Home
        Photovoltaic MULTI-TRACERS Operations & Maintenance
         Contents
1.   an onsite calibration using the MCAL software  See the instructions for running  MCAL in Section 4    RD 1600 3200 Operations Manual page 7    2 3    2 4    The File Menu  Four active sub menus may be accessed from the File menu     About   shows information about the MTRACE software program   Load Configuration   user may search for and load a previously saved file   Save Configuration   user may designate a location and save a configuration file  Exit   user may exit MTRACE    The View Menu  Four active sub menus may be accessed from the View menu     Active Channels   displays status data for active channels    Temp  amp  Aux   displays data from connected temperature irradiance sensors   Error Log   displays all Mtrace errors to date  Can be cleared    Last Curve   displays last l V curve taken of the specified channel     These windows may be selected  moved  or re sized using the mouse and normal    Windows techniques     2 5 The Execute Menu    Three active sub menus may be accessed from the Execute menu     Calibrate   offers the user the opportunity to Quit MTRACE and run the calibration  program MCAL  Note  MCAL and MTRACE cannot run at the same time    Reset Hardware   will re establish communications between the PC and the Multi   Tracer and re initialize the Multi Tracer  Note  This is done automatically each  time MTRACE is started    Take Curve   allows the user to manually take an l V curve on one or more modules     2 6 The Configuration Menu    Eight activ
2.  A description of these units is given in Section 1 followed by  instructions for the operating software in the Section 2  The operating software will be  the information most often consulted after initial setup and calibration of the hardware   Section 3 contains instructions for connecting the hardware and using the calibration  routines  Maintenance and Troubleshooting techniques are included in Section 4     Performance specifications for the Multi Tracers are provided in Appendix A   To monitor PV module performance with a Multi Tracer     1  Become familiar with your unit and review all warning statements   Think Safety    2  Start the PC  install  and setup the operating and calibration software    3  Make connections from the modules to the Multi Tracer  Connect pyranometers  and thermocouples  not provided  to the marked inputs    4  Connect the PC to the Multi Tracer using the Ethernet  USB  or serial port    5  Run the MCAL calibration software    6  Run the MTRACE configuration software    7  Begin data collection     Instructions for these steps are described in this manual     Daystar Multi Tracers are built to specification by Raydec  Inc   8210 La Mirada  NE  Suite  700  Albuquerque  NM 87109  505 292 5002     RD 1600 3200 Operations Manual page iii    WARNINGS    IMPROPER USE OF THIS INSTRUMENT CAN PRESENT AN ELECTRICAL  SHOCK HAZARD THAT CAN CAUSE DEATH OR SERIOUS INJURY     THIS INSTRUMENT SHOULD ONLY BE USED AS DESCRIBED IN THIS  OPERATIONS MANUAL   ke    
3.  I V Curve Files  amp  Formats  The MTRACE l V curve files use the DS Tracer    IVA    file format  File names are    created with a time and channel stamp     mmddhhmm nnc    where     mm is the month    dd is the day of the month    hh is the hour    mm is the minute  and   nn is the channel number of the I V curve    c is a single character file designator defined by the user  a  b  c  etc       Each line of the file starts with a unique ID followed by a space  The ID and space are  used to decode the file  Note  Line starting with the letter  A  are considered auxiliary data  lines and are not recognized as part of a standard DS  Tracer file  Therefore  other  programs such as IVPC for the DS Tracer can read these files  but will ignore the auxiliary  data  The format is     F  MTrace    D Date   T Time   S Site   B Sub system   M Module ID   P Module Temperature Before l V Curve  Q Ambient Temperature Before I V Curve  R Irradiance Before l V Curve  X Channel Number   H Short circuit current      Open circuit voltage   C Current at peak power   K Voltage at peak power   W Peak power   L Fill factor   A1 AUX 1   A2       2          AUX3   A4 AUX4   A5   AUX5   A6 AUX6   A7 AUX7   A8   AUX 7    A9 AUX TEMP 1  A10 AUX TEMP 2  A11 AUX TEMP 3    RD 1600 3200 Operations Manual    A12  A13  A14  A15  A16  A17  A18  A19  A20  A21  A22  A23    AUX TEMP 4   AUX TEMP 5   AUX TEMP 6   AUX TEMP 7   AUX TEMP 8   System Area   Aperture Area   System Efficiency   Aperture Efficiency   M
4.  Input  amp  Temperature Connections  Auxiliary thermocouple input connections are the same as the module thermocouples     They use the same circuitry and have the same limitations and specifications  These inputs    may be used for any temperature measurements such as ambient air temperature     The auxiliary inputs are commonly used for pyranometer measurements  Refer to  Appendix A for detailed specifications  In either case  these inputs use standard BNC  connectors  It is recommended that coax or shielded cable be used  This will minimize  noise in the measurements  These inputs are quasi differential with a 10 K ohm resistor  from the negative  shield  input to the Multi Tracer ground  Therefore signal sources such  as reference cells and pyranometers may be connected if grounded or floating  However   grounded signals typically have less measurement error due to noise  All inputs must    remain within the common mode range of the Multi Tracer as specified in Appendix A     RD 1600 3200 Operations Manual page 25    4 0 Calibration  Maintenance   amp  Troubleshooting    4 1 Calibration  Calibrate the Multi Tracer using the MCAL EXE software supplied with the Multi     Tracer  This software provides a step by step guide to the calibration  Complete calibration  details are supplied in the help screens of the MCAL program  In general  a full calibration  is recommend every 6 months  more often if the Multi Tracer is operated over varying  temperatures or if it is moved or
