Home

SoftLogix Controllers, Version 21

image

Contents

1. Downloading to a SoftLogix 5800 controller while another controller in the chassis is running a motion application may affect the motion application Do not perform a download to a SoftLogix 5800 controller in the chassis while another controller in the same chassis is running a motion application Doing so may impact the motion execution Be sure to only single click the SoftLogix 5800 icon during installation Do not double click the SoftLogix 5800 icon on the installation browser dialog box This can cause two copies of the SoftLogix 5800 installation procedure to launch If two copies of the installation program start you may not be able to perform a normal uninstall If this occurs you will see this error message when an uninstall is attempted Failed to load dll _UninstallTmp If this situation occurs you have to manually uninstall the program The manual uninstall procedure is available as Knowledgebase document KB22639 Avoid mixed operand types between the destination and its inputs For maximum portability across platforms it is best to avoid mixed operand types between the destination and its inputs If getting identical results for similar operations across languages is important to you make sure to perform floating point operations However floating point operations do not perform as well Other considerations exist as well such as how compatible your operands are with that of the 1 0 being used and so on
2. Incorrect setting for Initialization bit may cause incorrect function block execution values When you perform a Partial Import Online PIO of a function block routine that contains S Curve function blocks across Logix platforms set the Initialize bit in the backing tag control structure of all S Curve instructions This configuration causes the S Curve instructions to re initialize themselves Failure to set the Initialize bit in the backing tag control structure of all S Curve instructions may cause the S Curve function block to execute with uninitialized values Lgx00114927 Lgx00114935 Download of converted Logix Designer project to SoftLogix 5800 controller causes need for additional tasks The Totalizer TOT instruction may not function properly when a converted project is downloaded to a SoftLogix 5800 controller catalog number 1789 L10 1789 L30 or 1789 L60 version 20 00 00 or later This anomaly may occur under these conditions e An RSLogix 5000 project is running on a SoftLogix 5800 controller catalog number 1789 L10 1789 L30 or 1789 L60 version 18 00 00 or earlier with the TOT instruction in Run mode e The project is uploaded and saved to a new file The new file is changed to use a SoftLogix 5800 controller catalog number 1789 L10 1789 L30 or 1789 L60 version 19 00 00 or later and is downloaded to a new controller of the same catalog number e The project transitions to Run mode Upon transitioning
3. Table 7 Known Anomalies with Version 21 Controllers Cat No 1789 L10 1789 L30 1789 L60 Description No Arithmetic Overflow Minor fault is seen in the Softlogix software but is seen in a hard controller if you are passing parameters to an Add On Instruction and the source value exceeds the range of Add On Instruction s parameter For example if the Add On Instruction input parameter type is SINT and the source value passed to the Add On Instruction is 99999 9999 exceeds the range of SINT which is 128 to 127 in a hard controller you will see overflow minor fault but will not in the Softlogix software Lgx00118782 Lgx00127537 Repeated power cycling or resetting the ethernet switch that connects the Softlogix 1 0 module to the control system may cause the Softlogix ethernet connections not to be re established Resolving this condition requires removing the Softlogix ethernet module from the Chassis Monitor then re insert the Softlogix Ethernet module once the power to the ethernet switch has been restored Lgx00126929 When the MCR zone is disabled all rungs inside the MCR zone are expected to be disabled However if LBL instruction is used in a rung inside the disabled MCR zone the instructions after LBL in that rung will be enabled which is incorrect Lgx00136977 When using the Automatic Device Configuration ADC feature the Logix controller owns the configuration in the drive Do not use the HIM or other
4. external tools such as DriveExplorer to change drive parameters Doing so may cause a sequence of events to occur that results in the connection between the controller and the drive to be dropped and causes the controller to not be able to re establish the connection Consider using the Write Mask function drive Parameter 888 Write Mask Cfg to prevent tools connected to ports other than the Embedded EtherNet IP port from writing to the drive Lgx00129012 Lgx00129165 SoftLogix 5800 controllers operate differently in integer calculations involving XPY Operands in XPY are converted to REAL before executing XPY Multiplication however is treated as an integer operation The increased precision in XPY may lead to discrepancy in behavior compared to using multiplication Lgx00114013 The use of Windows Vista or Server operating systems does not result in an expected EtherNet IP configuration error If you are using the Windows XP operating system and have two EtherNet IP modules in the same chassis configured with the same IP address an error is indicated by a red X on top of the last EtherNet IP module added to the SoftLogix chassis configuration This is the expected behavior for such a configuration when any of the operating systems is used However if you are using Windows Vista or Server operating systems you can configure two EtherNet IP modules in one SoftLogix chassis with identical IP addresses This configuration should result
