Contents

1. the error Expansion Rack Cable 12 Do not connect or disconnect the expansion rack cable while the CPU is running This will cause the PLC to go to the STOP HALT mode Expansion Rack Power 13 Expansion racks should be powered up at the same time that the main rack is powered up or they should be powered up after the main rack has completed its power up initialization Do not power up an expansion rack while the CPU is running power up diagnostics Memor y Usage 14 Ageneral rule of thumb for memory usage is 48 bytes per I O point plus register memory in bytes Timer Operation 15 Care should be taken when timers ONDTR TMR and OFDTR are used in program blocks that are NOT called every sweep The timers accumulate time across calls to the sub block unless they are reset This means that they function like timers operating in a program with a much slower sweep than the timers in the main program block For program blocks that are inactive for large periods of time the timers should be programmed to account for this catch up feature Similar to this are timers that are skipped because of the use of the JUMP instruction Timers that are skipped will NOT catch up and will therefore not accumulate time in the same manner as if they were executed every sweep 1 0 Link Interface 16 When powering up the PLC CPU without a battery and I O Link Interface boards are present an incorrect Loss of Module fault will be logged for each I O
2. Link Interface board but the PLC CPU will not consider these boards as lost and the boards will continue to operate properly Constant Sweep 17 Constant Sweep time when used should be set to about 10 ms greater than the normal sweep time to avoid any oversweep conditions when monitoring or performing on line changes with the programmer The smallest valid constant sweep time setting is 10 milliseconds for the Model 788 and 789 CPUs Win dow completion faults will occur if the constant sweep setting is not high enough External Devices Writing to CPU Memory 18 At CPU power up both the model 788 and 789 CPUs prohibit external devices PCMs Ethernet boards CMMs etc from having write access into PLC memory config data program code R P L Q AI WAQ T M G including GA through GE The only devices that are permitted write access are parallel IC641 programming software anything via the built in serial port and IC66 Bus Controllers GBC NE s If external devices require write access to portions of memory these areas which can be written to can be made available by the application using Service Request 31 Important Product Information GFK 1059B This new Service Request 31 permits a range within each memory reference type to be defined as writable by external devices Service Request 31 does not require that every memory reference type have a writable area but does limit the writable area to a single cont
3. problem with input data coherency Ina system with a large CPU sweep time and a short IC66 bus scan time a problem could be seen if a device was lost Input data could be defaulted off while the CPU is reading data from the GBC NE It is recommended to update existing GBC NBC hardware with Bus Controller IC697BEM731M or later when updat ing PLC CPU firmware to release 5 01 Foreign VME Modules 6 IC641 programming software Release 5 00 allows foreign VME modules to be configured for five modes BUS INTERFACE INTERRUPT ONLY FULL MAIL IO SCAN and REDUCED MAIL However the IC697 CPU Release 5 01 and earlier supports only the BUS INTERFACE mode The other modes should not be configured Maximum PLC Sweep 7 In systems configured for IC66 Bus Redundancy a complete PLC sweep must be executed every 500 ms or less even though it is possible to configure the watchdog timer to higher limits This also means that resetting of the watchdog timer with Service Request 8 cannot be done indefinitely Serial Communications 8 The following operational restrictions exist for the Serial Communications feature 1 Serial communications may add up to 5 ms of time to any given sweep This should be taken into ac count when setting the watchdog timer 2 The following procedure is recommended when changing baud rates in the PLC and the WSI board First enter the configuration package and change the baud rate on the PLC then store the new config urat
4. October 22 1998 GFK 1059B IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product Programmable Controller CPU Modules IC697CPU788 DA 1C697CPU788 EA IC697CPU789 DA IC697CPU789 EA Important These products have tested Year 2000 capability affected It is strongly recommended that you read the Year 2000 information contained in this document Introduction This document contains information not available in any other publication therefore we recommend you keep it for future reference This document covers two subjects 1 Year 2000 remediation workarounds covered in the Year 2000 Information section and 2 information about the IC697CPU788 and 1C697CPU789 CPU modules and firmware release 5 01 These CPU modules are used in IC66 IC660 or 1C661 Modular Redundancy Systems GMR systems The purpose of firmware release 5 01 is to support Phase II of the GMR system Also several of the features provided in release 5 00 of the standard IC697 CPU modules are also made available in the GMR CPUs Sequential Function Chart user programs Parameterized Subroutines and other new features described under New Features and Functionality Release 5 01 of the GMR CPUs also fixes problems described under Problems Resolved by Firmware Release 5 01 Table 1 Catalog Numbers New Catalog Number Replaces IC697CPU788 DA IC697CPU788D IC697CPU789 DA IC697CPU789D Packaging Note Effectiv
