Home
Q SERIES Installation & Servicing Instructions
Contents
1. A Boiler AO Connection terminal Q A1 ATAG BrainQ thermostat RSC 4 Outside sensor ARV12 tra Thermostatic radiator valve BP Automatic by pass Use always a by pass in combination with thermostatic radiator valves figure 16 Installation amp Servicing Instructions J O Installation amp Servicing Instructions 17 2 Radiator installation with underfloor heating zone D C A B 2 5 4 4 5 yo 1 2 31 4 5 6 7 8 9 10 11 EEEE Pa 2223 24 25 26 27 Tv NBS cs esi O HARARE M BERS O eat e C B D installation example figure 17 A Boiler AO Connection terminal ATAG Q A4 Outside sensor ARV12 A9 MadQ zone controller 23BC A10 Connection terminal MadQ built in B Oylinder B3 Oylinder sensor B5 Three way valve cylinder C Direct zone C6 Pump direct zone D Mixing zone D2 Flow sensor mixing zone D5 Three way valve mixing zone 230V D6 Pump mixing zone See also the installation manual MadQ Zone controller 18 E
2. epe c lee e etm ete a iR HR debes 39 The appliance should only be installed by a Competent Gas Installer A Work on the boiler must be carried out by a competent person Ref Gas Safety Installation Use and Regulations using correctly calibrated instruments with current test certification Installation amp Servicing Instructions O Installation amp Servicing Instructions A 1 Introduction l These instructions describe the functioning installation use and primary maintenance of ATLANTIC BOILERS units for the United Kingdom and Ireland Where necessary the different regulations for each country are separately described These instructions are intended for the use by Corgi registered installers or registered Bord Gas installers in connection with the installation and putting into operation of ATLANTIC units Itis advisable to read these instructions thoroughly well in advance of installation Separate instructions for use are supplied with the unit for users of ATLANTIC central heating units ATLANTIC is not liable for the consequences of mistakes or shortcomings which have found their way into the installation instructions or users manua Further ATLANTIC reserves the right to alter its products without prior When delivering the unit give the customer clear instructions concerning its use present the customer with the user s manual and card Each unit is fitted with an identification plate
3. 23 Filling and venting the boiler and installation 24 10 1 3Hotwatersupplyas intonat ete ee a beet et tetto 24 Commissioning the boiler 25 11 1 Central heating vee cence oda 25 11 2 SHOT waer SUBO inks iicet ettet teed 25 11 9 22 eed edet tee ede sete eu pne ene o tee Dea eee dives ete 26 11 4 Activating factory settings green key function 28 Isolating the boiler e cd e tot 29 COMMISSIONING a dicunt eno tete atone e e t a te f etas 29 13 1 Checking for contamination 29 13 2 Checking of the zero pressure control 30 19 3 Checkingthe CO rca 31 E CEE E TATE AA t dente uice due iti aea deua 32 141 Frequency of maintenance aa 32 142 Maintenance activities 33 14 3 33 Tectinicalspecifications cree eter ned tee iin ee eee ee iene ee eee eee 34 Parts Of Ihe DONG p m 35 Installation examples akwama 36 17 1 Radiator installation without thermostatic radiator valves 36 17 2 Radiator installation with underfloor heating zone 37 Errorinidicatior unto meet antc ea 38 Declarationot COMTOMMILY
4. installation height above pre charge pressure the expansion vessel of the expansion vessel 5m 0 5 bar 10m 1 0 bar 15m 1 5 bar choice of expansion vessel table 4 All Combi boilers are provided with an expansion vessel connection This pipe is connected with the three way valve and boiler pump This prevent the expanding water during hot water production is being closed off from the expansion vessel when the thermostatic radiator valves are fully closed A second expansion vessel in the installation is not a problem The Solo boilers 0155 0255 and Q38S are provided with an expansion vessel connection When this boiler is combined with a cylinder the expansion vessel connection is included in the internal piping of the cylinder circuit to which the expansion vessel can be connected In connection with correct functioning of the boiler it is necessary for the YA expansion vessel to be connected to the expansion vessel pipe of the boiler The Solo boilers Q51S and Q60S are not provided with an expansion vessel connection When one of these Solo boilers is combined with a cylinder then one has to take into account that the expansion vessel should be connected between the three way valve and the boiler circulation pump 6 2 Expansion vessel module expansion vessel module figure 4 The ATLANTIC Q25S 0385 boilers can be provided with an expansion vessel module By this means t
5. water pressure sensor P1 orange SIG SH oe white red esee green red flue gas sensor T5 blue Display Option flow sensor T4 electrical diagram figure 11 9 Boiler controls The boiler is provided with a fully automatic microprocessor control called CMS Control Management System This control simplifies operation by undertaking all major control functions Initially when power to the unit is switched on it will remain on standby There is no indication Led on untill one of the programme keys is pressed The control panel display will show the relevant state When the installation is empty the display will show FILL The various parameters can be called up in two ways The Good state or standard read out Technical read out The first way shows a simple display read out The boiler in operation will always show Good When a message is necessary this will be shown instead of Good Thesecond wayis atechnical read out In normal situations the following will be shown onthe left the status in which the boiler is active onthe right the flow temperature the water pressure in the installation When a message error or blocking code is necessary this will be shown instead of the technical read out To switch over from the Good state to
6. x 33 m3 total number of burner run hours number of burner run hours CH number of burner run hours DHW total number of hours counter total number of run hours pump CH and DHW within how many hours is service required Service chapter SERV Value Description Range 1 OFF boiler in operation with burner function on OFF max 2 OFF fan adjustable and burner off OFF max 3 OFF pump adjustable with burner on OFF max 4 OFF showroom position ON active and OFF non active ON OFF ERRO Value Description Err L Err 5 Last saved error until 5 last predecessing errors 1 error code 2 operation status boiler 3 flow water temperature 1 4 return water temperature 2 5 kW load 6 pump capacity Parameter Info Service and Error chapters Table 6 Most of the data in this table can be requested by the BrainQ Most of the adjustments which are stated in this table are unnecessary when in combination with the ATLANTIC BrainQ thermostat and will be taken care of by the BrainQ itself and do not have to be adjusted For further information regarding to the BrainQ thermostat we refer to the ATLANTIC BrainQ installation manual 110 80 70 60 50 40 flow water temperature in 30 OTN ON OO AN Nee itl GNI xn raum 20 outside temperature in heating line adjustments Parameter Step 6 and 7 graph 2 11 4 Activating factory settings green key function To acti
7. clean both part by flushing it with clean water grease the O rings again wit acid free O ring grease to make fitting easier ifthereis aleak atthe siphon cup or tray the complete siphon unit has to be replaced by 54451610 remove the plug from the flue gas sensor if present turnthetwo shortclamping rods 4turn and remove them by pulling them forward Note the right turning direction red indicator lift the flue gas pipe out of the condensate tray press the condensate tray carefully downwards and remove it by pulling it forward replace the gasket between condensate tray and heat exchanger by a new one clean the condensate tray with water and a hard brush check the condensate tray on leaks Refitting is done in reverse order Note that the gasket of the condensate tray seals completely Make sure that during refitting the clamping rods they are put in the right position They should be turned vertical Replace always all removed gaskets of dismantled parts during the maintenance activities Put the boiler into operation and check the CO see page 32 14 3 Warranty For warranty conditions we refer to the warranty card supplied with the boiler 15 Technical specifications Boiler type Input Hs CH Q Input Hi CH Q Input DHW Efficiency class according BED Efficiency according EN677 36 30 part load Hi Efficiency according EN677 80 60 full load Hi Modulation range CH ca
