UPS + AVR User`s Manual
Contents
1. Back up silenced No load 2 beeps every 4 sec Back up Loading No can Not 4 beeps per sec Battery Low be silenced Yes 8 beeps per sec Battery NG 5 4 Auto self test Function In normal mode of UPS turn on your computer and push the button on the front panel for self test The UPS will simulate a power outage and transfer your load to the UPS s battery If low battery warning sounds during the test it means that the battery set is weak and requires extended recharge If battery NG warning sounds it means that the battery set is damaged and requires replacement 5 5 DIP Switch Settings Available for standard models 1200 1500 2000 3000 long run models 750 1000 1500 2000 amp universal input model 1500 D10 1000A DIP Switch 1 2 3 4 Function Table of DIP Switch 2 Wika AN 1 F unction Up Down Up Down Up Down Up Down Voltage 100V 200V V V Voltage 110V 220V V V Voltage 115V 230V V Voltage 120V 240V V Frequency for DC Start X 50Hz 60Hz Green Power Enable Disable Yes No Xx Frequency for DC start is not available for universal input series P S Program setting active only after the UPS is re started 5 6 Remote Control The UPS can be set for daily shutdown wake up This command must be set through the RS 232 interface When this function is set
2. 4sec Voltage gt 126 or lt 77 Low Battery Alarm Battery Fail Alarm Over load Alarm RED Lighting J B Continuously Thermal Alarm RED Flashing G ba Re G 16beeps 2sec R silence 2sec 17 Part C for long run models 750L 1000L 1500L 2000L only Rear Panel NEMA Type Haz IEC Type lelelel Fuse Inlet of city power Outlet s NEMA IEC RS 232 Interface DIP switch Phone jacks for fax machine optional by DIP switch Battery connector D10 1000A 18 D10 1000A Part C specifications for long run models 750 1000 1500 2000 CAPACITY 750VA 1000VA 1500VA 2000VA Max Loading 750W 1000W 1500W 2000W lt 30sec lt 30 sec lt 30 sec lt 30 sec Selectable 100 110 115 120V 1 or 200 220 230 240V 19 Frequency 50Hz 60Hz Auto detect OUTPUT Voltage 100 110 115 120V 1 or 200 220 230 240V 1 3 for Back up Mode lt 10 forAVR Frequency 50Hz or 60Hz 0 1Hz Selectable under DC start Wave Form True Sine Wave Current 110V 220V Transfer Time lt 3ms 24V optional 36V optional Level Ind Protection for reverse batery polan ves CHARGE Voltage 40 95V 27 3V 54 60V 40 95V 54 60V 81 90V Maximum Current LED ALARM INDICATION Normal city power Frequency gt 65Hz or lt 47Hz Abnormal Voltage of City power B B B B 2beeps 4sec Voltage gt 126 or lt 77 Transfer to backup mode Low Battery Alarm B
3. 5 2 Operation status LED 5 3 Audible alarm 5 4 Auto self test function 5 5 DIP switch settings 5 6 Remote control 5 7 Reset the UPS 6 COMMUNICATION INTERFACE Page 11 6 1 The definition and setup for RS 232 6 2 The definition and setup for DB9 optional 7 TROUBLE SHOOTING Page 12 8 SPECIFICATIONS en ee ee ee ER DERES Page 13 21 9 IMPORTANT SAFETY INSTRUCTIONS Page 23 D10 1000A 1 1 1 2 1 3 INTRODUCTION for standard models 650 1000 only Overview The series UPS is an advanced Line Interactive Uninterruptible Power System which produces pure sine wave power to your equipment unlike the traditional off line UPS the series provide very short transference when blackouts happen and zero transference from AC mode to battery mode or from battery mode to AC mode The voltage regulation performance of series is similar to an On line UPS however the series provide efficiency over 98 under normal power condition Two charge modes quick charge and trickle charge are provided to maintain the batteries in the best condition Battery replacement warning The self test function by pushing the button will inform you with an alarm when the batteries are weak and require replacement Communication interface A communication interface port for sensing input voltage output voltage battery capacity output power le
4. Low Battery Alarm ORG Flashing B B B B B B 4 beeps sec nm Battery Fail Alarm Over load Alarm Thermal Alarm RED Flashing Greet Rites G 16beeps 2sec R silence 2sec DC START ALARM RESET s nere ves ves 30 95 Non Condensing 38 x 20 x 18 cm 45x 20 x 18 cm SHIPPING DIM Lx Hx W 48 x 33 x 30 cm 54x 33 x 30 cm WEIGHT N W GW 17 18kgs 22 23kgs 21 D10 1000A IMPORTANT SAFETY INSTRUCTIONS When replacing the batteries use the same number and the same type of batteries Do not dispose of batteries in a fire the battery may explode Do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles To prevent an overbalance of this unit with the installation the additional stabilizer are to mount at the bottom side This unit should be installed from service personnel The equipment can be operated by any individuals with no previous experience The socket outlet shall be installed near the equipment and easily accessible With the installation of this equipment it should be prevented that the sum of the leakage current of the UPS an the connected consumer does not exceed 3 5mA Attention hazard
