection df dt  81R     Rate of change of frequency  ROCOF or df dt  function is used for  fast load shedding  to speed up operation time in over  and under   frequency situations and to detect loss of grid     A special application for ROCOF is to detect loss of grid  loss of  mains  islanding   The more the remaining load of the local  generator differs from the load before the loss of grid  the better  the ROCOF function detects the situation     Frequency behaviour during load switching    Load switching and fault situations may generate chang
257. r gt   67     5 Protection functions Technical description       5 5     Directional overcurrent protection la  ir gt    67     Directional overcurrent protection can be used for directional short  circuit protection  Typical applications are    e Short circuit protection of two parallel cables or overhead lines  in a radial network    e Short circuit protection of a looped network with single feeding  point    e Short circuit protection of a two way feeder  which usually  supplies loads but is used in special cases as an incoming  feeder    e Directional overcurrent protection in low impedance earthed  networks  Please note that in this case the device has to  connected to line to neutral voltages instead of line to line  voltages  In other words the voltage measurement mode has to  be  3LN   See chapter 7 6      The stages are sensitive to the amplitude of the highest  fundamental frequency current of the three measured phase  currents  The phase angle is based on the phase angle of the  three phase power phasor  For details of power direction see  chapter 7 8  A typical characteristic is shown in Figure 5 5 1  The  base angle setting is  30    The stage will pick up  if the tip of the  three phase current phasor gets into the grey area     NOTE  If the maximum possible earth fault current is greater than the most    58    sensitive directional over current setting  the device has to connected to  the line to neutral voltages instead of line to line voltages in order to get
258. re  CC     Figure 5 8 1 Ambient temperature correction of the overload stage T gt      V210 EN M A011 71    5 8 Thermal overload protection T gt  5 Protection functions Technical description     49        72    Example of a behaviour of the thermal model    Figure 5 8 2 shows an example of the thermal model behaviour    In this example t   30 minutes  k   1 06 and kO   1 and the  current has been zero for a long time and thus the initial  temperature rise is 0    At time   50 minutes the current changes  to 0 85xlgn and the temperature rise starts to approach value   0 85 1 06     64   according the time constant  At time 300 min   the temperature is about stable  and the current increases to 5    over the maximum defined by the rated current and the service  factor k  The temperature rise starts to approach value 110    At  about 340 minutes the temperature rise is 100   and a trip  follows     Initial temperature rise after restart    When the relay is switched on  an initial temperature rise of  70   is used  Depending of the actual current  the calculated  temperature rise then starts to approach the final value     Alarm function    The thermal overload stage is provided with a separately settable  alarm function  When the alarm limit is reached the stage  activates its start signal     Temperature rise thermbeh              overload    100  Omax     alarm  80  _ LY Reset ratio   95     Op  60             Settings   T   30 minutes  k  1 06    alarm   90     bax   k Iy To
259. re a separate zero sequence voltage  transformer is not needed  The setting values are relative to  the configured voltage transformer  VT  voltage V3    e Line Up  The zero sequence voltage is measured with voltage  transformer s  for example using a broken delta connection   The setting values are relative to the VTo secondary voltage  defined in configuration     NOTE  The U  signal must be connected according the connection diagram     Figure 10 2 1  in order to get a correct polarization  Please note that  actually the negative Uo     Up  is to be connected to the relay     V210 EN M A011    Technical description 5 Protection functions 5 16 Zero sequence voltage  protection U0 gt   59N        Two independent stages    There are two separately adjustable stages  Up gt  and Up gt  gt   Both  stages can be configured for definite time  DT  operation  characteristic     The zero sequence voltage function comprises two separately  adjust table zero sequence voltage stages  stage Uo gt  and Uo gt  gt     Setting groups    There are two settings groups available for both stages  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     U0sblock    Start    Event  register    Trip    Event  register    Blocking       Setting Release Delay Enable  Uo gt s delay events    Figure 5 16 1 Block diagram of the zero sequence voltage stages U  gt  and Up gt  gt     V210 EN M A011 103    5 16 Zero sequenc
260. rmer  if any   UnBB     e Rated generator side voltage of the unit transformer  if any   UnGS      UNITS FOR MIMIC DISPLAY    e Unit for voltages  V   The choices are V  volt  or kV  kilovolt    e Scaling for active  reactive and apparent power  Power   The  choices are k for kW  kvar and kVA or M for MW  Mvar and   MVA     V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       V210 EN M A011    DEVICE INFO    Relay type  Type VAMP 210   Serial number  SerN   Software version  PrgVer   Bootcode version  BootVer     DATE TIME SETUP    e Day  month and year  Date    e Time of day  Time    e Date format  Style   The choices are  yyyy mm da     dd nn yyyy  and  mm dd yyyy      CLOCK SYNCHRONISATION   e Digital input for minute sync pulse  SyncDI   If any digital input  is not used for synchronization  select          Daylight saving time for NTP synchronization  DST     Detected source of synchronization  SyScr     Synchronization message counter  MsgCnt     Latest synchronization deviation  Dev      The following parameters are visible only when the access level is   higher than  User     e Offset  i e  constant error  of the synchronization source   SyOS     e Auto adjust interval  AAlIntv     e Average drift direction  AvDrft    Lead  or  lag     e Average synchronization deviation  FilDev      39    2 4 Configuration and parameter 2 Local panel user interface Operation and configuration  instructions    set
261. rol  0 or 1  of the Trip relays  o Forced control  0 or 1  of the Alarm relays  o Forced control  0 or 1  of the IF relay  e The configuration of the output signals to the output relays  The  configuration of the operation indicators  LED  Alarm and Trip  and application specific alarm leds A  B and C  that is  the  output relay matrix      NOTE  The amount of Trip and Alarm relays depends on the relay type and  optional hardware     36 V210 EN M A011    Operation and configuration    2 Local panel user interface 2 4 Configuration and parameter  setting       2 4 6     2 4 7     V210 EN M A011    Protection menu Prot    The following functions can be read and set via the submenus of  the Prot menu     e Reset all the counters  PROTECTION SET CIAII    e Read the status of all the protection functions  PROTECT  STATUS 1 x    e Enable and disable protection functions  ENABLED STAGES  1 x    e Define the interlockings between signals  only with VAMPSET     Each stage of the protection functions can be disabled or enabled   individually in the Prot menu  When a stage is enabled  it will be in   operation immediately without a need to reset the relay    The relay includes several protection functions  However  the   processor capacity limits the number of protection functions that   can be active at the same time     Configuration menu CONF    The following functions and features can be read and set via the  submenus of the configuration menu     DEVICE SETUP    e Bit rate for the 
