Home
GE Panametrics PanaFlow™ MV80 Flow Meter Manual
Contents
1. Field Connection Remote Connection for Communicator for Communicator Figure 4 1 HART Communications Wiring Diagram HART Communications 4 1 June 2007 HART Menus Online Menu 1 Device Setup 1 Process Variables lSnsr 2PV 2 Al Rnge 1 4mA 3PVAO 3A01 2 20 mA 3 Other 4 End l4mA 1 Test Device 2 20mA 2 Diag Service 2 Loop Test 3 Exit 3 Calibration 1 Apply Values 4 DJA Trim 2 Enter Values SE 2PVURV 3PVUSL 1Ta 2 PV unt 1PVLRV FENLSE f 3 Range Values PPVURY 3 Basic Setup 4 Device Information 3PVLSL 5 PV Xfer fnctn 4PVUSL 6 PV Damp 1 Distributor 2 Model 3 Dev id 4Tag 5 Date 6 Write Protect 7 Descriptor 8 Message 9 PV snsr s n Final assy 1 Universal Rev Revision s 2 Fld dev Rev 3 Software Rev 1PV 1 Sensors 2 PV Sensor Unit PV LSL PV USL PV Min span 3 Sensor information 1Snsr Damp 2 URV 1PVLRV 2 Signal Conditi ignal Condition 3 ALLRV 2 PV URV 4 Xfer Fnctn 5 AI rnge 1A01 14mA a 2
2. Meter Size Series 220 meter size or Pipe ID Series 221 pipe internal diameter inches Y Meter calibration constant pangs Series 220 pulses ft Series 221 pulses ft v Process Temp F Used to correct Meter Factor for thermal XXX expansion of meter body for Series 220 v Density Units are Ib f XXX v l Ref Density Units are DIr Used for calculation of E standard cubic meters standard cubic feet y and normal cubic meters Viscosity Wl ne Units are centipoise Cp ee Adaptive filter setting Low Flow Cutoff lt Vol xxx Xxx gt lt Mass xxx xxx XX gt XXX gt XXX e Low Flow Cutoff Low Flow Cutoff setting displayed setting displayed Serial Number in volumetric flow in mass flow XXXXXXXXX units view only units view only y Operation 3 9 June 2007 Password Menu Use the Password Menu to set or change the system password The factory set password is 1234 ENTER Run Mode JJ Password ENTER Password Menu SetPassword 1234 E Use T dk Gm keys to access menus 3 10 Operation Chapter A HART Communications June 2007 Wiring Figure 4 1 below details the proper connections required for HART Communications Vortex Meter Loop Power Pulse Output Rload 250 ohm min Optional Backlight Al Power Current Meter
3. A Startup To begin flowmeter operation 1 Verify the flowmeter is installed and wired as described in Chapter 2 2 Apply power to the meter At start up the unit runs a series of selftests that check the RAM ROM EPROM and all flow sensing components After completing the self test sequence the Run Mode screens appear see figure below Note Starting the flowmeter or pressing EX T will always display the Run Mode screens 3 The Run Mode displays flow information as determined by system settings Press the 4 arrow keys to view the Run Mode screens 4 Press the ENTER key from any Run Mode screen to access the Setup Menus Use the Setup Menus to configure the meter s multiparameter features to fit your application PF Mass FI ENTER Een p Password Volume QUU Flow Rate Setup Press EXIT to return Menus to Run Mode Total V Use ap d keys to access each item 3 2 Operation June 2007 Using the Setup Menus Mass Flow ENTER Rate p Password Setup Menus Volume ENTER Flow Rate Output Display Totalizer Units Diagnostics Calibration Password 358 Menu Menu Menu Menu Menu Menu Menu ota f M Y v v v v v v 4 20 mA Cycle Time Tot
4. 2 6 K yp d A Leld sca d ad 3 1 Flow Unobstructed Requirements 2 2 Velocity Range 1 3 Frequency Sensing ssuueuuununnn 1 3 Index June 2007 Index cont M Measurement Velocity eoe ess or ere Rea dE ee 1 2 Menus Calibration eines epee ig eee 3 9 Duagnoettc oo 3 8 Displ y x io iet tti eod 3 5 Hidden Diagnostics 5 1 Passwords o papis 3 10 Sep oput ebbe bod 3 3 Totalizer isi ties een ERE RA 3 6 Units oem ert Gaye ences 3 7 Meter Orientation Adjusting 2 21 O Operation Specifications A 3 Outputs Connections 4 20MA 2 25 Pulse Connections 2 26 Setting Ad hee ey EEN ee AE ee 3 4 P Packing Gland Connection 2 16 2 20 PanaFlow MV Flowmeter Configurations 1 5 Display Keypad Setup 3 1 ElECTrOMIES iss Ge Gee ser eren 1 6 Flange Spe 2 6 EI Te 2 12 Installation 2 1 Operation 0 0 00 eee 1 1 Overview sse nies p nee a 1 1 Programming 3 3 Run Mode 3 2 Series MV80 In Line 1 5 Series MV82 Insertion 1 5 2 8 Setup Memes 3 2 SAUDE ws os Wet wel Pte ede 3 2 Water Stvle eee eee 2 4 Password Men 3 10 Performance Specifications A 1 Permanent Insertion Tool 2 17 Physical Specifications A 4 Programming 3 3 Pulse Output 0 0 0 00 000005 2 26 R Rem
5. 1 of rate over a 1 296 of rate over 1 596 of rate over Flow Rate a 30 1 range 30 1 range a 30 1 range a 30 1 range Notes 1 Accuracies stated are for the total volumetric flow through the pipe 2 Nominal rangeability is stated Precise rangeability depends on fluid and pipe size Repeatability 0 1 of rate Response Time Adjustable from 1 to 100 seconds Material Capability Series MN SO In Line Flowmeter Any gas liquid or steam compatible with 316L stainless steel C276 hastelloy or A105 carbon steel Not recommended for multi phase fluids Series MV82 Insertion Flowmeter Any gas liquid or steam compatible with 316L stainless steel Not recommended for multi phase fluids Flow Rates Typical volumetric flow ranges are given in the following tables Precise flow range depends on the fluid and pipe size MV82 insertion meters are applicable to pipe sizes from 2 inch and above Consult factory for sizing program Table A 2 Air Minimum and Maximum Flow Rates scfm Nominal Pipe Size inches Pressure E 0 psig 100 psig 200 psig 300 psig 400 psig 500 psig Standard conditions are 70 F and 1 atmosphere Specifications A 1 June 2007 Flow Rates cont J Table A 3 Steam Minimum and Maximum Flow Rates lb hr Nominal Pipe Size in Pressure 1 1 5 2 3 4 6 8 Se l 722 1265 psig 9598 16815 l E 1651 2893 109 psig 50219 8798
6. Flowmeter Configurations eee June 2007 Overview Operating the PanaFlow MV The GE Sensing Series MV80 In Line and the Series MV82 Insertion PanaFlow MV Vortex Flowmeters provide a reliable solution for process flow measurement From a single entry point in the pipeline PanaFlow MV meters offer precise measurements of mass or volumetric flow The velocity sensor reduces the effects of pipeline vibration by incorporating a unique piezoelectric element that senses the vortex frequency To extend range ability at the low end of flow the meter s smart electronics calculates the Reynolds number Re based on constant values of fluid density and viscosity stored in memory and automatically corrects for any non linearity down to Re 5 000 PanaFlow MV digital electronics allows reconfiguration for most gases liquids and steam The instrument is loop powered 12 to 36 VDC with two output signals The pulse output signal is proportional to volumetric flow rate the analog linear 4 20 mA signal offers your choice of volumetric flow rate or mass flow rate The mass flow rate is based on a constant value for fluid density stored in the instrument s memory The local key pad display provides instantaneous flow rate in engineering units or to talized flow Figure 1 1 In Line Vortex Multi Parameter Mass Flowmeter The Series MV80 and MV82 P
7. rnge View Analog output range 1 4 3 1 1 AO1 View Analog output mA 1 4 3 1 2 AO alarm typ N A Not used HART Communications 4 3 June 2007 Fast Key Sequence cont Sequence Description Access Notes 1 4 3 1 3 1 4 mA View Loop test fix analog output at 4 mA 1 4 3 1 3 2 20 mA View Loop test fix analog output at 20 mA 1 4 3 1 3 3 Other Edit Loop test fix analog output at mA value entered 1 4 3 1 3 4 End Exit loop test 1 4 3 1 4 D A trim Edit Calibrate electronics 4mA and 20mAvalues 1 4 3 1 5 Scaled D A trim N A Not used 1 4 3 2 1 Poll addr Edit Poll address 1 4 3 2 2 Num reg preams View Number of required preambles 1 4 3 2 3 Burst mode N A Not used 1 4 3 2 4 Burst option N A Not used 1 4 4 1 Distributor N A Not used 1 4 4 2 Model N A Not used 1 4 4 3 Dev id View Device identification 1 4 4 4 Tag Edit Tag 1 4 4 5 Date Edit Date 1 4 4 6 Write Protect View Write protect 1 4 4 7 Descriptor Edit Vortex flowmeter 1 4 4 8 Message Edit 32 character alphanumeric message 1 4 4 9 PV snsr s n View Primary variable sensor serial number 1 4 4 menu Final assy Edit Final assembly number 1 4 4 menu 1 Universal Rev View Universal revision 1 4 4 menu 2 Fld dev Rev View Field device revision 1 4 4 menu 3 Software Rev View Software revision 1 5 Review N A Not used 2 PV View Primary variable value 3 PV AO View Analog out
8. Figure 2 4 on page 2 6 Table 2 1 below provides the recommended minimum stud bolt lengths for wafer style meter body size and different flange ratings The meter inside diameter is equal to the same size nominal pipe ID in schedule 80 For example a 2 meter has an ID of 1 939 2 schedule 80 Do not install the meter in a pipe with an inside diameter smaller than the inside diameter of the meter For schedule 160 and higher pipe a special meter is required Consult the factory before purchasing the meter Series MV80 Meters require customer supplied gaskets When selecting gasket material make sure that it is compatible with the process fluid and pressure ratings of the specific installation Verify that the inside diameter of the gasket is larger than the inside diameter of the flowmeter and adjacent piping If the gasket material extends into the flow stream it will disturb the flow and cause inaccurate measurements Table 2 1 Mininimum Stud Bolt Lengths for Wafer Meters Stud Bolt Lengths for Each Flange Rating inches Line Size Class 150 Class 300 Class 600 1 inch 1 5 inch The required bolt load for sealing the gasket joint is affected by several application dependent factors therefore the required torque for each application may be different Refer to the ASME Pressure Vessel Code guidelines for bolt tightening standards 12 bolt Figure 2 2 Flange Bolt Torquing Sequence Installati
9. Flow Channel Flow Profile FM Ft Ft 2 Ft 3 gpm Hz In Line Flowmeter Insertion Flowmeter Cross sectional area Actual Cubic Feet Per Minute volumetric flow rate American Society of Mechanical Engineers A non streamlined body placed into a flow stream to create vortices Also called a Shedder Bar British Thermal Unit an energy measurement European Electrical Code A factor used to correct for the non ideal changes in a fluid s density due to changes in temperature and or pressure Canadian Standards Association Width of a bluff body or shedder bar Diameter of a flow channel Frequency of vortices generated in a vortex flowmeter usually in Hz A pipe duct stack or channel containing flowing fluid A map of the fluid velocity vector usually nonuniform in a cross sectional plane of a flow channel usually along a diameter Factory Mutual Foot 12 inches a measure of length Square feet measure of area Cubic feet measure of volume Gallons Per Minute Hertz cycles per second A flowmeter which includes a short section of piping which is put in line with the user s piping A flowmeter which is inserted into a hole in the user s pipeline Glossary B 1 June 2007 Joule LCD 3e mA AP p act p std Permanent Pressure Loss Piezoelectric Crystal PRTD psia psig Py H Rangeability Reynolds Number or Re A unit of energy equal to one watt for one se