5. if necessary and then converts the result from a real to the destination type if necessary In this example n is converted to 800 0 and m is converted to 1000 0 The result of the operation is 0 8 That result then gets converted to an integer where rounding rules apply and the final destination value is 1 This difference between ladder and function block instructions applies to all Logix platforms Function block instructions perform only floating point operations Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 11 Fu nctionality Issues in Specific You may experience some or all of these issues when you program or use your Circumstances SoftLogix 5800 controller Table 9 Possible Functionality Issues Issue Performance Description The latest drivers for various items like video and networking devices may be required for satisfactory system operation We recommend that you use Microsoft certified drivers for video cards and Ethernet NICs if performance problems are observed when running motion applications Certified drivers can be found on the Microsoft website You can also use Windows Update utility to update drivers on Windows 2000 XP systems or see the website of the hardware manufacturer General If you use drive image software to duplicate your hard disk drive to deploy multiple SoftLogix 5800 systems follow these steps to be sure of proper operation
6. to Run mode the TOT instruction s output value is different from the last value generated when the same project was running on the first controller To reset an invalid Totalizer value set the ProgResetReq or OperResetReq to move the value of the instruction s Reset input parameter to the instruction s Total output parameter Repeat this task once more to move the invalid value out of the instruction s OldTotal output parameter Lgx00114767 Lgx00116677 Lgx00114731 Logix CPU security tool The Logix CPU security tool does not work with version 20 controllers RSLogix 5000 Clock Update Tool The RSLogix 5000 Clock Update tool does not support Windows 7 or Windows Server 2008 operating systems Rockwell Automation Publication 1789 RN210B EN P April 2014 10 SoftLogix Controllers Version 21 Performing Typed Operations Consider the following when performing typed operations Typed Operation Across Logix platforms Description Due to the fact that the SoftLogix family is based on open systems technology the controller performs computational operations much the same way as open systems platforms and tools This becomes important when performing mixed typed operations such as dividing two integers and storing the result in a real Integer operations typically truncate the rational portion of a computation result while floating point operations preserve it For example when a SoftLogix program performs a n
7. your application offline before going online Rockwell Allen Bradley Rockwell Software Automation 2 SoftLogix Controllers Version 21 E About This Publication This publication describes SoftLogix 5800 controllers version 21 03 00 Information that has been added or changed since the last revision of this publication is indicated by a change bar as shown to the side of this paragraph In addition to information specific to the most recent software version the information from previous minor versions is retained in these release notes We strongly recommend that you review the information provided regarding previous software versions We recommend that you do so because if you are upgrading your software through multiple previous versions all of the information specific to all of the versions is applicable About Publication 1789 RN210B EN P This revision of the SoftLogix Controllers Release Notes publication 1789 RN210B provides updated information specific to version 21 03 00 Table 1 Controller Versions Identified in Publication 1789 RN210B Cat No Version 1789 L10 21 03 00 1789 130 1789 L60 About Publication 1789 RN210A EN P This publication describes SoftLogix 5800 controllers version 21 00 00 Table 2 Controller Versions Identified in Publication 1789 RN210A Cat No Version 1789 L10 21 00 00 1789 30 1789 L60 Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogi
8. 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1789 RN210B EN P April 2014 Supersedes Publication 1789 RN210A EN P January 2013 Copyright 2014 Rockwell Automation Inc All rights reserved Printed in the U S A
9. 7793 The SoftLogix 5800 controller gives different results than hard controllers when performing a divide instruction with 0 0 The result on a hard controller is 1 9 infinity while on a SoftLogix 5800 controller it is 0 0 This is because in the Windows operating system 0 will be converted to a DINT before dividing while in hard controllers 0 is treated as REAL Lgx00123474 These restrictions exist for version 21 controllers Table 8 Restrictions with Version 21 Controllers Restriction Description Using alarms Depending on the number of alarms in user program and the performance of the computer if the user requests the computer to shut down the Softlogix controller can delay the shut down process 3 minutes or longer for each controller in the virtual chassis to save Alarms information During that time the computer will display a Shutting Down message to the user If an improper computer shut down is performed the integrity of the Alarm records cannot be guaranteed Lgx00136426 Remotely accessing the SoftLogix 5800 Do not attempt to remotely access the computer running the SoftLogix 5800 controller If you attempt to remotely access a controller results in a system crash computer running the SoftLogix 5800 controller the system running the SoftLogix 5800 controller crashes Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 9 Table 8 Restri