262. rom the    V210 EN M A011    Technical description 6 Supporting functions 6 8 Circuit breaker condition  monitoring       figure above  The table is edited with VAMPSET under menu   BREAKER CURVE                                 Point Interrupted current Number of permitted   kA  operations   1 0  mechanical age  10000   2 1 25  rated current  10000   3 31 0  maximum breaking current  80   4 100 1   5 100 1   6 100 1   7 100 1   8 100 1                   Setting alarm points    There are two alarm points available having two setting  parameters each     e Current   The first alarm can be set for example to nominal current of the  CB or any application typical current  The second alarm can be  set for example according a typical fault current    e Operations left alarm limit  An alarm is activated when there are less operation left at the  given current level than this limit     Any actual interrupted current will be logarithmically weighted for  the two given alarm current levels and the number of operations  left at the alarm points is decreased accordingly  When the   operations left  i e  the number of remaining operations  goes  under the given alarm limit  an alarm signal is issued to the output  matrix  Also an event is generated depending on the event  enabling     Clearing  operations left  counters   After the breaker curve table is filled and the alarm currents are  defined  the wearing function can be initialised by clearing the  decreasing operation counters with p
263. rse delay minimum time   IDMT  type of operation   is available for several protection  functions  The common principle  formulae and graphic  representations of the available inverse delay types are described  in this chapter     Inverse delay means that the operation time depends on the  measured real time process values during a fault  For example  with an overcurrent stage using inverse delay a bigger a fault  current gives faster operation  The alternative to inverse delay is  definite delay  With definite delay a preset time is used and the  operation time does not depend on the size of a fault      Stage specific inverse delay    Some protection functions have their own specific type of inverse  delay  Details of these dedicated inverse delays are described  with the appropriate protection function     Operation modes    There are three operation modes to use the inverse time  characteristics     1  Standard delays  Using standard delay characteristics by selecting a curve  family  IEC  IEEE  IEEE2  Rl  and a delay type  Normal  inverse  Very inverse etc   See chapter 5 29 1    2  Standard delay formulae with free parameters  Selecting a curve family  IEC  IEEE  IEEE2  and defining one s  own parameters for the selected delay formula  This mode is  activated by setting delay type to    Parameters     and then  editing the delay function parameters A     E  See chapter  5 29 2    3  Fully programmable inverse delay characteristics  Building the characteristics by settin
264. ry  Voltage measurement mode is   3LN    VT   12000 110    Three phase symmetric voltages connected to the relay s inputs  Ua  Ub and Uc are 57 7 V     gt  Primary voltage is Upri   V3x58x12000 110   10902 V    Example 3  Primary to secondary  Voltage measurement mode is   2LL Uo      VT   12000 110  The relay displays Upri   10910 V     gt  Secondary voltage is Usec   10910x110 12000   100 V    Example 4  Primary to secondary  Voltage measurement mode is   3LN      VT   12000 110   The relay displays U12   U23   Us    10910 V      Symmetric secondary voltages at Ua  Up and U   are  Usec   10910 V3x110 12000   57 7 V     205       7 10 Primary  secondary and per unit 7 Measurement functions Technical description    scaling       206    Per unit  pu  scaling of line to line voltages    One per unit   1 pu   1xUgn   100    where Uan   rated voltage  of the generator                                         Line to line voltage scaling  Voltage measurement mode   Voltage measurement mode    3LN    2LL Uo   secondary   gt  per oe U sec   VT pri U  J3   U sec i VT prr  anit Ye U   Vi ess U  SEC GN SEC GN  per unit  gt  U  U   VT U on U i    ee WP ssc i U on  secondar SEC   PU SEC SEC   PU  y VT err V3 VT pri             Example 1  Secondary to per unit  Voltage measurement mode is   2LL Uo      VT   12000 110   Ucn   11000 V   Voltage connected to the relay s input Ua or Up is 100 8 V      Per unit voltage is   Upu   100 8 110x12000 11000   1 00 pu   1 00xUen   100      Example 2  
265. ry 20    ms     V210 EN M A011    159    6 2 Disturbance recorder 6 Supporting functions Technical description       Running virtual comtrade files with VAMP relays    Virtual comtrade files can be run with VAMP relays with the  v 10 74 software or a later version  Relay behaviour can be  analysed by playing the recorder data over and over again in the  relay memory     Steps of opening the VAMPSET setting tool    1  Go to    Disturbance record    and select Open     A     2  Select the comtrade file from you hard disc or equivalent   VAMPSET is now ready to read the recording    3  The virtual measurement has to be enabled  B  in order to  send record data to the relay  C     4  Sending the file to the relay   s memory takes a few seconds   Initiate playback of the file by pressing the Go  button  D   The     Change to control mode    button takes you back to the virtual  measurement       Blelo c    P Bev itual measurement  Be EE   ee JEMTDC_Simulation 1  Show AVG  z an RMS Reading record file  Show MIN m    tor  STITT  T                               Sending record data to device           078 1515457   mem C47F26 FD F4 FE O4 FE 12 FE OC FE 1A FE 16 FE 00 FEOS TD a                             Enable vitual measurement    a C        Protected target VAMP 52             Frequency   50 000 Hz       Repeats  7       Note  The sample rate of the comtrade file has to be 32 cycle  625  os when 50 Hz is used   The channel names have to correspond  to the channel names in Vamp rela
266. s                                                    vamp210appl_1    Figure 10 1 1 Generator connected directly to the distribution busbar  Earthed  generator neutral     The device is suitable for use in directly earthed  high low  resistance earthed and isolated systems  The differential and  directional earth fault protection provides a sensitive and selective  protection solution in high resistance earthed and isolated  systems     In directly earthed or low resistance earthed systems the non   directional earth fault stage constitutes a sufficiently selective  earth fault protection when energized from two current  transformers forming a differential current connection    The rotor earth fault protection can be realized with the non   directional earth fault stage using the energizing current input lo2 in  combination with a simple current injection device  for example  type VEO MSV     V210 EN M A011 235    10 2 Directly connected generator 10 Applications Technical description  with unearthed generator neutral       10 2  Directly connected generator with  unearthed generator neutral              Protection function                                 50 51 67 51V       3 gt  3 gt   gt                    gt   3p gt  3b gt  46       ap gt  gt  ia             3b gt  gt                           50N 51N     gt        3P gt  gt  gt                                49  T gt                    37                                  u gt  gt            gt  gt  gt              81H 81L
267. s true   8 Vdc   in front panel port of VAMP relays     Fast Fourier transform  Algorithm to convert time domain signals to    frequency domain or to phasors     l e  dead band  Used to avoid oscillation when comparing two near by    values    Another name for pick up setting value I gt    Another name for pick up setting value Ip gt    Nominal current of the Io  input of the relay   Nominal current of the loz input of the relay   Nominal current of lo input in general   Nominal current of the protected device   Nominal current  Rating of CT primary or secondary     International Electrotechnical Commission  An international    standardization organisation   Institute of Electrical and Electronics Engineers    Abbreviation for communication protocol defined in standard IEC 60870   5 103    Local area network  Ethernet based network for computers and relays     V210 EN M A011    Technical description    13 Abbreviations and symbols 12 4 Supporting functions       Latching    NTP    PF    Pu    PT  pu    Un  Us  Uc  Uan  Un  UTC    VT  VTPRI  VTsec  WWW    V210 EN M A011    Output relays and indication LEDs can be latched  which means that they  are not released when the control signal is releasing  Releasing of lathed    devices is done with a separate action    Network time protocol for LAN and WWW   Active power  Unit    W    Power factor  The absolute value is equal to cos     but the sign is     for  inductive i e  lagging current and       for capacitive i e  leading curr
