Home

User Manual

image

Contents

1. button p Move to the upper menu Input MENU Default 1 5000 b SCALE input Shortcut key W 7999 meee yes o o scum Enter the scale value of the input sensor by using the buttons After setting up a value 39999 is changed by pressing mem _ser button E Move to the upper menu Input MENU Default 1000 0 3 3 Auto calibration Shortcut key MB S ms gt mme 7 8 oy rese gt aa After permitting the load weight on the sensor input it by using the buttons After setting up the value BE is changed by pressing mT key E M Move to the upper menu Input MENU W Y Set up the display unit Moving Moving Average Set up the number of movement average uo 0e T I Diaital Setup the digita shit Shift Filter Analo inalog i Set up the analog filter 12 4 1 Unit Unit setup Shortcut key ope y ves p mt 5 gt Fase x22 9 Set up the display unit corresponding to the display value wp o LE o ger E Move to the upper menu Input MENU EESN EH Set up the unit by pressing EH Ej keys Pressing _ser key Mmmm is changed Default NONE Select 79 kinds 5 Input setup 4 8 Shortcut key 222 gt m Lee DER sme ao h iain io Designate and display the display range When it is out the range display the digital limiter value Limi
2. 10 2 1 Pattern Select Shortcut key ops Ls see 5 O Les Select the Pattern POO P15 to use Select the wanted pattern by pressing al E keys Pressing _ser key 29 is changed E I Move to the upper menu Input MENU Default POO POO P15 2 2 Pattern Copy Shortcut key ops LES p m y ALS Select the Pattern POO P15 to copy Select the wanted pattern by pressing EI Ej keys Pressing sr key 9 js changed 2M Move to the upper menu Input MENU Default POO POO P15 3 INPUT Setup 2 8 Shortcut key ove gt zs gt meee BE EN Pase gt i Manual ij 2 al A user enters the characteristic values of the Zera Auto Galibration Gallbration Manual calibration corresponding sensor while looking a data sheet Auto _gailtration Put the actual load weight which can be guaranteed calculate the calibration value and save it 3 2 Manual calibration Shortcut key 399 E Sp omm S s pases y aE S lp Enter the sensor characteristic calibration value 8E Enter the sensor characteristic scale value E p Move to the upper menu Input MENU 3X Move to the MAIN MENU 11 a CAL input Shortcut key ons s s gt ee ES _ Pase calibration gt CAL h Enter the output value of the sensor by using the buttons After setting up a value is changed by pressing
3. ES n case the comparison is selected as the Reference the Replay performs OK and NG according to the reference setting Relay 1 CE ECI p Output Type For the left figure the Relay 1 outputs ON when it is bigger 17005 905 RefHigh I Ref Low than the setting reference g The Type selects High On Low On Range and R Over Range Over As the output type the Output Type sets up Fast Display Decide Graph End M D etc Ref High and Ref Low sets the hysteresis value apply the hysteresis that the each value makes the relay ON and OFF and remove the relay ON OFF repetition phenomenon due to the minimal change of the measured value 4 3 Mode setup menu EN n case of the Relay Channel Mode select the comparison uem sp method of the input source Default Display Display Graph Source Source 18 Display The standard value is regarded as the value displayed on the screen after comparing the relay Graph The standard value is regarded as the graphic output value after comparing the relay Source The standard value is regarded as the input source after comparing the relay 4 4 Type setup menu In case of the limit mode select the output type The output type selects it between HH HI OK LO and LL 1 A y BH Select an item by pressing keys Ew Pressing key after selecting the item MEE is displayed and the setup is completed Limit mode SELECT NL CMM
