        Dual DPT Technical manual
         Contents
1.  12    Technical manual DUAL DPT       Request      0b03200000018f60   Response      0b030200002045  0x0b Slave address 1 byte  0x03 Function code 1 byte  0x2000 Address 2 bytes  0x0001 Quantity 2 bytes  Ox8f60 CRC 2 bytes  0x0b Slave address 1 byte  0x03 Function code 1 byte  0x02 Quantity 1 byte  0x0000 Value1 2 bytes  0x2045 CRC 2 bytes    Page 13          lechnical data    Technical specification  DUAL DPT    Power supply    Temperature range   Relative humidity   Cabinet protection   Differential pressure transducer  Pressure measurement   Air connection    Overpressure  Accuracy    Resolution   Onboard temperature sensor  Accuracy  Resolution   External temperature sensors    Temperature range    Accuracy    Resolution    Communication    Weight  Dimensions  Mounting    Housing material    Page 14    12 VDC to 32 VDC  Via RS485 port      25  C    85  C   Max  95 RH  non condensing   IP54   2  0   250 Pa   0     1250 Pa   Air only   Tube     inner diameter of air hose  5 mm  Max  8 kPa    0     250 Pa  2 25  fullscale     6 Pa  0     1250 Pa  1 5  fullscale     19 Pa   incl  aging  temperature drift and conversion     1 Pa  1   30  C    70  C     C   1  C   Option of 2  NTC  Signal and Gnd   50  C     99  C      3  C in the range  50  C    36  C     1  C in the range  35  C    49  C     3  C in the range  50  C    99  C   lt   1 0  C in the range  lt   35  C    lt   0 2  C in the range  35  C    39  C   lt   1 0  C in the range  40  C    85  C   lt   1 5  C in the range 
2.  MEME MEME ME E 19    Page 2    Technical manual DUAL cer         Page 3          Read this first    The contents of this manual are subject to change without  notice  Lodam electronics holds the copyright to this user s  manual  The user shall follow any instructions given in this  user manual entirely and not only partly  Any non follow   ing of this user manual result in exclusion of all warranties   guarantees  and liabilities  CopyrightO 2014 by Lodam  electronics a s  All Rights Reserved        Disposing of the parts of the controller     INFORMATION FOR USERS ON THE  CORRECT HANDLING OF WASTE ELECTRI   CAL AND ELECTRONIC EQUIPMENT  WEEE     In reference to European Union directive 2012 19 EU and  the related national legislation  please note that     1  WEEE cannot be disposed of as municipal waste and  such waste must be collected and disposed of sepa   rately    2  The public or private waste collection systems defined  by local legislation must be used  In addition  the equip   ment can be returned to the distributor at the end of its  working life when buying new  equipment    3  The equipment may contain hazardous substances   the improper use or incorrect disposal of such may  have negative effects on human health and on the  environment    4  The symbol  crossed out wheeled bin  shown on the  product or on the packaging and on the instruction  sheet indicates that the equipment has been intro   duced onto the market after 13 August 2005 and that it  must be disp
3.  Off   7 Parity on     off On off  6 Parity even     odd Even Odd  5 Stopbits 1 2  4 Jan Baudrate    Bit pattern    Baudrate   vawe   switch a     115200  300  1200  4800  9600  19200  38400  115200       o O A    NPD     o     e  o    Page 11       6 10  Status information    The following input registers hold status for the module    Bitmask field      0x0001  Stopped Input Stopped  Device stops performing its regulation   Operation Dono 0x0002  Started register Started  Device is performing its regulation   0x0008  Error  0x0080  Restarting  0x0000 0xFFFF T  Input Application error codes   Eres Uie DACIE register BO Reflects a previous Opsignal command     Opsignal    6 11  MODBUS sample communi   cation    Note  The following sample is a general MODBUS commu   nication sample and is not for the DUAL     DPT     Request   0b041000000e75a4   Response      ObO4lcffffQ000095008b0e4a80014000b000108e   108fIffffOOOf  0002fff39f8e  OxOb Slave address 1 byte  0x04 Function code 1 byte  0x1000 Start addr 2 bytes  0x000e Quantity 2 bytes  0x75a4 CRC 2 bytes  OxOb Address 1 byte  0x04 Function code 1 byte  Oxic NB bytes of data 1 byte  Oxffff Value1 2 bytes  0x0000 Value2 2 bytes  0x0950 Value3 2 bytes  0x08b0 Value4 2 bytes  0xe4a8 Value5 2 bytes  0x0014 Value6 2 bytes  0x000b Value  2 bytes  0x0001 Value8 2 bytes  0x08e1 Value9 2 bytes  Ox08f1 Value10 2 bytes  Oxffff Value11 2 bytes  0x000f Value12 2 bytes  0x0002 Value13 2 bytes  Oxfff3 Value14 2 bytes  Ox9f8e CRC 2 bytes    Page
