HAT270A ATS (Automatic Transfer Switch) Controller USER MANUAL
Contents
1. 2 P BE Bees 6 AC VALID OPTION o lt lt 8 PROGRAMMED PARAMETER AND 2 000001 9 TERMINALS 8 9 TYPICAL 10 10 CASE DIMENSIONS P 13 FAULT FINDING 13 HAT270A ATS Control Module ISSUE 2011 05 20 Version1 1 Page 3 of 13 HAT270A ATS Control Module 1 SUMMARY HAT270A ATS controller using microprocessor as its core can precisely monitor 2 Way 3 phase voltage make accurate judgment on abnormal voltage loss of power over voltage under voltage lack of phase and control ATS to transfer after delay When 1 power is abnormal the controller will send signal to start genset HAT270A controller is suitable for controlling SOCOMEC VS VE ATyS3 ATySM3s model and other ATS switches of similar function 2 PERFORMANCE AND CHARACTERISTICS HAT270A controller can monitor 2 way 3 phase voltage 2 way mains and 2 way gens or 1 way mains and 1 way gens and control ATS to transfer Its performance and characteristics are shown as below Realized computer programming control use computer to set voltage abnormal delay and genset stop delay switch priority correct voltage value and other functions
2. dry contact capacity is 7A Terminal LO NO It is the power supply for ATS LO NO separately comes from A and N phase of 1 and Zl power When A phase and N phase of lor I power is normal the two terminals will output power capacity is 5A 250VAC Terminal COM SOCOMEC ATS closing and opening control Terminal SOCOMEC ATS opening control contact capacity is 3A 250VAC Terminal l SOCOMEC closing control contact capacity is 3A 250VAC Terminal Il SOCOMEC ll closing control contactor capacity is 3A 250VAC 9 TYPICAL APPLICATION SOCOMEC VS Type Switch LOAD L1 L2 L3 9 9 N2 5 e R1 R2 gt 51 HU 52 0 Z Ti 2e 222 E a 2 HT 5 S ii Ts VS TYPE SOCOMEC 103 102202 203 205 402403 405 N1 C1B1A1 LO NO COM A2 B2 C2 N2 G 2 SLY 95019 1 5 0 2 tC 115 9S0 4 9JElIS 50 2 2 GENSET B Remote CONTROLLER gt eo HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 10 of 13 HAT270A ATS Control Module SOCOMEC VE Type Switch LOAD L1 L2 L3 R1 S1 T1 N1 LOdNI OV L VES ee SOCeoMmeEs 1 C1 B1 1 esolosL yeeig 115 9S0 D 1 BIE S S0 9 1 CONTROLLER ros 102 202 203 204 205 302 203 305 104 105 IM SH SOCOMEC ATyS3e Type Switch LOAD L1 L2 L3 1 AC INPUT 22 LO NO N1C1B1 A1COM 95010 2 ejejs
3. 1 0 9 E1S 2 CONTROLLER HAT270A ATS Control Module ISSUE 2011 05 20 Version1 1 A2 B2 C2 N2 2 AC INPUT 44 GENSET Page 11 of 13 HAT270A ATS Control Module SOCOMEC ATySM8s Type Switch LOAD Li L2 L3 1 AC INPUT 2 AC INPUT R1 51 11 1 LO 1 1 1 1 COM 95019 1 asolo 2 1 15 350 9 1 SIEIS 3950 3 4 CONTROLLER SOCOMEC ATyS3s Type Switch LOAD L1 L2 L3 N R1 51 Tie 1 x LAdNI OV Z LNdNI OW Ls AlyS3ss ret es or oa me N1 C1 B1 A1 LO NO COM A2 B2 C2N2 J8MOd 519 asoj l asol 2 91815 350 3 2 1815 9S0 D 2 ul B UD ul e CONTROLLER Note 81 84 1 closing N O auxiliary contact of ATyS3s switch 91 94 11 closing N O auxiliary contact of ATyS3s switch The SOCOMEC ATyS3s switch has not marked the closing auxiliary contact Please refer to the wiring diagram for the specific position HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 12 of 13 HAT270A ATS Control Module 10 CASE DIMENSIONS PANEL CUTOUT 130mm 119 mm 111mm F 31 11 FAULT FINDING Check connections of 1 and Zl power Check the fuse of and llipower Check ATS mechanism Check the connection between ATS and controller 1 or 11 normal indicator Check aif 3 phase voltage is normal over under flashes volt
4. Smartgen HAT270A ATS Automatic Transfer Switch Controller USER MANUAL Smartgen Technology f E FB F Chinese trademark Smartgen Smartgen make your generator Smart English trademark Smartgen Technology Co Ltd No 28 Jinsuo Road Zhengzhou Henan Province P R China Tel 86 371 67988888 67981888 86 371 67991553 67992951 67992952 86 371 67981000 overseas Fax 0086 371 67992952 Web http www smartgen com cn http www smartgen cn Email sales smartgen com cn All rights reserved No part of this publication may be reproduced in any material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder omartgen Technology reserves the right to change the contents of this document without prior notice Software Version Date 2010 04 02 Original release 14 2011 05 20 Modify Typical Application and operation procedures of the controller panel HAT270A ATS Control Module CONTENT utis 4 PERFORMANCE AND CHARACTERISTICS 4 SPECIFICATION e 5 PANEL DESGRIPTIOIN iioi oe 6 PANEL OPERATION AND 00 nnd 6 5 1 Delay 6 5 2 Control Setting