4. SET Pressing key after selecting the item ME is n case of the reference mode select the output type The output type selects it between High On Low On RANGE and R OVER Select an item by pressing Y keys displayed and the setup is completed Reference mode 4 5 Output type setup Select the output type Output type selects it between Fast Display Decide Graph Pow o End and M D Select an item by pressing keys Pressing key after selecting the item BEEN is displayed and the setup is completed Output Type Fast Synchronize with the sampling time 19 Display Synchronize with the screen output Decide When inputting the decide signal output a result Graph End When finishing drawing a graph output the graph end signal and relay at the same time M D 1005 905 4 6 Ref High and Ref low setup _ReHigh RefLow Input the Ref Hysteresis value The Ref High sets the bigger value of the hysteresis and the Low sets the smaller value HHHigh HHLow set up the hysteresis value of HH on the limit mode The hysteresis can be set up according to the each item of HH HI LO and LL 5 Relay Ach reference setup 10 11 Input the reference of Ach T lw set up the hysteresis value of HH on the limit mode The hysteresis can be set up according to the each item of HH HI LO and LL 6 Relay Bch r
5. as 0x00 OxFF The data comprises the index and actual values of each item and index 2byte and 8 byte or the data of 2 byte Command Code R Request the current value PC DN GI200 D Transmit the current value DN GI200 gt PC 7 2 Current Value Request PC gt DN GI200 Example Device ID No 1 channel No 1 data request 40102R0100D6 L Length Channel Checksum ETX Iu NE ANC eS ee ee The ID and channel is displayed as OxOO OxFF which is the Hex value of 07255 When requesting the current value the data is Index 00 20 7 3 Current Value Transmission DN GI200 PC Example Device ID No 1 channel No 1 data value 492 0 010AD0100 00492 0010327 L Data channel and current value 01 00492 0 STX ID Length Code Channel Index Data Hold Peak Relay ChecksumETX 10 1 O0 E D O0 1 0 0 000 492 0 0 1 0 3 2 744 When transmitting the current value the data comprises Index 00 display value 00492 0 Hold Peak 01 Relay 03 29 Example DN GI200 graphic mode setting In case the process result screen is the same as below on the graphic mode the infection point and relay setting is proceeding with the below order 1 Test Measure p n 40 00kgf ZERO MODE Y 120 00 PEAK mm 4 HOLD 0 X 150 00 0 2 Measured Waveform Analysis According to t
6. memory activation key 10 00 0 guason y cursor display key E cursor moving key GE l all sorts of data input mode conversion key 8IXIT GRAPH START key 3 Caution screen Shortcut key Z When entering the MODE it alarms the caution Pressing 388 enter to the MODE Pressing 39 return to the MAIN MENU 6 2 MODE Screen 1 Mode screen 1 2 Shortcut key ove _5 wes Pressing 2 move to the MAIN MENU E cet up the value of Ach ww e es Set up the value related to the relay output C Set up the hold function Page Page peer 5ew set up the function of a SD memory 2 Mode screen Shortcut key 39 x9 p Se Set up the basic function ZI up the graph Waveform u SYStlel n EH Set up the basic function 2 6 3 INPUT 1 Selecting INPUT channel Shortcut key Mone gt ss y eee When setting up the INPUT this is an Ach Bch selection screen Move to the upper menu MODE _ ENT Move to the MAIN MENU u Ach O Select the Ach channel 2 INPUT setting 1 8 Shortcut key 2922 gt m apum p 3 ES Move to the upper menu select the INPUT channel cono B oo B FN Move to the main menu E ee Select the saved pattern Pattern PES p Copy the saved pattern Bensor ovr Display the sensor voltage Pattern Copy
7. 2 OUT RY2 A OK 15 3 OUT RY3 A LO 16 4 OUT RY4 B HI 17 5 OUT RY5 B OK 18 INPUT PO 6 OUT RY6 B LO 19 INPUT P1 7 OUT RY7 BUSY 20 INPUT P2 8 OUT RYS GRAPH END 21 INPUT P3 9 OUT COM N24 PLC 22 INPUT 10 INPUT GRAPH 23 INPUT HoldSave SD 11 24 INPUT MORY SD 12 25 INPUT Graph Hold 13 26 INPUT P24 PLC 5 2 DIO HRS 40Pin Pinmap HRS TML HRS TML I O FUNCTION I O FUNCTION NO NO NO NO 1 A1 OUT COM N24 PLC 2 B1 INPUT P24 PLC 3 A2 OUT RY8 GRAPH END 4 B2 INPUT Graph Hold 5 A3 OUT RY7 BUSY 6 B3 INPUT MORY SD 7 A4 OUT RY6 B LO 8 B4 INPUT HoldSave SD 9 A5 OUT RY5 B OK 10 B5 INPUT 11 A6 OUT RY4 B HI 12 B6 INPUT P3 13 A7 OUT RY3 A LO 14 B7 INPUT P2 15 A8 OUT RY2 A OK 16 B8 INPUT P1 17 A9 OUT RY1 A HI 18 B9 INPUT PO 19 A10 20 B10 INPUT GRAPH 21 A11 22 B11 23 A12 24 B12 25 A13 26 B13 27 A14 28 B14 29 A15 30 B15 31 A16 32 B16 33 A17 34 B17 35 A18 36 B18 37 A19 38 B19 39 A20 40 B20 5 3 DIO HRS 30Pin Pinmap HRS TML HRS TML I O FUNCTION I O FUNCTION NO NO NO NO 1 A1 IN COM P24 PLC 2 B1 IN COM P24 PLC 3 A2 INPUT PO 4 B2 INPUT P1 5 A3 INPUT P2 6 B3 INPUT P3 7 A4 IN