4.  gt   85  C    1 RS485 port  dual connection  Half duplex  max 115 kB  Receiver Rin  gt   12 kOhm    80g  103 0 mm  w    85 6 mm  d    33 mm  h   With two screws    PC Lexan  transparent    Technical manual DUAL wj       O  Drawings                                                                                                                                                                                                                                                                                     i  E i  ds        E  A f  M   VA AN e  cc   A   TA c  LJ  CX   If IT IL I  Y  sil    es  68 4 mu    8 36 a  M 91  103                                                                                                                    7      Ro atado  sm  r    TU    bla dha   04 ml La    Page 15       9  Standards    The product is manufactured according to the following  standards       RoHS 2011 65 EC    Low voltage 2006 95 EU      EMC 2004 108 EC    61000 6 x Generic EMC    The following standards have been used    EN 61010 1   Safety requirement for electrical equipment for measure   ment and control     EN 61000 6 2  Immunity standard for industrial environments     EN 61000 6 3  Emission standard for residential  commercial and  light industrialenvironments     CE approved     Page 16    10  Trouble shooting      Check if there is power to the DUAL     DPT  range 12 VDC  to 32 VDC        Check if the communication address setting matches  the selected  Note  Address O shou
5.  position   300 Pa for the DPT 1250   150 Pa for  the DPT 250     When calibrated the Calibrate register is reset to O  If the  calibration is rejected the value of Calibrate is set to  1     6 3  Pressure readings    Read the following two input registers     regardless if it is a  Dual   DPT 250 or a Dual   DPT 1250     Address Possible Register Description  Values type    Pressure reading  transducer 1   Pressure1 0x0003 0 to 1250 Input register Pa  signed short integer     Pressure reading  transducer 2     Pressure2 0x0004 O to 1250 Input register Pa  signed short integer     6 4  Temperature readings    Read the following input registers     regardless if itis a  Dual   DPT 250 or a Dual   DPT 1250     Address Possible REST Default Description  Values type     10000 to  Templnternal 0x0005 c dig  Input register   Gar Ado ne  R   10000 to External NTC sensor input 1   mai   0x0006 EE or   metis Je WALE ea  15000   short circuit  TempExter  ROD    Tues CES  lt a  nal2 waco Cu 100  linpui regjister E  7000   not connected    15000   short circuit    Page 9       6 5  Hardvvare information    HWType    CmdReply    Status    Cmd    Address    Baudrate    Stopbits    Parity    OxFFO6    OxFFO7    OxFFO8    OxFF80    OxFF81    OxFF82    OxFF83    OxFF84    0x0020 DPT1250 Dual  Ox0021 DPT 250 Dual  0x0027 DPT1250 Single  0x0028 DPT 250 Single    Ox00   Nothing   0x02   Programming Done  0x82   Programming Error  0x03   Going to Application  mode    0x83   Cannot go to applicati
6. 674  1876  1341  975  720  540  401  315    Page 17       12  Index    A  Air connection 14    C   Cabinet protection 14  Communication 14  Communication modes 11  Connections 6  Connection samples 6    D   Definitions 5  Dimensions 14  Dipsvvitches 10  Dravvings 15    E  External temperature sensors 14    F  Function 7    H  Hardware information 9  Housing material 14    How to    6  M  MODBUS 7    MODBUS communication 12    N  NTC temperature   resistance table 17    O  Onboard temperature sensor 14  Overpressure 14    P   Power supply 14   Pressure measurement 14  Pressure readings 9  Pressure sensor calibration 9    Page 18    R  Relative humidity 14    S   