Home

1. Introduction 2. Architecture

image

Contents

1. A and B by default or if null key A transaction 00 and key B transaction 01 Arming a zone not performed Sound a bip bip ID Request when input s on alarm during entry exit delay For transactions Card or PIN Card only PIN only Card and PIN Card or PIN Card only PIN only Card and PIN Card or PIN Card only PIN only Card and PIN Card or PIN Card only PIN only Card and PIN Example To define that the terminal 00 belongs to Alarm Zone 01 with an exit delay of 45 sec transactions code for keys A and B are 18 and 19 card or PIN are requested from the user and a bip bip is sound during the entrance or exit delay the script to write is 45 10 01 ED 84 12 13 The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 5 6 Note on an Alarm Zone dispatched in several controllers When the user arms the terminal alarm zone the inputs of this zone managed by the Domain controller will be armed after the alarm exit delay dd programmed see Par 5 1 1 But if other inputs of this zone are managed by other controllers they will be armed immediately To allocate also a delay to these inputs message 45 must also be sent to all the controllers which manage these inputs as follows 45 1t AZ dd 00 00 00 1t AZ and dd as explained in Par 5 1 1 The command will be inserted in the script menu of the corresponding controller 5 1 2 Domain
2. 2 may also be connected other controllers max 32 and terminals max 16 All these items constitute a Domain and the TPL 00 is called the Domain controller Terminals belonging to the domain may control via TPL 00 all the inputs outputs of the controllers belonging to the same Domain and this without the PC intervention Note that all controllers connected by their 2nd communication port must be provided with the kit COM 2 The terminals and therefore all the controllers on the bus may communicate only at 9600 or 19200 baud To be operational the DDS terminal doesn t need any programming as soon as turned on it is looking on the network for the Domain controller TPL 00 and when found displayed the time and date received The terminal is then ready to received transactions from users and sends them to the Domain controller Notes 1 At the Amadeus application Cardholders or supervisors supposed to use the DDS Terminal must have in their Access group definition the Reader no 1 of the Domain Controller 00 2 The Domain controller may receive from Amadeus some parameters for the following purposes Terminal parameters Alarm zone exit delay etc via Mess 45 see par 5 1 1 List of the controllers belonging to the domain via Mess 45 see par 5 1 2 Transactions name via Mess 51 see par 5 2 The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 1 6 3
3. Installing the terminal DDS Terminal Connection Keypad Controller Connect the terminal to a bus 2 via its RS485 port AUX RED 12Vde This bus must be connected to port 2 of TPL 00 COM BLK Ov All the controllers of the domain i e connected to BUS YEL Hi RS485 bus 2 the same Bus 2 must get a firmware dated from BUS GRN Lo RS485 bus 2 1 12 2010 or later Because up to 15 terminals may be connected to the same bus each if them needs a different address set by its internal dip switches inside the housing on the PCB near the LCD display as follows on on on off 07 Note that each terminal adds 191 to this physical address to communicate with the Domain controller so that addresses 00 to 15 may be used by the controllers 4 Using the terminal 4 1 Transaction entry To perform a transaction the user has first to identify himself either by presenting his card front of the terminal or by keying in his PIN code at the keypad He then can enter the transaction requested as shown in Table 1 An Audible Tone Buzzer is sounded when a card is correctly read or when a key pressed The authorized amount of time is 8 seconds between key entries If the time expires all keys entered and possible card code read are cleared and the user must start the sequence from the beginning Pressing the Clear key at any moment will cancel the transaction Keeping this Clear key pressed during 4 secon
4. a specific text may be user defined from Amadeus like Exit busy Maintenance etc via Mess 51 see par 5 2 The following table shows the transactions format recognized by the terminal The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 2 6 Table 1 Transactions recognized by the DDS Terminal Operation User action Comments TRN Code data Alarm transactions Arm Alarm Zone No aa IDC aa aa alarm zone No 26 aa Disarm Alarm Zone No aa ID SS aa aa alarm zone No 27 aa Query status of Alarm zone No aa ID aa aa alarm zone No 29 aa Time amp Atendance transactions Display the key A transaction name A No transaction recorded Display the key B transaction name B No transaction recorded Display transaction nn name nn C No transaction recorded Record a transaction with key A default code ID A Record a transaction with key B default code ID B Record a transaction with code nnf IDC m C Remote control Transaction with code nn IDC m C Perform an action ex open a door using A or B ID A or ID B Activate Reflex No RR IDC r D Local action Cancel Clear Press Reset the terminal Press during 4 sec Get the terminal firmware version Press D during 4 sec Notes l Transaction code and data Within the Amadeus system each cardholder transactio
