        SPM-3000 - Paragon Controls
         Contents
1.  11 3  Normal Status LED  DL3     LED State Operation State                            On Normal state  Off Alarm state  Blink Space returns to normal state with no Alarm  Acknowledge          2 2 11 4  Alarm Status LED  DL4                                               LED State Operation State  On Alarm state and Alarm Acknowledged  Off No Alarm state  Blink Alarm state with no Alarm Acknowledge  2 2 11 5  SMD LED   s  DL9 10   LED State   Status LED  DL9    Diag  LED  DL10   On IrDA Comm  Established    Off  Blink                            5 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    2 2 12  Buttons  amp  Switches    The Micro Guardian unit has three buttons  two slide switches  and one dip switch  Button and switch  functions are shown below  see Section 2 1 1 for component location      2 2 12 1  Button Functions                      Function Button State  Field Calibration Enable Press S3 and S4 simultaneously for 3 seconds   Zero Calibration Press S3   Span Max Calibration Press S4   Span Min  Bi polar sensor  Press S4 after span calibration   Alarm Acknowledge Press S2   All Alarms Off Press S2 3 times and then hold down for 3  seconds  Repeat process to turn alarms back on                 2 2 12 2  Switch Functions    Switch   Function  S5  Slide switch  Unit Power On Off  S6  Slide switch  Analog output Voltage Current select   S1 1  Dip switch  Au
2.  Refer to Figure 2 0 for clarification on the front component layout     CALIBRATION STATUS  INDICATION    CAL  DL8        STATUS 53 MODE  O NORMAL e    POSITIVE  ZERO   ZERO  S3  AND SPAN  S4   lt    NEGATIVE 81 1 AUDIBLE ALARM OFF   ON  CALIBRATION SWITCHES sa S1 2 BACNET TERMINATION OFF   ON   O ALARM       OFF S6 PROCESS OUTPUT  ROOM CALIBRATION room    ner mom SELECT  mA   V   PRESSURE CONNECTION a A et  m       Ere S2 ALARM   REFERENCE CALIBRATION   ES  AARM ACKNOWLEDGE  PRESSURE CONNECTION se 7 OO U ACKNOWLEDGE    AUDIBLE  ALARM       POWER SWITCH    FIGURE 2 0       2 Paragon Controls Incorporated  Rev  V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480     ze  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    2 1 2  Back Component and Connector Layout  Refer to Figure 2 1 for clarification on the back component and connector layout              REFERENCE PRESSURE    CONNECTION V GUARD PLATE  J4  BLACK TUBING   14  LONWORKS   BACNET  13S  ROOM PRESSURE  CONNECTION  J3  CLEAR TUBING  R  12 6  CONNECTION TO RPM  111S  J2 ile PING SWITCH    QL  REFERENCE  10     PROCESS OUTPUT Ne   k  ie uS   LONWORKS   BACNET  al A O  181   9   PROCESS OUTPUT   SY  Ja  3 O  Ne 3 ROOM  CLEAR TUBE  ON CONNECTION TO RPM  7  3  NO SPACE PRESSURE ALARM i J2   gt  co 103    PROCESS OUTPUT  6     COM s 5 wot 9    PROCESS OUTPUT  D    8  y NC  5 S OFF MODE SELECT de Serial    7 5 NO PRESSURE ALARM  utput  6 y COM  4 OPEN   NORMAL   CLOSED   OFF    De   S GEE MODE SELECT   a C
3.  flash green three       7 Paragon Controls Incorporated  Rev  V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    times indicating the value was accepted  If the new value is determined to be  outside of factory allowed limits  the cal LED  DL8  will flash red three times  indicating the value was not accepted  If the positive span calibration was not  accepted  repeat Steps 3 thru 5    Step 7  Connect the low pressure air source output to the pressure fitting labeled  REF     Step 8  Apply and verify negative span pressure value to the transducer    Step 9  Once negative span pressure is verified  press the Span button  S4  located on the  board    Step 10  The CPU will begin taking samples  This will last for 5 seconds  The CPU will  store this value in a secondary flash memory location and will be used by the CPU  instead of the factory calibrated value  The green cal LED will flash three times  indicating the value was accepted  If the new value is determined to be outside of  factory allowed limits  the red cal LED will flash three times indicating the value  was not accepted  If the negative span calibration was not accepted  repeat Steps 1  thru 9     Step 11  Re connect  ROOM  and  REF  tubing as shown in Section 2 1 1     3 3  UNIDIRECTIONAL SPAN CALIBRATION    Note  Uni directional devices can monitor only positive pressure values     Note  It is recommended that a zero calibration be comple