10. Release Notes AB Allen Bradley SoftLogix Controllers Version 21 Catalog Numbers 1789 L10 1789 L30 1789 L60 Topic Page Compatible Software Versions 3 System Requirements 4 Before You Begin 5 Enhancements 5 Corrected Anomalies 5 Known Anomalies 7 Restrictions 8 Performing Typed Operations 10 Functionality Issues in Specific Circumstances 11 Additional Memory Requirements 12 Additional Resources 21 IMPORTANT Consider the following before upgrading your SoftLogix 5800 controller e Before updating your controller we strongly recommend that you review information pertinent to previous major versions For example when updating from version 18 x 20 x view information for versions 18 15 and 19 11 in these publications SoftLogix 5800 Controllers Version 18 Release Notes publication 1789 RNO18 SoftLogix 5800 Controllers Version 19 Release Notes publication 1789 RNO19 SoftLogix 5800 Controllers Version 20 Release Notes publication 1789 RN519 Release notes contain material for all minor versions subsequent to each major version If your controller for example is at version 18 11 and not the latest version such as 20 x you should view all of the information for version 18 11 19 11 before updating to version 20 x Release notes are available at http www rockwellautomation com literature e After upgrading your controller we strongly recommend that you retest and or validate
11. Then add the following memory requirements to your project Which comes from this type of from revision add memory all that apply Component Increase Decrease Per 1 0 Data and Safety Instance Logic 15 x to 16 x If you use a tag of the types listed below increase the memory as indicated for each instance Tag that uses ALARM_ANALOG data type with no associated tag references 16 bytes WA Tag that uses ALARM_DIGITAL data type with no associated tag references 4 bytes vA Tag that uses ALARM_ANALOG data type if associated tags are configured for 22 bytes vA the ALARM_ANALOG tag A 9 x the number of configured associated tags 3 x the sum of the bytes used by the data type of each of the configured associated tags For example an analog alarm moved to version 16 03 00 with two Associated Tags one DINT 4 bytes and one STRING 88 bytes would need to add 22 9 2 3 92 316 bytes Tag that uses the COORDINATE_SYSTEM data type 132 bytes vA 14 x to 15 x Input module 4 bytes v If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 12 bytes vA Consumed tag 4 bytes v Tag that uses COORDINATE_SYSTEM data type 748 bytes v Tag the uses any AXIS data type 800 bytes vA Task 20 bytes v Program or equipment phase 24 bytes vA Routine 4 bytes v Serial port 1120 bytes v Project 4012 bytes vA Rockwell Automation Publication 1789 RN210B EN P A
12. ag as the subscript for an array in an instruction such as 60 bytes v an Array_A Tag_B This memory change applies only if the array Uses a structure as its data type Does not use one of these data types CONTROL COUNTER PID or TIMER Has only one dimension such as UDT_1 5 9 x to 10 x Program 12 bytes vA Routine 16 bytes v 8 x to 9 x If you use a tag of the types listed below increase the memory as indicated for each instance Tag that uses the MESSAGE data type 376 bytes vA Rockwell Automation Publication 1789 RN210B EN P April 2014 20 SoftLogix Controllers Version 21 Table 10 Estimate Additional Memory If you upgrade Then add the following memory requirements to your project Which comes from this type of from revision add memory all that apply Component Increase Decrease Per 1 0 Data and Safety Instance Logic 7 x to 8 x Project 1050 bytes vA Tag 0 55 bytes vA Message that transfers more than 500 bytes of data and targets a controller in the 2000 bytes v same chassis This memory is allocated only when the MSG instruction is enabled To estimate count the number of these messages that are enabled and or cached at one time 6 x to 7 x If you use a tag of the types listed below increase the memory as indicated for each instance Base tag 24 bytes vA Alias tag 16 bytes v Produced tag DINT 4 12 bytes vA REAL 4 12 bytes v Con
13. ctions with Version 21 Controllers continued Restriction External access options have software requirements Description For best results with the new External Access tag attributes provided with RSLogix 5000 software version 18 00 00 and controller version 18 00 00 use RSLinx Classic software version 2 56 and RSLinx Enterprise software version 5 21 or later Using earlier versions of RSLinx Classic and RSLinx Enterprise software may result in anomalous behavior from the data servers with the External Access options Read Only and None For more information about tag data access attributes see the Logix5000 Controllers 1 0 and Tag Data Programming Manual publication 1756 PM004 Lgx00103263 Repeated minor faults can cause the controller to display a red X If your SoftLogix 5800 controller experiences repeated minor faults it may display a red X This happens only in systems in which minor faults are repeatedly generated on each program scan To avoid this correct any programs that may cause repeated minor faults to occur Trends may momentarily block the SoftLogix 5800 thread from executing Running or stopping a trend momentarily blocks the SoftLogix 5800 thread from executing Depending on your application and system performance this can affect motion by causing increased errors in axis position or velocity Controllers containing programs that generate motion should be in Program mode when starting or stopping a trend
14. ed User 4 Click Add and provide the domain logon name for the desired user You can click Check Names to verify that the name was found 5 To allow access for all authenticated users navigate to Network System Users and Groups User Groups right click the User Groups folder and choose New gt Windows Linked User Group 6 Click Add and type the name of the user group Authenticated Users The Log On to FactoryTalk dialog box may also display when using Remote Desktop to connect to the personal computer running RSLogix 5000 software This is due to FactoryTalk Security not recognizing the computer name To enable access through Remote Desktop for a specific computer you should add the name of the computer initiating the Remote Desktop connection to the Network System Computers and Groups Computers folder in the FactoryTalk Administration Console To allow all computers to connect follow these steps 1 Open the FactoryTalk Administration Console and log in to the Network directory using your domain credentials 2 Navigate to Network System Security Policy In the Computer Policy Settings section set Identify terminal server clients using the name of to Server Computer IMPORTANT If Use single sign on is set to disable in FactoryTalk software then the Log On to FactoryTalk dialog box will be displayed each time RSLogix 5000 software is launched and proper user credentials must be entered to continue By default Use single sign on is set to enab