5. delay via Mess 45 byte P see par 5 1 1 If the domain has been defined see par 5 1 2 when arming an Alarm zone from the terminal the Domain controller first checks that all the inputs belonging to that zone even if managed by another controllers of the domain are not in their alarm state If no the Alarm Zone i e all the inputs belonging to this zone will be armed If one or several of these inputs are under alarm for example input 2 of controller 02 C02 12 see diagram in par 2 the keypad LCD will prompt the user with a warning message saying LCD Line 1 16 characters CnnIn on alarm For example C0212 on alarm LCD Line 2 16 characters Continue The user will then have the following choices Status Display the next input under alarm if exist Arm Arm the zone anyway even with inputs under alarm Cancel the Arming operation If the user doesn t press any key during 10 sec the arming operation will be cancelled Notes 1 If the user decides to arm the zone while an alarm input is in its alarm state and have already sent an start alarm message no alarm will be raised because the system sends alarm ONLY after a change on a input i e only when an input goes from its normal state to its alarm state Therefore for example if the zone is armed while input C02 I2 in its alarm state it will not raise any alarm until it goes back to its nor
6. the red periods The DDS terminal allows the user who must be defined as Supervisor to manually change the status of such a zone Ifa Weekly Program is attributed to the zone the change will take effect until the next time period of the program If no Weekly Program is attributed or a Weekly Program without time periods The default Always and Never Programs the change will take effect till the next manual change Notes 1 Only inputs which belong to the same domain i e managed by all the controllers connected together via their bus2 may be updated via the DDS terminal connected to the domain 2 To be able to manage Alarm zones the two following lines have to be inserted in the ini file of the application AlarmZones 1 ControllerInputGroup 1 Terminal Alarm Zone and led ARM According to its physical location a terminal may belong to an Alarm Zone defined from Amadeus via Mess 45 see par 5 1 1 When this zone is armed the led ARM of the terminal is on and when the zone is disarmed the led is off When the zone is manually armed by a user from the terminal the ARM led blinks for the period of the defined Exit delay in Mess 45 during which the zone is still disarmed to give the user time to leave the zone After this delay the zone is armed and the led turns on It is possible to program the terminal to sound a bip bip indication during this exit
7. Definition When the user requests to arm an alarm zone the Domain controller may query the other controllers of the domain if their inputs which belong to this zone are on alarm If yes the Domain controller will prompt the user via the terminal LCD if he wants to continue the arming operation Therefore the Domain controller must know the list of the controllers in the domain This is done via Mess 45 as follows 45 00 00 tto tti ttz tts Where tts tto is the list of the controllers belonging to the domain in a bit map form tto bit 0 represents controller 00 tto bit 7 controller 07 tt bit 0 controller 08 until tt bit 7 for controller 31 A controller belongs to the domain if its corresponding bit is set Example if the domain contains controllers 01 02 03 and 09 the command to insert in the script screen will be 45 00 00 OF 02 00 00 Note that bit 0 of tto stands for the Domain controller 00 and therefore may also be set 5 2 Transaction Name Message 51 When a transaction is acknowledged by the domain controller it displays via the terminal LCD screen the cardholder number in the first line and in the second line the transaction code used It is possible to pre defined transaction names which will be displayed instead of the transaction code as follows 51 ss cc ddy ddi Where ss is the string num