4. 2 09 09  Phone 707   579 1424  Fax 707   579 8480     ze  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    4  TROUBLESHOOTING GUIDE                TROUBLESHOOTING TABLE  SYMPTOM SOLUTION  1  Status  amp  Mode LED s are not 1  Verify ON OFF switch is in ON position  see  illuminated LCD Display is Blank Section 2 1 1      2  Verify correct input power and connection at  connector J1  see Section 2 1 2      3  Verify input power wire insulation has been  properly removed and the wire fully inserted into  the J1 power plug     4  Contact Factory Service Department     2  Display characters are too dim or too 1  Remove front cover  Adjust Display potentiometer  dark R87 located at the top of the LCD board     2  Contact Factory Service Department     3  Display reads zero pressure and does 1  Verify room calibration pressure tubing is  not respond to input pressure changes connected as shown in Section 2 1 1     2  Squeeze each room calibration tube independently  with your fingers  If the display responds  proceed  to step 3  If the display does not respond  contact  Factory Service Department     3  Turn the power switch to OFF  Remove the Micro  Guardian from the wall box and verify the input  signal tubing is connected as shown in Section  2 1 2     4  Contact Factory Service Department     4  Display is reading a pressure but does 1  Turn the power switch to OFF  Remove the Micro  not respond to input pressure changes Guardian from the wall box and inspect for  
5. Functions   All  OFF and can not be changed via Alarms OFF section  Follow the instructions to  communication network  restore Operation Mode     2  Contact Factory Service Department     9  LonWorks not communicating with 1  Turn power switch OFF  Remove Micro Guardian  the Micro Guardian from the wall box  Carefully turn power switch  ON  Press service pin located on the LonWorks  board  Turn power switch to OFF and reinstall  Micro Guardian     2  Swap wires on J4 pins 13  amp  14  see Section 2 1 2      3  Contact Factory Service Department                          10 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    He SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    TROUBLESHOOTING TABLE    SYMPTOM SOLUTION    10  BACnet not communicating with the 1  Verify two devices do not have the same Instance  Micro Guardian Number and MAC code  Change to an unused  Instance Number and MAC code                 2  Verify wires connected to J4 pins 13  amp  14 are  correct  If not  swap the wires and retest              3  Contact Factory Service Department                    11 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    PC    PARAGON    CONTROLS  INCORPORATED    Paragon Controls Incorporated    P O  Box 99  Forestville  CA 95436  http   www paragoncontrols com  Phone 707   579 1424   Fax 707   579 8480   IOM  SPM 3000RevV1 12127 09 09  Copyright O 2009    
6. If the new value is determined to be  outside of factory allowed limits the cal LED  DL8  will flash red three times  indicating the value was not accepted  If the zero calibration was not accepted   repeat steps 1 thru 4     3 2  BIDIRECTIONAL SPAN CALIBRATION    Note  Bi directional devices can monitor both positive and negative pressure values     Note  It is recommended that a zero calibration be completed before performing a span calibration   Reference Section 2 1 1 for component location     3 2 1  Equipment Required    Low pressure air source  Paragon PS 100 or equivalent     Manometer for measuring low pressure    3 2 2  Procedure   Step 1  Remove the tubing from the pressure fittings labeled on the board as  ROOM   and  REF     Step 2  Connect the low pressure air source output to the pressure fitting labeled   ROOM     Step 3  Press both the Zero  S3  and Span  S4  buttons together for 3 seconds  The cal  LED  DL8  will flash green three times and remain on to indicate the Micro  Guardian is in the calibration mode    Step 4  Apply the positive span pressure value  see the ID label located on guard plate  attached to the back of the board     Step 5  Once the span pressure is verified  press the Span  S4  button located on the board    Step 6  The CPU will begin taking samples  This will last for 5 seconds  The CPU will  store this value in a secondary flash memory location and will be used by the CPU  instead of the factory calibrated value  The cal LED  DL8  will