8. PUT 8 B4 INPUT HoldSave SD 9 A5 INPUT Memory SD 10 B5 INPUT Graph Hold 11 A6 INPUT GRAPH 12 B6 INPUT Graph Save 13 A7 INPUT 14 B7 INPUT 15 A8 OUT RY1 A H H 16 B8 OUT RY2 A HI 17 A9 OUT RY3 A OK 18 B9 OUT RY4 A LO 19 A10 OUT RY5 A L L 20 B10 OUT RY6 B H H 21 A11 OUT RY7 B HI 22 B11 OUT RY8 B OK 23 A12 OUT RY9 B LO 24 B12 OUT RY10 B L L 25 A13 OUT RY11 BUSY 26 B13 OUT RY12 GRAPH END 27 A14 28 B14 29 A15 OUT COM N24 PLC 30 B15 OUT COM N24 PLC 5 3 Time Chart 1 1100ms 0 100ms 0 it BEES MEMORY SD en E 2 GRAPH BUSY OUT 5 4 INPUT OUTPUT Circuit Diagram P24 INPUT COM INPUT OUTPUT A Inside of meter me gt OUT COM 6 Name and Function of Display Screen 6 1 Main Menu 1 SINGLE display screen _ mars display conversion key GRAPH SINGLE Display on amp off state of ER 3 20 relay Hu output 7 Pressing the corresponding key it is possible to set up a value immediately Ea digital zero HOLD PEAK operation status monitor When changing the operation status Homm BEHK 2 GRAPH display screen GRAPH y T wonc assi display conversion key GRAPH SINGLE 200 00 Ach BN digital zero key PEAK HOLD 0 80839 l data SD
9. User Manual Model DN GI200 3 AD ba r 1 L palig ATT a INDICATI 5 ia LITE DACE Li DACELL CO LTD Address 681 1 Cheoksan Ri Nami Myeon Cheongwon Gun Chung Buk Korea TEL 82 43 260 2242 FAX 82 43 260 2245 nttp www dacell com E Mail info dacell com Thank you for choosing our product The User Manual explains how to use and how to be careful of the product Wrong handling may cause safety accidents and damage of the product Therefore you must read the user manual before using the product and use it correctly If any issues occur while you use the product refer to the user manual or contact the technical department of our company Details of the user manual can be changed without any notice according to a version of the product 1 Characteristic The product amplifies the output signals of various sensors converts them into digital and then indicates them as graphs on a LCD the graph data are saved on a SD memory and analyzed in a PC Details of the characteristics are as below 1 1 A D Conversion Method A D device is adapted which is converting the input signals from a sensor over 1000 times per second 1 2 Calibration Method Two methods are available that one is an auto calibration by an actual load standard weight and the other is a manual calibration by inputting the rated input value of a sensor 1 3 Various Input amp Output Functions The internal paramete
10. dication Comply with the digital scaling Input calibration rage 0 1 3 5mV V CAL Display load rage 99999 499999 Nonlinearity Within 0 02 FS 1digit When inputting 3mV V 23 C 5 C Analog filter Select it between 10 100 and 1000 Hz 3 2 Input Section B ch 3 3 General Specifications Backup The setting data data zero value amp display screen is saved in a flash ROM Data setting method The operation of each setting menu and touch panel Power AC100 AC240V 10 50 60Hz Consumption power About 50VA maximum Dimension 96mm W x 96mm H x 160mm D Used temperature humidity range 0 40 C 35 85 RH non dew condensation Weight About 1 0kg 4 Front and Rear Panel GRAPHIC INDICATOR UTWCELL gr DN GI200 4 1 Front Panel 4 3 Mounting drawing 1 Touch panel LCD Display amp display the data D SD memory Save the measured data 4 2 Rear Panel 3 DIO 4 232 communication panel COM TXD RXD 5 Sensor input terminal CUTTING 6 CAL FILTER SIZE 92 7 Ach digital input Sensor input terminal Encoder 9 Bch DIGTAL input Power input terminal AC 907220V 11 GND terminal 5 DIO instruction 5 1 DIO D SUB 26Pin HD Pinmap Add the hold data save input and change the input pin PIN NO I O FUNCTION PIN NO I O FUNCTION 1 OUT RY1 A HI 14
