Home
AQUA4-IOM-1405-E
Contents
1. 6 2 ELECTRICAL CONNECTIONS OF WATER VANE OPERATED FLOW SWITCH Available for all units is an additional vane operating flow switch installed in series with the water and electrical circuits and wired in the unit configuration 6 3 ELECTRIC CONNECTIONS OF THE CIRCULATION PUMP If selected on ordering it they is are supplied pre wired with all AQUA units For dual pump kits whether set up according to an AND or OR logic rotation is controlled on a time basis and triggered in the event of a fault Possible pump tank configurations Built in tank available only on utility side system 2 pumps which can be configured on demand can be installed on the buffer tank 1 utility side pump 1 DHW side pump 2 utility side pumps with OR Standby rotation or AND parallel logic 2 DHW side pumps with OR Standby rotation or AND parallel logic Two external pumps can be managed from the electrical control board with OR Standby rotation or AND parallel logic with a very low voltage 24 Vac control by an insulating transformer or clean contacts If there is not buffer tank the dual pump can be installed on board either on the utility side or on the DHW side with OR Standby rotation or AND parallel logic The pump s must be started before the chiler and stopped after the latter minimum recommended delay 60 seconds If included as an option this function is already performed
2. You should be extremely careful when attempting to implement any of the possible remedies suggested overconfidence can result in injuries even serious ones to inexpert individuals Therefore once the cause has been identified you are advised to contact the manufacturer or a qualified technician for help Plate heat exchanger Dryer filter Hydronic unit one pump per circuit Lamination valves Cold water outlet Hot water outlet Jr Hot water Cold water inlet inlet AQUA IOM 1405 E 26 LENNON The unit does not start No power supply Check that power is being supplied Mu RN both to the primary and auxiliary circuits the power supply Alarms have been triggered Check whether any alarms are signalled on the microprocessor control panel eliminate the causes and restart the unit The phase sequence is wrong Reverse two phases in the primary power line after disconnecting them upstream from the unit The compressor is noisy The compressor is rotating in the Check the phase sequence relay wrong direction Reverse the phases on the terminal board after disconnecting the unit contact the manufacturer Presence of abnormally high Insufficient flow of air to pressure condenser turning properly Check the air T at the condenser inlet and make sure no back suction occurs Check whether the effective RMS voltage to the fans 15 the maximum If necessary check the pressure
3. 5096 5096 blend of R32 R125 is used the glide will be negligible 0 2 C and the fluid can be considered like a pure fluid 7 5 STOPPING THE UNIT The unit can be stopped by pressing the OFF button on the front panel by turning off the main switch or via the specific commands on the LCD user interface Warning you should avoid stopping the unit using the main switch The latter device should be used to disconnect the unit from the electricity supply when there is no passage of current i e when the unit is already turned OFF Moreover if you completely disconnect the unit from the electricity supply the crankcase heating elements will receive no power thereby jeopardising the integrity of the compressor the next time the unit is started AQUA IOM 1405 E 19 LENNOX _ 8 OPERATING LIMITS Operating limits of AQUA chillers in relation to the outlet water temperature in brackets in cooling mode and outdoor air temperature Mi _ Evaporator outlet water temperature C 5 30 12 45 0 4 External air temperature C Maximum temperature of Domestic How Water C 50 81 WATER FLOW TO EVAPORATOR The nominal flow rate is based on a temperature differential of 5 C between inlet and outlet water in relation to the cooling capacity provided at the nominal water 12 7 C and air 85 C temperatures The maximum allowed flow rate is associated with a temperature differential of 3
4. AQUA IOM 1405 E 306 LENNOX High evaporation pressure Water T too high Check the thermal load and or efficiency of the thermostat function Check the efficiency of the thermostatic valve Defrosting absent or incomplete Error in parameter settings Check the setting of the start and end defrost parameters on the microprocessor properly drained from the coils Check the uniformity of the refrigerant circuit outlet temperatures at the top and bottom of the coils the maximum temperature differential allowed is 10 C Check the refrigerant level The 4 way valve has failed whether it is regularly work energized and deenergized 13 WATER PRESSURE DROPS 13 1 PRESSURE DROPS IN EVAPORATOR NB for further details contact the LENNOX technical department 13 2 PRESSURE DROPS IN HEAT RECUPERATOR NB for further details contact the LENNOX technical department AQUA IOM 1405 E 29 LENNOX _ 14 SUMMARY TABLE OF WEIGHTS L3 Li L5 L1 L2 This drawing shows the points of the unit for which the weights for the low noise version were calculated in configuration without pumps without tank and empty with treated water They are shown on the following table AQUA IOM 1405 E 0000000000000 280 LENNOX _ gt Multi purpose AQUA weights MS ML MS ML MS ML MS ML MS ML MS ML MS ML MS ML MS Mt MS ML MS ML PS PL PS PL PS PL PS PL PS PL PS
5. 3 633 3045 7 495 626 56 53 FRANCE SPAIN 33 1 64 76 23 23 34 902 533 920 GERMANY UKRAINE 49 0 40 589 6235 13 38 044 585 59 10 ITALY UNITED KINGDOM AND IRELAND 4 39 495 26 200 44 1604 669 100 NETHERLANDS 48 58 48 610 OTHER COUNTRIES NS PORTUGAL LENNOX DISTRIBUTION Due to Lennox s ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liability C Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and service must be performed by a qualified installer and servicing agency AQUA4 IOM 1405 E
6. A Therefore only qualified personnel may perform any kind of work on the unit THE UNIT MUST BE STARTED UP FOR THE FIRST TIME EXCLUSIVELY BY QUALIFIED PERSONNEL AUTHORISED BY LENNOX SEE ATTACHMENT FAILURE TO COMPLY WITH THE RULES PROVIDED IN THIS MANUAL OR ANY MODIFICATION MADE TO THE UNIT WITHOUT PRIOR AUTHORISATION WILL RESULT IN THE IMMEDIATE INVALIDATION OF THE WARRANTY A Warning Before performing any kind of work on the unit make sure it has been disconnected from the power supply AQUA IOM 1405 E 6 LENNOX lt 4 INSPECTION CONVEYANCE SITING 4 1 INSPECTION On receiving the unit check that it is perfectly intact the chiller left the factory in perfect conditions immediately report any signs of damage to the carrier and note them on the Delivery Slip before signing it Check in particular that the fins of the finned block heat exchangers are not bent and have not undergone impacts that may have impaired the system s tightness under pressure LENNOX or its Agent must be promptly notified of the entity of the damage The Customer must submit a written report describing every significant sign of damage commissioning report wiring diagram warranty certificate and list of authorised service centres check the integrity of the documents accompanying the unit and of this manual 4 2 LIFTING AND CONVEYANCE While the unit is being unloaded and positioned utmost care must be taken to avoid abr