5.  shipped  MCAL is also a Windows based application and is  installed by running the  Setup  file on the MCAL installation disks     The basic steps of calibration are    e Software calibrate each module voltage   e Software calibrate each module current   e Software calibrate each auxiliary input     Equipment needed for calibration includes      Voltage source with output near the full scale voltage of each module     Current source with output near the full scale current of each module     Low voltage  mV  source for calibrating auxiliary inputs     By following the step by step procedure outlined in the MCAL program  a complete  unit calibration can be done in less than 2 hours  Since each module input must be  calibrated independently  the calibration goes much more quickly if precision voltage and  current sources are used  This allows constant inputs and avoids having to re type a new    value into the program for every module     4 2 Exterior Cleaning  The exterior surface of the Multi Tracer should be cleaned with a soft damp cloth only     Do not use detergents  abrasive cleansers  or other solvents  Turn the Multi Tracer OFF    and disconnect AC power and all module and signal inputs before cleaning     4 3 Transportation  The Multi Tracer should be treated with the same care used for a desk top computer     Specifically         Do not bump  drop  or otherwise jar the unit  particularly during operation     RD 1600 3200 Operations Manual page 26      Double box and 
6.  si rnaar      16  CAUTIONS 16  3 1 Installation Procedure                     sse 17  3 2 Ground                                                                   18  3 3 PV Module Connections                                             19  3 4 Voltage  Drop S TT i  onn nl m te tete it ed tS 21  3 5 Module Thermocouple                                                                           22  3 6 Computer Connections                  ssssssssssssseseeene mme 22  3 7 Auxiliary Input  amp  Temperature Connections                                           24  4 0 Calibration  Maintenance   amp  Troubleshooting                                             25  4 1 Gallbrationcs   4i dett                      ene 25  4 2 Exterior Cleaning corrr PRI bas heute eee ee 25  4 3 Transportation    od be dac Lee pec ep d e e a ERR e 25  4 4 Troubleshooting s ri                 e reu e pde tue 26  APPENDIX A   GENERAL SPECIFICATIONS                                                     1    APPENDIX B   USB Drivers              itineri            de E Cd dd a ERE REO Du Rai x a EN aa 1    page i    RD 1600 3200 Operations Manual page ii    Summary    The Multi Tracer is an integrated measurement system for testing multiple  photovoltaic  PV  modules under natural or simulated sunlight  It is controlled with  MTRACE software operating on an IBM compatible computer  PC   This manual  contains instructions for setup  calibration  operation  and maintenance of either model  RD 1600 or RD 3200 
7.  the network connection  Therefore  it is recommended that the USB or serial RS 232  connection be used temporarily to change the Multi Tracer network settings     The following values may be set for the Multi tracer     IP Address  1      10 0 0 10   Netmask  I E  255 255 255 0   Gateway Address  optional     The IP address and net mask must be assigned  unless using DHCP   The gateway  address is only used if the controller computer and Multi Tracer do don t operate on the    same network  Therefore  the gateway value is typically left blank     USB    If the controller computer is located near the Multi Tracer a USB connection may be  used  Even if Ethernet is used  the USB connection may be needed to setup the network or  for calibration  For example  when calibrating it is essentially a requirement that the control  computer and Multi Tracer be near each other  However  a notebook computer could be  used temporarily if the control computer is located some distance from the Multi Tracer     In order to use the USB connection  the USB drivers must be installed as described  in Appendix B     RS 232 Serial  Serial RS 232 ports  commonly called COM ports   may also be used  The Multi     Tracer uses COM port 1 for control  see back panel  while the MTrace and MCAL software  may use any COM port from 1 to 16  Use the port settings dialog in MTrace and MCAL to  set the appropriate COM port used by the control computer     RD 1600 3200 Operations Manual page 24    3 7 Auxiliary
8. THIS INSTRUMENT MAY PRESENT AN ELECTRICAL SHOCK HAZARD THAT  CAN RESULT IN DEATH OR SERIOUS INJURY IF THE FOLLOWING PRECAUTIONS  ARE NOT FOLLOWED       THIS INSTRUMENT MUST ONLY BE USED FOR TAKING ELECTRICAL  CURRENT AND VOLTAGE  l V  CURVES OF PHOTOVOLTAIC  PV   MODULES       THIS INSTRUMENT MUST NOT BE USED BEYOND ITS OPERATING RANGE  OF VOLTAGE  CURRENT  AND POWER AS DESCRIBED IN THIS MANUAL  AND SHOWN AT THE INPUT CONNECTIONS ON THE MULTI TRACER   S  PANEL       THIS INSTRUMENT MUST BE GROUNDED AS DESCRIBED IN THIS  MANUAL       THIS INSTRUMENT MUST ONLY BE USED BY PERSONNEL WHO HAVE  EXPERIENCE HANDLING HIGH VOLTAGE DC PHOTOVOLTAIC SOLAR  MODULES       THIS INSTRUMENT IS INTENDED FOR USE IN AN AIR CONDITIONED  ENVIRONMENT       THIS INSTRUMENT MUST NOT BE USED IF IT IS NOT FUNCTIONING AS  EXPECTED  REFER TO USER MANUAL FOR PROPER OPERATION      e MULTI TRACERS ARE HEAVY   USE TWO  2  PEOPLE WHEN LIFTING OR  MOVING THE UNIT TO AVOID BACK OR MUSCLE INJURIES     RD 1600 3200 Operations Manual page iv    NOMENCLATURE    l V    Current Voltage  PV Photovoltaic   V Voltage     Current   A Amperes or Amps  Hz Hertz    Voc   Open Circuit Voltage  The maximum voltage a photovoltaic cell can  generate with the output terminals open circuited     lac Short Circuit Current  The maximum current photovoltaic cell can  generate with the output terminals shorted    RD 1600 3200 Operations Manual page 1    1 0 The Multi Tracer    This manual provides instructions for the proper set up an
