1. LPS LP amp 2 PE RECTI FI ER TOTAL QUIPUT CONNECT PR GUIPUT BATTERY PE PE RECTI Fl ER PUT BATTERY PE E A B N N A CGC A B C4 E E A B C N N A B C E Al BoC a a d AC NPUT LOAD BATTERY NPUT AC NPUT BATTERY NPUT UPS2 output wires connect to UPS1 terminal on which marked connect UPS2 output two units UPS bypass input is come from output of bypass cabinet Note turn on operation step 1 Two units UPS connect wires must be connected following the above wiring diagram before electrify it must be insure the parallel cables connect correctly and firmly 2 When two units UPS connect to the utility battery voltage is low pls close rectifier switch There is no S appear in the begin start UPS S is not disappear in the end start UPS if S disappear pls stop turn on which is show two units UPS signal disconnect 3 Closing bypass switch and battery switch one by one again 4 Before closing output switch pls examine the two UPS output voltage difference make sure the voltage difference is within 10V between phase and phase then the two units UPS will parallel 28
2. or shut down and turn to bypass output 042 UPS restart 043 UPS is battery testing statue 044 Cancel buzzer alarming by hand 045 Shut down UPS by hand 051 Users send out the order and close the UPS from long distant monitoring 052 Users send out the order and start the UPS from long distant monitoring 053 Users send out the order and test the UPS from long distant monitoring 054 Users send out the order and cancel the buzzer alarming from long distant monitoring 061 Rectifier start to work 062 Rectifier stop working Others Unknown trouble wrong trouble record 15 Notes 1 Please press button with facial location of forefinger or middle finger please do not press the screen with sharp device in order to prevent scratching the touch sensitive screen surface 2 After parameter setting system will will use the new setting 3 Incident that are record inside the UPS is not permanent It records most recent incident and over ride the old record automatically User can through menu delete all incident record directly 4 Time format is 24 hours record 5 User must set the time and date at the first time of using the UPS If users can understand or want to get more detasiled help to the content of the manual while using please contact distributor or consult to our company we will serve you 27 REMARK UPS parallel operate step
3. inverter supply power There are some conditions under this temporary statue for example overload after bypass supply power UPS will return to power supplied by inverter 8 7 Alarming 7 Bypass output overload If overload time is too long for example overload 125 inverter can supply power Imin then turn to bypass UPS will renew normal running statue 8 8 Alarming 8 High temperature or fan failure 14 When control system of UPS inverter power module or rectifier power module is over temperature because of high temperature or fan failure UPS turn to bypass 9 UPS start up process It must be operated in these sequence thought there is battery in the UPS Start up UPS 9 1 Open input rectifier switch Up 9 2 Open bypass switch UP 9 3 After battery low voltage indicator crust out turn on the battery switch When UPS has no any alarm statue indicator bypass will turn to inverter statues Notice it will display alarming information about the wrong phase sequence if rectifier switch is not cut off at this time please press F1 and silence carry out UPS start up process 10 UPS maintenance shut down process 10 1 open maintenance switch up 10 2 close battery switch down 10 3 close rectifier switch up 10 4 close bypass switch down 10 5 close UPS output switch down 11 Emergency shut down process In the case of fire electric shock user should turn off all switchs 12 Touch s
4. 100 100 100 100 100 100 100 100 100 200 200 6 6 Battery connection Opening battery pack Installation battery on the corresponding position and connecting the battery connecting wire 6 7 Connection inspection connect all input output battery wire and check the following Whether all battery connecting wires join correctly and keep securityly fasten Ensure that input output and the earth connection has already been connected in the corresponding wiring on the equipment is arranged correctly The input voltage of input end frequency phase should keep the same with voltage of bypass frequency and phase 7 Specification 7 1 UPS series specification 7 1 1 Rectifier input parameter Please refer to the following table 1 10 Table 1 ode 10 15 20 30 40 50 60 80 100 120 ode KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Capacity KVA 10 15 20 30 40 50 60 80 100 120 Input single max current 25 33 40 55 71 86 102 133 164 195 Working way and principle On line static bypass switch zero transfer time Double switch technology output power to totally isolate Phase 3phase N G Nominal voltage 415 400 380 220 200AC 25 415 400 380 AC 25 Nominal frequency 50Hz 10 60Hz 10 Voltage harmonics distortion lt 10 Soft start O0 100 Ssec 7 1 2 Rectifier output parameter Please r