8. THE DDS LCD KEYPAD TERMINAL DDS 7K USER MANUAL AND COMMUNICATION PROTOCOL P Building Security Together publication No 07UE102 October the 12th 2010 1 Introduction The DDS LCD Keypad terminal is a multi purpose unit which can be used as a remote station of the Amadeus PC software Once the user has identified himself through his PIN code or his card he may perform one of the following applications Access Control to restricted area According to a pre defined code the unit may grant access to a corresponding secured area 2 Alarm keypad e ia D The unit allows user to perform manual changes in the Amadeus security system like Arm or disarm Alarm Zones J ij Query Alarm zones status Perform actions pre defined at the Amadeus Application Time amp attendance terminal Cardholders may use the unit to record entry exit or specific transactions exit busy start job etc which will be used by the Amadeus application for time amp attendance purpose Amadeus remote control station The terminal may be used by Amadeus to display a message for example to a specific cardholder upon his access to allow authorized users to execute pre defined processes activate relays etc etc 2 Architecture Domain DS216 Controller 01 TPL 03 04 05 TPL 02 00 Port 4 A DDS Terminal must be connected to the RS485 port 2 of a TPL controller address 00 To this RS485 bus
9. ber from 01 to 31 therefore up to 31 codes may be pre defined ce the transaction code from 00 to 19 or 30 to 99 with Bit 7 set to 1 i e cc h80 to h93 or h9E to hE3 and dd to dds the transaction name in ASCII If the name has less than 16 characters 00 must be added 5 3 Script example Hereunder an example of a script which can be copied and pasted to the script screen of Amadeus5 controller 00 51 01 8A 20 20 20 53 74 61 72 74 20 4D 65 61 6C 20 20 20 string 01 TRN code 10 start meal 51 02 8B 20 20 20 20 45 6E 64 20 4D 65 61 6C 20 20 20 20 string 02 TRN code 11 end meal 51 03 8C 45 78 69 74 20 4D 61 69 6E 74 65 6E 61 6E 63 65 string 03 TRN code 12 Exit Maintenance 51 04 8D 20 45 78 69 74 20 54 72 61 69 6E 69 6E 67 20 20 string 04 TRN code 13 Exit Training 45 00 00 05 00 00 00 Domain def Cnt 00 and 02 45 10 01 c8 80 OA OB Trm 00 AZ 01 Exit delay 8 sec Key A Trn code 10 Key B Trn code 11 45 12 02 02 80 OC OD Trm 02 AZ 02 Exit delay 2 min Key A Trn code 12 Key B Trn code 13 Note that a comment may be written after each command if it is preceded by the character The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 6 6
10. cepted codes 20 to 29 which are reserved for pre defined applications 20 21 23 24 25 28 reserved for future used 22 Reflex activation 26 27 Alarm zone armed disarmed 29 Query Alarm Zone status If a door must be opened a network reflex may be defined to activate the required door relay upon a specific transaction code To do so Reader No 1 of controller 00 must be selected at the field Reader of the Amadeus Network reflex screen Then if key A is for example redefined with this transaction code using Mess 45 See 5 1 opening the door will be performed by the ID A key entry 6 On some terminals the symbols are replaced by the following text MDC O O C Gm Examples of transactions Transaction with code 18 using a card or the PIN 1234 Card 18 C or 1234 ZS 18 C Arm Alarm zone No 01 using a card Card 01 Arm Arm Alarm zone No 01 using a card and the PIN 1235 Card 1235 01 Arm Arming Disarming ALL the Alarm zones use the Alarm zone No 00 The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 3 6 4 4 Alarm Zone Management An Alarm Zone or Input group is a group of alarm inputs grouped together through the Amadeus application The inputs of an Alarm Zone may belong to different controllers A Weekly Program WPz may be attributed to an Alarm Zone the zone will be automatically armed during the green periods of this program and disarmed during
11. ds will reset the terminal while keeping the D key pressed will display the firmware version 4 2 Terminal built in Card reader The terminal contains a proximity card reader RFID which may read the 32 data bits of any proximity EM card 125 Khz The format read i e hexadecimal decimal or other is the same as the one defined for Reader 1 of the Domain controller Controller address 00 Note that the DDS Terminals read the 32 bits of a DDS EM Card while the DDS readers read only 26 Bits of these cards To get the same hexadecimal code from the DDS terminal and the DDS reader the Wiegand format 09 must be defined at all the readers of the Domain controller Alternatively to read the card in one of the decimal format recognized by the controller formats Decimal Decimal 24 bits or Decimal 6 digits this format must be defined at all the readers of the Domain controller via the PC Amadeus application screen Controller Reader Miscellaneous Badge format The reader antenna is located around the terminal keypad and therefore to be read a card must be presented few centimeters in front of the keypad 4 3 Transaction Display On stand by the terminal displays the stand by text Wait for ID and the actual time and date When a transaction is performed the unit sends it to the host and when acknowledged displays the corresponding text To each type of transaction defined by its code see next note 1
