MSII 6K ENGLISH NEUTRAL user manual

image

Contents

1. L 3 i B1 B2 S4 B1 B3 S4 15 3 4 Terminal Block Explanation Tower model OUTPUT N22 L22 N21 L23 L21 UPS OUTPUT G2 OUTPUT EARTH GROUND rae baa nat cw waif ee A oe L11 N1 BYPASS INPUT DIMTYPE ONLY UTILITY INPUT INPUT EARTH GROUND L12 N1 G1 INPUT UTILITY _ INPUT 192407SH00006100 OUTPUT N22 L22 N21 L23 L21 UPS OUTPUT G2 OUTPUT EARTH GROUND B N1 BYPASS INPUT D E ONLY R S T N1 UTILITY eur G1 INPUT EARTH GROUND 6000C or RT6K model C ourer ner ea nze oat or wi ue 1L21 N22 UPS OUTPUT G2 OQUTPUTEARTH G1 GROUND UTILITY BYPASS iN FI T L 12 L 11 DIM ONLY RT10K model 16 Li2 N1 UTILITY INPUT INPUT EARTH GROUND e L11 N1 B N1 the terminal for Bypass Input to provide the power source when the UPS is working under bypass mode L12 N1 R S T N1 the terminal for Utility Input to provide the power source when the UPS is working under Utility mode e G1 the terminal for UPS Input Ground L21 L23 N21 L22 gt N22 the terminals for UPS Output e G2 the terminal for UPS Output Ground Remarks 1 The maximum current for each terminal is 30Arms for 6Kva 50Arms for 10Kva 2 If the UPS is DIM Dual Input type whose Utility and Bypass Sources are the same L11 and L12 would have to be
2. 3 Remove the screw of the battery pack fastener as shown in Step 3 4 Remove the fastener as shown in Step 4 5 Unplug the hot swappable battery connectors as shown in Step 5 38 39 PT Battery Voltage amp Inner Temperature 8 Specifications Self Diagnostics Upon Power on Front Panel Setting amp Software Control 24 hour routine checking INPUT Voltage Window 160 280Vac 19 277 485Vac 30 Frequency 45 65 Hz Phase Wire Single Line Neutral Ground Power Factor Up to 0 99 at 100 Linear Load Current THD 100 linear load sis OUTPUT Voltage Window 220 230 240Vac Selectable 208 120 Vac optional Voltage Adjustment 0 1 42 3 Voltage Regulation 2 Capacity E Rated Power Factor 0 7 Lagging Sine Wave THD lt 3 no load to full load Frequency Stability 0 2 Free Running 11 13 Crest Factor Efficiency AC to AC Normal Up to 91 Efficiency AC to AC ECO Up to 97 Autonomy gt 8 min DC Start Yes BATTERY ALARMS Audible and Visual Line Failure Battery Low Transfer to Bypass System Fault Conditions PHYSICAL 290x645x748 without transformer Dimensions Tower model 290x645x748 290x645x881 WxDxH mm with transformer with transformer 440x680x88 440x680x132 Input Output Connection External Battery Connection Plug in amp Play Net Weight Tower model 87 113 8K Kgs without jannot 86 112 92 118 8KP isolation Aon 96 122 10K i 101 127 10KP
3. To re confirm the change of UPS Setting Go to next page UPs OFF Switch Special functions log in out D UPS is working under ECO Economic mode UPS Fault or Abnormal 10 2 3 2 Rear Panel Explanation Tower Model 6000C Model NE D CBA D CBA 16 Also available for Rack E NTT Normal Trip a SSM LUAU rT w JZ RT10KIG I JP my r mM s Bacio aok a m vy OZZ AC7 TOMmMIODS e DIM RS232 Port Terminal Resistor for Parallel function CAN Bus Connection Port for Parallel System Customer Options Slot 1 Customer Options Slot 2 Cooling Fan External Battery Connector External Charger Connector Utility Input Breaker CB1 Bypass Input Breaker CB2 for Dual Input Model Only CAM Switch Maintenance Bypass Switch Input Output Terminal Block Fixing Holes for External Charger Cabinet EPO Emergency Power Off Short to enable the function Thermal breaker for the protection of Load in abnormal condition CB3 Air Ventilation Hole Dual Input Model SIM Single Input Model 12 2 4 Communication Port Explanation The Communication port on the UPS provides true RS232 type to communicate with UPS software to remote monitoring the power and UPS status With optional interfaces cards which contains R2E 2 RS232 RSE RS485 USE USB DCE Dry Contact as well as SNMP card you may combine them according to your demand However the R2E card RSE card and USE card are prohibited t