9. a file contains all data channels for that particular time or  average interval along with a time stamp  An example data file created on March 16  2007  is shown below  It contains the first 15 averaged data values after which the voltage   current  power  and temperature of each connected module would be written  A description    of each field in a data line is given below the example file     MT070316 MTD  file name  not included in file   07 03 16 6 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 6 15 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 6 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 6 45 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 7 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 7 15 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 7 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 7 45 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 8 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0     07 03 16 8 15 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0       RD 1600 3200 Operations Manual    1                                      Description  year   month   day of month  hour   minute   AUX Input 1  AUX Input 2  AUX Input 3  AUX Input 4  AUX Input 5  AUX Input 6  AUX Input 7  AUX Input 8  AUX TEMP 1  AUX TEMP 2  AUX TEMP 3  AUX TEMP 4  AUX TEMP 5  AUX TEMP 6  AUX TEMP 7  AUX TEMP 8    V1  Voltage for channel 1    Current for channel 1    T1  Temperature for channel 1    Power for channel 1     11      1  V2  12   T2  P2    page 13    RD 1600 3200 Operations Manual page 14    2 6 2
10. channel     e Do not connect the Multi Tracer to any PV module with a short circuit current  Isc   greater than the maximum current for the that input channel       Module input channels have different ratings  The input voltage  current  and  power ranges are printed on the back of the Multi Tracer next to each connector   Do not exceed any of these ranges  Specifically  note that the product of the  maximum voltage and current far exceeds the power range  NEVER exceed the  power range       Connecting a PV module with reverse polarity will short the PV module even if  the AC power is OFF     RD 1600 3200 Operations Manual page 17    3 1 Installation Procedure    CAUTION    The Multi Tracer is intended for installation indoors  In general  the unit should be  operated at room temperature  25  C   The full operating range is listed in Appendix A   More accurate measurements are made if the Multi Tracer is operated at the temperature  used during calibration  The Multi Tracer is packaged for desk top mounting although  optional rack mount ears are provided  Note  When rack mounting  use equipment slides to  support the weight of the unit  In all installations  leave a minimum of one foot clearance  both front and back for airflow  Special care should be taken to ensure proper grounding  as described in the following section  Proper grounding helps prevent fire and shock    hazards  It will also aid in minimizing noise in measurements     The basic connections of the Multi Trac
11. d use of the RD 1600 or the  RD 3200 Multi Tracer photovoltaic l V curve tracer  These units provide an integrated  measurement system for testing multiple photovoltaic  PV  modules under natural or  simulated sunlight  The Multi Tracer is designed to interface with an IBM compatible  computer  PC   Some of the features offered are     e Peak power  fixed voltage  or user set voltage profile electrical loading of PV  modules     e Periodic l V curve measurement of attached modules     PV module voltage  current  and temperature data acquisition   e Pyranometer and ambient temperature data acquisition       Rugged MOSFET loads with individual over voltage and thermal cut off  protection on each load transistor  The RD 1600 can dissipate 1200 W steady   state  The RD 3200 can dissipate 2400 Watts     Figures 1 and 2 show the front and back panels of an RD 1600  The RD 3200 is similar in  appearance but housed in two rack mountable cases        Figure 1  Face plate of the Multi Tracer     RD 1600 3200 Operations Manual page 2       Figure 2  Back plate of the Multi Tracer      1 1 Electrical Loading  Each Multi Tracer has separate and isolated inputs for a number of PV modules     Because each unit is built to custom specifications  please consult the specification sheet  your specific unit  Under software control  the Multi Tracer independently loads each  module and operates each at its peak power point  at a set voltage value  or at a user   defined voltage profile  For examp
12. daystar  inc   daystar  inc     dh  daystar  inc     Energy Engineering       Photovoltaic  MULTI TRACERS    RD 1600        RD 3200    Operations  amp  Maintenance  Manual    Version 4 2    December 2007    RD 1600 3200 Operations Manual    Table of Contents                OfO oE S e a ORI i  SUIMIMANY aaa aE E AE AE I RON EE EON EAE O ENEE ii  WARNI N G O ern aire          eter      DH ee E etn             ae iii                                                a ar aaao        zer bxsc esteem rar E dE cime cie iv  1 0  The M  lti Tracer          netter enn Oe           a aa aa 1  1 1 Electrical Loading    ilr te tee HL ed eei te De eee dh 2  1 2 GurVe  Bracing   ci oae tint te                           ob      artus 3  1 3 PV Module Data Acquisition                        sss 3  1 4 Auxiliary  Inputs      tet to co tese eet A ee eti 4  2 0 Operating                                                         rawani aa Kakanin aiik nena 5  2 1       16   1 6                               5  2 2 Software Installation  amp  Operation                                                          5  2 3 The File Menus   iiu ne tete               7  24 The View  Menu           notare endet ice tne dest begun enin it nena eed e 7  2 5 The Execute                           nennen 7  2 6 The Configuration Menu                             7  2 7 The Windows Menu                                                  10  2 8 File Types  seen dd ede         11  3 0  Installing Your Multi  Tracer  taani