5. 8900 3 phase in and 3phase out series UPS is high power and true on line UPS with range from 1OKVA to 200KVA which adopts advanced digital design high speed 16 bit chip ASIC DDC and large power IGBT amp SCR and shows large capacity high stability and high performance compared with other models in the market All the products come integrated latest hardware and powerful software in itself which could provide optimum pure power to integrated server center This system supports several units connected in parallel through unique control technology The liquid crystal display of touch sensitive screen is that UPS which our company develops newly shows the module which is adopt nowadays most popular touch screen interfaces Compared with the situation that general LCD shows the module this touch screen shows the operating sequence without complication of the module users press the simulation button on the display and can obtain corresponding information directly Operation and is easily understood and it brings real time clock and memory by oneself can store up to 256 information and other establishment messages 2 Operation demand gt Please read carefully the user manual before using the UPS gt This manual must be understood and conserved by engineer gt This manual does not introduce the detail specification 2 gt This manual just suit to 8900 3 phase in and 3phase out series UPS 3 Notices 3 1 Make sure proper pow
6. PS can work steadily and reliably Input sampl ing Output LED dispaly LCD display SPWM signal Besides UPS others parts inverter transformer input inductance IGBT SCR controlled and switch 4 2 Standard UPS principle Manual bypass switch 0 Bypass switch a ae Static switch Rectifier output Input oni n output switch Rectify switch i aera ol Inverter ttery switch Battery ersten 4 3 Mains inverter principle After AC input turn to DC through rectifier then inverter invert via SPWM and output AC Rectifier inverter Rectit T ve BS Be jo Output output switch 4 3 1 Normal inverter model Battery have been recharge fully AC input via rectifier and inverter then output ee Input 7 Battery system Output Rectifier Inverter iH 4 3 2 Inverter normal and battery recharge working model Battery voltage is low after AC inverter on one hand it will charge the battary on the other hand inverter output AC aR Rectifier gt Output Inverter Battery system 4 3 3 AC input failure battery working model When no AC input battery supply energy to the invertor then supply AC R gt Output Rectifier Dall Inverter Battery system 4 3 4 Bypass output working model There is AC input but inverter has been closed output is via bypass L gt Output 4 4 Function module 4 4 1 R
7. PS_vwersion 2004 10 01 00 00 00 Picture 12 14 Incident code System will automatic to write down some important incident and date time that incident happen in order to to refer in the future System can only store up to 256 incidents Every kind of different incident is expressed with different code CODE Users press the buttons and get the incident records At the same time besides the incident code and time it will also provide simple incident We will provide all incident codes and detailed incident records in the following forms one 26 Incident code Incident code Detail incident description 000 Empty no records 001 Mains failure 002 Battery low voltage 003 UPS overload 004 Over Temperature 005 Phase sequence abnormal the UPS input phase sequence is wrong 006 Inverter abnormal there is something wrong with inverter 007 System abnormal 008 Bypass output UPS turn to bypass output 009 Inverter output UPS turn to inverter output 010 Rectifier abnormal there is something wrong with rectifier 021 Mains returns to normal 022 The voltage of the battery returns to normalo 023 Load returns to normal 024 UPS temperature returns to normal 025 UPS input phase sequence returns to normal 031 Transmit abnormal 032 Transmit return to normal Automatic shut down because battery low voltage or others failure UPS Automatic
8. Touch screen UPS 10 200 KVA User s Manual Content 1 Brief introduction 2 2 Operation demand 2 3 Notices 2 4 Working principle 3 5 Front panel 7 6 Installation 8 7 Specification 10 8 Alarming 13 9 UPS start up process 15 10 UPS maintenance shutdown process 15 11 Emergency shutdown process 15 12 Touch screen introduction 15 13 Operating interface introductions 16 14 Incident code 27 15 Notes 28 1 Brief introduction