11. eference setup 10 11 1005 905 ENSEM noh HHLow LOHigh 95 omg rcm ora c3 us Reset The hysteresis can be set up according to the each item of Input the reference of B Ch set up the hysteresis value of HH on the limit LL High HH HI LO and LL 20 6 6 Hold 1 Hold 1 3 Shortcut key MENU ERU gt iin Pattern Select Select the saved pattern Pattern Pattern Copy Copy the saved pattern Select Level Start Pattern Start Condition Set up the starting condition Copy Condition _ Type em Set up the Hold type 1 1 Pattern Select Refer to 6 3 Input Pattern Select 1 2 Pattern Copy Refer to 6 3 Input Pattern Copy Start 1 3 Start Condition Condition SELECT EN CEN E This is not used currently Riging Edge Trailing Edge Set up the Hold Start Condition 1 4 Type Type ES Set up the Hold Type The Hold type can be set up as below Normal Sample Area Peak AreaValley AreaPeakVall P P D Time Time Valley Time Peak Vall Level TimeP Levels Time V Lev TimeP V MaximalValue MinimalValue Infection P zl 2 Hold 2 3 Eg The menu is not used currently Detection Detection Minimal Value Detection 3 Hold 3 3 Inflection pos Range b Set up the inflection point detection range Inflection lecto B we Set
12. etection set up the output for a result n order to distinguish the measured result between OK and NG use the inflection point value and X axle maximum value From the replay setting decide Ach by the standard of the load value of the inflection point and decide B Ch by using the deflection maximum value od
13. he measured result value select the detecting method to decide OK or NG In case of the above decide it by using the inflection point detection r3 Interval ChA Start Inflection Inflection ime Level Condition Range Start Start Type ChB Start Inflection Leve Condition Before Inflection n case of the above the inflection point detection is done by shown as the above and the graph start condition is set as E S D S n addition set up ChB Level on the GRAPH 4 6 screen as 100 00 Start Condition Riging Edge and begin to measure from the point that the value of X axle is 100 00 For the inflection point and start condition decide the proper value by repeating 1 Test Measure several times 30 3 Inflection Detection Detecting the inflection point according to the setting of 2 the screen pops up as below GRAPH 40 00kof ZERO MODE Abch ch PEAK HOLD 0 0 105 200m 10 33kgf 105 20mm on the middle of the bottom screen is the inflection point detection location and they are displayed as green X on the graph 120 00mm of the right center indicates X axle maximum value which represents the maximum movement distance 3 Detection Waveform Screen Setting In order to make the inflection point and start condition setting more clear change the start points of XY axles and end point E n 40 00kgf ZERO MODE Abch 100 00 s When completing the setup for the d
14. inflammable gas or steam and dust must not be avoided for installation e Ground terminal GND must be grounded e Make sure that the wiring of a wattmeter or with lots of noise should be wired separately e For an analog output surely connect a load over 10KQ without fail and do not connect an inductive load e For a sensor cable you must use four wire two pair shield cable In case of the wiring with lots of noise it must be wired separately 2 2 Cautions for Use e As the product is a precision instrument to measure physical quantity be careful of having an effect of noise If required select an optional noise block method Main noise source wiring of a wattmeter wireless equipment electric welder motor inverter etc e Do not remodel the product for other purposes other than measuring e For the no load condition and actual load inputs wait until it is stable without wobble and then input them e Pressing a touch key under unstable condition causes a calibration error e Do not press the touch key arbitrarily in use and refer to the function and input method of the touch key 5 Name and function of display screen 3 Specifications 3 1 Input Section Ach Sensor power DC10V 5V 2 5V 10 output below 120mA Conformance sensor Various sensors four wire system of a strain gauge type Parallel connection is available for 3500 strain gauge type sensor up to 4 units Input signal range 3 5mV V 3 5mV V In
