Home
E-tube System Manual - Telford Copper Cylinders
Contents
1. Temperature sensor The collector has a built in sensor sleeve If there are two or more collectors mounted in series the sensor is to be inserted into the collector sleeve nearest the return flow back to the hot water store Optimal contact can be achieved between the manifold and sensor by way of smearing the sensor with heat paste prior to insertion An optional lightening protection device can be istalled to protect the sensor from over voltage Maintenance The collector and arrays must be checked periodi cally An annual close up inspection must be per formed to check for damage leaks contamination and tube failures a less solar isolation in you b solar collector is shaded from sunlight Low working performance from heat pipe solar collector e Incorrect instal lation angle Calculate correct collector size amp ad just accordingly or install additional heat source i e Gas boiler Where possible re move source of shade or relocate collector c Failed vacuum tube ba failed vac uum tube with d Poorly installed heat pipe Refit the heat pipe Apply heat paste to condenser surface Reposition collector to an angle 51 10 UK only Free standing planning prior to deciding Wind load on roofs can create suction forces on the solar collectors In order to minimize suction forces the mounting frame must be installed as follows The subsurface must be sufficiently sustainable and
2. The collector field can be mounted at different angles according to individual applications For example larger systems used for heating support require a 60 degree angle in winter time to maximise solar gain this reduces the system efficiency in sum mer when the system is not required for heating Systems that require all year coverage such as hot water require 45 degree angle to maximise summer winter gain Systems that are predominantly used in summer are most efficient at 30 degree angle Install the profile rails in the in the pre drilled holes in the hypotenuse of the bracket insert the clamp and hanger brackets on the lower and upper profile rails mount the collector on the hanger brackets and clamp down each collector one at a time connecting the compression fittings to each collector as you install the next collector O mint renewables System Installation Schematics Steca Wiring Connections Pump connections Live Neutral Earth T1 T2 Position of the terminals Power connections Live Neutral Earth Refer to controller user manual for time date and system configuration set up g mint renewables Unvented thon with dur fine ff foo A E Fah Aral soler pump iaaa f ir EA Premurued orliafert hen cod 1 I T rt COM PRESSURED CYLIHDER Unvented Frk d r iver s re T n E AibA ci a Al f r HOT YWER I e More
3. secondary fittings Above ground 26 Proposed number of Asis One collectors 33 Isa pool cover used when pool is not in use Yes No Proposed Portrait vertical Gas 27 mounting configuration Fully filled pressurised LPG Proposed solar Type of fuel used Landscape horizontal F Oil L JU OU Uo oo 28 34 circuit type De to heat the pool Electricity 29 Approximate distance between proposed solid fuel solar collector location and solar cylinder S eesssssessereres m None Please note recommendations for solar complications or special features 35 not been described in 14 to 20 please pro vide dimensions and notes on structure System commissioning checklist Customer details Name Address Telephone number Mobile number E mail address Installer details Company name Address Telephone number Mobile number E mail address Web site MCS number System summary Number of Asis One 1A collectors Type and volume of cylinder Type of pump station and controller Type of solar circuit fitted Commissioning date Solar collector serial numbers Solar collector mounting brackets and clips inspected and secure Solar collector connections inspected and properly fitted and tightened Type of weatherproofing of roof penetrations for in let and outlet pipe work and sensor cable Penetration weatherproofing inspected and properly fitted Collector sensor probe securely f
4. appropriate for the weights to be installed Upon it is therefore important to verify in advance that the roof structure is suitable to withstand the distributed load If the mounting frame will not be connected with the subsurface structure roof sub construction a loading of at least 200 kg per collector is required see fig 1 Additionally the mounting frame can be connected with wire ropes at fixed hold points Support elements and fasteners must be provided by the installer Moreover in order to avoid wind noise to a large extent the mounting frame must be installed at least 1 m from the roof edge In areas with high wind speed or high construction heights the loading must be calculated by a structural engineer Please refer to lightning protection and bonding to the structure Installation of the mounting frame on large open surfaces of galvanised or trapezoidal sheet roofs This types of installation should be specified only by a qualified structural engineer in accordance with current building regulations for such roofs The frame can be bolted through these roof structures using oversized washers and rubber grommets to seal the roof howeverthe sheets mustbe loaded with pebbles or substrate to equivalent weight i mint renewables C f High heatloss due to poorly insulated pipe lines Insulate all pipes with high tempera Free standing planning prior Wind load on roofs can create suction forces