serial number of the module 10  Standards 16   Status information 12    1  Technical data 14  Temperature range 14  Temperature readings 9  Trouble shooting 16    VV  Weight 14    Technical manual DUAL DPT    13  Notes    Page 19    Innovative and energy saving  climate control    When it comes to climate control Lodam is one of the most experienced you can turn to  For  more than four decades we have developed  produced and implemented electronic solutions  dedicated to optimising applications like     Compressors   Condensing units   Heat pumps   Air conditioning   Refrigerated truck and trailer  Reefer containers    We know the importance of reliable  energy efficient operation     and constantly push techno   logical boundaries to bring you the most innovative and forward thinking solutions     As part of the BITZE
7. R Group we are backed by one of the world s leading players in the  refrigeration and air conditioning industry  This alliance provides us with extensive network and  application knowhow and allows us to stay at the forefront of climate control innovation  And  to help ensure comfortable surroundings for humans and reliable protection of valuable goods  anywhere in the world     Lodam electronics a s   Kaervej 77 Tel   45 7342 3737  6400 Sanderborg Fax  45 7342 3730  Denmark lodam lodam com       For more information visit     www lodam com    27 02 2015 Contents are subject to change without notice     
8. ZLodam    BY BITZER GROUP                 UN    7    q dg Lo     4                                   ae  CS  a  o       Tp        Dual Differential Pressure tranducer    Technical manual    5  m DUAL DPT       Version 3 0    24          Contents    ls Read thiSTIST gt  uites oerte rete hurts ttg e gaudes bet a Ga 4  1 1  Reading instructions    eee 4  12  Userrnarn  al      stada eiae c e i Gos a da 4  2  General eR REPRE 5  3  Definitions 5 HETT                                     5  4  HOWIOns                                   E 6  Du COMMCCTIONS sc EE 6  O  FUNC HOM m                       7  6 1  Overview of Modbus functions 2 0 00    cece cee e eee e tee eeeeeeees 8  6 2  Pressure sensor calibration          cece cece aaa 9  6 3  Pressure readings              eee 9  6 4  Temperature readinss           eee 9  6 5  Hardware information    10  6 6  Reading the serial number of the module                                          10  6 7  Dipswitches         iaia eina 11  6 8  MODBUS address setting    11  6 9  Communication modes           iii n  6 10  Status Information    aaa E et Cents cR eei A ad 12  6 11  MODBUS sample communication    12  7  Technical data    eee eed be e ena Hn dici enden grape st e Rd ed 14  8  DIAWIMES  rescat crise querentes P I IH Re ERU at e a 15  O Standards  ptt mood ERO em tuia tun iue adt 16  10  Tro  ble  Shooting  oreet er oce a oder te vids d eot bert aded tel 16  Tl  NTC temperature resistance table    17  IDEE 18  ISSINOIBS UI Uu ERES I
9. done  4  Store filter constant done  131  Load filter constant error  132  Store filter constant error    write   Ox0000  Ready  Ox0001  Stop  Ox0002  Start  Ox0008  Reset Error  0x0080  Restart    Calibrate pressure sensors  Writing  OXOI calibrates pressure sensor  Read   signed short int    1  Failed  O  Calibration success  T  Calibrate  2  Using calibration value  from eeprom  3  Not calibrated    Oto50    Oto50    Application Commands  O  Ready   1  Clear   4  Load filter constant  5  Store filter constant    4  1250 Pa Dual  5  250 Pa Dual  6  1250 Pa Single  7  250 Pa Single    Register  type    Input register    Input register    Input register 0x0000    Input register    Input register      Input register      Input register      Input register      Input register    Input register    Input register 0    Input register    Holding       0x0000  register    Holding  register    Holding  register    Holding  register    Holding      0x0000  register    Holding  register    Unused    Stopped  Device stops performing  its regulation    Started  Device is performing its  regulation     Application error codes   Reflects a previous Opsignal com   mand     Pressure reading  transducer 1   Pa  signed short integer     Pressure reading  transducer 2   Pa  signed short integer     Onboard temperature sensor   OC  signed short integer     External NTC sensor input 1   OC  signed short integer     000   not connected  15000   short circuit    External NTC sensor input 2   9C  si