9. ain menu 7 Back space Press button this return to the previous level 8 Help Press this button and consult help information 9 System information Press this button and consult UPS s information 0 system records Press this button and consult all history records SYSTEM MANAGEMENT SYS INF Picture 4 13 6 1 Import password interface Some operation will change the present working state of UPS for instance ON OFF system system at this moment will require operator input password otherwise system will not accept any operator s instruction The initial operation password from the factory is 1234 please consult the picture 5 1 Password It will apperance each time the user enter the password 2 Number button Input corresponding number 3 Enter After 2 press this button and enter into interface 4 ESC Withdraw from the introduction password communication frame When the password is correct system will carry out corresponding operation SYSTEM MANAGEMENT Picture 5 13 6 2 History records interface 20 Press system history records button from the menu it will enter the history records menu and press corresponding button 1 The permutation order in the memory of the incident the newest incident is arranged foremost the serial number is minimum 2 Incident code 3 Incident time Time records when it has happened 4 incident description It describes the
10. creen Introductions The liquid crystal display of touch sensitive screen is that UPS which our company 15 develops newly shows the module which is adopt nowadays most popular touch screen interfaces Compared with the situation that general LCD shows the module this touch screen shows the operating sequence without complication of the module users press the simulation button on the display and can obtain corresponding information directly Operation and is easily understood and it brings real time clock and memory by oneself can store up to 256 information and other establishment messages 13 Operating interface introductions 13 1 Start up screen It will show the compay logo when UPS starts the machine When the interval of the touch sensitive screen is not touched for four minutes CPU will cut off the power in a dim light of touch sensitive screen automatically this way can lengthen in a dim light service life and the compay logo will return if UPS is under warning state to get back to at the starting time the touch sensitive screen will have priority to show the warning information frame CPU can not cut off touch sensitive screen in a dim light power before canceling warning information 13 2 The flow chart interface When the logo is on the touch screen you can touch it anywhere and enter into the flow chart interface You can know the basic information and working statues about this UPS 1Mains Press it you can l
11. ds deletion interface Will delete all incidents to write down in this interface this is non irrecoverable after the data are deleted The interface is as show on picture10 24 1 message box 2 Progress mark Show that deletes the completion of election o SETUP OPERATION PASSWORD atk MESSAGE Picture 10 13 7 4 Langue interface Press language button when setup interface display then enter into language choose interface to set up You can choose languages used while showing of system in this interface the system supports two kinds of languages Chinese and English The interface is showing on picture 11 shows 1 message box 2 Chinese Pressing this button will use the Chinese language to show various kinds of information 3 English Pressing this button will use the English language to show various kinds of information SETUP OPERATION Picture 11 13 8 Alarming interface When UPS is in warning state Display module will show the warning menu automatically and preferentially If UPS warning information does not canceled and the display menu show warning interface continuly user can cancel the alarming by hand The warning menu is as picture 12 shows 1 Warning information frame Warning information shows in this news frame 2 Alarming information display 3 Enter Push this key and cancel UPS alarming withdraw from warning interface at the same time Manufacturer UPS_model U
12. ear is not set is displaying When users import new number value from the figure button show the digital value that users input 3 Date Show the date when the year is not set is displaying When users import new number value from the figure button show the digital value that users input 4 Enter After inputting press this button to conform 5 Cancel button Withdraw from the new clock communication frame of introduction 6 Number key Input corresponding number 23 7 Minute Show the minute when the year is not set is displaying When users import new number value from the figure button show the digital value that users input 8 Seconds Show the second when the year is not set is displaying When users import new number value from the figure button show the digital value that users input 9 Hours Show the hours when the year is not set is displaying When users import new number value from the figure button show the digital value that users input Picture 9 Notice Users set up the time system from left to right while setting up namely set up the order Year Month gt Date Hour gt Minute Second user input one figure each time cursor then move to right one automatically place corresponding are input by user 13 7 3 Incident records deletion interface Press Incident records deletion button and input right password then enter into Incident recor