7. LOSED   OFF  e Nuron ID    Ji  SA   e   EF 8 EARTH GROUND  3  EARTH GROUND east   24VAC  2 5 y  4 24VAC  50 60HZ   ID LABEL CONNECTION LABEL  FIGURE 2 1    2 2  HARDWARE SPECIFICATIONS OF INPUTS AND OUTPUTS    2 2 1  Power Input    The power input is 20 28VAC at 50 60Hz  Line power is connected to input socket  J1   The unit has  an isolated DC DC converter  which creates electrical isolation between the power input and the unit     2 2 2  Pressure Sensor Input    The SPM 3000 is factory configured for bi directional or uni directional pressure input  Bi directional  pressure input provides both positive and negative pressure values  Uni directional pressure input  provides only positive pressure values     2 2 3  Analog Output    Pins 9 10 of  J2  connector are used for analog output  The Micro Guardian unit provides 4 20mA or  0 10V analog output  S6 slide switch is used for Voltage Current output selection  The maximum  output load impedance for current output is 500 ohms  The minimum load impedance for voltage output  is 1000 ohms     2 2 4  Remote Space Pressure Alarm relay  The contact rating of the SPDT alarm relay is 0 6A at 125VAC or 110VDC and 2 0A at 30VDC        3 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    2 2 5  Off Mode Select    The Micro Guardian has 4 options available to the user to select the OFF mode  The Manual mode is  described in secti
8. PARAGON  CONTROLS  INCORPORATED       SPM 3000    Micro Guardian Space Pressure  Monitor and Alarm System    Operation  amp  Maintenance Manual    Engineered for accuracy  applicability   durability and simplicity    Ke  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual       TABLE OF CONTENTS  FABLEOR CONTENTS RE Us tac  n i  dhe     INTRODUCTION siisii nannan acta T e car le aa td 1  Til     BASIC OPERATION sis cdas 1  A A ARR SE EE AR AR 1  121    I  CHIEAL  ORTECHONS SR as 1  1 2 2  Static Electricity anitae n a R nn A E tr  s 1  2  HARDWARE CONFIGURATION it is 2  2 1  MICRO GUARDIAN COMPONENT LAYOUT inserer 2  LLL  Front A A AR OR EE rl eG See 2  2 12  Back Component and Connector Layouts 3  2 2  HARDWARE SPECIFICATIONS OF INPUTS AND OUTPUTS coocooconiccniconinnncnnncconccnnnconnccnns 3  2 2 1  PON  CIADUES LS SR SR nn AA 3  222  Pressure SENS OT DIU cutie de 3  22 3  Analog Outp  t  sios eresien ae oE eE E nus nine tirs 3  2 2 4  Remote Space Pressure Alarm relay ist is 3  20  CHEMOdE Seu o 4  2 2 6  RPM OUE SR nn Ra OA OREA A E 4  22 7  Lonworks  BacnetOutp  t   een nt at De ns let net 4  2 2 8  EDA Portrait ad 4  220 E A D A os aes steas cae pe pasta eat com areas S TE om uae 4  22 10  Audible ALA As 4  ZA LED Susi dls A one en et 5  2 2 12   lt  A Sn RS ce nr men mel An nr te ede 6  36  FIELD  CALIBRATION td nr nn er eue 7  Bee ZEROQCALBPBRA TON cs SES ig O ne 7  3 1 1  PEGCC CUES os dessein eei i e me a e tet e LA ee ath aei 7  3 2  BIDIRECTIONAL SPAN CALIB
9. RATION sccsscsesccesesesedacstesdcctasncsatenssecead souensactasnaeaunnansdcneecesees 7  3 2 1  A O 7  32 2  A SR A nn TN ed cutee 7  3 3  UNIDIRECTIONAL SPAN CALIBRATION ses 8  3 3 1  Equipment Required iia 8  3 3 2  Procedure eiae r ER E A ER Sit 8  A gt  TROUBLESHOOTING GUIDE 5 nr ei aier arte anie seisa Re en 9  i Paragon Controls Incorporated  Rev  V1 12  12 09 09    Phone 707 579 1424  Fax 707   579 8480     ze  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    1  INTRODUCTION    This user manual provides information on product features and guides you through all basic  functionality     1 1  BASIC OPERATION    The Micro Guardian is a true differential space pressure measurement system  The Micro Guardian  integrates the newest microprocessor technologies with state of the art  industrial grade  highly accurate   ultra low range differential pressure sensing cells  The combination of these two technologies ensures  exceptional accuracy and long term stability     The Micro Guardian is a complete system package including space and reference pressure sensors and a  central signal processing module  The central module includes an in wall mounting box  local LED  indication of alarm status and operational mode  audible alarm with alarm acknowledge button  and an  optional LCD for local display of the space pressure  Device monitoring and configuration is performed  via LonWorks   or BACnet   MS TP communication networks  Additionally  the monitor can be  configu