15. on the figure it is converted to the key input D screen and the values of each point can be set up PEAK PL HOLDM 0 0 Zo 3 GRAPH 3 6 Interval al Time Set up the graph start delay time Graph Disp Sete b Graph start method Interval Time Free Run Repeat the graph continuously Start Type EN Ext Signal Get started by the external start signal Start Level Start the graph by the set level E S W S Start the graph by the external signal and setup level of Ach E S D S Start the graph by the external signal and setup level of B Ch E S W S DZ Start the graph by the external signal and setup level of Ach and reset it when starting B Ch distance value 4 GRAPH 4 6 ChA pn Level Set up the start level of Ch A Graph Disp EN j ChB Lee Set up the start level of Ch B Level Condition Start Condition Set up the start condition of each channel ChB Start Level Condition Start condition Pass When passing the set start level Riging Edge When passing up the set level Trailing Edge When passing down the set level More In case of bigger than the set level Less In case of smaller than the set level 5 GRAPH 5 6 Ey When the hold type is the area mode on the graphic screen EJ MENU set up the comparison range Area High Area Low Each item is indicated as the coordination values of the ChB rm graphic screen and the digits below
16. or Relay keys E Pressing key MEME is displayed and it is set e ul Move to the upper menu Input MENU Ew SIEF T T I T Limit Mode Relay Mode 3 Relay operation setup 2 9 11 EN nuca Select the input source Ach Bch Signal Off u Mode ECH ECH Select the relay output mode Display Graph Source ciao Set up the relay comparison method a es Set up the relay output type a OutputType Set up the output speed HHHigh Hilo Set up the upper and lower limit values for the comparison Each separate setup for eight relay units is available 3 1 Input setup Select the input by pressing keys Select it by pressing the key between Ach Bch LOAD amp DIST E and Signal Bch Pressing key M is displayed and set ut Move to the upper menu Input MENU Default Ach Ach Bch LOAD amp DIST Signal 16 In case of selecting Ach or Bch set up each relay in accordance with 4 LOAD amp DIST does not have a setup In case of the Signal refer to 3 2 as below 3 2 Input signal EN In case of setting up the input as the signal the relay can E gl output the internal setting signal The output signal is SD Busy Graphic End Sync etc Select the output signal by selecting the mode menu Select the input by pressing keys Select it by pressing the key between Busy G
17. r can be set up by using the touch of the front panel and the auto zero function can be performed On the rear panel RS 232C connection terminal relay contact output terminal graph memory pattern select hold zero input terminals are available 1 4 Replay output function Display the measured the analog input and output the result comparing the set HH HI values and LO LL values to the relay contact signal 1 5 Data Preservation Function In case of a blackout or the electric power is cut off the inputted data is preserved because the setting values such as zero scale relay etc are stored in a flash memory device 1 6 Display Method amp Control Function of Response Speed Two types digital filter and analog filter for a sensor input are adapted in order to obtain the required response speed according to the digital display and purpose of the front panel 1 7 Various Data Output As an option the analog power output 10V BCD BIN output serial interface RS 232C 4 20mA and 0 20mA analog current output can be used 2 Standard built in Product 1 Main body 2 Instruction manual 2 1 Cautions for Installation and Use For a safe use of the product please read and be familiar with the following cautions e Make sure that the installation site has no water e The site of installation must be free from vibration impact high temperature and humidity dust and air containing salt and ion e The sites containing