13. ectifier 2 RANE Power factor Battery correction Rectifier contro Rectifier protection switch Lightning arrestor 6 12 Pulse rectifier Input inductance gt gt gt gt gt Battery temperature compensation gt Battery floating charging gt Battery time balanced charging gt The input of rectifier can be limited in rated numerical value at the same time battery recharge in constant current constant voltage engineer can change rectifier working through setting parameter 4 4 2 Inverter IGBT bridge type pluse width of sine modulates the circuit Invert transformer Control Output current Self checking Testing Output Voltage Running os Failture Protection gt Inverter output isolation transformer gt 3 Phase PWM inverter bridge gt Current sampling gt Voltage sampling gt Feedback control gt Self testing gt Hardware sense gt Protection circuit 5 Front panel introduction 1 LCD display it indicates various kinds of data 2 LED statue display it indicates working statue 3 Input rectifier switch Control rectifier input 4 Bypass switch Control by
14. efer to the following table 2 Table 2 Mo el 10 15 20 30 40 50 60 80 100 120 ode KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Max output voltage 405VDC Microcomputer setting 1A 50A depend on battery capacity charge current 7 2 Battery Please refer to the following table 3 Table3 ade 10 15 20 30 40 50 60 80 100 120 ode KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Max discharge current A 28 42 56 85 113 141 169 225 282 338 Battery quantity 30pcs Nominal battery voltage 360VDC Floating voltage 405VDC Charge current 3A 30A depend on battery capacity 7 3 Inverter specification Inverter Please refer to the following table 4 11 Table 4 Model 10 15 20 30 40 50 60 80 100 120 KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Rated power KW COSo 0 8 8 12 16 24 32 40 48 64 80 96 Phase 3phase N G Nominal voltage 415 400 380 220 200AC 25 415 400 380 AC 25 1 steady load 5 load fluctuate Nominal frequency 50Hz 0 05 60Hz 0 05 battery supply power Frequency stability lt 0 05 Out sync Frequency stability lt 42 Synchronization Crest factor 3 1 Output wave Sine wave Total harmonic distortion Linearity load lt 3 non linearity load lt 5 Dynamic load voltage transient from 0 to 100 ab
15. er input output battery cable 3 2 It must be steady grounding system 3 3 There are a lot of high voltage energy stored in the UPS please don t open the case and check otherwise cause danger to move the UPS around accept the consequences by oneself The operator must have understand electrician knowledge and pore over the operation instructions 3 4 Without permission do not dismantle any kinds of connection cables without authorization 3 5 Because this product is larger in volume weight is heavy can t move around fequence keep the UPS well ventilating 3 6 Ensure UPS is instealled in clean and dust free enviromrnt 3 7 The battery must be changed by the professional and technical person the used battery changed out must be deliver special circulation and give a new lease of life to the organization to deal with The battery is poisonous waste material 3 8 When the UPS is not been used for long time the battery disposed will discharge automatically the battery must be charged in every three months if the temperature is greater than 30 degrees Centigrade the battery should be charged once every two months You need to start UPS while charging and run at least for 24 hours under the normal work pattern 4 Working principle 4 1 This 3 3 series UPS adopts advanced digital design improved MTBF and steadily a single main control panel control all system functions Which adopts microprocessor control and ensure the U
16. f UPS and two sides should be kept more than 80cm away from the wall gt Do not store any goods on the top of the UPS gt It must have enough room for inspection in the front of equipment and above gt Battery box of equipment must have keep enough room on right hand side for battery replacement gt Power line must be connected from bottom of machine 6 4 Terminal connection diagram Groundina Before UPS is not being installed please disconnect all switches Left R S T N connect three phase input phase line and median line Right N R S T connect three phase output phase line and median line E connect earth line connect battery positive pole and negative pole 6 5 UPS three phase output system 5 200KVA cable specification unit mm2 Input Output Battery capacity R S T N E R S T N 5KVA 4 4 4 4 4 4 4 4 4 6 6 10KVA 6 6 6 6 6 6 6 6 6 10 10 20KVA 10 10 10 10 10 10 10 10 10 20 20 30KVA 16 16 16 16 16 16 16 16 16 30 30 SOKVA 25 25 25 25 25 25 25 25 25 50 50 80KVA 40 40 40 40 40 40 40 40 40 80 80 100KVA 50 50 50 50 50 50 50 50 50 100 100 120KVA 60 60 60 60 60 60 60 60 60 120 120 150KVA 75 75 75 75 75 75 75 75 75 150 150 200KVA