5. br camari coe biler bo f r bier aia F p ler aie Unvented m Wri Anm ees fe E Seca pm A s C General mint renewables g Installing the temperature sensor The solar collector temperature sensor should be installed in the sensor sleeve nearest to the collector array flow To ensure optimal contact between the temperature sensor and the surrounding environment the gap between the sensor sleeve and the sensor element should be filled with a suitable conducting compound All materials used for installing temperature sensors sensor element conducting compound cables sealing and insulating materials must be suitably temperature resistant up to 250 C Operating pressure The maximum operating pressure is 10 bar Removal of air from the system bleeding The system should be properly bled at commissioning to remove as much air as possible from the system We would recom mend that after 2 to 4 weeks of operation the system is bled again Warning When bleeding the system there is a risk of scalding due to steam and hot transfer fluid and appropriate care must be taken Only operate the bleeding valve if the temperature of the heat transfer fluid is below 60 c When bleeding the system the collectors must not be hot Cover the collectors and if possible bleed the system in the morning Checking heat transfer fluid The heat transfer fluid must be checked at least every four years with regard to its antifreeze
6. always apply counter pressure with a wrench or another spanner to prevent damage to the manifold connections Collector inclination General notes The collector is suitable for installation at an angle of between 15 75 Steps must be taken to ensure that water and other contaminants such as dust etc are prevented from getting into the collector connections and ventilation holes Warranty Warranty claims can only be made if an appropriate specification of antifreeze is used and maintenance is carried out correctly Ladder and scaffolding assembly B tei a ae Safety Precautions Before commencing mounting work on roofs it must be ensured in all cases that the non personal fall protection and fall arrest systems required by DIN 18338 Roof Covering and Roof Sealing Works and DIN 18451 Scaffolding Works are in place See also Builders Protection Ordinance A If non personal fall protection or fall arrest systems cannot be installed for technical reasons all personnel must be secured by means of suitable safety harnesses Only use safety harnesses safety belts lanyards and straps shock absorbers fall arresters that were tested and certified by authorized testing bodies If non personal fall protection or fall arrest systems are not provided working without the use of suitable safety harnesses may lead to falls from heights and therefore cause serious or lethal injuries La
7. ground or hooking devices Only lean ladders against secure points Secure ladders in traffic areas by suitable Cordoning Contact with live electric overhead cables can be lethal Wear protective goggles when drilling and handling solar collectors evacuated tube collectors have a danger if damaged of implosion Wear safety shoes when carrying out installa tion Work Ae TA SG is Wear cut proof safety gloves when mounting collectors and handling evacuated tube collectors ae i i danger of implosion MOE 1 aia 4 Wear a helmet mint renewables e A Check the proposed collector siting is suitable The collector is suitable for flat roof tiled roof cement and concrete roof structures The installation should be carried out by able and qualified persons only Its is the responsibility of the end user to adhere to local planning and conservation regulations Prior to installation The collectors must be fixed only to a load bearing roof structure and substructures A structural survey may be required to calculate the permitted load Do not mount the collector if you are unsure the structure will carry the load The location of the collector should be positioned at least 1 meter from any edge or ridge A pre assessment of the location should take into account any additional factors that could lead to additional loads ie wind air jets and snow The collector arrays m