10. gned short integer    7000   not connected  15000   short circuit    Dip switch Com reading    Dip switch Com reading    Dirty flag for FilterC1  FilterC2    Application command reply    Ready     Commands can be issued   the sensor is always running   Stop     regulation   Start     regulation   Reset     operation error message  Restart     reboot  after 3 seconds      Filter constant in seconds  Use AppCmd to store setting    Filter constant in seconds  Use AppCmd to store setting    Application Commands   See AppCmdReply for reply to  AppCmd    1  Clear AppCmdReply   4  Reload filter constants   5  Update and store filter constants    Internal value  don t change    Technical manual DUAL DPT       Ox0000  Bootstrapper       AppType OxFFOO 0x0001  Bootloader Input register 0x0002 Application type  0x0002  Application  0x0018 DPT1250 Dual    0x0019 DPT 250 Dual s US   AppID OXFFOI 0x0022 DPT1250 Single Input register 0x0000 Application ID  0x0023 DPT 250 Single  Ee OxFFO2 0x0000     OxFFFF Input register   SW release number  SWVersion OxFFO3 0x0000     OxFFFF Input register   SW version number  SWLevel OxFFO4 Ox0000     OxFFFF Input register   SW level number  SWPatch OxFFO5 Ox0000     OxFFFF Input register   SW patch number    6 2  Pressure sensor calibration    To ensure a better accuracy  the DPT transducers can be  calibrated  Calibration is initiated by writing OXO1 to the  Calibrate register     It is possible to calibrate the sensor if the pressure is within  resting
11. ical manual DUAL wj       6 7  Dipswitches    There are two DIP switches on the pcb  one for MODBUS  Address and one for Com mode  baud rate etc      The DIP switches are only read during start up and the  values for Com mode and address are used  Any changes  on any DIP switch after start up will have no influence on  the running system     Dip switch       COM Mode Address             8  7   6  5  4  3   2   1 8  17  61 51141 18112111                                                                                                                                  Numbers are those printed on the DIP switch  A DIP switch  is on  1  if itis in the ON position     6 8  MODBUS address setting    Modbus address is selected using the 8 bit dipswitch  labelled adr on the pcb     Address O can not be selected since it is the broadcast  address  and it will be defaulted to address 23 for the  DPT1250 and address 24 for DPT250     Address          o EE NON O  EN E BR E                                                                Msb Lsb    6 9  Communication modes    Communication speed  parity  stop bits is selected using  the dipswitch labelled COM on the pcb     Se also the label in section 5  Connections on the module     COM Mode          811  1161 5114   3  2  11                                                                Msb Lsb    If no COM mode is selected it is defaulted to 115200 baud   1 stop bit and even parity    Switch   Description EET TE  On    8 RS485 Termination
12. in the  following sections     Client Server       Initiate request     pump  Bi Perform the action    Initiate the response    Receive the response      MODBUS configuration     register layout  Specification of  the protocol     Protocol   Modbus  RTU mode    Please see  http  Awww modbus org specs php    Modbus address   DUAL     DPT 1250Pa uses default address 24   DUAL     DPT 250Pa uses default address 25     Baud rate   Default 115200  but 9600 and 19200 are selectable    Number of data bits   8    Number of stop bits   Default 1  but 2 is selectable    Parity   Default Even  but None and Odd are selectable    Page 7       6 1  Overview of Modbus functions    Reserved    Operation    ErrCode    Pressure     Pressure2    Templn   ternal    TempEx   ternall  TempEx     