5. charging for at least 5 hours before your first use The batteries are charged automatically by the UPS whenever the UPS is connected with city power No need to turn on the UPS INSTALLATION amp OPERATION Installation Inspecting the packing carton for damage that may have occurred while in transit Immediately notify the carrier and place of purchase if any damage is found Retain the package for future use Plugging the power cord to a 3 wire grounding receptacle If an extension cord must be used between the UPS and the nearest wall outlet use a 3 wire grounding type rated for at least 20 Amps D10 1000A 4 2 4 2 1 4 2 2 4 2 3 4 2 4 4 2 5 4 3 Connecting your equipment to the UPS To ensure that your computer equipment will be protected during a utility failure it is important to make sure that the maximum power need from the equipment is not over the rated capacity of the UPS Red LED will lighted up and alarm will beep if the load is over the rated value Meantime if the overload is severe the UPS will shut down immediately for protecting UPS itself Operation After installation with normal city power the UPS will charge the battery automatically and the status LED blinks green every 2 seconds Please push the button about one second on the front panel then the UPS will give power to the outlets after a short time of self test Pushing the button for 4 seconds the UPS will turn off the power on the
6. off by the green power function In a long time black out situation you won t miss any FAX data by this function D10 1000A 5 INDICATION AND CONTROL 5 1 Battery level and load level LEDs The battery level LEDs show the voltage level both in back up mode and in normal mode When the LED indicates 20 of the capacity in back up mode it means that the UPS is going to shut down for the length of backup time left it will depend on the load While when all five LEDs light in normal mode it means that the battery is fully charged The load level LEDs show the percentage of added load by the UPS s rated capacity When all five LEDs light the UPS is over loaded 5 2 Operation status LED The status LED shows the UPS status in the normal utility power duration LED shows Green In the event of a utility outage LED shows Orange Ifthe UPS is under fault operation LED shows Red 5 3 Audible alarm During a utility failure or fault operation the UPS emits beep for warning In back up mode the beeping can be silenced by pushing the button However the warning of low battery will still sound for urging user to leave computer without any data loss Basic Indication Table PERIOD STATUS Idle mode One flash every 2 sec Utility Good One flash every 2 sec Utility outage One flash every 2 sec Timer on refer to Item 5 6 Green No Beep Continuously Normal Utility good Orange Yes can be Onebeep every 4 sec
7. D10 1000A UPS AVR Uninterruptible Power System User s Manual Line Interactive Sine Wave Standard models 650 1000 1200 1500 2000 3000 Long run models 750 1000 1500 2000 Universal input models 1000 1500 NORMAL BACK UP LOW BATT OVER LOAD D10 1000A TABLE OF CONTENTS Part A for Standard models 650 1000 only Page 3 1 INTRODUCTION 1 1 Overview 1 2 Battery replacement warning 1 3 Communication interface Part B for standard models 1200 1500 2000 3000 only Page 4 1 INTRODUCTION 1 1 Overview 1 2 Battery replacement warning 1 3 DIP switches 1 4 Communication interface Part C for long run models 750L 1000L 1500L 2000L only Page 5 1 INTRODUCTION 1 1 Overview 1 2 Battery replacement warning 1 3 DIP switches 1 4 Communication interface Part D for universal input models 1000 1500 only Page 6 1 INTRODUCTION 1 1 Overview 1 2 Battery replacement warning 1 3 DIP switches 1 4 Communication interface FOR ALL MODELS 2 MAIN FEATURES Page 7 3 CAUTION Page 7 4 INSTALLATION AND OPERATION Page 7 4 1 Installation 4 2 Operation 4 3 Connecting the FAX machine 5 INDICATION AND CONTROL Page 9 10 5 1 Battery level and load level LEDs