8. on the solar collectors In order to minimize suction forces the mounting frame must be installed as follows The subsurface must be sufficiently sustainable and appropriate for the weights to be installed Upon it is therefore important to verify in advance that the roof structure is suitable to withstand the distributed load If the mounting frame will not be connected with the subsurface structure roof sub construction a loading of at least 200 kg per collector is required see fig 1 Additionally the mounting frame can be connected with wire ropes at fixed hold points Support elements and fasteners must be provided by the installer Moreover in order to avoid wind noise to a large extent the mounting frame must be installed at least 1 m from the roof edge In areas with high wind speed or high construction heights the loading must be calculated by a structural engineer Please refer to lightning protection and bonding to the structure Installation of the mounting frame on large open surfaces of galvanised or trapezoidal sheet roofs This types of installation should be specified only by a qualified structural engineer in accordance with current building regulations for such roofs The frame can be bolted through these roof structures using oversized washers and rubber grommets to seal the roof however the sheets must be loaded with pebbles or substrate to equivalent weight as in figure 1 to deciding Mounting
9. I mint Seu YH FEET E DI Jj Evacuated tube collector MY MN HH JJ f D if System Manual mint renewables g Table of contents General Terms NNN x patsaacetionsaetacedaenaeeaerdemnactessieuematacccas 3 VPN 4 VENN 5 System SG ClO EE EE NaS 7 fate Eu elg eee a gate EEE ERE 11 General ae EE 12 Design and Survey RNA 14 System Commissioning Ch cklist jnn ssssmsneimssismimersriesennsis devede 16 Technical amp Dimensi n S osc dcceticiesuieete onsaaceccesentastonve E 18 Warranty amp Solar Key Mark cccccsecccseccssceeeseceeceeeeeessenseeseseeeeteuss 19 General Terms and Conditions Installation and commissioning should be undertaken by an MCS Certified Solar Installer Company General terms and conditions of warranty state that all installations must completed by a MCS certified and qualified solar installer company who is currently on the live MCS register of installers All installer companies should work to the Building Regulations in force at the time of installation The manufacturer s warranty will only apply if these installation instructions are followed The warranty does not cover any damage caused by non observance of this manual The correct functionality of the system is only guaranteed if the installation instructions are followed The end client should be informed at system handover that system should be checked visually once pre year and the heat exchange fluid ch
10. age is this manual 7 Transport damages are to be notified immediately stipulated on the delivery note and signed by the sub contractor 8 After the expiration of the legal warranty period the warrantee must provide the necessary aid in case of reparation work and is obliged to assume the necessary services like transport installation etc In the event of warranty we recompense for on roof installation max 200 00 VAT for the first collector and max 80 00 VAT for each additional collector incl All consumables for in roof installation max 300 00 VAT for the first collector and max 90 00 VAT for each additional collector incl All consumables 9 This warranty does not justify claims exceeding the legal liability for physical or personal injuries that have been caused by thedefects of the purchased object Retrospective actions and abatements exceeding legal regulations are not justified either 10 Other legal claims for warranty and damages in respect of bad installation remain untouched by this warranty 11 The exchange or rectification of the collectors or other parts of the solar system must be carried out by the installer and only after having consulted Eco pipe Otherwise an entitlement to compensation does not exist 12 Notifications of claim are to be announced in writing to H2 Solar Shop Limited and by presenting the installation and maintenance record as well as the respective proofs immediately after the d
11. also take into account any special features of the particular site that could lead to increased loads high wind speeds snow loads etc m mint renewables g Lightning protection Potential bonding of the building It is not necessary to connect collector arrays to the lightning protection of the building please observe the specific electrical regulations For installations on metal substructures at the installation site authorised lightning protection specialists must be consulted The metal tubes of the solar circuit must be connected to the main potential equalization bus by means of a conductor green yellow with a cross section of at least 16mm CU HO7V U or R It is possible to ground the collectors to a ground rod The grounding line must be laid outside the house The ground rod must also be connected to the main potential equalization bus by a line with the same crosssection as above Connections compression connection fittings Connect the collectors using the certified solar compression connections supplied with your kit Precautions must be taken to protect the connection pipes against temperature fluctuations caused by heat expansion expansion bends flexible piping In this case no more than 6 collectors may be connected in series Larger collector arrays must be assembled with expansion bends or flexible members inserted in the links IMPORTANT check the pump design When tightening the connections
