Home
CPC 100 Accessories
Contents
1. electronic protection relay with integrator OMICRON CT Ratio Rogowski Measures the ratio for CTs with Rogowski coil principle induced voltage is proportional to the conductor current differentiated with respect to time After entering primary current secondary voltage test current nominal frequency and pressing the Start button the test card e measures the amplitude of the injected current e measures the Rogowski coil s output voltage and phase angle e calculates the actual ratio e calculates the deviation from the nominal ratio Duration of the test 5 s including automatic reporting Output up to 800 A 2000 A with Current Booster CP CB2 Input up to 3 V AC built in CTRatiov CTRogowski ima z CT Ratio Low Power 181 2 I prim 20008 V sec 225 m CT gn RA aame Measures the ratio for CTs with low power ltest 2000A f 50 00 Hz Auta sid NORRA vies 5 principle output voltage is proportional to primary C Use est booster current prim fiss 99A After entering primary current secondary voltage and the test current and pressing the Start button the test card Veec 2253amv 0 00 od Manual input Ratio 200 0 22 53 A m 0 138 Polarity foK e measures the amplitude of the injected current e measures the low power output voltage and phase angle e calculates the actual ra
2. Technical Data Power Supply 8 12 V DC external 100 240 V 50 60 Hz Li lon battery 11 2 V 4 8 Ah Connectors 1 x fiber optical network 2 x BNC Indicators 2 x LED Temperature 0 C 55 C operating 10 C 70 C storage Humidity 5 100 non condensing Inp Frequency Range V input 0 Hz 4 3 kHz PD input 0 Hz 20 MHz Inp Impedance V input 1 MQ in parallel 1 uF PD input 50 Q Input Voltage V input 60 V rms max PD input 10 V rms max Dynamic Range V input 102 dB PD input 132 dB overall 70 dB per input range selection Measurement Uncertainty PD level 2 of calibrated PD value voltage 0 05 of calibrated voltage frequency 1 ppm Ordering Information VE004110 Single Channel PD measuring system VE004130 Three Channel PD measuring system VE004120 Hardware Gating system VESM4101 Optional software module ADVANCED VESM4102 Optional software module CABLE VESM4103 Optional software module REPORT Various charge calibrators and signal aquisition accessories available upon request For detailed information about the MPD 600 please ask for our respective product brochure or the product video series available on our homepage TanDetia Measuring System Mi 600 The mtronix MI 600 universal current measuring system is a high precision modular acquisition and analysis system for gauging current and key characteristics of high voltage equip ment includi
3. lt 2 kg 4 4 Ibs without measuring cables 21 kg 46 3 Ibs 26x5x26 5cm 10 25x2 x 10 5 inch 42x21x55 cm 16 5x8 3x21 5 inch DC 10 Vto24V 10W Highest possible repeatability of the test results due to screw type connection clamps which provide reliable electrical contact to the transformer and an innovative double braid solution which forms a shield around the bushing PC Software for e operation of the FRAnalyzer e diagnosis of the measuring results e database handling e reporting PC requirements minimum Interface USB 1 1 PC operating system Windows XP or Windows Vista Processor Pentium 1 GHz or higher Memory 1 GB RAM or higher Drive CD ROM Ordering Information VE000660 FRAnalyzer complete set transport case included VEHZ0673 Clamp set for short bushings For detailed information about the FRAnalyzer please ask for our respective product brochure or the product video available on our homepage Dielectric Response Analyzer DIRANA DIRANA determines the dissipation factor of nearly any kind of insulation including transformers bushings cables electrical machines in an extremely short time Using an advanced analysis software it determines the water content and oil conductivity in oil paper insulations Applications e Measurement of dissipation factor capacitance permittivity resistance and polarization current of HV insulations e Analysis of water content in oil paper insulation
4. 1 0876 3 TH Measurement of the complex impedances of a transformer CPC 100 Applications CURRENT TRANSFORMER CT CT Ratio Burden and Excitation CTRatia prim 200 0 4 ere 50004 ltest 200 04 F 50 00 Hz Auto CI Use est booster C Curent clamp sec prim E sec Boza o0 D Manual input Raio Bosom oee Polarity fox Measure burden W sec fray a415 od Manual input Burden 8 6492 VA Cos p fosza Assessed n a zec 5 000 A ltest 5 000 A f i 5 000 A Veeco zav 2015 E Manual input Burden 8 6682 VA COs i 0 565 PE Save As Template im 101m 100m knee fi BF 4 m Y kree fe B a2 iy Assessed n a P1 Piya vec a Vere CT a eee P1 Burden P1 Burden CT P2 A 1S1 2S1 a Burden Note for input current measuring the direct current input or the current probe can be used CT Ratio Burden Tests ratio polarity and burden with direct injection to CT primary current input and measuring of secondary output After entering primary secondary and test current and pressing the Start button the test card measures e Secondary current with magnitude and angle CT angle error e Ratio with error in percent e Polarity on the CT termi
5. C 19 3 x 1 5 mm 2 5 m with open ends VEHK0621 TestBase database system for test object administration available in the packages listed below Standard CPC package single user version Upgrade to Enhanced CPC Package single user version Server License TestBase Enterprise Edition refer to page 25 Client License TestBase CPC Enhanced Package Accessories CP amplifier test card for using the CPC 100 like an amplifier Ground resistance accessory set 4 electrodes 50 m cable reel red 100 m cable reel black CP CB2 current booster up to 2000 A includes connection cable to CPC VEHK0611 ground cable w clamp VEHK0615 high current cable set w plugs amp clamps VEHK0610 including transport case with wheels VEHPOO7 1 CP TD1 TanDelta Power Factor upgrade includes CP TD1 12 kV hardware w ref capacitor TanDelta test card TD1 Accessories cable drums w HV amp Measure cables 20 m Trolley elFC card if needed VEHZ0646 CP TC12 12 kV test cell for measuring permittivity and TanDelta Power Factor of insulation liquids like transformer oil CP CR500 compensating reactor that includes two inductors rated 40 H each 2 A compensation w inductors paralleled 500 nF CP CU1 amp CP GB1 includes CP CU1 coupling unit w accessories for line impedance k factor mutual coupling ground impedance step and touch voltage and signal cable coupling measurements Includes CP GB1 grounding box VEHZ0672 Step and touch vol
6. OMICRON Ny D M N ey d ey a Company Profile CUSTOMER AND COMPANY PROFILE About our customers AS fo Subjects covered in other catalogs Typical customers of our CP product line which represents our products for primary testing are engineers and technicians working mainly in commissioning maintenance testing and test fields of e Power transformers e Current transformers e Voltage transformers e Power cables e Circuit breakers e Rotating machines and other electrical power system equipment in utilities and industry Our test equipment is also used for automated measuring of resistances contact resistances winding resistances grounding resistances cable impedances power factor dissipation factor and capacitance but also for single phase testing of primary and secondary protective relays I gt V gt V lt or frequency relays OMICRON electronics is an international company providing Innovative solutions for primary and secondary testing Combining innovation leading edge technology and creative software solutions OMICRON s sales have earned world leader status for OMICRON within this niche market With sales in more than 100 countries offices in Europe the United States and Asia and a worldwide network of distributors and representatives OMICRON has truly established its reputation as a supplier of the highest quality The automated testing and docume
7. 10 Frequency range 5 000 0 0001 Hz Ranges for the combination PDC FDS Frequency 0 1 mHz 5 kHz Switch frequency to time domain 0 1 Hz Capacitance 10 pF 10 uF Weight Instrument lt 2 3 kg 5 lb Complete case 16 kg 34 Ib Ordering Information VE000670 Complete DIRANA set transport case and accessories included VEHZ0607 DIRANA accessories VEHPOO72 Transport case for DIRANA For detailed information about DIRANA please ask for our respective product brochure PD Analysis System MPD 600 The mtronix MPD 600 Partial Discharge Analysis System Is a high end high precision modular acquisition and analysis toolkit for detecting recording and analyzing partial discharge events in both laboratory and on site applications of transformers rotating machines and cable systems including HV and EHV cables Features and Benefits The fully digital system guarantees e true parallel and synchronous multi channel PD measurements of large systems due to easy expandability to up to 960 channels no noise entry from mains supply due to battery operation significantly reduced basic noise level due to optical fiber connections highest measurement accuracy and sample rate a significant improvement in safety and accuracy due to a complete electrical insulation between individual acquisition units and the control PC via a fiber optical network Active noise suppression means e perfect adaptation of the me