15. ements for Version 21 Controllers Category Description Personal computer IBM compatible Pentium 4 1 6 GHz or later Other requirements include the following e FactoryTalk Activation Manager if you are currently using Factory Activation software e Ahard disk that supports bus mastering e Theneed for bus mastering drivers for the personal computer s chip set for Intel motherboards this software is called Application Accelerator Applications that are resource intensive including applications that use sequential motion and other local applications running on the computer may require a dual CPU to achieve performance requirements The Logix Designer application version 21 is not required Operating systems Microsoft Windows 7 Home Premium Service Pack 1 e Windows 7 Professional Service Pack 1 e Microsoft Windows Server 2008 R2 Standard Edition Service Pack 1 IMPORTANT When a SoftLogix controller is installed the following modules are available in the Chassis Monitor SoftLogix controller Soft ENBT Input output simulator module IMPORTANT Motion ControlNet and DeviceNet modules are currently not supported in SoftLogix controllers version 21 RAM 1GB min Hard disk space 64 MB of free hard disk space per controller instance or more based on application requirements Network requirements Supports EtherNet IP and Ethernet port of the personal computer Third party networks are supported t
16. esponding and require removal and re insertion in the virtual chassis to recover from this fault The RSLogix 5000 project will also have to be re downloaded You can prevent this problem by using the Cache Connections option on the Communications tab of the message configuration dialog box You can cache as many as 32 instructions with any combination of message instructions and block transfer instructions For example you can cache 28 message instructions and 4 block transfer instructions If you configure more than 32 cached connections some of the connections will be made without caching which causes this issue to continue to occur In general lower the frequency of less critical messages block transfers and use caching for critical messages block transfers The SoftLogix 5800 controller executes on a 32 bit microprocessor which can perform 80 bit floating point operations Due to extensive accuracy comparisons between one REAL operand and another could reveal small differences in the lesser significant digits for example 1 000005 and 1 000052 As an alternative use the LIM instruction when REAL operands are involved For more information on configuring your SoftLogix 5800 system see the SoftLogix 5800 System User Manual publication 1789 UMO002 Rockwell Automation Publication 1789 RN210B EN P April 2014 12 SoftLogix Controllers Version 21 Additional Memory Requirements This controller version may require more memory than pr
17. evious versions for example 10 x 11 x To estimate additional memory requirements for your application you can either use the memory estimation tool provided with the Logix Designer application or the tables provided in these release notes Use the Estimate Tool To estimate the amount of memory required by your application convert the project to the controller version desired and use the Estimate tool available in the Memory tab of the Controller Properties ty Controller Properties App_001 o x General Serial Port System Protocol User Protocol Major Faults Minor Faults Date Time Advanced SFC Execution File Redundancy Nonvolatile Memory Memory Memory Option Estimated I O Memory A Total 7 L Free E Used i a Max Used Largest Block Free Estimated Data and Logic Memory 505 856 bytes Total 8 388 608 bytes 488 352 bytes z L Free 8 372 496 bytes 17 504 bytes E Used 16 112 bytes 17 504 bytes g Max Used 16 112 bytes 488 352 bytes Largest Block Free 8 372 496 bytes Estimate Estimate Based on Application Components If you do not have the desired version of the Logix Designer application use this table to estimate the additional memory that your project may require If you are upgrading your system through multiple controller versions add all components your application uses for each of the versions you upgrade through For example if you are upgrading fro
18. f you upgrade from revision add all that apply Which comes from this type of memory Rockwell Automation Publication 1789 RN210B EN P April 2014 Component Increase Decrease Per 1 0 Data and Safety Instance Logic 16 x to 17 x Task 4 bytes vA Program 4 bytes v Equipment phase 8 bytes vA LD routine 12 bytes vA FBD routine 8 bytes v SFC routine 28 bytes vA ST routine 4 bytes v Add On Instruction 12 bytes vA If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 4 bytes 4 bytes number of consumers Consumed tag 8 bytes Tag that uses MESSAGE data type 4 bytes vA Tag that uses ALARM_ANALOG data type 64 bytes v Tag that uses ALARM_DIGITAL data type 28 bytes vA Tag that uses AXIS_SERVO_DRIVE or AXIS_GENERIC_DRIVE data type 34 bytes vA 2 bytes x number of output cam execution targets Tag that uses AXIS data type other than AXIS_SERVO_DRIVE or 52 bytes vA AXIS_GENERIC_DRIVE 2 bytes x number of output cam execution targets Tag that uses COORDINATE_SYSTEM data type of 2 dimensions with 2 20 bytes vA transform dimensions Tag that uses COORDINATE_SYSTEM data type of 3 dimensions with 3 108 bytes vA transform dimensions 18 SoftLogix Controllers Version 21 Table 10 Estimate Additional Memory If you upgrade