ternal2    DIPCOM  DIPADDR    AppStatus    AppCm   dReply    OpSignal    Calibrate    FilterC1    FilterC2    AppCmd    Sensor  Type    Page 8    0x0000    0x0001    0x0002    0x0003    0x0004    0x0005    0x0006    0x0007    0x0013  0x0014    0x0015    0x0016    0x0800    0x0801    0x0802    0x0803    0x0805    0x0806    Bitmask field     0x000 1  Stopped  0x0002  Started  0x0008  Error  0x0080  Restarting    0x0000 0xFFFF  0x0085 Wrong Opsignal    O to 1250    Oto 1250     10000 to 20000   Scale 100      10000 to 20000   Scale 100      10000 to 20000   Scale 100     Oto 127  Oto 255    O  If nothing changed  1  If FilterC1 of FilterC2 is changed  and not stored yet     O  Ready   3  Load filter constant 
13. ld not be used       Check if the communication speed matches the select     ed       Check if communication is running  The green LED is    flashing regularly at start up and when no communi   cation is active  It flashes irregularly together with the  normal flash frequency when communication is active     Technical manual DUAL DPT       I  NIC temperature   resistance table    The DUAL     DPT temperature inputs are for a NTC  temperature sensor  The curve for a standard Lodam NTC  temperature sensor is used     The table below shows the relation between temperature  and measured resistance in the NTC sensor and can be  used to measure if the read temperature matches the  measured resistance     Resistance is in Ohm and temperature is in 9C  The right  columns lists the resistance at a temperature of the left  most column plus the temperature in the heading of the  right column  i e  O9C   2  C  440C etc     667828 579718   40 335671 294193   30 176683 156199   20 96974 86415   10 55298 49663  0 32651 29500  10 19904 18093  20 12494 11420  30 8056 7402  40 5325 4916  50 3601 3339  60 2487 2315  70 1752 1637  80 1256 1178  90 916 862  100 679 640  110 510 483  120 389 369    504230  258307  138322  17121  44610  26688  16465  10450  6807  4542  3098  2157  1530  1105  811  604  457  350    439445  227196  122687  68927  40150  24173  15001  9572  6266  4200  2877  2011  1432  1037  768  571  433  332    383712  200184  108991  61693  36183  21922  13683  8777  5774  3887  2
14. on    mode  0x04   Going to Bootloader  mode    0x84   Cannot go to bootloader    mode  Ox8F   Function not supported    O  Cfg Not dirty  1  Cfg Dirty    O  Nothing   Clear   1  Clear  CmdReply   0    2  Program Configuration   3  Set Application mode and    Input register    Input register    Input register    reboot   wait 3 sec  a   4  Set Bootloader mode and E   reboot   wait 3 sec    5  Reset communication to   factory settings   OxOOXX Holding  register   Ox0001   9600 I   0x0002   19200 del   0x0003   115200 8  Holding   Us register   i  Dos Holding   2  Odd register    Note 1  Selected using DIP switches     6 6  Reading the serial number of    the module    Serial number is exchanged using Modbus files  To support    the Modbus files layout a device must implement Modbus  function  0x14  read  and Ox15  write      Read only files  RO  are identified in the range from  OxFFOO to OxFF7F and Read Write files  RW  are identi   fied in the range from OxFF80 to OxFFFF     Standard Modbus files      Payload    File num  Record     Descrip   ber number n do tion perau  yte  OxFF80 0x0000 0 31 PCBA S N  gt   Module  OxFF80 0x0001 0 31 S N    Page 10    Ox001C    0x0000    0x0000    0x0000    Ox0012    Ox0003     115200    1  Even    Reply to a command in Cmd register    If any register from OxFF80 upwards  has changed this field reflects the  dirty status     Cmd returns to O when a command  has been executed     Read only 1    Read onlyl    Read onlyl    Read onlyl    Techn