12. amage has occurred 13 Solar accessories are subject to the warranty as specified by their Manufacturer DIN CERTCO TUVRheinland TET Fess ere yi y y manufacturer Harstederagaber dannbe par te fabnsant DIN CERTCO AlboinstraBe 56 e 12103 Berlin Tal 49 30 7562 1131 Fax 49 30 7562 1141 E Mail inogpdncerico de waw dincertco de soz StandEdition 10 07 Druck Prini 18 2009 A reliable hand for expert advice and support Mint Renewables Limited 3 Kelham Court Kelham Street Doncaster DN1 3RF Tel 01302 325000 Email enquiries mintrenewables co uk
13. anged once every four years This document is part of the warranty and should be kept in a safe place and handed over to the end user client on completion of works Instructions for installation and transport Mint Solar Collectors kits are delivered on pallets Never store outside in water logged conditions Always store on a flat surface with glass facing upwards maximum 8 collectors per stack or vertical with glass facing outwards The use of a carrying strap is recommended for transporting the collector The collector must not be lifted at the connections Avoidimpactsandmechanicalactionsonthesolarcollector Mint Solar Collectors should only be used in professionally designed systems with all system components and materials being appropriately rated for use in solar water heating systems and properly installed Structure de may only be mounted on sufficiently oad bearing roof surfaces and substructures The structural load bearing capacity of the roof and the substructure must be assessed on site by a suitably experienced professional before mounting the collectors Particular attention should be paid to the quality of the timber substructure in terms of the stability of the screw joints necessary for installing the collectors In particular it is essential to have the entire collector structure verified at the installation site by a qualified engineer in regions with high wind speeds The assessment should
14. any assembly is required Extreme caution should be adhered to when transporting evacuated tubes Tubes are made from very strong glass but will break if handled incorrectly All cartons must be stored on a flat level surface Cartons must not be stacked more than 5 high Cartons must not be stored upright Due to their weight and fragile nature two people are required to lift all cartons Please dispose of all packaging sensibly Cardboard can be recycled Solar collector carton contents a Manifold 1x per collector b Tail stock 1x per collector Front leg 2x per collector Horizontal bar As per collector Evacuated tubes As per collector 1 f Anti dust circle 1x per tube opening g Nuts bolts Supplied quantity as per mounting 1x per collector C d e h Heat transfer paste C mint renewables e k The Heat pipe condenser can become very hot at the top end from diffused sun radiation gt 200 C Therefore the pipes should be covered before assembly and also to be protected against impact With the manifold down Align the pre drilled upside _ holes on the front leg over the A 4 bolts attached to the manifold a Insert the two bolts on the manifold through the holes on 8 _ the leg Secure them together using 2x M8 nuts provided Repeat steps 1 amp 2 to Following this turn the manifold right side up _ Place the tail stock over the bottom of the legs Align the 10 B
15. bles e On Roof Mounting A 0O 0 1 Measure and mark out the position of the collector field 2 Remove roof tiles to expose rafter 3 Offer up bracket to rafter Reinforce rafter with additional timbers to a width of 90 mm always bolt additional timbers Never nail 4 Note bracket fixing position 5 Mark the tile underside with chalk and cut a 6 8 mm groove to sit neatly over tile when re fixed to the roof 6 Repeat procedure for remaining brackets l S T Screw in additional grounds to ap 120 m Locate and remove tiles where the roof Ensure the roof bracket is fitted to the lowest point of the tile to assist drain off of rain from the roof Relieve the rear of each roof tile with an angle 5 mint renewables e Tile mounting FIG 7 Select the rafters so that the collector juts out 30 cm at the right and left side It is therefore recommended to measure first the distance of the rafters and determine a centre line before fitting in the collector Start with roof hook above left Take out tile from rafter and screw roof hook to rafter with screws Then replace tile to roof Mounting of additional roof hooks Mount the other 3 roof hooks of the module in the same manner and ac cording to the measures The hooks must be mounted horizontally and vertically in alignment If necessary mount further hooks for additional modules Mounting of side rails FIG 10 Screw the side rails at the roof h