10. Inactive Mass Volume Example Y Maximum flowrate 600 gallons per minute 600 gallons per minute 10 gallons per second unit P ulse XXXX If unit per pulse is setto 600 gallons per pulse Y the totalizer will pulse once every minute Reset Total YES or NO If unit per pulse is set to 10 gallons per pulse ZEN the totalizer will pulse once every second Use the Totalizer Menu to configure and monitor the totalizer The totalizer output is a 50 millisecond 05 second positive pulse relay closed for 50 milliseconds The totalizer cannot operate faster than one pulse every 100 millisecond 1 second A good rule to follow is to set the unit per pulse value equal to the maximum flow in the same units per second This will limit the pulse to no faster than one pulse every second Example for Setting the The following sets the totalizer to track volumetric total gallons Totalizer Note All outputs are disabled while using the Setup Menus First set the desired units of measurement 1 2 3 Use the gt keys to move to the Units Menu see page 3 7 Press the y key until Volume Flow Unit appears Press ENTER Press the y key until gal appears in the numerator Press the key to move the underline cursor to the denominator Press the y key until min appears in the denominator Press ENTER to select Press the 4 key until the Units Menu appears 3 6 Opera
11. The meter should read electrical noise 60 Hz for example If all readings are correct re install the vortex sensor wires 4 Verify all meter configuration and troubleshooting steps previously described There are many possible causes of this problem consult factory if necessary SIGNAL SIGNAL Figure 5 2 Measuring Resistance Sensor Pin to Meter Ground Troubleshooting and Repair 5 5 June 2007 Electronics Assembly Replacement All Meters Returning Equipment to the Factory IWARNING Before attempting any flowmeter repair verify that the line is not pressurized Always remove main power before disassembling any part of the flowmeter Caution Electronics boards are electrostatically sensitive Wear a grounding wrist strap and be sure to observe proper handling precautions for static sensitive components Turn off power to the unit Locate and loosen the small set screw which locks the larger enclosure cover in place Unscrew the cover to expose the electronics stack Locate the sensor harnesses which come up from the neck of the flowmeter and attaches to the circuit board Use small pliers to pull the connector off the circuit board Locate and loosen the small set screw which locks the smaller enclosure cover in place Unscrew the cover to expose the field wiring strip Tag and remove the field wires Remove the screws that hold the black wiring label i
12. downstream of the sensor Note For liquid applications in vertical pipes avoid installing with flow in the downward direction because the pipe may not be full at all points Choose to install the meter with flow in the upward direction if possible Flow meter Flow meter Example 1 Example 4 x D o aa One 90 elbow before meter Reduction before meter Flow meter Example 2 Example 5 Flow conditioner Two 90 elbows before meter in one plane Expansion before meter if used Flow meter Flow meter Flow conditione if used Example 3 Example 6 Two 90 elbows before meter out of plane if three Regulator or valve partially closed before meter 90 bends present double recommended length If valve is always wide open base length requirements on fitting directly preceding it Flow conditioner if used Minimum Required Minimum Required Upstream Diameters Downstream Diameters No Flow No Flow With Flow Conditioner With Flow Conditioner Conditioner Conditioner Example A A C C B 10D N A 5D 15D 10D 5D 25D 10D 10D 10D 20D 10D 25D 10D D Internal diameter of channel N A Not applicable Figure 2 1 Recommended Pipe Length Requirements for Installation Series MV80 amp MV82 2 2 Installation June 2007 Series MV80 In Line Flowmeter Installation Install the Series MV80 In Line Flowmeter between two conventional pipe flanges as shown in Figure 2 3 on page 2 4 and
13. 0 750 inch diameter tubular stem The stem is inserted into the pipe until the sensing head is properly located in the pipe s cross section The sensing head fits through any entry port with an 1 875 inch minimum internal di ameter The sensing head of an insertion vortex flow meter directly monitors the velocity at a point in the cross sectional area of a pipe duct or stack re ferred to as channels The velocity at a point in the pipe varies as a function of the Reynolds number The insertion vortex flow meter com putes the Reynolds number based on constant values of the fluid s density and viscosity stored in its memory and then computes the total flow rate in the channel The output signal of insertion meters is the total flow rate in the channel The accuracy of the total flow rate computation depends on adherence to the piping installation requirements given in Chapter 2 If adherence to those guidelines cannot be met contact the factory for specific installation advice Introduction 1 5 June 2007 Flowmeter Electronics PanaFlow MV Flowmeter electronics are available mounted directly to the flow body or remotely mounted The electronics housing may be used indoors or outdoors including wet environments The instrument requires 4 20 mA loop power 12 to 36 VDC One analog output signal is available for your choice of volumetric flow rate or mass flow rate A pulse output is available for totalization The meter includes a
14. 4111 Web www gesensing com Ireland Sensing House Shannon Free Zone East Shannon Co Clare Ireland
15. ELE 3 6 U its MENU a i n b ee ve ted rq eR M i ecco dan ew Gb ortos edt ven 3 7 DIAGRAMA ni en lo aa r e a del a a 3 8 A Eoo etd bo pida Cold ek ede Contes bete teo ee 3 9 Password EE 3 10 June 2007 pU Has ei Table of Contents cont Chapter 4 HART Communications MALI ester vence pU Dt M EM EAM EI EM 4 1 HART MORS o enr eem er RAPI A steel v eeu eto hs 4 2 Fast Key SEQUENCE oss a aes eu ic ie tb bU e rebel pte desees 4 5 Chapter 5 Troubleshooting and Repair hidden Diagnostics Me isss ca sais o bb re id E Bode Eee be eed 5 1 Column One Hidden Diagnostics Values eene 5 2 Column Two Hidden Diagnostic Valdes o come o I ECCE do 5 3 Analog output calli dtlobi 22 oot edd o dedisset eis 5 3 Troubleshooting the Flowmeter irie tea dope vn MSto dot ctos att td Sad 5 3 Symptom QUEIBUEOEBO DAR pid tita br cta Gs deae dora Gee dose tcu 5 3 SVMPLOMAERFAWE OU DUE cbe a bee mee COR e quete ecu 5 4 Symptom NO DU concisa tal pU EAR pr ehe de RS RON eO dr 5 5 Electronics Assembly Replacement All Meiers 5 6 Returning Equipment to tbe Faetoryods eet ue tad ce e ae e 5 6 Appendix A Specifications SEO se ET Puta UR Aet pote Una e ic c Das ud cetus eege A 1 Operatie ir A peii eduies iu qs A 3 ls AAA ere Eet gege Elbe reg tue ab ES Wise Eae a ud A 4 SEENEN x RP VAT AS ar EE A 4 Appendix B Glossary Vi Chapter 1 Introduction OVetVIeW NEEN e E ie Va A ew OES Operating the PanaFlow MV
16. for pipes ten inches amp smaller Five inches for pipe diameters larger than ten inches Thickness of the pipe wall Measure the disk cut out from the tapping procedure or check a piping handbook for thickness Figure 2 11 Insertion Calculation Meters without Insertion Tool Example To install a Series MV82 Flowmeter with a standard probe S 29 47 into a 14 inch schedule 40 pipe the following measurements are taken F 3 inches R 5 inches t 0 438 inches The example insertion length is 21 03 inches All dimensions are in inches 2 20 Installation June 2007 Insertion Procedure with No Insertion Tool Packing Gland Connection Adjusting Meter IWARNING The line pressure must be less than 50 psig for installation Caution The sensor alignment pointer must point downstream in the direction of the flow Calculate the required sensor probe insertion length Fully retract the stem until the sensor head is touching the bottom of the stem housing Remove the two top stem clamp nuts and loosen two stem clamp bolts Slide the stem clamp away to expose the packing gland nuts Loosen the two packing gland nuts Align the sensor head using the sensor alignment pointer Adjust the alignment pointer parallel to the pipe and pointing downstream Insert the sensor head into the pipe until insertion length I is achieved Do not force the stem into the pipe Tighten the packing gl
17. it can withstand across the output terminals is 200 volts However there are current and power specifications that must be observed The relay can conduct a current up to 40 mA and can dissipate up to 320 mW The relay output is isolated from the meter electronics and power supply V R current limit 10K Pulse Pulse voltage V Pulse O Select resistor so that current through pulse lt 40mA Figure 2 17 Isolated Pulse Output with External Power Supply Optional Backlight The Sierra Model MV80 has an optional backlight connection Connection provided It is intended to be powered by a separate 12 to 36 VDC power supply or by the pulse power input Both are shown below Pwr Bklght Pwr Bklght 12 to 36 VDC Figure 2 18 Backlight Conn Powered by 12 36VDC Pwr Supply R current limit 10K DC Power 5 O Pwr Bklght Pulse Q DC Common OO Pwr Bklght Pulse Pulse voltage V Select resistor so that current through pulse 40mA Figure 2 19 Backlight Conn Powered by Pulse Power Input 2 26 Installation June 2007 nmm U e Remote Electronics Wiring The remote electronics enclosure should be mounted in a convenient easy to reach location For hazardous location installations make sure to observe agency requirements for ins
18. table Table 1 1 Measurable Ranges 1 ft s English p Ib ft 30 ft s Be Metric p kg m 9 1 m s The pressure drop for series MV82 insertion meters is negligible The pressure drop for series MV80 in line meters is defined as AP 00024 p V English units AP in psi p in IZ V in ft sec AP 000011 p V Metric units AP in bar p in kg m V in m sec The linear range is defined by the Reynolds number The Reynolds number is the ratio of the inertial forces to the viscous forces in a flowing fluid and is defined as Ro copo u Where Re Reynolds Number p mass density of the fluid being measured V velocity of the fluid being measured D internal diameter of the flow channel u viscosity of the fluid being measured Introduction 1 3 June 2007 Flow Velocity Range cont The Strouhal number is the other dimensionless number that quantifies the vortex phenomenon The Strouhal number is defined as SE V Where St 2 Strouhal Number f frequency of vortex shedding d shedder bar width V fluid velocity As shown in Figure 1 3 below PanaFlow MV meters exhibit a constant Strouhal number across a large range of Reynolds numbers indicating a consistent linear output over a wide range of flows and fluid types Below this linear range the intelligent electronics in PanaFlow MV automatically corrects for the variation in the Strouhal number PanaFlow MV s smart electronics
19. 0 2229 3905 200 psig 91485 160275 um 2685 4707 psig 132750 232570 3078 5393 ERR 174505 305721 TE 3433 6014 psig 216983 331080 Linear Range Smart electronics corrects for lower flow down to a Reynolds number of 5 000 The Reynolds number is calculated using the fluid density and viscosity entered into the memory Rangeability depends on the fluid process connections and pipe size Consult the factory for your application Velocity rangeability under ideal conditions is as follows Liquids 30 1 1 foot per second velocity minimum 30 feet per second velocity maximum Gases 30 1 10 feet per second velocity minimum 300 feet per second velocity maximum Process Fluid Pressure Table A 5 MV80 Pressure Ratings Process Connection Material Rating Flanged 316L SS A105 Carbon Steel C276 Hastelloy 150 300 600 Ib Wafer 316L SS A105 Carbon Steel C276 Hastelloy 600 Ib Specifications June 2007 Process Fluid Pressure cont Compression Fitting Packing Gland Packing Gland with Removable Retractor Packing Gland with Permanent Retractor Operation Process Fluid Temperature Ambient Temperature Power Requirements Output Signals Display Table A 6 MV82 Pressure Ratings Probe Seal Process Connection Ordering Material Code 2 inch MNPT ANSI 600 Ib 2 inch 150 Ib flange ANSI 150 Ib 2 inch 300 Ib flange ANS