8. control principal with on off thermostat 100 on off thermostat 100 on off weather dependant heating line K factor see also heating line graph heating line exponent see also heating line graph heating line climate zone see also heating line graph fine adjustment heating line day temperature fine adjustment heating line night tempe rature gradient speed booster after night reduction no yes frost safety temperature switch off temperature of additional cyl inder with Q boiler type of three way valve VC 2010 VC 8010 VC 8610 VC 6940 modulating maximum power DHW in kW Not applicable minimum pump capacity Value in parenthesis for Q60S maximum pump capacity CH address setting interface Spare Bus thermostat BrainQ Smart boiler 1 8 in cascade Range 20 906 01 02 03 04 min max 00 01 0 2 3 5 1 1 1 4 20 0 5 until 5C 5 until 5 C 0 15 00 01 20 until 10 40 80 00 01 min max 00 01 25 100 40 100 Yo 01 00 00 07 Information chapter INFO Value GJ GJ GJ hour hour hour hour hour hour Description flow water temperature T1 return water temperature T2 DHW temperature T3 outside temperature T4 flue gas temperature T5 actual power in 96 actual power in kW actual load in kW indication bus communication consumption total in GJ x 38 m3 consumption in GJ x 33 m3 consumption DHW GJ
9. LPG ATLANTIC BOILERS provides special kits for this purpose Special instructions are supplied with the kit Always check the installation of all of the parts through which gas flows A using leak search spray Hot water supply Connection of the drinking water installation should be done according to the national water laws The sanitary water pipes can be connected to the installation by means of compression fittings The cold water inlet on the Combi boilers must be provided with the following counted in the water flow direction Dosing valve supplied Safety group Expansion vessel 6bar potable water blue A dosing valve must be fitted in the cold water pipe The dosing valve ensures that a quantity of water is supplied which has a guaranteed outlet temperature of 600 assuming a cold water temperature of 10 C The quantity of water is virtually unaffected by the water pressure With a water pressure lower than 1 5 bar itis advisable to remove the inside mechanism of the dosing valve 6 6 Condensation drain pipe gt gt gt ATLANTIC BOILERS produce condensate This condensate must be drained otherwise the boiler will not function Thecollecting condensation drain pipe should be connected to the drain by means of an open connection By this means the possibility of drain gases ending up in the boiler is prevented The drain connection should have a minimum diameter of 32mm Connect the condensation drain pipe a
10. absorbed current consumption of the external circulation pump may be 230 W 1 Amp The extra external pump must be selected according the installation resistance and required flow 0 0 0 5 pump index lines As standard the boiler is provided with a water filter in the return pipe of the boiler With this possible contamination of the central heating water is prevented from ending up in the boiler The boiler is also provided with an internal safety valve set at 3 bar This is connected to the waste discharge together with the condensation discharge If all or a large part of the radiators are provided with thermostatic radiator valves it is advisable to use a pressure difference control bypass order to preventflow problems in the installation The boiler is designed to be used on sealed system only Additives in the installation water are only permitted in consultation with the country distributor When using more than one boiler in an installation please refer to the cascade installation instructions O Installation amp Servicing Instructions Installation amp Servicing Instructions N 6 2 Expansion vessel The central heating system must be provided with an expansion vessel The expansion vessel which is used should be geared to the water content of the installation The pre charge pressure depends on the installation height above the mounted expansion vessel See table 4
11. alternate with indication of water pressure boiler power of 5096 is possible The installation needs to be topped up HIGH indication remains continuously visible the boiler is taken out of operation The installation pressure needs to be decreased by draining water 12 13 Ins Wei ET 4 Regulatioris eaten at ear KUPATA YA 4 SCOPE OF tlie sdpply s s euin eese sec t eee ESL SC Ls 6 Description of the boler cane 6 Mountinig thic DOUG AIKA 6 5 1 Bro ieee alee ca nia tein een ed 7 Connecting the Dola Tende kd ag ae 9 6 1 Central heating system 9 6 2 ExpansiOn VOSSEl aaa ke kawa 11 6 2 1 Expansion vessel module Kamisaa aaa 12 6 3 Underfloor heating system plastic 13 06 4 GASCON OCTO a WA ere Mp ena poe avid EA 13 6 5 pa WAA KA Ua UA AAA WAKAWA NAA AAA tuber eR WAWA 13 6 6 Gondernsatioridralrm plpo ret dette ar p ur odi rc feda 14 6 7 Flue gas exhaust system and air supply system 15 6 7 1 Dimensions of the flue gas and air intake 18 External hot water cylinders cer nete e tee mie dv tag 19 Electrical COnneGtiori 2 AA as eet EE pO RENNES ERR 20 Ec 22 9 1 Explanation of the function keys
12. filling topping up the installation you use the filling loop according to the following procedure Switch on the power supply The display will show FILL All functions off heating DHW and pump Push briefly the STEP button P x x water pressure in bar Open the filling loop Indication on display increases Fill up slowly to 1 5 to 1 7 bar STOP appears on the display Close the filling loop ON DO oa De aerate the complete installation start at the lowest point 10 Check the water pressure and if necessary top it up 11 Close the filling loop 12 Activate the functions in use heating fim DHW 57 and or pumps 13 If A xx appears on the display wait for 17 minutes 14 Check the water pressure and if necessary top it up to 1 5 to 1 7 bar 15 Close the filling loop 16 Press the STEP button 17 Be sure that the filling loop is closed 18 After the automatic de aeration program A xx is finished the boiler will return to the Good state or Technical read out Check the water pressure regularly and top up the installation when necessary The working pressure of the installation should be between 1 5 and 1 7 bar when the installation is cold It can take a while before all air has disappeared from a filled installation Especially in the first week noises may be heard which indicate the presence of air The automatic air vent in the boiler will make this air disappear which means t
13. fitted in a different location then the pipe can be lengthened by means of a 32 mm PVC sleeve The flue gas exhaust system and air supply system It consists of a concentric connection 80 125 mm Cold and hot water pipes Only Combi boilers These consist of 15 mm copper pipe and can be connected to the installation by means of compression fittings It is recommended that isolation valves are fitted to all heating and hot water A connections to facilitate ease of future maintenance It is advisable to spray clean all of the unit s connecting pipes and or to spray clean blow clean the installation before connecting it to the unit 6 1 Central heating system Connect the central heating system according to the actual regulations The boiler pipes can be connected to the installation by means of compression fittings Reducers should be used for connecting to thick walled pipe welded or threaded When removing the plastic sealing caps from the pipes contaminated testing IN water may be released The boiler has a self adjusting and self protecting control system for the load and the pump capacity By this means the temperature difference between the flow and return water is checked Table 3 shows the water displacement which supplies the circulation pump at certain installation resistance Boiler type pump type water flow rate permissible installation resistance Vh kPa UPER l min mbar Q25C 20 60 16 2 972 29 290 Combi Q3