13. dule while the host PC may be located hundreds of feet away if necessary if using    RD 1600 3200 Operations Manual page 4    ethernet   Caution  Do not exceed temperature limits of the Multi Tracer    Some of the basic analog measurement features are     Module voltage using a 4 wire connection and resistive voltage dividers     e Module current using 50 mV current shunts  at full scale      Module temperature using type T thermocouples     A 16 bit A D with a nominal  5 V input range is used for data acquisition in the Multi   Tracer  Voltage measurements are made using resistive voltage dividers and are wired  differentially  These signals are multiplexed and sent to the A D board  The current shunt  signals are amplified before being applied to the A D  The thermocouple inputs are also  amplified before applying A D conversion  The data sampling rate is determined by the  operating software     1 4 Auxiliary Inputs  Each Multi Tracer has additional inputs for pyranometers and thermocouples  Refer    to Appendix A for details  In general  these inputs are suitable for pyranometers and    reference cells   reference cells require external shunt resistors     RD 1600 3200 Operations Manual page 5    2 0 Operating Software    2 1 Introduction  MTRACE is a Windows based program designed to control and operate the Multi     Tracers  It implements all data collection features as well as timing  averaging  and  storing data on disk  As a Windows program  MTRACE incorporates most 
14. e sub menus may be accessed from the Configuration menu     Channels   displays status data for selected channel in an editable window  User  may enter change information using the keyboard  moving from field to field  using the  Tab  key  Data in the  aperture  and  system areas  are used to  calculate the efficiencies displayed for the I V curve display and the active  channel window   Irradiance Channel  is used to select the pyranometer input  channel for this module  Channels 1 through 8 are external voltage inputs   channel 9 is a manual input   Aux  Temp erature   Channel  is used to select the    RD 1600 3200 Operations Manual page 8    auxiliary temperature channel associated with this module    E   secondary  temperature     The Aux String control defines if auxiliary string data is collect for a given channel  when and I V curve is taken  Also the starting character position and number of  string characters can be specified  Refer to the configuration menu for auxiliary  string data for more details     Note  Average 1  uSeconds should be set to    100    unless testing under  simulated light is in progress  To take accurate sample data or l V Curves under  varying light sources the Average should be increased because the output of  many artificial light sources pulsate due to their power sources  To obtain valid  data under such light sources  the RD 1600 Multi Tracer averages a number of  data points at each load setting to obtain data points  The higher the numb
15. er   the longer it takes to sample data or take an I V curve  and  theoretically  the  better the data  Experience shows that after a certain point  any improvement  becomes exceedingly small     Because the averaging period can be set in uS  it is possible to define the  average period equal to the pulse period  or multiple of pulse periods  of the  artificial light source  This makes it possible to dramatically reduces the variations  caused by an artificial light     The amount of averaging  number of data points  and speed of IV curves and  sampling depends not only on the light source but the type of module tested and  the quality of the data desired  This operator decision will be based on  experience with the RD 1600     IV Curves   offers user control for taking l V curve  how often  when  under what  irradiance conditions are data to be collected  and where curves are to be saved   Standard Windows folder  directory  selection boxes are available to select which  folder is used to store l V curve data  The    New Folder  button allows a new  folder to be created     Global   allows the user to set commands for all attached modules  The Global  command displays two selection boxes with radio control buttons  one for Load    RD 1600 3200 Operations Manual page 9    Control and one for Setting l V Curve data acquisition   Load Control  options  include All Loads Off  Peak Power Tracking for all modules  Fixed Voltage  Operation for all modules  Voltage Profile for all m
16. er are shown in Figure 3  Note that the Multi   Tracer and PC are grounded at the same location and that the PV modules are grounded  inside the Multi Tracer  Referencing the PV modules to ground at any other point will  cause measurement errors and could possible present a safety hazard  If the PV modules  are disconnected from the Multi Tracer they will lose ground reference and possibly create  a shock hazard  The connectors supplied  for mounting to the PV module cables  are  recessed and are difficult to come in contact with  However  treat all disconnected cables  carefully     Multi Tracer    Ethernet  USB  or RS 232    AUX  GND       Figure 3  MULTI TRACER Basic Connections     RD 1600 3200 Operations Manual page 18    3 2 Ground Connections  As shown in Figure 3  there are three ground connections   two to the Multi Tracer    and one to the PC  The PC ground connection is provided by the 3 prong plug of your  computer s AC power cord  The Multi Tracer has a similar 3 prong power cord with a  ground  The third connection to ground is a case ground for the Multi Tracer  This ground is  necessary to ensure the Multi Tracer case remains grounded for the worst case condition  of having all PV module currents flowing to ground  The Multi Tracer AC power cord is not  capable of handling this much current  Therefore this separate ground point is provided as  shown in Figure 4        Figure 4  MULTI TRACER Ground Connector     Connect a  2 AWG wire with lug to the Multi Trace
