Home
        NI 9244 User Manual and Specifications
         Contents
1.    EMC     Online Product Certification    To obtain product certifications and the Declaration of Conformity   DoC  for this product  visit ni com certification  search by  module number or product line  and click the appropriate link in  the Certification column     44   nicom   NI 9244 User Manual and Specifications    Shock and Vibration    To meet these specifications  you must panel mount the system  If  you are using the NI 9244 with screw terminal  you also must  either affix ferrules to the ends of the terminal wires   Operating vibration  Random  IEC 60068 2 64           5 gms  10 Hz to 500 Hz  Sinusoidal  IEC 60068 2 6          5 g  10 Hz to 500 Hz    Operating shock   IEC 60068 2 27                                30 g  11 ms half sine   50 g  3 ms half sine   18 shocks at 6 orientations    Environmental    Refer to the manual for the chassis you are using for more  information about meeting these specifications     Operating temperature   IEC 60068 2 1  IEC 60068 2 2         40   C to 70   C    Storage temperature   IEC 60068 2 1  IEC 60068 2 2        40   C to 85   C    Ingress protecton  IP 40    NI 9244 User Manual and Specifications   National Instruments   45    Operating humidity            60068 2 56                                10  to 90  RH   noncondensing   Storage humidity    IEC 60068 2 56                                5  to 95  RH   noncondensing   Pollution Degree    s s seeseeeeeeerseeeeees 2   Maximum altitude                              5 000 
2.   Refer to the Specifications section for more information  about the data rate range  When using the internal master timebase  of 12 8 MHz  the result is data rates of 50 kS s  25 kS s    16 667 kS s  and so on down to 1 613 kS s  depending on the value  of n  When using an external timebase with a frequency other than  12 8 MHz  the NI 9244 has a different set of data rates     Note The NI 9151 R Series Expansion chassis does not  support sharing timebases between modules     NI 9244 User Manual and Specifications      National Instruments   31    Sleep Mode       This module supports a low power sleep mode  Support for sleep  mode at the system level depends on the chassis that the module is  plugged into  Refer to the chassis manual for information about  support for sleep mode  If the chassis supports sleep mode  refer to  the software help for information about enabling sleep mode     Typically  when a system is in sleep mode  you cannot  communicate with the modules  In sleep mode  the system  consumes minimal power and may dissipate less heat than it does  in normal mode     Related Information  Power Requirements    32   nicom   NI 9244 User Manual and Specifications    Specifications       The following specifications are typical for the range  40   C to 70   C  unless otherwise noted     Input Characteristics       Scaling                                                  118 911 nV LSB  Number of channels        ssssseeeseeeee seee 4 analog input channels  ADC reso
3.  9244 User Manual and Specifications      National Instruments   19    Connecting Three Phase Measurement  Configurations    You can connect WYE or delta measurement configurations to the  NI 9244     Figure 7  Connecting a 4 Wire WYE Measurement Configuration       Phase A       Phase B       Phase C       Neutral       20   nicom   NI 9244 User Manual and Specifications    Figure 8  Connecting a High Leg Delta Measurement Configuration    Phase A         Phase B All       Phase C Al2       Neutral Neutral    SE ees cee Seo eee ty erue    NI 9244 User Manual and Specifications      National Instruments   21    Figure 9  Connecting a 3 Wire Delta Measurement Configuration    Phase A   AIO         Phase B       Phase C       22   nicom   NI 9244 User Manual and Specifications    Figure 10  Connecting a Corner Grounded 2 Wire Delta  Measurement Configuration       Phase A         Phase B       Phase C    Note The 9244 can not measure the entire tolerance  range or high crest factor signals on 690 Vms systems in  this configuration  Refer to the Specifications section for  more information about the input range     NI 9244 User Manual and Specifications      National Instruments   23    Connecting Single Phase Measurement  Configurations   You can connect 3 wire or 2 wire single phase measurement  configurations to the NI 9244     Figure 11  Connecting a 3 Wire Measurement Configuration   Split Phase                     24   nicom   NI9244 User Manual and Specifications    Figur