14. order to be able to fit a coaxial flue system or a twin supply On the left side of the boiler at least 50 mm and on the right side 10 mm must be reserved to allow fitting or removing of casing The location of the boiler can be determined by using the template located inside the boiler packaging Lift the boiler only by the boilers rear wall Lifting and carrying precautions Liftonly a manageable weight or ask for help Whenliftingthe boiler bendthe knees and keep the back straight and feet apart Donotlift and twist at the same time Lift and carry the boiler close to the body Wear protective clothing and gloves to protect from any sharp edges Installation amp Servicing Instructions 0D ZEB Installation amp Servicing Instructions 5 1 Dimensions 50 wall i wall dimensions in mm Boiler type Height Width Depth Left side flue gas exhaust m gt Centre to centre flue gas exhaust and supply back flue gas exhaust Left side gas pipe Left side flow pipe Left side return pipe Left side condensate pipe Left side expansion pipe Left side return pipe DHW Left side cold water pipe Left side hot
15. such as burner pressure and adjustment of the air quantity are unnecessary due to the fact that the boiler operates with a so called zero pressure control This means the correct gas quantity is controlled by the suction operation of the fan The fine adjustment which is carried out at the factory is once only which means that adjusting of these values is unnecessary Only in case of replacing of the gas valve venturi and or fan the zero pressure and the incorrect CO2 adjustment has to be checked and if necessary adjusted at the right value Always check the installation of all parts through which gas flows using leak search spray 13 1 Checking for contamination In order to be able to check the boiler for contamination in the following running years itis advisable to measure the maximum air displacement in the boiler when putting the boiler into operation This value can be different with each type of boiler In order to be able to measure this value follow the next procedure Press the MODE key for 5 seconds The display will show COGE followed by an arbitrary number Select by means of the or the key the code C123 Check point Press the Store key to confirm the code code blinks 1 igure Press the MODE key until SERV is shown Press the STEP key until 2 is shown alternately 2 and OFF will be shown Turnthe upper measuring nipple on the gas valve open fig 12 Connectthe hos
16. the Technical read out and vice versa Press 5 sec on the STEP key When the system has been filled the automatic venting program starts when a programme has been selected by pressing the key for Central Heating DHW or pump programme Quir Jo se The programme takes 17 minutes and stops automatically After this the unit will function normally See also Filling and venting the boiler and installation call for heating or hot water the control system will select the required water control temperature This water temperature is called the T set value On a call for central heating the boiler ignites first at low input The input is then changed slowly to match the load required The boiler operates in this way to avoid excessive water noises and temperature overshoot On a call for hot water supply the T set value of central heating return water temperature is monitored Depending on the amountof sanitary water which is withdrawn from the DHW cylinder the central heating return water temperature from which the input is adjusted will vary Installation amp Servicing Instructions N O Installation amp Servicing Instructions N I 9 1 Explanation of the function keys When the pump is switched on continuously it can lead to undesired heating up of the central heating system during the summer Central Heating programme key Switching the Central Heating on or off Led on off Hot Water pr
17. the flue gas outlet are in the same pressure area Room sealed system Open boiler en room sealed systerr figure 8 The appliance connection diameter is 80 125 mm to which the flue gas outlet and air supply system can be fitted with or without elbow pieces The maximum permissible pipe length is set out in Table 5 It is also possible to use a parallel pipe connection of 2x 80mm In this case a separate cover 125mm should be ordered Art nr 54323410 We advise to build a simple flue gas system and air supply system out of table 6 For further information aboutthe available components ofthe flue gas and air supply system we recommend you consult the Monopass Flue systems The ATLANTIC BOILERS flue gas system is meant and designed solely the use on ATLANTIC BOILERS central heating boilers adjusted for Nat gas or LPG The maximum flue gas temperatures are below 70 full load 80 60 C The proper operation can be influenced harmfully by changes of or adjustments to the correct set up Possible warranty claims will not be honoured if incorrect changes result in non compliance with the installation manual or local rules and regulations The flue gas systems described in this document are solely suited for ATLANTIC central heating boilers of the ATLANTIC boiler range For this purpose the CE Certificate has been supplemented under the Gastec nr 0063BQ3021 0063AS3538 and 0063AU31 10 The flue gas s
18. 0 V 8 Calonfier connection Outside Brain Room External 24V PowerSupply Ex Q threeway sensor Smart therm safety 100 mA 3 sonsor orion Three way valve VC2010 or VC6940 Ei a LL 9s In case of application S gs Anticipation resistance aa 5 sensor T3 900 654321 Combi or Solo with non resident calorifier lonisation Ignition External trafo 230 0 0O brown f SV o Ins blue black geel groen x8 e blue 2 05 o4 o3 24V 230V white red black red green blue green o5 o4 o3 o2 Gas valve 24V X5 grey CMS brown brown yellow FoR oP ss 25 8 green black return sensor T2 white white yellow brown blue red
19. 2 45 9 6666 6666 109 1 109 3 97 4 97 3 6 0 33 3 88 447 6 8 36 3 9 8 48 7 69 70 3 62 4 86 165 150 53 64 500 660 5 7 20 70 20 70 22 Q60S 60 54 6666 109 3 97 3 8 8 52 5 9 8 57 3 70 5 71 168 64 660 20 70 Table 7 Installation amp Servicing Instructions oO Installation amp Servicing Instructions ATAG C2 o 16 Parts of the boiler 08 3 4 O08 X OO G Q SERIES T1 flow sensor T2 return sensor T3 cylinder sensor DHW combi P1 water pressure sensor G gas pipe A flow connection central heating R return connection central heating C condensate pipe figure 15 1 heat exchanger 8 ceramic burner cassette 15 thermostatic mixing valve 2 ignition unit 9 cylinder DHW Combi 16 flue gas discharge 3 fanunit 10 operating panel 17 combustion air supply 4 airinlet damper 11 Control Tower CMS 18 air box 5 gas valve 12 water filter return CH 19 type plate 6 safety valve 18 three way valve 7 automatic air vent 14 circulationpump E expansionvesselpipe Q51C K cold water pipe combi W hot water pipe combi 17 Installation examples 17 1 Radiator installation without thermostatic radiator valves MAMA 18 19 20 22 23 24 25 26 27 installation example 230 V 230 v 230 V
20. 8C 20 70 24 6 1478 20 200 Q51C 20 70 30 1 1803 Q25S 20 60 9 7 583 47 470 Q25S 20 60 16 2 972 32 320 Solo Q38S 20 70 24 6 1478 22 220 Q51S 20 70 30 1 1803 Q60S 20 70 38 9 2333 Installation resistance table 3 A low velocity header must be connected to the Q51C Q51S and 0605 to prevent flow problems over the boiler ATLANTIC supplies the AA1OVO9U Low velocity header for 1 boiler This can be IN connected directly under the boiler on the flow and return pipe external installation pump with low velocity header figure 3 If the installation resistance is higher than the stated value the pump will rotate at maximum pump capacity and the load will be adjusted until an acceptable temperature difference between flow and return water has been obtained If after this the temperature difference remains to much then the boiler will switch itself off and wait until an acceptable temperature has arisen If an unacceptable temperature is detected then the control will repeatedly try to achieve water flow and if this does not work then the boiler will switch off If the capacity of the boiler pump is insufficient an extra external pump can be installed in combination with a low velocity header in series with the boiler The electrical side of this external circulation pump can be connected in the Control Tower by which means this pump switches at the same times as the boiler pump The maximum