7. C Higher flow rates though admissible cause pointless high drops in pressure The minimum allowed flow rate is associated with a temperature differential of 8 C or a minimum pressure drop of 10 kPa lower flow rates cause a reduction in heat exchange coefficients and excessively low evaporation temperatures which may trigger the safety devices and cause the unit to stop 8 2 CHILLED WATER TEMPERATURE The minimum temperature of the water leaving the evaporator is 5 C lower temperatures are possible but for such applications the Manufacturer should be consulted at the time the order is placed The maximum temperature of the water entering the evaporator is 20 C To allow higher temperatures specific equipment solutions must be adapted split circuits three way valves bypasses storage reservoirs applications outside the specified limits may be authorised by LENNOX subject to verification and subsequent authorisation in writing 8 3 OUTDOOR AIR TEMPERATURE The units are designed and built to work with outdoor air temperatures ranging from 10 with condensation control to 45 C Applications outside the specified limits may be authorised by LENNOX subject to verification and subsequent authorisation in writing On request the units may be equipped with an electric heating element for heating the evaporator in cases where the unit is exposed to severe temperatures during wintertime shutdown periods The heating element is activate
8. DHW 75 DHW 75 DHW 50 DHW 50 DHW 25 DHW 25 DHW AQUA P 2 pipes units 2 compressors 2 thermodynamic circuits All the year Summer to winter o 100 Cooling o 5096 Cooling o 100 Cooling 50 to 100 Heating o 50 Cooling 50 to 100 Heating o 10096 Heating o 5096 Heating AQUA P 2 pipes units 4 compressors 2 thermodynamic circuits All the year Summer to winter 100 Cooling 75 Cooling 5096 Cooling 25 Cooling 100 Cooling 5096 to 100 Heating 75 Cooling 2596 to 75 Heating 50 Cooling 25 to 100 Heating 25 Cooling 25 to 75 Heating 100 Heating 75 Heating 50 Heating 25 Heating AQUA IOM 1405 E 5 LENNOX 2 FIELD OF APPLICATION These machines are designed to cool heat water and solutions containing up to 35 glycol percentage by weight in civil industrial and technological air conditioning systems They must be used in observance of the operating limits specified in this manual failure to comply with said limits will invalidate the warranties provided in the contract of sale 3 GENERALITIES When installing or servicing the chiller you must strictly follow the rules provided in this manual comply with the directions on the units and take all such precautions as are necessary The fluids under pressure in the cooling circuit and the presence of electrical components may cause hazardous situations during installation and maintenance work
9. by the microprocessor on the unit 6 4 REMOTE CONTROLS If you wish to include a remote control for switching the unit on and off you must remove the jumper between the contacts indicated in the wiring diagram and connect the remote ON OFF control to the terminals themselves see annexed wiring diagram All remote controls work with a very low voltage 24 Vac supplied by the insulating transformer on the electric control board AQUA IOM 1405 E 14 LENNOX lt 6 5 REMOTE SUMMER WINTER SWITCHING If you wish to include a remote control for switching the unit between the summer and winter operating modes you must remove the jumper between the contacts indicated in the wiring diagram and connect the remote switching control to the terminals themselves see annexed wiring diagram The switching modes vary according to whether the microprocessor control is of the basic or advanced type detailed instructions are provided below see extract of corresponding wiring diagram and in the microprocessor user manual an integral part of the documentation provided pCO ONLY ONE REFRIGERANT CIRCUIT 18 A1 17 8 24 xi n e J8 DIGITAL INPUTS 18 El REMOTE ON OFF SUMMER REMOTE WINTER SETPOINT SELECTION SERIOUS EXTERNAL ALARM AQUA IOM 1405 E 15 LENNOX 7 STARTING UP 7 1 PRELIMINARY CHECKS Check that all the valves in the cooling circuit are open liquid line Ch
10. by means of the valves situated in the highest points e Check the efficiency of the flow switch or differential pressure switch e Check the heating elements where present of the compressor crankcases e Clean the metal mesh filters mounted externally on the water pipes e Check the humidity indicator on the liquid level indicator green dry yellow humid if the indicator is not green as shown on the indicator sticker replace the filter every 6 months e Check that the noise emissions of the unit are regular every 6 months and more specifically that no vibrations and or knocking can be detected LENNOX is not responsible for inexact translations of the manual in languages other than English AQUA IOM 1405 E 209 2 LENNOX 10 3 REPAIRING THE COOLING CIRCUIT Warning while performing repairs on the cooling circuit or maintenance work on the compressors make sure the circuit is left open for as little time as possible Even if briefly exposed to air ester oils tend to absorb large amounts of humidity which results in the formation of weak acids If the cooling circuit has undergone any repairs the following operations must be carried out tightness test emptying and drying of the cooling circuit charging with refrigerant equipment the refrigerant should be handled exclusively in the liquid phase A If the system has to be drained always recover the refrigerant present in the circuit using suita