4.  delay    ecce        40 312  f    1 7 us  Passband   Frequency  i  ese eee isa  0 453   f   Flatness   0 kHz to 20 kHz                             100 mdB max   0 kHz to 10     2                           20 mdB max       Negative phase sequence error at 50 Hz and 60 Hz  At 5  unbalance       Maximum        0 1396  Typical        0 05   At 1  unbalance  Maximum    0 13   Typical                  esses 0 05     Zero phase sequence error at 50 Hz and 60 Hz  At 5  unbalance  Maximum    0 13   0 05        Typical    NI 9244 User Manual and Specifications      National Instruments   37    At 1  unbalance       E 0 13   KEE 0 05   Stopband  Frequency deed ere 0 547   f   Rejection  95 dB  Alias free bandwidth                          0 453   f   Anti alias rejection  f5 50 kS s          50 dB   3 dB bandwidth  f    50 kS s            0 49   f   Crosstalk  60   2                                 100 dB  Crosstalk  1     2                                  74 dB    CMRR  f    60 Hz   78 dB       SFDR  1 kHz   60 dBFS      120 dB   Total Harmonic Distortion  THD     LK  eL ee  98 dB   OO kKEIz    toe ene  100 dB   MTBE i dU Contact NI for Bellcore  MTBF or MIL HDBK 217F  specifications     38   nicom   NI 9244 User Manual and Specifications    Power Requirements  Power consumption from chassis    Active mode    332 mW max   Sleep mode  50 uW max  Thermal dissipation   Active mode                    sss 652 mW max   Sleep mode                                   320 uW           Physical 
5.  using 12 AWG  to 14 AWG wires     NI 9244 User Manual and Specifications      National Instruments   11    Figure 3  12 AWG to 14 AWG Installation                1 Route wires over the strain relief piece   2 Secure strain relief piece and NI 9969 backshell in place using captive    Screws        12   nicom   NI9244 User Manual and Specifications    Installing the NI 9969 Using16 AWG Wire    Complete the following steps to install the NI 9969 using 16 AWG  wires     NI 9244 User Manual and Specifications      National Instruments   13    Figure 4  16 AWG Installation                1 Route wires through the strain relief pieces   2 Secure strain relief piece and NI 9969 backshell in place using captive    Screws        14   nicom   NI9244 User Manual and Specifications    Installing the NI 9969 Using18 AWG to 24 AWG Wire  Complete the following steps to install the NI 9969 using 18 AWG  to 24 AWG wires     NI 9244 User Manual and Specifications      National Instruments   15    Figure 5  18 AWG to 24 AWG Installation                  1 Route wires over the strain relief piece   2 Secure strain relief piece and NI 9969 backshell in place using captive    Screws        16   nicom   NI9244 User Manual and Specifications    Signals    The NI 9244 has three AI terminals and a Neutral terminal    You can connect three phase and single phase measurement  configurations to the NI 9244  The NI 9244 supports standard  service levels up to 400        Line to Neutral  L N  and 690 V   L
6. 244 at ni com calibration     Calibration                                            1 year    NI 9244 User Manual and Specifications      National Instruments   47    Worldwide Support and Services       The National Instruments website is your complete resource for  technical support  At ni com support you have access to  everything from troubleshooting and application development  self help resources to email and phone assistance from   NI Application Engineers     Visit ni com services for NI Factory Installation Services   repairs  extended warranty  and other services     Visit ni com register to register your National Instruments  product  Product registration facilitates technical support and  ensures that you receive important information updates from NI     A Declaration of Conformity  DoC  is our claim of compliance  with the Council of the European Communities using the  manufacturer s declaration of conformity  This system affords the  user protection for electromagnetic compatibility  EMC  and  product safety  You can obtain the DoC for your product by visiting  ni com certification  If your product supports calibration   you can obtain the calibration certificate for your product   at ni com calibration     48   nicom   NI 9244 User Manual and Specifications    National Instruments corporate headquarters is located at   11500 North Mopac Expressway  Austin  Texas  78759 3504   National Instruments also has offices located around the world  For  telephone suppor