4. i 24 kg 45Kg Tower amp RT model without Isolated lt 600W 10K Transformer ADOI lt 550W 10KP Heat at full Linear ee Load Dissipation Tower model with Isolated Transformer lt 615W lt 1100W 10K at Full Linear lt 1050W 10KP Load Leakage Current lt 3mA at Full Load Marks CE cUL UL Type Sealed Lead Acid Sealed Lead Acid 160 176Vac for 1 phase input model or 277 305Vac for 3 phase input model Maintenance Free Maintenance Free at lt 75 load aa Aa pa 3 phase input model lt 30 ees Isolation transformer net 53kgs for 6000VA 10000VA Quantit Voltage Recharge Time DISPLAY Status On LED LCD Line Mode Backup Mode ECO Mode Bypass Supply Battery Low Battery Bad Disconnect Overload Transferring with interruption amp UPS Fault Readings on LCD Input Voltage Input Frequency Output Voltage Output Frequency Load Percentage Crest Factor J o o oo o Efficiency AC to AC Normal Up to 91 _ 41 42 a 192321132000008
5. Parallel Redundancy On Line UPS User s Manual 6 10KVA aa 1 1 L2 R 22 235 2 4 asl 32 Ser 3 4 3 5 4 1 5 1 Ja 6 1 6 2 6 3 6 4 6 5 6 6 Table of Contents Tportant Sarety MSAC Oian a A 2 AM INPOoran NOC resres r a EEEE 2 Stora se MS CU ON sein a E E 4 Produc EOC CHO Mi san a a A E 5 Generali Character UOS ror i a E EEE 5 Symbolson the LED Display Paneth sernir n E N 7 Papet explain on e a e ES 10 Communication Port Explanation ccccccecccceeccceecceeeeeeeeeseeeeeeeeeeeeeeeeeaaas 13 Installaqon and Operalon saien a a a 14 NACI Nd afenn e E E E a 14 Selecting Installation Posio Messiaen aa E EE E E E 15 Hsellatonror Accesores K Ib A 15 Terminal Block Explanation cccccccccccccceeccceecceeaeeeeseeseeeeceeeeeeeseeeeaaaaags 16 Operation Test and Installation Instruction eeeeeeesessseseeeeereeeerrsssssssssssese 19 Trou BleshOOtng Guldens sanai n E TE E EEO EEA 31 Trouble SOOT G 2a a a a N 31 Bundled Software Installation Guide ccccccssssseseeesseeeeeeeeeeeeeeeeeeenaaas 33 Hardware Tras Cea ACO aa ae vik eens be ecto Paw cette seed oe tee ele Deut EE ENERO eee 33 SOR Ware Install OMen E EEE 33 Customer OPUONS SIOS a N 34 R ECRARS 22 Can ea a E noua ee eae 34 RSE RS 403 hea E E E AOT 34 USES BIC aen a Seceewteaaaackivas eclemoandaceea tees 34 DCE Dry Contact B card en neeseeesssssssseeeeeeresesssssssssssrertereersssssssssssseeeereeeo 35 SNM
6. in self test LOAD LOAD T D E2 LINE UPS ee TL It shows Fail in self test 20 3 5 2 It shows 220Vac in Utility Input 3 5 1 8 In case of failure in self test the LCD display will illustrate from Drawing D to drawing E2 then an error code or error status will be shown on the screen 3 5 1 9 Your start up operation of the UPS is completely now Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteries of the UPS are fully charged Start up in Battery Mode Cold Start 3 5 2 1 Make sure the UPS you have has already been installed at least 1 set 20pcs of 12V 7AH batteries 3 5 2 2 Push the UPS On Switch once for approx 5 seconds to awake the UPS and then the buzzer sounds twice The LCD display will illustrate from drawing A to drawing G and keep awake for approx 15 seconds 3 5 2 3 Press the UPS On Switch of the UPS again for about 3 seconds till the LCD display illustrates from drawing G to drawing H then the UPS will be in self test Mode The UPS may offer energy to the output in a minute and the LCD display illustrates as drawing I In case of failure in pushing the UPS On Switch within 15 seconds the UPS will automatically turn off You then have to go through step 3 5 2 1 to 3 5 2 3 once again 3 5 2 4 G LINE UPS LOAD It shows Off which means the UPS pre start is successful 21 H LINE UP
7. Chapter 6 for installation 5 2 Software Installation Please refer to the user s manual of the software for installation 33 6 Customer Options Slots 6 1 R2E 2nd RS 232 card 1 gt VCC 5V 6 1 1 CN1 is for RS232 DB9 2 gt D 6 1 2 For communication protocol please refer 3 gt D to Chapter 2 4 1 4 gt Ground 6 1 3 Installation Position slot1 CHA CN4 or slot 2 CHB CN5 6 3 3 Installation Position slot CHA CN3 or slot 2 CHB CN4 6 2 RSE RS 485 card 6 4 DCE Dry Contact B card 6 2 1 CN1 is for the function of the terminal resistor Short pin1 2 to enable the function and short pin2 3 to disable it 6 4 1 The pin assignments of 10 Pin Terminal 6 2 2 CN2 for RS485 and CN3 for remote power i PAS penon e al CN2 WEN Pin 1 UPS on Bypass mode 17213 1 gt Ground Pin 2 Utility Abnormal PPE 2 gt A Data Pin 3 Utility Normal 3 gt B Data Pin 4 Inverter On Pin 5 Battery Low Pin 6 Battery Bad or Abnormal CN3 Pin 7 UPS Alarm Pin 8 Common Pin 9 Shutdown UPS positive signal Pin 10 Shutdown UPS positive signal 1 12 1 gt AC Lin 2 gt AC 6 2 4 Installation Position slot 6 4 2 The shutdown function will be activated after a 6 25Vdc is put between pin9 and pin10 for 5 seconds 6 4 3 The capacity of each relay contact is 40Vdc 25mA 6 4 4 Installation Position slot1 CHA CN7 or slot 2 CHB CN8 6 4 5 Flexible signal output for N C Normal close