8. Pin 7 D10 1000A 11 D10 1000A 7 TROUBLE SHOOTING Problem Possible Cause Action to Take UPS no reaction while AC is connected 1 Line cord plug is loose 2 Fuse on rear panel blown Inside the drawer of inlet 3 Dead wall socket 1 Check the line cord plug 2 Replace fuse 3 Check wall socket with a table lamp Power output is normal UPS UPS is over loaded Tum off UPS and unplug emits continuous beep excessive loads from UPS status LED shows RED UPS emits continuous beep UPS has shut down due to Unplug excessive loads from status LED show RED amp no overload UPS press button to reset the power on outlets buzzer and turn on the UPS again UPS does not provide 1 Excessive loads connected Do not operate the UPS and expected run time at UPS s outlets 2 Battery is weak and can not provide enough capacity leave the UPS plugged in for 10 hours Then test it again if UPS still can not provide expected run time battery should be replaced Button on front panel 1 The CPU inside UPS is not 1 Push the button for 10 doesn t work running correctly seconds to reset the UPS 2 Button damaged 2 Unplug line cord and all loads from the UPS to let it shut down automatically and call for service To push button for testing Battery is weak and should be Replace batteries under AC mode UPS emits replaced urgent beep 8 beeps per sec and RED LED b
9. attery Fail Alarm Over load Alarm Thermal Alarm i G 16beeps 2sec R silence 2sec 19 Part D for universal input models 1000 1500 only Rear Panel NEMA Type An IEC Type O lelelel Fuse Inlet of city power Outlet s NEMA IEC RS 232 Interface DIP switch 1500VA Phone jacks for fax machine optional by DIP switch Battery connector enclosed upon request D10 1000A 20 Part D specifications for universal input models 1000 1500 CAPACITY 1000VA 600W 1500VA 900W INPUT Voltage 100 110 115 120V 19 or 200 220 230 240V 19 Auto detect Frequency 50Hz 60Hz Auto detect Current 110V 220V 10A 5A 16A 8A OUTPUT Voltage 100 110 115 120V 19 3 for Back up Mode lt 10 for AVR Frequency 50Hz or 60Hz 0 1Hz Selectable under DC start Wave Form True Sine Wave Current 110V 220V 9A 4 5A 13 6A 6 8A TRANSFER TIME Transfer Time lt 3ms BATTERY Lead Acid maintenance free Voltage Capacity Level Ind Recharge Time 90 within 5 hrs 90 within 2 hrs LED ALARM INDICATION LED Normal city power GRN L Lighting l Back up Mode Abnormal Freq of City power ORG Flashing quick B B B B 2 beeps 4sec Frequency gt 65Hz or lt 47Hz Transfer to backup mode Abnormal Voltage of City power ORG Flashing slow B B B B 2beeps 4sec Voltage gt 126 or lt 77 00 I Transfer to backup mode _ nm
10. bnormal Voltage of City power ORG Flashing slow B B B B 2beeps 4sec Voltage gt 126 or lt 77 Transfer to backup mode Low Battery Alarm Battery Fail Alarm B B B B B B B B Over load Alarm Thermal Alarm RED Flashing Gees a Re G 16beeps 2sec R silence 2sec YES YES YES YES YES YES 0 37 C ENVIRONMENT HUMIDITY 30 95 Non Condensing 38 x 20 x 18 cm 48 x 33 x 30 cm 15 16 kgs D10 1000A D10 1000A Part B for standard models 1200 1500 2000 3000 only 9 Rear Panel NEMA Type lelele ae Fuse Inlet of city power Outlet s NEMA IEC RS 232 Interface DIP switch Phone jacks for fax machine optional by DIP switch Battery connector enclosed upon request D10 1000A Part B specifications for standard models 1200 1500 2000 3000 Frequency 50Hz 60Hz Auto detect Current 110V 220V OUTPUT Voltage 100 110 115 120V 1 or 200 220 230 240V 1 3 for Back up Mode lt 10 forAVR Frequency 50Hz or 60Hz 0 1Hz Selectable under DC start Wave Form True Sine Wave Current 110V 220V VoltageCapacity Level Ind Recharge Time LED ALARM INDICATION Normal city power Back up Mode Abnormal Freq of City power Frequency gt 65Hz or lt 47Hz YES YES 90 within 2 hrs LED GRN Lighting ORG Flashing quick Transfer to backup mode Abnormal Voltage of City power ORG Flashing slow B B B B 2beeps
11. his port you can remote control the UPS for turning on and off by customized schedule and setting the auto test procedure D10 1000A 1 INTRODUCTION for universal input models 1000 1500 only 1 1 Overview The series UPS is an advanced Line Interactive Uninterruptible Power System which not only produces pure sine wave power but also provide universal input range to your equipment unlike the traditional off line UPS the series provide very short transference when blackouts happen and zero transference from AC mode to battery mode or from battery mode to AC mode The voltage regulation performance of the series is similar to an On line UPS however the series provide efficiency over 95 under normal power condition Two charge modes quick charge and trickle charge are provided to maintain the batteries in the best condition The series is made with Universal input but single output 110V or so 1 2 Battery replacement warning The self test function by pushing the button will inform you with an alarm when the batteries are weak and require replacement 1 3 DIP switches Available for 1500VA DIP switches allow you to adjust the UPS for different line voltages and frequencies in different areas It also allows you to enable the green power function to shut down the UPS automatically if the load is less than 25W and then to extend the battery life 1 4 Communication interface A communication interface port for sensi