8. CPC 100 with CP TD1 U1 Line amp Ground Impedance Testing g 19 CP CU1 Technical Data CP CU1 and CP GB1 MOTI CC ESOC apor r 20 Oil Test Cell Compensating Reactor 21 Polarity Checker Current Booster 23 Package Options Test amp Maintenance Management Database eee 24 TestBase Test and Maintenance Management Current Transformer Testing ANAIYSIS oo ceceeeee 26 CT Analyzer Technical Data Sweep Frequency Response ANAlYZEN iii 27 FRAnalyzer Technical Data Pileci Response anast EEEIEE EEEE o 28 DIRANA Technical Data Partial Discharge Analysis system EEE E SIE 29 MPD 600 Technical Data Universal Current Measuring SYSTEM 30 MI 600 Technical Data 31 Contact Addresses ISO 9001 certified CPC 100 OVERVIEW Multifunctional Primary Test System for Substation Commissioning and Maintenance This world wide unique system allows for automated testing of power transformers CTs VTs resistance testing and more Providing up to 800 A or 2000 A with current booster and 2000 V with a frequency range of 15 400 Hz it also comes complete with an integrated PC Its software routines test a wide range of substation equipment and automatically create customizable reports The compact design 29 kg 64 Ibs and the innovative software save testing time and minimize transportation costs Analog voltages and currents can be measured with very high precision Its Q meters offer ranges from uQ to
9. Single phase nominal 100 VAC 240 V AC 16 A 5A 0 40 0 10 0 20 0 20 0 05 0 10 Single phase permissible 85 V AC 264 V AC L N or L L Frequency nominal 50 60 Hz 20 mA 0 10 0 10 0 20 0 05 0 05 0 10 Power consumption lt 3500 VA lt 7000 VA for short time lt 10 sec Connection ECS 20 C20 Guaranteed values valid over one year within 23 C 5 C 73 F 10 F in the frequency range of 45 65 Hz or DC Accuracy values indicate that the error is smaller than Value read Reading Environmental conditions error Full Scale of the range Full Scale Error Operating temperature 10 55 C 414 131 F With mains voltage 230 V with 2 x 6 m high current cable at 23 C 5 C 73 F 10 F Storage temperature 20 70 C 4 158 F ambient temperature B i i i Humidity range Rel humidity 5 95 non condensing 2 Signals below 50 Hz or above 60 Hz with reduced values possible Shock IEC68 2 27 operating 15 g 11 ms half sine 3 Output can be synchronized with mains a Vibration IEC68 2 6 operating 10 150 Hz 2g 4 The input output is protected with surge arrestors between the pins and against protective S earth In case of energies above a few hundred Joule the lightning arrestors apply a permanent EMC Emission Europe EN 61000 6 4 EN 61000 3 2 short circuit to the input output International IEC 61000 6 4 IEC 61000 3 2 gt Signals below 50 Hz or above 20
10. North and South America OMICRON electronics Corp USA 12 Greenway Plaza Suite 1510 Houston TX 77046 USA Phone 1 713 830 4660 1 800 OMICRON Fax 1 713 830 4661 info omicronusa com www omicronusa com Asia Pacific OMICRON electronics Asia Ltd Suite 2006 20 F Tower 2 The Gateway Harbour City Kowloon Hong Kong S A R Phone 852 2634 0377 Fax 852 2634 0390 info asia omicron at www omicron at Prs am OMICRON L090 Subject to change without notice Last update September 2008 a e r 1
11. diameter x height Weight approx 6 kg 13 2 Ibs Article No VEHZ0601 Compensating Reactor CP CR500 The CP CR500 allows Power Factor Tangent Delta measurements of large motors and generators In combination with the multifunctional Primary Test Set CPC 100 and the Tangent Delta Power Factor unit CP TD1 one CP CR500 compensates capacities of up to 500 nF To compensate even larger capacities two devices can be connected in parallel This allows compensation of up to 1000 nF Benefits e Portable high power solution due to size and weight e Flexible by using different numbers of units and or by changing the test frequency 35 85 Hz Technical Data with one CP CR500 Maximum Test Voltage 12 kV rms gt 50 Hz Inductors 2x 40H Current Compensation 2x1A Capacity Compensation 2 x 250 nF 50 Hz 2 x 500 nF 35 Hz Dimensions 468 x 394 x 233 mm 18 6 x 15 5 x 9 2 Weight 33 kg 73 Ibs 4 g For detailed information on these products please see our Article No VEHZ0602 single unit product information sheet 12 kV Oil Test Cell CP TC 12 and VEHZ0603 set of two units Compensating Reactor CP CR 500 CPC 100 Accessories POLARITY CHECKER CURRENT BOOSTER Polarity Checker Replacement for Battery Checking Method Checks a series of test points for correct wiring Just inject a the special continuous test signal at one point with the CPC 100 and check the polarity at all t
12. edition can be individually tailored according to the customer s needs and provides the following additional features Offline Mode with Data Replication TestBase supports automated synchronization when connected to the server The user has Comet Serve access to all features when working on site without a server connection Opera a DETI Ey al i CENENE lis Software Integration TestBase can be integrated into the existing IT infrastructure including migrating existing we i E To See asset data from other applications e g existing local databases Establishing data exchanges tg TER hontel between TestBase and ERP enterprise resource planning system software avoids double input Mi 5 5 and mismatch of data ik 5 The TestBase Enterprise edition works with a client server architecture while one server and Desktop PC Hotebook A Wotebok E several clients communicate in a network environment e g LAN The central TestBase database is installed on the Microsoft SQL server and the TestBase applications run on the clients Ordering Information OS700015 Server License TestBase Enterprise Edition OS700018 Client License TestBase CPC Standard Package OS700019 Client License TestBase CPC Enhanced Package OS700024 Client License TestBase User Defined Package For detailed information about TestBase please ask for our respective product brochure Current Transformer Testing CT Analyzer OMICRON s CT Analyzer delivers
13. pressing Save Results Output up to 6 A DC or 100 A DC 6 5 V Input up to 10 V DC Voltage Withstand Tests the voltage withstand capability of the insulation between primary and secondary winding or ground and secondary winding After entering the test voltage and the duration and pressing the Start button the test card e determines the leakage current flowing through the insulation The current threshold for maximum leakage current can be entered The CPC 100 will automatically switch off if the maximum leakage current is exceeded Duration of the test can be set by the user the test report will be created after the test automatically Output up to 2 kV AC CT Ratio V Tests ratio and polarity with direct injection of the voltage to the CT secondary input common method for bushing CTs After entering primary and secondary current and the test voltage and pressing the Start button the test card e measures the actual ratio e calculates the deviation of amplitude and phase angle of the voltage of the CT primary side Duration of the test 3s including automatic reporting Output up to 130 V Input up to 3 V and 300 V AC CT Ratio Rogowski CT Ratio Low Power Ipin 24004 Vesec 150 0 rm Lan f nom 50 00 Hz ltest 2400A 50 00 Hz Auto S L Use est booster prim 23387A V sec aaam O Man inp sec jassa oe Rai paoms mez Saves Polarity o Assessed n a
14. voltage 5000 VA cos lt 0 4 for 8s 115 V ac mains voltage Accuracy Measured value Typical accuracy Current range 0 05 0 2 Q 1 0 0 5 100 A O24 a O 0S aa 03 Fo 100 A 2 see G2 0 3 50 A De 2 0 3 20 A 25 300 Q 0 3 1 0 10A For detailed information about the CP CU1 please ask for our respective product brochure CPC 100 Accessories 12 KV OIL TEST CELL COMPENSATING REACTOR 12 kV Oil Test Cell CP TC12 The CP TC12 is used in conjunction with the CPC100 and the CP TD1 to measure the Permittivity and Tangent Delta Power Factor of insulation liquids e g transformer oil The three electrode design with guard allows precise measurement especially of small losses The circular electrodes are constructed from rigid stainless steel and require a sample of 1 2 to 2 liters 41 to 68 fl oz Electrical connection to the Test Cell is made using the standard cables provided with the CP TD1 Technical Data Cell Type Three terminal guarded Cell Gap Spacing 11 mm 2 31 nominal Sample Volume 1 2 liters min to 2 liters max 41 to 68 fl oz Cell Capacitance 65 pF nominal in air Maximum Test Voltage 12 kV rms Voltage Operating Range 2 5 to 12 kV for a stress of 200 to 1100 V mm 7 87 to 43 31 V inch Connectors 6 mm 0 24 sockets for high voltage cable 4 mm 0 15 sockets for measuring cables Dimensions 22 x25 cm 8 7 x 10 2
15. 0 Hz with reduced values possible a FCC Subpart B of Part 15 Class A 98 of all units have an accuracy better than specified as Typical EMC Immunity Europe EN CIONO A EN O1U00 see 20H e i International IEC 61000 6 2 IEC 61000 4 2 3 4 8 Input is galvanically separated from all other inputs Safety Europe EN 61010 1 V1 and V2 are galvanically coupled but separated from all other inputs International IEC 61010 1 There are power restrictions for mains voltages below 190 V AC Produced and tested in an EN ISO 9001 certified company 0 Fuse protected Weight 29 kg 64 lbs robust case with cover P Dimensions 468 x 394 x 233 mm 18 6 x 15 5 x 9 2 Error of reading lt than value W x H x D with cover without handles CPC 100 Applications APPLICATIONS The software described in the Software section runs in the embedded processor within the CPC 100 and can be operated with front panel control No additional PC is required Quick Manual Control Quick Testing almost any function using direct manual control of the current and voltage outputs and measurements This function allows any manipulation of the selected output range of the CPC 100 All output terminals available on the CPC 100 can be selected and controlled Measuring two quantities in two columns such as AC or DC voltages in amplitude and phase angle AC or DC currents in amplitude and angle or the frequency of any selected output is easily done by