8. find ID1 UPS in parallel system al ae CVCF mode with Bypass input 37 Er27 The UPS must be operated in normal mode in parallel system SC stem eat omen Gi The specified modes include Normal mode ECO mode CVCF mode etc gt ester ee emer a Ce B Bypass Overload Time out and cut off output The settings of both control board and driver board are not matched each other at se Isolated transformer overheat Er Other Error code Battery Weak or Dead Output Short Circuit Inverter Over current UPS Overheat Asl w Wrong Procedure to enter Maintenance Mode Output Parameters Set Error in Parallel System ID Numbers are in conflict in Parallel System Er17 SAE or ID number Error in single unit 8 2 3 Panel explanation 2 3 1 Front Panel Function Explanations 1 2345 6 7 LcD Display Green LED lights up to indicate the UPS has the capability to run under redundancy mode Green LED steadily lights up to indicate that the Utility input voltage is within the window the LED flashes flickeringly to indicate that the Utility input voltage is within the acceptable window D Green LED lights up to indicate Bypass Input is normal UPS ON Alarm Silence Go to previous page or change the setting of the UPS
9. of applications DC start function makes sure of the start up of UPS during power outages 5 2 1 12 2 1 13 2 1 14 2 1 15 2 1 16 Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut off point and extend the life of batteries Intelligent temperature controlled fan may not only extend the life of the fan but also reduce annoying noise because of sudden fan spin It remains your office quiet and comfortable as usual When UPS is out of order you may read out the possible fault reason from the LCD screen directly which may reduce down unnecessary repair task a lot In case the UPS is out of order Fault status will be shown on the LCD screen When the UPS is operated under CF50 or CF60 mode the recommended load connected shall be 75 of rated capacity if the input voltage is 176 280Vac and 50 of the rated capacity if the input voltage is 160 280Vac 2 2 Symbols on the LCD Display Panel Utility or Bypass Source UPS Working in specified mode A Blackout Transfer occurred in UPS Output Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at ECO mode ie Utility Input Abnormal LINE UPS Abnormal Lock arene 4 Digits Measurement Display a Indicate the item desired to be measured UPS ON Switch or Alarm Silence Previous Page or Setting Change an ND Parallel communication error communication wire disconnected or failure to
10. or N O Normal open contact by shorting pin1 2 or pin2 3 from JP 1 5 6 4 6 The shutdown function will be enabled in 1 minute after blackout occurs if the pin1 2 of both CN1 and CN6 be shorted by cap Or the shutdown function can only be enabled by pin9 10 of CN3 if the pin2 3 of both CNiand CN6 be shorted by cap Refer to 6 4 2 6 3 USE USB card 6 3 1 CN1 for USB 6 3 2 Definition 6 3 2 1 Comply with USB version 1 0 1 5Mbps 6 3 2 2 Comply with USB HID Version 1 0 6 3 2 3 The Pin Assignments of the USE card 34 35 6 5 SNMP Cards 6 6 The Installation of those Interface Cards 6 5 1 SNMP WEB card 6 5 1 1 For installation please refer to the user s manual attached with the card 6 5 1 2 Installation 6 5 1 3 Position slot 2 CHB 6 5 2 Net Agent Il Internal Card 6 5 2 1 For installation please refer to the eu user s manual attached with the card 6 5 2 2 Installation 6 5 2 3 Position slot 2 CHB coo cocce s KJ H vs eee 36 37 7 Replacing Battery Qualified personnel allowed only 6 Turn the battery pack handle at 90 degree as shown in Step 6 1 Unscrew the bottom of the front panel as indicated in Step 1 as below 7 Remove the battery packs from the UPS as shown in Step 7 2 Remove the front panel as indicated in Step 2