15. osed of separately    5  In the event of illegal disposal of electrical and elec   tronic waste  the penalties are specified by local waste  disposal legislation     Page 4       1 1  Reading instructions    The following symbols are used to draw the reader s  attention to different warning levels     E Important information   Danger   General danger     1 2  User manual    Before installation the user should be thoroughly  familiarized with this user manual  especially with  purposes  installation and operation     Special care should be taken when installing and connect   ing external equipment  air hoses and MODBUS com   munication cables  and handling the modules correctly  according to protection against ESD     Installation of the DUAL     DPT must be performed   by authorized personnel only  All warranties are   excluded in case installation is performed by  unauthorized personnel or in case the DUAL     DPT has not  been correctly installed     Technical manual DUAL DPT       2  General    The DUAL     DPT  Differential Pressure Transducer  is   a general purpose differential pressure transducer for  measuring air pressure  The DUAL     DPT has tvvo integrat   ed pressure sensor elements     Application areas could be ventilation systems for mon   itoring filter status and this way tell the actual pollution  level of the filter  Another area could be to measure  pressure levels to obtain maximum efficiency and reliabil   ity of fans     The DUAL     DPT has also an in
16. t DUAL     DPT on  the bus must therefore be terminated with the on board  120 Ohm termination resistor using DIP switch number 8  on the COM DIP switch     Power for the DUAL   DPT is taken from the RS485  connection     Page 6    5  Connections    Connections on the module  Label inside the Dual   DPT       module   a Ratings   N   VDC  12VDC to 32VDC  Temp2 Temp 1    Please see manual for complete data   a    a a    NTC tem  NTC temp2  NTC temp1  NTC tem         COM Addres  Selector Selector  See Manual See Manual          Adr128  E   Adr64  Z   4 3 2 1 4 3 2 1 Adr32  E6   oooo oooo   JE  Baudrate Adr8 JCZ1  Gnd  B A  VDC Gnd  B A  VDC   Baudrate Adr4  EZ   Modbus Modbus Baudrate Adr   CO  Baudrate Adrl   X Default 8xOFF E        Note  The External Supply is a future option     4VDC Future option  External power supply   12 VDC    32    VDC  Gnd Future option  Neutral  Temp1 NTC element 1     two wires  Temp2 NTC element 2   two wires  2 connections   same port  Used for wiring looping to  NE     the next DUAL     DPT unit   Gnd Neutral   B Data   inverted signal  A Data   signal  4VDC Power supply via RS485      12 VDC    32 VDC    COM selector 8 bit Dip switch for setting communication settings and    Baud rate  Address Setting the Modbus address in the range  selector 1 254    Technical manual DUAL wj       O  FUNCTION    Communication with the DUAL     DPT is via MODBUS   RTU   Configuration and reading of pressures and  temperatures from the DUAL     DPT is described 
17. ternal temperature sensor  and connection for two external NTC temperature sensors      allowing measurement of the temperatures where the  pressures are measured     With one DUAL     DPT two pressures and two temper   atures can be measured with just one unit  This ensures  a simple installation and reduces the space needed  All  connections are from one side     Communication with the DUAL     DPT is via MODBUS   RTU  over RS485     3  Definitions    Product range    ESD Electro Static Discharge   HW Hardware electronics   MODBUS Application layer messaging protocol   http   www   modbus org specs php   NTC Negative Temperature Coefficient   RS485 Hardvvare communication standard    Page 5       A HOW tO       Connection samples  The DUAL     DPT is connected using a 4 wired connector   RS485      There is 1RS485 port but it is with two connections so  the MODBUS signal can be looped on to the next device  without having to use double wires in the terminals     One master controller and one DUAL     DPT                                                                 MODBUS  RTU  via RS485  Master   DUAL Termination  120 Ohm  Controller DPT sblivated  One master controller and two DUAL     DPT   MODBUS  RTU  via RS485  4  Master DUAL  Controller DPT  MODBUS  RTU   via RS485  DUAL Termination  diis 120 Ohm  activated             To ensure proper operation of the MODBUS communica   tion both ends of the communication link must be termi   nated with a 120 Ohm resistor  The las
    