7. Characteristics  If you need to clean the module  wipe it with a dry towel        Note For two dimensional drawings and  three dimensional models of the C Series module and  connectors  visit ni  com dimensions and search by  module number     Screw terminal wiring                        0 511 mm diameter   24 AWG  to 2 053 mm  diameter  12 AWG  copper  conductor wire with 7 mm   0 28 in   of insulation  stripped from the end    NI 9244 User Manual and Specifications      National Instruments   39    Torque for screw terminals                0 5N  mto0 6N  m   4 42 Ib    in  to 5 30 lb   in      Berrules      e 0 25 mm  to 2 5 mm   KEE 150 g  5 3 oz   Safety    Connect only voltages that are within the following limits   Maximum working voltage  channel to earth ground  Up to 2 000 m altitude   Continuous               esessses 400 Vms    2 001 to 5 000 m altitude  Continuous                           400 Vms   Measurement Category II or   300 Vms    Measurement Category III   Division 2 and Zone 2 hazardous locations applications   Channel to earth ground                    300 Vins   Measurement Category III       40   nicom   NI 9244 User Manual and Specifications    Measurement Category III is for measurements performed in the  building installation at the distribution level  This category refers  to measurements on hard wired hardware such as hardware in  fixed installations  distribution boards  and circuit breakers  Other  examples are wiring  including cables  bus bar
8. I 9244 User Manual and Specifications    Electromagnetic Compatibility    This product meets the requirements of the following EMC  standards for electrical equipment for measurement  control  and  laboratory use     s EN 61326 1  IEC 61326 1   Class A emissions  Industrial  immunity    s EN 55011  CISPR 11   Group 1  Class A emissions      EN 55022  CISPR 22   Class A emissions       EN 55024  CISPR 24   Immunity   e AS NZS CISPR 11  Group 1  Class A emissions   e AS NZS CISPR 22  Class A emissions   e FCC 47 CFR Part 15B  Class A emissions     ICES 001  Class A emissions    Ka Note In the United States  per FCC 47 CFR    Class A equipment is intended for use in commercial   light industrial  and heavy industrial locations   In Europe  Canada  Australia and New Zealand   per CISPR 11  Class A equipment is intended for use  only in heavy industrial locations     NI 9244 User Manual and Specifications      National Instruments   43    Note Group   equipment  per CISPR 11  is any  Ka industrial  scientific  or medical equipment that does not    intentionally generates radio frequency energy for the  treatment of material or inspection analysis purposes     Ka Note For EMC declarations and certifications  refer to  the Online Product Certification section     CE Compliance C        This product meets the essential requirements of applicable  European Directives as follows     e  2006 95 EC  Low Voltage Directive  safety     e  2004 108 EC  Electromagnetic Compatibility Directive
9. IIC T4  and  Ex nA IIC T4 hazardous locations  and nonhazardous locations  only  Follow these guidelines if you are installing the NI 9244 ina  potentially explosive environment  Not following these guidelines  may result in serious injury or death     A Caution Do not disconnect I O side wires or connectors  unless power has been switched off or the area is known  to be nonhazardous     Caution Do not remove modules unless power has been  switched off or the area is known to be nonhazardous     Caution Substitution of components may impair  suitability for Class I  Division 2     Caution For Division 2 and Zone 2 applications  install  the system in an enclosure rated to at least IP 54 as  defined by IEC EN 60529      pp    6   nicom   NI9244 User Manual and Specifications    Special Conditions for Hazardous Locations Use in  Europe   This equipment has been evaluated as Ex nA IIC T4 Gc equipment  under DEMKO 12 ATEX 1202658X  Each module is marked          3G and is suitable for use in Zone 2 hazardous locations  in  ambient temperatures of  40   C  lt  Ta  lt  70   C  If you are using the  NI 9244 in Gas Group IIC hazardous locations  you must use the  device in an NI chassis that has been evaluated as Ex nC        4   EEx nC      T4  Ex nA      T4  or Ex nL      T4 equipment     A Caution The system shall be mounted in an ATEX  certified enclosure with a minimum ingress protection rating  of at least IP54 as defined in IEC EN 60529 and used in an  environment of not more 