20. AO alarm typ e Setup 3 Output Condition 1 Analog Output 3 Loop test 2 20mA SVEN 2 HART Output A D A trim 3 Other 5 Scaled D A trim 4 End 4 PV LRV 1PVLRV m 5 URV 2PVURV 1 Distributor 2 Model 1 Poll addr 3 Devid 2 Num req preams n 3 Burst mode ate d 4 Device Information 6 Write Protect SEU copian 7 Descriptor 8 Message 9 PV snsr s n Final assy 1 Universal Rev Revision s 2 Fld dev Rev 3 Software Rev 4 2 HART Communications Fast Key Sequence June 2007 nmm e Use password 16363 Sequence Description Access Notes 1 1 1 Snsr View Primary variable value 1 1 2 Al Rnge View Analog output range 1 1 3 AO1 View Analog output mA 1 2 1 Test Device N A Not used 1 2 2 1 4 mA View Loop test fix analog output at 4 mA 1 2 2 2 20 mA View Loop test fix analog output at 20 mA 1 2 2 3 Other Edit Loop test fix analog output at mA value entered 1 2 2 4 End Exit loop test 1 2 3 1 1 4 mA N A Not used apply values 1 2 3 1 2 20 mA N A Not used apply values 1 2 3 1 3 Exit Exit apply values 1 2 3 2 1 PV LRV Edit Primary variable lower range value 1 2 3 2 2 PV URV Edit Primary variable upper range value 1 2 3 2 3 PV USL View Primary variable upper sensor limit 1 2 3 2 4 PV LSL View Primary variable lower sensor limit 1 2 4 D A Tri
21. GE Sensing PanaFlow MV Vortex Flowmeter User s Manual GE Sensing Panaflow MV Vortex Flowmeter User s Manual 910 279A June 2007 June 2007 Warranty Return Policy Each instrument manufactured by GE Sensing Inc is warranted to be free from defects in material and workmanship Liability under this warranty is limited to restoring the instrument to normal operation or replacing the instrument at the sole discretion of GE Fuses and batteries are specifically excluded from any liability This warranty is effective from the date of delivery to the original purchaser If GE determines that the equipment was defective the warranty period is one year for general electronic failures of the instrument one year for mechanical failures of the sensor If GE determines that the equipment was damaged by misuse improper installation the use of unauthorized replacement parts or operating conditions outside the guidelines specified by GE the repairs are not covered under this warranty The warranties set forth herein are exclusive and are in lieu of all other warranties whether statutory express or implied including warranties of merchantability and fitness for a particular purpose and warranties arising from course of dealing or usage or trade If a GE Sensing Inc instrument malfunctions within the warranty period the following procedure must be completed 1 Notify GE giving full details of th
22. I 300 Ib 2 inch 600 Ib flange ANSI 600 Ib 2 inch MNPT 2 inch 150 Ib flange 2 inch 300 Ib flange 2 inch MNPT 2 inch 150 Ib flange 2 inch 300 Ib flange 2 inch MNPT 2 inch 150 Ib flange 2 inch 300 Ib flange 2 inch 600 Ib flange Standard temperature sensor 40 to 400 F 40 to 205 C Medium temperature sensor 250 to 500 F 120 to 260 C High temperature sensor 250 to 750 F 120 to 400 C Operating 5 to 140 F 20 to 60 C Storage 40 to 150 F 40 to 65 C 0 98 relative humidity non condensing conditions Loop powered 12 to 36 VDC Analog field rangeable linear 4 20mA output signal 1000 ohms maximum loop resistance selected by user for volumetric flow rate or mass flow rate Pulse field rangeable volume pulse output for totalization is a 50 millisecond duration pulse operating a solid state relay capable of switching 40 VDC 40mA maximum Alphanumeric 2 x 16 LCD digital display Six push button switches up down right left ENTER EXIT operable either directly on the display panel or with a hand held magnet through the display glass of the explosion proof enclosure Viewing at 90 mounting intervals Specifications A 3 June 2007 pU L Totalizer Physical Wetted Materials Enclosure Electrical Ports Mounting Connections Mounting
23. Position Certifications FM approvals Based on user determined flow units six significant figures in scientific notation Total stored in non volatile memory Series MV80 In Line Flowmeter 316L stainless steel standard C276 hastelloy or A105 carbon steel optional Series MV82 Insertion Flowmeter 316L stainless steel standard PTFE packing gland below 500 F 260 C Graphite packing gland above 500 F 260 C NEMA 4X cast enclosure Two 3 4 inch female NPT ports Series MV80 Wafer or 150 300 600 Ib ANSI flange PN16 PN40 PN64 flange Series MV82 Permanent installation 2 inch MNPT 150 300 600 Ib ANSI flange with compression fitting probe seal Series MV82 Hot Tap installation 2 inch MNPT 150 300 600 Ib ANSI flange and optional retractor with packing gland probe seal Removable under line pressure Series MV80 In Line Flowmeter No effect Series MV82 Insertion Flowmeter Meter must be perpendicular within 5 of the pipe centerline For liquid applications the pipeline must remain full at all times Construction Inspection ANSI ASME B31 3 Materials NACE MR 01 75 90 CE and FM approved CSA CENELEC approval pending Class I Division 1 Groups B C amp D T6 at Tamb 60 C Class I II Division 1 Groups E F amp G IP66 NEMA 4X A 4 Specitications Appendix B Glossary June 2007 A acfm ASME Bluff Body BTU Cenelec Compressibility Factor CSA
24. RTD scfm Shedder Bar Strouhal Number or St Totalizer Traverse Uncertainty V VAC VDC VORTEX Resistance temperature detector a sensor whose resistance increases as the temperature rises Standard cubic feet per minute flow rate converted to standard conditions usually 14 7 psia and 20 C A non streamlined body placed into a flow stream to create vortices Also called a Bluff Body A dimensionless number equal to the frequency of vortices created by a bluff body times the width of the bluff body divided by the velocity of the flowing fluid i e St fd V This is an important number for vortex flowmeters because it relates the vortex frequency to the fluid velocity An electronic counter which records the total accumulated flow over a certain range of time The act of moving a measuring point across the width of a flow channel The closeness of agreement between the result of a measurement and the true value of the measurement Velocity or voltage Volts alternating current Volts direct current An eddy of fluid Glossary B 3 June 2007 Index A G AC Power Wirld8 ooo oococoooo 2724 sGlOS8ary ie bI REX B 1 Adjusting Meter Orientation 2 21 Guidelines Analog Output Calibration 5 3 Cold Tap nose RB 2 9 Hot KEE 2 10 C Calibration H Analog Output o ooocococcoc o 5 3 Hidden Diagnostics Menu o a m E PERS 3 9 Column One 5 2 Cer
25. Type Example To install a Series MV82 meter with a standard probe S 29 47 in into a 14 inch schedule 40 pipe the following measurements are taken F 3 inches R 5 inches t 0 438 inches The insertion length for this example is 21 03 inches Insert the stem through the fitting until an insertion length of 21 03 inches is measured with a ruler All dimensions are in inches Installation 2 13 June 2007 A s B Installation with a Caution Compression Connection The sensor alignment pointer must point downstream cont in the direction of the flow IWARNING To avoid serious injury DO NOT loosen the compression fitting under pressure Enclosure adapter alignment pointer Compression nut Compression t Stem housing Sensor head 2 inch NPT connection connection Figure 2 7 Flowmeter with a Compression Type Fitting 2 14 Installation June 2007 Installation with a Compression Connection cont Calculate the required sensor probe insertion length Fully retract the stem until the sensor head is touching the bottom of the stem housing Slightly tighten the compression nut to prevent slippage 3 Bolt or screw the flowmeter assembly into the process connection Use PTFE tape or pipe sealant to improve the seal and prevent seizing on NPT styles Hold the meter securely while loosening the compression fitting Insert the sens
26. alin Mass Flow Sim Vor Meter Size Set Output 1 sec g Unit Freq or Pipe ID Password Number of Unit per Volume Highest E Digits Pulse Flow Unit Velocity Meter Factor Display TC ResetTotal Process sec Temp F Display i VFlow Density Display i Flow Ref Density Display ert Total Viscosity Vortek Coef Ck Low Flow Cutoff Serial Number 1 Enter the Setup Menu by pressing the ENTER key until prompted Programming the Flowmeter for a password All outputs are disabled while using the Setup Menus 2 Use the 4 y gt keys to select the password characters 1234 is the factory set password When the password is correctly displayed press ENTER to continue 3 Use the Setup Menus described on the following pages to customize the multiparameter features of your PanaFlow MV Flowmeter The entire lower display line is available for entering parameters 4 To activate a parameter press ENTER Use the 4 y gt keys to make selections Press ENTER to continue Press EXIT to save or discard changes and return to Run Mode Operation EE June 2007 Output Menu ENTER Run Mode JJ Password ENTER Use PF JV GO keys to access menus v Measure 4 20mA Output 1 None lt 4mA Xxxx gt lt 20mA xxxx gt TimeConst sec More gt Mass Be XXXX gt XXXX gt XXXX Volume P Example for Setting an The follow
27. anaFlow MV Vortex Flowmeters use a unique velocity sensor head to monitor volumetric flow rate The built in flow computer calculates mass flow rate based on a constant value of fluid density stored in the instrument s memory To measure fluid velocity the flow meter incorporates a bluff body shedder bar in the flow stream and the velocity sensor measures the frequency of vortices cre ated by the shedder bar The velocity sensor head is located downstream of the shedder bar within the flow body Introduction 1 1 June 2007 Velocity Measurement Vortex Shedding Frequency The PanaFlow MV vortex velocity sensor is a patented mechanical design that minimizes the effects of pipeline vibration and pump noise both of which are common error sources in flow measurement with vortex flowmeters The velocity measurement is based on the well known Von Karman vortex shedding phenomenon Vortices are shed from a shedder bar and the vortex velocity sensor located downstream of the shedder bar senses the passage of these vortices This method of velocity measurement has many advantages including inherent linearity high turndown reliability and simplicity Von Karman vortices form downstream of a shedder bar into two distinct wakes The vortices of one wake rotate clockwise while those of the other wake rotate counterclockwise Vortices generate one at a time alternating from the left side to the right side of the shedder bar Vortices inte