11. other equipment related to human safety c Public system or critical computer systems Do not install the UPS in an environment with sparks smoke or gas Make sure the UPS is completely turned off when moving the UPS from one place to another It might cause electrical shock if the output is not cut completely The Maintenance Bypass Switch is equipped with the UPS Please follow the procedures strictly to switch on off the Maintenance Bypass Switch The UPS offers CVCF Constant Voltage Constant Frequency setting function a For correct setting and wiring please contact with your local agent b Do not do it by yourself otherwise your warranty will be void This UPS has been designed and constructed to protect your assets from the wide range of power aberrations experienced on Utility power lines today It is your insurance for reliable clean and stable voltage supply It is worth taking care to install the system correctly and to have it maintained correctly by your local dealer 1 1 25 SAVE THESE INSTRUCTIONS This Manual Contains Important Instructions that should be Followed during Installation and Maintenance of the UPS and Batteries 1 1 26 Intended for Installation in a Controlled Environment 1 1 27 Disconnection Device CAUTION A disconnect switch shall be provided by others for ac output circuit To reduce the risk of fire connect only to a circuit provided with branch circuit over current protection for 30
12. P OG He fc a A A A ECE Ty Te 36 The Installation of those Interface Cards 200 0 cccccsssssesesseeeeeceeeeeeeeeeeeeneaas 37 Hot Swappable Battery Replacement cccccccccsssensssssesseseeeeeeeeseeeeeneaas 38 DPC CILIC ALONG i tnd ioaridiadi nde eaacndeat a a borate A 40 1 Important Safety Instruction 1 1 sa ee 1 1 2 1 1 10 1 1 12 ga ea eS An Important Notice For Parallel System installation please refer to MSII 6KVA Parallel system Installation Guide Because of LITTLE LEAKAGE CURRENTS generated by the EMI filter of the UPS it is necessary to double ensure if the earth of the UPS is properly grounded before AC Mains is connected with To ensure safety in all applications where a UPS is hard wired to the Electrical Supply ensure that the system is installed by a Qualified Electrical Contractor The UPS has its own internal energy source battery Should the battery be switched on when no AC power is available there could be voltage at the output terminals Make sure that the AC Utility outlet is correctly grounded Do not open the case as there are no serviceable parts inside Your Warranty will be void Do not try to repair the unit yourself contact your local supplier or your warranty will be void Please make sure that the input voltage of the UPS matches the supply voltage Use a certified input power cable with the correct plugs and sockets for the appropriate voltage syst
13. S LOAD A E It shows Utility input is 0 and Utility Abnormal I LINE UPS LOAD A 3 5 3 Check Measured Values amp Figures detected by UPS 3 5 3 1 If you would like to check the measured values amp figures detected by the UPS please use scroll up G and scroll down key pads When you use scroll down key pad the LCD display will illustrate as Drawing C Voltage from Utility Input gt Drawing 11 Voltage from Bypass Input gt Drawing J Frequency from Utility Input gt Drawing K Frequency from Bypass Input gt Drawing L UPS Output Voltage gt Drawing M UPS Output Frequency gt Drawing N UPS Output Load Drawing O UPS Battery Voltage gt Drawing P UPS Inner Temperature LINE UPS LOAD J rT OCELI It shows voltage comes from Bypass Input 22 LINE UPS LOAD A It shows UPS output Voltage LINE UPS LOAD A It shows UPS output frequency LINE UPS LOAD A It shows UPS output load level 23 LINE UPS LOAD qi It shows Battery Voltage P LINE UPS LOAD CI It shows UPS Inner Temperature 3 5 4 UPS Default Data and Special Function Execution 3 5 4 1 After UPS completely starts up press key pad to change the LCD display screen to drawing Q1 Q1 It shows buzzer On Q2 It shows buzzer Off 3 5 4 2 Press O key pad to scroll down th