11. for pressure drops Check the efficiency of the pump system check valve optional Malfunctioning of thermostatic Warming the bulb with your hand valve check whether the valve opens and adjust it if necessary If it does not respond replace it Filter clogged Pressure drops upstream and downstream from the filter should not exceed 2 C If they do replace the filter Low condensation T Check the efficiency of the condensation control device where oresent Low level of refrigerant Check the refrigerant level by measuring the degree of subcooling if it is below 2 C replenish the charge Coil covered with frost in the case Check whether the defrost of heat pump operation parameters have been properly set Check the efficiency of the 4 way valve Low outdoor T if the unit is Check compliance with the operating with the heat pump operating limits and eliminate bypasses and back flow of air The compressor does not start The internal thermal protection In the case of compressors device has tripped equipped with a protection module check the thermal contact Identify the causes after restarting The circuit breakers or line fuses Pinpoint the cause by measuring have been tripped by a short the resistance of the individual windings and the insulation to the casing before restoring power switches has tripped eliminate the causes the distribution compartment
12. in temperature will significantly reduce the amount of refrigerant dissolved in it thus ensuring that the lubricating function desired is maintained At the same time it should be observed that a slight foaming 1 5 mm of the oil at start up pressure drop gt decrease in of solubility is normal and will not compromise the system s reliability Check that the plumbing connections have been properly made according to the indications given on the plates to be found on the unit itself proper inlet and outlet connections Make sure that the water circuit is duly bled to completely eliminate the presence of air fill the circuit gradually and open the air vent valves on the top part which the installer should have set in place AQUA IOM 1405 E 16 LENNOX 7 2 STARTING OPERATION Before starting the chiller turn the main switch off select the operating mode desired from the control panel red button heating green button cooling and press the ON button on the control panel The unit will start up if enabled bythe safety devices of the water circulation pump s by the flow switch or differential pressure switch by the T sensor measuring the temperature of the water returning from the system chiller inlet no alarms have been triggered Starting up e Check that all external cocks of the water circuit are open and water flows properly the flow alarm should not triggered e Put the main swit
13. section sizes specified in the wiring diagram which is an integral part of the documentation accompanying the chiller the diagram code also appears on the rating plate inside the compressor compartment A The size of the cable and line protections must conform to the specifications provided in the wiring diagram The supply voltage may not undergo fluctuations exceeding 5 and the unbalance between phases must always be below 2 The above operating conditions must always be complied with failure to ensure said conditions will result in the immediate invalidation of the warranty The electrical connections must be made in accordance with the information shown in the wiring diagram provided with the unit and current regulations Electrical connections and preliminary checks e Put on the main switch turn the turn locking screws of the electric enclosure and open it e Introduce the power cable 400 3 50 N through the hole provided on the left side of the unit after first removing and making a hole in the aluminium square based on the diameter of the electric cable and secure it with a cable gland e Connect the power supply and earthing wire to the terminals of the main switch e Open the fuse carriers F1 and F2 or Q1 and Q2 for the motor overload cutouts of the compressors F1 F2 F3 F4 for the fuses or Q1 Q2 Q3 Q4 for the overload cutouts in the case of AQUA 4 compressor models to prevent them from starting up in the wrong
14. ACKING The packing must be carefully removed to avoid the risk of damaging the unit Different packing materials are used such as wood cardboard nylon etc It is recommended to keep them separately and deliver them to suitable waste disposal or recycling facilities in order to minimise their environmental impact Warning if the unit is supplied with a pump or pumps and or storage reservoir you will find the expansion tank packaged in the fan compartment it must be fixed to the pump intake pipe where a TEE is fixed so as to form a tight seal or on the tank itself Remove the cap and screw in the expansion tank operation to be performed by qualified personnel check the pre fill pressure 0 5 1 0 bars r before filling the water circuit and starting up the chiller Warning the size of the expansion tank will depend both on the volume of water contained in the system and the water temperature range always check the tank capacity in relation to the water content of the system 4 4 SITING You should bear in mind the following aspects when choosing the best site for installing the unit and the relative connections size and origin of water pipes location of power supply accessibility for maintenance or repairs solidity of the supporting surface ventilation of the air cooled condenser and necessary clearance direction of prevalent winds avoid positioning the unit in such a way that the prevalent winds favour
15. ARANCE REQUIREMENTS It is of fundamental importance to ensure an adequate volume of air both on the intake and outlet sides of the finned condenser evaporator coils it is highly important to prevent the air delivered from being re aspirated as this may impair the performance of the unit or even cause an interruption in normal operation For this reason it is necessary to guarantee the following clearances see figure on this page rear side plumbing connections min 1 0 meter to guarantee access to plumbing connections and or for any necessary maintenance on the pumps reservoir expansion tank and flow switch electric control board side min 1 0 meter to guarantee access for inspection and or maintenance of cooling components finned pack heat exchanger side min 1 5 meters to ensure proper air circulation and access to the compressor compartment also from the side top side there must be no obstacle to expulsion 0000000000000000 1 0 m front oooooeooooooooco Top view of the unit AQUA IOM 1405 E 9 LENNOX lt 5 2 GENERAL GUIDELINES FOR PLUMBING CONNECTIONS When you are getting ready to set up the water circuit for the evaporator you should follow the directions below and in any case make sure you comply with national or local regulations use the diagrams included in this manual as your reference Connect the pipes to the chiller using flexible couplings to prevent the transmission of vibrations a