28. and nuts to stop leakage around the stem Do not torque over 20 ft Ibs Slide the stem clamp back into position Torque stem clamp bolts to 15 ft Ibs Replace the stem clamp nuts and torque to 10 15 ft Ibs Depending on installation requirements you may need to adjust the Orientation meter orientation There are two adjustments available The first rotates the position of the LCD display keypad and is available on both in line and insertion meters The second is to rotate the enclosure position This adjustment is allowed only on Series MV80 In Line meters Installation 2 21 June 2007 Display Keypad Adjustment All Meters Rotate display keypad in 90 increments maximum 180 from original position T Y Figure 2 12 Display Keypad Viewing Adjustment The electronics boards are electrostatically sensitive Wear a grounding wrist strap and make sure to observe proper handling precautions required for static sensitive components To adjust the display 1 Disconnect power to the flowmeter 2 Loosen the small set screw which secures the electronics enclosure Unscrew and remove the cover 3 Loosen the 4 captive screws 4 Carefully pull the display microprocessor board away from the meter standoffs Make sure not to damage the connected ribbon cable 5 Rotate the display microprocessor board to
29. ch full port isolation valve if used Use PTFE tape or pipe sealant to improve seal and prevent seizing on NPT style 3 Loosen the two packing gland nuts on the stem housing of the meter Loosen the stem lock bolt adjacent to the sensor alignment pointer Align the sensor head using the sensor alignment pointer Adjust the alignment pointer parallel to the pipe and pointing downstream Tighten the stem lock bolt to secure the sensor position Installation 2 17 June 2007 Insertion Procedure for Flowmeters with Permanent Insertion Tool cont Insertion Procedure for Flowmeters with Removable Insertion Tool 4 Slowly open the isolation valve to the full open position If necessary slightly tighten the two packing gland nuts to reduce the leakage around the stem 5 Turn the insertion tool handle clockwise to insert the sensor head into the pipe Continue until the top of the upper retractor bracket aligns with the insertion length position scribed on the stanchion Do not force the stem into the pipe 6 Tighten the packing gland nuts to stop leakage around the stem Do not torque over 20 ft Ib Note f line pressure is above 500 psig it could require up to 25 ft lb of torque to insert the flowmeter Do not confuse this with possible interference in the pipe Upper retractor bracket Stem lock bolt center Sensor alignment pointer Stem Stem clamp nuts Stem clamp bolts Packing gland nuts covered by s
30. cond Also equal to a Newton meter Liquid crystal display Mass flow rate Milli amp one thousandth of an ampere of current Viscosity a measure of a fluid s resistance to shear stress Honey has high viscosity alcohol has low viscosity Permanent pressure loss Line pressure psia or bar absolute The density of a fluid at the actual temperature and pressure operating conditions The density of a fluid at standard conditions usually 14 7 psia and 20 C Unrecoverable drop in pressure A material which generates an electrical charge when the material is put under stress An resistance temperature detector RTD with platinum as its element Used because of high stability Pounds per square inch absolute equals psig atmospheric pressure Atmospheric pressure is typically 14 696 psi at sea level Pounds per square inch gauge Liquid vapor pressure at flowing conditions psia or bar absolute Flow rate usually volumetric Highest measurable flow rate divided by lowest measurable flow rate A dimensionless number equal to the density of a fluid times the velocity of the fluid times the diameter of the fluid channel divided by the fluid viscosity e Re pVD u The Reynolds number is an important number for vortex flowmeters because it is used to determine the minimum measurable flow rate It is the ratio of the inertial forces to the viscous forces in a flowing fluid B 2 Glossary June 2007
31. correct for this non linearity by calculating the Reynolds number based on constant values of the fluid s density and viscosity stored in the instrument s memory PanaFlow MV Vortex Flowmeters automatically correct down to a Reynolds number of 5 000 Corrected Range o w Linear Range e h o a D Q E 3 Z o ic 5 e a o o 10 1 10 10 10 10 10 5000 Reynolds Number Re Figure 1 3 Reynolds Number Range for the PanaFlow MV 1 4 Introduction June 2007 Flowmeter Configurations PanaFlow MV Vortex Flowmeters are available in two configurations e Model MV80 in line flowmeter replaces a section of the pipeline e Model MV82 insertion flowmeter requires a cold tap or a hot tap into an existing pipeline The in line and insertion configurations are similar in that they use identical electronics and have similar sensor heads Besides installation differences the main difference between an in line flowmeter and an insertion flowmeter is their method of measurement For an in line vortex flowmeter the shedder bar is located across the entire diameter of the flow body Thus the entire pipeline flow is included in the vortex formation and measurement The sensing head which directly measures velocity temperature and pressure is located just downstream of the shedder bar An insertion vortex flow meter has its sensing head at the end of a
32. culated Ck at current operating conditions Ck is a variable in the equation that relates signal strength density and velocity for a given application It is used for noise rejection purposes Ck directly controls the fi value see above If the Ck is set too low in the calibration menu then the fi value will be too low and the vortex signal will be rejected resulting in zero flow rate being displayed The calculated Ck valun in this menu can be compared to the actual Ck setting in the calibration menu to help determine if the Ck setting is correct Lvl Threshold level If the Low Flow Cutoff in the calibration menu is set above this value the meter will read zero flow The Lvl level can be checked at no flow At no flow the Lvl must be below the Low Flow Cutoff setting or the meter will have an output at no flow Adj Filter Adjustable filter Displays filtering in decibels Normally reads zero If value is consitently 5 or 10 for example the Ck or density setting may be wrong O Pulse Out Queue Factory use only Pulse output queue This value will accumulate if the totalizer is accumulating faster than the pulse output hardware can function The queue will allow the pulses to catch up later if the flow rate decreases A better practice is to slow down the totalizer pulse by increasing the value in the unit pulse setting in the totalizer menu TOF G f Factory use only Sig Rev Signal boar
33. d hardware and firmware revision Miro Rev Microprocessor board hardware and firmware revision AD R T F PT V Factory use only SPR Err Rcv Sent Factory use only 5 2 Troubleshooting and Repair June 2007 Column Two Hidden Diagnostic Values Table 5 2 Column Two Hidden Diagnostic Values 4 20 1 Zero Analog counts to calibrate zero on analog output 4 20 1 FScale Analog counts to calibrate full scale on analog output Vor Freq Direct Frequency output setting used by factory calibration Set to NO if totalizer is used Reynolds Corr Reynolds number correction for the flow profile Set to Enable for Series MV82 insertion and set to Disable for Series MV80 inline Gain Control Manual gain control factory use only Leave set at 1 0 Filter Control Manual filter control This value can be changed to any number to force the fi value to a constant A value of zero activates the automatic filter control which sets D at a level that floats above the f value Factory Defaults Meter Type Reset to factory defaults If you change this to YES and press ENTER all factory configuration is lost and you must reconfigure the entire program Consult the factory before performing this process It is required only in very rare cases Insertion Model MV82 or Inline Model MV80 meter Test Pulse Out Analog Output Calibration Force totalizer pulse Set t
34. e for Changing a Run Mode Display Item Display Menu Use 4 dk Gm keys to access menus Cycle Time sec 0 If Cycle Time is set to zero manual advance is required Y Number of Digits 2 Used to set the number of digits displayed after decimal point Y Display TC sec 1 TC Display Time Constant used to smooth display Y Display VFlow YES or NO Y Display MFlow YES orNO For each parameter m Select Yes to view parameter in Run Mode Select No to hide parameter in Run Mode Y Display Total YES orNO y Use the Display Menu to set the cycle time for automatic screen sequencing used in the Run Mode change the precision of displayed values smooth the values or enable or disable each item displayed in the Run Mode screens The following shows how to remove the mass flow screen from the Run Mode screens Note All outputs are disabled while using the Setup Menus 1 2 3 4 5 Use the lt gt keys to move to the Display Menu Press the y key until Display MFlow appears Press ENTER to select Press the y key until N appears Press ENTER to select Press EXIT and then ENTER to save changes and return to the Run Mode Operation June 2007 Totalizer Menu ENTER Run Mode gt Password ENTER Totalizer Menu Use T dk Gm keys to access menus Totaling
35. e problem and provide the model number and serial number of the instrument If the nature of the problem indicates the need for factory service GE will issue a RETURN AUTHORIZATION number RA and shipping instructions for the return of the instrument to a service center will be provided 2 If GE instructs you to send your instrument to a service center it must be shipped prepaid to the authorized repair station indicated in the shipping instructions 3 Upon receipt GE will evaluate the instrument to determine the cause of the malfunction Then one of the following courses of action will then be taken fthe damage is covered under the terms of the warranty the instrument will be repaired at no cost to the owner and returned f GE determines that the damage is not covered under the terms of the warranty or if the warranty has expired an estimate for the cost of the repairs at standard rates will be provided Upon receipt of the owner s approval to proceed the instrument will be repaired and returned Y June 2007 a Table of Contents Chapter 1 Introduction OVET EW A AS AAA ee 1 1 Operating the PanaFlow adas de ade cd 1 1 AAA A Ponta O O 1 2 Flowmeter Configurations tE A b R A 1 5 owners Elec ies ti ida 1 6 Chapter 2 Installation OVErV EW LEUR 2 1 Flowmeter Installation RequireMents 6 cece cence rr 2 1 Unobstructed Flow Requirements See Ee EE EE Ee 2 2 Series MV80 In Line Flowmeter Installa
36. e the following pages for instructions on using the setup menus The flowmeter s digital electronics enable you to set adjust and monitor system parameters and performance A full range of commands is available through the display keypad The LCD display gives 2 x 16 characters for flow monitoring and programming The six push buttons can be operated with the enclosure cover removed Or the explosion proof cover can remain in place and the keypad operated with a hand held magnet positioned at the side of the enclosure as shown in the illustration at the left From the Run Mode the ENTER key enables access to the Setup Menus through a password screen Within the Setup Menus pressing ENTER activates the current field To set new parameters press the ENTER key until an underline cursor appears Use the 4 y gt keys to select new parameters Press ENTER to continue If change is not allowed ENTER has no effect All outputs are disabled when using the Setup Menus The EXIT key is active within the Setup Menus When using a Setup Menu EXIT returns you to the Run Mode If you are changing a parameter and make a mistake EXIT enables you to start over The 4 y gt keys advance through each screen of the current menu When changing a system parameter all 4 y gt keys are available to enter new parameters Figure 3 1 Flowmeter Display Keypad Operation 3 1 June 2007 DC