10. Lloyd   s Register  certification for a product  visit       com certification and  search for the LR certificate  or look for the Lloyd   s Register mark  on the product label     A Caution In order to meet the EMC requirements for  marine applications  install the product in a shielded  enclosure with shielded and or filtered power and  input output ports  In addition  take precautions when  designing  selecting  and installing measurement probes  and cables to ensure that the desired EMC performance is  attained     NI 9244 User Manual and Specifications      National Instruments   9    Connecting the NI 9244    The NI 9244 provides connections for four analog input channels   Figure 2  NI 9244 Pinout                                                                                                    Alo  0 j   AH 1   Al2 2  Neutral 3                                                                10   nicom   NI 9244 User Manual and Specifications    Connector    The NI 9244 has a 4 terminal  detachable screw terminal  connector     Backshell    Caution For safe operation with hazardous voltages   you must use the NI 9969 Connector Backshell  as shown  in Figure 1  with the 4 terminal connector on the NI 9244     You can use the backshell with 12 AWG to 24 AWG wires with the  NI 9969  12 AWG to 14 AWG  16 AWG  and 18 AWG to 24 AWG  require different strain relief pieces    Installing the NI 9969 Using12 AWG to14 AWG Wire    Complete the following steps to install the NI 9969
11. USER MANUAL AND SPECIFICATIONS    NI 9244    4 Channel  400 Vms L N  800 Vms L L   24 Bit Simultaneous Analog Input Module    Fran  ais Deutsch HAR SSO         ni com manuals                              c NATIONAL  INSTRUMENTS    WwW    This document describes how to use the National Instruments 9244  and includes specifications and pin assignments for the NI 9244          Note The safety guidelines and specifications in this  document are specific to the NI 9244  The other  components in the system might not meet the same safety  ratings and specifications  Refer to the documentation for  each component in the system to determine the safety  ratings and specifications for the entire system     Related Information    Chassis Compatibility  ni com info   compatibility    NI CompactRIO Documentation      NI CompactDAO  amp     ni com info c   cseriesdoc       e     Services  ni com services    Ce    e Software Support   Ceo        9 ni com info   softwareversion     2             2   nicom      9244 User Manual and Specifications    Safety Guidelines       Operate the NI 9244 only as described in this user manual       N Hot Surface This icon denotes that the component may  be hot  Touching this component may result in bodily  injury     AN Warning This icon denotes a warning advising you to  take precautions to avoid electrical shock     A Caution Do not operate the NI 9244 in a manner not  specified in this user manual  Product misuse can result  in a hazard  You can comprom
12. a rate   The stopband rejection is the minimum amount ofattenuation applied  by the filter to all signals with frequencies within the stopband     NI 9244 User Manual and Specifications      National Instruments   29    Alias Free Bandwidth    Any signal that appears in the alias free bandwidth of the NI 9244  is not an aliased artifact of signals at a higher frequency  The  alias free bandwidth is defined by the ability of the filter to reject  frequencies above the stopband frequency  and it is equal to the  data rate minus the stopband frequency     Understanding NI 9244 Data Rates    The frequency ofa master timebase  fy  controls the data rate  f   of  the NI 9244  The NI 9244 includes an internal master timebase with  a frequency of 12 8 MHz  but the module also can accept an  external master timebase or export its own master timebase  To  synchronize the data rate of an NI 9244 with other modules that use  master timebases to control sampling  all of the modules must share  a single master timebase source  Refer to the software help for  information about configuring the master timebase source for the  NI 9244  Visit       com info and enter cseriesdoc for  information about C Series documentation        30   nicom   NI 9244 User Manual and Specifications    The following equation provides the available data rates of the  NI 9244     _ Bez 256  n      s    where n is any integer from 1 to 31     However  the data rate must remain within the appropriate data rate  range
13. e 12  Connecting a 2 Wire Measurement        AIO  mo    A    L  1      9244    Neutral       Converting L N Measurements to L L    To convert L N measurements to L L values  calculate the voltage  difference between the AI channels using your application  software     Refer to the following equation for an example of converting L N  measurements to L L     Phase A to Phase B Voltage   AIO         where AIO is the reading from Phase A       is the reading from Phase B    NI 9244 User Manual and Specifications      National Instruments   25    Converting L N Measurements to L Earth    To convert L N measurements to L Earth values  add the neutral  channel reading to each AI channel reading     Refer to the following equation for