16. 0 mm 7 3 x 6 5 x 8 7 without handle 16 0 kg 35 3 Ibs Dimensions Weight With mains voltage 230 V at 23 C 5 C 73 F 10 F ambient temperature Signals below 50 Hz or above 60 Hz with reduced values possible 3 Outputs in series 4 Outputs in parallel Connection cable to CPC 100 High current cable set for CP CB2 4x 1 5 m with 95 mm with plugs and clamps for CP CB2 1 x 0 6 m with 95 mm for serialization of outputs z VEHK0610 20 m 3x2 5 mm VEHKO611 Includes in option e CP CB2 Current Booster e Connection cable to CPC 100 e High current cable set for CP CB2 e Grounding cable same as for CPC 100 shown on page 22 e Transport case similar model as for CPC 100 shown on page 22 but with different inner shell l The Current Booster CP CB2 connected to CPC 100 CPC 100 Accessories Cables clamps and plugs supplied with CPC 100 Standard Package High current cable set 800 A 70 mm2 2x6m_ VEHKO0612 2x9m _ VEHKO617 KaLe P Measurement cable set 2 5 mm2 6x6m_ VEHK0614 6 xX 10 mVEHK0619 standard alternative standard alternative Crocodile clamps for connection of banana plugs 4 x 4 mmVEHZ0620 Transport cases High voltage cable set 2000 V screened 0 5 mm2 standard 2x6m_ VEHK0613 alternative 2 x 10mVEHK0618 Low voltage adapter VEHKO0O623 for V2 AC low voltage level input 0 3 V low voltage plug VEHS0610 Current Clamp
17. 670 VEHK0612 VEHK0617 VEHK0613 VEHK0618 VEHK0614 VEHK0619 VEHZ0610 VEHZ0620 VEHK0615 VEHK0622 VEHK0623 VEHZ0666 VESDO601 VESDO600 VEHZ0665 VEHZ0644 OS700002 OS700004 OS700015 OS700019 VESM0660 VEHZ0660 VEHZ0630 VE000641 VEHZ0601 VEHZ0602 VEHZ0671 VEHZ0625 VEHZ0622 Customized packages with individual combinations are available on request Requires CP Sequencer Test Card PACKAGE OPTIONS 1 Packages Description CPC 100 Multifunctional Primary Test System including hardware and built in software for testing of the CT s VT s power transformers resistance etc The basic system includes e CPC 100 multifunctional test set hardware 110 230 V 50 60 Hz with AC 800 A AC 2000 V DC 400 A e QUICK test card manual control of the test set e Transport case with wheels for CPC 100 VEHPO061 e Carry bag for CPC 100 accessories VEHPO069 CP CT test cards ratio V ratio excitation curve burden winding resistance voltage withstand test 2 kV Rogowski coils Low power CT s CP VT test cards ratio burden voltage withstand test 2 kV electronic voltage transformers CP transformer test cards winding resistance tap changer check ratio voltage withstand test 2 kV CP resistance test cards contact resistance uQ mQ winding resistance uQ kQ CP ramping test card programmable ramping generator and determination of thresholds CP sequencer test card sequencer test card for testi
18. Active ac and dc current probe with voltage output Connection clamps for high voltage for connection with banana plugs 4 mm VEHZ0610 Power cord with open ends VII connector VEHK0621 VEHK0616 standard alternative A and frequencies up to 1 kHz 6 2 measuring ranges 10 Aand 80A Frequency range dc to 10 kHz Accuracy error lt 2 for currents up to 40 Phase error lt 0 5 at 50 60 Hz Length 230 mm 9 1 Article No VEHZ4000 Grounding cable GR YE 1 x 6 m 6 mm with connection clamp VEHKO615 BS connector VEHK0624 alternative ZA connector VEHK0620 alternative USB memory stick I 512 MB Article No VEHZ0666 symbol picture OMICRON offers sturdy transport cases with hard form interiors Recommended for heavy transport stress or for shipping Case model For CPC 100 Capacity Dimensions LxHxD CPC 100 manual power cord 700 x 450 x 500 mm 27 6 x 17 7 x 19 7 10 8 kg 23 8 lb Article No VEHPO061 Carry bag for CPC 100 auxiliaries For Current Booster CP CB2 CP CB2 connection cable Cable sets current clamps 400 x 250 x 450 mm 15 7 x 9 8 x 17 7 9 2 kg 20 3 b VEHPO069 high current cable set 700 x 450 x 360 mm 27 7 611 7 x 14 2 9 0 kg 19 8 Ib VEHPOO7 1 CPC 100 Package Options CPC 100 Package Overview Item No VESM0610 VESM0615 VESM0620 VESM0625 VESM0630 VESM0635 VESM0640 VESM0645 VESMO0665 VESM0
19. Check AiGround LEJ add Itet 1 0008 fee f 22 00 Hz RAMS 875 0 mA WRMS A745 m 7607 Delete Card Rename Card Clear Results Rit 228 3 mit ii 21 33 mil Save s Template Assessed n a Resistance Q measurement Ground Resistance auxiliary auxiliary electrode electrode V approx No 10xa OO T D m __ substation ground Resistance Q Measurement Measures test objects with very low resistance such as contacts of circuit breakers and buswire connectors After connecting the test object 4 wires entering the test current and pressing the Start button the test card measures e the resistance of the test object The test current can be selected from 0 400 A Duration of the test 5 s including automatic reporting Output up to 400 A DC Input up to 10 V DC Ground Resistance Measures ground resistance or soil resistivity The ground resistance of substations can be measured with two auxiliary electrodes which are put into the ground To avoid influences from the mains current and its harmonics this measurement should preferably be carried out with 128 Hz The high output power of the CPC 100 ensures a high ratio of the signal level to the noise level Thanks to the signal processor technology the measuring procedure is very selective and disturbances by ground currents are reduced to a minimum For large gr
20. a unique capability for the fast comprehensive testing and calibration of current transformers for protection and metering engineers as well as CT and switchgear manufacturers The equipment provides automatic testing and calibration for all types of low leakage flux current transformers both on site in the power system as well in the controlled environment of CT and switchgear manufacturers A wide range of measurement functions can be provided e Burden measurement e CT Winding resistance measurement e CT Excitation characteristic recording e CT transient behavior measurement IEC 60044 6 e CT ratio measurement with consideration of nominal and connected burden e CT phase and polarity measurement e Determination of accuracy limiting factor ALF instrument security factor FS secondary time constant Ts remanence factor Kr transient dimensioning factor Ktd knee point voltage current class saturated and non saturated inductance e Assessment according to defined standards IEC 60044 1 IEC 60044 6 IEEE C57 13 1993 upique CT Analyzer Features amp Benefits e Extremely small and lightweight lt 8 kg 17 Ib particularly beneficial for on site testing e Reduced commissioning time due to fully automatic testing according to IEC 60044 1 IEC 60044 6 and IEEE C57 13 Results within seconds First portable device that can test CTs built according to IEC 60044 6 with defined transient behavior Calibratio
21. asurement settings to the on site conditions with a freely selectable center frequency outstanding SNR signal to noise ratio due to variable bandwidth filters easy suppression of phase fixed noise signals by an unlimited number of gates optimum ability to separate internal and external PD using an external gating unit dynamic noise gating which enables gating out of unwanted cyclical non phase relational pulses easy to use 3PARD Three Phase Amplitude Relation Diagram and 3CFRD 3 Center Frequency Relation Diagram functionality which separate noise from inner PD Innovative user interface provides e different user interface modi according to user demands e multiple visualization possibilities of PD events to match the user requirements e full overview of all relevant data like PD level test voltage system status etc according to IEC 60270 2000 e intuitive oscilloscope functionality and view e support of RIV and DC measurements Real time amp data post processing replay of the measurement enables comprehensive assessment of the PD measurement back in the office easy to use 3PARD functionality allows the separation of several PD faults Microsoft Excel based report generator gives the possibility to create customized reports Applications Detection recording and analysis of partial discharges in both laboratory and on site applications of transformers rotating machines and cable systems including HV and EHV cables
22. d Interval oos Dev m Temperature compensation tor Cu T meas 25 0 C Clear Results T ref 70 0 SEN E084 miki YTElectronics Ytest f2000 0 F Switch off on AC gt Auto vac eok AC 360 0 p 50 00 Hz foo O04 max 560 0 p CTBurden CTExcitation Add 200 08 lsec 50004 Gi V test S0 00H2 F Auto Delete Card Wo sec 50 010 al V prim 1 2536 015 od Manual input Ratio 200 0 5 0134 azer Clear Results Polarity fox SU OU F Save As Choose test card Winding Resistance Voltage Withstand Test and CT Ratio V Time 20 000 s f P1 Burden Burden Burden Winding Resistance Measures CT winding resistance After entering the test current and pressing the Start button the test card e displays the deviation of the measurement over time during the period of charging the winding e automatically performs a discharging of the winding after saving the measurement e measures the DC voltage e measures the resistance e optionally compensates the temperature behavior of copper where the applied temperature compensation calculates the resistance for working temperature Duration of the test depending on the charging time After the charging period the user creates the report by
23. e CPC 100 Current Output Ranges Current range Compliance voltage O 10 Arms 500 V rms 0 20 Arms 250 V rms O 50 Arms 100 V rms 0 100 Arms 50 V rms Measuring Transformers VT 600 V 30 V class 0 1 CT 100 A 2 5A class 0 1 Mechanical Data Protection IP 20 Dimensions w x h x d 450 x 220 x 220 mm 17 7 x 8 7 x 8 7 inch Weight 28 5 kg 63 Ib Environmental Conditions Operating temperature 10 55 C 14 131 F Transport amp storage Temperature 20 70 C 4 158 F Relative humidity 5 95 non condensing Safety EN 61010 1 Prepared for IEEE 510 EN 50191 VDE 104 EN 50110 1 VDE 105 Part 100 LAPG 1710 6 NASA 1 At an ambient temperature of 23 C 5 C 73 F 10 F Multifunctional primary test system CPC 100 in combination with the coupling unit CP CU7 and the grounding box CP GB1 CP CU7 requires the CPC 100 to have the CP Sequencer card to work CPC 100 includes the transport case Technical Data CP GB1 Electrical Data Nominal ac spark over voltage Short circuit proof Mechanical Data Dimensions x h Weight Accessories lt 1000 V rms up to 30 kA for 100 ms 200 x 190 mm 7 9 x 7 5 inch 6 8 kg 13 2 Ib including grounding cable Special accessories for step touch and ground impedance on request Overall System with CPC 100 Output Power 5000 VA cos lt 1 0 for 8s 230 V ac mains