37. e top of the upper retractor bracket lines up with the insertion length mark scribed on the stanchion Do not force the stem into the pipe Note f line pressure is above 500 psig it could require up to 25 ft lb of torque to insert the flowmeter Do not confuse this with possible interference in the pipe Tighten the packing gland nuts to stop leakage around the stem Do not torque over 20 ft Ibs Slide the stem clamp back into position Torque stem clamp bolts to 15 ft Ibs Replace the stem clamp nuts and torque to 10 15 ft Ibs Attach the safety chain from the stem clamp to the hook on the enclosure adapter at the nearest link To separate the insertion tool from the flowmeter remove four socket head cap bolts securing the upper and lower retractor brackets Remove the insertion tool Installation 2 19 June 2007 Installation with a Packing Use the following formula to determine insertion depth for meters Gland Connection and No with a packing gland connection NPT and flanged without an Insertion Tool insertion tool Insertion Length Formula I S F R t Where I Insertion length Stem length the distance from the center of the sensor head to the base of the enclosure adapter S 29 47 inches for standard probes S 41 47 inches for 12 inch extended probes Distance from the raised face of the flange or top of NPT stem housing to the outside of the pipe wall Pipe inside diameter 2
38. es Normally gate valves are used 1 875 inch min valve bore 2 inch 2 Verify that the valve s valve size body and flange rating are within the flowmeter s maximum operating Isolation Valve Requirements pressure and temperature 3 Choose an isolation valve with at least two inches existing between the flange face and the gate portion of the valve This ensures that the flowmeter s sensor head will not interfere with the operation of the isolation valve 2 8 Installation June 2007 Cold Tap Guidelines Refer to a standard code for all pipe tapping operations Caution When using toxic or corrosive gases purge the line with inert gas for a minimum of four hours at full gas flow before installing the flowmeter IWARNING All flowmeter connections isolation valves and fittings for cold tapping must have the same as or higher pressure rating than the main pipeline The following tapping instructions are general in nature and intended for guideline purposes only 1 9 Weld the flowmeter pipe Install the isolation valve Turn off the flow of process gas liquid or steam Verify that the line is not pressurized Confirm that the installation site meets the minimum upstream and downstream pipe diameter requirements see Figure 2 1 on page 2 2 Usea cutting torch or sharp cutting tool to tap into the pipe The pipe opening must be at least 1 875 inches in diameter Do not attempt
39. ific flowmeter approvals before any hazardous location installation Before installing the flowmeter verify that the installation site allows for these considerations 1 Line pressure and temperature will not exceed the flowmeter rating 2 The location meets the required minimum number of pipe diameters upstream and downstream of the sensor head as illustrated in Figure 2 1 on page 2 2 3 There is safe and convenient access with adequate overhead clearance for maintenance purposes 4 The cable entry into the instrument meets the specific standard required for hazardous area installations 5 For remote installations the supplied cable length is sufficient to connect the flowmeter sensor to the remote electronics Also before installation check the flow system for anomalies such as e leaks valves or restrictions in the flow path that could create disturbances in the flow profile that might cause unexpected flow rate indications Installation 2 1 June 2007 PIED _ A Unobstructed Flow Select an installation site that will minimize possible distortion in the Requirements flow profile Valves elbows control valves and other piping components may cause flow disturbances Check your specific piping condition against the examples shown below In order to achieve accurate and repeatable performance install the flowmeter using the recommended number of straight run pipe diameters upstream and
40. ing shows how to set Output 1 to measure volumetric flow Output with 4 mA 0 gal min and 20 mA 100 gal min with a time constant of 5 seconds All outputs are disabled while using the Setup Menus First set the desired units of measurement 1 Use the gt keys to move to the Units Menu see page 3 7 2 Press the y key until the Volume Flow Unit appears Press ENTER 3 Press the y key until gal appears in the numerator Press the key to move the underline cursor to the denominator Press the 4 key until min appears in the denominator Press ENTER to select 4 Press the 4 key until the Units Menu appears Second set the analog output 1 Use the gt keys to move to the Output Menu 2 Press the y key until 4 20 mA Output 1 appears 3 Press the key to access Measure selections Press ENTER and press the y key to select Volume Press ENTER 4 Press the key to set the 4 mA point in the units you have selected for volume of gal min Press ENTER and use the 4 y gt keys to set 0 or 0 0 Press ENTER 5 Press the key to set the 20 mA point Press ENTER and use the 4 gt keys to set 100 or 100 0 Press ENTER 6 Press the gt key to select the Time Constant Press ENTER and use the 4 y gt keys to select 5 Press ENTER 7 Press the EXIT key and answer YES to permanently save your changes 3 4 Operation June 2007 Display Menu Run Mode ENTER EL Password Exampl
41. ite meets the required minimum upstream and downstream pipe diameters 2 Seatthe meter level and square on the mating connections with the flange marked inlet facing the flow Position a gasket in place for each side Make sure both gaskets are smooth and even with no gasket material extending into the flow profile Obstructions in the pipeline will disturb the flow and cause inaccurate measurements 3 Install bolts in both process connections Tighten the nuts in the sequence shown in Figure 2 2 on page 2 3 Check for leaks after tightening the flange bolts Installation June 2007 Series MV82 Insertion Flowmeter Installation Mounting Position Isolation Valve Selection Prepare the pipeline for installation using either a cold tap or hot tap method described on the following pages Refer to a standard code for all pipe tapping operations The following tapping instructions are general in nature and intended for guideline purposes only Before installing the meter review the mounting position and isolation value requirements given below Allow clearance between the electronics enclosure top and any other obstruction when the meter is fully retracted An isolation valve is available as an option with Series MV82 meters If you supply the isolation valve it must meet the following requirements 1 A minimum valve bore diameter of 1 875 inches is i required and the valve s 2 inch mint body size should be two EC UM inch
42. local 2 x 16 character LCD display housed within the enclosure Local operation and reconfiguration is accomplished using six push buttons For hazardous locations the six push buttons can be operated through the sealed enclosure using a hand held magnet thereby not compromising the integrity of the hazardous location certifi cation The electronics include nonvolatile memory that stores all configuration information The memory allows the flowmeter to function immediately upon power up or after an interruption in power 1 6 Introduction Chapter 2 Installation ANNE AA each eee sk EE EEG Des 2 1 Series MV80 In Line Flowmeter Installation sssneessnsna 2 3 Series MV82 Insertion Flowmeter Installation 2 8 Flowmeter Insertion eve ereecht rre EE X I Teens 2 12 Adjusting Meter Orientation 0 eee eee eee eee 2 21 Wiring Connections cece cece cece eee eee eee tenes 2 23 June 2007 Overview Flowmeter Installation Requirements The PanaFlow MV Flowmeter installations are simple and straightforward Both the Series MV80 In Line and Series MV82 Insertion type flowmeter installations are covered in this chapter After reviewing the installation requirements given below see page 2 3 for Series MV80 Installation instructions See page 2 8 for Series MV82 Installation instructions Wiring instructions begin on page 2 23 Caution Consult the flowmeter nameplate for spec
43. lowmeters with a compression type connection NPT or flanged follow the instructions beginning on page 2 13 For flowmeters with a packing gland type connection NPT or flanged configured with an insertion tool follow the instructions beginning on page 2 16 For flowmeters with a packing gland type connection NPT or flanged without an insertion tool follow the instructions beginning on page 2 20 IWARNING An insertion tool must be used for any installation where a flowmeter is inserted under pressure greater than 50 psig Installation June 2007 Installation with a Use the following formula to determine insertion length for Compression Connection flowmeters NPT and flanged with a compression process connection The installation procedure is given on page 2 15 Insertion Length Formula I S F R t Insertion length Stem length the distance from the center of the sensor head to the base of the enclosure adapter S 29 47 inches for standard probes S 13 1 inches for compact S 41 47 inches for 12 inch extended Distance from the raised face of the flange or top of NPT stem housing to the outside of the pipe wall Pipe inside diameter 2 for pipes ten inches and smaller Five inches for pipe diameters larger than ten inches Thickness of the pipe wall Measure the disk cut out from the tapping procedure or check a piping handbook for thickness Figure 2 6 Insertion Calculation Compression
44. m Edit Calibrate electronics 4mA and 20mAvalues 1 3 1 Tag Edit Tag 1 3 2 PV unit Edit Primary variable units 1 3 3 1 PV LRV Edit Primary variable lower range value 1 3 3 2 PV URV Edit Primary variable upper range value 1 3 3 3 PV LSL View Primary variable upper sensor limit 1 3 3 4 PV USL View Primary variable lower sensor limit 1 3 4 1 Distributor N A Not used 1 3 4 2 Model N A Not used 1 3 4 3 Dev id View Device identification 1 3 4 4 Tag Edit Tag 1 3 4 5 Date Edit Date 1 3 4 6 Write Protect View Write protect 1 3 4 7 Descriptor Edit Vortex flowmeter 1 3 4 8 Message Edit 32 character alphanumeric message 1 3 4 9 PV snsr s n View Primary variable sensor serial number 1 3 4 menu Final assy Edit Final assembly number 1 3 4 menu 1 Universal Rev View Universal revision 1 3 4 menu 2 Fld dev Rev View Field device revision 1 3 4 menu 3 Software Rev View Software revision 1 3 5 PV Xfer fnctn View Linear 1 3 6 PV Damp Edit Primary variable damping time constant in seconds 1 4 1 1 PV View Primary variable value 1 4 1 2 PV Sensor Unit Edit Primary variable units 1 4 1 3 Sensor Information View PV LSL PV USL PV Min span 1 4 2 1 Snsr Damp Edit Primary variable damping time constant in seconds 1 4 2 2 1 PVLRV Edit Primary variable low range value 1 4 2 2 2 PVURV Edit Primary variable upper range value 1 4 2 3 1 PVLRV Edit Primary variable low range value 1 4 2 3 2 PVURV Edit Primary variable upper range value 1 4 2 4 Xfer Fnctn View Linear 1 4 2 5 Al