14. amperes for 6Kva and 40 amperes for 8Kva 10Kva See below details rating in accordance with the National Electric Code ANSI NFPA 70 Output No Over current protection No 1 L21 N21 SKVA120V 5 No 2 L22 N22 SKVA 120V 45 Oo D O 45 No 3 L23 TA 10 KVA 208 V 50 No 4 OTN 10 KVA 240 V 1 1 28 CAUTION To reduce the risk of fire unit input connect only to a circuit provided with branch circuit over current protection for 40 amperes for 6Kva and 50 amperes for 8Kva and 65 amperes for 10Kva amperes rating in accordance with the National Electric Code ANSI NFPA 70 1 1 29 The Units are to be installed so that is not likely to be contacted by people 1 1 30 Maximum ambient operating temperature 40 C or equivalent 1 2 Storage Instruction For extended storage through moderate climate the batteries should be charged for 12 hours every 3 months by plugging the UPS power cord into the wall receptacle and turn on input breaker on front panel Repeat this procedure every 2 months under high temperature environment 2 Product Introduction Zoi 2 1 1 2 1 2 2 1 10 2 1 11 General Characteristics True online architecture continuously supplies in your critical device with a stable regulated transient free pure sine wave AC Power 20KHz PWM sine wave topology yields an excellent overall performance The high crest factor of the inverter handles all high inrush current loads without a need to upgrade the po
15. at 3 5 1 4 you may put the UPS back to normal working mode then turn back the CAM switch to INV mode fasten back the cover and repeat 3 5 1 5 to 3 5 1 8 The UPS will switch back to inverter mode It is required to go through 3 5 8 1 1 first then go through 3 5 8 1 2 If you skip 3 5 8 1 1 the UPS will alert for 10 seconds to warn that the procedure is abnormal which may damage the UPS due to uncertain utility status The UPS will switch back to Inverter mode immediately if you turn the CAM switch back to INV 30 4 Troubleshooting Guide 4 1 Trouble Shooting When the UPS malfunctions during operation you may check the followings a Are the wirings of input and output correct b If the input voltage of the Utility is within the input window of the UPS In case problems or symptoms still exist please proceed the followings for proper adjustment Should the problem persists please contact your local distributor for help 31 Check Items UPS Red Fault Check the error code LED lights up shown on the LCD screen 1 Er05 twa GS 2 Er06 Er10 Er12 Er28 amp 10 other error code UPS fails to offer battery backup or its back up time is Shorter than its calculation UPS locks itself and it can not be turned off 1 Check to see if the battery connection is properly done then re charge the batteries for 8 hours to see whether the UPS may backup normally otherwise consult your local distributor ri
16. ded 3 5 6 3 2 Check to see Chapter 2 2 to trouble shoot the problem of the UPS Otherwise consult your local distributor for service 3 5 6 3 3 Press Off key pad for 5 seconds and buzzer will sound twice 3 5 6 3 4 Turn Off the Breaker of Utility Input 3 5 6 3 5 The UPS lock problem is solved now but you shall contact with your Local distributor to make sure the error message shown is solved 3 5 7 Shut Off 3 5 7 1 Press Off key pad for about 5 seconds the Inverter output will be turned off then the output load is supplied by Bypass loop and the LCD screen shows as drawing B 3 5 7 2 Turn Off the breakers of Utility and Bypass Input 3 5 7 3 The UPS is turned off completely 3 5 8 Maintenance Bypass Mode 29 3 5 8 1 It is for UPS maintenance only A Non authorized technician is not 3 5 8 1 1 3 5 8 1 2 3 5 8 1 3 3 5 8 1 4 3 5 8 1 5 allowed to operate the following procedures If there is any damage under unauthorized condition your warranty will be void immediately Press the Off key pad for approx 5 seconds the LCD screen shows as drawing B and the UPS output is on bypass mode Release the cover of the CAM Switch Maintenance Bypass Switch first then turn on the CAM Switch to Bypass mode and at the right hand upper Corner of the LCD screen will show sign Turn off the UPS Utility breaker as well as Bypass Input Breaker you then may proceed UPS maintenance now To repe
17. e screen and check the UPS settings The LCD display will show in consequence between Drawing Q1 buzzer gt Drawing R1 Self test gt Drawing S1 Bypass Voltage Windows gt Drawing T Output Frequency Synchronization Window gt Drawing U Inverter Output Voltage gt Drawing V1 UPS Operation Mode gt Drawing W Output Voltage Micro Tune Value gt Drawing X UPS Id gt Drawing Y Parallel function status i Enon It shows self test is NOT on i Erun It shows self test is On i Sto It shows Bypass Voltage is adjusted to narrow one S2 It shows bypass voltage is adjusted to wider one 25 O F l T It shows the UPS is operated in CVCF 60Hz mode It shows Frequency Window is 3Hz 0 o o 00 320 It shows inverter output voltage It shows Output Voltage Adjustment from 0 to 3 or 0 to 3 f el O idi It shows the UPS is operated in normal mode It shows UPS Identification Number O Eco It shows the UPS is operated in Eco mode It shows the UPS is in the No 1 of parallel systems 3 5 4 3 Press scroll up key pad you may execute special functions The Functions includes buzzer ON as drawing Q1 or buzzer OFF as drawing Q2 Alarm silence for UPS Warning and self test OFF As drawing R1 or self test ON as drawing R2 UPS will execute battery test for 10 seconds If the self test is successful it will show as Drawing E1 otherwise it