5. To correct the failure power cycle the expansion racks The IC697 GDS module does not operate with the release 5 01 model 788 or 789 CPU It will not correctly power up if present in a PLC that uses a release 5 01 model 788 or 789 CPU Do not use the GDS module in a PLC that has a release 5 01 model 788 or 789 CPU module
6. data but continued to send a token Examples of these devices are any device providing global data or IC670 blocks This problem requires corresponding fixes in both the IC697 CPU and the IC697 GBC NE modules Release 5 01 of CPU models 788 and 789 have the CPU fix All IC697 GBC NEC modules having catalog number IC697BEM731L or later have the corresponding GBC NE fix New features and Functionality Provided by Firmware Release 5 01 Sequential Function Chart 1 Release 5 01 of the PLC CPU together with Release 5 of the IC641 programming software has the ability to create load store and execute Sequential Function Chart SFC user programs SFC is a method specifically developed for describing industrial sequential control systems SFC is a graphic method which represents the functions of a sequential automated system as a sequence of steps and transitions Each step represents commands or actions that are either active or inactive The flow of control passes from one step to the next through a conditional transition that is either True 1 or False 0 If the transition condition is true 1 indicated by setting the transition variable control passes from the active step which becomes inactive to the next step which then becomes active Parameterized Subroutine Blocks 2 AParameterized Subroutine Block PSB is an optional user defined function block configured with between zero 0 and seven 7 input output parameter pairs A param
7. e with this product release the product manual will no longer be shipped in the box with every product Product manuals are provided in a library which is a complete set of manuals with IC641 programming software products are available on CD ROM or are available as individual manuals These catalog numbers have CE Mark approval Important Product Information GFK 1059B Identification Hardware and software identification is summarized in the following tables Table 2 Hardware Identification Board Catalog Number Identification Board Revision 1C697CPU788 DA CPHA2 44A731786G01 RO7 or later 1C697CPU789 DA CPHA2 44A731786G01 R07 or later Table 3 Firmware Identification Catalog Number EPROM Location EPROM Label 397 017C 5 01 73 397 018C 5 01 74 397 020C 5 01 75 397 019C 5 01 72 397 021C5 01 73 397 022C 5 01 74 397 024C 5 01 75 397 023C 5 01 1C697CPU788 DA 1C697CPU789 DA Gee cd eeacd Documentation The following table lists the applicable documentation for the IC697CPU788 and IC697CPU789 CPUs Table 4 User Documentation 1C697CPU788 LA GFK 0806A 1C697CPU789 DA GFK 0807A Read this document before installing or attempting to use the IC697CPU788 or IC697CPU789 PLC CPU Module For more information refer to the applicable Programmable Controller Installation Manual Programming Software User s Manual Programmable Controller Reference Manual and GMR User s Manual Important Product Infor
8. eterized subroutine enables you to reuse relay ladder logic within the same program or in multiple programs Logic that needs to be repeated Important Product Information GFK 1059B can be entered in a parameterized subroutine Calls would then be made to that subroutine to access the logic In this way total program size is reduced Dividing a program into smaller subroutines simplifies programming and reduces the overall amount of logic needed for the program Release 5 01 of the PLC CPU together with Release 5 of the IC641 programming software has the ability to create load store and execute parameterized Subroutine Blocks RANGE Function Block 3 Anew RANGE function block has been added which is used to compare a single input value against two delimiters to determine whether the input value falls within the range of delimiters Release 5 of IC641 programming software is required for this feature ARRAY RANGE Function Block 4 Anew Array RANGE function block has been added which is used to compare a single input value against two arrays of delimiters that specify an upper and lower bound to determine whether the input value falls within the range specified by the delimiters Release 5 of IC641 programming software is required for this feature User Memory Parity 5 Release 5 01 of the PLC CPU models 788 and 789 supports parity on the user and system memory The following versions of CPU modules and expansion memory module provide t
9. his functionality CPU Module IC697CPU788 DA IC697CPU789 DA 32 bit Expansion Memory Module 512K bytes IC697MEM735D Background Task Window 6 There are now PLC diagnostic tests that will run in the Background Task Window The background Timer configuration value defaults to zero If you want the tests to run in the Background Window then change the Background Timer to a non zero value Also refer to Additions to the PLC Reference Manual for a description of SVCREQ 5 Change Background Task Window State and Values Restrictions and Open Problems 1 If an expansion rack powers up while the CPU in the main rack is in the RUN mode the slot fault contacts will prematurely indicate that the modules in the expansion rack are not faulted before they complete their power up 2 Inamulti rack system false LOSS OF RACK faults may occur when the system loses power If this fault is configured to be fatal the system will power up in STOP mode 3 When there is no logic stored ina CPU module the Q and M tables will be cleared when the CPU is placed in RUN mode In this context no logic stored means that no program had ever been stored or that the clear function on the IC641 programming software had been used to clear logic and configuration 4 When the Bit Sequencer sequences from one step to another the negative transitional contact that corre sponds to the original step is not set The transition contact for the new step is set and remai