16. content and pH value e Check the antifreeze with an antifreeze tester and replace or refill if necessary We would recommend a target protection of 25 c e Check the pH value with a pH indicator rod If the limit pH value is less than 7 0 then replace the heat transfer fluid Collector maintenance The solar collectors should be inspected visually once a year for any signs of damage leaks or contamination Design and survey report Domestic hot water DHW 1 System type l Date DHW plus space heating Reference Swimming pool heating Completed by O O O OIO O Surveyor contact no nm Building type if House 0 bd aseeseen nn ee house record wether Block of flats F detached semi Client details detached or Sheltered housing Name terraced Address Commercial describe mvvsrnnnnrnvnerrnns Tel 3 Number of storeys lt lt lt mane 4 Approximate age of building men Su 5 Is building listed Yes No 6 Is building in conservation area Yes No Low circa 50 ia 7 Solar fraction Medium circa 60 E High circa 70 E 8 No of occupants Approximate Low 30 litres daily hot water usage at 50 Medium 50 litres per occupant OD High 70 litres Design and survey report continued 19 Available roof Width mme m space Height up roof gt assesseer m Any roof obstructions e g Dormer sky Gas light chimney stack EEE Type of fuel O je kWh 20 se i kWh heating a
17. dders not properly secured against sinking in sliding or falling over may lead to danger ous falls Whenever you are near live overhead electric cables where contact is possible only work if it is ensured that they are voltage free and this is secured for the duration of work The live parts are secured by the ESB by covering them or cordoning them off And are deemed safe by ESB transmission supervisor Or advised safety distances are maintained Voltage radius EE voltages up to 1000V 3m with voltages from 1000V to 11000V 4m with je voltages from 11000V to 22000V 5m with ee voltages from 22000V to 38000V gt 5m in case of unknown voltages The manufacturer hereby guarantees to take back products identified with an eco label and to recycle the materials used Only the heat transfer medium specified may be used gt gt PR PRPS 00 OPP gt gt Pe Safety harnesses should be fixed above the users whenever possible Safety harnesses should only be fastened to sufficiently load bearing structures or fixing points Never use damaged ladders e g wooden ladders with split runners or rungs or bent or buckled metal ladders Never try to repair broken runners rungs or steps on wooden Ladders Ensure that ladders are put up safely Ob serve the correct leaning angle 68 75 Prevent ladders from sliding falling over or sinking into the ground e g using wider feet feet suited to the
18. ee holes and secure tightly using x4 M8 nuts and bolts i Align the horizontal cross bars against the holes on the legs 5 1 1 and attach securely using the M8 nuts and bolts Insert the silicon sealing rings into the manifold openings 6 1 2 One seal per opening Unscrew the tail stock end cap If this is done on the roof care should be taken to prevent it rolling off Slide the tube through the tail stock up to the manifold Pull the heat pipe from the glass tube to expose 200mm Smear heat transfer paste mount the left amp right leg 3 9 evenly over the condenser firmly into the manifold surface Insert the condenser Apply a covering of soapy water onto the end 100mm of the glass tube Using a twisting motion insert the tube firmly into the manifold Replace the end cap onto the tail stock Repeat steps 7 12 for the remaining tubes It is advisable to mount the collector onto the roof amp fill and flush the system see page 7 before continuing to point 7 installing the evacuated tubes System Please note the maximum allowable heat pipes in series is 90 to 3 E tube 30 modules For high flow systems the recommended flow rate for a heat pipe system is 60 litres m2 hour Example 1 HP 65 30 3 m2 60 180Ltr hour Required Flow meter setting 3 litre minute Example 2 3 HP 65 30 9m2 60 540Ltr hour Required Flow meter setting 9 litre minute Large collecto
19. itted into collector sensor pocket Primary pressure limit of weakest component System pressure when cold Fuse rating for fused spur supply to controller and pump Controls and sensors checked and operating correctly At setting for controller for switching system on At setting for controller for switching system off Maximum cylinder temperature setting in controller Cylinder temperature sensors secured and sensor cable tied neatly Expansion vessel capacity Expansion vessel pre charge pressure System commissioning checklist continued Declaration to be completed by the commissioning engineer Volume of drain back vessel if drainback circuit I confirm that the system described in this commissioning checklist has been used NN litres installed at the address stated System flow rate The system design is in line with best practice and the system has been litres installed to comply with the Microgeneration Certification Scheme Standard MIS3001 and with all legal requirements All notifiable works have been carried out by suitably qualified personnel and have been notified to the Primary circuit volume Type of heat transfer fluid used Farth bonding present E relevant authorities Direction of non return valve checked C Signed Print name Position and type of air vents used Date of commissioning Air vent s isolated after commissioning Yes No Type and thickness of insulation used Pipe work all insulated apart f