24. e Cp e Dissipation factor tan 6 tangent delta e Power factor cos e Power active reactive apparent e Impedance absolute value phase inductivity resistance Q Technical Data CP TD1 with CPC 100 The CP TD1 is connected via interfaces to the CPC 100 and thus does CP TD1 with transport trolley not need further control elements High voltage output Dissipation factor DF tan y Tmax at f Hz Range Resolution Accuracy Conditions 300 mA gt 2 min 0 0 i 15 70 Hz 0 12 kV AC 15 400 EE aa e g 100 mA gt 60 min capacitive 0 005 lt 8 mA 0 100 5 diaits error lt 0 5 reading i 0 10000 J 0 02 Voltage current measurement Range Resolution Accuracy 12000 V AC 1V error lt 0 3 reading 1V Power factor cos gt AAC 5 digits error lt 0 5 reading Range Resolution Accuracy Conditions s 8 mA AC error lt 0 3 reading 100 nA 0 10 a aii error lt 0 1 reading 15 70 Hz capacitive g 0 005 lt 8 mA Capacitance Cp equivalent parallel circuit o 0 100 5 digits error lt 0 5 e teading i Range Resolution Accuracy Conditions 0 02 p _ a are ali lt 8mA Representation of the following values is also possible 1 pF 3 uF 6 digits AR e Power active reactive apparent error lt 0 2 reading gt 8 mA e Impedance absolute value phase i
25. eatures an 11 level input gain control that is adjustable via the control software Its high sensitive input reliably resolves currents as low as 20 WA An on board shunt automatically deployed under software control enables input currents of up to 100 mA to be directly measured without the need for an external shunt Ordering Information VE004400 MI 600 2 Dual Channel TanDelta Measurement System Specifications Acquisition Unit Dimensions wxdxh 110x190x44 mm Power Supply 9 12 V DC External 100 240 V 50 60 Hz battery pack incl Li lon battery 11 2 V 4 8 Ah Indicators 2 x LED Stand by Power Optical Fiber Data Integrity Fiber Optics 2 x ST Input Conn 1x INC Temp 0 C 45 C Operating 10 C 60 C Storage Humidity 5 80 Non condensing Input Freq 5 Hz 50 kHz Input Imped 50 Ohms Input Current 20 uA 100 mA rms direct Extern Shunts 4 A 15 A 28 A Measurement Accuracy Dissipation factor power factor Test Object Capacitance 2E 2 of Display Value 0 25 of Display Value MI 600 Requirements Operating System Windows 2000 Professional XP or VISTA Processor Pentium 4 2 5 GHz or M 1 5 GHz Core or Core 2 AMD Athlon 64 or Turion 64 processor Memory 512MB RAM 1 GB RAM recommended Interface USB 2 0 compatible 2 x measurement unit MI 600 controller unit MCU 502 with USB cable precision shunt 4 A basic SW package user ma
26. econdary voltage and test voltage and pressing the Start button the test card e measures amplitude and phase of the voltage on the transformer s secondary side e calculates the actual ratio the deviation and the polarity Duration of the test 5 s including automatic reporting Output up to 2 kV Input up to 300 V AC VT Burden Measures the connected secondary burden of the VT After entering the nominal secondary voltage and the test voltage and pressing the Start button the test card measures e the connected secondary burden with voltage injection on the VT s secondary side e the connected secondary burden in VA and the power factor cos including the secondary current and the angle between voltage and current Duration of the test 5s including automatic reporting Output up to 130 V AC Input up to 10 A AC and 300 V AC Electronic Voltage Transformer Measures ratio and polarity of non conventional electronic VTs After entering the primary voltage the secondary voltage and the test voltage and pressing the Start button the test card e measures the low level secondary voltage e calculates the actual ratio the deviation and the polarity Duration of the test 5s including automatic reporting Output up to 2 kV Input up to 3 V or 300 V AC Voltage Withstand Test The voltage withstand test is described in the CT section page 10 Polarity Checker The Polarity Checker option can be found in the Access
27. el File Loader template Post processing will be done automatically and you get your calculated results and your report for example for e Transformer Tap Changer e Transformer Ratio and Dissipation Power Factor e Accuracy Limiting Factor for CT s e Line Impedance CPC Editor Reduce on site testing time to a minimum by preparing tests offline on a standard PC The CPC Editor allows setting up single test cards or entire tests with several test cards Saved tests can be used as templates or procedures CPC 100 Accessories CP TD1 TANGENT DELTA amp POWER FACTOR The CP TD1 capacitance and tangent delta power factor measuring instrument is an accessory unit to the CPC 100 completing its use for power transformer testing with the ultimate insulation diagnosis solution Controlled by the CPC 100 the CPC 100 CP TD1 combination provides fully automated testing and reporting capabilities for the comprehensive testing of transformer parameters within one portable system The application of innovative measurement techniques and the use of high precision components in the CP TD1 bring laboratory precision with a rugged design into the field of insulation condition testing The CP TD1 also offers new test methods such as testing with frequency sweeps A custom built trolley allows for practical handling on and off site along with easy and quick breakdown into portable components Quantities measured include e Capacitanc
28. erminals with CPOL as shown in fig 1 getting a clear indication whether the polarity is OK green LED or not red LED This procedure is much faster than the conventional method and can easily be performed by a single person Duration of the test depending on the number of test points 3 5 s per test point Polarity Checker Range aceon A Ampl 600 04 A Intermill Torn 1 000 s _ Toff 3 Location Assessment _ Pai OF The Polarity Checker in use Current Booster CP CB2 Tests applications requiring up to 2000 A The output current of the CPC 100 can be increased to up to 2000 A by an electronically controlled current booster The CP CB2 can be connected close to the busbar using short high current leads and to the CPC 100 with a long control cable Polarity check test card CPOL polarity checker Current Booster CP CB2 Current outputs Range Amplitude tmax Vmax Powermax f 0 1000 A 25s 4 90 V 4900 VA 15 400 Hz 1000 A AC 0 500 A 30 min 5 00 V 2500 VA 15 400 Hz 2000 A 0 2000 A 255 2 45 V 4900 VA 15 400 Hz Internal measurement of outputs Guaranteed accuracy Typical accuracy Output Amplitude Phase Amplitude Phase Reading Full Scale Full Scale Reading Full Scale Full Scale 2000 A AC 0 25 0 25 0 50 0 13 0 13 0 25 1000 A AC 0 25 0 25 0 50 0 13 0 13 0 25 186 x 166 x 22
29. g PE ra Ta iW aay rile 1 LTE mk Fy Thy ET sr i FLY LHA Lim i ta r R Automatically Generated Report LI Bm Te E e e e e ee om fifa eb 2 aj Be a be a a i i r a a wth a iz ee Tee Pv a So ee Pee es op i Le hr lt Fa a OL a e F m Lg don os eter mrp rea bri ami emie e E hm a omeri En a kaei KEL Mia iik EEEE S r m mar bm ii h Pan F E jr 2S Ge y e o a z br mna a eg B E We Ghee ES Pe ark re Ta i Ea Sl I 1 ii Oe bare a pi w a Re j l l my ia 77a Bd Pie P i ae DE hi o FEE sa Se jeri e LY Pl ee ff a re in Ee ees ee ee ee T zru AF mart m iau miam In a ea Fi i Lem iTi NE ima f MAT i BM ria s fm ral mee a s Peers ke tm oH Fizl F e D ni el ae ina haere aaa Pe E i aur Cres mo a i ee imira rai w i aha H im fom OUP el ae OMICRON Device Browser and CPC Explorer The OMICRON Device Browser which is embedded in the Microsoft Windows Explorer and the CPC Explorer are PC Software tools that are shipped together on the CPC 100 Explorer CD You have access to your stored data and tests on the CPC 100 which allows easy management and organization of test data like e direct reporting e direct editing of tests only with the OMICRON Device Browser e copy and paste data from and to the CPC 100 e easy upgrading of CPC 100 software e service and maintenance remote trouble shooting e direct connectio
30. g will increase decrease the value in ever smaller steps 18 Up down keys for navigation and entering values 19 Test start stop button CPC too Technical Data INTERFACE ELEMENTS CONTINUED Plug to connect external functions e external test start stop push button e external I O signal lights 2 Serial interface for devices like CP TD1 3 Connection of CPC 100 to a network or direct connection to a PC s network connector 4 Connection of a USB memory stick Sry jen 4004 DC m e a 800A AC 1 Grounding terminal 2 High AC Voltage Output 2 kV AC 1 A 5 A AC 3 Ext BOOSTER for the connection of the booster options 4 High DC current output 400 A DC 5 High AC current output 800 A AC 6 Mains power supply 1 phase 85 V 264 V AC 7 Overcurrent protection 8 POWER O I CPC 100 Technical Data Inputs TECHNICAL DATA Measuring inputs Guaranteed accuracy Typical accuracy Input Imped Range Amplitude Phase Amplitude Phase The output is either voltage or current and is automatically selected by the software or f Full Full Full Full ee Reading Reading manually by the user Current and voltage outputs are overload and short circuit proof and Scale Scale Scale Scale protected against over temperature 10AAC 0 10 0 10 0 20 0 05 0 05 0 10 O O o O O o Generato
31. ice browser the templates and test results can be transferred between TestBase and the CPC The test results are stored in TestBase and can be automatically visualized in the CPC Excel file loader Most 3 party file based systems are supported by TestBase by opening the application and saving the test document formats directly from TestBase e g doc files xls files 3 party formats Document Management With the integrated document management system the user gets easy access to the infor mation required during testing e g manuals test specifications safety instructions factory tests certificates individual notes Reminder Function The user can define actions for each individual object and is reminded by an alarm signal light if an action is due Reporting The following reports are included technical data activities on an object and test results TestBase TESTBASE ENHANCED amp ENTERPRISE Upgrade to Enhanced CPC Package single user version OS700004 Upgrade to the enhanced package provides the following additional features Management of Additional Assets within Power Utilities 3 i In addition to the standard package object models for batteries rectifiers and uninterruptible COO p power supplies are supported The user can model further equipment into the system With the m Ey ae Pr J a ne 3 ii i ra m pii x general link option object