17. he main menu UPS AC output check and measure 220 220 220 A C output voltage V 50 0 50 0 50 0 AC output frequency Hz 00 0 00 0 00 0 AC output current A 000 000 000 Load capacity Bypass switch working statue ON Inverter switch working statue OFF 2004 10 01 00 00 00 Picture 2 13 4 Display panel introductions Picture 3 13 5 LED and button introduction 1 Mains input indictor 2 Bypass indictor 3 Inverter indicator 4 Battery low voltage indicator 5 Overload indicator 6 system abnormal indicator 7 F1 combined key silencing key 8 F2 shut down Press F1 and F2 at the same time and shut down UPS Press F1 and enter into set up model 13 6 Manage interface setting introductions 1 ON OFF When UPS is closed the key display ON Press this button and start UPS when UPS is started the key display OFF press this button and close the UPS system will demand to enter password in order to avoid mistake 2 Battery measure button When UPS is working press this and enter into battery measure mode system will demand to enter password in order to avoid mistake 3 about Press this button and consult the touch screen version number information 4 Silencing Make the buzzer silence system will demand to enter password 5 UPS current working statue 6 ESC Press this button and return to the m
18. incident type 5 UP There are 8 levels of incidents 6 Down To see previous 8 levels of incident records 7 ESC Press this button and withdraw from all catalogues and get back to main menu 8 Back space Press this button and consult all history records Incident record DA No Code Time Incident 044 2004 TODI Silencing alarming 000 00 00 03 002 2004 10 01 001 00 00 00 Battery low voltage 2004 10 01 00 00 00 Input unusual 2004 09 30 00 00 00 Transmit the trouble 2000 00 00 00 00 00 mal 2004 10 01 00 00 00 1 Picture 6 003 004 aie 13 6 3 Current UPS working statue Press current working statue button when the menu interface display and then enter into 21 current UPS working statue interface and press corresponding button 1 it shows current UPS working statue 2 ESC Press this button and withdraw from all catalogues and return to main menu 3 Back space Press this button and consult all history records UPS current working statue UPS has been shut down battery low voltage input unusual bypass Output Picture 7 2004 10 01 00 00 00 13 7 Setup display interfaces Refer to picture 8 press the corresponding button and can alter the systematic parameter of UPS in this picture 1 Time setup button It can change system time system will demand to enter password in order to a
19. ook at the Mains input statue and data display 2UPS basic information Display UPS basic information include manufacturer UPS model and version number 3 Thin dotted line It shows that the UPS has stopped to work 4Heavy line It shows that the UPS is working 16 5Output Press it you can look at the UPS output statue and data display 6Inverter Press it you can look at inverter working statue and data display 7The systematic parameter establishes the module It can set up time and language SUPS serial No it display UPS product serial number QBattery Press it you can look at battery working statue and data display 10system time it can display time 1islave marks it show this UPS is working when it is parallel connection 12systems manage module it can control UPS and consult the system records 13tectifier Press it you can look at the rectifier working statue and data display UPS_model UPS_wersion Picture 1 13 3 Measure data display interface Press Mains key output key inverter key battery key and rectifier key then enter into corresponding measure data display interface please consult the picture 2 and it show the output information and data display 1 Form subject 2 Form contents All kinds of statue and data display 3 System time System time display 4 Back space Press this button to return to the previous 17 5 ESC Press this button and return to t