16. ES 10 3REPAIRING THE COOLING CIRCUIT 10 4 TIGHTNESS TEST 10 5HARD VACUUM AND DRYING OF THE COOLING CIRCUIT 10 6 CHARGING WITH R410A REFRIGERANT 10 7 ENVIRONMENTAL PROTECTION RETIRING THE UNIT TROUBLESHOOTING WATER PRESSURE DROPS 13 1 PRESSURE DROPS IN EVAPORATOR 13 2PRESSURE DROPS IN HEAT RECUPERATOR SUMMARY TABLE OF WEIGHTS 14 1 PUMPING AND STORAGE SYSTEMS OO OOO O O PAGE AQUA IOM 1405 E LENNOX _ Declaration of conformity The declaration of conformity is individually appended to the documents accompanying the unit normally placed inside the electrical enclosure AQUA IOM 1405 E LENNOX lt 1 Model number and codification The AQUA units are identified by the following codes Example AAH081MS Air Cooled Nominal Cooling capacity x10 kW ex 08 80 kW 1 1 2 compressors 2 circuits 4 4 compressors 2 circuits P 4 pipes S S standard noise level L Low noise Description of operation The machine has 4 water connections referring to two different hydraulic circuits Circuit 1 2 production of cold water summer hot water winter Circuit 2 production of hot water for example for domestic hot water The machine is equipped with 3 distinct heat exchangers Finned pack coil S3 with both evaporating and condensing function for heat exchanger with the thermal source outdoor air Plate heat exchanger S1 intended for utility circuit with evaporatin
17. LENNOX Think far Installation operating and maintenance Polyvalent air cooled heat pump 90 gt 330 kW AQUA4 IOM 1405 E gt C AIR CONDITIONING SOLUTIONS FOR YOUR FUTURE LENNOX c N 10 11 12 13 14 CONTENTS Model number and codification FIELD OF APPLICATION GENERALITIES INSPECTION CONVEYANCE SITING 4 1 INSPECTION 4 2 LIFTING AND CONVEYANCE 4 3 UNPACKING 4 4 SITING INSTALLATION 5 1 INSTALLATION CLEARANCE REQUIREMENTS 5 2 GENERAL GUIDELINES FOR PLUMBING CONNECTIONS 5 3 WATER CONNECTION TO THE EVAPORATOR 5 4 SAFETY DEVICES ON THE HIGH PRESSURE SIDE ELECTRICAL CONNECTIONS 6 1 GENERALITIES 6 2 ELECTRICAL CONNECTIONS OF WATER VANE OPERATED FLOW SWITCH 6 3 ELECTRIC CONNECTIONS OF THE CIRCULATION PUMP 6 4 REMOTE CONTROLS 6 5 REMOTE SUMMER WINTER SWITCHING STARTING UP 7 1 PRELIMINARY CHECKS 7 2 STARTING OPERATION 7 3 CHECKS DURING OPERATION 7 4 CHECKING THE REFRIGERANT LEVEL 7 5 STOPPING THE UNIT OPERATING LIMITS 8 1 WATER FLOW TO EVAPORATOR 8 2 CHILLED WATER TEMPERATURE 8 3 OUTDOOR AIR TEMPERATURE 8 4 OPERATION WITH WATER AT LOW TEMPERATURES SETTING OPERATING PARAMETERS 9 1 GENERALITIES 9 2 MAXIMUM PRESSURE SWITCH 9 3 MINIMUM PRESSURE SWITCH 9 4 SERVICE THERMOSTAT 9 5 ANTIFREEZE THERMOSTAT 9 6 ANTI RECYCLE TIMER 9 7 OIL DIFFERENTIAL PRESSURE SWITCH ROUTINE MAINTENANCE AND CHECKS 10 1 WARNINGS 10 2GENERALITI
18. PL PS PL PS PL PS PL PSPL PS PL TEE ee EXE 36 39 190 193 n se gt m e m n o e Lu os o o o o m 2 2 Lu os o o o o m oe 2 2 Lu qos o o o o m m s o o o o m n o oe MS ML MS ML MS ML MS ML MS ML PS PL PS PL Ps PL PsPL PS PL ma 24 za ma TEE TL T AQUA IOM 1405 E 354 4 LENNOX _ 14 1 PUMPING AND STORAGE SYSTEMS AQUA units may be equipped with 6 types of pumping systems complete with expansion tank low pressure single pump high pressure single pump low pressure twin pumps parallel operating high pressure twin pumps parallel operating low pressure twin pumps normal backup switching high pressure twin pumps normal backup switching In the case of pump systems including a back up pump the microprocessor controls the pumps in such a way as to equally divide the hours of operation changing over the pumps in the event of a fault A All of these considerations can also be chosen on the DHW side AQUA IOM 1405 E LENNOX lennoxemeia com SALES OFFICES BELGIUM AND LUXEMBOURG RUSSIA 32
19. ach full operating capacity depends on the starting conditions system size and load conditions AQUA IOM 1405 E Evan LENNOX _ 7 4 CHECKING THE REFRIGERANT LEVEL After a few hours of operation check whether the liquid level indicator has a green crown a yellow colour indicates the presence of humidity in the circuit In such a case the circuit must be dehumidified by qualified personnel Large quantities of bubbles should not appear through the liquid level indicator A constant passage of numerous bubbles may indicate that the refrigerant level is low and needs to be topped up A few minutes after the compressors have started up check that the end of condensation temperature shown on the pressure gauge refer to the pressure gauge scale for the refrigerant R410A marked with the initials D P Dew Point is about 16 22 C depending on the type of unit and charging conditions higher than the temperature of the air entering the condenser with the fans running at top speed Also check that the end of evaporation temperature shown on the pressure gauge refer to the pressure gauge scale for the refrigerant R410A marked with the initials D P Dew Point is about 3 5 5 0 C lower than the temperature of the water leaving the evaporator Make sure the superheating of the refrigerant fluid is limited to between 5 and 8 C To this end 1 read the temperature indicated by a contact thermometer placed on the compressor int
20. ake pipe 2 read the temperature indicated on the scale of a pressure gauge likewise connected to the intake side refer to the pressure gauge scale for the refrigerant R410A marked with the initials D P Dew Point The degree of superheating is given by the difference between the temperatures thus determined Make sure the subcooling of the refrigerant fluid is limited to between 4 and 6 C To this end 1 read the temperature indicated by a contact thermometer placed on the condenser outlet pipe 2 read the temperature indicated on the scale of a pressure gauge connected to the liquid inlet at the condenser outlet refer to the pressure gauge scale for the refrigerant R410A marked with the initials B P Bubble Point The degree of subcooling is given by the difference between the temperatures thus determined Warning the refrigerant R410A requires POE polyolester oil of a type approved by the compressor manufacturer For no reason should a mineral oil be introduced into the oil circuit Compressor discharge Average T T14 T2 2 T1 start of condensation DFW POINT T2 end of condensation RURRI POINT Enthalpy h AQUA IOM 1405 E 2185 LENNOX _ The difference between the Dew Point and Bubble Point is known as GLIDE and this is a characteristic property of refrigerant mixtures If pure fluids are used the phase change occurs at a constant T and thus the glide is equal to zero If HFC R410A