5. DESCRIPTION 3 phase cannot lack phase Set via PC only ZA72 1007 GENS START SOCOMEC AC INPUT 2 AC INPUT 1 CONNECT TERMIANAL m E Ed i LO 7 7 oO 1 Terminals A1 B1 C1 1 Separately connect A B C of 1 power Terminals A2 B2 C2 2 Separately connect A B C and N of 11 power Terminal 51 Closing status input of 1 power supply dry contact input grounding Terminal S2 Closing status input of 11 power supply dry contact input grounding Terminal FO VIN It is a multiplex port both for DC power positive and Forced Open input Controller will automatically choose DC power input or Forced Open input When this port is grounding controller will execute forced open action HAT270A ATS Control Module ISSUE 2011 05 20 Version1 1 Page 9 of 13 HAT270A ATS Control Module When connects DC power supply grounding will result in short circuit Only when DC power supply is disconnected can this port be grounding When this port is grounding whether in manual mode or automatic mode ATS will be switched to OFF position both manual and automatic operations are disable Forced Open is activated only for switches with OFF position like SOCOMEC VE type ATyS3 type and ATySMSS type but SOCOMEC VS type is invalid Terminal GND DC power cathode Terminal M1 M2 GENSET START Genset start relay
6. illuminates and then 1 power Supply is main power to supply for the power priority 1 HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 7 of 13 HAT270A ATS Control Module Press key 1 power supply indicator illuminates and then ll power supply is main power to supply for the load 11 power supply priority zal Press Q key 1 power supply power supply indicator illuminates which means no priority there is no priority supply for the load between 1 and 11 power supply Not detect Press O detection of ll Closing closing closing status status of 1 Indicator power 72 flashes Detect closing Press O detection of 1 and ll closing input is disabled s closing input is enabled 1 Note Once the controller is power on its priority can be judged by the following three conditions 1 power supply indicator flashing rapidly for three times indicates 1 power supply for priority transfer 2 11 power supply indicator flashing rapidly for three times indicates 11 power supply for priority transfer 3 Both and 11 power supply indicators flashing for three times indicates there is no priority transfer 2 Note Once the controller is power on and 11 power supply indicators flash simultaneously 1 and 11 closing input detection is enabled if not the detection is disabled Detect enabled l and closing status is judged by input status Detect d
7. procedures are as below Pressing car circularly select the setting items Different items have different flashing LED indicators on the panel The setting the item as below After adjusting l power supply normal delay potentiometer vesc power indicator illuminates which confirms the setting Set range 0 60 s After adjusting power supply normal Power 1 power abnormal indicator s poner delay potentiometer l abnormal delay flashes power indicator illuminates which delay confirms the setting oet range 0 60 s power abnormal delay Press 1 power indicator illuminates which confirms the action Abnormal delay of 1 1 power supply is 5s by default After adjusting l power supply normal Restore factory default delay potentiometer O automatic status indicator illuminates which confirms the setting Set range 0 60 s After adjusting ll power supply normal delay potentiometer press start delay Automatic start stop status delay indicator stop delay key automatic status indicator flashes illuminates which confirms the setting Set range 0 60 s Press key automatic status indicator illuminates which confirms the setting Stop delay is 90s by default Restore factory value 11 power indicator flashes itl power Press key 1 power supply supply priority indicator
8. with overall graphical interface operation When programming with computer the front panel must be opened then use SG72 interface module USB to LINK to program via the PC test software Please refer to 270 Test Software Manual for more information about PC software Power supply of the device is A phase and N phase of 1 and 11 power supply Normal delay l power supply or power supply can be set in 0 60 seconds Genset start delay can be set in 0 60 seconds Abnormal delay of 1 power supply or Zll power supply can be set in 0 60 seconds Genset stop delay can be set in 0 60 seconds itl Priority Auto Manual No Priority and Priority can be set through panel knobs to ensure l Power Priority Power Priority or No Priority and maintenance Isolated design of 2 way Neutral With forced breaking input When the input port is enabled ATS will automatically transfer to Breaking OFF Position LED can clearly display working status of switch With dual power supply conversion circuit LO NO output 250V AC can be applied directly as the power supply for ATS Output contact capacity of start relay GENS START is 7A 28VDC passive contact Controller has strong ability of anti electromagnetic interference can be used under complex electromagnetic interference environment Modular configuration design flame resisting ABS plastic