17. inimized  If longer  leads are necessary use larger wire for most of the distance and attached  12 tails to this  wire to fit in the mating connector of the Multi Tracer     Use calculations similar to the above example to determine wiring loses  As module  voltage increases  voltage drops become a smaller percentage of Voc  Therefore the values  are closer to Isc relative to the l V curve Voc  Additionally  higher Voc will result in lower lsc    for the same power  Lower currents create lower voltage drops  Inversely  lower voltage    RD 1600 3200 Operations Manual page 22    modules increase the significance of the voltage drop  In the previous example  Isc was 10  A  Assuming a standard Multi Tracer module input power of 100 W  Voc would be less than  13 V assuming an 80  fill factor PV module  Given a combined voltage drop of 1 V  the  minimum voltage is 8  of this Voc value  This may or may not be acceptable depending on  the shape of the I V curve    Note  This issue does not affect the accuracy of voltage measurements  The 4 wire    connection removes wire losses as a source of measurement error     3 5 Module Thermocouple Connections  The Multi Tracer includes a thermocouple input for each module  Mating connectors    are supplied with the Multi Tracer  Use these connectors as well as the appropriate  thermocouple wire  not supplied   The Multi Tracer is equipped with type T thermocouple  inputs  Thermocouple inputs do not have a shield connection point  If shielded w
18. ire is  used  connect the shield to the thermocouple  Note  The thermocouple inputs are not  isolated  Therefore you must use un bonded thermocouples  thermocouples must be    electrically insulated      3 6 Computer Connections  The Multi Tracer supports 3 different connections types  Ethernet  USB  and RS 232     Ethernet is recommended unless the Multi Tracer and controller computer are located near    each other     Ethernet  The Multi Tracer has a standard 10 100 Ethernet port and can be connected to the    LAN common to the controller computer  While the data rates of the Multi Tracer are   relatively low  performance may be affected by other network traffic  Therefore  for best  performance  the recommended connection is to connect the Multi Tracer and controller  computer into a networks switch and connect this switch to the LAN  This will keep LAN  traffic from affecting the Multi Tracer  but still allow the control computer to use the LAN     In order to use the Ethernet connection  the Multi Tracer needs a unique network IP  address  While the Multi Tracer does support DHCP  assigning a static IP address to the  Multi Tracer is the simplest and most reliable approach     RD 1600 3200 Operations Manual page 23    Note  Both the Multi Tracer and MTrace software must be set to the same IP  address  Use the MCAL software to change the Multi Tracer network settings  Keep in  mind that typically it is impossible to properly change the Multi Tracer network settings  using
19. le  modules 1  3  4  5  and 13 could be operated at their  respective peak power points while modules 2  6  7  8  and 9 operate at a fixed voltage of  12 V and modules 10  11  14 and 16 operate at voltages that change with time as defined  by the voltage profile  The actual functions available to the user are defined by the  operating and control software  See Section 2 0 for the details on the MTRACE operating    software     The Multi Tracers can operate PV modules at voltages from slightly greater than 0 V  to their Voc value  The Multi Tracer controls the module voltage to a resolution of  approximately 1 30 000 of the maximum voltage for that input channel  For example  if the  Multi Tracer input channel is rated for 100 V DC  the control resolution is 3 mV   100  V 30 000  The MTRACE operating and control software must periodically update the  settings of the loads  The rate depends on the software and the speed of the control    computer  but is typically once every second     While peak power tracking  the Multi Tracer sweeps the module voltage up and down  as it searches for maximum power from the module  Although the search ranges over a    RD 1600 3200 Operations Manual page 3    significant voltage range  perhaps as much as x0 5 V  the power from the module will be  within 0 296 of the maximum power after the Multi Tracer has achieved peak power  tracking     Because the Multi Tracer does not  know  the module characteristics when a new  module is connected  the u
20. negative  grounding  By default all Multi  Tracer channels are configured this way  However  some  module technologies specifically require positive grounding  Please consult Daystar if you  need to convert one or more of the Multi Tracer channels from negative to positive  grounding    The module output is connected to either the positive input  A  and ground  E  or to  the negative input  B  and ground  E   It is never connected to positive  A  and negative  B   at the same time  However  no damage should result result  But the unit will not function  properly     RD 1600 3200 Operations Manual page 20  The voltage sense lead is connected the same regardless of the grounding scheme    While the diagrams below show the shield of the voltage sense cable connected to ground   at the Multi Tracer  Other shielding connections may perform better depending on the   specifics of the installation  Generally it is best to connect a shield at one end only       Voltage Sense  C      Voltage Sense  D     Ground  E     No Connection                 PV  B        Figure 6  MULTI TRACER PV Module Wiring  For Negative Grounding    No Connection                 PV  A     Ground  E       Voltage Sense  C      Voltage Sense  D        Figure 7  MULTI TRACER PV Module Wiring  For Positive Grounding    Four wires connect the PV module to the Multi Tracer       Positive PV Power Lead  Large Gauge      Negative PV Power Lead  Large Gauge      RD 1600 3200 Operations Manual page 21      Positive Vol