32. ime The measurement table displays long dead time CB closing time 3 1910 s Ramping The functionality of the Ramping test card includes the automatic measurement of the pick up and drop off values of overcurrent relays Also CB contact resistances can be measured with ramp functions to avoid induced voltages in CT windings Up to five ramps can be defined with detailed results being available for each CPC 100 Applications POWER FACTOR amp IMPEDANCE MEASURING Insulation Diagnosis Tangent Delta Power Factor Test The condition of the insulation is an essential aspect for the operational reliability of electrical power transformers generators and other high voltage equipment CPC 100 CP TD1 provide laboratory precision for capacitance and dissipation power factor measurements in the field Quantities measured include e Capacitance Cp e Dissipation factor tan 6 tangent delta e Power factor cos e Power active reactive apparent e Impedance absolute value phase inductivity resistance Q Assessed 12 12 03 I5 0AM d Primary Measurements Line amp Ground Impedances k factors mutual coupling Accurate data of the primary lines feeders and grounding are critical for operational reliability of electrical power systems where modeling programs are used for design or when protective settings are applied 2 L1 E LIL2L3 E Insert euz E or O Repeat card CPC 100 CP CU1 coupling unit p
33. kQ to allow for a wide variety of applications Testing of unconventional equipment such as Rogowski Coils or current sensors completes the spectrum Additional applications can be added with the use of flexible accessories to include tangent delta power factor testing and primary measurements of power system equipment LIGHTWEIGHT 29 kg 64 Ibs eLess than one fourth the weight of equivalent conventional equipment e Lower transportation costs saves money e Easier handling reduces manpower needs eLow weight reduces injury potential ONE TEST UNIT FOR MULTIPLE USES e Replaces need for multiple test sets e g high current and voltage sources uQ meter e Saves time by eliminating need for multiple training e User friendly interface reduces training time to one day AUTOMATED TESTING AND REPORTING e Prepare test plans ahead of time in office saves time in field testing phase eSet up test once push button to start saves testing time e Results automatically saved saves time and reduces errors by eliminating manual recording of data e Automatic report generation saves time by eliminating manual report writing accelerates project completion e Print reports via external PC SAFETY FEATURES e Emergency shut off button e Safety key lock block unauthorized use e Overvoltage protection on all inputs and outputs PREPARED FOR THE FUTURE e Able to test unconventional equipment like Rogowski Coils or current sensors e Unit accessib
34. le in a network or with direct PC connection via standard internet protocols e Maximum flexibility for future enhancements by using DSPs for signal generation and switched mode amplifier technique Fr E CT Excitatior 1000 CURRENT TRANSFORMER CT automatic testing of Ratio burden and polarity Phase and magnitude error e Excitation curve Winding resistance e Secondary burden e Dielectric withstand voltage 2kV ac eCT circuit continuity VOLTAGE TRANSFORMER VT automatic testing of e Ratio and polarity e Phase and magnitude error e Secondary burden e Dielectric withstand voltage 2kV_ac eVT circuit continuity POWER TRANSFORMER e Ratio e Winding resistance eTap changer testing e Excitation current e Short circuit impedance measurement eLeakage reactance RESISTANCE TESTING e Contact resistance uQ eWinding resistance uQ kQ Ground resistance e Measuring of complex impedances winding impedances cable impedances etc PROTECTION RELAYS Single phase testing of primary and secondary relays I gt V gt V lt or frequency relays ADDITIONAL APPLICATIONS e TANGENT DELTA POWER FACTOR TEST Add the CP TD1 accessory for the most flexible insulation diagnosis system in the industry e LINE amp GROUND IMPEDANCES k FACTOR MUTUAL COUPLING Add the CP CU1 accessory for the safest most accurate system for measuring primary power system parame
35. n of measuring transformers A typical accuracy of 0 02 1 enables field calibration and verification of class 0 1 CTs for metering e Automated assessment according to the defined standards IEC 60044 1 IEC 60044 6 or IEEE C57 13 1993 also of specialized CTs such as PX TPS TPX TPY and TPZ e Allows testing of CTs for power frequencies from 16 7 to 400 Hz e Name plate guesser function allows automatic parameter search and analysis of CTs with unknown data European Patent EP1 653 238 B1 High level of safety all tests use low voltages 120 V European Patent EP 1 398 644 A1 e Precise measurement of ratio error and phase displacement up to x times the rated current and for all burden values without the need to connect burden hardware independent of the application e g bushings and GIS e Test of CTs with very high knee point voltages up to 30kV e Automatic demagnetization of the CT after the test CT Analyzer The unique analyzing solution for current transformers European Patent EP 1 398 644 B1 and EP 1 653 238 B1 Calibration A typical accuracy of 0 02 1 enables field calibration and verification of class 0 1 CTs for metering Assessment Automatic result assessment according to the defined standard IEC 60044 1 IEC 60044 6 or IEEE C57 13 1993 using implemented expert knowledge even for CTs defined according to IEC 60044 6 with defined transient performance TPS TPX TPY TPZ Rep
36. n to a data base for data exchange only with the OMICRON Device Browser The CPC 100 provides internet connectivity through an Ethernet connection both in a network and via a directly connected PC Automatic saving of all results or test parameters All test results are automatically saved and stored with the test This data can be organized according to the user s needs Saving tests as templates allows easy reproduction of any test at any time no matter how complex Customized Reports amp Standard Reports A standard report of your results can be created at any time via the Microsoft Windows Explorer using the OMICRON Device Browser or CPC Explorer PC software Since the test data is stored in XML format a standard format for data exchange the report is provided in HTML format Custom reports can be created with the CPC Excel File Loader Microsoft Word databases or any standard text editor software as XML format is used CPC Excel File Loader Reporting and Analysis Tool Using the CPC Excel File Loader you can load your test results into Microsoft Excel for further calculations of your measurements and for creating your own reports With the OMICRON Device Browser you can directly open your tests from the CPC 100 CPC Templates amp Customized Templates Save time by using the provided CPC templates or by using your own templates Perform the test with the CPC 100 Load the results into the corresponding CPC Exc
37. nals e Connected burden in VA and power factor cos Duration of the test 3s including automatic reporting Output up to 800 A 2000 A AC Input up to 10 A AC 3 V or 300 V via current clamp CT Burden Measures connected CT burden load with direct injection of secondary current with disconnected CT After entering the secondary nominal current and the test current and pressing the Start button the test card measures e Secondary voltage in magnitude and angle e Connected burden in VA and power factor cos Duration of the test 3s including automatic reporting Output up to 6 A AC Input up to 10 A AC 3 V via current clamp and 300 V CT Excitation Tests the excitation curve The necessary wiring is only two leads from the voltage output to the open secondary wiring of the CT After entering the current and voltage limits and pressing the Start button the test card will automatically record the CT excitation curve according to IEC 60044 1 ANSI 45 or ANSI 30 standards and the knee point will be automatically calculated After the test the core is demagnetized The test is done using a regulated voltage source Duration of the test 30 s including automatic reporting with recorded excitation curve and calculated knee point voltage Output up to 2000 V AC CT CONTINUED best 50004 Fi min 20 00 wo fa99904 A max 200000 voc 25430 3 R meaz 508 7 mii Time 31 0003 Car
38. nductivity resistance Q Nominal voltage CPC 100 1 x 100 240 VAC 50 60 Hz 16 A Operating temperature 10 55 C 14 131 F Transport and storage 20 70 C 4 158 F Relative humidity 5 95 non condensing 1 Signals below 45 Hz with reduced values possible Capacitive linear loads CPC 100 Accessories CP CU1 LINE amp GROUND IMPEDANCE The multifunctional primary test system CPC 100 in combination with the coupling unit CP CU1 is the world wide unique measurement system for e Line impedances and k factors of overhead lines or power cables e Mutual coupling of parallel lines e Coupling of power lines into signal cables e Ground impedances of large substations e Step and touch voltages The test system overcomes the problem of power system frequency interference that has previously made it necessary to use extremely large high power equipment to carry out these measurements The use of switched mode amplifiers and frequency shift techniques facilitates accurate measurements with compact portable equipment The CP CU1 can be ordered with several accessory kits which facilitate and soeed up measurements of step and touch voltages as well as ground impedances of large substations CP AL with Adapter Technical Data CP CU1 with CPC 100 For detailed information on the CP CU1 please see our product information brochure CP CU1 Extension to th