45. n depth install flowmeter Figure 2 5 Hot Tap Sequence Installation 2 11 June 2007 Flowmeter Insertion Use the Correct Insertion Formula The sensor head must be properly positioned in the pipe For this reason it is important that insertion length calculations are carefully followed A sensor probe inserted at the wrong depth in the pipe will result in inaccurate readings Insertion flowmeters are applicable to pipes 2 inch and larger For pipe sizes ten inches and smaller the centerline of the meter s sensing head is located at the pipe s centerline For pipe sizes larger than ten inches the centerline of the sensing head is located in the pipe s cross section five inches from the inner wall of the pipe i e its wetted depth from the wall to the centerline of the sensing head is five inches Insertion flowmeters are available in three probe lengths e Standard Probe configuration is used with most flowmeter process connections The length S of the stem is 29 47 inches Compact Probe configuration is used with compression fitting process connections The length S of the stem is 13 1 inches e 12 Inch Extended Probe configuration is used with exceptionally lengthy flowmeter process connections The length S of the stem is 41 47 inches Depending on the flowmeter s process connection use the applicable insertion length formula and installation procedure as follows For f
46. n place Remove the label Locate the four Phillips head screws which are spaced at 90 around the terminal board These screws hold the electronics stack in the enclosure Loosen these screws Note 7hese are captive screws They will stay inside the enclosure 7 Carefully remove the electronics stack from the opposite side of the enclosure If the electronics stack will not come out gently tap the terminal strip with a screwdriver handle This will loosen the rubber sealing gasket on the other side of the enclosure wall Be careful that the stack does not hang up on loose sensor harnesses Repeat steps 1 through 6 in reverse order to install the new electronics stack Before returning any PanaFlow MV flowmeter to the factory contact Customer Service When contacting Customer Service be sure to have the meter serial number and model code When requesting further troubleshooting guidance record the following values first f fi G and A at no flow and during flow if possible Pressure temperature and flow rate Troubleshooting and Repair Appendix A Specifications Performante en DE A 1 lee Le A 3 Bee eecht as ioa eet A A CertilicdtioliS vs noe ex eee AA coda A 4 June 2007 Performance Accuracy Table A 1 Accuracy Specifications MV80 Series In Line Meters MV82 Series Insertion Meters Process Variables Liquids Gas amp Steam Liquids Gas amp Steam Volumetric 0 7 of rate over
47. nput terminals to operate correctly The maximum loop resistance load for the current loop output is dependent upon the supply voltage and is given in Figure 2 16 The 4 20 mA loop is optically isolated from the flowmeter electronics Rioad iS the total resistance in the loop including the wiring resistance Rioad R the loop use the maximum loop current 20 mA The voltage drop in the loop due to resistance is 20 mA times Rj q and this drop is wire Rsense To calculate Rmax the maximum R 44 for subtracted from the input voltage Thus The maximum resistance Rjj44 Rmax 50 X V 12V supply Vsupply Rmax volts ohms CY 12 0 18 300 SES S 24 600 N Operating xj Range 30 900 SBS 36 1200 12 18 24 30 36 Vsupply volts Figure 2 16 Load Resistance Versus Input Voltage Installation 2 25 June 2007 ED M Hi Pulse Output Connections The pulse output is used for a remote counter When the preset volume or mass defined in the totalizer settings see page 3 6 has passed the meter the output provides a 50 millisecond square pulse The pulse output requires a separate 5 to 36 VDC power supply The pulse output optical relay is a normally open single pole relay The relay has a nominal 200 volt 160 ohm rating This means that it has a nominal on resistance of 160 ohms and the largest voltage that
48. nu Run Mode ENTER p Password ENTER Diagnostics Menu Use T 4b lt a keys to access menus Sim Vor Freq Simulate Vortex XXX Frequency Hz Highest Velocity Highest Recorded XXX Velocity ft sec Y Use the Diagnostics Menu to simulate flow and review the highest recorded velocity in ft sec The simulated vortex frequency is used for testing the meter to verify that the programming is correct Enter any value for the sensor input in Hz The meter will calculate a flow rate based on the corresponding value and update the analog output and totalizer pulse output Note When your diagnostic work is complete make sure to return the simulated frequency to zero to allow the electronics to use the actual value 3 8 Operation June 2007 Calibration Menu The Calibration Menu contains the calibration coefficients for the flowmeter These values should by changed only by properly trained personnel The Vortex Coef Ck and Low Flow Cutoff are set at the factory Consult the factory for help with these settings if the meter is showing erratic flow rate The units of measurement used in the Calibration Menu are preset and are as follows Density Ibm ft Reference Density Ibm ft Viscosity centipoise ENTER Run Mode gt Password ENTER Calibration Menu Use oOo eo keys to access menus
49. o YES and press ENTER to send one pulse Very useful to test totalizer counting equipment To check the 4 20 mA circuit connect a DVM in series with the output loop Select zero or full scale from the second column of the hidden diagnostics and then actuate the ENTER key twice This action will cause the meter to output its 4 mA or 20 mA condition If the DVM indicates a current greater than 0 006 mA from 4 or 20 adjust the setting up or down until the output is calibrated Note These settings are not for adjusting the output zero and span to match a flow range That function is located in the Output Menu Troubleshooting the Flowmeter Symptom Output at no The low flow cutoff is set too low At no flow go to the first column Flow of the hidden diagnostics menu and record the Lvl value The low flow cutoff must be set above this value Example At no flow Lvl 25 Set the low flow cutoff in the Calibration Menu to approximately 28 and the meter will no longer read a flow rate at no flow Troubleshooting and Repair 5 3 June 2007 Symptom Erratic Output 1 The flow rate may be too low just at the cutoff of the meter range and the flow cycles above and below the cutoff making an erratic output The meter range is stamped on the label on the outside of the electronics enclosure cover based on application conditions when the meter was ordered Consult the factory if necessary to confirm the meter range based on c
50. ollowing tapping instructions are general in nature and intended for guideline purposes only 1 Confirm that the installation site meets the minimum upstream and downstream pipe diameter requirements Weld a two inch mounting adapter on the pipe Make sure the mounting adapter is within 5 perpendicular to the pipe centerline see page 2 9 The pipe opening must be at least 1 875 inches in diameter 3 Connect a two inch process connection on the mounting adapter Connect an isolation valve on the process connection The valve s full open bore must be at least 1 875 inches in diameter Hot tap the pipe Close the isolation valve Run a static pressure check on the welds If pressure loss or leaks are detected repair the joint and re test Connect the flowmeter to the isolation valve Calculate the sensor probe insertion depth as described on the following pages Insert the sensor probe assembly into the pipe 2 10 Installation June 2007 Check upstream and downstream piping requirements Weld mounting adapter Connect process connection flange or NPT Connect isolation valve Hot tap pipe Test for leaks purge pipe Connect meter to valve calculate insertio
51. on 2 3 June 2007 Wafer Style Flowmeter Install the wafer style meter between two conventional pipe flanges of the same nominal size as the flowmeter If the process fluid is a liquid make sure the meter is located where the pipe is always full This may require locating the meter at a low point in the piping system Note Vortex flowmeters are not suitable for two phase flows i e liquid and gas mixtures For horizontal pipelines having a process temperature above 300 F mount the meter at a 45 or 90 angle to avoid overheating the electronics enclosure To adjust the viewing angle of the enclosure or display keypad see Display Keypad Adjustment on page 2 22 Enclosure and display keypad are adjustable to suit most viewing angles Shedder bar bluff body Incorrect gasket position is positioned upstream Do not allow any gasket of the sensor material to extend into the flow profile B y Figure 2 3 Wafer Style Flowmeter Installation Caution When using toxic or corrosive gases purge the line with inert gas for a minimum of four hours at full gas flow before installing the flowmeter When installing the meter make sure the section marked inlet is positioned upstream of the outlet facing the flow This ensures that the sensor head is positioned downstream of the vortex shedder bar and is correctly aligned to the fl
52. or into the pipe until the calculated insertion length L is measured between the base of the enclosure adapter and the top of the stem housing or to the raised face of the flanged version Do not force the stem into the pipe Align the sensor head using the sensor alignment pointer Adjust the alignment pointer parallel to the pipe and pointing downstream Tighten the compression fitting to lock the stem in position When the compression fitting is tightened the position is permanent Installation 2 15 June 2007 Installation with a Packing Gland Connection Use the formula below to determine the insertion depth for flowmeters NPT and flanged equipped with an insertion tool To install see page 2 17 for instructions for meters with a permanent insertion tool For meters with a removable insertion tool see page 2 18 Insertion Length Formula I F R t 1 35 Where I Insertion length F Distance from the raised face of the flange or top of the process connection for NPT style meters to the top outside of the process pipe R Pipe inside diameter 2 for pipes ten inches amp smaller R Five inches for pipe diameters larger than ten inches t Thickness ofthe pipe wall Measure the disk cut out from the tapping procedure or check a piping handbook for thickness Figure 2 8 Insertion Calculation Meters with Insertion Tool Example 1 Flange Style Meters To install a Series MV82 Flo