19. hrough the Rockwell Automation Encompass program Video requirements 16 color VGA graphics adapter 640 x 480 or later resolution 256 color 800 x 600 min for optimal resolution 1 The SoftLogix 5800 controller has been tested and qualified only on genuine Intel processors Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 5 Before You Begin Before you upgrade your controller consider how close it is to the limits of memory This version may require more memory than previous versions To see what components of your current project require more memory see Additional Memory Requirements on page 12 IMPORTANT Rockwell Automation does not assume responsibility or liability to include intellectual property liability for actual use of the external routines featured in a control system application The Logix Designer application lets you estimate the memory requirements of the controller offline Enhancements This enhancement is available when you use controller version 21 00 00 and later Table 5 Enhancements with Version 21 Controllers Cat No 1789 L10 1789 L30 1789 L60 Description In shipping versions of the Logix Designer application including versions 20 19 18 17 and 16 changes were made to pre scan execution of Add On Instructions In these versions of the Logix Designer application when an Array Index is out of bounds during pre scan execut
20. ile a Motion Group Shutdown MGSD is still executing motion error 7 that is Shutdown State Error results The purpose of an MGSR instruction is to bring an axis group out of the shutdown state However when the scenario described in the previous paragraph exists the MGSR instruction is not executed because the shutdown procedure initiated by the MGSD instruction has precedence Thus the MGSR instruction generates motion error 7 because the shutdown procedure has not completed The shutdown procedure must complete before any attempt to reset the shutdown Lgx00095484 IMPORTANT This anomaly occurs only in SERCOS applications that use Kinetix SERCOS drives and linear motors Under certain conditions it is possible that the Real Time Axis attribute VelocityFeedback contains an incorrect value The inaccuracy is the result of incorrect scaling of that attribute Your program will have an incorrect value for the VelocityFeedback attribute if you follow these steps 1 While offline you write your RSLogix 5000 program and as part of that program the VelocityFeedback attribute is selected 2 You save the program and download it to the controller 3 You go online The VelocityFeedback attribute value is incorrect because that attribute was enabled before the program was saved downloaded and put online To work around this anomaly do not enable the VelocityFeedback attribute until the RSLogix 5000 program is online Lgx0010
21. in an error but does not Lgx00107669 Lgx00107451 PI function block appears to stop executing as the output does not change and no instruction faults are logged If the PI instruction is being used in Linear mode this floating point equation is used to calculate the ITerm WidInput WldInput _ Kp x Wld x 5 x DeltaT ITerm _ Due to the use of the single precision floating point values it may be possible depending on the values of WLD and KP for the ITerm value to be small enough less than 0 0000001 to be lost when adding to the ITerm For more information regarding the PI instruction see the Logix5000 Controllers Process Control and Drives Instructions User Manual publication 1756 RMO006 Lgx00070832 Changes made to the Buffer Timeout value for FactoryTalk Alarms and Events subscribers do not take effect until the existing buffer has been deleted The FactoryTalk Alarms and Events alarm buffer stored in Logix controller memory is designed to persist through power cycles If you change the Buffer Timeout value via the Communication Setup dialog box in FactoryTalk View SE software the controller does not use the new timeout value until the existing buffer is deleted and then recreated To force recreation of this buffer do one of the following e Redownload the project to the controller Disconnect the FactoryTalk Alarms and Events subscriber and leave it disconnected until the existing timeout expires Lg
22. ion of the Add On Instruction the instruction is partially executed and the remainder of the instruction execution is skipped during pre scan Corrected Anomalies These anomalies have been corrected with these controller versions Table 6 Corrected Anomalies with Version 21 Controllers Cat No Description 1789 L10 CORRECTED In SFCs when using time limited actions in steps if the program stays on a given step for greater than 24 days 2 32 ms the timers accumulate 1789 L30 ACC will roll over and the action body starts to execute again 1789 160 The time limited action initializes its timer when it starts step is first scanned On subsequent scans it compares the timers PRE and ACC value If ACC lt PRE the action body will execute If ACC gt PRE it is not executed When the roll over occurs the ACC PRE and the action body will again execute when it should not Lgx00124689 Lgx00124697 CORRECTED The controller only supports three active reconfigure messages at a time If more than three are triggered at a time they will complete DN bit will go high but not all the modules will be reconfigured For example if you send five reconfiguration messages at the same time three reconfigure messages will truly complete DN bit will go high and the 1 0 modules will be reconfigured The other two reconfigure messages will indicate complete DN bit will go high but the 1 0 modules will not be reconfigured In this case the last tw