21. ble 10 4 TIGHTNESS TEST Fill the circuit with anhydrous nitrogen supplied from a tank with a pressure reducing valve until the pressure rises to 10 bar During the pressurisation phase do not exceed the pressure setting of the safety valves otherwise you will cause the latter to open The presence of any leaks must be determined using special leak detectors Should any leaks be detected during the test empty out the circuit before repairing the leaks with suitable alloys explosion as well as the certainty of extensive oxidisation in high temperature areas Do not use oxygen in the place of nitrogen as a test agent since this could cause a risk of 10 5 HARD VACUUM AND DRYING OF THE COOLING CIRCUIT To achieve a hard vacuum in the cooling circuit it is necessary to use a pump capable of generating a high degree of vacuum i e 15 Pa of absolute pressure If there is no suitable vacuum pump available or whenever the circuit has remained open for long periods of time you are strongly recommended to adopt the triple evacuation method This method is also recommended when there is a presence of humidity within the circuit The vacuum pump should be connected to the inlets The procedure to be carried out is as follows Evacuate the circuit until you reach an absolute pressure of at least 35 Pa At this point inject nitrogen into the circuit until you reach a relative pressure of about 1 bar Repeat the step described abov
22. ch in the ON position o pump will start immediately o After 60 seconds the compressor will start e Check the water temperature differential 12 7 C to be detected by means of a thermometer on the inlet and outlet water pipes of the unit e Check that there are no leaks on the refrigerant side and water side e Using all the screws supplied close the unit If the unit fails to start up check whether the set point has been set on the desired values You should not disconnect the unit from the power supply during periods when it is inoperative but only when it is to be taken out of service for a prolonged period e g at the end of the season To turn off the unit temporarily follow the directions provided in the section Stopping the Unit 7 3 CHECKS DURING OPERATION Check the phase sequence relay on the electrical control board to verify whether the phases occur in the correct sequence if they do not disconnect the unit from power supply and reverse two phases at the unit input Never attempt to modify internal electrical connections any undue modifications will render the warranty null and void set direction of rotation and were harmonized in the factory All the three phase devices on the unit compressor water pump and fans some versions have a Check that the temperature of the water entering the evaporator returning from the system is close to the setpoint value entered How long it will take to re
23. d whenever the temperature of the water leaving the evaporator falls below the temperature set on the antifreeze probe 8 4 OPERATION WITH WATER AT LOW TEMPERATURES The standard units are not designed to work with chilled water temperatures below 5 C at the A evaporator outlet In order to work below this limit the unit requires specific technical adjustments in such cases contact the Manufacturer AQUA IOM 1405 E 20 LENNOX _ 9 SETTING OPERATING PARAMETERS 9 1 GENERALITIES All the control devices are set and tested in the factory before the unit is dispatched However after the unit has been in service for a reasonable period of time you can perform a check on the operating and safety devices The settings are shown in Tables and Il The control devices may be serviced SOLELY BY QUALIFIED TECHNICIANS incorrect A settings may cause serious damage to the unit and injury to persons Many of the operating parameters and system settings are configured by means of the microprocessor control and are protected by passwords TABLE SETTING OF CONTROL DEVICES AQUA SERIES Service thermostat HS HL PS PL TABLE Il SETTING OF SAFETY CONTROL DEVICES AQUA SERIES m ____ ol Minimum pressure switch Modulating condensation control device Time lapse between two starts of the same S compressor Delayinflowswtchalam s 20 J Delay in low pressure alar
24. direction in the event of an incorrect phase sequence e Switch on the power supply by turning the main switch QS to ON e Verify whether the phase sequence H S T is correct by checking on the phase sequence relay situated in the middle of the electric control board that the green power on LED and yellow LED indicating the correct sequence both light up if this does not occur disconnect the chiller power supply from the external distribution panel and swap over two phases then repeat the operation IN NO CASE SHOULD YOU TAMPER WITH THE WIRING DOWNSTREAM FROM THE MAIN SWITCH since this may alter the correct sequence of other devices e g pump s e Close the fuse carriers F1 and F2 of the compressors F1 F2 F3 F4 in the case of 4 compressor models e Close the electric enclosure and lock it by means of the 1 turn locks An earth connection is required by law The installer must connect the earthing wire using the earthing terminal situated on the electric control board yellow and green wire The power supply to the control circuit is shunted from the power line through an insulating transformer situated on the electric control board The control circuit is protected by suitable fuses A standard feature of all units is a phase sequence relay that verifies the correct phase sequence this is necessary to assure that the chiller is completely functional before enabling a compressor start up AQUA IOM 1405 E 13 LENNOX
25. e Carry out the step described above for the third time but in this case attempting to reach the hardest vacuum possible Using this procedure you can easily remove up to 99 of pollutants AQUA IOM 1405 E 24 LENNOX 10 6 CHARGING WITH R410A REFRIGERANT Connect the tank of refrigerant gas to the male 1 4 SAE inlet situated on the liquid line after discharging a little gas to eliminate air in the connection pipe Carry out the charging operation with the refrigerant in liquid form until you reach 75 of the total charge Then connect to the inlet on the intake line and complete the charging process with the refrigerant in liquid form until no more bubbles can be seen on the liquid level indicator and the operating parameters specified in the section Checking the refrigerant level have been reached since R410A is a binary blend of R32 and R125 it is advisable to charge with refrigerant in the A unit that was originally charged with R410A in the factory cannot be charged with other refrigerants 10 7 ENVIRONMENTAL PROTECTION liquid phase to ensure the correct percentage of the 2 components Charge through the charging inlet provided between the expansion valve and evaporator inlet The law implementing the regulations reg EEC 2037 00 which govern the use of ozone depleting substances and greenhouse gases bans the dispersal of refrigerant gases in the environment and requires whoever is in their possessi