12. ion will not have any effect on the RTX buttons 5 Programming the Terminal through the Amadeus 5 Script Menu The terminal doesn t need any programming to be operational As soon as connected to the Domain controller and powered up it searches on the network for the Domain controller TPL 00 and when found displayed the time and date received The terminal is then ready to received transactions from users and sends them to the Domain controller However the Domain controller may receive from Amadeus some parameters via Mess 45 and 51 of protocol 4 as described hereunder They may be automatically sent by Amadeus5 if they are recorded in the Script screen which appears when clicking on Shift F12 at the Controller screen of the Domain Controller All the data must be written in hexadecimal 5 1 Terminals Parameters and Domain Definition Message 45 5 1 1 Terminals Parameters Command 45 allows to define the terminal parameters as follows 45 1t AZ dd P A B Where t Terminal number 0 F AZ Terminal Alarm zone in hexa from 01 to h7F When armed the arm led is lit on dd Terminal exit delay in hexa i e the delay the zone stays disarmed after that the user has armed it 0l BFh 1 191 minutes The terminal Arm led blinks slowly during this delay Clh FCh 1 60 seconds The terminal Arm led blinks quickly during this delay P Terminal parameters see table 5 1 1 A and B Transaction codes in hexa for Keys
13. mal state and then to its alarm state 2 It is possible however to prevent users to arm a zone in the case that at least one input is under alarm Via Mess 45 byte P see par 5 1 1 When this option is set if the Domain controller detects such an input it will automatically cancel the arming request Accessing an armed zone via a reader When a zone is armed access to a reader which belongs to the zone is denied excepted for cardholders defined as Supervisors For them access is granted the zone is disarmed during the Entrance delay the led ARM blinks and a bip bip can be sound at the terminal see par 5 1 1 Such supervisors may then access the zone and reach the terminal to disarm it A zone is attributed to a reader from Amadeus screen Controller Reader Miscellaneous Badge format where the entrance delay may also be defined The DDS LCD Keypad Terminal User Manual Doc 07UE102 Issue 12 10 10 Page 4 6 Request to Exit RTX button Any controller input may be used for a RTX button When a Weekly program is attributed to such an input the RTX button operates only during the green period of this program If no Weekly program is attributed the RTX button is always operational Note It is possible to group all the RTX inputs in a specific alarm zone and then arming or disarming the zone from Amadeus will make the buttons operational or not However if performed from a terminal this operat
14. n is recorded with a code which describes the type of transaction and therefore the type of process Amadeus has to perform upon reception of the transaction According to the user keypad entries transactions performed at the DDS Terminal get their own code to perform specific operations like entrance or exit busy for time attendance application arm or disarm alarm zones for alarm monitoring activate pre define reflexes etc Note that some transactions require also a parameter the transaction data like the alarm zone number to be armed or disarmed etc Table 1 shows how to perform transactions from the DDS terminal and which transaction code and data are generated and sent to the host 2 These transactions may be performed only by authorized users defined as Supervisor from Amadeus 3 ID stands for user identification either the user s card or his PIN recorded from Amadeus It is also possible to force the user using his card or his PIN or both Via Mess 45 byte P see par 5 1 1 Note that if only the card is requested the Bypass key is not needed after 4 The default terminal transaction for key A is 00 Entrance and for Key B is 01 Exit but may be changed from Amadeus via Mess 45 see par 5 1 1 5 A transaction with a specific transaction code will trigger a possible action pre defined for this code at the Amadeus application Any code may be used for transaction from 00 to 99 ex

Download Pdf Manuals

image

Related Search

Related Contents

  EarthMinded RS45-RC Installation Guide  Fluke PN 4060712 User's Manual  3com 3100 Entry Phone  Image forming apparatus and image reading apparatus with locking  Bedienungsanleitung Sony-Ericsson G900  Fugoo Bluetooth Speaker User Manual  TCW 2000 User presentation  MATIC-M-MA Parte seconda - NORME PER L  