an example of converting L N  measurements to L Earth     Line to Earth   Alx   Neutral  where   Ax is the analog input channel reading    Neutral is the Neutral channel reading    26   nicom   NI 9244 User Manual and Specifications    Wiring for High Vibration Applications   If an application is subject to high vibration  National Instruments  recommends that you either use ferrules to terminate wires to the  detachable screw terminal connector  Refer to Figure 13 for an  illustration of using ferrules     Figure 13  4 Terminal Detachable Screw Terminal Connector  with Ferrule       NI 9244 User Manual and Specifications      National Instruments   27    Understanding NI 9244 Filtering       The NI 9244 uses a combination of analog and digital filterin
14. g to  provide an accurate representation of in band signals while  rejecting out of band signals  The filters discriminate between  signals based on the frequency range  or bandwidth  of the signal   The three important bandwidths to consider are the passband  the  stopband  and the alias free bandwidth     The NI 9244 represents signals within the passband  as quantified  primarily by passband ripple and phase nonlinearity  All signals  that appear in the alias free bandwidth are either unaliased signals  or signals that have been filtered by at least the amount of the  stopband rejection     Passband    The signals within the passband have frequency dependent gain or  attenuation  The small amount of variation in gain with respect to  frequency is called the passband flatness  The digital filters of the  NI 9244 adjust the frequency range of the passband to match the  data rate  Therefore  the amount of gain or attenuation at a given  frequency depends on the data rate  Figure 14 shows typical  passband flatness for the NI 9244     28   nicom   NI 9244 User Manual and Specifications    Figure 14  Typical Passband Response of the NI 9244                               0 025   0 000  a  S      oO   9       0 025   0 050   0 0 1 0 2 0 3 0 4 0 5  Frequency Data Rate  Hz   Stopband    The filter significantly attenuates all signals above the stopband  frequency  The primary goal of the filter is to prevent aliasing   Therefore  the stopband frequency scales precisely with the dat
15. ine to Line  L L         Note You must use 2 wire ferrules to create    secure  connection when connecting more than one wire to a  single terminal on the NI 9244     Circuitry    Each channel on the NI 9244 provides an independent signal path  and ADC  Each terminal has the same input impedance to ground     NI 9244 User Manual and Specifications      National Instruments   17    The NI 9244 returns the voltage between each AI terminal and the  Neutral terminal as well as the voltage between the Neutral  terminal and the chassis ground  Refer to Figure 6 for a diagram of  the equivalent voltages the module returns     Figure 6  Internal Circuitry for the NI 9244                                             Alo  V  477  Alt  All        Leed  Al2  Al2  Neutral       ZEZ  Neutral 4 4 5 v  GND           NI 9244             18   nicom   NI9244 User Manual and Specifications    To ensure that measurements to chassis ground are correct  NI  recommends connecting the chassis to earth ground using the  chassis grounding screw  Refer to your chassis manual for  information about connecting the chassis to earth ground     Connecting Phase Measurements    You can connect three phase measurement configurations and  single phase measurement configurations to the NI 9244    NI recommends using the following phase measurement  configurations for typical power distribution networks  Other valid  connections are possible if the connections do not exceed the safety  rating of the NI 9244     NI
16. ise the safety protection  built into the product if the product is damaged in any  way  If the product is damaged  return it to National  Instruments for repair     NI 9244 User Manual and Specifications      National Instruments   3    Safety Guidelines for Hazardous Voltages    If hazardous voltages are connected to the module  take the  following precautions  A hazardous voltage is a voltage greater  than 42 4 Vy or 60 VDC to earth ground     A Caution Ensure that hazardous voltage wiring is  performed only by qualified personnel adhering to local  electrical standards     Caution Do not mix hazardous voltage circuits and  human accessible circuits on the same module     Caution Make sure that devices and circuits connected  to the module are properly insulated from human contact     Caution When module terminals are hazardous voltage  LIVE   gt 42 4V   60 VDC   you must ensure that devices  and circuits connected to the module are properly  insulated from human contact  You must use the NI 9969  connector backshell kit to ensure that the terminals are  not accessible      gt   gt        4   nicom   NI 9244 User Manual and Specifications    Figure 1 shows the NI 9969 connector backshell   Figure 1  NI 9969 Connector Backshell          NI 9244 User Manual and Specifications      National Instruments   5    Safety Guidelines for Hazardous Locations    The NI 9244 is suitable for use in Class I  Division 2  Groups A  B   C  D  T4 hazardous locations  Class I  Zone 2  AEx nA 