18. em To eliminate any overheating of the UPS keep all ventilation openings free from obstruction and do not store things on top of the UPS Keep the UPS 30 cm away from the wall Make sure the UPS is installed within the proper environment as specified 0 40 C and 0 90 non condensing humidity Do not install the UPS in direct sunlight Your warranty may be void if the batteries fail Install the UPS indoors as it is not designed for installation outdoors 2 1 14 1 15 1 16 1 17 1 18 19 1 20 1 21 1 22 1 23 1 24 Dusty corrosive and salty environments can do damage to any UPS Install the UPS away from objects that give off excessive heat and areas that are excessively wet If liquids are split onto the UPS or foreign objects dropped into the unit the warranty will be null and void The battery will discharge naturally if the system is unused for any length of time It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void When installed and being used the batteries will be automatically recharged and kept in top condition This UPS supports electronic equipment in offices telecommunications process control medical and security applications Non authorized technician is not allowed to install the UPS in the following areas a Medical equipment directly related to human life b Elevator Metro Subway system or any
19. ght away If the CB3 is tripped please turn off the UPS completely and keep the CAM switch at position INV before pressing CB3 Then remove some uncritical load at the UPS output end If any damage of the coating of AC power cord please replace a new one 3 Remove the short circuit occurred at the EPO terminal 4 Remove the objects blocked onto the ventilation holes 5 Check the cooling fans on rear panel are working normally 6 Make sure the UPS is operated normally If it is on CVCF mode you have to turn off and turn on the UPS again 7 All of parameters except ID Number in the parallel UPS must be same Please refer chapter 3 5 5 to set them again 8 Reconnect the RJ 45 wire or set a UPS with ID 1 9 When the UPS is on CVCF mode it is prohibited to have bypass input You have to turn off the UPS and bypass input and re start the UPS 10 Consult your local distributor for help If the backup time is still too short after 8 hours of charge please contact your local distributor for battery replacement Please refer to chapter 3 5 6 to trouble shoot the problem otherwise consult your local distributor for help 32 5 Bundled Software Installation Guide 5 1 Hardware Installation 1 Connect the male connector of RS232 cable to the UPS communication port 2 Connect the female connector of the RS232 cable to a dedicated RS232 port of the computer 3 For optional interface cards you may refer to
20. he UPS with Isolation transformer amp dual input gt Ditto but with additional 3pcs wire No 7 3 1 5 Package for the UPS without isolation transformer but dual input gt Ditto but with additional 1pcs wire No 7 p s Wire No 7 is to be used at the input output terminal block of the UPS Please refer to Chapter 3 4 for installation ee ee Tower model 4 x2 A2 o gt o X2 X1 X4 gt X5 RT model RT10K only 3 2 Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the UPS and extend the life of the UPS Please follow the advice below 1 Keep at least 30cm 12 inches clearance from the rear panel of the UPS to the wall 2 Do not block the air flow to the ventilation openings of the unit 3 Please check the installation site to avoid overheat and excessive moisture 4 Do not place the UPS in an environment near dust corruptive or salty material or flammable objects 5 Do not expose the UPS to outdoors 3 3 Installation of Accessories Kit Relative humidly non condensation 30 90 p a T WW el co MOM coro OO suo M ji iil f eo f