268. sed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      Under impedance protection Z lt   21     Under impedance protection can be used to detect near short  circuit faults  even when excitation of the generator collapse thus  limiting the available short circuit current  It is an alternative for the  voltage restrained overcurrent protection  chapter 5 6   When the  generator s short circuit current capacity is limited any high set  overcurrent stage might not pick up  but an under impedance  stage will still detect the fault     The stage is sensitive to positive sequence impedance Z4  which  is calculated using the equation    U  Z         where  L        Z     absolute value of positive sequence impedance   U    positive sequence voltage  l   positive sequence current   UnderlmpedanceZplane   cap R A  ind  jx    MINI   PA        0UMUy 0  w   Loy   ba           ZO KN  er j WAE PRY       s    NORMAL    OPERATION    AREA OF THE    GENERATOR   R        ind  cap    Figure 5 20 1 The trip region of under impedance stage is a circle in origin  The  radius Z lt  is the setting value  The bigger circle  stator limit  represents the  rated power of the generator     The impedance relay is insensitive to the phase angle between  current and voltage  Its characteristics in an impedance plane is a  circle in origin  where the horizontal axis represents resistance R  and the vertical axis represents reactance jX  Figure 5
269. set for trip area origin Set  in pu   Ros ohm   Resistive offset for trip area origin  in primary ohms   Xos xZn Reactive offset for trip area origin  in primary ohms              For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero  F   Editable when force flag is on    V210 EN M A011    125    5 23 Reverse power and under  5 Protection functions Technical description    power protection P lt   32           23     126    Recorded values of the latest eight faults   There are detailed information available of the eight latest earth  faults  Time stamp  fault impedance  fault angle  elapsed delay  and setting group     Recorded values of the under reactance stages  X lt   X lt  lt   40                          Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit Zn Fault impedance  Angle R Fault angle  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      Reverse power and under power  protection P lt   32     Reverse power function can be used for generators against  motoring to protect the prime mover against over speeding or to  disconnect a motor in case the supply voltage is lost and thus  prevent any power generation by the motor  Under power function  can be used to detect loss of the mechanical load of a motor   Reverse and under power function is sensi
270. setting extended     Data points added to DNP3 0 and IEC 60870 5 101  protocols     Protocol menus visible in Vampset only if protocol is  selected into use to a port     Corrections and additions to IEC 60870 5 101  DNP 3 0   Profibus and Modbus  slave and TCP  protocols     DeviceNET protocol support added   DCF 77 time syncronisation support added           291    16 Revision history Operation and configuration    instructions       292    6 71    Phase voltage and power measurement corrections   Synchrocheck correction in voltage mode  2LL Ly      Second harmonics stage added    Data points added to DNP3 0 IEC 60870 5 101 and  Modbus  slave and TCP  protocols RMS mode added and   Operation delay  setting extended for I gt  gt     Transient Intermittent  67NI  protection function  improvements   Operation delay  min setting reduced        10 38    First release with new CPU Older versions of VAMPSET  parameter files are not compatible with 10 x firmware     Native IEC61850 support including GOOSE added   DeviceNET protocol support added    UTF 8 support for local HMI panel  Russian  added   RTD Inputs  Quick Setup support added for VIO 12Ax  EthernetIP added     Improvements added to DNP3 0 IEC 60870 5 101  protocols        10 45    NVRAM event buffer size is user parameter        10 48    Support for HMS Profibus solution   IRIG BOO3        10 49    Polarity added for relays    Read write MAC address to from EEPROM with new chip   IEC61850  DI counters are reported via de
271. setting group     Recorded values of the reverse under power stages  8 latest    faults  P lt   P lt  lt   32                       Parameter Value Unit   Description  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Flt xPm   Minimum power  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2                      129    5 24 Second harmonic O C stage 5 Protection functions Technical description    If2 gt  51F2        5 24     130    Second harmonic O C stage I2 gt  51F2     This stage is mainly used to block other stages  The ratio between  the second harmonic component and the fundamental frequency  component is measured on all the phase currents  When the ratio  in any phase exceeds the setting value  the stage gives a start  signal  After a settable delay  the stage gives a trip signal     The start and trip signals can be used for blocking the other  stages    The trip delay is irrelevant if only the start signal is used for  blocking    The trip delay of the stages to be blocked must be more than 60  ms to ensure a proper blocking        Setting Delay Enable events  2 Harm    Figure 5 24 1 Block diagram of the second harmonic stage     Setting parameters of second harmonic blocking 2 Ha 51F2                              Parameter   Value Unit Default Description   If2 gt  10   100   10 Setting value If2 lfund   t_f2 0 05   300 0  s 0 05 Definite operating time   S_On Enabled    E
272. steresis any noise in the  measured signal or any noise in the measurement itself would  cause unwanted oscillation between fault on and fault off  situations     Hysteresis GT    hysteresis    PICK UP LEVEL                 gt  PICK UP   l    Figure 5 3 3 Behaviour of a greater than comparator  For example in  overcurrent and overvoltage stages the hysteresis  dead band  acts according  this figure     V210 EN M A011    Technical description    5 Protection functions 5 4 Overcurrent protection I gt   50 51        5 4     V210 EN M A011    Hysteresis_LT    hysteresis        l  K    PICK UP LEVEL                 lt  PICK UP   l    Figure 5 3 4 Behaviour of a less than comparator  For example in under voltage  and under frequency stages the hysteresis  dead band  acts according this  figure     Overcurrent protection l gt   50 51     Overcurrent protection is used against short circuit faults and  heavy overloads    The overcurrent function measures the fundamental frequency  component of the phase currents  The protection is sensitive for  the highest of the three phase currents  Whenever this value  exceeds the user s pick up setting of a particular stage  this stage  picks up and a start signal is issued  If the fault situation remains  on longer than the user s operation delay setting  a trip signal is  issued     Three independent stages   There are three separately adjustable overcurrent stages  I gt   I gt  gt   and I gt  gt  gt   The first stage l gt  can be configured f
273. synchronism  The under excitation  protection protects the generator against the risk of lost of  synchronism     When the generator produces capacitive power  that is when the  reactive component of the power phasor is negative  the excitation  current can be so low  that the synchronism is lost     This stage supervises the amount of capacitive power and in case  it exceeds the setting a start signal is issued  If the fault continues  longer than user s operation delay time setting  a trip signal is  issued     The measurement of the degree of excitation is based ona  complex three phase power vector  which is calculated from the  fundamental components of the phase currents and line to line  voltages     Trip area on a PQ plane    The tripping area of the under excitation stage on a PQ plane is  defined with two parameters  Q1 and Q2  see Figure 5 21 1 and  Figure 5 21 2  When the tip of the power phasor lies on the left  side of the left side of a straight line drawn through Q1 and Q2 and  on the negative side of P axis   the stage picks up     The P coordinate of the setting point Q1 has a fixed value equal to  zero and the Q coordinate is adjustable    The P coordinate of the setting point Q2 has a fixed value of 80   of the rated power of the generator and the Q coordinate is  adjustable     119    5 21 Under excitation protection Q lt  5 Protection functions Technical description     40        120    P P Q Circlel       Figure 5 21 1 Setting of the under excitation st