21. Adjustments When the boiler is installed it is in principal ready for use All adjustments of the boiler control are already pre programmed for a heating system with radiators convectors with a flow temperature of 85 C The adjustments ar e described in the Parameter chapter on page 28 In certain cases adjustment have to be altered in case of Lowerflowtemperature More boilers in Cascade i e Read through the Parameter chapter to adjust the boiler to its installation Contact ATLANTIC BOILERS in case of doubt Please follow next procedure to alter adjustments Press the Mode key for 5 seconds The display shows COGE followed by an arbitrary number Press by means of the or the key until the code C123 is shown Press the STORE key to confirm the code code blinks1 x Now you have access to the installer level There are 4 chapters PARA Parameters Information chapter no adjustments possible SERV Service chapter ERRO Error chapter no adjustments possible The content of the chapters is described on the following pages Press briefly the MODE key to select one of the 4 chapters i e PARA Press once or more briefly on the STEP key to select a Parameter parameter visible on the left value on the right Alter the value if necessary possible by means of the or the key Press briefly on the STORE key to confirm the alteration When you have to change more values repeat from step 5
22. Consult the details on this plate to verify whether the unit is compliant with its intended location e g gas type power source and exhaust classification On completion of the installation the installer or commissioning engineer must fill out and complete the Benchmark commission section of the boiler log book and hand to customer or end user for future record keeping The Benchmark log book must also be filled out and completed by the service agent following each service call and returned to the customer A copy of the Benchmark commissioning certificate must be returned to ATLANTIC BOILERS along with the warranty registration card to register the appliance for the standard warranty benefits Relevant Installation Service and User manuals Cascade Hydraulic cascade system Monopass Flue system individual PP Overpressure Flue system cascade BrainQ Digital room thermostat MadQ Cascade Zone controller Regulations The following regulations apply to installation of ATLANTIC central heating Legislation and Regulations Gas Safety Installation and Use All gas appliances must by law be installed by a competent person eg Members of CORGI and in accordance with the current Gas Safety Regulation Failure to install appliance correctly could lead to prosecution In addition to the above regulations this appliance must be installed in compliance with the current IEE Regulations the Building Standards Scotland Consolidation
23. Installation amp Servicing Instructions ATLANTIC BOILERS Q Series Boiler G C No Q25S 41 310 08 Q 38S 41 310 09 Q51S 41 310 10 Q 60S 41 310 11 Q25C 47 310 10 Q38C 47 310 11 Q51C 47 310 12 CE PIN 0063BQ3021 8G 51 40 00 03 06 Changes reserved These instructions to be retained by user O Installation amp Servicing Instructions N Explanations of symbols and signs on the Control Tower display display Central heating Domestic hot water DHW Pump programme Mode key 1 e i 6 2 8 e Operation indication in the first display position by technical read out No heat requirement Ventilation phase Ignition phase Burner active on central heating Burner active on hot water Fan check Burner off when room thermostat is demanding Pump overrun phase for central heating Pump overrun phase for hot water Burner off because of to high flow water temperature Automatic venting programme Reset key From Good read out to Technical read out and vice versa Press 5 sec on the STEP key FILL Water pressure is to low lt 0 7 bar FILL indication remains continuously visible the boiler is taken out of operation The installation needs to be topped up We URS nE Water pressure is too low 1 0 Water pressure is to high 22 8 if bar flashing FILL will
24. Press once or more on the MODE key until StBY or Good is shown After a few seconds the text StBY will be replaced by the technical read out or Good state Depending from the position the access code is keyed in When you want to return from an arbitrary position to the original read out press once or more on the MODE key until StBY is shown When during 20 minutes no single key is used the display will return automatically to its original read out Good state or technical read out O Installation amp Servicing Instructions N O Installation amp Servicing Instructions N Parameter chapter PARA 1 2 5 6 is 10 111 14 15 23 31 36 43 45 48 49 89 Factory 850 01 max 00 2 3 1 4 10 0c 0c 30 63 max 0 25 50 100 00 Description maximum flow temperature CH type of CH installation radiators air heating convectors T max flow 85 K factor heating line 2 3 gradient 5 C min gear differential 6 radiators with large surface areas or underfloor heating as additional heating T max flow 70 factor heating line 1 8 gradient 5 C min gear differential 5 under floor heating with radiators as additional heating T max flow 606 factor heating line 1 5 gradient 4 C min gear differential 4 full under floor heating T max flow 506 factor heating line 1 0 gradient C min gear differential 3 maximum power CH in kW
25. Regulations Regulations and bye laws of the Local Water Authority and the Current Health and Safety Regulation Ireland Irish standard 813 Domestic gas installations Ba OC X pp The current Electricity at Work Regulation must be complied with and also be in accordance with the relevant and current editions of the British Standards The Q Series boiler is a certified appliance and must not be modified or installed in any way contrary to this Installation Manual Manufacturers instructions must not be taken in any way as overriding statutory obligations The Q Series is a central heating unit with an optional integrated hot water function These units must be connected according to these instructions and all installation norms in respect of the part of the unit to be connected Observe the following rules of safety All work on the unit must take place in a dry environment ATLANTIC units may never be in operation without their housing except in connection with maintenance or adjustments see Chapter 13 and 14 Never allow electrical or electronic components to come into contact with water Carry out the following tasks in connection with maintenance etc to an already installed unit Shut down all programmes Close the gas tap Remove the plug from the wall socket Close the stop cock of the unit s intake connection Take note of the following when maintenance or adjustments are needed Th