23. ix 5370 L3 24 bytes vA CompactLogix 5370 L3 14 984 bytes vA 1756 L7xS 48 bytes v 1756 L7xS 24 720 bytes vA 1756 L7x 16 bytes v 1756 L7x 24 720 bytes vA 1789 L10 1789 L30 1789 L60 76196 vA Rockwell Automation Publication 1789 RN210B EN P April 2014 14 SoftLogix Controllers Version 21 Table 10 Estimate Additional Memory If you upgrade from revision add all that apply 19 x to 20 x Then add the following memory requirements to your project Which comes from this type of memory Component Increase Decrease Per 1 0 Data and Safety Instance Logic Task 1312 bytes v Program 16 bytes vA Equipment phase 8bytes vA Routine 24 bytes v Add On Instruction 32 bytes vA Project with any tags that use ALARM_ANALOG or ALARM_DIGITAL data type 76 bytes v Tag that uses ALARM_ANALOG data type 4 bytes v Tag that uses ALARM_DIGITAL data type 24 bytes v Tag that uses MOTION_GROUP data type 56 bytes v Tag that uses COORDINATE_SYSTEM data type 940 bytes vA Tag that uses AXIS_CIP_DRIVE data type 676 bytes v Tag that uses AXIS data type other than AXIS_CIP_DRIVE 672 bytes vA Standard Produced tag 4 bytes 4 bytes x number of consumers Standard Consumed tag 12 bytes Safety Produced tag 4 bytes vA Safety Consumed tag 4 bytes v 1 0 module 8 bytes vA Module input connection 4 bytes vA Mod
24. le Lgx00124955 CORRECTED Micro830 controllers will cause an error when opening the SoftLogix Chassis Monitor To avoid this problem keys were deleted in the registry after plugging in the Micro830 controller HKEY_LOCAL_MACHINE SOFTWARE Rockwell Automation VirtualBackplaneMonitor Installed Modules 0001 000E 00XX 0001 000E 007B 0001 000E 007C 0001 000E 007D 0001 000E 007E 0001 000E 007F 0001 000E 0080 0001 000E 0081 0001 000E 0082 0001 000E 0087 0001 000E 0088 0001 000E 0089 0001 000E 008A Lgx00125634 CORRECTED Changes made to the Buffer Timeout value for FactoryTalk Alarms and Events subscribers do not take effect until the existing buffer has been deleted The FactoryTalk Alarms and Events alarm buffer stored in Logix controller memory is designed to persist through power cycles If you change the Buffer Timeout value via the Communication Setup dialog box in FactoryTalk View SE software the controller does not use the new timeout value until the existing buffer is deleted and then recreated To force recreation of this buffer do one of the following e Redownload the project to the controller Disconnect the FactoryTalk Alarms and Events subscriber and leave it disconnected until the existing timeout expires Lgx00069461 Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 7 Known Anomalies These anomalies have been identified with version 21 controllers
25. m where the data types for a ni and m are real integer and integer respectively this specifies an integer divide between n and m and places the answer into a performing an integer to real conversion If n 800 and m 1000 the result is 0 and gets stored into a as 0 0 Alternatively when a ControlLogix program performs the same a n m where the data types for a n and m are real integer and integer respectively this specifies a floating point divide between n and m and places the answer into a with no conversion needed If n 800 and m 1000 the result is 0 8 and gets stored into a as 0 8 In SoftLogix software the input operand types dictate the operation while in the ControlLogix program if any of the operands are real a floating point operation is performed SoftLogix software performs the operation exactly like a C routine would Across languages There are instruction differences across programming languages as well as across Logix platforms The following examples use the operation i n m where all the operands are integers Ladder DIV instructions perform an integer divide operation and store the immediate result in the destination For n 800 and m 1000 i is equal to 0 The DIV function block instructions only does floating point operation The function block instruction converts the inputs to reals
26. m version 15 x to version 20 x total your application components for revisions 15 x to 16 x 16 x to 17 x 17 x to 18 x 18 x to 19 x 19 to 20 and 20 to 21x Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 13 Table 10 Estimate Additional Memory If you upgrade from revision add all that apply 20 x to 21 x Then add the following memory requirements to your project Which comes from this type of memory Component Increase Decrease Per 1 0 Data and Safety Instance Logic PROGRAM 8 bytes vA Add On Instruction 12 bytes vA SFC Routine 8 bytes v Tag that uses AXIS_GENERIC data type 32 bytes vA Tag that uses OUTPUT_CAM data type 512 bytes vA Tag that uses AXIS_SERVO_DRIVE data type 8 bytes vA Tag that uses CIP_DRIVE data type 4 bytes v PRODUCE_TAG 2 bytes vA Tag that uses ALARM_DIGITAL data type 64 bytes v Tag that uses ALARM_ANALOG data type 436 bytes vA Tag that uses MOTION_GROUP data type 8 bytes v For each controller CompactLogix 5370 L1 376 bytes vA CompactLogix 5370 L1 6600 bytes vA CompactLogix 5370 L2 1769 L24ER 0B1B 1392 bytes vA CompactLogix 5370 L2 1769 L24ER 0B1B 13 588 bytes vA CompactLogix 5370 L2 1769 L24ER QBFC1B or 1769 L27ERM QBFC1B 1392 bytes vA CompactLogix 5370 L2 1769 L24ER QBFC1B or 1769 L27ERM QBFC1B 13 564 bytes WA CompactLog
27. o should have errored ER bit but do not Lgx00125204 Lgx00124996 Rockwell Automation Publication 1789 RN210B EN P April 2014 6 SoftLogix Controllers Version 21 Table 6 Corrected Anomalies with Version 21 Controllers continued Cat No 1789 L10 1789 130 1789 L60 Description CORRECTED Log On to FactoryTalk Dialog Box Displays When Launching RSLogix 5000 Software When launching RSLogix 5000 software the Log On to FactoryTalk dialog box may be displayed This dialog box may be seen when you do not have Administrator privileges on the personal computer and the current user does not exist in the FactoryTalk directory If this dialog box is cancelled the RSLogix 5000 software will not be launched When the dialog box is displayed entering the credentials for a user that has Administrator privileges on the personal computer will then allow RSLogix 5000 software to be launched To avoid seeing this dialog box you can add the current user or user group to the FactoryTalk directory Follow these steps to add a user or user group to the FactoryTalk directory 1 Launch the FactoryTalk Administration Console available from the Start menu 2 Select the Network directory when prompted You may need to provide credentials for a user with Administrator privileges to continue 3 To allow access for a particular user navigate to Network System Users and Groups Users right click the Users folder and choose New gt Windows Link