21. odule Temperature After l V Curve  Ambient Temperature After l V Curve  Irradiance After l V Curve    current value voltage value  current value voltage value   There may be up to 257 IV data pairs     page 15    RD 1600 3200 Operations Manual page 16    3 0 Installing Your Multi Tracer  CAUTIONS      The Multi Tracer AC Power switch should be in the OFF position when making or  breaking connections to PV modules  Making or breaking PV module  connections while the Multi Tracer is turned ON  fans blowing  may cause an  arc  Electrical arcs may cause burns to the user and damage the Multi Tracer       The Multi Tracer uses DC fuses for each module input  However  because these  fuses are rated higher than the rated current of the PV module inputs  they will  not provide protection against short circuiting PV modules  These fuses provide  protection to the Multi Tracer should the user inadvertently connect a PV module  with a current output exceeding the input rating       Do not change any fuses  AC or DC  when the Multi Tracer is turned ON   Changing a fuse while the unit is operating can cause an arc that could damage  the Multi Tracer and injure the user       Do not connect the Multi Tracer to anything other than an ungrounded PV  module within the operating range of the unit  Note  The Multi Tracer provides  grounding to the modules       Do not connect the Multi Tracer to a PV module with an open circuit voltage   Voc  greater than the maximum voltage for the that input 
22. odules  and Channel Defined   For channel defined operation  the settings from the Channels configuration  see  above  are used     Selections in the  I V Curves  area include None  All Channels  and Channel  Defined  The l V curve parameters of when and under what conditions l V curve  are taken still apply  This setting overrides the  Enable l V Curve  selection from  the channels configuration     Global control does not edit channel configurations  but rather overrides the  current channel settings  Global control provides as convenient short term  testing  but can be used for all testing if  for example  all modules are to be peak   power tracked     Data Logging   allows user control of the sample interval  number of samples to  average  and where to save the data  The  Average Interval   entered in  minutes  is the time over which data are averaged and written to disk  Note  a  small average interval will result in relatively large amounts of data written to  disk  Also  this average is not to be confused with the averaging when taking  data under simulated light sources     As with l V curves  the folder used for storing sampled data may be selected   Sampled data files are designated by the     MTD    file type     Voltage Profile   opens a spreadsheet that allows an entry for every 15 minutes for  up to 16 modules  This spreadsheet format simplifies data entry through use of            cut  paste  and fill commands  This mode of operation is very similar to  fixed v
23. of the  features of that operating environment   common Windows techniques using the mouse  or keyboard commands will allow the user to quickly become comfortable with  MTRACE     For testing PV modules under simulated sun conditions  MTRACE allows the user  to set the number of microseconds  uS  that will be averaged to obtain values for a    module l V curve  This option permits modules to be operated under a variable light       source  In this mode  the load provided to the module by the Multi Tracer is fixed until  the data are obtained and averaged to determine the value of voltage and current   Then the load is stepped to the next value and the process is repeated  The Multi   Tracers will operate with a mixture of modules  some in artificial light and others in    natural conditions     2 2 Software Installation  amp  Operation   A number of files and a specific directory structure are required for MTRACE  operation  These files are included on the installation CD ROM  MTRACE is a  Windows   application and must be installed on Windows 20006  or Windows XP     Operation on other Windows   versions may be possible  but has not been tested     Insert the CD ROM and the setup program will prompt you for information on  where you want to install MTRACE  If you are unsure  use the defaults which create  appropriate sub directories in the programs folder     MTRACE Setup automatically installs the necessary files in the designated  directory and makes additions to your Wind
24. oltage operation except the fixed voltage values are updated every 15  minutes  Note  Due to load control regulation  voltage changes do not occur  instantly  but may take several update cycles to change to the updated value     Auxiliary Scales   allows user input of conversion factors  units volt   Channel 9 is  not a true data channel  i e    a pyranometer is not used  but accepts a manual    RD 1600 3200 Operations Manual page 10    input in Watts m2  The value entered here will be used for any channels which  specifies channel 9 as its irradiance channel     Although these channels are typically used for irradiance measurements  they  may be used for any signal meeting the input specifications  Note  Standard  voltage inputs have a maximum range of   5 V  In all cases inputs are auto  scaling in decades providing accurate measurement of even mV signals     Port   allows the selection of which port to use and values appropriate to that port     Aux String   allows the user to set the parameters and port for adding auxiliary string  data to I V curve files  Auxiliary string data can be recorded and saved with any I   V curve  This string data can come from any serial COM port  No limitation is  placed on the source of this data other than a string is defined as data terminated  by a carriage return  Baud rate and other serial port parameters are set in this  menu  Note  The time out parameter sets how long the I V curve routine should  wait for string data  Furthermore  au