26. The air box remove the transparent air box clean the box with a cloth with a simple non abrasive cleaning agent The fan unit and burner cassette remove the electrical connection plug from the gas valve and fan motor loosen the nut of the gas pipe under the gas valve replace the gasket by a new one loosen the front cross head screw of the black plastic silencer afterthis turn the two clamping rods 1 4turn and remove them by pulling them forward Note the right turning direction red indicator Slightly lift the fan unit and remove it towards the front of the heat exchanger remove the burner cassette out of the fan unit check the burner cassette on wear pollution and possible cracks Clean the burner cassette with a soft bruch and vacuum cleaner If burners are cracked replace the complete burner cassette replace the gaskets between burner and fan unit and the gasket between fan unit and heat exchanger check the venturi and the gas air distribution plate for pollution and clean this part if necessary with a soft brush and vacuum cleaner If the air box contains a lot of dirt Q it is plausible that the fan itself is dirty as well To clean this the fan has to be removed from the hood and the venturi Clean the fan with a soft brush and a vacuum cleaner Replace the gasket and ensure that all gaskets of the fan parts are Heat exchanger check the heat exchanger for contamination Clean this if necessa
27. ccording to the actual regulations The following components are connected to the collective condensation drain pipe Condensation discharge Safety valve Draining of the condensation water to the external rain guttering is not permitted in view of the danger of freezing Before putting the boiler into operation fill the siphon with 300 ml of water The condensate pipe must be run using suitable corrosion resistant materials eg plastic O Installation amp Servicing Instructions O Installation amp Servicing Instructions 6 7 Flue gas exhaust system air supply system The flue gas exhaust system and air supply system consists of Flue gas pipe Air supply pipe Roof or wall terminal The flue gas exhaust system and air supply system must comply with ni Kin m The flue gas outlet and air supply installation must comply with the current regulation requirements IG UP 10 and BS 715 Ireland Irish standard is 813 section 9 10 1 All flue gas parts which are outside the fire resistant cover need to be in stainless steel la m PP Air filter la wi 1 Open boiler Boiler Class B IE A Free exhaust area SS FP PP MW PP MW Boiler Class C Permitted only when the air Lo intake and
28. cted to the control The burner is blocked until the flue gas sensor is reconnected Block 82 The flue gas sensor has short circuited heat requirement blocked and pump capacity at minimum LESS Block 85 The control has not detected a water flow The venting cycle is started If during this cycle water flow is detected the venting cycle is ended and the burner is released Error with a number in the last two positions Error 00 Poor flame forming Error 01 short circuit of 24 volt circuit E 002 02 flame forming Error 04 adjustment or error for voltage interruption Error 05 adjustment Error 12 fuse 24 volt 3AT faulty Error 18 maximum flow temperature exceeded Error 19 maximum return temperature exceeded Em un R8 En E 28 Error 28 number of revolutions not reported back from fan Error 69 or incorrect display D Error 80 maximum flue gas sensor temperature exceeded rn O Installation amp Servicing Instructions ATLANTIC BOILERS Atlantic 2000 Box 11 Ashton Under Lyne Lancashire 016 Tel 0161 621 5960 or 020 7237 4912 Fax 0161 6215966 E mail info atlantic2000 co uk Web www atlanticboilers com 40
29. e of the digital pressure gauge to the upper measuring nipple of the gas valve Press the key until the maximum value is achieved The fan will function to its maximum revolutions burner stays off Measure the under pressure and write down this value At the next commissioning visit this value may drop 20 of its original value on the moment of installation When this value is dropped more than 20 the boiler needs maintenance Press the key until OFF is shown keep key pressed With this the procedure is finished 13 2 Checking of the zero pressure control Check point contamination figure 13 Adjustment zero pressure figure 14 The zero pressure control is set at the factory To measure this value you need a difference pressure gauge with a range of 0 2 to 0 8 mbar Follow the next procedure Press the MODE key for 5 seconds The display will show COdE followed by an arbitrary number Select by means of the or the key the code C123 Press the Store key to confirm the code code blinks 1 x Press the MODE key until SERV is shown Press the STEP key once until 1 is shown alternately 1 and OFF will be shown Turn the upper measuring nipple on the gas valve open fig 13 Connectthe hose of the digital pressure gauge to the upper measuring nipple of the gas valve Press the key until the minimum value is achieved The fan will function to its
30. e unit must be able to function during these activities for this reason the unit s supply voltage gas pressure and water pressure must be maintained Ensure that these is not a source of potential danger during these activities Following maintenance or other activities always check the installation of all parts through which gas flows using leak search spray Following maintenance or other activities always replace the housing and secure it with the screw behind the door at the front of the casing The following safety symbols may be encountered in these installation instructions and on the unit This symbol indicates that the unit must be stored away from frost This symbol indicates that the packaging and or contents can be damaged as a result of insufficient care taken during transport This symbol indicates that whilst still in its packaging the unit must be protected from weather conditions during transport and storage KEY symbol This symbol indicates that assembly or dismantling must be carried out ATTENTION symbol This symbol indicates that extra attention must be paid in connection with a particular operation Useful tip or advice O Installation amp Servicing Instructions Installation amp Servicing Instructions o 3 Scope of the supply The boiler is supplied ready for use The supply kit is composed as follows Boiler with casing Template on the package wrapper Automa
31. e until 1 is shown alternately 1 and OFF will be shown Calibrate the CO meter Place the lance of the CO meter into the check point see fig 15 Press the key until the maximum value in kW is achieved The boiler will burn on full load value on display in kW Check Table 7 for the correct CO percentage page 35 Let the CO meter do its measuring procedure Adjust if necessary the adjustment screw to correct the CO value see fig 16 Ending the CO measuring procedure Press the key until OFF is shown keep key pressed With this the procedure has ended Replace the black cover on the gas valve and fix it with the screw 14 Maintenance Maintenance or changes to the unit may only be carried out by an authorised technician 141 Thefrequency of maintenance Weadvisethataninspectionis carried out every year with an overhaul everythree years depending from the running hours mentioned in the warranty conditions When doing this the circumstances ofthe boiler s location must be taken into account From this one can determine whetherto deviate from this advice Please contact the country distributor for further guidance on the frequency and service requirements 14 2 Maintenanceactivities To carry out the maintenance activities please follow the next procedure switch off the power supply remove the screw behind the door on the front of the casing Liftthe casing and remove it towards the front
32. ed on an incline sloping down towards the outside to prevent rainwater from coming in The appliance produces a white wisp of condensation pluming This wisp of condensation is harmless but can be unattractive particularly in the case of outlets in outside walls At this time there are 2 different ways of connecting the flue gas air intake system The flue gas duct forthe 60 100 80 125 and 100 150 are push fit connections see figure 10 The air intake for the 60 100 is a clamp ring connection These two types are interchangeable Cutting the pipe goes as follows Take out the inner tube by turning it until it releases from its security position Cutjust as much from the air intake part as from the flue gas part Take off the burrs from the cutting edge to prevent cutting the seals Click the pipes back together again Use special grease to simplify the fitting When mounting the flue gas system pay attention to the flow direction An arrow onthe product points this out Itis not permitted to mount a system upside down and will lead to complaints Installation amp Servicing Instructions LT g p 2 Pia Vy Das 60 100 250mm Dismantlement and shorten pipes figure 11 80 125 280mm 6 7 1 Dimensioning ofthe flue gas and air intake duct Example A 25kW with a concentric flue gas system 280 125mm has according to the table a