28. ockwell Automation sales representative Tech Notes and other resources are available at the Technical Support Knowledgebase http www rockwellautomation com knowledgebase Rockwell Automation Publication 1789 RN210B EN P April 2014 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com rockwellautomation support overview page or contact your local Rockwell Automation representati
29. of the systems The installation of a SoftLogix computer on a computer generates a unique CIP serial number that is used to identify messages from that node on the network This serial number must be unique for every SoftLogix 5800 computer in the system 1 Prior to running the drive image software to produce the master image make sure that there are no controllers in the chassis and then terminate the Chassis Monitor by right clicking the icon in the tool tray and choosing Shutdown Monitor 2 Delete the key ASASerialNumber from the Windows registry by using the regedit exe tool provided with your Windows operating system 3 HKEY_LOCAL_MACHINE SOFTWARE Rockwell Automation VirtualBackplaneMonitor Installed Modules 0001 000E 000F ASASerialNumber 4 Create the drive image with the computer in this state making sure that you do not run the Chassis Monitor again because that will cause the CIP serial number to be regenerated in the registry After the master image is copied to your new computer and the computer is restarted a unique CIP serial number will be generated the first time that the Chassis Monitor is launched Instruction set Ifyou run SoftLogix 5800 software and you perform continuous messaging or block transfers where the instructions are triggered by their own enable bits EN there is a potential for the instructions to stop executing and remain in a state with only the enable bit set The SoftLogix 5800 controller may stop r
30. on engineering design tools and capabilities It is the one place for design engineers to develop all of the elements of their control system Rockwell Automation Publication 1789 RN210B EN P April 2014 4 SoftLogix Controllers Version 21 System Requirements This table identifies system requirements for the SoftLogix 5800 controller IMPORTANT Use the computer that is running the SoftLogix controller like an industrial controller not a personal computer The SoftLogix 5800 controller executes real time operations If you use other programs or applications on the computer when the SoftLogix 5800 controller is executing real time operations those operations can be disrupted IMPORTANT SoftLogix controllers and software do not support Integrated Motion on the EtherNet IP network The ControlNet and DeviceNet networks are supported in SoftLogix controllers version 20 and earlier When using a SoftLogix controller on a Microsoft Windows 7 operating system an Ethernet network is the only communication network supported No other communication modules are supported or should be used Rockwell Automation PCI based cards are not supported when using the Microsoft Windows 7 operating system If you need information on Compatible PCl based cards for previous versions see SoftLogix 5800 Controllers Version 20 Release Notes publication 1789 RN519 For more information see Knowledgebase document KB 509008 Table 4 System Requir
31. pril 2014 SoftLogix Controllers Version 21 19 Table 10 Estimate Additional Memory If you upgrade Then add the following memory requirements to your project Which comes from this type of from revision add memory all that apply Component Increase Decrease Per 1 0 Data and Safety Instance Logic 13 x to 14 x If you use a tag of the types listed below increase the memory as indicated for each instance Tag that uses the COORDINATE SYSTEM data type 60 bytes vA Tag that uses any AXIS data type 4 bytes v 12 x to 13 x Program 12 bytes vA Task 4 bytes vA User defined data type 4 bytes vA 1 0 module 16 bytes Vis v3 bytes bytes If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 8 bytes vA Consumed tag 8 bytes v 11 x to 12 x 1 0 module with a comm format Rack Optimization 90 bytes v 1 0 module with a comm format something other than Rack Optimization such 144 bytes vA as a direct connection CompactLogix 1769 1 0 module 170 bytes vA Bridge module with a comm format None 160 bytes vA Bridge module with a comm format Rack Optimization 220 bytes v 10 x to 11 x User defined data type 128 bytes v Number of user defined data types in the controller organizer gt Data Types folder gt User Defined folder Not the use of that data type in tags Indirect address using a t
32. sumed tag DINT 4 12 bytes REAL 4 12 bytes Routine 68 bytes v 5 x to 6 x Routine 116 bytes vA Rockwell Automation Publication 1789 RN210B EN P April 2014 Additional Resources SoftLogix Controllers Version 21 21 These documents contain additional information concerning related products from Rockwell Automation Resource Logix5000 Controllers Common Procedures Reference Manual publication 1756 PM001 Description Contains information specific to procedures related to programming your controller SoftLogix 5800 Controllers Version 17 Release Notes publication 1789 RNO17 Describes anomalies and enhancements related to controller version 17 SoftLogix 5800 Controllers Version 18 Release Notes publication 1789 RN018 Describes anomalies and enhancements related to controller version 18 Logix5000 Controllers General Instructions publication 1756 RM003 Contains information about general instructions Logix5000 Motion Controllers Instructions Reference Manual publication MOTION RM002 Contains information about motion instructions Logix5000 Process Controls and Drives Instructions Reference Manual publication 1756 RM006 Contains information specific to the PI instruction You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or R