26. eck that the electrical connections have been made properly and that all the terminals are securely tightened This check should also be included in a periodic six month inspection Check that the voltage at the RST terminals is 400 V 5 and make sure the yellow indicator light of the phase sequence relay is on The phase sequence relay is positioned in the middle right part of the electric control board if the sequence is not duly observed it will not enable the machine to start Make sure there are no refrigerant leaks that may have been caused by accidental impacts during transport and or installation Check the power supply to the crankcase heating elements where present function is carried out automatically when the main switch is off Their function is to raise the T The heating elements must be turned on at least 5 10 minutes before the unit is started This A of the oil in the sump and limit the quantity of refrigerant dissolved in it To verify whether the heating elements are working properly check the lower part of the compressors it should be warm or in any case at a temperature 10 15 C higher than the ambient temperature Pressure in crankcase of R410A dissolved in oil The diagram above illustrates a specific property Charles Law of gases which are more soluble in liquids as the pressure increases but less soluble as the temperature increases if the oil is held at a constant pressure an increase
27. fluid J kg C p fluid density kg m3 At minimum time lapse between 2 compressor restarts 5 AT allowed water T differential C Cc Cooling capacity W Ns N of capacity control steps P chem Outgoing water T Incoming water T This check must be performed even though it must considered that the AQUA units cannot be configured with the tank on board AQUA IOM 1405 E EE LENNOX A standard feature of AQUA units is a device for controlling the flow rate vane operated flow switch in the water circuit in the immediate vicinity of the evaporator Any tampering with said device will immediately invalidate the warranty It is compulsory to install a metal filter with a mesh smaller less 1mm on the inlet water pipe It is strongly recommended to install a safety valve in the water circuit In the event of serious equipment faults e g fire it will enable water to be drained from the system thereby preventing possible bursts Always connect the drain outlet to a pipe with a diameter at least as large as that of the valve opening and direct it toward an area where the discharge of water cannot harm people This is a standard feature of units equipped with the optional buffer tank optional gt P P 5 4 SAFETY DEVICES ON THE HIGH PRESSURE SIDE A Cooling circuit safety devices are provided on each refrigerant circuit according to the volumetric capacity of the compressors ins
28. g function in summer mode and condensing in winter mode Plate heat exchanger S2 intended for DHW circuit condensing function normally and evaporating function only during defrost cycle AQUA IOM 1405 E ud LENNOX lt The possible operations are Summer Mode a Cooling Only represented on following page the system produces cold water on circuit 1 with the heat exchanger S1 and the heat removed together with the power absorbed by the compressors is dispersed into the outdoor air by means of finned coils S3 which act as condensers Ventilation is modulated to vary the air flow depending on condensation pressure Cooling DHW represented on following page the system produces cold water on circuit 1 with the heat exchanger S1 and hot water on circuit 2 with the heat exchanger S2 The heat removed by the heat exchanger S1 together with the power absorbed by the compressors is yielded to the hot water by means of the plate heat exchanger S2 Both circuits have the same priority namely both will be brought to the set point The finned pack heat exchangers are used to dispose of remove heat from the air only when requests are not equivalent Ventilation is normally disabled in this mode If the finned pack heat exchanger S3 is used ventilation is modulated in order to vary air flow autonomously from the two circuits depending on the condensation evaporation pressure DHW Only represented on fol
29. lowing page the system produces hot water on circuit 2 removing heat from outdoor air which together with the power absorbed by the compressors is yielded to the water by means of the plate heat exchanger S2 Ventilation is modulated to vary the air flow depending on evaporation pressure Winter Mode d Heat Only represented on following page the system produces hot water on circuit 1 removing heat from outdoor air which together with the power absorbed by the compressors is yielded to the water by means of the plate heat exchanger S1 Ventilation is modulated to vary the air flow depending on evaporation pressure LENNOX Possible operation combinations as the thermal load varies AQUA M 2 pipes units 2 compressors 2 thermodynamic circuits Summer Cooling mode Winter Heating mode o 100 Cooling o 100 Heating o 50 Cooling o 50 Heating o 100 Cooling 50 to 100 DHW o 50 Cooling 50 to 100 DHW o 100 DHW o 100 DHW o 50 DHW o 50 DHW o 50 Heating 50 DHW AQUA M 2 pipes units 4 compressors 2 thermodynamic circuits Summer Cooling mode Winter Heating mode 10096 Cooling 10096 Heating 75 Cooling 75 Heating 5096 Cooling 5096 Heating 25 Cooling 25 Heating 100 Cooling 50 to 100 DHW 7595 Cooling 25 to 75 DHW 25 Heating 25 to 50 DHW 50 Cooling 25 to 100 DHW 50 Heating 25 to 50 DHW 25 Cooling 25 to 75 DHW 100 DHW 100
30. m s __ Le m End ofdefrostpressue bar Maximum defrost Minimum time lapse between 5 defrosting operations AQUA IOM 1405 E 21 LENNOX _ 9 2 MAXIMUM PRESSURE SWITCH The high pressure switch is of the manually reset type and classifiable as category IV under EEC 97 23 It directly stops the compressor when the discharge pressure exceeds the set value See section 5 4 To verify its efficiency while the compressors are running close off the passage of air into the condensers and check by referring to the compressor outlet pressure gauge previously installed whether the pressure switch trips i e the compressors stop when the set value is reached pressure switch will step in to shut down the unit in any event however you should be ready to shut off the unit as directed in the section Stopping the Unit see also section 5 4 Warning during this operation if the safety device fails to trip the second cascade connected The high pressure switch must be manually reset this is possible only when the pressure falls below the set differential see Table 1 9 3 MINIMUM PRESSURE SWITCH The low pressure switch stops the compressor when the intake pressure falls below the set value for more than 60 seconds The switch is automatically reset when the pressure rises above the set differential see Table 1 however the unit will not resume operation until the alarm memory on the