21. l mode The settable numbers are from 1st to 4th The number must be 1st if the UPS is not in parallel 3 5 5 10 Drawing Y means the parallel function status The P 01 means parallel function disabled and the P 02 means parallel function enabled 3 5 5 11 When all the setting changes are done you have to press enter key Pad to save all the changes when the LCD screen shows as drawing Z then the LCD screen will show as drawing AA to complete the setting changes If you don t want to change those settings you may press OFF key pads for 5 seconds then the LCD screen turns to Drawing AA directly which means your setting changes are invalid Please press Enter key to save data 28 AA It SNOWS the UFS IS loCKed 3 5 5 12 Turn Off the breaker of Utility Input 3 5 5 13 Your Setting changes are complete 3 5 6 UPS Is Off Due to Unknown Reason and Its Trouble Shooting 3 5 6 1 If there is a serious abnormal condition occurred the UPS will lock it itself in OFF position as shown in drawing AA and a abnormal message will show on the LCD screen 3 5 6 2 After 3 seconds all messages will be locked except Bypass messages LEDPeJ 2 amp LCD gt Incase the Utility is abnormal after the UPS is locked the LED 2will be extinguished and the LCD__ will be shown on the LCD screen 3 5 6 3 To release the UPS lock please proceed the followings 3 5 6 3 1 Check those error messages recor
22. lity breaker and Bypass breaker are On Off position 3 5 1 3 Make sure the voltage of Utility matches with the input voltage window of the UPS 3 5 1 4 Connect the Utility separately to the terminal blocks of UPS Utility and Bypass Inputs Switch on the Power Breaker of the distribution panel and the breakers of the UPS Utility and Bypass Inputs and then the UPS starts up Green LEDs pai amp ev light up to show the Utility and Bypass Inputs are normal and the LCD display with parallel function will illustrate from drawing A1 drawing A2 to drawing B Otherwise the LCD display will illustrate from drawing A2 to drawing B Al LINE UPS LOAD A gt Com A2 B D q gt LINE UPS LOAD J nn Ls 19 3 5 1 5 Then the UPS is on Bypass Mode now and it will proceed self test automatically If there is no abnormal message occurred it means the pre startup of the UPS is successful and the charger starts to charge the batteries 3 5 1 6 Press the UPS On Switch for approx 3 seconds then the Buzzer sounds twice and the LCD display changes from drawing B to drawing C ye Ty i C LINE UPS LOAD A re lt E ri t 3 5 1 7 Then the UPS is under self test mode again the LCD display will illustrate from drawing C to drawing D and remain approx 4 seconds under battery mode then illustrate from drawing E1 to drawing F if the self test is successful E1 LINE UPS It shows OK
23. o be used Simultaneously The bundled software of the UPS is compatible with many operating systems such as Windows 98 amp 2000 ME NT and XP For other applications like Novell NetWare Unix Linux please contact your local distributor for a proper solution When the optional interface cards are used together with onboard RS232 port in communication the EPO signals will get the highest priority in control command then the SNMP WEB card then the shutdown command at the DCE card amp also R2E RSE and USE then onboard RS232 port get the lowest priority 2 4 1 True RS232 type 2 4 1 1 The RS232 interface settings The RS232 interface shall be set as follows Baud Rate 2400 bps Data Length 8bits _ _ StopBit it bit Parity Nome _ _ _ 2 4 1 2 The Pin Assignments of true RS232 type The Pin Assignments of true RS232 type are illustrated as follows Pin 3 RS232 Rx Pin 2 RS232 Tx Pin 5 Ground 13 3 Installation and Operation The packing condition and the external outlook of the unit should be inspected carefully before installation Retain the packing material for future use 3 1 Unpacking 3 1 1 Take the UPS out of the PE foam 3 1 2 Unwrap the UPS 3 1 3 Standard Package includes gt 1 set of Quick Start Manual gt 1 set of User s Manual gt 1set of UPS communication software with RS232 cable gt 1 set of Metal Accessories Kit for Tower model or RT model as below 3 1 4 Package for t