274. t  EDly   Elapsed time of the operating time  setting  100    trip  SetGrp 1 Active setting group during fault  2  5 10  Directional earth fault protection log gt      67N     The directional earth fault protection is used for generator s stator  earth faults in networks where a selective and sensitive earth fault  protection is needed and in applications with varying network  structure and length     The relay consists of versatile protection functions for earth fault  protection in various network types     The function is sensitive to the fundamental frequency component  of the residual current and zero sequence voltage and the phase  angle between them  The attenuation of the third harmonic is more  than 60 dB  Whenever the size of l    and Uo and the phase angle  between Ip and    Uo fulfils the pick up criteria  the stage picks up  and a start signal is issued  If the fault situation remains on longer  than the user s operation time delay setting  a trip signal is issued     Polarization    The negative zero sequence voltage  Uo is used for polarization  i e  the angle reference for Io  This  Uo voltage is measured via  energizing input Uo or it is calculated from the phase voltages  internally depending on the selected voltage measurement mode   see chapter 7 6      e LN  the zero sequence voltage is calculated from the phase  voltages and therefore any separate zero sequence voltage  transformers are not needed  The setting values are relative to  the configured volta
275. t  scaling    Many measurement values are shown as primary values although  the relay is connected to secondary signals  Some measurement   values are shown as relative values   per unit or per cent  Almost   all pick up setting values are using relative scaling  The scaling is  done using the given CT  VT and generator name plate values     The following scaling equations are useful when doing secondary  testing   7 10 1  Current scaling  NOTE  The rated value of the relay s current input  5 A or 1A   does not have any  effect in the scaling equations  but it defines the measurement range and  the maximum allowed continuous current  See chapter 12 1 1 for details     Primary and secondary scaling                   Current scaling    CT prr  secondary   primary    ppp   Isc     CT sc  ve CT src  primary   secondary   J op    1 pp      CT pri                For residual currents to inputs lo1 or lo2 use the corresponding  CTpri and CTgec values  For earth fault stages using locaic Signals  use the phase current CT values for CTpri and CTsec     Example 1  Secondary to primary    CT   500 5   Current to the relay s input is 4 A      Primary current is Iprpi   4x500 5   400 A  Example 2  Primary to secondary    CT   500 5   The relay displays lpr     400 A     gt  Injected current is Isec   400x5 500   4 A    202 V210 EN M A011    Technical description    7 Measurement functions 7 10 Primary  secondary and per       V210 EN M A011                unit scaling  Per unit  pu  scali
276. t 50 ms  Reset ratio 0 97  Transient over reach  any t  lt 10   Inaccuracy     Starting  3  of the set value or 5 mA secondary    Operation time  1  or  25 ms          This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts     V210 EN M A011 273    12 3 Protection functions 12 Technical data    Technical description       Directional overcurrent stages lair gt  and lair gt  gt   67        Pick up current    0 10   4 00 x len       Mode    Directional non directional       Minimum voltage for the direction solving    0 1 V secondary       Base angle setting range     180   to   179         Operation angle     88         Definite time function     Operating time    DT  0 06        300 00 s  step 0 02 s        IDMT function      Delay curve family    Curve type     Time multiplier k     DT   IEC  IEEE  RI  Prg   El  VI  NI  LTI  MI   depends on the family  0 05     20 0  except   0 50     20 0 for RXIDG  IEEE and IEEE2          Start time Typically 60 ms  Reset time  lt 95 ms  Retardation time  lt 50 ms   Reset ratio 0 95   Reset ratio  angle  2     Transient over reach  any t  lt 10        Inaccuracy     Starting    Angle      Operate time at definite time function    Operate time at IDMT function           3  of the set value or  0 5  of the rated value   2   U gt 5 V    30   U gt 0 1 V    1  or  30 ms    5  or at least  30 ms                 This is the instantaneous time i e  the mini
277. t situation  remains on longer than the user s operation time delay setting  a  trip signal is issued     Blocking during VT fuse failure    As all the protection stages the undervoltage function can be  blocked with any internal or external signal using the block matrix   For example if the secondary voltage of one of the measuring  transformers disappears because of a fuse failure  See VT  supervision function in chapter 6 7   The blocking signal can also  be a signal from the user s logic  see chapter 8 7      Self blocking at very low voltage    The stages can be blocked with a separate low limit setting  With  this setting  the particular stage will be blocked  when the biggest  of the three line to line voltages drops below the given limit  The  idea is to avoid purposeless tripping  when voltage is switched off   If the operating time is less than 0 08 s  the blocking level setting  should not be less than 15   to the blocking action to be enough  fast  The self blocking can be disabled by setting the low voltage  block limit equal to zero     V210 EN M A011 99    5 15 Undervoltage protection U lt   27  5 Protection functions Technical description       Figure 5 15 1 shows an example of low voltage self blocking     A The maximum of the three line to line voltages ULLmax iS  below the block limit  This is not regarded as an under  voltage situation     The voltage Uttmin is above the block limit but below the  pick up level  This is an undervoltage situation     Voltag
278. t the order in which the events are sorted  If the     Order     parameter is set to    New Old        then the first event in the  EVENT LIST is the most recent event     31    2 3 Operating measures    2 Local panel user interface Operation and configuration  instructions       2 3 4     Forced control  Force     In some menus it is possible to switch a signal on and off by using   a force function  This feature can be used  for instance  for testing   a certain function  The force function can be activated as follows    1  Move to the setting state of the desired function  for example  DO  see Chapter 2 4  on page 33     2  Select the Force function  the background color of the force  text is black      VAMP 210 force    Pick RELAY OUTPUTS 1  Enable forcing  T1    0  0  0  0  0  0  0  F       Figure 2 3 4 1  Selecting Force function    3  Push Oa     4  Push or to change the  OFF  text to  ON   that is  to  activate the Force function     5  Push to return to the selection list  Choose the signal to be    controlled by force with and v  for instance the T1  signal     6  Push to confirm the selection  Signal T1 can now be  controlled by force     7  Push or to change the selection from  0   not alert  to   1   alert  or vice versa     8  Push to execute the forced control operation of the  selected function  e g   making the output relay of T1 to pick  up    9  Repeat the steps 7 and 8 to alternate between the on and off  state of the function    10  Repeat the steps 1   4
279. t_ylivirtaporras    ly  100xly gt                        ly   0 20x1 gt  pf          4         U      0 2 Uy 0 8 1    Figure 5 6 1 Characteristics of a voltage restrained overcurrent function ly gt      When the generator pole voltage falls below the set voltage level   the start current level of the overcurrent stage ly gt  also starts falling  linearly controlled by the voltage according to the characteristic  curve in Figure 5 6 1    When the setting parameters are selected according to Figure  5 6 2  the function is said to be voltage controlled     NOTE  The overcurrent function can be used as a normal high set overcurrent    64    stage I gt  gt  gt   if IY1 and IY2 are set to 100      r Uohj_ylivirtaporras  K gt     Iy    1 00 x I gt     Iy     0 20 x I gt        Ux  Ux   0 4 Un  Figure 5 6 2 Voltage controlled overcurrent characteristics     The voltage setting parameters Ux  and Ux2 are proportional to the  rated voltage of the generator  They define the voltage limits   within which the start current of the overcurrent unit is restrained   The multipliers ly  and ly2 are used for setting the area of change  of the start level of the overcurrent function in proportion to the Ux   and Ux settings    The voltage restrained controlled overcurrent stage operates with  definite time characteristic  The start current ly gt  and the operating  time t gt  can be set by the user     V210 EN M A011    Technical description    5 Protection functions 5 6 Voltage restrained contr