39. ng dissipation factor power factor and capacitance Complete electrical insulation between acquisition units and the control PC provide superior safety in high voltage setups High res olution digital processing enables exceptional measurement preci sion The easy to use control software features various real time visualization and monitoring options and integrates with multiple mtronix products System Features e Modular compact design The MI 600 consists of two acquisition units a fiber optical USB controller and a PC USB 2 technology allows for plug and play with any recent desktop rack mount or laptop computer Complete electrical insulation between the acquisition units and the control station is achieved by means of optical fibers each of which can be up to 2 km in length This guarantees unprecedented safety and flexibility Maintenance free operation No controls are present on the acquisition units All functions are available under remote control from the software Superior precision and performance The MI 600 features latest digital technology and advanced software design High speed and high resolution A D converters coupled with sophisticated digital processing algorithms deliver outstanding accuracy Low power consumption Optimized for battery operation due to a power consumption of less than 4 W in measuring mode In standby mode each acquisition unit consumes less than 10 mW Wide input range The MI 600 f
40. ng with different states required to use CP CU1 CP GR ground resistance test option includes testing software hardware accessory VEHZ0660 CPOL polarity checking for CT VT wiring including software hardware accessory VEHZ0650 CP TD1 test card capacitance and dissipation power factor measurements CPC editor software for offline test preparation on a PC Standard 2 x 6 m 70 mm2 800 A Alternative 2 x 9m 70 mm 800 A High voltage cable set 2 kV screened Standard 2 x 6 m 0 5 mm2 Alternative 2 x 10 m 0 5 mm2 Standard 6 x 6 m 2 5 mm2 1 x 0 5 m 2 5 mm2 Alternative 6 x 10 m 2 5 mm2 1 x 0 5 m 2 5 mm2 High voltage clamps connection with banana plugs 4 mm 1 red 1 black 2 Kelvin clamps High current cable set Measurement cable set Crocodile clamps for connection of the banana plugs 4 mm 2 red 2 black Grounding cable GR YE 1 x 6 m 6 mm2 with connection clamp Ethernet PC connection cable 3 m Low voltage adapter 4 mm banana to low voltage plug USB memory stick 512 MB User manual Reference manual included on the CPC Explorer CD ROM CP SA1 surge arrestor box for 100 A winding resistance measurement from firmware v1 4 gt TH3631 temperature humidity measurement unit for humidity ambient amp surface temperature measurement Power cord VII connector for most of EU M East VEHK0616 ZA connector for South Africa Namibia and India VEHKO620 BS connector for UK Hong Kong etc VEHK0624
41. nia Sequencer Typical Applications e Testing of auto reclosure cycles with primary current injection up to 2000 A opening closing of the circuit breaker contact is detected internally by the OMICRON hardware so no extra wiring is required e Measurement of the opening closing time of circuit breakers e Testing of primary overcurrent relays e Testing of low voltage circuit breakers with protection functions etc e Automatic testing with different amplitudes e g CT ratio at 0 05 In 0 2 In 0 5 In 1 In and 1 2 In The user can define consecutive states and the transition between states which can be initiated by a time out a trigger or a combination of the two Seven successive automatic measurements on predefined levels are possible Further the signals can be generated with a repeat function so that the sequence can be run in an endless loop up to 100 results can be recorded Example Overcurrent relay with auto reclosure function State 1 wait for the circuit breaker CB to open Output 400 A until the trigger condition Overload occurs The measurement table displays relay time the CB opening time 290 ms State 2 wait for the CB to close short dead time Output 50 A until the Overload condition that started state 2 clears The measurement table displays short dead time CB closing time 477 ms State 3 wait for the CB to open Like state 1 State 4 wait for the CB to close long dead t
42. ntation capabilities of OMICRON testing solutions are important benefits in light of the changing market conditions resulting in restructured organizations required to do more with less Today OMICRON s products revolve around a testing concept which provides the solutions to many challenges created by these competitive trends in the marketplace This integration of lightweight and reliable hardware with flexible and user friendly software is referred to as the OMICRON Test Universe Services in the area of consulting commissioning relay testing and training make OMICRON s product range complete Specialization in power system testing along with visionary leadership allows OMICRON to continue with innovative developments for its testing solutions to meet the customer needs of the 21st century SECONDARY TESTING CM line catalog OMICRON s product range in the area of secondary testing For a detailed list on literature currently available please refer to www omicron at support literature or www omicronusa com support literature Table of Contents TABLE OF CONTENTS 4 Overview 5 Interface Elements 7 Technical Data 8 Applications 9 Current Transformer CT 12 Voltage Transformer VT 13 Power Transformer 14 Resistance 15 Automatic Test Procedures 16 Power Factor Impedance Measuring 17 Reports Offline Test Preparation 100 Pe E 10 Tangent Delta Power Factor Testing 18 CP TD1 Technical Data
43. nual fiber optic cables measurement cables power supplies batteries and charger Separately available accessories VEHZ4112 4 A precision shunt VEHZ4114 15 A precision shunt VEHZ4113 28 A precision shunt VEHZ4105 MPP 600 Li lon battery set incl combined charger power supply and cable VEHZ4106 MPP 600 Li lon battery 11 2 V 4 8 Ah VEHPO040 mtronix aluminum case MBT 560 for 600 series VEHZ4121 Adapter for measurement tap of Micafil bushing type RTKG VEHZ4122 Adapter for measurement tap of F amp G HSP bushing type EKTF VEHZ4123 Adapter for measurement tap of HSP bushing type SETF For detailed information about the MI 600 please ask for our respective product brochure Worldwide CONTACT ADDRESSES North and South America Europe Africa Middle East Asia Pacific OMICRON electronics Corp USA OMICRON electronics GmbH OMICRON electronics Asia Ltd 12 Greenway Plaza Suite 1510 Oberes Ried 1 Suite 2006 20 F Tower 2 Houston TX 77046 USA A 6833 Klaus Austria The Gateway Harbour City Phone 1 713 830 4660 or 1 800 OMICRON Phone 43 5523 507 0 Kowloon Hong Kong S A R Fax 1 713 830 4661 Fax 43 5523 507 999 Phone 852 2634 0377 Email info omicronusa com Email info omicron at Fax 852 2634 0390 Email info asia omicron at 2M i ss aN ENN na A J OMICRON has a worldwide customer base which continues to grow Direct customer contact is essential in developing and building lasting rela
44. ories section page 21 CPC 100 Applications POWER TRANSFORMER Power Transformer Ratio Tap Changer Test VT Burden VT Electronics hi in Y pim 110000 0 Y sec froooo 0 1 3 7 13 Ratio 6 3509 W test 2000 0 W F 50 00 Hz prim 40 0 p fa 4 B Tap ia Count down ai Tap YPim Seef tf O13 1 999k 314 56 1 25 655 0013 Ol2 1 999k 31201 1 35 641 0 932 Keep O14 1 999k 308 64 1 25 646 2034 Result Back to Assessed n a l Top Min best fi O00 A Interval 110 000 DC na T oes E IE VDC nra Er 70 0 E Max Tap 0o07 Count up Tap Ameas Cev Fret Fipple Slope i Keep Result 001 508 7m O42 608 4m 2 117 11 64m O02 526 5m 0 52 324m 2 7 0 14 172m 003 542 6m O62 659 m 2235 17 32m 004 568 5m O22 6F84m 2 68 13 45m OOF S89 m 1 63 B93 am 42 31 626 5m m Assessed n a Transformer Ratio per Tap Measures ratio and excitation current per tap For this test a test voltage of up to 2 kV is injected on the transformer high voltage side This voltage is measured internally with high precision The voltage amplitude and phase angle on the low level voltage winding is measured back via the measuring input The ratio is calculated automatically The excitation current in amplitude and phase angle is also measured and reported Duration of the test 5 s
45. orting Comprehensive viewing and printing of test reports on a PC for different applications standards and classes using the predefined Microsoft Excel templates Simulation Existing test reports can be loaded at any time to recalculate the test results for different burden values and primary currents This way no further on site measurements are necessary to verify whether a changed burden influences the behavior of a CT The recalculation of the test results can be easily performed in the laboratory using the existing measurement data Remote Control and Test Automation Remote interface to integrate CT Analyzer into an automatic production process CT Analyzer can fully be controlled over the remote interface All parameters can be read from the device or from a test report with a simple to use software interface Ordering Information CT Analyzer CT1 incl accessories VE000652 CT Analyzer standard package VE000650 Accessories set for CT Analyzer For detailed information about the CT Analyzer please ask for our respective product brochure Sweep Frequency Response Analyzer FRAnalyzer The FRAnalyzer detects defects in power transformer windings and faults in the magnetic core After the transportation of transformers or following through faults with high currents the frequency response test should be made to ensure that the windings or core were not damaged Unique features of FRAnalyzer e High reliability of resul