10. iguous range in each memory reference type specified Interaction of IC641 Programming Software with Closed Programming Window 19 The IC641 programming software Sweep Control and Monitor screen cannot be used to change the PLC Sweep Modes or timers Constant Sweep Time Program Window Times etc while the program window is closed Use Service Requests 1 through 4 to perform these functions IC641 programming software cannot be used to change the PLC mode STOP RUN etc while the programming window is closed Use the toggle switch on the CPU module instead Problems Resolved by Firmware Release 5 01 1 If the CPU s toggle switch was moved to STOP and back to RUN while a C block was sending text out the serial port the serial port used to stop working and the CPU had to be power cycled to make SNP and C block messages work again This no longer happens the serial port should continue to work When power is cycled on an expansion rack in a system that is running a large sweep time when IC641 programming software is not connected GBCs NEs in that rack will now configure properly The COM_REQ function incorrectly allowed the value of the TASK parameter to be greater than 127 When a TASK value greater than 127 was specified an incorrect TASK value was sent to the device specified by the SYSID parameter GBC NB s could overwrite inputs after passing data to the CPU This would occur when a device on the IC66 bus stopped sending
11. ion Now power off the PLC and then go to the WSI setup screen and change the WSI baud rate Finally power the PLC back on 3 The link idle time setting in IC641 programming software Config for Serial Communications should be set to 10 seconds or greater Otherwise a communications failure will occur when storing the con fig to the PLC Serial Port Mode Configuration 9 There is a serial port configuration parameter under software configuration for the PLC called MODE This configuration parameter can be one of two values SNP to indicate that the serial port will be used for SNP communications or MSG to indicate that the serial port will be used to send printf commands from a C program block to the connected device If you have configured MODE to be MSG and are also using serial IC641 programming software as a means of communicating with the PLC communications with 1C641 programming software is lost when going to the RUN mode since the serial port is currently configured for printf commands from C program blocks 1C641 WSI Attach 10 Do not connect or disconnect the WSI BTM cable while the programmer host is powered on This action may cause a running PLC to Stop Important Product Information GFK 1059B Expansion Rack ID 11 The expansion racks for the IC641 PLC are shipped with the rack ID strapped for rack 0 the main rack If the rack jumper is not changed the PLC will not recognize the rack at all and may not properly identify
12. mation GFK 1059B Year 2000 Information One issue causing these two CPUs to test Year 2000 capability affected has been identified This issue does not affect all users of these CPUs Please read item 1 below to determine if it applies to you Note that two solutions are offered for this issue One is a suggested workaround that provides guidance on how to prevent this issue from affecting your application The alternative suggestion is to replace your CPU with a newer model that doesn t display this characteristic For that solution a list of replacement CPUs is provided Versions Tested The following table identifies the CPU firmware versions tested for Year 2000 capability CPU Firmware Versions Tested for Year 2000 Capability Series 90 70 Versions Y2K Versions Versions Versions Not CPU Capable Containing Y2K Containing Y2K Tested As Defined Leap Year Issue SVC 7 Write to Below TOD CPU788 aa DA EA 5 01 andearlier S D 4 16 and earlier CPU789 PF DA EA 5 01 andearlier Po D 4 16 and earlier Year 2000 Capable Defined For the solutions that are stated to be Year 2000 Capable in the paragraphs below that term is defined to mean that 1 the Product s functionality will not be materially adversely affected as a result of the date change from 1999 to 2000 including leap year calculations provided that all products used with the Product function properly including without limitation properly exchanging accu
13. mation IC697 CPUs maintain a byte value for the year date This means that only the two least significant digits of the year are provided This two digit format supports dates from 1980 through 2079 For example for the year 1998 only the 98 is provided by the CPU or for the year 2001 only the 01 is provided It is customary for the user to create appropriate program logic to supply the other two digits if they are required Important Product Information GFK 1059B Firmware Upgrade Information Upgrade kits are available to upgrade GMR PLC CPUs to firmware version 5 01 Existing units may be upgraded for a charge by ordering the applicable field upgrade kit Note Firmware version 5 01 of these CPUs is not Year 2000 Capable Please refer to the previous section Year 2000 Information for details on identifying the problem and its remediation Table 5 Upgrade Kits 444731244602 IC697CPU788D 1C697CPU788 DA 44 A731245G02 IC697CPU789D 1C697CPU789 DA Special Operation Notes GMR CPU Expansion Memory Board 1 The release 5 01 IC697 CPU models 788 and 789 GMR CPUs should only be used with the IC697 expansion memory board IC697MEM735D or later CBlocks 2 When using C blocks with CPU model 788 the C Programmer s Toolkit for IC697 PLCs IC641SWP709B or later must be used to create the C Blocks s 1C641 Compatibility 3 This release of the PLC CPU modules is compatible with the versions of IC641 programmi