280. tal input is in active state  when the trip circuit is complete  This is applicable for dry inputs DI7   DI20     V210 EN M A011 239    10 4 Trip circuit supervision 10 Applications Technical description        V ux   24 Vdc     240 Vdc       VAMP relay    ss a as eve F    Alarm relay  for trip  circuit failure Trip Circuit  failure alarm    relay compartment       circuit breaker compartment    close control        ee eee ee ee TCS1Dlopen    Figure 10 4 1 2 Trip circuit supervision using a single dry digital inout  when the  circuit breaker is in open position     Note  If for example DI7 is used for trip circuit supervision  the usage of DI8      DI14 is limited to the same circuitry sharing the V aux in the common  terminal     DIGITAL INPUTS       DIGITAL INPUTS       Figure 10 4 1 3 An example of digital input DI7 configuration for trip circuit  supervision with one dry digital input     240 V210 EN M A011       Technical description 10 Applications 10 4 Trip circuit supervision  OUTPUT MATRIX  T4 T2 T3 T4 Af A2    connected    connected and latched  A   DI     V210 EN M A011    Figure 10 4 1 4 An example of output matrix configuration for trip circuit  supervision with one dry digital input     Example of dimensioning the external resistor R   Uaux   110 Vdc 20  10     Auxiliary voltage with tolerance    Up   18 Vdc  Threshold voltage of the digital input  lpi   3 mA    Typical current needed to activate the digital input  including a 1 mA safety margin    Poot   SOW  R
281. tarting time  lt 100 ms  Reset time  lt 120 ms  Reset ratio  f gt  and f gt  gt   0 998  Reset ratio  f lt  and f lt  lt   1 002  Reset ratio  LV block  Instant  no hysteresis   Inaccuracy     starting  20 mHz    starting  LV block  3  of the set value or  0 5 V    operating time  1  or  30 ms                   Suitable frequency area for low voltage blocking is 45   65 Hz  Low voltage blocking is checking  the maximum of line to line voltages       This is the instantaneous time i e  the minimum total operational time including the fault detection  time and operation time of the trip contacts    NOTE  f lt  if device restarts for some reason there will be no trip even if the  frequency is below the set limit during the start up  Start and trip is  blocked   To cancel this block  frequency has to visit above the set limit     Underfrequency stages f lt  and f lt  lt                 Frequency measuring area 16 0   75 0 Hz   Current and voltage meas  range 45 0     65 0 Hz   Frequency stage setting range 40 0     64 0 Hz   Low voltage blocking 10     100  Uen      Definite time function     operating time 0 10      300 0 s  step 0 02 s   Undervoltage blocking 2 100     Starting time  lt 100 ms   Reset time  lt 120 ms   Reset ratio 1 002   Reset ratio  LV block  Instant  no hysteresis   Inaccuracy      starting  20 mHz     starting  LV block  3  of the set value or  0 5 V    operating time  1  or  30 ms          Suitable frequency area for low voltage blocking is 45   65 Hz  Low
282. tead  in case the clock is leading  it is softly slowed down  to maintain causality           System clock parameters                   Parameter   Value Unit   Description Note  Date Current date Set  Time Current time Set  Style Date format Set  y   d   m Year Month Day  d m y Day Month Year  m d y Month Day Year  SyncDI The digital input used for clock ne    synchronisation     DI not used for synchronizing       DI1     DIG Minute pulse input  TZone  12 00     UTC time zone for SNTP Set   14 00     synchronization     Note  This is a decimal number   For example for state of Nepal  the time zone 5 45 is given as                               5 75  DST No Daylight saving time for SNTP Set  Yes  Parameter   Value Unit   Description Note                         V210 EN M A011 179    6 10 System clock and  synchronization    6 Supporting functions    Technical description       180                      SySrc Clock synchronisation source  Internal No sync recognized since 200 s  DI Digital input  SNTP Protocol sync  SpaBus Protocol sync  ModBus Protocol sync  ProfibusDP Protocol sync  IEC 103 Protocol sync  DNP3 Protocol sync  MsgCnt 0     65535  The number of received  0    etc  synchronisation messages or  pulses  Dev  32767 ms   Latest time deviation between  the system clock and the  received synchronization  SyOS  10000 000 s Synchronisation correction for Set  any constant error in the  synchronizing source   A positive value will compensate  a lagging external sync and 
283. tep 0 01 s            This is the instantaneous time i e  the minimum total operational time including the fault  detection time and operation time of the trip contacts     Transformer supervision    Current transformer supervision                   Pick up current 0 00     10 00 x In   Definite time function  DT     Operating time 0 06     600 00 s  step 0 02 s   Reset time  lt 60 ms   Reset ratio Imax gt  0 97   Reset ratio Imin lt  1 03   Inaccuracy      Activation  3  of the set value     Operating time at definite time function  1  or  30 ms             V210 EN M A011          Technical description    12 Technical data    12 4 Supporting functions       12 4 4     12 4 5     V210 EN M A011    Voltage transformer supervision                      Pick up setting U2 gt  0 0     200 0     Pick up setting 12 lt  0 0     200 0     Definite time function  DT     Operating time 0 06     600 00 s  step 0 02 s   Reset time  lt 60 ms   Reset ratio 3  of the pick up value  Inaccuracy       Activation U2 gt     Activation l2 lt     Operating time at definite time function        1  unit   1  unit   1  or  30 ms          Voltage sags  amp  swells                      Voltage sag limit 10  120     Voltage swell limit 20     150     Definite time function  DT     Operating time 0 08     1 00 s  step 0 02 s   Low voltage blocking 0 50    Reset time  lt 60 ms   Reset ration      Sag 1 03     Swell 0 97     Block limit 0 5 V or 1 03  3     Inaccuracy      Activation  0 5 V or 3  of the set
284. the active   Set  setting group  S None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  vox Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   ILmax A The supervised value  Max  of  IL1  IL2 and IL3  lp gt  gt  gt  gt  A Pick up value scaled to primary  lp gt  gt  gt  gt  gt  value  lp gt  gt  gt  gt  xIgn Pick up setting Set  lp gt  gt  gt  gt  gt   t gt  gt  gt  s Definite operation time  for Set  t gt  gt  gt  gt  definite time only   Mode Dir Directional  67  Set  Undir Undirectional  50 51   Offset 2 Angle offset in degrees Set     S Measured power angle  U1  Un Measured positive sequence  voltage             For details of setting ranges see chapter 12 3   Set   An editable parameter  password needed     C   Can be cleared to zero    F   Editable when force flag is on    Recorded values of the latest eight faults    There are detailed information available of the eight latest faults   Time stamp  fault type  fault current  load current before the fault   elapsed delay and setting group     62    V210 EN M A011    Technical description    5 Protection functions 5 6 Voltage restrained controlled  overcurrent function IV gt   51V        5 6     V210 EN M A011    Recorded values of the directional overcurrent stages  8  latest faults  lair gt   lair gt  gt   lair gt  gt  gt   lair gt  gt  gt  gt   67                   
285. the rated generator current  this delay is enabled  The idea is  to avoid purposeless alarms  when the generator circuit breaker is  open and the excitation is switched off  By setting the delay equal  to zero  this feature is disabled     Two independent stages    There are two separately adjustable stages  U  lt  and U  lt  lt   Both  stages can be configured for definite time  DT  operation  characteristic     97    5 14 Undervoltage protection U1 lt      27P     5 Protection functions    Technical description       98    Setting groups    There are two settings groups available for both stages  Switching  between setting groups can be controlled by digital inputs  virtual  inputs  mimic display  communication  logic  and manually     Parameters of the under voltage stages U  lt   U  lt  lt   27P                                               Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1 or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group  z None  Dix Digital input  Vix Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   U1 V The supervised positive  sequence voltage in primary  volts  U1   The supervised positive  seque