18. raph End and Sync Graph End n Pressing key BEEN is displayed and set ync V A al Move to the upper menu Input MENU Default Busy Busy Graph End Sync 4 Relay channel mode operation EZ n case of selecting the relay input as the Ach or Bch the detailed operation can be set E ELS Each operation is performed differently according to the choice of the comparison The comparison is divided as two operations limit and reference Ea Select the input by pressing Y keys Select it by pressing the key between the Limit and Reference keys Reference NENNEN Pressing key HEN is displayed and set ul Move to the upper menu Input MENU Default Limit Limit Reference 17 4 1 Limit comparison n case the comparison is selected as the Limit the Replay EN NH lt performs OK and NG according to the set HH HI LO and LL values in advance OutputType For the left figure the Relay 1 performs the output as the HH 10 58 905 HHHigh B HH Low Limit The Type selects HH HI OK LO and LL As the output type the Output Type sets up Fast Display Decide Graph End M D etc HH High and HH Low sets the hysteresis value apply the hysteresis that the each value makes the relay ON and OFF and remove the relay ON OFF repetition phenomenon due to the minimal change of the measured value 4 2 Reference comparison
19. stopped Model When the data exceeds the set value it is saved from the front default StopWrite Mode1 2 SD setup 2 2 Shortcut key aos ss gt ES ES Pase gt EL n Ei Setup Late amp Time File Save setting Date amp Time Setting Set up a date and time Setup File Load Setup S File Delte 14 2 1 DATE amp TIME setting Shortcut key M2 gt xs Lue y 808m eese PS h Set up the values year month date hour minute amp second by using the keys How to enter Using L2 keys enter the values after selecting the wanted value red color Pressing key it is Clear 0 Pressing F key mamasa is changed E Move to the upper menu SD Setup MENU 6 5 Relay 1 Selecting the Relay Shortcut key _ E gt 8 gt Mw Move to the Relay setting screen A Move to the upper menu MODE u MENU Pattern z Move to the MAIN MENU 2 Relay mode setup 1 11 channel Ere Relay Disp MENU W Move to the MAIN MENU Pattern E ta u Move to the upper menu Select the Relay Ach Bch Select the saved pattern b Copy the saved pattern ik b Select the Relay display method 2 1 Pattern Select Refer to 6 3 Input Pattern Select 2 2 Pattern Copy Refer to 6 3 Input Pattern Copy Lo 2 3 Relay Disp ES Select the Relay display method by pressing the limit
20. te by pressing BI Ej keys Pressing _set key 313 8 is changed E p Move to the upper menu SETUP MENU Default 10 10 0 5 0 2 5 1 0 0 5 1 2 Display Rate Shortcut key 298 5 x58 gt m p IE y Sie 1 3 Sampling Rate Select the rate by pressing a E keys Pressing T key Mmmm js changed Move to the upper menu SETUP MENU 2000 CFS OPS Default 1000CPS 4000 2000 1000 500 200 100 50 20 10 1000 CPE 1000 CPS SET X Depending on the choices the graph data storage maximum time is changed 2 Setup 2 5 Shortcut key ons gt 8 gt Fase gt x3 Digtal ZEKO l d When turning the power off the data is set to be Backup stored Whenever pressing somo key Maw Digital zero value change is stored Mmmm js changed _ Move to the upper menu MENU 20 6 9 System Basic function setup 2 Shortcut key MOM pE gt ese gt seem Initialize u me p All set data is initialized 1 System 3 4 Initialize Initialize Waveform Setup Initialize Initialize Output ALL 1 2 Initialize ALL Shortcut key W E pws gt vtm eue o gt TAE All stored data is initialized 3X When initializing all stored data is deleted Zt 7 Summary of Communication Protocol 7 1 Communication Protocol eee ee eee m L 2 Output device ID 00 FF Indicate ID from 0 to 255 and the Hex value