53. ote Electronics Wiring 2 27 Removable Insertion Tool 2 18 Replacement Electronics Assembly 5 6 Returning Boupment 5 6 Run Mode zo ERE Se 3 2 Display Item Changing 3 5 S Sensing Frequency oooooooooooo o 1 3 Series MV80 Flowmeter Torquing Sequence 2 3 Series MV80 In Line Flowmeter Installati0N oooo oo oomom o oo 2 3 Series MV 82 Insertion Flowmeter Installation naeun 2 8 Setup Menus 3 2 3 3 Shedder Bar 1 2 Shedding Frequency 1 2 Specifications Certifications llle ees A 4 Operation eese A 3 Performance A 1 Physical ate ea A 4 Wetted Materials o oo o o A 4 Startup secos AEN be EEE Ee 3 2 T Torquing Sequence Flange Bolts 2 3 Totalizer Mem kA eu eet em 3 6 Selling o evt ber uel 3 6 Troubleshooting Symptoms Erratic Output o oooooococooooo 5 4 No Outp t ans 5 5 Output at no How 5 3 U Units Ee RE 3 7 Unobstructed Flow Requirements 2 2 Index June 2007 nmm B E OE RE Index cont V Velocity Measaurement n nnnnnennana 1 2 W Wafer Style Flowmeter 2 4 Wetted Materials Specifications A 4 Wiring AC POW ik d feta ek thi eked ele ee 2 24 Connections e 2 23 DG Powet tec ise Mate en en 2 24 Remote Electronics 2 27 Index 3 USA 1100 Technology Park Drive Billerica MA 01821
54. ow Installing the meter opposite this direction will result in completely inaccurate flow measurement Installation June 2007 Wafer Style Flowmeter cont To install the meter 1 Turn off the flow of process gas liquid or steam Verify that the line is not pressurized Confirm that the installation site meets the required minimum upstream and downstream pipe diameters 2 Insert the studs for the bottom side of the meter body between the pipe flanges Place the wafer style meter body between the flanges with the end stamped inlet facing flow Center the meter body inside the diameter with respect to the inside diameter of the adjoining piping 3 Position the gasket material between the mating surfaces Make sure both gaskets are smooth and even with no gasket material extending into the flow profile Obstructions in the pipeline will disturb the flow and cause inaccurate measurements 4 Place the remaining studs between the pipe flanges Tighten the nuts in the sequence shown in Figure 2 2 on page 2 3 Check for leaks after tightening the flange bolts Installation June 2007 Flange Style Flowmeter Install the flange style meter between two conventional pipe flanges of the same nominal size as the flowmeter If the process fluid is a liquid make sure the meter is located where the pipe is always full This may require locating the meter at a low point in the piping system Note Vortex flowmeters are not sui
55. put mA 4 1 PV LRV Edit Primary variable lower range value 4 2 PV URV Edit Primary variable upper range value 5 1 PVLRV Edit Primary variable lower range value 5 2 PV URV Edit Primary variable upper range value 4 4 HART Communications Chapter 5 Troubleshooting and Repair Hidden Diagnostics Menus eese 5 1 Analog Output Calibration cece eee eee eee eee 5 3 Troubleshooting the Flowmeter eee e eee e eee eees 5 3 Electronics Assembly Replacement All Meters 5 6 Returning Equipment to the Factory 5 6 June 2007 Hidden Diagnostics Menus f fi 4 20 1 Zero G XXX Al A2 4 20 1 F Scale A3 M XXXX E SE Kb d Reynolds Corr e Gain Control i Filter Control Bs Pd Factory Defaults i Meter Type rene ae Test Pulse Out TOF Vv G f Sig Rev Micro Rev Not present on 220 models AD R T F PT V Spi Err Rev Sent Vv The menus shown above can be accessed using the password 16363 then moving to the display that reads Diagnostics Menu and pressing ENTER rather than one of the arrow keys Caution Password 16363 will allow full access to the configuration and should be used carefully to avoid changes that can adversely alter the function of the meter Use the right arrow key to move to the second column Press EXIT to move from the
56. ract with their surrounding space by over powering every other nearby swirl on the verge of development Close to the shedder bar the distance or wave length between vortices is always constant and measurable Therefore the volume encompassed by each vortex remains constant as shown below By sensing the number of vortices passing by the velocity sensor the PanaFlow MV Vortex Flowmeter computes the total fluid volume Velocity Sensor Vortex Shedder Bar Vortices 1 Constant Wave Length Figure 1 2 Measurement Principle of Vortex Flowmeters 1 2 Introduction June 2007 Vortex Frequency Sensing The velocity sensor incorporates a piezoelectric element that senses Flow Velocity Range the vortex frequency This element detects the alternating lift forces produced by the Von Karman vortices flowing downstream of the vortex shedder bar The alternating electric charge generated by the piezoelectric element is processed by the transmitter s electronic circuit to obtain the vortex shedding frequency The piezoelectric element is highly sensitive and operates over a wide range of flows pressures and temperatures To ensure trouble free operation vortex flowmeters must be correctly sized so that the flow velocity range through the meter lies within the measurable velocity range with acceptable pressure drop and the linear range The measurable range is defined by the minimum and maximum velocity using the following
57. s the adaptive filter fi setting During flow view the f and fi values in the first column of the hidden diagnostics The fi value should be approximately 10 20 higher than the f value If you raise the Ck setting in the Calibration Menu then the fi value will increase The fi is a low pass filter so by increasing it or lowering it you can alter the range of frequencies that the meter will accept If the vortex signal is strong the fi value will increase to a large number this is correct 5 4 Troubleshooting and Repair June 2007 Symptom No Output 1 For remote mounted electronics carefully check all the wiring connections in the remote mount junction box There are six connections that must be correct Verify each color black and red shield and wire number 2 Check the density value in the Calibration Menu to see if it is correct for the current operating conditions 3 Using ESD precautions and hazardous area precautions remove the electronics enclosure window cover Disconnect the vortex sensor from the Signal board Measure the resistance from each Sensor pin to the meter ground each should be open see Figure 5 2 below Measure the resistance from the Ground pin to the meter ground this should be grounded to the meter With the sensor still disconnected go to the first column of the hidden diagnostics and display the vortex shedding frequency f Hold a finger on the four exposed pins on the Signal board
58. second column back to the first press EXIT while in the first column to return to the setup menus Each of the menus above will first be defined followed by specific troubleshooting steps Troubleshooting and Repair 5 1 June 2007 Column One Hidden Diagnostics Values Table 5 1 Column One Hidden Diagnostic Values Description Vortex shedding frequency Hz If an asterisk is displayed after the f value a valid vortex signal is being registered for the flow Adaptive filter Should be approximately 25 higher than the vortex shedding frequency This is a low pass filter Note If the meter is using the Filter Control see below in the manual mode fi will be displayed as fm Gain applied to vortex signal amplitude Gain defaults to 1 0 and can be changed using the Gain Control see below Amplitude of vortex signal in Volts rms A1 A2 A3 A4 A D counts representing the vortex signal amplitude Each stage A1 A4 cannot exceed 512 Beginning with stage A1 the A D counts increase as the flow increases When stage A1 reaches 512 it will shift to stage A2 This will continue as the flow rate increases until all 4 stages read 512 at high flow rates Higher flow rates stronger signal strength will result in more stages at 512 Kc It Kb Profile equation factory use only Series 221 only V Calculated average pipe velocity ft sec Re Calculated Reynolds number Cal
59. table for two phase flows i e liquid and gas mixtures For horizontal pipelines having a process temperature above 300 F mount the meter at a 45 or 90 angle to avoid overheating the electronics enclosure To adjust the viewing angle of the enclosure or display keypad see Display Keypad Adjustment on page 2 22 Enclosure and display keypad are adjustable to suit most viewing angles Shedder bar bluff body Incorrect gasket position is positioned upstream Do not allow any gasket of the sensor material to extend into the flow profile a AU Figure 2 4 Flange Style Flowmeter Installation Caution When using toxic or corrosive gases purge the line with inert gas for a minimum of four hours at full gas flow before installing the flowmeter When installing the meter make sure the flange marked inlet is positioned upstream of the outlet flange facing the flow This ensures that the sensor head is positioned downstream of the vortex shedder bar and is correctly aligned to the flow Installing the meter opposite this direction will result in completely inaccurate flow measurement Installation June 2007 Flange Style Flowmeter cont To install the meter 1 Turn off the flow of process gas liquid or steam Verify that the line is not pressurized Confirm that the installation s
60. tallation Allow some slack in the interface cable between the junction box and the remote electronics enclosure To prevent damage to the wiring connections do not put stress on the terminations at any time The meter is shipped with temporary strain relief glands at each end of the cable Disconnect the cable from the meter s terminal block inside the junction box not at the remote electronics enclosure Remove both glands and install appropriate conduit entry glands and conduit When installation is complete re connect each labeled wire to the corresponding terminal position on the junction box terminal block Make sure to connect each wire pair s shield Note ncorrect connection will cause the meter to malfunction BLK 1 O RED 1 O BLK2 RED2 O SHIELDS 1 amp 2 Figure 2 20 Junction Box Sensor Connections Note The numeric code in the junction box label matches the wire labels Installation 2 27 Chapter 3 Operation Introduction sssini exc Eee SERERE Ee ta ae 3 1 De E BEE 3 1 CL ET EE 3 2 Using the Setup Menus nee 3 3 June 2007 Introduction Display Keypad After installing the PanaFlow MV Vortex Flowmeter you are ready to begin operation The sections in this chapter explain the display keypad commands meter start up and programming The meter is ready to operate at start up without any special programming To enter parameters and system settings unique to your operation se
61. tem clamp Removable insertion tool Lower retractor bracket Stem housing Sensor head Figure 2 10 Flowmeter with Removable Insertion Tool Installation June 2007 Insertion Procedure for Flowmeters with Removable Insertion Tool cont Caution The sensor alignment pointer must point downstream in the direction of the flow Calculate the required sensor probe insertion length Measure from the depth marker arrow down the stanchion and scribe a mark at the calculated insertion depth Fully retract the flowmeter until the sensor head is touching the bottom of the stem housing Attach the meter assembly to the two inch full port isolation valve if used Use PTFE tape or pipe sealant to improve seal and prevent seizing on NPT style Remove the two top stem clamp nuts and loosen two stem clamp bolts Slide the stem clamp away to expose the packing gland nuts Loosen the two packing gland nuts Loosen the stem lock bolt adjacent to the sensor alignment pointer Align the sensor head using the sensor alignment pointer Adjust the alignment pointer parallel to the pipe and pointing downstream Tighten the stem lock bolt to secure the sensor position Slowly open the isolation valve to the full open position If necessary slightly tighten the two packing gland nuts to reduce the leakage around the stem Turn the insertion tool handle clockwise to insert the stem into the pipe Continue until th