33. etpipe Such conditions must be considered and where necessary insulation ofthe inlet pipe may be required In cold and or humid weather water vapour may condense on leaving the flue terminal The effect of such pluming must be considered The terminal must not be located in a place where it is likely to cause a nuisance For protection of combustibles refer to IS 813 section 9 10 1 where the terminalis less than 2m 6 6ft above a pavement or platform to which people have access including any balcony or flat roof the terminal must be protected by a guard of durable material A suitable guard is available from the country distributor Where a terminal is fitted below a window which is hinged at the top and A where the hinge axis is horizontal and the window opens outwards the terminal shall be 1m below the bottom of the window opening If the boiler is to be located under stairs a smoke alarm meeting the requirements of I S 409 or equivalent must be fitted The flue must be terminated in a place not likely to cause a nuisance gt gt For horizontal sections the outlet system should always be fitted on an incline 50 mm m sloping down towards the appliance so that no condensation water is able to accumulate in the outlet system The chances of icicles forming on the roof outlet is minimised by causing the condensation water to run back towards the appliance Inthe case of horizontal outlets the inlet system should be fitt
34. he external expansion vessel is not required This expansion vessel module is placed behind the Q SERIES boiler by which means the expansion vessel is not noticeable The content of the two expansion vessels is 20 litres The pre charge The expansion vessel module canbe supplied with the necessary pipes to connect with the SERIES boiler The connecting pipes for the installation correspond with those the boiler and have the same centre to centre distance to the wall When checking the expansion vessels these are accessible via the left right and upper sides From these sides the tanks are also removable and the boiler does not have to be dismantled The space which is required for mounting the expansion vessel module corresponds with the required space for mounting an Q SERIES boiler They included template and mounting strip for the boiler which can be used for the expansion vessel module The boiler is fitted on to this after the expansion vessel module has been mounted The necessary mounting strip for the boiler is present on the module Article numbers the expansion vessel module without pipe connections AA1EMO9U pipe connections for expansion vessel module AA1LE04U 540 385 155 wall 660 105 side view of the module with boiler dimensions in mm figure 5 front view of the module with boiler dimensions in mm figure 6 O Installation amp Servic
35. he water pressure can reduce during this period and therefore top ping up with water will have to be done 10 1 Hot water supply Apply the water pipe pressure to the cylinder open main valve and or stop valve of the safety group Vent the cylinder and the hot water installation by opening a hot water tap Leave the tap open for as long as required until all air has disappeared from the cylinder and the pipes and only water is flowing from the tap O Installation amp Servicing Instructions N Installation amp Servicing Instructions N 11 Commissioning the boiler Before the boiler is fired ensure thatthe boiler and the system are well vented and free of air Purge the gas line between the gas meter and the boiler and carry out a gas soundness test as specified in the current Gas Safety Regulations The boiler does notrequire adjustment of the burner pressure and air quantity because itis self adjusting and is factory set at the correct value 11 1 Central Heating system Provided there is a heat requirement from the thermostat or control the central heating programme will be put into operation by means of the key central heating programme The circulation pump will start circulating and the boiler will start the burner 11 2 Hot water supply Provided there is a heat requirement from the cylinder the hot water programme will be put into operation by means of the JI key hot water programme 11 3
36. ing Instructions O Installation amp Servicing Instructions ES 6 3 Underfloor heating system plastic pipes When connecting or using an underfloor heating system designed with plastic pipes or plastic pipes are used elsewhere in the installation one should ensure that the plastic pipes used comply with the DIN 4726 4729 standard It is set out in this standard that the pipes may not have oxygen permeability higher than 0 1 g m3 d at 40 If the system does not comply with this DIN standard the underfloor heating component will have to be separated from the central heating appliance by means of No recourse can be made to the terms of the warranty in the event of failure L to observe the regulations pertaining to plastic underfloor heating pipes Gas connection The appliance pipe is fitted with an internal thread into which the tail piece of the gas tap can be screwed The gas supply must comply to the current Gas Safety Regulations Ireland Irish standard 813 Domestic gas installations The connection to the appliance must include a suitable method of disconnection and a gas control cock must be installed adjacent to the appliance for isolation purposes The nominal inlet working gas pressure measured atthe appliance should be 20 mbar for Nat gas G20 Make sure that the gas pipe work does not contain dirt particularly with new N pipes When the boiler has to be converted from natural gas to
37. length 0 8 5 bend resistance length 0 9 Maximum straight length 80 6 Maximum straight length 100 18 87 bend resistance length 18 45 bend resistance length 0 8 45 bend resistance length 0 9 60 100mm Concentric flue system B B B inm 980 125mm in m 9100 150mm inm STA Maximum straight length 60 100 12 Maximum straight length 80 125 31 Maximum straight length 100 150 40 87 bend resistance length 1 87 bend resistance length 87 bend resistance length 45 bend resistance length 1 45 bend resistance length 1 1 45 bend resistance length 1 1 Maximum straight length 80 125 13 Maximum straight length 100 150 34 Maximum straight length 80 125 6 Maximum straight length 100 150 40 45 bend resistance length 1 1 Dimensions flue gas system and air supply system Table 5 Installation amp Servicing Instructions ATAG Installation amp Servicing Instructions N e 7 External hot water cylinders Depending of the comfort preferences different external hot water cylinders can be connected to the boiler The choice of the cylinder depends on the coil output The coil output must comply with the boiler output A cylinder which is used in combination with a Q 51S or Q 60S should have a minimal capacity of 40 kW resp 45kW minimal 928mm coil The maximum permitted pressure drop is respectively 20 a
38. maximum flue straight length of 31m In the system that is going to be put in there are 2 x 45 bends so the maximum flue gas length is 40 2x 1 1 37 8 meters 16 25 kW The flue diameter is determined bythe total length of the run including for the connection pipe elbows fittings and terminal covers etc and the type andnumber of boilers installed into the system Anundersized flue pipe can lead to disorders Look attable 1 forthe choice of the system and the correct diameter The table below shows the maximum flue lengths with the different boiler outputs A longer flue gas length can be achieved by increasing the diameter to 100mm Explanation table 1 Two pipe flue gas system maximum noted length distance between boiler and roof terminal A Concentric flue gas system maximum noted length distance between boiler and roof terminal B When using bends the noted value behind every bend should be deducted from the maximum straight length Pipes with 60 100 diameter are only permitted on wall terminals in combination with ATLANTIC BOILERS until 25kW Two pipe flue system chimney lining A 2100mm inm Maximum straight length 80 31 Maximum straight length 100 40 87 bend resistance length 1 5 87 bend resistance length 1 8 457 bend resistance length 0 8 5 bend resistance length 09 Maximum straight length 80 18 Maximum straight length 100 39 45 bend resistance