25. ows system directory  Setup also creates a  new program group icon in the program manager window     RD 1600 3200 Operations Manual page 6    Double click on the MTRACE icon to start MTRACE  A setup screen similar to that  shown in figure 1 will be displayed  Menu actions may be executed with the mouse or  keyboard  Pertinent event time status is displayed across the bottom of the screen  These  fields are updated to show the ongoing activity of the Multi Tracer  On successive startups  of MTRACE  the configuration parameters that were last used will be loaded  If other  parameters are desired  use the Load Configuration command under the File menu to  load previously saved MTRACE configurations    MTC   files           MTRACE for Windows Configuration C  MTRACE10 WMTRACE MTC       File View Execute Configuration    Windows    Active Channels Error Log    of ae JEE E   E   au     2  Unknown Module     3  Unknown Module     4  Unknown Module         Unknown Module     B  Unknown Module  Unknown Module     8  Unknown Module  Eg  Unknown Module     18  Unknown Module     11  Unknown Module  Estar Unknown Module    SPooococc                       0 0                3_         B Temp 4 pur    12 8 37  12 35 12 jidle  Errors 0     Next Curve 05 00 00  Next Sample 12 35 16  Next Store 12 35 21       Figure 1  MTRACE Screen    Note  The hardware must be calibrated before you setup MTRACE for the first  time  Your Multi Tracer has been factory calibrated  but you may prefer to perform
26. pack with at least 3 inches of packing foam between the inside  and outside boxes for shipping     e Use two people when lifting or moving the unit     4 4 Troubleshooting    All modules are always at Voc     The Multi Tracer has no AC power  fans not blowing         Turn AC power ON using the switch on the back panel     Multi Tracer is turned ON and fans are not blowing     AC power fuse has blown        Turn AC power OFF  unplug AC power cord  replace fuse  reconnect AC  power cord  and turn AC power ON     A single module is always at Voc     Input fuse for module has blown        Turn Multi Tracer OFF  replace fuse  and turn unit ON     Fixed voltage or load profile voltage is set above module Voc       Correct channel fixed voltage setting and load profile       Load has overheated and thermal protection circuit has activated        Check that module power is less than maximum for that channel and that  Multi Tracer is operating within its operating range     Single module is always near 0 V or negative     Module is not connected        Turn Multi Tracer OFF  connect module  and turn Multi Tracer ON       Module polarity is reversed        Turn Multi Tracer OFF and carefully disconnect module  CAUTION   Shade PV module before disconnecting to prevent arcing  Be sure to  wear proper eye protection and gloves to provide protection from  electrical arcs     Measurements are incorrect      The Multi Tracer needs calibration       Calibrate using MCAL software     e Using o
27. r ground connector  Be sure to  securely attach the lug to the mounting post shown in Figure 4  Keep this ground lead as  short as possible and firmly attach it to the ground system  All ground connections should  be made to the same point  Note  Significant voltage potentials can exist between grounds   Therefore  the AC power grounds used for the 3 prong plugs must be connected to the  same ground as the  2 wire from the Multi Tracer  Be sure that the ground connection is  capable of handling the total current from all of the PV modules connected to the system    Note  For model RD 3200 the slave load must be connected to the master load to  properly ground all module  Do not run the RD 3200 without having both loads connected  and grounded     RD 1600 3200 Operations Manual page 19    3 3 PV Module Connections  The Multi Tracer uses a 5 pin connector for each PV module input  The connector and    each pin function is shown in Figure 5     Ground  E       Voltage Sense  D       Voltage Sense  C        Figure 5  MULTI TRACER PV Module Input Connector     While all modules are grounded when connected to the Multi Tracer  the Multi Tracer  supports grounding either the module negative or module positive  Note  A simple wiring  modification is required inside the Multi Tracer to convert it from positive to negative  grounding  Therefore  each channel is predefined as a positive or negatively ground  channel    Most modules can be connected in the more conventional way of using 
28. s will not refer to the  Multi  Tracer driver by name     When you first connect the Multi Tracer to your computer using the USB  connection  Windows will recognize that new hardware has been connected and begin  the process of installing the driver  The instructions on the CD ROM provide much more  detail  but in general  you will want to have Windows use the drivers in the driver folder  on the CD ROM using the  Have Disk  option     