17. lution                   sees 24 bits  Type Of  A DC              Delta Sigma   with analog prefiltering   Sampling                                           Simultaneous  Internal master timebase  fy   Frequency  iecit 12 8 MHz  JACCUTACY              100 ppm max  Data rate range  f   using internal master timebase            1 613 kS s  Maximum              eee 50 kS s  Data rate range  f   using external master timebase  MiniMUM eee 390 625 S s  Maximum                       51 2 kS s    NI 9244 User Manual and Specifications   National Instruments   33         256    Data rates                                              n 1 2     31  Input voltage ranges         and Neutral to GND  AlIx to Neutral   Ku 997 5 Vox  Minimum                eee 992 Vox  Overvoltage withstand                        800 Vms continuous   1000 Vims for 1 s  Surge withstand                              s  5 kV  1 2 ps  50 us   Input coupling                        esses DC    Input impedance  AIx to Ground  and Neutral to GND                           2MQ         The data rate must remain within the appropriate data rate range  Refer to the  Understanding NI 9244 Data Rates section for more information     34   nicom   NI 9244 User Manual and Specifications    Table 1  DC and AC Accuracy                         Percent of Percent of  Reading Range   Measurement Conditions  Gain Error     Offset Error   Calibrated max   40   C to 70   C  0 17  0 14   Calibrated typ  23   C  5   C  0 043  0 012   U
18. m    Indoor use only     Environmental Management    Nl is committed to designing and manufacturing products in an  environmentally responsible manner  NI recognizes that  eliminating certain hazardous substances from our products is  beneficial to the environment and to NI customers     For additional environmental information  refer to the Minimize  Our Environmental Impact Web page at ni   com environment   This page contains the environmental regulations and directives  with which NI complies  as well as other environmental  information not included in this document          Refer to the Safety section for more information about altitude     46   nicom   NI 9244 User Manual and Specifications    Waste Electrical and Electronic Equipment  WEEE   X EU Customers At the end of the product life cycle    all products must be sent to a WEEE recycling center   For more information about WEEE recycling centers   National Instruments WEEE initiatives  and compliance  with WEEE Directive 2002 96 EC on Waste and  Electronic Equipment  visit        com environment   weee                 axe SDE  HE ROHS   RS E National Instruments 4T t ES fa E   9   T  dd rp           REA dz da  RoHS   T  National Instruments  F El RoHS ZO  TEESE  ni com environment rohs_china   For information  about China RoHS compliance  go to ni   com   environment rohs china                           Calibration    You can obtain the calibration certificate and information about  calibration services for the NI 9
19. ncalibrated max   40   C to 70   C  0 42  0 32   Uncalibrated typ  23   C  5   C  0 18  0 08                         Range equals 565 7 V  400 Vims           Note Accuracy specifications are valid for 1 1  LN  and L Earth measurements     Input noise at 50 kS s  L Earth and N Famh  4 22 MV ims  LN and 1 11    6 mV          The module returns L N and N Earth values only  Refer to Converting L N  Measurements to L L and Converting L N Measurements to L Earth sections for  details on changing the point of reference of the measurement    NI 9244 User Manual and Specifications   National Instruments   35    Note When measuring the amplitude of the   Ka fundamental frequency over one or several power cycles  the noise of the measurement reduces significantly   theoretically with the square root of the number of  samples in the acquisition window      Nonlinearity  at 25                            24 ppm  Stability   Gain drift               sess 5 ppm   C   Offset drift    6 mV   C  Post calibration gain match  channel to channel  max   Up to 20         109 mdB  Up to 10 kHz    39 mdB  Up to 3 8 kHz    eene 19 mdB  Phase mismatch  channel to channel                             0 202  kHz  Phase mismatch   module to module  max                   0 202   kHz   360    Gd fu  Phase nonlinearity  f  50 kS s    0 kHz to10                                  0 02   max   0 kHz to 20     2                          0 06  max    36   nicom   NI 9244 User Manual and Specifications    5    Inp  t