20. nd 10 approximate LPG PA kWh annual consumption in Electricty od aan kWh kWh Solid fuel Please sketch the E Hot water Vented proposed location of the solar collec 21 tors relative to the roof plan of the Yes No building 11 storage type Unvented Does property 12 have combi boiler If yes type EE Pitched roof Proposed Flat roof E 13 location for solar collectors Ground mounted C 22 Are there any access restrictions for i erecting scaffold if so draw on sketch in h h yieieseritaccerteernioccies Frame mounted on wall 14 Roof orientation For pitched roof 15 Roof pitch 23 collectors are to 16 Type of roof covering eg Slate flat tile be Roof integrated a pan tile etc Mounted on roof Space for solar Height aesesevnsennnssnnnsvnnene m 17 Roof condition 24 cylinder s in airing 18 Any shading eg none from a tree from a cupboard plant Width An m structure part of the day a lot of the day room Depth Design and survey report continued Additional information for swimming pools Length 0 audensiesieasbeidadense Volume ere litres 31 Pool dimensions Width Number of coils uusesevsrvnenevunnvnenenesee Proposed solar Average depth musrrsserrnnnvvnnnsvnnnsvnsnne 25 cylinder type Vented indoors F Unvented i Outdoors 32 Pool location Please note and special cylinder fittings In ground 26 required e g shower fitting pumped
21. ooks Fixation of manifold case Slide manifold case with the profile rail into the hook of the side rail Screw the bracket on the side bar System Filling the system It is advisable to fill and flush the system prior to installing the evacuated tubes If this is not possible cover over the tubes to block out the sunlight The system should be filled with a glycol based anti freeze with anti corrosion inhibitors Tap water must not be used The system can be filled with a hand fill pump or a pressure fill pump and must be bled to eradicate any air bubbles from the solar circuit Do not operate the air vent if the system is hot There is a high risk of scalding Only bleed the system if the temperature of the heat transfer fluid is less than 55 c Operating pressure Operating pressure 1 5bar cold The maximum operating pressure is 6 bar The maximum test pressure must not exceed 10 bar Good tube Silver base Vacuum present Heat transfer media The system must be filled with a glycol based anti freeze with added corrosion inhibitors The fluid must be checked once in every two years in respect to its antifreeze and ph value Antifreeze is to be checked with a tester The target value to be 20 c If the target level is not reached replace the heat transfer fluid Ph levels are to be checked with a pH indicator rod The target value to be pH7 5 If the target level is not reached replace the heat transfer fluid
22. r field flow rate calculations are dependent on layout design Example 3 Low flow system 6 HP65 30 collectors mounted 3 3as diagram below 3 HP 65 30 9m2 60 540Ltr hour Required Flow meter setting 9 litre minute mint renewables CO Oo ON OO BP OO N gt Tile roof Natural slate roof Slate roof Roof hook Collector pipe Brackets Base support Side rails T or cross piece 6a 6b Screws M8 x 25 Wooden screw Heat conductive paste Manifold Manifold case Fitting for additional collectors Sensor pocket Temperature sensor De aeration valve Flexible metal tube Tube holder Clamp Corrugated sheet iron roof or slate roof Clamp for rolled steel joist Mounting and assembly Mechanical data Working pressure Recommended flow rate Manifold tails Tube size Wall thickness of tube Glass material borosilicate glass Vacuum tube metalic Stagnation Temperature Emission co efficiency Solar absorptions Heat output solar radiant intensity 1000w m Max 6bar 3 5 8 Litres M h 3 4 tapered thread 58mm x 1800mm 1 8mm High quality QB AL N AL 200 3 C lt 0 06 for 80 C 94 to 96 69W per tube Manifold Powder coated aluminium alloy Frame Heat pipe Manifold high temp sotdering older L Ag 15 F 852mm SZ10 1242mm SZ15 1632mm SZ20 2412mm SZ30 1820mm 2020mm Fixing zone Ea C mint renewa
23. rom tee off to expansion vessel and air vent Pump operation and checked and pump running Td quietly Pump speed setting Method of anti scalding in DHW circulation Location of fused isolation switch Location of pressure gauge System explained to customer C System documentation provided to customer i E tube evacuated tube heat pipe technology Our E tube range of evacuated tubes are designed to offer excellent performance efficiencies at the most competitive prices possible for high quality evacuated tubes The evacuated tube collectors use a vacuum space within each tube s borosilicate glass shell to offer very high efficiency and heat loss protection in any climate In the unlikely event of a tube breaking it can be removed and the entire system will continue to function ensuring a heating source that will not fail There are three unique heat pipe evacuated tube models E tube 15 15 tubes E tube 20 E tube technical data E tube 15 E tube 20 E tube 30 e Ultra high performance evacuated tubes Zero loss collector efficiency 73 4 73 4 73 4 e Low profile contoured manifold Heat loss coefficient 1 529 1 529 1 529 pares selective surface Overall area 2 42m 3 18m 4 70m coating e Silver brazed condenser Aperture area 1 40m 1 87m 2 79m riser head Length x width 1950mm x 1242mm 1950mm x 1632mm 1950mm x 2412mm e Solar keymark certified e Multiple mounting and Max operating pressure 10 bar 10 bar 10 bar Selec