39. minimum revolutions burner is active Measure the negative pressure Value should be 0 to 4Pa 0 to 0 04 mbar If the zero pressure deviates too much Remove black cover of the gas valve Remove cap with Torx key fig 14 Turn slightly the Torx screw behind the cap Turn left is positive pressure deviation Turn right is negative pressure deviation Ending this procedure is done by pressing the Reset key Proceed by checking the incorrect CO2 value and correct it if necessary O Installation amp Servicing Instructions O Installation amp Servicing Instructions N 13 3 Checkingthe CO A checkpoint CO figure 15 adjustment screw CO figure 16 The CO percentage is factory set This has to be checked at commissioning maintenance and faults This can be checked by means of the following procedure Remove the black cover of the gas valve by unscrewing the sealed screw Put the boiler into operation and take care that it can deliver its heat lip It there is no demand tor heat on CH turn the hot water tap completely open and measure the incorrect CO Press the MODE key for 5 seconds The display will show COGE followed by an arbitrary number Select by means of the or the key the code C123 Press the Store key to confirm the code code blinks 1 x Press the MODE key until SERV is shown Press the STEP key onc
40. nd 10 kPa at a flow of respectively 1417 and 1587 I h See installation example 16 2 on page 37 for the hydraulic connection 8 Electrical connection The appliance complies with the CE Machinery Directive 89 392 EEC The EC Low Voltage Directive 72 23 EEC and the EC EMC Directive 89 336 EEC A 230V 50Hz mains electrical supply is required fused externally at 5A The installation must continue to comply with the national rules for electrical installations the ECTI national rules for electrical installations The appliance must be connected to an earthed socket this must be visible and within reach The following general stipulations also apply Nochanges may be made to the wiring of the appliance All connections should be designed in accordance with the enclosed regulations Should it be necessary to change it the mains power supply cable may only be replaced with a mains power supply cable item No S4407300 The room thermostat and controls must be connected to their allocated connections All othertypes or makes of room thermostats or controls which are used must have a Volt free contact When using an on off thermostat or control itis possible that an anticipating resistance must be installed in order to prevent too high temperature fluctuations As a standard rule this means mercury thermostats This resistance wire is present in the Control Tower and must be connected to clamps 23 and 27 The anticipating resi
41. ogramme key Switching the Domestic Hot Water DHW facility on or off Led on off PC programme key adjusts the pump to continuous water circulation in the central heating system Led on or according to the pump overrun times on the relevant programs Led off e Mode key After briefly pressing a selection of the data chapters can be retrieved After pressing for 5 seconds it is possible to enter the code as described in chapter 11 3 Step key After briefly pressing the water pressure can be retrieved and pages per chapter can be retrieved After pressing for 5 seconds it switches from the Good state to technical read out and vice versa Reset key After briefly pressing for unlocking errors ending the access code After pressing for 5 seconds an operating stop is made for example for activating the automatic venting programme Some keys have other functions These functions are only active when according to the procedure described in chapter 11 3 adjustment has to be changed or data must be retrieved from the CMS The other functions are Central Heating programme key function Hot Water programme key function programme key store function which means that by means of this key a modified setting is confirmed Step key scrolling in a data chapter 10 Filling and venting the boiler and installation The central heating installation needs to be filled with potable water For
42. oiler anticipates the heat demand of the central heating system or the hot water facility When an outside sensor is connected to the boiler works weather dependently This means that the boiler control measures the outside temperature and flow temperature With this data the boiler calculates the optimal flow temperature for the installation Explanation of the type indication ATLANTIC 51C Type 51 Nominal load in kW C Combi S Solo The boiler has been tested according to valid CE standards and has a CE certificate and SEDBUK A rating Statement No banned materials including asbestos mercury CFC s have notor will not be included in the product 5 Mounting the boiler The room where the boiler will be placed must always be frost free Itis NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is installed Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed due to the extremely low surface temperature ofthe boiler casing during operation Therefore the requirements of BS 6798 Clause 12 and BS5440 2 may be disregarded The boiler can be mounted practically to any wall with the suspension bracket and the enclosed fixing equipment The wall must be flat and of sufficient strength in order to be able to carry the boiler weight with its water content Above the boiler there must be at least 250 mm working space in
43. pacity 80 60 C Modulation range CH capacity 50 30 C Nox class EN483 CO Flue gas temp CH 80 60 C on full load Flue gas temp CH 50 30 on low load Gas consumption G20 CH DHW at 1013 mbar 15C Electr power consumption max Electr power consumption stand by Current Fuse rating Degree of protection acc EN 60529 Weight empty Width Height Depth Water content CH Water content DHW After run time pump CH After run time pump DHW Pms Water pressure min max Pauw Water pressure DHW max Flow temperature max Pump type Available pump height CH Label DHW flow at 38 DHW flow at 60 DHW temperature T 210 C CE product identification number PIN Technical specifications kW Yo kW kW Yo m h Ww V Hz kg mm mm mm min min bar bar UPER kPa l min l min Q25C 25 22 5 31 5 0000 109 7 97 5 6 0 21 9 6 8 23 9 68 79 840 20 60 29 13 4 7 5 60 Combi O38C 38 34 2 6666 109 1 97 4 6 0 33 3 6 8 36 3 69 3 62 165 79 840 20 70 20 16 6 9 3 60 Q51C 51 45 9 0000 109 3 97 3 8 8 44 7 9 8 48 7 70 4 86 150 89 1000 20 70 23 2 13 60 Q Series Q25S 25 22 5 0000 109 7 97 5 4 4 21 9 4 9 23 9 5 9 68 31 2 38 106 10 230 50 5 IPXOD 50 500 680 385 3 5 5 1 3 85 20 60 32 Sedbuk A rate 0063BQ3021 Solo 0385 Q51S 38 51 34
44. rror indication A detected error is indicated on the display by means of blocking or error messages Adistinction should be made between these two messages due to the fact that blocking can be of a temporary nature however error messages are fixed lockings The control will try its utmost to prevent locking and will temporarily switch off the unit by blocking it Hereunder is a list of some messages Blocks with a number in the last 2 positions Block 01 External safety contact cut off Block 11 Maximum T of flow and return sensor in central heating has repeatedly been exceeded During the block normal operation of the hot water supply is possible The pump continues to operate at minimum capacity during the block TENE Block 12 Maximum T of flow and return sensor in domestic hot water has repeatedly been exceeded During the block normal operation of the central heating installation is possible During the block the pump continues to operate at minimum capacity LEGG Block 60 Incorrect parameter setting of the minimum or maximum power Block 67 T has been detected between flow and return sensor whereas the burner is not in operation After the T has disappeared the block will disappear Block 80 Maximum flue gas temperature has been exceeded if present The block will not be cancelled until the flue gas temperature has arrived below the temperature Block 81 The flue gas sensor is not connected although it was conne