20. s  junction boxes   switches  socket outlets in the fixed installation  and stationary  motors with permanent connections to fixed installations     Measurement Category II is for measurements performed on  circuits directly connected to the electrical distribution system   This category refers to local level electrical distribution  such as  that provided by a standard wall outlet  for example  115 V forU S   or 230 V for Europe     Caution Do not connect the NI 9244 to signals or use  for measurements within Measurement Categories or IV     Hazardous Locations   US  UL   eset titre tte Class I  Division 2   Groups A  B  C  D  T4   Class I  Zone 2   AEx nA IIC T4    NI 9244 User Manual and Specifications      National Instruments   41    Canada  C UL                                    Class I  Division 2   Groups A  B  C  D  T4   Class I  Zone 2   Ex nA        4    Europe  DEMKO                               Ex nA IIC T4 Gc    Safety and Hazardous Locations Standards    This product meets the requirements of the following standards of  safety for electrical equipment for measurement  control  and  laboratory use        EC 61010 1  EN 61010 1   e UL 61010 1  CSA 61010 1     EN 60079 0 2009  EN 60079 15 2010            60079 0 2007  Ed 5  IEC 60079 15 2010  Ed 4  e UL 60079 0  Ed 5  UL 60079 15  Ed        CSA 60075 0 2011  CSA 60079 15 2012    Note For UL and other safety certifications  refer to the  product label or the Online Product Certification section     42   nicom   N
21. t in the United States  create your service request  at ni com support or dial 1 866 ASK MYNI  275 6964   For  telephone support outside the United States  visit the Worldwide  Offices section of ni com niglobal to access the branch office  websites  which provide up to date contact information  support  phone numbers  email addresses  and current events     NI 9244 User Manual and Specifications      National Instruments   49    Refer to the WI Trademarks and Logo Guidelines at ni   com  trademarks for more information on National  Instruments trademarks  Other product and company names mentioned herein are trademarks or trade names of  their respective companies  For patents covering National Instruments products technology  refer to the appropriate  location  Help  Patents in your software  the patents   txt file on your media  or the National Instruments Patent  Notice at ni   com patents  You can find information about end user license agreements  EULAs  and  third party legal notices in the readme file for your NI product  Refer to the Export Compliance Information at  ni com legal export compliance forthe National Instruments global trade compliance policy and  how to obtain relevant HTS codes  ECCNs  and other import export data         2014 National Instruments  All rights reserved     376131B 01 Mar14    
22. than Pollution Degree 2     A Caution The enclosure must have a door or cover  accessible only by the use of a tool     NI 9244 User Manual and Specifications      National Instruments   7    Electromagnetic Compatibility Guidelines       This product was tested and complies with the regulatory  requirements and limits for electromagnetic compatibility  EMC   as stated in the product specifications  These requirements and  limits are designed to provide reasonable protection against  harmful interference when the product is operated in its intended  operational electromagnetic environment     This product is intended for use in industrial locations  There is no  guarantee that harmful interference will not occur in a particular  installation  when the product is connected to a test object  or if the  product is used in residential areas  To minimize the potential for  the product to cause interference to radio and television reception  or to experience unacceptable performance degradation  install and  use this product in strict accordance with the instructions in the  product documentation     Furthermore  any changes or modifications to the product not  expressly approved by National Instruments could void your  authority to operate it under your local regulatory rules     8   nicom   NI 9244 User Manual and Specifications    Special Guidelines for Marine Applications    Some products are Lloyd   s Register  LR  Type Approved for  marine  shipboard  applications  To verify 
    