12. links at the same time UPS can not be turned on 1 Battery polarity wrong 2 UPS fault 1 Check battery connection 2 Call for service 12 FRONT PANEL FOR ALL MODELS O 100 O O 80 O O 60 O 0 0 4 Q O 20 O e Loan NE BATTERY BACK UP LOW BATT OVER LOAD LEDs of battery voltage level and load level LED of operation status OD Control button D10 1000A Part A for standard models 650 1000 only Rear Panel NEMA Type IEC Type Fuse Inlet of city power Outlet s NEMA or IEC RS 232 Interface Phone jacks for fax machine Battery connector enclosed upon request D10 1000A 14 8 SPECIFICATIONS Part A specifications for standard models 650 1000 CAPACITY 650VA 1000VA INPUT Voltage Selectable 100 110 115 120V 10 or 200 220 230 240V 19 Frequency 50Hz 60Hz Auto detect Current 110V 220V 6 5A 3 25A 10A 5A OUTPUT Voltage 100 110 115 120V 19 or 200 220 230 240V 19 3 for Back up Mode lt 10 forAVR Frequency 50Hz or 60Hz 0 1Hz Selectable under DC start Wave Form True Sine Wave Current 110V 220V 5 8A 2 9A 9 1A 4 6A BATTERY Voltage Capacity Level Ind YES YES Recharge Time LED ALARM INDICATION Normal city power Back up Mode Abnormal Freq of City power ORG Flashing quick B B B B 2 beeps 4sec Frequency gt 65Hz or lt 47Hz Transfer to backup mode A
13. ng input voltage output voltage battery capacity output power level and UPS statuses are provided through this port you can remote control the UPS for turning on and off by customized schedule and setting the auto test procedure D10 1000A FOR ALL MODELS 2 4 1 MAIN FEATURES Line Interactive structure Microprocessor based design Green Power design with auto on off function RS 232 interface for communication Protection for overload short circuit amp over heat Pure sine wave output Zero Transference CAUTION The UPS is designed to power computer loads and the associated peripheral devices such as monitors modems external H Disk drivers etc To ensure the performance of the UPS Do Not load the UPS with laser printer motor or any type of inductive load Connecting the UPS to a two pole three wire grounding mains receptacle Connection with any other type of receptacle may result in a shock hazard and may violate local electrical codes Do not allow water or any foreign object to get inside the UPS And do not put objects containing liquid on or near the unit Keep UPS away from fire or heating sources The standard models of 650 1000 1200 1500 2000 3000 are shipped from the factory with fully charged internal batteries however the batteries may lose some energy during delivery and storage To ensure that the UPS will provide the expected run time during a blackout the UPS must be left in
14. ous through electric shock Also with disconnection of this unit from the main hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole through the from the outer enclosure accessible battery fuses when maintenance or service work inside the UPS is considered The lead acid battery may cause chemical hazard The battery presents a risk of electric shock and energy hazard Batteries will be disposed by the manufacturer or importer Customers need to send them back with no charge for disposal Electrical hazard the discharge time is about 5 min 22
15. outlets But the UPS will keep charging if city power is normal To stop the charging please pull out the power cord to shut down the UPS completely During a blackout push the button for entering idle mode Ref Indication Table then push again for one second and the UPS will be turned on and enter into backup mode To turn off the power from UPS please push the button for 4 seconds then UPS s status LED will blink orange every 2 seconds wait for 5 seconds and UPS will turn off the power automatically In idle mode UPS will turn off the power automatically within 12 seconds during a utility failure while UPS will keep charging the batteries if the utility power is normal When utility power is normal please pull out the power cord if you want to turn off the UPS completely When Green Power function is enabled the UPS will turn off the power within 30 seconds after blackout occurs with the power consumption lower than 25W Connecting the FAX machine When you are connecting a FAX machine or modem with the UPS please also connect the phone line through the UPS The UPS may offer protection against damaging power fluctuations and surges that travel through the phone line The UPS also offers a ring on function when the power is off UPS power will be turned on automatically when a ringing signal exists in the phone line and the UPS will keep power on until the FAX machine finishes receiving work then the UPS will be turned