286. ting       2 4 8     40    Protocol menu Bus    There are three communication ports in the rear panel  In addition    there is a connector in the front panel overruling the local port in  the rear panel     REMOTE PORT X5    e Communication protocol for remote port X5  Protocol     e Message counter  Msg    This can be used to verify that the  device is receiving messages    e Communication error counter  Errors     e Communication time out error counter  Tout     e Information of bit rate data bits parity stop bits   This value is not directly editable  Editing is done in the  appropriate protocol setting menus    The counters are useful when testing the communication     LOCAL PORT X4  pins 2  3 and 5     This port is disabled  if a cable is connected to the front panel  connector     e Communication protocol for the local port X4  Protocol   For  VAMPSET use  None  or  SPABUS     e Message counter  Msg    This can be used to verify that the  device is receiving messages    e Communication error counter  Errors     e Communication time out error counter  Tout     e Information of bit rate data bits parity stop bits   This value is not directly editable  Editing is done in the  appropriate protocol setting menus  For VAMPSET and  protocol  None  the setting is done in menu CONF DEVICE  SETUP     PC  LOCAL SPA BUS     This is a second menu for local port X4  The VAMPSET   communication status is showed    e Bytes size of the transmitter buffer  Tx     e Message counter  Msg  
287. tion  systems  Any light source combination and a delay can be  configured starting from 0 01 s to 0 15 s  The resulting signal is  available in the output matrix to be connected to BO  output relays  etc     Pick up scaling  The per unit  pu  values for pick up setting are based on the  current transformer values     Arcl gt   1 pu   1xly   rated phase current CT value   Arclo1 gt   1 pu   1Xlo1n   rated residual current CT value for  input lot    Arcloz gt   1 pu   1Xlo2n   rated residual current CT value for  input loo     V210 EN M A011    Technical description    5 Protection functions 5 28 Arc fault protection   50ARC 50NARC   optional        V210 EN M A011    Parameters of arc protection stages  Arcl gt   ArcloiA  Arclo2 gt   50 ARC 50NARC                 Parameter   Value Unit Description Note  Status   Current status of the stage  Start Light detected according Arclin F  Trip Light and overcurrent detected F  LCntr Cumulative light indication C  counter  S1  S2 or BI   SCntr Cumulative light indication C    counter for the selected inputs  according parameter Arclin          TCntr Cumulative trip counter C  Force Off Force flag for status forcing for Set  On test purposes  This is a    common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout        Value of the supervised signal                                     ILmax Stage Arcl gt   lo1 Stage Arclo  gt   lo2 Stage Arclos gt   Arcl gt  pu Pick up setting xin Set  Arclo1 gt  pu 
288. tion  yyyy mm dd Time stamp of the recording  date  hh mm ss ms Time stamp  time of day  Fit pu Maximum earth fault current  EDly   Elapsed time of the operating time  setting  100    trip  Angle 2 Fault angle of Ip     Up   0    Uo   Max  Up voltage during the fault  SetGrp 1 Active setting group during fault  2                      Intermittent transient earth fault  protection loint gt   67NI     NOTE  This function is available only in voltage measurement modes     which    include direct  U measurement like for example 2U   Up  but not for  example in mode 3U y     The directional intermittent transient earth fault protection is used  to detect short intermittent transient faults in compensated cable  networks  The transient faults are self extinguished at some zero  crossing of the transient part of the fault current lFaut and the fault  duration is typically only 0 1 ms    1 ms  Such short intermittent  faults can not be correctly recognized by normal directional earth  fault function using only the fundamental frequency components of  lo and Up    Although a single transient fault usually self extinguishes within  less than one millisecond  in most cases a new fault happens  when the phase to earth voltage of the faulty phase has recovered   Figure 5 11 1         1 The voltage measurement modes are described in a separate chapter   85    5 11 Intermittent transient earth fault 5 Protection functions Technical description    protection IOINT gt   67NI        86       E
289. tion of phase  current IL2      THDIL3   I HARM  DISTORTION   Total harmonic distortion of phase  current IL3      Diagram   I HARMONICS of IL1 Harmonics of phase current IL1       see Figure 2 3 2 1   Diagram   I HARMONICS of IL2 Harmonics of phase current IL2               see Figure 2 3 2 1        29       2 3 Operating measures    2 Local panel user interface    Operation and configuration  instructions                                                                                        Value Menu Submenu Description  Diagram   I HARMONICS of IL3 Harmonics of phase current IL3       see Figure 2 3 2 1   Uline U LINE VOLTAGES Average value for the three line  voltages  V   U12 U LINE VOLTAGES Phase to phase voltage U12  V   U23 U LINE VOLTAGES Phase to phase voltage U23  V   U31 U LINE VOLTAGES Phase to phase voltage U31  V   UL U PHASE VOLTAGES   Average for the three phase voltages   V   UL1 U PHASE VOLTAGES   Phase to earth voltage UL1  V   UL2 U PHASE VOLTAGES   Phase to earth voltage UL2  V   UL3 U PHASE VOLTAGES   Phase to earth voltage UL3  V   Uo U SYMMETRIC Residual voltage Uo      VOLTAGES  U1 U SYMMETRIC Positive sequence voltage      VOLTAGES  U2 U SYMMETRIC Negative sequence voltage      VOLTAGES  U2 U1 U SYMMETRIC Negative sequence voltage related to  VOLTAGES positive sequence voltage      THDU U HARM  DISTORTION   Total harmonic distortion of the mean  value of voltages      THDUa_   U HARM  DISTORTION   Total harmonic distortion of the voltage  input a  
290. tive to active power   Whenever the active power goes under the pick up value  the  stage picks up and issues a start signal  If the fault situation stays  on longer than the delay setting  a trip signal is issued     Scaling of pick up setting  The pick up setting is proportional to the nominal power of the    prime mover parameter Pm  which is part of the basic  configuration     V210 EN M A011    Technical description 5 Protection functions 5 23 Reverse power and under   power protection P lt   32        ReversePowerPQplane  NORMAL   ie    OPERATION  AREA OF THE end  GENERATO 1m  I       u  a     m  5  m o  lt    lt   J u  JE 2  p  ZZ on    Lo m g    JE i  s O  ml  g STABILITY LIMIT  i  I     i  I     ind i  cap  P A 7    Figure 5 23 1 Characteristics of reverse power function   Reverse power    For reverse power protection a negative pick up value is used   Figure 5 23 1      V210 EN M A011 127    5 23 Reverse power and under  5 Protection functions Technical description  power protection P lt   32        UnderPowerPQplane  NORMAL 15   OPERATION                     Z  ind  ER ANA    Figure 5 23 2 Characteristics of under power function      cap    Under power   When the pick up value is positive  the function is called under   power  Figure 5 23 2     Two independent stages   There are two separately adjustable stages available  P lt  and P lt  lt      Setting groups   There are two settings groups available  Switching between  setting groups can be controlled by digital 
291. tor ResCap       Base angle setting range     180   to   179         Operation angle     88    10     170          Definite time function     Operating time    0 10        300 00 s  step 0 02 s        IDMT function      Delay curve family    Curve type     Time multiplier k     DT   IEC  IEEE  RI Prg   EI  VI  NI  LTI  MI   depends on the family     0 05   20 0  except   0 50     20 0 for RXIDG  IEEE and IEEE2       Start time   Reset time   Reset ratio   Reset ratio  angle     Typically 60 ms   lt 95 ms   0 95   20       Inaccuracy     Starting Uo amp lo  rated value In  1    5A       Starting Uo amp lo  Peak Mode when  rated  value lon  1    10A       Starting Up amp lo  locaic     Angle      Operate time at definite time function         Operate time at IDMT function        3  of the set value or  0 3  of the rated value     5  of the set value or  2  of the rated value   Sine wave  lt 65 Hz      3  of the set value or  0 5  of the rated value   2    when U gt  1V and lo gt 5  of lon   else  20      1  or  30 ms    5  or at least  30 ms                 El   Extremely Inverse  NI   Normal Inverse  VI   Very Inverse  LTI   Long Time Inverse    Ml  Moderately Inverse        The measuring range may limit the scope of inverse delays  See chapter 5 29 for details     277    12 3 Protection functions    12 Technical data    Technical description       Voltage protection    Overvoltage stages U gt   U gt  gt  and U gt  gt  gt   59        Overvoltage setting range     U gt   U gt  