14. ng software listed in the table below However version 5 01 or later is required to access all of the CPU s features and functionality CPU Model 1C641 Programming Software Version 4 02 or later Version 4 02 or later If Release 5 01 PLC CPU firmware is used with IC641 programming software Release 4 02 the PLC Sweep Control and Monitor screen F3 F8 should ONLY be used to change tune the constant window or constant sweep time Any other use may result in the background window time being incorrectly set to 255 milliseconds For this IC641 programming software release used with a Release 5 01 CPU the configuration package must be used to set the desired sweep modes or window times PCM and BTM Compatibility 4 With the introduction of timing improvements and new features in release 5 00 it is highly recommended that systems using PCMs use IC697PCM 711J or later It is also highly recommended that systems using BTMs use IC697BEM713B or later Use of boards of an earlier revision may result in lower system performance Important Product Information GFK 1059B Notice to Upgrade GBC Hardware 5 With the introduction of new features in this release timings with the IC66 Bus Controllers GBCs NBes have changed this has uncovered a problem in the GBC NE firmware GBCs NBE s in expanded racks could be lost if the system is fully configured and only the main rack cycles power Also in previous versions of the GBC NE there was a
15. ns set until the sequencer sequences to the next step This operation is identical to the operation of the previous ver sions of the CPU firmware 10 10 Important Product Information GFK 1059B If multiple faults exist in an IC697 PLC remote drop and one of them is corrected a FAULT contact that uses the remote drop s module reference will incorrectly indicate that no faults exist at the remote drop User application faults logged for Service Request 21 can only use error codes between 0 and 2047 Use of any other error codes could cause the PLC to treat the alarms as Remote Scanner alarms An IC66 Bus Fault may set the fault condition for the M_rsbmm r rack s slot b bus mm SBA of GBC NED fault and nofault contacts This fault condition will persist until either the fault tables are cleared or the GBC s NBe s rack is power cycled An Analog Input Base module and its expander modules may not come online if they are configured in an expansion rack that is missing when the main rack powers up Power up the expansion rack first then power up the main rack If the main rack loses power during PLC configuration analog input base boards ALG230 in expansion racks that do not lose power may fail The failure would occur on the subsequent configuration PLC configuration occurs during power up store of configuration and reads from Retentive Flash Memory To prevent the fail ure tie all racks to a common power source
16. o that screen to cause the programming software to request the time and date from the PLC again This is not a characteristic of the Windows PLC programming software It displays the actual PLC time and date in its Target Comm Data tab window because it requests this information from the PLC and updates this window once each second Workaround Solution To avoid this inaccurate date condition you can check and reset the PLC s date if it s not correct on the day following the February 28 date of each year Application of this workaround solution will make the Product Year 2000 Capable See the item Year 2000 Capable Defined MS DOS and Windows are registered trademarks of Microsoft Corporation Important Product Information GFK 1059B Alternate Solution Replace the CPU The replacement CPUs are Year 2000 Capable See the items Year 2000 Capable Defined and Updating Your CPU Module Updating your CPU Module The following replacement recommendations are provided for users who wish to replace their CPU with a newer model that does not display the Leap Year characteristic described above Contact your distributor or the factory to order the replacements listed below CPU Replacement Recommendations CPU to be Replaced Replacement CPU IC697CPU788 1IC697CPM790 IC697CPU789 1C697CPM790 Note About the Two Digit Year Format This item is not a Year 2000 capability issue It has been included here for your infor
17. rate date data with the Product and 2 to the extent applicable to the Product s normal operating specifications and subject to any upper and lower limits Note on Year Date Format As a separate item a note is included at the end of this section explaining the two digit year date format for the IC697 CPUs 1 Incorrect Leap Year Management Possible Problem These CPUs do not manage leap years properly It has been observed that years that should be leap years sometimes have only 28 days in February and years that are not leap years may have 29 days in February This is only a problem to users who are using this date information in their application For example some use the PLC s date information to time events or for dating messages and reports Observing this condition on the TIME OF DAY CLOCK screen of the MS DOS PLC programming software package may produce inaccurate results The programming software running on a personal computer requests the date from the PLC initially then maintains its own version of the PLC date based on the personal computer s time clock until either 1 communications with the PLC are lost or 2 a different screen is displayed Therefore if you were observing the date change at midnight of February 28 using the programming software you would be observing the programming software s version of the date With the passing of midnight you would need to exit the TIME OF DAY CLOCK screen then go back t