45. ry with a soft brush and a vacuum cleaner Prevent dirt falling down into the heat exchanger Flushing the heat exchanger from the top down is not permitted Refitting of the components is done in reverse order Make sure that during refitting the clamping rods they are put in the right position They should be turned vertical Installation amp Servicing Instructions O Installation amp Servicing Instructions A Ignition electrode The replacement of the electrode is only necessary when the electrode is worn off This canbe checked by measuring the ionisation current The minimum ionisation currenthas to be higher the 4 on full load If the viewing glass is damaged the complete electrode must be replaced Replacement goes as follows remove the electrical connections of the electrode press theclips on both sides of the electrode to both sides and remove the complete electrode remove and replace the gasket Refitting of the components is done in reverse order Siphon and condensate tray first remove the condensate cup Check this for pollution If there is no sign of strong pollution it is not necessary to clean the condense tray If there is a strong pollution in the cup it is necessary to remove and clean the condensate tray remove the inner siphon pipe which remains in the condensate tray check the O rings of the cup as well as those from the pipe and replace if necessary
46. stance in the room thermostat has to be set at 0 11 A For more detailed questions regarding the components which are not supplied the country distributor should be contacted 230 V 230 V 230 V 230 V a Calorifier connection Outside Brain Room External 24 V Power Supply External Pump three way valve DHW sensor Smart therm safety 100 mA TINILIZINILIEINILI IE N L 9 pawn Qd A On Off contact 12 14 15 16 17 19 20 J BE 24 25 26 27 9 _ S BES 2 S os gt wn 55 55 gt 0 5 9 0 o o o gt E d iX fs o so v o 5 T D gt gt S72 To pum ESO a 9 Xx SS 9 e 5 Sg 338 Eo NO A D N o Oo ul Connection terminal figure 10 Connection terminal Q O Installation amp Servicing Instructions N N N Installation amp Servicing Instructions O 2 o3 4 A Pump PWM 230V 230 V 230 V 23
47. tic vent inside the boiler Installation instructions Safety valve inside the boiler Operating manual Suspension bracket Warranty Draining valve with T piece e Benchmark logbook Fixing material consisting of plugs and screws 4 Description of the boiler Room sealed boiler The boiler retrieves its combustion air to outside then dis charges the flue gasses to the outside Condensing Retrieves heat from the flue gasses Water condensates on the heat exchanger Modulating Higher or lower burning according to the heat demand Stainless Super solid kind of steel which keeps its quality for life It will not rust or erode in con trast to composition materials like alumi nium The Q SERIES boiler is a room sealed condensing and modulating central heatin boiler with or without an integrated hot water facility The boiler is provided with a compact stainless steel heat exchanger with smooth tubes A well thought out principal using durable materials The boiler bums gas for supplying warmth The heat is transferred in the heat exchanger to the water in the central heating system By cooling down the flue gasses condensate is formed This results in high efficiency The condensate which has no effect on the heat exchanger and the function of the boiler is drained through an internal siphon The boiler is provided with an intelligent control system CMS Control Management System The b
48. vate the factory settings again please follow the next procedure Note all altered adjustments will be set back Select when necessary the technical read out Select with the MODE key chapter PARA Press the STORE key The word Copy will appear and the factory settings are active again Installation amp Servicing Instructions N Installation amp Servicing Instructions 12 Isolating the boiler In some situations it may be that the entire boiler must be switched off By switching off the three keys with the lamps for central heating hot water and pump programme 2 Jor zk the boiler is switched off Leave the plug in the wall socket which means the circulation pump andthe three way valve are activated once every 24 hours in order to prevent jamming A In the event of frost danger it is advisable to drain the boiler and or the installation 13 Commissioning Work on the boiler must be carried out by a competent person Ref Gas Safety Installation Use and Regulations using correctly calibrated instruments with current test certification To commission the boiler the casing has to be removed The casing is locked with a screw behind the door on the front and the top of the casing is hooked behind a locking edge After removing this screw the casing must be lifted at the bottom by which means itis released from the locking edge Then the casing can be removed forward The boiler settings
49. water pipe Pipe length of g Pipe length of c Pipe length of f r e d w Back Centre of pipe c Back Centre of pipe g U Back Centre of pipe f r e d dimensions 270 65 185 285 370 430 475 18 50 60 25 40 50 680 660 385 495 120 270 65 185 445 530 18 50 60 25 40 50 680 840 385 335 120 270 65 185 285 370 430 725 795 18 50 60 25 40 50 680 1000 385 495 120 270 65 185 445 530 590 885 955 18 50 60 25 40 50 figure 1 talel 1 if zc boiler connections figure 2 Boiler type Gas pipe g V2 female 34 female V female 34 female Return pipe r mm 28 35 28 35 Expansion pipe e Hot water pipe w connection diameters table 2 Installation amp Servicing Instructions Installation amp Servicing Instructions e 6 Connecting the boiler The boiler has the following connection pipes Thecentral heating pipes These can be connected to the installation by means of compression fittings Thegas pipe Itis provided with a female thread into which the tail piece of the gas valve can be screwed Thecondensation drain pipe It consists of an oval 24 mm plastic pipe The drain pipe can be connected to this by means of an open connection If the open connection is
50. ystem should be built up using only ATLANTIC program products Combinations with other brands or systems are without written permission from ATLANTIC BOILERS is not permitted Horizontal flue system should always be installed sloping towards the boiler in order to avoid condensate lying in the flue system The minimum gradient is 50mm Mtr With the condensate running back to the boiler the risk of ice forming at the terminal is reduced The terminal should be located where dispersal of combustion products is notimpeded and with due regard for the damage or discolouration that might occur to building products in the vicinity see fig 9 terminal position for fan assisted boiler ee an open window or other opening 300 below gutters soil pipes or drain pipes mm 75 C below eaves mm 200 D below balconies or car port roof mm 200 E from vertical drain pipes and soil pipes mm 75 F from internal or external corners mm 300 G above ground or below balcony level mm 300 figure 9 H from a surface facing a terminal mm 600 from a terminal facing a terminal mm 1200 UA E ee K vertically from a terminal on the same wall mm 1500 L horizontally from a terminal on the same wall mm 300 M horizontally from a vertical terminal to a wall mm 300 Dimensions table 6 O Installation amp Servicing Instructions J O In certain weather conditions condensation may also accumulate on the outside of the airinl
Download Pdf Manuals
Related Search
Related Contents
SIMPLE Optoma WM02 交互型折りたたみ式歩行器 取扱説明書 note to installer: this manual should be left with the equipment user. リニアアンプ型サーボドライバ 取扱説明書 Jamo SUB 650 Manuale d`uso Peerless Industries PARAMOUNT PT660 User's Manual Copyright © All rights reserved.
Failed to retrieve file