24. shorted for 1 phase input model and short B and R for 3 phase input model 3 If the UPS is SIM Single Input type only AC source can be supplied to UPS from L12 N1 terminal for 1 phase input model and R S T N1 terminal for 3 phase input model 4 When the Isolation transformer is NOT installed into the tower type UPS the UPS output terminals will be L22 N22 5 When the Isolation transformer is installed into the tower type UPS a For 100 110 115 120Vac system you may connect as shown in below L22 N21 123 110Vac T 6KVA Max b For 200 100Vac 220 110Vac 230V 115Vac or 240 120Vac or 240 208 120Vac system You may connect as shown in below 208Vac 6KVA Max y eee 120Vac 120Vac 3KVA Max 3KVA Max 240Vac 6KVA Max 17 e Use Mounting Cable Tie to fix cables Tower model 6 Please refer to the specs of input current output current and recommended conductors listed as below 6000C model 6KRT model a AC input and output 75 C minimum copper wire 6KVA wess J toKva sesa awG 6 23ibin b Battery input aw a O me 10KVA AWG 10 AWG 10 18 3 5 Operation Test and Installation Instruction 3 5 1 Start Up in Normal Mode 3 5 1 1 Open the terminal block cover on the rear panel refer to 2 3 2 Before start the installation please make sure the grounding is connected properly 3 5 1 2 Make sure Utility breaker UPS Uti
25. wer rating Multi functional LCD LED panel may display various status of the UPS The LED display may show UPS working status Utility Status and UPS Abnormal status in the mean while the LCD display may show Input Output Voltage Frequency Load Status Inner cabinet temperature and Abnormal Phenomenon To protect the unit from overloading it automatically switches to bypass mode in 160 seconds 40ms if loading is at 105 150 of rating and in case of overloading at 150 of rating it switches to bypass mode immediately It will automatically switch back to inverter mode once overload condition ceases Should the output becomes short circuit the UPS holds the system and cuts the output automatically till the short circuit situation is removed manually Should the unit become overheated the internal thermal Switch will detect the heat and switch to bypass mode and vice versa Fully digitalized control circuit built in the UPS may upgrade the functionality Of the UPS as well as reach a high level protection of the UPS Through powerful Communication capability built it enhances its ability for remote control and monitoring easily Maintenance free sealed type battery minimizes after sales service Maintenance bypass switch it provides an easy and safe troubleshooting or maintenance function when the Utility is normal Providing four different working modes such as Normal ECO CF50 and CF60 it may widely be used in a variety
26. will show as drawing E2 amp error message in the same time V3 It shows the UPS is operated in CVCF 50Hz mode 26 Zi 3 5 5 3 5 4 4 UPS Default Settings and their alternatives 3 5 5 1 IOTZ 3 5 5 3 3 5 5 4 3 5 5 5 3 5 5 6 3 5 5 7 3 5 5 8 3 5 5 9 Make sure the UPS is not On yet Press On Switch and scroll down O key pads simultaneously for approx 3 seconds the buzzer will sound twice the LCD display screen shows as drawing Q1 then the UPS is under setting mode now To scroll down the LCD screen you may refer to Chapter 3 5 4 2 Except Buzzer as drawing Q1 amp Q2 and Self test as drawings R1 amp R2 all the rest default settings may be changed by pressing scroll up key pad Drawings S1 and S2 mean the bypass input acceptable window itcan be 184Vac 260Vac or 195Vac 260Vac Drawing T means the bypass frequency window of the Inverter Output the acceptable setting values are 3Hz and 1Hz Drawing U means the acceptable Inverter Output Voltage of which voltage is 200Vac 208Vac 220Vac 230Vac or 240Vac Drawing V1 V2 V3 and V4 mean the operation modes of the UPS of which alternative is Online Eco Economic mode fixed 50Hz Output or fixed 60Hz Output Drawing W means the adjustments of the Inverter Output which may be calibrated as 0 1 1 2 2 3 or 3 Drawing X means a specified address amp position of the UPS when the UPS is in Paralle

Download Pdf Manuals

image

Related Search

Related Contents

石産協通信vol35  BON DE COMMANDE SPICE Intra-auriculaires Sur-Mesure  LIVRET D`ACCUEIL - Le syndicat SUD a Steria  Koolbreeze - Electrocomponents  CONCORRÊNCIA PÚBLICA 019/2010  La ULTM, comunica a todos los países miembros de la  User's Guide  (AUS/NZ) Installation and Operating Instructions Ritz  JVC LCT2104-001A-A User's Manual    