9. age lack of phase including lack of neutral line Switch is not activated In Auto mode lor Il Set the controller as Manual Mode and see if it can normal indicator switch illuminates but cannot Check voltage normal delay shorten the delay time switch Check the connection between ATS and controller Only when l voltage is abnormal controller will send failed to start Start signal Check start delay shorten the delay time HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 13 of 13
10. isabled and closing status is judged by closing opening action and closing input is inactive After setting the parameters press 1 and 11 closing keys simultaneously all panel indicators will illuminate and then release the keys the setting is completed 6 AC OPTION According to practice application use can define the AC options Phase A must Phase B C cannot lack phase Phase B C can lack one phase have voltage have no voltage HAT270A ATS Control Module ISSUE 2011 05 20 Version1 1 Page 8 of 13 HAT270A ATS Control Module 7 PROGRAMMED PARAMETER AND RANGE voltage normal oet panel Set via panel 0 60 delay potentiometer potentiometer only 11 voltage normal set panel Set via panel 0 60 delay potentiometer potentiometer only Genset start delay 0 60 5 i en Pane et d potentiometer potentiometer only l voltage 0 60 s Set panel abnormal delay potentiometer only s Os 3 LT lt ull voltage 0 60 abnormal delay potentiometer only Genset stop delay 0 90 9 Set a panel potentiometer only 7 Voltage upper limit 50 300 V 264V Set via PC only Voltage lower limit 50 300 V 172V Set via PC only 1 priority Set via panel Power priority 11 priority 1t Priority potentiometer or PC no priority See AC AC option option for details Closing Status oet via panel Enable detection potentiometer only 8 TERMINALS
11. shell inserted type HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 4 of 13 HAT270A ATS Control Module terminals connection with compact structure and easy installation 3 SPECIFICATION Power supply input AC power supply AC230V 20 50 Hz 60Hz from A phase and N phase of l and 11 Measured voltage rated 380V 50 Hz 60Hz 3 phase 4 wire and other measured voltage class please consult before ordering Range of abnormal power Over Voltage threshold 264V only be set via PC Under Voltage threshold 172V only be set via PC Action time Closing time 5 seconds During this period if detected close signal is enabled immediately disconnect Opening time 3 seconds During this period if detected close signal is disabled immediately disconnect Voltage normal delay 0 60 seconds adjusted via panel potentiometer Voltage abnormal delay 0260 seconds default 5 seconds adjusted via panel potentiometer Genset start delay when 1 abnormal is confirmed delay begins 0 60 seconds adjusted via panel potentiometer Genset stop delay when l normal is confirmed delay begins 0 60 seconds adjusted via panel potentiometer 1 II closing monitoring can be programmed via panel keys Default detect 1 11 closing status and the controller must access the closing status signal Power consumption When module is in rated voltage power consumption of voltage circuit is not more than 2 En
12. vironment conditions Temperature 30 70 C Humidity 20 95 Weight Net weight 0 47Kg HAT270A ATS Control Module ISSUE 2011 05 20 Version1 1 Page 5 of 13 HAT270A ATS Control Module 4 PANEL DESCRIPTION power indication 1 power indication 11 close indication 11 close indication power normal delay potentiometer Manual indication power normal delay l power Manual close potentiometer power Manual close power open Automatic Manual switch 5 PANEL OPERATION AND CONNECTIONS Automatic indication 5 1 Delay Adjustment 1 normal delay potentiometer judgment time 0 60 seconds 11 normal delay potentiometer judgment time 0 60 seconds 5 2 Control Setting a Automatic Manual Operation When controller is running sressing can set the controller as Auto mode or Manual mode via automatic and manual status indicator In Manual mode press load will be transferred to power supply key load will be transferred 11 power supply b Voltage Abnormal Delay Start Stop Delay 1 Il Power Priority And Closing Status Detection When controller is running and key simultaneously and hold l power indicator automatic status indicator and l power indicator are flashing which means HAT270A ATS Control Module ISSUE 2011 05 20 Versionl 1 Page 6 of 13 HAT270A ATS Control Module the controller can be set The setting
Download Pdf Manuals
Related Search
Related Contents
HOME AUDIO SYSTEM Voice Center™ Conference Phone User's Manual SMS Desk 2.01.0000 - User Guide - Issue 1.00 décision d`extension d`usages pour une matière fertilisante Invacare® I AT-POE4520 取扱説明書 User Manual SERVICE MANUAL Washing Manual de usuario CMU 100 - WORK PRO Audio Copyright © All rights reserved.