31. microprocessor control is cleared 94 SERVICE THERMOSTAT The function of this device is to start and stop the compressors according to the demand for chilled water as determined by a sensor placed at the evaporator inlet water returning from the circuit This device is a function included in the microprocessor control and works with a proportional band width that may be set as desired 9 5 ANTIFREEZE THERMOSTAT The antifreeze sensor situated at the evaporator outlet detects the presence of excessively low temperatures and stops the unit Together with the flow switch and low pressure switch this device protects the evaporator from the risk of freezing as a result of faults in the water circuit This device is a function included in the microprocessor control 96 ANTI RECYCLE TIMER The function of the timer is to prevent excessively frequent compressor starts and stops This device is a function included in the microprocessor control It imposes a minimum time lapse of 300 seconds between two successive starts A Never attempt to change the delay set in the factory wrong settings could cause serious damage to the unit 9 7 OIL DIFFERENTIAL PRESSURE SWITCH AQUA units are equipped with spinning scroll compressors these compressors do not have a lubricant pump and therefore no oil differential pressure switch is provided AQUA IOM 1405 E 2109 s LENNOX _ 10 ROUTINE MAINTENANCE AND CHECKS 101 WARNINGS All the operatio
32. nd to compensate for thermal expansions These units are all configured for installation of the water inlet outlet pipes outside the unit on the rear and these pipes are supplied as a standard accessory at no extra cost for the customer Itis recommended to install the following components on the pipes e pair of quick connect couplings with pipe section to be welded optional that may be selected from the price list They facilitate the operations of connecting to the plumbing system greatly speeding up installation etemperature and pressure indicators for routine maintenance and monitoring of the unit Checking the pressure on the water side will enable you to verify whether the expansion tank is working efficiently and to promptly detect any water leaks within the equipment e traps on incoming and outgoing pipes for temperature measurements which can provide a direct reading of the operating temperatures Temperature readings can in any case be obtained from the microprocessor installed on the unit e regulating valves gate valves for isolating the unit from the water circuit e metal mesh filter incoming pipes with a mesh not to exceed 1 mm to protect the exchanger from scale or impurities present in the pipes e air vent valves to be placed at the highest points of the water circuit for the purpose of bleeding air The internal pipes of the unit are fitted with small air vent valves for bleeding the unit itself this ope
33. ns described in this chapter MUST ALWAYS BE PERFORMED BY QUALIFIED PERSONNEL Before carrying out any work on the unit or accessing internal parts make sure you have disconnected it from the mains electricity supply The upper part and outlet pipe of the compressor may reach temperatures as high as 110 C Be especially careful when working in the surrounding area while the unit is running Be especially careful when working in proximity to finned coils since the 0 11 mm thick aluminium fins can cause superficial injuries due to cuts After completing maintenance jobs always replace the panels enclosing the units and secure them with the fastening screws provided gt P P P P 10 2 GENERALITIES is a good idea to carry out periodic checks to ensure that the unit is working properly e Check the efficiency of all the control and safety devices as previously described e Check the terminals on the electric control board and compressor terminal boards to ensure that they are securely tightened The movable and fixed contacts of the contactors must be periodically cleaned and replaced whenever they show signs of deterioration e Check the refrigerant level by means of the liquid level indicator every 6 months e Check the oil levels through the windows provided on the compressor crankcases every 6 months e Check the water circuit for leaks every 6 months e Check the filling of the water circuit bleeding air from the circuit
34. on to recover them and at the end of their useful life either to return them to the dealer or take them to a suitable waste disposal facility The refrigerant HFC R410A is not harmful to the ozone layer but is included among the substances responsible for the greenhouse effect and thus falls within the scope of the aforesaid regulations Therefore special care should be taken when carrying out maintenance work to minimise refrigerant leaks 11 RETIRING THE UNIT When the unit has reached the end of its working life and needs to removed and replaced a series of operations should be carried out the refrigerant gas it contains should be recovered by specialised personnel and sent to a waste collection facility the lubricating oil in the compressors should also be recovered and sent to a waste collection facility if they cannot be reused the framework and components should be scrapped and separated according to the type of material this applies especially for the considerable quantities of copper and aluminium present in the unit This will make the job of waste collection disposal and recycling facilities easier and minimise the environmental impact of such processes AQUA IOM 1405 E 25 LENNOX lt 12 TROUBLESHOOTING On the next pages you will find a list of the most common causes that may cause the chilling unit to fail or malfunction These causes are broken down according to easily identifiable symptoms