10. dible alarm On  Enable Off  Disable  S1 2  Dip switch  BacNet Rs 485 Termination On Off  Note  S1 2 in the ON position adds a 200 ohm resistor across the BacNet terminals for noise  suppression when long wire lengths are required                                   6 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    3  FIELD CALIBRATION    The field calibration process can be performed to compensate for slight changes in the pressure sensors  over time  Reference Section 2 1 1 for component location     3 1  ZERO CALIBRATION    The following zero calibration procedure can be performed without the need to perform a span  calibration     3 1 1  Procedure   Step 1  Remove the tubing from the pressure fittings labeled on the board as  ROOM   and  REF   This ensures a zero differential pressure to the transducer    Step 2  Press both the Zero  S3  and Span  S4  buttons together for 3 seconds  The Cal  LED  DL8  will flash green three times and remain on to indicate that the Micro  Guardian is in the calibration mode    Step 3  Press and release the Zero button  S3   Wait 5 seconds    Step 4  The CPU will begin taking samples  This will last for 5 seconds  The CPU will  store this value in a secondary flash memory location and will be used by the CPU  instead of the factory calibrated value  The cal LED  DL8  will flash green three  times indicating the value was accepted  
11. on 2 2 5 1  Remote mode described in section 2 2 5 2  OFF mode selection via the  communication network or the Palm programming tool     2 2 5 1  Manual OFF Mode Select    This function will disable all alarms by switching the Operating Mode to OFF and can be  performed with the front cover attached  To switch to the OFF mode  press the ALARM  ACKNOWLEDGE button 3 times and then hold the button down for 3 seconds  The  Micro Guardian Mode LED will change to OFF  The alarms can only be restored by  repeating the same procedure     2 2 5 2  Remote OFF Mode Select    This function will disable all alarms by switching the Operating Mode to OFF  This can  be performed by attaching a SPST switch to pins 4  amp  5 of J2 located on the back side of  the board  Contact closure will force the Micro Guardian to the OFF mode and an open  contact will return the Micro Guardian to the previous operating mode     2 2 6  RPM Output  Pins 11 12 of  J3  are used to connect to a Paragon Remote Pressure Monitor  RPM 2000      2 2 7  Lonworks   Bacnet Output    Pins 13 14 of  J4  are used to connect to a LonWorks   or BACnet   MS TP communication network   The output requires a Lon Works or BACnet daughter board to be installed in the main board     2 2 8  IrDA Port    The Micro Guardian unit provides IrDA communication with a PALM handheld unit or PC software  MGUSim V4xx  For proper communication  the IrDA instrument must be aligned with the unit IrDA  window and the maximum distance must be ke
12. possible pinched or disconnected tubing  Reinstall  and verify operation     2  Remove ROOM and REF end of Room Calibration  tubing  see Section 2 1 1   If the display returns to  a zero reading  check for pinched or plugged  tubing at the PE 4000 pressure sensor or input  signal lines  If the display does not respond   contact the factory Service Department                       9 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 3000 Micro Guardian Operation  amp  Maintenance Manual                TROUBLESHOOTING TABLE  SYMPTOM SOLUTION  5  No Process output  Voltage Current  1  Verify correct output selection  see S6 in Section  or Incorrect Output 2 1 1      2  Disconnect output signal wires and verify output  signal at Micro Guardian connector J2 is correct   see Section 2 1 2      3  Contact Factory Service Department     6  Audio Alarm not functioning 1  Verify switch S1 1 is not in the ON position  see  Section 2 1 1      2  Verify correct alarm setpoint values     3  Verify alarm is not turned OFF via the  communication network     4  Verify MODE LED OFF is not illuminated on  Front Panel  see Sections 2 2 5 and 2 2 12 1     5  Contact Factory Service Department   7  Red Alarm LED remains ON 1  Verify alarm setpoint values     2  Verify input pressure tubing is connected correctly   see Section 2 1 2     3  Contact Factory Service Department     8  Operation Mode indicator LED is in 1  See Section 2 2 12 1 Button 