46. ounding systems the auxiliary electrode for the current injection is replaced by a second grounding system which is connected to the current output of the CPC 100 via an auxiliary line For this application the use of CP CU1 see page 19 is recommended to obtain higher output power For measuring the soil resistivity four auxiliary electrodes are used Duration of the test 5 s including automatic reporting Output up to 6 A AC Input up to 3 V or 300 V AC and 10 A AC Winding Resistance The winding resistance test is described in the CT section page 10 CPC 100 Applications AUTOMATIC TEST PROCEDURES seuence and Ramping With general application cards some simple testing of single phase relays is possible such as the determination of trip times of I gt V gt V lt or frequency relays With Sequencer and Ramping the user can create her his own automatic test procedures 400 0 50 00 Overload n a 30 000 S00 50 00 Overload n a 30 000 400 0 50 00 Overload m a 30 000 50 0 50 00 Overload m a 30 000 1 Out efi ac Bin Time mee a Lz a Ez Ge En as E 399 8 0 00 C 290m ave He 35 6 0 00 F 4r rm Default 399 8 0 00 amp 291m 35 6 000 C Ramping acs ffs soor pele Amplitude 50 00H2 Stark val Moois Delete 2 200 0 10 000 Binary n a 00 10 000 Binary n a Card Clear Results Save As 170 29 0 00 EJ i Default 1852 33 0 00 y 1 1000 Assessed
47. per tap including automatic reporting Output up to 2 kV Input up to 300 V Resistance and Continuity of OLTC per Tap Measures winding resistance per tap and detects interruptions of on load tap changer OLTC diverter switches The voltage drop at the winding resistance is measured with a sense line The resistance value of each tap can easily be saved to a table containing all taps An automatic temperature compensation is possible Interruptions of the current because of a faulty diverter can be detected Duration of the test depends on the inductivity of the winding inductance Due to the high output voltage of up to 65 V testing time is reduced Output up to 6 A DC 65 V or up to 100 A DC 6 5 V Input up to 10 V DC and 10 A DC Leakage Reactance A test template to determine the leakage reactance is provided For the measurement the sequencer card is used and the results are carried out in Excel Voltage Withstand Test The voltage withstand test is described in the CT section page 10 Winding Resistance The winding resistance test is described in the CT section page 10 Power Factor See CPC 100 Accessories CP TD1 tangent delta power factor measuring page 18 CPC 100 Applications RESISTANCE PolCheck odd Range oae A RA min Card test aia A mas n a Auto Inc fesas94 W DC fi 2e50y F Manual input Clear R 4 283 rut Save As Template Assessed n a Eg TAT ap
48. quency range 15 400 Hz 2 kV AC Protection of AC DC input 10 A FF fuse 0 2 kV gt 2h 0 5 A 1 0 kVA 15 400 Hz Binary input for dry contacts or voltages up to 300 V DC see 7 on page 5 Trigger criteria Toggling with potential free contacts or voltages of up to 300 V 0 1 kV 1 min ZSA 2 5 kVA 15 400 Hz input impedance gt 100 kO 1 kV AC 0 1 kV gt 2h 1 0 A 1 0 kVA 15 400 Hz Response time 1 ms 0 0 5 kV 1 min 5 0 A 2 5 kVA 15 400 Hz Q meter DC 500 V AC 0 0 5 kV gt 2h DO A 1 0 kVA 15 400 Hz Accuracy full scale i Mode Connection Range Current 130 V AC 0 130 V gt 2h 3 0 A 390 VA 15 400 Hz G aranteed Typical e EE Cul a 0 5 UQ 12 5 mMQ 4wire 400ADC 400A 0 85 0 45 Guaranteed accuracy Typical accuracy 10 UQ 1 Q 4 wire 6ADC 6A 0 60 0 35 Output Range Amplitude Phase Amplitude Phase 100 uQ 10 Q 4 wire 6 A DC 1A 0 40 0 25 Reading Full Scale Full Scale Reading Full Scale Full Scale 0 2 2 20 KQ 2 wire VDCin lt 5 mA 1 00 0 2 Q 0 50 0 1 Q 800 A AC 0 20 0 20 0 20 0 10 0 10 0 10 General 400 A DC 0 40 0 10 0 20 0 05 Display 1 4 VGA greyscale LCD display USB Memory USB 2 0 2000 V 0 10 0 10 0 20 0 05 0 05 0 10 1000 V 0 10 0 10 0 30 0 05 0 05 0 159 Guaranteed communication of USB sticks supplied by OMICRON Power Supply 2 kV AC 500 V 0 10 0 10 0 40 0 05 0 05 0 20
49. r Output PESAN 1AAC 0 10 0 10 0 30 0 05 0 05 0 15 10ADC 0 05 0 15 0 03 0 08 Current outputs ae oE a ae o4 0 03 0 08 Range Amplitude tmax Vmax Powermax f 300V 0 10 0 10 0 20 0 05 0 05 0 10 ce 258 ay BOONE 12 QO eZ 30V 0 10 0 10 0 20 0 05 0 05 0 10 800 AAC 0 400 A 8 min 6 4 V 2560 VA 15 400 Hz V1 AC 500 kQ as 3V 0 20 0 10 0 20 0 10 0 05 0 10 es eet OY ue 12 a0 ne 300 mV 0 30 0 10 0 20 0 15 0 05 0 10 10 as ok a ao oe oe 3v 0 05 0 15 0 20 0 03 0 08 0 10 10 ae One nen MOY NA 1A00 Ra v2 ac 10M2 300 mv 0 15 0 15 0 20 0 08 0 08 0 10 De ODS 2 vale ono ZOO ES 30 mv 0 20 0 50 0 30 0 10 0 25 0 15 400 A DC 0 300 A 3 min 6 5 V 1950 W DC ran eae er i Ter i CaA gt 2h OY Tee De 1V 0 05 0 15 0 03 0 08 va VDC 500 ka CADE DGA A sa aot os 100 mV 0 10 0 20 0 05 0 10 3 i H A 2000 A AC with an optional Current Booster Please see page 21 for details 10mV 0 10 0 30 0 05 0 15 k Voltage outputs e Automatic range switching Range Amplitude tmax Imax Power max f Galvanically separated potential groups AC DC V1 amp V2 V DC 0 2 kV 1 min 1 25 A 2 5 kVA 15 400 Hz AC fre
50. rovides the ability to safely and ih eh eet ret at Delete accurately measure parameters of overhead lines power cables and 7 20 30 00 Mo T 2 000 ee Oe Noa nie eon i grounding grids This system can determine 17 00 70 00 Mo Trigger nia 2 000 a 120m 7000 Kio Trinner nia 7 nnn i IDI si T fore TAES ce ee ee mee tee Line Impedances amp k factors of Results Pa Se oe se t Overhead lines or power cables 19 872 0 00 85 554 nja nja Hisave as E 19 672 0 00 85 549 nja nja Default amp W Sse Mutual coupling of parallel lines ars ewj aeo i agi es ane e Coupling of power lines to signal 19 643 0 00 187 75 nja nja AEE Tii ae Ts e Ground Impedances of large EF Prides nites erpedarca Ij BA Lid 8g eres ree og EY Hei Compensation Factor Hare Ld Bika Opaja Factor substations e Step amp touch voltages Transferred 5 Maite Compensation Factor WE PL ad AES IL measurement results gt ae wt Nest eget CA CES PO Pa eG C6 a Bsr CPC 100 Report Test Preparation REPORTS amp OFFLINE TEST PREPARATION E CEE Tal h ere a T Fie EEL F 7 Hi ued bec A es Des A E a k aara i LLE ee fal Tiger COP ete Gai lier CSA Le ec oa mall 1E Ler 1 Y mut an Pe te ENN A Fup a Pij Ja wes Beets d i F SITY Eiti a T5 a E L ny im ie Hmi H i a i iil Li 4 AAR re 1 IED mA 1 Ji me BU my p 1a ft eh E TFI Li ek Ha lw HE i y LES E B nel USE
51. rprise Edition These packages can be combined with the TestBase CMC packages to form a comprehensive database system TestBase uses MS SQL server and runs on Windows 2000 XP Pro and Vista OS700002 The TestBase CPC Standard Package Personal Edition which comes at no extra cost with new CPC units provides the following features Standard CPC package single user version Management of Primary Assets Typical name plate data and important life cycle data for many primary objects are stored in TestBase and can be administered and directly exported to other programs e g MS Excel Location changes and object replacements can be easily managed within TestBase and are tracked automatically Specific object models for power transformers bushings diverter switches and instrument transformers are defined For other kinds of power supply networks equipment general data can be assessed in the object group miscellaneous Browsing and Filtering Mechanism A configurable tree view browser and comprehensive filter mechanisms facilitate naviga tion between the objects The display can be sorted by various parameters e g by location object type installation date Test Administration TestBase allows the consistent use of test templates for specified test categories OMICRON CPC templates and Excel templates can be automatically filled with name plate data and specific parameters when they are launched from TestBase With the OMICRON dev
52. s can be assigned to a parent object The link inspector displays such eT z relations between objects Sa Management of Additional Objects and Parameters m a i sie The user can define customized object groups or adapt existing models by adding certain asi s ia parameters e g data used for testing oat S S Maintenance Planning Support sa Maintenance cycles can be defined for individual assets or asset groups Alarm signals show object status not due due or overdue for maintenance Journaling TestBase automatically tracks important events change of operating state asset exchange activities planned and done etc in an event journal The user is able to generate additional events Customization Tool TestBase provides a tool where various data like the state of parameters and tests event types Pane IAT erent etc can be individually defined and changed by the user Measurements and data analysis et Sa For tan delta tests the detailed measurements are automatically extracted from CPC test f ES e G i documents and also from other 3 party test documents e g Doble into a measurement ATA ian structure By filtering the user is able to analyze and compare results e g different CPC tests T with Doble and to transfer them into Excel graphs e g time trending poe Reporting EE a a Reports on multiple objects maintenance schedules maintenance reports TestBase Enterprise edition The TestBase Enterprise
53. s of power and instrument transformers also for insulations of aged transformers e Diagnosis of OIP RBP and RIP HV bushings e Diagnosis of generator and motor insulations e Diagnosis of cable insulations Water is an ageing product and accelerates the further deterioration of cellulose through de polymerization In addition high water content in oil may cause bubble formation and lead to unexpected electrical breakdowns DIRANA uses two well established dielectric resoonse measuring methods The Polarization Depolarization Current PDC method in the time domain and the Frequency Domain Spectroscopy FDS in the frequency domain The time domain method enables a fast measurement but has limited accuracy at higher frequencies In practice the typical upper frequency limit is 1Hz The frequency domain method can be applied to low and high frequencies but it needs a long measuring time for very low frequencies The combined use of both methods makes DIRANA the fastest dielectric response analyzer on the market Measurements at higher frequencies are done in frequency domain whereas the built in PDC device accelerates the measuring time for the frequencies below 0 1 Hz The combination of the time and frequency domain measuring method reduces the measuring duration by 53 compared to mere frequency domain measurements For instance data acquisition for a frequency domain measurement from 1 kHz down to 0 1 mHz will typically take 6 ho