24. tive Coating Yi e On roof e Flat roof Outer Tube Inner Tube Glass Wool Insulation Internal Reflector Warranty Conditions for Eco pipe Vacuum tube and flat plate collectors All deliveries and services are carried out according to our general terms and conditions of sale 1 The warranty period for the collector function amounts to 5 years for vacuum tubes and 10years for Manifold amp plates Within that period all parts proven to be useless or considerably reduced in their usability due to production or material defects are repaired or replaced ex works at expiration of the legal warranty period we have the choice between rectification or replacement 2 The warranty begins with the delivery of the collectors to the end user and under condition that the system has been installed and setup by a specialised company according to our installation and operating instructions as well as the locally valid current building regulations Further the warranty is dependent on a carefully completed installation and maintenance record which must be filled out by the installer and kept by the system owner 3 The guaranteeing implies that The collectors are transported installed operated and maintained according to our installation and operating instructions the collector system is exclusively operated with our solar liquid or approved equivalent product 4 The guaranteeing does not refer to damages due to wear and tear e
25. ust be mounted in a way as to avoid snow piles reaching the collectors Use the correct mountings The collector can be sup plied with the correct fixings for both slopping roof and flat roof types Not using the recommended fixings as outlined in this manual will invalidate any warranty Please note metal straps are not a recommended method of fixing Lightening protection Non metal structures Lightening protection is not required for collector arrays mounted to non metal structures although it is recommended that protection diodes for the temperature sensors are installed Lightening protection diodes protect the control unit from over voltage in the event of a lightening strike Metal structures For installations mounted and fixed to metal structures a lightening protection specialist must be consulted Connection of collectors in series The collector manifold inlet and outlet is 3 4 male soldering onto the collector manifold is not permitted and will invalidate any warranty claim Connections can be of either copper tube or flexible metal pipe When using copper tube precautions must be taken to account for temperature fluctuations caused by heat expansion Do not connect more than 6 collectors SZ10 20 or 4 collectors SZ30 in series without the use of expansion connectors Transport and Handling All Micoe SZ series collectors are packed in cartons are easy to assemble and can be transported to the site before
26. xcessive wear inappropriate operation or inappropriate use use of and unsuitable solar fluid or results of corrosion caused by a solar fluid chemical or electro chemical influences incorrect system layout 5 Moreover the warranty does not apply for damages as a result of an inappropriate storage of the collectors prior to installation and damages that are ascribed to force adjure The warranty regarding the safety glass refers to its condition and here only to manufacturing and material defects The cover security is examined in the context of the inspection requirements for collectors and ensured only according to these requirements 6 The warranty expires if arising and obvious defects are not notified in writing within 10 days after receipt or hidden defects immediately after emerging In case of hidden defects it is only valid for the warranty exceeding the legal warranty period if the collectors are changed or maintained by not specialised persons or companies or undertaken without or prior agreement if the possibility to inspect the entire system is not guaranteed or if the collector are removed without or agreement if original components are exchanged by other components or if inappropriate installation material and system components as well as non authorized solar fluid are used if the annual inspection is not realized within the time limit The proper execution is to be documented by the specialized company in the appropriate p
Download Pdf Manuals
Related Search
Related Contents
Tascam DR-03 User's Manual Espressione 1334/1 Use and Care Manual Copyright © All rights reserved.
Failed to retrieve file