13. pt to 1 foot or less     2 2 9  LCD    An optional backlit two line graphical LCD providing eight characters of data display is used for  monitoring pressure and engineering units  The decimal point and polarity will be changed  automatically based on the engineering unit and range selection        0023    Inch we       2 2 10  Audible Alarm    A 85dB  max   40mA buzzer is used for providing continuous or interval audible alarm  The audible  alarm can be acknowledged by pushing the ACK button on the front cover plate  The buzzer output can  be enabled or disabled via switch S1 1 located on the front side of the board  For component location   see Section 2 1 1        4 Paragon Controls Incorporated  Rev V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 3000 Micro Guardian Operation  amp  Maintenance Manual    2 2 11  LED   s    The Micro Guardian unit has one bi color  two SMD  Surface Mount Device   and five solid LED   s   LED functions are shown below     2 2 11 1  Field Calibration Bi color LED  DL8     State Operation State          On Field Calibration Enabled   Off Field Calibration Disabled   Blink Red Field Calibration Error        Blink Green Field Calibration Correct or in calibration mode   starts blinking 3 times and then turns solid                       2 2 11 2  Operation Mode Indicator LED   s  DL5  6 7                 Mode Positive  DL5    Negative  DL6    Off  DL7   Positive Room On Off Off  Negative Room Off   Off Room On             2 2
14. red locally via IR communication using a laptop or Palm Tungsten E2    or equivalent   A  separate BACnet   communication port is available for connection to an optional Remote Pressure  Monitor  Communication network variables include the measured space pressure  high and low pressure  alarm values  operational mode selection  alarm status  alarm delay value and audible alarm on off  selection     The Micro Guardian also incorporates a form C SPDT room pressure alarm relay for remote alarm  activation and an analog output signal linear to the measured space differential pressure     1 2  SAFETY    1 2 1  Electrical Connections  Before any electrical connections are made  ensure the POWER SWITCH is in the OFF position     1 2 2  Static Electricity    The circuit board contains components which are susceptible to damage caused by static electrical  discharge  Should it be necessary to remove the circuit board from the enclosure  appropriate  precautions must first be taken to ensure that the operator and the circuit board are at the same electrical  potential        1 Paragon Controls Incorporated  Rev  V1 12  12 09 09  Phone 707   579 1424  Fax 707   579 8480     ze  SPM 3000 Micro Guardian Operation  amp  Maintenance Manual  2  HARDWARE CONFIGURATION    The Micro Guardian combines the pressure measurement circuits  digital input outputs  analog outputs   Voltage Current  and LCD unit in a single board     2 1  MICRO GUARDIAN COMPONENT LAYOUT    2 1 1  Front Component Layout 
15. ted before performing a span calibration   Reference Section 2 1 1 for component location     3 3 1  Equipment Required    Low pressure air source  Paragon PS 100 or equivalent     Manometer for measuring low pressure    3 3 2  Procedure   Step 1    Remove the tubing from the pressure fittings labeled on the board as  ROOM   and  REF     Step 2  Connect the low pressure air source output to the pressure fitting labeled   ROOM     Step 3  Press both the Zero  S3  and Span  S4  buttons together for 3 seconds  The cal  LED will flash green three times and remain on to indicate the Micro Guardian is  in the calibration mode    Step 4  Apply the positive span pressure value  see ID label located on guard plate  attached to the back of the board     Step 5  Once the span pressure is verified  press the Span  S4  button located on the board    Step 6  The CPU will begin taking samples  This will last for 5 seconds  The CPU will  store this value in a secondary flash memory location and will be used by the CPU  instead of the factory calibrated value  The cal LED  DL8  will flash green three  times indicating the value was accepted  If the new value is determined to be  outside of factory allowed limits  the cal LED  DL8  will flash red three times  indicating the value was not accepted  If the positive span calibration was not  accepted  repeat Steps 3 thru 6     Step 7  Re connect  ROOM  and  REF  tubing as shown in Section 2 1 1        8 Paragon Controls Incorporated  Rev V1 12  1
    