292. transferring event information to a SCADA system     After testing the force flag will automatically reset 5 minute after  the last local panel push button activity    The force flag also enables forcing of the output relays and forcing  the optional mA outputs     Start and trip signals   Every protection stage has two internal binary output signals  start  and trip  The start signal is issued when a fault has been detected   The trip signal is issued after the configured operation delay  unless the fault disappears before the end of the delay time     Output matrix    Using the output matrix the user connects the internal start and trip  signals to the output relays and indicators  For more details see  chapter 8 4     V210 EN M A011    Technical description    5 Protection functions 5 3 General features of protection  stages       V210 EN M A011    Blocking    Any protection function  except arc protection  can be blocked with  internal and external signals using the block matrix  chapter 8 5    Internal signals are for example logic outputs and start and trip  signals from other stages and external signals are for example  digital and virtual inputs     Some protection stages have also inbuilt blocking functions  For  example under frequency protection has inbuilt under voltage  blocking to avoid tripping when the voltage is off     When a protection stage is blocked  it won t pick up in case of a  fault condition is detected  If blocking is activated during the  operatio
293. ugate of the measured phase L2  fundamental frequency current phasor   Measured voltage phasor corresponding the  fundamental frequency voltage of phase L3     Complex conjugate of the measured phase L3  fundamental frequency current phasor     Apparent power  active power and reactive power are calculated  similarly as with line to line voltages    s  s   P real S   Q   imag S   P  cosp          V210 EN M A011    Technical description    7 Measurement functions 7 8 Direction of power and current       7 8     V210 EN M A011    Direction of power and current    Figure 7 8 1 shows the concept of three phase current direction  and sign of cos  and power factor PF  Figure 7 8 2 shows the  same concepts  but on a PQ power plane      90       ind  cap  Reverse inductive power   Forward capacitive power  current is leading current is leading  cos       cosp      PF   PF              cap  ind   Reverse capacitive power   Forward inductive power  current is lagging current is lagging   COS       cos          PF   PF      Figure 7 8 1 Quadrants of voltage current phasor plane    Q   90      lt          cap  ind  Reverse capacitive power   Forward inductive power  current is lagging current is lagging  cosm       cos        PF      PF   s       pP o     ind  cap  Reverse inductive power Forward capacitive power  current is leading current is leading  coso       cos       PF   PF       Figure 7 8 2 Quadrants of power plane    Table of power quadrants                      Power Current P
294. used to ensure that the wiring from the  protective device to a circuit breaker is in order  This circuit is  unused most of the time  but when a protection device detects a  fault in the network  it is too late to notice that the circuit breaker  cannot be tripped because of a broken trip circuitry     The digital inputs of the device can be used for trip circuit  monitoring  The dry digital inputs are most suitable for trip circuit  supervision  The first six digital inputs of VAMP 200 series relays  are not dry and an auxiliary miniature relay is needed  if these  inputs are used for trip circuit supervision     Also the closing circuit can be supervised  using the same  principle    In many applications the optimum digital inputs for trip circuit  supervision are the optional inputs DI19 and DI20  They don t  share their terminals with any other digital inputs     Trip circuit Supervision with one digital input    The benefits of this scheme is that only one digital inputs is  needed and no extra wiring from the relay to the circuit breaker   CB  is needed  Also supervising a 24 Vdc trip circuit is possible     The drawback is that an external resistor is needed to supervise  the trip circuit on both CB positions  If supervising during the  closed position only is enough  the resistor is not needed     e The digital input is connected parallel with the trip contacts   Figure 10 4 1 1     e The digital input is configured as Normal Closed  NC     e The digital input delay 
295. ustry  An external  VPA 3CG or an internal Profibus module  see the order code in  chapter 15   is required     Device profile  continuous mode     In this mode the device is sending a configured set of data  parameters continuously to the Profibus DP master  The benefit of  this mode is the speed and easy access to the data in the Profibus  master  The drawback is the maximum buffer size of 128 bytes   which limits the number of data items transferred to the master   Some PLCs have their own limitation for the Profibus buffer size   which may further limit the number of transferred data items     Device profile  Request mode     Using the request mode it is possible to read all the available data  from the VAMP device and still use only a very short buffer for  Profibus data transfer  The drawback is the slower overall speed  of the data transfer and the need of increased data processing at  the Profibus master as every data item must be separately  requested by the master    NOTE  In request more it is not possible to read continuously only one single    data item  At least two data items must be read in turn to get updated  data from the device     There is a separate manual for VPA 3CG available for the  continuous mode and request mode     Available data    VAMPSET will show the list of all available data items for both  modes  A separate document    Profibus parameters pdf    is also  available    The Profibus DP communication is activated usually for remote  port via a
296. verse X  MI Moderately inverse X X  STI Short time inverse X  STEI   Short time extremely inverse X  RI Old ASEA type X  RXIDG   Old ASEA type X                            142 V210 EN M A011    Technical description    5 Protection functions 5 29 Inverse time operation       V210 EN M A011    IEC inverse time operation    The operation time depends on the measured value and other  parameters according Equation 5 29 1 1   Actually this equation  can only be used to draw graphs or when the measured value   is  constant during the fault  A modified version is implemented in the  relay for real time usage     Equation 5 29  1 1    t Operation delay in seconds   k   Users multiplier       Measured value   Ipickup User s pick up setting   A B   Constants parameters according Table 5 29 1 2     There are three different delay types according IEC 60255 3   Normal inverse  NI   Extremely inverse  El   Very inverse  VI  and  a VI extension  Additional there is a de facto standard Long time  inverse  LTI      Table 5 29 1 2 Constants for IEC inverse delay equation                         p  lav i Parameter  elay type A B  NI Normal inverse 0 14 0 02  El Extremely inverse 80 2  VI Very inverse 13 5 1  LTI Long time inverse 120 1                   Example for Delay type  Normal inverse  NI        k   0 50      4 pu  constant current   pickup   2pu  A   0 14  B   0 02  ee 0 50  0 14  50    0 02  G     2    143    5 29 Inverse time operation 5 Protection functions Technical description     