21. ter HI sen set up the minimum renewal range of the display 999999 0 value Limiter LO 5 1 Digital Limiter HI Shortcut key woe xes S20 meme 5 om 35 ERES h Enter the Limiter HI value using the buttons After setting up the value 3399 is changed by pressing _set button E l Move to the upper menu Input MENU Default 99999 0 99999 99999 5 2 Digital Limiter LO Shortcut key mwj y s p mee 5 BE 35 Eee h Enter the Limiter LO value by using the buttons After setting up the value 99k9 js changed by pressing E EN fea EN _ser button _ Move to the upper menu Input MENU Default 99999 0 99999 99999 lo 5 3 Step Step width Shortcut key OBE ps pomme y ease x 3 57 Select the step width by pressing a E keys Pressing _ser key Mf is changed E I Move to the upper menu Input MENU Default 1 1 2 5 10 6 4 SD Setup 1 SD Setup 1 2 Shortcut key W 5 mew y soseem f eae Set up the data save method SD Write Waveform Mode File Delete Waveform Available Data ap Menor Overvrite Made 1 2 Overwrite mode Shortcut key 2 gt ses lm Ea Tee Set up the mode by pressing EH Ej keys p Pressing ser key is changed stoplirite Move to the upper menu SD Setup MENU 1 1 _ geste When the data exceeds the set value it is
22. the decimal point are displayed according to the set decimal places 24 oe woe n case of the above setup the graph screen indicates this 100 00 area comparison screen 6 GRAPH 6 6 After completing a graph on the graph mode check a result by expanding a characteristic section of the X axle Graph Mag Graph Mag EN JOD tar Set up the graph expansion start point SIM MN n Set up the graph expansion On Off setup Set up the graph expansion end point opem woe This figure indicates the result in case of turning the graph 100 00 expansion on under the above setup Display the previous screen and expanded screen in turn by HOLD 0 pressing 40m key on the figure 6 8 Setup 1 Setup 1 5 Shortcut key 2992 gt gt se Lm Set Select the meter operation Displav m _ hate Select the cycle to renew the display value Meter sampling Setup Rate sampling u MN Select the storage maximum time of X axle Display Rate Example When setting up 4000 CPS it is 1 sec and when setting up CPS it is 2 sec Zo 1 1 Meter Setup Shortcut key MODE DES _5 Page EBENE gt sets Select the channels by pressing al E keys When pressing r key Me js changed Move to the upper menu SETUP MENU Default Ach Ach Bch 2 ch Wave A Wave B W amp D Shortcut key 39 o0 paseo gt se EXE Select the ra
23. up the detecting time B ange Inflection Infection After Set up the detecting time A etore Inflection S tart H e 2 H a Start detecting the inflection point Inflection Inflection Range Range Input the change vale R on the figure to detect the inflection point Inflection Inflection Before Before Input the inflection point comparison standard time B on the figure Inflection Inflection After After Input the inflection point detection change time A on the figure Inflection Inflection Start Start The input level condition to start the inflection detection 2A 6 7 GRAPH 1 GRAPH 1 6 Shortcut key MENU eS gt itl z Pattern Graph Disp EN Select Pattern Pattern a Copy Select Pattern Copy Pattern 1 1 Pattern Select Select Refer to 6 3 Input Pattern Select Pattern 1 2 Pattern Copy Copy Refer to 6 3 Input Pattern Copy 2 GRAPH 2 6 b Select the saved pattern Copy the saved pattern pue Set up the minimum maximum values of the XY axles on the _ Y Min NEL Y Max _u X Min _ Mt X Max graph screen b Set up the Y axle display start point value b Set up the Y axle display maximum value Set up the X axle display start point value Set up the X axle display maximum value The value setup is available by using the touch keys on the graph screen TAE wok Touching C

Download Pdf Manuals

image

Related Search

Related Contents

HP Saw 438A User's Manual  Manual do Usuário  取扱説明書[DS-PK3/PK4] (2.60 MB/PDF)    MetalTech I-CISGR Instructions / Assembly  ET STEVIE WONDER = COMMENTAIRE SUR LE TRAITÉ  AXIS 2120 User`s Manual  manuale - MAIR systems  Service Manual APX 7000 - Carl Valentin Drucksysteme  TCSESM_Installation Guide_S  

Copyright © All rights reserved.
DMCA: DMCA_mwitty#outlook.com.