35. ration may only be carried out when the unit is disconnected from the power supply make sure that the circuit is completely full of water then carefully bleed out the air and check again to make sure no air is present before starting the pump for the first time AQUA IOM 1405 E LENNON 5 3 WATER CONNECTION TO THE EVAPORATOR It is of fundamental importance that the incoming water supply is hooked up to the connection marked Water Inlet Otherwise the evaporator would be exposed to the risk of freezing since the antifreeze thermostat would not be able to perform its function moreover the reverse cycle would not be activated in the cooling mode resulting in additional risks of malfunctioning The dimensions and position of plumbing connections are shown in the dimension tables at the end of the manual water supplied to the evaporator remains constant 15 in all operating conditions The water circuit must be set up in such a way as to guarantee that the nominal flow rate of the The compressors often work intermittently since the chilling requirements of the user generally do not coincide with the output of AQUA unit In systems containing little water where the thermal inertia of the water is lower it is a good idea to check that the water content in the section delivering to users satisfies the condition below Ccx px Shx AT x Ns V water content in user section m3 Sh specific heat of the
36. talled as prescribed by Directive 97 23 PED in particular with respect to equipment design this Directive requires manufacturers to abide by the technical standard nearest to the type of object produced in the case of chillers designed for air conditioning or liquid cooling systems standard UNI EN 378 2 is taken into consideration According to this standard for refrigerant mass flow rates of up to 25dm3 per circuit only one pressure limiting device is required beyond this limit 2 must be applied Practically speaking these are safety pressure switches designed to protect the cooling circuit in a cascade fashion What is meant by cascade protection is illustrated in the figure Pressure switch 1 Cut out Pressure switch 2 Cut out Cut in Cut in where pressure switch 1 is set at the PS maximum admissible pressure of the system while pressure switch 2 will have the setting PS x 0 9 in accordance with the reference technical standard AQUA IOM 1405 E gt n LENNOX 6 ELECTRICAL CONNECTIONS 6 1 GENERALITIES A Before carrying out any job on electrical parts make sure the power supply is disconnected Check that the mains electricity supply is compatible with the specifications voltage number of phases frequency shown on the unit rating plate The power connection is made by means of a three core cable plus neutral and earth cable or single core cables one per phase earth according to the minimum cross
37. the backflow of air to the condenser coils a speed of 8 m s 28 8 km h already generates a sufficient stagnation pressure to guarantee approx 60 of the nominal air flow rate possible reverberation of sound waves All models belonging to the series are designed and built for outdoor installation avoid covering them with roof structures or positioning them near plants even if they only partly cover the unit which may interfere with the regular ventilation of the unit condenser It is a good idea to create a base of adequate dimensions to support the unit This precaution becomes essential when the unit is to be sited on unstable ground various types of soil gardens etc It is advisable to place a rigid rubber strip between the base frame and the supporting surface Whenever more effective insulation is required it is recommended to use vibrating damping spring supports In the case of installation on roofs or intermediate storeys the unit and pipes must be insulated from walls and ceilings by placing rigid rubber joints in between and using supports that are not rigidly anchored to the walls If the unit is to be installed in proximity to private offices bedrooms or areas where noise levels must be kept down itis advisable to conduct a thorough analysis of the sound field generated and verify its compatibility with the local laws in force AQUA IOM 1405 E ae LENNOX lt 5 INSTALLATION 5 1 INSTALLATION CLE
38. transducers via the revolution speed controller where oresent optional Check the cleanliness of the finned coils Presence of air in the refrigerant Drain and pressurise the circuit circuit as revealed by the check for leaks Generate a presence of bubbles in the flow slow vacuum longer than 3 hours indicator also with subcooling until reaching a pressure of 15 Pa values exceeding 5 C and then recharge in the liquid ohase subcooling of more than 8 C Thermostatic valve and or filter Check the temperatures upstream obstructed These symptoms may downstream from the valve also occur in the presence of an and filter and replace them if abnormally low pressure necessary Insufficient flow of water in the Check the water circuit case of heat pump operation pressure drops and or whether the pump is working properly direction of rotation Check the outgoing water T and make sure it is less than or equal to 45 C AQUA IOM 1405 E ey ae LENNON Low condensation pressure Transducer fault Check the transducers and the efficiency of the needle pusher on the Schrader valves they are connected to of strong winds device and or protect the unit from prevalent winds oump operation compatible with the unit s potential Low evaporation pressure Insufficient flow of water Check whether the pumps are rotating in the right direction Check the water system
39. upt or violent manoeuvres The unit must be handled carefully and gently avoid using machine components as anchorages when lifting or moving it The unit should be lifted using 01 GAS steel pipes at least 3mm thick to be inserted in the round holes provided ro sul basamento une Cinghia on the base side members see fig below and identified in base structure Bope Belt im Grundrahmen by means of stickers The pipes which should protrude by at least 250 300mm on every side must be slung with ropes of equal length secured to the lifting hook provide stops at the ends of the pipes to prevent the ropes from Secun bolt slipping off due to the weight uid Dado di serraggio 9Icherungsmutter ee Y ubo 02 1 2 N ube o2 1 2 N Stahlrohr 22 1 2 Use ropes or belts long enough to extend beyond the height of the unit and place spacer bars and boards on the top of the unit to avoid damaging the sides and top of the unit itself The rectangular holes are provided for the attachment of vibration damping supports optional Foro sul basamento Holes jn base structure L cher im Gruncrahmen Selle Gue Dado di serraggio Locknut gent X oicherundgsmutter mls ERE Jupo 03 v2 23 1 uc Uc 2 Stahlrohr c2 1 2 Bullone di sicurezza Security bolt Sicherneitsb lzen AQUA IOM 1405 E ee LENNOX _ 43 UNP
Download Pdf Manuals
Related Search
AQUA4 IOM 1405 E
Related Contents
TF40 Touch Samsung 40" Full HD Flat Smart TV J5300 Series 5 manual do usuário Télécharger le manuel 取扱・施工説明書 - 瀧住電機工業株式会社 U 87 Ai Bedienungsanleitung Operating Instructions JVC CB-V91U User's Manual Westinghouse Indoor Lighting Fixture 12804 User's Manual GW-D000901V LGX ZN55 Industrial IP67 LED Touchscreen Display 取扱説明書ダウンロード(PDF) Copyright © All rights reserved.
Failed to retrieve file