29. ser should follow the recommended procedure for connecting  modules  Otherwise it may take many minutes for the Multi Tracer to locate the peak   power point and begin tracking     The Multi Tracer should be turned OFF when connecting modules    to the unit     The AC power switch is on the back panel  Leave the power off for a minimum of 5  seconds after connecting a module to ensure the RD 1600 will sense the module Voc  The  peak power tracking algorithm uses the module Voc to estimate and quickly reach the    peak power point     1 2 Curve Tracing  In addition to electrically loading the PV modules  the Multi Tracers can generate a    current voltage  1     curve that characterizes the photovoltaic modules under test  At user   defined intervals  the Multi  Tracer sweeps an l V curve from lsc to Voc for each module  connected  Because of wiring and other load resistance  the Multi Tracer cannot operate  the modules at true Isc  zero voltage   The RD 1600 does make voltage current  measurements for voltages near zero   typically less than 0 5 V at full scale current  Wiring  resistance from the PV module to the Multi Tracer is the major factor in preventing  operation at zero volts  Refer to Section 3 for details on module connections and    resistance calculations     1 3 PV Module Data Acquisition  The Multi Tracer has several connection options to the control computer  Ethernte     USB  or serial RS 232  The connection allows the Multi Tracers to be located near the  mo
30. tage Sense Lead    Negative Voltage Sense Lead    Use a shielded  twisted pair wire with a voltage rating greater than Voc of the PV  module for the voltage sense lead  Connect the shield of this cable to pin E of the Multi   Tracer or other suitable ground point  Only connect the shield at one end  Keep the power  leads as short as possible and use  12 AWG wire  This is the largest wire that can be  used with the Multi Tracer connectors  After crimping the pins to the lead  solder may be    used to minimize the voltage drop across the connection     3 4 Voltage Drop  amp  Isc  It is important to minimize the resistance in all circuits  The lower the short circuit    resistance  the closer to true Isc the Multi Tracer will operate  If the voltage drop is too  large  it becomes unacceptable to use the current measurement at this minimum voltage as    an approximation of Isc  The following example illustrates the effect of lead resistance on Isc    measurement     If a PV module with an Isc of 10 Amperes is connected using 20 foot leads of  12 wire  the voltage drop near Isc may be estimated as      lac   10A  e Rwire   1 6          specification for  12 stranded copper wire       Rtotal   1 6 mO  ft x 40 ft   64 mQ  20 ft Module to Multi Tracer and 20 ft back     Vdrop   Isc X Rtotal   10 A x 64 mQ   640 mV   0 64 V    Add to this the internal resistance of the Multi Tracer and it may be impossible to get  closer than 1 V to true lac  For this reason  the lead length must be m
31. ut of date   CFG   file      Use most recent calibration data  configuration file      RD 1600 3200 Operations Manual page A1    APPENDIX A   GENERAL SPECIFICATIONS    General Specifications  Number of Module Inputs 16  Number of Aux  Inputs    Number of Aux  Temp  8    Approximate Size of Each Load Unit 14  H x 18 W x 35 D    Power 120 VAC  70W RD 1600  140W RD 3200   AC Fuse 3A  250 V Slow Blow 3AG   Module Fuse 250 V Fast Blow 3AG  Amperage varies  refer to back panel   Connectors   Module Connectors 97 4102A 18 11P by Amphenol   Module Cable Connectors 97 4106A 18 11s by Amphenol   Crimp Connector Pins 97 38 1216P 920  by Amphenol   Crimp Connector Sockets 97 38 12165 920                         Thermocouple Sockets MPJ T F by Omega Engineering   Thermocouple Plugs SMP T M by Omega Engineering   Aux  Inputs BNC    RD 1600 3200 Operations Manual page B1    APPENDIX B   USB Drivers    In order to use the Multi Tracer USB port for control  the Multi Tracer USB drivers  must be installed on the control computer running MTrace and MCAL  The driver will be  a USB device driver labeled  Multi Tracer      The Multi Tracer USB drivers are located on the installation CD ROM supplied  with the unit in the USB Drivers folder  This folder contains detailed instructions on how  to install the drivers for your version of the operating system     Note  These instructions are not specific to the Multi Tracer and where provided  by the USB hardware manufacturer  Therefore these instruction
32. xiliary string data is completely  asynchronous  MTRACE does not perform any handshaking with the string data  source     2 7 The Windows Menu    This sub menu shows open and active windows and serves as an alternate method    for selecting windows     RD 1600 3200 Operations Manual page 11    2 8 File Types    2 8 1 Data Files   Mtrace works with the following file types      MTRACE CFG    this is the calibration and hardware configuration file created by  MCAL  This file is unique for every unit and stores the calibration constants       MTC      These        the MTRACE configuration files used by MTRACE to store the  various channel  l V curve  data logging and other parameters  The default file is     MTRACE MTC     but any configuration file may be used  Use the Load and Save  commands under the file menu  The last used MTC file is automatically used when  MTRACE is restarted  The file name is displayed as part of the title in the MTRACE    window       MTD    These are the sample data files  There is a separate file for each day s  data  All channel and auxiliary input data are stored in this file     The naming convention for data files is MTyymmdd MTD  where     yy isthe year   e mm is the month  and    dd is the day of the month   The files are created daily and contain data for that day  The data are comma    delineated ASCII and can be viewed with a text editor or imported into a spreadsheet     RD 1600 3200 Operations Manual page 12    Each line of data in the dat
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
取扱説明書 - M  son m - Assistance      FINAL EUREKA MANUAL - Central Vacuum Supplier  estetocopios de cabeza doble.indd  Honeywell Optiflex Home Theater Server User Manual  ORF Monitor user manual  FR-0201 取扱説明書  Les complments spatiaux dynamiques dtachs en tte :    Copyright © All rights reserved. 
   Failed to retrieve file