297. vertoap   1 05 Imax    I   1   l 45 min  Ip   0 85 Iy i   l   l       Time    100 min 200 min 300 min 400 min 500 min  Figure 5 8 2 Example of the thermal model behaviour     V210 EN M A011    Technical description    5 Protection functions    5 8 Thermal overload protection T gt        V210 EN M A011                                                           49   Parameters of the thermal overload stage T gt   49   Parameter Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  Time hh mm s Estimated time to trip  s  SCntr Cumulative start counter C  TCntr Cumulative trip counter C  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   T   Calculated temperature rise  F  Trip limit is 100     MaxRMS Arms   Measured current  Highest of  the three phases   Imax A kxIgn  Current corresponding to  the 100   temperature rise   k gt  xIgn Allowed overload  service Set  factor   Alarm   Alarm level Set  tau min Thermal time constant Set  ctau xtau Coefficient for cooling time Set  constant  Default   1 0  kTamb xIgn Ambient temperature corrected  max  allowed continuous current  Imax40  lgn   Allowed load at Tamb  40   C  Set  Default   100     Imax70  lgn   Allowed load at Tamb  70   C  Set  Tamb   C Ambient temperature  Editable Set  Samb n a  Default    40   C  Samb Sensor for ambient temperature  n a No sensor in use for 
298. wn a generator     This undervoltage function measures the positive sequence of  fundamental frequency component U4 of the measured voltages   for calculation of U  see chapter 7 9   By using positive sequence  all the three phases are supervised with one value and in case the  generator looses connection to the network  loss of mains   the  undervoltage situation is detected faster than by using just the  minimum of the three line to line voltages     Whenever the positive sequence voltage U  drops below the  user s pick up setting of a particular stage  this stage picks up and  a start signal is issued  If the fault situation remains on longer  than the user s operation time delay setting  a trip signal is issued     Blocking during VT fuse failure    As all the protection stages the undervoltage function can be  blocked with any internal or external signal using the block matrix   For example if the secondary voltage of one of the measuring  transformers disappears because of a fuse failure  See VT  supervision function in chapter6 7   The blocking signal can also  be a signal from the user s logic  see chapter 8 7      Self blocking at very low voltage    The stages will be blocked when the voltage is below a separate  low voltage blocking setting  With this setting  LVBlk  both stages  are blocked  when the voltage U  drops below the given limit  The  idea is to avoid purposeless alarms  when the generator is not  running  The LVBIk setting is common for both stages  The
299. x    Figure 8 4 1 Output matrix        211    8 5 Blocking matrix 8 Control functions Technical description       8 5  Blocking matrix    By means of a blocking matrix  the operation of any protection  stage can be blocked  The blocking signal can originate from the  digital inputs DI1 to DI6  or it can be a start or trip signal from a  protection stage or an output signal from the user s programmable  logic  In the block matrix Figure 8 5 1 an active blocking is  indicated with a black dot      in the crossing point of a blocking  signal and the signal to be blocked    NOTE  The display show 20 Dis  even only 6 of them are available  Digital input  19  amp  20 are only available with DI19  DI20 option     Output_mattx    Output relays Operation  LdbJbIbILILILIL indicators    HHHHHHHH 8 amp 88           Block matrix S Relay matrix  Reset all latches    Figure 8 5 1 Blocking matrix and output matrix       Digital Inputs    212 V210 EN M A011    Technical description    8 Control functions 8 6 Controllable objects       8 6     V210 EN M A011    Controllable objects    The relay allows controlling of six objects  that is  circuit breakers   disconnectors and earthing switches  Controlling can be done by   select execute  or  direct control  principle     The logic functions can be used to configure interlocking for a safe  controlling before the output pulse is issued  The objects 1   6 are  controllable while the objects 7   8 are only able to show the  status   Controlling is
300. y includes a disturbance recorder  Arc protection is  optionally available    The relay communicates with other systems using common  protocols  such as the Modbus RTU  ModbusTCP  Profibus DP   IEC 60870 5 101 IEC 60870 5 103  IEC 61850  SPA bus Ethernet    IP and DNP 3 0     1 2  User interface    The relay can be controlled in three ways     e Locally with the push buttons on the relay front panel   e Locally using a PC connected to the serial port on the front  panel or on the rear panel of the relay  both cannot be used  simultaneously    e Via remote control over the remote control port on the relay  rear panel     1 3  Operating Safety       A WARNING       HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC  FLASH    A live current transformer secondary circuit must not be opened  without turning off the primary side of the transformer and short  circuiting transformer secondary circuits first    Failure to follow these instructions can result in death   serious injury  or equipment damage             V210 EN M A011    2 1 Relay front panel 2 Local panel user interface Operation and configuration  instructions       2  Local panel user interface    2 1  Relay front panel    The figure below shows  as an example  the front panel of the  relay VAMP 210 and the location of the user interface elements  used for local control           VAMP 210    Scheider                                     Figure 2 1 1  The front panel of VAMP 210    1  LCD dot matrix display   2  Keypad   3  LED
301. ys  IL1  IL2  IL3  lo1  lo2  U12   U23  UL1  UL2  UL3 and Uo     160 V210 EN M A011    Technical description    6 Supporting functions 6 3 Cold load pick up and inrush  current detection       6 3     V210 EN M A011    Cold load pick up and inrush current  detection    Cold load pick up    A situation is regarded as cold load when all the three phase  currents have been less than a given idle value and then at least  one of the currents exceeds a given pick up level within 80 ms  In  such case the cold load detection signal is activated for a given  time  This signal is available for output matrix and blocking matrix   Using virtual outputs of the output matrix setting group control is  possible     Application for cold load detection    Right after closing a circuit breaker a given amount of overload  can be allowed for a given limited time to take care of concurrent  thermostat controlled loads  Cold load pick up function does this  for example by selecting a more coarse setting group for over   current stage s   It is also possible to use the cold load detection  signal to block any set of protection stages for a given time     Inrush current detection    Inrush current detection is quite similar with the cold load detection  but it does also include a condition for second harmonic relative  content of the currents  When all phase currents have been less  than a given idle value and then at least one of them exceeds a  given pick up level within 80 ms and the ratio 2  harm
302. z and normal  overvoltage protection  The volts hertz characteristics on the left depend on the  frequency while the standard overvoltage function on the right is insensitive to    frequency  The network frequency  50 Hz or 60 Hz  is automatically adopted by  the relay     93    5 13 Volts hertz over excitation    protection Uf gt   24     5 Protection functions    Technical description       94    The setting for a certain V Hz value K can be calculated using the  following formala    U ser  K     where    fy       SEC     100       Uiser   setting in per cent  K   secondary volts per hertz sensitivity   fn   rated network frequency   VTsec   rated secondary of the voltage transformer    Example    K  2 56 Vsec Hz  fn   50 Hz   VTsec  110 V    U  2 56   gt   100    116   SEF imo         50    Parameters of the volts hertz over excitation stage U  gt   24                                            Parameter   Value Unit Description Note  Status   Current status of the stage  Blocked  Start F  Trip F  SCnir Cumulative start counter C  TCntr Cumulative trip counter C  SetGrp 1or2 Active setting group Set  SGrpDI Digital signal to select the active   Set  setting group    None  Dix Digital input  VIX Virtual input  LEDx LED indicator signal  VOx Virtual output  Force Off Force flag for status forcing for Set  On test purposes  This is a  common flag for all stages and  output relays  too  Automatically  reset by a 5 minute timeout   Umax V The supervised value  Max  of  U12  U23
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Baixar manual    Installation Manual 18-24.cdr - Thermospace air conditioners    FS-1116MFP Manual de usuario  Marvel Industries 77237/77184 User's Manual    SK613 User Manual  BDA-082NS BDA  #R6262 DTC GHSTBSTR PROP REP PKE MTR Dom IS.ai    Copyright © All rights reserved. 
   Failed to retrieve file