54. selecting the desired quantities Quick also automatically performs calculations derived from the quantities described above such as S P Q Z R R X R L R C ratio 1 ratio 5 AV and Al and displays them in the third column Doe a fae ae Sere Any relevant measured value can easily be stored by pressing Keep Result Thus all important results caaea O00 599m O061000e 0 are arranged and displayed in a table and can be further investigated at any time The entire testing session can be saved as a file A trigger functionality allows for triggering to a certain event such as reaching a threshold value or the switching of a contact The trigger can be binary or analog or it can be an overload of the unit For each trigger event both the current output value and the delay time are measured which allows the testing of pick up and drop off values of primary relays Complex impedances of transformers inductors or capacitors can be measured The amplifier technology used enables a wide range of testing frequencies different from the mains frequency The built in digital filters allow for sensitive and selective measuring without interference problems With this concept a lot of tests can be performed with small test signals instead of using big and heavy conventional test equipment with high test signals at mains frequency Reporting is done automatically oa 7 0381 0 00 15128 24 59 Ez 1 0579 O00 1 6179 29 70 1 3284 on
55. tage set for CP CU1 incl CP AL1 FFT voltmeter pair of foot electrodes ground electr and accessory cables Ground impedance set for CP CU1 includes GPS Garmin eTrex Rogowsky coil 6 cable reels and 3 ground electrodes CPC 100 Standard VE000611 CPC 100 Enhanced VE000621 CP TD1 Test Set VE000640 S S S S SSSS TOS ON NI ONT ON ONT OS SSS SSNPS SS NASI SUNS INIA S S SS SON ENON OS OSES SASAS CP Transformer Test Set VE000645 KS S TestBase TESTBASE TEST amp MAINTENANCE MANAGEMENT fam iF ne ee eee a ee ee O a i OMICRON TestBase is a database application for test administration and maintenance management of electrical assets in the electrical power supply industry TestBase provides a unique repository for power system management data such as name plate content test templates and test results The browsing and filtering options provide an immediate over view on all test objects installed with their most important data TestBase is available in two packages which are specially designed for usage with the CPC 100 freeing staff from many administrative tasks and paperwork TestBase is available in two packages for use with primary technology TestBase CPC Standard and TestBase CPC Enhanced Package Both packages are available in a single user version Personal Edition and with client server architecture Ente
56. ters CPC too Technical Data INTERFACE ELEMENTS ADA Ua ar oe oe s S 14 OM TCRONM 1 6 Aor 130 V AC Output 2 Current Output 6 A DC 3 Current Measuring Input AC or DC 4 Voltage Measuring Input 300 V AC 5 Low Level Voltage Measuring Input 3 V AC 6 Voltage Measuring Input V DC 2 wire resistance measurement 7 Binary input for potential free contacts or voltages up to 300 V DC See page 7 for details on outputs and inputs 8 Safety key lock If locked the quantities which are currently put out are frozen The unit does not accept any commands except for an Emergency stop 9 Signal Lights Green light indicates a safe operation whereas red light indicates an operation with hazardous voltage and or current levels at the outputs 10 Emergency stop button 11 Keys for quick selection of your application 12 Keys for quick selection of your desired view 13 LCD monitor 14 Soft touch keys changing according to the selected application 15 Keys for selecting stacked test cards 16 Numerical keyboard 17 Advanced jog dial hand wheel with click Enter function The hand wheel allows for navigation within test cards within other views or across views and it also allows for the entering of values In entering mode the wheel s adaptive acceleration function will increase decrease the input value in ever bigger steps if the wheel Is turned fast Slow turnin
57. tio e calculates the deviation from the nominal ratio Duration of the test 5 s including automatic reporting Output up to 800 A 2000 A with Current Booster CP CB2 Input up to 3 V AC Polarity Checker The Polarity Checker option can be found in the Accessories section page 21 CPC 100 Applications VOLTAGE TRANSFORMER VT Vorim lO0DLOY W sec onov 143 143 P 13 ytes 20000 e 5000H M Auto VW prim 2000 ky Yo sec fsooery oa od Manual input Ratio PlOooDoWatonasWs oan Z Polarity fox Clear Results Save As W sec onoo 143 f 50 00 Hz A Auto W test m T Curent clamp sec V sec zza sec zima 23600 Manual input Burden 1 2726 VA COs yp fase VW prim fioooo oy sec ooo 143 14f3 13 W best 2000 0 f 50 00 He E Auto YW prim 2000 ky VY sec jonam 005 T Manual input patio Moona ona ozer Polarity fo Results Save s Template VT Ratio Polarity and Burden Electronic VT VT By transformer electronic voltage twi n a shielded cable with sted wires Burden electronic protection relay with low V input VT Ratio and Polarity Measures the capacitive or inductive VT ratio and polarity After entering the primary voltage s
58. tionships around the world To achieve this OMICRON has an extensive network of more than 50 representatives distributors and local offices To identify the contact for your area please visit Contact Us on our website at www omicron at or www omicronusa com OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions The application of OMICRON products provides users with the highest level of confidence in the condition assessment of primary and secondary equipment on their systems Services offered in the area of consulting commissioning testing diagnosis and training make the product range complete Customers in more than 130 countries rely on the company s ability to supply leading edge technology of excellent quality Broad application knowledge and extraordinary customer support provided by offices in North America Europe South and East Asia and the Middle East together with a worldwide network of distributors and representatives makes the company a market leader in its sector With its policy of pioneering development OMICRON continues to lead the field in creating solutions to meet the needs of 21st century customers OMICRON Sales Service Centers Europe Middle East Africa OMICRON electronics GmbH Oberes Ried 1 A 6833 Klaus Austria Phone 43 5523 507 0 Fax 43 5523 507 999 info omicron at Wwww omicron at
59. ts due to the applied measurement method SFRA and innovative connection technique specially designed for SFRA testing e Extremely small size of the test instrument through the use of leading edge technology e Ease of use because of creative software e Portability resulting from battery operation For high frequencies the equivalent circuit diagram of a transformer winding can be drawn as a complex network of resistors inductors and capacitors The frequency response of this network is unique like a fingerprint Winding deformation causes one or more of the capacitors in this network to be changed To Identify these changes which can be quite small the new fingerprint is compared to reference results Deviations are an indicator of e Coil deformation axial amp radial e Faulty core grounds e Partial winding collapse e Hoop buckling e Broken or loosened clamps e Shorted turns amp open windings technical Data FRAnalyzer Frequency range 10 Hz to 20 MHz Source Output FRA Method Sweep frequency Output impedance 50 Q Connector BNC double shielded Amplitude 2 83 V p p Inputs Reference CH1 Measurement CH2 Impedance 50 Q 1 MQ selectable Connector BNC double shielded Dynamic range gt 120 dB Accuracy lt 0 1 dB down to 80 dB lt 0 3 dB down to 100 dB Mechanical data supply voltage Weight Instrument Complete set Dimensions w x h x d Instrument Complete case DC power supply
60. urs DIRANA will acquire this data in less than 3 hours Two measurement channels instead of one channel enable the simultaneous measurement of two insulation gaps like HV to LV winding and LV to Tertiary winding which results in an additional time savings of 50 The easy to use software determines moisture content in the solid insulation DIRANA analyzes the dielectric response and determines the humidity in the solid insulation The automated algorithm com pensates for disturbing influences such as temperature insulation geometry oil conductivity and aging by products Conductive aging by products appear as water and cause an over estimation of the moisture content leading to unnecessary drying DIRANA compensates for this influence and thus reliably detects moisture even in aged transformers HV insulation curves Heavily aged wet Dissipation factor New dry Technical Data Test modes UST A UST B UST A B GST GSTa GSTb GSTa b PDC Current measurement Range 20 mA Resolution 0 1 pA Input resistance 10 kOhm Accuracy 0 5 0 1 pA Voltage source Measurement voltage Maximum continuous output current 200 V variable 50 mA Time range 1 10 000 s 1 0 0001 Hz FDS Measurement voltage 0 200 V peak Measurement current 0 50 mA peak Capacitance Range 10 pF 10 uF Dissipation factor range 0 10 Dissipation factor accuracy 0 5 104 Dissipation factor resolution O 10