16. provided through this port you can remote control the UPS for turning on and off by customized schedule and setting the auto test procedure D10 1000A 1 1 1 2 1 3 1 4 INTRODUCTION for long run models 750L 1000L 1500L 2000L only Overview The series UPS is an advanced Line Interactive Uninterruptible Power System which produces pure sine wave power to your equipment unlike the traditional off line UPS the series provide very short transference when blackouts happen and zero transference from AC mode to battery mode or from battery mode to AC mode The voltage regulation performance of the series is similar to an On line UPS however the series provide efficiency over 98 under normal power condition Two charge modes quick charge and trickle charge are provided to maintain the batteries in the best condition Battery replacement warning The self test function by pushing the button will inform you with an alarm when the batteries are weak and require replacement DIP switches DIP switches allow you to adjust the UPS for different line voltages and frequencies in different areas It also allows you to enable the green power function to shut down the UPS automatically if the load is less than 25W and then to extend the battery life Communication interface A communication interface port for sensing input voltage output voltage battery capacity output power level and UPS statuses are provided through t
17. the timer inside the UPS will begin to run and the load will be turned off by the shutdown wake up schedule During the period of turn off to the next turn on the status LED blinks red every 2 seconds 5 7 Reset the UPS If any abnormal condition occurs and the item 4 2 1 4 2 4 can not be executed please push the button for at least 10 sec until the status LED becomes orange then the UPS is reset 10 6 COMMUNICATION INTERFACE The UPS provides both computer interfaces smart software RS 232 and dry contact DB 9 by using different software and cable the UPS shows different monitoring function 6 1 The definition and setup for RS 232 is as following Baud Rate 2400 dps Data Length 8 bits Stop Bit 1 bit Parity None 5432 1 9876 Pin 6 RS 232 data Tx out Pin 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In 6 2 The definition and setup for DB9 optional is as following Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 amp Pin 5 Pin 5 UPS Battery Low Pin 6 Turn off UPS Pin 7 GND of Pin6 The interface with computer is diagramed as above for your reference Use Pin 4 as the common of Pin 2 and Pin 5 Pin 2 and Pin 4 will become close loop from open when the utility fails Pin 5 and Pin 4 will become close loop from open when the battery level is low The UPS will shut down itself when the high level from RS 232 sustained for 3 seconds which is applied between Pin 6 and
18. vel and UPS statuses are provided through this port you can remote control the UPS for turning on and off by customized schedule and setting the auto test procedure D10 1000A 1 1 1 2 1 3 1 4 INTRODUCTION for standard models 1200 1500 2000 3000 only Overview The series UPS is an advanced Line Interactive Uninterruptible Power System which produces pure sine wave power to your equipment unlike the traditional off line UPS the series provide very short transference when blackouts happen and zero transference from AC mode to battery mode or from battery mode to AC mode The voltage regulation performance of series is similar to an On line UPS however the series provide efficiency over 98 under normal power condition Two charge modes quick charge and trickle charge are provided to maintain the batteries in the best condition Battery replacement warning The self test function by pushing the button will inform you with an alarm when the batteries are weak and require replacement DIP Switches DIP switches allow you to adjust the UPS for different line voltages and frequencies in different areas It also allows you to enable the green power function to shut down the UPS automatically if the load is less than 25W and then to extend the battery life Communication interface A communication interface port for sensing input voltage output voltage battery capacity output power level and UPS statuses are