33. ule output connection 4 bytes v For each controller gt 1 Kb change 1756 L6x 1264 bytes vA 1756 L6x 1268 bytes v 1756 L6xS 1264 bytes vA 1756 L6xS 1316 bytes v 1756 L6xS 1312 bytes vA 1756 L7x 5588 bytes WA 1756 L7x 1296 bytes vA Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 15 Table 10 Estimate Additional Memory If you upgrade Then add the following memory requirements to your project Which comes from this type of from revision add memory all that apply Component Increase Decrease Per 1 0 Data and Safety Instance Logic 19 x to 20 x 1768 L4x 1768 L4xS 1212 bytes vA 1768 L4x 1292 bytes v 1768 L4xS 1340 bytes vA 1768 L4xS 1312 bytes vA 1769 L23 2488 bytes v 1769 L31 2492 bytes vA 1769 L32C 1769 L35CR 2812 bytes v 1769 L32E 1769 L35E 2496 bytes vA 18 x to 19 x lt no change gt 17 x to 18 x Program 8 bytes vA Equipment phase 20 bytes vA Add On Instruction 12 bytes vA Each tag 4 bytes v In addition if you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 36 bytes 24 bytes number of consumers Consumed tag 24 bytes Data access control 4 bytes per symbol vA Tag that uses ALARM_ANALOG data type 20 bytes v Tag that uses ALARM_DIGITAL data type 28 bytes vA Tag that
34. uses MOTION_GROUP data type 76 v Tag that uses AXIS_SERVO_DRIVE or AXIS_GENERIC_DRIVE data type 786 bytes vA Tag that uses AXIS data type other than AXIS_SERVO_DRIVE or 818 bytes vA AXIS_GENERIC_DRIVE Tag that uses COORDINATE_SYSTEM data type with no transform dimensions 40 bytes v Tag that uses COORDINATE_SYSTEM data type with transform dimensions 100 bytes vA Module input connection 20 bytes vA Module output connection 24 bytes v Safety controller 8 bytes vA Safety partner 8 bytes v Rockwell Automation Publication 1789 RN210B EN P April 2014 16 SoftLogix Controllers Version 21 Table 10 Estimate Additional Memory If you upgrade from revision add all that apply 17 x to 18 x Then add the following memory requirements to your project Which comes from this type of memory Component Increase Decrease Per 1 0 Data and Safety Instance Logic For each controller gt 1 Kb change 1756 L6x 1756 L6xS 1756 L63XT 16 728 bytes vA 1768 L4x 1768 L4xS 14 448 bytes vA 1769 L2x 35 084 bytes vA 1769 L31 14 740 bytes vA 1769 L32C 1769 L35CR 35 400 bytes v 1769 L32E 1769 L35E 35 036 bytes v 1789 L10 1789 L30 1789 L60 4992 v Rockwell Automation Publication 1789 RN210B EN P April 2014 SoftLogix Controllers Version 21 17 Table 10 Estimate Additional Memory Then add the following memory requirements to your project I
35. ve New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation CompactLogix RSLinx RSLogix Encompass SoftLogix Logix5000 Kinetix FactoryTalk ControlFLASH ControlLogix and Micro830 ate trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation ate property of their respective companies Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Rockwell Otomasyon Ticaret A S Kar Plaza Ig Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90
36. x Controllers Version 21 3 Compatible Software Versions To use version 21 03 00 these minimum software versions are required Table 3 Compatible Software Versions Software Required Software Version Min Compare Tool 3 40 00 ControlFLASH 12 00 00 FactoryTalk AssetCentre 4 10 00 CPR9 SR5 1 FactoryTalk Services Platform 2 51 00 CPR9 SR5 1 FactoryTalk Activation 3 51 00 CPR9 SR5 1 RSLinx Classic 3 51 01 CPR9 SR5 1 RSLinx Enterprise 5 51 00 CPR9 SR5 1 Studio 5000 Logix Designer 21 03 00 CPR9 SR5 1 IMPORTANT ControlNet and DeviceNet networks are supported in SoftLogix controllers version 20 and earlier The Studio 5000 Engineering and Design Environment combines engineering and design elements into a common environment The first element in the Studio 5000 environment is the Logix Designer application The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix5000 controllers for discrete process batch motion safety and drive based solutions Rockwell Software Studio 5000 Create Open Explore New Project Existing Project Help From Import Sample Project Release Notes From Sample Project From Upload About Recent Projects Sept_Test Integrated_Motion_Co August_2012 The Studio 5000 environment is the foundation for the future of Rockwell Automati
37. x00069461 Rockwell Automation Publication 1789 RN210B EN P April 2014 8 SoftLogix Controllers Version 21 Table 7 Known Anomalies with Version 21 Controllers continued Cat No 1789 L10 1789 L30 1789 L60 Restrictions Description Under some rare occurrences if a Motion Axis Move MAM instruction with Merge Enabled is activated during the deceleration segment of an active MAM instruction then the new MAM instruction may overshoot its programmed endpoint The occurrence of the overshoot depends on the following factors The original MAM instruction s remaining travel distance at the time of the merge and the new MAM instruction s remaining travel distance The relationship of the decel jerk of the new MAM instruction to the decel jerk of the original MAM instruction e Ifthe original MAM instruction is decelerating Typically the overshoot does not occur If either of the following conditions exist you will avoid the overshoot The new MAM instruction is programmed with Merge Disabled If there is no other motion active at the time of the merge then the Merge Disable results in the same operation as the Merge Enable e The new MAM instruction has a slightly higher jerk in units seconds than the original MAM instruction You should note though lower value of jerk in of time results in higher value of jerk in units seconds Lgx00078822 If a Motion Group Shutdown Reset MGSR instruction is executed wh

Download Pdf Manuals

image

Related Search

Related Contents

Centrum KD/VOX Usuario  Bushnell 118213 Binoculars User Manual  Bedienungsanleitung    SS-box製品カタログ(2.45MB)  ADSLモデム-MS5取扱説明書  cf7 he  Continental Electric CE23431 User's Manual  

Copyright © All rights reserved.
Failed to retrieve file