62. the desired position Maximum turn two positions left or two positions right 180 6 Align the board with the captive screws Check that the ribbon cable is folded neatly behind the board with no twists or crimps 7 Tighten the screws Replace the cover and set screw Restore power to the meter 2 22 Installation June 2007 Enclosure Adjustment Series MV80 Only Loosen three setscrews and rotate enclosure maximum 180 from original position Figure 2 13 Enclosure Viewing Adjustment To avoid damage to the sensor wires do not rotate the enclosure beyond 180 from the original position To adjust the enclosure 1 Remove power to the flowmeter 2 Loosen the three set screws shown above Rotate the display to the desired position maximum 180 3 Tighten the three set screws Restore power to the meter Wiring Connections IWARNING To avoid potential electric shock follow National Electric Code safety practices or your local code when wiring this unit to a power source and to peripheral devices Failure to do so could result in injury or death All wiring procedures must be performed with the power off Installation 2 25 June 2007 Wiring Connections cont Input Power Connections DC Power Wiring The NEMA 4X enclosure contains an integral wiring compartment with one d
63. tifications iuc nre dle A 4 Column Two 5 3 Cold Tap Guidelines o o 2 9 Men is dd 5 1 Compression Connection 2 13 Hot Tap Guidelines lesus 2 10 Connections 0 ee ee ee eee 2 23 4 20mA Out 2 25 Input Power 2 24 Pulse Om 2 26 Ppt Power Connections 2 24 Insertion D Correct Formula 2 12 FHlovwmeter mo 2 12 DC Power WirlM8 ooo oococooooo 2 24 Installation Diagnostic Menu 3 8 Compression Connection 2 13 Display a pices eos cg Bape oon a a eS 3 1 Display Keypad Adjustment 2 22 lem Seet vetrine 3 5 Enclosure Adjustment MV80 2 23 Display Keypad Flange Style Flowmeter 2 6 Adjustment sss 2 22 Insertion with No Insertion Tool 2 21 e EE 3 1 Packing Gland Connection 2 16 2 20 Permanent Insertion Tool 2 17 E Pipe Lengths 0000008 2 2 Removable Insertion Tool 2 18 Electronics Requirements 2 1 Assembly Replacement SE ende 5 6 Series MV80 Flange Bolts 2 3 Remote Wiring Ap O 2 27 Series MV80 In Line Flowmeter 2 3 Enclosure Adjustment MV80 2 23 Series MV82 Insertion Flowmeter 2 8 Equipment Returning 5 6 Wafer Style Flowmeter 2 4 F Isolation Valve Selection 2 8 Flange Bolts Torquing Sequence 2 3 K Flange Style Flowmeter
64. tion 0 c ccc e cence ene ence nen e ee neee 2 3 Wafer Stvi FOWmMete reir aii eet ee E eee 2 4 Plange Stvle Flowmeters enetan d coast bebe AS Pies te 2 6 Series MV82 Insertion Flowmeter Installation oooooooocoooococrcroorrmo 2 8 Dogma Guidelines aci eee at eT n Vr E 2 9 Hot TOP CUISINE ERE Mec en Mc bruit 2 10 Flowmeter eet ds acy Dos 2 12 Installation with a Compression Connection 66 ccc cece cece nnn eens 2 13 Installation with a Packing Gland Connection 0 0 c cece ccc cee e eee 2 16 Installation with a Packing Gland Connection and No Insertion Tool 2 20 Adjusting Meter Orientation EE 2 21 Display Keypad Adjustment All Meiers 2 22 Enclosure Adjustment Series MV80 On 2 23 Wiring Connectors cs seo te ov eue tee C d QNI Me 2 23 Input Power Connections susci ecd cotes decet eed aca tc a ees 2 24 4 20 MA OUT OUD EC ae TIONS s sescenti HEAR OO COR IBN EACH o cab SC a ARP e RO Sud 2 25 PUISSOUTDUECONMECHONG La al Perse te de rod EE euet 2 26 Optional Backlight Connection us cosi eos eae ES 2 26 Remote Electronics Wiring s cues Mie Seed tri RP ODORE rabiar depara 2 27 Chapter 3 Operation ees rt MEE PM 3 1 EE ele E AAA A O 3 1 A e Peery eh Shaws ga VIR NR dore ae cae Ree ne ee H 3 2 Using the Setup Menus ss roe oor tore Noo pee OO rd cias geb Uds 3 3 Programiting thietloimieler s ces ral te RM Ep RR o OCC bs 3 3 CUTOUT IB DEE 3 4 Display MENU M MS 3 5 Ee UE
65. tion June 2007 Example for Setting the Second set the pulse output Totalizer cont 1 Use the gt keys to move to the Totalizer Menu 2 Press the y key until Totaling appears 3 Press ENTER and press the y key to select Volume Press ENTER 4 Press the y key to set the gallons per pulse Press ENTER and use the 4 y gt keys to set the pulse value equal to the maximum flow in the same units per second This will limit the frequency to Hz Press ENTER 5 To reset the totalizer press the y key until Reset Total appears Press ENTER and the y key to reset the totalizer if desired Press ENTER 6 Press the EXIT key and answer YES to permanently save your changes Units Menu Use the Units Menu to configure the flowmeter with the desired units of measurement These are global settings and determine what appears on all screens ENTER RunMode 9 Password Use T Zb Gm keys to access menus lb pounds Ston 2000 pounds Lton 2240 pounds gram grams kg 1000 grams Mton Metric Ton 1000 kg scf standard cubic feet nm normal cubic meters Volume Flow Unit gal gal US gallons MilG T MilG 1 000 000 US gallons ImpG Dro ImpG 1 20095 US gallons bbl hr bbl barrels 2 42 US gallons lit d lit liters MilL y Mill 1 000 000 liters m m cubic meters fe f amp cubic feet Operation 3 7 June 2007 Diagnostics Me
66. to insert the sensor probe through a smaller hole Remove all burrs from the tap Rough edges may cause flow profile distortions that could affect flowmeter accuracy Also obstructions could damage the sensor assembly when inserting into the pipe After cutting measure the thickness of the cut out and record this number for calculating the insertion depth connection on the pipe Make sure this connection is perpendicular to the pipe centerline within 5 Correct Alignment Incorrect Alignment if used When welding is complete and all fittings are installed close the isolation valve or cap the line Run a static pressure check on the welds If pressure loss or leaks are detected repair the joint and retest Connect the meter to the pipe process connection 10 Calculate the sensor probe insertion depth as described on the following pages Insert the sensor probe into the pipe Installation June 2007 Hot Tap Guidelines Refer to a standard code for all pipe tapping operations IWARNING Hot tapping must be performed by a trained professional U S regulations often require a hot tap permit The manufacturer of the hot tap equipment and or the contractor performing the hot tap is responsible for providing proof of such a permit IWARNING All flowmeter connections isolation valves and fittings for hot tapping must have the same as or higher pressure rating than the main pipeline The f
67. ual strip terminal block located in the smaller end of the enclosure Two 3 4 inch female NPT conduit entries are available for separate power and signal wiring For all hazardous area installations make sure to use an agency approved fitting at each conduit entry If conduit seals are used they must be installed within 18 inches 457 mm of the enclosure Optional Loop Pulse Backlight Power Output Power qom E lejelele e o Figure 2 14 Pulse and Power Terminals To access the wiring terminal blocks locate and loosen the small set screw which locks the small enclosure cover in place Unscrew the cover to expose the terminal block Connect 4 20 mA loop power 12 36 VDC to the Pwr and Pwr terminals on the terminal block Torque all connections to 4 43 5 31 in Ibs 0 5 0 6 Nm The DC power wire size must be 20 10 AWG with the wire stripped 1 2 inch 14 mm The nominal voltage required to operate the 4 20 mA loop is 12 volts at the meter The 4 20 mA loop is optically isolated from the flow meter electronics 12 to 36 VDC Figure 2 15 DC Power Connections 2 24 Installation June 2007 4 20mA Output Connections The standard PanaFlow MV Flowmeter has a single 4 20 mA loop The 4 20 mA loop current is controlled by the meter electronics The electronics must be wired in series with the sense resistor or current meter The current control electronics require 12 volts at the i
68. urrent operating conditions It may be possible to lower the low flow cutoff to increase the meter range See the example above for output at no flow only this time the low flow cutoff is set too high You can lower this value to increase the meter range as long as you do not create the output at no flow condition previously described Mechanical installation may be incorrect Verify the straight run is adequate as described in Chapter 2 For in line meters make sure the meter is not installed backwards and there are no gaskets protruding into the flow stream For insertion meters verify the insertion depth and flow direction The meter may be reacting to actual changes in the flow stream The output can be smoothed using a time constant The displayed values can be smoothed using the time constant in the Display Menu The analog outputs can be smoothed using the time constant in the Output Menu A time constant of 1 will result in the change in value reaching 63 of its final value in one second A time constant of 4 is 22 10 is 9 5 and 50 is 1 9 of the final value in one second The time constant equation is shown below TC z Time Constant change to final value in one second 100 1 gc TOX The vortex coefficient Ck may be incorrectly set The Ck is a value in the equation used to determine if a frequency represents a valid vortex signal given the fluid density and signal amplitude In practice the Ck value control
69. wmeter into a 14 inch schedule 40 pipe the following measurements are taken F 12 inches R 5 inches t 2 0 438 inches The example insertion length is 16 09 inches Example 2 NPT Style Meters The length of thread engagement on the NPT style meters is also subtracted in the equation The length of the threaded portion of the NPT meter is 1 18 inches Measure the thread portion still showing after the installation and subtract that amount from 1 18 inches This gives you the thread engagement length If this cannot be measured use 55 inch for this amount F 12 inches R 5 inches t 2 0 438 inches The example insertion length is 15 54 inches All dimensions are in inches 2 16 Installation June 2007 Insertion Procedure for Flowmeters with Permanent Insertion Tool Upper retractor bracket Stem lock bolt center Scribe mark Sensor alignment pointer Stem Packing gland nuts Stem housing Permanent insertion tool Sensor head Figure 2 9 Flowmeter with Permanent Insertion Tool Caution The sensor alignment pointer must point downstream in the direction of the flow 1 Calculate the required sensor probe insertion length refer to page 2 16 Measure from the depth marker arrow down the stanchion and scribe a mark at the calculated insertion depth 2 Fully retract the flowmeter until the sensor head is touching the bottom of the stem housing Attach the meter assembly to the two in
Download Pdf Manuals
Related Search
Related Contents
Kohler CH270 User's Manual Samsung NX mini (9 mm) Εγχειρίδιο χρήσης CONSIGNES DE SECURITE IMPORTANTES Télécharger - Saint-Quentin-en Tiger XR, Tiger XR T, Tiger XRX, Tiger XC, Tiger XC A, Tiger XCX Arat NS1255 holder Liebherr Chest Freezer 7081 157-00 User's Manual Brother 885-X18 Sewing Machine User Manual Manual SSW05 Copyright © All rights reserved.
Failed to retrieve file