20. pass input 5 Output switch Control output 6 Battery switch Control battery input 7 Maintenance bypass switch Control AC bypass just use it only during maintenance 8 Line bank Connect input output battery and grounding 9 RS232 communication port 6 INSTALLATION 6 1 Installation environment gt Temperature 0 C 40 C gt Relative humidity 30 90 gt Altitude 1000M gt Installation environment dimension LxW H 2000 2000 2000 gt Board pressure 3000KG M7 The indoor environment demanded is as follows gt No dust gt Appropriate indoor temperature please operate UPS in 0 40 C But it is at 0 Cwhen the UPS has just been switch on The idea operation temperature is 25 C gt There should be a good heat dissipation system the following is a feasible method A Natural ventilating system Only suitable for low heat and vast space B man made ventilating systems Need to install the air conditioner when the peripheral temperature TE in chassis temperature TA exceeds As the TE and TA is close the capacity of the heat distribution system will increase 6 2 Check before installation Unpack the equipment and inspect again to determine if any external or internal damage has occurred Opening the main entrance and please check if all switches are disconnected 6 3 Installation site gt Please place the UPS in the place where there is good ventilation Rear panel o
21. rupt ae change Moment restart time lt 10ms Balance load voltage lt 1 lt 5 imbalance load voltage Overload capability 125 1min 150 1S Inverter efficiency load 91 91 92 92 93 93 93 95 95 95 100 7 4 Bypass Please refer to the following table 5 Table 5 ay 10 15 20 30 40 50 60 80 100 120 ode KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Phase 3phase N G Nominal voltage 380VAC 25 Nominal frequency 50Hz45 60Hz 5 Inverter bypass transfer time overload Oms 12 7 5 systems specification Please refer to the following table 6 Table 6 vedd 10 15 20 30 40 50 60 80 100 120 ode KVA KVA KVA KVA KVA KVA KVA KVA KVA KVA Efficiency load 100 gt 80 PC communication interface RS232 Working temperature 0 40 C Humidity 30 90 non condensing Working height Max lt 1000m per100m power decline 1 Max 4000m Type of cooling Forced draught Noise dB according to load and temperature far away 40 50 45 55 55 65 machine 1M Case color Gray option Input cable The bottom back Easy maintenance The front the above left and right Dimension 600 700 1350 710 720 1450 710 850 1500 1100x860x 1680 WxDxH mm Weight kg 200 300 400 460 550 620 700 860 900 950 Inp
22. ut device Terminal Output device Terminal 8 Alarming 8 1 Alarming 1 Bypass voltage failure or bypass fuse SCR failure It will alarm under these conditions 1 Bypass input voltage is wrong 2 Bypass input switch cut off 3 Bypass SCR fuse cut off or burned because of output short circuit or fuse cut off 8 2 Alarming 2 Main input power failure or rectifier input switch cut off It will alarm under these conditions 1 Input voltage is not in the range 184 287 Vac 2 Input frequency is not in the range 47 5 52 5 Hz 2 Rectifier input switch cut off 3 Because UPS is abnormal and cause one phase of three phase rectifier can not work normally please find out the fault 8 3Alarming 3 Battery low voltage It will alarm under these conditions 1 Battery voltage is too low 2 The time battery running is shorter than setting time 8 4 Alarming 4 Battery discharge When battery discharge it will alarm at once after 2 minutes alarm will stop Once battery discharge is up to battery final voltage alarm start again 8 5 Alarming 5 Output overload When load power is bigger than rated output voltage namely more than 100 if load current is over big UPS will alarm When UPS alarm it needs to reduce load capacity Or UPS will turn to bypass we get the time depend on over load value s inverse ratio 8 6 Alarming 6 Temporality bypass working It indicates bypass supply power UPS will turn to normally run statue
23. void mistake 2 langue setup button You can choose one langue ENGLISH CHINESE 3 Help Press this button and ask for some help 4 Back space Press this button and consult all history records 5 ESC Press this button and withdraw from all catalogues and get back to main menu 6 Cancel button Cancel all history records system will demand to enter password in order to avoid mistake 7 Revise the password Revise the systematic operation password In order to prevent operating by mistake the system will require the old operation password You will be asked to verify the new password if the new password input twice is unanimous the 22 new password is set up Gono oo oo Picture 8 13 7 1 Import password interface Some operation will change the present working state of UPS for instance ON OFF system system at this moment will require operator input password otherwise system will not accept any operator s instruction The initial operation password from the factory is 1234 Please consult the 13 6 1 about the operation 13 7 2Time setup interface Press time setup button and enter password This interface is mainly for inputting the new systematic clock the interface is as showing picture 9 1 Year Show the year when the year is not set is displaying When users import new number value from the figure button show the digital value that users input 2 Month Show the month when the y